ZX Platform Condensing Unit

User Manual

Index

Disclaimer............................................................................................................................................ 1

Introduction To ZX Platform CDU......................................................................................................... 1

Receiving Your Unit............................................................................................................................... 1

Features And Value............................................................................................................................... 1

Nomenclature...................................................................................................................................... 2

Bill Of Material (BOM)........................................................................................................................... 2

Physical Layout..................................................................................................................................... 3

Product Specification

Qualified Refrigerants And Oils .................................................................................................................... 4

E2 Control Board - Rotary Switch And Dip Switch Setting (ZX-MT & ZXL-LT).................................................. 5

Defrost Module Function Set....................................................................................................................... 6

Digital Scroll Controller (ZXD)...................................................................................................................... 6

Installation

Condensing Unit Handling........................................................................................................................... 7

Electrical Connection................................................................................................................................... 7

Refrigeration Connection............................................................................................................................. 8

Location and Fxing....................................................................................................................................... 9

Start Up & Operation............................................................................................................................. 10

Diagnostic Initialization Message (ZX-MT and ZXL-LT)............................................................................ 10

Diagnostic Messaging - LED Definition (ZX-MT and ZXL-LT)..................................................................... 11

Alarm Messaging - Digital Scroll Controller (ZXD).................................................................................. 11

Wiring Diagram.................................................................................................................................... 12

Contact Lists......................................................................................................................................... 17

1

ZX Platform CDU

Disclaimer

Thank you for purchasing the ZX platform condensing unit from Emerson Climate Technologies. ZX platform CDUs are the best in class within the capacity and operating range available in the market. ZX CDU is designed to operate reliably and to deliver high operating efficiencies in medium and low temperature refrigeration applications. It also provides constant monitoring of the compressor operating conditions and displays the running or fault conditions of the CDU. ZX platform CDUs have to be installed by following the industry trade practices for its safe and reliable operation. It is assumed that the CDU is selected, installed and serviced only by professionals. The user manual does not cover good industry practices which are essential on a refrigeration equipment installation. No responsibility can be accepted for damage caused by inexperienced or inadequately trained site technicians or improper installation design.

If in doubt, please consult your local sales office, quoting unit model and serial number as shown on each unit nameplate. In case of any ambiguity, the wiring diagram supplied with each unit takes precedence over the diagram in this manual.

Introduction to ZX Platform CDU

ZX medium temperature, ZXD digital medium temperature and ZXL low temperature series have been highly successful in the

Asian market and enjoys proven success with its energy savings and customer-friendly electronic features. ZX, ZXD and ZXL

CDUs have been applied by several well known end-users and chain retailers throughout Asia. The ZX platform is also gaining wider acceptance in the global market and specific variants have been developed and exported to the USA and to the European and Middle East markets.

Receiving your unit

All units are shipped with a holding charge of dry nitrogen inside at a low but positive pressure. Suitable labeling is prominently displayed on both the unit and the packaging. Service connectors are provided on the CDU service valve for the convenient checking of the integrity of the holding charge.

Caution!

It is very important to check that this holding pressure exists at the time you receive each unit from us or our authorized representatives. Please inform us or our authorized representative if the holding charge is non-existent. Failure to do so could void the claim for other related system faults at a later period.

Transit damage is essentially an insurance claim and is not covered under manufacturing defect. It is also advisable to inspect the rest of the unit for obvious physical damage and inform us or our authorized representative in case any is discovered.

ZX Platform Condensing Unit was designed based on three factors demanded by industry users:

Energy Efficiency

- Utilizing Copeland Scroll ® compressor technology, variable speed fan motor, large capacity condenser coil and advanced control algorithms, energy consumption is significantly reduced. End-users can save more than 20% on annual energy costs rather than using hermetic reciprocating units.

Reliability

- Combining the proven reliability of Copeland Scroll ® compressors with advanced electronics controller and diagnostics, equipment reliability is greatly enhanced. Fault code alerts and fault code retrieval capabilities provide information to help improve speed and accuracy of system diagnostics. Integrated electronics provide protection against over-current, over-heating, incorrect phase rotation, compressor cycling, high pressure resets, low pressure cut-outs. It can also send out a warning message to an operator when there is a liquid floodback, which can prevent critical damage on the unit.

Flexibility

- The slim shape and light weight make the ZX Condensing Unit aesthetically appealing and eases the installation process. The ultra quiet variable-speed fan motor significantly reduces exterior sound levels, allowing additional location flexibility. Combined with wall mounting capability, the ZX Condensing Unit delivers unmatched flexibility.

ZX Condensing Units are greatly suitable for walk-in cooler and freezer applications.

The advance scroll compressor technology, fan speed control and electronic controller are precisely collaborated in all units. It also introduces variable-speed fan motors that go beyond national standards. Guaranteed dependable performance and operation in foodservice applications while conveying higher energy efficiency and lower sound levels are the main objectives.

ZX Platform Condensing Unit

ZXD Series

Variable Speed Fan

Motor and High

Efficiency Fan Blade

Oversized Condenser

Coil for Maximum Heat

Transfer

Diagnostic Protection

Flexibility

Highest Efficiency

- Shuts down unit during failure

- With real time monitoring of compressor operating conditions

Increased Reliability and Lower Maintenance Costs

More Installation Options

Lower Energy Bills

ZX and ZXL Series

Proprietary Electronic Algorithms to Control Fan Speed,

Optimizing Energy Performance for Local Seasonal Ambient

Temperatures

Diagnostic

Digital

Messaging

Built-in ZX

Platform

Controller

• Compressor Reverse Rotation

• Compressor Over Current

• Compressor Internal Motor

Protector Trip

• Discharge Gas Over Heat

• High Pressure Cut Out

• Low Pressure Cut Out (only on

MT series)

• Refrigerant Flood Back

• Compressor Minimum Off Time

• Internal Thermal Sensor Failure

Copeland Scroll Compressor Technology

– High Efficiency, Ultra Quiet, High

Reliability

Figure 01.

ZX Platform CDU Features

Nomenclature

Z X L 0 2 0 E T F D 4 5 1

Base Model

BOM

CDU Family

BOM

Liquid Line Filter Dryer/Sight Glass

Oil Separator

Accumulator

Adjustable LP Switch

Fixed LP Switch

E2 Controller

Diagnostic Module

Buzzer

Digital Scroll Controller

Fan Speed Controller

Circuit Breaker

Sound Jacket

Defrost Module

Filter Drier

401

ACC

Notes: - E2 controller has fan speed control function

- “V” indicates flare type connection

- “ACC” indicates accessory

ZX

451

ACC

Electrical Code

451

ACC

ZXL

461

Bill of Material

471

ACC

V

450

ZXD

451 461

2

Physical Layout

The following figures give an introduction to the physical layout of the ZX Platform CDU.

Figure 02: Identifies the Electronic controller assembly on a ZX platform CDU.

ZX- MT, ZXL-LT E2 Controller

* ZXD Digital Scroll Controller

Scroll Compressor

* ZXD Digital scroll controller not shown in Fig. 02. See Fig. 05 for LED and keypad

Figure 03: Identifies other major components layout on a ZX platform CDU.

3

Oil Separator

(Optional In MT CDU)

Liquid Receiver

Liquid Sight Glass/

Moisture Indicator

Liquid Filter Drier

Service Valve

Receiver Out Service Valve

Compressor Oil Sight Glass

Figure 04: Shows the layout of the E2 controller, electrical components, dip switches and rotary switch in the E2 control board.

E2 Power Board

Power Isolation Switch

Rotary Switch

E2 Control Board

3-Bit Dip Switch

2-Bit Dip Switch

Compressor Contactor Diagnostic Module

Fuse Holder

Defrost Module

(optional)

Electrical Cable connectors

Figure 05: Shows LED and keypad of ZXD digital scroll controller.

ZX Platform Condensing Unit

Enter Alarm

Manual Restart

Setup Menu

Condenser temperature display

Program Mode: browses parameter codes or increase value

Hot Key Insert : Hot key programming procedure

INFO Menu: Press and release it to access

INFO Menu

Program Mode: below parameter codes or decrease value

Maintenance /Clock

Product Specification

For application envelope, envelope varies according to applications and refrigerants. Please refer to ZX platform product catalogue, product manual, or Copeland ® Brand Products Selection Software.

Qualified refrigerants and oils

REFRIGERANT

R404A/507

R22

OIL

Emkarate RL 32 3MAF

Mobil EAL Artic 22 CC

Suniso 3GS

Oils are pre-charged in both compressor and oil separator. Total oil volume (liter) for each unit is shown in the table below:

ZX ZXD ZXL

Model

ZX0200/E

ZX0250/E

ZX0300/E

ZX0400/E

ZX0500/E

ZX0600/E

ZX0750/E

ZX0760/E

401

1.18

1.33

1.33

1.83

1.83

1.66

1.66

1.66

BOM

451

1.68

1.83

1.83

2.33

2.33

2.16

2.16

2.16

Model

ZXD0400/E

ZXD0500/E

ZXD0600/E

ZXD0750/E

BOM

ALL

1.74

2.27

2.27

2.27

Model

ZXL0200/E

ZXL0250/E

ZXL0300/E

ZXL0350/E

ZXL0400/E

ZXL0500/E

ZXL0600/E

ZXL0750/E

BOM

ALL

1.74

1.74

2.27

2.27

1.06

1.06

1.06

1.74

4

5

E2 Control Board - Rotary Switch And Dip Switch Setting (ZX-MT & ZXL-LT)

Model

ZX0200/E-PFJ

ZX0250/E-PFJ

ZX0300/E-PFJ

ZX0400/E-PFJ

ZX0200/E-TFD

ZX0300/E-TFD

ZX0400/E-TFD

ZX0500/E-TFD

ZX0600/E-TFD

ZX0750/E- 760/E-TFD

ZX0200/E-TF5

ZX0300/E-TF5

ZX0400/E-TF5

ZX0500/E-TF5

ZX0600/E-TF5

ZX0750/E- 760/E-TF5

ZX0200/E-TF7

ZX0300/E-TF7

ZX0400/E-TF7

ZX0500/E-TF7

ZX0600/E-TF7

ZX0750/E- 760/E-TF7

ZXL0200/E-TFD

Rotary

Switch

3

4

1

2

4

5

6

2

3

A

1

7

8

9

A

A

8

9

B

1

5

6

7

3-Bit

No. 3

2-Bit 1/2

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

ON

ON

ON

ON

OFF

ON/ON

ON/ON

ON/ON

OFF/OFF

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

OFF/OFF

OFF/OFF

OFF/OFF

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

Model

ZXL0250/E-TFD

ZXL0300/E-TFD

ZXL0350/E-TFD

ZXL0400/E-TFD

ZXL0500/E-TFD

ZXL0600/E-TFD

ZXL0750/E-TFD

ZXL0200/E-TF5

ZXL0250/E-TF5

ZXL0300/E-TF5

ZXL0350/E-TF5

ZXL0400/E-TF5

ZXL0500/E-TF5

ZXL0600/E-TF5

ZXL0750/E-TF5

ZXL0200/E-TF7

ZXL0250/E-TF7

ZXL0300/E-TF7

ZXL0350/E-TF7

ZXL0400/E-TF7

ZXL0500/E-TF7

ZXL0600/E-TF7

ZXL0750/E-TF7

Rotary

Switch

6

7

4

5

8

2

3

1

1

6

7

8

4

5

2

3

C

D

D

A

B

8

9

3-Bit

No. 3

2-Bit 1/2

ON

ON

ON

ON

ON

ON

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

ON

ON

ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

OFF/OFF

OFF/OFF

OFF/OFF

OFF/OFF

OFF/OFF

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

ON/ON

OFF: Evaporator fan ON/OFF logic is same as compressor and this is the factory default setting.

ON: Evaporator fan will be ON for all time irrespective of whether the compressor is turned ON or OFF

Not applicable

Use setting in the table

ON

1 2 3

Notes: The settings given in the table are pre-set at the factory for new units .

ZX Platform Condensing Unit

Defrost Module Function Set

Time of Defrost Time of Defrost Interval

Rotary

Switch1

2

3

4

0

1

5

6

7

Time(min)

0

5

10

15

20

25

30

35

Rotary

Switch2

2

3

4

0

1

5

6

7

Time

(hours)

2

3

4

0

1

5

6

7

Manual Defrost

Button

Remote Connector

For Manual Defrost

Defrost Duration (in Minutes)

Defrost Interval

(In Hours)

E2 Connector

Figure 06

Figure 06: ZX Platform Defrost Module

Digital Scroll controller (ZXD)

The controller has been pre-programmed with a number of parameter values that are set for typical application. Individual installation requirements, however, may make it necessary to alter parameter settings. The control target of the digital scroll compressor controller is to maintain the suction pressure (or saturated suction temperature) at a defined value by varying the available compressor capacity. The set-point can be altered using the SEtC parameter. Factory setting SEtC is -6 o C.

The control target of the fan speed controller is to maintain the average condenser mid-coil temperature and hence the average discharge pressure at a defined value. This is achieved by varying the fan speed. The set-point can be altered using the SEtF parameter. Factory setting SEtF is 25 o C.Initial setting of set point for saturated suction temperature.Pre-set value is located in the

SEtC position as shown in the diagram below:

press for more than 2 sec

SEtC value

Flashing

or to change set value within 30 seconds

press to memorize new set value.

Then SEtF (fan speed control set point) will be displayed automatically.

SEtC value

Flashing

or to change set value within 30 seconds

press to memorize new value and Exit, or wait for

30 seconds without pressing any key to memorize value and exit

6

Installation

Copeland ZX condensing units are delivered with a holding charge of neutral gas. The condensing unit should be located in such a place to prevent any dirt, plastic bag, leaves or papers from covering the condenser and its fins. The unit must be installed without restricting the airflow. A clogged condenser will increase the condensing temperature, thus reduce the cooling capacity, and lead to a high-pressure switch tripping. Clean the condenser fins on a regular basis.

Condensing Unit Handling

Transport And Storage

Move ZX/ZXD/ZXL unit only with appropriate mechanical or handling equipment according to weight. Keep in the upright position. Do not stack single boxes on top of each other without pallet in any case. Keep the packaging dry at all times.

Storage

2 max

300 Kg

1

Transport

2 max

300 Kg

1

Net Weight

ZX

Model

ZX0200/E

ZX0250/E

ZX0300/E

ZX0400/E 1

ZX0500/E

ZX0600/E

ZX0750/E

ZX0760/E

Weight (kg)

108

112

118

121

76

79

79

91

Model

ZXD0400/E 2

ZXD0500/E 3

ZXD0600/E 4

ZXD0750/E 5

ZXD

Weight (kg)

104

112

114

122

Model

ZXL0200/E

ZXL0250/E

ZXL0300/E

ZXL0350/E

ZXL0400/E

ZXL0500/E

ZXL0600/E

ZXL0750/E

ZXL

Weight (kg)

93

106

116

121

79

81

81

93

7

Notes:

1 100 kg for models under 60 Hz TF5/7 and 50 Hz PFJ

2 109 kg for models under 60 Hz TF7

3 117 kg for models under 60 Hz TF7

4 121 kg for models under 60 Hz TF7

5 127 kg for models under 60 Hz TF7

Electrical Connection

Power supply

The ZX condensing unit electrical connection to the power supply must be made by qualified technicians, who should refer to the electrical diagrams located inside the electric connection panel. The units are designed for below power supply at ±

10% voltage tolerance. The circuit breaker must be switched off before opening the front panel.

Codes

PFJ

TFD

TF7

TF5

HZ

50

50

60

60

Phase

1

3

3

3

Voltages

220/240

380/420

380

200/230

Electrical wiring

Before commissioning, ensure that neutral “N” wire is connected to the terminal block (“N” furthest to the right). After proper connection of the ZX condensing unit, the control LED on the power board and control board will light. For more details, see wiring diagram in Appendix.

ZX Platform Condensing Unit

Refrigeration connections

Refrigeration piping installation

All interconnecting pipes should be of refrigeration grade, clean, dehydrated and must remain capped at both ends until installation. Even during installation, if the system is left for any reasonable period of time (say two hours), pipes should be recapped to prevent moisture and contaminants from entering the system.

Do not assume that the service connection sizes on the unit (at the service valves) are the correct size to run your interconnecting refrigeration pipes. The service valve sizes have been selected for convenience of installation and in some cases (larger units) these may be considered too small. However for the very short pipe run within our units, these service connection sizes are adequate. All interconnecting pipes should be sized to satisfy the duty required.

Usually the suction line is insulated, but the liquid line is not. However the liquid line can pick up additional heat from the ambient and adversely affect the sub-cooling desirable for the liquid refrigerant before it enters the expansion valve.

The pipe should be sized to ensure optimum performance and good oil return. The sizing must also take into account the full capacity range through which this particular unit will need to operate.

Pipe runs should be kept as short as possible, using the minimum number of directional changes. Use large radius bends and avoid trapping of oil and refrigerant. This is particularly important for the suction line. The suction line should ideally slope gently towards the unit. Recommendation slope is 1/200~1/250. P traps, double risers and reduced pipe diameters may be required for suction lines where long vertical risers cannot be avoided. All pipes should be adequately supported to prevent sagging which can create oil traps. The recommended pipe clamp support distance is shown in the table.

Tube Size

12.7mm (1/2 inch)

16.0mm (5/8 inch)

22.0mm (7/8 inch)

28.5mm (1 1/8 inch)

Max distance between

2 clamp support

1.20 m

1.50 m

1.85 m

2.20 m

ZXL liquid line insulation

ZXL liquid line should be insulated with a 19 mm insulation thickness. Temperature could be as low as –15°C.

Brazing recommendations

Maintain a flow of oxygen-free nitrogen through the system at a very low pressure during brazing. Nitrogen displaces the air and prevents the formation of copper oxides in the system. If copper oxidization is allowed to form, the copper oxide material can later be swept through the system and block screens such as those protecting capillary tubes, thermal expansion valves, and accumulator oil return holes. This minimizes any entry of contaminants and moisture.

• Remove the liquid line connection cap.

• Then remove the suction connection cap.

• Open both valves midway. Care should be taken to avoid the holding charge from releasing too quickly.

• Be sure tube fitting inner diameter and tube outer diameter are clean prior to assembly.

• Since both tubes are extended from the condensing unit housing, we recommend insulating the housing by using a wet cloth on the copper tubing.

• Recommended brazing materials: a copper / phosphorous or copper / phosphorous / silver alloy rod should be used for joining copper to copper whereas to join dissimilar or ferric metals, use a silver alloy rod, either flux coated or with a separate.

• Use a double tip torch.

End of tube

During brazing protect housing with damp cloth

OUTSIDE INSIDE UNIT

During brazing pull back fire insulation

8

Location and fixing

The unit should always be installed in a location that ensures clean air flow. It is recommended that a clearance of 300 mm from the wall (or the next unit) be maintained from the unit’s left and rear panels whereas a clearance of 500 mm must be maintained from the unit’s right, top and front panels (seen facing the front of the unit). Both service access and airflow have been considered in making these recommendations. Where multiple units are to be installed in the same location, the contractor needs to consider each individual case carefully. There can be many variations of unit quantities and available space and it is not the intention of this manual to go over these. Ideally, the unit should be mounted on a solid concrete slab with anti-vibration pads between unit feet and concrete. However the ZX condensing unit has also been designed for wall mounting on suitable brackets. Wall mounting brackets are not included. Another factor to consider in finding a good installation site is the direction of the prevailing wind. For example if the air leaving the condenser faces the prevailing wind, the air flow through the condenser can be impeded, causing high condensing temperatures ultimately resulting in reducing unit life. A baffle is a remedy for this situation.

300

70

1029

70

23

500

500 352 300

Service Valve

Service Valve

94

424

2-R7.5MM GROOVE

580

2 Holes 15mm DIA

Single Fan Unit

2 to 4 HP

Fixing dimensions and distances - Single fan unit

1029

300 70 70

23

500

500 352 300

Power

Supply Hole

Suction

Liquid

Service Valve

424

94

2-R7.5MM GROOVE

580

2 Holes 15mm DIA

Dual Fan Unit

4 to 7.6 HP

Fixing dimensions and distances - Dual fan unit

9

ZX Platform Condensing Unit

Start Up and Operation

Before commissioning, ensure that all valves on the condensing unit are fully opened.

Evacuation

The evacuation procedure is based upon achieving an actual system vacuum standard and is not time dependent. Before the installation is put into commission, it has to be evacuated with a vacuum pump. Proper evacuation reduces residual moisture to 50ppm. The installation of adequately sized access valves at the furthest point from the compressor in the suction and liquid lines is advisable. To achieve undisturbed operation, the compressor valves are closed and the system is evacuated down to

0.3 mbar / 0.225 Torr. Pressure must be measured using a vacuum pressure (Torr) gauge on the access valves and not on the vacuum pump; this serves to avoid incorrect measurements resulting from the pressure gradient along the connecting lines to the pump.

Charging procedure

Refrigerant charging procedure

The scroll compressor design requires system charging as quickly as possible with liquid refrigerant into the liquid line. This will avoid running the compressor under conditions where there is insufficient suction gas. Sufficient suction gas is available to cool not only the motor but also the scrolls. Temperature builds up very quickly in the scrolls if this is not done. Do not charge vapor

(gas) refrigerant into the ZX Scroll unit. The suction service valve must not be fully closed at any time while the compressor is running. To do so would cause damage to the compressor in the same manner as explained above. This valve is provided for ease of connection and for the fitting of service gauges without removing the unit panel. It is recommended to charge the ZX unit with refrigerant via its service valves. It is recommended to break the vacuum in the system with a partial charge of the refrigerant, before starting the system. For charge adjustment, it is recommended to check the liquid sight glass just before the expansion valve.

Oil charging procedure

Emerson ZX condensing units are supplied only with a compressor oil charge. After commissioning, the oil level should be checked and topped up if necessary. The oil level should be approximately halfway up the sight glass (ZXL/ZXD units). Oil can be charged through the Schraeder valve on suction valve.

Scroll compressor rotation direction

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. The direction of rotation is not an issue with single-phase compressors since they will always start and run in the proper direction. Threephase compressors will rotate in either direction depending upon the phasing of the power. Since there is a 50-50 chance of connecting power in such a way that causes rotation in the reverse direction, it is important to include notices and instructions in appropriate locations on the equipment to ensure proper rotation direction when the system is installed and operated.

Maximum compressor cycle

Maximum permitted starts per hour is 10.

Check before starting & during operation

Both valves should be fully opened on the liquid line, in order to prevent trapping liquid.

• Check that all valves are fully opened.

• After starting and operation conditions are stabilized, it is recommended to check the oil level in compressor(s) and see if there is a need to add oil to ensure a sufficient oil level (halfway up the sight glass).

Diagnostic Initialization Message (ZX-MT and ZXL-LT)

When the unit is initially powered on, the diagnostic module will show the following signals.

(1 second)> (3 seconds)-> (3 seconds)->

- Software Version No.

- Unit Identification Code

“F”-With OD Fan Speed Control; “-”- W/O OD Fan Speed Control

“-” - ZX; “L” - ZXL

- Power On

LED 2

LED 1

10

Diagnostic messaging - LED definition (ZX-MT and ZXL-LT)

LED1-Unit Status LED2-Error/Warning Code

Display Status

Display

Error/Warning

Idle (Stop When

Reach To Set-point)

Run

About To Start 1

Defrost

Stop Due to Error

Lockout

Display Warning Signal

Controller

Pause Unit

Automatic

Reset

Controller

Lock Unit

Manual Reset

No error/warning

Compressor Phase Error (Wrong Phase Sequence/Loss of

Phase)

Compressor Inside Thermal Protector Trip

Compressor Over Current

Overheat

Compressor High Pressure Cut Out

Compressor Low Pressure Cut Out

DLT Thermistors Failure

2

Ambient Temperature Sensor Failure

Mid-coil Temperature Sensor Failure

PHE Vapor In Temperature Sensor Failure or Over Range 3

PHE Vapor Out Temperature Sensor Failure or Over Range 3

System Liquid Flood Back Warning

Every Protection Action

Every Protection Action

Every Protection Action NA

Every Protection Action

Every Protection Action

Every Protection Action

Every Protection Action

Every Protection Action

<5 times

Protection In

1 Hour

ZX: <5 times

Protection In 1

Hour

ZXL: Every

Protection

<5 times

Protection In 1

Hour

Every

Protection

<5 times

Protection In 1

Hour

Every Protection Action NA

Every Protection Action NA

Every Protection Action

Every Protection Action

~20% Liquid Back

NA

NA

NA

NA

NA

6th Protection

In 1 Hour

ZX: <6th

Protection In 1

Hour

ZXL: NA

6th Protection

In 1 Hour

NA

NA

NA

NA

NA

NA

NA

Notes:

1 New start, normal start by program and any start request delay

2

3

“LP Cutout”signal is not applicable in ZXL condensing unit.

PHE Vapor In/Out temperature sensor is not applicable in ZX medium temperature condensing unit.

Alarm messaging - Digital scroll controller (ZXD)

Alarm Mode dtL

E01L

Set Points

DLT >= dtL after dLd time delay

Low pressure is lower than ELP

(Level 3 Parameter)

Controller Actions

- Compressors are turned off

- Compressors are turned off

- Fans are unchanged

Reset

Auto reset when DLT < dtL-dLH

E0L

C-LA

C-HA

E0H

Mechanical LP switch opens

LP < LAL

LP >= HAL

Condensing Temperature

High

- Compressors are turned off

- Fans are unchanged

- Signaling only

- Signaling only

- Compressors are turned off - Fans are turned on

Auto reset when LP >= ELP(Level 3)

Auto reset when Number of activations < PEn in PEi time

Manual reset when Number of activations >= PEn in PEi time

- Press key for 3 sec or

- Turn off and on the unit

Auto reset when LP = LAL + delta (0.3bar)

Auto reset when LP = HAL -delta (0.3bar)

Auto reset when Number of activations

< PEn in PEi time

Manual reset when Number of activations

>= PEn in PEi time

- Press key for 3 sec or - Turn off and on the unit

Auto reset when HAF + delta (0.3bar)

F-HA

HP >= HAF

P1

P2

Suction Transducer failure or out of range

Condenser Mid Coil Sensor failure or out of range

P3

Discharge Temp Sensor failure or out of range

DLT: Discharge line temperature

LP: Low pressure

HP: High pressure

- HFC = yes, compressor are turned off

- Compressors are activated according to SPr or PoPr

- Fans are activated according to FPr

-The functions related to No.3 probe are disabled

Auto reset when probe is normal

Auto reset when probe is normal

Auto reset when probe is normal

Remarks

DLT

LP

LP

LP

LP

LP

Cond Mid Temp.

Cond Mid

Cond Mid Temp.

LP

Cond Mid Temp.

DLT

11

ZX Platform Condensing Unit

12

13

ZX Platform Condensing Unit

14

15

COND. Mid Coil Temp

Pressure Transducer

Out 0~10V

Digital Scroll Controller

Output: 12VAC

Input: 230VAC

Circuit Breaker

COND. Mid Coil Temp.

Pressure Transducer

ZX Platform Condensing Unit

Out 0~10V

Digital Scroll Controller

Output: 12VAC

Input: 230VAC

Circuit Breaker

16

Contact List

Emerson Climate Technologies

Asia Pacific Headquarters

10/F, Pioneer Building,

213 Wai Yip Street,

Kwun Tong, Kowloon, Hong Kong

Tel: (852) 2866 3108

Fax: (852) 2520 6227

India - Mumbai

Emerson Climate Technologies (India) Ltd

Unit No. 4,5,6 & 7, Bhaveshwar Arcade

LBS Marg, Opp. Shreyas Cinema

Ghatkopar (West)

Mumbai 400 086, Maharashtra, India

Tel: (91-22) 2500 6630/ 2500 6632

Fax: (91-22) 2500 6570 Australia

Emerson Climate Technologies Australia

Pty Ltd

Unit R7, 391 Park Road

Regents Park, NSW 2143, Australia

Tel: (61-2) 9795 2800

Fax: (61-2) 9738 1699

China - Beijing

Emerson Climate Technologies (Suzhou)

Co. Ltd

Beijing Sales Office

Room 1017 JianWei Building,

66 Nan Lishi Road, XiCheng District,

Beijing, PRC

Tel: (86-10) 5763 0488

Fax: (86-10) 5763 0499

China - Guangzhou

Emerson Climate Technologies (Suzhou)

Co. Ltd

Guangzhou Sales Office

508-509 R&F Yinglong Plaza,

No. 76 Huangpu Road West,

Guangzhou, PRC

Tel: (86-20) 2886 7668

Fax: (86-20) 2886 7622

India - PUNE

Emerson Climate Technologies (India) Ltd

Plot No. 23, Rajiv Gandhi Infotech Park,

Phase - II, Hinjewadi,

Pune 411 057, Maharashtra, India

Tel: (91-20) 2553 4988

Fax: (91-20) 2553 6350

Indonesia

PT Emerson Indonesia

Wisma 46 - Kota BNI, 16th Floor, Suite 16.01,

Jl. Jend.Sudirman Kav.1.

Jakarta 10220, Indonesia

Tel: (62)21-2513003

Fax: (62)21-2510622

Japan

Emerson Japan Ltd

Shin-yokohama Tosho Building

No. 33-9-5 Shin-Yokohama, Kohoku-ku

Yokohama 222-0033 Japan

Tel: (81-45)475 6371

Fax: (81-45)475 3565

China - Shanghai

Emerson Climate Technologies

(Suzhou) Co. Ltd

Shanghai Sales Office

1801 Building B, New CaoHeJing

International Business Center,

391Guiping Rd, Shanghai, PRC

Tel: (86-21) 3418 3968

South Korea

Emerson Electric (South Korea) Ltd.

3F Pharos Tower, 119 Nonhyeon-dong

Gangnam-gu, Seoul, South Korea 135-010

Tel: (82-2) 3483-1500

Fax: (82-2) 592-7883 / 592-7886

Malaysia

Emerson Electric (Malaysia) Sdn. Bhd.

Level M2, Blk A, Menara PKNS-PJ

Jalan Yong Shook Lin

46050 Petaling Jaya, Selangor, Malaysia

Tel: (60-3) 7949 9222

Fax: (60-3) 7949 9333

Middle East & Africa

Emerson Climate Technologies

PO Box 26382

Jebel Ali Free Zone – South

Dubai, UAE

Tel: (971- 4) 811 8100

Fax: (971- 4) 886 5465

Philippines

Emerson Climate Technologies

23rd Floor San Miguel Properties Centre

#7 St. Francis Street, Ortigas Center,

Mandaluyong City, Philippines

Tel: (632) 689 7288 / (632) 479 5200

Taiwan

Emerson Electric (Taiwan) Co. Ltd

3F No. 2 DunHua South Road Sec.1,

Taipei (105), Taiwan

Tel: (+886-2) 8161 7688

Fax: (+886-2) 81617614

Thailand - Bangkok

Emerson Electric (Thailand) Ltd

34th Floor Nation Tower

1858/133 Bangna Trad

Bangkok 10260 , Thailand

Tel: (66-2) 716 4700

Fax: (66-2) 751 4240

Vietnam

Emerson Climate Technologies - Vietnam

Suite 307-308,

123 Truong Dinh St., Dist.3

Ho Chi Minh, Vietnam

Tel: 84 908 009 189

EmersonClimate.com/Asia

Asia 02 A01 10 – R00 Issued 4/2012

Emerson, Copeland PerformanceAlert and Copeland Scroll are trademarks of Emerson Electric Co. or one of its affiliated companies.

©2011 Emerson Climate Technologies, Inc. All rights reserved.