- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Electrical relays
- User manual
advertisement
VOLTMETER
EVM-3 / EVM-3C
Precautions For Installation and Safe Use
Failure to follow those instructions will result in death or serious injury.
Disconnect all power before working on equipment.
When the device is connected to the network, do not remove the front panel.
Do not try to clean the device with solvent or the like. Only clean the device with a dried cloth.
Verify correct terminal connections when wiring.
Electrical equipment should be serviced only by your compedent seller.
Only for rack panel mounting.
No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences arising out of the use of this material.
EVM-3 (Voltmeter) :
EVM-3 is designed for accurate measuring of the AC RMS voltage and for saving the minimum and maximum values of the measured voltages. Minimum and maximum values remain stored in the memory when the power supply is off. This stored values can be read when the power is on. Although EVM-3 is mainly used for electrical panels, this device can also be used with any application in which accurate voltage readings should be done between 10-600V. The measurement (3-4) and power supply (1-2) connections are located on the rear panel and the digital display is centered on the front panel.
EVM-3C (Setpointed Voltmeter) :
EVM-3C has the same functions of the EVM-3. In addition to these functions, an high voltage level and time delay can be set. When the measured voltage is over the high set point value, the output relay is activated at the end of the adjusted time delay, generates an alarm signal and display starts blinking.
Note: If the measurement that the device made or the primary value is over
9999 V, k led on the device is on.
Note: If the voltage on the measurement input of the device is over 600 V or measurement according to the ratio of entered primary/seconder is over 999.000
V, there will be on the display.
Voltage Transformer Ratio: Voltage transformer can regulate the primary and secondary voltage values separately. Primary value can be entered between
1-40.000 and the secondary value can be entered between 1-250.
Note: If the primary and secondary values changed, control the setpoint and hysterisis values. This is important for the device working the way that it was arranged.
Minimum and Maximum Voltage :
The minimum and maximum voltage values are stored. User may read or delete these values. Stored minimum and maximum voltage values remain stored, when the power supply is off.
Setpoint ( s p v e s p ): When the AC current which flows through the device is over the high setpoint value or it is under the low setpoint value, the output relay is switched on in order to generate an error signal at the end of programmed delay time ( The point which is on the below right corner of display blinks). If the AC current value returns within preset limits, before the end of the delay time, the relay resets itself and no tripping occurs.
Latch Function ( ) : Latch function is used to select the output relay operation mode. Either oF or on position may be selected.
At position oF: If the current value returns to preset limits, output relay is switched off.
At position on: Even if the current value returns to preset limits, output relay remains switched on and switches off only by pressing the Set button.
Instant Tripping ( ) : If the AC current value is over the1,5 times of setting value or it is under the 0,5 times of setting value, the output relay is switched on without any delay time. This function is user-selectable.
Setting of Voltage Transformer Primary Voltage Value (for EVM-3C)
SET Press the SET button for 3 sec.
Press UP or DOWN buttons until Prý is displayed.
SET
SET
Press SET button.
Press UP or DOWN buttons until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
0250
0225
Setting of Voltage Transformer Secondary Voltage Value (for EVM-3C)
SET Press the SET button for 3 sec.
Press UP or DOWN buttons until SEC is displayed.
SET
Press SET button.
SET
Press UP or DOWN buttons until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
Setting of High Setpoint Value (for EVM-3C)
SET Press the SET button for 3 sec.
0250
0225
SET
SET
Press UP or DOWN buttons until SP h is displayed.
Press SET button.
Press UP or DOWN buttons until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
250.0
275.0
2
Setting of Low Setpoint Value (for EVM-3C)
SET Press the SET button for 3 sec.
Press UP or DOWN buttons until SP L is displayed.
SET Press SET button.
SET
Press UP or DOWN buttons until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
Setting of Hysteresis Value (for EVM-3C)
SET Press the SET button for 3 sec.
025.0
022.5
Press UP or DOWN buttons until hYS is displayed.
SET Press SET button.
Press UP or DOWN buttons until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
SET Press SET button to save.
Setting of On Time Value (for EVM-3C)
SET Press the SET button for 3 sec.
020.0
Press UP or DOWN buttons until on t is displayed.
SET Press SET button.
Press UP or DOWN buttons until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
SET Press SET button to save.
Setting of Off Time Value (EVM-3C için)
SET Press the SET button for 3 sec.
Press UP or DOWN buttons until oF t is displayed.
SET
Press SET button.
Press UP or DOWN buttons until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
SET Press SET button to save.
Setting of Instant Tripping Function (for EVM-3C)
Set Press the SET button for 3 sec.
Press UP or DOWN buttons until trP is displayed.
Set Press SET button.
Set
Press UP or DOWN buttons until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
Setting of Latch Function (for EVM-3C)
Set Press the SET button for 3 sec.
Press UP or DOWN buttons until LAtC is displayed.
Set Press SET button.
Press UP or DOWN buttons until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Set Press SET button to save.
Displaying and Deleting Tripping Number (for EVM-3C)
Set Press the SET button for 3 sec.
Press UP or DOWN buttons until oP is displayed.
Set
Set
Press SET button.
Press UP button to delete tripping number, else do not press any button.
Press SET button to save.
0002
0000
VOLTMETER
EVM-3 / EVM-3C
Setting of Contact Situation (for EVM-3C)
SET Press the SET button for 3 sec.
Press UP or DOWN buttons until oUt is displayed.
SET
SET
Press SET button.
Press UP or DOWN buttons until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
Escaping the Set Menu (for EVM-3C)
If you do not want to change any adjustment in the menu;
Press UP or DOWN buttons until ESC is displayed.
Set Press the SET button.
c e s c
Displaying Minimum Voltage
Press and hold the DOWN button to see. (for EVM-3C)
Press one time to see the minumum voltage value. (for EVM-3)
Displaying Maximum Voltage
Press and hold the UP button to see. (for EVM-3C)
Press two time to see the maximum voltage value. (for EVM-3)
Deleting the Minimum and Maximum Voltages
Press UP and DOWN buttons at the same time.(for EVM-3C)
Press and hold for two second to delete demands values. (for EVM-3)
If the button is not pressed again within 20 seconds, EVM-3 turns back automatically in measuring mode. (for EVM-3)
The decimal point blinks while the display shows demand values (for EVM-3).
Factory Setting :
Voltage transformer primary voltage value ( )
Voltage transformer secondary voltage value ( )
High set point value ( )
Low set point value ( )
Hysteresis value ( )
On time ( )
Off time ( )
Instant tripping function ( )
Latch function ( )
Contact situation ( )
: 0100
: 0100
: 250.0
: 150.0
: 010.0
: 010.0
: 010.0
: on
: oF
: no (Normaly open)
Connection Diagrams
EVM-3
(72x72)
4 3 2 1
EVM-3
(48x96)
EVM-3
Slim-96
3 4 5 6
4 3 2 1
Ölçüm
Giriþi
L
N
Measuring
Input
L
N
Measuring
Input
Output
Contact
6 5
EVM-3C
(72x72)
4 3 2 1
Output
Contact
Measuring
Input
EVM-3C
(48x96)
6 5 4 3
Output
Contact
Measuring
Input
2 1
EVM-3C
Slim-96
3 4 5
8
6
7
Measuring
Input
L
N
L
N
Warning :
a) A switch or circuit breaker must be connected between the network
and the auxiliary supply input of device.
b) Connected switch or circuit breaker must be in close proximity to the
device.
c) Connected switch or circuit breaker must be marked as the disconnecting device for the equipment.
d) The type of the used fuse must be FF type and the current of the used
fuse must be 1A.
e) No need of a vantilator in the installation area f ) Do not use with generator.
L
N
L
N
Dimensions
72mm
TYPE PR 18 (72x72)
96mm
TYPE PR 25 (96x96)
96mm
TYPE PR 20 (48x96)
The Area Measurements on The Control Panel
Wall Wall Wall
82.5mm
75mm
79.3mm
70mm
63mm
54 mm
50mm
TYPE PR 18 (72x72)
Control Panel Cut Out
50mm
TYPE PR 25 (96x96)
50mm
TYPE PR 20 (48x96)
2
A3986 / Rev.5
66mm
TYPE PR 18 (72x72)
91mm
TYPE PR 25 (96x96)
91mm
TYPE PR 20 (48x96)
Technical Data
Operating Voltage (Un),*
Operating Range(
DU)
Operating Frequency(f)
Accuracy
: Please look at labels on the device.
: 45-65 Hz
: 1% ±1 digit [(%10-%100) full scale]
Measuring Input (Vin) : 10-600 V AC (for EVM-3, EVM-3C)
Power Consumption(Pcons) : <4 VA
Burden : <1 VA (per phase)
Output Contact : 5 A, 250 V, 1250 VA (Resistive) (for EVM-3C)
Voltage Transformer Ratio
Primary
Secondary
Ins. Tripping
Hysteresis
Delay Time
Enclosure
Equipment Protection
: 1-40000 (for EVM-3C)
: 1-250 (for EVM-3C)
: >1.5 x SPH or <0.5 x SPL (for EVM-3C)
: 0-0.5 x Full scale (for EVM-3C)
: 0.0 - 999.9 sec. (for EVM-3C)
: Non-flammable
: Double Insulation ( ),
Ambient Temperature
Degree of Protection
Installations
Measuring CategoryIII
: -5 O C; +50 O C
: IP 40 (Front Panel)
: Flush mounting with rear terminals
Wire Cross section (for terminals): 2.5 mm2
Dimensions : Type PR 18, PR 25, PR 20
Weight : 0.28 kg (for PR 18)
0.30 kg (for PR 25)
0.25 kg (for PR 20)
Packaging Information
Pcs per Package
Package Weight
Pcs per Package
Package Weight
Pcs per Package
Package Weight
: 16 Pcs (for PR 18)
: 4.5 kg
: 12 Pcs (for PR 25)
: 3.6 kg
: 20 Pcs (for PR 20)
: 5 kg
!
* Please check the device label for proper value.
*Different supply voltages are adjustable upon request.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement