59TN6A
Infinity
R
Two---Stage, Variable Speed
4---Way Multipoise
Condensing Gas Furnace
Series 100
A11263
The 59TN6A Multipoise Variable--Speed Condensing Gas Furnace features the two--stage Infinity
R
System. The Comfort Heat
Technology
R two--stage gas system is at the heart of the comfort provided by this furnace, along with the variable--speed ECM blower motor, and two--speed inducer motor. With an Annual Fuel
Utilization Efficiency (AFUE) of up to 96.7%, the Infinity two--stage gas furnace provides exceptional savings when compared to a standard furnace. This Infinity Gas Furnace also features 4--way multipoise installation flexibility, and is available in four model sizes. The 59TN6A can be vented for direct vent/two--pipe, ventilated combustion air, or single--pipe applications. A Carrier Infinity Control and Infinity Air
Conditioner or Heat Pump can be used to form a complete Infinity
System. All units meet California Air Quality Management District emission requirements. All sizes are design certified in Canada.
STANDARD FEATURES
S
Infinity
R
System; compatible with single-- and multiple--zone
Infinity systems
S
Quiet operation. Compare for yourself at HVACpartners.com
S
Ideal height 35--in. (889 mm) cabinet: short enough for taller coils, but still allows enough room for service
S
Infinity Features—match with the Infinity Control for Infinity
Product Data
System benefits
S
Integral part of the Ideal Humidity System
R
Technology
S
Silicon Nitride Power Heat
™
Hot Surface Igniter
S
SmartEvap
™ technology helps control humidity levels in the home when used with a compatible humidity control system
S
ComfortFan
™ technology allows control of continuous fan speed from a compatible thermostat
S
External Media Filter Cabinet included
S
4--way multipoise design for upflow, downflow or horizontal installation, with unique vent elbow and optional through-the--cabinet downflow venting capability
S
Variable--Speed blower motor, two--speed inducer motor, and two--stage gas valve
S
Self--diagnostics and extended diagnostic data through the
Advanced Product Monitor ( APM) accessory or Infinity User
Interface
S
Adjustable blower speed for cooling, continuous fan, and dehumidification
S
Aluminized--steel primary heat exchanger
S
Stainless--steel condensing secondary heat exchanger
S
Propane convertible (See Accessory list)
S
Factory--configured ready for upflow applications
S
Fully--insulated casing including blower section
S
Convenient Electronic Air Cleaner and Humidifier connections
S
Direct--vent/sealed combustion, single--pipe venting or ventilated combustion air
S
Installation flexibility: (sidewall or vertical vent)
S
Residential installations may be eligible for consumer financing through the Retail Credit Program
LIMITED WARRANTY*
S
10 year parts and lifetime heat exchanger limited warranty to the original purchaser upon timely registration.
S
Limited warranty period is five years for parts and twenty years for the heat exchanger if not registered within 90 days of installation.
{
* For owner occupied, residential applications.
{
Jurisdictions where warranty benefits cannot be conditioned on registration will receive registered limited warranty benefits.
Always Ask For
C E RT I F I E D
Use of the AHRI Certified
TM
Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org.
1
Heating Capacity and Efficiency
Input
Output
Efficiency
High Heat
Low Heat
High Heat
Low Heat
AFUE % (ICS)
Certified Temperature
Rise Range ºF (ºC)
Airflow Capacity and Blower Data
Certified External Static
Pressure (in. w.c.)
Airflow Delivery
@ Rated ESP (CFM)
Cooling Capacity (tons)
@ 400, 350 CFM/ton
Direct-Drive Motor Type
Direct-Drive Motor HP
Motor Full Load Amps
RPM Range
Speed Selections
Blower Wheel Dia x Width
Air Filtration System
Filter Used for Certified Watt Data
Electrical Data
Input Voltage
Operating Voltage Range
Maximum Input Amps
Unit Ampacity
Minimum Wire Size
Maximum Wire Length
@ Minimum Wire Size
Maximum Fuse/Ckt Bkr
(Time-Delay Type Recommended)
Transformer Capacity (24vac output)
External Control Power
Available
Controls
Gas Connection Size
Burners (Monoport)
Gas Valve (Redundant)
Gas Conversion Kit - Natural to Propane
Gas Conversion Kit - Propane to Natural
Manufactured (Mobile) Home Kit
Ignition Device
Limit Control
Heating Blower Control (Heating Off-Delay)
Cooling Blower Control (Time Delay Relay)
Communication System
Thermostat Connections
Accessory Connections
(BTUH)
(BTUH)
(BTUH)
(BTUH)
High Heat
Low Heat in.
SPECIFICATIONS
Heating
Cooling
High Heat
Low Heat
Cooling
400 CFM/ton
350 CFM/ton
Volts-Hertz-Phase
Min-Max
Amps
Amps
AWG
Feet
(M)
060-14 080-14 100-20 120-22
60,000
39,000
58,000
37,000
96.3
35 - 65
(19-36)
30 - 60
(17-33)
060-14
0.12
0.5
1075
855
1335
3
3.5
80,000
52,000
78,000
50,000
96.2
40 - 70
(21-38)
30 - 60
(17-33)
080-14
0.15
0.5
1500
1060
100,000
65,000
98,000
63,000
96.7
45 - 75
(25-41)
30 - 60
(17-33)
100-20
0.20
0.5
1515
1335
1375
3.5
2030
5
4 5.5
Electronically Commutated Motor (ECM)
1/2
7.7
1
12.8
1/2
7.7
1
12.8
11 x 8
300 - 1300
Variable (Communicating)
11 x 8 11 x 10
Factory Supplied Media Cabinet
Field Supplied Filter
11 x 11
KGAWF1306UFR KGAWF1306UFR KGAWF1406UFR KGAWF1506UFR
060-14 080-14 100-20 120-22
115-60-1
104-127
9.7
12.7
14
29
(8.8)
9.7
12.7
14
29
(8.8)
14.8
19.2
12
30
(9.1)
14.8
19.2
12
30
(9.1)
120,000
78,000
117,000
76,000
96.7
45 - 75
(25-41)
30 - 60
(17-33)
120-22
0.20
0.5
1820
1640
2185
5.5
6
Amps 15 15 20 20
Heating
Cooling
40 VA
24.3 VA
34.6 VA
060-14
1/2” - NPT
3
080-14 100-20 120-22
6
Manufacturer
Minimum Inlet Gas pressure (in. W.C.)
Maximum Inlet Gas pressure (in. W.C.)
4
White Rogers™
5
4.5
180
13.6
KGANP5201VSP
KGAPN4401VSP
not approved for MH use
Silicon Nitride
170 160
Adjustable: 90, 120, 150, 180 seconds
90 seconds
Infinity; Infinity Zoning
W2, Y1, DHUM, G, COM 24V, W/W1, Y/Y2, R
EAC (115vac); HUM (24vac); 1-stg AC (via Y/Y2)
160
2
MODEL NUMBER NOMENCLATURE
1 - 2
Family
59
3
Htg. Stages
T
4
Tier
N
Family
S - Single Stage
T - Two Stage
M - Modulating
C - Comfort
P - Performance
N - Infinity
5
Effy.
6
0 --- 90 AFUE
3 --- 93 AFUE
5 --- 95 AFUE
6 --- 96 AFUE
7 --- 97 AFUE
6
Major Series
A
7 - 9
Htg. Cap.
060
10
Motor
V
11 - 12
Width
17
Major Series
040=40,000 BTU
060=60,000 BTU
S - Standard
E - Energy Efficient
080=80,000 BTU
100=100,000 BTU
120=120,000 BTU
V - Variable Speed
14 - 14.2”
17 - 17.5”
21 - 21.0”
24 - 24.5”
Not all familes have these models.
13
Voltage
--
Voltage
14
Minor Series
--
15 - 16
Airflow
14
08 - 800 CFM
10 - 1000 CFM
12 - 1200 CFM
14 - 1400 CFM
16 - 1600 CFM
18 - 1800 CFM
20 - 2000 CFM
22 - 2200 CFM
Minor Series
A11160
FURNACE COMPONENTS
GAS BURNER
HOT SURFACE
IGNITER
MANUAL RESET
ROLLOUT SWITCH
FLAME
SENSOR
MANUAL RESET
ROLLOUT SWITCH
GAS VALVE
OPERATING INSTRUCTIONS
NOT SHOWN (LOCATED ON
MAIN FURNACE DOOR, SEE
OPERATING INSTRUCTIONS
INSIDE DOOR FIGURE).
ELECTRICAL JUNCTION
BOX (IF REQUIRED,
LOCATION MAY VARY)
BLOWER DOOR
SAFETY SWITCH
FURNACE
CONTROL
BOARD
MAIN LIMIT SWITCH
(BEHIND GAS VALVE)
INDUCER MOTOR
ASSEMBLY
MEDIA CABINET
BLOWER AND
MOTOR
CAPACITOR/
POWER CHOKE
(IF USED)
RATING PLATE NOT SHOWN
(LOCATED ON BLOWER DOOR)
REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPEARANCE.
A11408
3
DESCRIPTION
Venting, Drainage and Installation
Vent Kit - Through the Cabinet
Vent Terminal - Concentric - 2” (51 mm)
Vent Terminal - Concentric - 3” (76 mm)
Vent Terminal Bracket - 2” (51 mm)
Vent Terminal Bracket - 3” (76 mm)
CPVC to PVC Drain Adapters - 1/2” CPVC to 3/4” PVC
Horizontal Trap Grommet - Direct Vent
Freeze Protect Kit - Heat Patch for Drain Trap
Freeze Protect Kit - Heat Tape
Furnace Base Kit for Combustible Floors
Gas Conversion
Gas Cnv Kit - Nat to LP; Var-spd Products
Gas Cnv Kit - LP to Nat; Var-spd Products
Gas Orifice Kit - #42 (Nat Gas)
Gas Orifice Kit - #43 (Nat Gas)
Gas Orifice Kit - #44 (Nat Gas)
Gas Orifice Kit - #45 (Nat Gas)
Gas Orifice Kit - #46 (Nat Gas)
Gas Orifice Kit - #47 (Nat Gas)
Gas Orifice Kit - #48 (Nat Gas)
Gas Orifice Kit - #54 (LP)
Gas Orifice Kit - #55 (LP)
Gas Orifice Kit - #56 (LP)
Gas Orifice Kit - 1.25mm (LP)
Gas Orifice Kit - 1.30mm (LP)
Indoor Air Quality
Carrier Infinity Air Purifier - 16x25 (406x635 mm)
Carrier Infinity Air Purifier - 20x25 (508x635 mm)
Carrier Infinity Air Purifier Repl. Filter- 16x25 (406x635 mm)
Carrier Infinity Air Purifier Repl. Filter- 20x25 (508x635 mm)
EZ Flex Cabinet 16” (406 mm)
EZ Flex Cabinet 20” (508 mm)
Cartridge Media Filter - 16” (406 mm)
Cartridge Media Filter - 20” (508 mm)
Cartridge Media Filter - 24” (610 mm)
EZ-Flex Filter - 16” (406 mm)
EZ-Flex Filter - 20” (508 mm)
EZ-Flex Filter - 24” (610 mm)
EZ-Flex Filter with End Caps - 16” (406 mm)
EZ-Flex Filter with End Caps - 20” (508 mm)
EZ-Flex Filter with End Caps - 24” (610 mm)
Filter Pack (6 pack) - Washable - 16x25x1 (406x635x25 mm)
Filter Pack (6 pack) - Washable - 24x25x1 (610x635x25 mm)
Controls
Infinity™ Control User Interface
Infinity™ Control Zoning User Interface
Service Tools
Advanced Product Monitor - APM (CBP, Only)
ECM Motor Simulator Kit
X -- Used with this model furnace
N/A -- Not used with this model furnace
ACCESSORIES
PART NUMBER
KGADC0101BVC
KGAVT0701CVT
KGAVT0801CVT
KGAVT0101BRA
KGAVT0201BRA
KGAAD0110PVC
KGACK0101HCK
KGAHT0201CFP
KGAHT0101CFP
KGASB0201ALL
KGANP5201VSP
KGAPN4401VSP
KGAHA0150N42
KGAHA0250N43
KGAHA0350N44
KGAHA0450N45
KGAHA0550N46
KGAHA1550N47
KGAHA1650N48
KGAHA0650P54
KGAHA0750P55
KGAHA0850P56
KGAHA5750125
KGAHA5750130
GAPAAXCC1625-A08
GAPAAXCC2025-A08
GAPACCCAR1625-A05
GAPACCCAR2025-A05
EZXCABCC1016-A20
EZXCABCC1020-A20
FILXXCAR0016
FILXXCAR0020
FILXXCAR0024
EXPXXFIL0016
EXPXXFIL0020
EXPXXFIL0024
EXPXXUNV0016
EXPXXUNV0020
EXPXXUNV0024
KGAWF1306UFR
KGAWF1506UFR
SYSTXCCUID01-V
SYSTXCCUIZ01-V
KGASD0301APM
KGASD0301FMS
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
100-20
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
080-14
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
120-22
X
N/A
X
N/A
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
060-14
X
X
X
X
X
X
X
X
X
X
X
X
4
INPUT
BTUH
60000
INPUT
BTUH
80000
INPUT
BTUH
100000
AIR DELIVERY -- CFM (BOTTOM RETURN WITH FILTER)
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Cooling Switch Settings
SW2-3 SW2-2 SW2-1 0.1
0.2
0.3
External Static Pressure (E.S.P.)
0.4
0.5
0.6
0.7
0.8
1035 OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON ON ON
Maximum Cooling Airflow
2
High Heat Airflow
3
Low Heat Airflow
3
Cooling Switch Settings
SW2-3 SW2-2 SW2-1
OFF OFF OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON ON ON
Maximum Cooling Airflow
2
High Heat Airflow
3
Low Heat Airflow
3
ON
OFF
ON
OFF
Cooling Switch Settings
SW2-3 SW2-2 SW2-1
OFF OFF OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON ON ON
Maximum Cooling Airflow
2
High Heat Airflow
3
Low Heat Airflow
3
ON
OFF
ON
OFF
1120
1275
1455
1805
0.3
1805
755
935
1805
2050
1515
1355
1120
1270
1445
1810
0.2
1810
775
940
1810
2055
1515
1335
1095
1245
1440
1815
0.1
1815
765
930
1815
2055
1495
1325
905
1080
1255
1255
0.3
1080
505
680
1255
1450
1450
1080
895
1065
1245
1245
0.2
1065
505
685
1245
1485
1485
1065
885
1055
1245
1245
0.1
1055
520
665
1245
1520
1520
1055
1060
545
710
875
1060
1235
1235
1235
1425
1075
855
1070
530
710
880
1070
1240
1240
1240
1425
1085
855
1080
520
710
890
1080
1250
1250
1250
1405
1095
860
1445
1800
1800
2045
730
930
1105
1280
1520
1365
1450
1785
1785
2030
710
935
1095
1290
1525
1370
1080
525
695
895
1080
1255
1255
1075
510
690
895
1075
1255
1255
1065
890
1065
1250
1250
1050
1255
1370
1095
870
1255
1335
1090
870
1250
1300
1080
865
External Static Pressure (E.S.P.)
0.4
0.5
0.6
0.7
1075 1065 1050 1045
1230
1260
1065
860
495
660
900
1075
1255
1255
1255
1415
1415
1075
490
665
900
1065
1260
1260
1260
1375
1375
1065
895
1050
1255
1255
1255
1335
1335
1050
External Static Pressure (E.S.P.)
0.4
0.5
0.6
0.7
1800 1785 1765 1745
885
1045
1250
1250
1250
1300
1300
1045
885
1050
1230
1230
1100
1280
1440
1765
1765
2015
1520
1355
1745
1995
1515
1360
1085
1285
1440
1745
1190
1225
1050
855
880
1035
1190
1190
0.8
1035
1235
1265
1265
1035
875
1035
1235
1235
0.8
1720
1720
1940
1505
1345
1075
1270
1425
1720
0.9
1025
1.0
1010
1710
1870
1490
1330
1055
1260
1415
1710
1685
1805
1480
1310
1050
1245
1405
1685
1155
1190
1035
845
870
1025
1155
1155
1115
1155
1020
785
855
1010
1115
1115
0.9
1025
1.0
1005
1220
1225
1225
1025
860
1025
1220
1220
1185
1190
1190
1005
845
1005
1185
1185
0.9
1710
1.0
1685
5
INPUT
BTUH
AIR DELIVERY -- CFM (BOTTOM RETURN WITH FILTER) (CONTINUED)
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Cooling Switch Settings
SW2-3 SW2-2 SW2-1 0.1
0.2
0.3
External Static Pressure (E.S.P.)
0.4
0.5
0.6
0.7
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
1850
765
930
1855
745
925
1860
740
915
1855
705
900
1850
680
885
1830 1805
0.8
1775
0.9
1750
1.0
1730
120000
6
OFF
ON
ON
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
1095
1265
1465
1850
1100
1255
1455
1855
1110
1265
1470
1860
1105
1280
1465
1855
1085
1275
1465
1850
1285
1470
1830
1270
1455
1805
1260
1450
1775
1250
1435
1750
1230
1415
1730
ON ON ON
Maximum Cooling Airflow
2
2200
2200
2200
2200
2200
2200
2190
2190
2185
2185
2170
2170
2145
2145
2085
2085
1990
1990
1890
1890
High Heat Airflow
3
1815 1820 1825 1820 1815 1795 1775 1745 1720 1700
Low Heat Airflow
3
1640 1640 1645 1650 1645 1645 1630 1620 1600
1.
Nominal 350 CFM/ton cooling airflow is delivered with SW1-5 and SW4-2 set to OFF.
Set SW1-5 to ON for nominal 400 CFM/ton (+15% airflow).
Set SW4-3 to ON for nominal 325 CFM/ton (-7% airflow).
Set both SW1-5 and SW4-3 to ON for nominal 370 CFM/ton (+7% airflow).
2.
Maximum cooling airflow is achieved when switches SW3-1, SW3-2, SW3-3 and SW1-5 are set to ON, and SW4-3 is set to OFF.
3.
All heating CFM's are when low heat rise adjustment switch (SW1-3) and comfort/efficiency adjustment switch (SW1-4) are both set to OFF.
4.
Ductwork must be sized for high-heating CFM within the operational range of E.S.P. Operation within the blank areas of the chart is not recommended because high-heat operation will be above 1.0 E.S.P.
5.
All airflows on 21" (533 mm) casing size furnaces are 5% less on side return only installations.
6.
Side returns for 24.5" (622 mm) casing sizes require two sides, or side and bottom, to allow sufficient airflow at the return of the furnace.
1580
6
MAXIMUM EQUIVALENT VENT LENGTH -- FT. (M)
NOTE: Maximum Equivalent Vent Length (MEVL) does NOT include elbows or terminations. Use Table 2 - Deductions from
Maximum Equivalent Vent Length to determine allowable vent length for each application.
Table 1 – Maximum Equivalent Vent Length -- Ft. (M)
0 to 4500 Ft. (0 to 1370 M) Altitude
DIRECT VENT (2-PIPE) AND NON---DIRECT VENT (1---PIPE)
Altitude
FT (M)
0 to 2000
(0 to 610)
2001 to 3000
(610 to 914)
Unit Size
BTU/Hr
40,000*
60,000
80,000
100,000
120,000
40,000*
60,000
80,000
100,000
120,000
2
3001 to 4000
(914 to 1219)
40,000*
60,000
80,000
100,000
120,000
4001 to 4500
(1219 to
1370)
40,000*
60,000
80,000
100,000
120,000
* Not all families have these models.
NOTES
: See notes at end of venting tables.
See Table 3 for altitudes over 4500 ft. (1370 M)
36
21
14
39
23
15
45
27
17
50
30
20
1-1/2
NA
NA
(15.2)
(9.1)
(6.1)
(13.7)
(8.2)
(5.2)
NA
NA
(11.9)
(7.0)
(4.6)
NA
NA
NA
NA
(11.0)
(6.4)
(4.3)
177
115
56
17
184
119
59
19
198
127
64
22
210
135
70
25
2
NA
NA
(64.0)
(41.1)
(21.3)
(7.6)
(60.4)
(38.7)
(19.5)
(6.7)
Vent Pipe Diameter (in.)
2-1/2
232
222
165
104
11
250
235
175
110
15
(76.2)
(71.6)
(53.3)
(33.5)
(4.6)
(70.7)
(67.7)
(50.3)
(31.7)
(3.4)
265
235
235
100
250
222
223
93
NA
(56.1)
(36.3)
(18.0)
(5.8)
(53.9)
(35.1)
(17.1)
(5.2)
214
210
155
98
8
205
204
150
94
(65.2)
(64.0)
(47.2)
(29.9)
(2.4)
(62.5)
(62.2)
(45.7)
(28.7)
235
210
211
86
NA NA
228
202
205
83
3
NA
NA
NA
NA
(80.8)
(71.6)
(71.6)
(30.5)
(76.2)
(67.7)
(68.0)
(28.3)
(71.6)
(64.0)
(64.3)
(26.2)
(69.5)
(61.6)
(62.5)
(25.3)
265
265
250
249
250
237
232
236
224
224
229
217
4
NA
NA
NA
NA
(75.9)
(76.2)
(72.2)
NA
NA
(80.8)
(80.8)
(76.2)
(70.7)
(71.9)
(68.3)
NA
NA
(68.3)
(69.8)
(66.1)
Table 2 – Deductions from Maximum Equivalent Vent Length -- Ft. (M)
Pipe Diameter (in): 1-1/2
Mitered 90º Elbow
Medium Radius 90º Elbow
Long Radius 90º Elbow
Mitered 45º Elbow
3
4
8
5
(2.4)
(1.5)
(0.9)
(1.2)
Medium Radius 45º Elbow
Long Radius 45º Elbow
2.5
1.5
(0.8)
(0.5)
2.5
1.5
Tee
16 (4.9) 16
* Note: 3--- and 4---in. Vent pipe systems require long radius elbows.
3
4
8
5
2
(2.4)
(1.5)
(0.9)
(1.2)
(0.8)
(0.5)
(4.9)
2.5
1.5
16
3
4
8
5
2-1/2
(2.4)
(1.5)
(0.9)
(1.2)
(0.8)
(0.5)
(4.9)
NA
NA
3
NA
NA
1.5
16
3*
NA
NA
(0.9)
NA
NA
(0.5)
(4.9)
NA
NA
3
NA
NA
1.5
16
4*
NA
NA
(0.9)
NA
NA
(0.5)
(4.9)
Venting System Length Calculations
The maximum length for each vent pipe (inlet or exhaust) equals the Maximum Equivalent Vent Length (MEVL) from Table 1 or Table 3 minus the number of elbows multiplied by the deduction for each elbow in Table 2.
Standard vent terminations and concentric vent terminations count for zero deductions.
Example
A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M ) with 2--in. (51 mm) vent piping. Venting system includes,
FOR EACH
PIPE
, (3) 90
_ long radius elbows, (2) 45
_ long radius elbows and a concentric vent kit.
Maximum Equivalent Vent Length
Deduct (3) 90 long radius
Deduct (2) 45 long radius
Maximum Vent Length
3 x
2 x
3 ft.
1.5 ft.
=
=
=
=
127 ft.
(From Table 1)
- 9 ft.
(From Table 2)
- 3 ft.
(From Table 2)
115 ft.
For
EACH
vent or inlet pipe
7
MAXIMUM EQUIVALENT VENT LENGTH -- FT. (M) (CONTINUED)
NOTE: Maximum Equivalent Vent Length (MEVL) does NOT include elbows or terminations. Use Table 2 - Deductions from
Maximum Equivalent Vent Length to determine allowable vent length for each application.
Altitude
FT (M)
4501 to 5000
(1370 to
1524)
5001 to 6000
(1524 to
1829)
6001 to 7000
(1829 to
2134)
7001 to 8000
(2134 to
2438)
Unit Size
40,000*
60,000
80,000
100,000
120,000
40,000*
60,000
80,000
100,000
120,000
40,000*
60,000
80,000
100,000
120,000
40,000*
60,000
80,000
100,000
120,000
40,000*
60,000
80,000
100,000
120,000
27
16
11
33
20
13
1-1/2
NA
NA
(10.1)
(6.1)
(4.0)
(8.2)
(4.9)
(3.4)
NA
NA
21
13
(6.4)
(4.0)
NA
NA
NA
15
10
(4.6)
(3.0)
NA
NA
NA
10
7
(3.0)
(2.1)
NA
NA
NA
Table 3 – Maximum Equivalent Vent Length -- Ft. (M)
4501 to 10,000 Ft. (1371 to 3048 M) Altitude
DIRECT VENT (2-PIPE) AND NON---DIRECT VENT (1---PIPE)
145
96
44
10
158
103
49
12
171
111
54
16
133
89
40
121
82
35
2
NA
NA
NA
NA
NA
NA
NA
(52.1)
(33.8)
(16.5)
(4.9)
(48.2)
(31.4)
(14.9)
(3.7)
(44.2)
(29.3)
(13.4)
(3.0)
(40.5)
(27.1)
(12.2)
(36.9)
(25.0)
(10.7)
Vent Pipe Diameter
2-1/2
196
198
146
91
(59.7)
(60.4)
(44.5)
(27.7)
NA
179
186
137
85
(54.6)
(56.7)
(41.8)
(25.9)
NA
162
174
120
79
(49.4)
(53.0)
(36.6)
(24.1)
NA
146
163
120
73
(44.5)
(49.7)
(36.6)
(22.3)
NA
130
152
111
67
(39.6)
(46.3)
(33.8)
(20.4)
NA
168
148
157
56
181
159
167
62
194
171
178
68
207
183
188
74
221
195
200
80
3
NA
NA
NA
NA
NA
(67.4)
(59.4)
(61.0)
(24.4)
(63.1)
(55.8)
(57.3)
(22.6)
(59.1)
(52.1)
(54.3)
(20.7)
(55.2)
(48.5)
(50.9)
(18.9)
(51.2)
(45.1)
(47.9)
(17.1)
216
222
211
200
208
199
185
195
187
NA
170
182
175
4
NA
NA
NA
NA
(61.0)
(63.4)
(60.7)
NA
NA
(65.8)
(67.7)
(64.3)
(56.4)
(59.4)
(57.0)
NA
(51.8)
(55.5)
(53.3)
8001 to 9000
(2438 to
2743)
156
170
164
NA
NA
(47.5)
(51.8)
(50.0)
40,000* 5 (1.5) 110 (33.5) 115 (35.1) NA NA
9001 to
10,000
(2743 to
3048)
60,000
80,000
100,000
NA
NA
NA
76
31
NA
(23.2)
(9.4)
142
103
62
(43.3)
(31.4)
(18.9)
156
137
147
(47.5)
(41.8)
(44.8)
142
157
NA
(43.3)
(47.9)
120,000 NA NA NA 51 (15.5) 153 (46.6)
* Not all families have these models.
NOTES
:
1. 3--- and 4---in. Vent pipe systems require long radius elbows.
2. Total equivalent vent lengths under 10’ for 40,000 BTUH furnaces, require the use of an outlet choke plate at altitudes 0 to 2000 ft (0 to 610 M).
Failure to use an outlet choke when required may result in flame disturbance or flame sense lockout.
3. Vent sizing for Canadian installations over 4500 ft (1370m) above sea level are subject to acceptance by the local authorities having jurisdiction.
4. NA --- Not allowed; pressure switch will not close, or flame disturbance may result.
5. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
6. Size both the combustion---air and vent pipe independently, then use the larger diameter for both pipes.
7. Assume the two 45
_ elbows equal one 90
_ elbow. Wide radius elbows are desirable and may be required in some cases.
8. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
9. The minimum pipe length is 5 ft. (1.5 M) for all applications.
10. Use 3---in. (76 mm) diameter vent termination kit for installations requiring 4---in. (102 mm) diameter pipe.
8
MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH INSULATION TABLE -- FT. / M
Two
Stage
Furnace
High Heat
Input
40000*
Winter
Design
Temp
°
F
(
°
C)
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
Pipe
Length in
Ft. & M
Ft.
M
Ft.
M
Ft.
M
Ft.
M
Maximum Length of Uninsulated and Insulated Vent Pipe-Ft (M)
No Insulation
Pipe Diameter-in. (mm)
3/8-in. (9.5 mm)
Pipe Diameter-in. (mm)
1/2-in. (12.7 mm)
Pipe Diameter-in. (mm)
1.5
(38)
2.0
2.5
3.0
4.0
1.5
(51) (64) (76) (102) (38)
40.0
35.0 35.0
N/A N/A 50.0
2.0
2.5
104.0 94.0
3.0
N/A
4.0
N/A
1.5
50.0
2.0
2.5
(51) (64) (76) (102) (38) (51) (64)
122.0 110.0
3.0
N/A
4.0
(76) (102)
N/A
12.2
10.7 10.7
N/A N/A
19.0
14.0 12.0
N/A N/A
5.8
4.3
3.7
N/A N/A
9.0
2.7
3.0
0.9
3.0
0.9
0.0
0.0
1.0
0.3
0.0
0.0
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
15.2
50.0
15.2
50.0
15.2
39.0
11.9
31.7
28.7
N/A
61.0
54.0
N/A
18.6
16.5
N/A
41.0
35.0
N/A
12.5
10.7
N/A
29.0
23.0
N/A
8.8
7.0
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
15.2
37.2
33.5
50.0
74.0
65.0
15.2
22.6
19.8
50.0
51.0
43.0
15.2
15.5
13.1
48.0
37.0
30.0
14.6
11.3
9.1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
60000
80000
100000
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
Ft.
M
Ft.
M
Ft.
M
Ft.
M
M
Ft.
M
Ft.
Ft.
M
Ft.
M
Ft.
M
Ft.
M
Ft.
M
Ft.
M
30.0
51.0 51.0 45.0
N/A
9.1
15.5 15.5 13.7
N/A
30.0
24.0 23.0 16.0
N/A
9.1
7.3
7.0
18.0
11.0
9.0
5.5
10.0
3.4
3.0
2.7
0.0
3.0
0.9
0.0
4.9
1.0
0.3
0.0
0.0
N/A
N/A
N/A
N/A
N/A
30.0
135.0 138.0 120.0
N/A
9.1
41.1
42.1
36.6
N/A
30.0
93.0
82.0
69.0
N/A
9.1
30.0
9.1
30.0
9.1
28.3
65.0
19.8
48.0
14.6
25.0
56.0
17.1
40.0
12.2
21.0
44.0
13.4
29.0
8.8
N/A
N/A
N/A
N/A
N/A
30.0
135.0 162.0 141.0
N/A
9.1
41.1
49.4
43.0
N/A
30.0
111.0 98.0
83.0
N/A
9.1
33.8
29.9
25.3
30.0
79.0
68.0
55.0
9.1
24.1
20.7
16.8
30.0
59.0
50.0
38.0
9.1
18.0
15.2
11.6
N/A
N/A
N/A
N/A
N/A
20.0
64.0 64.0 56.0 47.0
6.1
19.5 19.5 17.1 14.3
20.0
32.0 30.0 22.0 11.0
6.1
9.8
9.1
6.7
3.4
20.0
17.0 14.0
6.0
6.1
5.2
4.3
1.8
0.0
0.0
15.0
4.6
7.0
2.1
5.0
1.5
0.0
0.0
0.0
0.0
20.0
6.1
20.0
6.1
20.0
6.1
20.0
6.1
70.0 173.0 150.0 125.0
20.0
70.0 175.0 177.0 147.0
21.3
52.7
45.7
38.1
6.1
21.3
53.3
53.9
44.8
70.0 104.0 87.0
67.0
20.0
70.0 124.0 104.0
82.0
21.3
31.7
26.5
20.4
6.1
21.3
37.8
31.7
25.0
70.0
71.0
57.0
40.0
20.0
70.0
86.0
71.0
21.3
21.6
17.4
12.2
6.1
21.3
26.2
21.6
52.0
15.8
61.0
52.0
40.0
24.0
20.0
70.0
64.0
50.0
18.6
15.8
12.2
7.3
6.1
21.3
19.5
15.2
33.0
10.1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
25.0 79.0 70.0 59.0
7.6
24.1 21.3 18.0
25.0 40.0 31.0 19.0
7.6
12.2
9.4
5.8
23.0 21.0 13.0
0.0
7.0
6.4
4.0
0.0
13.0 10.0
1.0
4.0
3.0
0.3
0.0
0.0
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
25.0 110.0 186.0 155.0
N/A
7.6
33.5
56.7
47.2
25.0 110.0 109.0 86.0
7.6
33.5
33.2
26.2
N/A
N/A
N/A
25.0
91.0
74.0
54.0
7.6
27.7
22.6
16.5
25.0
68.0
53.0
35.0
7.6
20.7
16.2
10.7
N/A
N/A
N/A
N/A
25.0 110.0 219.0 182.0
7.6
33.5
66.8
55.5
25.0 110.0 131.0 104.0
7.6
33.5
39.9
31.7
25.0 110.0
90.0
7.6
33.5
27.4
25.0
83.0
66.0
7.6
25.3
20.1
68.0
20.7
46.0
14.0
120000
20 (-10)
0 (-20)
-20 (-30)
Ft.
M
Ft.
M
Ft.
M
N/A
N/A
N/A
N/A
N/A
N/A
N/A 15.0 85.0 73.0
N/A 4.6
25.9 22.3
N/A 15.0 41.0 29.0
N/A 4.6
12.5
8.8
N/A 15.0 20.0
7.0
N/A 4.6
6.1
2.1
N/A
N/A
N/A
N/A
N/A
N/A
N/A 15.0 100.0 190.0
N/A
N/A 4.6
30.5
57.9
N/A
N/A 15.0 100.0 109.0
N/A
N/A 4.6
30.5
33.2
N/A 15.0
94.0
71.0
N/A 4.6
28.7
21.6
N/A
N/A
N/A
N/A 15.0
100.0 224.0
N/A 4.6
30.5
68.3
N/A 15.0
100.0 131.0
N/A 4.6
30.5
39.9
N/A 15.0
114.0
88.0
N/A 4.6
34.7
26.8
-40 (-40)
Ft.
M
N/A
N/A
N/A 15.0
7.0
N/A 4.6
2.1
0.0
0.0
N/A
N/A
N/A 15.0
69.0
48.0
N/A 4.6
21.0
14.6
N/A
N/A
N/A 15.0
85.0
N/A 4.6
25.9
62.0
18.9
* Not all families have these models.
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length calculated from Table 1 or 3.
† Insulation thickness based on R value of 3.5 per in.
9
RETURN AIR TEMPERATURE
This furnace is designed for continuous return--air minimum temperature of 60
_
F (15
_
C) db or intermittent operation down to 55
_
F (13
_
C) db such as when used with a night setback thermometer. Return--air temperature must not exceed 80
_
F (27
_
C) db. Failure to follow these return air limits may affect reliability of heat exchangers, motors and controls.
80 / 27 ˚ C
SUPPLY AIR
60 / 16 ˚ C
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
POSITION
Rear
Front (Combustion air openings in furnace and in structure)
Required for service
All Sides of Supply Plenum
Sides
Vent
Top of Furnace
* Recommended
CLEARANCE
0 (0 mm)
1 in. (25 mm)
*24 in. (610 mm)
1 in. (25 mm)
0 (0 mm)
0 (0 mm)
1 in. (25 mm)
COMBUSTION--AIR PIPE FOR NON--DIRECT (1--PIPE) VENT APPLICATION
FIELD-SUPPLIED
2-IN. (51 mm) DIA.
TIGHT RADIUS
PVC 90
°
ELBOW
FIELD-SUPPLIED
2-IN. (51 mm) DIA.
PVC PIPE
A10490
12” (300 mm) Minimum
A11487
10
DOWNFLOW SUBBASE
LOCATING
TAB
1 1 /
4
" TYP
PLENUM
OPENING
A
B
D
1 2
3 4
LOCATING
TAB
FACTORY-SUPPLIED
FIELD-INSTALLED
INSULATION
C
4 3
2 1
A97427
Assembled Disassembled
FURNACE
CASING WIDTH
17---1/2 (444.5)
21 (533.4)
24---1/2 (622.3)
FURNACE IN DOWNFLOW
APPLICATION
DIMENSIONS (IN. / MM)
Furnace with or without Cased Coil
Assembly or Coil Box
Furnace with or without Cased Coil
Assembly or Coil Box
Furnace with or without Cased Coil
Assembly or Coil Box
PLENUM OPENING*
A
15---1/8
(384.2)
18---5/8
(396.4)
22---1/8
(562.0)
B
19 (482.6)
19 (482.6)
19 (482.6)
FLOOR OPENING
C D
16---3/4
(425.5)
20---1/4
(514.4)
23---3/4
(603.3)
*The plenum should be constructed 1/4---in. (6 mm) smaller in width and depth than the plenum dimensions shown above.
20---3/8
(517.5)
20---3/8
(517.5)
20---3/8
(517.5)
A88207
HOLE NO. FOR
WIDTH
ADJUSTMENT
3
2
1
Concentric Vent Kit
A93086
A concentric vent kit allows vent and combustion--air pipes to terminate through a single exit in a roof or side wall. One pipe runs inside the other allowing venting through the inner pipe and combustion air to be drawn in through the outer pipe.
Downflow Subbase
A88202
One base fits all furnace sizes. The base is designed to be installed between the furnace and a combustible floor when no coil box is used or when a coil box other than a Carrier cased coil is used. It is
CSA design certified for use with Carrier branded furnaces when installed in downflow applications.
11
23-5/8"
(600mm)
23-3/8”
(594mm)
MEDIA FILTER CABINET
25-5/8"
(651mm)
24-1/4”
(616mm)
Opening with Flanges Bent
23-1/8”
(588mm)
Opening
A
Furnace Side
23-3/4”
(603mm)
Centerline Screw Slots
MEDIA FILTER CABINET
16 (406.4)
20 (508.0)
24 (609.6)
5
3
4
"
(146mm)
DIMENSIONS (IN. / MM)
A
17 (432.8)
21 (533.4)
25 (635.0)
B
16 (406.4)
20 (508)
24 (609.6)
Duct Side
SHIPPED WITH SIZES
040---08, 040---12, 060---08,
060---12, 080---12, 080---16
080---20, 100---16, 100---20
120---20, 140---20
A11456A
BLOWER
DOOR
SWITCH
BLK
WHT
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
BLK
WHT
FIVE
WIRE
THREE-WIRE
HEATING-
ONLY
TYPICAL WIRING SCHEMATIC
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
NOTE 2
W C Y R G
1-STAGE
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
208/230- OR
460-VOLT
THREE
PHASE
JUNCTION
BOX
R
O
L
N
T
C
O
W2
COM
W/W1
Y/Y2
R
G
NOTE 1
CONDENSING
UNIT
GND
208/230-
VOLT
SINGLE
PHASE
24-VOLT
TERMINAL
BLOCK
FURNACE
NOTES:
1.
2.
3.
Connect Y/Y2-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
A11401
12
DIMENSIONAL DRAWING
29 1/2 [749.3]
28 3/4 [730.5]
26 11/16 [678.1]
26 3/8 [370.0]
22 7/16 [670.0]
21 1/16 [535.8]
[44.5] GAS CONN
[22.2] THERMOSTAT ENTRY
28 3/8 [720.4]
28 5/8 [726.9]
30 7/16 [773.7]
16 9/16 [420.9]
17 7/16 [442.3]
20 1/4 [513.9]
11/16 [17.5]
1 5/16 [33.3]
23 3/8 [592.0]
26 5/16 [668.8]
6 15/16 [176.1]
2 3/10 [58.4]
6 11/16 [170.1]
26 11/16 [678.1]
26 3/8 [670.0]
25 1/8 [638.7]
23 5/16 [592.9]
19 1/8 [485.8]
5/8 [15.8]
[76.2] AIR INTAKE
[44.5] GAS CONN
[76.2] VENT
32 5/8 [829.5]
28 5/8 [726.4]
28 3/16 [715.9]
25 3/16 [639.1]
20 1/4 [513.9]
22 15/16 [581.9]
17 5/16 [439.2]
16 9/16 [420.9]
14 13/16 [376.3]
11/16 [17.5]
26 5/16 [668.8]
13
CONDENSATE DRAIN TRAP LOCATION
A11519
GUIDE SPECIFICATIONS
General
System Description
Furnish a ______________________ 4--way multipoise gas--fired condensing furnace for use with natural gas or propane (factory-authorized conversion kit required for propane); furnish cold air return plenum; furnish external media cabinet for use with accessory media filter or standard filter.
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces. Unit will carry the CSA Blue Star
R and Blue Flame
R labels. Unit efficiency testing will be performed per the current DOE test procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the latest AHRI Consumer’s Directory of Certified Efficiency Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only. Warranty certificate available upon request.
Equipment
Blower Wheel and ECM Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and dynamically balanced. Blower motor of ECM type shall be permanently lubricated with sealed ball bearings, of _______hp, and have infinitely variable speed from 300--1300 RPM operating only when 24--VAC motor inputs are provided. Blower motor shall be direct drive and soft mounted to the blower scroll to reduce vibration transmission.
Filters
Furnace shall have reusable--type filters. Filter shall be ______ in.
(mm) X ________ in. (mm). An accessory highly efficient Media
Filter is available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre--painted galvanized steel.
Draft Inducer Motor
Draft Inducer motor shall be two--speed design.
Primary Heat Exchangers
Primary heat exchangers shall be 3--Pass corrosion--resistant aluminized steel of fold--and--crimp sectional design and applied operating under negative pressure.
Secondary Heat Exchangers
Secondary heat exchangers shall be of a stainless steel flow--through of fin--and--tube design and applied operating under negative pressure.
Controls
Controls shall include a micro--processor--based integrated electronic control board with at least 16 service troubleshooting codes displayed via diagnostic flashing LED light on the control, a self--test feature that checks all major functions of the furnace, and a replaceable automotive--type circuit protection fuse. Multiple operational settings available, including separate blower speeds for low heat, high heat, low cooling, high cooling and continuous fan.
Continuous fan speed may be adjusted from the thermostat.
Cooling airflow will be selectable between 325 and 400 CFM per ton of air conditioning. Features will also include temporary reduced airflow in the cooling mode for improved dehumidification when an Infinity Control or TP--PRH edge
R is selected as the thermostat.
Operating Characteristics
Heating capacity shall be _________________ Btuh input;
______________ Btuh output capacity.
Fuel Gas Efficiency shall be __________ AFUE.
Air delivery shall be ________________ cfm minimum at 0.50 in.
W.C. external static pressure.
Dimensions shall be: depth_________in.
(mm); width
__________in. (mm); height___________in. (mm) (casing only).
Height shall be _________in. (mm) with A/C coil and
_________________in. (mm) overall with plenum.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal).
Minimum wire size shall be ________AWG; maximum fuse size of HACR--type designated circuit breaker shall be _________ amps.
Special Features
Refer to section of the product data identifying accessories and descriptions for specific features and available enhancements.
Copyright 2011 Carrier Corp.
S
7310 W. Morris St.
S
Indianapolis, IN 46231 Printed in U.S.A.
Edition Date: 10/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
14
Catalog No: 59TN6A---02PD