Air Conditioners
Technical Data
Wall Mounted Unit
EEDEN10-100
CTXU-G
Air Conditioners
Technical Data
Wall Mounted Unit
EEDEN10-100
CTXU-G
• Indoor Units • R-410A • CTXU-G2V1B
TABLE OF CONTENTS
CTXU-G2V1B
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
For indoor units only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3
3
4
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
6
4
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring diagram
6
....................................................... 8
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Split Sky Air • Indoor Units
9
1
• Indoor Units • R-410A • CTXU-G2V1B
1
t i y nB k 1U S V 2 r AGt o 0- i o 1U ld 4X np-T RCS•I
Features
URURU humidification: maintains a comfortable humidity level
without any separate water supply
Dual air discharge flow for better air distribution
•
ECONO mode decreases power consumption so that other
appliances that need large power supply can be used
•
Especially designed to combine with Ururu multi outdoor unit (MXU)
•
Fresh air intake for healthy living
•
•
2 area intelligent eye: air flow is sent to the area in a room where no
person is detected
Flat front panel: its stylish appearance blends easily within any
interior décor and is more easy to clean.
•
Indoor / outdoor unit silent operation
•
Weekly timer: allows to program the unit on a weekly basis
•
Powerful mode can be selected for rapid cooling or heating
•
Comfort mode guarantees draught free operation
•
•
3D air flow
Titanium apatite photocatalytic air purification filter absorbs
microscopic particles, decomposes odours and even deactivates
bacteria and viruses
standard
integrated
titanium apatite
2
•
• Split Sky Air • Indoor Units
2 rooms
• Indoor Units • R-410A • CTXU-G2V1B
2
Specifications
2-1 FOR INDOOR UNITS ONLY
Nominal input
(Indoor only)
CTXU25G2V1B
kW
0,018
0,026
0,024
0,026
kW
0,021
0,028
0,030
0,032
CTXU25G2V1B
CTXU35G2V1B
CTXU42G2V1B
CTXU50G2V1B
Colour
Dimensions
Packing
Unit
White
Height
mm
366
366
366
366
Width
mm
870
870
870
870
274
Depth
mm
274
274
274
Height
mm
295
295
295
295
Width
mm
800
800
800
800
Depth
215
mm
215
215
215
Unit
kg
9
10
10
10
Packed Unit
kg
13
14
14
14
mm
605
605 + 602.7
605 + 602.7
605 + 602.7
2
2+1
2+1
2+1
1.2
1.2+1.6
1.2+1.6
1.2+1.6
18
18+12
18+12
18+12
10.2
Dimensions
Length
Nr of Rows
Fin Pitch
mm
Nr of Stages
Tube type
Fin
Fan
Type
Air Flow Rate
Cooling
Heating
Cooling
Heating
Fan
Motor
ø6.35 Hi-XU
Type
ML fin (Multi louvre)
Cross flow fan
High
m³/min
9.1
10.4
9.1
Medium
m³/min
7.1
7.7
7.7
8.6
Low
m³/min
5.2
4.8
6.3
7.0
Silent
m³/min
Operation
3.7
3.5
5.4
6.0
High
m³/min
9.8
10.6
11.2
11.0
Medium
m³/min
7.9
8.5
9.4
9.3
Low
m³/min
6.2
6.4
7.7
7.6
Silent
m³/min
Operation
5.2
5.4
6.8
6.7
High
cfm
321
367
321
360
Medium
cfm
252
270
273
305
Low
cfm
182
170
221
246
Silent
cfm
Operation
130
125
190
212
High
cfm
346
374
395
388
Medium
cfm
280
302
333
330
Low
cfm
217
226
271
267
Silent
cfm
Operation
183
191
240
236
1,390
Model
KFD-280-23-8A
Number of steps
Motor
Speed
(cooling)
Speed
(heating)
Fan
CTXU50G2V1B
Heating
Casing
Heat
Exchanger
CTXU42G2V1B
Cooling
2-2 TECHNICAL SPECIFICATIONS
Weight
CTXU35G2V1B
Motor
5 steps, silent and auto
High
rpm
1,150
1,370
1,310
Medium
rpm
950
1,090
1,170
1,230
Low
rpm
750
800
1,020
1,060
Silent
rpm
Operation
600
670
930
960
High
rpm
1,220
1,370
1,410
1,440
Medium
rpm
1,030
1,160
1,230
1,270
Low
rpm
850
940
1,050
1,090
Silent
rpm
Operation
730
840
960
1,000
Output
(high)
23
23
23
23
W
• Split Sky Air • Indoor Units
3
• Indoor Units • R-410A • CTXU-G2V1B
2
Specifications
2-2 TECHNICAL SPECIFICATIONS
Cooling
Heating
CTXU25G2V1B
CTXU35G2V1B
CTXU42G2V1B
Sound Power
High
dBA
54
58
58
CTXU50G2V1B
59
Sound
Pressure
High
dBA
38
42
42
43
Medium
dBA
32
34
38
39
Low
dBA
25
26
33
34
Silent
dBA
Operation
22
23
30
31
Sound Power
High
dBA
55
58
58
60
Sound
Pressure
High
dBA
39
42
42
44
Medium
dBA
34
36
38
39
Low
dBA
28
29
33
34
Silent
dBA
Operation
25
26
30
31
Refrigerant
Type
Piping
connections
Liquid (OD)
Diameter
(OD)
mm
6.35
6.35
R-410A
6.35
6.35
Gas
Diameter
(OD)
mm
9.52
9.52
9.52
12.7
Drain
Diameter
(OD)
mm
18
18
18
18
Heat Insulation
Both liquid and gas pipes
Air Filter
Removable/washable/Mildew proof
Air direction control
Right, Left, Horizontal, Downward
Temperature control
Standard
Accessories
Microcomputer control
Item
Titanium apatite photocatalytic air purification filter
Quantity
2
2
Item
2
2
1
1
1
1
1
1
1
1
2
2
1
1
2
2
1
1
Air supply filter
Quantity
1
1
Item
Operation manual
Quantity
1
1
Item
Installation manual
Quantity
1
1
Item
Wireless remote control
Quantity
1
1
Item
Batteries
Quantity
2
2
Item
Remote control holder
Quantity
1
1
Item
Indoor unit fixing screws
Quantity
2
2
Item
Mounting plate
Quantity
1
1
In humidity operation under heating and ventialtion operation, in addition, the operation sound of indoor unit shall be increased 2dBa.
Notes
The humidifying amount 0.45l/h is measured under following conditions: outdoor temperature (DB/WB): 7/6°C;
humidity hose length: 4m; indoor unit air flow rate: H tap (max)
SL: The silent fan level of the air flow setting
Nominal cooling and heating capacity are based on the following conditions: cooling 27°CDB/19°CWB, heating 20°CDB
2-3 ELECTRICAL SPECIFICATIONS
Power Supply
CTXU25G2V1B
CTXU35G2V1B
Name
Phase
Current
Wiring
connections
4
CTXU42G2V1B
CTXU50G2V1B
50
50
V1
1~
Frequency
Hz
Voltage
V
Cooling
Nominal
running current Heating
(RLA)
A
0.09-0.08-0.08
0.12-0.12-0.11
0.11-0.11-0.10
0.12-0.12-0.11
A
0.10-0.10-0.09
0.13-0.13-0.12
0.14-0.14-0.13
0.15-0.14-0.14
3
3
3
For Power
Supply
Quantity
50
50
220-230-240
3
Remark
• Split Sky Air • Indoor Units
4 for interunit wiring ( including earth wiring)
• Indoor Units • R-410A • CTXU-G2V1B
3
Dimensional drawing & centre of gravity
3-1
Dimensional drawing
The mark (Y) shows piping direction
unit (mm)
Air flow (indoor)
(Including mounting plate)
Right
Left
30 MIN.
Rear
50 MIN.
50 MIN.
((space for
maintenance))
Front grille fixing
screws
(Inside)
(space for
performance)
CTXU25,35,42G
Required space
((space for
maintenance))
Connection position of
humidifying hose
Bottom
Terminal block with
earth terminal
(Inside)
Intelligent eye sensor
Flaps
Signal receiver
Multi-monitor lamp
Gas pipe 9.5Cut (The length of
pipe outside the unit: about 350)
Timer lamp
Intelligent eye lamp
Indoor unit ON/OFF switch
Liquid pipe 6,4 Cut (The length of pipe
outside the unit: about 400)
Room Temp. + humidity sensors (inside)
Drain hose (connecting part I.D. J
14.0, O.D. J 18.0)
(The hose length on the
outside of the unit is
approx. 465)
Model name plate
Signal transmitter
Blade angles
Up/down (automatic)
Heating
Cooling/Dry
Fan
Wall hole for embedded piping J70 hole
Right/Left
(Automatic)
Infrared remote control
Wall hole J70 hole
Standard locations of wall holes
3D063372
The mark (Y) shows piping direction
Air flow (indoor)
unit (mm)
(Including mounting plate)
Right
Left
30 MIN.
Rear
50 MIN.
50 MIN.
((space for
maintenance))
Front grille fixing
screws
(Inside)
(space for
performance)
CTXU50G
Required space
((space for
maintenance))
Connection position of
humidifying hose
Bottom
Terminal block with
earth terminal
(Inside)
Intelligent eye sensor
Flaps
Signal receiver
Multi-monitor lamp
Gas pipe 9.5Cut (The length of
pipe outside the unit: about 350)
Timer lamp
Intelligent eye lamp
Indoor unit ON/OFF switch
Liquid pipe 6,4 Cut (The length of pipe
outside the unit: about 400)
Room Temp. + humidity sensors (inside)
Signal transmitter
Drain hose (connecting part I.D. J
14.0, O.D. J 18.0)
(The hose length on the
outside of the unit is
approx. 465)
Model name plate
Up/down (automatic)
Cooling/Dry
Blade angles
Heating
Fan
Right/Left
(Automatic)
Infrared remote control
Wall hole for embedded piping J70 hole
Wall hole J70 hole
Standard locations of wall holes
3D063373
• Split Sky Air • Indoor Units
5
• Indoor Units • R-410A • CTXU-G2V1B
3
Dimensional drawing & centre of gravity
3-2
Centre of gravity
CTXU-G
4D059112B
6
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • CTXU-G2V1B
4
Piping diagram
Indoor unit
CTXU25,35,42G
6.4 CuT
Heat exchanger
Thermistor on
heat exchanger
Cross flow fan
Field piping
6.4 CuT
Fan motor
Field piping
9.5 CuT
9.5 CuT
Refrigerant flow
Cooling
Heating
4D058897C
Indoor unit
CTXU50G
6.4 CuT
Heat exchanger
Cross flow fan
Thermistor on
heat exchanger
Field piping
6.4 CuT
Fan motor
Field piping
12.7 CuT
9.5 CuT
Refrigerant flow
Cooling
Heating
• Split Sky Air • Indoor Units
4D058898C
7
• Indoor Units • R-410A • CTXU-G2V1B
5
Wiring diagram
5-1
Wiring diagram
CTXU-G
Wiring diagram
Field wiring
Rectifier
Outdoor
Transmission
circuit
CAUTION
Humidity sensor
Note that operation will restart automatically if
the main power supply is turned off and then
back on again.
NOTES:
1 Size: length 70 x width 120.
2 Refer to purchasing specification AS303002, unless otherwise
specified.
3 This drawing was drawn on CAD system.
R
FG
F1U
H1P
H2P∼H4P
M1F
M1S,M2S,M3S
PCB1,PCB2,PCB3
R1T, R2T
S1∼S51
S1W
X1M
Intelligent eye sensor
Infrared remote
control
Signal
receiver
: Protective earth
: Frame ground
: Fuse
: Multi monitor
: Pilot lamp
: Fan motor
: Swing motor
: Printed circuit board
: Thermistor
: Connector
: Operation switch
: Terminal strip
Indoor
3D062523
8
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • CTXU-G2V1B
6
Sound data
6-1
Sound pressure spectrum
CTXU25G (Cooling)
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
CTXU25G (Heating)
approximate
threshold hearing
for continuous
noise
approximate
threshold hearing
for continuous
noise
3D059556B
3D059556B
Octave band center frequency (Hz)
NOTE
1
Octave band center frequency (Hz)
NOTE
Operation noise differs
with operation and
ambient conditions.
Standard external static pressure
1
Operation noise differs
with operation and
ambient conditions.
50Hz 220-240V (H)
50Hz 220-240V (L)
Cooling
A
Location of microphone
50Hz
220-240V (L)
25
Overall (dB)
Scale
A
The operation noise measuring method is in accordance with JISC9612
Location of microphone
50Hz
220-240V (H)
39
50Hz
220-240V (L)
28
The operation noise measuring method is in accordance with JISC9612
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
CTXU35G (Heating)
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
CTXU35G (Cooling)
approximate
threshold hearing
for continuous
noise
approximate
threshold hearing
for continuous
noise
Octave band center frequency (Hz)
3D059557B
Operation noise differs
with operation and
ambient conditions.
Octave band center frequency (Hz)
3D059557B
NOTE
1
NOTE
Standard external static pressure
1
Operation noise differs
with operation and
ambient conditions.
50Hz 220-240V (H)
50Hz 220-240V (L)
Cooling
A
50Hz 220-240V (H)
50Hz 220-240V (L)
Measure in anechoic room
Overall (dB)
50Hz
220-240V (H)
42
Standard external static pressure
Heating
Measure in anechoic room
Scale
50Hz 220-240V (L)
Measure in anechoic room
Overall (dB)
Scale
50Hz 220-240V (H)
Heating
Measure in anechoic room
50Hz
220-240V (H)
38
Standard external static pressure
Location of microphone
50Hz
220-240V (L)
26
Overall (dB)
Scale
A
The operation noise measuring method is in accordance with JISC9612
• Split Sky Air • Indoor Units
50Hz
220-240V (H)
42
Location of microphone
50Hz
220-240V (L)
29
The operation noise measuring method is in accordance with JISC9612
9
• Indoor Units • R-410A • CTXU-G2V1B
6
Sound data
6-1
Sound pressure spectrum
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
CTXU42G (Heating)
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
CTXU42G (Cooling)
approximate
threshold hearing
for continuous
noise
approximate
threshold hearing
for continuous
noise
Octave band center frequency (Hz)
3D059558B
NOTE
1
Octave band center frequency (Hz)
3D059558B
NOTE
Operation noise differs
with operation and
ambient conditions.
Standard external static pressure
1
Operation noise differs
with operation and
ambient conditions.
50Hz 220-240V (H)
50Hz 220-240V (L)
Cooling
A
Location of microphone
50Hz
220-240V (L)
33
Overall (dB)
Scale
A
The operation noise measuring method is in accordance with JISC9612
Location of microphone
50Hz
220-240V (H)
42
50Hz
220-240V (L)
33
The operation noise measuring method is in accordance with JISC9612
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
CTXU50G (Heating)
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
CTXU50G (Cooling)
approximate
threshold hearing
for continuous
noise
approximate
threshold hearing
for continuous
noise
Octave band center frequency (Hz)
3D059559B
Operation noise differs
with operation and
ambient conditions.
Octave band center frequency (Hz)
3D059559B
NOTE
1
NOTE
Standard external static pressure
1
Operation noise differs
with operation and
ambient conditions.
50Hz 220-240V (H)
50Hz 220-240V (L)
Cooling
A
Location of microphone
50Hz
220-240V (L)
34
50Hz 220-240V (L)
Overall (dB)
Scale
A
The operation noise measuring method is in accordance with JISC9612
10
50Hz 220-240V (H)
Measure in anechoic room
Overall (dB)
50Hz
220-240V (H)
43
Standard external static pressure
Heating
Measure in anechoic room
Scale
50Hz 220-240V (L)
Measure in anechoic room
Overall (dB)
50Hz
220-240V (H)
42
50Hz 220-240V (H)
Heating
Measure in anechoic room
Scale
Standard external static pressure
• Split Sky Air • Indoor Units
50Hz
220-240V (H)
44
Location of microphone
50Hz
220-240V (L)
34
The operation noise measuring method is in accordance with JISC9612
The present publication is drawn up by way of information only and does not constitute an offer binding
upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for
particular purpose of its content and the products and services presented therein. Specifications are subject
to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect
damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All
content is copyrighted by Daikin Europe N.V..
Daikin products are distributed by:
Daikin Europe N.V. is participating in the EUROVENT
Certification Programme. Products are as listed in the
EUROVENT Directory of Certified Products.
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
EEDEN10-100 • CD • 04/10 • Copyright Daikin
The present publication supersedes EEDEN09-100
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern
for the environment is set in the EMAS and ISO 14001 systems.
Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende
Daikin’s unique position as a manufacturer of air
conditioning equipment, compressors and refrigerants
has led to its close involvement in environmental issues.
For several years Daikin has had the intention to become
a leader in the provision of products that have limited
impact on the environment. This challenge demands the
eco design and development of a wide range of products
and an energy management system, resulting in energy
conservation and a reduction of waste.