DB98_08728A(1)_CO 12/20/02 3:27 PM Page 3

ROOM AIR CONDITIONER

INDOOR UNIT

SH12VCD

SH09VCD

OUTDOOR UNIT

SH12VCDX

SH09VCDX

SERVICE Manual

AIR CONDITIONER

1. Precautions

CONTENTS

2. Product Specifications

3. Operating Instructions and

Installation

4. Disassembly and Reassembly

5. Troubleshooting

6. Exploded Views and Parts List

7. PCB Diagrams

8. Wiring Diagrams

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 1-1

1. Precautions

1. Warning: Prior to repair, disconnect the power cord from the circuit breaker.

2. Use proper parts: Use only exact replacement parts. (Also, we recommend replacing parts rather than repairing them.)

3. Use the proper tools: Use the proper tools and test equipment, and know how to use them.

Using defective tools or test equipment may cause problems later-intermittent contact, for example.

4. Power Cord: Prior to repair, check the power cord and replace it if necessary.

5. Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in malfunction or fire.

6. After completing repairs and reassembly, check the insulation resistance.

Procedure: Prior to applying power, measure the resistance between the power cord and the ground terminal. The resistance must be greater than 30 megaohms.

7. Make sure that the grounds are adequate.

8. Make sure that the installation conditions are satisfactory.

Relocate the unit if necessary.

9. Keep children away from the unit while it is being repaired.

10. Be sure to clean the unit and its surrounding area.

Fig. 1-1 Avoid Dangerous Contact

Fig. 1-2 No Tapping and No Extension Cords

Fig. 1-3 No Kids Nearby!

Samsung Electronics

Fig. 1-4 Clean the Unit

1-1

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 1-2

M E M O

1-2 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 2-1

2. Product Specifications

2-1 Table

Item

Power Source

Capacity

Model(Indoor/Outdoor)

Cooling

Energy efficiency ratio

Air Flow

Moisture removal

Noise level Indoor(Hi/Mid/Low)

Noise level Outdoor

Capacity

ø-V-Hz

W

Btu/h

Btu/wh m 3 /min

\/h dBA Performance

Electrical

Rating

Compressor

Heating

Energy efficiency ratio

Air Flow

Noise level Indoor(Hi/Mid/Low)

Noise level Outdoor

Available voltage range

Running amperes

Cooling Power input

Heating

Power factor

Running amperes

Power input

Power factor

Starting current

Fuse capacity

Power cord

Cable-connector

Type

Model name

Oil/Quantity

Safety devices

Fan motor

Indoor

Outdoor

Refrigerant tube

Capillary tube

Model name

Running capacitor

Model name

Running capacitor

Narrow tube : Liquid

Wide tube : Gas

Cooling

Heating

Refrigerant to charge (R22)

Additional Refrigerant (R22)

Indoor unit : W x H x D

Dimension

Outdoor unit : W x H x D

Indoor unit

Weight

Outdoor unit

Remark : Test condition

Cooling test

Heating test m 3

W

Btu/h

Btu/wh

/min dBA

µF x VAC mmxMT mmxMT mm mm gr gr/m mm

-

-

CC

-

-

µF x VAC

mm

Kg

Kg

%

A

A x V

A x V mm 3 x G

%

A

W

V

A

W

Indoor room

DB27˚C / WB19˚C

DB20˚C / - -

SH12VCD/SH12VCDX

1-220 / 240-50

3510(2340~4100)

12000(8000~14000)

9.0(11~7.7)

7.8

1.9

39 / 37 / 35

52

3800(2550~4980)

13000(8700~17000)

9.3(11.9~7.5)

8.3

39 / 37 / 35

53

187~264

5.9(3.2~8.2), MAX12A

1330(720~1820)

97.1(96.3~96.5)

6.1(3.3~10.0), MAX12

1400(730~2260)

99.8(96.2~98.3)

12

3.15 x 250 / 20 x 250

15 x 250

1.5 x 4

Single Rotary

48A135RV2EL

SUN ISO4GSD-T / 410

204CT

AMPFS-022WTVA

1.2 x 450

AMASS-020WTVB

1.7 x 450

OD 6.35 x 5

OD 12.7 x 5

1.7 x 800

780

30

790 x 245 x 165

750 x 530 x 245

8

42

Samsung Electronics

SH09VCD/SH09VCDX

1-220 / 240-50

2630(1640~3010)

9000(5600~10300)

8.6(10.8~7.8)

6.5

1.5

38 / 36 / 34

52

3310(1900~4100)

11300(6500~14000)

9.8(12.0~9.1)

7.1

38 / 36 / 34

53

187~264

4.6(2.5~5.8), MAX12

1040(520~1315)

98.3(90.4~98.6)

5.2(2.6~6.7), MAX12

1152(545~1530)

94.5(90.4~99.3)

12

3.15 x 250 / 20 x 250

15 x 250

1.5 x 4

Single Rotary

44B092QV2EL

SUN ISO4GSD-T / 360

204CT

AMPFS-022WTVA

1.2 x 450

AMASS-020WTVB

1.7 x 450

OD 6.35 x 5

OD 9.52 x 5

ID1.5 x 1000

670

20

790 x 245 x 165

750 x 530 x 245

8

39

Outdoor room

DB35˚C / WB24˚C

DB7˚C / WB6˚C

Remark

JAPAN SUN OIL

More 5m

2-1

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 2-2

2-2 Dimensions

2-2-1 Indoor Unit

Air out

Air in

(Front view)

790

165

(Remote control)

45 22

Installation plate

2-2 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 2-3

2-2-2 Outdoor Unit

10

(Front view)

600

720

765

145 55

245

(Rear view)

P roduct Specifications

Samsung Electronics 2-3

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 2-4

2-3 Refrigerating Cycle Block Diagram

INDOOR UNIT

T

1

2-way valve

Capillary tube

Liquid side

OUTDOOR UNIT

Heat exchanger

(Evaporator)

Heat exchanger

(Condenser)

T

2

Gas side

3-way valve

Compressor

4-way valve

Cooling

Heating

Gas leak check point

2-4 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 2-5

6

7

3. Operating Instructions and Installation

3-1 Operating Instructions

3-1-1 The Feature of Key in remote controller

NO FEATURE OF KEY

FUNCTION OF KEY

1

Power On/Off button to start and stop airconditioner or timer set up.

2

3

(UP)

(DOWN)

Temp. up button. To increase the temperature by the pressing the temperature button.

Temp. down button. To decrease the temperature by the pressing the temperature button.

Each time you press this button,

MODE is changed in the following order.

: Auto Mode

: Cool Mode

: Dry Mode

: Fan Only

: Heat Mode

Press until the appearance. the air conditioner cools or heats the room as quickly as possible.

After 30minutes, the airconditioner is reset automatically to the previous mode.

4

Press until the appearance. the sleep timer can be used when you are cooling or heating your room to switch the air conditioner off automatically after a period of six hours.

Each time you press this button,

FAN SPEED is changed in the following order.

5

8

9

Adjust air flow vertically.

The ON Timer enables you to switch on the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours.

To cancel, press the (Set/Cancel) button.

The Off Timer enables you to switch off the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours.

To cancel, press the (Set/Cancel) button.

To select the 5 way function with the remote control, press the (5 way) button one or more times until the desired mode is selected.

Each time you press the (5 way) button, each 5 way indicator on the indoor unit lights up in order.

Samsung Electronics 3-1

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 2-6

Operating Instructions and Installation

3-1-2 Name & Function of Key in remote controller

1. AUTO CHANGEOVER FUNCTION :

*To operate in the “Auto change over” mode, set the MODE on “AUTO”.

*According to the outdoor and indoor temperatures while starting the operation, one of the modes from the cooling, dehumidifying and heating is selected automatically to operate.

*The operation mode shall be set again if the other condition different from that of the operating conditions(cooling, heating, dehumidifying mode) is kept for 60 minutes during the change-over operation.

1) Mode selection for operation start

2) Mode selection during the operation

Outdoor temperature

21˚C over

21˚C over

18˚C over

21˚C less

18˚C less

18˚C less

Indoor temperature

31˚C over

29˚C over 31˚C less

27˚C over 29˚C less

25˚C over 27˚C less

25˚C less

All area

27˚C over

21˚C over 23˚C less

21˚C less

Operation type

Set temperature

Wind volume

Cooling

Dehumidfying

Heating

28˚C

27˚C

26˚C

25˚C to be set automatically by controller according to the indoor temperature at the operation start.

Automatic

23˚C

21˚C

Outdoor temperature

21˚C over

Indoor temperature

31˚C over

29˚C over 31˚C less

27˚C over 29˚C less

25˚C over 27˚C less

21˚C over

18˚C over

21˚C less

18˚C less

18˚C over

21˚C less

18˚C less

25˚C less

23˚C over

27˚C over

23˚C less

27˚C less

Operation type

Set temperature

Wind volume

Cooling

Dehumidfying

Heating

28˚C

27˚C

26˚C

25˚C to be set automatically by controller according to the indoor temperature at the operation start.

Automatic to be set automatically by controller according to the indoor temperature at the operation start.

23˚C

21˚C

2. COOL MODE : The unit operates according to the difference between the setting and room temperature.(setting Temp.:

18°C~30°C)

3. HEAT MODE : The unit operates according to the difference between the setting and room temperature.(setting Temp.:

16°C~30°C)

*Prevention against cold wind : For about

3~5 minutes after initial operation (thermo control or “de-ice”), the indoor fan will either not operate or operate very slowly, then switch to the selected fan speed. This period is to allow the indoor unit's heatexchanger to prewarm until emitting warm air.

3-2 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 3-1

Operating Instructions and Installation

*High temperature release function : The outdoor unit and compressor ON/OFF is controlled for safety operation when heat exchanger of indoor unit is over heated.

*De-ice : Deicing operation is controlled by outdoor unit's heat exchanger temperature and accumulating time of compressor's operation.

De-ice ends by sensing of the processing time by de-ice Condition.

*According to the difference between the set temperature (Ts) and indoor temperature (Tr), the operation frequency of compressor is controlled as each area.

(Cooling area/COMPor ON/OFF area/Monitoring area)

➟ Cooling area : same as the cool mode

➟ COMPor ON/OFF area : repeat of

COMPor frequency 36[Hz] for 4 minutes operation/0[Hz](off) for 6 minutes

➟ Monitoring area : COMPor off.

5. TURBO MODE : This mode is available in

AUTO, COOL, HEAT, DRY, FAN MODE.

When this button is pressed at first, the air conditioner is operated in “powerful” state for 30 minutes regardless of the set temperature, room temperature.

When this button is pressed again, or when the operating time is 30 minutes, turbo operation mode is canceled and returned to the previous mode.

*But, if you press the TURBO button in

DRY or FAN mode, it is changed into

AUTO mode automatically.

6. SLEEP MODE : Sleep mode is available only in COOL or HEAT mode.

The operation will stop after 6 hours.

*In COOL mode : The setting temperature is automatically raised by 1°C each 1hour

When the temperature has been raised by total of 2°C, that temperature is maintained.

*In HEAT mode : The setting temperature is automatically droped by 1°C each

1hour.

When the temperature has been droped by total of 2°C, that temperature is maintained.

7. FAN SPEED : Manual (3 step), Auto (4 step)

Fan speed automatically varies depending on the difference between setting and the room temperature.

8. COMPULSORY OPERATION :

For operating the air conditioner without the remote controller, the tact key in indoor unit can be used.

When started with this key, the mode is set on “AUTO”.

The operating is the same function as

AUTO MODE in the remote controller.

Each time you press this key, 5WAY function is changed in the following order;

STD(standard) ➝ NATURE ➝

POWER(High-speed) ➝ Saving(Power-

Saving) ➝ SILENCE

❊ STD(standard)( ) : General operation

Mode

❊ NATURE( ) : The unit is operated according to health pattern control

❊ POWER( ) : The unit is operated in powerful state

❊ SAVING( ) : The unit is operated in power saving state

❊ SILENCE( ) : The unit is operated quitely

Each mode has Auto(Cool or Heat) operation designed in advance.

9. SWING : BLADE-H is rotated vertically by the stepping motor.

*Memory louver : When ON/OFF button is pressed at stop state, the BLADE-H returns to its original location which is operating state before stop.

Samsung Electronics 3-3

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 3-2

Operating Instructions and Installation

*Swing Set : Press the button under the remote control is displayed on LCD the and the blades move up and down. If the one more time press the button, blade location is stop.

10. 24-Hour ON/OFF Real Setting Timer. :

The air conditioner is turned ON at a specified time using .

OFF TIMER : The air Conditioner is turned OFF at a specified time using .

*ON TIMER : Only timer LED lights on.

*OFF TIMER : Both timer and operation

LED lights on.

11. SELF Diagnosis

Indoor unit

LAMP of Display Monitor Description

TIMER

X

STD

X

NATURE POWER SAVING SILENCE

X X X X

: Lamp on

: Lamp flickering

: Lamp off X

Indoor unit room temperature sensor error(open or short)

X

X X

X

X

X

X

X

X

X

Indoor unit heat exchanger temperature sensor error(open or short)

Indoor fan motor mal function

EEPROM error option error

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

Outdoor unit temperature sensor error (open or short)

- outdoor temp-sensor

- deice temp-sensor

- OLP temp-sensor

- discharge temp-sensor

- heatsink temp-sensor

Abnormal communication

(Indoor - Outdoor unit)

Abnormal increase of operation current

Abnormal increase of discharge and OLP temperature

Over current of IPM circuit

Trouble of the PTC circuit of the outdoor

Trouble of AC current sensor(open/short) and Leakage of refrigerant (R-22)

Outdoor unit

LAMP of inverter PBA

Yellow

X

X

X

X

Blue

X

X

Red

X

X

X

Description

: Lamp on

: Lamp flickering

: Lamp off

Normal operation and communication (Indoor-Outdoor unit)

Abnormal communication

(Indoor-Outdoor unit)

Trouble of the control power of the outdoor

Abnormal communication

(Sub-Main micom)

No zero-crossing signal

X

X

X

X

X

X

X

X

Trouble of option setting

Abnormal increase of discharge temperature

Abnormal increase of OLP temperature

Abnormal increase of operation current

Over current of IPM circuit

Over voltage of IPM circuit

Over voltage and current of PFC circuit

Trouble of DC link voltage circuit

Trouble of discharge temp-sensor

(open/short)

Trouble of outdoor temp-sensor

(open/short)

Trouble of de-ice temp-sensor

(open/short)

Trouble of OLP temp-sensor

(open/short)

Trouble of AC current sensor

(open/short) and Leakage of refrigerant(R-22)

12. BUZZER SOUND : Whenever the

ON/OFF button is pressed or whenever change occurs to the condition which is set up or select, the compulsory operation mode, buzzer is sounded "beep".

3-4 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 3-3

3-2 Installation

3-2-1 Selecting Area for Installation

Select an area for installation that is suitable to the customer's needs.

3-2-1(a) Indoor Unit

1. Make sure that you install the indoor unit in an area providing good ventilation. It must not be blocked by an obstacle affecting the airflow near the air inlet and the air outlet.

2. Make sure that you install the indoor unit in an area allowing good air handling and endurance of vibration of the indoor unit.

3. Make sure that you install the indoor unit in an area where there is no source of heat or vapor nearby.

4. Make sure that you install the indoor unit in an area from which hot or cool air is spread evenly in a room.

5. Make sure that you install the indoor unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances (at least 1 meter).

6. Make sure that you install the indoor unit in an area which provides easy pipe connection with the outdoor unit, and easy drainage for condensed water.

7. Make sure that you install the indoor unit in an area which is large enough to accomodate the measurements shown in figure on the next page.

3-2-1(b) Outdoor Unit

1. Make sure that you install the outdoor unit in area not exposed to the rain or direct sun light.

(Install a separate sunblind if exposed to direct sun light.)

2. Make sure that you install the outdoor unit in area allowing good air moment, not amplifying noise or vibration, especially to avoid disturbing neighbours.

(Fix the unit firmly if it is mounted in a high place.)

3. Make sure that you install the outdoor unit in area providing good ventilation and which is not dusty. It must not be blocked by any obstacle affecting the airflow near the air inlet and the air outlet.

4. Make sure that you install the outdoor unit in area free from animals or plants.

5. Make sure that you install the outdoor unit in area not blocking the traffic.

6. Make sure that you install the outdoor unit in area easy to drain condensed water from the indoor unit.

7. Make sure that you install the outdoor unit in area which provides easy connection within the maximum allowable length of a coolant pipe(15 meters).

Note

1. Add 20 grams of refrigerant (R-22) for every 1 meter if the pipe length exceeds the standard pipe length of 5 meters.

2. Maintain a height between the indoor and outdoor units.

8. Make sure that you install the outdoor unit in an area which is large enough to accommodate the measurements.

3-2-1(c) Remote Control Unit

1. Make sure that you install the remote control unit in an area free from obstacles such as curtains etc, which may block signals from the remote control unit.

2. Make sure that you install the remote control unit in an area not exposed to direct sunlight, and where there is no source of heat.

3. Make sure that you install the remote control unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances (at least 1 meter).

Caution

It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.

Samsung Electronics 3-5

DB98_08728A(1)_SM_1 12/20/02 3:24 PM Page 3-4

Operating Instructions and Installation

3-2-2(a) Refrigerant Refill

• Refill an air-conditioner with refrigerant when refrigerant has been leaked at installing or using.

1. Purge air(for new installation only).

2. Turn the 3-way valve clockwise to close, connect the pressure gauge(low pressure side) to the service valve, and open the 3-way valve again.

3. Connect the tank to refill with Refrigerant

4. Set the unit to Low pressure checking mode.

* Press the ON/OFF switch for 5 second.

*All lamps blink on the indoor unit.

5. Check the pressure indicated by the pressure gauge(low pressure side).

* Refer to Low pressure graph.

Compound gauge

Press this ON/OFF

Switch for 5sec.

And then the

Airconditioner operating on rating speed.

6. Open the refrigerant tank and fill with refrigerant until the rated pressure is reached.

* It is recommended not to pour the refrigerant in too quickly, but gradually while operating a pressure valve.

For mounting other and of hose when not in use

Suspension hook

High pressure gauge

Hand wheel

Finger tight fittings

Connected to high pressure side

Charging line

R-22 7. Stop operation of the air conditioner.

8. Close the 3-way valve, disconnect the pressure gauge, and open the 3-way valve again.

9. Close the cap of each valve.

3-6 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-5

Operating Instructions and Installation

• MODEL NAME : SH12VCD(SH12VCDX)

6.5

6

5.5

5

4.5

4

3.5

20 25 30 35

Outdoor inlet air DB temp.(˚C)

40 45

32.4

30.6

28.8

27.0

24.0

21.5

• MODEL NAME : SH09VCD(SH09VCDX)

5

4.5

4

7

6.5

6

5.5

20 25 30 35

Outdoor inlet air DB temp.(˚C)

40 45

32.4

30.6

28.8

27.0

24.0

21.5

3-2-2(b) Refrigerant Adjustment

Class

Connection

Pipe Length

5m

(standard)

6~15m

Air-Purge

Method

Refer to the detailed Air-Purge

Procedure

For installation

Refrigerant

Adjustment

Unnecessary

Add 20g of refrigerant

(R-22) for every 1m.

Air-Purge

Method

Purge air using a vaccum pump or an additional refrigerant cylinder.

For service

Refrigerant

Quantity refer to specification sheet

Add 20g of refrigerant

(R-22) for every 1m.

3-2-2(c) Flare unt fixing torque

Outter diameter

ø 6.35 (9000Btu, 12000Btu)

(Liquid Side)

ø 9.52 (9000Btu)

(Gas Side)

ø 12.7 (12000Btu)

(Gas Side)

Torque (kg-cm)

Fixing Torque Final Torque

160 200

300

500

350

550

Samsung Electronics 3-7

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-6

4. Disassembly and Reassembly

Stop operation of the air conditioner and remove the power cord before repairing the unit.

4-1 Indoor Unit

No

1

Parts

Front Grille

Procedure

1) Stop the air conditioner operation and block the main power.

2) Seperate tape of front panel upper.

Remark

3) Contract the second finger to the left, and right handle and pull to open the inlet grille.

4) Take the left and right filter out.

*Taking off the deodorizing filter.

5) Loosen one of the right fixing screw and seperate the terminal cover.

6) Loosen three fixing screws of front grille.

7) Pull the upper left and right of discharge softly for the outside cover to be pulled out.

8) Pull softly the lower part of discharge and push it up.

Caution;

Assemble the front panel and fix the hooks of left and right.

4-1 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-7

No

2

3

Parts

Ass’y Tray Drain.

Procedure

1) Do “1”above

2) Take all the connector of PCB upper side out.

(Inclusion Power cord)

3) Separate the outdoor unit connection wire from the terminal block.

4) If pulling the Main PCB up. it will be taken out.

Electrical Parts

(Main PCB)

1) Do “1”, “2” above

Separate the drain hose from the extension drain hose.

2) Pull tray drain out from the back body.

4 Heat Exchanger 1) Do “1” and “2”, “3” above

2) Loosen two fixing earth screws of right side.

3) Separate the connection pipe.

4) Separate the holder pipe at the rearside.

5) Loosen the three fixing screws of right and left side.

6) Lifting the heat exchanger up a little to push the up side for separation from the indoor unit.

5 Fan Motor and

Cross Fan

1) Do “1”, “2”, ”3”, “4” above.

2) Loosen the fixing two screws and separate the motor holder.

3) Loosen the fixing screw of fan motor.

(By use of M3 wrench)

4) Separate the fan motor from the fan.

5) Separate the fan from the left holder bearing.

Disassembly and Reassembly

Remark

Samsung Electronics 4-2

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-8

4-2 Outdoor Unit

Take care of the electrical shock by contact on the charging parts before the discharge after power off. (If takes approximately 2 minutes to discharge.)

No

1

Parts Procedure

Common Work

&

Ass’y-control Out

1) Loosen the fixing screw and separate the

Cover-Valve.

2) Separate the Cable-Connector Wire from the

Terminal-Block.

Remark

3) Loosen five fixing screws and separate the

Cabi-Upper.

4) Loosen five fixing screws from the

Ass’y-Control Out.

5) Separate the Terminal-Housing from the

Ass’y-Control Out.

6) Separate the Ass’y-Control Out from the outdoor unit.

7) Loosen seven fixing screws and separate the

Cabi-Side.

4-3 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-9

No

2

Parts

Fan-Motor

Procedure

1) Loosen Four fixing screw of the Guard-

Fan.

Disassembly and Reassembly

Remark

2) Remove the nut flange (Turn to the right to remove, as it is a left hand screw)

3) Separate the fan.

4) Loosen four fixing screws to separate the motor.

3 Heat Exchanger 1) Do “1” above.

2) Loosen three fixing screws of Ass’y-Frame and Partition.

3) Disassemble the inlet and outlet pipe by welding.

4) Separate the heat exchanger.

Samsung Electronics 4-4

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-10

Disassembly and Reassembly

No

4

Parts

Compressor

Procedure

1) Do “1” above.

2) Open the terminal cover of compressor and unscrew the connection terminal.

3) Disassemble the inlet and outlet pipe of compressor by welding.

4) Disassemble the inlet and outlet pipe of condenser by welding.

5) Loosen the three bolts of the lower part.

6) Separate the compressor.

Remark

4-5 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-11

5. Troubleshooting

Since the inverter air conditioner is equipped with Electrical control circuits at both Indoor & outdoor unit, the trouble shooting shall be performed according to the error mode.

Inside the controller of the outdoor unit (inverter), the large capacity of electrolytic condenser so that it takes the time to discharge after the power off since the electrical charge remains

(the charging voltage DC 340V).

Take care of the electrical shock by contact on the charging part before the discharge after the power off. (It takes approximately 2 minutes to discharge).

5-1 Basic items for trouble shooting

1) Is the power source proper?

The power source shall be in the range of the rated voltage

±10%

. If it is out of this range, it may cause the abnormal operation.

2) Is the connection made between the indoor and outdoor unit?

The connection between indoor and outdoor unit shall be performed with 4 wire. (connection cable of indoor and outdoor unit + ground wire).

3) The phenomena as follows are not out of order.

NO

1

Phenomena

The operation is not done.

Cause and reason

Is the power off or the power unplugged?

Does it stop because it is the completion time?

Unplug and plug again the power source for 2 minutes.

2 The wind comes out but the heating/cooling is not performed.

Is the filter clogged with dust or dirty?

Is there any direct light on the outdoor unit or any obstacle against it?

Is the selected temperature too high? Lower the selected temperature lower than the current one (during cooling).

Is the selected temperature too low? Raise the desired temperature than the current one (during heating).

Is the “Fan only Mode” operation?

3 The remote controller does not operate.

Is the battery run out?

Is the battery inserted in the wrong way(+, -)?

Is the detection part of the indoor unit blocked?

Does it interfered with the radio of neon sign?

4 The wind volume is not adjusted.

Is the operation selected among one of Auto / Dry / Turbo / Sleeping?

The temperature setting is not required since the wind volume set automatically.

Check again at the state of Cooling / Fan only / Heating.

5 The temperature is not set.

Is the operation selected among the Dry / Turbo / Sleeping / Fan only Mode.

Since the temperature is automatically set, the temperature setting is not required.

Check again at the cooling/heating state.

The standard temperature ±2˚C during the automatic operation.

6 The operation lamp continues to be flickering.

Push the Operation / Stop button.

Unplug and plug the power source.

7 The immediate operation starts without control of remote controller when plugged

It is the case that the auto restart function works.

# Auto restart function is the convenient function where the operation state is memorized in the Memory IC during the blackout and the operation restarts when the power comes back.

Samsung Electronics 5-1

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-12

5-2 The first determination method of troubled part

5-2-1 Error mode display of indoor unit

POWER indicator

NATURE indicator

STANDARD indicator Remote Control

Sensor

On/Off & 5 Way

Selection button

TIMER indicator

SILENCE indicator

SAVING indicator

TIMER

X

X

X

X

X

X

X

X

X

STD

X

X

X

LAMP of Display Monitor

Description

X

: LAMP ON

: LAMP FLICKERING

: LAMP OFF

NATURE POWER SAVING SILENCE

X X X X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

Indoor unit room temperature sensor error(open or short)

Indoor unit heat exchanger temperature sensor error

(open or short)

Indoor fan motor mal function

EEPROM error

Option error

Outdoor unit temperature sensor error(open or short)

- outdoor temp-sensor

- deice temp-sensor

- OLP temp- sensor

- discharge temp-sensor

- heatsink temp-sensor

Abnormal communication (Indoor - Outdoor unit)

\Abnormal increase of operation current

Abnormal increase of discharge and OLP temperature

Over current of IPM circuit

Trouble of the PTC circuit of the outdoor

Trouble of AC current sensor (open/short) and Leakage of refrigerant(R-22)

5-2 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-13

5-2-2 Error mode display of outdoor unit board

Troubleshooting

RED GREEN YELLOW

LED3 LED2 LED1

YELLOW

X

X

X

X

LAMP of inverter PBA

GREEN

X

X

RED

X

X

X

X

X

X

X

X

X

X

Description

X

: LAMP ON

: LAMP FLICKERING

: LAMP OFF

Normal operation and communication (Indoor-Outdoor unit)

Abnormal communication(Indoor-Outdoor unit)

Trouble of the control power of the outdoor

Abnormal communication (Sub-Main micom)

No zero-crossing signal

Trouble of option setting

Abnormal increase of discharge temperature

Abnormal increase of OLP temperature

Abnormal increase of operation current

Over current of IPM circuit

Over voltage of IPM circuit

Over voltage and current of PFC circuit

Trouble of DC link voltage circuit

Trouble of discharge temp-sensor(open/short)

Trouble of outdoor temp-sensor(open/short)

Trouble of deice temp-sensor(open/short)

Trouble of OLP temp-sensor(open/short)

Trouble of AC current sensor(open/short) and Leakage of refrigerant(R-22)

Samsung Electronics 5-3

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-14

5-3 Sequence of trouble shooting for inverter aircon

OPERATION START

• The indoor unit does not work even though the power is plugged.

•There is no sound “DING”

•The lamp is not on the display.

The indoor unit does not work when operated by the remocon.

Check the indoor unit control board. (5-3-1)

Checking the Remocon. (5-3-2)

Check the control board and the display board of indoor unit.(5-3-2)

Check the error mode by confirming the lamp flickering of indoor unit display.

The lamp of the indoor display is flickering and the indoor unit stops several minutes after the indoor unit starts.

Timer lamp( ) flickering

Check of the indoor temperature sensor (5-3-3)

Standard( ), Timer( ) lamp flickering

Check of the indoor heat exchanger (5-3-3)

Nature( ) lamp flickering

Check of indoor unit fan motor (5-3-4)

Timer( ), Nature( ) lamp flickering

Check the lines of the indoor and outdoor communication (5-3-5)

Standard( ), Nature ( ) lamp flickering

Check of the outdoor unit temperature sensor

: Discharge temperature sensor (5-3-6)

: Comp top OLP temperature sensor (5-3-6)

: Deice temperature sensor (5-3-7)

POWER( ) flickering

Timer( ), POWER( ) lamp flickering

Nature( ), POWER lamp( ) flickering

: Outdoor temperature sensor (5-3-7)

Check of the abnormal increase protection of the operation Current (5-3-8)

Check of the instantaneous over-current protection mode of IPM circuit (5-3-9)

Check the abnormal increase of the comp discharge gas temperature and OLP protection mode.(5-3-10)

Check the indoor unit

Check of the

Communication line

Check of the Outdoor unit

5-4 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-15

Troubleshooting

5-3-1 Check of indoor unit control board

Unplug the power cord and plug it after 5 seconds.

Press the on/off switch located in indoor unit inside to operate the air conditioner.

•If the air conditioner operates, check the remocon and indoor unit display board.

•If the air conditioner does not operate, check according to the sequence of the followings:

Check sequence of indoor unit control board

Step 1 : Check whether two wires of power cord (Sky-blue, brown) are connected correctly to the terminal block.

•Sky -blue : connected to “N”

•Brown : connected to “L”

Step 2: Check whether the wire connected to the terminal block is connected correctly to the control board.

(Control board)

JN

RY71

RY71

JC

(Terminal block)

SKY-BLU SKY-BLU

BRN

ORG

BLK

1

2

N

L

(N1)

Step 3 : Check whether the fuse (F701)(F702) on the control board is normal. (5

[A]/250[V]:F701) (1[A]/250[V] : F702)

• If the fuse is broken, replace it with the new one.

Step 4 : check the output of SMPS on the control board.

• Input power AC187~AC264V—-IC 02 Input: DC 12V

IC 02 Output : DC 5V

5-3-2 Display board and remocon check of indoor unit

Check whether the connection wire of Display board is correctly connected to CN91 connector.

Check the voltage of remocon battery. - the voltage of one battery shall be higher than about

1.4 V, and then the remocon operates normally.

Check whether the neon sign is on and the 3 wave long fluorescent lamp is on around the indoor unit. - After putting all lamps of the indoor out and then operate it by remocon. If it operates with the remocon, it is the abnormality due to the interference from the light of lamps. (Aircon unit is normal).

5-3-3 Check the indoor temperature sensor and indoor heat exchanger temperature sensor.

Take out the thermistor connected to the connector (CN41) of control board of indoor unit and measure the resistance between two wires and if it is same as follows: it is normal but if not, replace it.

Ambient temperature

(°C)

Resistance of thermistor [K

]

15°C

14.68

20°C

12.09

25°C

10

30°C

8.31

35°C

6.94

40°C

5.83

Samsung Electronics 5-5

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-16

Troubleshooting

5-3-4 Check of indoor unit fan motor

Check whether the wire of fan motor is connected to the connector of control board (CN42,

CN71) of indoor unit.

Check whether the error mode displays after the strong revolution for approximately 15 seconds since aircon is on.

In case the error mode displays after the fan motor is rotating for 15 seconds → Defect of

HALL IC of fan motor and Control board

In case that the error mode displays without running of fan motor after 15 seconds. →

Operate with the pin of SSR(SS71) short of indoor unit control board and then if the fan motor does not run, it is the fan motor defect.

If it rotates, it is the defect of control board (SS71, IC05, IC04).

5-3-5 Check of communication line between the indoor unit and outdoor unit

(Communication error mode)

1) Check of connection

Check whether the cable wire connecting the indoor unit with outdoor unit is correctly connected to the (N1), 1, 2 terminal. (If the wire is connected reversely, the communication error occurs)

If the cable connecting the indoor unit and outdoor unit is longer than 20m, error mode occurs (shorten the cable length).

(Check of indoor unit)

Check whether the connection wire of the terminal block and control board of indoor unit is correct.

(Control board)

JN

RY71

RY71

JC

(Terminal block)

SKY-BLU SKY-BLU

BRN

ORG

BLK

N

L

1

2

(N1)

(Check of outdoor unit)

Check whether the connection wire of the terminal block and control board of outdoor unit is correct.

(Control board)

#1 of CN31

N

L

BLK

SKY-BLU

BRN

(Terminal block)

2

(N1)

1

2) Check of power supply to the outdoor unit

After operation of aircon, select the turbo mode and approximately 3minutes later, check whether the red color lamp of control board (to be seen if the top cover of outdoor unit) is on.

If the red lamp (LED 3) is not on, check the power part of control board of outdoor unit.

Check the connection of reactor.

If the red lamp (LED3) is on and green lamp is flickering, it is normal.

5-6 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-17

Troubleshooting

5-3-6 Check of discharge temperature sensor and comp top OLP temperature sensor.

Connector of outdoor unit control board

(PIN#3,4 of CN51 - discharge temperature sensor), (PIN#1,2 of CN52-OLP Temperature sensor)

Measure the resistance between two wires and if it is same as follows, it is normal but if not, replace.

Ambient temperature

(°C)

Resistance of thermistor [K

]

0°C

553

10°C

362

20°C

242

30°C

166

40°C

165

50°C

82

5-3-7 Check the deice temperature sensor and outdoor temperature sensor

Connector of outdoor unit control board

(PIN#1,2 of CN51 - outdoor temperature sensor),(PIN#3,4 of CN52-deice Temperature sensor)

Measure the resistance between two wires and if it is same as follows, it is normal but if not, replace it.

Ambient temperature

(°C)

Resistance of thermistor [K

]

15°C

14.68

20°C

12.09

25°C

10

30°C

8.31

35°C

6.94

40°C

5.83

5-3-8 Check of operation current abnormal increase mode

The operation abnormal current mode is the protection control for the safe operation by detecting the operation current of inverter aircon by the current sensor on the control board.

If the operation current abnormal increase occurs,

The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50 °C)

Reinstall the outdoor unit so that the good ventilation can be made.

If the Refrigerant is overcharged.

Check the amount of Refrigerant.

If the comp is locked.

Replace the comp.

If the comp is operating without the revolution of fan motor.

Check the fan motor connector, replace the fan motor.

If the protection cover is operating with bending to the outdoor.

Take out the protection cover.

If two outdoor units are operating face to face. (the bad ventilation is made)

Reinstall the outdoor unit for the good ventilation.

The air circulation is bad due to the attachment of falling leaves

Take away the leaves for the good ventilation.

Samsung Electronics 5-7

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 3-18

Troubleshooting

5-3-9 Check of instantaneous over-current protection of IPM circuit.

Inverter instantaneous over-current protection mode is the mode to be actuated in order to prevent the damage of elements from the peak current of IPM circuit elements.

In case that the inverter circuit instantaneous over-current protection mode actuates, check the following items.

(Condition of installation)

The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50 (°C) )

Reinstall the outdoor unit so that the good ventilation can be made.

In case that the operation is made with the cover bent of the outdoor unit.

Take out the cover.

If two outdoor units are operating face to face, (the bad ventilation is made)

Reinstall the outdoor unit for the good ventilation.

The air circulation is bad due to the attachment of falling leaves.

Take away the leaves for the good ventilation.

If the Refrigerant is overcharged.

Check the amount of Refrigerant.

(Unit defect)

If the comp is locked.

Replace the comp.

If the comp is operating without the revolution of fan motor.

Check the fan motor connector and replace the fan motor.

In case the parts of the control board is damaged.

Replace simultaneously the inverter control board.

5-3-10 Check of the comp discharge gas temperature and OLP temperature abnormal rise.

If the comp discharge gas temperature and OLP temperature rises higher than a certain level, it protects the circuit.

If the comp discharge gas temperature and OLP temperature rises abnormally, check the following items.

(Condition of installation)

The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50 (°C) )

Reinstall the outdoor unit so that the good ventilation can be made.

In case that the operation is made with the cover bent of the outdoor unit.

Take out the cover.

If two outdoor units are operating face to face, (the bad ventilation is made)

Reinstall the outdoor unit for the good ventilation.

The air circulation is bad due to the attachment of falling leaves

Take away the leaves for the good ventilation.

If the refrigerant is insufficient.

Fill up the amount of refrigerant.

(Unit defect)

If the comp is locked.

Replace the comp.

If the comp is operating without the revolution of fan motor

Take out the protection cover.

Check the fan motor connector and replace the fan motor.

5-8 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 4-1

5-4 Fault Diagnosis of Major Parts

Parts Diagnosis

Indoor ”Temp.Sensor”

Indoor “Heat ex. Sensor”

Outdoor “Temp.Sensor”

Outdoor “Deice Temp. Sensor”

Measure resistance with a tester.

Normal

Ambient temperature

Resistance of thermistor[K

]

15°C

14.68

20°C

12.09

25°C

10

30°C

8.31

Abnormal

, O

… open or short

Outdoor “Discharge Normal

Temp.Sensor”

Outdoor “OLP Temp.Sensor”

Ambient temperature 0°C

Resistance of thermistor[K

]

553

10°C 20°C 30°C

362 242 166

Abnormal

, O

… open or short

Indoor Fan Motor Measure resistance between terminals (CN72) with a tester

Normal At ambient temperature (10°C ~ 30°C) between

Red, Blue

Red, Yellow

Voltage

410±10%

325±10%

Main

Sub

35°C 40°C

6.94

5.83

40°C 50°C

165 82

Outdoor Fan Motor

Abnormal

, O

… open or short

Measure the voltage between ground and signal wire of the fan motor

Normal between

Gray, Orange

Yellow, Orange

Voltage

0.5V~4.5V

5V

Abnormal

Normal

Abnormal if voltage does not change from 0V to 5V.

At ambient temperature (10°C ~ 30°C) between

Black, Red

Black, White

Resistance

275±10%

350±10%

Stepping Motor

(UP/DOWN swing motor)

Abnormal

, O

… open or short

Measure resistance between red wire and each terminal.

Abnormal

, O

… open or short

Main

Sub

Samsung Electronics 5-9

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 4-2

5-5 Set up the Model option

❈ If you make the replacement of the ASS’Y CONTROL-IN or MAIN PCB ,

Be sure to be set up the model option as follow the steps

Remote controller operation method as per the step

1st step

Method)

! Remove the battery of remote controller

@ Press the temperature raise/down key simultaneously

# Insert the battery again

(Result)

If the screen of remocn displays as shown in the right, go to the second step

Applicable key Display status

2nd step

Method)

If the first digit of LCD is 0 on the remocon screen, go to the 3rd step.

❊ If it is 1, press the mode key once to change to 0 and go to the 3rd step.

3rd step

Method)

Press the marked key to input the option number.

example) 021E31

Result)

Go to 4th step if it displays as shown in the right

(The number increases from 1~9, and A, b, C, d, E,

F whenever pressing the key.)

5-10 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 4:02 PM Page 4-3

Display status

Troubleshooting

Remote controller operation method as per the step

4th step

Method)

After completion of 3rd step, and if the MODE KEY is pressed once,

! 1~3 steps are saved internally

@ If the first number at the time is “1”, it is correct and so go to 5th step

❊ If pressing mode key and the first digit becomes 0, the screen of 1~3 steps can be seen.

5th step

Method)

Pressing the marked key to input the option number.

example) 142285

Result)

If it displays as shown in the right go to the 6th step

Applicable key

6th step

Method)

When pressing the operation ON/OFF key with the direction of remote controller for set, the sound

“Ding, or Diriring is heard and then the input of option is completed.

ERROR MODE

1. When the lamps of (STANDARD( ),

NATURE( ), TIMER( ) is flickering → failute of option input

After removing the set power cord and insert it again, pressing the operation on/off key to retry and if the condition is same, EPROM is deffcective or misinsertted. So replace the

PCB.

❊ Refer to the right side if the error appears.

2. When all lamps of indoor unit

( ) are flickering with the sound of Dididiring,

→ The current option input is different from that of already input one: Check the option number correctly and if it is correct, press the key once more to input the option. (check correctly)

→ If the option is not input at the time and all lamps are continuously flickering ; since it is the case that the option number is out of the input range, check the option number again and do again the steps from 1 - 6steps

Samsung Electronics 5-11

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 4-4

Troubleshooting

<Table of the option code>

MODEL

SH12VCD

SH09VCD

OPTION CODE

007315-10123F

007d08-1010Fb

5-12 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 4-5

M E M O

Samsung Electronics 5-13

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 4-6

6. Exploded Views and Parts List

6-1 Indoor Unit

16

20-1

20-5

20-4

20-3

20 20-6

20-6-1

20-2

19

14

24

9

15

10

13-1

11

13

13-2

13-3

13-4

12

8

22

21

6

17 18

25

5

7

4

23

3

2

1

6-1

You can search for the updated part code number through the ITSELF.

URL : http://itself.sec.samsung.co.kr

Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 4-7

■ Parts List

No.

CODE NO Description

24

25

DB61-00219A

DB93-01601A

DB94-00056G

DB94-00104A

DB61-00165A

DB39-00146A

DB39-00147A

DB70-00036A

DB94-00058N

DB94-00062E

DB66-00127A

DB66-00128A

DB66-00128B

DB63-00082A

DB95-20138A

DB31-10129A

DB64-00354A

DB63-00064A

DB95-00287G

DB63-00067A

DB92-00248G

DB67-00051A

DB67-00032A

DB63-00083A

DB94-00040F

DB60-20011A

DB31-00033A

DB32-00020A

DB93-00960D

DB93-00951A

DB65-00076A

DB93-01558A

DB61-40251A

DB67-60030A

DB96-01248A

DB96-01247C

DB94-40003A

DB93-00251L

20

20-1

20-2

20-3

20-4

20-5

20-6

20-6-1

20-7

21

22

23

16

17

18

19

13-3

13-4

14

15

12

13

13-1

13-2

8

9

10

11

4

5

6

7

1

2

3

GRILLE-AIR INLET

GUARD-AIR FILTER

ASS´Y-CLEANER FILTER

COVERTER-TERMINAL

ASSY PANEL-FRONT

SPACER-EVAP LOW

SPACER-EVAP UP

COVER U-BEND

ASSY-CROSS FAN

BOLT-SPECIAL

MOTOR-FAN-IN

THERMISTOR-WIRE ASSY

ASSY CONTROL IN

ASSY PCB MAIN

TERMINAL BLOCK

HOLDER-CLAMP IN

ASSY DISPLAY

ASSY BACK BODY

ASSY-HOLDER MOTOR

HOLDER-PIPE

CONNECT WIRE- DISPLAY

CONNECT WIRE-PCB

PLATE-HANGER

ASSY TRAY DRAIN

ASSY DRAIN-HOSE

BLADE-H

BLADE-V,A

BLADE-V,B

SCREEN-SAFETY WIRE

ASSY-MOTOR STEPPING

MOTOR-STEPPING

ASSY DISPLAY-CENTER

HOLDER-SENSOR

SPRING-SENSOR

ASSY CYCLE IN

ASSY CYCLE IN

RUBBER BEARING

ASSY REMOCON

Samsung Electronics

Exploded Views and Parts List

SH12VCD

1

1

1

1

1

1

3

6

1

1

1

1

1

1

1

1

1

1

1

-

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

2

1

1

Q’TY

SH09VCD

1

1

1

1

1

1

3

6

1

1

1

1

1

1

1

1

1

1

-

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

2

1

1

6-2

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 4-8

6-2 Outdoor Unit

8-1

6-3 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-1

Exploded Views and Parts List

■ Parts List

No.

CODE NO Description

3

4

1

2

5

6

6-1

7

8

8-1

9

10

DB63-00104B GUARD-FAN

DB60-30004A NUT-FLANGE

DB67-50063A PROPELLER-FAN

DB31-10058E MOTOR-FAN OUT

DB90-00241P ASS’Y-FRAME

DB90-00241N ASS’Y-FRAME

DB94-00160B ASS’Y-PARTITION

DB94-00160A ASS’Y-PARTITION

DB33-00021A REACTOR

DB90-00627A CABI-UPPER

DB93-00962B ASS’Y-CONTROL OUT

DB93-00962A ASS’Y-CONTROL OUT

DB93-00953B ASS’Y-MAIN PCB

DB93-00953A ASS’Y-MAIN PCB

DB63-00380B FELT COMP BOTTOM

DB63-00380A FELT COMP BOTTOM

DB72-00211A CLOTH COMP SIDE

DB72-00162A CLOTH COMP SIDE

17

18

19

14

15

16

11

12

13

20

21

DB72-00658A CLOTH COMP UPPER

48A135RV2EL COMPRESSOR

44B092QV2EL COMPRESSOR

DB73-00070A GROMMET-ISOLATOR

DB73-00067A GROMMET-ISOLATOR

DB60-30029A NUT-WASHER

DB63-20003A GASKET

DB63-10034A COVER-TERMINAL

DB32-10043F THERMISTOR-OLP

DB60-30018A NUT-FLANGE

DB99-00187A ASSY-4WAY VALVE

DB99-00168A ASSY-4WAY VALVE

DB99-00186A ASS’Y-CAPI TUBE

DB99-00169A ASS’Y-CAPI TUBE

DB96-01588A ASS’Y-CONDENSER

DB96-10502A ASS’Y-CONDENSER

21-1 DB32-10040D THERMISTOR-OUT

22 DB64-00433A CABI-SIDE

23 DB64-00400A HANDLE-CABI RH

Specification

FELT

48A135RV2EL

44B092QV2EL

NR

NR

HEX 2C MB ZPC

EPDM

NYLON

204CT/103AT

M5,SM20C

ASS’Y

ASS’Y

ASS’Y

ASS’Y

ASS’Y

ASS’Y

ASS’Y

SECC-P

PP

ASS’Y

ASS’Y

ASS’Y

ASS’Y

FELT

FELT

FELT

FELT

HSWR

2C SM20C M6 NTR

AS+G/F,ø405

AMASS-020WTVB

ASS’Y

ASS’Y

ASS’Y

ASS’Y

12A,21mH

SECC-P

SH12VCDX

1

0

1

0

1

1

1

0

1

1

1

0

3

1

1

1

1

0

3

1

0

1

0

1

0

1

0

1

0

1

1

1

1

1

1

1

0

Q’TY

SH09VCDX

0

1

0

1

1

1

0

1

1

1

1

3

3

1

1

1

0

1

0

0

1

0

1

0

1

0

1

0

1

1

1

1

1

1

1

0

1

Samsung Electronics 6-4

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-2

6-3 Remote Control & PCB Box

6-3-1 ASS'Y Remote Control : (DB93-00251L)

3

■ Parts List

No

5

6

7

3

4

1

2

1

2

Description

INLAY LCD

CASE TOP

LCD

KEY RUBBER

ASS’Y PCB REMOCON

CASE LOW

BATTERY COVER

4

5

Q’TY

1

1

1

1

1

1

1

6

Remark

7

6-5 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-3

6-3-2 ASS’Y-Control IN(Indoor unit) : DB93-00960D

Exploded Views and Parts List

■ Parts List

No

1

2

3

Description

HOLDER CONTROL

ASSY MAIN PCB

ASSY TERMINAL BLOCK

4

9

10

11

12

13

7

8

5

6

14

15

16

17

18

Samsung Electronics

CONNECTOR WIRE FAN MOTOR

BRACKET EARTH

CONNECTOR WIRE EARTH

SCREW

CREW

HOLDER CLAMP IN

SEAL-PANEL FRONT RH

SEAL-H/CONTROL FRONT

MF CAPAITOR

CONNECTOR WIRE MF CAPACITOR

CONNECTOR WIRE EARTH

LEAD WIRE(N)

LEAD WIRE(L)

LEAD WIRE(C)

ASSY DISPLAY PC

Specification

ABS, UL94-V0

UL1015 AWG#16, ORG/SKY-BLUE/BRN

ASTRO1010

P.B.T+CF30%(BLK)

C2680-1/2H

SMP250-05(1), SMT-250(5)

SMP200-05(1), YMT-200(5)

SGCC-M

UL1015 AWG#16, GRN+YEL

WP, TH, +, M4, L8, ZPC(WHT), T.C

PH, +, M3, L22, ZPC(YEL), SWRCH10A

SGCC-M

1200nF, 450V, 39.6 x 16 x 27

ST730619

UL1015 AW#22, WHT

UL1015 AWG#20, GRN+YEL

UL1015 ASG#16, ORG

UL1015 AWG#16, SKY=BLUE

UL1015 AWG#16, BLK

Q’TY

4

1

5

1

1

2

1

1

2

1

1

1

1

2

2

1

1

1

1

2

1

6-6

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-4

Exploded Views and Parts List

6-3-3 ASS’Y-Control-Out(Outdoor unit) - 9K : DB93-00962A / 12K : DB93-00962B

APPLY SILICONE SEALANT

6-7

ASSY TERMINAL BLOCK DIAGRAM

CONNECT THIS TO LOWER PART OF TERMINAL BLOCK

ISOMETRIC VIEW

Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-5

Exploded Views and Parts List

■ Parts List

11

12

9

10

13

14

7

8

5

6

15

3

4

18

19

20

21

*

16

17

No.

1

2

Description

CASE CONTROL BASE

HEAT SINK

SCREW-MACHINE

PCB-ASSY

SCREW-MACHINE

SCREW-MACHINE

SCREW-TAPPING

SCREW-TAPPING

ASSY TERMINAL BLOCK

SCREW-MACHINE

RUBBER CLAMP

HOLDER WIRE

SCREW-MACHINE

COVER

CONNECTOR WIRE COMP

CONNECTOR WIRE REACTOR

CONNECTOR WIRE POWER

CONNECTOR WIRE RUN CAP.

CONNECTOR WIRE AC

FOAMLEX

MICA

RUN CAPACITOR

Samsung Electronics

Specification

RESIN-ABS

UL1015 AWG#16/RED

TR25-12G5/3T

UL1015 AWG#16/WHT

UL1015 AWG#16/SKY BLUE

LSA13024/ENAMAL 18T

UL1015 AWG#16/BLU

UL1015 AWG#16/GRN, YEL

TR-22-1-13/2T

165 x 30 x T2

18.4 x 23.3 (Hole : ø3.6)

1.7uF/ 400V

RESIN-ABS

DB62-00774A

DB62-01050A

M4 x 16 WSP PH+

DB93-00953A

DB93-00953B

M3 x 16 WSP PH+

M4 x 16 WSP PH+

M3 x 8 2S PH+

M3 x 14 SWP PH+

CBF-HARNESS

M4 x 25 WSP PH+

NBR

RESIN-ABS

M4 x 16 WSP PH+

Q’TY

DB93-00962A DB93-00962B

1 1

1

1

1

2

1

1

1

1

2

1

-

2

2

1

1

-

1

1

1

1

1

1

1

1

1

1

1

1

1

2

1

1

1

1

2

1

1

2

2

-

-

1

1

1

1

1

1

1

1

1

1

1

6-8

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-6

7. PCB Diagrams

7-1 ASS’Y PCB IN : DB93-00951A

TOP

BOTTOM

7-1 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-7

PCB Diagrams

■ Parts List

No Design Location Description Specification

42 C111

43 C601,701

44 C101,102

45 X301

46 SS71

47 F702

48 F701

49 F701

50 CN72

51 CN71

52 CN42

53 CN41

54 CN91

55 CN61

56 ST11

57 DSA1

58 PC01

59 PC31,32

60 PC02

61 BZ61

62 FT72

63 RY71

1 D701,702,703

8

9

6

7

4

5

2

3

D101

BD71

ZD11

ZD12

ZD71

CD11

Q201,401,602

Q603

10 Q301,302,601

11 Q901 ~ 904

12 IC05,06

13 IC04

14 IC51

DIODE-RECTIFIER

DIODE-RECTIFIER

DIODE-BRIDGE

DIODE-ZENER

DIODE-ZENER

DIODE-ZENER

DIODE-TVS

TR-SMALL SIGNAL

TR-SMALL SIGNAL

TR-SMALL SIGNL

TR-DIGITAL

TR-ARRAY

IC-MCU

IC-EEPROM

MRA4005,600V,1A,SMA,TP

UG2B, 100V, 2A, DO-204AC,TP

DF06S, 600V, 1A, SMD-4,TP

BZX84C3V/6, 350mW,SOT-23,T

BZX84-C11, 6V, 35MW, S

INR4749,24V/1W

ST02D-200,200W,DO

2SC2412K,NPN,200mW,SOT-2

MMST2907,PNP,200mW,SOT-

DTC114EKA,PNP

DTA114EKA,PNP,200MW,10K/10K

ULN2003AFW,NPN,1W,SOP-16 uPD780034

93LC56,128*16Bit,SOP

15 IC03

16 IC01

17 IC02

18 VA71,72,73

19 R606

20 R202 ~ R205

21 R206,601,602,902

22 R201,207,208,301,401,403,607,905

23 R102 ~ 104

24 R106,107

25 R503,504

26 R101,303,603,703,901

27 R105,302,604,605

28 R501,502

IC-VOLTAGE COMP KA7533,TO-92,30,SINGLE

IC-PWM CONTROLLLER TNY255P,DIP,8P,300MIL

REGULATER

VARISTOR

KA78L05

470V,4500A,17*12mm,BK

R-CHIP

R-CHIP

R-CHIP

R-CHIP

560OHM,5%,1/10W,DA,TP,2012

100KOHM,5%,1/8W,DA,TP,3216

10KOHM,5%,1/10W,DA,TP,2012

1KOHM,5%,1/10W,DA,TP,2012

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

220KOHM,5%,1/8W,DA,TP,3216

220OHM,5%,1/10W,DA,TP,2012

330OHM,5%, 1/10W,DA,TP,2012

4.7KOHM,5%,1/10W,DA,TP,2012

470OHM, 55,1/10W,DA,TP,2012

6.8KOHM,1%,1/10W,DA,TP,2012

29 R510,511

30 R701,706,707

31 R704,705

32 R702

R-CHIP

R-CARBORN

R-CARBORN

R-CARBORN

33 R402

34 XC71

R-CHIP

C-CERAMIC

35 C106 C-AL

36 C702 C-CERAMIC

37 C703

38 C301,510,511,903

39 C203,204,401,705

40 C103,107,109,110,112,201,202,302,500,501,502, 901

41 XC72

C-CERAMIC

C-CHIP

C-CHIP

C-CHIP

C-FILM

47KoHM,5%,1/10W,TP,2012

82KOHM,2W

10KOHM,2W

100KoHM,1/10W

6.8KOHM,5%,1/10W,DA,TP,2012

DISC,2.2nF,20%,400V,Y5V,TP,12

1000uF,10%,25V

10nF,+8—20%,50V,Y5V,TP1

4.7nF,275V

CL21B102KBNC

CL21B103KBNC

CL21B104KBNC

100nF,10%,275V,BK,18*6*12,15

C-AL

C-AL

C-AL

RESONATOR-CERAMIC

SSR

FUSE

FUSE-HOLDER

FUSE

CONNECTOR-HEADER

CONNECTOR-HEADER

CONNECTOR-HEADER

CONNECTOR-HEADER

CONNECTOR-HEADER

CONNECTOR-HEADER

TRANS SWITCHING

POSISTOR

PHOTO-COUPLER

PHOTO-COUPLER

PHOTO-COUPLER

BUZZER

FILTER

RELAY-POWER

470uF,20%,16V,GP,TP,10*12.5,5

47uF,20%,50V,GP,TP,6.3*11,5

6.8uF,20%,450V,GP,TP,10*16,T

10MHz,0.5%,TP,10*5

12VDC,2A,1mS

250V,1A,TIME-LAG

FUSE-HOLDER

250,5A

YW396-03AV,WHT

YW396-05AV,WHT

SMW250-03,BLU

SMW200-04,WHT

SMW200-12,WHT

SMW200-05,WHT

DC12V

DSA-332M,2pF,MAX,100MOHM

TLP181GB

TLP181

TLP620GR

CBE2220BA

LS403110

UKH-12S

2

5

8

3

4

4

3

1

5

2

1

1

1

1

2

1

2

3

1

1

1

Q’TY

3

2

1

1

1

1

1

1

1

3

4

2

1

1

1

1

2

1

1

1

1

1

1

1

1

2

4

11

1

2

1

1

1

1

1

1

1

Samsung Electronics 7-2

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-8

7-2 ASS’Y PCB Control-Out : DB93-00953A

TOP

7-3 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-9

BOTTOM

PCB Diagrams

Samsung Electronics 7-4

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-10

PCB Diagrams

■ Parts List

No Design Location Description Specification Q’TY

1 C101,C102,C103(7k,9k)

2 C101,C102,C103(12k)

C-AL

C-AL

3 C115

4 C408,C409,C410

5 C110,C201,C415

6 C107,C108,C109,C112

C-AL

C-AL

C-AL

C-AL

7 CABLE(JU;JV;JW=RED;BLU;YEL) CBF-HARNESS

8 CABLE(REACTOR01;02=YEL;WHT) CBF-HARNESS

9 CABLE(DCN01/DCN02) CBF-HARNESS

10 CABLE(PC01;PC02)

11 C303

12 C302,C506

CBF-HARNESS

C-CERAMIC,CHIP

C-CERAMIC,CHIP

13 C401,C402,C403,C404,C405,C406, C-CERAMIC,CHIP

C407

14 C701,C702

15 C202,C501,C502,C503,C504,C505,

C-CERAMIC,CHIP

C507,C508,C509,C703,C704,C706 C-CERAMIC,CHIP

16 C203

17 C305,C306

C-CERAMIC,CHIP

C-CERAMIC,CHIP

18 C106,C111,C116,C204,C705,C802

19 C414

20 C412

C-CERAMIC,CHIP

C-CERAMIC,CHIP

C-CERAMIC,CHIP

21 C113,C114,C411,C803

22 C104,C105,C304

23 C005,C006,C007

24 C001,C002

25 C301

C-CERAMIC,CHIP

C-CERAMIC,DISC

C-CERAMIC,DISC

C-CERAMIC,DISC

C-FILM,MPET

26 C413

27 C004

C-FILM,MPP

C-FILM,MPPF

28 C003 C-FILM,MPPF

29 Running capacitor(Main case+ screw) C-FILM,MPPF

30 CABLE (L;N=BRN;BLU) COIL CHOKE ASS’Y

31 FT00

32 FT01

33 L101

34 L001

35

40

45

50

51

52

53

54

55

CN51

36 CN52

37 CN02,CN31

38 CN01

39 X501

X701

41 D301,D103,D104,D105,D106

42 D101

43 D201

44 BD01

ZD21

46 ZD31

47 D102,D401,D402,D403

48 ZD22

49 FUSE

FUSE CLIP

H/S(PFC)

IC51

IC83

IC41

IC81

56 MICOM

57 IC15,IC21,IC31,IC32,IC54

58 IC11

59 IC16

RADIAL,560UF,105˚,20%,400V,2PIN,BK,35x50mm

RADIAL,680uF,105˚,20%,400V,2PIN,BK,35x50mm

RADIAL,RG 450V 10UF 12.5*20 TP

RADIAL,RZ 35V 22uF 6.3x11 TP

RADIAL,RZ 35V 47uF 6.3x11 TP

RADIAL,WD 25V 220uF 8x11.5 TP

HA01, #16, 270,280,290mm,RED,BLU,YEL(COMP)(CORE #1)

HA02, #16, 270,270mm,WHT,YEL(REACTOR)

HA04, #16, 140mm,BLU(DC-)

HA05, #20, 140mm,WHT(CON)

CL10B102KBNC

CL10B103KBNC

CL10C101JBNC

CL10C220JBNC

3

3

1

3

3

4

1

1

1

2

1

2

7

2

CL10F104ZANC

CL21B102KBNC

CL21B103KBNC

CL21B104KBNC

CL21B222KBNC

CL21B223KBNC

CL31F105ZANC

RADIAL,SC E 222M 10FF7

RADIAL,SCE 103Z 14FF7

RADIAL,SCE 472M 14FF7

RADIAL,5TY2ARB103KAN TP

RADIAL,PC2J104K 630V TP

RADIAL,330nF,10%,275V,TP,26x8.5x18m

RADIAL,680nF,10%,275V,BK,31x11x21

RMES-45H015UA

(LSA15009 ASS’Y, —mH,43X32X28mm,18Turn,CABLE)+C54

COIL CHOKE

COIL CHOKE

COIL CHOKE

COIL-CHIP

LS615014,—mH,38.5x38x30mm, 20Turn, 4PIN

LS615014S,—mH, 38.5X38X30mm,15Turn ,6PIN

RADIAL,10mH(DR6.5*7.5)

FCI 3216 R47K (0.47uH)

CONNECTOR-HEADER SMAW250A-04,RED,YENHO

CONNECTOR-HEADER SMAW250A-04,WHT,YENHO

CONNECTOR-HEADER YAW396A-03AV,WHT,YENHO

CONNECTOR-HEADER YAW396A-05AV,WHT,YENHO

CRYSTAL-RESONATOR CST 4MHZ

CRYSTAL-RESONATOR HC-49/S,12.288MHz

DIODE

DIODE

DIODE

DIODE-BRIGE

DIODE-ZENER

DIODE-ZENER

DIODE-ZENER

DIODE-ZENER

FUSE

FUSE-CLIP

ES1D,D0-214AC, 200V

FEP30JP,FORMING

US1G,D0-214AC, 400V

GS1B2560,FORMING

AXIAL,1N4749A

AXIAL,1N4751A

AXIAL,1N4937

MMBZ5232B

65TL 250V,20A

FC61B

12

1

2

6

1

1

4

3

3

2

1

1

1

1

1

1

1

1

1

1

1

1

2

1

1

1

5

1

1

1

1

1

4

1

1

2

HEAT SINK

IC-MASK

IC-LOGIC

IC-LOGIC

IC-LOGIC

27X17.5X40

S3C9434XZ0-SKB4

74HCT00D,SOP-14

LM324D

1

1

1

1

ULN2003ADR 1

IC-MICOM

IC-PHOTO-COUPLER

TMP88PH47F(MASK),QFP

TLP181(GRH-TLP),SOP,TP

IC-PWM CONTROLLER TOP222P

IC-REG KA78L05AZTA(0.1A Positive Vol Reg)

1

5

1

1

7-5 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-11

PCB Diagrams

■ Parts List

No Design Location Description

60 IC17

61 Q801

62 Q002

63 Q001

64 Q201,Q202,Q301,Q302,Q802

65 Q803

66 IC14

67 IC52,IC71

68 IPM(7k,9k)

69 IPM(12k)

70 LED2

71 LED3

72 LED1

73 PCB

74 R801

75 R003

76 R411

77 R501,R504

78 R502,R503

79 R205,R904,R905,R906

80 R204

81 R505

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

82 R303, R304 R-CHIP

83 R305,R401,R402,R403,R404,R405 R-CHIP

R406,R407,R506,R508,R702

84 R306

85 R101,R102

R-CHIP

R-CHIP

86 R803

87 R810

88 R113

89 R109

90 R805

91 R108

92 R106

93 R207,R806,R807

94 R507,R701

95 R414

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

IC-REG

IC-TR

IC-TR

IC-TR

IC-TR-DIGITAL

IC-TR-IGBT

IC-VOL REF

IC-VOL

IPM

IPM

LED_GRN

LED_RED

LED_YEL

PCB

R-CEMENT(S)

R-CEMENT(S)

R-CEMENT(S)

96 R413

97 R802

98 R412

99 R408,R409,R410

100 R107

101 R203,R302,R804

102 R415

103 R105

104 R110,R111,R112

105 R001, R002

106 R004

107 RV01,RV02

108 RV03

109 R005

110 R202

111 R201

112 R301

113 R104

114 DSS

115 DSA

116 PT01

117 PT02

118 VA02,VA05,VA06,VA07

119 VA01,VA04

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

R-CHIP

RELAY

RELAY-POWER

R-METAL OXIDE(S)

R-METAL OXIDE(S)

R-METAL OXIDE(S)

R-METAL OXIDE(S)

R-METAL OXIDE(S)

SURGE-ABSORBER

SURGE-ABSORBER

THERMISTER-PTC

TRANS-PULSE

VARISTER

VARISTER

Specification

KA78M05TU(0.1A Positive Vol Reg)

BC847B,NPN, SOT-23

KTA1715

KTC2814

KRC102S,NPN,200mW,10K-10K,SOT

IRG4BC30F(004).TO-220AB, IR

KA431DTF(3-Terminal Adjustable Reg)

RN5VT45(46)CA,SOT-23-5

PS21244-E, MIT,600V,15A

PS21245, MIT,600V,20A

SM4433(FORMING)

SA4433(FORMING)

SY4433(FORMING)

FR4,GREEN, 220X140mm, 15/20A-MISTU

3RJ 0.045ohm(10%,3W,CB,BK,12x8x25mm)

5RJ 200ohm(5%,5W,CB,BK,13x9x25.5mm)

7RJ 0.015ohm(10%,7W,CA,BK,35x9.5xmm)

MCR03EZH F1802, 18Kohm, 1/10W, 1%, 1608

MCR03EZH F2402, 24Kohm, 1/10W, 1%, 1608

MCR03EZH J102, 1.0Kohm, 1/8W, 5%, 1608

MCR03EZH J203, 20Kohm, 1/10W, 5%, 1608

MCR03EZH J331, 330ohm, 1/10W, 5%, 1608

MCR03EZH J471, 470ohm, 1/8W, 5%, 1608

MCR03EZH J472, 4.7Kohm, 1/10W, 5%, 1608

MCR03EZH J561, 560ohm, 1/10W, 5%, 1608

MCR100EZH J184, 180kohm, 1W, 5%, 6432

MCR100EZH J222, 2.2Kohm, 1W, 5%, 6432

MCR10EZH F1002, 10Kohm, 1/8W, 1%, 2012

MCR10EZH F1502, 15Kohm, 1/8W, 1%, 2012

MCR10EZH F1801, 1.8Kohm, 1/8W, 1%, 2012

MCR10EZH F2201, 2.2Kohm, 1/8W, 1%, 2012

MCR10EZH F6801, 6.8Kohm, 1/8W, 1%, 2012

MCR10EZH J102, 1.0Kohm, 1/8W, 5%, 2012

MCR10EZH J103, 10Kohm, 1/8W, 5%, 2012

MCR10EZH J105, 1.0Mohm, 1/8W, 5%, 2012

MCR10EZH J202, 2.0Kohm, 1/8W, 5%, 2012

MCR10EZH J203, 20Kohm, 1/8W, 5%, 2012

MCR10EZH J221, 220ohm, 1/8W, 5%, 2012

MCR10EZH J222, 2.2Kohm, 1/8W, 5%, 2012

MCR10EZH J330, 33ohm, 1/8W, 5%, 2012

MCR10EZH J332, 3.3Kohm, 1/8W, 5%, 2012

MCR10EZH J472, 4.7Kohm, 1/8W, 5%, 2012

MCR10EZH J473, 47Kohm, 1/8W, 5%, 2012

MCR10EZH J6R8, 6.8ohm, 1/8W, 5%, 2012

MCR18EZH F4703, 470Kohm, 1/4W, 1%, 3216

MCR50EZH F4703, 470Kohm, 1/2W, 1%, 5025

MCR50EZH J101, 100ohm, 1/2W, 5%, 5025

F3AA012E

UKH-12S,12VDC

AXIAL,MOR 1/4TSJ 100ohm, 5%, 1/4W, AA TP

AXIAL,MOR 2TSJ 100Kohm ,5%,2W,AA,TP

AXIAL,MOR 2TSJ 47Kohm,,5%,2W,AA,TP)

AXIAL,MOR 2TSJ 5.6Kohm,5%,2W,AA,TP)

MOR 3TSJ 47Kohm,5%,3W,AA,TP)

AXIAL,300V,DSS-301

AXIAL,500V,DSA-501

J512Q24E270M265

PT_20A , 1.4mH

470V,0.6W,50A,14MM,INR14D471K

470V,0.6W,50A,14MM,INR20D471K

Samsung Electronics

Q’TY

1

1

1

1

1

2

1

1

1

1

1

1

1

1

5

1

1

2

2

4

1

1

2

11

4

2

1

1

1

1

1

1

1

1

2

1

1

1

3

1

1

3

2

1

1

1

3

1

1

1

3

2

1

1

2

1

1

1

1

1

7-6

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-12

PCB Diagrams

7-3 ASS’Y DISPLAY : DB93-01601A

■ PART LIST

No

7

8

5

6

9

10

3

4

1

2

Description

PCB-DISPLAY

MODULE REMOCON

TACT SWITCH

C-CERAMIC

C-CERAMIC

DIODE SWITCHING

R-CARBON

CONNECTOR WAFER

C/W DIS & MODULE

HOLDER-LED

Specification

FR-1, T1.6

KSM-713TH5

KPT-1105A

CA 0A 50V 102K

CA 0A 50V 104Z

1N4148

470 1/2W 5%

SMAW200-05(WHT)

UL1007 AWG/26/11

HIPS

7-7

Q’TY

3

1

1

1

1

1

1

1

1

1

Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-13

8. Wiring Diagrams

8-1 Indoor Unit

Samsung Electronics 8-1

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-14

8-2 Outdoor Unit

8-2

CODE NO. : DB98-03527A

Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-15

Wiring Diagrams

YELLOW

ERROR MODE

LAMP of inverter PBA

BLUE RED

X

X

X

X X

X X

X

X

X

X

X

X

X

X

X

Description

Normal operation and communication(Indoor - Outdoor unit)

Abnormal communication(Indoor - Outdoor unit)

Trouble of the control power of the outdoor

Abnormal communication(Sub-Main micom)

No zero-crossing signal

Trouble of option setting

Abnormal increase of discharge temperature

Abnormal increase of OLP temperature

Abnormal increase of operation current

Over current of IPM circuit

Over voltage of IPM circuit

Over voltage and current of PFC circuit

Trouble of DC link voltage circuit

Tourble fo discharge temp-sensor(open/short)

Trouble of outdoor temp-sensor(open/short)

Trouble of deice temp-sensor(Open/short)

Trouble of OLP temp-sensor(open/short)

Trouble of AC current sensor(open/short) and Leakage of refrigerant (R-22)

X

: LAMP ON

: LAMP FLICKERING

: LAMP OFF

Samsung Electronics 8-3

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-16

M E M O

8-4 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-17

M E M O

Samsung Electronics 8-5

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-18

M E M O

8-6 Samsung Electronics

DB98_08728A(1)_SM_1 12/20/02 3:25 PM Page 5-19

Application date

UPDATE LOG SHEET

Page Part# Note(Cause & Solution) S/Bulletin#

Use this page to keep any special servicing information. (Service Bulletin, etc.)

If only parts number changes, Just change parts number directly on parts list.

And if you need more information, please see the service website.

Itself Solution

Integrated technology supporting electronic library http://itself.sec.samsung.co.kr

Copyright © 2002

By Samsung Electronics Co., Ltd.

All rights reserved.

This manual may not, in whole or in part, be copied, photocopied, reproduced, translated, or converted to any electronic or machine readable from without prior written permission of

Samsung Electronics Co., Ltd.

Printed in Korea.

DB98_08728A(1)_CO 12/20/02 3:27 PM Page 2

ELECTRONICS

© Samsung Electronics Co., Ltd. Dec. 2002.

Printed in Korea.

Code No. DB98-08728A(1)

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement