DPMbc2-9.qk
1/27/05
3:10 PM
Page 3
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
DPMbc2-9.qk
1/27/05
3:10 PM
Page 2
Digital Panel Meters for
Industrial Monitoring and Control
In many automation and process control applications it is
important to visually monitor and control variables such
as temperature, pressure, vibration etc. A digital panel
meter can perform these functions and more - it can
provide analog and/or serial re-transmission of the
measured value for feedback or data-logging purposes.
Carlo Gavazzi offers a complete range of digital panel
meters from very basic indicators with no outputs (DI
Series) to more complex types (UDM Series), which
provide new features, such as the new multi-color alarm
display (also called the "traffic light" function) and the
16-point linearization feature for non-linear input signals.
With its modular design, the new UDM Series offers great
flexibility by providing any input/output combination.
The range includes a new cost-effective Universal Signal
Conditioner (USC Series), which is a DIN rail mounted,
modular device. By sharing the same input/output
modules as the UDM Series, it offers a tremendous
number of measuring and control capabilities with a very
limited number of modules being required.
2
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
DPMbc2-9.qk
1/27/05
3:10 PM
Page 3
The Characteristics
A wide range of available inputs for
various applications: voltage, current,
frequency, resistance and temperature
Modular architecture for medium and
high-end meters, offering flexiblity
and easy configuration
Different types of outputs available to
retransmit the measured variable:
analog signal, alarm contacts or serial port
Easy to program via keypad or software ports
3, 3 1/2 or 4-digit LED display with
alarm and over-range indication
3
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
DPMbc2-9.qk
1/27/05
3:10 PM
Page 4
A New Concept of Modularity
USC: 5-slot Module Holder
• Maximum In-field Flexibility
• Quick Assembly and Configuration
• Easy Future Expansion
Measurement Inputs
0.2-2-20mA AC/DC
0.2-2-20mA AC/DC + excitation output
0.2, 2, 5A AC/DC; 20, 200, 500V AC/DC
TC: J-K-S-T-E, Pt100-250-500-1000, Ni100
Ω: 0.02, 0.2, 2, 20kΩ
4
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
UD
3-
DPMbc2-9.qk
1/27/05
3:10 PM
Page 5
UDM35: 3 1/2-Digit Read-out,
3-Digit + Dummy 0 Read-out
Display Base
UDM40: 4-Digit
Read-out, 3-Color Display
Power Supply
90 to 260V AC/DC
18 to 60V AC/DC
Communication Port
RS485 and RS232 ports
Outputs
Analog outputs:
Max 1 analog output:
0 to 20mA or 0 to 10VDC
Alarm outputs:
1 relay output
2 relay outputs
2 relay + 2 open collector outputs
4 relay outputs
Specifications are subject to change without notice.
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
5
DPMbc2-9.qk
1/27/05
3:10 PM
Page 6
Features and Benefits of the Digital Panel Meters
DI3 DIN, DI3 72, LDI3
• Indicators for DIN-rail and panel mounting
• Various input capabilities
• Easy product configuration via dip switches
MDM40
UDM40
LDI35, LDM35H
UDM35
•
•
•
•
UDM35
Price
• Multi range and multi signal indicator and controller
• Powerful scaling capability
• Universal power supply (LDM35H only)
USC
LDI35/LDM35
Powerful performance
Plug and play modules
Maximum in-field flexibility
Possibility to expand the inputs/outputs
as required
DI3 LDI3
Features
UDM40
•
•
•
•
State of the art performance
Maximum in-field flexibility
Input signal linearization capability
3-color display
USC
•
•
•
•
Universal signal conditioner
Maximum in-field flexibility
Input signal linearization capability
Programming and network software
MDM40
•
•
•
•
Two-alarm tachometer
Dual input and multifunction capability
Management of all available sensors
Reverse speed control
LDI35, LDM and UDM
In process control
applications, it is
important to be able to
manage signals such
as “mA and volts”
which are proportional
to pressure or other
variables being
measured.
The LDI, LDM or UDM
Series fulfill this
requirement with
powerful scaling and
filter capabilities.
UDM40 Color Display
RED
High priority,
abnormal condition
AMBER
Low priority,
abnormal condition
GREEN
Normal condition
6
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
DPMbc2-9.qk
1/27/05
3:10 PM
Page 7
Available Modules
Type
Output(s) UDM35
UDM40
USC
Ordering Code
UDM35 base
BD35
UDM40 base
BD40
USC base
BDXX
AC/DC inputs: 200µA, 2mA, 20mA, 200mV, 2V, 20V
1
BQLSX
AC/DC inputs: 200µA, 2mA, 20mA, 200mV, 2V, 20V + excitation output
1
BQLSE
AC/DC inputs: 200mA, 2A, 5A, 20V, 200V, 500V
1
BQHSX
Inputs: 20Ω, 200Ω, 2kΩ,20kΩ; TC: J-K-S-T-E, Pt100-250-500-1000, Ni100
1
BQTRX
Analog output: 0 to 20mA, 0 to 10V DC
1
BOAV
Relay output
1
BOR1
Relay output
2
BOR2
Outputs: 2 relays + 2 open collectors
4
BOR4
4 Relay output
4
BOR5
RS485 communication port
1
BRSX
RS232 communication port
1
BRSY
18 to 60V AC/DC power supply
BPL
90 to 260V AC/DC power supply
BPH
UDM35 / UDM40
USC
Slot
A
B
C
D
A
B
C
D
E
Inputs/Outputs
1
2
3
4
1
2
3
4
5
Measurement inputs: LSX, LSE, HSX, TRX
RS485 communication port: SX
RS232 communication port: SY
Analog output (*): AV
Relay and open collector outputs: R1, R2, R4, R5
Power supply: H, L
(*) Note: A maximum of one analog output module
Specifications are subject to change without notice.
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
7
DPMbc2-9.qk
1/27/05
3:10 PM
Page 8
DI3 DIN
Page 10
DI3 72
Page 10
LDI3
Page 10
LDI35
Page 11
DIN rail mounting
Panel mounting
Modular
Indicator
Controller
3-color display
Signal conditioner
Linearization capability
Multi input (A-V)
Temperature measurement
Tachometer
Command inputs
Up to 1 alarm
Up to 2 alarms
Up to 4 alarms
Analog output
Serial communication
Universal power supply
8
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
DPMbc2-9.qk
1/27/05
3:10 PM
Page 9
Modular
LDM35H
Page 12
MDM40
Page 13
UDM35
Page 14
UDM40
Page 15
USC
Page 16
Specifications are subject to change without notice.
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
9
DPM10-19.qk
1/27/05
3:08 PM
DI3 DIN
Page 10
DI3 72
LDI3
This series includes three basic indicators and is a cost
effective solution for panel builders.
DI3 DIN
The best DPM to suit your needs!
Description
Housing (H x W x D)
Performance
Mounting
Display type
Variables on display
Measured signals
DI3 72, LDI3
DI3 DIN
Hardware
10
Functions
Type of signals
Engineering units
Accuracy
Temperature drift
Sampling rate
Command inputs
Outputs:
Alarm
Analog
Serial
Signal/display scaling
Power supply
Approvals
Protection degree
DI3 72
LDI3
3-DGT µP-based indicator
89 x 53.5 x 58.8 mm (DIN)
72 x 72 x 75 mm (72)
48 x 96 x 83 mm (LDI3)
DIN rail, panel mounting (72, LDI3)
3 DGT, red LED
YES
1A/60mV/100-500VDC
1A/100VAC, 5A/500VAC
1 to 1000Hz
DC or AC
mA, A, V, Hz
±(0.5%FS, + 1DGT)
±350ppm/°C
1 time per second
Not Available
Not Available
Not Available
Not Available
YES (CT and PT sel. by dip-switch)
24V, 48V, 115V, 230V AC
UR (except DI3), CSA, CE
IP40 (DIN); IP50 (72), IP50
(LDI3), IP65 (LDI3 on request)
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
1/27/05
3:08 PM
Page 11
LDI35
This series is available in two basic models:
• LDI35, offered as an indicator only
• LDI35, with one alarm relay output
Each model has a specific version for:
• Process applications with 2-20mA and 0.2-20V-200V input
• Higher current/voltage applications with 2-5A and
200-500VAC/DC input
The range includes an ohmmeter and a temperature controller
which can accept various types of RTDs and thermocouples.
LDI35
Description
The best DPM to suit your needs!
Performance
DPM10-19.qk
Housing (H x W x D)
Mounting
Display type
Variables on display
Measured signals
Type of signals
Engineering units
Accuracy
Hardware
Functions
Input/Output
Temperature drift
Sampling rate
Command inputs
Outputs:
Alarm
Analog
Serial
Other available characteristics
Power supply
Approvals
Protection degree
3 1/2-DGT µP-based indicator
and controller
48 x 96 x 83 mm
Panel mounting
3 1/2-DGT or 3DGT+ dummy 0, red LED
YES
(2-20mA, 20-200V); (2-5A, 200500V); (TC: J-K-S-T-L, Pt100-1000,
Ni100, 200-2000 Ω)
DC and AC
Label set
DC: ±(0.3%FS + 1DGT)
AC: ±(0.5%FS + 1DGT)
±200ppm/°C
4 times per second
Not Available
Up to 1
Not Available
Not Available
Signal/display scaling. Digital
filter, Peak and valley. Burn-out
control on temperature input
24, 48, 115, 230VAC, 9 to 32VDC,
40 to 150VDC
UR, CSA, CE
IP65 (on request)
Specifications are subject to change without notice.
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
11
DPM10-19.qk
1/27/05
3:08 PM
Page 12
LDM35H
This series is available in two basic models:
• LDM35H, offered as an indicator only
• LDM35H, with one or two relay outputs
Both versions are provided with a universal power supply
Each model has a specific version for:
• Process applications with 0.2-2-20mA and
0.2-2-20V DC/AC input
• Higher current/voltage applications with 0.2-2-5A and
20-200-500V AC/DC input
TRMS measurement significantly improves the accuracy
of the measurement on both distorted current and
voltage signals.
LDM35H
Description
Housing (H x W x D)
Mounting
Display type
The best DPM to suit your needs!
Variables on display
Measured signals
Type of signals
Engineering units
Accuracy
Performance
Temperature drift
Sampling rate
Command inputs
Outputs:
Alarm
Analog
Serial
Other available characteristics
Hardware
Functions
Input/Output
Power supply
Approvals
Protection degree
12
3 1/2-DGT µP-based indicator
and controller
48 x 96 x 83 mm
Panel mounting
3 1/2-DGT or 3-DGT + dummy 0,
red LED
YES
(0.2-2-20mA, 0.2-2-20V); (0.2-2-5A,
20-200-500V)
DC and AC TRMS
Self sticking label set
DC: ±(0.3%RDG + 3DGT)
AC: ±(0.5%RDG + 3DGT)
±150ppm/°C
5 times per second
Not Available
Up to 2
Not Available
Not Available
Signal/display scaling. Digital
filter, Peak and valley.
90 to 260V AC/DC,
18 to 60V AC/DC
UR, CSA, CE
IP65, IP67 (on request)
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
1/27/05
3:08 PM
Page 13
MDM40
The MDM40 tachometer is a high performance instrument
which is suitable to be used in all applications requiring:
• The capability to measure a very slow speed or
frequency (0.001 Hz)
• The management of pulse signals from proximity switches,
photoelectric sensors, NAMUR proximity sensors,
encoders and magnetic switches
• The rate-tacho-frequency-period meter functions
The two independent inputs, with proper parameter programming are capable of measuring rate, speed, frequency
and period variables using mathematical formulas such as:
A, B, 1/A, A/B, A-B, (A-B)/B, B/(A+B) and reverse speed
control.
The best DPM to suit your needs!
Performance
DPM10-19.qk
Hardware
Functions
Input/Output
MDM40
Description
4-DGT multi-range controller for
pulse signal
Housing (H x W x D)
48 x 96 x 124 mm
Mounting
Panel mounting
Display type
4 DGT, red LED
Variables on display
YES
Measured signals
Speed, frequency, rate, period
Type of signals
DC or AC
Engineering units
Label set
Accuracy
±(0.001% RDG + 3DGT)
Temperature drift
±100ppm/°C
Sampling rate
Programmable
Command inputs
1 (display hold, key pad lock)
Outputs:
Alarm
2
Analog
1 (20 mA, 10 VDC)
Serial
RS485
Other available characteristics Signal/display and analog out scaling.
Digital filter.
Peak and valley.
24,48,115,120,230,240 VAC
Power supply
9 to 32, 40 to 150 VDC
Approvals
UR, CSA, CE
Protection degree
IP65, IP67 (on request)
Specifications are subject to change without notice.
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
13
DPM10-19.qk
1/27/05
3:08 PM
Page 14
Modular Panel Meter
UDM35
The UDM 35 is a universal Digital Panel Meter that has
been developed to meet the most advanced application
requirements. The UDM35 offers:
• Quick assembly and maintenance using
plug and play modules
• Easy and quick parameter programming and
parameter cloning on other UDMs by means of
UdmSoft or PC HyperTerminal
• Powerful variable control by means of up to four alarms
• Analog output and RS485/RS232 communication ports
UDM35
The different type of alarm controls:
• Up-down functions with automatic reset
• Up-down functions with manual reset
• Down with disable function at power-on
These alarms can be
combined to offer up
to four abnormal steps
known as pre-alarms
and alarms.
Performance
The best DPM to suit your needs!
Hardware
14
Functions
Input/Output
Description
3 1/2-DGT µP-based controller
with modular housing
Housing (H x W x D)
48 x 96 x 105 mm
Mounting
Panel mounting
Display type
3 1/2-DGT or 3-DGT + dummy 0,
red LED
Variables on display
YES
(0.2-2-20mA, 0.2-2-20V); (0.2-2-5A,
Measured signals
20-200-500V); (TC: J-K-S-T-E, RTD, Ω)
Type of signals
DC and AC TRMS
Engineering units
Self sticking label set
DC: ±(0.1%RDG + 3DGT)
Accuracy
AC: ±(0.3%RDG + 3DGT)
Temperature drift
±150ppm/°C
Sampling rate
5 times per second
Command inputs
1 (display hold, key pad lock or
latch alarm reset)
Up to 4
Outputs:
Alarm
1 (20mA,10VDC)
Analog
Serial
RS485, RS232
Other available characteristics Signal/display scaling. Analog
output scaling. Digital filter, Peak
and Valley. Burn-out control on
temperature inputs only.
90 to 260 AC/DC,
Power supply
18 to 60V AC/DC
Approvals
UR, CSA, CE
Protection degree
IP65, IP67 (on request)
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
1/27/05
3:08 PM
Page 15
Modular Panel Meter
UDM40
The UDM40 offers the same basic characteristics as the
UDM35, but with these additional benefits:
• Display color adaptable to other existing instruments
by means of a 3-color choice
• Management of non linear signals coming from special
process transmitters using a 16-point linearization capability
• Provides reliable process information, working out a
complex or disturbed signal by a programmable
input integration time and/or a smart digital filter
Alarm status at a glance using the easy “traffic light”
principle. The instrument may show the alarm status based on
a sequence of colors that can be programmed by the user.
UDM40
Description
Housing (H x W x D)
Mounting
Display type
Variables on display
Measured signals
Type of signals
Engineering units
Accuracy
The best DPM to suit your needs!
Temperature drift
Sampling rate
Command inputs
Outputs:
Alarm
Analog
Serial
Other available characteristics
Performance
DPM10-19.qk
Power supply
Hardware
Functions
Input/Output
Approvals
Protection degree
4-DGT µP-based controller with
modular housing
48 x 96 x 105 mm
Panel mounting
4-DGT, color LED
YES
(0.2-2-20mA, 0.2-2-20V); (0.2-2-5A,
20-200-500V); (TC: J-K-S-T-E, RTD, Ω)
DC and AC TRMS
Self sticking label set
DC: ±(0.1%RDG + 3DGT)
AC: ±(0.3%RDG + 3DGT)
±150ppm/°C
5 times per second
1 (display hold, key pad lock or
latch alarm reset)
Up to 4
1 (20mA, 10VDC)
RS485, RS232
Signal/display scaling. Analog output
scaling. Digital filter. Integration time.
Peak and valley. Burn out control on
temperature inputs only. Linearization.
“Traffic light” function.
90 to 260 AC/DC,
18 to 60V AC/DC
UR, CSA, CE
IP65, IP67 (on request)
Specifications are subject to change without notice.
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
15
DPM10-19.qk
1/27/05
3:08 PM
Page 16
Modular Signal Conditioner
USC
The key benefit of the USC Universal Signal Conditioner is
its architecture. It is created with a module holder on
which it is possible to plug in modules with different
functions: power supply, measurement, alarm, control
and signal retransmission. The different combination of the
modules allows for a simple signal conditioner or a very
sophisticated controller with communication port.
The USC offers:
• Easy and quick parameter programming and parameter
cloning on other USCs by means of UscSoft or PC
HyperTerminal
• Powerful variable control by means of up to four alarms
• Remote control via an analog output
• RS485 and RS232 communication ports
• Management of non linear signals coming from special
process transmitters using a 16-point linearization capability
• Reliable process information, working out a complex
or disturbed signal by a programmable input
integration time and/or smart digital filter
• Interchangeable I/O modules with the UDM Series
The Best Signal Conditioner to suit your needs!
The LEDs on the modules
show the power supply and
communication status all the
time.
USC
Description
Housing (H x W x D)
Mounting
Display type
Variables on display
Measured signals
Type of signals
Engineering units
Accuracy
Performance
Temperature drift
Sampling rate
Command inputs
Outputs:
Alarm
Analog
Serial
Other available characteristics
Hardware
Functions
Input/Output
Power supply
Approvals
Protection degree
16
µP-based signal conditioner with
modular housing
44 x 113 x 107 mm
DIN-rail mounting
Not Available
Not Available
(0.2-2-20mA, 0.2-2-20V); (0.2-2-5A,
20-200-500V); (TC: J-K-S-T-E, RTD, Ω)
DC and AC TRMS
Not Available
DC: ±(0.1%RDG + 3DGT)
AC: ±(0.3%RDG + 3DGT)
±150ppm/°C
5 times per second
1 (latch alarm reset)
Up to 4
1 (20mA, 10VDC)
RS485, RS232
Signal/display scaling. Analog
output scaling. Digital filter.
Integration time. Peak and valley.
Burn-out control on temp.Inputs
only. Linearization up to 16 points.
90 to 260 AC/DC,
18 to 60V AC/DC
UR, CSA, CE
IP20
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
DPM10-19.qk
1/27/05
3:08 PM
Page 17
Accessories
Types
SIU-PC85
SIU-DIN 8585
SIU-DIN.RLY
PSU-DIN (DC/AC)
PSU-DIN (AC/DC)
Serial communication
line adapter
Front: 65x80mm
RS232
2-wire comm.
N.A.
N.A.
9-pole, female
RS422
RS485
Serial communication
line amplifier, driver
Front: 89x71.5mm
RS485, RS422
2 or 4-wire comm.
YES
YES
Screw terminal block
RS422
Serial communication
relay outputs
Front: 89x71.5mm
RS485, RS422
2 or 4-wire comm.
N.A.
YES
Screw terminal block
4 relays
5A, 250V
Working mode
Line Bias
Line termination
Connections
Baud rate
Protection
Indication
(by means of LEDs)
4-wire comm.
YES
YES
Screw terminal block
Max 19200 Baud
All inputs/outputs
Power-on
Data-stream
4-wire comm.
YES
YES
Screw terminal block
Max 19200 Baud
All inputs/outputs
Power-on
Power supply unit
AC to DC
Front: 89x71.5mm
N.A.
N.A.
N.A.
N.A.
Screw terminal block
5VDC (max. 200mA)
12VDC (max. 100mA)
24VDC (max. 50mA)
By transformer
N.A.
N.A.
Screw terminal block
N.A.
Output: electronic
Power-on
Insulation
Input/output: 2kV
input/output and
power supply: 4kV
0 to +50°C (R.H.
≤90% non condensing)
-10 to +60°C (R.H.
≤90% non condensing)
1.8m cable with 9 to
9-pole connectors,
power supply cable
Input/output: N.A.
input/output and
power supply: 4kV
0 to +50°C (R.H.
≤90% non condensing)
-10 to +60°C (R.H.
≤90% non condensing)
N.A.
SPDT contacts
N.A.
N.A.
Screw terminal block
Max 9600 Baud
N.A.
Power-on
Comm. status
Output status
Input/output: 2kV
input/output and
power supply: 4kV
0 to +50°C (R.H.
≤90% non condensing)
-10 to +60°C (R.H.
≤90% non condensing)
N.A.
Power supply unit
DC to AC
Front: 89x71.5mm
N.A.
N.A.
N.A.
N.A.
Screw terminal block
24VDC (max. 250mA)
48VDC (max. 125mA)
115VDC (max. 50mA)
Switching mode
N.A.
N.A.
Screw terminal block
N.A.
Output: by fuse
Power-on
N.A.
Input/output: 4kV
0 to +50°C (R.H.
≤90% non condensing)
-10 to +60°C (R.H.
≤90% non condensing)
N.A.
0 to +50°C (R.H.
≤90% non condensing)
-10 to +60°C (R.H.
≤90% non condensing)
N.A.
Other characteristics
Wrong-line connection and full overvoltage protection.
Reverse conversion
capability.
Dual purpose: distance increase by
1200m per unit; network increase
4 relay outputs to be
driven by an RS485
communication port
Stabilized AC voltage
output.
Stability: ≤4%
Un @ max. current
Power supply input
24VAC, 48VAC
115VAC, 230VAC
24VAC, 48VAC
115VAC, 230VAC
24VAC, 48VAC
115VAC, 230VAC
Protection degree
IP20
IP40
IP40
80 to 240VDC
18 to 60VDC
9 to 16VDC
IP40
Stabilized DC voltage
output.
Stability: ≤0.5%
Un @ max. current
Non-stabilized DC
voltage outputs:
2V-20V-30VDC
24VAC, 48VAC
115VAC, 230VAC
Description
Housing
Signal input
Working mode
Line Bias
Line termination
Connections
Output
Operating temperature
Storage temperature
Included set
IP40
Specifications are subject to change without notice.
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com
17
DPM10-19.qk
1/27/05
3:08 PM
Page 18
Current Transformer
Types
Class
Bus–bar size
Dimensions (H x W x D)
Standards
Accuracy class
depending on the
burden output
Primary current at
rated output
current of 1A/5A
Types
Class
Bus–bar size
Dimensions (H x W x D)
Standards
Accuracy class
depending on the
burden output
Primary current at
rated output
current of 1A/5A
TADK
TADK2
TAD 2
TAD 3
TAD 4
0.5
Wounded primary
115.5x75x44 mm
IEC 60185/EN 60185
Class 0.5
Burden
VA
1 A 10
5 A 10
10 A 10
15 A 10
25 A 10
40 A 10
0.5
25x5 mm fixed bar
115.5x75x44 mm
IEC 60185/EN 60185
Class 0.5
Burden
VA
1 A 10
5 A 10
10 A 10
15 A 10
25 A 10
40 A 10
50 A 10
60 A 10
80 A 10
100 A 10
150 A 10
200 A 10
250 A 10
0.5/ 1/ 3
Ø 22 mm
98.5x58x44 mm
IEC 60185/EN 60185
Class 0.5 1
3
Burden
VA
VA VA
40 A
3
50 A
3
60 A
3
80 A
3
100 A
3
4
150 A 3
4
6
200 A 3
4
6
250 A 5
8
10
300 A 5
8
10
0.5/ 1
21x14 or 31x11 mm
98.5x58x44 mm
IEC 60185/EN 60185
Class 0.5 1
Burden
VA
VA
100 A
3
150 A 3
4
200 A 3
4
250 A 5
8
300 A 5
8
400 A 6
10
500 A 6
10
600 A 6
10
0.5/1
32x16, 41x11, Ø 32 mm
75x115.5x44 mm
IEC 60185/EN 60185
Class 0.5 1
Burden
VA
VA
100 A
3
150 A
3
200 A 4
250 A 6
300 A 6
400 A 10
500 A 10
600 A 10
800 A 10
TAD 6
TAD 8
TAD 12
TACO 110
TACO 200
0.5/1
55x22, 65x20, Ø 52 mm
105x145x44 mm
IEC 60185/EN 60185
Class 0.5 1
Burden
VA
VA
400 A 6
12
500 A 6
12
600 A 10
20
800 A 10
20
1000A 20
40
1200A 20
40
1500A 30
60
2000A 30
60
0.5/1/5P10
82x32 or 65x34 mm
140x120x55 mm
IEC 60185/EN 60185
Class 0.5 1 5P10
Burden
VA
VA VA
400 A 4
8
5
500 A 6
12
5
600 A 10
20
5
800 A 15
30
5
1000A 20
40
5
1200A 30
50
5
1500A 40
60
5
2000A 50
80
5
2500A 60
100 5
0.5/1/5P10
127x51 or 102x53 mm
183x170x65 mm
IEC 60185/EN 60185
Class 0.5 1 5P10
Burden
VA VA VA
800 A 15 30 10
1000A 20 40 10
1200A 30 60 10
1500A 40 80 10
2000A 50 100 10
2500A 60 120 10
3000A 80 160 10
4000A 100 200 10
0.5/1/5P10
Max. Ø 110 mm
183x170x 65 mm
IEC 60185/EN 60185
Class 0.5 1 5P10
Burden
VA VA VA
800 A 15 30 10
1000A 20 40 10
1500A 40 80 10
2000A 50 100 10
2500A 60 120 10
3000A 80 160 10
4000A 100 200 10
0.5/1/5P10
Max. Ø 200 mm
295x280x45 mm
IEC 60185/EN 60185
Class 0.5 1 5P10
Burden
VA VA VA
1000A 15 30 10
1500A 15 30 10
2000A 15 30 10
2500A 40 80 10
3000A 40 80 10
4000A 50 100 10
5000A 50 100 10
6000A 50 100 10
Cable/Bus–bar type current transformers. Standard output 5A (1A on request). Rated primary currents from 40A to 6000A. DIN–rail or panel mounting.
Current transformer 1-phase AC; operating frequency: 40 to 60 Hz; max system voltage: 0.72 kV; rated insulation level: 3kV/1min @ 50Hz; security factor: ≤5;
rated secondary current: 5A standard (1A on request).
A full range of split-core current
transformers is available from 100A to 6000A
18
To instantly view a data sheet and specify products, visit www.GavazziOnline.com
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · sales@grossautomation.com