York YCJF24 THRU 60 Troubleshooting guide

Add to My manuals
20 Pages

advertisement

York YCJF24 THRU 60 Troubleshooting guide | Manualzz

®

USER'S

INFORMATION

MANUAL

SPLIT AIR CONDITIONER WITH GAS FURNACE

(602) 943-3426 (520) 292-6858

9828 North 19th Avenue

Phoenix, AZ 85021-1992

4065 East Illinois Street

Tucson, AZ 85714-2106

www.ChasRoberts.com

Important Facts You Should Know About

Your Gas Furnace and Air Conditioner

Gas Furnace

(602) 943-3426 or (520) 292-6858 www.ChasRoberts.com

If You Smell Gas – Call your gas company, at once, from a neighbor’s phone. DO NOT touch any electrical switches or light any flames.

If Smoke Appears – Don’t be alarmed, THIS IS NORMAL, the first time the furnace is started. Your smoke alarms may sound, but they will reset when the smoke clears. The reason this happens is because the factory applies a layer of oil inside the furnace to protect it during shipment. The burners will burn away this oil the first time the furnace is started. The furnace will smoke this one time only.

Before you call for service, check these simple items first:

 Is the furnace plugged in and are the breakers and disconnects turned on?

 Is the thermostat set above the room temperature?

 Is the thermostat switch set in the heat position:

 Is the gas line connected to the furnace? If not, call you builder or plumbing contractor.

 Is the gas manual shut off valve open? The gas valve handle is located just outside the furnace and the handle should be turned parallel with the gas pipe to be on. If it is turned at a right angle, it is off.

 Is the air filter dirty or full of lint? A dirty filter will block needed air flow to the furnace and shut it down prematurely.

• If you have checked all these things, and the furnace still does not operate, CALL your builder or Chas

Roberts Air Conditioning.

• Important, more detailed information on your furnace should be reviewed in your homeowner’s operation and maintenance manual.

Air Conditioner

• During the cooling season, your gas furnace provides air flow for your air conditioning.

• Do Not turn the air conditioning system off. Part-time cooling is poor economy. If the system is left off during the morning, the home will soak up heat and be more difficult to cool in the afternoon. You can actually save money by letting the thermostat determine when cooling is needed.

• During the hot, dry seasons, we recommend keeping the air conditioner blower on continuously. The air conditioning unit cools more evenly when the blower switch is in the ON position. The blower provides refreshing air movement and even temperatures throughout the home. The blower also circulates air through the filter, which helps remove dust, lint and other pollutants more efficiently.

• During the more humid monsoon season, we recommend switching the blower to the AUTO position to help dehumidify the air more efficiently. Check you condensate drain to make sure the moisture being removed from the house is draining properly. The bottom drain outside your house should be dripping and the emergency overflow drain above should be dry.

• Shades, drapes, shutters, or screens should be installed on windows that are exposed to direct sunlight.

Also, plant a tress or put up a canopy to protect your windows from the direct sun.

• For cooling and heating . . . Leave your thermostat alone. When you have found a temperature that you prefer, it is best to leave the thermostat at that setting.

• Clean or replace the filters frequently. Dirty filters will lower performance and efficiency of your cooling.

The filters are usually located at the return grille or at the indoor section of your unit.

USER’S INFORMATION

MANUAL

OUTDOOR SPLIT-SYSTEM

AIR CONDITIONER

MODELS: 13, 14+ SEER SERIES

1 TO 5 TONS

LISTED

ISO 9001

Certified Quality

Management System

TABLE OF CONTENTS

CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

HOW YOUR AIR CONDITIONER WORKS . . . . . . . . . . . . . . . . . . . . . 1

SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

SETTING THE THERMOSTAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Fan Operation Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

MANUAL CHANGE-OVER THERMOSTAT . . . . . . . . . . . . . . . . . . 2

ELECTRONIC THERMOSTAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

TO MAXIMIZE OPERATING EFFICIENCY . . . . . . . . . . . . . . . . . . . . . 2

HEATING CONSERVATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

COOLING CONSERVATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

CARE OF SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

COIL CARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

CARE OF FAN MOTORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

FILTER CARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

OUTDOOR UNIT FINISH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

POWER INTERRUPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Heating Season . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Cooling Season . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

SERVICE CALLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

PARTS INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

CONTACT INFORMATION

• Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.

• Contact us by mail:

Johnson Controls Unitary Products

Consumer Relations

5005 York Drive

Norman, OK 73069

This high efficiency air conditioning system has been precision engineered, manufactured of high quality materials, and passed many rigorous tests and inspections to ensure years of satisfactory service. That’s why you can rely on efficient, trouble-free operation.

Your system is fully automatic. Set the thermostat and forget it. And it’s automatically protected from damage by voltage fluctuations or excessive heating or cooling demands.

Your split system air conditioner consists of two units - one installed outdoors and one installed indoors. The indoor unit may be installed in a basement, attic, or crawl space.

HOW YOUR AIR CONDITIONER WORKS

If your hand is wet and you blow on it, it feels cool because some of the moisture is evaporating and becoming a vapor. This process requires heat. The heat is being taken from your hand, so your hand feels cool.

That’s what happens with an air conditioner. During the cooling cycle, your system will remove heat and humidity from your home and will transfer this heat to the outdoor air.

SYSTEM OPERATION

Your thermostat puts full control of the comfort level in your home at your fingertips. DO NOT switch your thermostat rapidly “On” and “Off” or between “Heat” to “Cool” This could damage your equipment. Always allow at least 5 minutes between changes.

SETTING THE THERMOSTAT

Although thermostats may vary widely in appearance, they are all designed to perform the same basic function: to control the operation of your air conditioning or heat pump system. Regardless of size or shape, each thermostat will feature a temperature indicator; a dial, arm, or push button for selection of the desired temperature; a fan switch to choose the indoor fan operation; and a comfort switch for you to select the system mode of operation.

Only approved thermostats have been tested and are fully compatible with this equipment. Please be aware that many different thermostats operate on batteries or “power stealing” principals. These types of thermostats can not be supported as trouble free when used with this product.

A complete operating instruction is provided by the manufacturer for each thermostat. Familiarize yourself with its proper operation to obtain the maximum comfort with minimum energy consumption.

If your system has been designed to allow both cooling and heating operation, you may have either a manual change-over type, or a programmable electronic type thermostat.

Manual change-over simply means that the comfort switch must be manually positioned every time you wish to switch from the cooling to heating or heating to cooling modes of operation.

The computerized electronic thermostat is actually a sophisticated electronic version of a manual change-over type. This thermostat includes features which allow “set-back” temperature variations for periods of sleep, or while you are away during the day, and means energy savings for you. The thermostat also features a digital clock.

The main power to the system must be kept “ON” at all times to prevent damage to the outdoor unit compressor. If necessary, the thermostat control switch should be used to turn the system

“OFF”. Should the main power be disconnected or interrupted for 8 hours or longer, DO NOT attempt to start the system for 8 hours after the power has been restored to the outdoor unit. If heat is needed during this 8 hour period, use emergency heat.

126114-UUM-I-0608

126114-UUM-I-0608

Fan Operation Selection

A multi-position fan switch allows you to choose the type of fan operation of the indoor fan.

AUTO - With the thermostat fan switch set to “AUTO”, the fan will run intermittently as required for either heating or cooling. This position will provide the lowest operating cost. If you purchased one of our thermostats, they have an Intelligent fan mode which continually circulates the air during occupied modes or when you are at home, and can cycle the fan during unoccupied mode or during the night while you sleep to further conserve energy.

ON - If the fan switch is set to “ON”, the indoor fan will not shut off. However, the system will still operate as required by room temperatures.

This provides continuous air filtering and more even temperature distribution throughout the house, which is especially useful in houses with basements.

Usually during spring and fall, when neither heating nor cooling is required, you may want to run only the fan to ventilate, circulate, and filter the air in your home or building. Set the comfort control switch to

“OFF” and the fan switch to “ON”. Be sure to return the switches to their original positions for normal operation.

MANUAL CHANGE-OVER THERMOSTAT

COOLING YOUR HOME: With the comfort control switch in the

“COOL” position, the system will operate as follows: When the indoor temperature rises above the level indicated by the temperature adjustment setting, the system will start. The outdoor unit will operate and the indoor fan will circulate cool, filtered air. When the room temperature is lowered to the setting selected, the system will shut off.

HEATING YOUR HOME: If your system includes a heating unit and the comfort control switch is in the “HEAT” position, the system will operate as follows: When the indoor temperature drops below the level indicated by the temperature adjustment setting, the system will start. The heating system will operate and the indoor fan will circulate warm, filtered air. When the room temperature rises to the setting selected, the system will shut off.

Whether heating or cooling, the fan will continue to operate if the fan switch was set in the “ON or Intelligent” position. The “AUTO” setting on the fan switch will allow the fan to shut off when your system does.

ELECTRONIC THERMOSTAT

The computerized electronic thermostat, when programmed, will function automatically to operate the system as follows: When the indoor temperature rises above the higher (COOL) setting, the outdoor unit will operate and the indoor fan will circulate cool, filtered air. When the room temperature is lowered to the selected level, the system will shut off.

When the indoor temperature drops below the lower (HEAT) setting, the heating system will operate, and the indoor fan will circulate the warm, filtered air. When the indoor temperature rises to the selected setting, the system will shut off. The indoor fan will either shut off or run continuously, depending upon your choice of fan switch setting.

TO MAXIMIZE OPERATING EFFICIENCY

HEATING CONSERVATION

For the most efficient operation, keep storm windows and doors closed all year long. They not only help insulate against heat and cold, but they also keep out dirt, pollen, and noise.

Closing drapes at night, keeping fireplace dampers closed when not in use, and running exhaust fans only when necessary will help you to retain the air you have already paid to heat.

Keep lamps, televisions, or other heat producing sources away from the thermostat. The thermostat will sense this extra heat and will not be able to maintain the inside temperature to the desired comfort level.

COOLING CONSERVATION

To comfortably cool your home, your air conditioner must remove both heat and humidity. Don’t turn your system off even though you will be away all day. On a hot day, your system may have to operate between 8 to 12 hours to reduce the temperature in your home to a normal comfort level.

Keep windows closed after sundown. While the outdoor temperature at night may be lower than indoors, the air is generally loaded with moisture which is soaked up by furniture, carpets, and fabrics. This moisture must be removed when you restart your system.

The hotter the outside temperature, the greater the load on your system. Therefore do not be alarmed when your system continues to run after the sun has set on a hot day. Heat is stored in your outside walls during the day and will continue to flow into your home for several hours after sunset.

Use your kitchen exhaust fan when cooking. One surface burner on

“HIGH” requires one ton of cooling. Turn on your bathroom exhaust fan while showering to remove humidity. However, exhaust fans should not be run excessively. It would decrease efficiency by removing conditioned air.

You can also help your system in the summer by closing drapes or blinds and by lowering awnings on windows that get direct sunlight.

CARE OF SYSTEM

IMPORTANT: The owner/user should not attempt to disassemble the equipment nor perform periodic maintenance unless they are experienced and qualified to do so.

A periodic inspection, cleaning, lubrication, and adjustment of your heat pump is available from your dealer. Be sure to ask him about this service.

For those who prefer to do-it-yourself, follow the instructions below to care for your system.

COIL CARE

Keep the outdoor unit free of loose snow, foliage, grass clippings, leaves, paper, and any other material which could restrict the proper air flow in and out of the unit. The coil may be vacuumed to remove any debris from between the fins. However, don’t knock ice off the outdoor unit’s coil surface following an ice or severe snowstorm. The blows could mash the coil fins shut (blocking air passage), or break the refrigerant tubing allowing the refrigerant to escape.

If the coil becomes excessively dirty, turn the main disconnect switch to

“OFF” and wash the coil with your garden hose. Avoid getting water into the fan motor and control box. Flush dirt from base pan after cleaning the coil.

CARE OF FAN MOTORS

Some fan motors are provided with lubrication ports. Inspect your indoor and outdoor units to determine whether or not lubrication ports are provided.

The fan motor is shipped with an oil supply which will last for several years under normal operating conditions. After this time, each motor bearing should be oiled with 10-15 drops (approximately 1/4 teaspoon) of SAE 20 non-detergent electric motor oil or automobile oil. DO NOT use definite purpose oils such as sewing machine, cleaning, rust preventative, cutting, household, etc.

SCHEDULE FOR RELUBRICATION

Running Hours

Per Day Normal

Environment

0-8 Every 5 Yrs.

Dirty

Every 4 Yrs.

9-16

17-24

Do not over oil

Every 4 Yrs.

Every 3 Yrs.

Every 3 Yrs.

Every 2 Yrs.

2 Johnson Controls Unitary Products

126114-UUM-I-0608

If your system is an add-on type, (installed in conjunction with a standard furnace) inspect your furnace blower motor and care for it in the same way.

FILTER CARE

Inspect the air filter(s) at least once a month. If they are dirty, wash reusable filters with a mild detergent per manufacturer’s recommendations. Replace disposable filters with new filters.

Install the clean filters with “air flow” arrow in the same direction as the air flow in your duct. Filters should be clean to assure maximum efficiency and adequate air circulation. Drapes, furniture or other obstructions blocking your supply and return air grilles will also decrease efficiency.

OUTDOOR UNIT FINISH

If you wish to maintain the finish of the outdoor unit, it can be polished with car wax. It is recommended the unit be cleaned with soap and water prior to waxing.

PROBLEM

No Heat or

Cooling

Wet on Floor or in Furnace

CHECK

1. Thermostat for proper settings.

TROUBLESHOOTING GUIDE

ACTION TO TAKE

Set thermostat to proper setting.

2. Circuit breakers and fuses.

3. Check outdoor unit for dirty coil (Cooling).

Reset circuit breakers - Replace blown fuses.

Clean coil, see “COIL CARE” section.

4. Outdoor unit for snow accumulation. (Heating).

Remove loose snow only.

5. Indoor unit for dirty filter (Heating).

Clean or replace, see “FILTER CARE” section.

6. Emergency heat light status on thermostat.

Light on = Malfunction

Light flashing = Malfunction

Check 1 - 5, call qualified service person.

Check 1 - 5, call qualified service person.

Check 1 - 5, call qualified service person with fault code.

Condensate drain and “P” trap Remove blockage, usually mold or fungus.

CLEARANCES

The minimum clearances shown below must be maintained should any patio or yard improvements be done around the outdoor unit.

Top

Coil Side

Access

Fan Side

Vertical Discharge Horizontal Discharge

60” N/A

6”

18”

N/A

6”

24”

6”

POWER INTERRUPTION

When ice, snow, wind storms, etc. disrupt electrical power supply to your house, proceed as follows:

Heating Season

1.

Switch thermostat to emergency heat.

NOTE: There will be no heat available until power is re-established.

2.

Leave on emergency heat for at least 8 hours after electrical power is re-established if the power was off more than 8 hours.

3.

Switch thermostat back to heating or auto.

FAULT CODE

-

2

-

-

3

2

-

2

-

Cooling Season

1.

Switch thermostat to OFF position.

2.

Do not switch to cooling or auto until electrical power has been reestablished for 8 hours if the power was off more than 8 hours.

SERVICE CALLS

There are a few instances where you can avoid unnecessary service calls. (See Troubleshooting Guide above). Some models provide fault codes. The flashing light on the system thermostat is capable of providing you with time and money saving information. The fault code numbers listed can be handled by taking the corrective action indicated. Call qualified service person if displaying fault code numbers not listed.

PARTS INFORMATION

Replacement parts are available from local contractor/dealers or the nearest distribution center.

Johnson Controls Unitary Products 3

The Most Com fort able Call You Can Mak e!

Chas Roberts Air Conditioning is proud to be a family owned and operated business, serving Arizona since

1942.

As your HVAC system Installer, we can provide you with services to meet all of your Heating and Air

Conditioning needs after you have taken possession of your new home:

• Sales

• Service & Repair

• Extended Warranties

• Preventative Maintenance

We are available to speak with you Monday-Friday

7am to 8pm, Saturday 7am to 5pm, and Sunday 9am to 4pm with extended hours during the summer.

Please call, or visit our website, with all of your

HVAC questions or concerns.

(602) 943-3426 or (520) 292-6858 www.ChasRoberts.com

ROC19133 ROC069769 ROC073706

Limited Warranty

UPG warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace any parts that prove to have such defects according to the terms outlined on this warranty. This warranty covers only the equipment described by the Product

Model Number and Serial Number listed on the Warranty Registration Card.

For your benefit and protection, return the Warranty Registration Card to UPG promptly after installation. This will initiate the warranty period and allow us to contact you, should it become necessary. In the absence of a recorded Warranty Registration Card, the warranty period will begin upon product shipment from

UPG.

This warranty extends only to the original consumer purchaser and is non-transferable. For this warranty to apply, the product must be installed according to

UPG recommendations and specifications, and in accordance with all local, state, and national codes; and the product must not be removed from its place of original installation. The warranty period for repair or replacement parts provided hereunder shall not extend beyond the warranty period stated below.

CONDENSING UNITS

1

COMPRESSOR CONDENSING UNITS

H*RD, H*BD, ERCS, AC13, H*ZD, CCBD,

LCBD, TCGD, GCGD, AY,

YCHD, YCJD, CCJD, LCJD

H*RE, FRCS, H*BE, TCGF, YCJF, CCJF, LCJF

5 yrs

10 yrs

10 yrs

PARTS

5 yrs

5 yrs

5 yrs

1.

All 3 phase condensing units have 5-year compressor and 1-year parts (Model Numbers with 25/46 or T/W voltage codes).

UPG strongly recommends regular periodic preventative maintenance on this equipment. The person most familiar with the equipment in your HVAC system is a UPG dealer. The UPG dealer can ensure your maintenance program meets the conditions of the "UPG Warranty", maximize the efficiency of the equipment, and service your unit within the mandated guidelines with regard to unlawful discharge of refrigerants into the atmosphere.

This warranty applies only to products installed in the United States and Canada.

EXCLUSIONS

This warranty does not cover any:

1.

Shipping, labor, or material charges.

2.

Damages resulting from transportation, installation, or servicing.

3.

Damages resulting from accident, abuse, fire, flood, alteration, or acts of God (tampering, altering, defacing or removing the product serial number will serve to void this warranty).

4.

Damages resulting from use of the product in a corrosive atmosphere.

5.

Damages resulting from inadequacy or interruption of electrical service or fuel supply, improper voltage conditions, blown fuses, or other like damages.

6.

Cleaning or replacement of filters.

7.

Damages resulting from failure to properly and regularly clean air and/or water side of condenser and evaporator.

8.

Damages resulting from: (I) freezing of condenser water or condensate; (II) inadequate or interrupted water supply; (III) use of corrosive water; (IV) fouling or restriction of the water circuit by foreign material or like causes.

9.

Damages resulting from operation with inadequate supply of air or water.

10.

Damages resulting from use of components or accessories not approved by UPG (vent dampers, etc.).

11.

Increase in fuel or electric cost.

THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABIL-

ITY AND FITNESS FOR A PARTICULAR PURPOSE.

SOME STATES DO NOT ALLOW THE DISCLAIMER OF IMPLIED WARRANTY, SO THAT THE ABOVE DISCLAIMER MAY NOT APPLY TO YOU.

SOME STATES ALLOW ONLY A PARTIAL LIMITATION ON IMPLIED WARRANTIES TO LIMIT THE DURATION OF IMPLIED WARRANTIES TO THE DURA-

TION OF THE EXPRESS WARRANTY. IN SUCH STATES, THE DURATION OF IMPLIED WARRANTIES IS HEREBY EXPRESSLY LIMITED TO THE DURA-

TION OF THE EXPRESS WARRANTY ON THE FACE HEREOF.

IN NO EVENT, WHETHER AS A RESULT OF BREACH OF WARRANTY OR CONTRACT, TORT (INCLUDING NEGLIGENCE) STRICT LIABILITY OR OTH-

ERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE OF

THE EQUIPMENT OR ASSOCIATED EQUIPMENT, LOST REVENUES OR PROFITS, COST OF SUBSTITUTE EQUIPMENT OR COST OF FUEL OR ELEC-

TRICITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF UPG'S SUPPLIERS AND SUBCONTRACTORS. THE ABOVE LIMITATION ON

CONSEQUENTIAL DAMAGES SHALL NOT APPLY TO INJURIES TO PERSONS IN THE CASE OF CONSUMER GOODS.

SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, OR FOR STRICT

LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS AND LIMITATIONS MAY NOT APPLY TO YOU.

UPG DOES NOT ASSUME, OR AUTHORIZE ANY OTHER PERSON TO ASSUME FOR UPG, ANY OTHER LIABILITY FOR THE SALE OF THIS PRODUCT.

THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.

For Owner's Information:

PRODUCT MODEL. NO. ____________________ INSTALLATION DATE ______________________________

UNIT SERIAL NO. _________________________ INSTALLING DEALER ______________________________

Subject to change without notice. Printed in U.S.A.

Copyright © 2008 by Johnson Controls, Inc. All rights reserved.

Johnson Controls Unitary Products

5005 York Drive

Norman, OK 7306

126114-UUM-I-0608

Supersedes: 126114-UUM-H-0208

USER’S INFORMATION,

MAINTENANCE AND

SERVICE MANUAL

HIGH EFFICIENCY

TUBULAR HEAT EXCHANGER SERIES

MODELS: GY8S*DH / GM8S*DH / LY8S*DH / LM8S*DH

(Single Stage Downflow/Horizontal / Standard & Low NOx)

EFFICIENCY

RATING

CERTIFIED

ISO 9001

Certified Quality

Management System

TABLE OF CONTENTS

CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 FURNACE MAINTENANCE SECTION . . . . . . . . . . . . . . . . . . . . . . .4

USER’S INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTRUCTIONS FOR EXAMINING THE

FURNACE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

HOW YOUR GAS FURNACE WORKS . . . . . . . . . . . . . . . . . . . . . . 3

START-UP AND SHUTDOWN INSTRUCTIONS . . . . . . . . . . . . . . . 3

Read the Instructions Below Before Trying to Start the Furnace . 3

Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . 3

Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Removing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Blower Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . 4

SAFETY SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

FURNACE CLEANING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Burner Removal/Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Cleaning the Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Continuous Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Intermittent Blower - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Heating Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . .6

DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL . . . . . .7

REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . .10

WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

CONTACT INFORMATION

• Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.

• Contact us by mail:

York International

Consumer Relations

5005 York Drive

Norman, OK 73069

The manufacturer recommends that the user read all sections of this manual and keep the manual for future reference.

FIRE OR EXPLOSION HAZARD - Failure to follow safety warnings exactly could result in serious injury, death, or property damage.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS:

• Do not try to light any appliance.

• Do not touch any electrical switch; do not use any phone

(including cell phone) in your building.

• Leave the building immediately.

• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

• If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by a qualified installer, service agency or the gas supplier.

SECTION I: USER’S INFORMATION

SAFETY

1.

The furnace area must be kept clear and free of combustible materials, gasoline and other flammable vapors and liquids.

2.

Insulating materials may be combustible. The furnace must be kept free and clear of insulating materials. The furnace area must be examined when installed in an attic or other insulated space or when insulation is added to be sure that the insulation material has been kept away from the furnace.

3.

The furnace needs air for combustion in order to operate properly and safely. Do not block or obstruct air openings on the furnace, air openings to the area where the furnace is installed, or spaces around the furnace.

4.

Follow the instructions exactly as shown on the OPERATING

INSTRUCTION LABEL or the Start-up and Shutdown Instructions on Page 3 of this manual when lighting the furnace or turning the furnace off.

5.

Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.

6.

Do not use this furnace if any part has been under water. A flooddamaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.

268895-UUM-A-0407

268895-UUM-A-0407

CONTROL

BOARD

VENT PIPE

FLUE

COLLAR

ELECTRICAL

JUNCTION BOX

PRESUURE

SWITCH

SILICONE

TUBE

GAS VALVE

FLAME

SENSOR

SAFETY SHUTOFF

SWITCH

INDUCED DRAFT

ASSEMBLY

INDUCED DRAFT

MOTOR

LIMIT

SWITCH

IGNITOR

MANIFOLD

PIPE

FIGURE 1: Component Locations

7.

NEVER . . .Store flammable materials of any kind near your furnace. Gasoline, solvents, and other volatile liquids should be stored only in approved containers outside your home. These materials vaporize easily and are extremely dangerous.

8.

NEVER . . .Store cleaning materials near your furnace. Materials such as bleaches, detergents, powdered cleansers, etc., can cause corrosion of the heat exchangers.

9.

NEVER . . . Use the area around your furnace as a storage area for items which could block the normal flow of air. This flow of air is required for ventilation of the various furnace components.

INSTRUCTIONS FOR EXAMINING THE FURNACE

INSTALLATION

It is the owner’s responsibility to ensure that an annual inspection of the entire heating portion of the unit is made by a qualified service agency.

Examine the furnace as outlined below in steps “1 - 6” before each heating season. Use Figure 3 for visual reference.

1.

Examine the heat exchanger, vent pipe, combustion air passesges, vent connectors and chimney to be sure they are clear and free of obstructions.

2.

Examine the vent pipe making sure it is firmly in place, that it slopes slightly upward and is physically sound without holes and all of the connections are secure.

3.

Examine the return-air duct connections to make sure they are physically sound, sealed to the furnace casing, and the ducts terminate outside the space containing the furnace.

4.

Examine the furnace casing making sure the physical support is sound without sagging, cracks or gaps. Examine the furnace base making sure it is physically sound without cracks, gaps or sagging and has a good seal.

5.

Examine the furnace casing for obvious signs of deterioration.

6.

Examine the burner flames to make sure they are in good adjustment. Refer to the pictorial sketch shown in Figure 2 as a comparison to the actual flame.

BLUE CONE PORTION OF FLAME SHOULD

ENTER HEAT EXCHANGER TUBE

FIRE OR EXPLOSION HAZARD

This furnace is designed and approved for use with Natural Gas and (LP) Propane Gas ONLY. DO NOT BURN

ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.

Burning any unapproved fuel will result in damage to the furnace heat exchanger, which could result in Fire, Personal Injury, and/or Property Damage.

EXAMINE EXTERNAL

VENT PIPE

3

EXAMINE

RETURN AIR

DUCT

CONNECTION

FIGURE 2: Burner Flame Drawing

5 EXAMINE ENTIRE

FURNACE CASING

SHOWN IN ALL

DRAWINGS

3

EXAMINE

RETURN AIR

DUCT

CONNECTION

6

REMOVE

PANEL

TO EXAMINE

BURNER

FLAMES

4 EXAMINE

FURNACE

CASING

FIGURE 3: Furnace Examination Checkpoints

1 EXTERNAL HEAT

EXCHANGER

INTERNAL

VENT COMBUSTION

AIR PIPE. MUST

REMOVE PANEL TO

EXAMINE.

2

4 EXAMINE

FURNACE

CASING

6

REMOVE PANEL

TO EXAMINE

BURNER FLAMES

Unitary Products Group

268895-UUM-A-0407

HOW YOUR GAS FURNACE WORKS

Your furnace is a very easy appliance to take for granted. Season after season, it sits there in your home, keeping you warm and comfortable.

For this reason, you may never have given much thought to the way your furnace operates. In order to get the safest and most efficient operation from your furnace, you should understand how your furnace does its job.

When you set your thermostat to provide more heat in your home, you are starting the heating cycle of the furnace. First, the inducer motor starts to purge the heat exchanger of any remaining gases. Next, the hot surface ignitor glows and after a warm-up period the gas valve opens and ignition occurs. A short time later, the blower starts and distributes the warm air throughout the home. When the temperature setting on your thermostat is reached, the gas valve closes, the main burners are turned off, and the blower continues to run until the remaining warm air in the system is distributed. When the blower stops, the heating cycle has ended.

START-UP AND SHUTDOWN INSTRUCTIONS

Read the Instructions Below Before Trying to Start the

Furnace

To Turn Off the Appliance:

1.

Set the thermostat to lowest setting.

2.

Turn off all electric power to the appliance if service is to be performed.

3.

Remove burner access panel.

4.

Move gas control switch to the “OFF” position. See Figure 4.

5.

Replace burner access panel.

Should overheating occur, or the gas valve fail to shut off, turn the external manual gas valve in the gas supply line to the furnace to the “off” position and let the furnace cool off before shutting off the electrical power supply. Refer to

Figure 5.

OUTLET

PRESSURE

PORT

INLET

VENT PORT

OUTLET

WRENCH

BOSS

INLET

PRESSURE

PORT

OFF

ON

ON/OFF SWITCH

(Shown in ON position)

MAIN REGULATOR

ADJUSTMENT

FIGURE 4: Gas Valve - White Rodgers

EXTERNAL MANUAL

SHUTOFF VALVE

TO GAS

SUPPLY

TO GAS

SUPPLY

If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, and/or loss of life.

A.

This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.

B.

BEFORE OPERATING; smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

C.

Use only your hand to push the gas control switch to the “on” position. Never use tools. If the switch will not operate by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D.

Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.

Operating Instructions:

1.

STOP! Read the safety information above.

2.

Set the thermostat to the lowest setting.

3.

Turn off all electric power to the appliance.

4.

Remove furnace door.

5.

Move gas control switch to the “OFF” position. Do not force. See

Figure 4.

6.

Wait five (5) minutes to clear out any gas. If you then smell gas,

STOP! Follow “B” in the safety information above. If you don’t smell gas, go to next step.

7.

Move gas control switch to the “ON” position. Do not force. See

Figure 4.

8.

Replace burner access panel.

9.

Turn on all electric power to the appliance.

10. Set thermostat to the desired setting. Burner will light, which may take 30-60 seconds.

11.

After three (3) trials for ignition, if the appliance will not operate follow the instructions, “TO TURN OFF THE APPLIANCE” and call your service technician or gas supplier.

DRIP

LEG

GROUNDED JOINT UNION

MAY BE INSTALLED

INSIDE OR OUTSIDE UNIT.

FIGURE 5: Gas Piping

NOTE: The spring-loaded safety cut-off switch, mounted under the blower deck will automatically cut off the electrical power supply to the furnace when the blower panel is removed. As a safety precaution, all electrical power and the gas supply to the furnace should be turned off before servicing.

FURNACE USER MAINTENANCE

Before proceeding, be sure the area is well ventilated. Turn the thermostat OFF. If the blower is running, wait until it stops automatically. Turn OFF the gas and electrical power supplies to the furnace. Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin.

Unitary Products Group 3

268895-UUM-A-0407

Every time the filters are changed the following items should be visually inspected:

• Check combustion air and vent pipe for blockage or leakage.

• Check all components to be sure they are in good condition and that there are no obvious signs of deterioration.

• Check the drain lines to make sure there are no cracks or leaks.

• Check for dirt or lint on any surfaces or on components. Do not try to clean any of the surfaces or components. Cleaning of the furnace and its components must be done by a qualified service professional.

If during the inspection of your furnace, you find any of the following conditions:

• Excessive amounts of dust and lint on components.

• Damaged or deteriorated components or surfaces.

• Leaks or blockage in the vent pipe passages.

• Water on any surface inside or outside of the furnace.

Do not operate the furnace, call a certified dealer / servicing contractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace.

If all components appear to be in good operating condition, replace the front panels. Turn ON the gas and electrical power supplies to the furnace, and set thermostat to the desired temperature.

Air Filters

Dirty filters greatly restrict the flow of air and may cause damage to the moving parts of the furnace. If the filters become clogged the heat exchangers and blower motor could overheat resulting in a potentially dangerous situation. The filters should be checked every 3 months. On new construction, check the filters every week for the first four weeks and every three weeks after that, especially if the indoor fan is running continuously. When replacing the filter(s) you must use filters that are the same size as those recommended in Table 1 to be sure you install the right size filter for your furnace. Never operate your furnace without a suitable air filter.

Removing Filters

Externally Mounted Air Filters

Some installations may have the air filter in a rack attached to the casing of the furnace or placed in the return air duct. You can gain access to the filter by pulling on the door or unscrewing the retaining screw, then slide the filter(s) out of its channel. Replace throw away filter(s) with the same size new filter(s). Throw away filter(s) may be replaced with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as described in the manufacturer instructions or as described below and then re-installed.

To replace the filter after cleaning you must do the following:

1.

Slide filter into place.

2.

Snap the door on or place the door in position and tighten the retaining screws, if provided.

3.

Make sure the door is secure to the end of the filter rack.

TABLE 1: Recommended Filter Sizes

Cabinet Size

A

B

C

D

Top Return (in)

(2) 14 x 20

(2) 14 x 20

(2) 14 x 20

(2) 14 x 20

Top Return (cm)

(2) 35.6 x 50.8

(2) 35.6 x 50.8

(2) 35.6 x 50.8

(2) 35.6 x 50.8

NOTES:

1. Air velocity through throwaway type filters may not exceed 300 feet per minute. All velocities over this require the use of high velocity filters.

How to Clean your Filter

High-velocity filters may be cleaned with a vacuum cleaner or washed with a garden hose. Be sure to shake off excess water and allow filter to completely dry before re-installing the filter.

4

Blower Care

Even with good filters properly in place, blower wheels and motors will become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vacuum cleaner. If the blower cannot be properly cleaned without removing it from the furnace, then this service must be performed by a qualified service agency.

Make sure you DO NOT move the clip on weight on the indoor fan wheel when cleaning the wheel. This weight is used to balance the wheel. Moving the weight will cause the fan wheel to vibrate.

Motor Lubrication

The motors in these furnaces are permanently lubricated, and do not require periodic oiling.

SECTION II: SERVICE AND MAINTENANCE

MANUAL

SAFETY SECTION

The following safety rules must be followed when servicing the furnace.

ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.

Improper servicing could result in dangerous operation, serious injury, and death or property damage.

• Before servicing, disconnect all electrical power to the furnace.

• When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.

• Verify proper operation after servicing.

FURNACE MAINTENANCE SECTION

The furnace should be cleaned and adjusted by a certified dealer or qualified service contractor once a year or before the start of every heating season. The following items must be cleaned and serviced or replaced if there are signs of deterioration.

1.

The vent terminal.

2.

The furnace vent and combustion air intake passageways. Should it be necessary to service the vent/air intake system, the manufacturer recommends this service be conducted by a qualified service agency. The operation of this appliance requires the reassembly and resealing of the vent/air intake system.

3.

The furnace burners, ignitor and flame sensor.

4.

The condensate collection and disposal system. If any disassembly of components containing flue or vent gases is required, a qualified service agency must perform the service.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

Unitary Products Group

268895-UUM-A-0407

FURNACE CLEANING SECTION

NOTE: The cleaning operations listed below must be performed only by a qualified service agency.

Burner Removal/Cleaning

The main burners should be checked periodically for dirt accumulation.

If cleaning is required, follow this procedure:

1.

Turn off the electrical power to the unit.

2.

Turn off the gas supply at the external manual shut-off valve and loosen the ground union joint.

3.

Remove the upper access panel and remove the burner box cover.

4.

Disconnect wires from flame sensor, rollout switch and HSI igniter.

Remove igniter carefully, as it is easily broken.

5.

Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.

6.

Remove burners from the burner assembly.

7.

Burners may be cleaned by rinsing in hot water.

8.

Reassemble the burners in the reverse order.

Cleaning the Heat Exchanger

Lower Heat Exchanger Access

1.

Turn off the electrical power to the unit and turn off gas supply at the shutoff valve.

2.

Remove the blower and burner compartment access doors. Disconnect the gas supply piping at the union to permit removal of the entire burner and gas control assembly from the vestibule panel.

Use the wrench boss on the gas valve when removing or installing this piping. See Figure 4.

3.

Unplug the igniter from the wire harness. Disconnect sensor and rollout switch wires located on top of the air shield. Identify and note the location of all leads for ease of reinstallation. Also disconnect the wires at the side rollout switches (upflow only) and the gas valve wires.

4.

Remove the screws holding the burner assembly to the vestibule panel and remove this assembly. Handle the assembly carefully since it contains the igniter, which is fragile and easily broken. The lower portion of the heat exchanger will now be exposed. To clean the burner assembly, use a vacuum cleaner, or remove the burners as outlined in burner cleaning, and clean in hot water.

Upper Heat Exchanger Access

1.

Perform steps 1-4 above.

2.

Disconnect vent piping from the vent motor assembly at the top panel on the furnace (upflow only). On downflow models, the vent pipe is attached to the vent motor outlet. Remove this screw before proceeding.

3.

Unplug the vent motor wires and ground wire. Remove the pressure switch tubing at the tap on the vent motor housing.

NOTE: It is recommended that replacement gaskets be available before removing vent motor.

4.

Remove six mounting screws that hold the vent motor to the restrictor plate. The surface is gasketed and the gasket can be reused if it is carefully removed. It is necessary to remove this assembly to gain access to the restrictor plate mounting holes.

The assembly may be vacuumed if cleaning is necessary. If any vent assembly parts are damaged, replace with an entire new assembly (except for gaskets).

5.

Remove the perimeter screws attaching the restrictor plate assembly to the vestibule panel. The surface is also gasketed. The assembly, including the flue baffle plate (rear) may be vacuumed or cleaned with hot water if necessary.

6.

The upper portion of the heat exchanger is now accessible. With a long flexible wire brush, clean inside each tube at both the top and bottom. The brush must pass around the rear heat exchanger tubes. Vacuum loose scale and dirt from each tube.

7.

Clean - Replace all components in reverse order. Re-gasket all surfaces which required a gasket. Reconnect all wiring. Reattach vent pipe and gas supply lines before restoring service to furnace.

Restore electrical power, check gas supply piping for leaks, and then verify furnace operation.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

SEQUENCE OF OPERATION

The following describes the sequence of operation of the furnace. Refer to Figure 1 for component location.

Continuous Blower

Cooling/heating thermostats have a fan switch that has an ON and

AUTO position. In the ON position the thermostat circuit is completed between terminals R and G. The motor will operate on the speed tap selected on the Continuous Fan speed Jumper on the control board (HI

COOL, LO COOL, or HEAT pins).

Intermittent Blower - Cooling

Cooling/heating thermostats have a fan switch that has an ON and

AUTO position. In the AUTO position the thermostat circuit is completed between terminals R and G when there is a call for cooling. The motor will operate on the speed tap wire that is connected to the HI COOL terminal on the control board. The fan off setting is fixed at 60 seconds for

SEER enhancement.

Heating Cycle

When the thermostat switch is set on HEAT and the fan is set on AUTO, and there is a call for heat, a circuit is completed between terminals R and W of the thermostat. When the proper amount of combustion air is being provided, the pressure switch will close, the ignition control provides a 17-second warm-up period, the gas valve then opens, the gas starts to flow, ignition occurs and the flame sensor begins its sensing function. The blower motor will energize 30 seconds after the gas valve opens, if a flame is detected. Normal furnace operation will continue until the thermostat circuit between R and W is opened, which causes the ignition system and gas valve to de-energize and the burner flames to be extinguished. The vent motor will operate for an additional 15 seconds and the blower motor will operate for the amount of time set by the fan-off delay jumper located on the control board. See Figure 6. The heating cycle is complete, and ready for the start of the next heating cycle.

Unitary Products Group 5

268895-UUM-A-0407

FAN OFF

ADJUSTMENT

JUMPER

TWIN

PARK PARK

HI COOL

HEAT

EAC-H

L1

XFMR

YELLOW-MED. LOW

RED-LOW

BLACK-HI

BLUE-MED. HI

HUM

FIGURE 6: Furnace Control Board

If the flame is not detected within 7 seconds of the gas valve opening, the gas valve is shut off and a retry operation begins. If the flame is lost for 2 seconds during the 10-second stabilization period, the gas valve is shut off and a retry operation begins. During a retry operation, the vent motor starts a 15 second inter-purge and the ignitor warm-up time is extended to 27 seconds. If the flame is established for more than 10 seconds after ignition during a retry, the control will clear the ignition attempt (retry) counter. If three retries occur during a call for heat, the furnace will shut down for one hour. If at the end of the one hour shut down there is a call for heat, the furnace will initiate a normal start cycle.

If the problem has not been corrected the furnace will again lockout after three retries.

A momentary loss of gas supply, flame blowout, or a faulty flame probe circuit will result in a disruption in the flame and be sensed within 1.0

seconds. The gas valve will de-energize and the control will begin a recycle operation. A normal ignition sequence will begin after a 15 second inter-purge. If during the five recycles the gas supply does not return, or the fault condition is not corrected the ignition control will lockout for 60 minutes.

During burner operation, a momentary loss of power for 50 milliseconds or longer will de-energize the gas valve. When the power is restored, the gas valve will remain de-energized and the ignition sequence will immediately restart.

Hot Surface Ignition System

HOT SURFACE IGNITION SYSTEM

Do not attempt to light this furnace by hand (with a match or any other means). There may be a potential shock hazard from the components of the hot surface ignition system. The furnace can only be lit automatically by its hot surface ignition system.

TROUBLESHOOTING

The following visual checks should be made before troubleshooting:

1.

Check to see that the power to the furnace and the ignition control module is ON.

2.

The manual shut-off valves in the gas line to the furnace must be open.

3.

Make sure all wiring connections are secure.

4.

Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system’s response. Then use the troubleshooting section in this manual to check the system’s operation.

6

Never bypass any safety control to allow furnace operation. To do so will allow furnace to operate under potentially hazardous conditions.

Do not try to repair controls. Replace defective controls with UPG Source 1 Parts.

Never adjust pressure switch to allow furnace operation.

FURNACE CONTROL DIAGNOSTICS

The furnace has built-in, self-diagnostic capability. If a system problem occurs, a blinking LED shows a fault code. The LED can flash red, green or amber to indicate various conditions. It is located behind a clear view port in the blower compartment door.

The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced, as the control is not field repairable.

Flash sequence codes 1 through 10 are as follows: LED will turn “on” for 1/4 second and “off” for 1/4 second. This pattern will be repeated the number of times equal to the code. For example, six “on” flashes equals a number 6 fault code. All flash code sequences are broken by a 2 second “off” period.

SLOW GREEN FLASH: Normal operation.

SLOW AMBER FLASH: Normal operation with call for heat.

RAPID RED FLASH: Twinning error, incorrect 24V phasing. Check twinning wiring.

RAPID AMBER FLASH: Flame sense current is below 1.5 microamps.

Check and clean flame sensor. Check for proper gas flow.

4 AMBER FLASHES: The control board is recieving a “Y” signal from the thermostat without a “G” signal, indicating improper thermostat wiring.

1 RED FLASH: This indicates that flame was sensed when there was not a call for heat. With this fault code the control will turn on both the inducer motor and supply air blower. A gas valve that leaks through or is slow closing would typically cause this fault.

2 RED FLASHES: This indicates that the normally open pressure switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring.

3 RED FLASHES: This indicates the normally open pressure switch contact did not close after the inducer was energized. This could be caused by a number of problems: faulty inducer, blocked vent pipe, broken pressure switch hose or faulty pressure switch.

Unitary Products Group

4 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.

5 RED FLASHES: This fault is indicated if the normally closed contacts in the rollout switch opens. The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch after correcting the failure condition.

6 RED FLASHES: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat. If the main blower is in a “Delay on” mode it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.

7 RED FLASHES: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out. Low gas pressure, faulty gas valve, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart.

8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle. This could be caused by low gas pressure or faulty gas valve. The furnace will lock out for one hour and then restart.

9 RED FLASHES: Indicates reversed line voltage polarity or grounding problem. Both heating and cooling operations will be affected. Check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.

10 RED FLASHES: Gas valve energized with no call for heat. Check gas valve and gas valve wiring.

11 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes. This condition is usually caused by a failed blower motor or blower wheel.

12 RED FLASHES: This code indicates an open igniter circuit, which could be caused by a disconnected or loose wire or by a cracked or broken igniter.

STEADY ON RED: Control failure. Replace control board.

268895-UUM-A-0407

60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control includes a “watchdog” type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6,7,8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored, at some point the “watchdog” would restart the unit and provide heat for the house.

NOTE: If a flame is detected the control flashes the LED for 1/8 of a second and then enters a flame stabilization period.

IGNITION CONTROL

Normal flame sense current is approximately

3.7 microamps DC (µa)

Low flame signal warning starts at 1.5 microamps.

Low flame signal control lockout point is

0.1 microamps DC (µa)

DIAGNOSTIC FAULT CODE STORAGE AND

RETRIEVAL

The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily. This memory will be retained even if power to the furnace is lost. This feature should only be used by a qualified service tech- nician.

The control stores up to five separate error codes. If more than five error codes have occurred since the last reset, only the five most recent will be retained. The furnace control board has a button, labeled "LAST

ERROR" that is used to retrieve error codes. This function will only work if there are no active thermostat signals. So any call for heating, cooling or continuous fan must be terminated before attempting to retrieve error codes.

To retrieve the error codes, push the LAST ERROR button. The LED on the control will then flash the error codes that are in memory, starting with the most recent. There will be a two-second pause between each flash code. After the error codes have all been displayed, the LED will resume the normal slow green flash after a five second pause. To repeat the series of error codes, push the button again.

If there are no error codes in memory, the LED will flash two green flashes. To clear the memory, push the LAST ERROR button and hold it for more than five seconds. The LED will flash three green flashes when the memory has been cleared, then will resume the normal slow green flash after a five-second pause.

Thermostat Satisfied

(Seconds) 0 2 17

Thermostat Calling for Heat

22

Fan on Delay

30 Seconds

52 0

ON

THERMOSTAT

OFF

INDUCER

OFF

ON

ON

IGNITOR

MAIN VALVE

OFF

OFF

HUMIDIFIER

OFF

ELECTRONIC

AIR CLEANER

CIRCULATING

BLOWER

OFF

OFF

ON

OFF

ON

OFF

OFF

ON

ON

OFF

OFF

15 Sec.

Post

Purge

OFF

OFF

OFF

OFF

OFF

60, 90, 120, 180 SEC.

Selectable Fan Off Delay

OFF

FIGURE 7: Furnace Control Event Schedule

Unitary Products Group 7

268895-UUM-A-0407

SECTION III: REPLACEMENT PARTS LIST

30

16

21

15

10

46

7

17

19

24,36

9

8

41

23

37

45

29

3

44

5

34

22

27

2

4

11

6,20

26

12,35

13

1

28

32

39

25

19

7

36

24

11

12

35

8 Unitary Products Group

268895-UUM-A-0407

ITEM DESCRIPTION

5

6

3

4

MOTOR

1 MOTOR,DIRECT DRIVE BLOWER

2 MOTOR,VENTOR ASS’Y

ELECTRICAL

CAPACITOR (7.5MFD/370V)

CONTROL, HIGH LIMIT

CONTROL,FURNACE

IGNITOR

7

8

SENSOR, FLAME

SWITCH, AIR PRESSURE

9 SWITCH, DOOR

10 TRANSFORMER

11 VALVE, GAS

12 CONTROL, LIMIT (Blower)

13 CONTROL, AUXILARY LIMIT

14 FUSE

AIR MOVING

15 HOUSING, BLOWER

15A PANEL, FILLER WRAP

16 WHEEL, BLOWER

FABRICATED PARTS

17 SHIELD, SECONDARY AIR

18 BAFFLE, FLUE

19 BURNER, MAIN GAS

20 BRACKET, IGNITOR

21 DECK, BLOWER (Rear)

22 DECK, FRONT

23 HEAT EXCHANGER ASS’Y (Primary)

24 MANIFOLD, GAS

NOTE: *Not Shown

Major components and suggested stocking items are shown with shaded item number.

ITEM DESCRIPTION

25 PANEL, BURNER ACCESS

26 PANEL, BASE

27 BRACKET, DOOR

28 PANEL, BLOWER ACCESS

29 PANEL, TOP

30 WRAPPER, INSULATED

MISCELLANEOUS

31 FILTER (2 Req’d) (.75 x 14 x 20)

31A FILTER BRACKET

32 PLUG, WINDOW, CLEAR - .875”

33

34 GASKET, VENT PIPE

35 BRACKET, ROLL-OUT SWITCH

36 ORIFICE, BURNER (Natural #45)

37 PLATE, RESTRICTOR

38 COLLAR, FLUE

39 HANDLE, DOOR

40 GASKET, RESTRICTOR PLATE

41 TUBING, SILICONE

42 WIRING DIAGRAM

43 WIRING HARNESS

44 HOUSING FLUE

45 VENT PIPE

47 MOTOR MOUNT

48 FERRULE

49 GROMMET

50 LO-NOX SCREEN

51 GASKET KIT, INDUCER

Unitary Products Group 9

268895-UUM-A-0407

TABLE 2: Field Installed Accessories - Non Electrical

MODEL NO.

1NP0347

1PS0301

1PS0311

1CB0314

1CB0317

1CB0321

1CB0324

DESCRIPTION

PROPANE (LP) CONVERSION KIT

HIGH ALTITUDE PRESSURE SWITCH KIT

(Does Not Include Orifices)

COMBUSTIBLE FLOOR BASE FOR DOWNFLOW UNITS

REPLACEMENT PART CONTACT INFORMATION

This is a generic parts list. To request a complete parts list, refer to the contact information below:

• Visit our website at www.source1parts.com for the following information:

1. Search for a part or browse the catalog.

2. Find a dealer or distributor.

3. Customer Service contact information.

a. Click on the “Brand Links” button b. Click on the “Customer Service” button

• You can contact us by mail. Just send a written request to:

York International

Consumer Relations

5005 York Drive

Norman, OK 73069

USED WITH

ALL MODELS

40, 60, 80 MBH

100, 115, 130 MBH

14-1/2” (”A”) CABINETS

17-1/2” (“B”) CABINETS

21” (“C”) CABINETS

24-1/2” (“D”) CABINETS

10 Unitary Products Group

SECTION IV: WIRING DIAGRAM

268895-UUM-A-0407

FIGURE 8: Wiring Diagram

Unitary Products Group 11

The Most Com fort able Call You Can Mak e!

Chas Roberts Air Conditioning is proud to be a family owned and operated business, serving Arizona since

1942.

As your HVAC system Installer, we can provide you with services to meet all of your Heating and Air

Conditioning needs after you have taken possession of your new home:

• Sales

• Service & Repair

• Extended Warranties

• Preventative Maintenance

We are available to speak with you Monday-Friday

7am to 8pm, Saturday 7am to 5pm, and Sunday 9am to 4pm with extended hours during the summer.

Please call, or visit our website, with all of your

HVAC questions or concerns.

(602) 943-3426 or (520) 292-6858 www.ChasRoberts.com

ROC19133 ROC069769 ROC073706

Limited Warranty

UPG warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace any parts that prove to have such defects according to the terms outlined on this warranty. This warranty covers only the equipment described by the Product

Model Number and Serial Number listed on the Warranty Registration Card.

UPG warrants the primary heat exchangers in the product to be free from defects in factory workmanship and material under normal use and service and will at its option, repair or furnish a replacement heat exchanger, either new or reconditioned, that meets the intended fit, use and function of the original heat exchanger for any heat exchanger furnished by UPG which proves to have such defects within the duration of warranty coverage. Alternatively, UPG may, at its option, extend a replacement allowance to be applied toward the purchase of a new furnace or packaged unit marketed by UPG. The exact amount of the allowance will be determined at the discretion of UPG, based upon current market conditions, but in no case shall this allowance exceed thirty (30) percent of the original consumer purchase price of the furnace, excluding such items as ductwork, wiring, piping and installation costs. UPG shall have no responsibility hereunder for installation, shipping, handling or other charges except as specifically provided herein.

For your benefit and protection, return the Warranty Registration Card to UPG promptly after installation. This will initiate the warranty period and allow us to contact you, should it become necessary. In the absence of a recorded Warranty Registration Card, the warranty period will begin upon product shipment from

UPG.

This warranty extends only to the original consumer purchaser and is non-transferable. For this warranty to apply, the product must be installed according to

UPG recommendations and specifications, and in accordance with all local, state, and national codes; and the product must not be removed from its place of original installation. The warranty period for repair or replacement parts provided hereunder shall not extend beyond the warranty period stated on this warranty.

FURNACE TYPE

HEAT EXCHANGER

Residential Applications

Original Owner

20

Subsequent Owner

N/A

Non-Residential

Applications

10

PARTS

80% GY8S*DH / GM8S*DH / LY8S*DH / LM8S*DH 5

UPG strongly recommends regular periodic preventative maintenance on this equipment. The person most familiar with the equipment in your HVAC system is a UPG dealer. The UPG dealer can ensure your maintenance program meets the conditions of the "UPG Warranty", maximize the efficiency of the equipment, and service your unit within the mandated guidelines with regard to unlawful discharge of refrigerants into the atmosphere.

This warranty applies only to products installed in the United States and Canada.

EXCLUSIONS

This warranty does not cover any:

1.

Shipping, labor, or material charges.

2.

Damages resulting from transportation, installation, or servicing.

3.

Damages resulting from accident, abuse, fire, flood, alteration, or acts of God (tampering, altering, defacing or removing the product serial number will serve to void this warranty).

4.

Damages resulting from use of the product in a corrosive atmosphere.

5.

Damages resulting from inadequacy or interruption of electrical service or fuel supply, improper voltage conditions, blown fuses, or other like damages.

6.

Cleaning or replacement of filters.

7.

Damages resulting from failure to properly and regularly clean air and/or water side of condenser and evaporator.

8.

Damages resulting from: (I) freezing of condenser water or condensate; (II) inadequate or interrupted water supply; (III) use of corrosive water; (IV) fouling or restriction of the water circuit by foreign material or like causes.

9.

Damages resulting from operation with inadequate supply of air or water.

10.

Damages resulting from use of components or accessories not approved by UPG (vent dampers, etc.).

11.

Increase in fuel or electric cost.

THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABIL-

ITY AND FITNESS FOR A PARTICULAR PURPOSE.

SOME STATES DO NOT ALLOW THE DISCLAIMER OF IMPLIED WARRANTY, SO THAT THE ABOVE DISCLAIMER MAY NOT APPLY TO YOU.

SOME STATES ALLOW ONLY A PARTIAL LIMITATION ON IMPLIED WARRANTIES TO LIMIT THE DURATION OF IMPLIED WARRANTIES TO THE DURA-

TION OF THE EXPRESS WARRANTY. IN SUCH STATES, THE DURATION OF IMPLIED WARRANTIES IS HEREBY EXPRESSLY LIMITED TO THE DURA-

TION OF THE EXPRESS WARRANTY ON THE FACE HEREOF.

IN NO EVENT, WHETHER AS A RESULT OF BREACH OF WARRANTY OR CONTRACT, TORT (INCLUDING NEGLIGENCE) STRICT LIABILITY OR OTH-

ERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE OF

THE EQUIPMENT OR ASSOCIATED EQUIPMENT, LOST REVENUES OR PROFITS, COST OF SUBSTITUTE EQUIPMENT OR COST OF FUEL OR ELEC-

TRICITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF UPG'S SUPPLIERS AND SUBCONTRACTORS. THE ABOVE LIMITATION ON

CONSEQUENTIAL DAMAGES SHALL NOT APPLY TO INJURIES TO PERSONS IN THE CASE OF CONSUMER GOODS.

SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, OR FOR STRICT

LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS AND LIMITATIONS MAY NOT APPLY TO YOU.

UPG DOES NOT ASSUME, OR AUTHORIZE ANY OTHER PERSON TO ASSUME FOR UPG, ANY OTHER LIABILITY FOR THE SALE OF THIS PRODUCT.

THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.

For Owner's Information:

PRODUCT MODEL. NO. ____________________ INSTALLATION DATE ______________________________

UNIT SERIAL NO. _________________________ INSTALLING DEALER ______________________________

Subject to change without notice. Printed in U.S.A.

Copyright © by York International Corp. 2007. All rights reserved.

Unitary

Products

Group

268895-UUM-A-0407

Supersedes: 167254-UUM-B-0706

5005 Norman

York OK

Drive 73069

advertisement

Related manuals