CB100,400,500,700,900 E


Add to my manuals
12 Pages

advertisement

CB100,400,500,700,900 E | Manualzz

Digital Controller

CB100/CB400/CB500/CB700/CB900

INSTRUCTION MANUAL

IMCB25-E3

Thank you for purchasing the RKC instrument. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference.

WARNING

• An external protection device must be installed if failure of this instrument could result in damage to the instrument, equipment or injury to personnel.

• All wiring must be completed before power is turned on to prevent electric shock, fire or damage to instrument and equipment.

• This instrument must be used in accordance with the specifications to prevent fire or damage to instrument and equipment.

• This instrument is not intended for use in locations subject to flammable or explosive gases.

• Do not touch high-voltage connections such as power supply terminals, etc. to avoid electric shock.

• RKC is not responsible if this instrument is repaired, modified or disassembled by other than factory-approved personnel.

Malfunction can occur and warranty is void under these conditions.

1. PRODUCT CHECK

CB100

CB400

CB500

CB700

CB900

-

- / /Y

(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)

(1) Control action

F: PID action with autotuning (Reverse action)

D: PID action with autotuning (Direct action)

W: Heat/cool PID action with autotuning (Water cooling)

1

A : Heat/cool PID action with autotuning (Air cooling)

1

(2) Input type, (3) Range code

:

See “9. INPUT RANGE TABLE.”

(4) First control output [OUT1] (Heat-side)

M: Relay contact T: Triac V: Voltage pulse

8: Current (4 to 20 mA DC) G: Trigger (for triac driving)

(5) Second control output [OUT2] (Cool-side)

No symbol: When control action is F or D. M: Relay contact

T: Triac V: Voltage pulse 8: Current (4 to 20 mA DC)

(6) Alarm 1 [ALM1], (7) Alarm 2 [ALM2]

CAUTION

• This is a Class A instrument. In a domestic environment, this instrument may cause radio interference, in which case the user may be required to take adequate measures.

• This instrument is protected from electric shock by reinforced insulation. Provide reinforced insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.

• Be sure to provide an appropriate surge control circuit respectively for the following:

- If input/output or signal lines within the building are longer than 30 meters.

- If input/output or signal lines leave the building, regardless the length.

• This instrument is designed for installation in an enclosed instrumentation panel. All high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel.

• All precautions described in this manual should be taken to avoid damage to the instrument or equipment.

• All wiring must be in accordance with local codes and regulations.

• All wiring must be completed before power is turned on to prevent electric shock, instrument failure, or incorrect action. The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.

• To prevent instrument damage of failure, protect the power line and the input/output lines from high currents with a protection device such as fuse, circuit breaker, etc.

• Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid electric shock, fire or malfunction.

• Tighten each terminal screw to the specified torque found in the manual to avoid electric shock, fire or malfunction.

• For proper operation of this instrument, provide adequate ventilation for heat dispensation.

• Do not connect wires to unused terminals as this will interfere with proper operation of the instrument.

• Turn off the power supply before cleaning the instrument.

• Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.

• To avoid damage to instrument display, do not rub with an abrasive material or push front panel with a hard object.

• Do not connect modular connectors to telephone line.

NOTICE

N: No alarm

A: Deviation high alarm

B: Deviation low alarm

C: Deviation high/low alarm L: Process low alarm with hold action

D: Band alarm

E: Deviation high alarm

P: Heater break alarm (CTL-6)

2

S: Heater break alarm (CTL-12)

2 with hold action R: Control loop break alarm

3

F: Deviation low alarm with hold action

G: Deviation high/low alarm with hold action

(8) Communication function

N: No communication function

(9) Waterproof/dustproof

2. MOUNTING

H: Process high alarm

J: Process low alarm

K: Process high alarm with hold action

V: SV high alarm

W: SV low alarm

N: No waterproof/dustproof

2.1 Mounting Cautions

5: RS-485 (2-wire system)

1: Waterproof/dustproof

(10) Case color

N: White A: Black

1

No self-tuning function is provided in the W or A control action type.

2

Heater break alarm cannot be specified in case of ALM1. Also, it isn’t possible to specify when control output is current output.

3

As control loop break alarm, only either the ALM1 or ALM2 is selected.

Check that power supply voltage is also the same as that specified when ordering.

Mounting frame (CB100): 1

Instruction manual (IMCB25-E3): 1

<Accessories>

Mounting brackets (CB400/CB500/CB700/CB900): 2 *

*CB900 waterproof/dustproof option: 4 pieces environmental conditions. (IEC61010-1)

[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]

(2) Use this instrument within the following ambient temperature and

• This manual assumes that the reader has a fundamental knowledge of the principles of electricity, process control, computer technology and communications.

• The figures, diagrams and numeric values used in this manual are only for purpose of illustration.

• RKC is not responsible for any damage or injury that is caused as a result of using this instrument, instrument failure or indirect damage.

• Periodic maintenance is required for safe and proper operation of this instrument. Some components have a limited service life, or characteristics that change over time.

• Every effort has been made to ensure accuracy of all information contained herein. RKC makes no warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.

• No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored, processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.

All Rights Reserved, Copyright

 1998, RKC INSTRUMENT INC.

® ambient humidity.

• Allowable ambient temperature: 0 to 50 °C

• Allowable ambient humidity: 5 to 95 % RH

(Absolute humidity: MAX. W. C 29 g/m

3

dry air at 101.3 kPa)

(3) Avoid the following when selecting the mounting location.

• Rapid changes in ambient temperature which may cause condensation.

• Corrosive or inflammable gases.

• Direct vibration or shock to the mainframe.

• Water, oil, chemicals, vapor or steam splashes.

• Excessive dust, salt or iron particles.

• Excessive induction noise, static electricity, magnetic fields or noise.

• Direct air flow from an air conditioner.

• Exposure to direct sunlight.

• Excessive heat accumulation.

RKC INSTRUMENT INC.

2.2 Dimensions

CB100

(Unit: mm)

48

CB400

(Unit: mm)

48

CB500

(Unit: mm)

CB700

(Unit: mm)

72

CB900

(Unit: mm)

96

96

9.2

8.2

9.2

8.2

9.2

8.2

9.2

8.2

1 )

9.2

8.2

1 * 1 )

1 * 1 )

100

100

1 *

1 )

100

100

100

*

2

Individual mounting

25

+0.6

45

0

Close horizontal mounting

L1

+0.6

0

L1=(48 × n-3)

n

: Number of controllers (2 ≦

n

≦ 6)

Individual mounting

25 45

+0.6

0

Close horizontal mounting

L1

+0.6

0

L1=(48 × n-3)

n

: Number of controllers (2 ≦

n

≦ 6)

Individual mounting

30 92

+0.8

0

Close vertical mounting

92

+0.8

0

L1=(48 × n-3)

n

: Number of controllers (2 ≦

n

≦ 6)

Individual mounting

25

68

+0.7

0

Individual mounting

25

92

+0.8

0

25

Close horizontal mounting

L1

+0.7

0

L1=(72 × n-4)

n:Number of controllers (2 ≦

n

≦ 6)

Close horizontal mounting

L1

+0.8

0

L1=(96 × n-4)

n

: Number of controllers (2 ≦

n

≦ 6)

*1 Rubber (option)

*2 Up to four mounting brackets can be used.

For mounting of the instrument, panel thickness must be between 1 to 10 mm.

(When mounting multiple instruments close together, the panel strength should be checked to ensure proper support.)

Waterproof and dustproof are not effective when instruments are closely spaced.

2.3 Mounting Procedures

CB100

1. Prepare the panel cutout as specified in 2.2 Dimensions.

2. Insert the instrument through the panel cutout.

3. Insert the mounting frame into the mounting from the rear of the instrument.

4. Push the mounting frame forward until the frame is firmly secured to the panel. (Fig.1)

5. Fix the instrument to the panel by using the two screws. (Fig.2)

Mounting frame

When using the mounting screws, only turn one full revolution after the screw touches the panel.

Screw

Fig.1

Fig.2

The waterproof/dustproof option on the front of the instrument conforms to IP66 when mounted on the panel. For effective waterproof/dustproof, the gasket must be securely placed between instrument and panel without any gap. If the gasket is damaged, please contact RKC sales office or the agent.

If the hook in the mounting frame is disengaged from the case, the mounting frame can be removed (Fig.3). If the instrument is fixed to the panel by tightening the screws, first loosen the screw.

Fig. 3

CB400/CB500/CB700/CB900

1. Prepare the panel cutout as specified in 2.2 Dimensions.

2. Insert the instrument through the panel cutout.

3. Insert the mounting bracket into the mounting groove of the instrument. (Fig.1)

4. Pull till click sounds to the direction shown by the arrow. (Fig.2)

5. Tighten up the screw. (Fig.3)

6. The other mounting bracket should be installed the same way described in 3. to 5.

Mounting bracket

Fig.1

Fig. 3

Fig.2

When using the mounting screws, only turn one full revolution after the screw touches the panel.

When the instrument is mounted, always secure with two mounting brackets so that upper and lower mounting brackets are positioned diagonally.

The waterproof/dustproof option (CB900: mounting bracket 4 pieces) on the front of the instrument conforms to IP65 when mounted on the panel. For effective waterproof/dustproof, the gasket must be securely placed between instrument and panel without any gap. If gasket is damaged, please contact RKC sales office or the agent.

If the hook in the mounting bracket is disengaged from the case, the mounting bracket can be removed

(Fig. 4).

If the mounting bracket is fixed with screw, loosen these screws.

Fig. 4

2

IMCB25-E3

3. WIRING

3.1 Wiring Cautions

• For thermocouple input, use the appropriate compensation wire.

• For RTD input, use low resistance lead wire with no difference in resistance between the three lead wires.

• To avoid noise induction, keep input signal wire away from instrument power line, load lines and power lines of other electric equipment.

• If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.

- Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction.

Instrument power

Twist these leadwires

IN OUT

- Always install the noise filter on a grounded panel. Minimize the wiring distance between the noise filter output and the instrument power supply terminals to achieve the most effective noise reduction.

Shorten distance between pitches

Noise filter

Minimize distance

Instrument power terminals

- Do not connect fuses or switches to the noise filter output wiring as this will reduce the effectiveness of the noise filter.

• Power supply wiring must be twisted and have a low voltage drop.

• About four seconds are required as preparation time for contact output every time the instrument is turned on. Use a delay relay when the output line, is used for an external interlock circuit.

• This instrument is not furnished with a power supply switch or fuses. Therefore, if a fuse or power supply switch is required, install close to the instrument.

- Fuse type: Time-lag fuse

- Recommended fuse rating: Rated voltage 250 V Rated current: 1 A

• For the current input specification, a resistor of 250 Ω (±0.02 % ±10 ppm, 0.25 W or more) must be connected between the input terminals. This resistor must be provided by the customer.

• Use the solderless terminal appropriate to the screw size.

- Screw size: M3 x 6

- Recommended tightening torque: 0.4 N m [4 kgf cm]

• For an instrument with 24 V power supply, supply power from a SELV circuit.

3.2 Terminal Configuration

CB100

NO: Normally open

NC: Normally closed

Trigger

T2

T1

4

OUT1

5

G 6

Triac

OUT1

4

Voltage pulse

Current

Triac out

5

+

5

OUT1

6

F, D action types

Relay contact

4

OUT1

NC

NO

5

6

AC L

1

24V

N

2

DC

24V

+

1

2

Power supply

AC L

1

100 to 240V

N

2

Control output

Triac

OUT2

Triac out

3

4

Voltage pulse

Current

+

3

OUT2

4

Relay contact

OUT1

Triac out

5

+

OUT1

5

6

6

W, A action types

OUT2

NO

OUT1

NO

3

4

5

6

4

5

6

1

2

3

Communication

SG

13

RS-485

T/R(A)

14

T/R(B)

15

(Option)

13

14

15

16

17

18

10

11

12

7

8

9

CT input

Current transformer input

17

CT1

18

(Option)

* Cautions for Communication terminal wiring:

Conduct wiring so that the power supply terminals (screw heads) do not touch the communication terminal lugs. Especially when two lugs are connected to one communication terminal for the use of multidrop connection, much care should be exercised not to touch the power supply terminals with the lugs.

Alarm output

Alarm 2

Alarm 1

7

NO

ALM2

8

NO

ALM1

9

(Option)

Input

RTD input

10

A

11

RTD

B

TC input

12

Current input

0 to 20 mA DC

4 to 20 mA DC

11

+

12

B

11

+

12

TC

Voltage input

0 to 5 V DC

1 to 5 V DC

11

+

IN

12

It is recommended that the host computer communication line be isolated from the power supply and earth.

CB400

NO: Normally open

NC: Normally closed

Trigger

T2

T1

4

OUT1

5

G 6

Triac

OUT1

4

Voltage pulse

Current

Triac out

5

+

5

OUT1

6

F, D action types

Relay contact

4

OUT1

NC

5

NO

6

AC

24V

L

N

1

2

DC

24V

+

Control output

Triac

OUT2

3

Voltage pulse

Current

+

3

OUT2

Relay contact

Triac out

4

4

OUT1

5

Triac out

+

5

OUT1

6

6

W, A action types

OUT2

3

NO

OUT1

5

NO

4

6

1

2

Power supply

AC L

1

100 to 240V

N

2

Alarm 2

Alarm output

Alarm 1

7

NO

ALM2

8

NO

ALM1

9

(Option)

The terminal arrangement of CB500 is as shown in the following diagram, but the terminal configuration of CB500 is the same as that of CB400.

13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6 7 8 9 10 11 12

Input

RTD input

10

A

11

RTD

B

12

B

1

2

3

4

7

8

5

6

9

10

11

12

TC input

11

+

TC

12

13

14

15

16

17

18

19

20

21

22

23

24

Current input

0 to 20 mA DC

4 to 20 mA DC

11

+

12

Communication

SG

RS-485

T/R(A)

13

14

T/R(B)

15

(Option)

CT input

Current transformer input

23

CT1

24

(Option)

Voltage input

0 to 5 V DC

1 to 5 V DC

11

+

IN

12

IMCB25-E3

3

CB700

Control output

Triac

OUT2

3

Voltage pulse

Current

+

3

Relay contact

Triac out

4

OUT2

4

OUT1

5

Triac out

+

5

6

OUT1

6

W, A action types

OUT2

3

NO

4

OUT1

5

NO

6

AC

24V

L

N

1

2

DC

+

24V

1

2

Power supply

AC L

1

100 to 240V

N

2

Communication

SG

RS-485

T/R(A)

7

8

T/R(B)

9

7

8

5

6

9

3

4

1

2

14

15

16

17

18

10

11

12

13

Alarm output

Alarm 2

Alarm 1

10

NO

ALM2

11

NO

ALM1

12

(Option)

CT input

Current transformer input

14

CT1

15

(Option)

(Option)

Trigger

T2

T1

4

OUT1

5

G

6

Triac

OUT1

4

Voltage pulse

Current

Triac out

5

+

5

OUT1

6

F, D action types

Relay contact

OUT1

4

5

NC

NO

6

NO: Normally open

NC: Normally closed

Input

RTD input

16

A

17

RTD

B

18

B

TC input

17

+

TC

18

Current input

0 to 20 mA DC

4 to 20 mA DC

17

+

18

Voltage input

0 to 5 V DC

1 to 5 V DC

17

+

IN

18

CB900

Control output

Triac

OUT2

3

Triac out

4

Voltage pulse

Current

+

3

OUT2

4

Relay contact

OUT1

5

Triac out

+

5

OUT1

6

6

W, A action types

OUT2

3

NO

4

OUT1

5

NO

6

AC

24V

Alarm 2

L

N

Alarm output

Alarm 1

1

2

DC

24V

7

NO

ALM2

8

NO

ALM1

9

+

1

2

Power supply

AC L

1

100 to 240V

N

2

7

8

9

10

11

12

1

2

3

4

5

6

19

20

21

22

23

24

13

14

15

16

17

18

Communication

SG

RS-485

T/R(A)

T/R(B)

CT input

13

14

15

(Option)

Current transformer input

(Option)

NO: Normally open

NC: Normally closed

23

Trigger

Relay contact

Input

CT1

T2

T1

4

OUT1

5

G 6

Triac

OUT1

4

Voltage pulse

Current

4

OUT1

NC

5

NO

6

RTD input

10

A

RTD

11

B

12

B

Current input

0 to 20 mA DC

4 to 20 mA DC

11

+

12

Voltage input

0 to 5 V DC

1 to 5 V DC

11

+

IN

12

24

Triac out

5

+

5

OUT1

6

F, D action types

TC input

11

12

+

TC

(Option)

Input:

Input type:

Thermocouple: K, J, R, S, B, E, T, N, PLII, W5Re/W26Re, U, L

Input impedance: Approx. 1 M

0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC (Z-1010)

0 to 20 mA DC, 4 to 20 mA DC

Input range: See

Control method:

PID control

ON/OFF, P, PI, or PD actions is available

Control output:

Relay contact output:

250 V AC, 3A (Resistive load)

Electrical life: 300,000 times or more (Rated load)

Voltage pulse output:

0/12 V DC (Load resistance 600

Ω or more)

Current output: 4 to 20 mA DC (Load resistance 600

Ω or less)

Trigger output (for triac driving):

Zero cross method for medium capacity triac driving (100 A or less)

Load voltage used: 100 V AC line, 200 V AC line

Load

Triac output: 0.5 A (Ambient temperature: 40

°C or less)

Alarm output:

Relay contact output:

250 V AC, 1A (Resistive load)

Electrical life: 50,000 times or more (Rated load)

Specifications

Voltage:

Current:

Performance:

Display accuracy (at the ambient temperature 23

°C ± 2 °C):

Thermocouple:

± (0.3 % of display value + 1 digit) or ± 2 °C [4 °F]

Whichever is greater

R, S and B input: 0 to 399

°C [0 to 799 °F]

Accuracy is not guaranteed.

T and U input:

−199.9 to −100.0 °C [−199.9 to −158.0 °F]

Accuracy is not guaranteed.

RTD:

± (0.3 % of display value + 1 digit) or ± 0.8 °C [1.6 °F]

Whichever is greater

Voltage/Current:

± (0.3 % of span + 1 digit)

Memory backup:

Backed up by Nonvolatile Memory

Number of write times: Approx. 1,000,000 times

Data storage period: Approx. 10 years

Power:

Power supply voltage:

85 to 264 V AC (Power supply voltage range), 50/60 Hz

Rating: 100 to 240 V AC

21.6 to 26.4 V AC (Power supply voltage range), 50/60 Hz

Rating: 24 V AC

21.6 to 26.4 V DC (Power supply voltage range)

Rating: 24 V DC

Power consumption:

7 VA max. (at 100 V AC)

5 VA max. (at 24 V AC)

10 VA max. (at 240 V AC)

160 mA max. (at 24 V DC)

Weight:

CB100: Approx. 170 g CB700: Approx. 290 g

CB400/CB500: Approx. 250 g CB900: Approx. 340 g

4

4. PARTS DESCRIPTION

CB100 CB400

PV

SV

RKC

AT

SET

OUT1 OUT2 ALM1 ALM2

R/S

CB100

(4) (5) (6) (7)

(1)

(2)

(3)

PV

SV

(1)

(1)

(2)

(3)

SET

AT OUT1 OUT2

ALM1 ALM2

R/S

RKC

CB400

PV

SET

RKC

CB500

(4)

CB500

SV

AT OUT1 OUT2 ALM1 ALM2

R/S

(5) (6) (7)

(2)

(3)

PV

SV

CB700, CB900

SET

RKC

CB900

AT OUT1 OUT2 ALM1 ALM2

R/S

(1)

(2)

(3)

(4) (5) (6) (7)

(1) Measured value (PV) display [Green]

Displays PV or various parameter symbols.

(2) Set value (SV) display [Orange]

Displays SV or various parameter set values (or

CT input value).

(3) Indication lamps

Alarm output lamps (ALM1,ALM2) [Red]

ALM1: Lights when alarm 1 output is turned on.

ALM2: Lights when alarm 2 output is turned on.

Autotuning (AT) lamp [Green]

Flashes when autotuning is activated. (After autotuning is completed: AT lamp will become

OFF)

Control output lamps (OUT1, OUT2) [Green]

OUT1: Lights when control output is turned on.*

OUT2: Lights when cool-side control output is

* Lamp indication becomes as follows for

current output.

For an output of less than 0 %: Extinguished

For an output of more than 100 %: Lit

For an output of more than 0 % but less than

100 %: Dimly lit.

Used for parameter calling up and set value registration.

5. SETTING

(4) (5) (6) (7)

R / S

Shift digits when settings are changed.

Select the RUN/STOP function.

(6) (DOWN key)

Decrease numerals.

(7) (UP key)

Increase numerals.

To avoid damage to the instrument, never use a sharp object to press keys.

5.1 Operation Menu

Power ON Parameter Setting Mode

Input type and Input range Display

Automatically (in 4 sec)

PV/SV Display Mode

This mode is used to set the parameters such as alarms, PID constants, etc. (See page 6.)

The following parameter symbols are displayed as the SET key is pressed.

(CT1)

Current transformer

(CT) input value 1 monitor

SET key

(ATU)

Autotuning (AT)

(T)

Heat-side proportioning cycle

The controller will display the measured value (PV) and the set value (SV).

The controller can be switched to RUN or

STOP mode (Factory set value: RUN).

SV

Press the SET key for 2 seconds.

(AL1)

Alarm 1 set value

(ALM1)

(STU)

SET key

Self-tuning (ST)

(Pc)

SET key

Cool-side proportioning band

PV

SV

PV/SV monitor

(RUN mode)

Press the <R/S key for 1 second.

STOP character display

(STOP mode)

Press the SET key

Press the <R/S key while pressing the

SET key.

(AL2)

(HbA1)

(LbA)

SET key

Alarm 2 set value

(ALM2)

SET key

Heater break alarm

(HBA) 1 set value

SET key

Control loop break alarm (LBA) time

SET key

(P)

(I)

(D)

SET key

Proportional band

SET key

Integral time

SET key

Derivative time

SET key

(db)

(t)

(Pb)

SET key

Deadband

SET key

Cool-side proportioning cycle

SET key

PV bias

SET key

SV Setting Mode

LBA deadband

(Ar)

Anti-reset windup

(LCK)

Set data lock

This is the mode used to set the SV.

(Lbd)

SET key SET key

SET key

PV

SV

SV setting

Return to the first parameter

Factory set value: 0

°C [°F] or 0.0 °C [°F]

Parameters which are not related to existing functions on the controller are not displayed.

This instrument returns to the PV/SV display mode if no key operation is performed for more than one minute.

Communication Setting Mode

This mode is used to set the communication parameters when specified. For details on protocol, identifiers and communication setting mode, see the Communication Instruction Manual (IMCB03-E ).

Input type and input range display

This instrument immediately confirms the input type symbol and input range following power ON.

Example: When sensor type of input is K thermocouple.

PV

SV

Symbol

Automatically

PV

SV

Input type symbol *

Unit for input and SV display

Input range high

Input range low

(Celsius: °C, Fahrenheit: °F, Voltage/current input: no character shown)

* Input Type Symbol Table

Symbol

Input type

Thermocouple (TC)

K J R S B E T N

(

)

PL II

W5Re/

W26Re

(

)

U L

(

∗): This input type is not displayed in the Z-1021 specification.

RTD

JPt

100

Pt

100

Voltage

(Current)

IMCB25-E3

5

5.2 Parameter List

Parameter symbols which are not related to existing functions on the controller are not displayed.

Symbol Name Setting range

Current transformer

(CT) input value 1 monitor

0.0 to 100.0 A

[Display only]

Alarm 1 set value (ALM1)

Alarm 2 set value (ALM2)

Temperature input:

Deviation alarm, Process alarm,

SV alarm:

−1999 to +9999 °C [°F] or

−199.9 to +999.9 ° C [°F]

Voltage/current inputs:

Deviation alarm:

−span to +span (Within 9999)

Process alarm, SV alarm:

Same as input range

Display input value from the current transformer. [Displayed only when the instrument has the heater break alarm ]

Set the alarm 1 set value and alarm 2 set value.

Temperature input:

50 (50.0)

For the alarm action type, see page 10 and 11.

Voltage/ current inputs:

5.0

Alarm differential gap:

Temperature input: 2 or 2.0

°C [°F]

Voltage/current inputs: 0.2% of span

Heater break alarm (HBA) 1 set value

1

Control loop break alarm

(LBA) time

2

LBA deadband

3

Autotuning

(AT)

Self-tuning

(ST)

0.0 to 100.0 A

0.1 to 200.0 minutes

Temperature input:

0 to 9999

°C [°F]

Voltage/current inputs:

0 to 100 % of span

0: AT end or cancel

1: AT start or execution

0: Self-tuning OFF

1: Self-tuning ON

See *1.

See *2.

See *3.

Alarm value is set by referring to input value from the current transformer (CT).

Used only for single-phase.

Set control loop break alarm set value.

Set the area of not outputting LBA.

No LBA deadband functions with 0 set.

Differential gap :

Temperature input: 0.8

°C [°F ]

Voltage/current inputs: 0.8 % of span

Turns the autotuning ON/OFF.

Turns the self-tuning ON/OFF.

0.0

8.0

0

0

0

Proportional band

Temperature input:

1 (0.1) to

span or 9999 (999.9)

Voltage/current inputs:

°C [°F]

0.1 to 100.0 % of span

Set when PI, PD or PID control is performed.

Heat/cool PID action: Proportional band setting on the heat-side.

Temperature input:

30 (30.0)

Voltage/current inputs:

ON/OFF action control when set to 0 (0.0).

ON/OFF action differential gap:

Temperature input: 2 (0.2)

°C [°F ]

Voltage/current inputs: 0.2 % of span

3.0

Integral time 1 to 3600 seconds

(0 second: PD action)

Derivative time 1 to 3600 seconds

(0 second: PI action)

Anti-reset windup (ARW)

1 to 100 % of heat-side proportional band

(0 %: Integral action OFF)

Heat-side proportioning cycle

Cool-side proportional band

Deadband

1 to 100 seconds

(Not displayed if the control output is current output.)

Set the time of integral action to eliminate the offset occurring in proportional control.

Set the time of derivative action to improve control stability by preparing for output changes.

Overshooting and undershooting are restricted by the integral effect.

Set control output cycle.

Heat/cool PID action:

Heat-side proportioning cycle

1 to 1000 % of heat-side proportional band.

Set cool-side proportional band when heat/cool PID action.

240

60

100

Relay contact output: 20

Voltage pulse output/

Trigger output for triac driving/Triac output: 2

100

0 or 0.0 Temperature input:

−10 to +10 °C [°F] or

−10.0 to +10.0 °C [°F]

Voltage/current inputs:

−10.0 to +10.0 % of span

Set control action deadband between heat-side and cool-side proportional bands.

Minus (

−) setting results in overlap.

Cool-side proportioning cycle

PV bias

Set data lock

(LCK)

1 to 100 seconds

(Not displayed if the control output is current output.)

Temperature input:

−1999 to +9999 °C [°F] or

−199.9 to +999.9 °C [°F]

Voltage/current inputs:

−span to +span

Set control cool-side output cycle for heat/cool PID action.

Relay contact output: 20

Voltage pulse output/

Triac output: 2

Sensor correction is made by adding bias value to measured value (PV).

0 or 0.0

Performs set data change enable/disable. 0000

Parameters other than SV and Alarms

0: Unlock 1: Lock

Alarms

0: Unlock

SV

0: Unlock

1: Lock

1: Lock

Initialization mode

0: Lock 1: Unlock

6

IMCB25-E3

1

Heater Break Alarm (HBA) function

The HBA function monitors the current flowing through the load by a dedicated current transformer (CT), compares the measured value with the HBA set value, and detects a fault in the heating circuit.

Low or No current flow (Heater break, malfunction of the control device, etc.):

When the control output is ON and the current transformer input value is equal to or less than the heater break determination point for the preset number of consecutive sampling cycle, an alarm is activated.

Over current or short-circuit:

When the control output is OFF and the current transformer input value is equal to or greater than the heater break determination point for the preset number of consecutive sampling cycle, an alarm is activated.

Precaution for HBA setting:

• Displayed only for when HBA is selected as Alarm 2.

• HBA is not available on a current output.

• Set the set value to approximately 85 % of the maximum reading of the CT input.

• Set the set value to a slightly smaller value to prevent a false alarm if the power supply may become unstable.

• When more than one heater is connected in parallel, it may be necessary to increase the HBA set value to detect a single heater failure.

• When the current transformer is not connected, the HBA is turned on.

2

Control Loop Break Alarm (LBA) function

The LBA function is used to detect a load (heater) break or a failure in the external actuator (power controller, magnet relay, etc.), or a failure in the control loop caused by an input (sensor) break. The LBA function is activated when control output reaches

0 % (low limit with output limit function) or 100 % (high limit with output limit function). LBA monitors variation of the measured value (PV) for the length of LBA time. When the LBA time has elapsed and the PV is still within the alarm determination range, the LBA will be ON.

Precaution for LBA setting:

• Displayed only for when LBA is selected as Alarm 1 or Alarm 2.

• No control loop break alarm can be used at heat/cool PID control action.

• The LBA function can not be activated when AT function is turned on.

• The LBA function is activated when control output reaches 0 % or 100 %. The time required for the LBA output to turn on includes both the time from the initial occurrence of loop failure and the LBA setting time. Recommended setting for LBA is for the set value of the LBA to be twice the value of the integral time (I).

• If LBA setting time does not match the controlled object requirements, the LBA selling time should be lengthened.

If setting time is not correct, the LBA will malfunction by turning on or off at inappropriate times or not turning on at all.

3

LBA Deadband function

The LBA may malfunction due to external disturbances. To prevent malfunctioning due to external disturbance, LBA deadband (LBD) sets a neutral zone in which LBA is not activated.

When the measured value (PV) is within the LBD area, LBA will not be activated. If the LBD setting is not correct, the LBA will not work correctly.

LBD differential gap*

Alarm area

Non-alarm area

Set value (SV) LBD set value

A: During temperature rise: Alarm area

During temperature fall: Non-alarm area

B: During temperature rise: Non-alarm area

* TC and RTD inputs: 0.8

°C [°F] (fixed)

B: During temperature rise: Non-alarm area

During temperature fall: Alarm area

Voltage/Current inputs: 0.8 % of span (fixed)

5.3 Changing Parameter Settings

Procedures to change parameter settings are shown below.

To store a new value for the parameter, always press the SET

key. The display changes to the next parameter and the new value will be stored.

− A new value will not be stored without pressing SET key after the new value is displayed on the display.

− After a new value has been displayed by using the UP and

DOWN keys, the SET key must be pressed within one minute, or the new value is not stored and the display will return to the

PV/SV monitor screen.

Change the set value (SV)

Change the set value (SV) from 0

°C to 200 °C

1. Select the SV setting mode

Press the SET key at PV/SV monitor screen until SV setting screen is displayed.

PV PV

SV

AT OUT1 OUT2 ALM1 ALM2

SV

AT OUT1 OUT2 ALM1 ALM2

SET

CB100

R/S SET

CB100

R/S

PV/SV monitor display

(PV/SV display mode)

SV setting display

(SV setting mode)

2. Shift the high-lighted digit

Press the <R/S key to high-light the hundreds digit.

The high-lighted digit indicates which digit can be set.

PV PV

SV

AT OUT1 OUT2 ALM1 ALM2

SET

CB100

R/S

SV

AT OUT1 OUT2 ALM1 ALM2

SET

CB100

R/S

3. Change the set value

Press the UP key to change the number to 2.

PV PV

SV SV

OUT1 OUT2 ALM1 ALM2 AT OUT1 OUT2 ALM1 ALM2 AT

SET

CB100

R/S SET

CB100

R/S

4. Store the set value

Press the SET key to store the new set value. The display returns to the PV/SV monitor screen.

PV PV

SV

AT OUT1 OUT2 ALM1 ALM2

SET

CB100

R/S

SV

AT OUT1 OUT2 ALM1 ALM2

SET

CB100

R/S

PV/SV monitor display

(PV/SV display mode)

Change parameters other than the set value (SV)

4 in the above " Change the set value (SV)". Pressing the SET key after the setting end shifts to the next parameter. When no parameter setting is required, return the instrument to the PV/SV display mode.

IMCB25-E3

7

6. OPERATIONS

6.1 Operation Procedures

CAUTIONS

All mounting and wiring must be completed before the power is turned on. If the input signal wiring is disconnected or short-circuited (RTD input only), the instrument determines that burnout has occurred.

− Displays:

• Upscale:

• Downscale

Thermocouple input, RTD input (when input break)

Thermocouple input (specify when ordering), RTD input (when short-circuited), Voltage input (1 to 5 V DC),

Current input (4 to 20 mA DC)

• For the voltage (0 to 5 V DC, 0 to 10 V DC*) or current (0 to 20 mA DC) input, the display becomes indefinite (display of about zero value).

* Z-1010 specification

− Outputs:

• Control output: OFF (Heat/Cool control: the control output on both heat-side and cool-side is turned off)

• Alarm output: Both of the Alarm 1 and Alarm 2 outputs of this instrument are turned on when burnout occurs regardless of any of the following actions taken (High alarm, low alarm, etc.). In addition, when used for any purposes other than these alarms (event, etc.), specify the Z-124 specification (not to be forcibly turned on).

A power failure of 20 ms or less will not affect the control action. When a power failure of more than 20 ms occurs, the instrument assumes that the power has been turned off. When power returns, the controller will retain the conditions that existed prior to shut down.

The alarm hold action is activated when not only the power is turned on, but also the SV is changed.

1. Prior to starting operation, check that the mounting and wiring have been finished, and that the SV and various parameters have been set.

2. A power supply switch is not furnished with this instrument. It is ready to operate as soon as the power is turned on.

(Factory set value: RUN).

This instrument holds the conditions that exist just before the power is turned on. For example, if the power is turned off in STOP mode, the instrument starts in STOP mode when the power is turned on again.

RUN/STOP

Each time the <R/S key is pressed for 1 second, RUN/STOP mode changes from RUN to STOP or STOP to RUN. If the instrument is switched to STOP mode, its display, output, etc. become as follows.

• Display:

• Output:

The PV display shows (STOP).

Control output OFF, Alarm output OFF

• Autotuning: AT canceled (The PID constants are not updated.)

RUN/STOP display (Z-1018 specification)

When operation is changed to the STOP mode by RUN/STOP selection, a parameter symbol to indicate the STOP mode is displayed on the SV display. Pressing the SET key with the STOP mode displayed can also check and change the set value (SV).

6.2 Set Data Lock (LCK) Function

The set data lock restricts parameter setting changes by key operation. This function prevents the operator from making errors during operation. There are 8 set data lock levels. (see below)

Set value Parameters which can be changed

0000 All parameters [Factory set value]

0001 SV, Alarms (ALM1, ALM2)

0010 All parameters except for Alarms (ALM1, ALM2)

0011 SV

0100 All parameters except for SV

(ALM1,

0110 All parameters except for SV and Alarms (ALM1, ALM2)

0111 No parameters (All Locked)

HBA, LBA and LBD can be locked when any of 0001, 0011, 0101 and

0111 is set.

Set Data Lock can be changed in both RUN and STOP mode.

Parameters protected by Set Data Lock function are still displayed for monitoring.

6.3 Autotuning (AT) Function

Autotuning (AT) automatically measures, calculates and sets the optimum PID and LBA constants. The following conditions are necessary to carry out autotuning and the conditions which will cause the autotuning to stop.

Caution for using the Autotuning (AT)

When a temperature change (UP and/or Down) is 1

°C or

less per minute during Autotuning, Autotuning may be cancelled before calculating PID values. In that case, adjust the PID values manually. It is possible to happen when the set value is around the ambient temperature or is close to the maximum temperature achieved by the load.

Requirements for AT start

Start the autotuning when all following conditions are satisfied:

• Prior to starting the AT function, end all the parameter settings other than PID and LBA.

• Confirm the LCK function has not been engaged.

When the autotuning is finished, the controller will automatically returns to PID control.

Requirements for AT cancellation

The autotuning is canceled if any of the following conditions exist.

• When the set value (SV) is changed.

• When the PV bias value is changed.

• When the RUN/STOP mode is changed to the STOP mode.

• When the PV becomes abnormal due to burnout.

• When the power is turned off.

• When power failure longer than 20 ms occurs.

• When the AT does not end in 9 hours after autotuning started.

If the AT is canceled, the controller immediately changes to

PID control. The PID values will be the same as before AT was activated.

When AT is completed, the controller immediately changes to PID control. If the control system does not allow the AT cycling process, set each PID constant manually to meet the needs of the application.

6.4 Self-tuning (ST) Function

The ST function is used to automatically calculate and set adaptive PID constants anytime the power is turned on, the SV is changed or the controller detects unstable control conditions.

The ST function should be turned off when the controlled system is affected by rippling that occurs due to periodic external disturbances.

The power to the controlled system must be turned on before the power to the instrument is turned on or SV is changed. This is required when ST function is on.

To activate the ST function, the following parameters must not be set to zero: P

0, I0, D0, ARW0.

When heat/cool PID action is selected, the ST function can not be activated.

When the AT function is activated, the ST function can not be turned on.

When the ST function is activated, the PID and ARW settings can be monitored, but not changed.

8

7. INITIAL SETTING

!

WARNING

Parameters in the Initialization mode should be set according to the application before setting any parameter related to operation. Once the Parameters in the Initialization mode are set correctly, those parameters are not necessary to be changed for the same application under normal conditions. If they are changed unnecessarily, it may result in malfunction or failure of the instrument. RKC will not bear any responsibility for malfunction or failure as a result of improper changes in the Initialization mode.

7.1

Go to Initialization Mode

1. Turn on the power to this controller. The instrument goes to the PV/SV display after confirming input type symbol and input range.

2. Press the SET key for two seconds to go to the Parameter

Setting Mode from the PV/SV display.

3. Press the SET key until “LCK” (Set Data Lock display) will be displayed.

4. The high-lighted digit indicates which digit can be set. Press

<R/S key to high-light the thousands digit.

(The section in each image of the controller shows the digits which are not high-lighted.)

PV

SV

AT OUT1 OUT2 ALM1 ALM2

7.2

Exit Initialization Mode

When any parameter setting is changed in the Initialization

Mode, check all parameter set values in SV Setting Mode and Parameter Setting Mode.

1. Press the <R/S key for two seconds while pressing the SET key from any display in the Initialization Mode. The controller goes back to the operation mode and the PV/SV display will be displayed.

2. Press the SET key for two seconds in the PV/SV display.

3. Press the SET key until “LCK” (Set Data Lock display) will be displayed.

4. The high-lighted digit indicates which digit can be set. Press

<R/S key to high-light the thousands digit.

(The section in each image of the controller shows the digits which are not high-lighted.)

5. Press the DOWN key to change 1 to 0.

SET

CB100

R/S

PV

Set data lock function display

5. Press the UP key to change 0 to 1.

PV

SV

AT OUT1 OUT2 ALM1

SET

CB100

R/S

ALM2

Set value

0: Initialization mode l ocked

1: Initialization mode unlocked

6. Press the SET key to store the new set value. The display goes to the next parameter, and the Initialization mode is unlocked.

PV

SV

AT OUT1 OUT2 ALM1

SET

CB100

R/S

ALM2

CT1 input value display

The parameter displayed varies on the instrument specification.

7. Press the <R/S key for two seconds while pressing the SET key to go to the Initialization Mode. When the controller goes to the Initialization Mode, “Cod” will be displayed.

PV PV

SV

AT OUT1 OUT2 ALM1 ALM2

SET

CB100

R/S

CT1 input value display

SV

AT OUT1 OUT2 ALM1 ALM2

SET

CB100

R/S

Initialize code selection display of initialization mode

Cod SL1 (Input type selection) See P. 10

0000 SL2 (Temperature unit and cooling type selection) See P. 10

SL4 (Alarm 1 type selection)

SL5 (Alarm 2 type selection)

SL11 (SV alarm type selection)

See P. 10

See P. 10

See P. 11

Cod SLH (Setting limiter [high])

0001 SLL (Setting limiter [low])

PGdP (Decimal point position)

See P. 11

See P. 11

See P. 11

SV

AT OUT1 OUT2 ALM1

ALM2

SET

CB100

R/S

Set data lock function display

6. Press the SET key to store the new set value. The display goes to the next parameter, and the Initialization mode is locked.

PV

SV

AT OUT1 OUT2 ALM1 ALM2

SET

CB100

R/S

The parameter displayed varies on the instrument specification.

CT1 input value display

7.3 Initial Setting Menu

The “Cod” display will be displayed when the controller goes to the Initialization Mode.

Do not change to any parameter in the Initialization Mode which is not described in the initial setting menu above.

It may result in malfunction or failure of the instrument.

PV/SV display mode or Parameter setting mode

Press the <R/S key while pressing the SET key for 2 seconds with the unlocked.

Set Cod to 0000.

(Cod)

Initialization code selection

Set Cod to 0001.

(SL1)

(SL2)

Input type selection

Temperature unit and cooling type selection

(SLH)

(SLL)

Setting limiter

[high]

Setting limiter

[low]

(SL4)

(SL5)

Alarm1 type selection

Alarm2 type selection

(PGdP)

Decimal point position

To PV/SV display mode

(SL11)

SV alarm type selection

To PV/SV display mode

Initialization code selection

: Press the SET key, or press the SET key several times.

: Press the <R/S key while pressing the SET key for 2 seconds.

IMCB25-E3

9

7.4 Input Type Selection (SL1)

When any parameter setting is changed in the Initialization

Mode, check all parameter set values in SV Setting Mode and Parameter Setting Mode.

Factory set value varies depending on the input type.

Set value Input type

0000 K

0001 J

0010 L

0011 E

0100 N

0111 R

1000 S

1001 B

0101 T

0110 U

1100 Pt100

Thermocouple

1

(TC)

3. Press the SET key to store the new set value. The display goes to the next parameter.

7.5 Temperature Unit and Cooling Type

(SL2)

Inappropriate settings may result in malfunction.

Control type between Heat Only and Heat/Cool cannot be changed by this parameter.

Factory set value varies depending on the instrument specification.

Set value unit

0000

°C

0001

0010

0011

°F

°C

°F

Description

Cooling type selection

Air cooling (A type) or Heat only type (F, D type)

Air cooling (A type) or Heat only type (F, D type)

Water cooling (W type)

Water cooling (W type)

Change Settings

Example: Change the temperature unit of the Heat only type

from

1. Press the SET key until SL2 is displayed.

2. Press the UP key to change the number to 1.

PV PV

RTD

1

7.6 Alarm 1 [ALM1] Type Selection (SL4)

Alarm 2 [ALM2] Type Selection (SL5)

If the alarm function is not provided with the instrument when shipped from the factory, no alarm output is available by changing

SL4 and/or SL5.

SL4 is set to 0000 in the following cases.

When the instrument does not have ALM1 output

When Control Loop Break Alarm (LBA) is provided and

assigned to ALM1

When the SV alarm is provided and assigned to ALM1

SL5 is set to 0000 in the following cases.

When the instrument does not have ALM2 output

When Control Loop Break Alarm (LBA) is provided and

assigned to ALM2

When the SV alarm is provided and assigned to ALM2

When the Heater Break Alarm (HBA) is provided

When the instrument has Z-168 specification

Factory set value varies depending on the instrument specification.

Set value

Details of setting

1110

1110

1111

1110

1111

0 to 5 V DC

0 to 10 V DC

2

1 to 5 V DC

0 to 20 mA DC

4 to 20 mA DC

Voltage

1

Current

1, 3

1

Any input change in TC&RTD Group is possible. Any input change in voltage&current Group except for 0 to 10 V DC input is possible. No input change between TC&RTD Group and voltage&current Group is possible.

2

The input type of Z-1010 specification is fixed to 0 to 10 V DC due to the

3 hardware difference.

For the current input specification, a resistor of 250

Ω must be connected between the input terminals.

4

W5Re/W26Re and B are not available with Z-1021 specification (Modbus communication).

Change Settings

Example: Change the input type from “K” to “J”

1. Set “Cod” to 0000, and press the SET key. The display will go to SL1.

PV PV

SV SV

0101

0010

Deviation low alarm

Deviation high/low alarm

0011

0111

1001

1101

1010

1011

1111

Process high alarm

Process low alarm

Deviation high alarm with hold action *

Deviation low alarm with hold action *

Deviation high/low alarm with hold action *

Process high alarm with hold action *

Process low alarm with hold action *

* Hold action:

When Hold action is ON, the alarm action is suppressed at start-up or the control set value change until the measured value enters the non-alarm range.

Alarm action type

Both of the Alarm 1 and Alarm 2 outputs of this instrument are turned on when burnout occurs regardless of any of the following actions taken (High alarm, low alarm, etc.). In addition, when used for any purposes other than these alarms (event, etc.), specify the Z-124 specification (not to be forcibly turned on).

Initialize code selection display

Input type selection

2. Press the UP key to change the number to 1.

PV

SV

Deviation high alarm

* (Alarm set value is greater than 0.)

OFF

Low

* (Alarm set value is less than 0.)

OFF

Low

Deviation low alarm

* (Alarm set value is greater than 0.)

ON

( : SV : Alarm set value)

ON

High

High

PV

PV

ON

Low

* (Alarm set value is less than 0.)

ON

Low

OFF

OFF

High

PV

PV

High

Deviation high/low alarm

Low

Band alarm

ON

OFF

Low

Process high alarm

OFF

Low

Process low alarm

ON

Low

OFF

ON

OFF

ON

OFF

ON

High

High

High

High

PV

PV

PV

PV

Change Settings

Example: Change the ALM1 type from “Deviation high alarm

(0001)” to “Deviation low alarm (0101)”

1. Press the SET key three times at SL1 until SL4 is displayed.

2. Press the <R/S key to high-light the hundreds digit.

3. Press the UP key to change the number to 1.

PV PV

SV SV

3. Press the SET key to store the new set value. The display goes to the next parameter.

SV SV

4. Press the SET key to store the new set value. The display goes to the next parameter.

10

7.7 SV Alarm Type Selection (SL11)

For ALM1 setting, the first digit from the right is set to “0” in the following cases.

When the instrument does not have ALM1 output.

When the ALM1 output is used for process/deviation/

band alarm or Loop Break Alarm (LBA).

For ALM2 setting, the third digit from the right is set to “0” in the following cases.

When the instrument does not have ALM2 output.

When the ALM1 output is used for process/deviation/

band alarm, Heater Break Alarm (HBA) or Loop Break

Alarm (LBA).

When Z-168 is specified.

To make SV alarm setting effective, set SL4 to “0000” when using ALM1 for SV alarm, or set SL5 to “0000” when using ALM2 for SV alarm. SL4 and SL5 have priority to

SL11 setting.

Factory set value varies depending on the instrument specification.

Alarm

Alarm 1

Details of setting

0 SV alarm not provided

1 SV alarm provided

1 SV alarm

0

Alarm 2 1

SV alarm not provided

SV alarm provided

Factory set value varies depending on the instrument specification.

Input type

Setting range

Setting limiter

[high]

Setting limiter

[low]

U

TC

600.0 to

−199.9 to SLH °C

SLL

°C

1652 0 to SLH

°F

JPt100

°F

Voltage

Current

0 to 5 V DC

0 to 10 V DC *

1 to 5 V DC

0 to 20 mA DC

4 to 20 mA DC

SLL to 9999

(Programmable scale)

−199.9 to SLH °F

−1999 to SLH

(Programmable scale)

* Z-1010 specification

Change Settings

Example: When the display range is scaled to 0.0 to 400.0 for a voltage input of 1 to 5 V DC.

1V 5 V

Factory set value → 0.0

Scaling

0.0

100.0

400.0

1. Set Cod to 0001, and press the SET key. The display will go to SLH.

PV PV

1 SV alarm

SV SV

SV alarm action type

SV high alarm

Low

SV low alarm

ON

Low

OFF

OFF

( : Alarm set value)

ON

High

High

SV

SV

Initialize code selection display

PV

Setting limiter [high] display

2. The high-lighted digit indicates which digit can be set. Press

<R/S key to high-light the first digit from the left.

SV

Change Settings

Example: Change the SV alarm type of the ALM1 from “SV high alarm (0001)” to “SV low alarm (0011)”

1. Press the SET key ten times at SL1 until SL11 is displayed.

2. Press the <R/S key to high-light the tens digit. Next, press the UP key to change the number to 1.

PV PV

SV SV

High-light

3. Press the SET key to store the new set value. The display goes to the initialize code parameter.

7.8 Setting Limiter [High] (SLH)

For voltage or current input, set scaling within the input range.

See Input range table (P. 12)

Factory set value varies depending on the instrument specification.

Setting range

Input type

Setting limiter

[high]

Setting limiter

[low]

K 1372

°F

J

R

0 to SLH

2502

1200

°F

°C

°F

0 to SLH

°C

0 to SLH

1769

°F

°C

S

B

3216

°C

0 to SLH

°F

1820

°C

3308

TC E SLL

0 to SLH

°F

0 to SLH

°C

0 to SLH

°F

0 to SLH

°C

T

W5Re/W26Re

1832

SLL

2372

400.0

752.0

2320

°F

°C

4208 0 to SLH

°F

PLII 1390 to

°C

°F

3. Press the UP key to change the number to 4.

PV

SV

4. Press the SET key to store the new set value. The display goes to SLL.

5. Set SLL to 0.0.

6. Press the SET key to store the new set value. The display goes to the next parameter.

7.9 Decimal Point Position (PGdP)

Use to select a decimal point position of the input range (voltage input and current input). PGdP is displayed only for voltage or current input.

Inappropriate settings may result in malfunction.

Set value

0000

0001

0002

0003

Description

No decimal place (

One decimal place (

)

. )

Two decimal places (

.

)

Three decimal places ( . )

[Factory set value]

Change Settings

Example:

Change the decimal point position from “One decimal place (0001)” to “No decimal place (0000)”

1. Press the SET key two times at SLH until PGdP is displayed.

2. Press the DOWN key to change the number to 0.

PV PV

SV SV

3. Press the SET key to store the new set value. The display goes to the next parameter.

IMCB25-E3

11

8. ERROR DISPLAYS

Error display

RAM failure (Incorrect set data write, etc.)

Overscale and Underscale

Measured value (PV)

[Flashing]

PV is outside of input range.

Overscale:

PV is above the high input display range limit.

[Flashing]

Underscale:

PV is below the low input display range limit.

[Flashing]

9. INPUT RANGE TABLE

Turn off the power once. If an error occurs after the power is turned on again, please contact RKC sales office or the agent.

!

WARNING

To prevent electric shock, always turn off the power before replacing the sensor.

Check input type, input range, sensor and sensor connection.

K

J

Input type

20

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0 to to to to to to

200

400

600 to 800 to 1000

1200

1372

100 to to to to to to to

300

450 to

500

800 to 1600 to 2502

70

200

400

600 to 800 to 1000 to 1200 to 450

C

C

C

C

F

C

C

C

C

C

C

C

C

C

F

F

F

C

C

C

C

C

K

K

K

Model code

K

01

K 02

K

K

K

K

03

04

05

06

07

13

14

J

J

K 17

K

20

K A1

K A2

K

K

J

A3

A9

01

02

03

J

J

J

04

05

06

J 10

J

R

S

E

*1

*1

*1

*1

*1

*1

*1

*1

*1

B

( *3 )

*1

*1

Input type

0

400

0

0

0

0

0

0

0

0

800

0

0

0

0

0

0

0

0

0

0

0 to 3308 to 800 to 1000 to 1600 to 1832

*1 0 to 399

C /0 to 799 F : Accuracy is not guaranteed.

*3 This input type can not be selected in the Z-1021 specification.

to 800 to 1600 to 2192 to to

400

300 to 1600 to 1769 to 1350 to 3200 to 3216 to 1600 to 1769 to 3200 to 3216 to 1800 to 1820 to 3200

C

C

F

F

C

C

F

F

C

C

F

F

F

F

F

C

F

F

C

C

F

F

Model code

J

J

J

J

A1

A2

A3

A6

J A7

R 01

R

R

02

04

R A1

R A2

S 01

S 02

S A1

S A2

B 01

B 02

B A1

B A2

E 01

E 02

E A1

E A2

N

T

*2

*2

*2

W5Re/

W26Re

( *3 )

PL

U

*2

*2 -199.9 to -100.0

Input type

-199.9

-199.9

-100.0

0.0

-199.9

-100.0

0

0

-199.9

C

0

0

0

0

0

0

0

0

0

0

-100.0

0.0

0.0

to 1200 to 1300 to 2300 to 2372 to to

+

400.0

+

100.0

to to to to to to to

752.0

to 2000 to 2320 to 4000 to 1300 to 1390 to 1200 to 2400 to 2534 to

+ 200.0

350.0

+

752.0

+

200.0

+

400.0

450.0

+

600.0

/-199.9 to -158.0

F

C

C

C

C

C

C

F

F

F

F

F

F

C

C

F

C

C

C

F

F

C

Model code

N 01

N 02

N A1

N A2

T 01

T 02

T 03

T 04

T A1

T A2

T A3

T A4

T A5

W 01

W 02

W A1

A 01

A 02

A 03

A A1

A A2

U 01

U

L

Pt100

*2

*2

Input type

-199.9

0.0

-199.9

-100.0

0.0

0

0

0

0

-199.9

-199.9

-100.0

-100.0

-100.0

0.0

0.0

0.0

0.0

0.0

-199.9

-199.9

-199.9

F : Accuracy is not guaranteed.

to to to to to to to to to to to to to to to

+

+

999.9

+

100.0

400.0

200.0

999.9

400

800

800 to 1600 to

+

649.0

to to

+

200.0

+

50.0

to to

+

100.0

+

200.0

to 50.0

100.0

200.0

300.0

500.0

+

999.9

+

400.0

+

200.0

C

C

F

F

F

C

C

F

F

C

C

C

C

C

C

C

C

C

C

F

F

F

U

U

U

Model code

U 02

03

A1

A2

U

L

A3

01

L 02

L A1

L A2

D 01

D 02

D 03

D 04

D 05

D

D

06

07

D

D

D

08

09

10

D A1

D A2

D A3

Input type

Pt100

-100.0

-100.0

0.0

0.0

0.0

0.0

-199.9

-199.9

JPt100

-100.0

-100.0

-100.0

0.0

0.0

0.0

0.0

0.0

0 to 5 V DC

0 to 10 V DC

1 to 5 V DC

0 to 20 mA DC

4 to 20 mA DC

**

to to to to to to to to to to to to to to to to

+

100.0

+

300.0

100.0

200.0

400.0

500.0

+

649.0

+

200.0

+

50.0

+

100.0

+

200.0

50.0

100.0

200.0

300.0

500.0

0.0

to

100.0

C

C

C

C

C

C

C

F

F

C

C

C

F

F

F

F

5

6

7

8

P 02

P 03

P 04

P 05

P 06

P

07

P

P

08

09

P

4

10

01

01

01

01

01

Model code

D A4

D A5

D A6

D

D

A7

A8

D A9

P 01

**Z-1010 specification

10. REMOVING THE INTERNAL ASSEMBLY

Usually, this instrument is not necessary to remove the internal assembly from the case. When removing the internal assembly without disconnecting the external wiring, take the following steps.

!

WARNING

To prevent electric shock or instrument failure, only qualified personnel should be allowed to pull out the internal assembly.

To prevent electric shock or instrument failure, always turn off the power before pulling out the internal assembly.

To prevent injury or instrument failure, do not touch the internal printed wiring board.

Lock (upper)

Apply pressure very carefully when removing internal assembly to avoid damage to the frame.

To conform to IEC61010-1 requirements for protection from electric shock, the internal assembly of this instrument can only be removed with an appropriate tool.

Lock (lower)

Recommended tool:

Blade screwdriver

(Blade width:

6 mm or less)

Unlocking points (marked with “ ”) depend on the model as follows:

CB400

CB500

CB100

CB700

CB900

Unlock using such a blade screwdriver.

Gently press down on handle for the upper lock and lift up for the lower lock.

The first edition: DEC. 2002 [IMQ00]

The third edition: AUG. 2004 [IMQ00]

®

RKC INSTRUMENT INC.

IMCB25-E3

HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN

PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: [email protected]

FAX: 03-3751-8585 (+81 3 3751 8585)

AUG. 2004

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement