humiSteam
electrode steam humidifiers
Installation
Operation
User Manual
Read and save these instructions.
Models UE001 to UE065
Single Cylinder Units
CAREL humiSteam
2
Installation, Operating & Maintenance Manual
IMPORTANT
BEFORE INSTALLING OR HANDLING THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW THE
INSTRUCTIONS AND SAFETY STANDARDS DESCRIBED IN THIS MANUAL AND ILLUSTRATED ON THE
LABELS ATTACHED TO THE MACHINE.
This humidifier produces non-pressurized steam by means of electrodes immersed in the water contained in the cylinder-boiler (hereafter called the cylinder). The electrodes pass current through the water, which also provides resistance, heating the water into steam, which is used to humidify environments or industrial processes, using special distributors.
The quality of the water used affects the process of evaporation, so the humidifier may be supplied with untreated water, as long as this is drinkable and not softened or demineralized; the evaporated water is automatically replaced using a fill valve. This humidifier has been designed exclusively to directly humidify rooms or ducts, using a distribution system. The installation, use and maintenance operations must be carried out according to the instructions contained in this manual and on the labels applied internally and externally.
The conditions of the environment and the power supply voltage must comply with the specified values.
All other uses and modifications made to the humidifier that are not authorized by the manufacturer are considered incorrect.
Liability for injury or damage caused by the incorrect use of the humidifier lies exclusively with the user.
Please note that the humidifier contains powered electrical devices and hot surfaces.
All service and/or maintenance operations must be performed by specialist and qualified personnel who are aware of the necessary precautions and are capable of performing the operations correctly.
Disconnect the humidifier from the main power supply before accessing any internal parts.
The humidifier must be installed in accordance with the local standards in force.
The local safety standards in force must be applied in all cases.
The humidifier is made up of metallic and plastic parts. All parts must be disposed of according to the
local standards on waste disposal.
Certification: the quality and safety of CAREL products are assured by CAREL's ISO 9001 certified design and production system, as well as listings from UL, cUL, CE, TUV, ETL and others.
WARNING: Your humidifier requires water to operate. Do NOT mount it above materials or machinery that could be damaged if a leak occurs. Carel assumes no responsibility for consequential or inconsequential damage as a result of any leaks.
Copyright © 2005 by Carel USA, LLC. All rights reserved.
3
CAREL humiSteam
Table of Contents
How The Humisteam Works................................................................................................................................................... 5
1 Installation............................................................................................................................................................................ 6
1.1 Positioning ................................................................................................................................................... 6
1.2.1 Removing the front cover ..................................................................................................................... 7
1.2.2 Fastening to the wall ............................................................................................................................ 7
1.3 Plumbing...................................................................................................................................................... 8
1.3.1 Water supply ........................................................................................................................................ 8
1.3.2 Water drain........................................................................................................................................... 8
1.4 Steam distribution...................................................................................................................................... 11
1.4.1A Duct injection ................................................................................................................................... 11
1.5 Power wiring .............................................................................................................................................. 15
1.6 Connect Control Wiring ............................................................................................................................. 17
1.6.1 Controls Placement ............................................................................................................................ 17
1.7 Control wiring............................................................................................................................................. 17
ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors........................................... 20
HC-101 and HC-201 Wall and Duct Humidistats ........................................................................................ 21
PC-301 Air Proving Switch.......................................................................................................................... 22
2 Start-Up.............................................................................................................................................................................. 23
2.1 Startup Checklist ....................................................................................................................................... 23
2.2 The HumiControl Controller....................................................................................................................... 24
2.3 Start-up Procedure .................................................................................................................................... 24
2.3.1 Starting with a new cylinder ............................................................................................................... 24
3 Operation............................................................................................................................................................................ 25
3.1 Display Information.................................................................................................................................... 25
3.2 Changing The Set Point ............................................................................................................................ 25
3.3 Activating Manual Drain............................................................................................................................. 25
3.4 Accessing/Changing Configuration Parameters........................................................................................ 25
3.5 Notes about special parameters................................................................................................................ 28
STANDARD CONFIGURATION SETTINGS .................................................................................................. 29
3.6 Seasonal Shut Down ................................................................................................................................. 30
3.7 The Remote Control .................................................................................................................................. 30
3.8 Resetting the Hour Counter....................................................................................................................... 31
3.9 Alarms........................................................................................................................................................ 31
3.10 Trouble-Shooting ..................................................................................................................................... 35
3.11 Resetting Factory Defaults ...................................................................................................................... 36
4 Maintenance ....................................................................................................................................................................... 37
4.1 Periodic checks ......................................................................................................................................... 37
4.2 Cylinder maintenance................................................................................................................................ 37
4.2.1 Replacing the cylinder........................................................................................................................ 37
4.2.2 Maintenance of the other plumbing components ............................................................................... 39
4.3 Replacement Parts .................................................................................................................................... 40
4.3.1 Single Phase Humidifiers ................................................................................................................... 40
4.3.2 Three Phase Humidifiers.................................................................................................................... 40
4.3.3 Replacement Steam Cylinders & Parts.............................................................................................. 41
5 Wiring Diagrams ................................................................................................................................................................ 43
6 Technical Specifications .................................................................................................................................................... 46
6.1 Model Numbers ......................................................................................................................................... 47
IMPORTANT: BEFORE beginning installation:
• Check for shipping damage to cartons. Mark the shipping waybill accordingly
• Open cartons and check for any hidden damage. Mark the shipping waybill accordingly.
• Check packing slip to ensure all items have been received. Notify Carel LLC of any shortages or damaged parts. You must notify Carel LLC within 5 working days of any shortages.
4
Installation, Operating & Maintenance Manual
How The Humisteam Works
HumiSteam is an electrode humidifier. It produces steam for humidification by passing electrode current through the water in the steam generator cylinder between metal electrodes. There are no heater elements. Steam output is directly proportional to the conductivity of the water, and the amount of electrode immersed in the water.
On a call for humidity, the HumiSteam controller will open the water fill valve
(1) and allow water to enter the system. A flow restrictor (2) prevents the unit from filling too quickly or with too much pressure. The water flows up the fill tube (3) and into the fill cup (7), where it flows over the conductivity probes (6), which feed the water conductivity back to the controller for analysis. Water then flows over the dam in the fill cup (7), which creates a
1” air gap to prevent backflow of contaminated water into the feed lines, and through the fill tube (4) and into the bottom of the steam cylinder (11).
As the water fills the cylinder, it will reach the electrodes (10) and current will begin to flow. As the water continues to fill the cylinder, the current will increase, and this is monitored by an amperage transformer placed on one of the power wires (9). When the desired current is reached, the fill valve will close (1) and the water will then begin to warm and produce steam. If the water reaches the cylinder full probes (8) prior to reaching the desired current level, the fill valve (1) will be closed to prevent overflow. If the current rises too much as the water fills the cylinder, the drain valve or pump (13) will be activated to drain away some water and reduce the current flow.
Periodically, based on the incoming water conductivity, the unit will drain some water to reduce the mineral concentration. A strainer (12) in the cylinder helps to prevent mineral debris from jamming the drain valve (13).
If there is no water in the cylinder, there will be no current flow and no steam production. The electrodes do not burn out, but they will eventually become completely coated with mineral and the cylinder will then need to be replaced or cleaned.
UE 025 through UE065
No. Description
1 Steam generator cylinder
2 Water drain pump
3 Water fill valve
UE 001 through UE 015
No. Description
1 Steam generator cylinder
2 Water drain valve
4 Fuses
7 On/Off and Manual drain switch
8 Wiring terminal block
9 Water fill valve
7 Relay
8 Fuses
9 Wiring terminal block
11 On/Off and Manual drain switch
5
CAREL
1 Installation humiSteam
1.1 Positioning
The HumiSteam has been designed for wall mounting
(although it can be placed on a stand) and, since it is an atmospheric steam humidifier, should be placed close to the point where the steam will be used, to minimize the steam hose length (and condensate). Certain clearances must be maintained around the unit:
Minimum
Dimension
(inches)
A B C D E F
12 8 8 16 28
With room blower units, other clearances are needed:
VSDU0A
A B C D E F H
Minimum dimension
(inches)
20 72 72 24 20 72 24
VRDXL
36 120 72 48 36 120 48
Unit Dimensions:
Weight
(lbs)
A
Dimensions
(inches)
B
C packaged empty installed
Model - UE
001-008 009-015 025-045* 045**-065
15 15 22 26
11 11 15 18
25 28 35 38
36 44 86 113
30 38 75 97
42 60 134 207
* = UE045 for 460-575/3 Vac
** = UE045 for 208-230/3 Vac
6
Installation, Operating & Maintenance Manual
1.2 Mounting
1.2.1 Removing the front cover
The front cover is secured by a capture screw located underneath the CAREL logo. Twist the CAREL logo to reveal the screw, and use a phillips head screwdriver to remove it. Then simply lift the front cover and pull out to remove it. Return it in reverse order.
1.2.2 Fastening to the wall
Using the screws and anchors supplied, fasten the mounting bracket to the wall.
Be sure that the screws anchor firmly into studs or supports. Note the unit installed weights from the Positioning section.
Once the mounting bracket is secured to the wall, hang the unit on the bracket. Fasten the remaining capture screws through the bottom holes in the unit to secure it to the wall.
Model UE
001-008 009-015 025-045 065
X
Y
Z
Z’ 4.41
7
CAREL humiSteam
1.3 Plumbing
1.3.1 Water supply
The HumiSteam must be supplied with water (not softened) having the following characteristics:
Instant flow rate
Connection
Temperature limits
Pressure limits
Hardness limits
Model UE
001-008 009-015 025-045 65
0.2 gpm 0.3 gpm 1 gpm 1.9 gpm
1/4" O.D. Compression 3/8" O.D. Compression
34 to 104°F
15 to 116 psi
<= 400 ppm CaCO3
Conductivity range 125 to 1250
µS
/cm (micromhos)
The water feed line should be 1/2” copper, PVC or poly tubing run to within 3 feet of the humidifier, then bushed down to 1/4” O.D. or 3/8” O.D. copper or poly to make the final connection to the 1/4” O.D. or 3/8” O.D. compression fitting underneath the humidifier. With poly tubing an insert should be used to support the tubing and prevent leaks. This insert is not provided.
NOTE: Softened water should NOT be used as it is generally corrossive to the electrode plating.
1.3.2 Water drain
The HumiSteam also requires connection to a drain. The drain water characteristics are:
Model UE
001 003 005 008 009 010 015 025 035 045 065
Drain rate per hour 0.7 gph 2.2 gph 3.7 gph 5.9 gph 6.6 gph 7.3 gph 11 gph 18.3 gph 25.7 gph 33 gph 47.7 gph
Instant drain rate 1.3 gpm 6 gpm
Connection 1-1/2" nominal diameter
Typical temperature 212°F
The drain line can be 1-1/2” schedule 40 CPVC, 1-1/2” copper, or 1-1/2” Polypropylene. In all cases, the drain tube is slipped over the drain outlet on the bottom of the humidifier. It is not glued or otherwise attached to the humidifier, so it must be supported by itself.
Drain line must be installed and plumbed to an open drain immediately after the unit.
For proper operation of the unit, the open drain should be installed before the trap (if allowed by local code).
8
Installation, Operating & Maintenance Manual
See the following diagram for a drain line installation diagram
Note: If utilizing the optional drain tempering devices, the drain line needs to be increased to a 2"
minimum nominal size for the UE025 to UE065.
WARNING: Do NOT use PVC piping unless the unit has the optional drain tempering valve installed.
9
CAREL
Water supply and drain connections are made according to the following diagram. humiSteam
Note: Drain line must be installed and plumbed to an open drain immediately after the unit. For proper operation of the unit, the open drain should be installed before the trap (if allowed by local code).
Physical location of the supply and drain connections are located as shown below.
NOTE: Carel can provide a drain tempering system which limits the water drain to no more than 140°F.
10
Installation, Operating & Maintenance Manual
1.4 Steam distribution
1.4.1A Duct injection
NOTE: If the ventilated steam distributor is to be used, then go to section 1.4.1B.
Each unit has either 7/8” (22 mm), 1-1/4” (30 mm) diameter outlet or 1-5/8” (40 mm) diameter outlets. Some units have multiple outlets. The duct distributors and steam hose must be matched in size to the diameter of the steam outlets for the units:
UNIT MODEL NUMBER
No.
Cylinders
Steam outlets
UE001 UE003 UE005 UE008 UE009 UE010 UE015 UE025 UE035 UE045 UE065
1
22mm x 1 30mm x 1 40mm x 1
Duct steam distributors must also be matched to the duct size they will be inserted into:
40mm x 2
Humidifier Steam Outlets, mm 22
Humidifier Steam Outlets, inches 7/8
Quantity Required per Unit
30 40 2x40
1-1/4 1-5/8 2x1-5/8
Ordering
Code
Description
22 mm Duct Distributors:
30 mm Duct Distributors:
40 mm Duct Distributors:
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
11
CAREL humiSteam
Distributor pipes should be mounted per the diagrams shown below, with a minimum of 6” from the center of the distributor pipe to the top of the duct and 3” minimum to the bottom.
To install the distributor pipes:
1. Cut a key shaped hole in the side of the duct to match the steam pipe and condensate return.
2. Apply silicone sealant to the mounting plate and insert the pipe through the hole and secure it with 4 sheet metal screws.
3. Connect the steam and condensate hoses using the hose clamps supplied.
(Note: end support bracked supplied only with 36” and longer distributors.)
IMPORTANT: Allow 2 feet of straight duct downstream of the distributor pipes when the air temperature will be >55oF. Allow 3 feet of straight duct if the air temperature will be <50oF. Always allow 2 feet upstream. Turbulent air flow may require longer lengths.
12
Installation, Operating & Maintenance Manual
1.4.1B Room distribution blower units
Refer to the manual supplied with the Room Distribution Units for specifics on the blower units themselves.
Clearances required are shown below.
VSDU0A
A B C D E F H
20 72 72 24 20 72 24
Minimum dimension
(inches)
VRDXL
36 120 72 48 36 120 48
Room Blower
Unit Model
Rated Power
Watts
Air Volume
CFM
Noise Level dBA
Model
UE001 UE003 UE005 UE008 UE009 UE010 UE015 UE025 UE035 UE045 UE065
VSDU0A VRDXL
30 35
100 380
50 40
Operating Temp/Humidity
(°F / %RH)
14 to 104°F
/ 10 to 60%
14 to 140°F
/ 10 to 80%
Cold rooms can be humidified using a Room Distribution Unit, making sure that this operates within its operating limits. The room must have operating temperatures of between -10°C and +20°C, with a percentage of relative humidity of no greater than 80% RH. If these limits are not possible, the steam can be distributed in the cold room using a distributor pipe in duct work. In any case, the steam must not come into direct contact with air discharge from the refrigeration unit in the cold room, to avoid possible condensation.
13
CAREL
1.4.2 Steam Hoses
humiSteam
NINETY PERCENT (90%) OF ALL OPERATION PROBLEMS ARE CREATED BY IMPROPER STEAM
PIPING FROM THE HUMIDIFIER UNIT TO THE DUCT DISTRIBUTOR PIPES. To avoid these problems, remember one simple fact when running the steam hose: steam naturally flows up hill, and condensate naturally flows down hill. Run the steam hose or piping to avoid any kinks, sharp elbows, or low spots that could collect or restrict the flow of steam to the distributor pipe, or the flow of condensate back to the humidifier.
Support the hose adequately to avoid sags.
The following diagrams are to provide you with some guidelines. If you have a situation you are unsure of,
please contact the factory for instructions.
IMPORTANT: Maximum length of rubber steam hose is 20 feet. Insulated copper tubing may be up to 40 feet. In all cases, minimize sharp bends and elbows – use 2-45° elbows instead of 90°s.
Hose size for UE 001, 003 = 22 mm.
Hose size for UE 005, 008, 009 and 015 = 30 mm.
Hose size for UE 025, 035, 045, 065 = 40 mm.
UE045 208-230V & UE065 need 2 hoses and distributors.
14
Installation, Operating & Maintenance Manual
1.5 Power wiring
Single Phase Terminals Three Phase Terminals
Check that the power supply voltage to be connected matches the value indicated on the rating plate inside the electrical panel. Insert the power and ground connection cables into the electrical panel compartment using the strain reliefs supplied, and connect to the terminals.
An external fused disconnect must be installed.
All wiring must be in accordance with local, state and national electric codes.
NOTE: to avoid unwanted interference, the power cables should be kept separate from any control wiring.
Per the table on the following page, make sure that the unit has the proper number of turns through the TAM (Torroid Amperage Monitor), which is on the control board in models UE001 through UE015, and separate in models UE025 through UE065. Also make sure that the TA
Rate DIP switches on the control board are set correctly per the table.
In models UE001 - UE015 make sure that the TAM on the circuit board has the proper number of power wire turns through it, and that the TA Rate DIP switches on the control board are set per the table on the following page.
In models UE025 - UE065 the TAM is independent and the jumper must then be on the right terminals per the table on the following page.
15
CAREL humiSteam
Voltage
Code
Voltage
Phase
Nominal
Current
(Amps)
Power
(kW)
Output
(kg/hr)
Output
(lbs/hr)
Turns
Through TA Rate
TAM
Model
UE001
UE003
UE005
UE008
UE009
UE010
UE015
UE025
UE035
U
D
K
K
N
K
M
N
208 - 1~N
230 - 1~N
U 208 - 1~N 10.8
D 230 - 1~N 9.8
W 208 - 3~ 6.2
230 - 3~
M 460 - 3~ 2.8
U 208 - 1~N 18
D 230 - 1~N 16.3
W 208 - 3~ 10.4
230 - 3~ 9.4
M 460 - 3~ 4.7
575 - 3~ 3.8
W 208 - 3~ 16.7
230 - 3~
460 - 3~
575 - 3~
5.4
4.9
5.6
15.1
7.5
6
U 208 - 1~N 31.4
D 230 - 1~N 29.3
W 208 - 3~ 20.8
K 230 - 3~ 18.8
M 460 - 3~ 9.4
N 575 - 3~ 7.5
W 208 - 3~ 31.2
K 230 - 3~ 28.2
M 460 - 3~ 14.1
N 575 - 3~ 11.3
W 208 - 3~ 52
K 230 - 3~ 47.1
M 460 - 3~ 23.5
N 575 - 3~ 18.8
W 208 - 3~ 72.9
K 230 - 3~ 65.9
M 460 - 3~ 32.9
N 575 - 3~ 26.4
W 208 - 3~ 93.68
1.12 1.5 3.3
2.25 3 6.6
6.52 9 20
1 20
2 20
2
1
1
1
60
20
20
20
3.75 5 11
2 20
1 40
1
1
40
20
1
2
20
20
2 20
1 40
6 8
2
17.6
1
60
20
1 20
1 60
1 60
1 40
7.5 10 22
11.25 15 33
18.75 25 55
26.25 35 77
UE045
K 230 - 3~ 84.72
M 460 - 3~ 42.4
N 575 - 3~ 33.9
33.75 45 99
M 460 - 3~ 61.19
UE065 48.75 65 143
N 575 - 3~ 48.95
NOTE: Tolerance allowed on main voltage = -15%, +10%
1
1
40
20
1 20
1 60
1
1
60
20
1 20
1 300
1
1
300
300
1 300
1 500
1
1
500
500
1 300
1 500
1
1
500
500
1 500
1 300
1 300
16
Installation, Operating & Maintenance Manual
1.6 Connect Control Wiring
A typical humidifier control system includes a wall or return duct sensor or controller, a high limit duct humidistat and an air-proving switch. Placement of these devices is critical to proper operation of the overall system.
1.6.1 Controls Placement
(See following diagram)
The return air RH sensor must always be located BEFORE any outside air intake, in order to insure accurate sensing of the air from the space. Alternatively, a room RH sensor or humidistat can be used. Room sensors should be located on an inside wall or post and should not be hit by any discharge air streams from ducts. In a
100% outside air system, the RH sensor may be placed in the supply duct, at least 10 feet down stream of the distributor pipe to act as both hi-limit and control.
The airflow switch must be positioned to accurately open on a loss of airflow, to prevent the humidifier from running when there is no air to absorb the moisture.
The hi-limit humidistat must be positioned far enough down stream of the steam distributor pipe(s) to prevent it from getting wet, but still allow it to accurately prevent over humidification of the duct that could result in condensation.
1.7 Control wiring
The HumiSteam control system allows up to two sensors to be connected, as well as various safety devices, remote on/off, alarm and serial communications.
Generally, the control sensor or humidistat (HT) is located in the room or return air duct. In the case where the HumiSteam uses a direct discharge blower unit, this is the only control needed. In ducts or air handlers, a high limit humidistat or sensor is usually added to act as a safety (CR), as well as an air flow proving device. The remote terminal HumiVisor (MT) may be added.
17
CAREL humiSteam
Remote Supervisor / Serial Communications:
This is a standard RS485 serial connection. It is recommended to keep wiring under 3,200 feet. Request Carel’s communications documentation for additional information on this option.
Control wiring is made directly to the control board terminals:
1. terminal block G (dehumidification contact);
2. terminal block H (alarm contact);
3. terminal block K (on/off, manual drain switch);
4. terminal block I (control signals);
5. terminal block J (to remote terminal or supervisory system);
6. dip-switch for selecting TA RATE.
For On/Off Operation:
Connect any simple humidistat, high-limits, air flow switch, and remote contacts in series from terminals 7I to 8I. DO NOT apply any voltage
to 7I & 8I.
Circuits must be completed from 4I to 5I by a jumper and from 7I to 8I for the unit to operate.
Use jumpers if devices are not connected.
Parameter A0 must be set to 0.
18
Installation, Operating & Maintenance Manual
For Modulating Operation with External Controller:
Connect any external controller (0-1 Vdc, 0-10 Vdc
Parameter A0 must be set to 1.
Parameter A2 must be set per the OUT signal from the regulator:
• voltage: 0 to 1 Vdc; 0 to 10 Vdc; 2 to 10 Vdc;
• current: 0 to 20 mA; 4 to 20 mA.
NOTE: Safeties are high-limit humidistat, air flow switch, and/or external enable. DO NOT apply any voltage to
7I & 8I.
For Stand-Alone Modulating Operation:
Connect a high limit sensor and control sensor per the diagram at right. DO NOT apply any voltage to 7I
& 8I.
Parameter A0 must be set to 2 if no high limit sensor, 3 if a high limit sensor is used.
Parameter A2 must be set per the OUT signal from the sensor:
• voltage: 0 to 1 Vdc; 0 to 10 Vdc; 2 to 10
Vdc;
• current: 0 to 20 mA; 4 to 20 mA.
Terminal 4I (+(G)) = 12 Vdc
Terminals 2I & 6I (M) = common
For Steam Baths (Turkish Baths):
In this case a temperature sensor is used to control the humidifier. Connect sensors per the diagrams below.
Parameter A0 must be set to 4. Parameter A2 must be set to 0.
Alarm Output:
The H terminals allows connection to an on-board SPDT alarm relay that provides No and NC contacts for remote indication of alarms.
Dehumidify Output:
Dehumidify contacts are also provided which can be used to control a dehumidifier from the humidifier control system (stand-alone modulating mode only). The contact is rated for 250 Vac, 8 Amp resistive and 2 Amp inductive loads.
19
CAREL humiSteam
ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors
Humidity (0-1 VDC or 4-20 mADC)
Temperature: NTC thermistor, 10 Kohm at 25°C (77°F)
(ASWC/ASDC only)
Accuracy: +- 0.25°C from 0 to 50°C (32 to 122°F)
ASWH100000 Wall Humidity sensor (replaces SHWOOP)
Humidity: Thin film capacitor
ASDH100000 Duct Humidity sensor (replaces SSDOMH00/1)
Linear 0-1 Vdc or 4-20 mAdc from 10 to 90%RH
Accuracy: +- 3%RH from 20 to 90%RH
Temperature & Humidity (NTC temp, 0-1 VDC or 4-20 mADC humidity) calibrated at 55%RH and 25°C (77°F)
ASWC111000 Wall Temp/hum sensor (replaces SWNTCTH0/1 & STHONTC0/1) +- 5%RH above 90%RH and below 20%RH
ASWC110000 Wall Temp/hum sensor (replaces STHOAP)
Response time: 60 seconds
Temperature & Humidity (0-1 VDC or 4-20 Madc temp & humidity)
Power: 12 to 24 Vac/dc or +12 to –12 Vdc
Housing: Wall: ABS with glassfiber fill
ASDC111000 Duct temp/hum sensor (replaces SDNTCTH0/1) Certifications: Calibrated to NIST traceable humidity/temperature standard, CE Approved
ASDC110000 Duct temp/hum sensor (replaces SSDOMHT0/1)
20
Installation, Operating & Maintenance Manual
HC-101 and HC-201 Wall and Duct Humidistats
Mounting the HC-101 room humidistat: Mount the HC-101 humidistat to an inside wall or post in the area to be humidified. Position it so that no drafts from registers or outlets are blowing on it.
Be sure that it is not placed over a device that could generate heat or vapor ie: stove, machinery, cleaning vat. The unit has three wire leads, Orange, Brown and Red. Use the Orange and Brown leads for control operation. Use the
Orange and Red leads for hi-limit operation.
Mounting the HC-201 duct humidistat: Cut a hole in the side of the duct and mount the HC-201 humidistat to the duct, using the screws provided, at least 6 feet down stream of any live steam or mist. The unit has three wire leads, Orange, Brown and Red. Use the
Orange and Brown leads for hi-limit operation.
Wiring Diagram
Brown (N.O.)
Red (N.C.)
Brown makes on drop in humidity
TABLE 1. SPECIFICATIONS
Drop in R.H.
Orange
Common
Part
No.
Type Scale Diff.
Range
%RH
%RH
HC-101 Wall 10 to 90 5
HC-201 Duct 15 to 95 5
Operating
Limits
°F (°C)
40 to 125
(4 to 2)
40 to 125
(4 to 2)
Shipping
& Storage
°F (°C)
-40 to 140
(-40 to 60)
-40 to 140
(-40 to 60)
Connection Cover Dimensions
In. (mm)
6" (150 mm) color coded leads
Coded screw terminals
Beige plastic
Metal
4-3/8 x 2-7/8 x 1-5/8
(111 x 73 x 41)
4-3/4 x 6-1/2 x 2-1/4
(121 x 165 x 57)
TABLE 2. MAXIMUM ELECTRICAL RATINGS
Part No.
HC-101
HC-201
AC Volt
50/60 Hz Amps VA
24 - - 8 60
120 7.2 43.2 8 345
240 3.6 21.6 8 345
21
CAREL
PC-301 Air Proving Switch
Mounting the PC-301 air flow switch:
Mount the airflow switch in the supply or return duct using the screws supplied. Mount the device so that the diaphragm is in a vertical position as shown at right. humiSteam
If the airflow switch is to be mounted on the return duct
(vacuum), then mount it in a vertical position by the small plate. Drill a 7/16" hole in the side of the duct and connect the supplied tubing to the low pressure tap on the airflow switch and then run it through the drilled hole in the duct. Put no more than 2" of tubing into the duct. Caulk around the tubing where it enters the duct. The high pressure tap is left open to atmosphere.
If the airflow switch is to be mounted to the supply duct
(pressure), then simply drill a 7/16 hole in the side of the duct, apply caulking to the large plate, and mount the device with the large plate to the duct and the high pressure tap/tubing mated the hole. The low pressure tap is left open to atmosphere.
MOUNTING DIAGRAMS
TABLE 1. MAXIMUM ELECTRICAL SWITCH RATINGS
Amps
24V -
120V 6.25
Amps
-
37.5
Pilot Duty
(VA)
Non-
Inductive
Amps
60 10
300 10
240V 3.1
277V 2.7
WIRING DIAGRAM
18.6
16.2
300
300
10
10
N.C.
Common
N.O. makes on increase in pressure.
N.O.
Increase
Pressure
22
Installation, Operating & Maintenance Manual
2 Start-Up
IMPORTANT WARNINGS:
1. Before starting, check that the humidifier is in perfect condition, that there are no water leaks and that the electrical parts are dry;
2. Do not connect power if the humidifier is damaged or even partially wet!
When installation is completed, flush the supply pipe for around 30 minutes by piping water directly
into the drain, without sending it into the humidifier; this will eliminate any scale or residues that may cause foam when boiling.
NOTE: for humidifiers with control H only, the same function can be performed automatically after staring the appliance (see par. 6.2.1).
2.1 Startup Checklist
Before starting the humidifier, the following should be checked:
Water is connected, the line has been flushed, and external valves are open.
Drain is connected, run to an open drain, and has a trap under the unit.
Electricity is connected in accordance with instructions, local codes and data labels in the unit.
The power fuses are installed and intact.
All control wiring is done and tested.
Airflow switch is wired to open on air flow loss.
Hi-limit humidistat is wired to open on humidity rise above set point.
Unit wires have been checked to make sure they and all connectors are tight from shipping.
The steam hose(s) are run correctly with no sags or kinks and sloped properly according to the manual.
Condensate hoses are run correctly with no sags or kinks and sloped properly according to the manual.
NOTE: If you ordered a factory startup, this checklist will be required. Failure to complete this checklist may result in additional charges.
23
CAREL
2.2 The HumiControl Controller
1: PRG - Access to most frequently used parameters.
Also resets alarm relay.
2: SEL - Displays unit of measure. Press for 2 seconds to access set point. Press with PRG for 5 seconds to enter parameters.
3: Ç - Displays control sensor value. In programming mode increases value or moves to previous parameter.
4: È - Displays high limit sensor value. In programming mode decreases value or moves to following parameter.
5: 2-1/2 digit display for values and parameters.
6: LED to indicate decimal point.
7: LED to indicate value must be multiplied by
1000.
8: LED to indicate dehumidify mode. humiSteam
9: LED to indicate alarm.
10: LED to indicate humidifier is producing steam.
Flashing indicates lower than required production.
11: LED to indicate when unit is filling.
12: LED to indicate when unit is draining.
2.3 Start-up Procedure
After closing the external fused disconnect to put power to the humidifier, press the top (I) part of the I/O switch on the side of the unit
Initially, all LEDs light - this lasts about 1-2 seconds.
Then the initialization phase begins with 3 dashes. During this phase diagnostics are conducted. This phase lasts about 4 seconds.
After running the diagnostics, the unit will start operation and display either the % of steam production (On/off and Modulating modes), the %RH (Stand-
Alone Modulating mode), or two dashes will light, indicating the humidifier is disabled or in alarm. The alarm code will flash.
2.3.1 Starting with a new cylinder
When starting with a new cylinder, you should activate the cylinder cleaning function by pressing the SEL and
È buttons simultaneously for 2 seconds after the initialization phase. This forces the unit to open both the drain and fill valves for 10 minutes to flush the lines, then fills and drains the cylinder 3 times to wash out any mold release or dirt. Once started, this function can be stopped by pressing the SEL and È buttons simultaneously for 2 seconds again.
When starting the unit with a new or empty cylinder, it may take a significant amount of time (hours) for the unit to build up enough mineral concentration to reach rated capacity. This time can be shortened by the addition of
Alka-Seltzer or salt (teaspoon) through the steam outlet on top of the cylinder.
24
Installation, Operating & Maintenance Manual
3 Operation
3.1 Display Information
Pressing the SEL button displays the unit of measure currently in use for the main display
Holding the Ç button displays the value of the control sensor preceded by the unit of measure.
Holding the È button displays the value of the high-limit sensor preceded by the unit of measure.
3.2 Changing The Set Point
Press the SEL button for 2 seconds until “St” appears. On releasing the button, the unit of measure is displayed followed by the current set point value. To change the set point, press the Ç or È button to increase or decrease the value. Press SEL or PRG to lock in the new set point. Waiting 5 seconds without pressing
SEL or PRG will revert to the old value.
3.3 Activating Manual Drain
In addition to the manual drain switch on the side of the humidifier, pressing the Ç and È buttons simultaneously for 2 seconds will force a manual drain which will completely empty the cylinder without having to hold the manual drain switch. This procedure can be stopped at any time by pressing the Ç and È buttons simultaneously for 2 seconds again.
3.4 Accessing/Changing Configuration Parameters
The numerical, configuration and control parameters are grouped into three levels:
LEVEL 1 - set point parameters: the value of the humidifier's main set point “St”, accessible directly via the keypad for both reading and modification. See “Changing The Set Point”.
LEVEL 2 - control parameters and measurements: the physical values measured and the operating parameters involving the control of the humidification process; these too can be accessed directly via the keypad for reading and modification.
LEVEL 3 - configuration parameters: consisting of the data needed to customize the controller’s operation. These parameters can be accessed only by password.
To display the Level 2 Control Parameters:
• Press and hold the PRG button for 5 seconds until P0 is displayed;
Ç and È buttons to scroll through the Px and dx parameters;
• Press the SEL button to display the value of any parameter (the unit of measure will display first for 1 second).
Code Range Default Unit Description
P0 20 to 100
100
100
%
Maximum output for H controllers
Maximum output for P controllers
P1 2.0 to 19.9 5 %RH, °C Humidification proportional band
P2 (1)
P3 to 100 100 %RH
P3 to 60 60 °C
High humidity or high temperature alarm set point
P3 (1) 0 to P2 0 %RH, °C
Low humidity/temp. alarm set point
P4 0 to 100 1 min Alarm delay (0 = 30 seconds) accessible only in stand-alone mode
(A0=2, 3 or 4)
P5 2 to 100 10 %RH Dehumidification dead zone
P6 1.0 to 19.9 5 %RH Dehumidification differential accessible only with the dehumidification function enabled
(b1 odd number) in stand-alone mode
(A0 = 2 or 3)
25
CAREL
Code Range Default Unit humiSteam
Description
P7 (1) St to 100 100 %RH Hi-limit set point
P8 2.0 to 19.9 5 %RH Hi-limit differential
P9 0 to 100 100 %RH Hi-limit alarm set point
Code Range Default Unit d1 (2) 0.0 to 199 read only
Accessible only with hi-limit control
(A0=3)
%RH, °C, Signal from external controller
% or sensor
Description
Not accessible in on/off mode (A0=0) d2 0.0 to 199 %RH
Signal from hi-limit or temperature sensor kg/h Steam output (actual)
Accessible only with hi-limit control
(A0=3) d3 0.0 to 199 d4
0.0 to
19999 d5 0 to 1555 d6 0.0 to 199 h Run time hours
µS/cm Conductivity of the feed water
A Current (Amperage) d9 0.0 to 199 kg/h Rated steam output
(1): when accessing parameter A0, parameters P2, P3, P7 and St are automatically reset to the corresponding default value.
(2): in proportional operation (A0=1), d1 displays the % of the control signal
To display the Level 3 Configuration Parameters:
• Press and hold the PRG and SEL buttons simultaneously for 5 seconds until 00 is displayed; the
• Press the SEL button and A0 should display;
Ç and È buttons to scroll through the configuration parameters;
• Press the SEL button to display the value of any parameter (the unit of measure will display first for 1 second);
• Press Ç and È buttons to change the value;
• Press SEL when the change is complete and then continue scrolling through the parameters;
• To leave the programming mode, press PRG at any time. NOTE: after more than 5 seconds without a button press, the display will begin to blink. 60 seconds after a button press, the controller will erase all changes and return to operating mode with the previous parameters.
Parameters for configuring standard operation:
Code Range Default Unit Description
A0 (1) 0 to 4 2 Operating mode
0=ON/OFF control
1=modulating
2=humidity control
3=humidity control with hi-limit control
A1 0, 1 0 Unit of measure
4=steam baths
0=°C, kg/h
1=°F, lbs/hr
A2 0 to 4 0
Type of room sensor; not
0=0 to 1V; 1=0 to 10V; 2=2 to 10V; 3=0 to 20mA; accessible in ON/OFF mode (A0=0)
4=4 to 20mA
A3 (2) 0 to A4 0 %RH, ºC Room sensor minimum
A4 (2) A3 to 255 100 %RH, ºC Room sensor maximum
Accessible only in control mode (A0=2, 3 or 4)
Used for scaling sensors
A5 -10.0 to 10.0 0 %RH, ºC Room sensor offset
26
Installation, Operating & Maintenance Manual
A6 0 to 4 0
Type of outlet sensor; accessible only in humidity control with outlet limiting (A0=3)
0=0-1V; 1=0-10V; 2=2-10V; 3=0-20mA;
4=4-20mA
A7 0 to A8 0 %RH Hi-limit sensor minimum
A8 A7 to 100 100 %RH Hi-limit sensor maximum
Accessible only in humidity control with outlet limiting, (A0=3)
A9 -10.0 to 10.0 0 %RH Hi-limit sensor offset
(1): when accessing parameter A0, parameters P2, P3, P7 and St are automatically reset to the corresponding default value.
(2): see WARNING to the side of Fig. 7.1.
Parameters for configuring the operation of accessory devices:
Description
Special functions
To enable more than one, sum the 0= no function b1 0 to 127 0 corresponding values and assign 1= dehumidifier management active them to b1; e.g.: b1=1+2+8=11 dehumidifier management active +
2= drain under power
4= disable draining on set point reduction drain under power + disable draining 8= disable draining for inactivity for inactivity of at least 7 consecutive 16= disable cylinder being depleted days (the other functions are deactivated) and cylinder depleted warnings
32= reverse the operation of the alarm relay
64= enable periodic draining s Shut-down delay time b2 0 to 120 0 b3 -10.0 to 10.0 0 b4
0 to 199
0k2, ….2k0
% Current measurement calibration
0 µS/cm value as the conductivity to control drain cycles. b5
0 to 199
0k2, ….2k0
1k5 µS/cm Conductivity pre-alarm set point b6
0 to 199
0k2, …, 2k0 b7 0 to 100
2k0 µS/cm Conductivity alarm set point b8 b9
50 to 200
50 to 200 bb 0* to 4000
50
100
100
1500
% Foam detection set point (0=no foam detect, 1=max sens., 100=min sens.)
%
Internal conductivity reached by the cylinder in stable conditions against rated value
% Adjust the duration of the drain for dilution h
Cylinder maintenance limit time (in hours)
0*= disable life alarm “Cy” and maintenance alarm “Mn” bE 1 to 120 24 h
100 hour step if bb>199 hours, hour step if bb<199 hours
Time limit between two periodic drain cycles
Accessible only if periodic draining is enabled (64 in "b1") bF 1 to 199 3 days Days to wait to drain due to inactivity
Not accessible if draining due to inactivity is disabled, (8 in "b1")
27
CAREL
Parameters for setting the serial connections and remote control:
Code Range Unit Description humiSteam
C0 1 to 6 1 Value normally displayed
1= room sensor measurement
2= outlet sensor measurement
3= steam output
4= hour counter
5= conductivity
6= current
C1 0 to 4 4
Enable keypad and remote control - keypad: remote control:
0= read of all param., (modify C1 only) read and modify param. P, d and St
1= read and modifiy all parameters read and modify param. P, d and St
2= read of all param., (modify C1 only)
3= read and modify all parameters
4= read and modify all parameters read parameters P, d and St read parameters P, d and St read and modify all parameters
C2 0 to 99 0 Remote control enabling code (see paragraph 8.2)
C3 0 to 199 1 Serial address
C4 0 to 3 3 Supervisor: baud-rate 0=1200, 1=2400, 2=4800, 3=9600
C5 0 to 11 0
Supervisor: frame
0=8,N.2
1=8,N,1
2=8,E.2
3=8,E,1
4=8,O.2
5=8,O,1
C6 0 to 199 0 Ms
C7 0 to 3 0
(character bits, parity, stop bits)
6=7,N.2
7=7,N,1
8=7,E.2
9=7,E,1
10=7,O,2
11=7,O,1 serial reply send delay
Graphic terminal configuration in cases 1,2,3 the OFF command is forced on start-up
0=terminal
1=terminal with ON/OFF control
2=term. with ON/OFF and room sensor
3=term. with ON/OFF and hi-limit sensor
3.5 Notes about special parameters
b1, setting 2: Drain under power
If parameter b1 includes setting 2, the humidifier will continue to produce steam during drain cycles. If this setting is turned off, the humidifier will open the power contactor during drain cycles.
b1, setting 4: Draining due to a significant reduction in the demand
If parameter b1 includes setting 4, then the humidifier will not drain if the demand for humidification decreases.
This helps to conserve conductivity and is useful in low conductivity waters. If b1, setting 4 is off, then the humidifier will drain to reduce the output if the demand is reduced by 33%.
b1, setting 8: Automatic draining of the cylinder after period of non-use
If parameter b1 includes setting 8, parameter “bF” may be used to cause the humidifier to empty the steam cylinder if there has been no demand for humidification for an extended period of time. This helps prevent premature corrosion of the electrodes and/or contamination of the water in the cylinder. The default setting is for 3 days. The unit will display “idr” when this drain function occurs.
b1, setting 64: Complete periodic draining
If parameter b1 includes setting 64, then parameter “bE” can be used to set the hours between total drains of the cylinder. This is useful if the water contains impurities that can cause erratic behavior.
28
Parameter
P2
P3
P4
P5
P6
P7
P8
P9
ST d4 d5 d9
P0
P1
N/A - Not Accessible
∗
- Read Only bE bF
C0
C1
C2
C3
C4 b4 b5 b6 b7 b8 b9 bb
C5
C6
C7 d1 d2 d3
A6
A7
A8
A9 b1 b2 b3
A0
A1
A2
A3
A4
A5
Installation, Operating & Maintenance Manual
STANDARD CONFIGURATION SETTINGS
HumiSteam Parameters
H Controller
DDC
0-10 vdc
DDC
4-20ma ON / OFF
STAND
STAND ALONE
WITH HIGH LIMIT
ALONE
1 1 0 2 3
1 1 1 1 1
N/A N/A N/A 0 0
N/A N/A N/A 100 100
N/A N/A N/A 0 0
N/A N/A N/A N/A 0
N/A N/A N/A N/A 0
N/A N/A N/A N/A 100
N/A N/A N/A N/A 0
2 2 2 2 2
0 0 0 0 0
0.0 0.0 0.0 0.0 0.0
0 0 0 0 0
1.5 1.5 1.5 1.5 1.5
2.0 2.0 2.0 2.0 2.0
75 75 75 75 75
100 100 100 100 100
100 100 100 100 100
0 0 0 0 0
N/A N/A N/A N/A N/A
3 3 3 3 3
1 1 1 1 1
4 4 4 4 4
0 0 0 0 0
1 1 1 1 1
3 3 3 3 3
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
∗
100 100 100 100 100
N/A N/A N/A 5 5
N/A N/A N/A 100 100
N/A N/A N/A 0 0
N/A N/A N/A 1 1
N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A
N/A N/A N/A N/A 100
N/A N/A N/A N/A 5
N/A N/A N/A N/A 100
N/A N/A N/A 50 50
29
CAREL humiSteam
3.6 Seasonal Shut Down
During seasonal shut-down or alternatively shut-down for maintenance of the electrical parts and/or the plumbing, the humidifier should be placed out-of-service.
NOTE: the water cylinder should be emptied before shutting down the humidifier, to prevent corrosion of the electrodes.
Follow these instructions:
• Press and hold the manual drain switch until the steam cylinder is empty, or use the Manual Drain procedure listed under “Activating Manual Drain”;
• Turn off the On/Off (I/O) rocker switch on the side of the humidifier, and disconnect power from the humidifier;
• Shut off the water to the humidifier.
In the event of malfunction of the drain valve, the cylinder can be emptied manually by lifting it out of the drain manifold and pouring the water into the bottom drain pan. For UE025 and larger humidifiers, use the manual drain device on the manifold, pulling the manual
drain tab until it releases (see sketch at right).
3.7 The Remote Control
A hand-held infra-red remote control is available for the HumiSteam. This device permits programming the humidifier(s) from across the room and also makes available buttons with specific functions.
NOTE: To use the remote control, parameter C2 must be set on each humidifier to give it an access code so that the remote control can address it. If all humidifiers in range of the remote control have the same access code, then they will respond simultaneously to commands from the remote control. Setting C2 to
0 on the humidifier will allow the remote control to be used without the need of a code.
To use the remote control, aim it at the humidifier and press ENABLE. All the humidifiers in range will display their activation codes. If a humidifier has its C2 parameter set to 0, it will skip this step and display the first parameter.
To program a humidifier, enter its access code into the remote control. If successful, the humidifier will display the first parameter.
To program main parameters, simply press the + or - button on the remote control of the parameter you want to modify and the humidifier will display that parameter code. Press the SEL button on the remote control and the value will be displayed. Modify the value by using the Ç and È buttons on the remote control. Then press the next parameter button and so on. Values are saved when you exit the programming phase.
To program other parameters, press any + or - button on a parameter, then use the SEL and Ç and È buttons on the remote control in the same way as the buttons on the front of the humidifier controller.
To exit the programming phase and save the modifications made to the parameters, press the PRG button.
To exit without saving the modifications, press the ESC button.
To exit the programming phase without confirming the modifications made:
• do not press any button for 60 seconds, if the parameter code is displayed;
• do not press any button for 120 seconds, if the value of the parameter is displayed.
30
Installation, Operating & Maintenance Manual
3.8 Resetting the Hour Counter
To reset the hour counter (parameter d4), proceed as follows:
• press the PRG button for 5 seconds, until the code P0 is displayed, indicating the first modifiable parameter; using the Ç and È buttons, scroll the parameters until d4 is displayed;
• press the SEL button to display the value of the hour counter (preceded for 1 second by the unit of measure);
• press the Ç and È buttons together for 5 seconds until the value is set to zero, preceded by a brief flash.
3.9 Alarms
In the event of an alarm, the alarm LED (9) will flash, the alarm relay will close, and the alarm code will flash in the display. Multiple alarms will flash in sequence, alternating with the main display. Pressing the PRG button will reset the alarms, although still active alarms will continue to display.
Controller Action
Humivisor Causes Solution
Reset display
Alarm relay
Reset relay
H H
EH
EL
EC
EP
E102
E103
E105
E113
Over-current at the electrodes; probable electrode malfunction or water conductivity temporarily too high
(especially when starting after a short stop)
1. Check the operation of the drain valve
2. Check for fill valve leakage
3. Drain part of the water and re-start
Power not available; no steam production when on
1. With the machine off and disconnected from the main power, check the internal electrical connections
1. Check limit set for b6
2. Turn the machine off and clean the water conductivity probes
3. If the problem persists, change the source of supply water or install a suitable
High supply water conductivity treatment system
(demineralization, even partial).
Note: the problem will not be resolved by softening the supply water.
1. Cylinder completely spent
Excessive reduction in or water with excessive foam. output Perform maintenance on the cylinder.
Shutdown
Shutdown
Shutdown
Shutdown
N/A Active
N/A Active
N/A Active
N/A
N/A
N/A
Manual Active Manual
31
CAREL humiSteam
Controller Action
Humivisor Causes Solution
Reset display
Alarm relay
Reset relay
H H
EF
EA
E114
E115
Lack of water
1. Check that the fill pipe from the main to the humidifier and the internal pipe are not blocked or bent and that there is sufficient pressure (0.1-0.8 mpa, 1-8 bar)
2. Check the operation of the fill valve
3. Check that the steam outlet is not working against excessive back-pressure, preventing the flow of water into the cylinder by gravity
4. Check that the steam outlet pipe is not is kinked and that there are no sags.
The formation of foam is generally due to the presence of surfactants in the water
(lubricants, solvents, detergents, water treatment agents, softeners) or an
Excessive foam in the cylinder during boiling excessive concentration of dissolved salts:
1. Drain the water supply lines
2. Clean the cylinder
3. Check for the presence of softeners (in this case, use another type of water or reduce the softening)
Shutdown
Signal only
Automatic when
Active water
Automatic when water returns returns
Manual Active Manual
Ed
Ec
E116
E131
Drain malfunction
High water conductivity pre-alarm
Check the drain circuits and the correct operation of the drain valve
Check the conductivity of the supply water if necessary, install a suitable treatment system
Note: the problem will not be resolved by softening the supply water.
Shutdown
Signal only
Manual Active Manual
Auto
Not active
-
E
-
E121
High humidity in the room (high temp.for T control)
Check the operation of the probe and the limit set for parameter P2
Signal only
Manual Active Auto
E
-
E122
Low humidity in the room (low temp.for T control)
Check the operation of the probe and the limit set for parameter P3
E
=
E124 High hi-limit humidity
Check the operation of the outlet probe
Signal only
Manual Active Auto
Signal only
Manual Active Auto
32
Installation, Operating & Maintenance Manual
Controller Action
Humivisor Causes Solution
Reset display
Alarm relay
Reset relay
H H
E0
EI
E2
E3
E4
E101
E112
E130
E120
E123
1. Reset the default parameters
Internal memory (see Chap. 7.5) error 2. If the problem persists, contact the CARE service center
Shutdown
Reprog.
By Carel
Active
Reprog.
By
Carel
1. With the machine off check that there are no defective electrical connections or faults, then
Error in the user reprogram the parameters parameters 2. Reset the default parameters
(see Chap. 7.5)
3. If the problem persists, contact the CARE service center
With the machine off check that there are no defective electrical Hour counter error connections or faults, then reset the hour counter (see par. 7.6)
Room sensor or control signal not connected
Check the connection of the probe, parameter A2 for the room probe and the setting of parameter A0
(see page 23)
Check the connection of the probe,
Hi-limit sensor not connected parameter A6 for the outlet probe and the setting of parameter A0
(see chap. 7)
Shutdown
Hour counter
Shutdown
Signal only
Reprog.
Params.
Active
Reprog.
Params.
Reset manual
Not active
Manual Active
Manual Active
N/A
Auto
Auto
CP
E132
Cylinder being depleted signal
Perform maintenance and/or replace the cylinder
Signal only
Manual
Not active
Auto
CL
EU
PC
E133
E134
-
Cylinder depleted signal cylinder
Perform maintenance and/or replace the only
With the machine off:
Cylinder full with 1. Check for any leaks from the fill machine off signal valve or the condensate return pipe
2. Check that the level sensors are clean total shut-down
Cleaning cylinder started signal
You have activated the automatic cylinder flushing sequence
Signal only
Not available
Not active
N/A
Shutdown
Manual Active Manual
- - - -
Cy
Nn
E135
E136
Timeout signal
(see parameter
"bb") for maintenance exceeded
Perform maintenance and/or replace the cylinder
Reached final limit (1.5xbb) of cylinder operating life
Replace the cylinder
Signal only
Shutdown
Manual reset hour counter
Manual reset hour counter
Active
Active
After the manual reset hour counter
After the manual reset hour counter
33
CAREL humiSteam
Controller Action
Humivisor Causes Solution
H H
Dr
Idr
Dr
-
-
-
Complete draining of the cylinder activated
Complete draining for extended inactivity
Complete periodical draining active
You have activated the manual drain sequence. Sequence ends on its own.
The unit is emptying the cylinder after an extended period of non-use.
Sequence ends on its own.
The unit has activated the periodic drain to flush excessive minerals.
Sequence ends on its own.
Reset display
Alarm relay
Reset relay
- - - -
- - - -
- - - -
AF
-
Anti-foam algorithm active
The unit is working to eliminate foaming.
- - - -
34
Installation, Operating & Maintenance Manual
3.10 Trouble-Shooting
problem causes solutions
1. no electrical power
2. on/off switch of the humidifier in position 0 (open) the humidifier does not turn on 3. control connectors improperly connected
4. blown fuses
5. transformer failure
1. check the safety devices upstream from the humidifier and the presence of power
2. close the switch on the panel: position I
3. check that the connectors are properly inserted in the terminal block
4. check the condition of fuses F1/F2/F3
5. check that the voltage across the secondary winding of the transformer is
24Vac the humidifier does not start operation
1. remote ON/OFF contact open
(relay/terminals AB - AB or 7I - 8I)
2. the humidistat has not been connected correctly
3. humidistat failure
4. control signal not compatible with the type set
5. value measured by the sensor/s higher than the corresponding set point
1. close ON/OFF contacts (relay/terminals
7I - 8I)
2. check the external connection
3. replace the humidistat
4. set parameters A0, A2-A9 correctly
5. check the values of the set point St and
P7 the humidifier fills with water without producing steam
1. high steam back pressure
2. fill valve strainer clogged
3. mineral in the fill cup
4. drain solenoid valve leaking
1. check that the steam hose is not kinked or sagging, trapping condensate
2. clean the fill valve strainer
3. clean the fill cup
4. check for 24Vac at the drain solenoid valve and/or drain solenoid replacement the thermal-magnetic overload switch is activated the humidifier wets the duct
1. thermal-magnetic overload switch is under-rated
2. over-current at the electrodes
1. the distributor is not installed correctly (too near the top of the duct or the condensate return is blocked)
2.system over-sized
3.humidifier active when the fan in the duct is off
1. check that the thermal-magnetic overload switch is rated for a current of at least 1.5 times the rated current of the humidifier
2. see description for alarm EH
1. check that the steam distributor is installed correctly
2. decrease the steam production set on the control
3. check the connection of the device (flow switch or differential pressure switch) slaving the humidifier to the ventilation in the duct (terminals 7I - 8I) the humidifier wets the floor below
1. the humidifier drain is blocked
2. the supply water or overflow circuit has leaks
3. the condensate drain pipe does not bring the water back to the drain pan
4. the steam hose is not properly fastened to the cylinder
1. clean the drain assembly and pan
2. check the entire water circuit
3. check the correct position of the condensate drain hose in the drain pan
4. check the fastening of the hose clamps on the steam outlet
35
CAREL humiSteam problem causes solutions
Water in the cylinder turns black 1. minerals in the cylinder have overconcentrated and are deteriorating the electrodes.
1. Check for sags & kinks that could trap condensate in the steam hoses that could cause a back pressure on the cylinder.
2. Check the duct static pressure.
3. Check the fill valve and inlet strainer.
4. Check the drain valve operation.
5. Correct installation problems and replace cylinder.
Heavy arcing occurs within hours of startup
1. The feed water contains large amounts of Iron, Copper or other conductive contaminants.
1. Contact the factory for an optional drain timer to force additional drains to control the minerals.
2. If you are using a softener, check the salt being used. If it contains any additives, discontinue use, flush all lines and convert to pure salt or unsoftened water.
3. Check the electrodes in the cylinder to be sure they were not damaged in shipping.
Humidifier continuously fills and drains without producing steam
1. Mineral has bridged between the electrodes.
2. There is back pressure from the steam hoses or duct.
3. The flow regulator in the fill valve is broken or out of place.
4. Water conductivity is very high.
5. Water is foaming excessively.
1. Clean or replace the cylinder.
2. Check the steam hoses for kinks or gullys that might be trapping condensate.
3. Replace the fill valve.
4. Consider using a mix of demineralized water with raw water.
5. Check cylinder - replace if exhausted. If feed water contains silica or nitrates, install a 1 micron water filter.
3.11 Resetting Factory Defaults
If errors have occurred when setting the parameters, the controller may be reset to the factory default values:
• in the first 5 seconds from start-up (while the three dashes are displayed), press the PRG button (2) until the upper dash in the center flashes (1);
• release the PRG button within 3 seconds to confirm the permanent reset of the factory defaults; to confirm the reset, the upper dash will stay on for 2 seconds;
• the factory reset is not carried out if the PRG button is pressed for more than 3 seconds, until the upper dash disappears.
Recalling the default parameters does not change the parameter relating to the unit of measure (A1), and it is thus recommended to check and if necessary select and save the unit of measure as required, and then recall the default parameters. In this way the default values will automatically be converted.
36
Installation, Operating & Maintenance Manual
4 Maintenance
4.1 Periodic checks
• After one hour of operation: For both disposable and cleanable cylinders, check that there are no significant water leaks.
• Every fifteen days or no more than 300 operating hours: For both disposable and openable cylinders check operation, that there are no significant water leaks and the general condition of the cylinder. Check that during operation there is no arcing between the electrodes.
• Every three months or no more than 1000 operating hours: For disposable cylinders, check operation, that there are no significant water leaks and, if necessary, replace the cylinder; for cleanable cylinders, check that there are no blackened parts of the cylinder. If there are blackened parts of the cylinder, check the condition of the electrodes, and if necessary replace them together with the o-rings and the cover gasket.
• Annually or no more than 2500 operating hours: For disposable cylinders, replace the cylinder; for cleanable cylinders check operation, that there are no significant water leaks, the general conditions of the cylinder, check that there are no blackened parts of the cylinder: if this is the case, check the condition of the electrodes, and if necessary replace them together with the o-rings and the cover gasket.
• After five years or no more than 10,000 operating hours: For both disposable and openable cylinders, replace the cylinder. After extended use or alternatively when using water with a high salt content, the solid deposits that naturally form on the electrodes may reach the stage where they also stick to the inside wall of the cylinder; in the event of especially conductive deposits, the consequent heat produced may overheat the plastic and melt it, and, in more severe cases, puncture the cylinder, allowing water to leak out. As a precaution, check the deposits and the blackening of the wall of the cylinder, and replace the cylinder if necessary.
CAUTION: always disconnect the main power before touching the cylinder in the event of leaks, as current may flow through the water.
4.2 Cylinder maintenance
The life of the cylinder depends on a number of factors, including: the amount and type of mineral in the water, the correct use and sizing of the humidifier, and the output, as well as careful and regular maintenance. Due to the aging of the plastic and the consumption of the electrodes, even an openable steam cylinder has a limited life, and it is therefore recommended to replace it after 5 years or 10,000 operating hours.
Important warnings
The humidifier and its cylinder contain live electrical components and hot surfaces, and therefore all service and/or maintenance operations must be performed by expert and qualified personnel, who are aware of the necessary precautions. Before performing any operations on the cylinder, check that the humidifier is disconnected from the power supply. Remove the cylinder from the humidifier only after having drained it completely using the manual drain button or procedure. Check that the model and the power supply voltage of the new cylinder correspond to the data on the rating label.
4.2.1 Replacing the cylinder
IMPORTANT WARNING: the cylinder may be hot. Allow it to cool before touching it or use protective gloves.
To replace the cylinder:
• completely drain the cylinder by pressing and holding the manual drain switch or by pressing the Ç and
È buttons simultaneously for 2 seconds to force a manual drain. This procedure can be stopped at any time by again pressing the Ç and È buttons for 2 seconds;
• turn the humidifier off and disconnect the main power;
• open and remove the cover;
• remove the steam hose from the cylinder;
• disconnect the electrical connections from the top of the cylinder;
• release the cylinder from its holding bracket and lift it up to remove it;
• install the new cylinder in the humidifier by performing the previous operations in reverse.
WARNING: Electrical connections to the cylinder must be tight or possible fire hazard may result.
Threaded nuts on power wires must be connected with 22 to 29 inch-pounds of torque.
37
CAREL
Wiring of cylinders for UE025, UE035, UE045, UE065 units and voltages
Connection of single or three phase UE 001 to 015 models humiSteam
Note: Photo does not represent all cylinder possibilities
Connection of three phase UE 025 to 065 models
Note: Photo does not represent all cylinder possibilities
Model Conductivity Power Supply (Vac)
208 230 460 575
025
035
045
065
125/350 / / B B
350/1250 / / B B
38
Installation, Operating & Maintenance Manual
UE001-UE015
4.2.2 Maintenance of the other plumbing components
IMPORTANT WARNINGS:
• When cleaning the plastic components do not use detergents or solvents;
• Scale can removed using a solution of Lime-A-Way ®
, CLR
®
, or 5% phosphoric acid, then rinse with water.
• External power must always be disconnected when performing any maintenance on the humidifier.
• Fill valve:
After having disconnected the cables and the hoses, remove the
Item No. Description valve and check the condition of the inlet filter; clean if necessary using the same cleaning solution as for the steam cylinder and a soft brush.
• Supply and drain manifold:
4
5 fill cup fill pipe cylinder supply pipe
6 overflow pipe
Check that there are no mineral deposits in the cylinder attachment and clean if necessary. Check that the seal (o-ring) is not damaged or cracked; replace if necessary.
9
10 drain column drain pipe
11 drain pump
• Drain valve /drain pump:
Remove the valve body or pump, clean if necessary using the same cleaning solution as for the steam cylinder and a soft brush.
• Drain pan:
Clean the pan of any mineral deposits and check that the water flows freely from the pan to the drain at the drain valve.
• Supply, fill, overflow pipes:
Check that these are clear and clean or replace if necessary.
IMPORTANT
WARNING: after having replaced or checked the plumbing, check that components have been reconnected correctly with the proper seals.
Re-start the humidifier and perform a number of supply and drain cycles (from 2 to 4), then check for any water leaks.
39
CAREL humiSteam
4.3 Replacement Parts
4.3.1 Single Phase Humidifiers
Standard spare parts
Water parts fill cup + conductivity meter fill valve kit
Drain valve kit internal pipe kit
Electrical parts
Contactor power transformer: 208/230/460/575-24 Vac,
100 VA NEW ( >1/1/06) fuse holder fuse
Electronic parts
LED display ver.C-P control module ver.H-T control board ver.C-P ** control board ver.H-T flat connection cable remote control
4.3.2 Three Phase Humidifiers
Standard Spare Parts
Model UE003 UE005
Water Parts
UE001 UE003
18C453A008 18C453A008
KITVC00006 KITVC00006
13C499A030 13C499A030
UEKT00000S UEKT00000S
0203000AXX 0203000AXX
0606192AXX 0606192AXX
0605319AXX 0605319AXX
UEKDP00000 UEKDP00000
98C474C004 98C474C004
59C460A003 59C460A003
TELUE0E000 TELUE0E000
UE008 UE010 UE015
Model
0203001AXX 0203001AXX
UE025
UE005
UE035
UE009
18C453A008 18C453A008
KITVC00006 KITVC00012
13C499A030 13C499A030
UEKT00000S UEKT00000M
09C565A002 09C565A002 09C565A002 09C565A002
0606192AXX 0606192AXX
0605319AXX 0605319AXX
UEKDP00000 UEKDP00000
98C474C004 98C474C004
59C460A003 59C460A003
TELUE0E000 TELUE0E000
UE045
Fill Cup + Conductivity Meter 18C453A008 18C453A008 18C453A008 18C453A008 18C453A008 18C453A008 18C453A008 18C453A008
Fill Valve Kit KITVC00006 KITVC00006 KITVC00006 KITVC00012 KITVC00012 KITVC00040 KITVC00040 KITVC00040
UE065
KITVC00070
Drain Valve Kit
Internal Pipe Kit
13C499A030 13C499A030 13C499A030 13C499A030 13C499A030 KITPS00000 KITPS00000 KITPS00000
UEKT00000S UEKT00000S UEKT00000S UEKT00000M UEKT00000M UEKT00000L UEKT00000L UEKT00000L
KITPS00000
UEKT0000XL
Conductivity
208-230V
400-460-575V
Electrical Parts
Contactors
18C480A011
18C480A011
0203000AXX 0203000AXX 0203000AXX 0203001AXX 0203001AXX 0203001AXX 0203008AXX 0203009AXX(5) 0203007AXX(2)(3)
0203007AXX
(2,3,4)
Power Transformers:
208/230/460/575-24 Vac,
100VA NEW ( >1/1/06)
Fuse Holders
09C565A002 09C565A002 09C565A002 09C565A002 09C565A002 09C479A062 09C479A062 09C479A062 09C479A062
208-230V
400-460-575V
Fuse 3
Fuse 4
Pump Relay
Electrical Parts
0606192AXX 0606192AXX 0606192AXX 0606192AXX 0606192AXX 0606193AXX 0606193AXX 0606193AXX 0606193AXX
0605319AXX 0605319AXX 0605319AXX 0605319AXX 0605319AXX 0605319AXX 0605319AXX 0605319AXX 0605319AXX
0605318AXX 0605318AXX 0605318AXX 0605318AXX
0605319AXX 0605319AXX 0605319AXX
0605624AXX 0605624AXX 0605624AXX
0102001AXX 0102001AXX 0102001AXX
0605319AXX
0605624AXX
0102001AXX
40
Standard Spare Parts
Model UE003
Control Module Ver. H-T
Control Board Ver. C-P **
Control Board Ver. H-T
Flat Connection Cable
Installation, Operating & Maintenance Manual
UE005 UE008 UE010 UE015 UE025
UEH0000000U00
UE035 UE045 UE065
UEP0000000U00
98C474C004 98C474C004 98C474C004 98C474C004 98C474C004 98C474C005 98C474C005 98C474C005 98C474C005
59C460A003 59C460A003 59C460A003 59C460A003 59C460A003 59C460A003 59C460A003 59C460A003 59C460A003
Remote Control TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000 TELUE0*000 TELEUE*000
4.3.3 Replacement Steam Cylinders & Parts
Single Phase Humidifiers
UE001 UE003 UE005 UE009 Model
Steam Cylinders - disposable
200-230/1 VAC
Standard conductivity
BL0S1F00H1 BL0S1F00H1 BL0S2F00H0 BL0S3F00H0
200-230/1 VAC
Low conductivity
Steam Cylinders - cleanable
200-230/1 VAC
Standard conductivity
200-230/1 VAC
Low conductivity
Replacement
Electrodes electrode kit 200-230/1 V
Standard conductivity electrode kit 200-230/1 V
Low conductivity
BL0S1E00H1 BL0S1E00H1 BL0S2E00H0 BL0S3E00H0
BLCS2F00W0 BLCS3F00W0
BLCS2E00W0 BLCS3E00W0
KITBLCS2F0
KITBLCS2E0
KITBLCS3F0
KITBLCS3E0 electrode gasket kit KITBLC2FG0 KITBLC3FG0
Three Phase Humidifiers
Model
UE065, 090,
UE003 UE005 UE008 UE010 UE015 UE025 UE035 UE045
130
Steam Cylinders - disposable
200-230/3 VAC
Standard conductivity
BL0T1B00H1 BL0T2B00H0 BL0T2B00H0 BL0T3B00H0 BL0T3B00H0 BL0T4C00H0 BL0T4B00H0 BL0T5A00H1
460/3 VAC
Standard conductivity
575/3 VAC
Standard conductivity
200-230/3 VAC
Low conductivity
460/3 VAC
Low conductivity
575/3 VAC
Low conductivity
Steam Cylinders - cleanable
200-230/3 VAC
Standard conductivity
460/3 VAC
Standard conductivity
575/3 VAC
Standard conductivity
200-230/3 VAC
Low conductivity
460/3 VAC
Low conductivity
575/3 VAC
Low conductivity
Replacement
Electrodes electrode kit 200-230/3 V
Standard conductivity electrode kit 460/3 VAC
Standard conductivity electrode kit 575/3 VAC
Standard conductivity electrode kit 200-230/3 V
Low conductivity
BL0T1D00H1 BL0T2D00H0 BL0T2D00H0 BL0T3D00H0 BL0T3D00H0 BL0T4D00H0 BL0T4D00H0 BL0T4D00H0 BL0T5D00H0
BL0T2D00H0 BL0T2D00H0 BL0T3D00H0 BL0T3D00H0 BL0T4D00H0 BL0T4D00H0 BL0T4D00H0 BL0T5D00H0
BL0T1A00H1 BL0T2A00H0 BL0T2A00H0 BL0T3A00H0 BL0T3A00H0 BL0T4B00H0 BL0T4B00H0 BL0T5A00H1
BL0T1B00H1 BL0T2C00H0 BL0T2C00H0 BL0T3C00H0 BL0T3C00H0 BL0T4D00H0 BL0T4C00H0 BL0T4C00H0 BL0T5C00H0
BL0T2C00H0 BL0T2C00H0 BL0T3C00H0 BL0T3C00H0 BL0T4D00H0 BL0T4D00H0 BL0T4D00H0 BL0T5D00H0
BLCT2B00W0 BLCT2B00W0 BLCT3B00W0 BLCT3B00W0 BLCT4C00H0 BLCT4B00H0 BLCT5B00H0
BLCT2D00W0 BLCT2D00W0 BLCT3D00W0 BLCT3D00W0 BLCT4D00H0 BLCT4D00H0 BLCT4D00H0 BLCT5D00H0
BLCT2D00W0 BLCT2D00W0 BLCT3D00W0 BLCT3D00W0
BLCT4D00H0
BLCT4D00H0 BLCT4D00H0 BLCT5D00H0
BLCT2A00W0 BLCT2A00W0 BLCT3A00W0 BLCT3A00W0 BLCT4B00H0 BLCT4B00H0 BLCT5B00H0
BLCT2C00W0 BLCT2C00W0 BLCT3C00W0 BLCT3C00W0 BLCT4D00H0 BLCT4C00H0 BLCT4C00H0 BLCT5C00H0
BLCT2C00W0 BLCT2C00W0 BLCT3C00W0 BLCT3C00W0 BLCT4D00H0 BLCT4D00H0 BLCT4D00H0 BLCT5D00H0
KITBLCT2B0 KITBLCT2B0 KITBLCT3B0 KITBLCT3B0 KITBLCT4C0 KITBLCT4B0 KITBLCT5B0
KITBLCT2D0 KITBLCT2D0 KITBLCT3D0 KITBLCT3D0 KITBLCT4D0 KITBLCT4D0 KITBLCT4D0 KITBLCT5D0
KITBLCT2D0 KITBLCT2D0 KITBLCT3D0 KITBLCT3D0 KITBLCT4D0 KITBLCT4D0 KITBLCT4D0 KITBLCT5D0
KITBLCT2A0 KITBLCT2A0 KITBLCT3A0 KITBLCT3A0 KITBLCT4B0 KITBLCT4B0 KITBLCT5B0
41
CAREL electrode kit 460/3 VAC
Low conductivity electrode kit 575/3 VAC
Low conductivity electrode gasket kit humiSteam
KITBLCT2C0 KITBLCT2C0 KITBLCT3C0 KITBLCT3C0 KITBLCT4D0 KITBLCT4C0 KITBLCT4C0 KITBLCT5C0
KITBLCT2C0 KITBLCT2C0 KITBLCT3C0 KITBLCT3C0 KITBLCT4D0 KITBLCT4D0 KITBLCT4D0 KITBLCT5D0
KITBLC2FG0 KITBLC2FG0 KITBLC3FG0 KITBLC3FG0 KITBLC4FG0 KITBLC4FG0
KITBLC4FG0
KITBLC5FG0
KITBLC5FG0
Low Conductivity cylinders for water conditions between 125-350 µS/cm
Standard Conductivity cylinders for water conditions between 350-1250 µS/cm
42
Installation, Operating & Maintenance Manual
5 Wiring Diagrams
UE001, UE003, UE005, UE009 Single Phase
43
CAREL
UE003, UE005, UE008, UE010, UE015 Three Phase humiSteam
44
Installation, Operating & Maintenance Manual
UE025, UE035, UE045, UE065 Three Phase
45
CAREL humiSteam
6 Technical Specifications
VAC/
Phase
208/1
(U)
230/1
(D)
Factor
UE
001
UE
003
UE
005
Lbs/hr 3.3 6.6 11.0
UE
008 kg/h 1.5 3 5
Amps 5.4 10.8 18.0
UNIT MODEL NUMBER: Capacity, Amperage, Kilowatts
UE
009
UE
010
UE
015
UE
025
UE
035
UE
045
19.1
8.7
31.3
6.52
UE
045
Lbs/hr 3.3 6.6 11.0 kg/h 1.5 3 5
Amps 4.9 9.8 16.3
19.8
9
29.3
6.75
Lbs/hr 6.6 17.6 22
208/3
(W)
Amps 6.2 16.7 20.8 31.2 52.0 72.9
KW 2.25 3.75 6.00 7.50 11.25 18.75 26.25
Lbs/hr 6.6 17.6 22
93.7
33.75
UE
065
230/3
(K)
460/3
(M)
UE
090
UE
130
Amps 5.6 15.1 18.8 28.2 47.1 65.9
KW
Lbs/hr kg/h
2.25 3.75 6.00
6.6 11.0 17.6
3 5 8
7.50 11.25 18.75 26.25
22 33 55 77 99
84.7
33.75
10 15 25 35 45
KW
7.5 9.4
2.25 3.75 6.00
23.5 32.9 42.4
132 198 286
60 90 130
61.2 84.7 122.4
48.75 67.50 97.50
575/3
(N)
Height
Width
Depth kg/h
KW
Dry weight
Wet weight
Max. water feed
Water feed connection
Max. drain rate
Drain connection
Min. drain piping
No. cylinders
Steam outlet (No.x size)
Control voltage
Ambient conditions
Feed water conditions
5 8 10 15 25 35 45
6.0 18.8 26.4 33.9
60 90 130
49.0 67.8 97.9
3.75 6.00
24.4” (620 mm)
14.4” (365 mm)
10.8” (275 mm)
35.3 lbs (16 kg)
41.9 lbs (19 kg)
0.16 gpm (0.6 l/min)
7.50 11.25 18.75 26.25 33.75
28.0” (710 mm) 35.0” (890 mm)
14.4” (365 mm) 21.9” (555 mm)
48.75 67.50 97.50
37.2" (945mm) 37.2" (945mm)
25.6" (650mm)
45.5"
(1156mm)
10.8” (275 mm)
44.0 lbs (20 kg)
59.5 lbs (27 kg)
0.32 gpm (1.2 l/min)
14.2” (360 mm)
75.0 lbs (34 kg)
133.4 lbs (60.5 kg)
1.06 gpm (4.0 l/min)
17.9" (455mm) 17.9" (455mm)
97.0 lbs (44 kg) 160 lbs (73 kg)
207.2 lbs (94 kg)
330 lbs (150 kg)
1.85 gpm (7 l/min)
4 gpm (15 l/min)
3/4” MPT (19 mm) bushed to 1/4” O.D. compression
12 gpm (45 l/min)
1 x 22/30 mm
1.32 gpm (5 l/min) 6.0 gpm (22.5 l/min)
1.6" hose (40mm)
¾” (19 mm) 1 ½” (38 mm)
1
1 x 30 mm 1 x 40 mm 2 x 40 mm
24 VAC 50/60 Hz.
34-140°F (1-40°C), 0-80 % RH, up to 8 inches W.C. duct static pressure (200 mm W.C.)
2
4 x 40 mm
15 – 116 psi (1-8 bar), 125-1250 MicroMhos conductivity
VSDU0A
VRDXL (One (1) required for each steam outlet. i.e. four (4) for UE130)
Power: 24 volt powered by unit Power: 220/1/50-60, 35 Watts
Ventilated steam distributors
Air volume: 112 cfm (192 m3/h)
Height/Remote: 6.3/10.75” (160.273 mm)
Air volume: 380 cfm (646 m3/h)
Height = 10.5” (267 mm)
Weight: 13.2 lbs. (6 kg)
Noise: 30 dBA (50)
Weight: 63 lbs. (24 kg)
Noise: 40 dBA
46
6.1 Model Numbers
Installation, Operating & Maintenance Manual
UE 025 H D U 1 0
UE =
Electrode
001 = 3.3 lbs/hr
003 = 7 lbs/hr
005 = 11 lbs/hr
008 = 18 lbs/hr
Control supply
For use with: U = 208/1
On/off or
Modulating
D = 230/1
W = 208/3
K = 230/3
Version number
Internal use only
USA
Cylinder
Type
1 = Disposable
Standard
Conductivity
2 = Disposable
Low
Conductivity
Optional
Equipment
0 = Standard
B = Direct
Mount Blower
010 = 22 lbs/hr or M = 460/3
015 = 33 lbs/hr DDC N = 575/3
025 = 55 lbs/hr
035 = 77 lbs/hr
045 = 99 lbs/hr
065 = 132 lbs/hr
Limited Warranty
All products manufactured by Carel USA, LLC are warranted to the original purchaser to be free from defects in materials and workmanship in the course of normal and reasonable use for a period of 2 years and 1 month from the date of shipment (The OEM controls warranty is 2 years from date of manufacture), humidifier replacement parts warranty is 90 days from date of Invoice. Warranty replacement parts are warranted for remainder of original unit warranty or 90 days, whichever is longer, so long as the product has been installed and operated in accordance with all appropriate manuals and wiring diagrams, and started up by a qualified Carel USA technician. Any product or part that is found to be defective will, at the option of Carel USA, LLC be replaced or repaired. Carel USA, LLC reserves the right to inspect any part or installation before replacing or repairing defective parts. After startup of the product, labor for repairs or replacement of parts is not covered by this warranty. Products not included in this warranty are NTC and PTC probes, transformers (TRA series), and routinely replaceable parts such as steam cylinders and gaskets. Carel USA, LLC assumes no liability for consequential or inconsequential damage, or damage due to negligence or improper use. Under the terms of this warranty, the original purchaser may have certain legal rights and other rights, which may vary from state to state. The Warranty will not be considered valid if a product is damaged due to negligence, mishandling or misapplication, or if the product label is missing. Carel USA will attempt to repair or replace the products within two (2) months of the receipt of the returned goods.
47
CAREL humiSteam
CAREL USA, LLC
385 S. Oak Street
Manheim, PA 17545
Form: +030221907, Rev. 0.6
48
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 How The Humisteam Works
- 6 1 Installation
- 6 1.1 Positioning
- 7 1.2.1 Removing the front cover
- 7 1.2.2 Fastening to the wall
- 8 1.3 Plumbing
- 8 1.3.1 Water supply
- 8 1.3.2 Water drain
- 11 1.4 Steam distribution
- 11 1.4.1A Duct injection
- 15 1.5 Power wiring
- 17 1.6 Connect Control Wiring
- 17 1.6.1 Controls Placement
- 17 1.7 Control wiring
- 20 ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors
- 21 HC-101 and HC-201 Wall and Duct Humidistats
- 22 PC-301 Air Proving Switch
- 23 2 Start-Up
- 23 2.1 Startup Checklist
- 24 2.2 The HumiControl Controller
- 24 2.3 Start-up Procedure
- 24 2.3.1 Starting with a new cylinder
- 25 3 Operation
- 25 3.1 Display Information
- 25 3.2 Changing The Set Point
- 25 3.3 Activating Manual Drain
- 25 3.4 Accessing/Changing Configuration Parameters
- 28 3.5 Notes about special parameters
- 29 STANDARD CONFIGURATION SETTINGS
- 30 3.6 Seasonal Shut Down
- 30 3.7 The Remote Control
- 31 3.8 Resetting the Hour Counter
- 31 3.9 Alarms
- 35 3.10 Trouble-Shooting
- 36 3.11 Resetting Factory Defaults
- 37 4 Maintenance
- 37 4.1 Periodic checks
- 37 4.2 Cylinder maintenance
- 37 4.2.1 Replacing the cylinder
- 39 4.2.2 Maintenance of the other plumbing components
- 40 4.3 Replacement Parts
- 40 4.3.1 Single Phase Humidifiers
- 40 4.3.2 Three Phase Humidifiers
- 41 4.3.3 Replacement Steam Cylinders & Parts
- 43 5 Wiring Diagrams
- 46 6 Technical Specifications
- 47 6.1 Model Numbers