B Power and Auxiliary Relay Packs
Snaps in for easy installation
Fully self-contained transformer and relay
Zero Crossing for reliability and increased product life Essential component for ceiling mounted occupancy sensor
UL 2043 Plenum
Rated
Product
Overview
Features
PROJECT
LOCATION/TYPE
Description
Power packs provide 24VDC operating voltage to all Watt Stopper 24VDC occupancy sensors and
LightSaver controllers. Auxiliary relay packs are similar to power packs but have no transformer power supply, only an isolated relay.
Operation
Power packs consist of a transformer and highcurrent relay combined in one small, powerful package. The transformer has a primary high voltage input and a secondary, low voltage output
(24 VDC,114 mA with relay connected). The secondary voltage provides operating power to Watt
Stopper sensors. When the occupancy sensors detect motion or light sensors detect inadequate ambient light, they electrically close an internal circuit which sends 24 VDC back to the power or auxiliary relay packs that control the lighting system.
Plenum Rated
The B power packs are UL 2043 plenum rated with teflon coated low voltage leads and plenum rated plastic. This means that the power packs do not need to be installed in the junction box, but can be installed in the plenum. They are housed in ABS,
UL-rated 94V-0 plastic enclosures.
Applications
Watt Stopper power and auxiliary relay packs are designed to be flexible enough to control almost any lighting or HVAC load. For example, power packs can control lighting circuits, self-contained air conditioners, pumps, fans, motors, VAV systems, motorized damper controls and setback thermostats. They are excellent for any application which requires high voltage switching through low voltage controls. By linking power packs and sensors, an almost unlimited number of configurations can be obtained.
• Self-contained transformer relay system
• Available for 120, 220 to 240, 277 and 347 volt systems
• Capable of switching up to 20 Amps of electrical load (ballast)
• Installation in J-box not required
• Low voltage leads are teflon coated for use in plenum applications
• Can be used as a low voltage switch for other applications or as stand-alone low voltage switch
• 1/2 inch snap-in nipple attaches to standard electrical enclosures via 1/2 inch knockouts
• Zero crossing circuitry for reliability and increased product life (120, 277, 240 volt versions only) www.wattstopper.com
8 0 0 . 8 7 9 . 8 5 8 5
Specifications
System
Layout
• Secondary voltage of 24 VDC
• Secondary output of 150 mA, 114 mA with relay connected
• Low voltage leads are rated for 300 volts
• UL-rated 94V-0 plastic enclosure
• UL 2043 plenum rated
• Dimensions: 1.6" x 2.75" x 1.6" (41mm x 70mm x 41mm) with a 1/2 inch snap-in nipple
• UL and CUL listed; Five year warranty
Power Pack Installation
Power Pack
High voltage connection made inside J-box
Power Pack Schematic
White
Neutral
Black (Hot)
Red
Red
(High Voltage)
Red (+24 VDC)
Black (-COM)
(Low Voltage)
Blue (+SW)
Wiring
Diagrams
Ordering
Information
Installation
Notes
Power Pack with Ceiling Sensor
Neutral
Hot
White
Black
Power
Pack
24VDC
Sensor
Red
Red
Load
Load
Switch
Auxiliary Relay Pack with Sensor
N White
Hot Black
Power Pack
White (neutral)
Red (line)
Off
Switch
Red (load)
L
O
A
D
BLU Control Output
BLK Common
RED +24VDC
Occupancy Sensor
Slave Pack Red (load)
Red (line)
Off
Switch
L
O
A
D
Hot
Neutral
Catalog No.
B120E-P*
B277E-P*
B230E-P*
B347D-P
S120/277/347E-P
Load Ratings
Description Input Voltage Ballast(A) Incan(A) Motor(HP) Output
Power Pack
Power Pack
Power Pack
Power Pack
Relay Pack
120 VAC; 60 Hz
277 VAC; 60 Hz
220-240 VAC; 50-60 Hz
347 VAC; 60 Hz
120/277/347 VAC; 60 Hz
20
20
20
15
20/20/15
13
-
13
-
13/-/-
* These power packs feature zero crossing
**Output is 150 mA before relay is connected and 114 mA after relay is connected.
Power packs are white; auxiliary relay packs are black.
1
-
1
-
1/-/-
24 VDC; 150 mA**
24 VDC; 150 mA**
24 VDC; 150 mA**
24 VDC; 150 mA**
1. All Watt Stopper power packs should be installed in accordance with state, local, and national electrical codes and requirements.
2. Power packs are designed to attach to existing or new electrical enclosures with 1/2 inch knockouts. (Check electrical codes in your area.)
3. Most applications require UL listed, 18-22 AWG, 3-conductor, Class 2 cable for low voltage wiring. For plenum return ceilings use UL listed plenum-approved cables.
Pub. No. 6707 www.wattstopper.com