Installation & Owner’s Manual
MINISPLIT
HIGH WALL
MODELS
RVHC 09-12DS
RVHC 18AS
AIR CONDITIONER
The units comply with one or more of the following marks - see unit for details.
J355-EN.indd 1
EN 035M00032-000
1/12/07 3:20:50 PM
CONTENTS
Safety Precautions ................................................... 3
Part Names ................................................................ 4
Manual Operation ..................................................... 5
How the Air Conditioner Works............................... 5
Optimal Operation .................................................... 6
Preparation Before Installation ............................... 6
Installation Procedure .............................................. 8
Maintenance ............................................................ 14
Operation Tips ........................................................ 15
Please read this installation
manual carefully before starting
the installation. It will tell you
necessary information.
Troubleshooting Guide .......................................... 16
Technical Specification .......................................... 17
Declaration of Conformity ..................................... 19
Quality POLICY
We will continuously strive to satisfy
our customers with consistent
reliability in product, service and
support through superior quality,
service culture and distinctive
technology.
J355-EN.indd 2
R410A
Set
RVHCxxDSAAAR / RVHCxxASAAAR
Outdoor
RVJCxxDS-AAR / RVJCxxAS-AAR
Indoor
RVKCxxDS-AAR / RVKCxxAS-AAR
1/12/07 3:20:51 PM
REQUIRED TOOLS
1.
2.
3.
4.
5.
6.
7.
8.
Screw driver
Hexagonal wrench
Torque wrench
Spanner
Reamer
Hole core drill
Tape measure
Thermometer
9.
10.
11.
12.
13.
14.
15.
EXTENDED PARTS
Manifold gauge
Gas leak detector
Vacuum pump
Pipe clamp
Pipe cutter
Flare tool set
Electrical circuit tester
1. Refrigarant Pipe
Models
Liquid size
Gas size
07-09
1/4 inch
3/8 inch
12-18
1/4 inch
1/2 inch
2. Pipe insulation material (Polyethylene foam 9 mm thick)
3. Vinyl tape
4. Putty
SAFETY PRECAUTIONS
• Please read this installation manual carefully before starting installation of the unit.
• This air conditioning system contains refrigerant under pressure, rotating parts and electrical connection which
may be dangerous and can cause injury. Installation and maintenance of this air conditioning system should only
be carried out by trained and qualified personnel.
• After unpacking, please check the unit carefully for possible damage.
• Before undertaking any work on the unit, make sure that the power supply has been disconnected.
WARNING & CAUTIONS
INSTALLATION
Do not store or unpack the unit in a wet area or
expose to rain or water.
Do not install in a place where flammable gas
may leak.
It may cause the unit to short circuit and may result electric
shocks or fire.
It may cause fire.
Do not conduct installation in wet area or in the
rain.
This system is designed for domestic or residential
use only.
It is a high risk to cause the electrical shocks.
If used in certain environments, such as a manufacturing
workplace, the equipment may not function efficiently.
ENGLISH
J355-EN.indd 3
EN
3
1/12/07 3:20:51 PM
PART NAMES
INDOOR UNIT
■ INDOOR & OUTDOOR UNIT
1
2
3
4
5
6
7
Front panel
Air inlet
Air filter
Air outlet
Horizontal air flow grille
Vertical air flow louver
Display panel
8 Remote controller signal
9
0
=
~
receiver
Remote controller
Manual control button
Connecting pipe, drain hose
Air inlet (side and rear)
Air outlet
■ DISPLAY PANEL
1 AUTO indicator
2
3
OUTDOOR UNIT
4
5
DISPLAY PANEL
Signal receptor
This indicator illuminates when the air conditioner is in AUTO
operation.
TIMER indicator
This indicator illuminates when TIMER is set ON/OFF.
DEFROST indicator (For Cooling & Heating models only)
This indicator illuminates when the air conditioner starts
defrosting automatically or when the warm air control feature
is activated in heating operation.
TEMPERATURE indicator
A) Usually it displays the temperature settings.
When change the setting temperature, this indicator
begins to flash, and stops 20 seconds later.
B) It displays the room temperature when the air
conditioner is in FAN only operation.
C) When the unit stops operation, it returns to original
factory settings.
D) Displays the malfunction code or protection code.
FREQUENCY indicator
This indicator appears only when the compressor is in
operation and indicates the current operating frequency.
NOTE
AUTO TIMER DEF.
1
2
3
FREQUENCY
4
5
All the pictures in this manual are for explanation purpose
only. They may be slightly different from the air conditioner
your purchased. The actual shape shall prevail.
OPERATING TEMPERATURE
Temperature
Mode
Cooling
operation
Heating
operation
Drying
operation
Room temperature
17°C-32°C
17°C-30°C
17°C-32°C
Outdoor
temperature
18°C-43°C
-7°C-24°C
18°C-43°C
CAUTIONS
1. If air conditioner is used outside of the above conditions,
certain safety protection features may come into operation
cause the unit to function abnormally.
2. Room relative humidity less than 80%. If the air conditioner
operates in excess of this figure, the surface of the air conditioner
may attract condensation. Please sets the vertical air flow
louver to its maximum angle (Vertically to the floor), and
set HIGH fan mode.
3. Optimum performance will be achieved within these
operating temperature.
4
J355-EN.indd 4
ENGLISH
1/12/07 3:20:53 PM
MANUAL OPERATION
Manual operation can be used temporarily in case you cannot find the remote controller or its batteries are
exhausted.
1 Open and lift the front panel up to an angle at which it
remains fixed with a clicking sound.
2 Press the button until the AUTO indicator is lit, the unit
will work in forced AUTO mode.
3 Close the panel firmly to its original position.
Panel
CAUTIONS
• Once you push the manual button, the operation mode
is shifted in an order as: AUTO, COOL, OFF.
• Push the button twice, the unit will operate in forced COOL
mode. This is used for testing purposes only.
• Third press will stop the operation and turn off the air
conditioner operation.
• To restore the remote controller operation, use the remote
controller directly.
AUTO / COOL
Manual control button
HOW THE AIR CONDITIONER WORKS
■ AUTOMATIC OPERATION
Press Sleep button
• When you set the air conditioner in AUTO mode, it will
automatically select cooling, heating (cooling/heating
models only), or fan only operation depending on
what temperature you have selected and the room
temperature.
• The air conditioner will control room temperature
automatically around the temperature point set by you.
• If the AUTO mode is uncomfortable, you can select desired
conditions manually.
1
1
Set
Temperature
1 hour
1 hour
Cooling
Press Sleep button
Set
Temperature
■ SLEEP OPERATION
• When you push SLEEP button during cooling, heating
(cooling only type without), or AUTO operation, the
air conditioner will automatically increase (cooling) or
decrease (heating) 1°C per hour. The set temperature
will be steady 2 hours later.
• The fan speed will be automatically controlled.
1
1
1 hour
Cooling
1 hour
Heating
■ DRYING OPERATION
Fan only
• The dry mode will automatically select the drying operation
based on the difference between the set temperature and
the actual room temperature.
• The temperature is regulated while dehumidifying by repeating
turning on and off of the cooling operation or fan only. The
fan is low.
Cooling
Fan only
Room
temperature
EN
Cooling
Time
set temperature
DRYING operation
ENGLISH
J355-EN.indd 5
5
1/12/07 3:20:54 PM
OPTIMAL OPERATION
To achieve optimal performance, please note the following:
• Adjust the air flow direction correctly so that it is not directed on people.
• Adjust the temperature to achieve the highest comfort level. Do not adjust the unit to excessive temperature
levels.
• Close doors and windows on COOL or HEAT modes, or performance may be reduced.
• Use TIMER ON button on the remote controller to select a time you want to start your air conditioner.
• Do not put any object near air inlet or air outlet, as the efficiency of the air conditioner may be reduced and the air
conditioner may stop running.
• Clean the air filter periodically, otherwise cooling or heating performance may be reduced.
• Do not operate unit with horizontal louver in closed position.
PREPARATION BEFORE INSTALLATION
• Before doing any work, check the interior power supply cord and the main breaker capacity are sufficient and the
installation area is sufficient and complies with the requirements.
• Check that the power supply available agrees with name plate voltage.
• Electrical work, wiring and cables must be in compliance with national and local wiring codes and standard.
• Do not use the extension cables. In the case extended cables are needed, use the terminal block.
SELECTION OF THE LOCATION
• Select a place which provides the space around the units as shown in the diagram below.
INDOOR UNIT
Models
OUTDOOR UNIT
07
09
12
18
Models
07
09
12
18
A
12cm
12cm
12cm
12cm
A
30cm
30cm
30cm
30cm
B
70cm
70cm
70cm
70cm
B
200cm
200cm
200cm
200cm
C
12cm
12cm
12cm
12cm
C
60cm
60cm
60cm
60cm
D
15cm
15cm
15cm
15cm
D
30cm
30cm
30cm
30cm
CAUTION
• Do not install in a place that cannot bear the weight of the unit.
6
J355-EN.indd 6
ENGLISH
1/12/07 3:20:56 PM
OUTDOOR UNIT PICTURES
RVJC 07-12
RVJC 18
750
285
843
313
135
351.2
590
694.5
301.5
141.5
560.1
335
125
290
235
62
530
110
PARTS INSTALLATION
Name of part
Number
Q’ty
1
2
Clip anchor
8
3
Self-tapping screw A ST3.9X25
8
4
3
12c
mm
inim
2
um
um
Installation plate
15cm minim
1
1
Connecting Liquid side ø 6.35
Parts you
pipe
ø 9.53 (<12000Btu/h model)
must
Gas
side
assembly
ø 12.7 (f12000Btu/h model) purchase
5
Remote controller
1
6
Self-tapping screw B ST3.9X10
2
7
Remote controller holder
1
8
Seal
1
9
Drain joint
1
EN
12cm min
imum
Air F
ilter
Self-tapping screw B
ST3.9X10
NOTES
5
Remote Controller
holder
CAUTIONS
Remote Controller
A
60cm minimum
• Ensure that the space around the left and right of the
indoor unit is more than 12cm.
The indoor unit should be installed allowing a minimum
clearance of 15cm from the ceiling.
• Use a stud finder to locate studs to prevent unnecessary
damage to the wall.
• A minimum pipe run of 3 metres is required to minimise
vibration & excessive noise.
• The indoor unit should be installed on the wall at a height
of 2.3 metres or more from the floor.
• A, B and C directions should be free from obstructions.
4
7
6
Except the above parts provided, the other parts needed
during installation you must purchase.
30cm
m
inimu
m
30cm
B
u
minim
m
m
inimu
mm
200c
60cm
m
inim
um
C
Loop the
connective
cable.
NOTES
• This illustration is for explanation purposes only.
• Copper lines must be insulated independently.
ENGLISH
J355-EN.indd 7
7
1/12/07 3:20:57 PM
INSTALLATION PROCEDURE
INDOOR UNIT
■ Fixing
■ Wiring
• Place the installation guide pattern on the designated
installation place and mark the hole position.
• Drill a hole and mount installation plate.
• This indoor unit is ready for connection to the outdoor unit.
ø 65 mm
• After determining the pipe hole position. Drill the hole
at a slight downward slant towards the outdoor side.
Note:
When installing the
refrigerant pipes from
others side. A hole
must be place to
allow fall towards the
outdoor unit.
. .. .. .
.. .. .. ..
.. .........
.
.
. ...... ..
.
..... ..
.
.. .. ..
. .
Indoor
A Right
B Right
150mm or more to ceiling
Installation plate
Indoor unit outline
45
250
120mm or more
to wall
Left refrigerant
pipe hole 65
750
120mm or more
to wall
MODEL 18
150mm or more to ceiling
Installation plate
120mm or more
to wall
F Left
E Rear Bottom
■ Piping
The auxiliary piping can be connected in the directions
shown the above diagram. To connect in the D, E and
F direction, pipes will need to be extended.
• Bend pipes carefully to avoid flattening or obstructing
them if the pipes are bent incorrectly, the indoor unit
may be unstable on the wall.
• Carefully arrange pipes so that pipes do not stick out
of the rear plate of the indoor unit.
120mm or more
to wall
293
Left refrigerant
pipe hole 65
D Right
C Right
CAUTIONS
Right refrigerant
pipe hole 65
( 12000Btu/h model)
Indoor unit outline
• Never modify the unit by removing any of the safety
guards or by passing any of the safety interlock
switches.
• Connect the interconnecting cable correctly and connect the connecting cable to terminal as identified with
their respective marking.
• Do not damage the conductor core or inner insulation
of power supply cables and do not deform or crush the
cables.
Outdoor
.
..
.. .. ..
.. .. .. .
.. .........
.
. .. .. .. .
.
........ ..
.
..... .. .
. ..
.
.
. . .
.. ..
• Make 6 mm 4-6 holes, in the wall at the four corners of
mounting plate (bracket) then insert appropriate mounting
devices.
• Install the mounting plate using 4-6 pieces of mounting
screw securely at four corners and tighten the screw
completely. Do not over tighten the screws and deform
the back plate.
MODEL 07-12
CAUTION
Right refrigerant
pipe hole 65
920
( 12000Btu/h model)
CAUTION
• Be careful when handling the sharp edge of the mounting plate.
8
J355-EN.indd 8
ENGLISH
1/12/07 3:20:58 PM
■ Drain hose
• Drain hose is flexible and can be routed to suit various
piping arrangements. The drain line must include elbow
trap (U bend). Connect a plastic condensate pipe with
an internal diameter of 12 mm.
For right connection
Drain hose
Drain cap
Verification of condensate water drainage:
Fill the drain pan with water and observe evacuation.
Note: Do not put the drain hose end into water.
• The drain hose can be connected to the left or the right
side.
For left and left rear piping (Factory standard)
Drain cap
EN
Drain hose
■ Indoor Unit Fixing
•
•
•
•
Thread the indoor unit piping and cable through the hole.
Hang the top of the unit onto the upper ridge of them in mounting plate.
Make sure that the unit is correctly hung in place by sliding it to the left, then to the right.
Press the bottom left and bottom right hand corners of the unit against the mounting plate until the fixing prongs
click into place in the retainers provided to that effect.
Drainage line
a
Interconnection cable
Condensate
drainage line
Vinyl tape
a) Access plate for the
condensate drainage
pump detection
(condensate pump
is available as an
accessory).
Note: The condensate evacuation line should be taped to the
refrigerant lines with vinyl tape.
ENGLISH
J355-EN.indd 9
9
1/12/07 3:21:00 PM
OUTDOOR UNIT
■ Fixing and Piping
• Piping must be performed by qualified personnel according to good refrigeration systems practices.
• Piping materials and insulation materials must be of
refrigerant quality.
• Select the pipe diameters according to the size of unit
and cut the pipe to design length by using pipe cutter.
• Install the flare nuts and flare the end of the pipes.
• Check that no foreign bodies are inside the piping.
• Align the central of the connecting pipes and tighten
the flare nut.
• Fix piping with pipe clamps and check that any pipe
vibrations cannot be transmitted to the building structure.
NOTES
• Connect the pipe correctly.
• Do not apply the excessive torque.
• Use an appropriate bending tool to form curves and
avoid over-tightening the refrigerant tubes.
• To prevent heat loss, the two lines must be insulated
separately.
■ Maximum Piping Length
Unit size
(m)
MODELS
7
9
12
18
10
15
18
20
Refrigerant charge to be added per extra meter
of piping length when more than 7.5 meters.
Unit size
g/m
MODELS
7
9
12
18
30
30
30
30
■ Refrigerant piping connections
(FLARE connections)
To avoid alteration of unit capacities, check that piping
lengths and changes in elevation are kept to a strict
minimum.
Before connectiong the refrigerant lines, follow the
procedures below (if pre-charged connection lines are
not supplied):
• Select copper pipe diameters according to the size of
unit to be installed.
• Install the refrigeration lines, checking that no foreign
bodies get inside the piping.
• Install the flare connectors and flare the ends of the
pipes.
• Evacuate the piping. This operation, which should last
at least 15 minutes if there are large piping lengths and
changes in elevation, should be followed by a leak test.
The suction line must have a 2% gradient up to the
compressor on horizontal sections.
Where piping lengths are unusually long and include a
large number of oil traps, it may be necessary to adjust
to compressor charge.
10
J355-EN.indd 10
ENGLISH
1/12/07 3:21:01 PM
To this effect, when the piping has been evacuated, close the pressure gauge tap, note the value on the gauge,
then wait for 15 minutes. If the needle moves, there is a leak in the system. Make the necessary adjustments or
repairs and repeat this procedure until the needle no longer moves.
• Open the service valves and top up the refrigerant charge if necessary.
Insulation
Low pressure
High pressure
Manifold
Liquid valve
Pressure tap
Minimum thickness 6 mm
Outdoor unit
Heat pump
(discharge)
Gas line
Gas valve
Indoor unit
Liquid line
Heat pump
R-410A
Liquid
Cooling
Cooling
(suction)
This unit is shipped complete with a charge of R-410A refrigerant
that will be sufficient for an interconnecting piping length of 7.5
meters.
Heat pump
(discharge)
Heat pump
EN
GAS
Liquid
Cooling
(suction)
Cooling
COLD AREA RECOMMENDATION
• Outdoor heat pump unit : install the unit at least 10 cm above ground level to facilitate drainage of defrost water
and prevent accumulation of ice. In effect, defrost water can cause accumulation of ice under the unit during
subfreezing outdoor temperatures.
• In areas with heavy snowfall it is best to install the unit on wall supports.
• In some regions, it is necessary to heat the bottom of the condensate drainage pan and the condensate drainage
piping to avoid ice formation, and resulting ice build-up in the fan compartment (heater strip must be at least
25 w/m).
OK
ENGLISH
J355-EN.indd 11
11
1/12/07 3:21:02 PM
■ Wiring
Prepare the power source for exclusive with the air conditioner.
The supply voltage must comply with the rated voltage of the air conditioner: The plug socket shall be accessible after
installation.
Remark: All the wiring must be based on the wiring nameplate which is shown on the model.
CAUTIONS
• Perform the wiring with sufficient capacity. Installation places legally require a short circuit isolator to be attached
to prevent electrical shock.
• Do not extend the power cable code by cutting.
• Power voltage should be in the range of 90%~110% of rated voltage.
• The plug of the air conditioner takes a grounding leg, and clients should use a grounding socket so that the air
conditioner can be grounded efficiently.
• If the power cord is damaged, replacement should be conducted by qualified technician or a serviceman.
NOTE
Remark per EMC Directive 89/336/EEC
To prevent flicker impressions during the start of the compressor (technical process), following installation conditions
do apply.
1. The power connection for the air conditioner has to be done at the main power distribution.
The distribution has to be of a low impedance, normally the required impedance reaches at a 32 A fusing point.
2. No other equipment has to be connected with this power line.
3. For detailed installation acceptance, please refer to your contract with the power supplier if restrictions do apply
for products like washing machines, air conditioner or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
5. For any question, contact your local dealer.
CAUTIONS
• Never modify the unit by removing any of the safety guards or by bypassing any of the safety interlock switches.
• Connect the connecting cable correctly and connect the connecting cable to terminal as identified with their
respective marks.
• Do not scratch the conductive core & inner insulator of power supply cables and do not deform or smash on the
surface of cables.
■ Electrical Connections
All electrical wiring and connections must comply with local codes and standards. Power supply cord and interconnection
cord used must not be lighter than Polychloroprene sheathed cord (245 IEC 57 or H05RN-F).
Disconnecting device must have a contact separation of at least 3 mm.
Models : 07-18
Power supply
220-240V/1Ph/50Hz
L
N
S
Indoor Unit
L
N
S
Outdoor Unit
For correct installation, a proper ground connection must be made for unit.
12
J355-EN.indd 12
ENGLISH
1/12/07 3:21:03 PM
■ Wiring Connection
Models : 07-18
Indoor
Outdoor
Terminal block of indoor unit
L
N
S
L
Terminal block of outdoor unit
N
L
S
N
S
Cord clamp
To outdoor unit
To indoor unit
To outdoor unit
7000/9000/18000Btu/h model
12000Btu/h model
■ Electrical Work
Model
Power Source
Switch and Fuse rating
Wiring size
25A
f 1.5 mm2
25A
f 2.5 mm2
220-240V ~ 50Hz
7000-12000 Btu/h
220-230V ~ 60Hz
220-240V ~ 50Hz
18000 Btu/h
220-230V ~ 60Hz
NOTE
The supply voltage must be consistent with the rate voltage of the air conditioner.
EN
■ Defrosting Operation (Available for heating only)
1. Condition to start defrosting: Units will switch to defrosting
mode when either of the following conditions is met.
a. Unit has been running under T3 < 0ºC for 40 minutes
and T3 < -3ºC for 3 minutes.
Starting Defrosting Mode under condition a.
T3 (°C)
2
1
0
5
10
15
20
25
30
35
40
45
0
50
Time
Elapsed
(min)
-1
-2
b. Unit has been running at high temperature protection
mode* for 90 minutes. (*High temperature protection
mode: when coil temperature of indoor unit reaches
55°C, outdoor unit will turn off external unit fan but
still keep compressor running).
2. Condition to stop defrosting: Units will switch back to
heating mode when either of the following conditions
is met.
a. Unit has been running at defrosting mode for 10
minutes.
b. T3 > 20°C
Remark: T3 is coil temperature of outdoor units.
-3
3 min
-4
-5
40 min
Heating mode
Defrosting mode
ENGLISH
J355-EN.indd 13
13
1/12/07 3:21:04 PM
MAINTENANCE
WARNING
Household
Drain
Cleaner
It is necessary to stop the air conditioner and disconnect the power
supply before cleaning.
No
■ Cleaning the indoor unit and remote controller
CAUTION
Thinner
• Use a dry cloth to wipe the indoor unit and remote controller.
• A cloth dampened with cold water may be used on the indoor unit if it
is very dirty.
• The front panel of the indoor unit can be removed and cleaned with
water. Then wipe it with a dry cloth.
• Do not use a chemically treated cloth or duster to clean the unit.
• Do not use benzine, thinner, polishing powder, or similar solvents for
cleaning. These may cause the plastic surface to crack or deform.
■ Cleaning the air filter
Filter Handle
A clogged air filter reduces the cooling efficiency of this unit. Please clean
the filter once every 2 weeks.
1. Lift the indoor unit panel up to an angle until it stops with a clicking
sound.
2. Take hold of the handle of the air filter and lift it up slightly to take it out
from the filter holder, then pull it downwards.
3. Remove the AIR FILTER from the indoor unit.
• Clean the AIR FILTER once two weeks.
• Clean the AIR FILTER with a vacuum cleaner or water, then dry it up
in cool place.
4. Remove the Electrostatic Filter from its support frame as shown in
the Figure on the left (Not applicable to the units without electrostatic
filter).
Do not touch this Electrostatic Filter within 10 minutes after opening
the inlet grille, it may cause an electric shock.
• Clean the Electrostatic Filter with mild detergent or water and dry in
the sunlight for two hours.
• Before re-install the Electrostatic Filter, check whether the corona
line or support frame is damaged or not.
5. Install the AIR FILTER back into position.
6. Insert the upper portion of the AIR FILTER back into the unit taking
care that the left and right edges line up correctly and place filter into
position.
■ Maintenance
If you plan to idle the unit for a long time, perform the following:
(1) Operate the fan for about half a day to dry the inside of the unit.
(2) Stop the air conditioner and disconnect power.
Remove the batteries from the remote controller.
(3) The outdoor unit requires periodic maintenance and cleaning. Do not
attempt to do this yourself.
Contact your dealer or servicer.
■ Checks before operation
• Check that the wiring is not broken off or disconnected.
• Check that the air filter is installed.
• Check if the air outlet or inlet is blocked after the air conditioner has not
been used for a long time.
CAUTION
• Do not touch the metal parts of the unit when removing the filter.
Injuries can occur when handling sharp metal edges.
• Do not use water to clean inside the air conditioner.
Exposure to water can destroy the insulation, leading to possible
electric shock.
• When cleaning the unit, first make sure that the power and circuit
breaker are turned off.
14
J355-EN.indd 14
ENGLISH
1/12/07 3:21:05 PM
OPERATION TIPS
The following events may occur during normal operation.
1. Protection of the air conditioner.
Compressor protection
• The compressor cannot restart for 3 minutes after it stops.
Anti-cold air (Cooling and heating models only)
• The unit is designed not to blow cold air on HEAT mode, when the indoor heat exchanger is in one of the
following three situations and the set temperature has not been reached.
A) When heating has just starting.
B) Defrosting.
C) Low temperature heating.
• The indoor or outdoor fan stop running when defrosting (Cooling and heating models only).
Defrosting (Cooling and heating models only)
• Frost may be generated on the outdoor unit during heat cycle when outdoor temperature is low and humidity is
high resulting in lower heating efficiency of the air conditioner.
• During this condition air conditioner will stop heating operation and start defrosting automatically.
• The time to defrost may vary from 4 to 10 minutes according to the outdoor temperature and the amount of
frost buildup on the outdoor unit.
2. A white mist coming out from the indoor unit.
• A white mist may generate due to a large temperature difference between air inlet and air outlet on COOL mode
in an indoor environment that has a high relative humidity.
• A white mist may generate due to moisture generated from defrosting process when the air conditioner restarts
in HEAT mode operation after defrosting.
3. Low noise of the air conditioner.
• You may hear a low hissing sound when the compressor is running or has just stopped running.
This sound is the sound of the refrigerant flowing or coming to a stop.
• You can also hear a low “squeak” sound when the compressor is running or has just stopped running. This is caused
by heat expansion and cold contraction of the plastic parts in the unit when the temperature is changing.
• A noise may be heard due to louver restoring to its original position when power is first turned on.
EN
4. Dust is blown out from the indoor unit.
This is a normal condition when the air conditioner has not been used for a long time or during first use of the
unit.
5. A peculiar smell comes out from the indoor unit.
This is caused by the indoor unit giving off smells permeated from building material, from furniture, or smoke.
6. The air conditioner turns to FAN only mode from COOL or HEAT (for cooling and heating models only)
mode.
When indoor temperature reaches the temperature setting on air conditioner, the compressor will stop automatically,
and the air conditioner turns to FAN only mode. The compressor will start again when the indoor temperature rises
on COOL mode or falls on HEAT mode (for cooling and heating models only) to the set point.
7. Dripping water may generate on the surface of the indoor unit when cooling in a high relatively humidity (relative
humidity higher than 80%). Adjust the horizontal louver to the maximum air outlet position and select HIGH fan
speed.
8. Heating mode (For cooling and heating models only)
The air conditioner draws in heat from the outdoor unit and releases it via the indoor unit during heating operation.
When the outdoor temperature falls, heat drawn in by the air conditioner decreases accordingly. At the same time,
heat loading of the air conditioner increases due to larger difference between indoor and outdoor temperature. If a
comfortable temperature can not be achieved by the air conditioner, we suggest you use a supplementary heating
device.
9. Auto-restart function
Power failure during operation will stop the unit completely. For the unit without Auto-restart feature, when the
power restores, the RUN indicator on the indoor unit starts flashing. To restart the operation, push the ON/OFF
button on the remote controller. For the unit with Auto-restart feature, when the power restores, the unit restarts
automatically with all the previous settings preserved by the memory function.
10. Lightning or a car wireless telephone operating nearby may cause the unit to malfunction.
Disconnect the unit with power and then re-connect the unit with power again. Push the ON/OFF button on the
remote controller to restart operation.
ENGLISH
J355-EN.indd 15
15
1/12/07 3:21:07 PM
TROUBLESHOOTING GUIDE
Problem
A. The air conditioner does
not run.
Probable cause
3.
4.
5.
6.
1. Wait for power resume.
2. Replace the fuse or reset the
breaker.
3. Find the cause and fix it.
4. Replace the faulty component.
5. Retighten the connection.
6. Check thermostat setting.
8. Incorrect wiring, terminal loose.
9. Pressure switch tripped.
7. Find the cause then replace
capacitor.
8. Check and retighten.
9. Find the cause before reset.
1. Power failure.
2. Fuse blown or circuit breaker open.
Voltage is too low.
Faulty contactor or relay.
Electrical connections loose.
Thermostat adjustment too low
(in heating mode) or too high
(in cooling mode).
7. Faulty capacitor.
B. The outdoor fan runs but
the compressor will not
start.
1. Motor winding cut or grounded.
C. There is insufficient heating
or cooling.
1. There is a gas leak.
2. Faulty capacitor.
2. Liquid and gas line insulated
together.
3. The room was probably very hot
(cool) when you started the
system.
D. The compressor runs continuously.
E. The compressor starts but
shuts down quickly.
J355-EN.indd 16
1. Remove charge, repair, evacuate
and recharge.
2. Insulate them separately.
3. Wait while unit has enough time
to cool the room.
1. Check thermostat setting.
1. Too much or too little refrigerant.
1. Remove charge, evacuate and
recharge.
2. Determine the cause and
replace compressor.
3. Remove charge, evacuate and
recharge.
4. Replace it.
3. Air or incondensables in
refrigerant circuit.
4. Changeover valve damaged or
blocked open (heat pump unit).
16
1. Check the wiring and the
compressor winding resistance.
2. Find the cause then replace
capacitor.
1. Thermostat adjustment too low
(in heating mode) or too high
(in cooling mode).
2. Faulty fan.
3. Refrigerant charge too low, leak.
4. Air or incondensables in refrigerant
circuit.
2. Faulty compressor.
F. Clicking sound is heard
from the air conditioner.
Remedy
In heating or cooling operation any
plastic parts may expand or shrink due
to a sudden temperature change in this
event, a clicking sound may occur.
2. Check condenser air circulation.
3. Find leak, repair and recharge.
4. Remove charge, evacuate and
recharge.
In heating or cooling operation any
plastic parts may expand or shrink
due to a sudden temperature change
in this event, a clicking sound may
occur.
ENGLISH
1/12/07 3:21:09 PM
TECHNICAL SPECIFICATIONS
Technical Specifications : WALL TYPE (RVHC 09-12DS, 18AS) EVEREST INVERTER - 50 Hz
Indoor
Unit
Model
Outdoor
Unit
Cooling Capacity
Heating Capacity
Power Supply
Power Consumption
COP
Cooling
Heating
Cooling
Heating
Refrigerant Type
Refrigerant Charge
g
Indoor
Outdoor
dB(A)
Fan
Power Supply
V/Ph/Hz
Air flow (Hi/Me/Lo)
m3/h
Input Power
W
Running Current
A
Height
mm
Dimension
Width
mm
Depth
mm
Weight
kg
System Operation Control
Power Supply
V/Ph/Hz
Qty
Compressor
Compressor type
Height
mm
Dimension
Width
mm
Depth
mm
Weight
kg
Type
Suction
inch
Pipe Size
Liquid
inch
Piping
Outdoor Unit
Indoor Unit
Noise Level
Btu/h
kW
Btu/h
kW
V/Ph/Hz
W
W
W/W
W/W
RVKC
RVKC12DS-AAA
RVKC18AS-AAA
RVJC
RVJC09DS-AAA
RVJC12DS-AAA
RVJC18AS-AAA
9000(3500-11000)
12000(4400-14500)
18000(6500-22500)
2.6(1.0-3.2)
3.5(1.3-4.2)
5.3(1.9-6.6)
10000(3500-13800)
14000(4800-20500)
19000(7500-25000)
2.9(0.8-4.1)
4.1(1.4-6.0)
5.6(2.2-7.3)
220-240/1/50
220-240/1/50
220-240/1/50
810(260-1350)
1050(520-1600)
1720(850-2300)
810(330-1550)
1130(520-2050)
1790(1000-2500)
3.21
3.33
3.08
3.58
3.63
3.13
R-410A
1030
1200
1770
37
40
44
51
54
58
220-240/1/50
500/430/370
580/500/420
800/700/600
35
44
55
3.3(1.5-7.0)
5.1(2.7-8.5)
7.5(3.8-10.5)
250
265
292
710
790
920
195
195
220
7.5
9
13
Wireless Control with LCD Display
220-240/1/50
1
1
1
Rotary Inverter
590
590
695
760
760
845
285
285
335
35
38
53
Flare+Nuts
3/8
1/2
1/2
1/4
1/4
1/4
RVKC09DS-AAA
EN
Remark : The above design and specifications are subject to change without prior notice for product improvement.
ENGLISH
J355-EN.indd 17
17
1/12/07 3:21:10 PM
TECHNICAL SPECIFICATIONS
Technical Specifications : Wall type Everest Inverter RVHC (RVKC-RVJC) R-410A 50Hz Rev.151206
Model
Set
RVHC09DSAAAF
Indoor unit
RVKC09DS-AAF
RVKC12DS-AAF
Outdoor Unit
RVJC09DS-AAF
RVJC012DS-AAF
Power supply
RVHC12DSAAAF
Ph-V-Hz
1, 220-240V~, 50Hz
1, 220-240V~, 50Hz
Btu/h
9,000(3,100~11,200)
12,000(3,800~14,700)
Input
W
660(300~1,100)
970(400~1,480)
Rated current
A
2.9(1.3~4.8)
4.3(1.8~6.5)
Btu/h
10,000(3,300~12,300)
13,000(4,000~15,200)
Input
W
690(310~1,150)
950(390~1,460)
Rated current
A
3.0(1.4~5.0)
4.2(1.7~6.4)
Moisture removal
L/h
0.8
1.2
Max. input consumption
W
1,500
1,600
Max. current
A
8
8.5
Starting current
A
8
8.5
PTC Heater (optional)
W
85
85
Rotary
Rotary
Capacity
Cooling
Capacity
Heating
Type
Capacity
Compressor
Btu/h
10,918
10,918
Input
W
855
855
Rated current (RLA)
A
5.3
5.3
Locked rotor Amp (LRA)
A
8
8
Thermal protector
Thermal protector
Protection Device
Indoor fan motor
Capacitor
µF
No
No
Refrigerant oil
ml
480
480
Input
W
38
38
Capacitor
µF
1.5
1.5
r/min
1,150/1,000/800
1,250/1,050/900
Speed (Hi/Med/Low)
a.Number of rows
c.Fin spacing
Indoor coil
d.Fin type (code)
e.Tube outside dia. and type
mm
f.Coil length×height×width
mm
Outdoor fan motor
hydrophilic aluminium
Ø7, innergroove tube
Ø7, innergroove tube
(637+615)×(168+126)×(26.74+26.74) (637+615)×(168+126)×(26.74+26.74)
41/35/30
43/37/30
Dimension (W*H*D)
mm
790*265*194
790*265*194
Packing (W*H*D)
mm
875*375*285
875*375*285
Net/Gross weight
Kg
8.5/10.5
9.0/11.0
Input
W
59
59
Capacitor
µF
2.5
2.5
r/min
800/550
800/550
b.Tube pitch(a)×row pitch(b)
mm
c.Fin spacing
mm
d.Fin type (code)
615/485/325
2
2
25.4x22
25.4x22
1.4
1.4
hydrophilic aluminium
hydrophilic aluminium
e.Tube outside dia. and type
mm
Ø9.53, innergroove tube
Ø9.53, innergroove tube
f.Coil length×height×width
mm
620×558.8×44
620×558.8×44
m3/h
1,650/1,060
1,650/1,060
dB(A)
52
54
Dimension (W*H*D)
mm
760*590*285
760*590*285
Packing (W*H*D)
mm
887*655*355
887*655*355
Net/Gross weight
Kg
40.5/43
40.5/43
g
1,230
1,230
mm
Ø6.35/Ø9.53
Ø6.35/Ø12.7
Max. refrigerant pipe length
m
12
12
Max. difference in level
m
5
5
m2
16-24
20-30
92/184/225
92/184/225
Outdoor air flow
Outdoor noise level
Refrigerant type R-410A
Liquid side/Gas side
Refrigerant piping
hydrophilic aluminium
590/470/325
a.Number of rows
Outdoor unit
1.3
m3/h
Speed
Outdoor coil
2
1.3
dB(A)
Indoor air flow (Hi/Med/Low)
Indoor noise level (Hi/Med/Low)
Indoor unit
mm
2
Application area
Qty’per 20’ /40’ /40’HQ
Remark : The above design and specifications are subject to change without prior notice for product improvement.
18
J355-EN.indd 18
ENGLISH
1/12/07 3:21:11 PM
TECHNICAL SPECIFICATIONS
Technical Specifications : High Wall RVHC09-18 (Everest Inverter R-410A MEPS) : 50Hz Rev.00
Model
Set
RVHC09DSAAAF-II
RVHC12DSAAAF-II
RVHC18ASAAAA-II
Indoor unit
RVKC09DS-AAF-II
RVKC12DS-AAF-II
RVKC18AS-AAA-II
Outdoor unit
RVJC09DS-AAF-II
RVJC12DS-AAF-II
RVJC18AS-AAA-II
Ph-V-Hz
1, 220-240V~, 50Hz
1, 220-240V~, 50Hz
1, 220-240V~, 50Hz
Btu/h
8,987(3,100~11,200)
11,539(3,800~14,700)
15,958(6,500-22,500)
kW
2.63(0.91~3.29)
3.38(1.11~4.31)
4.68(1.90-6.60)
kcal/h
2,265(781~2,822)
2,908(958~3,704)
4,021(1,638~5,670)
Input
W
660(300~1,100)
970(400~1,480)
1,701(850-2,300)
Rated current
A
2.97(1.3~4.8)
4.26(1.8~6.5)
7.5(3.8-10.5)
W/W
3.84
3.45
2.8
Btu/h
9,723(3,300~12,300)
12,361(4,000~15,200)
16,313(7,500-25,000)
Power supply
Capacity
Cooling
EER
Capacity
kW
2.850(0.967~3.605)
3.623(1.172~4.455)
4.781(2.198-7.327)
kcal/h
2,450(832~3,100)
3,115(1,008~3,830)
4,111(1,890~6,300)
Input
W
690(310~1,150)
950(390~1,460)
1,739(1,000-2,500)
Rated current
A
2.95(1.4~5.0)
4.32(1.7~6.4)
7.9(4.2-11.1)
W/W
4.2
3.64
2.8
Max. input consumption
W
2,400
3,000
4,000
Max. current
A
12
15
18
Starting current
A
3.8
4.5
9.0
Heating
COP
Type
Compressor
Rotary
Rotary
Rotary
Input
W
680
680
1,630
Rated current (RLA)
A
4.7
4.7
10.95
Locked rotor Amp (LRA)
A
10
10
55
Thermal protector
Indoor fan motor
Internal
Capacitor
µF
No
No
No
Refrigerant oil
ml
370
370
750
Input
W
38
38
55
Current
A
0.17
0.17
0.25
Capacitor
µF
1.2
1.5
1.5
r/min
1,360/1,100/880
1,300/1,000/800
1,140/1,060/980
2
2
2
1.3
1.3
1.3
Speed (Hi/Mi/Lo)
Number of rows
Fin spacing
Indoor coil
mm
Fin type
Tube outside dia.
Hydrophilic aluminium
mm
Ø7
Tube Material
Coil length×height×width
mm
538×252×26.74
637×294×26.74
806×232×26.74
500/430/370
580/500/420
800/700/600
dB(A)
39/35/29
41/36/30
44/40/37
Dimension (W*H*D)
mm
790×265×194
790×265×194
920×293×224
Packing (W*H*D)
mm
875×375×285
875×375×285
1,020×320×385
Net/Gross weight
Kg
8.5/10.5
9.0/11.0
13/15
Input
W
59
59
130
Current
A
0.27
0.27
0.6
Capacitor
µF
2.5
2.5
3
r/min
800
900
800
Indoor noise level (Hi/Mi/Lo)
Outdoor fan motor
Innergroove tube
m3/h
Indoor air flow (Hi/Mi/Lo)
Indoor unit
Speed
Number of rows
Fin spacing
Outdoor coil
mm
1.5
2
2
1.5
1.5
1.6
Fin type
Tube outside dia.
Hydrophilic aluminium
mm
Ø9.53
Tube Material
Coil length×height×width
mm
680×550×44
680×550×44
803×635×44
1,700
1,900
2,500
dB(A)
52
52
58
Dimension (W*H*D)
mm
760×590×285
760×590×285
845×695×335
Packing (W*H*D)
mm
887×655×355
887×655×355
970×770×395
Net/Gross weight
Kg
40.5/43
40.5/43
53/67
g
1,230
1,230
1,770
mm
Ø6.35/Ø9.53
Ø6.35/Ø12.7
Ø6.35/Ø12.7
Outdoor noise level
Refrigerant type R410A
Refrigerant piping
Innergroove tube
m3/h
Outdoor air flow
Outdoor unit
EN
Liquid side/Gas side
Remark : The above design and specifications are subject to change without prior notice for product improvement.
ENGLISH
J355-EN.indd 19
19
1/12/07 3:21:13 PM
DECLARATION OF CONFORMITY
DECLARATION OF CONFORMITY
Type of Equipment
Brand Name
Type Designation
Application of Council
Directive (s)
Air Conditioners
YORK
HAEA-HADA07/09/12FS, HAEB-HADB07/09/12FS, HAEC-HADC07/09/12FS, HAKA-HAJA07/09/12FS,
HAKB-HAJB07/09/12FS, HAKC-HAJC07/09/12FS, HEEB-HEDB07/09/12/18/24/30FS,
HEKB-HEJB07/09/12/18/21/24/30FS, HLEA-HLDA07/09/12/18/24FS, HLCA-HLHA24/28/FS,
HMEA09MC/MD/ME, HMDA18MC, HMDA21MD, HMDA27ME, HMKB09MC/MD/ME/MF,
HMKB12MD/MF, HMJB18MC, HMJB21MD, HMJB27ME, HMJB30MF, HRKB09AB/AG/AH,
HRKB12AG, HRJB18AB, HRJB21AG, HRJB27AH, HRKA09AB, HRJA18AB,
HSKB-HSJB07/09/12/18/24FS, HTEA-HTDA18/21/24/30FS, HVKA-HVJA09/12/21/24AS,
HVKC-HVJC07/09/12DS, HVKC-HVJC18AS, PECA09/12FD,
PECB09/12/14FS, PESA09/12FD, PESB09/12/14FS, PLCA09FC/FD, PLCB09FC/FD,
PLSA09FC/FD, PLSB09FC/FD
MACC-MAHC07/09/12/18/24FS, MECB-MEHB07/09/12/18/24FS, MLCA-MLHA07/09/12/18/24FS,
MLCB-MLHB07/09/12/18/24FS, RACC-RAHC07/09/12/18/24/28FS, RLCB-RLHB07/09/12/18/24/28FS,
RLCA-RLHA07/09/12/18/24/30FS, RTCA-RTHA/18/24/30RS/OS,
EMC Directive 89/336/EEC, Low Voltage Directive 73/23/EEC and Machine Safety Directive: MSD 98/37/CE
The following harmonized standards have been applied:
Standard (s)
EN 60335-2-40/A1:2000
EN 60335-2-40/A1:2000
EN 55014-1:2000/A2:2002
EN 55014-2:1997/A1:2001
EN 55022:1998/A1:2000
EN 61000-3-2:2000
EN 61000-3-3:1995/A1:2001
EN 61000-3-11:2000
EN 60825
EN 60335-1:1994+A11:1995+A1, A12:1996+A13, A14:1998+A15, A2:2000+A16:2001
EN 60335-2-40:1997+A1:2000
EN 55014-1:1993+A1:1997/A2:1999
EN 55104-2:1997
EN 61000-3-2:1995/A1:1998/A2:1998
EN 61000-3-2:1995/A14:2000
EN 61000-3-3:1995
EN 60335-2-40:2003
EN 50366:2003
EN 60335-1:2002 +A11
EN 55014-1/A2:2002
EN 55104-2/A1:2201
The product complies with the harmonized European safety standards and harmonized EMC standards listed above.
We have internal production control system that ensures compliance between the manufacturer products and the technical documentation.
The product is CE mark.
We declare under our sold responsibility that the equipment follows the provisions Of the Directives stated above.
Authorized Representative:
CM Choi
Shipping Manager
YORK International (Northern Asia) Ltd.
15/F., Tower II, World Trade Square, 123 Hoi Bun Road, Kwun Tong, Kowloon, Hong Kong
Telephone: (852) 2331 9286 Fax: (852) 2331 9840
Technical Service Division: Telephone: (852) 2331 9286 Fax: (852) 2304 0068
INSTALLATION, REMOVAL AND DISPOSAL
This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury!
All work must only be carried out by competent persons using suitable protective clothing and safety precautions.
Read the Manual
Risk of electric
shock
Unit is remotely controlled and
may start without warning
1. Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of electrical and gas
isolation are secured in the OFF position. The supply cables and gas pipework may then be disconnected and removed. For points of connection refer
to unit installation instructions.
2. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then be
reused, if appropriate, or returned to the manufacturer for disposal. Under No circumstances should refrigerant be vented to atmosphere. Where
appropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing disposal
of oily wastes.
3. Packaged unit can generally be removed in one piece after disconnection as above. Any fixing down bolts should be removed and then unit lifted from
position using the points provided and equipment of adequate lifting capacity. Reference MUST be made to the unit installation instructions for unit weight
and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above.
4. After removal from position the unit parts may be disposed of according to local laws and regulations.
J355-EN.indd 20
1/12/07 3:21:14 PM