F700 Series
Variable Frequency Drives
POCKET REFERENCE GUIDE
Mitsubishi Electric Automation, Inc.
Discover the Many Facets of Mitsubishi Electric. The Power in Automation Solutions.
F500 – F700 Conversion Chart
F500 Model Number
F700 Model Number
240 Volt
FR-F520-3.7K-NA
FR-F520-5.5K-NA
FR-F520-7.5K-NA
FR-F520-11K-NA
FR-F520-15K-NA
FR-F520-18.5K-NA
FR-F520-22K-NA
FR-F520-30K-NA
FR-F520-37K-NA
FR-F520-45K-NA
FR-F520-55K-NA
FR-F720-00167-NA
FR-F720-00250-NA
FR-F720-00340-NA
FR-F720-00490-NA
FR-F720-00630-NA
FR-F720-00770-NA
FR-F720-00930-NA
FR-F720-01250-NA
FR-F720-01540-NA
FR-F720-01870-NA
FR-F720-02330-NA
480 Volt
FR-F540-3.7K-NA
FR-F540-5.5K-NA
FR-F740-7.5K-NA
FR-F540-11K-NA
FR-F540-15K-NA
FR-F540-18.5K-NA
FR-F540-22K-NA
FR-F540-30K-NA
FR-F540-37K-NA
FR-F540-45K-NA
FR-F540-55K-NA
FR-F540L-75K-NA
FR-F540L-90K-NA
FR-F540L-110K-NA
FR-F540L-132K-NA
FR-F540L-160K-NA
FR-F540L-185K-NA
FR-F540L-220K-NA
FR-F540L-280K-NA
FR-F540L-375K-NA
FR-F740-00083-NA
FR-F740-00126-NA
FR-F740-00170-NA
FR-F740-00250-NA
FR-F740-00310-NA
FR-F740-00380-NA
FR-F740-00470-NA
FR-F740-00620-NA
FR-F740-00770-NA
FR-F740-00930-NA
FR-F740-01160-NA
FR-F740-01800-NA
FR-F740-02160-NA
FR-F740-02600-NA
FR-F740-03250-NA
FR-F740-03610-NA
FR-F740-04320-NA
FR-F740-04810-NA
FR-F740-06100-NA
FR-F740-07700-NA
This chart shows the closest equivalent in performance between the F500 and F700
inverters. In some cases this may result in the selection of a drive with a higher rating
than necessary for a specific motor size.
240V Selection Chart
Motor
Motor
kW
HP
Current
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
4.2
6.8
9.6
15.2
22
28
42
54
68
80
104
130
154
192
248
312
360
Inverter
Model Number
FR-F720-00046-NA
FR-F720-00077-NA
FR-F720-00105-NA
FR-F720-00167-NA
FR-F720-00250-NA
FR-F720-00340-NA
FR-F720-00490-NA
FR-F720-00630-NA
FR-F720-00770-NA
FR-F720-00930-NA
FR-F720-01250-NA
FR-F720-01540-NA
FR-F720-01870-NA
FR-F720-02330-NA
FR-F720-03160-NA
FR-F720-03800-NA
FR-F720-04750-NA
SLD
LD
Frame
Rating Rating Size
4.6
7.7
10.5
16.7
25
34
49
63
77
93
125
154
187
233
316
380
475
4.2
7
9.6
15.2
23
31
45
58
70
85
114
140
170
212
288
346
432
A
B
C
C
C
D
D
E
F
F
F
G
H
H
K
K
K
480V Selection Chart
Motor
kW
HP
1
2
3
5
7.5
10
15
20
25
30
40
50
60
60
75
100
125
150
175
200
250
300
350
400
450
500
550
600
650
700
750
800
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
45
55
75
90
110
132
150
185
220
250
300
335
375
400
450
485
500
560
600
Typical
Motor
Current
2.1
3.4
4.8
7.6
11
14
21
27
34
40
52
65
77
77
96
124
156
180
200
240
302
361
414
477
515
590
683
770
866
962
1094
1212
Inverter
Model Number
SLD
LD Frame
Rating Rating Size
FR-F740-00023-NA 2.3
FR-F740-00038-NA 3.8
FR-F740-00052-NA 5.2
FR-F740-00083-NA 8.3
FR-F740-00126-NA 12.6
FR-F740-00170-NA 17
FR-F740-00250-NA 25
FR-F740-00310-NA 31
FR-F740-00380-NA 38
FR-F740-00470-NA 47
FR-F740-00620-NA 62
FR-F740-00770-NA 77
FR-F740-00770-NA 77
FR-F740-00930-NA 93
FR-F740-01160-NA 116
FR-F740-01800-NA 180
FR-F740-01800-NA 180
FR-F740-02160-NA 216
FR-F740-02160-NA 216
FR-F740-02600-NA 260
FR-F740-03250-NA 325
FR-F740-03610-NA 361
FR-F740-04320-NA 432
FR-F740-04810-NA 481
FR-F740-05470-NA 547
FR-F740-06100-NA 610
FR-F740-06830-NA 683
FR-F740-07700-NA 770
FR-F740-08660-NA 866
FR-F740-09620-NA 962
FR-F740-10940-NA 1094
FR-F740-12120-NA 1212
2.1
3.5
4.8
7.6
11.5
16
23
29
35
43
57
70
70
85
106
144
144
180
180
216
260
325
361
432
481
547
610
683
770
866
962
1094
C
C
C
C
C
D
D
E
E
F
F
G
G
H
H
H
H
J
J
J
K
K
L
L
M
M
M
N
N
P
P
P
SLD = 40° C Ambient, 110% overload 60 secs, 120% for 3 secs, 2 kHz switching frequency
LD = 50° C Ambient, 120% overload 60 secs, 150% for 3 secs, 2 kHz switching frequency
Dimensions – 240V and 480V Drives
Frame
Size
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Dimensions in inches (mm)
Height
Width
10.2 (260)
4.3 (110)
10.2 (260)
4.3 (110)
10.2 (260)
5.9 (150)
10.2 (260)
8.7 (220)
11.8 (300)
8.7 (220)
15.8 (400)
9.8 (250)
21.7(550)
12.8 (325)
21.7(550)
17.1 (435)
24.4 (620)
18.3 (465)
29.1 (740)
18.3 (465)
39.8 (1010)
19.6 (498)
39.8 (1010)
26.8 (680)
52.4 (1330)
31.1 (790)
62.2 (1580)
39.2 (995)
Depth
4.3 (110)
4.9 (125)
5.5 (140)
6.7 (170)
7.5 (190)
7.5 (190)
7.7 (195)
9.8 (250)
11.8 (300)
14.2 (360)
15 (380)
15 (380)
17.3 (440)
17.3 (440)
Details of Factory Supplied DC Link Chokes
FR-F740-NA
01800
02160
02600
03250
03610
04320
04810
05470
06100
06830
07700
08660
09620
10940
12120
Dimensions in inches (mm)
Height
Width
Depth
13.4 (340)
13.4 (340)
15.9 (405)
15.9 (405)
15.9 (405)
15.9 (405)
17.3 (440)
17.3 (440)
19.5 (495)
19.5 (495)
19.7 (500)
19.7 (500)
17.9 (455)
18.1 (460)
18.1 (460)
5.9 (150)
5.9 (150)
6.9 (175)
6.9 (175)
6.9 (175)
6.9 (175)
7.5 (190)
7.5 (190)
8.3 (210)
8.3 (210)
8.7 (220)
8.7 (220)
8.5 (215)
8.5 (215)
8.5 (215)
7.5 (190)
7.7 (195)
7.9 (200)
8 (205)
9.4 (240)
9.4 (240)
9.8 (250)
10 (255)
9.8 (250)
9.8 (250)
9.8 (250)
10.6 (270)
13.6 (345)
14.2 (360)
14.2 (360)
Approx.
Weight
lbs (kg)
44 (20)
48 (22)
57 (26)
62 (28)
64 (29)
66 (30)
77 (35)
84 (38)
92 (42)
101 (46)
110 (50)
125 (57)
147 (67)
187 (85)
209 (95)
Operation mode switchover
At powering on (external operation mode)
Parameter setting
Monitor/frequency setting
PU Jog operation mode
(Example)
Value change
PU operation mode
(output frequency monitor)
and frequency flicker.
Frequency setting has been
written and completed!!
Output current monitor
Output voltage monitor
Display the current
setting
Parameter setting mode
(Example)
Value change
Parameter and a setting value
flicker alternately.
Parameter write is completed!!
Parameter clear
Parameter
all clear
Alarm clear
Alarm history
Parameter copy
[Operation for displaying alarm history]
Past eight alarms can be displayed.
(The latest alarm is ended by ".".)
When no alarm history exists,
is displayed.
Description
Operation Panel Lock
Operation tried during operation panel lock
Parameter Write Error
An error occurred at parameter writing
to
Copy Operation Error
An error occurred at parameter copying
The RES signal is on or the PU and inverter cannot make
normal communication
to
Minor
Fault *4
Warnings *3
Function Name
Error Message *2
Key to DU07 Keypad Display Codes
Error
Stall Prevention (Overcurrent)
Overcurrent stall prevention
Stall Prevention
(Overvoltage)
Electronic Thermal Relay
Function Prealarm
Maintenance Signal Output
Overvoltage stall prevention. Appears while the regeneration
avoidance function is activated.
The electronic thermal O/L relay has reached 85% of the
specified value
Stop/reset on the operation panel is pressed during
external operation
The cumulative energization time has exceeded the
maintenance output timer set value
Fan Fault
Cooling fan is malfunctioning
PU Stop
Major Failures *5
Overcurrent Shutoff
During Acceleration
Overcurrent Shutoff
During Constant Speed
Overcurrent Shutoff During
Deceleration or Stop
Regenerative Overvoltage
Shutoff During Acceleration
Regenerative Overvoltage Shutoff During Constant Speed
Regenerative Overvoltage Shutoff
During Deceleration or Stop
Inverter Overload Shut-off
(Electronic Thermal O/L Relay)*1
Motor Overload Shut-off
(Electronic Thermal O/L Relay)*1
An overcurrent occurred during acceleration
An overcurrent occurred during constant speed operation
An overcurrent occurred during deceleration and at a stop
An overvoltage occurred during acceleration
An overvoltage occurred during constant speed operation
An overvoltage occurred during deceleration and at a stop
The electronic thermal relay function for inverter element
protection is activated
The electronic thermal relay function for motor protection
is activated
Fin Overheat
Instantaneous Power Failure
Protection
Undervoltage Protection
The heatsink overheated
An instantaneous power failure occurred at an input
power supply
The main circuit DC voltage became low
Input Phase Failure
One of the three phases on the inverter input side opened
Stall Prevention
The output frequency dropped to 0.5Hz as a result of
deceleration due to excess motor load
Output Side Earth (Ground)
Fault Overcurrent Protection
An earth (ground) fault occurred on the inverter’s output side
Output Phase Failure Protect.
One of the three phases on the inverter output side opened
External Thermal Relay
Operation *6
The external thermal relay connected to the terminal OH
was operated
The motor overheat status is detected for 10s or more by the
external PTC thermistor input connected to the terminal AU
PTC Thermistor Operation
HC Unit Alarm
An alarm occurred in the option card or an AC power supply is
connected to the R/L1, S/L2, T/L3 when the high power factor
converter connection is set
Functional Option Error
A communication error occurred in the communication option
Option Card Disconnection
Card is disconnected or misconnected
Parameter Storage Device
Alarm
Operation of the element where parameters are stored
became abnormal. (control circuit board)
PU Disconnection
A communication error between the PU and inverter occurred,
the communication interval exceeded the permissible time
during the RS-485 communication with the PU connector, or
communication errors exceed the number of retries during the
RS-485 communication
Notes:
1. Resetting the inverter initializes the internal thermal integrated data of the electronic thermal relay function.
2. The error message shows an operational error. The inverter output is not shut off.
3. Warnings are messages given before major failures occur. The inverter output is not shut off.
4. Minor faults warn the operator of failures with output signals. The inverter output is not shut off.
5. When major failures occur, the protective functions are activated to shut off the inverter output and output the alarms.
6. The external thermal operates only when the OH signal is set in Pr. 178 to Pr. 189 (input terminal function selection).
Indication
Your Distributor:
Mitsubishi Electric Automation, Inc.
500 Corporate Woods Parkway
Vernon Hills, IL 60061
Phn: (847) 478-2100
Fax: (847) 478-2253
www.meau.com
Mitsubishi Electric Automation, Inc.
4299 14th Avenue
Markham, Ontario L3R 0J2
Phn: (905) 475-8989
Fax: (905) 475-7935
Printed with Soy inks.
Effective May, 2006.
Specifications subject to change without notice.
L-VH-04031
Mitsubishi Electric Automation, Inc.
Discover the Many Facets of Mitsubishi Electric. The Power in Automation Solutions.
Automation Platforms™ • Industrial Computers • Programmable Logic Controllers • Servo Systems • Motion Control • Variable Frequency Drives • Human Machine
Interfaces Uninterruptible Power Supply Systems • Software • Computerized Numerical Controls • PC Based Control • Robots • Industrial Sewing Equipment