Stratix 6000 Ethernet Managed Switches

Technical Data
Stratix Ethernet Switch Specifications
Stratix 5700 Catalog Numbers 1783-BMS06SL, 1783-BMS06SA, 1783-BMS06TL, 1783-BMS06TA, 1783-BMS06SGL,
1783-BMS06SGA, 1783-BMS06TGL, 1783-BMS06TGA, 1783-BMS10CL, 1783-BMS10CA, 1783-BMS10CGL,1783-BMS10CGA,
1783-BMS10CGP, 1783-BMS10CGN, 1783-BMS20CL, 1783-BMS20CA, 1783-BMS20CGL, 1783-BMS20CGP, 1783-BMS20CGN,
1783-BMS20CGPK
Stratix 8000 and 8300 Catalog Numbers 1783-MS06T, 1783-MS10T, 1783-RMS06T, 1783-RMS10T, 1783-MX04S, 1783-MX08S,
1783-MX08T, 1783-MX08F
Stratix 6000 Catalog Numbers 1783-EMS08T, 1783-EMS04T
Embedded Switch Technology Catalog Numbers 1783-ETAP, 1783-ETAP1F, 1783-ETAP2F
Stratix 2000 Catalog Numbers 1783-US03T01F, 1783-US06T01F, 1783-US05T, 1783-US08T, 1783-US8T
Topic
Page
Stratix 5700 Ethernet Managed Switches
2
Stratix 8000 and Stratix 8300 Ethernet Managed Switches
8
Stratix 6000 Ethernet Managed Switches
15
Embedded Switch Technology
18
Stratix 2000 Ethernet Unmanaged Switches
22
Accessories
26
Additional Resources
27
Stratix Ethernet Switch Specifications
Summary of Changes
This manual contains new and updated information. Changes throughout this revision are marked by change bars, as
shown to the left of this paragraph.
Topic
Page
Corrections to Stratix 5700 alarm relay ratings and power supply requirements
3
Addition of Stratix 8000 and Stratix 8300 expansion modules (cat. nos. 1783-MX04S, 1783-MX08S)
8
Addition of Stratix 2000 switch (cat. no. 1783-US8T)
22
Stratix 5700 Ethernet Managed Switches
Cat. No.
Total Ports
RJ45 Ports(1)
Combo Ports
SFP Slots
Software Type
CIP Sync
(IEEE 1588)
NAT
Conformal
Coating
1783-BMS06SL
6
4 FE
—
2 FE
Lite
—
—
—
1783-BMS06SA
6
4 FE
—
2 FE
Full
—
—
—
1783-BMS06TL
6
6 FE
—
—
Lite
—
—
—
1783-BMS06TA
6
6 FE
—
—
Full
—
—
—
1783-BMS06SGL
6
4 FE
—
2 GE
Lite
—
—
—
1783-BM06SGA
6
4 FE
—
2 GE
Full
—
—
—
1783-BMS06TGL
6
4FE + 2 GE
—
—
Lite
—
—
—
1783-BMS06TGA
6
4 FE + 2 GE
—
—
Full
—
—
—
1783-BMS10CL
10
8 FE
2 FE
—
Lite
—
—
—
1783-BMS10CA
10
8 FE
2 FE
—
Full
—
—
—
1783-BMS10CGL
10
8 FE
2 GE
—
Lite
—
—
—
1783-BMS10CGA
10
8 FE
2 GE
—
Full
—
—
—
1783-BMS10CGP
10
8 FE
2 GE
—
Full
Yes
—
—
1783-BMS10CGN
10
8 FE
2 GE
—
Full
Yes
Yes
—
1783-BMS20CL
20
16 FE
2 FE
2 FE
Lite
—
—
—
1783-BMS20CA
20
16 FE
2 FE
2 FE
Full
—
—
—
1783-BMS20CGL
20
16 FE
2 GE
2 FE
Lite
—
—
—
1783-BMS20CGP
20
16 FE
2 GE
2 FE
Full
Yes
—
—
1783-BMS20CGN
20
16 FE
2 GE
2 FE
Full
Yes
Yes
—
1783-BMS20CGPK
20
16 FE
2 GE
2 FE
Full
Yes
—
Yes
(1) FE = Fast Ethernet; GE = Gigabit Ethernet.
2
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
Stratix Ethernet Switch Specifications
Technical Specifications - Stratix 5700 Switches
1783-BMS10CL,
1783-BMS10CA,
1783-BMS10CGL,
1783-BMS10CGA
1783-BMS10CGN,
1783-BMS10CGP
1783-BMS20CL,
1783-BMS20CA,
1783-BMS20CGL,
1783-BMS20CGP,
1783-BMS20CGN,
1783-BMS20CGPK
Attribute
1783-BMS06SL,
1783-BMS06SA,
1783-BMS06TL,
1783-BMS06TA,
1783-BMS06SGL,
1783-BMS06SGA,
1783-BMS06TGL,
1783-BMS06TGA
Alarm relay ratings
1 A @ 30V DC or 0.5 A @ 48V DC
Power requirements
0.5…2.0 A max @ 12…48V DC
Power consumption
9.5 W @ 24V DC @ 40 °C (104 °F)
15 W max
Isolation voltage
50V (continuous), basic insulation type, DC power ports to ground, DC power ports to Ethernet ports, and DC power ports to alarm ports
No isolation between individual Ethernet ports
No isolation between console port and system
Type tested at 850V DC for 60 s
Ethernet connections
RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to
ISO/IEC 24702
DC power connections
0.5…0.8 mm2 (20…18 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max, 6.3 mm (0.25 in.)
±0.5 mm (0.02 in.) strip length
Alarm connections
0.5…0.8 mm2 (20…18 AWG) solid or stranded, UL/CSA-rated style 1007 or 1569 twisted-pair copper appliance wiring material (AWM) wire (such
as Belden part number 9318), 6.3 mm (0.25 in.) ±0.5 mm (0.02 in.) strip length
Ground connection
4.0 mm2 (12 AWG) min, stranded copper wire
SFP modules(1)
•
•
•
•
Memory card
1784-SD1
Torque
0.23 N•m (2.0 lb•in) on power and alarm connectors
0.96 N•m (8.5 lb•in) max on ground terminals
Weight, approx
1.11 kg (2.45 lb)
Wiring category(2)
3 - on console and alarm ports
2 - on DC power ports
2 - on Ethernet ports
Enclosure type rating
None (open-style)
North American temp code
T4
IEC temp code
T4
0.5…3.0 A max @ 12…48V DC
12.5 W @ 24V DC/40 °C (104 °F)
17 W max
15 W @ 24V DC/40 °C (104 °F)
20 W max
21 W @ 24V DC/40 °C (104 °F)
30 W max
1783-SFP100FX
1783-SFP1GSX
1783-SFP100LX
1783-SFP1GLX
1.25 kg (2.75 lb)
1.38 kg (3.05 lb)
2.04 kg (4.50 lb)
(1) SFP modules supported only on switches with combo ports or SFP slots.
(2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
3
Stratix Ethernet Switch Specifications
Environmental Specifications - Stratix 5700 Switches
4
Attribute
Stratix 5700 Switches
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-40…60 °C (-40…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
55 g
Emissions
CISPR11 (IEC 61000-6-4)
Class A
ESD immunity
IEC 61000-4-2
8 kV contact discharges
15 kV air discharges
Radiated RF immunity
IEC 61000-4-3
20V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz
20V/m with 200 Hz 50% pulse 100% AM at 900 MHz
10V/m with 1 kHz sine-wave 80% AM from 1000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz and ±2 kV at 100 kHz on DC power ports
±4 kV at 2.5 kHz, ±2 kV at 5 kHz, and ±1 kV at 100 kHz on alarm ports
±4 kV at 2.5 kHz, ±2 kV at 5 kHz, and ±1 kV at 100 kHz on Ethernet ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on DC power ports
±2 kV line-earth (CM) on Ethernet ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Voltage variation
IEC 61000-4-29
10 ms interruption on DC supply ports
Damped oscillatory wave immunity
IEC 61000-4-18
±1 kV line-line (DM) and ±2.5 kV line-earth (CM) on power ports
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
Stratix Ethernet Switch Specifications
Certifications - Stratix 5700 Switches
Certifications (when product is
marked)(1)
Stratix 5700 Switches
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
• AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA nC IIC T4X Gc
Korean
Korean Registration of Broadcasting and Communications Equipment, compliant with:
• Article 58-2 of Radio Waves Act, Clause 3
EtherNet/IP
ODVA conformance tested to EtherNet/IP specifications
(1) See the Product Certification link at http://www.ab.com for declarations of conformity, certificates, and other certification details.
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
5
Stratix Ethernet Switch Specifications
Dimensions - Stratix 5700 Switches
To prevent the switch from overheating, observe the following minimum clearances:
• Top and bottom: 105 mm (4.13 in.)
• Exposed side (not connected to the module): 90 mm (3.54 in.)
• Front: 65 mm (2.56 in.)
These diagrams are representative of the Stratix 5700™ switches. Actual faceplates vary depending on the catalog number.
6-port Switches
(1783-BMS06SL, 1783-BMS06SA, 1783-BMS06TL, 1783-BMS06TA,
1783-BMS06SGL, 1783-BMS06SGA, 1783-BMS06TGL,
1783-BMS06TGA)
7.48 cm
(2.94 in.)
10-port Switches
(1783-BMS10CL, 1783-BMS10CA, 1783-BMS10CGL, 1783-BMS10CGA)
9.14 cm
(3.6 in.)
12.95 cm
(5.1 in.)
11.67 cm
(4.59 in.)
10.92 cm
(4.3 in.)
6
12.95 cm
(5.1 in.)
0.75 cm
(0.29 in.)
11.67 cm
(4.59 in.)
10.92 cm
(4.3 in.)
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
0.75 cm
(0.29 in.)
Stratix Ethernet Switch Specifications
10-port Switches
(1783-BMS10CGP, 1783-BMS10CGN)
20-port Switches
(1783-BMS20CL, 1783-BMS20CA, 1783-BMS20CGL, 1783-BMS20CGP,
1783-BMS20CGN, 1783-BMS20CGPK)
9.14 cm
(3.6 in.)
12.7 cm
(5.0 in.)
12.95 cm
(5.1 in.)
13.58 cm
(5.34 in.)
12.83 cm
(5.05 in.)
12.95 cm
(5.1 in.)
0.75 cm
(0.29 in.)
13.58 cm
(5.34 in.)
12.83 cm
(5.05 in.)
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
0.75 cm
(0.29 in.)
7
Stratix Ethernet Switch Specifications
Stratix 8000 and Stratix 8300 Ethernet Managed Switches
Technical Specifications - Stratix 8000 and Stratix 8300 Switches
Attribute
1783-MS06T
1783-MS10T
1783-RMS06T
1783-RMS10T
Description
Stratix 8000™ managed switch,
Layer 2
• 6 ports
Stratix 8000 managed switch,
Layer 2
• 10 ports
Stratix 8300™ managed switch,
Layer 3
• 6 ports
Stratix 8300 managed switch,
Layer 3
• 10 ports
Inrush current, max
2.0 A
Switch input rating, max
2 A max @ 18…60V DC, CL 2/SELV
Alarm relay rating, max
1 A max @ 30V DC, CL 2/SELV
Power dissipation
15.1 W
15.7 W
15.1 W
15.7 W
Isolation voltage
75 V (continuous), basic insulation type, power to ground, power to network channels, and power to alarm
No isolation between individual Ethernet ports
No isolation between console port and system
Type tested at 1000V AC for 60 s
Ethernet connections
RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to
ISO/IEC 24702
DC power and alarm
connections
0.5…0.8 mm2 (20…18 AWG) solid or stranded copper wire rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation max
Functional ground
connection
3.3…5.3 mm2 (12…10 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater
SFP modules(1)
•
•
•
•
Memory card
1783-MCF
Torque
0.23 N•m (2.0 lb•in) on power and alarm connectors
Wiring category(2)
2 - on alarm ports
2 - on power ports
2 - on Ethernet ports
Enclosure type rating
None (open-style)
North American temp code
T4
IEC temp code
T4
1783-SFP100FX
1783-SFP1GSX
1783-SFP100LX
1783-SFP1GLX
1783-RMCF
(1) SFP modules supported only on switches with combo ports or SFP slots.
(2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
8
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
Stratix Ethernet Switch Specifications
Environmental Specifications - Stratix 8000 and Stratix 8300 Switches
Attribute
1783-MS06T, 1783-MS10T, 1783-RMS06T, 1783-RMS10T
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-40…60 °C (-40…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
20 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Emissions
CISPR11 (IEC 61000-6-4)
Class A
ESD immunity
IEC 61000-4-2
8 kV contact discharges
15 kV air discharges
Radiated RF immunity
IEC 61000-4-3
20V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 1000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 2.5 kHz and ±2 kV at 5 kHz on power ports
±4 kV at 2.5 kHz and ±2 kV at 5 kHz on alarm ports
±4 kV at 2.5 kHz and ±2 kV at 5 kHz on Ethernet ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±1 kV line-line (DM) and ±2 kV line-earth (CM) on alarm ports
±2 kV line-earth (CM) on Ethernet ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Magnetic field immunity
IEC 61000-4-8
30 A/m long duration and 300 A/m short duration at 50 and 60 Hz
Magnetic pulse immunity
IEC 61000-4-9
—
Oscillatory surge withstand
IEEE C37.90.1
2.5 kV
Voltage variation
IEC 61000-4-29
10 ms interruption on DC supply ports
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
9
Stratix Ethernet Switch Specifications
Certifications - Stratix 8000 and Stratix 8300 Switches
Certifications (when product is marked)(1)
1783-MS06T, 1783-MS10T, 1783-RMS06T, 1783-RMS10T
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File
E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
• AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA nC IIC T4X Gc
KC
Korean Certification of Broadcasting and Communications Equipment, compliant with:
• Framework Act on Telecommunications and Radio Waves Act
EtherNet/IP
ODVA conformance tested to EtherNet/IP specifications
(1) See the Product Certification link at http://www.ab.com for declarations of conformity, certificates, and other certification details.
Optional Expansion Modules - Stratix 8000 and Stratix 8300 Switches
Cat. No.
Description
1783-MX08T
Expansion module with 8 10/100 Base-T copper Ethernet ports
1783-MX08F
Expansion module with 8 100 Base-F fiber-optic Ethernet ports
1783-MX04S
Expansion module with 4 100 FX fiber-optic SFP slots
1783-MX08S
Expansion module with 8 100 FX fiber-optic SFP slots
Technical Specifications - Stratix 8000 and Stratix 8300 Expansion Modules
Attribute
1783-MX08T
1783-MX08F
1783-MX04S
1783-MX08S
Description
Expansion module
• 8 ports, copper
Expansion module
• 8 ports, fiber
Expansion module
• 4 SFP ports, fiber
Expansion module
• 8 SFP ports, fiber
Backplane power
3.3V DC, 1.7 A max
3.3V DC, 3.6 A max
3.3V DC, 2.5 A max
3.3V DC, 4.0 A max
Power consumption
5.6 W
11.8 W
8.25 W
13.2 W
Isolation voltage
75 V (continuous), basic insulation
type, expansion backplane to
network channels
No isolation between individual
Ethernet ports
Type tested at 1000V AC for 60 s
—
10
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
Stratix Ethernet Switch Specifications
Technical Specifications - Stratix 8000 and Stratix 8300 Expansion Modules
Attribute
1783-MX08T
1783-MX08F
Ethernet connections
RJ45 connector according to IEC
60603-7, 2- or 4-pair Category 5e
minimum cable according to TIA
568-B.1 or Category 5 cable
according to ISO/IEC 24702
—
SFP modules
—
Wiring category(1)
2 - on Ethernet ports
Enclosure type rating
None (open-style)
North American temp code
T4
IEC temp code
T4
1783-MX04S
1783-MX08S
• 1783-SFP100FX
• 1783-SFP100LX
—
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Technical Specifications - Stratix 8000 and Stratix 8300 Fiber Expansion Module
Attribute
1783-MX08F
Ethernet data rate
100 Mbps
Connecting mode
Full duplex
Optical wavelength
1310 nm
Optical cable length, max
Graded index multimode fiber; 2000 m
Optical link budget
8 db with 62.5/125 μm multimode cable
4 db with 50/125 μm multimode cable
Connector type
IEC 61754-20 LC connector
Environmental Specifications - Stratix 8000 and Stratix 8300 Expansion Modules
Attribute
1783-MX08T
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-40…60 °C (-40…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
20 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
1783-MX08F
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
1783-MX04S, 1783-MX08S
15 g
11
Stratix Ethernet Switch Specifications
Environmental Specifications - Stratix 8000 and Stratix 8300 Expansion Modules
Attribute
1783-MX08T
Emissions
CISPR11 (IEC 61000-6-4)
Class A
ESD immunity
IEC 61000-4-2
8 kV contact discharges
15 kV air discharges
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
20V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 1000…2700 MHz
10V/m with 1 kHz sine-wave 80%
AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse
100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse
100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80%
AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 2.5 kHz and ±2 kV at
5 kHz on Ethernet ports
—
Surge transient immunity
IEC 61000-4-5
±2 kV line-earth (CM) on
Ethernet ports
—
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave
80% AM from 150 kHz…80 MHz
—
Magnetic field immunity
IEC 61000-4-8
30 A/m long duration and 300 A/m short duration at 50 and 60 Hz
30 A/m long duration and 300
A/m short duration at 50 Hz
Magnetic pulse immunity
IEC 61000-4-9
—
300 A/m pulse
Oscillatory surge withstand
IEEE C37.90.1
2.5 kV
12
1783-MX08F
—
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
1783-MX04S, 1783-MX08S
Stratix Ethernet Switch Specifications
Certifications - Stratix 8000 and Stratix 8300 Expansion Modules
Certifications (when product is
marked)(1)
1783-MX08T, 1783-MX08F
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
—
1783-MX04S, 1783-MX08S
AEx/Ex nA IIC T4X Gc
CE
European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
• AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA IIC T4X Gc
KC
Korean Certification of Broadcasting and Communications Equipment, compliant with:
• Framework Act on Telecommunications and Radio Waves Act
EtherNet/IP
ODVA conformance tested to EtherNet/IP specifications
(1) See the Product Certification link at http://www.ab.com for declarations of conformity, certificates, and other certification details.
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
13
Stratix Ethernet Switch Specifications
Dimensions - Stratix 8000 and Stratix 8300 Switches
This illustration shows dimensions for the 1783-MS10T switch and the 1783-MX08T expansion module. Dimensions for
the other switches are the same as the 1783-MS10T switch. Dimensions for the other expansion modules are the same as
the 1783-MX08T expansion module.
Switch and Expansion Module
9.71 cm
(3.82 in.)
15.3 cm
(6.03 in.)
Switch and Expansion Module (mated)
24.3 cm
(9.57 in.)
14.8 cm
(5.83 in.)
9.81 cm
(3.87 in.)
33.27 cm
(13.1 in.)
11.1 cm
(4.38 in.)
Switch
(side view)
Switch and Expansion Modules (mated)
11.75 cm
(4.63 in.)
31801-M
For panel-mounting, the height of the center of the mounting holes on both the top and bottom latches
measures 8.73 mm (0.34 in.) above the top surface (or below the bottom surface) of the switch.
On the switch base unit, the tab hole center-to-center spacing is 6.83 cm (2.69 in.).
For expansion modules, the tab hole center-to-center spacing is 4.36 cm (1.72 in.).
Airflow around the switch and through the vents is unrestricted. To prevent the switch from overheating, these minimum
clearances must be met:
• Top and bottom: 105 mm (4.13 in.)
• Left and right: 90 mm (3.54 in.)
• Front: 65 mm (2.56 in.)
14
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
Stratix Ethernet Switch Specifications
Stratix 6000 Ethernet Managed Switches
Technical Specifications - Stratix 6000 Switches
Attribute
1783-EMS08T
1783-EMS04T
Description
Stratix 6000™ managed switch
• 8 ports
• 1 fiber SFP slot
Stratix 6000 managed switch
• 4 ports
Power requirements
250 mA @ 24V DC (12…48V DC) CL 2/SELV
100 mA @ 24V DC (12…48V DC) CL 2/SELV
Power dissipation, max
5.8 W
2.6 W
Thermal dissipation, max
24.6 BTU/hr @ 60 °C (140 °F)
Network ports
8 RJ45 10/100 full/half duplex ports, optional SFP
transceiver port
Protocols
TCP/IP, EtherNet/IP, Telnet, Http, DHCP, BOOTP, FTP, IGMP, SMTP
Indicators
16 port indicators
3 status indicators
EtherNet/IP features
MAC ID management, bandwidth alarming, port control, link status, scaled bandwidth information, and
connections active
Switch features
VLAN, IGMP snooping, IGMP query V1 and V2,
DHCP server, BOOTP server, QoS, port mirroring
Options
1 GB fiber-optic transceiver
Inrush current, max
2.2 A
Isolation voltage
50V (continuous), basic insulation type, power to ground and power to network channels
No isolation between individual network channels
Routine tested at 707V AC for 1 s
Ethernet connections
RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or
Category 5 cable according to ISO/IEC 24702
DC power connections
0.33…3.3 mm2 (22…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.)
insulation max
Functional ground connection
3.3 mm2 (12 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater
SFP modules(1)
• 1783-SFP1GSX
• 1783-SFP1GLX
Torque
1.36 N•m (12 lb•in) on DC power and functional ground
Wiring category(2)
2 - on DC power ports
2 - on Ethernet ports
Enclosure type rating
None (open-style)
North American temp code
T4
IEC temp code
T4
4 RJ45 10/100 full/half duplex ports
8 port indicators
2 status indicators
—
(1) SFP modules supported only on switches with combo ports or SFP slots.
(2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
15
Stratix Ethernet Switch Specifications
Environmental Specifications - Stratix 6000 Switches
Attribute
1783-EMS04T, 1783-EMS08T
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Operating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
15 g
Nonoperating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Emissions
CISPR11 (IEC 61000-6-4)
Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±2 kV at 5 kHz on power ports
±1 kV at 5 kHz on Ethernet ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on DC power ports
±2 kV line-earth (CM) on shielded Ethernet port
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Magnetic field immunity
IEC 61000-4-8
30 A/m long duration and 300A/m short duration at 50 and 60 Hz
Voltage variation
IEC 61000-4-29
10 ms interruption on DC supply ports
16
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
Stratix Ethernet Switch Specifications
Certifications - Stratix 6000 Switches
Certifications (when product is marked)(1)
1783-EMS04T, 1783-EMS08T
c-UL-us
UL Listed Information Technology Equipment, certified for US and Canada. See UL File E151729.
c-ETL-us
ETL Listed Industrial Control Equipment, certified for US and Canada.
ETL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada
CE
European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
• AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• EN 60079-0; General Requirements II 3 G Ex nA nL IIC T4X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
• Article 58-2 of Radio Waves Act, Clause 3
EtherNet/IP
ODVA conformance tested to EtherNet/IP specifications
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Dimensions - Stratix 6000 Switches
52.07 mm
(2.05 in.)
118 mm (4.64 in.)
107 mm (4.21 in.)
12 cm
(0.47 in.)
12 mm
(0.47 in.)
27.7 mm
(1.09 in.)
SFP Module Installed
88.9 mm
(3.50 in.)
Mount the switches, as shown, in the vertical position only. We do not recommend horizontal mounting due to thermal
considerations. Follow these guidelines:
• Provide 50 mm (2 in.) of space on all sides for adequate heat dissipation.
• Leave 100 mm (4 in.) for installation and removal if using the fiber-optic port on the bottom of the 1783-EMS08T
switch.
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
17
Stratix Ethernet Switch Specifications
Embedded Switch Technology
Technical Specifications - EtherNet/IP Taps
Attribute
1783-ETAP
1783-ETAP1F
1783-ETAP2F
Description
EtherNet/IP tap
• 3 copper ports
EtherNet/IP tap
• 2 copper ports
• 1 fiber port
EtherNet/IP tap
• 1 copper port
• 2 fiber ports
Tap type
Copper
Fiber, single-port
Fiber, dual-port
Current consumption, max
125 mA @ 24V DC
200 mA @ 24V DC
260 mA @ 24V DC
DC power supply voltage rating
24V DC (20.4…27.6V DC) CL 2/SELV
Isolation voltage
30V (continuous), basic insulation type, network channels to power and network channels to network channels
Type tested at 1250V DC for 60 s
Type tested at 853V AC for 60 s
Power consumption, max
3W
4.8 W
6.24 W
Power dissipation
3W
4.8 W
6.24 W
Ethernet connections
RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable
according to ISO/IEC 24702
DC power connections
One 0.33…3.3 mm2 (22…12 AWG) or two 0.33…1.3 mm2 (22…16 AWG) solid or stranded copper wire rated at 75 °C (167 °F)
or greater, 1.2 mm (3/64 in.) insulation max
Torque
0.6…0.8 N•m (5…7 lb•in) on power connectors
Wiring category(1)
1 - on power ports
2 - on communication ports
Enclosure type rating
None (open-style)
North American temp code
T5
T4A
T4
IEC temp code
T5
T4
T4
(1)
18
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
Stratix Ethernet Switch Specifications
Technical Specifications - EtherNet/IP Tap Fiber Connections
Attribute
1783-ETAP1F, 1783-ETAP2F
Fiber transceiver type
100Base-FX IEEE802.3u
Optical wavelength
1310 nm no cap
Transmitter launch power at Beginning of Life (BOL), min
Allow -1 dB at End of Life (EOL)
-19 dBm into 62.5/125 μm fiber, N/A = 0.275
-22.5 dBm into 50/125 μm fiber, N/A = 0.20
Receiver sensitivity, min
-31.8 dBm
Receiver sensitivity, max
-14 dBm
Fiber channel power budget at rated BER
(2 connected taps, either 1783-ETAP1F or 1783-ETAP2F)
12.8 dB for 62.5/125 μm multimode fiber
9.3 dB for 50/125 μm multimode fiber
Fiber connections
Glass
62.5/125 μm and 50/125 μm multimode fiber
Simplex or duplex
Jacket type and jacket diameter is dependent on connector selection
Graded Index (GI) fiber
Per IEC 60794-1-1, IEC 60793-2-10 category A1 fibers
Connector type
IEC 61754-20 LC connector, maximum insertion loss 0.75 dB per connection
Channel length, max
2 km (1.24 mi) (1)
(1) The channel, that is, connectors and cable, must not exceed the allowable power budget.
Environmental Specifications - EtherNet/IP Taps
Attribute
1783-ETAP
1783-ETAP1F, 1783-ETAP2F
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-25…70 °C (-13…158 °F)
-25…60 °C (-13…140 °F)
Temperature, surrounding air, max
70° C (158 °F)
60° C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
5 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
50 g
Emissions
CISPR11 (IEC 61000-6-4)
Class A
ESD immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
19
Stratix Ethernet Switch Specifications
Environmental Specifications - EtherNet/IP Taps
Attribute
1783-ETAP
1783-ETAP1F, 1783-ETAP2F
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4
±4 kV at 5 kHz on power ports
±3 kV at 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on communication ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Voltage variation
IEC 61000-4-29
10 ms interruption on DC supply ports
Certifications - EtherNet/IP Taps
Certification(1)
1783-ETAP
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A and B)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection “n”
• EN 60079-0; General Requirements
• II 3 G Ex nA IIC T5 X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
• Article 58-2 of Radio Waves Act, Clause 3
EtherNet/IP
ODVA conformance tested to EtherNet/IP specifications
1783-ETAP1F, 1783-ETAP2F
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection “n”
• EN 60079-0; General Requirements
• II 3 G Ex nA IIC T 4 X
(1) When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
20
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
Stratix Ethernet Switch Specifications
Dimensions - EtherNet/IP Taps
This illustration shows dimensions for the 1783-ETAP tap. The dimensions for the 1783-ETAP1F and 1783-ETAP2F taps
are the same.
122.68 mm
(4.83 in.)
131.57 mm
(5.18 in.)
104.9 mm
(4.13 in.)
35.05 mm
(1.38 in.)
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
21
Stratix Ethernet Switch Specifications
Stratix 2000 Ethernet Unmanaged Switches
Technical Specifications - Stratix 2000 Switches
Attribute
1783-US03T01F
1783-US06T01F
1783-US05T
1783-US08T
1783-US8T
Description
Stratix 2000™
unmanaged switch
• 3 copper ports
• 1 fiber port
Stratix 2000 unmanaged
switch
• 6 copper ports
• 1 fiber port
Stratix 2000 unmanaged
switch
• 5 copper ports
Stratix 2000 unmanaged
switch
• 8 copper ports
Stratix 2000 unmanaged
switch
• 8 copper ports
Inrush current, max
2.2 A
Power supply voltage
20V AC (10…24V AC)
24V DC (10…35V DC)
Isolation voltage
30V (continuous), basic insulation type, power to network channels
No isolation between individual network channels
Type tested at 500V AC for 60 s
Power consumption, max
4 W (6VA)
Current 400 mA @10V DC
Ethernet connections
RJ45 connector according to IEC 60603-7, 2- or 4-pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to
ISO/IEC 24702
DC power connections
1.5…2.5 mm2 (16…14 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater 1.2 mm (3/64 in.)
insulation max
24V (18...60V DC,
18...30V AC 50/60 Hz),
361 mA, Class 2/SELV
4.04 W @ 24V AC/DC
0.75…2.5 mm2
(18…14 AWG)
twisted-pair copper wire
suitable for 30 °C (86 °F)
above surrounding
ambient temperature
outside the enclosure.
Functional Earth
connection:
2.5 mm2 (14 AWG) copper
wire suitable for 86 °F (30
°C) above surrounding
ambient temperature
outside the enclosure,
with a suitable ring
terminal.
Torque, max recommended
0.8 N•m (7 lb•in) on power connectors
1.82 N•m (16 lb•in) on
power /functional earth
connector
Wiring category(1)
2 - on power ports
2 - on communication ports
1 - on power ports
2 - on communication
ports
Enclosure type rating
None (open-style)
North American temp code
T4
T5
IEC temp code
T4
T5
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
22
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
Stratix Ethernet Switch Specifications
Technical Specifications - Stratix 2000 Fiber Connections
Attribute
1783-US03T01F, 1783-US06T01F
Ethernet data rate
100 Mbps
Connecting mode
Full duplex
Optical wavelength
1310 nm
Optical cable length, max
Graded index multimode fiber; 2000 m
Optical link budget
8 db with 62.5/125 μm multimode cable
4 db with 50/125 μm multimode cable
Connector type
IEC 61754-20 LC connector
Fiber connections
Glass
62.5/125 μm and 50/125 μm multimode fiber
Simplex or duplex
Jacket type and jacket diameter is dependent on connector selection
Graded Index (GI) fiber
Per IEC 60794-1-1, IEC 60793-2-10 category A1 fibers
Environmental Specifications - Stratix 2000 Switches
Attribute
1783-US06T01F
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Operating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
15 g
Nonoperating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Emissions
CISPR11 (IEC 61000-6-4)
Class A
ESD immunity
IEC 61000-4-2
4 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
1783-US03T01F,1783-US05T, 1783-US8T
1783-US08T
6 kV contact discharges
8 kV air discharges
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
10V/m with 1 kHz sine-wave
80% AM from 80…2000 MHz
3V/m with 1 kHz sine-wave
80% AM from
2000…2700 MHz
23
Stratix Ethernet Switch Specifications
Environmental Specifications - Stratix 2000 Switches
Attribute
1783-US06T01F
EFT/B immunity
IEC 61000-4-4
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5
±1 kV line-line (DM) and ±2 kV line-earth (CM) on DC power ports ±2 kV line-line (DM) and ±4 kV
line-earth (CM) on DC power
±2 kV line-earth (CM) on communication port
ports
±2 kV line-earth (CM) on
communication port
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Magnetic field immunity
IEC 61000-4-8
—
30 A/m long duration and 300
A/m short duration at 50 Hz
Magnetic pulse immunity
IEC 61000-4-9
—
30 A/m pulse
1783-US03T01F,1783-US05T, 1783-US8T
1783-US08T
±4 kV at 5 kHz on power ports
±3 kV at 5 kHz on
communication ports
Certifications- Stratix 2000 Switches
Certifications (when product is marked)(1)
1783-US03T01F, 1783-US06T01F,
1783-US05T, 1783-US08T
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL
File E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
• AS/NZS CISPR 11; Industrial Emissions
Ex
European Union 94/9/EC ATEX Directive, compliant with:
• EN 60079-15; Potentially Explosive Atmospheres, Protection “n”
• EN 60079-0; General Requirements II 3 G Ex nA IIC T5X Gc
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
• Article 58-2 of Radio Waves Act, Clause 3
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
24
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
1783-US8T
Stratix Ethernet Switch Specifications
Dimensions - Stratix 2000 Switches
1783-US03T01F and 1783-US05T Switch Dimensions
1
P
W
R
2
108 mm (4.25 in.)
TX
4
L
I
N
K
1783-US03T01F
RX
3
127.8 mm
(5.03 in.)
22.5 mm (0.89 in.)
The 1783-US06T01F and 1783-US08T switches have the same depth and height as the switches above, but they are
45 mm (1.77 in.) wide.
1783-US8T Switch Dimensions
53.6 mm
(2.11 in.)
53.6 mm
(2.11 in.)
106.5 mm
(4.19 in.)
PWR
6 mm
(0.24 in.)
7
35 mm
(1.38 in.)
8
5
6
3
4
1
2
1783-US8T
135 mm
(5.31 in.)
32312-M
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
25
Stratix Ethernet Switch Specifications
Accessories
Small Form-factor Pluggable (SFP) Transceivers
Cat. No.
Description
Wavelength
Core Size/
Cladding Size
(micron)
Modal
Bandwidth
(MHz/km)
Cable Length
Compatibility
1783-SFP100FX
100 Base-FX multi-mode transceiver
1310 nm
50/125
500
2 km (6562 ft)
62.5/125
500
Stratix 5700
Stratix 8000
Stratix 8300
1783-SFP100LX
100 Base-LX single-mode transceiver
1310 nm
G.652
—
10 km (32.81 ft)
Stratix 5700
Stratix 8000
Stratix 8300
1783-SFP1GSX
1000 Base-SX multi-mode transceiver
850 nm
62.5/125
160
220 m (722 ft)
62.5/125
200
275 m (902 ft)
50/125
400
500 m (1640 ft)
Stratix 6000
Stratix 5700
Stratix 8000
Stratix 8300
50/125
500
550 m (1804 ft)
G.652
—
10 km (32.81 ft)
1783-SFP1GLX
1000 Base-LX/LH single-mode transceiver
1310 nm
Cat. No.
Description
Compatibility
1784-SD1
1 GB industrial SD card
Stratix 5700
1783-MCF
Stratix 8000 CompactFlash card (spare)
Stratix 8000
1783-RMCF
Stratix 8300 CompactFlash card (spare)
Stratix 8300
Memory Cards
26
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
Stratix 6000
Stratix 5700
Stratix 8000
Stratix 8300
Stratix Ethernet Switch Specifications
Ethernet Cable
Cat. No.
Description
Cable Length
1585J-M8PBJM-2
Unshielded (UTP) RJ45 to RJ45 patchcord
2 m (6.56 ft)
1585J-M8PBJM-5
5 m (16.41 ft)
1585J-M8PBJM-10
10 m (32.81 ft)
1585J-M8CBJM-2
Shielded (STP) RJ45 to RJ45 patchcord
2 m (6.56 ft)
1585J-M8CBJM-5
5 m (16.41 ft)
1585J-M8CBJM-10
10 m (32.81 ft)
1585-C8CB-S100
Unshielded Ethernet cable spool
100 m (328.08 ft)
1585-C8PB-S100
Shielded Ethernet cable spool
100 m (328.08 ft)
1585-C8PB-S300
300 m (984.25 ft)
1585-C8PB-S600
600 m (1, 968.51 ft)
1585J-M8CC-SH
Field attachable connector, IDC
—
For additional Ethernet media choices, see On-Machine™ Connectivity Catalog, publication M117-CA001.
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource
Description
EtherNet/IP Industrial Protocol White Paper, publication ENET-WP001
Describes how to implement services and data objects on a TCP/UDP/IP based
Ethernet network.
Stratix 5700 Ethernet Managed Switch Installation Instructions, publication 1783-IN009
Provides details about installing and configuring the switch.
Stratix 5700 Ethernet Managed Switches User Manual, publication 1783-UM004
Provides detailed information on configuring and managing the switches.
Stratix 8000 and 8300 Ethernet Managed Switches User Manual, publication 1783-UM003
Provides detailed information on configuring and managing the switches.
Stratix 6000 Ethernet Managed Switch User Manual, publication 1783-UM001
Provides details about how to configure and use the switch.
Stratix 2000 Ethernet Unmanaged Switch Installation Instructions, publication 1783-IN001
Provides details about installing and configuring the switch.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation® industrial system.
Product Certifications website, http://www.ab.com
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Rockwell Automation Publication 1783-TD001D-EN-P - June 2013
27
Important Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this publication are included solely for illustrative purposes. Because of the many variables
and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Allen-Bradley, Rockwell Software, Rockwell Automation, LISTEN.THINK.SOLVE., On-Machine, Stratix 2000, Stratix 5700, Stratix 6000, Stratix 8000, and Stratix 8300 are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
www.rockwel lautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Publication 1783-TD001D-EN-P - June 2013
Supersedes Publication 1783-TD001C-EN-P - December 2012
Copyright © 2013 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.