Energy Management
Modular Smart Power Quality Analyzer
Type WM5-96
• MODBUS RTU and TCP, JBUS protocol, iFIX SCADA
compatibility
• Real time clock function (without back-up)
• Up to 12 optional digital inputs (sync function, remote
digital input control)
• Up to 16 optional digital outputs (pulse, alarm, remote
control)
• 16 freely configurable alarms with OR/AND logic linkable with up to 4 relay outputs and up to 16 open collector outputs
• Up to 8 optional analogue outputs (+20mA, +10VDC,
+/- 5mA)
• Universal power supply: 18-60VAC/VDC, 90-260 VAC/VDC
• Front protection degree: IP 65, NEMA4x, NEMA12
• Class 0.2 (current/voltage)
• ARM® powered
• Back-lighted graph display (128x64 dots)
• Bargraph indication of instantaneous power (kW sys)
• Front size: 96x96 mm
• Measurement of single phase and system instantaneous
variables: W, var, VA, PF, VLL, VLN, AL, An, Hz, THD, ASY
VLL, ASY VLN (for all measurements max, min, dmd/AVG
and max dmd/AVG values)
• Measured energies (imported/exported): kWh and kvarh
• Current and voltage inputs with autoranging capability
• 4x4 DGT instantaneous variable read-out
• 4x9 DGT total energies read-out
• 4x9 DGT partial energies read-out
• Energy measurements according to ANSI C12.20, CA 0.5,
EN62053-22 CL 0.5S and ANSI C12.1, EN62053-23 CL 2
• 4 total 3-phase, 48 partial 3-phase and 12 total single
phase independent energy meters to be used as single, dual, multi-time tariff management
• Display refresh rate: 10 time / sec
• Harmonic distortion analysis (FFT) up to the 63rd harmonic
with graphic and numeric indication (current and voltage)
• Harmonics source detection
• Data stamping of up to 10,000 events: alarm, min,
max, digital input status, digital output status as
remote control, resets
• 4 independent communication ports:
optical front communication port (ANSI C12.18)
optional RS 422/485 serial port, optional RS232 + real
time clock function, optional Ethernet port
Product Description
How to order
WM5-96 see next page
How to order
Wm5Soft
3-phase utility grade power
quality analyzer. Particularly
recommended for the measurement of the main electrical variables.
Housing for panel mounting,
with optical communication
port (according to the ANSI
standards), RS485/RS232 or
Ethernet
communication
ports, pulse and alarm outputs. Parameters programming and data reading by
means of Wm5Soft.
Parameters programming and data reading by means of
Wm5Soft.
Modules Combination
Description
WM5-96 base with ANSI local port
WM5-96 base without local port
Power supply (18-60VAC/DC)
Power supply (90-260VAC/DC)
Measuring input (AV5: 400/690VL-L)
Measuring input (AV6: 120/208VL-L)
RS485 port (9 600 bps)
RS485 port (115,200 bps)
Ethernet/Internet port
Analogue output (20mA DC)
Analogue output (10V DC)
Analogue output (+/-5mA DC)
Relay output
Relay output
Open collector output
Open collector output
Open collector output
Digital inputs
Digital inputs + Aux
RS232 port + RTC (9 600 bps)
Part N.
AD2001
AD2000
AP1021
AP1020
AQ2030
AQ2031
AR1034
AR2040
AR1061
AO2050
AO2051
AO2052
AO1058
AO1035
AO1059
AO1036
AO1037
AQ1038
AQ1042
AR1039
Specifications are subject to change without notice
Slot A
Slot B
Slot C
Slot D
2-out
2-out
1-out
2-out
1-out
2-out
4-out
3-in
3-in
2-out
2-out
1-out
2-out
1-out
2-out
4-out
3-in
3-in
Slot E
1-port
1-port
1-port
2-out
2-out
2-out
1-out
2-out
2-out
2-out
1-out
1-out
2-out
4-out
3-in
3-in
1-out
2-out
4-out
3-in
3-in
WM5 96 DS ENG 210708
1-port
1
WM5-96
How to order WM5 96
Minimum modules for a basic unit on grey background
Ordering key (fully assembled instrument):
Description
Ch
WM5 96
Part No.
Legend
AD2001
WM5 96
AD2000
WM5 96
AQ2030
AQ2031
AV5.3
AV6.3
AP1021
AP1020
L
H
XX
E2
D1
D2
O4
O2
O1
R1
B1
W1
B2
AV53 H XX XX XX XX XX
Model
WM5-96 with optical port
ANSI C12.18 type
WM5-96 without optical port
Range code+sys (meas. inputs)
400/690VL-L 1/5A (10A)
120/208VL-L 1/5A (10A)
3
3
4
2
1
1
2
2
2
1
1
AQ1038
AQ1042
AO1037
AO1036
AO1059
AO1058
AO2050
AO2051
AO2052
AR1034
AR2040
None
Digital inputs
Digital inputs + aux
Open collector output
Open collector output
Open collector output
Relay output
Relay output
Analogue output 10VDC
Analogue output +/-5mA
3
3
4
2
1
1
2
2
2
AQ1038
AQ1042
AO1037
AO1036
AO1059
AO1058
AO1035
AO2051
AO2052
None
Digital inputs
Digital inputs + aux
Open collector output
Open collector output
Open collector output
Relay output
Relay output
Analogue output 10VDC
Analogue output +/-5mA
3
3
4
2
1
1
2
2
2
AQ1038
AQ1042
AO1037
AO1036
AO1059
AO1058
AO1035
AO2051
AO2052
1
AR1039
Utility grade with optical port
RS232 + RTC (utility grade)
“Type approval” Canada for further
“Revenue approval” process (*)
RS232+RTC + “XU” option
Utility grade without optical port
RS232 + RTC (utility grade)
without optical port
2
1
AR1039
1
AR1039
B
XX
D1
D2
O4
O2
O1
R1
B1
W1
B2
S1
S2
C
XX
D1
D2
O4
O2
O1
R1
R2
W1
B2
D
XX
D1
D2
O4
O2
O1
R1
R2
W1
B2
Example of which modules to order for:
WM5-96 AV53 H B1 S1 R2 O2 SX
Bill of material
WM5 96
AV53 measuring inputs (400/690VL-L)
90-260VAC/DC power supply
Analogue output 20mA (2 channels)
RS485 serial port 9600 bps
Relay output (2 channels)
Open collector (2 channels)
RS232 port+RTC
A
B
E
Power Supply
XU
SU
YY
SY
C
Ordering No.
AD2001
AQ2030
AP1020
AO2050
AR1034
AO1035
AO1036
AR1039
D
Options(E)
XX
SX
SLOT
None
Digital inputs
Digital inputs + aux
Open collector output
Open collector output
Open collector output
Relay output
Analogue output 20mADC
Analogue output 10VDC
Analogue output +/-5mA
RS485 9600bps
RS485 115200bps
A
SLOT
AR1061
AQ1038
AQ1042
AO1037
AO1036
AO1059
AO1058
AO2050
AO2051
AO2052
SLOT
1
3
3
4
2
1
1
2
2
2
SLOT
None
Ethernet/Internet port
Digital inputs
Digital inputs + aux
Open collector output
Open collector output
Open collector output
Relay output
Analogue output 20mADC
Analogue output 10VDC
Analogue output +/-5mA
OPTIONS
18-60VAC/DC power supply
90-260VAC/DC power supply
SLOT
Power supply
Measuring
Input
(Range+system)
(*) Available only for the assembled meters having the 2 possible
minimum base configuration, respectively made up of:
1. display module + power supply module H + AV5 3 special mode
2. display module + power supply module H + AV6 3 special mode.
Specifications are subject to change without notice
WM5 96 DS ENG 210708
WM5-96
Input specifications
Number of analogue inputs
Current
Voltage
Digital inputs (on request)
AQ1038
Purpose
Contact measuring current
AQ1042
Purpose
Excitation output
Contact measuring current
Common characteristics
Close contact resistance
Open contact resistance
Insulation
Accuracy (display, RS232, RS485)
Current (AL1, AL2, AL3)
(@20°C ±5°C, R.H. ≤75%)
Current (An)
Voltage (@20°C±5°C,R.H.≤75%)
range AV5:
range AV6:
Frequency
Active power and
apparent power
(@ 20°C ± 5°C, R.H. ≤ 75%)
Reactive power
(@ 20°C ± 5°C, R.H. ≤ 75%)
1 (1-phase; system code: 3)
3 (3-phase; system code: 3)
1 (1-phase; system code: 3)
4 (3-phase; system code: 3)
Up to 12
No. of inputs: 3 (voltage-free)
“dmd” measurements
synchronisation.
Tariff selection: energy.
Contact status reading.
Clock synchronisation.
<8mA/ 17.5 to 25VDC
Number of inputs: 3 +
excitation output
“dmd” measurements
synchronisation.
Tariff selection: energy.
Contact status reading.
Clock synchronisation.
16V<+Aux<24VDC Max 15mA
15mA
Max 1kΩ
Min 100kΩ
see “Insulation between
inputs and outputs” table
In: 5A, If.s.: 10A
Un: see voltage ranges below
from 0.05In to Imax:
±(0.2%RDG+2DGT)
from 0.01In to 0.05In:
±(0.5%RDG+2DGT)
±0.5% RDG (0.2 to 2 In)
@ 40 to 100 Hz
400/690VL-L AC
VL-N: 185 V to 460 V
VL-L: 320 V to 800 V
±(0.2%RDG+1DGT)
120/208VL-L AC
VL-N: 45 V to 145 V
VL-L: 78 V to 250 V
±(0.2%RDG+1DGT)
Includes also:
frequency, power supply
and output load influences
±0.1% RDG (40 to 440 Hz)
0.05In to Imax, PF 1:
±(0.5%RDG+1DGT)
0.01In to 0.05In, PF 1:
±(1%RDG+1DGT)
0.1In to Imax, PF0.5L, PF 0.8C:
±(0.6%RDG+1DGT)
0.02In to 0.1In,PF0.5L, PF 0.8C:
±(1%RDG+1DGT)
Energies
(@ 20°C ± 5°C, R.H. ≤ 75%)
Harmonic distortion
(@ 20°C ± 5°C, R.H. ≤ 75%)
Temperature drift
Sampling rate
Display
Display refresh time
Max. and min. indication
Front LED
Measurements
Coupling type
Crest factor
Input impedance
400/690VL-L (AV5)
120/208VL-L (AV6)
Current
Frequency
Overload protection
Continuous voltage/current
For 500ms: voltage/current
Active: class 0.5 according
to EN62053-22, ANSI C12.20
Reactive: class 2 according
to EN62053-23, ANSI C12.1
In: 5A, Imax: 10A
0.1In: 500mA,
Start-up current: 5mA
Un: 400/690VL-L (AV5)
Un: 120/208VL-L (AV6)
1% FS (FS: 100%)
phase: ±2°; Imin: 5mARMS;
Imax: 15Ap; Umin: 30VRMS;
Umax: 500Vp
≤ 200ppm/°C (A/V), ≤300ppm/°C
(all the other measurements)
6400 samples/s @ 50Hz
7680 samples/s @ 60Hz
Graph LCD backlighted
(128x64 dots). Read-out for
the instantaneous variables:
4x4 digit
Total energies: 4x9 digit;
Partial energies: 4x9 digit
100ms
Max. 9999 (999,999,999),
Min. -9999 (–999,999,999)
Red
Blinking light in case of virtual alarm
Fixed light in case of digital
output activation (alarm)
Current, voltage, power,
energy, power factor, frequency, harmonic distortion (see
“Display Pages”). TRMS
measurement of a distorted
wave (voltage/current) .
Direct.
< 3, max 10A peak
1.77 MΩ ±5%
885 kΩ ±5%
≤ 0.01Ω
40 to 440 Hz
(max values)
AV5: 460VLN, 800VLL/10A
AV6: 145VLN, 250VLL/10A
AV5: 800VLN, 1380VLL/36A
AV6: 240VLN, 416VLL/36A
0.1In to Imax,
senϕ 0.5L/C: ±(2%RDG+1DGT)
0.05In to 0.1In, senϕ 0.5L/C:
±(2.5%RDG+1DGT)
0.05In to Imax,
senϕ 1: ±(2%RDG+1DGT)
0.02In to 0.05In,
senϕ 1: ±(2.5%RDG+1DGT)
Specifications are subject to change without notice
WM5 96 DS ENG 210708
3
WM5-96
Output specifications
Analogue Outputs (on request)
Number of outputs
Up to 8 (max 4 x 20mA +
4 x 10VDC or 4 x 20mA +
4 x ±5mA or 8 x 10VDC or
8 x ±5mA)
Accuracy (@ 25°C ±5°C, R.H. ≤60%) ±0.1%FS (20mA or 10VDC)
±0.3%FS (±5mA), FS=10mA
0 to 20mA or 0 to 10 VDC
Range
or ±5mA
Programmable within the
Scaling factor:
whole range of retransmission; it allows the retransmission management of all
values from: 0 and
20 mA, 0 and 10VDC,
or -5mA and +5mA
Response time
≤ 400 ms typical
(filter excluded)
Ripple
≤ 1% (according to
IEC 60688-1, EN 60688-1)
Total temperature drift
≤ 500 ppm/°C
Load:
20 mADC
≤ 350 Ω
10 VDC
≥ 10kΩ
±5 mA
≤ 1400Ω
Insulation
see “Insulation between
inputs and outputs” table
Optical communication port
According to ANSI C12.18
RS422/RS485 port
(on request)
Multidrop
bidirectional (static and
dynamic variables)
Connections
2 or 4 wires, max. distance
1000m, termination directly
on the module
Addresses
1 to 247, selectable by key-pad
Protocol
MODBUS RTU /JBUS,
Data (bidirectional)
Dynamic (reading only)
All display variables (see also
the table, “List of the variables
that can be connected to”...)
All configuration parameters,
Static (writing only)
reset of energy, activation of
digital output
Stored energy (EEPROM)
max. 999.999.999 kWh/kvarh
Data format
1-start bit, 8-data bit, no
parity/even parity,
odd parity, 1 stop bit
Baud-rate
9.6k, 19.2k, 38.4k, 115.2k bit/s
selectable bauds
Insulation
see “Insulation between
inputs and outputs” table
RS232 output (on request)
Bidirectional (static and
dynamic variables)
3 wires, max. distance 15m,
Connections
1-start bit, 8-data bit,
Data format
no parity, even parity,
odd parity, 1 stop bit
Baud-rate
9.6k bit/s
Protocol
MODBUS RTU /JBUS
Other data
as for RS422/485
Ethernet/Internet port
Protocols
IP configuration
TCP port
Client connections
Connections
Digital outputs (on request)
Pulse type
Number of outputs
Type
Pulse duration
Alarm type
Number of outputs
Alarm modes
Set-point adjustment
Hysteresis
On-time delay
Output status
Min. response time
Note
Static (digital) outputs
Purpose
Signal
Insulation
Relay (digital) outputs
Purpose
Output type
Insulation
Electrical life:
Mechanical life:
4
Modbus TCP
Static IP
Selectable (default 502)
Max 5 simultaneously
RJ45 10/100 Base T
Up to 16
Programmable from 0.001 to
1000 pulses per kWh/kvarh
(total and partial)
Outputs connectable to the
total and/or partial energy
meters (Wh/varh)
≥ 100ms, < 120msec (ON),
≥ 100ms (OFF)
according to EN62053-31
up to 16, independent
Up alarm, down alarm, in
window alarm, out window
alarm. All of them can be
used with start up deactivation function and/or latch.
All the alarms can be connected to all variables (see
the table “List of the variables that can be connected
to”).
from 0 to 100% of the
electrical scale
from 0 to full scale
0 to 255s
Selectable; normally
de-energised and normally
energised
≤200ms, filters excluded,
Set-point on-time delay: “0 s”
The 16 digital outputs
can also work as
combination of pulse
outputs and alarm
outputs.
(on request)
For pulse outputs or for
alarm outputs
VON 1.2 VDC/ max. 100 mA
VOFF 30 VDC max.
see “Insulation between
inputs and outputs” table
(on request)
For alarm outputs or for pulse
outputs
Relay SPDT
AC 1-8A, 250VAC
DC 12-5A, 24VDC
AC 15-2.5A, 250VAC
DC 13-2.5A, 24VDC
see “Insulation between
inputs and outputs” table
≥ 105 operations
(@ 8A, 250 V, PF 1)
≥ 30 - 106 operations
Specifications are subject to change without notice
WM5 96 DS ENG 210708
WM5-96
Software functions
Password
1st level
2nd level
System selection
System 1
System 2, unbalanced
System 3, balanced
System 3, unbalanced
Transformer ratio
Filters
Filter operating range
Filtering coefficient
Filter action
Alarms
Working mode
Reset
Numeric code of max 4
digits from 0 to 1000;
2 protection levels of
the programming data
Password “0”: no protection
Password from 1 to 1000:
all data are protected.
1-phase (2 wires)
2-phase (3 wires)
3-phase (3 wires+1CT)
3-phase (3 wires)
3-phase (4 wires)
CT up to 30 kA (6000 max)
VT (PT) up to 600 kV
(6000 max)
0.1 to 100% of the input
electrical scale.
1 to 255
Display, alarms, serial outputs
(fundamental variables:
V, A, W and their derived ones).
Data stamping
Type of data
Number of events
Data management type:
Data storage type
Displaying
Energy meters
Stored events
Display language
Alarm, min, max, digital
input status, digital output
status as remote control,
resets. All events are stored
with date (dd:MM:yy) and
hour (hh:mm:ss) reference
Up to 10,000
FIFO
Data flash
4 variables per page
1 page that can be laid out by
the user
Up to 36 pages
Up to 28 pages depending on
the selected tariff mode. Displaying of the consumed
energy of the previous 12
months.
10,000 events.
Selectable:
English, Italian, French,
German, Spanish
“OR” or “AND” or
“OR+AND” functions (see
“Alarm parameter and logic”
page).
Freely programmable on up
to 16 alarms. The alarms
can be connected to any
variables available in the
table “List of the variables
that can be connected to”
By means of the key-pad or
of the configuration software,
it is possible to reset the
following data:
- all the min, max, dmd,
dmd-max values.
- total and partial counters.
- latch alarms.
- all the events.
Wm5Soft parameter programming and variable reading software
Wm5Soft
Working mode
Multi-language software
(Italian, English, French,
German, Spanish) for
variable reading,
instrument calibration and
parameters programming.
The program
runs under Windows
/98/98SE/2000/NT/XP.
Three different working
modes can be selected:
Specifications are subject to change without notice
Data Storing
Data Transfer
WM5 96 DS ENG 210708
- management of local
RS232 (MODBUS);
- management of local
optical port (MODBUS);
- management of a local
RS485 network (MODBUS);
In pre-formatted XLS files
(Excel data base).
Manual or automatic at
programmable timings.
5
WM5-96
Time period management
Meters
Total
Partial and multitariff
Tariffs
Time periods
Number of periods
Pulse output
Energy meter recording
Energy Meters
Total energy meters
4 (9-digit)
48 (9-digit)
Up to 12
Up to 24 per day
Up to 100 different days per
year
Connectable to total and/or
partial meters (multitariff)
Consumption history by
recording of the monthly
energy meters (12 previous
months). Recording of
total and partial energy
meters.
Energy meter recording
(EEPROM)
Max.999,999,999kWh/kvarh.
Monthly energy meters
Partial energy meters
4 (+kWh, +kvarh, -kWh, -kvarh)
It is possible to divide each
energy meter here above listed
in 3 additional energy meters
(1 for each phase “L1-L2-L3”)
48 (energy meters for
each month: “+kWh, +kvarh,
-kWh, -kvarh”)
16 (using digital inputs:
max 4 tariffs).
48 (using the internal clock:
max 12 tariffs)
Harmonic distortion analysis
Analysis principle
Harmonic measurement
Current
Voltage
Type of harmonics
Harmonic phase angle
6
FFT
Up to the 63rd harmonic
Up to the 63rd harmonic
THD (VL1 and VL1-N)
THD odd (VL1 and VL1-N)
THD even (VL1 and VL1-N)
The same for the other phases:
L2, L3.
THD (AL1)
THD odd (AL1)
THD even (AL1)
The same for the other phases:
L2, L3.
The instrument measures the
angle between the single harmonic of “V” and the single
harmonic of “I” of the same
order. According to the value
of the electrical angle, it is
Harmonic details
System
possible to know if the distortion is absorbed or generated.
Note: if the system has 3
wires the angle cannot be
measured.
The harmonic contents is displayed as a graph showing
the whole harmonic spectrum. This value is also given
as a numerical information:
THD % / RMS value
THD even % / RMS value
THD odd% / RMS value
single harmonics in % /
RMS value
The harmonic distortion
can be measured in singlephase, 3-wire or 4-wire
systems.
Tw: 0.02 sec@50Hz without
filter
Specifications are subject to change without notice
WM5 96 DS ENG 210708
WM5-96
General Specifications
Operating
-10° to +45°C (14° to 113°F)
temperature
(R.H. < 90% non-condensing)
Limit range of operating temp. -20° to +55°C (-4° to 131°F)
(R.H. <90% non-condensing)
Storage temperature
-30° to +60°C (-22° to
140°F)
(R.H. < 90% non-condensing)
Installation category
III
Pollution degree
2
Altitude
up to 2000m (6560 feet) above
sea-level
Insulation reference
voltage
300 VRMS to ground (AV5 input)
Dielectric strength
4kVACRMS (for 1 min)
Noise Rejection
100 dB, 48 to 62 Hz
CMRR
EMC
Emissions
EN61000-6-3, EN60688
residential environment,
commerce and light industry
Immunity
EN61000-6-2
industrial environment.
ANSI/IEEE C37.90-1989
(surge, withstand and fast
transient test)
Pulse voltage (1.2/50µs)
Safety standards
Measurement standards
Approvals
Connections 5(6) A
Housing
Dimensions
Material
Protection degree
Weight
EN61000-4-5
IEC60664, IEC61010-1
EN60664, EN61010-1
IEC60688, EN60688,
EN62053-22, EN62053-23,
ANSI C12.20, ANSI C12.1
CE, cURus and CSA
Screw-type
max. 2.5 mm2 wires (2x 1.5mm2)
Max. screws tighteinig torque:
0.5 Nm
96x96x140 mm
ABS,
self-extinguishing: UL 94 V-0
Front: IP65, NEMA4x,
NEMA12
Approx. 600 g
(packing included)
Supply specifications
AC/DC voltage
90 to 260V (standard)
18 to 60V (on request)
Power consumption
≤ 30VA/12W (90 to 260V)
≤ 20VA/12W (18 to 60V)
Revenue approval settings
• The access to the programming parameters via front key pad and/or serial communication ports is locked.
• The front key pad (up and down keys) allows the displaying of the variables only,
while the communication ports allows the transmission of the variables only.
• A proper “instrument settings” form must be filled up by the user before equipment
supplying.
• WM5-96 is supplied with the desired modules plugged and sealed in the proper slots.
• WM5-96 fulfils:
the ANSI/IEEE C12.20-1998 requirements;
the CAN3-C17-M84 requirements;
and can be certified according to:
C12.20-1998, class 0.5 (independent labs);
AE-0924 Industry Canada Approval.
In this case there are 2 base configurations:
1. display module + measuring input module
AV5 3 + power supply module H.
2. display module + measuring input module
AV6 3 + power supply module H.
Specifications are subject to change without notice
WM5 96 DS ENG 210708
7
WM5-96
Alarm parameters and logic
- Block enable.
- Controlled variable (VLN, ...).
- Alarm type (up, down, window int,
window ext).
- Activation function.
- Latch
- SET 1.
- SET 2.
- ON delay.
- OFF delay
- Logical function (AND, OR).
- Digital output (1 to 16).
ON alarm (SET 1)
In alarm 1 (SET 1)
Off alarm (SET 1)
A, B, C... up to 16
parameter control
blocks.
8
Out alarm 1 (SET 1)
In alarm 2 (SET 2)
(SET 2)
On alarm (SET 2)
OFF alarm (SET2)
Activation of the alarm function
Up alarm
SET 1 > SET 2
Down alarm
SET 2 < SET 1
In windows alarm
In alarm between
SET 1 and SET 2
Out windows alarm with
start up deactivation
In alarm over SET 1 and
below SET 2
Note: any alarm working mode can be linked to the “Activation” function which disables only the first alarm at the power on
of the instrument. All the alarms can be used with the latch function.
AND/OR logical alarm examples:
OR
AND
A: AND
A: AND
A: AND
8
B: AND
B: AND
B: AND
C: AND
C: AND
OR+AND
A: OR
A: OR
B: OR
B: OR
C: OR
C: AND
A: OR
A: OR
B: OR
B: OR
C: OR
C: AND
A: OR
A: OR
B: OR
B: OR
C: OR
C: AND
D: AND
D: AND
C: AND
Specifications are subject to change without notice
D: AND
WM5 96 DS ENG 210708
WM5-96
Function Description
Input and output scaling capability. Working of the analogue outputs (y) versus input variables (x)
Figure A
The sign of measured quantity and output quantity remains the same. The output
quantity is proportional to the
measured quantity.
Figure D
The sign of measured quantity and output quantity remains the same. With the
measured quantity being
zero, the output quantity
already has the value
Y1 = 0.2 Y2.
Live zero output.
0
50 A
100 A
0
50 A
100 A
0
10 mA
20 mA
4
12 mA
20 mA
Figure B
The sign of measured quantity and output quantity
changes simultaneously. The
output quantity is proportional to the measured quantity.
Figure E
The sign of the measured
quantity changes but the one
of the output quantity
remains the same. The output
quantity steadily increases
from value X1 to value X2 of
the measured quantity.
-100 kW
0
100 kW
-5 mA
0
+5 mA
-100 kW
0
Figure C
The sign of measured quantity and output quantity remains the same. On the
range X0...X1, the output
quantity is zero. The range
X1...X2 is delineated on the
entire output range Y0 =
Y1...Y2 and thus presented in
strongly expanded form.
0
100 kW
10 mA
20 mA
Figure F
The sign of the measured
quantity remains the same,
the one of the output quantity
changes as the measured
quantity leaves range X0...X1
and passes to range X1...X2
and vice versa.
80 V
100 V
120 V
0
50 A
100 A
0
5 mA
10 mA
-5 mA
0
+5 mA
Insulation between inputs and outputs
Meas. /digital inputs
Relay
output
Open collec- Analogue out. Analogue out.
tor output
10V, 20mA
±5mA
Meas. /digital
inputs
-
4kV
4kV
2kV
Relay output
4kV
4kV (*)
4kV
Open coll.out.
4kV
4kV
2kV
AR1034
AR2040
AR1039
Power Supply
90-260VAC/DC
Power Supply
18-60VAC/DC
2kV
4kV
2kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV (*)
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV (*)
4kV
4kV
4kV
4kV
4kV
4kV
2kV
4kV
4kV
4kV
200V (**)
4kV
4kV
4kV
4kV
4kV
AR1034
4kV
4kV
4kV
4kV
4kV
-
-
4kV
4kV
4kV
AR2040
2kV
4kV
4kV
4kV
4kV
-
-
4kV
4kV
4kV
AR1039
4kV
4kV
4kV
4kV
4kV
4kV
4kV
-
4kV
4kV
90-260VAC/DC
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
-
-
18-60VAC/DC
4kV
4kV
4kV
4kV
4kV
4kV
4kV
4kV
-
-
Analogue out.
10V, 20mA
Analogue out.
±5mA
NOTE: In case of fault of first insulation the current from the measuring inputs to the ground is lower than 2 mA.
(*) The given insulation is granted among outputs plugged in different slots. The modules equipped with two or four outputs
have therefore non insulation among the outputs. (**) Insulation between the 2 outputs of the same module is 200V for 1 min.
Specifications are subject to change without notice
WM5 96 DS ENG 210708
9
WM5-96
Digital outputs important note
Code
Description
AO1058
1 relay output
Slot A
Slot B
Slot C
Slot D
A0
B0
C0
D0
1 open coll. output A0
B0
C0
D0
A0 A1
B0 B1
C0 C1
D0 D1
AO1036
2 open coll. outputs A0 A1
B0 B1
C0 C1
D0 D1
AO1037
4 open coll. outputs A1 A2 A3 A4 B1 B2 B3 B4 C1 C2 C3 C4 D1 D2 D3 D4
AO1059
AO1035
2 relay outputs
The grey-marked digital outputs are activated for a while during the instrument
start-up, therefore they are not suggested
for pulse output purpose.
Accuracy
kWh, accuracy (RDG) depending on the current
PF=1
kvarh, accuracy (RDG) depending on the current
Error
PF=L0.5
or C0.8
+1.0%
+0.5%
+0.6%
sinϕ=1 Error
+2.5%
+2%
Class 0.5
Class 2
-0.6%
-0.5%
-1.0%
PF=1
PF=L0.5
or C0.8
0.05A
(0.01In)
0.1A
(0.02In)
0.25A
(0.05In)
0.5A
(0.1In)
-2%
-2.5%
5A (In)
10A (Imax)
sinϕ=1
5A (In)
10A (Imax)
sinϕ=0.5
Class 0.5 accuracy limits (Active energy) EN62053-21
5(10A) Start-up current: 5mA
0.1A
(0.02In)
0.25A
(0.05In)
0.25A
(0.05In)
0.5A
(0.1In)
5A (In)
10A (Imax)
5A (In)
10A (Imax)
Class 2 accuracy limits (Reactive energy) EN62053-23
5(10A) Start-up current: 5mA
Used calculation formulas
Phase variables
System variables
Instantaneous effective voltage
Equivalent three-phase voltage
Instantaneous active power
Voltage asymmetry
Instantaneous power factor
A S YLL =
(V L L m a x − V L L m in )
V LL ∑
ASY LN =
(V LN max − V LN min )
V LN ∑
Three-phase power factor
(TPF)
Energy metering
Three-phase reactive power
Instantaneous effective current
Neutral current
Instantaneous apparent power
An = AL1+AL2+AL3
Three-phase active power
Instantaneous reactive power
10
Three-phase apparent power
Where:
i= considered phase (L1, L2 or L3)
P= active power; Q= reactive power;
t1, t2 =starting and ending time points
of consumption recording; n= time
unit;∆t= time interval between two
successive power measurements;
n1, n2 = starting and ending discrete
time points of power recording
Specifications are subject to change without notice
WM5 96 DS ENG 210708
WM5-96
List of the variables that can be connected to:
Analogue outputs (all listed variables with the only exception of energies), alarm outputs (all listed variables with the
only exception of energies), pulse outputs (only energies), communication (all listed variables).
No
Variable
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
V L1
V L2
V L3
V L-N sys
V L1-2
V L2-3
V L3-1
V L-L sys
A L1
A L2
A L3
An
W L1
W L2
W L3
W sys
var L1
var L2
var L3
var sys
VA L1
VA L2
VA L3
VA sys
PF L1
PF L2
PF L3
PF sys
Hz
ASY VL-N
ASY VL-L
THD V1
THD V2
THD V3
THD V1-2
THD V2-3
THD V3-1
THD A1
THD A2
THD A3
THDo V1
THDo V2
THDo V3
THDo V1-2
THDo V2-3
THDo V3-1
THDo A1
THDo A2
THDo A3
THDe V1
THDe V2
THDe V3
THDe V1-2
THDe V2-3
THDe V3-1
THDe A1
THDe A2
THDe A3
Phase seq.
(x) = available
1-phase
system
x
o
o
o
o
o
o
o
x
o
o
o
x
o
o
o
x
o
o
o
x
o
o
o
x
o
o
o
x
o
o
x
o
o
o
o
o
x
o
o
x
o
o
o
o
o
x
o
o
x
o
o
o
o
o
x
o
o
o
2-ph. 3-wire 3-ph. 4-wire 3-ph. 3-wire 3-ph. 4-wire
system
bal. (1 CT)
unbal. sys. unbal. sys.
x
x
o
x
x
x
o
x
o
x
o
x
x
x
o
x
x
x
x
x
o
x
x
x
o
x
x
x
o
x
x
x
x
x
x
x
x
x
x
x
o
x
x
x
x
x
o
x
x
x
x
x
x
x
x
x
o
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
o
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
o
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
o
x
x
x
x
x
x
x
x
x
x
x
x
x
o
x
o
x
x
x
x
x
o
x
x
x
o
x
o
x
o
x
x
x
x
x
o
x
x
x
o
x
x
x
x
x
x
x
x
x
x
x
o
x
x
x
x
x
o
x
x
x
o
x
o
x
o
x
x
x
x
x
x
x
x
o
o
x
x
x
x
x
x
x
x
x
x
x
o
x
x
x
x
o
x
x
x
x
o
x
x
o
x
o
x
x
x
x
o
x
x
x
o
x
x
x
x
x
x
x
x
x
x
x
o
x
x
x
o
x
x
x
Notes
Sys = system = Σ
Sys = system = Σ
An=neutral current
Sys = system = Σ
Sys = system = Σ
Sys = system = Σ
Asymmetry of phase-neutral
Asymmetry of phase-phase
Phase sequence
(o) = not available
Specifications are subject to change without notice
WM5 96 DS ENG 210708
11
WM5-96
Display pages
Display variables in three-phase systems, 4-wire connections
No
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
12
1st variable
2nd variable
3rd variable
Selectable
Selectable
Selectable
V L1
V L2
V L3
V L1-2
V L2-3
V L3-1
A L1
A L2
A L3
W L1
W L2
W L3
var L1
var L2
var L3
VA L1
VA L2
VA L3
PF L1
PF L2
PF L3
V L1
A L1
PF L1
V L2
A L2
PF L2
V L3
A L3
PF L3
V L-L sys
ASY V L-L
Hz
V L-N sys
ASY V L-N
Hz
W sys
var sys
PF sys
THD VL1 tot
THD VL2 tot
THD VL3 tot
THD VL1 odd
THD VL2 odd
THD VL3 odd
THD VL1 even
THD VL2 even
THD VL3 even
THD VL1-2 tot
THD VL2-3 tot
THD VL3-1 tot
THD VL1-2 odd
THD VL2-3 odd
THD VL3-1 odd
THD VL1-2 even
THD VL2-3 even
THD VL3-1 even
THD AL1 tot
THD AL2 tot
THD AL3 tot
THD AL1 odd
THD AL2 odd
THD AL3 odd
THD AL1 even
THD AL2 even
THD AL3 even
Histogram FFT V1 (THD, THDo, THDe, Single harmonic)
Histogram FFT V2 (THD, THDo, THDe, Single harmonic)
Histogram FFT V3 (THD, THDo, THDe, Single harmonic)
Histogram FFT V1-2 (THD, THDo, THDe, Single harmonic)
Histogram FFT V2-3 (THD, THDo, THDe, Single harmonic)
Histogram FFT V3-1 (THD, THDo, THDe, Single harmonic)
Histogram FFT A1 (THD, THDo, THDe, Single harmonic)
Histogram FFT A2 (THD, THDo, THDe, Single harmonic)
Histogram FFT A3 (THD, THDo, THDe, Single harmonic)
Digital input status
Digital output status
Energy meters
Events
Alarms status
Info
Info
Info
4th variable
See note
V L-N sys
V L-L sys
An
W sys
var sys
VA sys
PF sys
W L1
W L2
W L3
An
An
VA sys
Note
kWh + kvarh meters + W% bargraph
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
instant.-min-max-dmd-max dmd
Specifications are subject to change without notice
WM5 96 DS ENG 210708
WM5-96
Wiring diagrams
1-phase, 2-wire input connections (1P)
Fig. 1
I
1
3
5
L1
L2
L3
2
4
6
1
3
5
2
4
6
8
L1
8
7
N
10
L3
L2
9
U
7
10
8
7
1
2
Fig. 2
9 10
L1
N
9
Direct connection
CT connection
2-phase, 3-wire input connections (2P)
Fig. 3
Fig. 4
8
9
7
1
2
3
Fig. 5
4
L1
L2
N
CT and VT connections
CT connection
Direct connection
3-phase, 3 and 4-wire input connections - Balanced load (3P)
Fig. 6
8
9
10
1
Fig. 7
Fig. 8
2
L1
L2
L3
Direct connection (3-wire system)
CT connection (3-wire system)
Specifications are subject to change without notice
WM5 96 DS ENG 210708
CT and VT connections (4-wire system)
13
WM5-96
Wiring diagrams (cont.)
3-phase, 3-wire input connections - Unbalanced load (3P)
Fig. 9
I
1
3
5
L1
L2
L3
2
4
6
1
3
5
2
4
6
8
L1
8
7
N
10
L3
L2
9
U
7
10
8
9
10
1
2
3
4
5
Fig. 10
6
L1
L2
L3
9
CT connection (3-wire system)
Direct connection (3-wire system)
3-phase, 3-wire input connections ARON (3P)
Fig. 11
CT and VT connections (3-wire system)
Fig. 12
ARON connection (3-wire system)
Fig. 13
ARON and VT connections (3-wire system)
3-phase, 4 wires input connections - Unbalanced load (3p+N)
Fig. 14
8
9
10
7
1
2
3
4
5
Fig. 15
Fig. 16
6
L1
L2
L3
N
Direct connection (4-wire system)
14
CT connection (4-wire system)
CT and VT connections (4-wire system)
Specifications are subject to change without notice
WM5 96 DS ENG 210708
WM5-96
Wiring diagrams (optional modules)
DC
DC
AO2050
2 analogue
outputs (0-20mA)
AO2052
2 analogue
outputs (+/-5mA)
AO1051
2 analogue
outputs (10V)
DC
DC
AO1037 4-open collector output connection:
This wiring diagram is valid also for the open
collector module with one or two outputs.
The load resistances (RC) must be designed so
that the close contact current is lower than
100mA; the VDC voltage must be lower than or
equal to 30VDC.
0
SERIAL
CONVERTER
AO1035
2 relay outputs
SERIAL
CONVERTER
AO1058
1 relay output
AR1034/AR2040
4-wire connection of RS485 serial port
AR1034/AR2040
2-wire connection of RS485 serial port
RS422/485 NOTE: additional devices provided with RS422/485 (that is RS 1, 2, 3...N) are connected in parallel. The termination of the serial output is carried out only on the last instrument of the network, by means of a jumper between (RX+) and (T).
Wiring diagrams: digital input modules
AQ1042
Connection by
means of NPN
transistors.
AQ1042
Connection by
means of PNP
transistors.
AQ1042
Connection by
means of contacts.
AQ1038
Connection by
means of contacts.
Specifications are subject to change without notice
WM5 96 DS ENG 210708
15
WM5-96
Front panel description
WM5-96
3
AL
Smart Power Quality Analyzer
Class 0.2 A/V
ARM R Powered
R
2
PRG
1
measures
!
4
S
1. Key-pad
Set-up, programming and display parameters are easily
controlled by the 3 push-buttons.
- S to enter programming and to confirm password.
▲ and ▼
- to program values
- to select functions
- to scroll display pages
2. Display
Instantaneous measurements:
- 4 digits (max display 9999)
Energies:
- 9 digits (max display 999 999 999).
Alphanumeric indications by means of LCD display for:
- Display of configuration parameters
- All measuring variables.
3. LED
Alarm LED.
4. Optical Port
For data reading and programming (or pulse output).
5mm
Dimensions
24mm
16
Specifications are subject to change without notice
WM5 96 DS ENG 210708
WM5-96
Modules
Dual analogue output modules
AO2050
AO2051
(-mA)(+V)
(20mADC)
(10VDC)
AO2052
(+/-5mADC)
(+mA)(-V)
analog (0)
(-mA)(+V) (+mA)(-V)
analog (1)
cd 8010582
Digital output modules
AO1058
Single relay output
AO1035
Dual relay output
AO1059
Single open collector
output
AO1036
Dual open collector
output
Other input/output modules
AO1037
4 open collector
outputs
AQ1038
3 digital inputs
AR1034
AR2040
RS485 port
AQ1042
3 digital inputs + aux
Power supply modules
AR1039
RS232 port + RTC
AP1021
18-60VAC/DC power supply
AP1020
90-260 VAC/DC power supply
Specifications are subject to change without notice
WM5 96 DS ENG 210708