Chromalox 2110 Single and Dual Channel User manual
Add to my manuals
28 Pages
The Chromalox 2110 Temperature Controller offers users an easy three-step setup process to get your process up and running quickly and accurately. With a 1/4 DIN rugged plastic housing, process temperature control is optimized for hosedown applications. Dual LED displays for temperature and set point make it easy to see current operating conditions.
advertisement
2110 Temperature
Controller
Chr omal ox
Loa d
Alarm Tem p
Set
Poin t
2110
°F
°C
Poin t
User Manual
0037-75409
PK498-1
May, 2012
C US
Table of Contents
Manual Sections
1–Quick Setup ........................................................................................1
2–Introduction ........................................................................................2
3–Installation and Wiring ........................................................................4
4–Adjusting Setpoint and Configuration ..............................................12
5–Controller and Alarm Operation ........................................................16
6–Replacing Output Modules ...............................................................17
7–Calibration ........................................................................................19
8–Specifications ...................................................................................21
9–Troubleshooting ................................................................................22
Illustrations
1.1 Dip Switch Settings ........................................................................1
1.2 Establishing the Set Point ..............................................................1
1.3 Adjusting the Set Point ...................................................................1
2.1 Front Panel Identification ...............................................................2
2.2 Typical Application .........................................................................3
2.3 Model Identification ........................................................................3
3.1 Default Dip Switch Settings ...........................................................4
3.2 Removing Mounting Collars ...........................................................5
3.3 Mounting Dimensions ....................................................................6
3.4 Mounting the 2110 .........................................................................6
3.5 Wiring Terminal Identification .........................................................7
3.6 Thermocouple Connections with Shield ........................................8
3.7 Three-Wire RTD Connections with Shield ......................................9
3.8 Two-Wire RTD Connections ...........................................................9
3.9 Control Output Wiring–R1 and S0 ................................................10
3.10 Control Output Wiring–R3 ............................................................10
3.11 Control Output Wiring–V0 ............................................................10
3.12 Control Output Wiring–S1 and S2 ................................................11
3.13 90-260 VAC Instrument Power Connections ...............................11
3.14 Alarm Connections .......................................................................11
4.1 Establishing the Set Point ............................................................12
4.2 Adjusting the Set Point .................................................................12
4.3 Configuring 2110 ..........................................................................13
4.4 Configuring 2110 ..........................................................................13
4.5 Configuring 2110 ..........................................................................13
4.6 Configuring 2110 ..........................................................................13
4.7 Configuring 2110 ..........................................................................13
4.8 Configuring 2110 ..........................................................................13
6.1 Replacing Output Module ............................................................18
iii
Chromalox 2110
2110 Temperature Controller
Section 1—Quick Setup
After the controller is properly wired into the system, the user only needs to verify the sensor input and control type and adjust the set point.
Setting the Sensor and Control Mode
Adjust the dip switches located on the bottom of the unit as shown in Figure 1.1. The factory settings are J, TC, °F, and PI. It is simpler to adjust the dip switch prior to mounting the 2110.
J
RTD
˚C
ONOF
K
TC
˚F
PI
J
RTD
˚C
ONOF
K
TC
˚F
PI
Figure 1.1
Dip Switch Settings
Adjusting the Set Point
1. Apply power to the unit.
2. To adjust the set point on the Chromalox 2110 Temperature Controller, press and hold the Set Point button (see Figure 1.2). The
Set Point light is illuminated.
3. While still pressing the Set Point button, press either the or button to adjust the set point to the desired value (see Figure 1.3).
Holding the or button increases the speed of the set point changes.
Chromalox
Load
Alarm
2110
° F
° C
Chromalox
Load
Alarm
2110
° F
° C
Temp Set Point Temp Set Point
Point Point
Section 1–Quick Setup
Figure 1.2
Establishing the Set Point
Figure 1.3
Adjusting the Set Point
The Controller is now operational with factory settings. For more precise control, set up of the alarm, etc., see Section 4 – Adjust- ing Set Point and Configuration.
1 Chromalox 2110
Section 2—Introduction
Description
The Chromalox 2110 Temperature controller offers simple setup, flexibility and control features in an attractive, compact design.
The 2110 is housed in a rugged, plastic 1/4 DIN package that only requires four inches behind the mounting surface. Straightforward operation and easy-to-use control features are major strengths of the 2110 controller.
Easy Three-Step Setup: The 2110 delivers exceptional process temperature control. Your process is up and running after three easy setup steps: 1) Select the sensor and control type, 2) Hook up the system and 3) Select the desired temperature.
NEMA 4X Front Panel
Construction for hosedown applications
Display
(4 Green, 7-Segment LEDs)
Actual process temperature displayed
Output LEDs
Indicates control load
ON and alarm status
Temp and Set Point LEDs
Indicates actual or set point temperature is displayed
Chromalox
Load
Alarm
Temp Set Point
2110
° F
° C
Green LEDs
Indicates °F or °C selected for temperature display
Set Point Button
• In Operation Mode, adjusts
Set Point
• In Configuration Mode with the or button as “Menu” button
, serves
Point
• In Operation Mode, pushbuttons adjust Set
Point.
• In Setup Mode, pushbuttons increase/ decrease MENU values.
Figure 2.1
Front Panel Identification
Inspection and
Unpacking
Your Chromalox 2110 controller should arrive in good condition.
Upon arrival, inspect the packaging for any visible damage.
Unpack the controller and carefully inspect for product damage that may have occurred during shipment. If the package or contents have been damaged in shipping, you must file a claim with the delivery service. The delivery service will not accept a claim from the shipper.
If not immediately installing the controller, store in a cool, dry environment in its original protective packaging. Temperature extremes and excessive moisture can damage the instrument.
Chromalox 2110 2 Section 2–Introduction
2110 Temperature Controller
Typical Application
Figure 2.2 shows the 2110 in a typical application.
Figure 2.2
Typical Application
Model
Identification
Before installation, please identify your controller model number.
The model number appears on a label on the side of the housing.
Use Figure 2.3 to identify the options in your controller.
Section 2–Introduction
Model
2110 1/4 DIN Controller, with Selectable Thermocouple or RTD Inputs
Code Control Output
R1
R3
V0
S0
S1
S2
Relay, 1 Amp Form A, 120/240Vac
Relay, 20 Amps Form A, 120/240Vac
Solid State Relay Drive, 24Vdc @ 40ma
Solid State Relay, 1 Amp, up to 240 Vac
Solid State Relay, 5 Amps, up to 240Vac
Solid State Relay, 10 Amps, up to 240Vac
Code Alarm Output (Kit Option)
0
1
No Alarm
Alarm Form “C” Relay, 5 Amps at 120Vac,
2.5 Amps at 240Vac
Code
0 Add to Complete Part Number
Code Power Supply
0 90-260Vac
2110 - R3 1 0 0 Typical Model Number
Figure 2.3
Model Identification
3 Chromalox 2110
Section 3—Installation and Wiring
Sensor and Control
Type Selection
Switches
Set the Chromalox 2110 controller’s configuration via mechanical dip switches, located on the bottom of the unit. Factory settings are
J, TC, °F, and PI Control. Switches are easier to set before mounting.
To change the switch settings, first disconnect all wiring and power from the unit. Adjust switch settings as follows:
Switch Function
A Thermocouple
B
C
D
Input Type
Temperature Units
Control Type
Setting Factory
Options Setting
J or K J
TC or RTD
°F or °C
ON-OFF or PI
TC
°F
PI
If input type is thermocouple, switch A selects either thermocouple type J or K.
Switch B selects input type thermocouple or RTD (resistance temperature detector). Note: If RTD is selected, switch A is ignored.
Switch C selects temperature units °F or °C.
Switch D selects either PI (Proportional-Integral) or ON-OFF control.
Chromalox 2110
J
RTD
˚C
ONOF
K
TC
˚F
PI
J
RTD
˚C
ONOF
K
TC
˚F
PI
Figure 3.1
Default Dip Switch
Settings
4 Section 3–Installation and Wiring
2110 Temperature Controller
Mounting
Two mounting collars securely hold the 2110 controller in the mounting hole. Remove these mounting collars before installation.
Removing Mounting Collars
1. To remove the rear collar, press the sides of the collar. This releases holding tabs on the top and bottom of the collar.
2. Slide the collar off the back of the unit.
3. Slide the front collar off the back of the unit
Press In
Holding
Tabs
Front Collar
Rear Collar
Press In
Section 3–Installation and Wiring
Figure 3.2
Removing Mounting Collars
5 continued
Chromalox 2110
Chromalox 2110
Mounting
continued
Mount the 2110
1. Cut out a 1/4 DIN, 3.6-inch (92mm) square hole in the mounting panel.
2. Insert the unit into the mounting hole as shown in Figure 3.4.
3. Slide the front mounting collar onto the back of the controller.
4. Slide the rear mounting collar onto the back of the controller until the holding tabs securely engage with the holding tab slots in the controller housing (see Figure 3.4).
5. Tighten the four rear collar mounting screws until the unit is held firmly in the panel. CAUTION: Do not overtighten.
The controller will now be held firmly in place.
(101.6)
Chromalox
Load
Alarm
Temp Set Point
2110
° F
° C
(10)
Point
(101.6)
Figure 3.3
Mounting Dimensions
(92) (12.7)
(90)
(102)
Holding
Tabs
Slots
(92)
3.6
(92)
Holding
Tabs
Figure 3.4
Mounting the 2110
6
Front Collar
Rear Collar
Rear Collar
Mounting Screw
Section 3–Installation and Wiring
2110 Temperature Controller
Good Wiring
Practices
!
Separate wire into bundles —When planning the system wiring, separate wiring into functionally similar bundles, e.g.
• Power leads
• Sensor leads (if power leads must cross sensor leads, they should cross at a 90° angle)
• Output signal lines
Separate sources of electrical noise —Locate all sources of electrical noise in your system, and separate these sources from the control system, e.g.
• Motors
• Contacts
• Solenoids
Electrical noise can affect the function of any control system. When driving a contactor coil or other inductive load, an appropriate rated
AC snubber circuit is recommended (Chromalox Part No. 0149-01305).
Connect before power is applied —Make all electrical wiring connections to the back of the controller before power is applied to the unit.
Comply with regulations—WARNING: All wiring practices must comply with local regulations. Failure to do so could result in damage to controller and/or personal injury or death from electrical shock.
This instrument is intended for panel mounting and the terminals must be enclosed within a panel. Use National Electric Code (NEC)
Class 1 wiring for all terminals except the sensor terminals.
Check wiring decal —Check the wiring decal on the side of the unit to verify the model number. The wiring decal shows the wiring terminations. All wiring will be connected to the terminals on the back of the instrument case. Specific wiring instructions for different input and output types are given in this section. See also Figure 3.5.
Additional information —For sensor wiring practices, see “Sensor
Input Wiring”. For additional information on good wiring practice, request IEEE Standard No. 518-1982 from IEEE, 345 East 47 th St., New
York, NY 10017 or www.ieee.org.
Sensor Input
Wiring COM NO NC
Alarm Wiring
Section 3–Installation and Wiring
Output
Wiring
(S1, S2)
Figure 3.5
Wiring Terminal Identification
7
Output Wiring
(R1, R3, V0, or S0)
Instrument
Power Wiring
Chromalox 2110
Sensor Input Wiring
Sensor Wiring Notes
For safety and best controller performance,
• Sensor leads (thermocouple and RTD) should not be run in the same conduit as power wiring.
• Twisted pair, shielded wire is recommended for sensor connections.
• False temperature readings can occur if the sensor wire is exposed to electrical noise.
• Ungrounded thermocouples are recommended.
• Thermocouple extension wire, if required, must be the same type as the thermocouple (i.e. if a Type K thermocouple is used, then
Type K extension wire must be used.)
• Shielded thermocouple wire, if used, must have the shield grounded at one end only, preferably at the shield ground terminal on the controller as shown in Figure 3.6.
• Three-wire RTDs are recommended for greatest accuracy.
• Standard shielded copper wire is recommended for RTD extensions.
Thermocouple Inputs
It is important to observe polarity (+,-) when connecting thermocouple leadwires. ANSI color coding for the thermocouples used with this instrument are
Thermocouple
Type Material Polarity (+) Polarity (-)
J iron/constantan white red
K chromel/alumel yellow red
Make thermocouple wiring connections to terminals as shown in Figure 3.6.
TC +
TC -
Chromalox 2110
NO COM NC
Shield Ground
Figure 3.6
Thermocouple Connections with Shield
8 Section 3–Installation and Wiring
2110 Temperature Controller
Sensor Input Wiring
continued
Three-Wire RTD Inputs
IMPORTANT: When making the three-wire RTD input connection, make the resistance of all three extension leadwires equal by using the same gauge and same length of wire for optimum accuracy. A three-wire RTD will generally have two wires of the same color. Connect the same colored wires to the RTDL connections.
Connect the alternate colored wire to the RTDH connection.
Make three-wire RTD connections to terminals as shown in Figure 3.7.
Section 3–Installation and Wiring
RTDH
RTDL
RTDL
NO COM NC
Shield Ground
Figure 3.7
Three-Wire RTD Connections with Shield
Two-Wire RTD Inputs
If using a two-wire RTD input, use heavier gauge leadwires to reduce leadwire resistance. Any leadwire resistance adds directly to sensor resistance, thus adding error to the process temperature measurement. It is also necessary to jumper the two RTDL terminals on the instrument to complete a two-wire hookup.
Figure 3.8
Two-Wire RTD Connections
9
RTDH
RTDL
RTDL
NO COM NC
Chromalox 2110
Control Output
Wiring
The following figures show the proper control output wiring for the various 2110 configurations.
R1 (1 Amp Relay) and S0 (1 Amp, Solid State Relay)
Output Wiring
When driving a contactor coil or other inductive load, an appropriately rated AC snubber circuit is recommended (Chromalox
Part. No. 0149-01305), as shown in Figure 3.9.
Chromalox 2110
COM NO NC 120/240
VAC
Neutral
Fuse
Load
Snubber
Figure 3.9
Control Output Wiring–R1 and S0
R3 (20 Amp Relay) Output Wiring
1/4” fast-on tabs are provided with the R3 output.
COM
NO
120/240
VAC
Neutral
Fuse
Load
Figure 3.10
Control Output Wiring–R3
COM NO NC
COM
NO NC
V0 (Solid State Relay Drive, 24Vdc, 40mA) Output Wiring
+
120/240VAC
AC Neutral
Fuse
SSR
4115
+
-
Load
-
Figure 3.11
Control Output Wiring–V0
COM NO NC
Section 3–Installation and Wiring
2110 Temperature Controller
Control Output
Wiring
continued
S1 (Solid State Relay, 5 Amps) and
S2 (Solid State Relay, 10 Amps) Output Wiring
Note: 2110 model S2 has a fan. 2110 model S1 does not have a fan.
Fan
COM NO NC
Fuse
Load
120/240
VAC
Neutral
Figure 3.12
Control Output Wiring–S1 and S2
Instrument Power
Wiring
Make 120 or 240 VAC instrument power connections to terminals as shown in Figure 3.13.
120/240VAC
Neutral
Ground
NO COM NC
Figure 3.13
90-260 VAC Instrument Power Connections
Alarm Wiring
The Form C Relay Output is connected as shown in Figure 3.14.
Alarm Out
C NO NC
COM NO NC
Section 3–Installation and Wiring
Figure 3.14
Alarm Connections
COM NO NC
11 Chromalox 2110
Section 4—Adjusting Set Point and Configuration
Adjusting the
Set Point
1. Set selection switches (see Figure 3.1).
2. Apply power to the unit.
3. To adjust the set point on the Chromalox 2110 Temperature Controller, press and hold the Set Point button (see Figure 4.1). The
Set Point light is illuminated and the set point value is displayed.
4. While still pressing the Set Point button, press either the or button to adjust the set point to the desired value (see Figure 4.2).
5. Release the Set Point button.
Chromalox
Load
Alarm
Temp Set Point
2110
° F
° C
Chromalox
Load
Alarm
Temp Set Point
2110
° F
° C
Point Point
Figure 4.1
Establishing the Set Point
Figure 4.2
Adjusting the Set Point
Configuration
While the 2110 default settings make it a simple setup controller for most applications, additional programmable menus can be configured through three front-panel pushbuttons.
To access the user configuration menus,
1. Press and hold the and buttons. After three seconds the display will begin to toggle between the current security code and LocH (LOCK). The Temp and Set Point LEDs will turn on.
See Figure 4.3.
2. Press the or button to adjust the value to the appropriate security number (see Security Codes and Levels). Only the value is displayed during adjustment. See Figure 4.4.
3. Press and hold the Set Point ( ) button and press the or
buttons to scroll the configuration menus. The display will show the name of the menu and then begin to toggle between the name and the current value. See Figures 4.5 and 4.6.
Chromalox 2110 12 Section 4–Adjusting Set Point and Configuration
2110 Temperature Controller
Configuration
continued
4. Press the or buttons to adjust the value (only the value is displayed during adjustment). See Figure 4.7. The new value is set when the or button is released.
5. Press and hold the Set Point ( ) button and press the button to advance to the next menu. See Figure 4.8. (Holding the Set Pointt ( ) button and pressing the button moves through menus in the opposite direction.)
Repeat steps 4 and 5 through the configuration menus.
Chromalox
Load
Alarm
Temp Set Point
2110
˚F
˚C
Chromalox
Load
Alarm
Temp Set Point
2110
˚F
˚C
Set
Point
Figure 4.3
Figure 4.4
Adjust lock to 458
Figure 4.5
Chromalox
Load
Alarm
Temp Set Point
2110
˚ F
˚ C
Move to next menu
Figure 4.6
Chromalox
Load
Alarm
Temp Set Point
2110
˚F
˚C
Set
Point
Continue until SP is displayed
Chromalox
Load
Alarm
Temp Set Point
2110
° F
° C
Chromalox
Load
Alarm
Temp Set Point
2110
˚F
˚C
Point
Set
Point
Figure 4.7
Adjust the set point value
Figure 4.8
Continue through the configuration menus
Exit Configuration
To exit configuration mode, press and hold both the and buttons for three seconds to return to the operation mode.
Note: If no buttons are pressed for three minutes while in user configuration mode, then the controller will exit user configuration and return to the operation mode.
Section 4–Adjusting Set Point and Configuration 13 Chromalox 2110
Security Codes and
Levels
To limit access to the user configuration interface, security codes are assigned to different menu levels. Make security codes available to operators, maintenance crew, supervisors, etc. according to what function level you want for each group. Security Level C
is not recommended for most users. Gain access to configuration menus using the following codes.
Security Level
A
B
C
Security Code
All Values
458
736
Function
Allows adjustment of the Set Point
Basic menus
Calibration menus
Configuration
Menus
The following configuration menus can be accessed through the user interface (see Configuration, page 12).
Menu
Code
Loch
Function
Security Lock
Proc
SP
Pb
ArSt
Adjustable
Range
0-999
Process Variable Display
Displays the actual process temperature.
Process Set Point Adjust
Adjusts the target process temperature.
Proportional Band
Temperature range above/below set point where proportional control is active. Most applications require a band between 10 to 200°F. This menu is active only when the dip switch is set to “PI”
Automatic Reset
Control feature that automatically corrects for small temperature offsets that occur in proportional control. The higher the setting, the faster the correction occurs. A high setting could cause overshoot during start-up. A low setting will not allow process temperature to reach to set point quickly enough. A setting of “0” turns off automatic reset. This menu is active only when the dip switch is set to “PI”.
Read Only
°F or °C
Sensor
Range
°F or °C
1 to Sensor
Span
Maximum
°F or °C
0.0 to 100.0
Repeats/
Min.
Factory
Default
458
N/A
0°F
25
0.1
Security
Level
A
A
A
B
Chromalox 2110 14 Section 4–Adjusting Set Point and Configuration
2110 Temperature Controller
Configuration
Menus
continued
Menu
Code
CYCL db
ALty
ALSP
ALdb
SPLL
SPUL outl
Function
Cycle Time
The time for the output to complete ON to OFF to
ON cycle. Used only with proportional control. A fast cycle time provides better control, but can cause premature wear to contactor or other power switching devices.
Magnetic contactors should not be switched at less than a 30 second cycle time. This menu is active when the dip switch is set to “PI”.
On/Off Dead Band
The range above/below set point in which no control action takes place. Determines at what temperature the output switches ON and OFF. For a 5°F dead band, 2.5°F is above and below the set point. This menu is active when the dip switch is set to “ONOF”.
Alarm Type
Select high or low alarm.
Alarm Set Point
Temperature level that will actuate the alarm.
Alarm Dead Band
Difference of temperature from alarm set point before an active alarm resets.
Set Point Lower Limit
Lower limit to which set point may be set without security code access.
Set Point Upper Limit
Upper limit to which set point may be set without security code access. This prevents an operator from setting the set point temperature to a level which would damage equipment or process.
Output Limit
Limits the percentage of output that can be applied in proportional control.
Adjustable
Range
.1 to 60.0
Sec.
1 to 100 °F or °C
Off, Hi or Lo
0 to 100 °F or °C
0 to 100 °F or °C
Sensor
Range
°F or °C
Sensor
Range
°F or °C
0 to 100%
Factory
Default
Output
R1, R3 =
30 sec.
S0, S1,
S2, V0 =
1 sec.
5 Foc
OFF
5
5
Span
Low
Span
High
100
Security
Level
B
For calibration menus (CoFF, dFLt, & CALS), see Section 7–
Calibration
B
B
B
B
B
B
B
Section 4–Adjusting Set Point and Configuration 15 Chromalox 2110
Section 5—Control and Alarm Operation
Control Operation
The 2110 is shipped from the factory with PI (proportional/integral) control. Proportional control actually determines the percent of heat needed to control the process. The factory setting for the Proportional Band is
25°F and the Automatic Reset (Integral) is set at 0.1 repeats/minute.
These settings will control many processes without any changes to the controller. If the process is unstable or too sluggish, the Proportional
Band and Automatic Reset can be changed in the menu configuration.
Alarm Operation
(optional)
Tuning PI Control
Adjust Proportional Band The objective of the proportional band adjustment is to find the proportional band setting at which the process temperature stabilizes and does not oscillate. If the temperature display is oscillating, increase the Proportional Band (doubling the value) until the temperature display has stopped oscillating. To establish a quick response to control upsets, adjust for the smallest band that provides stable control (does not oscillate). Note: The temperature at this point may not be at set point, but will be stable.
Adjust Automatic Reset (Integral) The Automatic Reset (Integral) automatically removes the offset between process temperature and set point. If the process is too sluggish in approaching set point, double the automatic reset. Too much automatic reset will make a process unstable.
Cycle Time Cycle time setting determines how often to switch the output to the heater. For example, if the cycle time is 1 second and the
2110 needs a 75% output, the output will be on for 3/4 of a second and off 1/4 of a second. Units with relay control outputs (R1 or R3) are shipped with a 30-second cycle time. Units with solid state relays or solid state relay drives (S0, S1, S2, or V0) are shipped with a 1-second cycle time.
An alarm relay output is optional on the 2110. An alarm can help protect the process when a too high or too low temperature occurs.
High Alarm: This alarm is a high absolute alarm that actuates when the process temperature is equal to or greater than the alarm set point. For example, if the high alarm set point is 500°F, the alarm will always actuate when the process temperature reaches 500°F.
Low Alarm: The low absolute alarm actuates when the process temperature is equal to or less than the alarm set point. The low alarm features a power-up inhibit to prevent undesirable alarms during process start up.
After the unit reaches control set point, the low alarm will respond.
Alarm Dead Band: The alarm relay de-energizes (resets) when the temperature crosses out of the alarm dead band. For example, if the high alarm is set to 500°F and the alarm dead band is 5°F, the alarm condition will not reset until the process temperature reaches 495°F.
To enable the alarm relay, select either high or low alarm type and set the alarm set point. An alarm condition is indicated when the Alarm light to the left of the display illuminates. Alarm type, set point, and dead band are selectable through the user configuration interface.
Chromalox 2110 16 Section 5–Control and Alarm Operation
2110 Temperature Controller
Section 6—Replacing Output Modules
The Chromalox 2110 Temperature Controller was shipped with the output modules installed as ordered. The 10A Solid State Relay and
20A Mechanical Relay output cards control small cartridge heater or strip heater loads directly, eliminating the need for a remote contactor or solid state relay. If a larger load is required, the 2110 can be configured with a 1A Pilot Duty Relay or Solid State Relay Drive.
The 2110 may be optionally configured with a 5A/120V Alarm Relay.
Alternate modules, configured with or without alarm, can be installed as needs change.
Control and alarm outputs can be changed in the field.
Module Option
Descriptions
Output Module options are as follows
Description
R1 Relay
Load/Sourcing
Specification
Form A contact, SPST,
N.O. 1.0 Amp at 120/240
VAC resistive load
R3 Relay Form A contact, SPST,
N.O. 20 Amp at 240
VAC, 28 VDC resistive load
V0 SSR
Drive
S1 Solid
State Power
Controller
24 VDC nominal at 40 mA
S1 TRIAC 1 amp continuous, 10
Amp in-rush 120/240
VAC
120/240 VAC, 5 Amp @
40°C ambient
S2 Solid
State Power
Controller
120/240 VAC, 10 Amp @
40°C ambient with builtin cooling fan mounted on rear of housing
Factory
Default
Cycle
Time
Part No w/o Alarm
Part No. w/
Alarm
30 sec.
0149-27133 0149-27147
30 sec.
1 sec.
1 sec.
1 sec.
1 sec.
0149-27132 0149-27146
0149-27135 0149-27149
0149-27134 0149-27148
0149-27136 0149-27150
0149-00022
(Fan Kit)
0149-00022
(Fan Kit)
Module Installation
!
Section 6–Replacing Output Modules
WARNING: Remove power from the controller before changing the output module. Failure to do so could cause damage to controller and/or personal injury or death from electrical shock.
When handling output modules, be careful to guard the module against static discharge. Follow the steps below to remove an existing output module and replace it with a new module.
Removal
1. Remove power from the controller.
2. Remove all terminal connections.
continued
17 Chromalox 2110
Module Installation
continued
!
3. Remove the back cover by lifting four housing clips on the controller. This releases the back cover. Then pull cover straight off the controller.
4. Gently pry around the sides to loosen and remove the module.
Pull module straight out to avoid bending pin connections.
WARNING: Do not remove module by the handling components on the module board. This could damage the module.
When removing an S2 output module (SSR with fan), a cable connects the fan to the far right center of the S2 board. Gently disconnect the cable from the connector on the output board. Do not remove the fan from the back cover. This is a single assembly.
For the S2 output module, reconnect the fan cable to the connector on the far right center of the module. Tuck the cable around the heatsink.
Replacement
1. Line up pins on the controller with pin connections on either side of the module and push the new module into place.
2. Reinstall the back cover.
Controller
Pin
Module
Chromalox 2110
Housing
Clip
Back Cover
Figure 6.1
Replacing Output Module
Auto Cycle Time
The Control Output Modules have a default cycle time of 1 second
(fast switching) or 30 seconds (slow switching) (See table on page
17). After replacing a control output, the 2110 verifies at power up if a slow or fast cycle time output has been installed. If an output with a different default cycle time is installed, the 2110 will change the cycle time to the new device’s default. If the user has changed the cycle time in configuration, the 2110 retains this value unless an output with a different default cycle time has been installed.
18 Section 6–Replacing Output Modules
2110 Temperature Controller
Section 7—Calibration
Calibration Offset
Calibration offset offsets the displayed value. Usually, this option is used to match displays of two different instruments that are measuring the same temperature, but are displaying different temperatures due to different thermocouple accuracy or placement of the thermocouples. Caution is advised when adding an offset to the display, since the actual sensed temperature will not be displayed.
Calibration offset (coFF) is available in the configuration mode, but only displays if the security lock (LocH) is set to 736.
Factory Default
Recovery
This option allow you to return the controller’s configuration parameters back to the factory default values (except for the LocH menu).
This parameter could be used when moving a unit from one application to another to give the operator an easy place to begin setup of the unit.
Factory Default Recovery is performed in the Configuration Mode, menu dFLt. The security lock (LocH) must be set to 736 to perform a factory default recovery.
To reestablish the factory default values:
1. Disconnect load power.
2. In the Configuration Mode, set security level ( LocH) to 736.
3. Go to menu dFLt and press . The controller will automatically reset the values. When the display cycles from rEdy to donE, the recovery is complete.
Calibration
The Chromalox 2110 Temperature Controller is factory calibrated before shipment. Recalibration is not needed when you receive and install the product. Periodic calibration checks or adjustments should not be necessary under normal operating conditions. Chromalox recommends you recalibrate the controller if all instruments in your facility are periodically calibrated to a known standard.
The 2110 always retains the original factory calibration values for the J, K, and RTD inputs. In an application, only one of these sensor inputs will be used. The 2110 only can retain manual calibration for a single sensor.
Calibration Notes:
Section 7–Calibration 19 continued
Chromalox 2110
Calibration
continued
When calibrating the 2110
1. You must have a sensor simulator to calibrate the 2110 controller.
Substitute a precision sensor simulator (Thermocouple simulator or resistance simulator box) for sensor inputs.
2. Disconnect load power to prevent damage to the process or load.
3. Calibrate RTD inputs using copper (Cu) wire. Calibrate thermocouple inputs using thermocouple extension wire of the same type as the thermocouple you are calibrating.
4. Allow the controller to warm up with the appropriate sensor simulator connected for at least one hour prior to calibration.
5. To access the calibration menu, you need level C (736) security.
Sensor Calibration:
1. Set the 2110 selection switch to RTD or TC. If TC is selected, then set the selection switch to J or K.
2. Connect the sensor simulator to the sensor input terminals.
3. Set the simulator to the low value of the sensor selected J TC
(-100°F), K TC (-100°F), RTD (-200°F or 48.46
W).
4. Go to the CALS parameter on the 2110. The display will toggle between CALS and inLo.
5. Wait 30 seconds for the electronics to fully stabilize. Press .
Dashes will appear in the display while the controller calibrates the low end of span.
6. When the controller prompts inHi in the display, adjust the sensor simulator to the high end of the selected sensor span.
J TC (1400°F), K TC (2400°F), RTD (1000°F or 293.49
W).
7. Wait 30 seconds for the electronics to fully stabilize. Press .
Dashes will appear in the display while the controller calibrates the high end of span. When finished, the controller will display
donE.
8. Calibration is complete.
Factory Calibration
Recovery
This procedure allows you to return the controller to its factory calibration settings in the event it is severely out of calibration due to poor technique or unauthorized calibration.
1. Disconnect load power.
2. Cycle the sensor selection switch twice from its original position (TC or RTD) to the opposite position (RTD or TC) and back to its original position. This brings back the factory calibration and deletes the manual calibration settings.
Chromalox 2110 20 Section 7–Calibration
2110 Temperature Controller
Section 8—Specifications
Control Modes ................................ ON/OFF; PI—Proportional with integral
Control Adjustments
Proportional Band ..................... 1 to sensor span maximum
Automatic Reset ........................ 0.0 to 100.0 repeats/minute
Cycle Time................................. 0.1 to 60.0 seconds
On/Off Deadband ...................... 1° to 100°F or °C
Set Point Upper Limit ................ sensor range °F or °C
Set Point Lower Limit ................ sensor range °F or °C
Output Limit............................... 0 to 100%
Alarm Adjustments
Type ........................................... Absolute High or Low
Set Point .................................... Sensor range °F or °C
Alarm Dead Band ...................... 0° to 100°F or °C
Control/Alarm Outputs
Relay (R1) .................................. 1 Amp Form A, 120/240VAC
Relay (R3) .................................. Form A, 120/240VAC resistive loads at 30 sec. cycle time
20 Amps, 500,000 Operations
15 Amps, 1 Million Operations
10 Amps, 5 Million Operations
5 Amps, 5 Million Operations
Solid State Relay Drive (V0) ....... 24VDC at 40mA
Solid State Relay (S0) ................ 1A Triac, up to 240VAC
Solid State Relay (S1) ................ 5A, up to 240VAC at 40°C
Solid State Relay (S2) ................ 10A, up to 240VAC at 40°C
Alarm ......................................... Form C, Relay 5 Amps at 120VAC,
2.5A at 240VAC
Sensor Input .................................... Switch selectable; J,K Thermocouple; RTD
Input Update Rate .......................... Four samples per second
Input Specifications ....................... Range °F Range °C Accuracy at 77°F ambient
J TC ........................................... -100 to 1400°F -73 to 760°C 0.2% Span +/-1 least significant digit
K TC .......................................... -100 to 2400°F -73 to 1316°C 0.2% Span +/-1 least significant digit
100 W Pt RTD (a=.00385) ........... -200 to 1000°F -128 to 538°C 0.2% Span +/-1 least significant digit
Readout Stability
J and K TC ................................ +/-1°F per 10°F change in ambient temperature
RTD ........................................... +/-0.5°F per 10°F change in ambient temperature
Open Sensor and
Out-of-Range Conditions .............. Displays “SEnS”, Control output 0%
Instrument Power ........................... 90 to 260VAC Less than 10 VA
Operating Environment .................. 0° to 65°C (32° to 150°F)
Dimensions
Overall ....................................... 4.0 x 4.0 x 4.0
inches (102 mm)
Depth Behind Display ................ 3.6 inches (92 mm)
Front Panel Projection ............... 0.4 inches (10 mm)
Panel Cutout.............................. 3.6 x 3.6 inches (92 mm x 92 mm)
Enclosure Material ......................... High temp ABS plastic rated for 0° to 175°F
Front Panel NEMA 4X construction, requires surface finish not rougher than 0.000032 inch
Influence of Line Voltage Variation .. +/-0.1% of sensor span per 10% change in nominal line voltage
Noise Rejection
Common Mode Noise ............... Less than 2°F with 240 VAC, 60 Hz applied from sensor input to earth ground
Series Mode Noise .................... Less than 2°F with 100mV, peak to peak series mode noise
RFI ............................................. Typically less than 0.5% of sensor span at distance of 1 meter (3.1 feet) from a transmitter of 4W at 464MHz
Sensor Leadwire Effect
J Thermocouple ........................ +1°F for 1000 ft. of 18 AWG thermocouple extension wire
K Thermocouple ........................ +2°F for 1000 ft. of 18 AWG thermocouple extension wire
RTD +/-0.1% of sensor span per 20 W balanced leadwire resistance (20 W is the total loop resistance)
Section 8–Specifications 21 Chromalox 2110
Section 9—Troubleshooting
The following Troubleshooting Guide offers simple solutions to common problems and explains the 2110’s Error Messages. Review this section for a possible solution to your problem before contacting Chromalox.
Note: For each symptom, perform correction steps in the order listed.
Symptom
Power applied, display does not light, and controller does not function
Probable Cause
1. No power applied
2. External fuse open
Correction Steps
1. Check power wiring and fusing
2. Power down and repower up
Display alternates between HI and
SENS, 2110 disables control output
Process does not heat up
Erratic operation
1. Open sensor
2. Out of calibration
1. No power being applied to the load
2. Load fuse open
1. Intermittent sensor connections
2. Controller failure
(internal electronics)
3. External electrical noise
1. Check sensor wiring
2. Check selection switches
3. To verify that controller is at fault, remove the thermocouple and place a jumper across the sensor terminals of the 2110. If the display reads approximately ambient, then the sensor is open. Replace the thermocouple.
4. See Section 7–Calibra-
tion
1. Verify Load LED is ON
2. Verify the heater or fuse is not open
3. Verify output limit is set to 100%
4. Verify set point is greater than process temperature
5. Verify output wiring
1. Check sensor wiring or substitute sensor simulator
2. Power down and repower up
3. Contact Chromalox
Chromalox 2110 22 Section 9–Troubleshooting
2110 Temperature Controller
Troubleshooting
continued
Symptom
Process not in control
Instrument continually goes through power-up reset
Probable Cause
1. Incorrect settings
2. Thermocouple
Wiring
1. Severe electrical noise
Correction Steps
1. Check Proportional
Band setting and Automatic Reset setting
2. Check thermocouple polarity
1. Separate sensor wiring from other wiring
2. Apply power line filter
3. Contact Chromalox
Section 9–Troubleshooting 23 Chromalox 2110
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at http://www.chromalox.com/customer-service/policies/termsofsale.aspx.
1347 HEIL QUAKER BLVD., LAVERGNE, TN 37086
Phone: (615) 793-3900 www.chromalox.com
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement