V5832B/V5833A

Small Linear Valves PN16

PRODUCT DATA

FEATURES

Pressure balanced plug

Range of fittings available for different connections

Easy to mount, no tools required

Flat sealing connections

Flat surfaces on body to fit installation tools

Standard external threads for Honeywell or field

V5832B V5833A

GENERAL

These small linear valves are used in combination with small electric linear valve actuators for the control of hot and/or chilled water for fan coil units, small reheaters/recoolers in electric/electronic temperature control systems. Because of the pressure-balanced plug, the close-off pressure is equal to the system pressure.

Adjustment cap for manual operation

SPECIFICATIONS

Operation Stem up to close port A to AB

Nominal pressure rating PN16

Capacity index (k

VS

)

Leakage rate see tables on page 2

0.05% of k

VS

Valve body:

Size DN25 (1”), DN32 (11/4”),

Trim:

Plug Brass

Suitable medium Water, with max. 50% glycol

Controlled water temperature: 2...130

C

Rangeability 50:1

Flow characteristic Linear for port A-AB, linear for bypass port B-AB

Dimensions see Fig. 3 on page 4

® U.S. Registered Trademark

Copyright © 2012 Honeywell Inc. • All rights reserved

EN0B-0408GE51 R0612

V5832B/V5833A SMALL LINEAR VALVES PN16 – PRODUCT DATA

FLOW CAPACITIES AND CLOSE OFF PRESSURE RATINGS

TWO-WAY VALVES

DN k

VS order no. close-off pressure (= max. operating pressure) in kPa for 300-N actuators

(M6410C,L / M7410C1015 / M7410E1028)

1600

1600

1600

1200

1000 close-off pressure (= max. operating pressure) in kPa for 400-N actuators

(ML6435B / ML7430E / ML7435E)

1600

1600

1600

1200

1000

THREE-WAY VALVES

DN k

VS order no. close-off pressure (= max. operating pressure) in kPa for 300-N actuators

(M6410C,L / M7410C1015 / M7410E1028) close-off pressure (= max. operating pressure) in kPa for 400-N actuators

(ML6435B / ML7430E / ML7435E)

OPERATION

A built-in return spring produces a closing force.

The valves are supplied with an adjustment cap for manual operation and to protect the stem. This allows the stem set up for filling or initial heating/cooling during the building construction phase without the use of a controller or actuator.

The small electric valve actuators provide automatic control during the opening and closing movement of the valve stem.

TYPICAL OPERATION

All types of valves should be mounted in the return flow. If the

p-values exceed 60 kPa, attention should be paid to the development of noise.

Two-Way Valves

Direction of flow always from port A to port B

Port B: Outlet

600

600

600

300

--

AB

B inlet

A

+

-

1600

1600

1600

1200

1000

Three-Way Valves

These valves are preferably used as mixing valves, this means:

Port AB: Total flow outlet

Port A:

Port B:

Controlled flow inlet

Bypass inlet

AB

B inlet

A

+

-

Fig. 2. Three-way valve operation inlet inlet

+

-

+

outlet outlet

Fig. 1. Two-way valve operation

EN0B-0408GE51 R0612 2

V5832B/V5833A SMALL LINEAR VALVES PN16 – PRODUCT DATA

MOUNTING

When installing the valve care must be taken that the flow direction is correct (see section "Typical Operation"). The valve must not be mounted with the stem pointing downward.

The adjustment cap must be removed from the valve only when the actuator is fitted. The valve should be installed as stress-free as possible with a tightening torque of 25 to

30 Nm.

The valve is supplied complete with mounting instructions.

The water quality should meet VDI 2035 requirements.

ACCESSORIES

Valves V5832B need two connection sets, valves V5833A need three connection sets.

Connection Pipe Size DN Order Number Connection Set

External

Thread

R1"

R11/4"

R11/2"

25

32

40

AC-25T

AC-32T

AC-40T

Internal

Thread

Rp1"

Rp11/4"

Rp11/2"

25

32

40

AC-25TF

AC-32TF

AC-40TF

Dimensions of Connection Sets a b c

Order Number

G11/2”

G2”

G21/4”

R1”

R11/4”

R11/2”

AC-25T

AC-32T

AC-40T

G11/2”

G2”

G21/4”

Rp1”

Rp11/4”

Rp11/2”

AC-25TF

AC-32TF

AC-40TF

Description

Consisting of 1 union nut

1 tailpiece and 1 gasket

Consisting of 1 union nut

1 tailpiece and 1 gasket

V5832B/V5833A SMALL LINEAR VALVES PN16 – PRODUCT DATA

DIMENSIONS

V5832B

Allow 200mm for the actuator and clearance for removal e

V5833A

DN a b c d e

G11/2” 92 52.5 62

32 105 G2” 92 52.5 62

Allow 200mm for the actuator and clearance for removal

Fig. 3. Dimensions (in mm)

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

Automation and Control Solutions

Honeywell GmbH

Böblinger Strasse 17

71101 Schönaich, Germany

Phone: (49) 7031 63701

Fax: (49) 7031 637493 http://ecc.emea.honeywell.com

Subject to change without notice. Printed in Germany

EN0B-0408GE51 R0612

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement