advertisement
V5832B/V5833A
Small Linear Valves PN16
PRODUCT DATA
FEATURES
Pressure balanced plug
Range of fittings available for different connections
Easy to mount, no tools required
Flat sealing connections
Flat surfaces on body to fit installation tools
Standard external threads for Honeywell or field
V5832B V5833A
GENERAL
These small linear valves are used in combination with small electric linear valve actuators for the control of hot and/or chilled water for fan coil units, small reheaters/recoolers in electric/electronic temperature control systems. Because of the pressure-balanced plug, the close-off pressure is equal to the system pressure.
Adjustment cap for manual operation
SPECIFICATIONS
Operation Stem up to close port A to AB
Nominal pressure rating PN16
Capacity index (k
VS
)
Leakage rate see tables on page 2
0.05% of k
VS
Valve body:
Size DN25 (1”), DN32 (11/4”),
Trim:
Plug Brass
Suitable medium Water, with max. 50% glycol
Controlled water temperature: 2...130
C
Rangeability 50:1
Flow characteristic Linear for port A-AB, linear for bypass port B-AB
Dimensions see Fig. 3 on page 4
® U.S. Registered Trademark
Copyright © 2012 Honeywell Inc. • All rights reserved
EN0B-0408GE51 R0612
V5832B/V5833A SMALL LINEAR VALVES PN16 – PRODUCT DATA
FLOW CAPACITIES AND CLOSE OFF PRESSURE RATINGS
TWO-WAY VALVES
DN k
VS order no. close-off pressure (= max. operating pressure) in kPa for 300-N actuators
(M6410C,L / M7410C1015 / M7410E1028)
1600
1600
1600
1200
1000 close-off pressure (= max. operating pressure) in kPa for 400-N actuators
(ML6435B / ML7430E / ML7435E)
1600
1600
1600
1200
1000
THREE-WAY VALVES
DN k
VS order no. close-off pressure (= max. operating pressure) in kPa for 300-N actuators
(M6410C,L / M7410C1015 / M7410E1028) close-off pressure (= max. operating pressure) in kPa for 400-N actuators
(ML6435B / ML7430E / ML7435E)
OPERATION
A built-in return spring produces a closing force.
The valves are supplied with an adjustment cap for manual operation and to protect the stem. This allows the stem set up for filling or initial heating/cooling during the building construction phase without the use of a controller or actuator.
The small electric valve actuators provide automatic control during the opening and closing movement of the valve stem.
TYPICAL OPERATION
All types of valves should be mounted in the return flow. If the
p-values exceed 60 kPa, attention should be paid to the development of noise.
Two-Way Valves
Direction of flow always from port A to port B
Port B: Outlet
600
600
600
300
--
AB
B inlet
A
+
-
1600
1600
1600
1200
1000
Three-Way Valves
These valves are preferably used as mixing valves, this means:
Port AB: Total flow outlet
Port A:
Port B:
Controlled flow inlet
Bypass inlet
AB
B inlet
A
+
-
Fig. 2. Three-way valve operation inlet inlet
+
-
+
outlet outlet
Fig. 1. Two-way valve operation
EN0B-0408GE51 R0612 2
V5832B/V5833A SMALL LINEAR VALVES PN16 – PRODUCT DATA
MOUNTING
When installing the valve care must be taken that the flow direction is correct (see section "Typical Operation"). The valve must not be mounted with the stem pointing downward.
The adjustment cap must be removed from the valve only when the actuator is fitted. The valve should be installed as stress-free as possible with a tightening torque of 25 to
30 Nm.
The valve is supplied complete with mounting instructions.
The water quality should meet VDI 2035 requirements.
ACCESSORIES
Valves V5832B need two connection sets, valves V5833A need three connection sets.
Connection Pipe Size DN Order Number Connection Set
External
Thread
R1"
R11/4"
R11/2"
25
32
40
AC-25T
AC-32T
AC-40T
Internal
Thread
Rp1"
Rp11/4"
Rp11/2"
25
32
40
AC-25TF
AC-32TF
AC-40TF
Dimensions of Connection Sets a b c
Order Number
G11/2”
G2”
G21/4”
R1”
R11/4”
R11/2”
AC-25T
AC-32T
AC-40T
G11/2”
G2”
G21/4”
Rp1”
Rp11/4”
Rp11/2”
AC-25TF
AC-32TF
AC-40TF
Description
Consisting of 1 union nut
1 tailpiece and 1 gasket
Consisting of 1 union nut
1 tailpiece and 1 gasket
V5832B/V5833A SMALL LINEAR VALVES PN16 – PRODUCT DATA
DIMENSIONS
V5832B
Allow 200mm for the actuator and clearance for removal e
V5833A
DN a b c d e
G11/2” 92 52.5 62
32 105 G2” 92 52.5 62
Allow 200mm for the actuator and clearance for removal
Fig. 3. Dimensions (in mm)
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone: (49) 7031 63701
Fax: (49) 7031 637493 http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
EN0B-0408GE51 R0612