Panasonic CS-A12GKD User Guide Manual Pdf

Add to my manuals
81 Pages

advertisement

Panasonic CS-A12GKD User Guide Manual Pdf | Manualzz
Order No. MAC0611059C8
Air Conditioner
CS-A7GKD CU-A7GKD
CS-A9GKD CU-A9GKD
CS-A12GKD CU-A12GKD
TABLE OF CONTENTS
PAGE
1 Safety Precautions----------------------------------------------- 2
2 Specifications ----------------------------------------------------- 4
2.1. CS-A7GKD CU-A7GKD---------------------------------- 4
2.2. CS-A9GKD CU-A9GKD---------------------------------- 6
2.3. CS-A12GKD CU-A12GKD ------------------------------ 8
3 Features ------------------------------------------------------------10
4 Location of Controls and Components ------------------11
4.1. Product Overview----------------------------------------- 11
PAGE
5 Dimensions ------------------------------------------------------- 12
5.1. Indoor Unit & Remote Control ------------------------ 12
5.2. Outdoor Unit----------------------------------------------- 13
6 Refrigeration Cycle Diagram -------------------------------- 14
7 Wiring Connection Diagram--------------------------------- 17
7.1. CS-A7GK CU-A7GK / CS-A9GK CU-A9GK------- 17
7.2. CS-A12GK CU-A12GK --------------------------------- 18
8 Electronic Circuit Diagram----------------------------------- 19
© 2006 Panasonic HA Air-Conditioning (M) Sdn. Bhd.
(11969-T). All rights reserved. Unauthorized copying and
distribution is a violation of law.
Downloaded from AC-Manual.com Manuals
11.13. Random Auto Restart Control -----------------------11.14. Remote Control Signal Receiving Sound---------11.15. Patrol Operation-----------------------------------------11.16. e-ion Operation------------------------------------------12 Servicing Mode-------------------------------------------------12.1. Auto OFF/ON Button ----------------------------------12.2. Select Remote Control Transmission Code------12.3. Remote Control Button --------------------------------13 Troubleshooting Guide --------------------------------------13.1. Refrigeration cycle system ---------------------------14 Disassembly and Assembly Instructions -------------14.1. Indoor Electronic Controllers and Control
Board Removal Procedures -------------------------14.2. Indoor Fan Motor and Cross Flow Fan
Removal Procedures ----------------------------------15 Technical Data --------------------------------------------------15.1. Thermostat Characteristics---------------------------15.2. Operation Characteristics ----------------------------16 Exploded View and Replacement Parts List----------16.1. Indoor Unit------------------------------------------------16.2. Outdoor Unit ----------------------------------------------
9 Printed Circuit Board ------------------------------------------ 20
9.1. Indoor Unit (Main Printed Circuit Board) ----------- 20
9.2. Indoor Unit (Power Printed Circuit Board) --------- 22
9.3. Indicator ---------------------------------------------------- 23
10 Installation Instruction ---------------------------------------- 24
10.1. Select The Best Location ------------------------------ 24
10.2. Indoor Unit ------------------------------------------------- 25
10.3. Outdoor Unit ----------------------------------------------- 27
11 Operation and Control----------------------------------------- 30
11.1. Heating Operation---------------------------------------- 30
11.2. Cooling Operation---------------------------------------- 31
11.3. Soft Dry Operation --------------------------------------- 32
11.4. Automatic Operation------------------------------------- 33
11.5. Operation Control ---------------------------------------- 34
11.6. Indoor Fan Speed Control ----------------------------- 41
11.7. Outdoor Fan Speed Control --------------------------- 43
11.8. Vertical Airflow Direction Control --------------------- 43
11.9. Horizontal Airflow Direction Control ----------------- 44
11.10. Powerful Operation -------------------------------------- 44
11.11. Quiet Operation------------------------------------------- 46
11.12. Timer Control---------------------------------------------- 48
48
48
49
52
55
55
55
56
57
57
59
59
61
63
63
64
76
76
78
1 Safety Precautions
• Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.
• Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and
main circuit for the model installed.
• The caution items stated here must be followed because these important contents are related to safety. The meaning of each
indication used is as below. Incorrect installation or servicing due to ignoring of the instruction will cause harm or damage, and
the seriousness is classified by the following indications.
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties.
• The items to be followed are classified by the symbols:
This symbol denotes item that is PROHIBITED from doing.
• Carry out test running to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1. Engage dealer or specialist for installation and servicing. If installation or servicing done by the user is defective, it will cause water
leakage, electrical shock or fire.
2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3. Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water
leakage, fire or electrical shock.
4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not
properly done, the set will drop and cause injury.
5. For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and
single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or
fire.
6. Use the specified cable and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no external
force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up or fire at the connection point of terminal, fire or electrical shock.
2
Downloaded from AC-Manual.com Manuals
8. When connecting the piping, do not allow air or any substances other than the specified refrigerant to enter the refrigeration cycle.
Otherwise, this may lower the capacity, cause abnormally high pressure in the refrigeration cycle, and possibly result in explosion and
injury.
9. It is desirable that the amount of residual oil is less than 40 mg/10m.
10. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with other electrical
appliances. Otherwise, it will cause fire or electrical shock.
11. After completion of the installation servicing confirm there is no leakage of refrigerant gas. It may generate toxic gas when the
refrigerant contacts with fire.
12. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.
1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the
unit, it may cause fire.
3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage
the furniture.
4. Pb free solder has a higher melting point than standard solder; typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use
a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
Pb free solder will tend to splash when heated too high (about 1100°F / 600°C).
5. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare
may break and cause refrigerant gas leakage.
6. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.
ATTENTION
1. Selection of the installation location. Select an installation location which is rigid and strong enough to support or hold the unit, and select a
location for easy maintenance.
2. Power supply connection to the conditioner. Connect the power supply cord of the air conditioner to the mains using one of the following
methods.
Power supply point shall be the place where there is ease for ease for access for the power disconnection in case of emergency.
In some countries, permanent connection of this room air conditioner to the power supply is prohibited.
1. Power supply connection to the receptacle using a power plug. Use an approved power plug with earth pin for the connection to the
socket.
2. Power supply connection to a circuit breaker for the permanent connection. Use an approved circuit breaker for the permanent
connection. It must be a double pole switch with a minimum 3.5 mm contact gap.
3. Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigeration parts. Take care of
the liquid refrigerant, it may cause frostbite.
4. Installation work. It may need two people to carry out the installation work.
5. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Downloaded from AC-Manual.com Manuals
3
2 Specifications
2.1.
CS-A7GKD CU-A7GKD
Item
Performance Test Condition
C Capacity
O
O
L EER
I
N Noise Level
G
H Capacity
E
A
T Cop
I
N Noise Level
G
Moisture Removal
Air Volume
kW
BTU/h
kcal/h
W/W
BTU/hW
dB (A)
Power level dB
kW
BTU/h
kcal/h
W/W
BTU/hW
dB (A)
Power level dB
l/h
(pt/h)
Heat Exchanger
Air Filter Type
High: 46 - 47
High: 61 - 62
2.10 - 2.10
7160 - 7160
1810 - 1810
4.20 - 4.00
14.3 - 13.6
High: 36 Low: 28
High: 49
High: 48 - 49
High: 64 - 65
1.3
2.7
cm3
—
—
Capillary Tube
ATMOS M60 or
m3/m (ft3/m)
Hi
m3/m (ft3/m)
SHi
kg (oz)
mm (inch)
mm (inch)
mm (inch)
kg (lbs)
mm (inch)
mm (inch)
m (ft)
m (ft)
g/m (oz/ft)
m (ft)
mm
mm
W
W
W
rpm
rpm
rpm
rpm
mm (inch)
4
Downloaded from AC-Manual.com Manuals
High: 33 Low: 26
High: 46
m3/m (ft3/m)
Me
Motor Type
Rated Output
Type
Material
Motor Type
Input power
Output power
Fan Speed
Lo (Cool / Heat)
Me (Cool / Heat)
Hi (Cool / Heat)
SHi (Cool / Heat)
Fin material
Fin Type
Row × Stage × FPI
Size (W × H × L)
Material
Style
Outdoor unit
JIS
2.00 - 2.00
6820 - 6820
1720 - 1720
3.28 - 3.17
11.2 - 10.8
Cooling;
29.5 (1040) - 30.0 (1060)
—
m3/m (ft3/m)
Refrigerant (Charged) R22
Dimension
Height
Width
Depth
Net Weight
Pipe Diameter
Gas
Liquid
Height Difference
Pipe Length Range
Additional Gas Amount
Refrigeration Charge Less
Drain Hose
Inner diameter
Length
Compressor
Type
Indoor unit
Cooling; 5.9 (210)
Heating; 6.4 (230)
Cooling; 7.0 (250)
Heating; 7.0 (250)
Cooling; 7.8 (280)
Heating; 9.0 (320)
Cooling; 9.0 (320)
Lo
Refrigerant Control Device
Refrigerant Oil (Charged)
Fan
Unit
—
—
SUNISO 4GDID (290cm3)
—
0.71 (25.0)
280 (11 - 1/32)
510 (20 - 3/32)
799 (31 - 15/32)
650 (25 - 19/32)
183 (7 - 7/32)
230 (9 - 1/16)
9 (20)
24 (53)
9.52 (3/8”)
6.35 (1/4”)
5 (16.4)
3 (9.8) ~ 10 (32.8)
20 (0.2)
7.5 (24.6)
16
—
650
—
—
Rotary (1 cylinder)
rolling piston type
—
Induction (2-poles)
—
550
Cross-flow Fan
Propeller Fan
ASG20K1
PP Resin
Induction (4-poles)
Induction (6-poles)
42 - 47
58 - 65
15
30
780 / 840
—
920 / 920
—
1030 / 1190
800 - 830 / —
1190 / —
—
Aluminium (Pre Coat)
Aluminium (Blue Coat)
Slit Fin
Louver Fin
2 × 15 × 19
1 × 19 × 17
610 × 315 × 25.4
22 × 483 × 576
Polypropelene
—
One-touch
—
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air
temperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°F
D.B.), 6°C W.B. (42.8°F W.B.)
Item
Power Source (Phase, Voltage, Cycle)
Unit
ø
V
Hz
Input power
Cooling
W
Heating
W
Starting Current
A
Running Current
Cooling
A
Heating
A
Power Factor
Cooling
%
Heating
%
Power factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Power Cord
Number of core
Length
m (ft)
Thermostat
Protection Device
Single
220
50
610
500
12.4
2.9
2.4
96
95
Single
230
50
630
525
12.4
2.8
2.4
98
95
3 (1.5mm)
2 (6)
—
—
—
2 Stage Overload Protector
Note:
• Specification are subjected to change without prior notice for further improvement.
5
Downloaded from AC-Manual.com Manuals
2.2.
CS-A9GKD CU-A9GKD
Item
Performance Test Condition
C Capacity
O
O
L EER
I
N Noise Level
G
H Capacity
E
A
T Cop
I
N Noise Level
G
Moisture Removal
Air Volume
kW
BTU/h
kcal/h
W/W
BTU/hW
dB (A)
Power level dB
kW
BTU/h
kcal/h
W/W
BTU/hW
dB (A)
Power level dB
l/h
(pt/h)
Heat Exchanger
Air Filter Type
High: 36 Low: 26
High: 49
High: 48 - 49
High: 63 - 64
2.80 - 2.85
9550 - 9720
2410 - 2450
4.00 - 3.85
13.6 - 13.1
High: 38 Low: 28
High: 51
High: 48 - 49
High: 64 - 65
1.6
3.4
m3/m (ft3/m)
cm3
—
—
Capillary Tube
ATMOS M60 or
Me
m3/m (ft3/m)
Hi
m3/m (ft3/m)
SHi
Motor Type
Rated Output
Type
Material
Motor Type
Input power
Output power
Fan Speed
Lo (Cool / Heat)
Me (Cool / Heat)
Hi (Cool / Heat)
SHi (Cool / Heat)
Fin material
Fin Type
Row × Stage × FPI
Size (W × H × L)
Material
Style
Outdoor unit
JIS
2.65 - 2.65
9040 - 9040
2280 - 2280
3.19 - 3.08
10.9 - 10.5
Cooling;
29.5 (1040) - 30.0 (1060)
—
m3/m (ft3/m)
Refrigerant (Charged) R22
Dimension
Height
Width
Depth
Net Weight
Pipe Diameter
Gas
Liquid
Height Difference
Pipe Length Range
Additional Gas Amount
Refrigeration Charge Less
Drain Hose
Inner diameter
Length
Compressor
Type
Indoor unit
Cooling; 6.4 (230)
Heating; 6.9 (240)
Cooling; 7.8 (270)
Heating; 7.8 (270)
Cooling; 9.4 (330)
Heating; 9.8 (350)
Cooling; 10.1 (360)
Lo
Refrigerant Control Device
Refrigerant Oil (Charged)
Fan
Unit
kg (oz)
mm (inch)
mm (inch)
mm (inch)
kg (lbs)
mm (inch)
mm (inch)
m (ft)
m (ft)
g/m (oz/ft)
m (ft)
mm
mm
W
W
W
rpm
rpm
rpm
rpm
mm (inch)
—
—
SUNISO 4GDID (350cm3)
0.67 (23.7)
510 (20 - 3/32)
650 (25 - 19/32)
230 (9 - 1/16)
27 (60)
9.52 (3/8”)
6.35 (1/4”)
5 (16.4)
3 (9.8) ~ 10 (32.8)
20 (0.2)
7.5 (24.6)
16
—
650
—
—
Rotary (1 cylinder)
rolling piston type
—
Induction (2-poles)
—
750
Cross-flow Fan
Propeller Fan
ASG20K1
PP Resin
Induction (4-poles)
Induction (6-poles)
42 - 47
58 - 65
15
30
830 / 890
—
1000 / 1000
—
1210 / 1300
800 - 830 / —
1300 / —
—
Aluminium (Pre Coat)
Aluminium (Blue Coat)
Slit Fin
Louver Fin
2 × 15 × 19
1 × 19 × 17
610 × 315 × 25.4
22 × 483 × 576
Polypropelene
—
One-touch
—
—
280 (11 - 1/32)
799 (31 - 15/32)
183 (7 - 7/32)
9 (20)
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air
temperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°F
D.B.), 6°C W.B. (42.8°F W.B.)
6
Downloaded from AC-Manual.com Manuals
Item
Power Source (Phase, Voltage, Cycle)
Unit
ø
V
Hz
Input power
Cooling
W
Heating
W
Starting Current
A
Running Current
Cooling
A
Heating
A
Power Factor
Cooling
%
Heating
%
Power factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Power Cord
Number of core
Length
m (ft)
Thermostat
Protection Device
Single
220
50
830
700
18
3.9
3.3
97
96
Single
230
50
860
740
18
3.9
3.3
96
97
3 (1.5mm)
2 (6)
—
—
—
2 Stage Overload Protector
Note:
• Specification are subjected to change without prior notice for further improvement.
7
Downloaded from AC-Manual.com Manuals
2.3.
CS-A12GKD CU-A12GKD
Item
Performance Test Condition
C Capacity
O
O
L EER
I
N Noise Level
G
H Capacity
E
A
T Cop
I
N Noise Level
G
Moisture Removal
Air Volume
kW
BTU/h
kcal/h
W/W
BTU/hW
dB (A)
Power level dB
kW
BTU/h
kcal/h
W/W
BTU/hW
dB (A)
Power level dB
l/h
(pt/h)
Heat Exchanger
Air Filter Type
High: 39 Low: 29
High: 52
High: 48 - 49
High: 63 - 64
4.00 - 4.05
13640 - 13810
3440 - 3480
3.67 - 3.62
12.5 - 12.3
High: 40 Low: 29
High: 53
High: 48 - 49
High: 64 - 65
2.0
4.2
m3/m (ft3/m)
cm3
—
—
Capillary Tube
ATMOS M60 or
Me
m3/m (ft3/m)
Hi
m3/m (ft3/m)
SHi
Motor Type
Rated Output
Type
Material
Motor Type
Input power
Output power
Fan Speed
Lo (Cool / Heat)
Me (Cool / Heat)
Hi (Cool / Heat)
SHi (Cool / Heat)
Fin material
Fin Type
Row × Stage × FPI
Size (W × H × L)
Material
Style
Outdoor unit
JIS
3.52 - 3.54
12000 - 12100
3030 - 3040
3.26 - 3.16
11.1 - 10.8
Cooling;
32.5 (1150) - 33.0 (1160)
—
m3/m (ft3/m)
Refrigerant (Charged) R22
Dimension
Height
Width
Depth
Net Weight
Pipe Diameter
Gas
Liquid
Height Difference
Pipe Length Range
Additional Gas Amount
Refrigeration Charge Less
Drain Hose
Inner diameter
Length
Compressor
Type
Indoor unit
Cooling; 6.1 (220)
Heating; 6.5 (230)
Cooling; 8.5 (300)
Heating; 8.5 (300)
Cooling; 9.9 (350)
Heating; 10.0 (350)
Cooling; 10.1 (360)
Lo
Refrigerant Control Device
Refrigerant Oil (Charged)
Fan
Unit
kg (oz)
mm (inch)
mm (inch)
mm (inch)
kg (lbs)
mm (inch)
mm (inch)
m (ft)
m (ft)
g/m (oz/ft)
m (ft)
mm
mm
W
W
W
rpm
rpm
rpm
rpm
mm (inch)
—
—
SUNISO 4GDID (410cm3)
1.05 (37.1)
540 (21 - 1/4)
780 (30 - 23/32)
289 (11 - 3/8)
37 (82)
12.70 (1/2”)
6.35 (1/4”)
5 (16.4)
3 (9.8) ~ 15 (49.2)
20 (0.2)
7.5 (24.6)
16
—
650
—
—
Rotary (1 cylinder)
rolling piston type
—
Induction (2-poles)
—
950
Cross-flow Fan
Propeller Fan
ASG20K1
PP Resin
Induction (4-poles)
Induction (6-poles)
42 - 47
72 - 80
15
31
800 / 860
—
1120 / 1120
—
1300 / 1320
845 - 860 / —
1320 / —
—
Aluminium (Pre Coat)
Aluminium
Slit Fin
Louver Fin
2 × 15 × 21
2 × 24 × 16
610 × 315 × 25.4
36.38 × 504 × 713:684
Polypropelene
—
One-touch
—
—
280 (11 - 1/32)
799 (31 - 15/32)
183 (7 - 7/32)
9 (20)
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air
temperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°F
D.B.), 6°C W.B. (42.8°F W.B.)
8
Downloaded from AC-Manual.com Manuals
Item
Power Source (Phase, Voltage, Cycle)
Unit
ø
V
Hz
Input power
Cooling
kW
Heating
kW
Starting Current
A
Running Current
Cooling
A
Heating
A
Power Factor
Cooling
%
Heating
%
Power factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Power Cord
Number of core
Length
m (ft)
Thermostat
Protection Device
Single
220
50
1.08
1.09
27
5.1
5.2
96
95
Single
230
50
1.12
1.12
27
5.1
5.1
95
95
3 (1.5mm)
2 (6)
—
—
—
Inner Protector
Note:
• Specification are subjected to change without prior notice for further improvement.
9
Downloaded from AC-Manual.com Manuals
3 Features
• High Efficiency
• Compact Design
• Wider range of horizontal discharge air
• Air Filter with function to reduce dust and smoke
• Automatic air swing and manual adjusted by Remote
Control for vertical airflow
• Long Installation Piping
- CS/CU-A7GK, CS/CU-A9GK, long piping up to 10 meter
- CS/CU-A12GK, long piping up to 15 meter
• e-ion Air Purifying System with Patrol Sensor
- Discharged Active e-ions capture dust particles and
bring it back with a boomerang-like mechanism
• Quality Improvement
- Random auto restart after power failure for safety restart
operation
- Gas leakage protection
- Prevent compressor reverse cycle
- Inner protector to protect Compressor
- Noise prevention during soft dry operation
- Blue Coated Condenser for high resistance to corrosion
• Operation Improvement
- Quiet mode to provide quiet operation
- Powerful mode to reach the desired room temperature
quickly
- 24-hour timer setting
• Serviceability Improvement
- Removable and washable front panel
10
Downloaded from AC-Manual.com Manuals
4 Location of Controls and Components
4.1.
Product Overview
4.1.1.
Indoor Unit
4.1.2.
Outdoor Unit
4.1.3.
Remote Control
11
Downloaded from AC-Manual.com Manuals
5 Dimensions
5.1.
5.1.1.
Indoor Unit & Remote Control
CS-A7GK CS-A9GK CS-A12GK
12
Downloaded from AC-Manual.com Manuals
5.2.
Outdoor Unit
5.2.1.
CU-A7GK CU-A9GK
5.2.2.
CU-A12GK
13
Downloaded from AC-Manual.com Manuals
6 Refrigeration Cycle Diagram
14
Downloaded from AC-Manual.com Manuals
7 Block Diagram
7.1.
CS-A7GK CU-A7GK / CS-A9GK CU-A9GK
15
Downloaded from AC-Manual.com Manuals
7.2.
CS-A12GK CU-A12GK
16
Downloaded from AC-Manual.com Manuals
8 Wiring Connection Diagram
8.1.
CS-A7GK CU-A7GK / CS-A9GK CU-A9GK
Resistance of Compressor Windings
Resistance of Indoor Fan Motor Windings
MODEL
CONNECTION
BLUE-YELLOW
YELLOW-RED
CS-A7GK
CS-A9GK
CWA921373
390.0 Ω
394.0 Ω
MODEL
CONNECTION
C-R
C-S
CU-A7GK
2RS122D5BC02
5.193 Ω
5.557 Ω
CU-A9GK
2PS156D3BB02
3.501 Ω
3.405 Ω
Note: Resistance at 20°C of ambient temperature.
Note: Resistance at 25°C of ambient temperature.
Resistance of Outdoor Fan Motor Windings
MODEL
CONNECTION
BLUE-YELLOW
YELLOW-RED
CU-A7GK
CU-A9GK
CWA951387J
287 Ω
238 Ω
Note: Resistance at 25°C of ambient temperature.
17
Downloaded from AC-Manual.com Manuals
8.2.
CS-A12GK CU-A12GK
Resistance of Compressor Windings
Resistance of Indoor Fan Motor Windings
MODEL
CONNECTION
BLUE-YELLOW
YELLOW-RED
CS-A12GK
CWA921373
390.0 Ω
394.0 Ω
MODEL
CONNECTION
C-R
C-S
Note: Resistance at 20°C of ambient temperature.
Note: Resistance at 25°C of ambient temperature.
Resistance of Outdoor Fan Motor Windings
MODEL
CONNECTION
BLUE-YELLOW
YELLOW-RED
CU-A12GK
CWA951117J
230 Ω
255 Ω
Note: Resistance at 25°C of ambient temperature.
18
Downloaded from AC-Manual.com Manuals
CU-A12GK
2KS206D5AF04
2.234 Ω
2.630 Ω
9 Electronic Circuit Diagram
19
Downloaded from AC-Manual.com Manuals
10 Printed Circuit Board
10.1. Indoor Unit (Main Printed Circuit Board)
TOP VIEW
20
Downloaded from AC-Manual.com Manuals
BOTTOM VIEW
21
Downloaded from AC-Manual.com Manuals
10.2. Indoor Unit (Power Printed Circuit Board)
TOP VIEW
BOTTOM VIEW
22
Downloaded from AC-Manual.com Manuals
10.3. Indicator
TOP VIEW
BOTTOM VIEW
23
Downloaded from AC-Manual.com Manuals
11 Installation Instruction
11.1. Select The Best Location
Indoor Unit
Indoor/Outdoor Unit Installation Diagram
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
Outdoor Unit
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over the rated length, additional refrigerant
should be added as shown in the table.
Model
C7GK/
C9GK
A7GK/
A9GK
C12GK
A12GK
Piping size
Gas Liquid
Additional
Max.
Max
Rated
Length Elevation Piping Refrigerant
(g/m)
Length
(m)
(m)
(m)
7.5
5
10
10
3/8”
1/4”
3/8”
1/4”
7.5
5
10
20
1/2”
1/2”
1/4”
1/4”
7.5
7.5
5
5
15
15
10
20
• This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
24
Downloaded from AC-Manual.com Manuals
11.2. Indoor Unit
11.2.1.
11.2.2.
How To Fix Installation Plate
To Drill A Hole In The Wall And
Install A Sleeve Of Piping
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
The mounting wall is strong and solid enough to prevent it from
the vibration.
Caution
When the wall is hollow, please be sure to use the sleeve for tube
ass’y to prevent dangers caused by mice biting the connecting cable.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
The centre of installation plate should be at more than 450 mm
at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm.
From installation plate left edge to unit's left side is 74 mm.
From installation plate right edge to unit's right is 94 mm.
: For left side piping, piping connection for liquid should be
about 15 mm from this line.
: For left side piping, piping connection for gas should be
about 45 mm from this line.
: For left side piping, piping connection cable should be
about 800 mm from this line.
11.2.3.
Indoor Unit Installation
For the right rear piping
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the left and right side edge of the installation plate. The meeting point of the extended line is the
centre of the hole. Another method is by putting measuring tape at position as shown in the diagram above. The
hole centre is obtained by measuring the
distance namely 150 mm and 125 mm for left and right
hole respectively.
• Drill the piping hole at either the right or the left and the
For the right and right bottom piping
hole should be slightly slanted to the outdoor side.
25
Downloaded from AC-Manual.com Manuals
For the embedded piping
Insert the connecting cable
Install the Indoor unit
Secure the Indoor Unit
Pull out the piping and drain hose
How to keep the cover
(This can be used for left rear piping & left bottom piping
also.)
26
Downloaded from AC-Manual.com Manuals
• Secure the cable onto the control board with the holder
(clamper).
• How to pull the piping and drain hose out, in case of the
embedded piping.
• In case of left piping how to insert the connecting cable and
drain hose.
11.3. Outdoor Unit
11.3.1.
Install The Outdoor Unit
• After selecting the best location, start installation according
to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and
horizontally by bolt nut (ø10 mm).
2. When installing at roof, please consider strong wind and
earthquake. Please fasten the installation stand firmly
with bolt or nails.
11.2.4.
Connect The Cable To The Indoor
Unit
1. The inside and outside connecting cable can be
connected without removing the front grille.
2. Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 3 (C7GK,
C9GK, C12GK) or 5 (A7GK, A9GK, A12GK) × 1.5mm2
flexible cord, type designation 245 IEC 57 or heavier
cord.
• Ensure the colour of wires of outdoor unit and the
terminal Nos. are the same to the indoor’s respectively.
• Earth lead wire shall be longer than the other lead wires
as shown in the figure for the electrical safety in case of
the slipping out of the cord from the anchorage.
Model
C7GK, C9GK, A7GK,
A9GK
A12GK, C12GK
11.3.2.
A
474
B
87
C
18.5
D
261
570
105
18.5
320
Connecting The Piping
Connecting The Piping To Indoor Unit
Please make flare after inserting flare nut (locate at joint portion
of tube assembly) onto the copper pipe. (In case of using long
piping)
Connect the piping
• Align the center of piping and sufficiently tighten the flare nut
with fingers.
• Further tighten the flare nut with torque wrench in specified
torque as stated in the table.
27
Downloaded from AC-Manual.com Manuals
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not
removed, gas leakage may be caused. Turn the piping
end down to avoid the metal powder entering the pipe.
3. Please make flare after inserting the flare nut onto the
copper pipes.
Model
C7GK, C9GK, A7GK, A9GK
C12GK, A12GK
Piping size (Torque)
Gas
Liquid
3/8” [42 N•m]
1/4” [18 N•m]
1/2” [55 N•m]
1/4” [18 N•m]
Connecting The Piping To Outdoor Unit
Decide piping length and then cut by using pipe cutter. Remove
burrs from cut edge. Make flare after inserting the flare nut
(locate at valve) onto the copper pipe. Align center of piping to
valves and then tighten with torque wrench to the specified
torque as stated in the table.
11.3.3.
Evacuation Of The Equipment
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to 76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
28
Downloaded from AC-Manual.com Manuals
CAUTION
•
•
•
•
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
If the leak stops when the piping connections are tightened further, continue working from step 3.
If the leak does not stop when the connections are retightened, repair the location of leak.
Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause frostbite.
11.3.4.
Connect The Cable To The Outdoor
Unit
1. Remove the control board cover from the unit by
loosening the screw.
2. Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 3 (C7GK,
C9GK, C12GK) or 5 (A7GK, A9GK, A12GK) × 1.5 mm2
flexible cord, type designation 245 IEC 57 or heavier
cord.
3. Secure the cable onto the control board with the holder
(clamper).
4. Attach the control board cover back to the original
position with the screw.
11.3.5.
Pipe Insulation
1. Please carry out insulation at pipe connection portion as
mentioned in Indoor/Outdoor Unit Installation Diagram.
Please wrap the insulated piping end to prevent water
from going inside the piping.
2. If drain hose or connecting piping is in the room (where
dew may form), please increase the insulation by using
POLY-E FOAM with thickness 6mm or above.
29
Downloaded from AC-Manual.com Manuals
12 Operation and Control
12.1. Heating Operation
• Heating operation can be set using remote control.
• This operation is applied to warm the room temperature reaches the setting temperature set on the remote control.
• The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to
30°C.
• During heating operation, the compressor will stop running and restart as shown in below figure.
12.1.1. Heating Operation Time Diagram
30
Downloaded from AC-Manual.com Manuals
12.2. Cooling Operation
• Cooling operation can be set using remote control.
• This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control.
• The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to
30°C.
• During cooling operation, the compressor will stop running and restart as shown in below figure.
12.2.1. Cooling Operation Time Diagram
31
Downloaded from AC-Manual.com Manuals
12.3. Soft Dry Operation
•
•
•
•
Soft Dry operation can be set using remote control.
Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control.
When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be turned “OFF”
for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the setting temperature as shown in
below figure.
• However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the indoor unit will
start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point.
12.3.1. Soft Dry Operation Time Diagram
32
Downloaded from AC-Manual.com Manuals
12.4. Automatic Operation
• Automatic operation can be set using remote control.
• This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature.
• After judged the temperature, the operation mode is determined by referring to the below standard.
• Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting
temperature as shown in below table.
• Operation mode will be determine again for judgement after 1 hour of operation, if the room temperature reaches to set
temperature and compressor off time is over 7 minutes 30 seconds continuously.
The present operation mode will be continued, if the room temperature does not reach to set temperature (Compressor keeps running)
eventhough after 1 hour from automatic operation mode started.
Automatic Set Temperature
Refer as below.
33
Downloaded from AC-Manual.com Manuals
• Automatic Set Temperature
For each operation, set temperature will automatically set as shown below.
However it can be selected 2°C higher or 2°C lower from standard set temperature by pressing the “Room Temperature Setting
button”.
• The setting temperature for all the operations can be changed one level up or one level down from the standard temperature as
shown in below table by pressing on the temperature up or temperature down button at remote control.
• The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the
circuit of JX1 at indoor electronic controller.
12.5. Operation Control
12.5.1. Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:- Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
- Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
12.5.2. Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5°C (cooling mode)/5°C (heating mode) or less for continuous 2 minutes, compressor will stop and restart
automatically.
• Time Delay Safety Control is activated before the compressor restart.
T = Intake air temperature - Indoor heat exchanger temperature
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
34
Downloaded from AC-Manual.com Manuals
12.5.3. 7 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
• This phenomenon is to reduce the built up humidity inside a room.
12.5.4. 60 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
• The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return
back to the outdoor unit.
12.5.5. Starting current Control
• When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
• The reason of the difference is to reduce the starting current flow.
12.5.6. Freeze Preventive Control
• To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to compressor.
• This control will activate when the temperature of indoor heat exchanger falls below 2°C continuously for more than 4 minutes.
• The current fan speed will change to freeze prevention speed after 70 seconds compressor on. When indoor pipe temperature
reaches certain temperature for 5 sec. the speed will be increased as in below figure.
• Compressor will turn off when indoor temperature falls below 2°C for more than 4 minutes. It will restart again when indoor heat
exchanger temperature rises to 10°C.
• Restart control (Time Delay Safety Control) will be applied in this control.
35
Downloaded from AC-Manual.com Manuals
12.5.7. Dew Prevention control
• To prevent dew formation at indoor unit discharge area.
• This control will be activated if:- Cooling mode or Quiet mode.
- Remote Control setting temperature is less than 25°C.
- Fan speed is at CLo or QLo.
- Room temperature is constant (±1°C) for 30 minutes.
- Compressor is continuously running.
• Fan speed and angle of horizontal louver (vertical airflow angle) will be adjusted accordingly in this control.
- Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
- The angle of horizontal louver will be changed as below figure.
Operation mode
Cooling, Soft Dry
A
B
Airflow direction auto-control
12° ~ 32°
20° ~ 30°
Airflow direction manual control
12°, 15°, 20°, 26°, 32°
22°, 24°, 26°, 28°, 30°
Note:
A = Normal operation angle of rotation
B = Dew prevention angle of rotation
Horizontal Louver Angle
During Anti-Dew condensation prevention, the horizontal louver angle in Auto-control are as below figure.
During Anti-Dew condensation prevention, the horizontal louver angle in Manual control are as below figure.
36
Downloaded from AC-Manual.com Manuals
12.5.8. 30 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 30 minutes and the intake air temperature falls between the
compressor OFF temperature (A) and compressor ON temperature (B) during the period.
• This is to maintain the room temperature as set. Despite of this, it is to prevent a wrong judgement of intake air temperature due
to poor installation near the sensor area.
12.5.9. Compressor Overload Protection Control
Outdoor Fan Control
• If the temperature of the indoor heat exchanger rises to 51°C, outdoor fan stops. The outdoor fan restarts when the indoor heat
exchanger temperature falls to 49°C.
Compressor high pressure protection
• If the indoor heat exchanger becomes 65°C or more, the compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
• This is to reduce the pressure, as to reduce the indoor heat exchanger temp. Nevertheless, is to protect the compressor from
overload of too high temperature.
12.5.10. 4-Way Valve Control
• 4-way valve always on during Heating operation. (except deicing operation)
• When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes.
• This is to prevent the refrigerant flow process sound for being occur.
12.5.11. Outdoor Fan Motor Control
• When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds (forced operation).
• This is to release the heat and to obtain the lowest pressure as fast as possible.
12.5.12. Hot Start Control
• Hot Start Control is to prevent cool air discharge into the room when heating operation start.
• When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
• Hot start is completed when indoor heat exchanger rises to 39°C or operation over 4 minutes.
37
Downloaded from AC-Manual.com Manuals
12.5.13. Anti Cold Draft Control
• This operation is to prevent the Cold Draft during Heating mode operation.
• The operation will start when compressor OFF (Thermo OFF) during Heating operation.
• For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat
exchanger temperature as shown below:
• After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
• Anti Cold Draft Control will stop when:
- Intake temperature < set temperature. (Time Delay Safety Control 4 minutes waiting is valid)
- 30 Minutes Time Save Control activates.
38
Downloaded from AC-Manual.com Manuals
12.5.14. Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
• Normal Deicing
Deice operations detection commences after 30 minutes of Heating operation starts or 60 minutes after previous deice
operation. If the TRS (Thermal Reed Switch) senses the outdoor piping temperature drops to -3°C (TRS CLOSE) or less for 50
sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
• Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and after
compressor starts for 1 minutes, deicing starts.
• Deicing ends when
1. 12 minutes after deicing operation starts;
2. TRS senses the outdoor piping temperature rises to 4°C (TRS OPEN).
Deicing will not end immediately as time delay (Td) is valid as shown below:
• Once deicing operation starts, it will not end for 60 seconds.
• After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
39
Downloaded from AC-Manual.com Manuals
Normal Deicing Time Diagram
Overload Deicing Time Diagram
40
Downloaded from AC-Manual.com Manuals
12.6. Indoor Fan Speed Control
• Indoor Fan Speed can be set using remote control.
12.6.1. Fan Speed Rotation Chart
Fan Speed (rpm)
S Hi
Hi
Me
H Lo
C Lo
LoS Lo
SS Lo
Q S Hi
Q Hi
Q Me
Q H Lo
Q Lo
CS-A7GKD
1190
1030
920
840
780
750
700
300
1090
930
820
770
680
CS-A9GKD
1300
1210
1000
890
830
780
750
300
1200
1110
900
790
730
CS-A12GKD
1320
1300
1120
860
800
750
700
300
1220
1200
1020
810
700
12.6.2. Automatic Fan Speed Control
• When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
- Fan speed rotates in the range of Hi, Me and Lo-.
- Deodorizing Control will be activated.
41
Downloaded from AC-Manual.com Manuals
• Auto Fan Speed during cooling operation:
1. Indoor fan will rotate alternately between off and on as shown in below diagram.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the
start of compressor. This cause the room temperature to achieve the setting temperature quickly.
4. During compressor stop, indoor fan will operate at Lo- for the beginning 3 minutes to prevent higher volume of refrigerant
in liquid form returning to the compressor.
5. For the resume of compressor operation, indoor fan will operate at Me fan speed to provide comfort and lesser noise
environment, after 70 seconds from the restart of compressor.
• Auto Fan Speed during Soft Dry operation:
1. Indoor fan will rotate alternately between off and Lo-.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.
This is to obtain the actual reading of intake air temperature.
42
Downloaded from AC-Manual.com Manuals
• Auto Fan Speed during Heating operation.
1. Indoor fan will rotate in the range of SLo → Me according to the heat exchanger temperature.
12.6.3. Manual Fan Speed Control
• Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
• There are 3 types of fan speed settings: Lo, Me, Hi.
12.7. Outdoor Fan Speed Control
• There is only one speed for outdoor fan motor.
• When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
• Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
12.8. Vertical Airflow Direction Control
12.8.1. Auto Control
• When the vertical airflow direction is set to Auto using the
remote control, the louver swings up and down as shown in
the diagram.
• When stop operation using the remote control, the discharge
vent is reset, and stop at the closing position.
• During Cooling operation or Soft Dry operation, indoor fan
motor may stop to rotate at certain periods. At that condition,
the louver will stop swinging and rest at the upper limit.
43
Downloaded from AC-Manual.com Manuals
Heating Operation
(Heating Operation condition)
• When the piping air temperature reaches 38°C, the louver is
changed from upper to lower limit. When the piping air
temperature falls to 35°C, the louver is changed from lower
to upper limit.
12.8.2. Manual Control
• When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in the diagram.
• The louver can be adjusted by pressing the button to the desired louver position.
• When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
• During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 10°, 15°, 20°, 26°, 32° to 22°, 24°,
26°, 28°, 30° under Cooling and Soft Dry operation mode.
Cooling and Soft Dry Operation
Heating Operation
12.9. Horizontal Airflow Direction Control
• The horizontal airflow direction louvers can be adjusted manually by hand.
12.10. Powerful Operation
• The Powerful operation is to achieve the setting temperature quickly.
(Cooling and Soft Dry Operation condition)
• When Powerful operation is set, the setting temperature will be automatically decreased 3°C internally against the present
setting temperature (Lower temperature limit: 16°C).
• This operation automatically will be running under SHi fan Speed (Cooling).
• Vertical Airflow Direction:- In “Manual” setting, the vane will automatically shift down 10° lower than previous setting.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
(Heating Operation condition)
• When Powerful operation is set, the setting temperature will be automatically increased 3°C against the present setting
temperature (Higher temperature: 30°C).
44
Downloaded from AC-Manual.com Manuals
• The Fan Speed will shift as shown below:
• Vertical Airflow Direction:- In “Manual” setting, the vane will automatically shift down 5° lower than previous setting.
- In “Auto” setting, the vane will automatically shift between upper and lower limit depending on the intake air temperature as
Heating Mode, Airflow Direction Auto-Control. However the upper and lower limit will be shifted 5° downward.
• Powerful operation stops when:- Powerful operation has operate for 15 minutes.
- Powerful button is pressed again.
- Quiet button is pressed.
- Stopped by OFF/ON operation button.
- Timer OFF activates.
- Operation mode is changed.
45
Downloaded from AC-Manual.com Manuals
12.11. Quiet Operation
(For Cooling Operation or cooling region of Soft Dry Operation)
• To provide quiet cooling operation condition compare to normal operation.
• Once the Quiet Mode is set at the remote control, the Quiet Mode LED illuminated. The sound level will reduce around 2 dB(A)
for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present operation sound level.
• Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1hr 30 min (1hr QLo, 30 min QLo + 50
rpm). After that, it goes back to Lo cool (However Quiet LED remains on).
• Manual Airflow Direction:- RPM control during Lo cool
- RPM control during Hi & Me cool
• Auto Fan Speed:-
• Quiet operation stops when:- Quiet button is pressed again.
- Stopped by OFF/ON operation button.
- Timer OFF activates.
- Operation mode button is changed.
46
Downloaded from AC-Manual.com Manuals
(Heating Operation condition)
• When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around 2 dB
(Lo) or 3 dB (Hi, Me), against the present sound level operation.
• Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
• Manual Fan Speed:- Rpm control during Lo, Me & Hi Cool
• Auto Fan Speed:- Rpm control depends on the piping air temperature sensor of Indoor heat exchanger
• Quiet operation stops when:- Quiet button is pressed again.
- Powerful button is pressed.
- Stopped by OFF/ON operation button.
- Timer OFF activates.
47
Downloaded from AC-Manual.com Manuals
12.12. Timer Control
12.12.1. ON Timer
•
•
•
•
When the ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so that the room
will reach nearly to the set temperature by the set time.
For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
For Automatic operation, the indoor fan will operate at SLo speed for 20 seconds, 30 minutes before the set time to detect the
intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.
12.12.2. OFF Timer
• When the OFF Timer is set by using the remote control, the unit will stop operate according to the desired setting.
Notes:
1. By pressing ON/OFF operation button, the ON Timer or OFF Timer setting will not be cancelled.
2. To cancel the previous timer setting, press CANCEL button.
3. To activate the previous timer setting, press SET button.
4. If main power supply is switched off, the Timer setting will be cancelled.
12.13. Random Auto Restart Control
• If there is a power failure during operation, the air conditioner will automatically restart after 3 to 4 minutes when the power is
resumed.
• It will start with previous operation mode and airflow direction.
• If there are more than one air conditioner unit in operation and power failure occur, restart time for each unit to operate will be
decided randomly using 4 parameters:- intake air temperature, setting temperature, fan speed and air swing louver position.
• This Random Auto Restart Control is not available when Timer is set.
12.14. Remote Control Signal Receiving Sound
• Short beep sound will be heard when:- enable initial Patrol Operation.
• Long beep sound will be heard for others setting.
48
Downloaded from AC-Manual.com Manuals
12.15. Patrol Operation
1. Purpose
To monitor air dirtiness level by using gas sensor and activates e-ion operation whenever air is dirty.
2. Control Condition
a. Patrol operation start condition
• When the unit operation is started with “OFF/ON” button.
• When the unit stops, “Patrol” button is pressed, Patrol individual operation will start.
• During cooling only operation, “Patrol” button is pressed.
b. Patrol operation stop condition
When any of the following condition is fulfilled:
• When “OFF/ON” button is pressed.
• During any operation with Patrol, "Patrol" button is pressed again.
• When “e-ion” button is pressed.
• When OFF Timer activates.
c. Patrol operation disable
• To disable the Patrol Operation during unit start (default) with “OFF/ON” button, press “Patrol” button and hold for 5
seconds, then release.
• To disable the Patrol Operation, press “Patrol” button and hold for 15 seconds, then release.
49
Downloaded from AC-Manual.com Manuals
3. Control Content
a. Gas Sensor Control
• First 2 minutes from Patrol function activates is stabilization time, during stabilization time, no air dirtiness level is
monitored. The Air Dirtiness level is set to level 2.
• After that, gas sensor starts to record the resistance value at fixed interval. Higher resistance value indicates cleaner air.
• The air dirtiness level is monitored by comparing the current resistance value with maximum resistance value from time to
time to get the Air Dirtiness Value.
• There are 3 air dirtiness level, based on the Air Dirtiness Value:
- Air Dirtiness level 0: Clean
- Air Dirtiness level 1: Moderate
- Air Dirtiness level 2: Contaminated
- Dirtiness level sensitivity adjustment.
It is possible to change the gas sensor sensitivity, where the Threshold value (G1 ~ G4) will be shifted accordingly:
a. Press and release “SET” button.
b. Press “Timer increment” / “Timer decrement” button to select sensitivity. (Low <–> Standard (Default) <–> High)
c. Confirm setting by pressing “Timer Set” button. LCD returned to original display after 2 seconds.
d. LCD returned to original display if remote control does not operate for 30 seconds.
b. e-ion Control
• When dirtiness level is 1 or 2, e-ion operation starts.
• If dirtiness level improves from level 2 to level 1, the unit carries out level change after 60 seconds.
• When dirtiness level returns to level 0 continuously for 10 minutes or more, e-ion operation stops.
Dirtiness Level Shift
• For Auto Fan Speed, the fan speed increased based on dirtiness level:
50
Downloaded from AC-Manual.com Manuals
c. Indoor Fan Control
• During any operation mode combines with Patrol operation, fan speed follows respective operation mode.
• During Patrol individual operation if e-ion starts, only Auto Fan Speed and no Powerful operation is allowed. Even if “Fan
Speed” button is pressed, no signal is sent to air conditioner, and no change on LCD display.
• During Patrol individual operation if e-ion stops, Indoor Fan stop operation.
d. Airflow direction (Horizontal, Vertical) Control
• During any operation mode combines with Patrol operation, air flow direction follows respective operation mode.
• During Patrol individual operation if e-ion starts, only Auto Air Swing is allowed. Even if “Air Swing” button is pressed, no
signal is sent to air conditioner, and no change on LCD display.
• During Patrol individual operation if e-ion stops, Airflow direction louver closed.
e. Indicator
• When Patrol operation starts, Patrol Sensor indicator ON.
• When e-ion operation starts based on dirtiness level, e-ion indicator ON.
f. Remote Control Receiving Sound
•
•
•
•
Normal Operation
Patrol Mode
Patrol Mode
Stop
→
→
→
→
Patrol Mode
Stop
Normal Operation
Patrol
: Beep
: Long Beep
: Beep
: Beep
g. Timer Control
• When ON timer activates when unit stops, previous operation resumes without Patrol operation.
• When ON timer activates during any operation, no change and carry on current operation.
• When OFF timer activates during any operation, all operation stops.
h. Power failure
• During Patrol individual operation, if power failure occurs, after power resumes, Patrol individual operation resumes
immediately.
• During combination operation, if power failure occurs, after power resumes combination operation resume immediately.
51
Downloaded from AC-Manual.com Manuals
12.16. e-ion Operation
1. Purpose
This operation provides clean air by producing negative ions to attract dust captured at the positively charged e-ion filters.
2. Control Condition
a. e-ion operation start condition
• During unit running at any operation mode, if “e-ion” button is pressed, combination operation (operation mode + e-ion
operation) starts.
• During unit is OFF, if “e-ion” button is pressed, e-ion individual operation starts.
b. e-ion operation stop condition
• When “OFF/ON” button is pressed to stop the operation.
• When “e-ion” button is pressed again.
• When “Patrol” button is pressed.
• When OFF Timer activates.
c. e-ion operation pause condition
• When indoor fan stop (during deice, odor cut control, thermostat off, etc.). e-ion operation resume after indoor fan
restarts.
• When indoor intake temperature 40°C. e-ion operation resume after indoor intake temperature < 40°C continuously for
30 minutes.
52
Downloaded from AC-Manual.com Manuals
3. Control Content
a. Indoor fan control
• During any operation mode combines with e-ion operation, fan speed follows respective operation mode.
• During e-ion individual operation - only Auto Fan Speed and no Powerful operation is allowed. Even if Fan Speed button
is pressed, no signal is sent to air conditioner, and no change on LCD display.
Auto Fan Speed for e-ion operation switches between HLo and CLo at pattern below:
b. Airflow direction control
• During any operation mode combines with e-ion operation, air flow direction follows respective operation mode.
• During e-ion individual operation, only Auto Air Swing is allowed. Even if Air Swing button is pressed, no signal is sent to
air conditioner, and no change on LCD display.
c. Timer control
• When ON timer activates when unit stops, previous operation resumes without e-ion operation.
• When ON timer activates during any operation, no change and carry on current operation.
• When OFF timer activates during any operation, all operation stops.
d. Indicator
• When e-ion operation starts, e-ion indicator ON.
e. e-ion Check Mode
• To check if e-ion is malfunctioning, during e-ion operation press “e-ion” button for 15 seconds and release to enter e-ion
Check Mode and supplies power to the e-ion AIR PURIFYING SYSTEM.
• If abnormal discharge is detected at filter (short-circuited) due to water or dust adhesion, etc., the e-ion indicator blinks
immediately.
f. Power failure
• During e-ion individual operation, if power failure occurs, after power resumes, e-ion individual operation resumes
immediately.
• During combination operation, if power failure occurs, after power resumes, combination operation resume immediately.
53
Downloaded from AC-Manual.com Manuals
g. Error Detection Control
When e-ion indicator blink, it indicates error listed below:
a. e-ion AIR PURIFYING SYSTEM main connector to PCB is open:
Judgment Method
• During e-ion operation (include during Patrol operation), e-ion AIR PURIFYING SYSTEM main connector to PCB is
opened.
Troubleshooting Methods
• Connect the connector or stop operation (include during Patrol operation) to cancel the blinking.
b. Abnormal Discharge
Judgment Method
• During e-ion operation, when feedback voltage is-Lo (at micro controller) is detected, it is judged abnormal discharge and
stops power supplies to the e-ion AIR PURIFYING SYSTEM.
• The unit retries after 30 minutes and repeat for 24 times. (not applicable for e-ion Check Mode)
Troubleshooting Method
• Press “e-ion” button or “OFF/ON” button to stop the operation and check the e-ion AIR PURIFYING SYSTEM main
connector to PCB.
• After that, press “e-ion” button again to confirm the e-ion indicator not blinking.
• The 24 times counter will be clear after 10 minutes of normal operation or when operation stops.
•
•
•
•
•
Error Reset Method
Press “OFF/ON” button to OFF the operation.
Press AUTO OFF/ON button at indoor unit to OFF the operation.
OFF Timer activates.
Press “e-ion” button during e-ion individual mode.
Power supply reset.
c. e-ion breakdown
Judgment Method
• When hi-feedback voltage (at micro controller) supplied to filter during e-ion stop, due to PCB or filter's high voltage power
supply damage.
• Operations except e-ion continue. Both Timer indicator and e-ion indicator blinks.
Troubleshooting Method
• Press “e-ion” button or “OFF/ON” button to stop the operation.
• Change main circuit board or filter's high voltage power supply.
• When lo-feedback voltage supplied to e-ion AIR PURIFYING SYSTEM during e-ion operation, e-ion indicator and Timer
indicator stop blinking.
54
Downloaded from AC-Manual.com Manuals
13 Servicing Mode
13.1. Auto OFF/ON Button
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be use to
operate air conditioner with limited function if remote control is misplaced or malfunction.
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5 seconds. A “beep”
sound will occur at the fifth seconds, in order to identify the starting of Test Run operation.
3. REMOTE CONTROL RECEIVING SOUND OFF/ON MODE
The Remote Control Receiving Sound OFF/ON operation will be activated if (within 20 seconds of Test Run Operation) the
Auto OFF/ON button is pressed for more than 5 seconds. 2 “beep” sound will occur at to identify the starting of Remote
Control Receiving Sound Off/On Mode.
Press “Auto OFF/ON button” to toggle remote control receiving sound.
- Short “beep”: Turn ON remote control receiving sound.
- Long “beep”: Turn OFF remote control receiving sound.
After Auto OFF/ON Button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON Mode is
restarted.
13.2. Select Remote Control Transmission Code
• There are 4 type of remote control transmission code could be selected and stored in EEPROM of indoor unit. The indoor unit
will only operate when received signal with same transmission code from remote control. This could prevent signal interference
when there are 2 or more indoor unit installed nearby together.
• To change remote control transmission code, short or open jumpers at the remote control printed circuit board.
• During Remote Control Receiving Sound OFF/ON Mode, press any button at remote control to transmit and store the desired
transmission code to the EEPROM.
55
Downloaded from AC-Manual.com Manuals
13.3. Remote Control Button
13.3.1. SET BUTTON
• To check current remote control transmission code.
- Press for more than 10 seconds.
• To change the air quality sensor sensitivity:
- Press and release with pointer.
- Press the Timer Decrement button to select sensitivity:
1. Low Sensitivity
2. Standard (Default)
3. Hi Sensitivity
- Confirm setting by pressing Timer Set button, a “Beep” sound will be heard. LCD returns to original display after 2 seconds.
- LCD returns to original display if remote control does not operate for 30 seconds.
13.3.2. CLOCK BUTTON
• To change the remote control’s time format.
- Press for more than 5 seconds.
13.3.3. RESET (RC)
• To clear and restore the remote control setting to factory default.
- Press once to clear the memory.
13.3.4. TIMER
• To change indoor unit indicator’s LED intensity.
- Press continuously for 5 seconds.
13.3.5. TIMER
• To change remote control display from Degree Celsius to Degree Fahrenheit.
- Press continuously for 10 seconds.
56
Downloaded from AC-Manual.com Manuals
14 Troubleshooting Guide
14.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
57
Downloaded from AC-Manual.com Manuals
14.1.1. Relationship Between The Condition of The Air Conditioner and Pressure and
Electric Current
Cooling Mode
Condition of the air
conditioner
Low Pressure
High Pressure
Heating Mode
Electric current
during operation
Low Pressure
High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or
Strainer
Short circuit in the indoor unit
Heat radiation deficiency of the
outdoor unit
Inefficient compression
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
14.1.2. Diagnosis Methods Of A Malfunction Of A Compressor And 4-way Valve
Nature of fault
Symptom
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
• The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
• The difference between high pressure and low pressure becomes almost zero.
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
• The compressor has a humming sound.
• Electric current during operation becomes approximately 80% lower than the normal value.
Insufficient switches of the 4-way valve
• The temperature different between from the discharge tube to the 4-way valve and from
suction
• tube to the 4-way valve becomes almost zero.
58
Downloaded from AC-Manual.com Manuals
15 Disassembly and Assembly Instructions
WARNING
• Cautions! When handling electronic controller, be careful of electrostatic discharge.
• Be sure to return the wiring to its original position.
• There are many high voltage components within the heat sink cover so never touch the interior during operation. Wait at least two minutes after
power has been turned off.
15.1. Indoor Electronic Controllers and Control Board Removal Procedures
59
Downloaded from AC-Manual.com Manuals
60
Downloaded from AC-Manual.com Manuals
15.2. Indoor Fan Motor and Cross Flow Fan Removal Procedures
61
Downloaded from AC-Manual.com Manuals
62
Downloaded from AC-Manual.com Manuals
16 Technical Data
16.1. Thermostat Characteristics
Cooling
Soft Dry
Heating
63
Downloaded from AC-Manual.com Manuals
16.2. Operation Characteristics
16.2.1. CS-A7GK CU-A7GK
64
Downloaded from AC-Manual.com Manuals
65
Downloaded from AC-Manual.com Manuals
66
Downloaded from AC-Manual.com Manuals
67
Downloaded from AC-Manual.com Manuals
16.2.2. CS-A9GK CU-A9GK
68
Downloaded from AC-Manual.com Manuals
69
Downloaded from AC-Manual.com Manuals
70
Downloaded from AC-Manual.com Manuals
71
Downloaded from AC-Manual.com Manuals
16.2.3. CS-A12GK CU-A12GK
72
Downloaded from AC-Manual.com Manuals
73
Downloaded from AC-Manual.com Manuals
74
Downloaded from AC-Manual.com Manuals
75
Downloaded from AC-Manual.com Manuals
17 Exploded View and Replacement Parts List
17.1. Indoor Unit
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
76
Downloaded from AC-Manual.com Manuals
REF. NO.
1
2
3
4
5
AI
6
7
8
A2
9
10
11
12
13
14
15
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
PART NAME & DESCRIPTION
CHASSY COMPLETE
FAN MOTOR, AC 15W SINGLE
CROSS FLOW FAN COMPLETE
BEARING ASS’Y
SCREW - CROSS FLOW FAN
ION GENERATOR
EVAPORATOR CO.
FLARE NUT (1/4)
FLARE NUT (3/8) (1/2)
E-ION AIR PURIFYING SYSTEM
CLIP FOR SENSOR
DISCHARGE GRILLE COMPLETE
VERTICAL VANE
CONNECTING BAR
CONNECTING BAR
CONNECTING BAR
A.S.MOTOR, DC SINGLE 12V300 OHM
CAP - DRAIN TRAY
HORIZONTAL VANE COMPLETE
BACK COVER CHASSIS
CONTROL BOARD CASING
TERMINAL BOARD COMPLETE
P.S.CORD W/OUT PLUG
ELECTRONIC CONTROLLER - MAIN
ELECTRONIC CONTROLLER - POWER
SENSOR COMPLETE
CONTROL BOARD FRONT COVER
INDICATOR COMPLETE
INDICATOR HOLDER
INDICATOR HOLDER
CONTROL BOARD TOP COVER
REMOTE CONTROL COMPLETE
FRONT GRILLE COMPLETE
INTAKE GRILLE COMPLETE
GRILLE DOOR COMPLETE
E-ION FILTER
SCREW - FRONT GRILLE
CAP - FRONT GRILLE
DRAIN HOSE
INSTALLATION PLATE
BAG COMPLETE - INSTALLATION SCREW
FULCRUM
QTY.
1
1
1
1
1
1
1
1
1
1
1
1
12
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
77
Downloaded from AC-Manual.com Manuals
CS-A7GKD
CWD50C1513
CWA921373
CWH02C1045
CWH64K007
CWH551146
CWH94C0014
CWB30C1844
CWT251026
CWT251027
CWH14C5332
CWH32143
CWE20C2627
CWE241157
CWE261092
CWE261071
CWE261091
CWA981091
CWH521096
CWE24C1183
CWD932454
CWH102321
CWA28C2162
CWA20C2589
CWA73C2467
CWA744529
CWA50C2122
CWH131207
CWE39C1168
CWD932744
CWD932745
CWH13C1171
CWA75C3002
CWE11C3638
CWE22C1329
CWE14C1010
CWD00K1001
XTT4+16CFJ
CWH521109
CWH851063
CWH361067
CWH82C067
CWH621049
CS-A9GKD
←
←
←
←
←
←
CWB30C2141
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
CWA73C2621
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
CS-A12GKD
←
←
←
←
←
←
CWB30C2138
←
CWT251035
←
←
←
←
←
←
←
←
←
←
←
←
CWA28C2163
←
CWA73C2620
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
←
17.2. Outdoor Unit
17.2.1. CU-A7GK CU-A9GK
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
78
Downloaded from AC-Manual.com Manuals
REF. NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
24
25
26
27
28
29
30
31
32
34
35
36
37
38
39
41
42
45
46
47
48
49
PART NAME & DESCRIPTION
CHASSY ASS’Y
SOUND PROOF MATERIAL
FAN MOTOR BRACKET
SCREW - FAN MOTOR BRACKET
FAN MOTOR (AC 30W SINGLE)
SCREW - FAN MOTOR MOUNT
PROPELLER FAN ASS’Y
NUT - PROPELLER FAN
COMPRESSOR
ANTI - VIBRATION BUSHING
NUT - COMPRESSOR MOUNT
CONDENSER
4-WAY VALVE
STRAINER
HOLDER COUPLING
2-WAY VALVE (LIQUID)
3-WAY VALVE (GAS)
OVERLOAD PROTECTOR
HOLDER - O.L.P.
TERMINAL COVER
NUT - TERMINAL COVER
SOUND PROOF BOARD
TERMINAL BOARD ASS’Y
CAPACITOR - COM.
HOLDER CAPACITOR
CAPACITOR - F.M
CABINET SIDE PLATE (L)
CABINET SIDE PLATE COMP.
CABINET FRONT PLATE ASS’Y
WIRE NET
CABINET TOP PLATE
CONTROL BOARD COVER
BAG COMPLETE
TUBE ASS’Y (CHK VALVE, CAPILLARY)
CAPILLARY TUBE ASS’Y
ELECTRO MAGNETIC SWITCH
ELCTROLYTIC CAPACITOR
TEMPERATURE RELAY
V-COIL COMPLETE
OPERATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
OPERATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
QTY.
1
1
1
2
1
3
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
79
Downloaded from AC-Manual.com Manuals
CU-A7GKD
CWD50K2112
CWG302255
CWD541075
CWH551198
CWA951387J
CWH55406J
CWH03K1020
CWH56053J
2RS122D5BC02
CWH50077
CWH56000J
CWB32C1979
CWB001024J
CWB11025
CWH351047
CWB021218
CWB011258
CWA121050J
CWH7041200
CWH171011
CWH7080300J
CWH151074
CWA28K1021J
DS371206CPNA
CWH301038
DS441205NPQA
CWE041110A
CWE04C1042
CWE06K1048
CWD041057A
CWE031041A
CWH13C1099
CWG87C900
CWT01C3976
—
CWA00059
CWA32C1003
CWA14C1009
CWA43C2187
CWF565377
CWF613059
CWF565456
CWF613060
CWF613061
CU-A9GKD
←
←
←
←
←
←
←
←
2PS156D3BB02
←
←
CWB32C1493
←
←
←
CWB021217
CWB011257
CWA121210J
←
←
←
←
←
DS371306CPND
CWH301035
←
←
←
←
←
←
←
←
—
CWB15K1166
←
←
←
←
←
←
←
←
←
17.2.2. CU-A12GK
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
80
Downloaded from AC-Manual.com Manuals
REF. NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
20
21
22
24
25
26
27
28
29
30
31
32
33
34
35
36
38
39
40
41
42
44
45
46
47
48
49
PART NAME & DESCRIPTION
CHASSY ASS’Y
SOUND PROOF MATERIAL
FAN MOTOR BRACKET
SCREW - FAN MOTOR BRACKET
FAN MOTOR (AC 30W SINGLE)
SCREW - FAN MOTOR MOUNT
PROPELLER FAN ASS’Y
NUT - PROPELLER FAN
COMPRESSOR
ANTI - VIBRATION BUSHING
NUT - COMPRESSOR MOUNT
CONDENSER
4-WAY VALVE
STRAINER
HOLDER COUPLING
2-WAY VALVE (LIQUID)
3-WAY VALVE (GAS)
TERMINAL COVER
NUT - TERMINAL COVER
SOUND PROOF BOARD
TERMINAL BOARD ASS’Y
CAPACITOR - COMP.
HOLDER CAPACITOR
CAPACITOR - F.M
CABINET SIDE PLATE (L)
CABINET SIDE PLATE COMP.
CABINET FRONT PLATE ASS’Y
WIRE NET
CABINET TOP PLATE
PLATE - C.B.COVER
CONTROL BOARD COVER
BAG COMPLETE
TUBE ASS’Y (CHK VALVE, CAPILLARY)
ELECTRO MAGNETIC SWITCH
ELCTROLYTIC CAPACITOR - COMPLETE
MAGNET RELAYS
TEMPERATURE RELAYS
V-COIL COMPLETE
HANDLE
OPERATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
OPERATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
QTY.
1
1
1
2
1
3
1
1
1
3
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
CU-A12GKD
CWD50K2074
CWG302410
CWD541030
CWH551198
CWA951117J
CWH55406J
CWH03K1006
CWH56053J
2KS206D5AF04
CWH50055
CWH561049
CWB32C1266
CWB001026J
CWB11025
CWH351023
CWB021117
CWB011482
CWH171012
CWH7080300J
CWH151023
CWA28K1034J
DS371356CPNC
CWH30060
DS441205NPQA
CWE041248A
CWE04C1118
CWE06K1034
CWD041111A
CWE031014A
CWH13C1064
CWH131295
CWG87C900
CWT01C3650
CWA00059
CWA32C067
K6A2C7A00002
CWA14C1009
CWA43C2273
CWE161010
CWF565377
CWF613059
CWF565456
CWF613060
CWF613061
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
[PHAAM] Printed in Malaysia
SSYW0612-00
81
Downloaded from AC-Manual.com Manuals

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement