Owner’s Manual
Vehicular Slide Gate Operator
P/N 9100-065 REV D, 5/07
Copyright 2000 DoorKing, Inc. All rights reserved.
DoorKing, Inc.
120 Glasgow Avenue
Inglewood, California 90301
U.S.A.
Phone: 310-645-0023
Fax: 310-641-1586 www.doorking.com
Page 2 9100-065-D-5-07
Use this manual with the following model only.
Model 9100-080 with circuit board 4602-010.
DoorKing, Inc. reserves the right to make changes in the products described in this manual without notice and without obligation of DoorKing, Inc. to notify any persons of any such revisions or changes. Additionally, DoorKing, Inc. makes no representations or warranties with respect to this manual. This manual is copyrighted, all rights reserved. No portion of this manual may be copied, reproduced, translated, or reduced to any electronic medium without prior written consent from DoorKing, Inc.
9100-065-D-5-07 3
Glossary
GATE: A moving barrier such as a swinging, sliding, raising, lowering, or the like, barrier, that is a stand-alone passage barrier or is that portion of a wall or fence system that controls entrance and/or egress by persons or vehicles and completes the perimeter of a defined area.
RESIDENTIAL VEHICULAR GATE OPERATOR – CLASS I: A vehicular gate operator (or system) intended for use in a home of one-to four single family dwelling, or garage or parking area associated therewith.
COMMERCIAL / GENERAL ACCESS VEHICULAR GATE OPERATOR - CLASS II: A vehicular gate operator
(or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units), hotels, garages, retail store, or other building servicing the general public.
INDUSTRIAL / LIMITED ACCESS VEHICULAR GATE OPERATOR - CLASS III: A vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.
RESTRICTED ACCESS VEHICULAR GATE OPERATOR - CLASS IV: A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.
VEHICULAR BARRIER (ARM) OPERATOR (OR SYSTEM): An operator (or system) that controls a cantilever type device (or system), consisting of a mechanical arm or barrier that moves in a vertical arc, intended for vehicular traffic flow at entrances or exits to areas such as parking garages, lots or toll areas.
VEHICULAR HORIZONTAL SLIDE-GATE OPERATOR (OR SYSTEM): A vehicular gate operator (or system) that controls a gate which slides in a horizontal direction that is intended for use for vehicular entrance and exit to a drive, parking lot, or the like.
VEHICULAR SWING-GATE OPERATOR (OR SYSTEM): A vehicular gate operator (or system) that controls a gate which moves in an arc in a horizontal plane that is intended for use for vehicular entrance and exit to a drive, parking lot, or the like.
SYSTEM: In the context of these requirements, a system refers to a group of interacting devices intended to perform a common function.
WIRED CONTROL: A control implemented in a form of fixed physical interconnections between the control, the associated devices, and an operator to perform predetermined functions in response to input signals.
WIRELESS CONTROL: A control implemented in means other than fixed physical interconnections (such as radio waves or infrared beams) between the control, the associated devices, and an operator to perform predetermined functions in response to input signals.
INHERENT ENTRAPMENT PROTECTION SYSTEM: A system, examples being a motor current or speed sensing system, which provides protection against entrapment upon sensing an object and is incorporated as a permanent and integral part of the operator.
EXTERNAL ENTRAPMENT PROTECTION DEVICE: A device, examples being an edge sensor, a photoelectric sensor, or similar entrapment protection device, which provides protection against entrapment when activated and is not incorporated as a permanent part of an operator.
ENTRAPMENT: The condition when an object is caught or held in a position that increases the risk of injury.
Page 4 9100-065-D-5-07
Entrapment Protection
Usage Class
Vehicular I and II
Vehicular III
Vehicular IV
Protection Against Entrapment
Gate Operator Category
Horizontal Slide, Vertical Lift,
Vertical Pivot
Swing and Vertical Barrier (arm)
Primary
A
Secondary
B1, B2 or D
Primary
A or C
Secondary
A, B1, B2, C or D
A, B1 or B2
A, B1, B2 or D
A, B1, B2, D or E
A, B1, B2, D or E
A, B1, B2 or C
A, B1, B2, C or D
A, B1, B2, C,
D or E
A, B1, B2, C,
D or E
TYPE A:
TYPE B1:
TYPE B2:
TYPE C:
TYPE D:
TYPE E:
Inherent entrapment protection system.
Provision for connection of, or supplied with, a non-contact sensor
(photoelectric sensor or the equivalent). When used as the PRIMARY device, must be monitored.
Provision for connection of, or supplied with, a contact sensor (edge device or the equivalent). When used as the PRIMARY device, must be monitored.
Inherent adjustable clutch or pressure relief device.
Provision for connection of, or supplied with, an actuating device requiring continuous pressure to maintain opening or closing motion of the gate.
An inherent audio alarm.
9100-065-D-5-07 5
Important Notices
Vehicular gate operator products provide convenience and security. However, gate operators must use high levels of force to move gates and most people underestimate the power of these systems and do not realize the potential hazards associated with an incorrectly designed or installed system.
These hazards may include:
• Reach through hazards
• Absence of entrapment protection devices
• Improperly located access controls
• Absence of vehicle protection devices
• Absence of controlled pedestrian access
In addition to these potential hazards, automated vehicular gate systems must be installed in accordance with the UL-325 Safety Standard and the ASTM F2200 Construction Standard. Most lay persons are unaware of, or are not familiar with, these standards. If an automated vehicular gate system is not properly designed, installed, used and maintained, serious injuries or death can result.
Be sure that the installer has instructed you on the proper operation of the gate and gate operator system. Be sure that the installer has trained you about the basic functions of the required reversing systems associated with your gate operating system and how to test them. These include reversing loops, inherent reversing system, electric edges, photoelectric cells, or other external devices.
• This Owner’s Manual is your property. Keep it in a safe place for future reference.
• Be sure that all access control devices are installed a minimum distance of 10 feet away from the gate and gate operator, or in such a way that a person cannot touch the
gate or gate operator while using the device. If access control devices are installed in violation of these restrictions, immediately remove the gate operator from service and contact your installing dealer.
• Loops and loop detectors, photo-cells or other equivalent devices must be installed to
prevent the gate from closing on vehicular traffic.
• The speed limit for vehicular traffic through the gate area is 5 MPH. Install speed bumps and signs to keep vehicular traffic from speeding through the gate area. Failure to adhere to posted speed limits can result in damage to the gate, gate operator, and to the vehicle.
• Be sure that all persons who will use the gate system are familiar with the proper use of the gate and gate operator and are familiar with the possible hazards associated with the gate system.
• Be sure that warning signs are permanently installed on both sides of the gate in an area where they are fully visible to traffic.
• It is your responsibility to periodically check all entrapment protection devices. If any of these devices are observed to function improperly, remove the operator from service immediately and contact your installing or servicing dealer.
• Follow the recommended maintenance schedule.
• Do not allow children to play in the area of the operator or to play with any gate-operating device.
• To remove the gate operator from service, operate the gate to the full open position and then shut off power to the operator at the service panel.
Page 6 9100-065-D-5-07
Important Safety Instructions
WARNING - To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2.
3.
Never let children operate or play with gate controls. Keep the remote control away from children.
Always keep people and objects away from gate. NO ONE SHOULD CROSS THE
PATH OF THE MOVING GATE.
4.
5.
6.
7.
8.
Test the operator monthly. The gate MUST reverse on contact (contact sensors must be installed) with a rigid object or stop or reverse when an object activates the noncontact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of injury or death.
Use the emergency release only when the gate is not moving.
KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate hardware.
The entrance is for vehicles only. Pedestrians must use separate entrance.
SAVE THESE INSTRUCTIONS!
Gate Construction
Vehicular gates should be constructed and installed in accordance with ASTM F2200; Standard
Specification for Automated Vehicular Gate Construction. For a copy of this standard, contact ASTM directly at 610-832-9585; [email protected]; or www.astm.org
.
9100-065-D-5-07 7
Instructions regarding intended installation:
• Install the gate operator only if:
1.
2.
The operator is appropriate for the construction of the gate and the usage class of the gate.
All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 4 feet (1.22 m) above the ground to prevent a 2 ¼ inch
(57.2 mm) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position.
3. All exposed pinch points are eliminated or guarded.
4. Guarding is supplied for exposed rollers.
• The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.
• The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment.
Swinging gates should not open into public access areas.
• The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do not over-tighten the operator clutch, pressure relief valve or reduce reversing sensitivity to compensate for a damaged gate.
• For gate operators utilizing Type D protection:
1. The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving.
A warning placard shall be placed adjacent to the controls. 2.
3. An automatic closing device (such as a timer, loop sensor, or similar device) shall not be employed.
4. No other activation device shall be connected.
• Controls intended for user activation must be located at least ten feet (10’) away from any moving part of the gate and where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or easily accessible controls should have a security feature to prevent unauthorized use.
• The Stop and/or Reset button must be located in the line-of-sight of the gate. Activation of the reset control shall not cause the operator to start.
• A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible.
• For gate operators utilizing a non-contact sensor:
1.
2.
3.
See the instructions on the placement of non-contact sensors for each type of application.
Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate is still moving in the opening direction.
One or more non-contact sensors shall be located where the risk of entrapment or obstruction exist, such as the perimeter reachable by a moving gate or barrier.
Page 8 9100-065-D-5-07
• For gate operators utilizing contact sensors:
1.
2.
3.
4.
5.
7.
One or more contact sensors shall be located where the risk of entrapment or obstruction exist, such as at the leading edge, trailing edge, and post mounted both inside and outside of a vehicular horizontal slide gate.
One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.
One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.
A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is not subjected to mechanical damage.
A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstructions. A wireless contact sensor shall function under the intended end-use conditions.
One or more contact sensors shall be located at the bottom edge of a vertical barrier
(arm).
9100-065-D-5-07 9
Slide Gate Requirements
All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of four (4) feet (1.22 m) above the ground to prevent a 2 1/4 inch (57.2 mm) diameter sphere from passing through the openings anywhere in the gate and in that portion of the adjacent fence that the gate covers in the open position.
(ref. UL325 56.8.4.a.2 and ASTM F2200 6.1.2)
Fence
A
Fence
Operator
The operator is intended for installation only on gates used for vehicles.
Pedestrians must be supplied with a seperate access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.
(ref. UL325 56.8.4.b)
Roadway
Pedestrian
Access
Fence
Vehicular Gate
Sidewalk
Gate
4 ft.
min
A gap, measured in the horizontal plane parallel to the roadway, between a fixed stationary object nearest the roadway (such as a gate support post) and the gate frame when the gate is in either the fully open position or the fully closed position, shall not exceed 2 1/4 inch (57.2 mm).
(ref. ASTM F2200 6.1.4)
Operator
A
B 2 1/4"
Max
2 1/4"
Max
Pad
A This area between the gate and fence has a high risk of entrapment. The gap between the fence and gate should not exceed
2 ¼ inches. Install a filler or barrier in this area to reduce this gap to 2 ¼ inches or less.
B Install a contact sensor (type B2) on the fence to help minimize the risk of entrapment in this area.
Page 10 9100-065-D-5-07
Slide Gate Protection
1 Loops to help minimize the potential of the gate to close when a vehicle is present. Number and placement of loops is dependent on the application.
2 Contact sensor installed on the fence to help minimize the potential of entrapment between the gate and fence.
1
Reverse
Loop
Fence
5
2
4
3 Non-contact sensor to help minimize the potential of the gate closing on vehicular or other traffic that loops cannot sense.
Operator
1
4 Non-contact sensor to help minimize the potential of entrapment during the back travel of the gate.
3
Reverse (Open)
Loop
5
6
Pedestrian
Access
Sidewalk
5 Warning signs are to be placed on each side of the gate so that they are easily visible from either side of the gate.
6 A separate pedestrian access located so pedestrians cannot come in contact with the vehicular gate.
1
Open Loop
(Optional)
Fence
9100-065-D-5-07 11
Table of Contents
Section 1 – Installation
1.1 Specifications ...........................................................................................................................................15
1.2.1
1.2.2
1.2.3
1.2.4
Front Position Pad Mount.........................................................................................................16
Front Position Post Mount ........................................................................................................16
Rear Position Pad or Post Mount .............................................................................................17
Center Position Post Mount......................................................................................................17
1.3.2 Post Mounted Operators ..........................................................................................................19
1.4.2 Post Mounted Operators ..........................................................................................................20
1.5.2
1.5.3
Front – Post Mount...................................................................................................................22
Rear – Pad or Post Mount........................................................................................................23
1.6 Warning Sign Installation..........................................................................................................................25
Section 2 – Wiring
Conduits ...................................................................................................................................................27
2.1 High Voltage Connections ........................................................................................................................28
2.3
2.4
2.5
2.6
Loop Detector Wiring................................................................................................................................30
Auxiliary Device Wiring.............................................................................................................................31
Primary / Secondary (Bi-parting) Gate Wiring ..........................................................................................32
Terminal Identification and Description
Section 3 – Adjustments
3.1 Circuit Board Adjustments ........................................................................................................................35
3.2.1
3.2.2
SW 1 (Left Switch) Description and Function...........................................................................37
SW 2 (Right Switch) Description and Function ........................................................................37
3.4.1 Reverse Sensitivity Adjustment................................................................................................39
Page 12 9100-065-D-5-07
Section 4 – Operating Instructions
4.1 Power and Reset Switches ......................................................................................................................41
4.2.2 Resetting a Soft Shutdown.......................................................................................................42
4.3
4.2.4 Resetting a Hard Shutdown .....................................................................................................43
Manual / Emergency Gate Operation
4.3.1 Emergency Vehicle Access Conditions....................................................................................44
4.3.2
4.3.3
Fail-Safe Manual Operation .....................................................................................................44
Fail-Secure Manual Operation .................................................................................................45
Section 5 – Maintenance and Troubleshooting
5.3 Accessories ..............................................................................................................................................51
9100-065-D-5-07 13
Page 14 9100-065-D-5-07
SECTION 1 - INSTALLATION
Prior to beginning the installation of the slide gate operator, we suggest that you become familiar with the instructions, illustrations, and wiring guide-lines in this manual. This will help insure that your installation is performed in an efficient and professional manner.
The proper installation of the vehicular slide gate operator is an extremely important and integral part of the overall access control system. Check all local building ordinances and building codes prior to installing this operator. Be sure your installation is in compliance with local codes.
1.1 Specifications
Class of Operation:
Type of Gate:
Class I, II, III, IV
Vehicular Slide Gates Only
Voltage / Phase:
Max Gate Weight:
Max Gate Length:
Cycles / Hr:
Speed:
Entrapment Protection:
115 VAC Single-phase only
1000 Lbs.
1
30 Ft.
1
60/Hr
Approximately 1 Ft./Sec.
Primary – Inherent (Type A)
Secondary – Provision for connection of a non-contact sensor (Type B1) and/or a contact sensor (Type B2).
Secondary entrapment protection devices are not supplied with the operator and must be ordered separately.
Note 1: Assumes gate is in good working condition installed on a level surface.
12
14.75
11.5
Figure 1
9100-065-D-5-07 15
The Model 9100 operator is designed so that it can be installed in any of the mounting positions shown below. Once the mounting position has been determined, the chain idlers must be adjusted to accommodate the mounting position chosen before the operator is mounted to the pad or post. The idlers are factory set for the front, pad mount position. (Note: Rear and center position, and postmounted operators require additional hardware not supplied with the operator).
1.2.1 Front Position Pad Mount
• This is considered the standard method of installing slide gate operators.
• Set both chain idlers in the top position (factory setting).
• Remove the TOP chain knockouts from each side of the operator.
• Chain passes through the operator and is attached to each end of the gate.
1.2.2 Front Position Post Mount
Figure 2
• Set both chain idlers in the bottom position.
• DO NOT remove chain knockouts. Using this mounting method, the chain enters and exits the operator from the bottom.
• Chain passes through the operator and is attached to each end of the gate.
• This mounting method allows for
Figure 3 the use of chain support attached to the gate. This is useful with long gates and helps prevent chain “stretching.”
• ADDITIONAL HARDWARE REQUIRED: Post Mount Base Plate P/N 2600-418 and two (2)
4” x 4” steel mounting post at least three feet in length. Mounting post are not available from
DoorKing.
Page 16 9100-065-D-5-07
1.2.3 Rear Position Pad or Post Mount
• Set one chain idler at the top position and one chain idler at the center position on the same side of the operator.
• Remove the top and bottom chain knockouts from the side of the operator.
• Chain enters and exits the operator from the same side.
Chain is attached to one end of the gate.
• This mounting method hides the chain when looking at the gate from the front.
Figure 4
•
ADDITIONAL HARDWARE REQUIRED: Endless Idler Assembly P/N 2600-818. Additional length of #41 Chain P/N 2600-441 (20 ft.). Note: additional chain may be required depending on the length of the gate.
• If operator is post mounted: Post Mount Base Plate P/N 2600-418 and two (2) 4” x 4” steel mounting post at least three feet in length. Mounting post are not available from DoorKing.
1.2.4 Center Position Post Mount
•
Set both chain idlers in the bottom position.
•
DO NOT re move chain knockouts.
Using this mounting method, the chain enters and exits the operator from the bottom.
•
Chain passes through the operator and is attached to one end of the gate.
• This mounting method allows for
Figure 5 the use of chain support attached to the gate. This is useful with long gates and helps prevent chain “stretching.”
• ADDITIONAL HARDWARE REQUIRED: Two (2) Endless Idler Assemblies P/N 2600-81
8.
Additional length of #41 Chain P/N 2600-441 (20 ft.). Note: additional chain may be required depending on the length of the gate. Post Mount Base Plate P/N 2600-418 and two (2) 4” x
4” steel mounting post at least three feet in length. Mounting post are not available from
DoorKing.
9100-065-D-5-07 17
Pad mounting can be used when the operator will be installed using either the front or rear mounting position. If the operator is to be center mounted, the post mounting method must be used.
1. Construct a form for the mounting pad according to the specifications shown in figure 6. Be sure to level the top edge of the form and that the top of the form is a minimum of four (4) inches above ground level. We suggest that you contact the local building department to determine the required depth of the pad since soil conditions and code requirements vary from city to city.
2. Set conduits, reinforcing bars and/or wire mesh if required. The number of conduits is determined by the application requirements. We suggest using a minimum of four (4) conduits. 1-High voltage power lines; 2-Low voltage control lines; 3-Loop lead-in wires (open loop); 4-Loop lead-in wires (reverse loops). See SECTION 2. Set additional conduits as required for your application.
NOTE: If conduits are not set in the pad, they can be routed to a J box where connections to the operator can be made after it is installed. There are three (3) ½inch knockouts and one (1) ¾-inch knockout on each side of the operator for this purpose.
3. Mix the concrete according to the manufacturers instructions. Pour the mixture into the form and tamp. Level and finish the surface after pouring is complete. Do not set anchor bolts in the concrete. Sleeve anchors should be used to secure the operator to the pad.
This allows greater flexibility in positioning the operator on the pad.
4. Allow the pad to cure for 48 hours before removing the forms or mounting the operator.
18
Minimum 1" clearance between gate and back of operator.
3.5
Gate
2.5
7
6.5
Conduits can be located in shaded areas.
24
4" minimum above ground level
Figure 6
Ground Level
Conduits
Depth of pad determined by soil conditions and local code
Page 18 9100-065-D-5-07
Post mounting can be used when the operator will be installed in any of the three mounting positions, and must be used if the operator is to be center mounted.
1. Post mounting the operator requires the use of an operator base plate
(P/N 2600-418) and two (2) 4 X 4 steel post (not supplied) welded to the base plate as shown in figure 7.
The length of the steel post and the depth of the pad are determined by soil conditions and local code requirements. We suggest that you contact the local building department to determine the required depth of the pad since soil conditions and code requirements vary from city to city.
4.5
Figure 7
Gate
4 x 4 Steel Post
(not supplied)
1.5
Base Plate
P/N 2600-418
2. After the posts have been welded to the base plate to form the mounting plate assembly, construct a form for the assembly according to the specifications in figure 8.
3. Position the mounting plate assembly into the form. Be sure that the base plate is a minimum of four (4) inches above ground level. Set conduits, reinforcing bars and/or wire mesh if required. The number of conduits is determined by the application requirements.
We suggest using a minimum of four (4) conduits. 1-High voltage power lines; 2-Low voltage control lines; 3-Loop lead-in wires (open loop); 4-Loop lead-in wires (reverse loops). See SECTION 2. Set additional conduits as required for your application.
NOTE: If conduits are not set in the pad, they can be routed to a J box where connections to the operator can be made after it is installed. There are three (3) ½-inch knockouts and one (1) ¾-inch knockout on each side of the operator for this purpose.
IMPORTANT!! Be sure that the mounting plate is level and parallel with the gate.
4. Secure the mounting plate assembly in the form. Mix the concrete according to the manufacturers instructions. Pour the mixture into the form and tamp. Level and finish the surface after pouring is complete.
5. Allow the pad to cure for 48 hours before removing the forms or mounting the operator.
Conduits
4 inch minimum
Depth of pad determined by soil conditions and local code.
20 12
Figure 8
9100-065-D-5-07 19
Prior to mounting the gate operator, be sure that the chain knockouts and chain idlers are set for the mounting position (front, center or rear) and the mounting option chosen (pad or post). Refer back to
SECTION 1.2.
• Position the operator on the pad so that there is a minimum clearance of one (1) inch between the back of the operator housing and the gate.
• IMPORTANT!! Be sure that the operator is parallel to the gate!
Installing the operator in any other manner will cause excessive chain noise, chain wear and stretching, and premature idler failure.
• Mark the mounting holes on the mounting pad. Use a concrete drill bit to drill the mounting holes to the size and depth required for the anchors being used. We recommend minimum 3/8 x 2 sleeve anchors (not supplied).
• After drilling the mounting holes, clean them out and install the sleeve anchors. Position the operator over the anchors and tighten.
90°
Figure 9
•
Position the operator on the mounting plate so that the mounting holes are in alignment. If the mounting plate/post assembly has been installed correctly, there should be a minimum of one (1) inch clearance between the back of the operator housing and the gate, and the opera tor should be parallel to the gate. If these conditions do not exist, make corrections now!
•
IMPORTANT!! Be sure that the operator is parallel to the gate! Installing the operator in any other manne r will cause excessive chain noise, chain wear and stretching, and premature idler failure.
• Secure the operator to the mounting plate/post assembly using six (6) ½-13 x 1 ½ bolts, lock washers and nuts (or equivalent ha rdware). NOTE: Hardware is not supplied with the operator or mounting plate.
Page 20 9100-065-D-5-07
1.5.1 Front – Pad Mount
1. Secure the chain brackets to each end of the gate so that the brackets are level with the top chain knockouts in the operator housing. Brackets should be attached to the inside of the frame so that the chain bolts, when attached, do not protrude beyond the frame of the gate (figure 10).
2. Route the chain through the gate operator: over the chain guide idlers and under the drive sprocket
(figure 12).
3. Slide each end of the chain through a chain stop
(optional). Chain stops are not required if the gate has physical stops.
4. Attach the chain to the chain bolts using the master links supplied, and then attach the chain bolts to the chain brackets using the hardware supplied (figure
10). Make any adjustments to the chain length at this time.
5. Adjust the chain bolts to tighten the chain. The chain should sag no more than one (1) inch per 10 feet of travel. Do not over tighten the chain. IMPORTANT!!
Be sure that the chain is parallel to the gate
(figure 11). Installing the chain in any other manner will cause excessive noise, chain idler
wear and chain stretching.
6. Manually open the gate to the full open position and secure the chain stop (if installed) to the chain so that it is in contact with the operator housing.
7. Manually close the gate to the full closed position and secure the chain stop (if installed) to the chain so that it is in contact with the operator housing.
Figure 10
Figure 11
Figure 12
9100-065-D-5-07 21
1.5.2 Front – Post Mount
1. Secure the chain brackets to each end of the gate so that the brackets are level with the bottom chain idlers in the operator housing. Brackets should be attached to the inside of the frame so that the chain bolts, when attached, do not protrude beyond the frame of the gate.
2. Route the chain through the gate operator: under the chain guide idlers and over the drive sprocket (Figure
15).
3. Slide each end of the chain through a chain stop
(optional). Chain stops are not required if the gate has physical stops.
4. Attach the chain to the chain bolts using the master links supplied, and then attach the chain bolts to the chain brackets using the hardware supplied (figure
13). Make any adjustments to the chain length at this time.
5. Adjust the chain bolts to tighten the chain. The chain should sag no more than one (1) inch per 10 feet of travel. Do not over tighten the chain. IMPORTANT!!
Be sure that the chain is parallel to the gate
(figure 14). Installing the chain in any other manner will cause excessive noise, chain idler
wear and chain stretching.
6. Manually open the gate to the full open position and secure the chain stop (if installed) to the chain so that it is in contact with the operator housing.
7. Manually close the gate to the full closed position and secure the chain stop (if installed) to the chain so that it is in contact with the operator housing.
Figure 13
Figure 14
Page 22
Figure 15
9100-065-D-5-07
1.5.3 Rear – Pad or Post Mount
1. Install an endless idler assembly (p/n
2600-818) at the gate opening between the gate and fence (figure 16, 18). Note that the chain is routed between the fence and the gate in this type of installation. IMPORTANT!! Be sure that the idler assembly is securely
attached to the gatepost, pilaster, etc.
2. Secure the chain brackets to the gate as shown in figure 16. The chain brackets should be attached to the gate frame so that they are approximately one (1) inch apart.
3. Route the chain through the gate operator: over the chain guide idlers and around the drive sprocket (Figure 18), and around the idler assembly.
4. Attach the chain to the chain bolts using the master links supplied, and then attach the chain bolts to the chain brackets using the hardware supplied
(figure 16). Make any adjustments to the chain length at this time.
5. Adjust the chain bolts to tighten the chain. The chain should sag no more than one (1) inch per 10 feet of travel. Do not over tighten the chain.
IMPORTANT!! Be sure that the chain is parallel to the gate (figure 17).
Installing the chain in any other manner will cause excessive noise,
chain idler wear and chain stretching.
6. Manually operate the gate to be sure that the chain is not binding and that the gate operates easily.
Figure 16
Figure 17
Figure 18
9100-065-D-5-07 23
1.5.4 Center – Post Mount
1. Install an endless idler assembly (p/n
2600-818) at each end of the gate opening (figure 21). Note that the gate travels between the fence and the chain in this type of installation. IMPORTANT!!
Be sure that the idler post/mount
assembly is secure.
2. Secure the chain brackets to the gate as shown in figure 19. The chain brackets should be attached to the gate frame so that they are approximately one (1) inch apart.
3. Route the chain through the gate operator: under the chain guide idlers and over the drive sprocket (Figure 21), and then around the two idler assemblies.
4. Attach the chain to the chain bolts using the master links supplied, and then attach the chain bolts to the chain brackets using the hardware supplied
(figure 19). Make any adjustments to the chain length at this time.
5. Adjust the chain bolts to tighten the chain. The chain should sag no more than one (1) inch per 10 feet of travel. Do not over tighten the chain.
IMPORTANT!! Be sure that the chain is parallel to the gate (figure 20).
Installing the chain in any other manner will cause excessive noise,
chain idler wear and chain stretching.
6. Manually operate the gate to be sure that the chain is not binding and that the gate operates easily.
Figure 19
Figure 20
Page 24
Figure 21
END VIEW
9100-065-D-5-07
This DoorKing slide gate operator is shipped with two warning signs. The purpose of the warning signs is to alert uniformed persons, and to remind persons familiar with the system, that a potential hazard may exist so that appropriate action can be taken to avoid the hazard or to reduce exposure to the hazard.
1. Permanently install the supplied warning signs in locations so that the signs are visible by persons on both sides of the gate.
2. Use appropriate hardware such as wood or metal screws
(not supplied) to install the warnings.
WARNING
Moving Gate Can Cause
Serious Injury or Death
KEEP CLEAR! Gate may move at any time without prior warning.
Do not let children operate the gate or play in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance.
Figure 22
9100-065-D-5-07 25
Page 26 9100-065-D-5-07
SECTION 2 – WIRING
Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the electrical panel is in the OFF position. Permanent wiring must be installed to the operator as required by local electrical codes. It is recommended that such work be performed by a licensed electrical contractor.
Since building codes vary from city to city, we highly recommend that you check with your local building department prior to installing any permanent wiring to be sure that all wiring to
the operator (both high and low voltage) complies with local code requirements.
THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!
PRIMARY
OPERATOR
SLIDE GATE CONDUIT REQUIREMENTS
(Typical)
SECONDARY
OPERATOR
Low Voltage Control Devices
Loop Lead-In Wires
High Voltage Power
Figure 23
• The conduit requirements shown in figure 23 are for a typical slide gate operator installation
(the secondary operator is shown for those applications where a secondary operator may be used). The conduit requirements for your application may vary from this depending on your specific needs.
• Use only sweeps for conduit bends. Do not use 90° connectors as this will make wire pulls very difficult and can cause damage to wire insulation.
• We suggest that minimum ¾-inch conduit be used.
• Be sure that all conduits are installed in accordance with local codes.
9100-065-D-5-07 27
Use Table 1 to determine high voltage wire size requirements. The distance shown in the chart is measured in feet from the operator to the power source. If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. Wire run calculations are based on a 110 VAC power source with a 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses in the system.
MODEL AMPS
12 AWG
WIRE SIZE / DISTANCE IN FEET
10 AWG 8 AWG 6 AWG
230 340 9100 DUEL 10.8 85
Table 1
• Route incoming high voltage power through conduit and into the operator as shown in figure 24.
• Be sure wiring is installed in accordance with local codes. Be sure to color code all wiring.
• Connect the power wires to the high voltage terminal strip as shown; BLACK to 115 VAC
HOT, WHITE to 115 VAC NEU and GREEN to GROUND LUG located next to the terminal strip.
• It is recommended that a surge suppresser be installed on the high voltage power lines to help protect the operator and circuit board from surges and power fluctuations.
135
Incoming
Power Wires
Conduits
Figure 24
Page 28 9100-065-D-5-07
Controls must be far enough from the gate so that the user is prevented from coming in contact with the gate while operating the controls. Outdoor or easily accessible controls should have a security feature to prevent unauthorized use.
Fence
C
Roadway
D
A B Gate
C
Open contact sensor placed on fence.
D
Close contact sensor placed on gate.
Wireless option available.
Receiver
Common
Relay
Power
Fire
Dept
Telephone
Entry OPEN
CLOSE
STOP
4
1
2
3
4602-010
Circuit Board
Open Photo
Close Photo
Open Edge
Close Edge
Common
A
Open direction non-contact sensor.
B Close direction non-contact sensor.
C Open direction contact sensor.
D Close direction contact sensor.
A
Z
Call
Stand-Alone
Card Reader
Stand-Alone
Keypad
Key
Switch
Diagram above is for illustration purposes. The actual placement of the secondary protection devices is dependent on the specific installation requirements.
Secondary entrapment protection devices must be installed with this gate operator. This protection may be provided by noncontact or contact sensors, or a combination of both.
Secondary device wiring shows inputs to the circuit board only.
Photo-cells must be supplied with power.
Refer to the safety instructions in the front of this manual for more information.
Controls must be installed a minimum of 10-feet from the gate or installed in such a way that the person using the control cannot come in contact with the gate or gate operator.
All inputs to the 4602 circuit board are Normally Open (N.O.).
1 Radio receiver power only. Power here is limited to 250 ma.
2 Partial open input. Devices connected here will open the gate to 14-feet only.
3 Reverse input functions only when gate is in the closing cycle.
4 Must use a DoorKing 3-button control station. Others will not work.
DOORKING, INC., INGLEWOOD, CA 90301
Title: Model 9100 and 9150
Control and Secondary Device Wiring
Date: 5/07 Dwg. No.
4602-CNTRL-1 Rev.
A
Figure 25
9100-065-D-5-07 29
2.3 Loop Detector Wiring
Loops and loop detectors must be installed with this gate operator to prevent the gate from accidentally closing on vehicles that may be in the path of the gate.
Loops and loop detectors MUST be installed with this gate operator to help prevent the gate from accidentally closing on vehicular traffic.
Loop detector wiring is shown for DoorKing plug-in loop detectors only. If other loop detectors are used, refer to the installation instructions supplied with those detectors for wiring instructions.
If other detectors are used, use a separate power supply to power these detectors.
Loop layout shown is for a typical slide gate application with two-way traffic, or one-way exit only traffic.
Reverse loops are wired in series. See detail A.
Refer to the Loop Information Manual (available from www.dkaccess.com) for more information on loops and loop detectors.
Exit
Reverse
From outside
Reverse loop
From inside
Reverse loop
TB 1
Reverse
Detail A
DoorKing
Loop Detector
Detail A
DoorKing
Loop Detector
Exit
Loop
Reverse
Loop
Timer
Power
Relay Contact
ON
Counter
LEDs
Reverse
Sensitivity
Page 30
Figure 26
DOORKING, INC., INGLEWOOD, CA 90301
Title: Model 9100 and 9150
Loop Detector Wiring
Date: 5/07 Dwg. No.
4602-LOOP-1 Rev.
A
9100-065-D-5-07
2
3
4
1
The auxiliary stop switch will stop a moving gate when activated or will prevent the gate operator from starting when activated. Note that this input is normally open and that a switch closure is required to activate the stop function. Because of this, the auxiliary stop shown must NEVER be used as a safety interlock device.
Jumper is placed across terminals 8 and 9 ONLY WHEN THE AUXILIARY STOP INPUT IS USED.
The Remote Alarm Reset Station MUST be mounted in the line-of-sight of the gate operator.
Using a 2351-010 Tracker Expansion Board, operator data can be sent to the access controller (DoorKing 1833, 1835, 1837 or 1838 only).
Refer to Installation Manual 2351-065 for detailed information.
1 Auxiliary Stop Using Magnetic Switch
Operator
Stopped
Normal
Operation
4602-010
Circuit Board
2
Open Photo
Close Photo
Open Edge
Close Edge
Common
3
DoorKing 1404-080
Remote Reset Switch
Green
Red
White
4
DoorKing 2351-010
Tracker Expansion Board
2351-010
Circuit Board
DOORKING, INC., INGLEWOOD, CA 90301
Title: Model 9100 and 9150
Auxiliary Device Wiring Diagram
Date: 5/07 Dwg. No.
4602-AUXDEV-1 Rev.
A
Figure 27
9100-065-D-5-07 31
2.5 Primary - Secondary (Bi-parting) Gate Wiring
The interface wiring between the two operators requires seven (7) wires (18 AWG minimum) for control and secondary entrapment protection device connection. Each operator must be connected to its own power source as described in section 2.1.
D E
A B C
D E
1
2
3
4
5
6
Connect the Primary / Secondary interconnection wiring as shown. Wire colors are based on DoorKing interconnection cable (P/N 2600-75x).
Place a jumper from terminal 4 to terminal 10 in the PRIMARY operator only.
Set SW 2, Switch 1 to the OFF position in the PRIMARY operator.
Plug a two-channel (P/N 9409-010) loop detector into the OPEN loop port in the
PRIMARY operator. Connect loops and loop detector as shown.
Connect radio receiver as shown. If 14-foot partial open feature is desired with radio receiver, connect receiver relay to terminal 5. Connect other OPEN devices to terminal 4
(Full Open) or terminal 5 (14-foot Open) as required.
Connect standard reverse devices to terminal 6 and/or connect secondary non-contact and/or contact sensors to Secondary Entrapment Protection inputs as shown.
Connect chassis ground to chassis ground.
Common
Relay
Power
4602-010
Circuit Board
Yellow
Violet
Brown
4
5
Reverse Loop
Reverse Loop
2
Open Photo
Close Photo
Open Edge
Close Edge
Common
5
Exit Loop
TB1 TB2
DoorKing
9409-010
3
TB3
Orange
6
Primary
Operator
Green
A Open direction non-contact sensor - Primary Operator.
B Close direction non-contact sensor - Both Operators.
C Open direction non-contact sensor - Secondary Operator.
D Open direction contact sensor - Primary Operator.
E Open direction contact sensor - Secondary Operator.
Conduit
1
Yellow
Violet
Brown
Orange
4602-010
Circuit Board
Open Photo
Close Photo
Open Edge
Close Edge
Common
5
6
Secondary
Operator
Green
Title: Model 9100 and 9150
Primary / Secondary Wiring Diagram
Date:
DOORKING, INC., INGLEWOOD, CA 90301
7/07 Dwg. No.
4602-DUAL-1 Rev.
A
Page 32
Figure 28
9100-065-D-5-07
2.6 Terminal Identification and Description
1.
2.
3.
4.
5.
RADIO RECEIVER LOW VOLTAGE COMMON
RADIO RECEIVER FULL OPEN INPUT
RADIO RECEIVER 24 VAC POWER – 250-ma MAX
FULL OPEN / CLOSE INPUT
When gate is closed, input will open gate to full position.
When gate is open and auto close timer is turned on, input will re-set and hold timer.
When gate is open and auto close timer is turned off, input will close gate.
When gate is closing, input will reverse gate.
14-FOOT OPEN / CLOSE INPUT
When gate is closed, input will open gate to 14-foot position.
When gate is open and auto close timer is turned on, input will re-set and hold timer.
When gate is open and auto close timer is turned off, input will close gate.
When gate is closing, input will reverse gate to 14-foot position.
When gate is fully closed or in the opening cycle, this input has no affect on the gate operator.
When gate is open and auto close timer is turned ON, input will re-set and hold timer.
When gate is open and auto close timer is turned OFF, input will prevent gate from closing.
When gate is closing, input will reverse gate if SW 2, switch 2 is OFF.
When gate is closing, input will stop gate if SW 2, switch 2 is ON.
8.
9.
OPEN INPUT - Use with DoorKing 3 button control station only (P/N 1200-006).
CLOSE INPUT - Use with DoorKing 3 button control station only (P/N 1200-006).
10. OPEN LOOP LOGIC OUTPUT
If SW 2, switch 1 is OFF, this terminal becomes the logic output of the loop detector plugged into the OPEN loop port (DoorKing loop detectors only).
11. ALARM RESET INPUT
13. GATE TRACKER - BUSY
14. GATE TRACKER - DATA
15. DRY RELAY CONTACT
Operation of relay is dependent on setting of SW 1, switches 4 and 5. Relay contacts can be set for Normally Open (NO) or Normally Closed (NC) operation. Contact rating is 1 amp maximum at 24 Volts.
16. DRY RELAY CONTACT
17. LED INDICATOR OUTPUT - Provides 24 VDC, 250-ma maximum to power LED.
Operation of LED is dependent on setting of SW 1, switches 4 and 5.
18. LOW VOLTAGE COMMON
9100-065-D-5-07 33
The auxiliary terminal is located on the 4602 circuit board just to the right of main terminals 8 and 9.
Auxiliary terminals are numbered 1 through 5 with the first terminal at the top.
This input is only active when the gate is in the opening cycle. An open photo-beam input during the opening cycle will cause the gate to stop. The gate will remain stopped until the photo-beam input is cleared, at which time the gate will resume the open cycle.
This input is only active when the gate is in the closing cycle. A close photo-beam input during the closing cycle will cause the gate to stop. The gate will remain stopped until the photo-beam input is cleared, at which time the gate will resume the close cycle.
This input is only active when the gate is in the opening cycle. An open edge input during the opening cycle will cause the gate to stop and then reverse.
If the gate reaches the full closed position, the gate will remain closed, ignore any maintained inputs and enter a soft shutdown condition. NOTE: If the gate was initially activated by a time clock with a contact closure across the gate operator open input, this input will be ignored until another input (open loop, reverse loop. etc.) is received by the gate operator.
If a close edge sensor is activated prior to the gate reaching the full closed position, the gate will stop and enter a soft shutdown condition.
This input is only active when the gate is in the closing cycle. A close edge input during the closing cycle will cause the gate to stop and then reverse.
If the gate reaches the full open position, the timer will automatically close the gate (if it is turned on). Once the gate starts to close again, if the close edge input is activated a second time prior to the gate reaching the full closed position, the operator will stop and reverse and will enter a soft shutdown condition.
If an open edge sensor is activated prior to the gate reaching the full open position, the gate will stop and enter a soft shutdown condition.
5. COMMON
Common terminal for the secondary entrapment protection device inputs.
Page 34 9100-065-D-5-07
SECTION 3 - ADJUSTMENTS
The switch settings and adjustments in this chapter should be made after your installation and wiring to the operator(s) is complete. Whenever any of the programming switches on the circuit board are changed, power must be shut-off, and then turned back on for the new setting to take effect.
3.1 Circuit Board Adjustments
• Set the DIP-switches on the circuit board to the desired setting. See switch-setting charts in section 3.2.
• Auto close timer (when turned on) can be set from 1 second (full counter clockwise) to approximately 23 seconds (full clockwise).
• Dry contact relay (terminals 15-16) can be set for Normally Open (NO) or Normally Closed
(NC) operation by placing the relay shorting bar on the NO or NC pins respectively.
• Power LED indicates that low voltage power is applied to the circuit board. Input LEDs should be OFF and will only illuminate when the input is activated. The pulse LEDs will blink as the operator is running. They can be either ON or OFF when the operator is stopped.
Exit
Loop
Reverse
Loop
Timer
Power
ON
Relay Contact Counter
LEDs
Figure 29
Reverse
Sensitivity
9100-065-D-5-07 35
The two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn on or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.
SW 1 (LEFT SWITCH)
SWITCH FUNCTION SETTING
ON
DESCRIPTION
Changes open / close direction of operator.
Timer ON
Auto-close timer is OFF. Manual input required to close gate.
Auto-close timer is ON. Adjustable from 1-23 seconds.
3 Motor OFF
ON
4 & 5 Relay & LED
Normal setting .
DC braking voltage applied to motor windings.
4-OFF 5-OFF
4-OFF 5-ON
4-ON 5-OFF
4-ON 5-ON
Relay activated and LED on when gate is FULL OPEN.
Relay activated and LED on when gate is NOT CLOSED.
Relay activated and LED on when gate is OPENING and OPEN.
Relay activated and LED on when gate is OPENING or CLOSING.
6 Self OFF
ON
Normal setting .
Runs self test – bench test only.
7 & 8 Open Back-Off 7-OFF 8-OFF
7-OFF 8-ON
7-ON 8-OFF
7-ON 8-ON
Normal setting . Back-off 0 inches from full open position.
Back-off 1 inch from full open position.
Back-off 2 inches from full open position.
Back-off 3 inches from full open position.
SW 2 (RIGHT SWITCH)
SWITCH FUNCTION SETTING DESCRIPTION
Output
Stop
ON
ON
ON
4 Solenoid OFF
ON
Switches logic level output of OPEN loop port to terminal 10.
Normal setting . Control board responds internally to loop detector plugged into open loop port.
Normal setting . Input to terminal 6 will reverse gate during close cycle.
Input to terminal 6 will stop gate during close cycle – gate will continue to close after input is cleared.
Normal setting . Input to terminal 5 opens gate 14 feet.
Used for model 9200 operator only.
Normal Setting . Fail-safe logic. Lock engages only if attempt is made to force gate open.
Fail-secure logic. Lock engages after each gate cycle.
ON
ON
Normal setting . Switch must be OFF for models 9100 and 9150 operators.
Switch is in the ON position for model 9200 operator only.
Normal gate operation.
Timer defaults to 1 second regardless of timer setting. Gate begins to close after reverse inputs (loops) are cleared regardless of the distance the gate has opened.
7 & 8 Close Back-Off 7-OFF 8-OFF
7-OFF 8-ON
7-ON 8-OFF
7-ON 8-ON
Normal setting . Back-off 0 inches from full close position.
Back-off 1 inch from full close position.
Back-off 2 inches from full close position.
Back-off 3 inches from full close position.
Page 36 9100-065-D-5-07
3.2.1 SW 1 (Left Switch) Description and Function
Switch 1: Set so that the operator cycles open upon initial power up and open command. If the operator cycles close, turn power off and change the setting on this switch.
Switch 2: Turns the auto close timer on or off. Set from 1 to 23 seconds.
Switch 3: This switch should be left in the OFF position when the slide gate is running on a level track and the gate does not coast. If the gate is on an incline, turning this switch on will apply a DC voltage to the motor windings when the gate is stopped. This applies braking power to the motor to prevent the gate from coasting.
Switches 4-5: These work in conjunction with each other and determine when the relay on the board will be activated. This relay can be used as a switch for various functions such as illuminating a warning light when the gate is moving, or turning on a green light when the gate is full open. If a magnetic lock is used with the gate operator, these switches must be set for magnetic lock operation which limits the relay to activate only when the gate is opening and full open.
Switch 6: This switch must be in the OFF position for normal operation. The self-test feature checks various functions of the operator. CAUTION - Do not run self-test with the operator connected to the gate. The drive chain must be disconnected from the operator to run the self-test.
Switches 7-8: These work in conjunction with each other and determine if the operator will stop the gate at the full open position, or if the gate should stop 1, 2 or 3 inches short of the full open position.
3.2.2 SW 2 (Right Switch) Description and Function
Switch 1: Determines if the output of the loop detector (DoorKing loop detectors only) plugged into the OPEN port will be sent directly to the microprocessor to open the gate, or if the output is directed to terminal 10 where it can then be connected to other input terminals.
Switch 2: Determines if an input to terminal 6 will reverse or stop a closing gate. If this switch is set to stop the gate (ON), once the input to terminal 6 is cleared, the gate will continue to close. This is typically used to help prevent tailgating.
Switch 3: Switch must be in the OFF position for models 9100 and 9150.
Switch 4: This switch determines the operation of the solenoid lock and is factory set. CAUTION: Do not change the setting of this switch unless the solenoid / lock assembly has been repositioned for the operation desired. Changing the setting of this switch without physically changing the lock assembly will damage the operator.
Switch 5: Switch must be in the OFF position for models 9100 and 9150.
Switch 6: Turning the timer override feature on will cause the auto close timer to close the gate after
1 second, regardless of the setting of the auto close timer potentiometer. This will also cause an opening gate to stop and reverse when the reverse (loop) inputs are cleared. This feature, along with switch 2 above, is useful to prevent tailgating.
Switches 7-8: These work in conjunction with each other and determine if the operator will stop the gate at the full closed position, or if the gate should stop 1, 2 or 3 inches short of the full closed position.
9100-065-D-5-07 37
3.3 Automatic Limit Adjustment
This gate operator does not use any mechanical limit switches or run timers to adjust the open and close positions of the gate. The gate open and close positions are determined by the physical stops
(or chain stops) of the gate. The gate operator will automatically measure the gate and will set its
"limits" from this measurement during this automatic sequence.
!! IMPORTANT !!
This automatic limit adjustment sequence must be run prior to testing the operator for normal operation, and prior to testing any of the safety features that are incorporated into this operator. This includes the primary and secondary entrapment protection features, and the entrapment alarm and reset features.
1. The limit adjustment is automatic and relies on the physical stop of the gate or on the chain stops installed on the chain. Be sure that the gate has a physical travel limitation in both directions prior to starting this sequence. DoorKing "Gate Stops" can be used if physical stops are not present on the gate.
2. If either the open and/or close back-off feature is going to be used, set SW1 and SW2 switches 7 and 8 to the desired settings (see Section 3.2).
3. Turn power to the operator ON. Activate an open device (or momentarily jumper between terminals 4 and 18). The gate operator should begin to cycle the gate to the OPEN position.
4. If the gate operator begins to cycle the gate to the CLOSED position, turn power to the operator OFF. Change the setting of the direction switch, SW 1 (left switch), switch 1, then repeat step 2.
5. After the gate reaches the full open position, the gate operator will shut off. Activate a keying device to close the gate (or allow the timer to close the gate if it is turned on).
When the gate reaches the full closed position, the gate operator will shut off.
NOTE: During this initial setup, be sure that the operator clutch does not slip while the gate is cycling from the full open to the full closed position. If the clutch slips during this period, the limits will be misadjusted.
6. After closing, the gate will open automatically and stop approximately one foot from the full open position, and then will continue to the full open position. Activate a keying device to close the gate (or allow the timer to close it if it is turned on). The gate will close and stop approximately one foot from the full closed position, and then will continue to the full close position.
7. The operator limits and coast settings are now set. Cycle the gate again. The operator should reach the full open and full close positions and then shut off automatically.
Page 38 9100-065-D-5-07
This vehicular gate operator is equipped with an inherent (Type A) entrapment sensing system. This system will sense an obstruction in either the opening or closing gate cycles and will cause the gate to reverse direction should an obstruction be encountered. For this system to function correctly, the gate must be properly installed and work freely in both directions. A good set of ball bearing wheels
(or rollers) is essential for proper slide gate operation.
1. Activate the gate operator my momentarily shorting terminal 4 and 18 with a 1-foot piece of 18 AWG wire. Be sure that the automatic limit adjustment has been completed as described in section 3.3.
2. While the gate is running, slowly rotate the reverse sensitivity potentiometer clockwise until the gate reverses travel, then rotate the potentiometer 1/8 turn counter clockwise.
Note: Rotating the sensitivity adjustment clockwise INCREASES the reverse sensitivity.
Rotating this adjustment counter-clockwise DECREASES the reverse sensitivity. NOTE:
After the gate has reversed, the operator will assume a "soft shutdown" making it necessary to initiate the cycle again by momentarily shorting across terminals 4 and 18 as in step 1.
3. Operate the gate a few times to be sure that it cycles completely.
4. Place an immobile object along the path of the gate so that the gate will strike it while in the open cycle. The gate must reverse direction after striking the object. If it does not, increase the reverse sensitivity by turning the potentiometer 1/8 turn clockwise, then repeat this test. NOTE: After the gate has reversed, the operator will assume a "soft shutdown" making it necessary to initiate the cycle again by momentarily shorting across terminals 4 and 18 as in step 1.
5. Place an immobile object along the path of the gate so that the gate will strike it while in the close cycle. The gate must reverse direction after striking the object. If it does not, increase the reverse sensitivity by turning the potentiometer 1/8 turn clockwise, then repeat this test. NOTE: After the gate has reversed, the operator will assume a "soft shutdown" making it necessary to initiate the cycle again by momentarily shorting across terminals 4 and 18 as in step 1 to reactivate the automatic close timer.
6. You may have to repeat step 2 several times to find the correct sensitivity adjustment.
DECREASE INCREASE
Figure 30
9100-065-D-5-07 39
In addition to the reverse sensitivity adjustment, this operator is equipped with a mechanical slip clutch to further reduce the possibility of injury should an entrapment occur. Do not over tighten the clutch in this gate operator to compensate for a damaged or poorly constructed gate, or to compensate for a gate that is too heavy or that has damaged wheels or rollers. Doing this can create a hazard which can result in serious injury or death to persons who may become entrapped.
1. Be sure power to the operator is turned OFF whenever adjustments to the clutch
are made. Loosen the center hex bolt to "un-lock" the jamb nut, and then loosen the jam nut. You may have to hold the large pulley to loosen this nut.
2. Tighten the jamb nut so that it is finger tight, and then tighten it one turn with a wrench.
Tighten the center hex bolt to lock the jamb nut in place.
3. Apply power to the gate operator and cycle it to allow the operator to adjust its limit settings as described in section 3.3.
4. Activate the gate operator by momentarily shorting across terminals 4 and 18 with a 1foot 18 AWG wire. When the gate begins to open, determine if the clutch is slipping. If the clutch is slipping, turn power OFF and tighten the jamb nut one more turn as described in step 2, then repeat steps 3 and 4 (This process may have to be repeated several times to get the right clutch adjustment).
5. After adjusting the clutch so that the gate opens and closes without it slipping, place an immobile object along the path of the gate so that the gate will strike it while in the open cycle. The clutch should slip and the gate must reverse direction after striking the object.
If it does not, repeat steps 1-3 and 5 to readjust the clutch. NOTE: After the gate has reversed, the operator will assume a "soft shutdown" making it necessary to initiate the cycle again by momentarily shorting across terminals 4 and 18.
6. Place an immobile object along the path of the gate so that the gate will strike it while in the close cycle. The gate must reverse direction after striking the object. If it does not, repeat steps 1-3 and 6 to readjust the clutch. NOTE: After the gate has reversed, the operator will assume a "soft shutdown" making it necessary to initiate the cycle again by momentarily shorting across terminals 4 and 18 to initiate the auto close timer.
7. The ideal clutch adjustment will allow the operator to move the gate through its entire travel cycle without slipping, but will slip upon contact with an obstruction with no more than 75 Lbs of force. This force can be measured with a gate scale, DoorKing P/N 2600-
225.
Page 40
Figure 31
Magnet Assembly
9100-065-D-5-07
SECTION 4 – OPERATING INSTRUCTIONS
WARNING - To reduce the risk of injury or death:
1.
2.
READ AND FOLLOW ALL INSTRUCTIONS.
Never let children operate or play with gate controls. Keep the remote control away from children.
3.
4.
5.
6.
Always keep people and objects away from gate. NO ONE SHOULD CROSS THE
PATH OF THE MOVING GATE
Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of injury or death.
Use the emergency release only when the gate is not moving and power has been shut-off.
KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate hardware.
The entrance is for vehicles only. Pedestrians must use separate entrance.
SAVE THESE INSTRUCTIONS.
7.
8.
4.1 Power and Reset Switches
Open the power switch cover located on the side of the operator to access the MAIN POWER switch and the operator RESET switch (Figure 37).
• The RESET switch is used to turn off the entrapment alarm and to reset the operator after a hard shutdown has occurred.
• The AC POWER toggle switch turns power to the operator ON (toggle up) or OFF (toggle down).
AC
POWER
OFF
Figure 32
9100-065-D-5-07 41
Under various entrapment conditions the operator will assume either a soft or hard shutdown (alarm) condition. To determine what type of reset action is required, you will need to understand how the different entrapment conditions affect the gate operator.
This occurs in various situations where the inherent or secondary entrapment protection devices have been activated. In a soft shutdown condition, the operator will not respond to any input that was present when the entrapment protection device sensed an obstruction. If the gate stops at the open position, the operator will not respond to the automatic close timer.
• Example 1: A time clock keys the gate open in the morning and an entrapment protection device senses an obstruction prior to the gate reaching the full open position. If the entrapment is sensed by the inherent system, the gate will reverse and run back to the closed position. The time clock input is still present, but the gate will not re-open.
NOTE: In some systems, the time clock input comes from the telephone entry system relay. This same relay may also provide open commands for a card reader, MicroPLUS transmitters and the visitor telephone entry. If so, these devices will also be disabled in a soft shutdown condition.
• Example 2: If the gate is closing and an entrapment protection device is activated, the gate will either stop or reverse and run back to the open position, depending upon if the secondary or inherent device was activated. The automatic close timer will not close the gate.
• Example 3: Vehicle arrives at open loop and the gate runs towards the open position. The inherent entrapment protection is activated. The gate reverses and runs back to the closed position. If the vehicle is still present at the open loop a soft shutdown condition does not occur. The loop input provides an immediate reset of the operator and the gate will again run to the open position.
4.2.2 Resetting a Soft Shutdown
In some conditions, a soft shutdown will reset as soon as the entrapment condition clears. For example, if a non-contact sensor (photo cell) is sensing an obstruction, the operator will stop the gate and assume a soft shutdown condition. When the photocell clears, the operator will return to normal operation.
When the operator is in a soft shutdown, activation of any "intended input" will reset the operator. An
"intended input" includes any command, any standard safety input and any loop input. Activating any of these inputs will reset the gate. At that point the gate will return to normal operation. If the gate is open, the automatic close timer will then time out and close the gate.
Page 42 9100-065-D-5-07
A hard shutdown condition occurs when the inherent entrapment protection system has sensed two consecutive obstructions before the gate reaches the full open or full closed position.
• Example: The gate is closing and the inherent entrapment protection system senses an obstruction and causes the gate to reverse direction. As the gate begins to run in the open direction, a second obstruction is sensed prior to the gate reaching the full open position.
Once the second obstruction has been sensed, the operator will stop, the audio alarm will be activated and all standard inputs are shut down (including open commands, safety commands, loop inputs, etc.).
• NOTE: The audio alarm will remain activated for a maximum of five minutes, or until the operator receives a reset input. The hard shutdown condition will remain in affect even if the audio alarm shuts off after five minutes.
• After 5 minutes, the audio alarm will “chirp” every 5 seconds. This indicates that the operator is in a hard shutdown condition and the reset switch must be activated to reset the operator and silence the alarm.
4.2.4 Resetting a Hard Shutdown
When the operator is in a hard shutdown condition (audio alarm activated or audio alarm “chirps” every 5 seconds), the only way to reset the gate operator and return it to normal operation is to activate the alarm reset input. An alarm-reset switch can be mounted external of the gate operator provided that it is installed in the line of sight of the gate and gate operator (see 2.6.1).
• Before resetting a hard shutdown, determine why the shutdown occurred. Inspect the gate for any obstructions along its path that could have activated the inherent entrapment sensing system. Inspect the gate and gate hardware.
• NOTE: DoorKing operators have a built-in alarm reset push button mounted on the operator above the power ON-OFF toggle switch. Activating this button will return the gate operator to normal operation, but will not activate the gate operator.
Once the gate has been reset, an open or close command is needed to start the gate operator. Most activating commands will cause the gate operator to cycle to the open position. This includes activation of a key switch or open command and activation of an open loop. Activation of a close command will run the gate to the closed position.
• NOTE: The gate operator will not lose its limit settings when a hard shutdown occurs.
9100-065-D-5-07 43
4.3 Manual / Emergency Gate Operation
This operator is equipped with a manual release system that will allow the gate to be pushed open in the event of a power outage or equipment failure.
There are two manual release systems that are available on this gate operator. The standard type release is the FAIL-SAFE system (required by many city codes), while an optional release is the
FAIL-SECURE system.
NOTE: Never attempt to manually push open any gate with an operator attached to it until you have verified that power to the operator has been shut-off.
The automatic vehicular gate system must be designed to allow access to emergency vehicles under different operating conditions.
1. During normal powered operation, emergency vehicles access the gate by use of the emergency vehicle access device installed on your gate system. The type of device that is used in your community is dependent on your city codes. These devices may include
(but are not limited to) Fire Department lock boxes, Click-2-Enter radio receivers, strobe light sensors, siren sensors, etc.
2. In the event of a power failure, the emergency vehicle access device may not be functional because the gate operator is un-powered. If the gate operator is equipped with a battery back-up system, this system will automatically open the gate when primary (AC) power is removed. NOTE: DC powered back-up systems are optional and your gate system may or may not be equipped with one. Check with your installer to determine if your gate system is equipped with a back-up power system.
3. In the event of a primary (AC) power failure and a back-up system (DC) power failure
(low charged or dead batteries for example), the system must have a release system to allow the gate to be manually operated. The release device must be accessible from either side of the gate and must be present so that emergency personnel can gain access through the gate under this condition.
The FAIL-SAFE manual operation system is the most reliable and safest method for placing an automated gate in manual operation and is the preferred method of emergency gate operation under worse case conditions by many Fire Chiefs and Building Inspectors and is typically used in CLASS I and CLASS II applications. This system requires no keys, cranks or other tools for manual gate operation and is completely automatic. This prevents any delays for emergency vehicle access in the event that a power outage has occurred.
• When AC power is removed (power failure or switch power off), the operator "FAILS" in a
"SAFE" condition allowing the gate to be manually pushed open without the need of any tools, keys, cranks or other devices. This assures emergency vehicle access under the worst-case conditions.
• For manual fail-safe gate operation, turn power to the operator OFF. If a backup power system is in use, be sure that this power is turned OFF also. Once power is OFF, the gate can be manually operated.
Page 44 9100-065-D-5-07
The FAIL-SECURE option locks the gate when primary (AC) power is removed and requires a keyed release to place the gate in manual operation. The FAIL-SECURE option is typically used in CLASS
III and CLASS IV applications.
• Be sure that primary (AC) and backup (DC) power is removed or shut-off prior to placing the gate operator in manual operation.
• Insert the manual release key into the keyed release on the side of the gate operator, and turn it clockwise 1/4 turn. The gate can now be manually operated.
1/4 TURN
Figure 33
9100-065-D-5-07 45
Page 46 9100-065-D-5-07
SECTION 5 – MAINTENANCE AND TROUBLESHOOTING
Inspection and service of this gate operator by a qualified technician should be performed anytime a malfunction is observed or suspected. High cycle usage may require more frequent service checks.
5.1 Maintenance
When servicing the gate operator, always check any secondary (external) reversing devices (loops, photo eyes, etc.) for proper operation. If external reversing devices cannot be made operable, do not place this operator in service until the malfunction can be identified and corrected.
Always check the inherent reversing system when performing any maintenance. If the inherent reversing system cannot be made operable, remove this operator from service until the cause of the malfunction is identified and corrected. Keeping this operator in service when the inherent reversing system is malfunctioning creates a hazard for persons which can result in serious injury or death should they become entrapped in the gate.
When servicing this gate operator, always turn power OFF!!
MAINTENANCE SCHEDULE
Alarm
Drive Belt
Chain
Clutch
Fire Dept.
Gate
Grease
Loop(s)
Primary Reverse
System
Pulleys
Release
Secondary
Reverse Device
Complete
Activate the primary (inherent) reverse system by blocking the gate with a solid object. When the gate reverses, block the gate in the opposite direction prior to the limit being reached. The entrapment alarm should activate. Press the reset button to silence the alarm.
Check for alignment, tightness and wear.
Check for sagging. Tighten if necessary.
Check for proper slippage when an obstruction is encountered.
Check emergency vehicle access device for proper operation.
Inspect for damage. Check gate wheels, rollers and guides for wear and grease if necessary.
Wheels and guide rollers if necessary.
Check vehicular reverse and shadow loops for proper operation.
Check that the gate reverses on contact with an object in both the opening and closing cycles. Adjust the clutch if necessary.
Check for alignment. Check setscrews.
Check manual release for proper operation.
Check that secondary (external) reverse device(s) stop or reverse the gate when activated.
Complete check of gate and gate operating system.
MONTHLY
INTERVAL
3 6 12
9100-065-D-5-07 47
5.2 Troubleshooting
Have a good VOM meter to check voltages and continuity. A Meg-Ohm meter capable of checking up to 500 meg-ohms of resistance is necessary to properly check the integrity of the ground loops.
When a malfunction occurs, isolate the problem to one of three areas: 1) the operator, 2) the loop system, 3) the keying devices. Use caution when checking high voltage terminals, motor
capacitor and the motor.
1. Check the input indicator LEDs. They should only come ON when a keying device (card reader, push button, etc.) is activated. If any of the input LEDs are ON continuously, this will cause the gate operator to hold open. Disconnect the keying devices one at a time until the LED goes OFF.
2. Check any external secondary entrapment protection devices. Any short or malfunction in these devices can cause the gate operator to stop or to hold open.
3. A malfunction in a loop or loop detector can cause the gate operator to hold open, or to not detect a vehicle when it is present over the loop. Pull the loop detector circuit boards from the loop ports on the operator circuit board. If the malfunction persists, the problem is not with the loop system. For more information on trouble shooting loops and loop detectors, refer to your loop detector instruction sheet and to the DoorKing Loop and
Loop Detector Information Manual.
4. Check to be sure that there are no shorted or open control wires from the keying devices to the gate operator. If a keying device fails to open the gate, momentarily jumper across terminals 4 and 18 on the gate operator circuit board. If the gate operator starts, this indicates that a problem exist with the keying device and is not with the gate operator.
5. If a three-button control station (open-close-stop) is connected to this gate operator, check for proper wiring. Only a DoorKing three button control station (P/N 1200-006) can be used with this gate operator. Others will cause a malfunction.
6. Check the high voltage supply. A voltage drop on the supply line (usually caused by using too small supply voltage wires) will cause the operator to malfunction. Refer to the wire size chart in section 2.1.
TROUBLESHOOTING
Operator will not run. Power LED is
OFF.
Operator will not run. Power LED is
ON.
•
Check that power to the operator is turned ON.
•
Transformer may be overheated. Turn power off and allow board to cool for several minutes then retest. Check for low 115 VAC power and low voltage shorts.
•
Check for 115 VAC at high voltage terminals. If voltage measures 0, check power. If voltage measures OK, check the terminal strip or replace the circuit board.
•
If a photo-cell is used as a secondary entrapment prevention device, check to be sure that the beam is not blocked.
•
Momentarily jumper terminal 4 to terminal 18. If the input LED does not come ON, check the terminal strip or replace the circuit board. If LED does come ON, proceed to next steps.
•
Be sure that the chain is not too tight. A too tight chain may cause the operator to stall.
•
Turn power switch OFF and remove the control board.
•
Place a jumper wire from the 117 VAC SWITCHED terminal to the POWER board connector terminal with the BLUE wire. CAUTION – HIGH VOLTAGE . Turn the power switch on. The motor should run. Turn the power switch off and remove the jumper.
•
Place a jumper wire from the 117 VAC SWITCHED terminal to the POWER board connector terminal with the RED wire. CAUTION – HIGH VOLTAGE . Turn the power switch on. The motor should run in the opposite direction. Turn the power switch off and remove the jumper.
•
If the motor runs in both steps above, replace the control board. If the motor does not run, or runs in only one direction, problem can be a bad motor, motor capacitor, motor resistors, wire connections from the control board to the motor or a bad control board.
Page 48 9100-065-D-5-07
Gate opens a short distance, then stops and reverses.
Gate opens but will not close.
Gate closes but will not open.
Gate starts to close, then reverses to open.
Gate closes and then re-opens.
•
Check that the clutch is adjusted properly and is not slipping.
•
Disconnect the gate from the gate operator and check that the gate slides freely without any binding.
•
Re-adjust the reverse sensitivity.
•
Check the COUNTER LEDs on the circuit board. They should blink as the operator is running. If either COUNTER LED is not blinking as the operator is running, check that the magnetic pickup transistors are within 1/8 inch of the plastic protective cover above the magnet assembly on the main shaft.
•
Replace the circuit board.
•
Check the input LEDs. Any ON will hold the gate open and indicates a problem with a keying device.
•
Check the secondary safety devices. Any activated will hold the gate open and indicates a problem with the safety device.
•
Check the loop detectors. Any activated can hold the gate open and indicates a problem with the loop detector or ground loop.
•
Operator may be in a “soft shutdown.” Activate any keying device to determine if operator returns to normal operation.
•
If automatic close is desired, be sure SW-1, switch 2 is ON.
•
Check motor as described on previous page.
•
Operator may be in a “soft shutdown.” Check input LEDs on terminals 2, 4 and 5. If any are ON, momentarily disconnect, then re-connect the wire going to the respective terminal.
Operator should open.
•
Check to be sure that the operator is running in the proper direction. Turn power OFF, and then back ON. Activate a keying device. Operator should run in the open direction. If operator runs in the close direction, turn power OFF and change direction switch SW-1, switch 1. Go to above section if operator now opens but will not close.
•
Be sure that the respective LED on the control board lights when the keying device connected to the respective terminal is activated. If LED does not light, momentarily place a jumper wire from terminal 18 to the input terminal being checked. If LED lights and gate opens, problem is with the keying device. If LED does not light, replace control board.
•
Check motor as described on previous page.
•
Check that the clutch is adjusted properly and is not slipping.
•
Re-adjust the reverse sensitivity.
•
Disconnect the gate from the operator and check that the gate operates freely without any binding.
•
Check the loop detector LEDs and input LEDs. Any that flash ON will cause the gate to reverse.
•
Check the COUNTER LEDs on the circuit board. If either COUNTER LED is not blinking as the operator is running, check that the magnetic pickup transistors are within 1/8 inch of the protective plastic cover above the magnet assembly on the main shaft.
•
Replace the circuit board.
•
Check for any input or loop detector LEDs that are ON.
•
Check that the operator is running in the proper direction (see “gate closes but will not open” above).
•
Turn power off, then back on and reset the operator limits.
•
Operator is in a “hard shutdown” condition. Reset switch must be activated to return operator to normal operation.
Entrapment alarm is sounding.
Operator will not run.
Entrapment alarm sounds a short beep every 5 seconds.
•
Operator has been in a “hard shutdown” condition in excess of 5 minutes. Reset switch must be activated to return operator to normal operation.
9100-065-D-5-07 49
Motor / Belt Access
To gain access to the inside of the gate operator, loosen the two bolts on each side of the electrical panel at the bottom. The entire panel can then swing up for easy access into the operator.
CAUTION!! Be sure power is OFF before accessing the inside of the operator. Be sure that the electrical panel is secured in the up position - it will not stay in this position by itself.
Figure 34
Page 50 9100-065-D-5-07
5.3 Accessories
The following accessory items can be used with the model 9100 slide gate operator.
Contact Sensor
Photo Cell
Loop Detector
Contact sensors for use as a secondary entrapment protection device.
Miller Edge, Inc. ME120, ME123, MG020, MGR20, MGS20
Non-contact (photo cells) sensors for use as a secondary entrapment protection device. Compliant with UL 325 and listed.
Infrared Thru-Beam with hoods and heater. 165-foot sensing distance.
P/N 8080-010
Photo-Reflective with reflector. 30-foot sensing distance.
P/N 8080-011
Detectors plug directly into ports on circuit board simplifying wiring.
P/N 9405-010 - Single channel detector.
P/N 9406-010 - Two channel detector
Loop Wire
Pre-Fab Loops
18 AWG loop wire with XLPE insulation is ideal for ground loops.
Available in 500 and 1000 foot rolls with red, blue or black insulation.
Prefabricated ground loops. 24-foot circumference with 50-foot lead-in.
Available in yellow, red or blue jackets. Not for use in asphalt roadways.
Loop Test Meter
Control Station
Meg-ohm meter checks the integrity of ground loops.
P/N 9401-045
Three button interior and exterior control stations provide manual openclose-stop gate operation.
P/N 1200-006 – Exterior / Interior
Time Clock
Surge Devices
Gate Scale
Speed Bumps
7 day and 365 day time clocks can be used to automatically open gate at pre-set time and days. Compact clock fits inside the operator.
P/N 2600-791 – 7-day clock.
P/N 2600-795 – 365-day clock.
High and low voltage surge suppressers help prevent circuit board failure caused by lightning strikes and power surges.
P/N 1876-010 - High Voltage.
P/N 1878-010 - Low Voltage.
Use to test ft/pounds required to move gate. P/N 2600-225
Prefabricated six-foot speed bump reduces traffic speed through gate system. P/N 1610-150
Endless Idler
Base Plate
Use when gate operator is rear or center mounted. P/N 2600-818
Required if operator is to be post mounted. P/N 2600-418
Nickel Chain
Stainless Chain
Nickel plated chain.
P/N 2600-443 (10 ft. #41)
P/N 2600-444 (10 ft. #40)
Stainless steel chain.
P/N 2600-475 (20 ft. #41)
Remote Reset Station Provides an audible tone and visible alarm when the operator is in a hard shutdown condition. Includes a reset button to return the operator to normal operation.
P/N 1404-080
9100-065-D-5-07 51
Page 52
Black
White
1/2 HP
Motor
Red
Blue
Motor Capacitor
Black
Power Switch
Black
White
Lock
115 VAC
INPUT
Black
White
Green
4602-010
Circuit Board
CAUTION - HIGH VOLTAGE
1 2 3 4 5 6 7 8 9 10 11 12 13 14
15
16 17 18
ALARM
RESET
ALARM
Title: Wire Diagram Model 9100 and 9150
1/2 HP - 115 VAC
Date:
DOORKING, INC., INGLEWOOD, CA 90301
5/07 Dwg. No.
4602-115-5 Rev.
A
9100-065-D-5-07
9100-065-D-5-07 53