FC1008, FC1012
Control units
Conventional
 8 or 12 zones (FD1008-D with 7 zones)
 Compatible with all conventional Siemens detector series
 2 selectable detector line standards for a wide range of detector compatibility
 2 or 6 monitored control lines for sirens, strobe lights etc.
 Programmable alarm organization for manned/unmanned operation
 Alarm verification
 Cross-zoning
 Suitable to collect non-fire related events with non-latching zone option
 Alarm counter
 320 event memory with stamped date and time
 Display of alarm delay countdown
 Simple user controls with isolate/test button per zone
 Key code user access with optional key-switch alternative
 Easy on-site configuration
 Polling facility for service information
 Integral capacity for emergency power of up to 72 h
 Battery 17 Ah (2 x 12 V)
Fire & Security Products
Siemens Building Technologies
System overview
Detector line AlgoRex DS110x
Detector line Synova 600
(non-current limited)
max. 32
Monitored control lines for
- horns, sirens
- beacons
max. 32
Detector line Synova 300
(current limited)
Detector line Synova 300
with line continuity
according to BS 5839 Pt1
Fire controls
- internal relays
- monitored control line
FC10
Remote transmission
- internal contact
- monitored control line
Call point line
Mixed line
(detector/call point with
differentiation)
EX-area
Intrinsically safe detectors
SB3
Linear smoke detector
or flame detector
VdS peripheral devices (DE)
FBF FBF fire brigade operating panel
SD
SD fire key safe
ÜE
ÜE alarm transmitter
DC1192
max. 1
24V
FAT
Fire brigade indication terminal
SST
Interface to connect
3rd party extinguishing control
max. 5
Series MS6/7/9
Non-fire alarm
(technical alarm)
EOL
Detector line termination with three different types, depending on type of control unit.
Line termination STANDARD
Type 1
3k9
Type 2
FCE1003-B
Line termination with line continuity with diode
bases according to British Standard
Type 3
FCE1004-F
Line termination to fulfil VdS 2489
Various types with different features
Types
FC1008-A/-H
FC1008-B
FC1008-C
FC1008-D
FC1008-E
FC1008-F
FC1012-A
FC1012-B
FC1012-C
FC1012-F
Legend
Zones
Control lines
Power supply
Battery size
Zones
8
8
8
7
8
8
12
12
12
12
Control lines
Power supply
Siemens Building Technologies
Fire & Security Products
7-segment
display
2 (+4)
2.5 A
17 Ah
(x)
2 (+4)
2.5 A
17 Ah
(x)
2 (+4)
2.5 A
17 Ah
(x)
2 (+4)
2.5 A
17 Ah *
(x)
2 + 4 (EVAC)
2.5 A
17 Ah
x
2
2.5 A
17 Ah
x
2 (+4)
2.5 A
17 Ah
(x)
2 (+4)
2.5 A
17 Ah
(x)
2 (+4)
2.5 A
17 Ah
(x)
2
2.5 A
17 Ah
x
* if remote transmission card is used, only 7.2 Ah possible
Number of detector lines (zones) for current
limited or non-current limited detectors (selectable per line)
Number of monitored control lines providing
max. 500mA in state alarm, figure in brackets
stands for optional number (FCA1003), state
active programmable (steady/pulsating)
Max. available current on 24 V-side
Max. battery capacity (2 x 12 V) that fits into
the cabinet, left figure stands for 30 h of emergency power operation (* = for 12 h)
2
Battery size
7-segment
display
VdS peripheral
devices
EOL
VdS
EOL
peripheral
devices
Type 1
Type 2
Type 1
Type 1
Type 1
x
Type 3
Type 1
Type 2
Type 1
x
Type 3
(x) = optional
indication module for alarm counter, alarm
delay count-down, clock, event memory, etc.
factory-mounted or available as add-on
(FCA1002)
facility to connect the VdS peripheral devices
(FSB, FAT, SD, ÜE, SST)
type of end-of-line units as shipped with the
control unit (detail see above)
System overview (continued)
The FC1008/12-xx is a compact 8 or 12 zone control unit. The control unit has been
designed to be very simple to use while offering exceptional flexibility via a comprehensive feature list.
Detection
 Each line programmable for current limited or non current limited operation
 Detectors and call points on same line with functional differentiation (where allowed)
 Intrinsically safe detectors via line coupler DC1192 and safety barrier SB3
 Each line programmable for non-latch function and/or technical alarms
Inputs / Outputs
 Dry contacts for general alarm and fault
 2 or 6 monitored control lines 24 V/500 mA for horns, external remote transm., etc.
 1 to 6 fire control relays, rated 10 A/250 V
 Driver output per detector line
 6 common driver control outputs
 6 control inputs (1 programmable)
PMI
 Individual indicator labeling with inscription stripe sets in various languages
 Numeric display for alarm counter, clock, alarm delay count down, event memory
 Individual isolate/test buttons for clear and easy user operation
Commissioning
 Basic functions that can be adapted on-site if required without laptop
 Simple “out of the box” start up with preset default values
 Service function to poll date and time of last test alarm or last configuration change
Types
FC1008-A
FC1008-B
FC1008-C
FC1008-D
FC1008-E
FC1008-F
FC1012-A
FC1012-B
FC1012-C
FC1012-F
Additional
line card
BS
x
x
-
Legend
Additional line card
BS
Door contact
RT isolation card
Door
contact
RT Isolation
card
Fire control
relays
x
x
(x)
(x)
(x)
(x)
(x)
(x)
(x)
(x)
-
(6)
(6)
(6)
(6)
(6)
(6)
(6)
(6)
(6)
(6)
To provide line continuity with diode bases
according to British Standard
Built in door contact to disable remote
transmission Alarm if cover is removed
Optional add-on card (FCA1005-D) to
isolate the remote transmission hardwarewise
3
Siemens Building Technologies
Fire & Security Products
Key
switch
(x)
(x)
x
x
(x)
(x)
(x)
(x)
x
(x)
Special functions
(standard function according to EN 54)
according to British Standard
with Nordic fire key switch (Nordic countries)
PMI with fire brigade terminal (Swiss standard)
with special EVAC control unit (Dutch standard)
with interface for VdS peripherals (German standard)
(standard function according to EN 54)
according to British Standard
with Nordic fire key switch (Nordic countries)
with interface for VdS peripherals (German standard)
(x) = optional
Fire control relays
Key switch
Max. number of optional relay units
(Z3B171) that can be mounted inside the
cabinet
Optional key switch (FCA1007) to provide
operating access instead of access code
Configuration of the control units
FC1008/12-A, FC1008/12-B, FC1008-C
1
3
4
8
9
6
2
5
Basic components
1
Main board
2
Line extension card, with FC1012-x
3
Power supply (70 W)
4
Display module (optional)
5
Control module (optional)
6
Fire control relays (optional)
7
Battery 17 Ah (2 x 12 V)
8
Add-on card for line continuity British Standard (BS), only
FC1008/12-B
9
Key switch Nordic, only FC1008/12-C
7
FC1008-D
FC1008-E
Additional
10 Key switch type
KABA on main
board
11 Battery 7.2 Ah
13
4
12
Additional
12 EVAC control card
13 Power supply
(70 W)
Factory equipped
4
Display module
6
10
11
FC1008/12-F
4
15
16
Additional
14 VdS card
15 RS 232 adapter
card (optional for
FAT)
16 SST interface card
or line extension
card with SST
(optional)
Factory equipped
4
Display module
4
Siemens Building Technologies
Fire & Security Products
Accessories to FC1008/12 (options)
Relay module Z3B171
1 changeover contact 250 VAC/10 A for
the connection of fire control installations such as fire doors.
Accessory for all control unit types.
Display unit FCA1002
To provide alarm counter, clock, 320
event memory, delay countdown.
– Factory equipped with: FC1008-E,
FC1008-F, FC1012-F
– Optional with: FC1008-A/-B/-C/-D,
FC1012-A/-B-C
Quiescent current:
– mains operation 33.5 mA
– battery operation 7.5 mA
Control card FCA1003
To provide 4 additional monitored control lines rated 24 V/500 mA.
Not possible with: FC1008-F, FC1012-F
Quiescent current: 84 mA
Line extension card FCA1004-F
Combined with interface SST (VdS).
Provides 4 additional detection lines
and connecting facility for external
extinguishing control.
Accessory for FC1012-F only
Quiescent current: 42.5 mA
For VdS only
For BS 5839 Pt1 only
For VdS only
Add-on line card FCA1007-B BS
To provide line continuity with diode
bases according to British Standard
BS5839 Pt1. One unit per 2 lines.
Accessory for FC1024-A if used with
FC1008/12-B
Quiescent current: 0 mA
RT-isolation card FCA1005-D
To provide hardware disconnecting
facility for the remote transmission
channels.
RS232 adapter FCA1006-F
to provide connecting facility to FAT
(VdS).
Accessory for FC1008-F, FC1012-F
Quiescent current: 47 mA including FAT
Key switch FCA1007
To provide operating access via key
switch instead of password.
Accessory for all control unit types.
Not possible with
FC1008/12-C, FC1008-D
Battery FA2005-A1
Capacity according to required emergency supply bridging time.
FA2005-A1: 17 Ah
Interface card SST (VdS) FCA1000-FF
To provide connecting facility to external extinguishing control.
Accessory for FC1008-F only.
Quiescent current: 2.5 mA
For VdS only
5
Siemens Building Technologies
Fire & Security Products
Operating panels
FC1008/12-A /-B/ -C (Standard/Great Britain/Nordic countries), 8 or 12 zones, with optional 7-segment display
Legend
1
Access code entry – Separate user and engineer code access.
2
Silence buzzer
3
Acknowledge, Reset
4
Silence, Enable alarm sounders, Manual switching, Manned/Unmanned, alarm delay cancel,
lamp / sounder test, sounder / control disable and disable remote transmission.
5
Optional display providing - Clock / counter – Provides current time, time of switching to unmanned, alarm counter, event memory and remaining alarm delay time.
6
Individual zone test / isolate controls.
FC1008-E (Netherland), 8 zones, with 7-segment display and special evacuation module
FC1008/12-F (Germany), 8 or 12 zones,
with 7-segment display and additional indicators
FC1008-D (Switzerland), 7 zones, with fire brigade control (FBA)
6
Siemens Building Technologies
Fire & Security Products
Technical data
Mains supply voltage
Power consumption
– FC1008/12-A/-B/-C/-D/-F
– FC1008-E
Quiescent current
– FC1008-A/-B/-C/-D
– FC1008-E
– FC1008-F
– FC1012-A/-B/-C
– FC1012-F
Emergency power operating
Outputs
– Dry contact Alarm
– Dry contact Fault
– Fire control relays (optional, 1...6)
– Monitored control lines (2 or 6)
– Driver outputs (14 or 18)
Control inputs (6)
Interfaces
Operating temperature
Storage temperature
Humidity (no condensation permitted)
at T = 25 ±3 °C
at T = 40 ±2 °C
Cabinet
– Dimension (W x H x D)
– Color metal chassis
– Color cover
FC10xx-A/-B/-C/-D/-E/-F
Protection category (IEC 60529)
Standards
Approvals VdS
AC 115/230 V, +10 %/–15 %, 50/60 Hz
25 … 45 VA / optional 20 … 110 VA
20 … 110 VA
125 mA
170 mA
180 mA
155 mA
220 mA
… 12 h / … 30 h / … 72 h
30 V/1 A, NO/NC
30 V/1 A, NO/NC
250 V/10 A, NO/NC
24 V/500 mA
24 V/40 mA
Positive potential via dry contact
VdS peripherals (only FC1008/12-F)
0 ….+50 °C
–20 ….+60 °C
≥95 % rel.
93 % rel.
506 x 378 x 125 mm
grey, ~RAL 9006
white, ~RAL 9003
IP40
EN 54-2, EN 54-4
request
Reference documents
Doc. No. A6V10277145_-Doc. No. A6V10265083_-Doc. No. A6V10265083_CH
Doc. No. A6V10265083_NL
Doc. No. A6V10265083_DE
Doc. No. 007995_--
FC10 2/4 zone
FC1008/12-A/-B/-C
FC1008/12-D
FC1008-E
FC1008/12-F
FC10
Data sheet
Technical manual
Technical manual
Technical manual
Technical manual
Operating manual
7
Siemens Building Technologies
Fire & Security Products
Details for ordering
Type
FC1008-A
FC1008-B
FC1008-C
FC1008-D
FC1008-E
FC1008-F
FC1012-A
FC1012-B
FC1012-C
FC1012-F
Part no
S54380-C4-A1
S54380-C4-A10
S54380-C4-A20
S54380-C4-A30
S54380-C4-A40
S54380-C4-A50
S54380-C5-A1
S54380-C5-A10
S54380-C5-A20
S54380-C5-A30
Designation
Control unit conventional 8 zone
Control unit conventional 8 zone GB
Control unit conventional 8 zone Nordic
Control unit conventional 7 zone CH
Control unit conventional 8 zone NL
Control unit conventional 8 zone DE
Control unit conventional 12 zone
Control unit conventional 12 zone GB
Control unit conventional 12 zone Nordic
Control unit conventional 12 zone DE
Weight
8.200 kg
8.100 kg
8.300 kg
8.300 kg
7.600 kg
8.300 kg
8.350 kg
8.250 kg
8.450 kg
8.500 kg
Accessories
FCA1002
FCA1003
FCA1004-F
FCA1000-FF
FCA1007-B
FCA1005-D
FCA1006-F
FCA1007
Z3B171
FCP1004-E
FA2005-A1
A6E60500021
S54380-C6-A1
A6E60500023
A6E60500055
A6E60500027
A6E60500024
A6E60500025
A6E60500026
4843830001
A6E60500054
A5Q00019677
Display unit
Control card
Line extension card SST
Interface card SST
Add-on line card GB
RT-isolation card
RS232 adapter
Kit key switch standard
Fire control relay
Power supply charger unit 3.5 A
Battery 12 V/17 Ah
0.090 kg
0.137 kg
0.257 kg
0.103 kg
0.003 kg
0.039 kg
0.084 kg
0.175 kg
0.040 kg
0.769 kg
2.481 kg
Inscription stripes shipped
with each control unit
Control unit type
FC1008/12-A
Control units
FC1008/12-B
FC1008/12-C
FC1008-D
FC1008-E
FC1008/12-F
Language of inscription stripes
Czech, Danish, Dutch, English, Flemish, French, German,
Italian, Polish, Portuguese, Spanish, *)
English
Danish, Finnish, Norwegian, Swedish
French, German, Italian
Dutch
German
–
–
–
–
–
–
–
*) Inscription stripes for other languages can be generated using a special Word template (available at
Hotline)
Siemens Switzerland Ltd
Industry Sector
Building Technologies Group
International Headquarters
Fire Safety & Security Products
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724 24 24
www.siemens.com/buildingtechnologies
© 2010 Copyright by
Siemens Building Technologies AG
Data and design subject to change without notice.
Supply subject to availability.
Document no.
A6V10277147_a_en_--
Manual -
Edition
03.2010
Section -