advertisement
▼
Scroll to page 2
of 206
for heating engineers VitocalĂ300 typeĂAW, BW and WW See notes on applicability, pageĂ3. VITOCAL 300 Vitocal 300, type AW Vitocal 300, type BW and WW Please keep safe Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. )#" *( +% " %%,% ( -.&%*! %&"% !!"$( &(#"& !#" ' & &% ( /%!!" #"& -%% " % -% !( 01&"# !%"!!" !"!-( /&-.*! "-%"(2% & !%"" *%!" &%"(3&%% !!-%"" !!"!"( 2 Repairs ! "! !%"( 4"&,! !*!%% #!! #",( Initial start-up 5%# #"% "& & & #"%6 % # &!( Instructing the system user 5%"% % !&%" %%% !%"( ¨ĂSafety instructions In this instruction manual, this heading denotes information which must be observed to prevent accidents and material losses. This symbol is a reference to other instructions which must be observed. Safety regulations ! ! ! "# #" !!$%& &&! '( Applicability 7!!#%-&%!!8 Brine/water heat pump or water/water heat pump Vitocal 300, type BW104, BW106, BW108, BW110, BW113, BW116, BW208, BW212, BW216, BW220, BW226, BW232, 4.8 to 32.6 kW and type WW104, WW106, WW108, WW110, WW113, WW116, WW208, WW212, WW216, WW220, WW226, WW232, 6.3 to 43.0 kW ( ( ( ( ( ( (9 ( (: ( ( ( Air/water heat pump Vitocal 300, type AW106, AW108, AW110, AW113, AW116, 5.4 to 14.8 kW ( ( ( ( (9 3 ; Index General Information +" (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( 7!!#" ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( )& ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( Primary connections 5"!72 (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( : 5"!2 22 ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( Secondary connections +" (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( < = &"< &! (((((((((((((((((((((((((((((((((((((((((( < =!-% ! & (((((((((((((((((((((( < =!-%%&-#& (((((((((((((((((((((((((((( < = &!-%%&" , ( < = &!-%" /%& # (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( < /!!-%,"!2 22 ! &# ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( 9< /!-%,"!72 ! &# ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( < /!!-%,"!2 22 !- & # (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( :< /!-%,"!72 !- & # (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( < /!-% #,& ((((((((((((((((((((( 9 : : 9 9 Initial start-up, inspection and maintenance +! ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( B% % ! ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( 4 Electrical connections +" (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( : > ! ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( : )"!!!! (((((((((((((((((((((((((((((((((((((( : ?&! ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( : /?2%&! (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( :: +%&"! (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( @A&@! ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( ; (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( = (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( ; Index $(' Troubleshooting /&#Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control unit settings =-Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 7&%%Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3"Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . =%&!!Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%!Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ;%.&&!Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . !&%" Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ;%&&% !"&&Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Heat pump control settings +&%!& Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%%&Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 7 Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%1! Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B1 &Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%1 ! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%1! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%%" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%$ &%!!' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%!&$ &%!!' . . . . . . . . . . . . . . . . +&%1!&$ &%!!' . . . . . . . . . . . . . . . 9 +&%%! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&% "!!- . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : +&%!"!!- . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&% &%%&-#& . . . . . . . . . . . . . . . . . . . . +&%!"!!! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%%#&$ &%!!' . . . . . . . . . . . . . . . . . . . . . . . . . . +&% $"!72' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%! $"!72' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%! $"!72' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%1 $"!72' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%1?) $"!72' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&% !$"!72' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&% %$"!2' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5 ; Index $(' +&!! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&%!"! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&% "% % . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&% %" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : +&%%!! " . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&% !$"!2' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%!% % . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&#.& . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&% "!!-%& % . . . . . . . . . . . . . . . . . . . . . . . +&& % . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7&% ! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Domestic hot water cylinder control settings +&%!& . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%1! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&%%" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&/?2" !" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +&%% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : +&%%! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : +&%#! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Control settings ć heating circuit with mixer +&%&-%1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&%!& . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&%%&Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 /1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&%1! Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&%1 ! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&%! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&%1-! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&%& . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&% & . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +&%!% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 +&%/?2" !" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 6 ; Index $(' Components )%"Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 + . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9: BĂ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ; !"Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connection and wiring diagrams + " ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( +" %!$,C' (((((((((((((((((((((((((((((((((((((((((((((((( ,"!72 (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( ,"!2 (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( ,"!22 ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( : Parts lists ,"!72 (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( : ,"!2 22 ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( : Appendix ;&! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +!"!72 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +!"!2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 +!"!22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . /" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 7 Positioning 2$- #' 5%# .! ## # *" ( ( : 5"!72 ( 9 5%% !% #! -% ! ! ( 5"!728 )%%!!%D" % #!!!! ( ( ( 1( 5"!2 22 ( ( ( 8 )" Type AW B- B C A D 9 E A 7 # :º B 7 &% C 2%& D B1# ! E ; 01Ğ + -(%( A B C D A , B 01% -% &% C 2%& D B1# ! 9 )" Type AW$(' 1. 3 !# ( 1% % %%!! ." ( Please note: Avoid short circuiting between the air inlet and outlet. Install ducts without stresses and strains. 2. ;% %- ! & % ( 3. + *"( 4. ;%1% % -% -%&$%- % !!1('( 5. E % %%!!&!% $%" ' $/('( Required equipment /! ?!!,"!72 A# )( "!! 7 # ! #F * "!! 2%!& #F * : 1 10 )" Type BW and WW 2%&%& !!%#$# -'!% % G.!$%! & '( 5!! #!!% !. ! ( 0*!#(/A99 -%1! " ( 71!" # !%&1! ( 5%1!# !! -% /A9( 5% !%& % 1! %" ##%% ( 5%! % !%&1!8 Technical guide for heat pumps -1-% D !Hº;'( 5%#- !! % !#% &%1( 1!( 5%! # %@5"@% ( -%!!8 F!#- $%!% !'( 2-%!! -%-% 8 ;--%#- ( Do notF!$!# &%%!!'( 0 *% !! %&%-!( 5%"!!% !" # & ! -%!( B%#-% ,% @5"@$0%"&" 11 )" Type BW and WW $(' AB 1. 3 %%!! - !!( 2. B%!!-. %. .( 3. B%#-%% @5"@ ( >!&!8 # =1(!# !&!8 # 4. !!-%! #( A )" $#& -' B )"$#& -' 5"! 222 @ @ @ J@ J@ J@ @ @ J@ J@ K@ K@ )" - 3II 12 )" Type BW Brine/water heat pumpĂć ground probe version 5 4 3 2 1 Required equipment /! A# )( 1 ?!!,"!2 "! ! 2 !# ( 3 4 & !# "!.(#% 1!!!&& "$(#' !"!! 3 !!(.28 25>)+9 1!$' 3 !!(.28 25>)+9 1!$' 3 !!(.28 25>)+ 1!$' 99 !-%$!' : 5 L L9 L 13 )" Type BW$(' ; & E E E A )0 4 5 7 6 F!# B M . 0,4% -! (9 1 !-% 7 >! 9 A 5 5 5 )0 E E E A )0 )0 6 14 )" Type BW$(' Brine/water heat pump ć ground probe version 5 4 3 2 1 Required equipment /! A# )( 1 ?!!,"!2 2 !# ( 3 4 & "!.(#% 1!!!&& "$(#' !"!! 3 !!(.28 25>)+9 1!$' 3 !!(.28 25>)+9 1!$' 3 !!(.28 25>)+ 1!$' 99 !-%$!' : 5 "! ! L L9 L 15 )" Type BW$(' ; & E E E A )0 4 5 7 !-% B M 7 >! . 0,4% -! (9 1 6 F!# 9 A 5 5 5 )0 E E E A )0 )0 6 16 )" Type WW Water/water heat pumpĂć ground probe version 9 8 qW 7 6 5 4 1 2 A 3 A -- 17 )" Type WW$(' Required equipment /! 1 ?!!, "!22N"!2!.$( !%qP qQ% "& --%qW' A# )( "! ! 2 /"- 3 3- 4 )"!!$& - "-' 5 6 7 /! ,%. %1%& #F( * #F( * #F( * 8 "!.(#% 1!!!&& "$(#' !! 3 !!(.28 25>)+9 1!$' 3 !!(.28 25>)+9 1!$' 3 !!(.28 25>)+ 1!$' !-% $!' "! ! L L9 L : 9 18 )" Type WW$(' ; & qW qE 4 8 9 A 5 5 5 )0 A 5 5 5 )0 qR qR qQ qP E E E A )0 E E E A )0 B M B M 1 qPqQ B!% qW B--% qE >! .0,4% - !(9 qR 3F!-%.& % 19 + " System versions Blocking 5%#.&%%!! !!"#"""!! $0,4'# % D (5%%!! !-#! % !!"!"( %%0,4 % -.$"' # -%%.!%" ! !%&%#& "!!( A B AB Direct heating water heater and immersion heater element +& #% ! ( 5%%!!;/%!! -%%( 1. 5%&%"%%%& "$!"-% &1&"' %- !!( B ! !!1!% %!!" #-( 5%%&" !!,%!! ,"!22$!& 20 2. ;".( >!&!8 =1!# !&!8 # # "!2!.' "!72&& "! !( A ?&--3@ B ?&-3@ + " System version 1 Modulating systemĂćĂmono-energetic operation System definition 5"!728 5"!2 22 < &&8 < -&8 Primary circuit of the heat pump %! #"%!$ %%&'%!!1 -%%%;/ %!!1% !"!!% !! " !!2!( Secondary circuit of the heat pump ?!!1!!%% %&( 5%;/& %!!1% %&--! %%%&( + "!!2%% %&-%O-"%& 3%/?2 " 4%%&( %& #( ) #"!$-'6 % %%& %-%&%% %!!( ?!!1!"!! % !! -% % !% !%&%% %%;/ ( 2%"%!# -% %&-%5 $"(&(!!!-% -%!!'(/%& -%5!!% %& &!. - !( 5%--%%%& & #"!& &%% %% 21 + " System version 1 $(' Domestic hot water heating with the heat pump %@ @/?2 %&#"%!!1 %!"%%& ! &%! (( &%&%( ?& /?2" ! 7 %;/ -%%&%O-"%& 3(5%%!! %-!% * /?2%&( 5%/?2#%% #" !!"%& "8$(&(% 0?>'( 5%;/-%% %&--%%& &% -"%& 3% /?2! 7%&%%% %;/( 22 + " System version 1 $(' 6 9 A B 3B +B 3= 7 7 qQ +B 5 2 3B +B 3B 7 8 qP 4 A > ! B 4 %& 1 ,E B3E 3 23 + " System version 1 $(' Required equipment /! 1 ?!!,"!722 22 A# )( "! ! 9 9 2 + "!! 23+O93 4)+O 3 5%O-"%& ;%&/?2%& !(.2 ! (.2 ! /%-" ,O"!;,$ !"' ,O"!0,$ !"' /%&-% .2 .2 >- ;" !&% /?2! 0!!"%&" %0?>P / %-% $! % -!º;' +"*!#.$*!! ' ;"&% /?2 % 999: 9 qQ ;"&% % 9 *1Only in conjunction with VitocellĆBĂ100. 9: 9 4 5 6 7 8 : 99 9:9 9: 9 qP "! ! 24 + " System version 1 $(' Connection diagram E E E A )0 qP qQ 5 8 2 7 3 qE = 1 B B Q( Q( Q( Q( A )0 : A A A )0 9 E E E A )0 qW 1 qW >!.0,4% -!(9 qE > ! 25/26 + " System version 2 Mono operation with de-coupled modulating storage unit Primary circuit of the heat pump %! #"!!!2 %&-#&3 -%%%;/ %!!1% !"!!% !! " !!4!( Secondary circuit of the heat pump ?!!1!!%% %&( 5%;/& %!!1% %&--! %%%&( + "!!4%% %&-% -" %&5%/?2 " 6%&- #&3% %&(?& !!7%%* -%%& ( 5%--%%%& & #"!& &%% %% %& #(7" %%!! $ "!!4'%&%D& %&!!7( 27 %&-#&3 !%%& !% #-%- (?%* #" %%& !%&-# &3( % ! # %!! !$&!&'( ?!!1-% & -%%! #"!8 %&-#& 3%% %! %;/(5% %&-%#!! #"%&-#& 3(>"-%%! !!!2 %&-#&3 #-%-% !!1#-% &(5% %&-#!! -% %#"%&-#& 3%" !!% -%%!!( System definition 5"!728 5"!2 22 < &&8 < -&8 27 + " System version 2 $(' Domestic hot water heating with the heat pump %@ @/?2 %&#"%!!1 %!"%%& ! &%! (( &%&%( ?& /?2" ! 9 %;/ -%%&%O-"%& 5( 5%%!!%!%* /?2%&( 5%/?2#%% #" !!"%& "qP$( &(% 0?>'( 5%;/-%% %&--%%& &% -"%& 5% /?2! 9%&%%% %;/( 28 + " System version 2 $(' qE qQ A B 3B +B 7 = 5 qW 7 +B 7 4 3B +B 3B P 9 2 qP 8 P 6 A > ! B 4 %& 3 ,E B3E 3 least one size up (DN) from the remaining pipework. *1At 1 29 + " System version 2 $(' Required equipment /! 1 ?!!,"!722 22 A# )( "! ! 2 5!#%%! -%%%&-#&$!' 9:9 3 ?&-#&, "!+,)$:!"' + "!! 23+O93 4)+O 5%O-"%& ;%&/?2%& !(.2 ! (.2 ! "! ! 6 /%-" ,O"!;,$ !"' ,O"!0,$ !"' 7 ?&!! 23+O93 4)+O 5!#%%! -%%%&-#& $#' ;" !&% /?2! qP 0!!"%&" %0?>P / %-% $! % -!º;' qQ qW +"*!#.$*!! ' ;"&% % 999: 9 qE >- *1Only in conjunction with VitocellĆBĂ100. 5 9: 9 8 9 30 9 9 "! ! 9 9 9:9 9:9 9: 4 + " System version 2 $(' Connection diagram E E E A )0 qW qP 4 7 9 5 8 2 qT = 1 B B B B Q( Q( Q( Q( Q( Q( Q( Q( A )0 : A A )0 A )0 9 E E E A )0 qR 1 qR >!.0,4% -!(9 qT > ! 31/32 + " System version 3 Mono operation with heating water buffer storage unit System definition 5"!728 "!2 22 < &&8 < -&8 9 9 99 Primary circuit of the heat pump %! #"!!!2 %&-#&3 -%%%;/ %!!1% !"!!% !! " !!4!( 7%-"% %!!$ " !!4'%&%D&%& !!7 8( $3 85% -%& !!7 8% # %%- " !!4'(%&- #&3!% %& !% #-%-(? %* #"%%& ! %&-#&3( %! # %!!!$& !&'( Secondary circuit of the heat pump ?!!1!!%% %&( 5%;/& %!!1% %&--! %%%&( + "!!4%% %&-%O-" %&5%/?2 " 6%&- #&3( ?&!!7 8 %%* - %%&( 5%-%%& & #"!& &% % % % %& # %&%1%& ( 33 33 + " System version 3 $(' DHW heating with the heat pump %@ @/?2 %&#"%!!1 %!"%%& ! &%%! (( &%&%( ?& /?2" ! qP %;/ -%%&%O-" %&5( 5%;/% -!% * /?2%&( 5%/?2#%% #" !!"%& "qQ$( &(% 0?>'(5%;/ -%%%&-%%&&% -" %&5% /?2! qP%&%%% %;/( ?!!1-% & -%%! #"!9 %&-#& 3%% %! %;/(5% %&-%#!! -%%#"%&-# &3(>"-%% !!!! 2 %&-# &3#-% -%!!1#-% &( 5%%&-#!! -%%#"%&-# &3%" !!% -%%!!( 34 + " System version 3 $(' qO qU B qO qI 7 A qW C 8 = = qT qZ qR +B 5= 7 7 qE 3B +B +B 4 3B 3B qP qQ 2 9 6 3 ,E B3E 3 A > ! B =1 C =1 $ %&' 1 35 + " System version 3 $(' 2 qR qT qZ qU qI qO 5!#%%! -%%%&-#&$!' ?&-#&, "!+,)$:!"' + "!! 23+O93 4)+O 5%O-"%& ;%&/?2%& !(.2 ! (.2 ! /%-" ,O"!;,$!"' ,O"!0,$!"' = O/%& #-% %&!!1 %&!!1 5!#%%! -%%%&-#&$#' ;" !&% /?2! 0!!"%&" %0?>P / %-% $! % -!º;' +"*!#.$*!! ' ;"&%% B- # / =11 =11 B-!1 B-!1 >- *1Only in conjunction with VitocellĆBĂ100. 3 4 5 A# )( "! ! 9:9 7 8 9 qP qQ qW qE 36 9 9 9: 9 6 "! ! "! ! % "! ! 9:9 9:9 9: 999: 9 99 99 99 9 9 :9 Required equipment /! 1 ?!!,"!722 22 + " System version 3 $(' Connection diagram E E E A )0 qE = qP B = 8 Q( Q( qZ B = 5 Q(: Q(: 7 B qT Q( Q( 4 A )0 qQ qI qU 9 2 wQ 1 B B B Q( Q( Q( Q( Q( Q( A )0 A )0 : A A )0 A 9 )0 A )0 9 E E E A )0 wP 1 wP >!.0,4% -!(9 wQ > ! 37/38 + " System version 4 Mono-energetic operation with solar heating system and Vitocell 333 Primary circuit of the heat pump %! #"!!! 2,3 %/?2 /?2 " !4 ,3-%% %;/%!" !!% !! "!!5 !-%%!!1& "( Secondary circuit of the heat pump and solar heating system ?!!1!!%% %&( +%&"C!" !!%!!1#- ! &%# &"(5%;/ & %!!1 % -"1D% %&--! %%&(%%& %% -,3( ?!!1% ! !! 2,3 -%%! %;/( ,3% 39 %O-"%&6 $!@7H@'( + "!!5% %&-,3 %%&( ?!!1-% & -%%! #"- 7,3% % %!% ;/(>"-%% !!! 2 ,3 #-%-% !!1# (? !!1-% ! !! 2%&%%% !%;/ $,3" % #"%%&"'( 4 %% %&-#!! -% %#"%&!!8 -&%,3( System definition 5"!728 5"!2 22 < &&8 < -&8 39 + " System version 4 $(' 5%--%%%& & #"!& &%% %% %& #(5%D& %&!!8" %%%!! $ "!!5'( ,3%&- #&!% %& !% %-(? * #"%%& !#",3( %! # %!!!$& !&'( 5%%&-#!! -%%#",3 %"!!% - %%!!( Domestic hot water heating with heat pumps and solar support %@ @/?2 %&%&%%!!1% !"%%&( ?& %& /?2" !4 % ;/-%%& %O-"%&6 $!@7H7@' -% %!!1( 5%;/% /?2" !% !!%" % * /?2%&( 5%% %- & %1%&!!-%& ,3(> % !"& -! % & % -%&!!#" %%&- %- " ( 5%-#*"% %* !#"% - %!!& ,3/?2 !( &"# %/?2#% 1" #"%"(5%/?2 #%% #" !!"%&"9 $( &(% 0?>'( 5%;/-%% %&--%%& &% -"%& 6 $!@7H@'% /?2 !4%&% %%%;/ ( 40 + " System version 4 $(' qR qI qT +B A C B 3B qU 8 qP 5 D +B 5 qZ 7 7 6 3B = = qE 4 P 2 5 9 P 7 qW 1 3 M2 qQ A > ! B ?& C + D 5%O-"1 *1At M2 ; - 3E 3 ,E B- least one size up (DN) from the remaining pipework. 41 + " System version 4 $(' Required equipment /! 1 ?!!,"!722 22 2 3 4 5 6 A# )( "! ! ;!#%%!( : -%%%&-#&$!' ?&-#&-%/?2 %&,"!+,M ;" !&/?2 9:9 !6# % 9 - + "!! 9 23+O93 9 4)+O 5% -"%&%&/?2 %& 9: !(.2 ! 9 (.2 ! ;!#%%!( : -%%%&-#& $#' = O/%& #-% "! %&!! ! 0!!"%&" 9: %0?> //?2% $! % -!º;' +"*!#.$*!! ' 999: ;"&% 9 % =1 99 B-! 9 >- :9 Heating by solar collector ;" !&% 9:9 /?2!6# % --%$ '$K@1@1@'% 9:9 !! +O/$!!&%' "! -%!!%%& ! ;! 99 8 9 qT qP qQ qZ qU qI qW qE qR 42 7 + " System version 4 $(' Connection diagram E E E A )0 qQ qR B B B B B Q(: Q(: Q( Q( Q( Q( Q( Q( Q( Q( = qE B 6 Q( Q( 8 B qZ Q( Q( 5 A )0 9 4 qW qU 7 2 wP = A )0 : A A )0 A 9 )0 A )0 9 E E E A )0 qO 1 1 qO >!.0,4% -!(9 wP > ! 43/44 + " System version 5 TypeĂBW and WW up to 17ĂkW Mono-energetic operationĂćĂmodulating system with DHW cylinder and Divicon heating circuit distributor System definition 5"!2 22 &&8 -&8 Primary circuit of the heat pump %! #"%! %!!1-%% %;/% !!1%!"!!% !! "!!2!( Secondary circuit of the heat pump ?!!1!!%% %&( 5%;/& %!!1% %&--! %%%&(5% "!!2%% %&-%O-" %&3%/?2 " 4%%&( "-%&%% %!!( ;" 7 % ! % * %!!1 % !&%!!1( ?!!1!"!! % !! -% % !% !%&%% %%;/ ( 45 5%-!# -% %&-%5 $"'(5% %&- %5!!% ! &!. !$xHº;'( 5%--%%%& & #"!& &%% %% %& #( -%/%& #6% 45 + " System version 5 $(' TypeĂBW and WW to 17ĂkW DHW heating by heat pump %@ @/?2 %&#"%!!1 %!"%%& ! &%! (( &%&%( ?& /?2" ! 8 %;/ -%%&%O-" %&3(5%;/ %!%* /?2%&( 5%/?2#%% #" !!"%& "9$( &(% 0?>'( 5%;/-%% %&--%%& &% -"%& 3% /?2! 8%&%%% %;/( 46 + " System version 5 $(' TypeĂBW and WW to 17ĂkW qW A B 5 3 +B = 6 qQ 3B +B 2 qP 3B +B 3B 8 9 4 7 3E 3 ,E B- A > ! B ?& 1 47 + " System version 5 $(' TypeĂBW and WW to 17ĂkW Required equipment /! 1 ?!!,"!2 22 4 5 6 2 3 7 /%-" ,O"!;,$ !"' ,O"!0,$ !"' /%&-% .2 .2 /%& #( "!!$ 4)+O' %O-"%& ?&-#&, "!+,2$!"' A# )( "! ! "! ! : 99 9 9:9 8 ;" !&% /?2! 9 0!!"%&" %0?>P / %-% $! % -!º;' qP ;"&% /?2 % 9 qQ ;"&% % 9 qW >- *1Only in conjunction with VitocellĆBĂ100. 9: 48 + " System version 5 $(' TypeĂBW and WW to 17ĂkW Connection diagram E E E A )0 qP qQ 3 8 qR B 2 B 9 5 Q( Q( Q( Q( A 2? : 4 1 A A A )0 9 E E E A )0 qE A = 1 Colour coding conforming to DINĂIECĂ757 A #- 4 # 2? -% qE >!.0,4% -!(9 qR > ! 49/50 + " System version 6 Type BW and WW Dual parallel operation with free-standing boiler 9 99 Central heating using a heat pump %! #"!!!2 %&-#&3 -%%%;/ %!!1% !"!!% !! " !!4!( Central heating using a boiler ?%&" %&-# &3(% ! #"!! !2%& -#&3- %%%;/ %!!1%!" !!% !! "!!4 !(%! !!!2 %&-#&3 -%%! %;/-% %;/ #B-#& -%%!& (%% ;/#%# "5 %O-"%&6 !@7H7@(5% %&%!! 51 #"%#(%# &(5%# %#"%# # "5 %! % -!7Ă% %&-#&3 %% %! %;/( /!! & ! 1(-!º;(+ %# &"( 5%O-"%&6 -% !@7H@( ?!!1 " !!4-% % ;/( System definition 5"!2 22 &&8 -&8 51 + " System version 6 $(' DHW heating by heating water buffer storage unit via heat pump %@ @% /?2%&#"% !!1%!"% %& ! &%%!(( &%&%( ?& %" ! 8/?2" 9 %;/-%% -%%O-"%& qP@7H7@(+ " !!4!(5% ;/%!%* /?2%&(5%/?2! # 1(º;( 5%/?2#%% #" %!!" %&"qQ$( &( %0?>'#" %&$#'( 5%;/-% % -"%&qP %!!1%&! $!@7H@'% /?2! 8%&%%% %;/(/?2 !!qW-#-% -O-"qE-# ( Type BW and WW DHW heating by boiler 5%#%%/?2#& # #"%;/( ;"qR%# ## -%%# /?2" !qT . %#(%;/ #.%# %&/?2/?2! qT -#-% "qR%&%1 qZ$W'(5% /?2!-%%!!1( M%&%6%-# !" %,, ( 52 + " System version 6 $(' Type BW and WW wU wR wU A wW wP = wT B wE wQ = wZ qP = 7 7 qU 4 qO L 8 qT = qQ 2 qE 7 wI = 7 7 9 qW M2 qI 3 M2 3E ,E L C ; - 3 B/?2 A =1 B =1 $ %&' C >O&O # 1 6 53 + " System version 6 $(' Type BW and WW Required equipment /! 1 ?!!,"!2 22 A# )( "! ! 2 5!#%%! -%%%&-#&$!' 9:9 3 ?&-#&, "!+,)$:!"' "! ! 4 + "!! 23+O93 4)+O 5!#%%! -%%%&-#& $#' /?2" !& %/?2!$;/' 8 9 9:9 /%-" ,O,"!;,7$ !"' ,O,"!0,$ !"' 5%O-"%& ;%&/?2%& !(.2 %!!! (.2 %!!! "! ! 0!!"%&" %0?>P$ ' qP 9: 9 qQ / %-% $! % -!º;' "! ! qW ;!!/?2" %& $#/?2%1%&' qE 5-O-" eQ ;"&%/?2%& $%1%&' 9 qU +"*!#.$*!! ' 999: 54 7 9 9 9:9 + " System version 6 $(' Type BW and WW /! qI ,%1%& A# )( "! ! wP wQ wW wE wR =11 =11 = O/%& #-% %&!!1 %&!!1 B-!1 99 99 "! ! 9 wT wZ wU B-!1 B- # / >- 9 99 :9 wI ,- 9 Central heating by boiler 5 ;"&%% -" %& #&%# 6 5% -"%&%&% !!%&# !(.2 %!!! (.2 %!!! 9: 9 qR DHW heating by boiler ;"&%/?2%&#" # 9 qT ;" !&% /?2!$#' 9:9 qZ qO B1 W(2 ;!!/?2" %& $#' "! ! *1Only with VitocellĆVĂ100, typeĂCVA, 300 to 500Ălitres capacity and VitocellĆVĂ300, typeĂEVI, with flange aperture. 55 + " Type BW and WW System version 6 $(' 56 + " System version 6 $(' Type BW and WW Connection diagram ? +5 > 53 EW Q > 53 +5 A E E E A )0 eE qZ qR 6 qT = 5 4 wP wW qP qE = = = qW wQ 8 wE wT wR 7 2 eP = 1 1 B B Q( Q( Q( Q( B Q( Q( B B Q(: Q(: Q( Q( B A A )0 A )0 A A E )0 A : A 9 )0 A )0 A )0 9 E E E A )0 eQ Q( Q( wO 1 wO >!.0,4% -!(9 eP > !$;/' eQ ;"!(9 eW ,$#' eE 3F!-%.&% 57/58 + " System version 7 Type AW Dual alternative operation with free-standing boiler System definition 5"!728 9 Central heating using a boiler ?%&" %&-# &3(% ! #"% ! #-%!# %;/ %O-"%&6 7-#!@7H7@ #"%;/ "5(7% %## "5(?!!1 -%# # (-% #!% ! 1"#"%# -%%& %#(? !!1-## ! % %#-##. %! #"% ! 1 %#! %;/$& 1%! '(B% !!%O-"%& 6 7-#-% !@7H@( Central heating using a heat pump %! #"!!!2 %&-#&3 -%%%;/ %!!1 "!!4!( 59 59 + " System version 7 $(' DHW heating by heating water buffer storage unit via the heat pump %@ @/?2 %&#"%!!1 %!"%%& ! &%! (( &%&%( ?& " !8 /?2" 9 %;/ -%%%O-" %&qP@7H7@( + "!!4 !(5%;/ %-!% * /?2%&(5% /?2!# 1(º;( 5%/?2#%% #" %!!" %&"qQ$( &( %0?>'#" %&$#'( 5%;/% -"%&qP % !!1%&! $!@7H@'% /?2! 81 %% ;/(/?2 !!qW-#-% -O-"qE-# ( Type AW DHW heating by boiler 5%#%%/?2#& # #"%;/( 7"qR% ### -%% #/?2" ! qT. %#(% ;/#.%# %&/?2/?2! qT-#-% "qR%&%1 qZ$W'(5% /?2!-%%!!1( M%&%6%-# !" %,, ( 60 + " System version 7 $(' Type AW wU wR wU A wW wP = wT B wE wQ = wZ qP = 7 7 qU 4 qO L qQ 8 qT = 2 qE wI 6 wO = 7 7 7 9 qW qI 1 3 C 7 7 = M2 M2 3E ,E L ; - 3 B/?2 A =1 B =1 $ %&' C >O&O # 61 + " System version 7 $(' Type AW Required equipment /! 1 ?!!,"!72 A# )( "! ! 2 5!#%%! -%%%&-#&$!' 9:9 3 ?&-#&, "!+,)$:!"' "! ! 4 + "!! 23+O93 4)+O /?2" !& %/?2!$;/' /%-" ,O,"!;,7$ !"' ,O,"!0,$ !"' 5%O-"%& ;%&/?2%& !(.2 %!!! (.2 %!!! 0!!"%&" %0?>P$ ' 8 9 qP "! ! 9: 9 qQ 9 9 9:9 / %-% $! % -!º;' "! ! ;!!/?2" %& $#/?2%1%&' qE 5-O-" eW ;"&/?2%&$% 1%&' 9 qU +"*!#.$*!! ' 999: qI ,%1%& "! ! qW 62 + " System version 7 $(' /! wP =11 wQ =11 wW wE wR wT wZ wU wI wO 5 6 7 Type AW A# )( 99 99 = O/%& #-% %&!!1 %&!!1 B-!1 B-!1 B- # / % "! ! 9 9 99 >- ,- 5!#%%! -%%%&-#& $#' :9 9:9 9 Central heating by boiler ;"&%% -" %& #&%# 5% -"%&%&% !!%&# !(.2 %!!! (.2 %!!! 9: 9 DHW heating by boiler qR ;"&/?2%&#" # 9 qT ;" !&% /?2!$#' 9:9 qZ qO B1 W(2 ;!!/?2" %& $#' "! ! *1Only with VitocellĆVĂ100, typeĂCVA, 300 to 500Ălitres capacity and VitocellĆVĂ300, typeĂEVI, with flange aperture. 63 + " Type AW System version 7 $(' 64 + " System version 7 $(' Type AW Connection diagram ? > 53 +5 A 53 eE Q > +5 E E E A )0 eR qZ qR 6 7 = = qT 5 4 wP wW qP qE = = = qW wQ 8 wE wT wR wO 2 eQ = 1 1 B B B B B B Q(: Q(: Q( Q( Q( Q( Q( Q( Q( Q( A A )0 A )0 A A E )0 A : A )0 A )0 A 9 )0 9 E E E A )0 EW Q( Q( eP 1 eP >!.0,4% -!(9 eQ > !$;/' eW ;"!(9 eE ,$#' eR 3F!-%.&% 65/66 + " System version 8 Type BW and WW Dual parallel operation with wall-mounted oil-/gas-fired boiler 9 99 Primary circuit of the heat pump %! #"!!!2 %&-#&3 -%%%;/ %!!1% !"!!% !! " !!4!( Secondary circuit of the heat pump ?!!1!!%% %&( 5%;/& %!!1% %&--! %%%&( + "!!4%% %&-%O-" %&5%/?2 " 6%&- #&3( ?&!!7 8 %%* - %%&(5% &"-%&%% 9( 5%-%%& & #"!& &% % % % %& # %&%1%& ( 67 7%-"% %!!$ " !!4'%&%D&%& !!7 8( 3 85% -%& !!7 8% # %%- " !!4(%&- #&3!% %& !% #-%-(? * #"%%& !%&- #&3(5% ! # %!! !$&!'( ?!!1!! & -%%! #"#! qP%&-# &3%% % !%;/ (5%%&-%# !! -%%#"%&- #&3(>"-% %!!! !2%& -#&3 #-%-% !!1# &( 5%%&-#!! -%%#"%&-# &3%" !!% -%%!!( 67 System definition 5"!2 228 &&8 -&8 + " Central heating with the wall-mounted boiler ?%&" %%%& -#&3-% &%%& -!( ;"qQ -%% #%- # %& ! #-% ! #!%;/ (5%%1 !- #$F!@Q @ );,3 -%% '( 5%- #(%!& %&-%%% # %%!!1 %&%!( 5%1(-!% # º;(E- % 9-%/?2! qW%" ! ( DHW heating by heat pump %@ @/?2 %&#"%!!1 %!"%%& ! &%! (( &%&%( ?& /?2" ! qR %;/ -%%&%O-"%& 5( 5%%!!%!%* /?2%&( 68 Type BW and WW 5%;/&% %&--%%& &% -"%& 5% /?2! qR1 %% ;/( DHW heating with the wall-mounted boiler 5%- #%% /?2#&# #"% ;/( ;"qE%# ## -%%# /?2" !qZ . %- #( 7%&%# # #"1( & %/?2!" !!/?2 %&-#!! 1 qT$.W'"% !!1% #%"( 7 &"%!%-%& /?2%&#-% !!1 %- #(2%/?2%&%# # %O-"%& 5%&!( System version 8 $(' + " System version 8 $(' Type BW and WW A wE wE B C wP wQ 7 qI = 8 qO = wW 9 qW 5= +B 7 7 +B qU 4 +B 3B 3B qZ qR wR 2 qP 6 3 3E 3 ,E B- A 2 O&O # -%-% ! B =1 C =1 $ %&' 1 69 + " System version 8 $(' Type BW and WW Required equipment /! 1 ?!!,"!2 22 A# )( "! ! 2 5!#%%! -%%%&-#&$!' 9:9 3 ?&-#&, "!+,)$:!"' "! ! 4 + "!! 23+O93 4)+O 5%O-"%& ;%&/?2%& !(.2 %!!! (.2 %!!! /%-" ,O"!;,$ !"' ,O"!0,$ !"' "! ! = O/%& #-% ?&!!1 ?&!!1 5!#%%! -%%%&-#& $#' /?2" !& %/?2!$;/' % "! ! 9:9 9:9 qU qI qO +"*!#.$*!! ' =11 =11 999: 99 99 wP wQ wW B-!1 B-!1 B- # / 9 9 99 wE >- :9 5 9: 9 6 7 8 qP qR 9 9 70 + " System version 8 $(' /! wR 0!!"%&" %0?>P$ ' / %-% $! % -!º;' 9 qQ qW Central heating by the wall-mounted oilĆ/gasĆfired boiler with weather-compensated control unit E-% ;"#&%- # ;" ! %- % Type BW and WW A# )( 9: 9 9: DHW heating by the wall-mounted oilĆ/gasĆfired boiler with weather-compensated control unit ;"&%/?2%&#" %- # 9 qT B1 .W(2 qZ ;" !&% /?2!$- # ' 9: *1Only in conjunction with VitocellĆBĂ100. qE 71 + " Type BW and WW System version 8 $(' 72 + " System version 8 $(' Type BW and WW Connection diagram E E E A )0 wU Q Q9 qZ qE . qT qQ 4 qI 7 = 5 qO = = 8 qR wQ wP qP 2 wZ 1 B B Q( Q( Q( Q( B Q( Q( B B Q(: Q(: Q( Q( B Q( Q( A )0 A )0 A A )0 : A A )0 A 9 )0 A )0 9 E E E A )0 wT 1 wT >!.0,4% -!(9 wZ > !$;/' wU 2 O&O #-%-% ! 73/74 + " System version 9 Type AW Dual alternative operation with wall-mounted oil-/gas-fired boiler 9 Heat pump ventilation air inlet (primary) %! #"!!!2 %&-#&3 /?2 " !4 /?2" 5-%% %;/% !!1 "!!6 !( Secondary circuit of the heat pump ?!!1!!%% %&( 5%;/& %!!1% %&--! %%%&( + "!!6%% %&-%O-" %&7%/?2 " 5%&- #&3( ?&!!8 9 %* - %%&("% --%&%%& -#&3 %O-"%&qP -%%! D %&%- % qQ(5%-% %&& 75 #"!& &% % % % %& # %&%1%& ( 7%-"% %%!!$ " !!6'%&%D&%& !!8 9( 3 85% -%& !!8 9% # %%- " !!6(%&- #&3!% %& !% #-%-(? * #"%%& !%&- #&3( %! # %!! !$&!'( System definition 5"!728 75 + " System version 9 $(' Type AW Central heating with the wall-mounted boiler ?%&" %%%& -#&3-% &%%& -!( 7"qE -%%#%- # % -" %&qP%& !#-% !#! %;/( %%!1 %- # $F!@Q @ );,3 -%% '( ?&-#&3 -%&#!! #" %&!!8 9( 76 5%- #%" ! -%% %&(?!!1 -% #"%;/ # %!& !(5%1! &%! %- #" #"%!% 1(E-% qQ -%" ! qR%" ! %- #( 5%# -% !% #% ( DHW heating by heat pump %@ @% /?2%&#"% !!1%!"% %& ! &%%!(( &%&%( ?& /?2" ! 4 %;/ -%%&%O-"%& 7(5%%!! %-!% * /?2%&( 5%;/-%% %&--%%& &% -"%& 7% /?2! 4%&%%% %;/( ?!!1-% & -%%! #"!qW %&-#& 3 %% %! %;/(5% %&-%#!! -%%#"%&-# &3(>"-%% !!!! 2%&-# &3#-% -%!!1# &( 5%%&-#!! -%%#"%&-# &3%" !!% -%%!!( + " System version 9 $(' Type AW DHW heating with the wall-mounted boiler 5%- #%% /?2#&# #"% ;/( 7"qT#% # #/?2 " !qZ . %- #( 7%&%# # #"1( & /?2 !#º; !/?2 %&-# # # 1 qU$.W'(/?2 %&&"& #"% ;/(7 &" % !%-%& /?2%&#-%!!1 %- #(2% /?2%&%## %O-"%&7 %&!( 77 + " System version 9 $(' Type AW A wR wR B C wW wQ 8 9 qO = wP = wE qQ 7 +B 7 7 qR qP = = 7 7 +B 6 +B qI 3B 3B qZ 4 wT 2 qW 5 3 3E 3 ,E B- A 2 O&O # -%-% ! B =1 C =1 $ %&' 1 78 + " System version 9 $(' Type AW Required equipment /! 1 ?!!,"!72 A( )( "! ! 2 5!#%%! -%%%&-#&$!' 9:9 3 ?&-#&, "!+,)$:!"' "! ! 4 /?2" !&% /?2!$;/' 9:9 5 /%-" ,O"!;,$!"' ,O"!0,$!"' + "!! 23+O93 4)+O "! ! 5% -"%&%&/?2 %& !(.2 %!!! (.2 %!!! 8 9 qW = O/%& #-% %&!!1 %&!!1 5!#%%! -%%%&-#&$#' "! % ! 9:9 qI qO wP +"*!#.$*!! ' =11 =11 999: 99 99 wQ wW wE B-!1 B-!1 B- # / 9 9 99 wR wT >- 0!!"%&" %0?>P $ ' //?2% $! % -!º;' :9 6 7 9: 9 9 9 9: 79 + " System version 9 $(' Type AW /! Central heating by the wall-mounted oilĆ/gasĆfired boiler with weather-compensated control unit qP 5% -"%&%&% !!%&- # !(.2 ! (.2 ! A# )( qQ E-% qE ;"&%% -" %& #&% - # ;" ! %- % 9 9: 9: 9 qR DHW heating by the wall-mounted oilĆ/gasĆfired boiler with weather-compensated control unit ;"&/?2%&#" - # 9 qZ 9: qU ;" !&% /?2!$- # ' B1 .W(2 *1Only in conjunction with VitocellĆBĂ100. qT 80 + " System version 9 $(' Type AW Connection diagram E E E A )0 wI Q Q9 qT qP = . qZ qU qE 6 qO 8 = 7 wP = = 4 9 wW wQ qW 2 wU 1 1 B B Q( Q( Q( Q( B Q( Q( B B Q(: Q(: Q( Q( B Q( Q( A A )0 A )0 A )0 A : A A )0 A 9 )0 A )0 9 E E E A )0 wZ 1 wZ >!.0,4% -!(9 wU > !$;/' wI 2 O&O #-%-% ! 81/82 + " System version 10 Dual alternative operation with solid fuel boiler VitoligĂ100 9 9 99 Primary circuit of the heat pump %! #"%! %!!1-%% %;/% !!1%!"!!% !! "!!2!( Secondary circuit of the heat pump ?!!1!!%% %&( 5%;/& %!!1% %&--! %%%&( + "!!2%% %&-%O-" %&3%/?2 " 4%&- #&5% %&( ?&!!6 7 %%* - %%&(5%%%& & #"!& &% % % % %& # %&%1%& ( 83 7%-"% %%!!$ " !!2'%&%D&%& !!6 7( 3 85% -%& !!6 7% # %%- " !!2(%&- #&5!% %& !% #-%-(? * #"%%& !%&- #&5(5% ! # %!! !$&!&'( ?!!1-% & -%%! #"!8 %&-#& 5 %% %! %;/(5% %&-%#!! #"%&-#& 5( System definition 5"!728 5"!2 22 <&&8 <-&8 83 + " System version 10 $(' Central heating via solid fuel boiler 2%%#-! º;! %qP%#% %!!1-#-% "qQ 0,4 qW !!qE #B-# ( 5%%&-# &5#% -% %! &*(? #& #"% ;/( DHW heating by heat pump %@ @/?2 %&#"%!!1 %!"%%& ! &%! (( &%&%( ?& /?2" ! qR % -%%&%O-" %&3(5%;/ %!%* /?2%&( 5%/?2#%% #" !!"%& "qT$( &(% 84 0?>'( 5%;/-%% %&--%%& &% -"%& 3% /?2! qR1 %% ;/( DHW heating by solid fuel boiler %#-! % #% #% %" qZ% #%&&%& -#&5# % (%! %&-#& 5%%! %qU !!qI%/?2 " 4%/?2 !" %qO /?2 " 4%% º;(? !!1-# # % !!%&/?2% /?2!" !qR%% %!%;/ ( >"-%%!!! !9%& -#&5 #-%-% !!1# &(5% %&-#!! -% %#"%&-#& 5%" !!% -%%!!( + " System version 10 $(' wZ wZ A B wE wR 6 wQ 7 wW = = wT 3= 7 7 qI wP qP 2 P qO qR qT qZ 9 qU qE 8 P 4 1 A =1 B =1 $ %&' C + #,& C 3E 3 ,E B- least one size up (DN) from the remaining pipework. *1At 5 wU 85 + " System version 10 $(' Required equipment /! 1 ?!!,"!722 22 A# )( "! ! 2 + "!! 23+O93 4)+O 5%O-"%& ;%&/?2%& !(.2 %!!! (.2 %!!! 4 /%-" ,O"!;,$ !"' ,O"!0,$ !"' "! ! 5 ?&-#&, "!+,)$:!"' "! ! = O/%& #-% %&!!1 %&!!1 5!#%%! -%%%&-#& $#' 5!#%%! -%%%&-#&$!' % "! ! 9:9 9:9 qP =!% % # HH qR /?2" !& %/?2!$;/' 9:9 qT 0!!"%&" %0?>P / %-% $! % -!º;' wP +"*!#.$*!! ' *1Only in conjunction with VitocellĆBĂ100. 3 9: 9 6 7 8 9: 999: 9 9 9 86 + " System version 10 $(' /! wQ =11 wW =11 A# )( 99 99 wE wR wT B-!1 B-!1 B- # / 9 9 99 wZ >- :9 Central heating by solid fuel boiler VitoligĂ100 qQ ;"-%&%%!! 0,4#.& 9 wU qE qZ 3!&"-% !! % %. 9: qU 5% %%&-#& $!'-%&%!!qI 9:: DHW heating by solid fuel boiler VitoligĂ100 ;!!/?2" %& ;" % %/?2" -%&%!!qI 9:: qI qO 87 + " System version 10 $(' 88 + " System version 10 $(' Connection diagram E E E A )0 wO eP 1 B wI Q( Q( 9 B 8 Q( Q( wE B qW wR Q( Q( = qR B = 7 Q( Q( A 9 )0 A )0 9 wW B = eQ 3 Q(: Q(: 6 qI B qO Q( Q( wQ = A )0 qU 2 E E E A )0 A )0 qE A qQ )0 qP = : A qT A )0 1 qW 0,4-% wI > ! wO R#1$' eP ;"!(9&%% eQ >!0,4#.& 89/90 0 Summary A >!%!! B .%! ! C );-%!QQ D 0# E ?!!! $, % !!' CB E A D A ;%# % -&!&%%& #% #%( /# "1, #( 91 91 0 Outside temperature sensor Q( B A Q( % ! %%% - -%&%!!1((6 ( ;#8 S(1(&!!( ;"#%& ( B A 5!QQ B > ! ! Primary pump/circulation pump for intermediate circuit A )0 5 5 A 5 = C B A =!-%%%! B )! =! "B8 )"!! $#& -' =! "B8 !! ;#8 ?2 B ?3AOB 92 ¨ĂSafety instructions Do not interchange cores. Observe the rotational direction of the pump. %!!%%F #1 #%!! $-!'( 0 Heating circuit components Secondary pump %!!%%F #1 #%!! $-!'( A )0 = C A B A 5!%!! B + "!! Remote controls ( B ( ( ( 93 0 Heating circuit components $(' 31 Q( Q( B A % -% !( ;#8 S(1(&!!( ¨ĂSafety instructions Do not interchange cores. Q( B9 B 31 Q( Q( A B Q( B9 B A 5!QQ B 3! 94 0 Heating circuit components $(' Flow temperature sensors B-!1 Q( B A Q( ;%%&-!! - #( %-! !#%1( Please note: Use heat transfer paste. Do not thermally insulate the sensors. B B-!1 Q(: B A Q(: B A 5!QQ B B-! 95 0 Heating circuit components $(' Mixer motors %1( =11 Installation instructions mixer motor 9 )0 A A = C B =11 )0 A A = C B A 5!%!! | >!1 ~ ;1 B =1 96 0 Heating circuit components $(' Heating circuit pumps %&!!$"! '( ?&!!1 Installation instructions heating circuit pump A )0 A = C ;#8 ?2 B ?3AOB B ?&!!1 A )0 A = C B A 5!%!! B ?&!! 97 0 Heating circuit components $(' Direct heating water heater Q : T A A B A ;@ B B Dimensions in mm E E E A )0 C B A 5!%!! B /%&-% ! C ;"$' 98 :: T 9 + %%&-% %&-%$"# "%D"' 3% . "( A 6ĂkW ¨ĂSafety instructions Do not interchange cores. +%%$º;' % -%( A 3ĂkW Q 0 DHW heating components DHW cylinder temperature sensor /?2" %&- #&( /%-" Q( B A Installation instructions DHW cylinder and/or the heating water buffer storage unit Q( B A 5!QQ B /?2" ! ?&-#& B Q( Q( A Q( Q( B C B A 5!QQ B E-/?2" ! C 4!!" ! 99 0 DHW heating components $(' ThreeĆway changeover valve %%O-"%& %-( 5%O-"%&-% !& A )0 : B 7 7 Installation instructions threeĆway changeover valve ¨ĂSafety instructions Do not interchange cores. A 5% -"%&% /%& # -%!& A A 4 A : 2? B 7 7 A 5!%!! B 5%O-"%& 7 % %- " 7 %%!! %%& Colour coding conforming to DIN IEC 757 A #- 4 # 2? -% 100 0 DHW heating components $(' Immersion heater element EHO E E E A )0 C A A B A ?!!! B % ! C ;"$' %% %/?2" ( Installation instructions immersion heater element 101 0 Solar heating system components Collector temperature sensor Q( B Installation instructions solar collector A Q( B A 5!QQ B + DHW cylinder temperature sensor ?&-#& Q( B Installation instructions heating water buffer storage unit or DHW cylinder A Q( B /%-" Q(: B A Q(: A 5!QQ B + 102 B 0 Solar heating system components $(' Swimming pool sensor Q( B A Q( B A 5!QQ B + Solar heating circuit circulation pump + /-% !!( A )0 A B Installation instructions Solar-Divicon ¨ĂSafety instructions Do not interchange cores. A ?!!! B ;!! = C 103 0 "Natural cooling" components Dew point sensor Q( B A Q( B A 5!QQ B /-! B-! !&:( =1!&:( ;!!!&:9( Central fault indication A Q9( ?!!"# !" !"( L E !"8 ,C7 Q9( E A A 5Q9% # 104 0 Mains electrical connection ¨ĂSafety instructions Provide fuse protection in accordance with the max. value stated under Specification (see pagesĂ213 to 224). The mains electrical connections should correspond to current regulations and meet the requirements of your local electricity supply company. C E E E A )0 E E E D A )0 B A A ?!!! B = C B D =&A)0C, 1. )"% $A)0C,'( ;#8 (S( 2. 3%#% %%!! -%% -&%-( Please note: Heat pump, DHW cylinder and water pipes should be connected with the earth bonding of the house in question. ¨ĂSafety instructions Do not interchange cores. 105 !! Steps For further instructions in connection with the individual steps see the respectively indicated page. !! 5-!! =! I I I I I I I I I I I I I I T T M M M T M 5. Checking the diaphragm expansion vessel and the system pressureĂ (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( : T T M M M M 6. Checking the function of all safety valves 1. Keeping a service reportĂ ((((((((((((((((((((((((((((((((((((((((((((((((((((((((( 2. Switching off/disconnecting the main fuseĂ 3. Checking the refrigeration circuit for leaksĂ (((((((((((((((((((( 4. Filling the heating systemĂ (((((((((((((((((((((((((((((((((((((((((((((((((((((( : T 7. Checking all water connections for leaks 8. Checking the condensate drain connectionĂ ((((((((((((((((((( 9. Filling the primary circuit and checking the pressureĂ 10. Checking the connections at terminals 5 and 6 11. Switching off the system On/Off switchĂ 12. Checking the security of electrical connections 13. Connection cable ć control unit/electronic boardĂ ((((((( 14. Switching the compressor offĂ (((((((((((((((((((((((((((((((((((((((((((((( M 15. Calibrating the collector temperature sensor (((((((((((((((( 16. Activating the "Natural cooling" functionĂ ((((((((((((((((((((( 17. Activating the remote controlĂ (((((((((((((((((((((((((((((((((((((((((((((( T M 18. Switching on/connecting the main fuseĂ 19. Checking the input terminals and contactorsĂ ((((((((((((((( 20. Setting the program selector to "9" (off) 21. Implementing the installation programĂ (((((((((((((((((((((((((( 22. Checking the sensor connectionsĂ (((((((((((((((((((((((((((((((((((((( 23. Checking pumps and defrost valvesĂ ((((((((((((((((((((((((((((((((( 24. Checking the rotational direction of the mixer motorĂ I I I I I I I I I )& 106 !! Steps $(' !! 5-!! =! )& I T M 25. Checking the anti-freeze concentration in the brine circuitĂ ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( 9 I I T T T M M M 26. Checking the anti-freeze thermostatĂ T M 29. Checking the frost protection sensor on the compressor T M 30. Re-tightening the screws on the solenoid valves I I I I I I I I 9 28. Cleaning the evaporator, weather grille and the condensate drain 31. Aligning the sensorsĂ ((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( T T T T T T T T M M M M M M M M I I I I 32. Connecting compressor 1 to terminal X8.2Ă ((((((((((((((((((( 33. Connecting compressor 2 to terminal X7.2Ă ((((((((((((((((((( ((((((((((((((((((((((((((((( : 34. Checking the heating circuit flow rateĂ 35. Checking the primary circuit flow rateĂ ((((((((((((((((((((((((((((( : 36. Checking the air flowĂ (((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((((( 37. Checking the refrigerant circuitĂ ((((((((((((((((((((((((((((((((((((((((((( 38. Checking the suction gas superheatingĂ ((((((((((((((((((((((((((( 39. Checking the condenser sludge level Ă (((((((((((((((((((((((((((((( 40. Checking the HP control switchĂ (((((((((((((((((((((((((((((((((((((((((( 41. Checking the compressor housing temperatureĂ ((((((((( 42. Setting the control unit parametersĂ (((((((((((((((((((((((((((((((((( 43. Commissioning the DHW cylinder systemĂ ((((((((((((((((((((( 44. Checking the DHW heatingĂ (((((((((((((((((((((((((((((((((((((((((((((((((((( 45.Checking the refrigeration circuit for leaks (see 3.) T M M 46. Repainting the bottom plate with rustproofing paint 47. Checking the heat pump housingĂ ((((((((((((((((((((((((((((((((((((((( 48. Instructing the system user I I (((((((((((((((((((((((((((((((( 27. Checking the flow switchĂ ((((((((((((((((((((((((((((((((((((((((((((((((((((((( 9 107 !! Further details to the individual steps For initial start-up, inspection and maintenance work, remove the front plate unscrew and open the control panel and close or re-install after completion. Observe the operating instructions during the initial start-up of the heat pump. Keeping a service report 0%# #% &% ! !% &!( Please note: You will find these reports in the appendix. Checking the refrigeration circuit for leaks ;%.%%!!-% &. . !"&.( 1. 3%!8 !%. A !%!! %!% #( A 2. "&% !%.% &( 3. ;%.& ( 108 !! Further details to the individual steps $(' Filling the heating system 1. >!" ( 4. B%%&"-%- %.%!( 2. ;%.%!% !%&1!( 5. 3% %!!( 3. 5%&%"%%%& "( Checking the diaphragm expansion vessel and the system pressure Carry out this test on a cold system. 1. /%!" % #" % !%!&& @@( 2. %!% !%&1! -%%" !!%-% &%! #%"!( 4. /&% !. %%!&& &( Only use anti-corrosion additives offered by the heating trade, which have been approved for heat pumps with DHW heating via single-walled heat exchangers (DHW cylinders). Example +% $ #-# %&%%&' ! ! # 3. 3 -%-%& !%&%%% !% !%& 1!( On a cold system the filling pressure must be approx. 0.2Ăbar higher than the static pressure. Max. operating pressure: 4Ăbar. 109 !! Further details to the individual steps $(' Checking the condensate drain connection (type AW) ;%.% " ()-%! " # &( Filling the primary circuit and checking the pressure (type BW) 1. B%!"-%% @5" º;@ ( 3. ;%. * F% !% !%& 1!( 2. ;%.%!"!( The pressure in the primary circuit should be approx.Ă2Ăbar. Connection cable ć control unit/electronics board ;%. * !&% #$###' %!&&% # (7-"% !&%(%( ( Switching the compressor off Single stage heat pump /%# Q($%# % ' Two stage heat pump /%# Q( Q9($% # %'( 110 !! Further details to the individual steps $(' Calibrating the collector temperature sensor 1. +-%%& !%%!!( B Q A A 0# B )& F!Q 2. 3 !&%F!QQ( Q(Q( Q(( 3. ;%%!! -% %!!"( 4. 5%! # Q( Q(( +"! (((((((((((((((((( B 5%( ((((((((((((((((((((( E 0 8 +757 ((((((((((((((((((((( PQRST ABCDE PQRST ABCDE FGHIJ !%( ((((((((((((((((((((((((((((((((((((((((((((((( 1O =%&!( ((((((((((( B +@B+@-% y :(º;-% +0.1 ć0.1 ( & 1 ((((((((((((((((((((((((((( BACK 5. +-%%& !%%!!( 6. 3 !&F!Q! Q( Q(( 7. ;%%!! -% %!!"( 111 !! Further details to the individual steps $(' Activating the "Natural cooling" function A B + >BB >A 1. +-%%& !%%!!( 2. + !-%+(+( +(@>A@( 3. ;%%!! -% %!!"( A 0# B /!-%#.+ Activating the remote control The remote control may be allocated to the heat pump circuit, to mixer circuit 1 or to mixer circuit 2. )&& (((((((((((((((((((((((((((((((((((( C +%* %& (((((((((((((((((((((( AB(((( +@+ @-%y @3@-% > < +& 1 ((((((((((((((((((((((( BACK Checking the input terminals and contactors %&!%E E% !%""!% !%"( ;%.%& "% %! %( ,&8,C 38.- 112 !! Further details to the individual steps $(' Implementing the installation program You will find a comprehensive description relating to all control settings in chapter "Additional information". Configuration prg: active Please set: 1.Rotary selector to OFF 2.Press OK 1. ) % %(%(."% - -% %">>-%(3 %#( The installation program will then start. 2. +%* &&( >M ( 3. Check the sensor temperatures ;%.% ( T%%1!& #"!&." BACK ( ( 4. Carry out a relay test +-%%%&%&% "-% ." ON OFF ( M" ALL -%"( T%%1!& #"!&." BACK ( 5%# &%&" ( 5. Set the date and time ;%&%%&%&% -%."+ -( )& BACK !% &#& # %1!& ( )&O%& %1!& ( 6. Implement system definition For implementation and table, see chapter "Control unit settings". 113 !! Further details to the individual steps $(' Checking the sensor connections Operating instructions ;%.-%%% # ! &(5 %@+ !@( Checking pumps and defrost valves 1. ;%.&% &( 2. >"%!!28 ;%!" %! D5N M#-%!"- !" -%%!$%. #""&" !&'( Please note In systems with a heating water buffer storage unit, the heating flow and heating return temperatures are identical with the buffer storage temperature. 3. >"%!!728 ;%.% %( Air must stream from top to bottom. 4. ;%%!! % ! D5NM #-%%&- %& -% %!%! ( 114 !! Further details to the individual steps $(' Checking the rotational direction of the mixer motor Mixer motor for Viessmann mixers DN 20 to 50 (welded version ć part no. 7450 657, accessory) Change the rotational direction by turning the plug-in connector 180 º. 58 2%"&" %$!&'% 1@>!@ @;@( =1 F8E &&%1% ( Rated voltage: Rated frequency : Power consumption: Protection level: A A )& % 1 9 )0 A A )0 A Torque: Operating time for 90 ºí: 230 VC 50 Hz 4W IP 32 acc. to EN 60529 3 Nm 120 s = C B A = C C A 5!%!! | >!1 ~ ;1 B =1 C =1 115 !! Further details to the individual steps $(' Installation examples %@as delivered condition@%1 ! %-&1!6%& ( ?, ?3 A B B%1!%1!& º( ?, ?3 B A ?3 ?& ?, ?&- A =.% B ?!!- 116 !! Further details to the individual steps $(' Checking the anti-freeze concentration in the brine circuit (type BW) 1. ;%. % D ( You will find reports in the appendix. 2. /&&% !%M ---%!! -% $ .-'( Checking the frost protection thermostat (type WW) 1. +%!% (º;( 2. +%%!!( At a primary outlet temperature of 3 to 4 ºC (for intermediate circuits, 1 to 2 ºC), the heat pump must switch off. 3. 5%%.%- ( At water inlet temperatures (primary flow) above +9 ºC, the flow switch will stop the heat pump earlier than the frost protection thermostat. Checking the flow switch (type WW) 1. +!%!"!! $##!!'% !!#" "&"$ !&'( 5% !"% @7@-%% !"!!$## !!'% !!%#!! % %& ( ,C# #- @@ @@6#- @@ @@"% --%% ( The flow switch must switch off below 50 to 60 % of the set water volume. 2. +%!"!! $##!!'% !!( 117 !! Further details to the individual steps $(' Matching sensors ;!%! !" %-% ! * ( Measure actual temperatures with thermometers and heat transfer paste. During these tests, liquid must circulate through these pipes. You will find a comprehensive description relating to the function "Matching sensor temp." in chapter "Control unit settings". Connecting compressor 1 to terminal X8.2 1. ;#Q(( 2. +%!&@h@ $ '( 3. 2%! $!!1('( 4. ;%.#"% -%%% %&--! -%% ! !#- %!"- ( Connecting compressor 2 to terminal X7.2 (if installed) 1. ;#Q9(( 2. +%!&@s@ $ ' % !&% "@+ !@( 3. 2% ! ( 118 !! Further details to the individual steps $(' Checking the heating circuit flow rate 1. 0#%%! #-%%& - ( 2. / % -%% &! %!! 1( 3. 5%--%!( D5&%% %& !(5%8 %%& %! % "!! % %%&!!( Set values DT: 8 to 12 K at 35 ºC heating flow and 10 ºC ventilation air, brine and water inlet temperature DT: 6 to 10 K at 35 ºC heating flow and 0 ºC ventilation air, brine and water inlet temperature Checking the primary circuit flow rate (type BW and WW) 1. 0#%%! #-!"- ( Carry out this test for the groundwater circuit or the brine circuit (possibly intermediate circuit) subect to the respective heat pump type. 2. / -%%& !%!! 1( Set values for type BW: DT: 3 to 5 K at 35 ºC heating flow and 10 ºC set inlet temperature DT: 2 to 4 K at 35 ºC heating flow and 0 ºC set inlet temperature for type WW: DT: 3 to 5 K at 35 ºC heating flow and 10 ºC water inlet temperature 3. 5%--%!( D5&%% %& !(5%8 ;%&% H %!! H &!!( 119 !! Further details to the individual steps $(' Checking the air flow rate (type AW) 1. /%! D5#-% ( 2. / % -%% &! %!! 1( 3. 5%--% ! D5 &%%(% %%% &$! !&'#. #" #( Set values for type AW106: DT: max. 4.5 K at 35 ºC heating flow and 10 ºC ventilation air temperature DT: max. 3.5 K at 35 ºC heating flow and 0 ºC ventilation air temperature for type AW108/110: DT: max. 6 K at 35 ºC heating flow and 10 ºC ventilation air temperature DT: max. 4.5 K at 35 ºC heating flow and 0 ºC ventilation air temperature for type AW113: DT: max. 10 K at 35 ºC heating flow and 10 ºC ventilation air temperature DT: max. 7 K at 35 ºC heating flow and 0 ºC ventilation air temperature for type AW116: DT: max. 11.5 K at 35 ºC heating flow and 10 ºC ventilation air temperature DT: max. 8.5 K at 35 ºC heating flow and 0 ºC ventilation air temperature 120 !! Further details to the individual steps $(' Checking the refrigerant circuit ĂSafety instructions This work may only be carried out by a refrigeration engineer. 1. >#%&%&% &8 ##U% # #-%%%&-% # º;( &#### % !%.% !& -% &( 2. ;%.%% " %&%&(5%& %.% %&%% "( Checking the suction gas superheating ĂSafety instructions This work may only be carried out by a refrigeration engineer. 1. ;%. * F% &!%&% !( 2. 0% &! %!! 1( Checking the condenser sludge level ĂSafety instructions This work may only be carried out by a refrigeration engineer. 2. 0% &! %!! 1( 1. /( 121 !! Further details to the individual steps $(' Checking the HP control switch /#"%.%%&- %-! #º;$#%&%% 9º;'( 0%!% #!! #"?)-%( The HP control switch has no reset button. For more rapid cooling of the second compressor, the threeĆway changeover valve can be opened manually or the defrost valve (K12) can be briefly started by a relay test (see pageĂ130). Checking the compressor housing temperature 1. +-%%%!! !( 2. =% ! %!%&-% !( The ouside of the housing must neither ice up, nor should it reach temperatures higher than 60 ºC (check with your local refrigeration specialist). Setting the control unit parameters 1. ;%.%& &%# & "%& %& !%!! 1( 2. ;%.%%!! "( 3. /&( T% @+@ %## F%!( You will find information on the subject of "Service level" and regarding the adjustment of control parameters in the "Control unit settings" chapter. Adjust the curve in accordance with the design temperature and your local climatic zone. 122 !! Further details to the individual steps $(' Commissioning the DHW cylinder system B% %-" ( Please note: No further settings are required for the operation of the DHW cylinder, if the system is correctly set up. At the control unit, cylinder temperature, switching times, operating mode, etc., can be set to the individual user requirements. You will find the required steps for setting the control unit under "Control unit settings". Checking the DHW heating 1. =%! %%&- -%/?2" ( 2. 0% &! %!! 1( Checking the heat pump housing +"%%&%%# %%&$#-"' -%!"1# ! &% %!!( Please note The cold pipes in the interior are deliberately left without insulation to be able to utilise all waste heat (e.g. from the compressor). 123 5#%& Diagnostic table Fault message in the display field Cause of fault Check 7 )- $!%' B" ;%.% !!"!%EE E ! %* )%%& %!!"# =6 & %&!%E E6.- * A""" !! 5"!28 !- %! %!" 5%!-% % $- -' )"!!8;%. %!! %# %##!! 7 0"#. $&' 5%"!! %#. %!!" !- 5%%!! !" %#. 7 5% "H!" !!M1 5"!728 M1% 2%% !!-% & %. -%%% !& 5"!28 5% " H!"!!% ;%.& ! %. %- & %.% !"!! +"?)-%% 3% ?) !% #%?)" -% 7 ! --% 7 +"?) ! 124 5#%& Diagnostic table $(' Fault message in the display field Cause of fault Check 79 E)! 5"!728 7 && ;% 5"!28 )".& "!"!! 7 ; ?) ! 7: 5% "! ;%.%! &&%!" !!%.% *! .& " !! ;%.!&& !! 7 %%& ,%%& + "!! %&!! ?& ;%. "!! %&!! 5% " H!% ;%.& ! %. %- & B%%%& 7 B! 5"!728 &!-% !-% & ! 5"!28 B! ! 2%% !! 7 +"?) ! 3% ?) !% #%?)" -% ?)"-%% 2%% !!6%. - ! 125 5#%& Diagnostic table $(' Fault message in the display field Cause of fault Check 7 E)! 5"!728 7 && ;% 5"!28 )".& "!"!! ;%.%! && %!" !!%.% *! . !!" 7 %%& ;%.!&& !! ,%%& + "!! %&!! ?& ;%. "!! %&!! 7 5% " ! 5% " !% ;%.& ! %. %- & 7 B! &!-% ! 5"!728 !-% ! 5"!28 B! % ! 2%% !! B%%%& 2%% !!6%. - 7 ; ?) ! 126 Heat pump DHW cylinder 1 DHW cylinder 2 Mixer 1 Mixer 2 Solar collector *1All System components Normal temperature Reduced temperature Timer/switching times Too warm/too cold Select op. mode Curve Additional sensor Fixed value contr. Fixed temperature Max.contr.temp. Contr. hysteresis Control tolerance Min. op. time Max. op. time Min. compressor off Secondary pump flow Fan flow Primary pump flow Final loading PP press.test after Number of satellites Hours run balance Air defrost Start defrost temp. End defrost temp. Maximum defrost time Max. HP defrost time Min. defrost pause Second heat source Alternative Min. prim. inlet temp. Start delay 2nd ht. src. Restart hysteresis Start delay HP Min. outside temp. Start temp. 2nd HS Electrical blocking Pump ON for 2nd HS Regulated 2nd HS 2nd output Tech. service level System components Normal temperature Reduced temperature Timer/switching times Too warm/too cold Select op. mode Curve Function Additional sensor Max. room temp. dev. Fixed value contr. Fixed temperature Over-temp. load Over-temp. load Max. flow temp. Active range Dead range Period DHW priority 0 # Second Heat source Solar collector Mixer 2 DHW cylinder 2 Mixer 1 System components DHW cylinder temp. Timer/switching times Select op. mode DHW cylinder max. DHW cylinder min. Restart hysteresis Additional sensor DHW priority 2nd heat source 2nd heat source DHW stages 9 DHW cylinder 1 Heat pump 0 Reload DHW cylinder Current loading Priorities Domestic hot water temp. Swimming bath temp. Heating temperature Start-up difference Max. water temperature DHW hysteresis Max. swimming bath temp. Swimming bath hysteresis Max. heating temp. Heating hysteresis 9 / Emergency Reset program menus with grey highlights will only be displayed after the specialist level has been activated (see page 130). System definition (Set SAURER code) Set language Install BUS # Switch relay manually Matching sensor temp. Frost protection limit Signal input Further menu items E and enter code: SATAG Hours run Average operating time No. of starts Fault messages 0 # Ctrl circuit overview (with curve) Set holiday period Set party period Statistics/faults System overview User overview Programming Summer/Winter limit Date and time System parameters Timer/switching times Sensor temperatures Information 5862 241 GB Control unit settings Menu structure overview 127/128 ;& General overview User overview Instr: 01 A:Information B:System parameters C:Programming D:DHW cylinder E:Second heat source F:Emergency reset program m 3" @3 !@ s 3" @+ !@ >!& ?!." /!" >!& ! =." 129 ;& Activating the technical service level Only those settings are described on the following pages, which are the exclusive domain of specialists operating at the technical service level. A code must be entered to access this level. Please note: Incorrect operation at the technical service level by system users will invalidate the warranty. = M" +"! (((((((((((((((((((((((((B 5%( ((((((((((((((((((((((((((((E 0 8 +757 ((((((((((((((((((((((((((((PQRST ABCDE PQRST ABCDE FGHIJ !% ((((((((((((((((((((((((((((((((((((((((((((((((((((((( 1O By activating the technical service level, the menus "Heat pump", DHW cylinder", "Mixer" etc. in the main menu "Programming" will also expand. These additional functions will be described on the following pages. Implementing a relay test The relay test enables all connected devices to be manually switched on and off for the purpose of commissioning or testing. = M" +"! (((((((((((((((((((((((((((B 5%( ((((((((((((((((((((((((((((E +-%"" ((((((((((((((((((((A +"#"!&."x y -%%"-% ." ON OFF ( M" ALL -% ( BACK 01 (((((((((((((((((((((((((((((((( 130 ;& Matching sensor temperatures This function enables sensor deviations caused by cable resistance to be compensated or corrected. Sensors need to be calibrated once. Data is stored even during power failures. = M" +"! (((((((((((((((((((((((((((B 5%( ((((((((((((((((((((((((((((E =%&!( (((((((((((((((((((B 0%! %( )& BACK % & %%&%&% ( +& 1 ((((((((((((((((((((((( BACK Setting the frost protection limit The frost protection of the heating system will be activated as soon as the outside temperature, averaged over a period of six hours, falls below the set temperature value. System characteristics during frost protection: The secondary pump and/or the heating circuit pumps operate. The mixers open the heating circuits, if the flow temperature falls below 20 ºC. = M" +"! (((((((((((((((((((((((((((B 5%( ((((((((((((((((((((((((((((E B! ((((((((((((((((((((((C ;%&%!#" !&+0.5> ć0.5> ( +& 1 ((((((((((((((((((((((((((((((( O 131 ;& Checking signal inputs Using this menu, you can regulate the system and check, in case of faults, whether the cause of the fault has been eliminated. In standard mode, the digital monitoring inputs are pulled "low". They go "high" if faults occur. A changeover to "high" is stored and displayed in the "Information"-"Statistic/Faults" menu. = M" +"! (((((((((((((((((((((((((((B 5%( ((((((((((((((((((((((((((((E +&! (((((((((((((((((((((((((((((((((((((((D +%&%%#"!& x y( 01 (((((((((((((((((((((((((((((((( BACK Implementing a system definition The system type is set in this menu. To access this function, enter the code "SAURER". Select a system from the following tables. = M" +"! (((((((((((((((((((((((((B 5%( ((((((((((((((((((((((((((E B% (((((((((((((((((((((((E +" (((((((((((((((((((((((((((A +" ((((((((((((((((((((((((((((((((((( O The "heating water buffer storage units" listed in the system definition are referred to in the control unit display as "const. temp. storage". = "%"#& !#"!&+ -( = "%"#! #"!&> <( +& 1 ((((((((((((((((((((((((((((((( O 132 ;& Implementing a system definition$(' Type No. of stages System 2 = &" 2 = &"/?2" 2 = &"/?2" /?2" 2 = &"%&" 2 = &"/?2" %& " 9 2 = &"/?2" /?2" %&" 2 / ! && 2 / ! &&/?2" 2 / ! &&/?2" /?2" 2 / ! &&%& " 2 / ! &&/?2" %&" 9 2 / ! &&/?2" /?2" %&" 2 ?&-#& 2 ?&-#&/?2" 2 ?&-#&/?2" /?2" 2 ?&-#&1 2 ?&-#&/?2" 1 2 ?&-#&/?2" /?2" 1 2 ?&-#&11 9 2 ?&-#&/?2" 1 1 2 ?&-#&/?2" /?2" 11 2 ?&-#&%&" No. 133 ;& Implementing a system definition$(' Type 2 ?&-#&/?2" %&" 2 ?&-#&/?2" /?2" %&" 2 ?&-#&1 %&" 2 ?&-#&/?2" 1 %&" 2 ?&-#&/?2" /?2" 1%&" 2 01 2 01/?2" 2 01/?2" /?2" 2 = &" 2 = &"/?2" 2 = &"/?2" /?2" 2 = &"%&" 2 = &"/?2" %&" 9 2 = &"/?2" /?2" %&" 2 / ! && 2 / ! &&/?2" 2 / ! &&/?2" /?2" 2 / ! &&%& " 2 / ! &&/?2" %&" 9 2 / ! &&/?2" /?2" %&" 9 2 ?&-#& 9 2 ?&-#&/?2" 9 2 ?&-#&/?2" /?2" 9 2 ?&-#&1 134 No. of stages System No. ;& Implementing a system definition$(' No. Type Number of stages System 9 2 ?&-#&/?2" 1 9 2 ?&-#&/?2" /?2" 1 9 2 ?&-#&1 1 99 2 ?&-#&/?2" 11 9 2 ?&-#&/?2" /?2" 11 2 ?&-#&%& " 2 ?&-#&/?2" %&" 2 ?&-#&/?2" /?2" %&" 2 ?&-#&1 %&" 2 ?&-#&/?2" 1%&" 2 ?&-#&/?2" /?2" 1%&" : 2 011 : 2 011/?2" : 2 011/?2" /?2" 72 = &" 72 = &"/?2" 72 = &"/?2" /?2" 72 = &"%&" 72 = &"/?2" %& " 9 72 = &"/?2" /?2" %&" 72 / ! && 72 / ! &&/?2" 135 ;& Implementing a system definition$(' Type No. of stages System 72 / ! &&/?2" /?2" 72 / ! &&%& " 72 / ! &&/?2" %&" 9 72 / ! &&/?2" /?2" %&" 72 ?&-#& 72 ?&-#&/?2" 72 ?&-#&/?2" /?2 " 72 ?&-#&1 72 ?&-#&/?2" 1 72 ?&-#&/?2" /?2 " 1 72 ?&-#&11 9 72 ?&-#&/?2" 11 72 ?&-#&/?2" /?2 " 11 72 ?&-#&%&" 72 ?&-#&/?2" %&" 72 ?&-#&/?2" /?2" %&" 72 ?&-#&1 +%&" 72 ?&-#&/?2" 1%&" 72 ?&-#&/?2" /?2" 1%&" 72 01 No. 136 ;& Implementing a system definition$(' Type Number of stages System 72 01/?2" 72 01/?2" /?2" 2 = &"1 2 = &"/?2" 1 2 = &"/?2" /?2" 1 2 = &"1 %&" 2 = &"/?2" 1 %&" 9 2 = &"/?2" /?2" 1%&" 2 / ! &&1 2 / ! && /?2" 1 2 / ! && /?2" /?2" 1 2 = &"1 2 = &"/?2" 1 2 = &"/?2" /?2" 1 2 = &"1 %&" 2 = &"/?2" 1 %&" 9 2 = &"/?2" /?2" 1%&" 2 / ! &&1 2 / ! && /?2" 1 2 / ! && /?2" /?2" 1 No. 137 ;&%!!& Select the required language = M" +"! (((((((((((((((((((((((((((B 5%( ((((((((((((((((((((((((((((E B% (((((((((((((((((((((((((E +&& ((((((((((((((((((((((((((((((((((B +& 1 ((((((((((((((((((((((((((((((( O Setting the operating mode Setting options: Off Reduced Standard Rotary selector BUS BWS (without function) Timer Remote control With the first three operating modes, the heat pump circuit will be operated at a constant temperature, irrespective of any other settings (e.āg. operating mode selector). With the "Rotary selector" setting, the actual mode selected at the operating mode selector is decisive. With the "Timer" setting, the heat pump operates independent of the operating mode selector in accordance with the programmed switching times. With the "Remote control" setting, the actual mode selected at the remote control unit is decisive. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A +& 1 ((((((((((((((((((((((( 138 BACK ?&%&%@+!( @-%% x y."(+%* !& -%%> <."( ?!!& Setting the heating curve The heat pump operates with a curve, which demonstrates the following context: for a modulating system or system with modulating storage unit TR = f (TA ) for a system with heating water buffer storage unit TS = f (TA ) TA Outside temperature TR Heat pump inlet temperature TS Temperature in the heating water buffer storage unit = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@@ ! -%?( ;%&%!-%."S s %!-% ."B b( 5%!!!! -# !" % !\º;º; Hº;( BACK +& 1 ((((((((((((((((((((((( 139 ?!!& Additional sensors 5%%!!"%# &" "-%%&-# &# ( Modulating system +&!8 A 3! 5%"@A@(7 !-#& "@3! @( 5%%@=1(! @!!$ !&'( 3 1 2 Standard or permanent operation 5%%& !%%&-& #"! 1 #"!2(5%!!& !3 4%(5%%&-# &-#"% !(5%!& #& &%!( Reduced operation 5%%& !%%&-& #"! 3 #"!4(5%& !1 2%(>"%!% %&-#&-#% !$! &'(5% !& #& &( 140 4 System with heating water buffer storage unit +&!8 A 1 (& 5%%&%%&- #&-# #"%!! -! %&(2%% @1 (&@&% %&%%&-# &# &! ( ?!!& Additional sensors$(' = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@7 @ F% -% ."> <( +& 1 ((((((((((((((((((((((( BACK Setting the maximum room temperature deviation This menu item is only displayed with modulating systems and when a room temperature sensor has been set up as "Additional sensor" (see page 140). The heat pump is stopped, if the actual room temperature exceeds the set value plus the value set here. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@1(!( (@ F-%." +0.1 ć0.1 ( BACK +& 1 ((((((((((((((((((((((( 141 ?!!& Fixed value control This menu item enables a constant set value for loading the heating water buffer storage unit to be determined. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A After entering "Yes", set the permanent temperature and the switching times. ?&%&%@B1 (@ F-%." YES NO ( +& 1 ((((((((((((((((((((((( BACK Setting the fixed temperature This menu item will only be displayed, if the heat pump has been agreed to operate under fixed value control (see above). = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@B1 !@ F%%%& -#&-%." +1.0 ć1.0 ( BACK +& 1 ((((((((((((((((((((((( 142 ?!!& Setting the maximum control temperature The control unit never lets the set control temperature (flow or return temperature) exceed the maximum value set here. All compressors are immediately stopped, if the control temperature should, nevertheless, rise higher than the set maximum value (e.g. because a consumer is suddenly switched off). = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@=1((!(@ F%! -%." +1.0 ć1.0 ( BACK +& 1 ((((((((((((((((((((((( 143 ?!!& Setting the control hysteresis The control hysteresis defines the working range of the active compressor: TRs $ DTRh As long as the control temperature TR remains within the operational rangeĂ1 of the active compressor, it will be neither switched on nor off. The active compressor will be stopped, if the control temperature rises above TRs + DTRh . The active compressor will be stopped, if the control temperature falls below TRs - DTRh . 53 53 D53% 1 = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ;! $-!' +! ;%" 5 See the chapter "Setting the max. operating time" (page 147). ?&%&%@;(%"@ F%%"-% ." +0.5 ć0.5 ( BACK +& 1 ((((((((((((((((((((((( 144 ?!!& Setting the control tolerance Multi-stage heat pumps Too much heat will be produced if the control temperature exceeds the upper tolerance range 1. Consequently, the heating output must be reduced. As the active compressor has already stopped when the upper control hysteresis was exceeded, but the compressor temperature continued to rise, the next lower compressor becomes the active compressor. More heat will be demanded than can be delivered by the currently active compressor if the control temperature falls below the lower tolerance range 2. Consequently, the heating output must be increased. The next compressor will be started as soon as the active compressor has reached its minimum operating time (see the bottom of this page). 53 53 D53% D53 1 ;! +! ;%" ; 5 2 = M" )&& (((((((((((((((((((((((((((((((((((((( C ?!! (((((((((((((((((((((((((((((((((((((((((((( A ?&%&%@;@ F%-% ." +0.5 ć0.5 ( BACK +& 1 ((((((((((((((((((((((( 145 ?!!& Setting the minimum operating time Multi-stage heat pumps The compressor should, in order to achieve a high efficiency level, operate for a certain minimum length of time. More heat will be demanded than can be delivered by the currently active compressor, if the control temperature falls below the lower tolerance range 1. The next compressor will be started as soon as the active compressor has reached its minimum operating time. The "run-up" of a multi-stage system therefore depends on the minimum operating time, since every compressor must initially run for its minimum operating time. 53 53 D53% ;! +! ;%" 5 1 = M" )&& (((((((((((((((((((((((((((((((((((((( C ?!! (((((((((((((((((((((((((((((((((((((((((((( A ?&%&%@=!(@ F%!& -%." +30s ć30s ( BACK +& 1 ((((((((((((((((((((((( 146 ?!!& Setting the maximum operating time Multi-stage heat pumps The compressor temperature is constantly in operating range 1. It is also slightly too high. The compressor is switched off as soon as the maximum operating time has expired, and the next lower compressor will be activated. The compressor temperature is constantly in operating range 2. This also lies within the lower hysteresis range, but does not reach the set value. Consequently, the heat demand is higher than the output of the active compressor. The next compressor is started after the maximum operating time of the active compressor has expired twice. 53 53 D53% 1 ;! +! ;%" 5 2 = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@=1(!(@ F %1!&-% ." +30s ć30s ( BACK +& 1 ((((((((((((((((((((((( 147 ?!!& Setting the minimum compressor rest time If necessary, this setting should only be corrected upwards (standard setting 15 min) to protect the solid shaft soft starter. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@=(!@ F%! !&-%."9( BACK +& 1 ((((((((((((((((((((((( 148 ?!!& Setting the secondary pump flow The heating water in the secondary circuits must already circulate, when the compressor is started, to safeguard the immediate heat transfer. A > > B D > > C E > > A ?& B ;! C + "!! D + " E B-H "!! = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@B-(!!@ F%--%."9 )( BACK +& 1 ((((((((((((((((((((((( 149 ?!!& Setting the primary pump or fan flow The flow time of the primary pump (type BW, WW) or the fan (typ AW) is required for ensuring that the primary circuit is already circulating, when the compressor is started. A > > B E > > C F > > D G > > A ?& B ;! C + "!! D )"!! E + " F B-H "!! G B-H!" = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@)"!!-@ @B-@ F%- -%."9 )( BACK +& 1 ((((((((((((((((((((((( 150 ?!!& Setting the final loading of the heating water buffer storage unit To ensure that the heating water buffer storage unit is fully loaded, when the system changes over to the standard tariff supply, it is re-loaded once more during the low tariff time with "Final loading". If, for example, 60 minutes is set, the "Final loading" would commence 60 minutes before the changeover to reduced operation (or Off). Preconditions: The actual temperature at the lower storage unit temperature sensor must be lower than the set temperature. The control unit must change over from permanent or standard operation to reduced operation or Off. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@B &@ F % &-%."6 &( BACK +& 1 ((((((((((((((((((((((( Match the discharge time to the storage unit size. Match the heat pump switching times to the changeover times from cheap to standard tariff (only possible for timer-dependent tariff changes implemented by your electricity supplier). 151 ?!!& Setting the primary pump pressure test Type BW The set value determines the amount of time which should lapse, until the flow switch or the brine pressure switch begin to monitor circulation. This enables flow to build up prior to measurements being taken, and safeguards a perfect heat pump start. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@))!(@ F-%."7 Ġ( +& 1 ((((((((((((((((((((((( BACK Number of satellites This menu has no function and should always be set to "0". 152 ?!!& Setting the hours run balance Multi-stage heat pumps The hours run balance determines which compressor is called upon to be part of the active stage, when a heat demand (not storage heating) occurs: Hours run balance: Yes (equal usage of compressors) In case of heat demand, the compressor which has operated the least hours is started first. The compressor which has operated the most hours is shut down first. Hours run balance: No (unequal usage of compressors) In every case, compressor 1 is started first; further heat demand is then covered by switching on compressor 2. Compressor 1 always remains the first compressor. The same applies to the second compressor. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@?#@ -%." YES NO ( BACK +& 1 ((((((((((((((((((((((( 153 ?!!& Setting the air defrost mode Type AW The compressor should always be defrosted with hot gas (through the compressor output). For that reason "Air defrost mode" should always be set to: No". = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ;%.-%%@7 @ @A>@68 ?&%&%@7 @ -%." NO ( +& 1 ((((((((((((((((((((((( BACK Setting the temperature for defrost start Type AW Defrosting starts when: the system has waited for the minimum defrost pause, the actual temperature at the compressor is lower than the "Start defrost temp." set here. As standard, 0 ºC is set up, i. e. at evaporator temperatures below 0 ºC after the defrost pause, the circulation pump is switched off, the heat demand is ignored and defrosting starts. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@+ !(@ F-%." +0.5 ć0.5 ( BACK +& 1 ((((((((((((((((((((((( 154 ?!!& Setting the temperature for defrost end Type AW Defrosting ends, if the set temperature has been exceeded at the compressor. The heating circuit pump is stopped again, the hot gas valve is closed, the liquid gas valve is opened and the fan is started. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@0 !(@ F-%." +1.0 ć1.0 ( +& 1 ((((((((((((((((((((((( BACK Setting the maximum defrost time Type AW Defrosting ends, if the temperature value set for the end of defrosting has not been reached, but the set defrost time has expired. The heating circuit pump is started again, the liquid gas valve is opened, the hot gas valve is closed and the fan is started. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%%@=1( @ F-%."6 &( BACK +& 1 ((((((((((((((((((((((( 155 ?!!& Setting the maximum HP defrost time Type AW The heating circuit pump is stopped, if defrosting has started. The liquid gas valve, the hot gas valve and the fan are only switched, if the pressure switch in the gas pressure pipe has reacted or the time set here has expired. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@=1(?) @ F-%."8 (( +& 1 ((((((((((((((((((((((( BACK Setting the minimum defrost pause Type AW The "Minimum defrost pause" is the minimum amount of time between two defrost phases. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@=( !@ F-%."6 &( BACK +& 1 ((((((((((((((((((((((( 156 ?!!& Setting the second heat source Type BW For type AW, the control unit is preset for operation with a second heat source (dual operating mode). = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@+ %@ F-%." YES NO ( +& 1 ((((((((((((((((((((((( BACK Setting alternative or parallel operation For type BW, this menu item only appears if the menu item "2 nd heat source" has been set to "Yes" (dual operating mode). If only one heat source (heat pump or second heat source) is active, set this option to "Alternative: Yes". If both heat sources are in parallel operation, adjust this option to "Alternative: No". = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@7@ F -%." YES NO ( BACK +& 1 ((((((((((((((((((((((( 157 ?!!& Setting the minimum primary inlet temperature For type BW, this menu item only appears if the menu item "2 nd heat source" has been set to "Yes" and "Alternative: Yes". The heat pump is stopped, if the primary inlet temperature (average over 1 minute) is lower than the value set here (bivalence point). The compressors, fans and the heating circuit pump are stopped, and the second heat source is activated. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%%@=(!!(@ F-%." +0.5 ć0.5 ( +& 1 ((((((((((((((((((((((( BACK Setting the start delay for the second heat source For type BW, this menu item only appears if the menu item "2 nd heat source" has been set to "Yes". The heat pump is stopped, if the actual temperature falls below the "Minimum primary inlet temperature" (bivalence point). The second heat source receives the heating command after the time set here has expired. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@+ " ?+@ F-%."6 &( BACK +& 1 ((((((((((((((((((((((( 158 ?!!& Setting the restart hysteresis For type BW, this menu item only appears if the menu item "2 nd heat source" has been set to "Yes". The actual primary inlet temperature is compared with the "Minimum primary inlet temperature" (bivalence point), plus the hysteresis set here, after the set start delay (see page 160) has expired. The heat pump starts again and the second heat source is stopped, if the primary inlet temperature is higher. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@3%"@ F-%." +1.0 ć1.0 BACK +& 1 ((((((((((((((((((((((( 159 ?!!& Setting the heat pump start delay For type BW, this menu item only appears if the menu item "2 nd heat source" has been set to "Yes". If the heat pump has stopped because the primary inlet temperature is too low (below bivalence point), the primary inlet temperature will only be re-checked after expiry of the start delay. The start delay re-commences prior to the next measurement being taken, if the primary inlet temperature is still too low. 1 5 )"! D5% 3%" 5I !" ! + "%!! -! -* + " % 5 2) ?!! (2Z + % 2 > > > > 3 160 ?!!& Setting the heat pump start delay $(' 1 5]5 5%!%1 %(5%%!! -#!! (5% %-# 1!"% "( 2 5U$5\D5%' 71!"% "%%!!%!" !%1 %!%"(5% %!! "$3' %%!! * ( 3 5% % "% %## % ( = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@+ " ?+@ F-%."6 &( BACK +& 1 (((((((((((((((((((((((((( 161 ?!!& Setting the minimum outside temperature Type BW This menu item is only displayed if "Alternative: No" has been selected. The compressor and the primary pump are stopped, if the average outside temperature over a three hour period falls below the value set here. Both will only be restarted, if the average outside temperature over three hours is higher than the value set here plus restart hysteresis (see page 159), and if there is a demand. 5 5 D5% 2) > ! =( ! 3%" 5 ?!! > > = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@=( !@ F-%." +1.0 ć1.0 ( BACK +& 1 (((((((((((((((((((((((((( 162 ?!!& Setting the switch-on temperature for the second heat source For type BW, this menu item only appears if "2 nd heat source: Yes" has been selected, and if "Alternative: No" has been selected for all types of heat pumps. If the average outside temperature over a three hour period falls below the value set here, the second heat source will be activated and, in case of demand, started after expiry of the start delay for the second heat source. After the start delay for the heat pump has expired the system checks, whether the average outside temperature over a three hour period is higher than the value set here plus stop hysteresis for the second heat source. The second heat source will be stopped if this is the case. If it is not, then the start delay restarts, prior to the outside temperature being scanned again. 5 D5% 5-* -! -* 2) (2Z > ! +!%" ?+ +! ?+ + "?) + " ?+ 5 ?!! + % > > = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@+( ?+@ F-%." +1.0 ć1.0 ( BACK +& 1 (((((((((((((((((((((((((( 163 ?!!& Setting electrical blocking For type BW, this menu item only appears if "2 nd heat source: Yes" has been selected. The second heat source is stopped and blocked, if the menu item "E blocking: Yes" has been selected and the electricity supplier has activated the blocking of your electricity supply. Upon demand, the second heat source will be restarted, if your electricity supplier has removed the E blocking signal (blocking removed). This function has no effect if "E blocking: No" has been selected. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@0#.&@ F -%." YES NO ( +& 1 (((((((((((((((((((((((((( BACK Setting the secondary pump with a second heat source For type BW, this menu item only appears if "2 nd heat source: Yes". This menu item decides, whether the secondary pump is started or stopped when operating with a second heat source. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@)!>A ?+@ F-%." YES NO ( BACK +& 1 (((((((((((((((((((((((((( 164 ?!!& Setting a regulated second heat source For type BW, this menu item only appears if "2 nd heat source: Yes" has been selected. The second heat source is controlled like a second heat pump stage, if in this menu item "Regulated 2 nd HS: Yes" has been selected. The second heat source is always the last stage, without hours run balancing. For heating water buffer storage units, only the upper sensor is taken into consideration. Terminal X8.8 is live as long as the second heat source is active, provided that in this menu item "Regulated 2 nd HS: No" has been selected. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@3& ?+@ F-%." YES NO ( +& 1 (((((((((((((((((((((((((( BACK Activating the second output For type BW, this menu item only appears if "2 nd heat source: Yes" has been selected. Terminal X8.13 is always live as long as the second heat source is active, provided that "2 nd output: Yes" has been selected. = M" )&& ((((((((((((((((((((((((((((((((((((((C ?!! ((((((((((((((((((((((((((((((((((((((((((((A ?&%&%@ !@ F -%." YES NO ( BACK +& 1 (((((((((((((((((((((((((( With setting "2 nd output: Yes", an immersion heater element (DHW cylinder) can not be connected to the control unit. 165 /%-" & Selecting the operating mode Setting options: Timer Off BUS BWS (without function) With the "Timer" setting, the DHW cylinder will be heated independently of the operating mode selector in accordance with the set switching times. With the "Off" setting, the DHW cylinder will not be heated, irrespective of other settings. = M" )&& ((((((((((((((((((((((((((((((((((((((C /?2" (((((((((((((((((((((((((((((((((((((((B ?&%&%@+!( @ %!& -%." > <( +& 1 (((((((((((((((((((((((((( BACK Setting the maximum temperature The threeĆway changeover valve in the heating flow will be changed over to the heating circuits, when the maximum temperature inside the DHW cylinder is exceeded. = M" )&& ((((((((((((((((((((((((((((((((((((((C /?2" (((((((((((((((((((((((((((((((((((((((B ?&%&%%@=1(/?2" @ F-%." +1.0 ć1.0 ( BACK +& 1 (((((((((((((((((((((((((( 166 /%-" & Setting the minimum temperature The minimum temperature prevents the DHW temperature from falling too low inside the DHW cylinder, when frost protection is active. The DHW cylinder is heated up to its minimum temperature plus hysteresis (independent of the selected operating mode), if the actual temperature falls below the minimum temperature level. If the DHW cylinder is equipped with two cylinder temperature sensors, the upper sensor will be used to control this function. = M" )&& (((((((((((((((((((((((((((((((((((((( C /?2" ((((((((((((((((((((((((((((((((((((((( B ?&%&%%@=(/?2" @ F-%." +1.0 ć1.0 ( +& 1 (((((((((((((((((((((((((( BACK Setting the hysteresis The hysteresis defines, at how many Kelvin below the set temperature the heating of the DHW cylinder should begin. Standard setting: 8 K. = M" )&& (((((((((((((((((((((((((((((((((((((( C /?2" ((((((((((((((((((((((((((((((((((((((( B ?&%&%%@?"@ F -%." +1.0 ć1.0 ( +& 1 (((((((((((((((((((((((((( BACK 167 /%-" & Additional sensors If a second cylinder temperature sensor is connected, that sensor must be defined as "Additional sensor: F top" (alternatively "Additional sensor: None". The upper cylinder temperature sensor is used for starting and the lower cylinder temperature sensor for stopping the heating of the DHW cylinder. = M" )&& (((((((((((((((((((((((((((((((((((((( C /?2" ((((((((((((((((((((((((((((((((((((((( B ?&%&%%@7 @ F-%."> <( +& 1 (((((((((((((((((((((((((( BACK Setting DHW cylinder priority "DHW cylinder priority: Yes" As priority, the DHW cylinder will be heated, as soon as a heat demand is signalled. "DHW cylinder priority: No" Upon demand, the DHW cylinder will only be heated if there is no heat demand from the heating circuits. = M" )&& (((((((((((((((((((((((((((((((((((((( C /?2" ((((((((((((((((((((((((((((((((((((((( B ?&%&%@/?2" !"@ F-%." YES NO ( BACK +& 1 (((((((((((((((((((((((((( 168 /%-" & Setting the immersion heater element Enter "2 nd HS: Yes" here, if an immersion heater element (DHW cylinder) should be regulated by the control unit. = M" )&& (((((((((((((((((((((((((((((((((((((( C /?2" ((((((((((((((((((((((((((((((((((((((( B ?&%&%@ ?+@ F-% ." YES NO ( +& 1 (((((((((((((((((((((((((( For the selection "2 nd HS: Yes", the switching times must also be selected for the immersion heater element in the menu "DHW cylinder", "Timer". BACK Selecting the immersion heater element set temperature This menu item is only displayed if in the control unit, an immersion heater element has been defined for the DHW cylinder. In the operating mode "2 nd heat source", the DHW cylinder will be heated by the immersion heater element to the temperature set here. Select the timing for this operating mode after the operating mode "Heat pump on". = M" )&& (((((((((((((((((((((((((((((((((((((( C /?2" ((((((((((((((((((((((((((((((((((((((( B ?&%&%@ ?+@ F% !-%." +1.0 ć1.0 ( +& 1 (((((((((((((((((((((((((( BACK 169 /%-" & Setting the number of compressors In standard setting, the heat pump generally only operates with the first compressor to provide DHW heating. The second compressor may be selected here for DHW heating via a suitably designed storage unit system. = M" )&& (((((((((((((((((((((((((((((((((((((( C /?2" ((((((((((((((((((((((((((((((((((((((( B ?&%&%@+&/?2" @ # #% !-%."+ -( BACK +& 1 (((((((((((((((((((((((((( 170 ;&H%&-%1 Setting a heating circuit with mixer A heating circuit with mixer is only feasible for systems with heating water buffer storage unit. The heating circuit with mixer can be operated in weather-compensated mode or as fixed value control. The heating circuit with mixer can be displayed as "B", "C", "D" or "E". In the following examples, it is described as "C". Selecting the operating mode Setting options: Off Reduced Standard Timer Rotary selector Remote control BUS BWS (without function) With the first three operating modes, the heating circuit with mixer will be operated at a constant temperature, irrespective of any other settings (e.g. operating mode selector). With the "Timer" setting, the heating circuit with mixer operates independent of the operating mode selector in accordance with the set switching times. For the "Rotary selector" setting, the actual mode selected at the operating mode selector is decisive. With the "Remote control" setting, the actual mode selected at the remote control unit is decisive. = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%@+!( @ %!& -%." > <( BACK +& 1 (((((((((((((((((((((((((( 171 ;&H%&-%1 Setting the heating curve The heating circuit with mixer operates with a curve (heating curve), which indicates the relationship between outside temperature and flow temperature. = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%@@ ! -%."?>!( ;%&%!-%."S s %!-% ."B b( 5%!!!! -# !" % !\º;º; º;( +& 1 (((((((((((((((((((((((((( BACK Determine mixer function With this menu you select whether the mixer operates as central heating fixed value controller or as cooling system( = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%@B@ % 1-%."> <( BACK +& 1 (((((((((((((((((((((((((( Activating this function changes the control unit menus. The modified menus are not described in the operating instructions. Please instruct the system user. 172 ;&H%&-%1 Additional sensor If a room temperature sensor is connected to the heating circuit with mixer, that sensor must be defined as "Additional sensor: room sensor" (alternatively "Additional sensor: None"). The additional menu item "Max. room temp. dev." appears if you select "Room sensor". = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%@7 @ F% -% ."> <( +& 1 (((((((((((((((((((((((((( BACK Setting the maximum room temperature deviation This menu item is only displayed when a room temperature sensor has been set up as "Additional sensor". The mixer is closed, if the actual room temperature exceeds the set value plus the value set here. = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%@=1(!( (@ F-%." +0.1 ć0.1 ( BACK +& 1 (((((((((((((((((((((((((( 173 ;&H%&-%1 Setting the fixed temperature This menu item is only displayed, if the heating circuit with mixer has been set up as fixed value control (see page 172). = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%@B1 !@ F-%." +1.0 ć1.0 ( +& 1 (((((((((((((((((((((((((( BACK Setting the load rise The load rise indicates the difference between the flow temperature of the heat pump circuit and the flow temperature of the heating circuit with mixer. "Load rise: No" means, that the heating circuit with mixer operates without feedback to the heat pump. "Load rise: Yes" means, that the heating circuit with mixer sends a heat demand signal to the heat pump control unit. = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%@E @ F-% ." YES NO ( BACK +& 1 (((((((((((((((((((((((((( 174 ;&H%&-%1 Setting the temperature differential for a load rise This menu item will only be displayed, if "Load rise: Yes" has been selected (see above). The flow temperature of the heat pump circuit is higher/lower than the flow temperature of the heating circuit with mixer by the amount set here. = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%@E @ F% ! -%." +1.0 ć1.0 ( +& 1 (((((((((((((((((((((((((( BACK Setting the maximum flow temperature The control unit calculates the flow temperature set value from the curve (heating curve), but never allows it to go higher than the value set here, minus the dead or active range (see page 176). The mixer closes, if the flow temperature should still rise higher than the maximum value set here. = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%%@=1(-!(@ F-%." +1.0 ć1.0 ( BACK +& 1 (((((((((((((((((((((((((( 175 ;&H%&-%1 Setting the active range The active range indicates the range, within which the mixer opens or closes. 3, 5, D5,% D5, A B C C B-! +-! 7& / & 5 A =1!" B =1$ &' C =1D D =1! E =1!"! D E = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%%@7&@ F-%." +0.5 ć0.5 ( +& 1 (((((((((((((((((((((((( BACK Setting the dead range The dead range describes that temperature range, in which the mixer motor is at zero volt (see active range illustration). The mixer motor begins to cycle in accordance with an impulse duration modulation, as soon as the flow temperature falls below or exceeds this range. = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C +& 1 (((((((((((((((((((((((((( 176 BACK ?&%&%%@/ &@ F-%." +0.5 ć0.5 ( ;&H%&-%1 Setting the phase duration The period influences the length of cycle. This does not affect the cycle ratio. The period must match the mixer motor speed. It should be shorter than 1/10 of the mixer operating time. = M" )&& ((((((((((((((((((((((((((((((((((((((C =1 (((((((((((((((((((((((((((((((((((((((((((((((((((((((C ?&%&%@) @ F-% ."7 /( +& 1 (((((((((((((((((((((((((( BACK Setting the DHW cylinder priority This menu item should always be set to "DHW cylinder priority:OFF", so that the heating circuit with mixer will be heated by the heating water buffer storage unit inspite of the need for DHW heating. 177 ;! Phase failure relay E E 7 7 The following deviations are set up in the "as delivered condition": > &8 ^ )%"8 ^ +-%& "8 E 3%%" (3&%" * ( 10 <>U 20 G 11 Asy 2 10 12 14 15 F E Ph D Rel 5 6 A % % 21 B 22 24 12 C Time s 0 A > &^ B )%"#"^ C +-%& " D >! !" E B !"!% !%* F B !"" G B !" & 178 ;! Sensor resistance curve > !!! &! -! 3 5!_; 9 ;! : 9 ? !`; 3 9 179 ;! Fuse The fuse is located in a fuse base on the carrier rail inside the control panel. B8(7, $1(&x(2' A 1. B!!%!( 2. >!%!% & - ( ¨ĂSafety instructions Opening automatically cuts the power. A B% -% % %!!! Central fault indication Heat pump system faults may be displayed optically as central fault messages. The fault display remains active, until the error has been removed. Connection L E !"8,C7 , 7 Q9( Please note: The fault message becomes active 10 seconds after the fault occurs. E ,C A Q9( 180 180 ; -& & Sensor connections and function for different system versions Sensor description p Function in heating mode Terminal code Solar heating mode Natural cooling B > ! Q(( B > ! Q(( B )"- Q(( B )" Q(( B /& B /?) B B9 a /-! Q(( Q(( 3 -%! 3! Q(( Q(( B ?!!- Q(( B: ?!! Q(:(: B ?&-#&! Q(( B ?&-#&# Q(( B B-1 B B-1 B /?2" ! Q(( B /?2" ! Q(9(9 B B9 a /?2" ! ;&- Q(( ;&- Q(:(: 3 -%! 3! Q(( Q(( B /& /-! Q(( B: /?) B ?&-#&! B ?&-#&# Q(9(9 ;%& Q(( Q(( +-&! Q(( B ;! Q(( B 181/182 ; -& & System terminals inside the control panel (230 V~) Function B!%& B!% & B--% 9 0,4% -. + "!! /%&-%$' =1>)0A 9 =1;E>+0 ?&!! : 5% -"%& %$' =1>)0A =1;E>+0 ?&!! 5% -"%& 9 %$' ;&D : ;&D +%&!! Terminal code 183/184 ; -& & Vitocal 300, type AW > 7 Q( Q( Q( Q( Q(: Q( Q( Q( Q( Q( : Q:( Q:( Q( Q( Q9( qR B Q( Q( qT B Q( Q( qZ B: Q(: Q(: qU B Q( Q( M qI B Q( Q( M Q:( Q Q Q M M M Q M9 M: qO B Q( Q( wP B Q(: Q(: M wQ B Q( Q( M9 M M M Q(9 Q(9 6 B B wE wR B B9 B B9 wT wZ 5 M B wU M M M M M M tZ tT tR tE Q( Q(9 Q( Q(: Q( Q( Q( Q( Q9( Q9( Q9(9 Q9( Q9(: Q9( M: Q9( Q9( M Q9( eI eO rP rQ 9 rW rE : rR rT rZ rU rI rO 9 tP tQ : tW M M wW B 185/186 Q( 3 Q9( 2 : qE B Q9( 1 Q:( Q9( L1 L2 L3 PE ) qW B Q( L1 L2 L3 PE Q:( Q( L1 L2 L3 N PE ) Q( Q( Q( 4 ,2 Q( Q( Q( 8 ) qQ B Q( Q( L1 L2 L3 N PE Q( Q( Q( Q( Q( 3 + 5 qP B Q( Q( Q( B 7 Q( Q( 4 Q( Q( Q(9 E E E 9 wIwO 9 Q( Q( M M eZ eU EW eE eR eT Q( eP eQ Q( 7 7 Q( Q( Q( Q( Q(9 B (7- ; -& & Vitocal 300, type AW$(' Connections 3/N/PE~400V 1 =A)0C, 2 ;! 3 B 4 )%"$!' 5 ;# 6 +# 7 )%"$-%& ' 8 +P Analogue inputs 9 ?& & qP > ! qQ )"-! qW )"! qE ?& & qR ?& & qT B-! qZ 3! qU 4!!! %&-#& qI E-! %&-#& qO B-! %&$"' wP B-!% %&$"' wQ E-!/?2 " wW 4!!! /?2" wE 4!!! %&-#& wR E-! %&-#& wT 3$"'( ! *1Only wZ 3$"'( ! wU ;! Digital inputs wI ?!! wO A7 eP R! eQ 0#.& eW M1 eE +"?) eR E-! eT ; ?) eZ ;!-%% " eU )-% Outputs eI +%& !! eO + "!! rP + % rQ =1>)0A rW =1;E>+0 rE ?&!! rR 5%O-"%& rT % rZ =1>)0A rU =1;E>+0 rI ?&!! rO 5%O-"%& tP % tQ ; D tW ; D tE B tR + * & tT + & tZ ;! for types 108, 110, 113 and 116. 187 ; -& & Vitocal 300, type BW Analogue inputs qP > ! qQ )"-! qW )"! qE ;! qR B-! qT 3! qZ 4!!! %&-#& qU E-! %&-#& qI B-! %&$"' qO B-!% %&$"' wP E-!/?2 " wQ 4!!!/?2 " wW 4!!! %&-#& wE E-! %&-#& wR 3$"'( ! wT 3$"'( ! Digital inputs wZ 3%!! 0,4& wU 3%!! 188 wI !-%P wO 0#.&$"' eP 5% "H!" !! eQ +"?)! eW E)! eE ; ?)! eR 5% "H !& eT +"?)! eZ E)! eU ; ?)! eI 5% "H ! Outputs eO +%& !! rP + "!! rQ + %$%& - -%' rW =1>)0A rE =1;E>+0 rR ?&!! rT 5%O-"%& rZ % rU =1>)0A rI =1;E>+0 rO ?&!! tP 5%O-"%& tQ % tW ;&D tE ;&D tR )"!! tT +% ! tZ + * & ! tU ;!& tI + * & ! tO ;!& *1Only for types 108, 110, 113, 116, 216, 220, 226 and 232. *2If not connected, remove the jumper between the terminals 5 and 6. Connections 3/N/PE~400V 1 =A)0C, 2 ;! 3 ;! 4 )"!! 5 )%"$!' 6 ;# 7 +# 8 )%"$-%& ' 9 +P ; -& & Vitocal 300, type BW$(' > 7 wI wO L1 L2 L3 PE L1 L2 L3 PE 1 2 3 4 B Q( Q( qR B Q( Q( qT B: Q(: Q(: qZ B Q( Q( qU B Q( Q( Q( Q( Q(: Q( Q( Q(9 Q( Q( Q( Q( Q( ) : : Q Q M M Q M Q M9 M M: M M Q( Q( qO B Q(: Q(: M Q( Q( wQ B Q(9 Q(9 ) Q:( eT Q:( ) eZ Q:( ) eU eI Q9( M qI B wP B Q:( Q:( M M9 M 7 B B wW wE M Q( Q( Please note: B&% F!#- $% F!%!'( PE Q( Q( ) B B9 B B9 wR wT 6 Q( M M M M: M M M Q( L1 L2 L3 N PE B Q9( 4 , 2 Q( Q( Q9( 4 ,2 9 qE B Q9( 9 qW B Q( Q( Q( L1 L2 L3 N PE 3 + 5 Q( Q( Q( 3 + 5 qQ B Q( 1( N(7 Q( Q( Q( Q( Q( B B qP B Q( Q( Q( 5 7 Q( Q( Q(9 E E E B ) 9 wZwU M Q( Q( M M eR eP eQ EW eE Q( 8 7 Q( Q( Q( Q( Q( B (7- tI Q(9 Q( Q(: Q( Q( Q( Q( Q9( Q9( Q9(9 Q9( Q9(: Q9( Q9( Q9( M Q9( eO rP rQ rW 9 rE rR : rT rZ rU rI rO tP 9 tQ tW : tE M M tO Q( tU tZ tT tR 189/190 ; -& & Vitocal 300, type WW > 7 4 , 2 L1 L2 L3 PE L1 L2 L3 PE 1 2 3 PE 4 PE 5 B Q( Q( B Q( Q( qT B Q( Q( qZ B: Q(: Q(: qU B Q( Q( qI B Q( Q( Q:( ) Q:( Q Q ) eI Q:( ) eO Q(9 Q( M Q Q( M Q(: M Q Q( M9 Q( M Q( M: Q( M Q9( M Q( Q( wP B Q(: Q(: M wQ B Q( Q( wW B Q(9 Q(9 Q9( Q9(9 M M 8 B B9 B B9 wT wZ 7 M Q( M Q9( Q9( M: M Q9( M Q9( rP rQ rW rE rR rT 9 rZ rU : rI rO tP tQ tW tE 9 tR tT : tZ M M M M zE Q9(: M M M Q9( M9 eU Q:( Q9( M qO B wE wR Q( Q( : Q( Q( Q( Q(: Q( Q( Q( M B B 191/192 : Q:( Q( Q( Q( Q( Q( Q( Q( Q( Q( Q( L1 L2 L3 N PE Q( Q( ) eT eZ zW zQ zP tO M tI tU qP qR B ) Q( 3 + 5 qE B Q( Q( Q9( 4 ,2 1( N(7 Q( Q( Q9( qP 1( N(7 qW B Q9( L1 L2 L3 N PE B ) 9 B Q( 3 + 5 B Q( Q( Q( B qQ B Q( 6 7 Q( E E E B B wUwI M Q( M Q( Q( Q(9 M M eQ EW eE eR wO eP Q( 9 7 Q( Q( Q( Q( Q(9 B (7- ; -& & Vitocal 300, type WW$(' Connections 3/N/PE~400V 1 =A)0C, 2 ;! 3 ;! 4 )"!!$' 5 !! $"' 6 )%"$!' 7 ;# 8 ;# 9 )%"$-%& ' qP +P Analogue inputs qQ > ! qW )"-! qE )"! qR +-&! qT B-! qZ 3! qU 4!!&! %&-# & qI E-&! %&-# & qO B-!% %&$"' wP B-!% %&$"' wQ E-!/?2 " wW 4!!!/?2 " wE 4!!&! %&-# & *1Only wR E-&! %&-# & wT 3$"'( ! wZ 3$"'( ! Digital inputs wU 3%!! 0,4& wI 3%!! wO B--% eP 0#.& eQ 5% "!" !! % " !! eW +"?)! eE E)! eR ; ?)! eT 5% "H !& eZ B!%H !P eU +"?)! eI E)! eO ; ?)! rP 5% "H !& eQ B!%H !P for types 108, 110, 113, 116, 212, 216, 220, 226 and 232. jumper when making this connection. *2Remove 193 ; -& & Vitocal 300, type WW$(' Outputs rW +%& !! rE + "!! rR + %$%& - -%' rT =1>)0A rZ =1;E>+0 rU ?&!! rI 5%O-"%& rO % tP =1>)0A tQ =1;E>+0 tW ?&!! tE 5%O-"%& tR % tT ;&D tZ ;&D tU ;!! tI )"!! tO +% ! zP + * & ! zQ ;!& zW + * & ! zE ;!& 194 194 ) Vitocal 300, type AW 9 A 9 : 9 195/196 ) Vitocal 300, type AW $(' When ordering spare parts: Z%"! ($ "!!' %(% * !$!!'( >#!" !!( A 5"!! Parts ;! B " +&%& "H + ?& 9 + 01! B +"?)-% ; ?)-% ?&% E)-% + % /?)-% 9 )%" ;M : 5% " 3.-%>> B% B(,$-' ; 0# ;/ + 9 ;(!!&. /%!! + !(%( 5!! 3! +&-%@ )$%-' : /(%(%!! + !(%( >!& 5% !!., 5% !!", > ! 197 ) Vitocal 300, type BW and WW Parts ;! B " +&%& "H + 01! +"?)-% : ; ?)-% 5%O-"P E)-% + % )%" ;M 71(?A 9 5% "$( (7' 5% " : 3.-%>> B% B(,$-' ; 0# ;/ + ;(!!&. 9 3& B! + !(%( +&-%@ +&-%J@ +&-%K@ ?& *1Only 198 for part nos. 3004Ă307 to 3004Ă312. )$%-' >!& 5% !!., 5% !!", > ! + !(%( A 5"!! B ;!( C ;!( 9 When ordering spare parts: Z%"! ($ "!!' %(% * !$!!'( >#!" !!( ) Vitocal 300, type BW and WW $(' 9 C A P : : : 9 B 9 9 199/200 7!! 1 Commissioning/service reports Actual values Commissioning: Maintenance/ Service 8 #"8 Anti-freeze concentration (brine medium) Maintenance/ Service 8 Maintenance/ Service 8 Maintenance/ Service 8 Maintenance/ Service 8 #"8 #"8 #"8 #"8 Set value º; Heating circuit flow rate ?&-! º; ?&! º; 5! D5 M º; º; OM M ;%. %-& 8 5"!!! ;!!& >-& Air flow rate (type AW) ,! º; 01%! º; 5! D5 M ;%. %-& 8 ?&-! º; 7#! º; + !& ! & Brine flow rate (type BW) ! º; ! º; 5! D5 º; º; M OM M º; º; º; ;%. %-& 8 ?&-! ;!!& 201/202 5"!!! 7!! 1 Commissioning/service reports $(' Actual values Commissioning: Maintenance/ Service 8 #"8 Maintenance/ Service 8 Maintenance/ Service 8 Maintenance/ Service 8 Maintenance/ Service 8 #"8 #"8 #"8 #"8 Set value Groundwater flow rate (type WW) 2! º; 2! º; 5! D5 º; M OM º; º; ;%. %-& 8 ?&-! 5"!!! ;!!& DHW heating /%-" ! º; ?&-! º; ?&! º; Suction gas superheating 5! º; Condenser sludge level ;! ) º; ) &! º; ?&-! º; ;! ) º; ) &! º; ?&-! º; 203/204 7!! 1 Commissioning/service reports $(' Only the parameters applicable to the individual system version will be displayed. Setting parameters Setting range: Standard settings: +- º;\º; º; +&%!" " !& +&% "! "! !& B!%% º;\:º; º; ;!& + >3 B1 + + ! $5 \(º;'\º; º; 3 ! $5 (º;' º; Actual values 8 Actual values 8 Actual values 8 Actual values 8 Actual values 8 System parameters / Heat pump parameters 5-% + 8 ( 3 8 ( +!& 3((((> 3 (+ 5 3" ; +N:6 Nº;º; +N(6Nº; 7 A1" 33( A =1(! (º;º; º; B1 & TA T B1 ! º;$1(!( º;' º; ;!1( º;º; º; ;%"\ º;º; º; ; º;º; º; =!& $1 ' 205/206 5 % 7!! 1 Commissioning/service reports $(' Setting parameters Setting range: Standard settings: =1(!& (!(!& + " B- !! B- B & A# ?#& TA T 7 & TA A Actual values 8 Actual values 8 Actual values 8 Actual values 8 Actual values 8 Heat pump parameters (cont.) /! º; /! º;º; º; =1 =1(?) = ! 7 TA T =(!"!( º;\º; º;\º; º; + " ?+ 3%" º; º; + "%!! = ! º;\º; +! ?+ º;\º; º; º; 0#.& TA T )! ?+ TA T 3& ?+ TA T ! TA A 207/208 7!! 1 Commissioning/service reports $(' Setting parameters Setting range: Standard settings: ;!& >> > +!& 5> 5 7 B! /?2" ! $5\º;'$51 º;' º; /?2" ! 1 $/?2" !( '::º; º; /?2" ! º;$/?2" !( ' º; /?2" %" º;º; º; Actual values 8 Actual values 8 Actual values 8 Actual values 8 Actual values 8 DHW cylinder parameters 5-% ( ( TA T ?+ TA A ?+ º;::º; º; /?2" !" 209/210 7!! 1 Commissioning/service reports $(' Setting parameters Setting range: Standard settings: ;!& + 3 > + + ! $5 \(º;'\º; º; 3 ! $5 (º;' º; 5-% + 8( 3 8 ( Actual values 8 Actual values 8 Actual values 8 Actual values 8 Actual values 8 Mixer parameters 5 % +!& 3(((> 3 (+ 5 3" ; +N:6Nº;º; +N(6Nº; 7 A1" 33( A =1(! (º;º; º; B1 & TA A B1 ! º;º; º; E TA T E º;\::º; º; º;::º; º; 7& º;º; º; / &\ (º;º; º; ) /?2" !" >>3 > =1-! 211/212 7!! 1 Specification Vitocal 300 Type AW 106, 108, 110 5"! Performance data .2 Rated output >!&!72P (0A .2 3&!" .2 )-! )e $;>)' Heat recovery B& 7 =1(!(! !(b1% =(! /& )! !& Heating water $ "' ; =(%&%!P B- 1(-! Electrical values ?!! 3 & 3 $1(' + ! + !$-% ' B$-' ) ; 3 & B$' 2 % ) º; 2 ^ 72 72 72 ( 9( :( (9 (9 ( (: ( ( ( ( ( !!1( !!1(9 !!1( 99 99 99 % # º;$7 ' º;$7 ' ( 7 7 7 A)0C,?D ( ( P 9 ( ( 7 7 1 ( 9 ) (9 : 9(: P ( 1 ,C?D (7?- *1Operating point: A2 = Air inlet temp. = 2 ºC / W35 = Heating water outlet temp. 35 ºC. safeguard the min. throughput. *3Incl. start-up current limiter. *2Always 213 7!! 1 Specification $(' Type AW 106, 108, 110 Vitocal 300 5"! Refrigeration circuit ) B ;! .& "! Dimensions >&% >- % >%&% 99 Max. operating pressure # 3 $' " Operating noise $ ' Weight .& 72 72 39; ( (9 ( ?" ! Connections ?&- 72 214 7!! 1 Specification $(' Vitocal 300 Performance data Rated output >!&!72P (0A 3&!" )-! )e$;>)' Heat recovery B& 7 1(!(! !( b1% =(! /& )! !& Heating water $ "' ; =(%&%!P B- =1(-! Electrical values ?!! 3 & 3 $1(' + ! + !$-% ' B$-' ) ; 3 & B$' Type AW 113, 116 5"! 72 72 .2 ( ( .2 .2 ( ( ( ( ( ( 2 % ) !!1( 99 !!1( 99 ( ( º; 2 ^ % # º;$7 ' º;$7 ' 7 7 7 A)0C,?D ( ( P P :( 9( 7 1 7 ) 1 ,C?D (7?- *1Operating point: A2Ă=ĂAir inlet temp.Ă=Ă2ĂºCĂ/ĂW35Ă=ĂHeating water outlet temp. 35ĂºC. safeguard the min. throughput. *3Incl. start-up current limiter. *2Always 215 7!! 1 Specification $(' Type AW 113, 116 Vitocal 300 5"! Refrigeration circuit ) B ;! .& "! Dimensions >&% >- % >%&% 99 Max. operating pressure # 3 $' @ Operating noise $ ' Weight .& 72 39; ( ( ?" ! 9 Connections ?&- 72 216 7!! 1 Specification $(' Single stage 2 2 2 .2 ( ( ( .2 .2 (9 ( ( ( ( (9 ( ( ( 5"! Rated output >!&! 2 P 3&!" )-! )e$;>)' Brine$!"' ; =(%&%!P B- =1(! =(! % # º; º; (9 : H ( : H ( : H Heating water $ "' ; =(%&%!P B- =1(-! % # º; ( ( ( 9 A)0C,?D (: ( : 9 ( ( ( P ( Electrical values ć heat pump 3 & 3 $1(' + ! + ! $-% ' B$-' ) Electrical values ć control circuit 3 & B$' Type BW 104, 106, 108 7 7 7 7 5"! Max. permissible op. pressure ?&$!"' ?&$ "' # # S ) S ,C?D (7?- 7 Refrigeration circuit ) B ;! *1acc. 39; (9 (: ?" ! .& ( to ENĂ255; B 0Ă=Ăbrine inlet temp.Ă=Ă0ĂºC/W 35Ă=Ăheating water outlet temp. 35ĂºC safeguard the min. throughput. *3Incl. start-up current limiter. Ă Ă *2Always 217 7!! 1 Specification $(' Single stage Type BW 110, 113, 116 2 2 2 .2 ( ( ( .2 .2 ( ( ( ( ( (: (9 ( ( 5"! Rated output >!&! 2 P 3&!" )-! )e$;>)' Brine$!"' ; =(%&%!P B- =1(! =(! % # º; º; (9 9 : H (9 : H (9 : : H Heating water $ "' ; =(%&%!P B- =1(-! % # º; (9 : ( ( A)0C,?D 9(: ( P P ( :( ( P 9( Electrical values ć heat pump 3 & 3 $1(' + ! + ! $-% ' B$-' ) Electrical values ć control circuit 3 & B$' 7 7 7 7 "! Max. permissible op. pressure ?&$!"' ?&$ "' # # S ) S ,C?D (7?- 7 Refrigeration circuit ) B ;! *1acc. 39; ( ( ?" ! .& to ENĂ255; B 0Ă=Ăbrine inlet temp.Ă=Ă0ĂºC/W 35Ă=Ăheating water outlet temp. 35ĂºC safeguard the min. throughput. *3Incl. start-up current limiter. *2Always 218 Ă Ă ( 7!! 1 Specification $(' Two-stage 2 2 2 .2 :( ( ( .2 .2 9( ( ( ( ( ( ( ( ( 5"! Rated output >!&! 2 P 3&!" )-! )e$;>)' Brine$!"' ; =(%&%!P B- =1(! =(! % # º; º; ( : H ( H ( H Heating water $ "' ; =(%&%!P B- =1(-! % # º; ( ( ( A)0C,?D 9( :( : 9 ( ( ( P ( Electrical values ć heat pump 3 & 3 $1(' + !$!!' + !$!!' $-% ' B$-' ) Electrical values ć control circuit 3 & B$' Type BW 208, 212, 216 7 7 7 7 "! Max. permissible op. pressure ?&$!"' ?&$ "' # # .& S ) S ,C?D (7?- 7 Refrigeration circuit ) B ;! *1acc. 39; S(9 S(: S?" ! S( to ENĂ255; B 0Ă=Ăbrine inlet temp.Ă=Ă0ĂºC/W 35Ă=Ăheating water outlet temp. 35ĂºC safeguard the min. throughput. *3Incl. start-up current limiter. Ă Ă *2Always 219 7!! 1 Specification $(' Type BW 220, 226, 232 2 2 2 .2 ( ( ( .2 .2 ( ( (: ( ( (9 ( 9( ( Brine$!"' ; =(%&%!P B- =1(! =(! % # º; º; 9( H :( 9 H :( 9 H Heating water $ "' ; =(%&%!P B- =1(-! % # º; ( : ( ( A)0C,?D ( ( P P ( :( ( P 9( Two-stage 5"! Rated output >!&! 2 P 3&!" )-! )e$;>)' Electrical values ć heat pump 3 & 3 $1(' + !$!!' + !$!!' $-% ' B$-' ) Electrical values ć control circuit 3 & B$' 7 7 7 7 S "! Max. permissible op. pressure ?&$!"' ?&$ "' # # S ) ,C?D (7?- 7 Refrigeration circuit ) B ;! *1acc. 39; S( S( S?" ! .& S( to ENĂ255; B 0Ă=Ăbrine inlet temp.Ă=Ă0ĂºC/W 35Ă=Ăheating water outlet temp. 35ĂºC safeguard the min. throughput. *3Incl. start-up current limiter. *2Always 220 Ă Ă 7!! 1 Specification $(' Single stage Rated output >!&!2 2 P 3&!" )-! )e$;>)' Heating water (secondary) ; =(%&%!P B- =1(-! Groundwater (primary) ; =(%&%!P B- =1(! =(! & - & -^& Electrical values ć heat pump 3 & 3 $1(' + ! + !$-% ' B$-' ) Electrical values ć control circuit 3 & B$' Refrigeration circuit ) B ;! 22 ( 22 ( 22 (: .2 .2 ( ( ( (: ( ( :( (: (9 % # º; ( ( ( 9 % # º; (9 : ( : ( : 9( ( 9( ( 9( ( A)0C,?D ( (: 9 : ( ( S ) ( P ( S 5"! .2 Max. permissible op. pressure -$!"' ?&-$ "' Type WW 104, 106, 108 º; º; 7 7 7 7 ,C?D (7?- 7 .& "! 39; (9 (: ?" ! # # # *1acc. to ENĂ255; W 10Ă=Ăgroundwater inlet temp. *2Always safeguard the min. throughput. *3Incl. start-up current limiter. Ă ( =Ă10ĂºC/W35Ă=Ăheating water outlet temp. 35ĂºC Ă 221 7!! 1 Specification $(' Single stage Rated output >!&!2 2 P 3&!" )-! )e$;>)' Heating water (secondary) ; =(%&%!P B- =1(-! Groundwater (primary) ; =(%&%!P B- =1(! =(! & - & -^& Electrical values ć heat pump 3 & 3 $1(' + ! + !$-% ' B$-' ) Electrical values ć control circuit 3 & B$' Refrigeration circuit ) B ;! 22 ( 22 ( 22 ( .2 .2 (9 ( ( ( ( (: 9( (9 ( % # º; (9 ( ( % # º; (9 9 : (9 9 : (9 : 9( ( 9( ( 9( ( A)0C,?D ( 9(: P P ( :( S ) ( P 9( S 5"! .2 Max. permissible op. pressure -$!"' ?&-$ "' º; º; 7 7 7 7 "! 39; ( ( ?" ! # # # *1acc.ĂtoĂENĂ255;ĂW 10Ă=ĂgroundwaterĂinletĂtemp.Ă=Ă10ĂºC/W 35ā Ă = heating water outlet temp. 35 ºC *2Always safeguard the min. throughput. *3Incl. start-up current limiter. 222 ,C?D (7?- 7 .& Ă ( Type WW 110, 113, 116 7!! 1 Specification $(' Two-stage Rated output >!&!2 2 P 3&!" )-! )e$;>)' Heating water (secondary) ; =(%&-%&%!P ; ! =1(-! Groundwater (primary) ; =(& -%&%!P 0!! =1(! =(! & - & -(^& Electrical values ć heat pump 3 & 3 $1(' + !$!!' + !$!!' $-% ' B$-' ) Electrical values ć control circuit 3 & B$' Refrigeration circuit ) B ;! 22 ( 22 ( 22 ( ( ( ( ( ( ( ( ( (9 % # º; ( ( ( % # º; ( : ( ( 9( ( 9( ( 9( ( A)0C,?D :( 9( 9 : ( ( ( P ( 5"! .2 Max. permissible op. pressure -$!"' ?&-$ "' Type WW 208, 212, 216 .2 .2 º; º; 7 7 7 7 S S ) ,C?D (7?- 7 .& "! 39; S(9 S(: S( S?" ! # # # *1acc. to ENĂ255; W 10Ă=Ăgroundwater inlet temp.Ă=Ă10ĂºC/W 35Ă=Ăheating *2Always safeguard the min. throughput. *3Incl. start-up current limiter. Ă Ă water outlet temp. 35ĂºC 223 7!! 1 Specification $(' Two-stage Rated output >!&!2 2 P 3&!" )-! )e$;>)' Heating water (secondary) ; =(%&-%&%!P ; ! =1(-! Groundwater (primary) ; =(& -%&%!P 0!! =1(! =(! & - & -(^& Electrical values ć heat pump 3 & 3 $1(' + !$!!' + !$!!' $-% ' B$-' ) Electrical values ć control circuit 3 & B$' Refrigeration circuit ) B ;! 22 ( 22 ( 22 ( .2 .2 ( ( ( ( ( (9 ( 9( (9: % # º; ( ( ( % # º; 9( :( 9 :( 9 9( ( 9( ( 9( ( A)0C,?D ( ( P P ( :( ( P 9( 5"! .2 Max. permissible op. pressure -$!"' ?&-$ "' º; º; 7 7 7 7 S "! # # # S ) S ,C?D (7?- 7 .& 39; S( S( S?" ! S( *1acc. to ENĂ255; WĂ10Ă=Ăgroundwater inlet temp.Ă=Ă10ĂºC/WĂ35Ă=Ăheating water outlet temp. 35ĂºC *2Always safeguard the min. throughput. *3Incl. start-up current limiter. 224 Type WW 220, 226, 232 7!! 1 Certificate of conformity for heat pumps 2,2.#?IIbII;/O97 !## "%%! Vitocal 300, type AW and BW incl. CD60 heat pump control unit conform to the following standards: 0A:55 0A: 0A: 0A9 0A 0A 0A55 0A: /A9 /A: /A:9 , /.#%, 7 %(=% This product is identified in accordance with the following guidelines: ::00; :00; 900; as follows: ,2.#?b; !!( )(/(O&(?& 225 7!! 1 226 7!! 1 Index A 7&9 7 /?2" ?!! ?&-%19 7 : 7%&%! 7!9 7!!#" B D 9 -%!! D / &9 /" / /&H /! / / /%.& /-! /?2" & /?2" %"9 /?2" !"99 /?2" /?2%&:: +%&" /?2" H1(!( /?2" H(!(9 /& /%&-%: E 0#.& 0# 0: 0,4% - C ; ;%& ;! ;# ; ;&! ;&$!' ;! ;%.&%&! ; =! A#/?2%&9 ; ; & ; -& & ;!(& ;!: ;: ;! ;&: ;& ;& ; ?&-%19 ?!!: 227 7!! 1 Index $(' G !#9 H ?&!!:9 ?&"&: ?&-#&H & ?&-- ?&- ?!!#.& ?!!%" ?!!! ?!! ?!!!& 19 ?&%!-% ?#& ?) 228 I % : %H !: ! !$!"' ! !& !!: L E&& E 9 M =!- = =1-!9 =9 =1 7&9 ;: / &9 B9 1! 3 O >!& /?2" ?!! ?&-%19 > !$' > !: F B B1 ! ?&-%19 ?!! B1 &9 B )"!! + "!!: B- ?&: )": B--%9 B-!H%& -%19 B-! : B!%9 B!%% B 7!! 1 Index $(' P )!9 ): ) 99 )%"9 )& )" )"!!: )"!!! )": )!%.& R 3& 3& % 3" 3 7 ;: 3%": 3! ?!! ?&-%19 +&! +!! +! + " ?!! + % +&!%& +-&! +" +" % ! +" T 5%( 5!QQ: 5#%& W 2 2 2-%!!9 S +" +# + " + "!!: + "!!-% % + %9 + ! + ;%.& ; =%& =%&! ) !9: +&%1?) 229 ) " " % #% !!( ,E ?- 5 +%!%5B9T) 58 $:'9 B18 $:'9 8 .c( 230 +#F% ,2.#?b; /O97 58$ '9O 518 $ '9O9 ---((
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project