ModPac™ II 1 to 5-Ton Vertical
Wall Mount Air Conditioners
Models AVPA12-20-24-30-36-42-48-60
General Description
The Marvair® ModPac™ II air conditioner
is a vertical, wall mounted, cost effective air
conditioner designed specifically for the modular
and relocatable building. The unit is manufactured
in eight sizes from 1 to 5 tons for a variety of
building types and applications. Electric heat
may be field or factory installed. Disconnects
are standard on all units including the 460v.
models. Accessories include a full range of grilles
and thermostats. Cabinet color choices include
standard Marvair beige and grey as well as other
options. A Marvair first, the built-in mounting
flanges simplifies installation. The sloped top,
another Marvair original, eliminates the need for a
rainhood.
Safety Listed & Energy Certified
All ModPac air conditioners are built to UL
standard 1995, 2nd edition and CAN/CSA C22,
No. 236-5, 2nd edition. For energy efficiency and
performance, the units are tested and rated in accordance to
the ANSI/ARI (Air-Conditioning and Refrigeration Institute)
Standard 390- 2003 (Single Package Vertical Units). All
AVPA units meet or exceed the efficiency requirements of ANSI/ASHRAE/IESNA
90.1.2007. The ModPac air conditioners are commercial units and are not intended
for use in residential applications.
Standard Features
Ease of Installation
•Factory installed disconnect may
eliminate need of outside disconnect.
•Built-in mounting flanges eliminate
need for side brackets.
•Sloped top sheds water and
minimizes chance of water leaks.
•Designed for installation in a modular
builder's facility.
Attractive and Built for Long Term
Operation
•Choice of colors - beige, white, grey,
light brown.
•Decorative coil guard.
•High efficiency compressors provide
reliable and quiet operation.
Ventilation Options
•Manual damper capable of up to
15% of rated air flow of outside air.
Field adjustable, no pressure relief.
(Standard, “N” Damper - AVPA12-60)
•Motorized, two position damper (open
and closed) capable of 0 to 450 cfm
of outside air and includes pressure
relief. A 24-volt actuator motor
controls the damper from an external
input such as a time clock, CO2
sensor, energy management system
or manual switch. (“B” Damper AVPA30-60)
1
PDS 84/2012 Rev. 8
ModPac II PDS ModPac
4/2012 rev.
Standard Features (continued)
Ease of Service
•Service access valves.
•All components accessible for field service.
•Nationwide network of service centers.
Quiet
•Twin blowers sized to accept full duct system.
•High and low refrigerant switches
•High density, foil backed insulation complies
with codes that require a cleanable surface
for the indoor air path.
M5 Configuration
The M5 configuration of the ModPac II air conditioner features the following as standard.
PC Board
The internal control board in the M5 configuration simplifies wiring, consolidates several of the
electrical functions onto one device and improves the reliability of the air conditioner. In addition,
the control board has LED’s that indicate operational status and fault conditions.
LED Indicator Lights
COLOR
TYPE
Green
Power
Red
Status
STATUS
DESCRIPTION
Constant On
24 VAC power has been applied
Constant On
Normal Operation
1 Blink
High pressure switch has opened twice
2 Blinks
Low pressure switch has opened twice
3 Blinks
Freeze stat (optional) - indoor coil temperature is below 35°F (1°C)
Modes of Operation
Normal Start-up: On a call for cooling, and the with the high pressure switch closed, the cooling
system
(compressor, indoor blower motor and outdoor fan motor) will be energized. (Note: See the Delay
on Make feature). The cooling system will remain energized during the three minute low pressure
switch bypass cycle. If the low pressure is closed, the cooling system will continue to operate after
the three-minute bypass. If the low pressure switch is open after the three-minute bypass, the
cooling system will be de-energized.
Lockout Mode: If either the high or low pressure switch opens twice on the same call for cooling,
the control board enters into the lockout mode. In the lockout mode, the compressor is turned off,
the alarm output is energized and the status LED’s will blink to indicate which fault has occurred.
If there is a call for air flow, the indoor blower will remain energized. When the lockout condition
has cleared, the unit will reset if the demand of the thermostat is removed or when power is reset.
The lockout circuit is factory wired for normally open contacts. The user can now have normally
closed contacts by moving a wire on the control board.
Delay on Make: On initial power up or on resumption of power, the air conditioner will wait .03 to
10 minutes from a call for cooling before allowing the contactor to energize.
In addition to the PC board, the M5 configuration has high and low refrigerant pressure switches
and foil backed insulation lines the indoor air path. A low ambient fan cycle control is available as
an option.
Accessories
Supply Grilles
For
For
For
For
AVPA12
AVPA20,24
AVPA30,36
AVPA42,48,60
ModPac PDS 4/2012 Rev. 8
17" x 5"
20” x 8”
28” x 8”
30” x 10”
P/N
P/N
P/N
P/N
Return Grilles
80682
80674
80675
80676
For
For
For
For
2
AVPA12
AVPA20,24
AVPA30,36
AVPA42,48,60
17" x 10"
20” x 12”
28” x 14”
30” x 16”
P/N
P/N
P/N
P/N
92352
80677
80678
80679
Return Filter Grilles
Used when filter must be changed from the interior. Also reduces sound level.
For AVPA12
17" x 10" P/N 80683
For AVPA20,24
20” x 12” P/N 80671
For AVPA30,36
28” x 14” P/N 80672
For AVPA42,48,60 30” x 16” P/N 80673
Thermostats
Thermostat, P/N 50121
Digital thermostat. 1 stage heat, 1 stage cool. Non-programmable. Fan switch: Auto & On.
Manual changeover system switch: Cool-Off-Heat. Low temperature protection. °F or °C selectable.
Thermostat, P/N 50123
Digital thermostat. 1 stage heat, 1 stage cool. 7 day programmable. Fan switch: Auto & On.
Auto-changeover. Keypad lockout. Non-volatile program memory. Title 24 compliant - no batteries
needed.
Thermostat, P/N 50218
Digital, non-programmable thermostat. One stage cool/One stage heat. Manual or auto
changeover. Fan mode: Auto or On. Permanent retention of settings upon power loss. Field
adjustable temperature calibration. Max heat and minimum cool set points. Adjustable temperature
differential. Remote sensor capable. Keypad lock out. Status LED. °F or °C selectable.
Thermostat, P/N 50246
Non-programmable, single stage heat, single stage cool. Manual changeover. Fan: Auto & On. 60
minute power back-up.
Thermostat, P/N 50289
Programmable 2-stage heat, 2-stage cool. System settings: Heat, Cool, Off, Auto-changeover. Fan
Auto & ON. 3-hour override and button lockout to prevent tampering.
Thermostat Guard, P/N 50092
For use with 50121, 50123 thermostats.
Choice of Colors
Beige is standard color with grey, white and light brown available.
Outside Air Ventilation Schedule
Designator
N
B
Outside Air
0 to 15% of Rated Air Flow
0 to 450 cfm
Pressure Relief Damper
No
Manual
Yes
Motorized
Model Identification
AVP A
A = R410
Refrigerant
Air Source
Vertical Package
•
AC •
• • •
M5
• •
•••
Nominal Cooling
Power Supply
Configuration
Special Option Code
12
20
24
30
36
42
48
60
A =208/230V,1ø,60Hz
M5 =PC Board &
Square Cornered
Cabinet
U = Scroll Compressor
A1 = PC Board
= 12,000
= 20,000
= 24,000
= 29,000
= 35,000
= 42,000
= 46,500
= 56,000
BTUH
BTUH
BTUH
BTUH
BTUH
BTUH
BTUH
BTUH
C =208/230V,3ø,60Hz
D =460V,3ø,60Hz
System Type
Air Conditioner
Electric Heat – kW
000 = No Heat
080
036 = 3.6 kW
090
040 = 4 kW
100
050 = 5 kW
120
060 = 6 kW
150
3
=
=
=
=
=
8 kW
9 kW
10 kW
12 kW
15 kW
Ventilation Code
Color Code
N = 0-15% fresh air with manual
damper, no pressure relief)
All Models
100
200
300
400
B = Motorized two position damper
(open & closed) capable of
0 to 450 cfm (up to 40%
of rated air flow) of outside
air, includes pressure relief)
Models AVPA30-60 only
= Beige (std)
= Grey
= Brown
= White
ModPac PDS 4/2012 Rev. 8
Certified Efficiency and Capacity Ratings at ANSI/AHRI
Standard 390 - AVPA Air Conditioners
Model Number
AVP12
AVP20
AVPA24
AVPA30
AVPA36
AVPA42
AVPA48
AVPA60
ACA
ACA
10,800
19,600
24,000
29,000
35,000
42,000
46,500
EER2
9.00
9.00
9.25
9.25
9.25
9.25
9.50
9.25
Rated Air Flow (CFM3)
400
735
840
1,000
1,220
1,575
1,760
1,850
Cooling BTUH1
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD
54,500
1
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
3
EER=Energy Efficiency Ratio
CFM=Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage from that of the rating
point will affect performance and air flow.
2
Sensible Total Heat Ratio @ 95ºF (35ºC)
Outside Air Dry Bulb - AVPA Air Conditioners
Model Number
Total Capacity
AVPA12 AVPA20
ACA
ACA
10,800
19,600
AVPA24
AVPA30
AVPA36
AVPA42
AVPA48
AVPA60
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD
24,000
29,000
35,000
42,000
46,500
54,500
Sensible Heat Ratio
0.74
0.76
0.71
0.75
0.69
0.75
0.76
0.72
Sensible Capacity
7,982
14,837
16,950
21,740
24,155
31,640
35,125
39,000
400
735
840
1,000
1,220
1,575
1,760
1,850
Rated Air Flow (CFM1)
1
CFM=Cubic Feet per Minute. Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C
DB/19.5°C WB) return air.
Cooling Performance (BTUH) at Various Outdoor Temperatures AVPA Air Conditioners
Outdoor Temperature
Model Number
75ºF /
24ºC
80ºF /
26.5ºC
85ºF /
29ºC
90ºF /
32ºC
95ºF /
35ºC
100ºF /
38ºC
105ºF /
40.5ºC
110ºF /
43.3ºC
115ºF /
46ºC
AVPA12AC
12,530
12,100
11,660
11,230
10,800
10,370
9,940
9,500
9,290
AVPA20AC
22,740
21,950
21,170
20,380
19,600
18,820
18,030
17,250
16,860
AVPA24AC
27,840
26,880
25,920
24,960
24,000
23,040
22,080
21,120
20,640
AVPA30AC
33,640
32,480
31,320
30,160
29,000
27,840
26,680
25,520
24,940
AVPA36AC
40,600
39,200
37,800
36,400
35,000
33,600
32,200
30,800
30,100
AVPA42AC
48,720
47,040
45,360
43,680
42,000
40,320
38,640
36,960
36,120
AVPA48AC
53,940
52,080
50,220
48,360
46,500
44,640
42,780
40,920
39,900
AVPA60AC
63,220
61,040
58,860
56,680
54,500
52,320
50,140
47,960
46,870
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
ModPac PDS 4/2012 Rev. 8
4
Electrical Characteristics - Compressor, Fan & Blower Motors AVPA Air Conditioner
COMPRESSOR
OUTDOOR FAN MOTOR
INDOOR FAN MOTOR
BASIC
MODEL
Type
VOLTS-HZ-PH
RLA1
LRA2
VOLTS-HZ-PH
RPM3
FLA4
HP5
VOLTS-HZ-PH
RPM3
FLA4
HP5
AVPA12ACA
ROTARY
208/230-60-1
4.7
25.0
208/230-60-1
1630
0.65
1/6
208/230-60-1
1650
0.85
1/5
AVPA20ACA
208/230-60-1
8.3
43.0
208/230-60-1
1075
1.5
1/5
208/230-60-1
1075
1.5
1/5
AVPA24ACA
208/230-60-1
12.8
54.0
208/230-60-1
1075
1.5
1/5
208/230-60-1
1075
1.5
1/5
AVPA30ACA
208/230-60-1
14.1
74.0
208/230-60-1
1075
1.8
1/4
208/230-60-1
1075
2.5
1/4
208/230-60-1
17.9
84.0
208/230-60-1
1075
1.8
1/4
208/230-60-1
1075
2.5
1/4
AVPA42ACA
208/230-60-1
19.8
84.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
3.1
1/2
AVPA48ACA
208/230-60-1
21.8
102.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
3.1
1/2
AVPA60ACA
208/230-60-1
26.2
130.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
5.2
3/4
AVPA24ACA
208/230-60-1
12.8
64.0
208/230-60-1
1075
1.5
1/5
208/230-60-1
1075
1.5
1/5
AVPA30ACA
208/230-60-1
14.1
77.0
208/230-60-1
1075
1.8
1/4
208/230-60-1
1075
2.5
1/4
AVPA36ACA
208/230-60-1
17.9
112.0
208/230-60-1
1075
1.8
1/4
208/230-60-1
1075
2.5
1/4
208/230-60-1
19.8
109.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
3.1
1/2
AVPA48ACA
208/230-60-1
21.8
117.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
3.1
1/2
AVPA60ACA
208/230-60-1
26.2
134.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
5.2
3/4
AVPA24ACC
208/230-60-3
8.3
61.0
208/230-60-1
1075
1.5
1/5
208/230-60-1
1075
1.5
1/5
AVPA30ACC
208/230-60-3
9.0
71.0
208/230-60-1
1075
1.8
1/4
208/230-60-1
1075
2.5
1/4
AVPA36ACC
208/230-60-3
13.2
88.0
208/230-60-1
1075
1.8
1/4
208/230-60-1
1075
2.5
1/4
208/230-60-3
13.6
83.1
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
3.1
1/2
AVPA48ACC
208/230-60-3
13.7
83.1
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
3.1
1/2
AVPA60ACC
208/230-60-3
15.6
111.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
5.2
3/4
AVPA24ACD
460-60-3
5.1
28.0
208/230-60-1
1075
1.5
1/5
208/230-60-1
1075
1.5
1/5
AVPA30ACD
460-60-3
5.6
38.0
208/230-60-1
1075
1.8
1/4
208/230-60-1
1075
2.5
1/4
AVPA36ACD
460-60-3
6.0
44.0
208/230-60-1
1075
1.8
1/4
208/230-60-1
1075
2.5
1/4
460-60-3
6.1
41.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
3.1
1/2
AVPA48ACD
460-60-3
6.2
41.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
3.1
1/2
AVPA60ACD
460-60-3
7.7
52.0
208/230-60-1
825
2.8
1/3
208/230-60-1
1075
5.2
3/4
AVPA36ACA
RECIPROCATING
SCROLL
AVPA42ACA
SCROLL
AVPA42ACC
SCROLL
AVPA42ACD
1
2
3
RLA = Rated Load Amps
LRA = Locked Rotor Amps
RPM = Revolutions per Minute
The 460 volt units will have a step down transformer for the 230 volt motors.
4
FLA = Full Load Amps
5
HP = Horsepower
Summary Electrical Ratings (Wire Sizing) - AVPA Air Conditioners
Manual Ventilation Damper (“N”) or Motorized Ventilation Damper (“B”)
ELECTRIC HEAT
BASIC
MODEL
000 = None
036 = 3.6 kw
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
150 = 15 kw
CKT #1
CKT #1
CKT #1
CKT #1
CKT #1
CKT #1
CKT #1
CKT #1
CKT #1
CKT #2
CKT #1
CKT #2
VOLTAGE
PHASE / HZ MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2
AVPA12ACA
208/230-1-60
7.4
15
26.9
30
AVPA20ACA
208/230-1-60
13.4
25
19.6
20
22.4
25
27.5
30
32.8
35
43.1
45
53.6
60
AVPA24ACA
208/230-1-60
19.0
30
22.4
30
27.5
30
32.8
35
43.1
45
53.6
60
AVPA30ACA
208/230-1-60
21.9
35
23.4
35
28.5
35
33.8
35
44.1
45
54.6
60
23.4
35
41.6
45
28.5
35
52.1
60
AVPA36ACA
208/230-1-60
26.7
40
26.7
40
28.5
40
33.8
40
44.1
45
54.6
60
26.7
40
41.6
45
28.5
40
52.1
60
AVPA42ACA
208/230-1-60
30.7
50
30.7
50
55.2
60
30.7
50
41.6
45
30.7
50
52.1
60
AVPA48ACA
208/230-1-60
33.2
50
33.2
50
55.2
60
33.2
50
41.6
45
33.2
50
52.1
60
AVPA60ACA
208/230-1-60
40.8
60
40.8
60
57.3
60
40.8
60
41.6
45
40.8
60
52.1
60
AVPA24ACC
208/230-3-60
13.4
20
19.5
20
28.6
30
37.6
40
AVPA30ACC
208/230-3-60
15.6
20
20.5
25
29.6
30
38.6
40
47.6
50
AVPA36ACC
208/230-3-60
20.8
30
20.8
30
29.6
30
38.6
40
47.6
50
AVPA42ACC
208/230-3-60
22.9
35
22.9
35
30.2
35
39.2
40
48.2
50
AVPA48ACC
208/230-3-60
23.0
35
23.0
35
30.2
35
39.2
40
48.2
50
AVPA60ACC
208/230-3-60
27.5
40
27.5
40
32.3
40
41.3
45
50.3
60
AVPA24ACD
460-3-60
7.9
15
9.8
15
14.3
15
18.8
20
23.3
25
AVPA30ACD
460-3-60
9.2
15
10.3
15
14.8
15
19.3
20
23.8
25
AVPA36ACD
460-3-60
9.7
15
10.3
15
14.8
15
19.3
20
23.8
25
AVPA42ACD
460-3-60
10.6
15
10.6
15
15.1
20
19.6
20
24.1
25
AVPA48ACD
460-3-60
10.7
15
10.6
15
15.1
20
19.6
20
24.1
25
AVPA60ACD
460-3-60
13.6
20
13.6
20
16.1
20
20.6
25
25.1
30
1
2
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse Size or HACR Breaker
This chart should only be used as a guideline for estimating conductor size and overcurrent protection. Always refer to the data label on the unit for the requirements of the specific
unit. MCA & MFS are calculated at 230v. for the 208-230v units (A & C models) and at 460 volt for the 460v. units (D models).
The 460 v. units (D models) have a step down transformer for the 230v. motors.
5
ModPac PDS 4/2012 Rev. 8
Unit Load Amps - AVPA Air Conditioner
CURRENT
AMPS
LOAD OF RESISTIVE HEATING ELEMENTS ONLY (AMPS)
AC1
IBM2
3.6
kW
208/230-1-60
6.1
0.85
15.0
208/230-1-60
11.3
1.5
16.7
20.8
25.0
33.3
41.7
18.2
22.3
26.5
34.8
43.2
AVPA24ACA
208/230-1-60
15.8
1.5
16.7
20.8
25.0
33.3
41.7
18.2
22.3
26.5
34.8
43.2
AVPA30ACA
208/230-1-60
18.4
2.5
16.7
20.8
25.0
33.3
41.7
50.0
62.5
19.2
23.3
27.5
35.8
44.2
52.5
65.0
AVPA36ACA
208/230-1-60
22.2
2.5
16.7
20.8
25.0
33.3
41.7
50.0
62.5
19.2
23.3
27.5
35.8
44.2
52.5
65.0
AVPA42ACA
208/230-1-60
25.7
3.1
20.8
41.7
50.0
62.5
23.9
44.8
53.1
65.6
AVPA48ACA
208/230-1-60
27.7
3.1
20.8
41.7
50.0
62.5
23.9
44.8
53.1
65.6
AVPA60ACA
208/230-1-60
34.2
5.2
20.8
41.7
50.0
62.5
26.0
46.9
55.2
67.7
AVPA24ACC
208/230-3-60
11.2
1.5
14.4
21.7
28.9
36.1
15.9
23.2
30.4
37.6
AVPA30ACC
208/230-3-60
13.3
2.5
14.4
21.7
28.9
36.1
16.9
24.2
31.4
38.6
AVPA36ACC
208/230-3-60
17.5
2.5
14.4
21.7
28.9
36.1
16.9
24.2
31.4
38.6
AVPA42ACC
208/230-3-60
19.5
3.1
14.4
21.7
28.9
36.1
17.5
24.8
32.0
39.2
AVPA48ACC
208/230-3-60
19.6
3.1
14.4
21.7
28.9
36.1
17.5
24.8
32.0
39.2
AVPA60ACC
208/230-3-60
23.6
5.2
14.4
21.7
28.9
36.1
19.6
26.9
34.1
41.3
AVPA24ACD
460-3-60
6.6
0.8
7.2
10.8
14.4
18.0
8.0
11.6
15.2
18.8
AVPA30ACD
460-3-60
7.8
1.3
7.2
10.8
14.4
18.0
8.5
12.1
15.7
19.3
AVPA36ACD
460-3-60
8.2
1.3
7.2
10.8
14.4
18.0
8.5
12.1
15.7
19.3
AVPA42ACD
460-3-60
9.1
1.6
7.2
10.8
14.4
18.0
8.8
12.4
16.0
19.6
AVPA48ACD
460-3-60
9.2
1.6
7.2
10.8
14.4
18.0
8.8
12.4
16.0
19.6
AVPA60ACD
460-3-60
11.7
2.6
7.2
10.8
14.4
18.0
9.8
13.4
17.0
20.6
BASIC
MODEL
NUMBER
VOLTAGE
PHASE / HZ
AVPA12ACA
AVPA20ACA
TOTAL MAXIMUM HEATING AMPS (STANDARD UNIT)
3.6
Kw
04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW
20.8
04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
15.9
21.7
2
1
AC = Air Conditioner
IBM = Indoor Blower Motor
Heating kW rated at 240v. for 208-230v. units (A & C models). Derate heat by 25% for operation on 208v. Heating kW rated at 480v. for 460v. units (D models). Total heating
amps for all 1ø units with 15 kW of heat includes both circuits (#1 & #2). Note: 3ø units contain 1ø motor loads. Values shown are maximum phase loads. Loads are not equally
balanced on each phase. Total maximum heating and cooling amps include motor loads.
CFM1 vs. External Static Pressure (Wet Coil)
0.10
0.20
0.25
0.3
0.4
0.5
AVPA12
MODEL
500
460
430
400
n/a
n/a
AVPA20
860
810
740
670
n/a
n/a
AVPA24
860
810
740
670
n/a
n/a
AVPA30
1,100
1,000
960
920
810
n/a
AVPA36
1,310
1,220
1,185
1,150
1,060
n/a
AVPA42
n/a
1,650
1,585
1,520
1,450
1,360
AVPA48
n/a
1,900
1,830
1,760
1,700
1,620
AVPA60
n/a
1,900
1,830
1,760
1,700
1,620
1
CFM=Cubic Feet per Minute. Air flow ratings are at 230 volts. Operation of units at a different voltage will affect air flow.
Filter Size
MODEL
AVPA12
AVPA20/24
AVPA30/36
AVPA42/48/60
FILTER SIZE (inches)
20 x 10 x 1
25 x 16 x 1
30 x 16 x 1
36-1/2 x 22 x 1
Filter Part Number
91913
80135
80136
80139
Ship Weights
Ventilation configuration
AVPA12
AVPA20-24
AVPA30-36
AVPA42
AVPA48
AVPA60
Lbs
Kg
Lbs
Kg
Lbs
Kg
Lbs
Kg
Lbs
Kg
Lbs
Kg
Ventilation configuration “N”
180
81.8
280
127.27
350
159.09
485
220.45
510
231.82
522
237.27
Ventilation configuration “B”
N/A
N/A
N/A
N/A
365
165.91
527
239.55
552
250.91
565
256.82
ModPac PDS 4/2012 Rev. 8
6
Dimensional Data – AVPA12 ModPac™ II
Air Conditioner (M5 Configuration)
7
ModPac PDS 4/2012 Rev. 8
Dimensional Data – AVPA20-24 ModPac™ II
Air Conditioner (M5 Configuration)
ModPac PDS 4/2012 Rev. 8
8
Dimensional Data – AVPA30-36 ModPac™ II Air Conditioner
9
ModPac PDS 4/2012 Rev. 8
1 21
[38]
84 21
[2146]
ModPac PDS 4/2012 Rev. 8
10
RH SIDE VIEW
11
22 16
[577]
AIR
INLET
3/4" X 1"
ELECTRICAL
K.O.'S
86
[2184]
7
116
[37]
4 43
[120]
FRONT VIEW
42
[1067]
AIR
OUTLET
FRESH AIR
SLOTS
BREAKER
ACCESS
COVER
C. TO C. MOUNTING HOLES
43 21
[1105]
6
[152]
19 43
[502]
41 21
[1054]
5
83 16
[2116]
19 43
[502]
.375Ø (6 PLC'S)
AVPA42-60
BOTTOM MOUNTING BRACKET
18
[457]
18
[457]
18
[457]
18
[457]
3/8" SQ
10 PLACES
9
40 16
[1030]
DIMENSIONS
AVPA42-60 ModPac II Air Conditioner
15
8
[41]
37
8
[98]
RH SIDE VIEW
AIR
INLET
5
116
[33]
3/4" X 1"
ELECTRICAL
K.O.'S
HEATER
ACCESS
COVER
COMPRESSOR
ACCESS
9
38 16
[979]
3
116
[30]
1 81
[28]
3°
3
30 8
[772]
CONDENSATE
DRAIN, 3/4"
3
32 8
[822]
2 43
[71]
BACK VIEW
RETURN AIR
OPENING
30 X 16
BOTH SIDES
ELECTRICAL K.O.'S
3/4" X 1"
SUPPLY AIR
OPENING
30 X 10
45
[1143]
29 7
8
[759]
2 43
[71]
11
26 16
[678]
15 43
[400]
30
[762]
97
8
[251]
2 1/8
[55]
Dimensional Data – AVPA42-60 ModPac™ II Air Conditioner
Notes
11
ModPac PDS 4/2012 Rev. 8
Notes
Please consult the Marvair® website at www.marvair.com for the latest product literature. Detailed dimensional data
is available upon request. A complete warranty statement can be found in each product’s Installation/Operation
Manual, on our website or by contacting Marvair at 229-273-3636. As part of the Marvair continuous improvement
program, specifications are subject to change without notice.
P.O. Box 400 • Cordele, GA 31010
156 Seedling Drive • Cordele, GA 31015
Ph: 229-273-3636 • Fax: 229-273-5154
Email: marvair@airxcel.com • Internet: www.marvair.com
ModPac PDS 4/2012 Rev. 8
12