Air Conditioners
Technical Data
W a l l M o u n t e d U n i t
CTXU-G
E E D E N 1 0 - 1 0 0
Air Conditioners
Technical Data
W a l l M o u n t e d U n i t
CTXU-G
E E D E N 1 0 - 1 0 0
• Indoor Units • R-410A • CTXU-G2V1B
TABLE OF CONTENTS
CTXU-G2V1B
1
2
3
4
5
6
Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
For indoor units only
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensional drawing & centre of gravity
. . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional drawing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Centre of gravity
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Piping diagram
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring diagram
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring diagram
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Sound data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound pressure spectrum
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
• Split Sky Air • Indoor Units 1
• Indoor Units • R-410A • CTXU-G2V1B
1 Features
y ni k 1B S 2V 0A or XU do 41 p CT S R• URURU humidification: maintains a comfortable humidity level without any separate water supply
• Especially designed to combine with Ururu multi outdoor unit (MXU)
• Fresh air intake for healthy living
• 2 area intelligent eye: air flow is sent to the area in a room where no person is detected
• Weekly timer: allows to program the unit on a weekly basis
• Comfort mode guarantees draught free operation
• 3D air flow
• Dual air discharge flow for better air distribution
• ECONO mode decreases power consumption so that other appliances that need large power supply can be used
• Flat front panel: its stylish appearance blends easily within any interior décor and is more easy to clean.
• Indoor / outdoor unit silent operation
• Powerful mode can be selected for rapid cooling or heating
• Titanium apatite photocatalytic air purification filter absorbs microscopic particles, decomposes odours and even deactivates bacteria and viruses standard
2 integrated titanium apatite
• Split Sky Air • Indoor Units
2 rooms
2
• Indoor Units • R-410A • CTXU-G2V1B
Specifications
2-1 FOR INDOOR UNITS ONLY
Nominal input
(Indoor only)
Cooling
Heating kW kW
2-2 TECHNICAL SPECIFICATIONS
Casing
Dimensions
Colour
Packing
Weight
Heat
Exchanger
Unit
Unit
Packed Unit
Dimensions
Height
Width
Depth
Height
Width
Depth
Length
Nr of Rows
Fin Pitch mm
Nr of Stages mm mm kg kg mm mm mm mm mm
Tube type
Fin
Fan Type
Air Flow Rate Cooling
Type
Fan
Motor
Fan
Heating
Cooling
Heating
Motor
Speed
(cooling)
Speed
(heating)
Motor
High m³/min
Medium m³/min
Low
Silent
Operation m³/min m³/min
High m³/min
Medium m³/min
Low
Silent
Operation m³/min m³/min
High cfm
Medium cfm
Low
Silent
Operation cfm cfm
High cfm
Medium cfm
Low
Silent
Operation cfm cfm
Model
Number of steps
High rpm
Medium rpm
Low
Silent
Operation rpm rpm
High rpm
Medium rpm
Low
Silent
Operation rpm rpm
Output
(high)
W
CTXU25G2V1B
0,018
0,021
CTXU25G2V1B
800
215
9
13
366
870
274
295
605
2
1.2
18
1,150
950
750
600
1,220
1,030
850
730
23
346
280
217
183
321
252
182
130
9.8
7.9
6.2
5.2
9.1
7.1
5.2
3.7
CTXU35G2V1B
0,026
0,028
CTXU42G2V1B
0,024
0,030
367
270
170
125
10.6
8.5
6.4
5.4
CTXU35G2V1B CTXU42G2V1B
White
800
215
10
14
366
870
274
295
605 + 602.7
2+1
1.2+1.6
18+12
ø6.35 Hi-XU
ML fin (Multi louvre)
Cross flow fan
605 + 602.7
2+1
1.2+1.6
18+12
10.4
7.7
4.8
3.5
9.1
7.7
6.3
5.4
800
215
10
14
366
870
274
295
321
273
221
190
11.2
9.4
7.7
6.8
1,370
1,160
940
840
23
374
302
226
191
395
333
271
240
1,370
1,090
800
670
KFD-280-23-8A
5 steps, silent and auto
1,310
1,170
1,020
930
1,410
1,230
1,050
960
23
388
330
267
236
360
305
246
212
11.0
9.3
7.6
6.7
10.2
8.6
7.0
6.0
1,390
1,230
1,060
960
1,440
1,270
1,090
1,000
23
CTXU50G2V1B
0,026
0,032
CTXU50G2V1B
800
215
10
14
366
870
274
295
605 + 602.7
2+1
1.2+1.6
18+12
• Split Sky Air • Indoor Units 3
4
2
• Indoor Units • R-410A • CTXU-G2V1B
Specifications
2-2 TECHNICAL SPECIFICATIONS
Cooling
Heating
Refrigerant
Piping connections
Sound Power High
Sound
Pressure
High
Medium dBA dBA dBA
Low
Silent
Operation dBA dBA
Sound Power High
Sound
Pressure
High
Medium dBA dBA dBA
Low
Silent
Operation dBA dBA
Type
Liquid (OD) mm
Gas
Drain
Diameter
(OD)
Diameter
(OD)
Diameter
(OD) mm mm
Heat Insulation
Air Filter
Air direction control
Temperature control
Standard
Accessories
Item
Quantity
Item
Quantity
Item
Quantity
Item
Quantity
Item
Quantity
Item
Quantity
Item
Quantity
Item
Quantity
Item
Quantity
Notes
CTXU25G2V1B
54
38
32
25
22
55
39
34
28
25
CTXU35G2V1B
58
42
34
26
23
58
42
36
29
26
CTXU42G2V1B
58
42
38
33
30
58
42
38
33
30
CTXU50G2V1B
59
43
39
34
31
60
44
39
34
31
R-410A
6.35
9.52
6.35
9.52
6.35
9.52
6.35
12.7
18 18 18 18
2
1
1
1
Both liquid and gas pipes
Removable/washable/Mildew proof
Right, Left, Horizontal, Downward
Microcomputer control
Titanium apatite photocatalytic air purification filter
2 2
Air supply filter
1 1
Operation manual
1 1
Installation manual
1 1
Wireless remote control
1 1
2
1
1
1
1 1
Batteries
2 2 2 2
Remote control holder
1 1 1 1
Indoor unit fixing screws
2 2 2 2
Mounting plate
1 1 1 1
In humidity operation under heating and ventialtion operation, in addition, the operation sound of indoor unit shall be increased 2dBa.
The humidifying amount 0.45l/h is measured under following conditions: outdoor temperature (DB/WB): 7/6°C; humidity hose length: 4m; indoor unit air flow rate: H tap (max)
SL: The silent fan level of the air flow setting
Nominal cooling and heating capacity are based on the following conditions: cooling 27°CDB/19°CWB, heating 20°CDB
2-3 ELECTRICAL SPECIFICATIONS
Power Supply Name
Phase
Frequency
Voltage
Current
Wiring connections
Nominal running current
(RLA)
For Power
Supply
Cooling A
Heating A
Hz
V
Quantity
Remark
CTXU25G2V1B
50
0.09-0.08-0.08
0.10-0.10-0.09
3
CTXU35G2V1B CTXU42G2V1B
V1
1~
50
0.12-0.12-0.11
0.13-0.13-0.12
220-230-240
50
0.11-0.11-0.10
0.14-0.14-0.13
3 3
4 for interunit wiring ( including earth wiring)
CTXU50G2V1B
50
0.12-0.12-0.11
0.15-0.14-0.14
3
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • CTXU-G2V1B
3 Dimensional drawing & centre of gravity
3 - 1 Dimensional drawing
CTXU25,35,42G The mark (Y) shows piping direction
Air flow (indoor)
Rear
(Including mounting plate)
Left Right
50 MIN.
((space for maintenance))
Front grille fixing screws
(Inside)
Required space
Bottom
Flaps
Signal receiver
Signal transmitter
Model name plate
Up/down (automatic)
Cooling/Dry
Intelligent eye sensor
Multi-monitor lamp
Timer lamp
Intelligent eye lamp
Indoor unit ON/OFF switch
Room Temp. + humidity sensors (inside)
Terminal block with earth terminal
(Inside)
Blade angles
Heating Fan
Gas pipe 9.5Cut (The length of pipe outside the unit: about 350)
Liquid pipe 6,4 Cut (The length of pipe outside the unit: about 400) unit (mm)
50 MIN.
((space for maintenance))
Connection position of humidifying hose
Drain hose (connecting part I.D. J
14.0, O.D. J 18.0)
(The hose length on the outside of the unit is approx. 465)
Infrared remote control
CTXU50G
Rear
The mark (Y) shows piping direction
Left Right
Front grille fixing screws
(Inside)
(Including mounting plate)
Right/Left
(Automatic)
Wall hole for embedded piping J70 hole
Standard locations of wall holes
Air flow (indoor)
50 MIN.
((space for maintenance))
Required space
Bottom
Flaps
Signal receiver
Signal transmitter
Model name plate
Up/down (automatic)
Cooling/Dry
Intelligent eye sensor
Multi-monitor lamp
Timer lamp
Intelligent eye lamp
Indoor unit ON/OFF switch
Room Temp. + humidity sensors (inside)
Terminal block with earth terminal
(Inside)
Blade angles
Heating Fan
Gas pipe 9.5Cut (The length of pipe outside the unit: about 350)
Liquid pipe 6,4 Cut (The length of pipe outside the unit: about 400)
Wall hole J70 hole
3D063372 unit (mm)
50 MIN.
((space for maintenance))
Connection position of humidifying hose
Drain hose (connecting part I.D. J
14.0, O.D. J 18.0)
(The hose length on the outside of the unit is approx. 465)
Infrared remote control
Right/Left
(Automatic)
Wall hole for embedded piping J70 hole
Standard locations of wall holes
Wall hole J70 hole
3D063373
• Split Sky Air • Indoor Units 5
• Indoor Units • R-410A • CTXU-G2V1B
3 Dimensional drawing & centre of gravity
3 - 2 Centre of gravity
CTXU-G
4D059112 B
6 • Split Sky Air • Indoor Units
4
• Indoor Units • R-410A • CTXU-G2V1B
Piping diagram
CTXU25,35,42G
Indoor unit
6.4 CuT
Heat exchanger
CTXU50G
Field piping
6.4 CuT
Field piping
9.5 CuT
Field piping
6.4 CuT
Field piping
12.7 CuT
Cross flow fan
Fan motor
9.5 CuT
Thermistor on heat exchanger
Indoor unit
6.4 CuT
Heat exchanger
Refrigerant flow
Cooling
Heating
4D058897 C
Thermistor on heat exchanger
Cross flow fan
Fan motor
9.5 CuT
Refrigerant flow
Cooling
Heating
4D058898 C
• Split Sky Air • Indoor Units 7
• Indoor Units • R-410A • CTXU-G2V1B
5 Wiring diagram
5 - 1 Wiring diagram
CTXU-G
Wiring diagram
Rectifier
Intelligent eye sensor
Infrared remote control
Signal receiver
Transmission circuit
Field wiring
Outdoor
Indoor
CAUTION
Note that operation will restart automatically if the main power supply is turned off and then back on again.
NOTES:
1 Size: length 70 x width 120.
2 Refer to purchasing specification AS303002, unless otherwise specified.
3 This drawing was drawn on CAD system.
R
FG
F1U
H1P
H2P
∼
H4P
M1F
M1S,M2S,M3S
PCB1,PCB2,PCB3
R1T, R2T
S1
∼
S51
S1W
X1M
: Protective earth
: Frame ground
: Fuse
: Multi monitor
: Pilot lamp
: Fan motor
: Swing motor
: Printed circuit board
: Thermistor
: Connector
: Operation switch
: Terminal strip
3D062523
8 • Split Sky Air • Indoor Units
• Indoor Units • R-410A • CTXU-G2V1B
6 Sound data
6 - 1 Sound pressure spectrum
CTXU25G (Cooling) CTXU25G (Heating) approximate threshold hearing for continuous noise
3D059556B Octave band center frequency (Hz)
1
NOTE
Operation noise differs with operation and ambient conditions.
Standard external static pressure
50Hz 220-240V (H)
50Hz 220-240V (L)
Cooling
Measure in anechoic room
Overall (dB)
Scale
A
50Hz
220-240V (H)
38
50Hz
220-240V (L)
25
The operation noise measuring method is in accordance with JISC9612
Location of microphone
CTXU35G (Cooling) approximate threshold hearing for continuous noise
3D059556B Octave band center frequency (Hz)
1
NOTE
Operation noise differs with operation and ambient conditions.
Standard external static pressure
50Hz 220-240V (H)
50Hz 220-240V (L)
Heating
Measure in anechoic room
Overall (dB)
Scale
A
50Hz
220-240V (H)
39
50Hz
220-240V (L)
28
The operation noise measuring method is in accordance with JISC9612
Location of microphone
CTXU35G (Heating) approximate threshold hearing for continuous noise
3D059557B Octave band center frequency (Hz)
1
NOTE
Operation noise differs with operation and ambient conditions.
Standard external static pressure
50Hz 220-240V (H)
50Hz 220-240V (L)
Cooling
Measure in anechoic room
Overall (dB)
Scale
A
50Hz
220-240V (H)
42
50Hz
220-240V (L)
26
The operation noise measuring method is in accordance with JISC9612
Location of microphone approximate threshold hearing for continuous noise
3D059557B Octave band center frequency (Hz)
1
NOTE
Operation noise differs with operation and ambient conditions.
Standard external static pressure
50Hz 220-240V (H)
50Hz 220-240V (L)
Heating
Measure in anechoic room
Overall (dB)
Scale
A
50Hz
220-240V (H)
42
50Hz
220-240V (L)
29
The operation noise measuring method is in accordance with JISC9612
Location of microphone
• Split Sky Air • Indoor Units 9
• Indoor Units • R-410A • CTXU-G2V1B
6 Sound data
6 - 1 Sound pressure spectrum
CTXU42G (Cooling) CTXU42G (Heating) approximate threshold hearing for continuous noise
3D059558B Octave band center frequency (Hz)
1
NOTE
Operation noise differs with operation and ambient conditions.
Standard external static pressure
50Hz 220-240V (H)
50Hz 220-240V (L)
Cooling
Measure in anechoic room
Overall (dB)
Scale
A
50Hz
220-240V (H)
42
50Hz
220-240V (L)
33
The operation noise measuring method is in accordance with JISC9612
Location of microphone
CTXU50G (Cooling) approximate threshold hearing for continuous noise
3D059558B Octave band center frequency (Hz)
1
NOTE
Operation noise differs with operation and ambient conditions.
Standard external static pressure
50Hz 220-240V (H)
50Hz 220-240V (L)
Heating
Measure in anechoic room
Overall (dB)
Scale
A
50Hz
220-240V (H)
42
50Hz
220-240V (L)
33
The operation noise measuring method is in accordance with JISC9612
Location of microphone
CTXU50G (Heating)
10 approximate threshold hearing for continuous noise
3D059559B Octave band center frequency (Hz)
1
NOTE
Operation noise differs with operation and ambient conditions.
Standard external static pressure
50Hz 220-240V (H)
50Hz 220-240V (L)
Cooling
Measure in anechoic room
Overall (dB)
Scale
A
50Hz
220-240V (H)
43
50Hz
220-240V (L)
34
The operation noise measuring method is in accordance with JISC9612
Location of microphone approximate threshold hearing for continuous noise
3D059559B Octave band center frequency (Hz)
1
NOTE
Operation noise differs with operation and ambient conditions.
Standard external static pressure
50Hz 220-240V (H)
50Hz 220-240V (L)
Heating
Measure in anechoic room
Overall (dB)
Scale
A
50Hz
220-240V (H)
44
50Hz
220-240V (L)
34
The operation noise measuring method is in accordance with JISC9612
Location of microphone
• Split Sky Air • Indoor Units
Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues.
For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.
The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..
Daikin products are distributed by:
Daikin Europe N.V. is participating in the EUROVENT
Certification Programme. Products are as listed in the
EUROVENT Directory of Certified Products.
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende