Air Conditioning
Technical Data
4-way blow ceiling suspended unit
EEDEN13-100
FUQ-C
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
TABLE OF CONTENTS
FUQ-C
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
3
Safety Device Settings
4
5
.......... ........... .......... .......... .......... .......... . 6
Options
. .......... ........... .......... .......... .......... .......... . 6
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Piping diagrams
Piping Diagrams
7
...... .......... .......... .......... .......... . 5
Options
Dimensional Drawings
6
9
7
...... .......... .......... .......... .......... . 7
........... .......... .......... .......... .......... . 8
. ........... .......... .......... .......... .......... . 8
Wiring diagrams
........... .......... .......... .......... .......... . 9
Wiring Diagrams - Single Phase
8
3
..... .......... .......... .......... . 9
External connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
External Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
Sound Pressure Spectrum
• Split - Sky Air • Indoor Unit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
1
tk iSw no Ul - b r t oy Ci oa - dlwQ np- U •IS4F
Features
User friendly remote control with contemporary design
•
Ideal solution for commercial spaces with no or narrow false ceilings
•
Easy to use: all main functions directly accessible
1
•
Low energy consumption thanks to specially developed small tube
heat exchanger, DC fan motor and drain pump
1
•
Easy setup: clear graphical user interface for advanced menu
settings
•
Stylish unit blends easily with any interior, as the flaps close entirely
when not in operation
•
Optimise your air conditioning system by activating a series of energy
saving functions (temperature range limit, setback function, off timer,
…)
•
Improved comfort thanks to automatic air flow adjustment to required
load
•
Keep track of your energy consumption with the kWh indication
showing an indicative electricity consumption
•
Individual flap control: one or more flaps can be easily closed via the
wired remote controller (BRC1E52) in case you would refurbish or
rearrange your interior
•
Set up to 3 independent schedules, so the user can easily change the
schedule himself throughout the year (e.g. summer, winter, midseason)
•
Can be installed in both new and existing buildings
•
Real time clock with auto update to daylight saving time
•
Same outlook for all models (unified dimensions)
•
Supports multiple languages (English, German, Dutch, Spanish,
Italian, Portuguese, French, Greek, Russian, Turkish and Polish)
•
Auto swing function ensures efficient air and temperature distribution
•
Possibility to individually restrict menu functions
•
Air can be discharged in 5 different angles between 0 and 60º
•
When a power failure occurs all settings remain stored up to 48 hours
thanks to the built-in backup power
•
Possibility to shut 1 or 2 flaps for easy installation in corners
•
Home leave operation maintains the indoor temperature at your
specified comfort level during absence, thus saving energy
•
Air flow distribution for ceiling heights up to 3.5m without capacity
loss
•
No optional adapter needed for DIII-connection, link your unit into the
wider building management system.
3 steps
standard
2
• Split - Sky Air • Indoor Unit
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
2
Specifications
2-1 Technical Specifications
Power input - 50Hz
Casing
Dimensions
Cooling
Heating
Colour
Material
Unit
Packed unit
Weight
Packing
Heat exchanger
Fan
Unit
Packed unit
Material
Weight
Inside length
Length
Outside length
Rows
Fin pitch
Face area
Stages
Empty tubeplate
hole
Tube type
Tube material
Tube diameter
Fin
mm
mm
295/1,026/1,016
kg
mm
mm
mm
Quantity
25
36
Carton / OSB boar d
mm
m²
1
2
Carton / OSB board
8.3
2,413
-
Car ton / OSB board
2,360
2,413
2,467
3
1.2
0.3380
Quantity
Quantity
0.3300
10
0
mm
Type
Treatment
Cooling High
Nom.
Low
Quantity
Model
Index of Pr otection
Insulation gr ade
Poles
Drive
Speed
3
26
38
2
Heating High
Cooling
Heating
0.185
0.180
Height/Width/
Depth
Height/Width/
Depth
Low
Sound power level
FU Q125 C
0.163
0.158
Fresh White
Resin
198/950/950
kg
kg
Type
Quantity
Air flow rate
Output
Phase x Voltage
Full load amps
(FLA)
FUQ100C
0.109
0.103
kW
kW
Nom.
Fan motor
FUQ7 1C
Nom.
Nom.
m³/min
cfm
m³/min
cfm
m³/min
cfm
m³/min
cfm
m³/min
cfm
m³/min
cfm
23
812
19.5
689
16
565
23
812
19.5
689
16
565
ARW5203DK
Steps
Cooling High/
Mediu
m/Low
Heating High/
Mediu
m/Low
High
Cooling
Heating
High/Nom./Low
High/Nom./Low
rpm
608/528/448
rpm
608/528/448
W
V
A
A
dBA
dBA
46
• Split - Sky Air • Indoor Unit
0.7
0.7
59/56/51
59/56/51
Hi-XA
Copper
5.0
Multi slit fin
Anti Corr osion Hydrophilic
Turbo fan
1
31
1,095
25.5
901
20
706
31
1,095
25.5
901
20
706
1
EHDS10DDK
20
Class "E"
8
Direct drive
3
804/680/555
804/680/555
32.5
1,148
26.5
936
20.5
724
32.5
1,148
26.5
936
20.5
724
840/697/555
840/697/555
106
DC280V
1.0
1.0
64/60/55
64/60/55
1.1
1.1
65/61/56
65/61/56
3
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
2
Specifications
2-1 Technical Specifications
1
2
Sound pressure level
Cooling
Heating
Refr iger ant
Piping connections
Type
Sound absorbing insulation
Liquid
Type/OD
Gas
Type/OD
Drain
Heat insulation
Air direction control
Air filter
High/Nom./Low
Super high/High/
Nom./Low
Type
Quantity
dBA
dBA
FUQ7 1C
FU Q100 C
FUQ12 5C
41/38/35
-/41/38/35
46/42/39
-/46/42/39
47/43/40
-/47/43/40
R- 410A
Not needed
C1220T (Flare connection) /9.52
C1220T (Flare connection) /15.9
VP25 (OD Ø32.0)
Needed
Up and downwards
Resin net with mold r esistance
1
600
mm
mm
pc
mm
Drain-up height
Standard Accessor ies : Drain hose;
Standard Accessor ies : Declaration of conformity;
Standard Accessor ies : Operation manual;
Standard Accessor ies : Installation manual;
Standard Accessor ies : Clamp metal;
Standard Accessor ies : Washer for hanger bracket;
Standard Accessor ies : Clamps;
Standard Accessor ies : Washer clamp;
Standard Accessor ies : Joint insulation & Sealing material;
Standard Accessor ies : Elbow;
Standard Accessor ies : Installation pattern;
Standard Accessor ies : Blocking material;
Standard Accessor ies : L-bent piping;
Standard Accessor ies : Screws;
Standard Accessor ies : Non woven fabric;
2-2 Electrical Specifications
Power supply
Current - 50Hz
Current - 60Hz
4
FUQ7 1C
Name
Phase
Frequency
Voltage
Maximum r unning current
Nominal running current
Hz
V
A
A
• Split - Sky Air • Indoor Unit
0.9
FU Q100 C
VE
1~
50/60
220- 240/220
1.3
-
FUQ12 5C
1.4
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
3
Safety device settings
3-1
Safety Device Settings
3
1
3
• Split - Sky Air • Indoor Unit
5
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
4
Options
4-1
Options
1
4
6
• Split - Sky Air • Indoor Unit
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
5
Dimensional drawings
5-1
Dimensional Drawings
3
1
5
• Split - Sky Air • Indoor Unit
7
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
6
Piping diagrams
6-1
Piping Diagrams
1
6
8
• Split - Sky Air • Indoor Unit
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
7
Wiring diagrams
7-1
Wiring Diagrams - Single Phase
3
1
7
• Split - Sky Air • Indoor Unit
9
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
8
External connection diagrams
8-1
External Connection Diagrams
1
8
10
• Split - Sky Air • Indoor Unit
• Indoor Unit • 4-way blow ceiling suspended unit • FUQ-C
9
Sound data
9-1
Sound Pressure Spectrum
3
1
9
• Split - Sky Air • Indoor Unit
11
The present leaflet is drawn up by way of inf ormati on only and does not
const itut e an of fer binding upon Daikin Europe N.V .. Daikin Europe N.V .
has compiled the content of t his l eaf let t o the best of it s knowl edge. No
express or i mplied warranty is given f or t he completeness, accuracy, reliability or fit ness f or parti cular purpose of its content and t he product s
and services present ed therein. Specifications are subject t o change
without prior not ice. Dai kin E urope N.V. expl icit ly rejects any liabi lity f or
any direct or indirect damage, in the broadest sense, arising from or related t o t he use and/or int erpret ation of t hi s leaf let. Al l cont ent i s copyright ed by Daikin E urope N.V.
Daikin Europe N. V. participat es in the Eurovent Cert ification programme for Air conditioners (AC), Liquid Chill ing Packages
(LCP) and Fan coil unit s (FCU), Check ongoing validity of certifi cate online: www.eurovent -cert ificat ion.com
or
usi ng:
www.certif lash.com”
BARCODE
Daikin products are dist ributed by:
N aamloze Ve nnootschap - Z andvoordestraa t 30 0, B-8400 Oostend e - Be lgium - w ww.d aikin.eu - BE 0412 120 336 - R PR Ooste nde
EED EN13 -100 • 1 1/12 • Cop yrigh t Da ikin
The p resen t pu bli cation su perse des EEDEN 12-1 00
Daikin’s unique posit ion as a m anufact urer of air
condit ioning equipment, com pressors and refrigerants has led to it s close involvement in environment al issues. For several years Daikin has had the
int enti on to become a leader i n the provision of
products that have limit ed i mpact on the environment. This chall enge demands t he eco desi gn and
development of a wide range of products and an energy m anagement system, resulting in energy conservat ion and a reduct ion of waste.