SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
May 2006
TECHNICAL DATA BOOK R410A
<Indoor unit>
[Model names]
INVERTER
PLA-RP·AA
PLA-RP·AA2
PEAD-RP·EA
PEAD-RP·EA2
PEAD-RP·GA
PKA-RP·GAL
PKA-RP·FAL
PCA-RP·GA
PCA-RP·HA
PSA-RP·GA
No. OCS05
REVISED EDITION-A
Revision:
• High dimension of PEAD-RP71EA are
modified in REVISED EDITION-A.
• Some descriptions have been
modified.
• Please void OCS05.
<Outdoor unit>
[Model names]
PUHZ-RP35/50/60/71/100/125/140VHA2
PUHZ-RP100/125/140YHA2
CONTENTS
1. REFERENCE SERVICE MANUAL·············································2
2. SPECIFICATIONS ······································································3
3. OUTLINES AND DIMENSIONS················································23
4. WIRING DIAGRAM···································································42
5. REFRIGERANT SYSTEM DIAGRAM ······································54
6. PERFORMANCE CURVES ······················································57
7. CORRECTION FACTORS ························································59
8. APPLICABLE EXTENSION PIPE FOR EACH MODEL ··········60
9. AIR FLOW DATA ······································································64
10. NOISE CRITERION CURVES ··················································78
11. OPTIONAL PARTS·····································································88
kW Model
OCS05A-1.qxp
1
06.5.15 0:50 PM
Page 2
REFERENCE SERVICE MANUAL
For information on service, please refer to the service manual as follows.
1-1. INDOOR UNIT
Model name
Service Ref.
PLA-RP35/50/60/71AA.UK
PLA-RP35/50/60/71AA
Service
Manual No.
OC335
PLA-RP35/50/60/71AA
OC327
PLA-RP100/125/140AA2
PLA-RP100/125/140AA2.UK
OC357
PCA-RP50/60/71GA
PCA-RP100/125/140GA
PCA-RP71/125HA
PCA-RP50/60/71GA
PCA-RP100/125/140GA
PCA-RP71/125HA
OC328
OC329
PKA-RP35/50GAL
PKA-RP35/50GAL
OC330
PKA-RP60/71/100FAL
PKA-RP60/71/100FAL
OC331
PSA-RP71/100/125/140GA
PSA-RP71/100/125/140GA
OC332
PEAD-RP50/60/71/125/140EA
PEAD-RP35/100EA2
PEAD-RP60/71/100GA
PEAD-RP50/60/71/125/140EA.UK
PEAD-RP35/100EA2.UK
PEAD-RP60/71/100GA.UK
HWE05210
HWE05060
1-2. OUTDOOR UNIT
Model name
Service Ref.
PUHZ-RP35/50/60/71VHA2
PUHZ-RP100/125/140VHA2
PUHZ-RP100/125/140YHA2
PUHZ-RP35/50/60/71VHA2
PUHZ-RP100/125/140VHA2
PUHZ-RP100/125/140YHA2
2
Service
Manual No.
OC374
OCS05A-1.qxp
06.5.15 0:50 PM
Page 3
SPECIFICATIONS
2
2-1. CEILING CASSETTE TYPE
Model name
Indoor unit
PLA-RP35AA
PLA-RP50AA
Btu/h
PUHZ-RP35VHA2
12,300
PUHZ-RP50VHA2
17,100
kW
3.6(1.6-4.5)
5.0(2.3-5.6)
kW
1.07
1.55
3.36
3.23
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
Btu/h
0.89
14,000
0.86
20,500
kW
4.1(1.6-5.2)
6.0(2.5-7.3)
kW
1.12
1.62
3.66
3.70
A
A
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
[
Cycle
Hz
50
V
230
Breaker size
A
11-12-13-14
14-15-16-18
CFM
390-425-460-495
495-530-565-635
External pressure
Pa
dB(A)
0
0
27-28-29-31
28-29-31-33
W : mm
D : mm
H : mm
W : inch
D : inch
Unit (Panel)
lbs
53 (11)
mm
32
inch
1-1/4
Air flow
CMM
35
1,240
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
44
46
Ivory Munsell 3Y 7.8/1.1
W : mm
800
D : mm
300+23
H : mm
600
W : inch
31-1/2
D : inch
11-13/16 + 7/8
H : inch
23-5/8
kg
45
Weight
Gas side O.D.
Liquid side O.D.
lbs
99
mm
12.7
inch
1/2
mm
6.35
inch
1/4
Height difference
m
Max. 30
Length
m
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
33-1/16 (37-3/8)
33-1/16 (37-3/8)
Unit drain pipe I.D.
Dimension
Cooling
840 (950)
258 (30)
10-3/16 (1-3/16)
24 (5)
External finish
NOTE:
White Munsell 0.70Y 8.59/0.97
840 (950)
kg
H : inch
Weight
Refrigerant pipe length
16
CMM
Dimension
Unit (Panel)
Refrigerant pipe size
1
Air flow
(Low-Medium2-Medium1-High)
Sound level
(Low-Medium2-Medium1-High)
External finish (Panel)
Outdoor unit
-
Phase
Voltage
Indoor unit
-
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
3
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 4
Indoor unit
PLA-RP60AA
PLA-RP71AA
Btu/h
PUHZ-RP60VHA2
20,500
PUHZ-RP71VHA2
24,200
kW
6.0(2.7-6.7)
7.1(3.3-8.1)
kW
1.65
1.97
3.64
3.60
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
Btu/h
0.78
23,900
0.74
27,300
kW
7.0(2.8-8.2)
8.0(3.5-10.2)
kW
1.85
2.34
3.78
3.42
A
B
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
[
Cycle
Hz
50
V
230
Breaker size
1
A
25
Air flow
(Low-Medium2-Medium1-High)
CMM
14-15-16-18
15-16-18-20
CFM
495-530-565-635
530-565-635-705
External pressure
Pa
dB(A)
0
0
28-29-31-33
28-30-32-34
Sound level
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
Unit (Panel)
W : mm
D : mm
H : mm
W : inch
D : inch
Unit (Panel)
lbs
53 (11)
mm
32
inch
1-1/4
Air flow
CMM
55
1,940
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
Weight
Gas side O.D.
Liquid side O.D.
NOTE:
Upper limit
Lower limit
Upper limit
Heating
Lower limit
47
48
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
943
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
37-1/8
kg
75
lbs
165
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
33-1/16 (37-3/8)
33-1/16 (37-3/8)
Unit drain pipe I.D.
Dimension
Refrigerant pipe length
840 (950)
258 (30)
10-3/16 (1-3/16)
24 (5)
External finish
Refrigerant pipe size
White Munsell 0.70Y 8.59/0.97
840 (950)
kg
H : inch
Weight
Outdoor unit
-
Phase
Voltage
Indoor unit
-
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
4
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 5
Indoor unit
PLA-RP100AA2
PLA-RP125AA2
PLA-RP140AA2
Btu/h
PUHZ-RP100VHA2
34,100
PUHZ-RP125VHA2
42,700
PUHZ-RP140VHA2
47,800
kW
10.0(4.9-11.4)
12.5(5.5-14.0)
14.0(5.5-15.3)
kW
3.02
3.87
4.65
3.31
3.23
3.01
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
B
Btu/h
0.78
38,200
0.74
47,800
0.71
54,600
kW
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
3.02
3.88
4.69
3.61
3.61
3.41
A
A
B
-
-
-
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
230
Breaker size
Indoor unit
1
A
32
CMM
19-21-23-27
24-25-27-30
CFM
670-740-810-950
850-880-950-1060
External pressure
Pa
dB(A)
0
0
33-36-39-41
37-40-43-45
Sound level
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
Unit (Panel)
White Munsell 0.70Y 8.59/0.97
840 (950)
W : mm
840 (950)
298 (30)
D : mm
H : mm
33-1/16 (37-3/8)
33-1/16 (37-3/8)
W : inch
D : inch
kg
11-3/4 (1-3/16)
32 (5)
Unit (Panel)
lbs
71 (11)
Unit drain pipe I.D.
mm
32
inch
1-1/4
Air flow
CMM
100
3,530
Sound level at cooling
CFM
dB(A)
49
Sound level at heating
dB(A)
51
H : inch
Weight
Outdoor unit
40
Air flow
(Low-Medium2-Medium1-High)
External finish
Dimension
50
52
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
121
116
lbs
267
256
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
53-1/8
kg
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
5
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 6
Indoor unit
PLA-RP100AA2
PLA-RP125AA2
PLA-RP140AA2
Btu/h
PUHZ-RP100YHA2
34,100
PUHZ-RP125YHA2
42,700
PUHZ-RP140YHA2
47,800
kW
10.0(4.9-11.4)
12.5(5.5-14.0)
14.0(5.5-15.3)
kW
3.02
3.87
4.65
3.31
3.23
3.01
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
B
Btu/h
0.78
38,200
0.74
47,800
0.71
54,600
kW
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
3.02
3.88
4.69
3.61
3.61
3.41
A
A
B
-
-
-
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
400
Breaker size
Indoor unit
3
A
16
Air flow
(Low-Medium2-Medium1-High)
CMM
19-21-23-27
24-25-27-30
CFM
670-740-810-950
850-880-950-1060
External pressure
Pa
dB(A)
0
0
33-36-39-41
37-40-43-45
Sound level
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
Unit (Panel)
White Munsell 0.70Y 8.59/0.97
840 (950)
W : mm
840 (950)
298 (30)
D : mm
H : mm
33-1/16 (37-3/8)
33-1/16 (37-3/8)
W : inch
D : inch
kg
11-3/4 (1-3/16)
32 (5)
Unit (Panel)
lbs
71 (11)
Unit drain pipe I.D.
mm
32
inch
1-1/4
Air flow
CMM
100
3,530
Sound level at cooling
CFM
dB(A)
49
Sound level at heating
dB(A)
51
H : inch
Weight
Outdoor unit
External finish
Dimension
50
52
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
135
130
lbs
298
287
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
53-1/8
kg
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -20˚C, W.B. -20˚C
D.B. 17˚C
6
3. Guaranteed voltage
Indoor unit
198~264V, 50Hz
Outdoor unit
342~457V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
3 phase 400V 50Hz
w
If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Page 7
2-2. CEILING-CONCEALED TYPE
Model name
Indoor unit
PEAD-RP35EA2
PEAD-RP50EA
Btu/h
PUHZ-RP35VHA2
12,300
PUHZ-RP50VHA2
16,700
kW
3.6(1.6-4.5)
4.9(2.3-5.6)
kW
1.12
1.52
3.21
3.22
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
Btu/h
0.89
14,000
0.82
20,500
kW
4.1(1.6-5.2)
6.0(2.5-7.3)
kW
1.20
1.65
3.41
3.64
B
A
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
-
Phase
[
Cycle
Hz
50
V
230
Voltage
Breaker size
Indoor unit
1
A
16
Air flow
(Low-High)
CMM
13.5-17
CFM
External pressure
Pa
dB(A)
476-600
30(70)
Sound level
(Low-High)
36-40
(70Pa : 38-44)
External finish
Dimension
Galvanized sheets
W : mm
935
D : mm
700
H : mm
295
W : inch
36-13/16
D : inch
27-5/8
H : inch
Weight
33
lbs
73
Air flow
CMM
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
External finish
Dimension
NOTE:
Upper limit
Lower limit
Upper limit
Heating
Lower limit
44
46
800
D : mm
300+23
H : mm
600
W : inch
31-1/2
D : inch
11-13/16 + 7/8
H : inch
23-5/8
kg
45
Gas side O.D.
lbs
99
mm
12.7
inch
1/2
mm
6.35
inch
1/4
Height difference
m
Max. 30
Length
m
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
35
1,240
W : mm
Liquid side O.D.
Refrigerant pipe length
77
Ivory Munsell 3Y 7.8/1.1
Weight
Refrigerant pipe size
35
R1(External thread)
Unit drain pipe
Outdoor unit
11-5/8
kg
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
7
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 8
Indoor unit
PEAD-RP60EA
PEAD-RP71EA
Btu/h
PUHZ-RP60VHA2
20,500
PUHZ-RP71VHA2
24,200
kW
6.0(2.7-6.7)
7.1(3.3-8.1)
kW
1.86
2.15
3.23
3.30
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
Btu/h
0.79
23,900
0.83
27,300
kW
7.0(2.8-8.2)
8.0(3.5-10.2)
kW
1.90
2.34
3.68
3.42
A
B
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
-
-
Phase
[
Cycle
Hz
50
V
230
Voltage
Breaker size
Indoor unit
kW
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
1
A
25
CMM
17-21
20-25
CFM
600-741
30(70)
706-883
70(130)
37-41
(70Pa : 39-46)
37-41
(130Pa : 40-45)
Pa
dB(A)
External finish
Dimension
Galvanized sheets
W : mm
1175
D : mm
700
H : mm
295
740
325
W : inch
46-1/8
D : inch
Weight
27-5/8
H : inch
11-5/8
12-13/16
kg
42
44
lbs
92
Outdoor unit
Air flow
CMM
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Upper limit
Lower limit
Upper limit
Heating
Lower limit
55
1,940
55
1,940
47
47
48
48
Ivory Munsell 3Y 7.8/1.1
W : mm
950
950
D : mm
330+30
330+30
H : mm
943
943
W : inch
37-3/8
37-3/8
D : inch
13 + 1-3/16
13 + 1-3/16
H : inch
37-1/8
37-1/8
kg
75
75
lbs
165
165
15.88
mm
15.88
inch
5/8
5/8
mm
9.52
9.52
inch
3/8
3/8
Height difference
m
Max. 30
Max. 30
Length
m
Max. 50
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
97
R1(External thread)
Unit drain pipe
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
8
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 9
Indoor unit
PEAD-RP100EA2
PEAD-RP125EA
PEAD-RP140EA
Btu/h
PUHZ-RP100VHA2
34,100
PUHZ-RP125VHA2
42,700
PUHZ-RP140VHA2
47,800
kW
10.0(4.9-11.4)
12.5(5.5-14.0)
14.0(5.5-15.3)
kW
3.06
3.89
4.65
3.27
3.21
3.01
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
B
Btu/h
0.86
38,200
0.82
47,800
0.83
54,600
kW
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
3.19
3.88
4.69
3.51
3.61
3.41
B
A
B
-
-
-
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
230
Breaker size
Indoor unit
1
A
32
40
Air flow
(Low-High)
CMM
33.5-42
36.5-46
CFM
1183-1483
External pressure
Pa
dB(A)
Sound level
(Low-High)
44-50
(130Pa : 46-52)
External finish
Dimension
1288-1624
70(130)
46-51
(130Pa : 47-53)
Galvanized sheets
W : mm
1415
1715
D : mm
740
H : mm
325
W : inch
55-11/16
67-1/2
D : inch
29-1/8
H : inch
Weight
12-13/16
kg
65
70
lbs
143
154
R1(External thread)
Unit drain pipe
Outdoor unit
Air flow
CMM
Sound level at cooling
CFM
dB(A)
100
3,530
49
Sound level at heating
dB(A)
51
External finish
Dimension
50
52
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
121
116
lbs
267
256
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
53-1/8
kg
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
9
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 10
Indoor unit
PEAD-RP100EA2
PEAD-RP125EA
PEAD-RP140EA
Btu/h
PUHZ-RP100YHA2
34,100
PUHZ-RP125YHA2
42,700
PUHZ-RP140YHA2
47,800
kW
10.0(4.9-11.4)
12.5(5.5-14.0)
14.0(5.5-15.3)
kW
3.06
3.89
4.65
3.27
3.21
3.01
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
B
Btu/h
0.86
38,200
0.82
47,800
0.83
54,600
kW
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
3.19
3.88
4.69
3.51
3.61
3.41
B
A
B
-
-
-
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
400
Breaker size
Indoor unit
3
A
16
Air flow
(Low-High)
CMM
33.5-42
36.5-46
CFM
1183-1483
1288-1624
External pressure
Pa
dB(A)
44-50
Sound level
(Low-High)
70(130)
External finish
Dimension
46-51
(130Pa : 47-53)
(130Pa : 46-52)
Galvanized sheets
W : mm
1415
1715
D : mm
740
H : mm
325
W : inch
55-11/16
67-1/2
D : inch
29-1/8
H : inch
Weight
12-13/16
kg
65
70
lbs
143
154
R1(External thread)
Unit drain pipe
Outdoor unit
Air flow
CMM
Sound level at cooling
CFM
dB(A)
100
3,530
49
Sound level at heating
dB(A)
51
External finish
Dimension
50
52
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
135
130
lbs
298
287
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
53-1/8
kg
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -20˚C, W.B. -20˚C
D.B. 17˚C
10
3. Guaranteed voltage
Indoor unit
198~264V, 50Hz
Outdoor unit
342~457V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
3 phase 400V 50Hz
w
If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 11
Indoor unit
PEAD-RP60GA
PEAD-RP71GA
PEAD-RP100GA
Btu/h
PUHZ-RP60VHA2
20,500
PUHZ-RP71VHA2
24,200
PUHZ-RP100VHA2
34,100
kW
6.0(2.7-6.7)
7.1(3.3-8.1)
10.0(4.9-11.4)
kW
1.68
2.15
3.08
3.57
3.30
3.25
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
A
Btu/h
0.88
23,900
0.83
27,300
0.86
38,200
kW
7.0(2.8-8.2)
8.0(3.5-10.2)
11.0(4.5-14.0)
kW
1.77
2.34
3.23
3.95
3.42
3.41
A
B
B
-
-
-
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
230
Breaker size
Indoor unit
1
A
25
Air flow
(Low-High)
CMM
16.5-21
CFM
582-741
External pressure
Pa
dB(A)
Sound level
(Low-High)
26.5-33
706-883
935-1165
35-38/37-41/37-43
(10/50/70Pa)
40-43/42-45/42-46
(10/50/70Pa)
10/50/70
33-37/35-40/36-42
(10/50/70Pa)
External finish
Dimension
32
20-25
10/50/70
Galvanized sheets
W : mm
1171
1411
D : mm
740
H : mm
W : inch
275
46-1/8
55-9/16
D : inch
29-1/8
H : inch
Weight
Unit drain pipe O.D.
Outdoor unit
42
50
lbs
93
111
mm
32
inch
1-1/4
Air flow
CMM
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
External finish
Dimension
10-13/16
kg
55
1,940
100
3,530
47
49
48
51
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
943
1350
W : inch
37-3/8
D : inch
37-1/8
kg
75
121
lbs
165
267
Weight
Refrigerant pipe size
13 + 1-3/16
H : inch
Gas side O.D.
mm
Liquid side O.D.
15.88
inch
5/8
mm
9.52
inch
Refrigerant pipe length
NOTE:
3/8
Height difference
m
Max. 30
Max. 30
Length
m
Max. 50
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
53-1/8
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Outdoor
D.B. 46˚C
D.B. -5˚C
w1
D.B. 21˚C, W.B. 15˚C
D.B. -11˚C, W.B. -12˚C w2
11
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w1. If optional Air protect guide installed. D.B.-15:
w2. For RP100 D.B. -20:, W.B. -20:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 12
Indoor unit
PEAD-RP100GA
Outdoor unit
Cooling
Capacity
Total input
Btu/h
PUHZ-RP100YHA2
34,100
kW
10.0(4.9-11.4)
kW
3.08
EER
3.25
Energy label class
A
SHF
Heating
Capacity
Total input
Btu/h
0.86
38,200
kW
11.0(4.5-14.0)
kW
3.23
COP
3.41
Energy label class
Booster heater
Power supply
-
Phase
[
3
Cycle
Hz
50
V
400
Voltage
Breaker size
Indoor unit
B
kW
A
16
Air flow
(Low-High)
CMM
26.5-33
CFM
935-1165
External pressure
Pa
dB(A)
Sound level
(Low-High)
10/50/70
40-43/42-45/42-46
(10/50/70Pa)
External finish
Dimension
Weight
Unit drain pipe O.D.
Outdoor unit
Galvanized sheets
W : mm
1411
D : mm
740
H : mm
275
W : inch
55-9/16
D : inch
29-1/8
H : inch
10-13/16
kg
50
lbs
111
mm
32
inch
1-1/4
Air flow
CMM
100
3,530
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
49
51
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Upper limit
Lower limit
Upper limit
Heating
Lower limit
W : mm
943
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
53-1/8
kg
135
lbs
298
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
Ivory Munsell 3Y 7.8/1.1
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -20˚C, W.B. -20˚C
D.B. 17˚C
12
3. Guaranteed voltage
Indoor unit
198~264V, 50Hz
Outdoor unit
342~457V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
3 phase 400V 50Hz
w
If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Page 13
2-3. WALL MOUNTED TYPE
Model name
Indoor unit
PKA-RP35GAL
PKA-RP50GAL
Btu/h
PUHZ-RP35VHA2
12,300
PUHZ-RP50VHA2
15,700
kW
3.6(1.6-4.5)
4.6(2.3-5.4)
kW
1.03
1.63
3.50
2.82
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
C
Btu/h
0.84
14,000
0.74
15,400
kW
4.1(1.6-5.2)
4.5(2.5-6.2)
kW
1.27
1.40
3.23
3.21
C
C
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
[
Cycle
Hz
50
V
230
Breaker size
A
16
CMM
9-10-11-12
CFM
320-355-390-425
External pressure
Pa
dB(A)
36-38-41-43
External finish
Dimension
White Munsell 0.70Y 8.59/0.97
990
D : mm
235
H : mm
340
W : inch
39
D : inch
9-1/4
H : inch
13-3/8
kg
16
Unit drain pipe O.D.
lbs
35
mm
20
inch
13/16
Air flow
CMM
35
1,240
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
External finish
Dimension
800
D : mm
300+23
H : mm
600
W : inch
31-1/2
D : inch
11-13/16 + 7/8
H : inch
23-5/8
kg
45
Gas side O.D.
Upper limit
Lower limit
Upper limit
Heating
Lower limit
lbs
99
mm
12.7
inch
1/2
mm
6.35
inch
1/4
Height difference
m
Max. 30
Length
m
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
46
W : mm
Liquid side O.D.
NOTE:
44
Ivory Munsell 3Y 7.8/1.1
Weight
Refrigerant pipe length
0
W : mm
Weight
Refrigerant pipe size
1
Air flow
(Low-Medium2-Medium1-High)
Sound level
(Low-Medium2-Medium1-High)
Outdoor unit
-
Phase
Voltage
Indoor unit
-
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
13
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 14
Indoor unit
PKA-RP60FAL
PKA-RP71FAL
PKA-RP100FAL
Btu/h
PUHZ-RP60VHA2
20,500
PUHZ-RP71VHA2
24,200
PUHZ-RP100VHA2
34,100
kW
6.0(2.7-6.7)
7.1(3.3-8.1)
10.0(4.9-11.4)
kW
1.55
1.98
2.93
3.87
3.59
3.41
A
A
A
Btu/h
0.83
23,900
0.77
27,300
0.77
38,200
kW
7.0(2.8-8.2)
7.6(3.5-10.2)
11.2(4.5-14.0)
kW
2.01
2.23
3.25
3.48
3.41
3.45
B
B
B
-
-
-
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
V
230
Voltage
Breaker size
Indoor unit
1
A
25
32
Air flow
(Low-High)
CMM
15-20
22-28
CFM
530-705
External pressure
Pa
dB(A)
39-45
W : mm
1400
Sound level
(Low-High)
External finish
Dimension
780-990
0
41-46
Munsell 3.4Y 7.7/0.8
1680
D : mm
235
H : mm
340
W : inch
55-1/8
D : inch
H : inch
Weight
Unit drain pipe O.D.
13-3/8
kg
24
lbs
53
Air flow
CMM
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
13/16
55
1,940
47
49
51
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
943
Gas side O.D.
Liquid side O.D.
1350
37-3/8
D : inch
Refrigerant pipe size
100
3,530
48
W : inch
Weight
62
20
External finish
Dimension
28
mm
inch
Outdoor unit
66-1/8
9-1/4
13 + 1-3/16
H : inch
37-1/8
53-1/8
kg
75
121
lbs
165
mm
267
15.88
inch
5/8
mm
9.52
inch
Refrigerant pipe length
NOTE:
m
Max. 30
Max. 30
Length
m
Max. 50
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
3/8
Height difference
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Outdoor
D.B. 46˚C
D.B. -5˚C
w1
D.B. 21˚C, W.B. 15˚C
D.B. -11˚C, W.B. -12˚C w2
14
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w1. If optional Air protect guide installed. D.B.-15:
w2. For RP100 D.B. -20:, W.B. -20:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 15
Indoor unit
PKA-RP100FAL
Outdoor unit
Cooling
Capacity
Total input
Btu/h
PUHZ-RP100YHA2
34,100
kW
10.0(4.9-11.4)
kW
2.93
EER
3.41
Energy label class
A
SHF
Heating
Capacity
Total input
Btu/h
0.77
38,200
kW
11.2(4.5-14.0)
kW
3.25
COP
3.45
Energy label class
Booster heater
Power supply
-
Phase
[
3
Cycle
Hz
50
V
400
Voltage
Breaker size
Indoor unit
B
kW
A
16
Air flow
(Low-High)
CMM
22-28
CFM
780-990
External pressure
Pa
dB(A)
41-46
Sound level
(Low-High)
External finish
Dimension
Weight
Unit drain pipe O.D.
Outdoor unit
Munsell 3.4Y 7.7/0.8
W : mm
1680
D : mm
235
H : mm
340
W : inch
66-1/8
D : inch
9-1/4
H : inch
13-3/8
kg
28
lbs
62
mm
20
inch
13/16
Air flow
CMM
100
3,530
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
49
51
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
53-1/8
kg
135
lbs
298
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
0
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -20˚C, W.B. -20˚C
D.B. 17˚C
15
3. Guaranteed voltage
Indoor unit
198~264V, 50Hz
Outdoor unit
342~457V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
3 phase 400V 50Hz
w
If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Page 16
2-4. CEILING SUSPENDED TYPE
Model name
Indoor unit
PCA-RP50GA
PCA-RP60GA
PCA-RP71GA
Btu/h
PUHZ-RP50VHA2
16,000
PUHZ-RP60VHA2
20,500
PUHZ-RP71VHA2
24,200
kW
4.7(2.3-5.4)
6.0(2.7-6.7)
7.1(3.3-8.1)
kW
1.67
1.63
2.14
2.81
3.68
3.32
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
C
A
A
Btu/h
0.76
18,800
0.86
23,900
0.74
27,300
kW
5.5(2.5-6.6)
7.0(2.8-8.2)
7.6(3.5-10.2)
kW
1.71
2.03
2.23
3.22
3.45
3.41
C
B
B
-
-
-
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
230
Breaker size
Indoor unit
1
A
16
25
Air flow
CMM
10-11-12-13
14-15-16-18
(Low-Medium2-Medium1-High)
External pressure
CFM
355-390-425-460
495-530-565-635
Pa
dB(A)
0
0
37-38-40-42
37-39-41-43
W : mm
1000
Sound level
(Low-Medium2-Medium1-High)
External finish
Dimension
White Munsell 0.70Y 8.59/0.97
1310
D : mm
680
H : mm
210
W : inch
39-3/8
51-9/16
D : inch
26-3/4
H : inch
Weight
Unit drain pipe I.D.
8-1/4
kg
27
34
lbs
60
75
mm
26
inch
Outdoor unit
Air flow
CMM
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
1
35
1,240
55
1,940
44
47
46
External finish
Dimension
W : mm
800
950
D : mm
300+23
330+30
H : mm
600
943
W : inch
31-1/2
37-3/8
D : inch
11-13/16 + 7/8
13 + 1-3/16
H : inch
23-5/8
37-1/8
kg
45
75
lbs
99
165
15.88
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
mm
12.7
inch
1/2
5/8
mm
6.35
9.52
inch
1/4
3/8
Height difference
m
Max. 30
Max. 30
Length
m
Max. 50
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
48
Ivory Munsell 3Y 7.8/1.1
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
16
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 17
Indoor unit
PCA-RP100GA
PCA-RP125GA
PCA-RP140GA
Btu/h
PUHZ-RP100VHA2
34,100
PUHZ-RP125VHA2
42,700
PUHZ-RP140VHA2
47,800
kW
10.0(4.9-11.4)
12.5(5.5-14.0)
14.0(5.5-15.3)
kW
2.92
3.88
4.65
3.42
3.22
3.01
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
B
Btu/h
0.75
38,200
0.77
47,800
0.75
54,600
kW
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
3.26
4.11
4.60
3.44
3.41
3.48
B
B
B
-
-
-
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
230
Breaker size
Indoor unit
1
A
32
40
Air flow
CMM
20-21-23-25
27-30-32-34
(Low-Medium2-Medium1-High)
External pressure
CFM
705-840-810-885
955-1060-1130-1200
Pa
dB(A)
0
40-41-43-45
W : mm
1310
Sound level
(Low-Medium2-Medium1-High)
External finish
Dimension
0
41-43-45-46
White Munsell 0.70Y 8.59/0.97
1620
D : mm
680
H : mm
W : inch
270
51-9/16
63-3/4
D : inch
26-3/4
H : inch
Weight
Unit drain pipe I.D.
Outdoor unit
10-5/8
kg
37
43
45
lbs
82
95
99
mm
26
inch
1
Air flow
CMM
Sound level at cooling
CFM
dB(A)
dB(A)
100
3,530
Sound level at heating
49
50
51
External finish
Dimension
52
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
53-1/8
kg
121
116
lbs
267
256
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
42-44-46-48
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
17
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 18
Indoor unit
PCA-RP100GA
PCA-RP125GA
PCA-RP140GA
Btu/h
PUHZ-RP100YHA2
34,100
PUHZ-RP125YHA2
42,700
PUHZ-RP140YHA2
47,800
kW
10.0(4.9-11.4)
12.5(5.5-14.0)
14.0(5.5-15.3)
kW
2.92
3.88
4.65
3.42
3.22
3.01
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
A
B
Btu/h
0.75
38,200
0.77
47,800
0.75
54,600
kW
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
3.26
4.11
4.60
3.44
3.41
3.48
B
B
B
-
-
-
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
400
Breaker size
Indoor unit
3
A
16
Air flow
CMM
20-21-23-25
27-30-32-34
(Low-Medium2-Medium1-High)
CFM
705-840-810-885
955-1060-1130-1200
External pressure
Pa
dB(A)
40-41-43-45
W : mm
1310
Sound level
(Low-Medium2-Medium1-High)
0
0
External finish
Dimension
41-43-45-46
White Munsell 0.70Y 8.59/0.97
1620
D : mm
680
H : mm
270
W : inch
51-9/16
63-3/4
D : inch
26-3/4
H : inch
Weight
Unit drain pipe I.D.
Outdoor unit
10-5/8
kg
37
43
45
lbs
82
95
99
mm
26
inch
1
Air flow
CMM
Sound level at cooling
CFM
dB(A)
dB(A)
100
3,530
Sound level at heating
49
50
51
External finish
Dimension
52
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
53-1/8
kg
135
130
lbs
298
287
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
42-44-46-48
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -20˚C, W.B. -20˚C
D.B. 17˚C
18
3. Guaranteed voltage
Indoor unit
198~264V, 50Hz
Outdoor unit
342~457V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
3 phase 400V 50Hz
w
If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 19
Indoor unit
PCA-RP71HA
PCA-RP125HA
PCA-RP125HA
Btu/h
PUHZ-RP71VHA2
24,200
PUHZ-RP125VHA2
42,700
PUHZ-RP125YHA2
42,700
kW
7.1(3.3-8.1)
12.5(5.5-14.0)
12.5(5.5-14.0)
kW
2.21
3.88
3.88
3.21
3.22
3.22
A
A
A
Btu/h
0.74
27,300
0.77
47,800
0.77
47,800
kW
7.6(3.5-10.2)
13.8(5.0-16.0)
13.8(5.0-16.0)
kW
2.23
4.05
4.05
3.41
3.41
3.41
B
B
B
-
-
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
[
Cycle
Hz
50
50
V
230
400
Breaker size
1
A
3
25
16
Air flow
(Low-High)
CMM
17-19
30-38
CFM
600-670
1060-1350
External pressure
Pa
dB(A)
0
0
34-38
44-50
W : mm
1136
Sound level
(Low-High)
External finish
Dimension
Stainless steel
1520
D : mm
650
H : mm
280
W : inch
44-3/4
D : inch
59-7/8
25-5/8
H : inch
Weight
Unit drain pipe I.D.
11
kg
41
56
lbs
90
124
mm
26
inch
Outdoor unit
1
Air flow
CMM
55
1,940
Sound level at cooling
CFM
dB(A)
100
3,530
47
50
Sound level at heating
dB(A)
48
52
W : mm
950
950
D : mm
330+30
330+30
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Ivory Munsell 3Y 7.8/1.1
H : mm
943
1350
W : inch
37-3/8
37-3/8
D : inch
13 + 1-3/16
13 + 1-3/16
H : inch
37-1/8
kg
75
116
lbs
165
256
mm
15.88
53-1/8
130
287
15.88
inch
5/8
5/8
mm
9.52
9.52
inch
3/8
3/8
Height difference
m
Max. 30
Max. 30
Length
m
Max. 50
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
-
Phase
Voltage
Indoor unit
kW
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Outdoor
D.B. 46˚C
D.B. -5˚C
w1
D.B. 21˚C, W.B. 15˚C
D.B. -11˚C, W.B. -12˚C w2
19
3. Guaranteed voltage
198~264V, 50Hz (RP125Y : 342~457V, 50Hz)
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
V: Single phase 230V 50Hz, Y: 3 phase 400V 50Hz
w1. If optional Air protect guide installed. D.B.-15:
w2. For RP125 D.B. -20:, W.B. -20:
OCS05A-1.qxp
06.5.15 0:50 PM
Page 20
2-5. FLOOR STANDING TYPE
Model name
Indoor unit
PSA-RP71GA
Outdoor unit
Cooling
Capacity
Total input
Btu/h
PUHZ-RP71VHA2
24,200
kW
7.1(3.3-8.1)
kW
EER
Energy label class
A
SHF
Heating
Capacity
Total input
Btu/h
0.73
27,300
kW
7.6(3.5-10.2)
kW
COP
Power supply
B
kW
-
Phase
[
1
Cycle
Hz
50
V
230
Voltage
Breaker size
Indoor unit
A
25
Air flow
(Low-High)
CMM
15-18
CFM
530-635
External pressure
Pa
dB(A)
40-45
Sound level
(Low-High)
External finish
Dimension
Weight
Unit drain pipeO.D.
Outdoor unit
White Munsell 0.70Y 8.59/0.97
600
D : mm
270
H : mm
1900
W : inch
23-5/8
D : inch
10-5/8
H : inch
74-13/16
kg
43
lbs
98
mm
20
inch
13/16
Air flow
CMM
55
1,940
Sound level at cooling
CFM
dB(A)
Sound level at heating
dB(A)
Dimension
Weight
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Upper limit
Lower limit
Upper limit
Heating
Lower limit
47
48
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
943
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
37-1/8
kg
75
lbs
165
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
0
W : mm
External finish
Refrigerant pipe size
2.23
3.41
Energy label class
Booster heater
2.20
3.23
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
20
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 21
Indoor unit
PSA-RP100GA
PSA-RP125GA
PSA-RP140GA
Btu/h
PUHZ-RP100VHA2
34,100
PUHZ-RP125VHA2
42,700
PUHZ-RP140VHA2
47,800
kW
10.0(4.9-11.4)
12.4(5.5-14.0)
13.8(5.5-15.3)
kW
2.99
4.12
4.91
3.34
3.01
2.81
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
B
C
Btu/h
0.81
38,200
0.75
47,800
0.74
54,600
kW
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
3.28
4.11
4.97
3.41
3.41
3.22
B
B
C
-
-
-
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
230
Breaker size
Indoor unit
1
A
32
CMM
24-31
26-33
27-35
CFM
850-1060
920-1165
955-1240
External pressure
Pa
dB(A)
Sound level
(Low-High)
0
44-49
External finish
Dimension
46-51
600
D : mm
350
H : mm
1900
W : inch
23-5/8
D : inch
13-3/4
H : inch
74-13/16
Unit drain pipeO.D.
kg
51
53
lbs
112
117
mm
20
inch
13/16
Air flow
CMM
100
3,530
Sound level at cooling
CFM
dB(A)
49
Sound level at heating
dB(A)
51
External finish
Dimension
50
52
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
53-1/8
kg
121
116
lbs
267
256
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
47-52
White Munsell 0.70Y 8.59/0.97
W : mm
Weight
Outdoor unit
40
Air flow
(Low-High)
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
21
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
Model name
Page 22
Indoor unit
PSA-RP100GA
PSA-RP125GA
PSA-RP140GA
Btu/h
PUHZ-RP100YHA2
34,100
PUHZ-RP125YHA2
42,700
PUHZ-RP140YHA2
47,800
kW
10.0(4.9-11.4)
12.4(5.5-14.0)
13.8(5.5-15.3)
kW
2.99
4.12
4.91
3.34
3.01
2.81
Outdoor unit
Cooling
Capacity
Total input
EER
Energy label class
A
B
C
Btu/h
0.81
38,200
0.75
47,800
0.74
54,600
kW
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
3.28
4.11
4.97
3.41
3.41
3.22
B
B
C
-
-
-
SHF
Heating
Capacity
Total input
COP
Energy label class
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
400
Breaker size
Indoor unit
3
A
16
Air flow
(Low-High)
CMM
24-31
26-33
27-35
CFM
850-1060
920-1165
955-1240
External pressure
Pa
dB(A)
44-49
46-51
Sound level
(Low-High)
0
External finish
Dimension
White Munsell 0.70Y 8.59/0.97
W : mm
600
D : mm
350
H : mm
1900
W : inch
23-5/8
D : inch
13-3/4
H : inch
74-13/16
Weight
Unit drain pipeO.D.
Outdoor unit
kg
51
51
53
lbs
112
112
117
mm
20
inch
13/16
Air flow
CMM
100
3,530
Sound level at cooling
CFM
dB(A)
49
Sound level at heating
dB(A)
51
External finish
Dimension
50
52
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
53-1/8
kg
135
130
lbs
298
287
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
47-52
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -20˚C, W.B. -20˚C
D.B. 17˚C
22
3. Guaranteed voltage
Indoor unit
198~264V, 50Hz
Outdoor unit
342~457V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
3 phase 400V 50Hz
w
If optional Air protect guide installed. D.B.-15:
OCS05A-1.qxp
06.5.15 0:50 PM
3
Page 23
OUTLINES AND DIMENSIONS
Unit : mm
INDOOR UNIT
PLA-RP35AA
PLA-RP50AA PLA-RP60AA PLA-RP71AA
PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
Ceiling hole
860 - 910
20 - 45
20 - 45
159
20 - 45
810
Suspension bolt pitch
Fresh air intake
16
197
{125
Burring hole pitch
120 _
158
20 - 45
3 - {2.8
Burring hole
120_
159
C
89
Detail drawing of fresh air intake
98
192
{150
159
840
{100
(Cut out hole)
Suspension bolt M10
or W3/8
1
Ceiling surface
Feeding hole
(Drain pump)
286
374
60
860 - 910
Ceiling hole
Terminal block
840
14 - {2.8
Burring hole
Suspension bolt pitch
605
Branch duct hole
350
{175
167
155
159
130
70_
100
90 100 100 90
Branch duct hole
(Cut out hole)
Drain pipe
VP-25connection
(O.D.{32)
High efficiency filter
& Fresh air intake casement (option)
17 +50
B
30
190
135
Ceiling surface
17
Control wire entry
Power line entry
Suspension bolt lower edge
+5
0
105
50 - 70
170
140
A
2
577
Air intake hole
Air intake grille
Grille
Drain hole
M
A
M
Emergency operation switch (cooling)
950
Emergency operation switch (heating)
Auto vane
577
Air intake hole
(WIRELESS PANEL)
411
Air outlet hole
A
DEFROST/STAND BY lamp
M
Receiver
77
Operation lamp
M
51
411
Air outlet hole
950
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
1 LIQUID SIDE
2 GAS SIDE
RP35, 50
RP60
RP71
RP100, 125, 140
[6.35
[6.35
—
—
[9.52
[9.52
[9.52
[9.52
[12.7
—
—
—
[15.88
[15.88
[15.88
[15.88
—
—
—
[19.05
Models
A
B
C
PLA-RP60,71AA
241
258
80
PLA-RP100,125,140AA2
281
298
84
PLA-RP35,50AA
Factory flare nut attachment to the heat-exchanger.
23
Vane motor
77
51
Branch
duct hole
OCS05A-1.qxp
06.5.15 0:50 PM
Page 24
Unit : mm
PEAD-RP35EA2
PEAD-RP50EA
PEAD-RP60EA
Model
A
RP35,50 772
RP60
B
305
1012 280
w Setting at shipment
F
G
R410A Outdoor unit : 6.35 w R410A Outdoor unit : 12.7 w
R407C Outdoor unit : 9.52 R407C Outdoor unit : 15.88
Outdoor unit (SUZ) : 6.35
15.88
290 1070 1044
R407C Outdoor unit : 9.52 w
C
D
E
-
830
804
Service space:500 or more
50~150 29
Refrigerant piping flare connection (liquid [ F copper tube):HP
Refrigerant piping flare connection (gas [G copper tube):LP
Drain R1(External thread)
Electrical parts box
Drain Pump (Option)
Set
Drain Pipe (Option) ... Flexible joint VP-25(I.D. [32)
Filter
55
Access door
81
C
B
81
197
450
Lifting bolt hole
(14×22)
C
13
13
30
277
45 80
85
282
288
256
176
Air inlet
E
6
40
24
10
179
227
2
35
1
243
109
3.5
21
10
10- [3 (RP35,50)
12- [3 (RP60)
D
30
61
4
In case of rear inlet
81
A
44 75
640
30
B
10
18
56
355
365~465
159
1
2
3
4
5
6
7
10- [3 (RP35,50)
12- [3 (RP60)
A
10
450
5
7
3.5
Air outlet
3
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
In case of bottom inlet
10- [3 (RP35,50)
12- [3 (RP60)
Air outlet
10
7
40
15
176
256
10
3.5
81
C
B
81
A
Air inlet
PEAD-RP71EA
PEAD-RP100EA2
PEAD-RP125EA
PEAD-RP140EA
Service space:500 or more
Air inlet
375
Lifting bolt hole
(14x22)
12-[3
44
E
75
D
243
6
5
7
Air outlet
4
C
A
13
307
45 122
113
1
81
80
2
35
53
B
365~465
323
308
30
10
680
C
197
450
169
20
30
12-[3
A
81
81
210
7
140
6
282
5
3.5
30
4
40
3
Refrigerant piping flare connection (liquid [9.52 copper tube):HP
Refrigerant piping flare connection (gas [F copper tube):LP
Drain R1 (External thread)
Electrical parts box
Drain Pump (Option)
Set
Drain Pipe (Option) ... Flexible joint VP25(I.D.[32)
Filter
319
261
181
2
3.5
1
55
Access door
3
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
24
B
81
10
F
A
B
C
D
E
Model
15.88
RP71 1012 280 290 1070 1044
RP100,125 1252 360 370 1310 1284 R410A Outdoor unit : 15.88 w
RP140 1552 460 470 1610 1584 R407C outdoor unit : 19.05
w Setting at shipment
10
50~150 29
450
13
30
OCS05A-1.qxp
06.5.15 0:50 PM
Page 25
Unit : mm
PEAD-RP60GA
PEAD-RP71GA
PEAD-RP100GA
Model
A
B
C
D
E
RP60 1125 1090 1050 1012 7
RP71 1125 1090 1050 1012 7
F
G
H
Outdoor unit(SUZ) : 6.35
Other outdoor unit : 9.52 w
840 8
9.52
840 8
RP100 1365 1330 1290 1252 9 1080 10
9.52
w Setting at shipment
25
J
15.88
15.88
R410A Outdoor unit : 15.88 w
R407C Outdoor unit : 19.05
360
405
420
495
Sleeve w1
[90
MITSUBISHI ELECTRIC
150 or more
m r.SLI m
Through hole
[90~[100
205
245
70 21
R52.5
Liquid pipe
Gas pipe
990
705 Air outlet
80
715 Air intake
400
12-Louvers(manual)
340 Air intake
ëOñ Å@ÇeÇqÇnÇmÇs
449
581
ÅrÇoÇoÅqÅ@
700 (Flexible hose total length800)
ÅrÇoÇoÅqÅ@
395
Auto vane
280 Air intake
225
40
86
54
70 35
MITSUBISHI ELECTRIC
mr.SLIm
190
160
235
ON STAND COOL HEAT
OFF BY
233
153
(Right side piping
installation)
Terminal block for
power supply (Heater (PKH-P35, 50GALH only))
Terminal block to
outdoor unit
Service panel
(Power supply access)
—
[9.52
—
[6.35
[9.52
[12.7
P35, 50
RP35, 50
INDOOR UNIT
PKA-RP35GAL PKA-RP50GAL
[15.88
[15.88
: Factory flare nut attachment to the heat - exchanger.
GAS SIDE
LIQUID SIDE
Knock out hole for right piping
Refrigerant pipe.Drain pipe.
Wiring hole
Less than 15
Knock out hole for under piping
Refrigerant piping.Drain pipe.
Wiring hole
235
60
Right side
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
ëOñ Å@ÇeÇqÇnÇmÇs
Front view(to open the grille)
Filter grip
50
Lower side
(Left side piping
installation)
Unit drain pipe O.D.20
35
272
310
322
230
190
130
0
35
55
80
(Necessary clearance for
Unit installation)
Less than 130
Right side
60
340
w1 Sleeves are available on the market.
w2 This size shows the lower end of through hole.
Right-rear
piping hole
R52.5
Unit center
Installation plate
balance point hole
Knock out hole for
right-rear piping
5
Model
35, 50
2.
Knock out hole for
left-rear piping
300
R5
Left-rear
piping hole
49-[5hole
for tapping screw
245
HEAT
95
Details of installation plate
190
230
210
14-[14hole
for bolts
5
STAND COOL
BY
150
50 or more
135
2.
R5
ON
OFF
75
32
20
0
35
0
26
170
190
30 or more
180 or more
260
Allowing clearances
Front view
320
345
53
79
Knock out hole for left piping
Refrigerant pipe.Drain pipe.Wiring hole.
495
Front view
80
Left side
425
198 Air intake
60
280
06.5.15 0:50 PM
31
245
70 21
OCS05A-1.qxp
Page 26
Unit : mm
OCS05A-1.qxp
06.5.15 0:50 PM
Page 27
Unit : mm
PKA-RP60FAL
PKA-RP71FAL
Display section
62.5
Top
45
235
235
45
235
45
Defrosting Initial heating lamp
13
235
Power lamp
Front
Right side
1400
Left side
Emergency switch(Heat)
Emergency switch(Cool)
Receiving
section
235
Knock out hole for right piping
Refrigerant pipe. Drain pipe
340
A
197
1090 Air intake
Terminal block for indoor/outdoor connecting line
15
Terminal block for heater (PKH only)
Liquid pipe
Knock out hole for
left piping
C
Gas pipe
25
Drain hose for
left-hand side piping
58
42
Bolt
Drain hose O.D.20
Drain hose
1110
183
55 (Gas pipe) 107
120
111
(Liquid pipe)
Lower side
Liquid pipe [9.52(3/8F)
Gas pipe [15.88(5/8F)
Auto vanes
1120
240
552 Air outlet
552 Air outlet
Louvers (manual)
Under panel
Removable at left-hand
side piping
Knock out hole for under-piping
B
Refrigerant pipe. Drain pipe
Unit center
990
245
455
Knock out hole for wiring
91
225
240
180
12-ø6 hole for
tapping screw
280
314
610
90
Rear piping opening
Range for left rear piping opening
27
C
30
100
B
37
74
39
98 32
39
37
74
4
32-ø12 hole for bolt
30
60
184
30
66-ø6 hole for
tapping screw
A
30
37
65
on left-hand side
Drainage range
on right-hand side
100
4 39
18
285
19
10
30
80
29
280
Wall fixture
10 91=(910)
900
18 Drainage range
OCS05A-1.qxp
06.5.15 0:50 PM
Page 28
Unit : mm
PKA-RP100FAL
Top
62.5
Display section
45
235
45
235
45
235
235
45
13
235
Receiving
section
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
Power lamp
Front
Left side
Knock out hole for right piping
Right side
1680
235
1370 Air intake
340
197
A
Knock out hole for left piping
C
Terminal block for indoor/outdoor connecting line
15
Terminal block for heater (PKH only)
Liquid pipe
Gas pipe
25
Drain hose O.D.20
Drain hose
Drain hose for left-hand side piping
58
42
Bolt
1110 Drain hose
183
Lower side
1400
55 (Gas pipe) 102
120
111
(Liquid pipe)
240
694 Air outlet
Use the current nuts meeting the pipe size
of the outdoor unit.
Available pipe size
RP100
P100
694 Air outlet
LIQUID SIDE [9.52
[9.52
[15.88
[19.05
[19.05
: Factory flare nut attachment to the
heat-exchanger.
GAS SIDE
Louvers (manual)
B
Under panel
(Removable at left-hand side piping)
Auto vane
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Unit center
1270
Knock out hole for wiring
Drainage range
91
on right-hand side
60
295
225
Range for left rear piping opening
240
180
280
750
30
41-ø12 hole for bolt
314
90
Rear piping opening
Range for left rear piping opening
12-ø6 hole for tapping screw
28
A
30
B
C
30
100
Drainage range
on left-hand side
285
19
37
74
39
98 32
39
13 91=(1183)
900
37
74
4
18
37
65
18
184
30
84-ø6 hole for
tapping screw
245
595
10
30
80
29
280
Wall fixture
100
4 39
Unit out line
OCS05A-1.qxp
06.5.15 0:50 PM
Page 29
Unit : mm
INDOOR UNIT
PCA-RP50GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
140
70
320
150
80
17
6
933 (suspension bolt pitch)
85
983
15
81 76
7
226
2
157
Electrical box
180
210
70
904
182
1000
gas
241
(Drainage)
254
506
680
56
Air outlet
liquid
201
Air intake
161
90
918
5
1 4
38
131
161
46 175
1
8
38 79
Ceiling
6~7
42
32
Electrical box [Front view]
179
3
2
1
2
3
4
5
6
7
8
Use the current nuts meeting the pipe size of the outdoor unit.
86
138
171
263
352
525
Drainage pipe connection (26mm I.D.)
Drainage pipe connection (for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection (gas pipe side/flared connection)
Refrigerant-pipe connection (liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Available pipe size
RP50
P50
5 LIQUID SIDE [6.35
928
[9.52
4 GAS SIDE
When electrical
box is pulled
down
[9.52
[12.7
[15.88
[15.88
: Factory flare nut attachment to the heat-exchanger.
29
OCS05A-1.qxp
06.5.15 0:50 PM
Page 30
Unit : mm
PCA-RP60GA
PCA-RP71GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
140
70
320
150
80
17
6
1240 (suspension bolt pitch)
85
1290
Electrical box
15
2
226
210
180
81 76
7
157
70
1214
182
(liquid)
1310
201
(5/8F gas)
241
(Drainage)
254
506
680
56
Air outlet
Air intake
161
90
1228
38
131
161
525
1 4
46 175 1
Ceiling
5
8
3879
32
[ Front view ]
6~7
42
179
3
Electrical box
2
1
2
3
4
5
6
7
8
Drainage pipe connection (26mm I.D.)
Drainage pipe connection (for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection (gas pipe side/flared connection)
Refrigerant-pipe connection (liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Use the current nuts meeting the pipe size of the outdoor unit.
86
138
171
263
416
1235
Available pipe size
RP60
RP71,P60,P71
5 LIQUID SIDE [6.35
[9.52
[9.52
4 GAS SIDE
When electrical
box is pulled
down
[15.88
[15.88
: Factory flare nut attachment to the heat-exchanger.
30
OCS05A-2.qxp
06.5.15 0:52 PM
Page 31
Unit : mm
PCA-RP100GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
140
70
320
150
80
18
6
1240 (suspension bolt pitch)
87
70
16
2
229
217
270
81 96
7
207
Electrical box
1214
182
(3/8F liquid)
1310
198
(5/8F, 3/4F gas)
245
(Drainage)
254
506
680
56
Air outlet
Air intake
161
90
1228
Ceiling
8
5
1
4
6~7
38
192
45
42
236
38 140
1
93
[ Front view ]
160
239
3
Electrical box
2
525
86
138
171
263
1
2
3
4
5
6
7
8
Drainage pipe connection (26mm I.D.)
Drainage pipe connection (for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection (gas pipe side/flared connection)
Refrigerant-pipe connection (liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
RP100
P100
5 LIQUID SIDE
687
1235
[9.52
[9.52
[15.88
[19.05
[19.05
4 GAS SIDE
When electrical
box is pulled
down
:Factory flare nut attachment to the heat-exchanger.
31
OCS05A-2.qxp
06.5.15 0:52 PM
Page 32
Unit : mm
PCA-RP125GA
PCA-RP140GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
140
70
320
150
80
18
6
1547(suspension bolt pitch)
87
70
16
229
2
217
270
81 96
7
207
Electrical box
1524
182
(3/8F liquid)
1620
198
(5/8F, 3/4F gas)
245
(Drainage)
254
506
680
56
Air outlet
Air intake
161
90
1535
[ Front view ]
Ceiling
8
5
1
4
192
236
Drainage pipe connection (26mm I.D.)
Drainage pipe connection (for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection (gas pipe side/flared connection)
Refrigerant-pipe connection (liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
6~7
38
45
42
160
38 140
1
93
Electrical box
239
3
2
1
2
3
4
5
6
7
8
525
687
1545
When electrical
box is pulled
down
86
138
171
263
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
RP125,140 P125,140
5 LIQUID SIDE
[9.52
[9.52
4 GAS SIDE
[15.88
[19.05 [19.05
:Factory flare nut attachment to the heat-exchanger.
32
<Air intake>
1098
1136
986 <Air
outlet>
bolt pitch>
75
21
110
<gas>
<liquid>
175
Suspension bolt
75
80
70
Filter element for the exchange
model:PAC-SG38KF-E (12pcs.)
360
handle
3
or more
100
<Flexible hose(accessory)>
650
289
<Suspension bolt pitch>
320
495
<Filter contour dimension>
Filter (3-pieces)
Inspection port
(pipe sensor)
<Air outlet>
1
243
1
Rear wall
Adjustable part
85
45
1136
Ceiling
176
105
140
18
318
2
4
or more
100
366
6
8
7
0
90˚
Terminal block box
[2
22
[ 20
9
130
250
Less than
Allowing clearances
480
(122 )
Refrigerant-pipe connection(gas pipe side/flared connection : 5/8F)
Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8F)
Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
Knock out hole for behind refrigerant-piping arrangement
Knock out hole for upper refrigerant-pipe arrangement
Knock out hole for wiring arrangement : 2- [ 27
Terminal block(indoor/outdoor connecting line)
Terminal block(remote controller)
Knock out hole (duct for fresh air intake): 2- [ 200
Option parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pc.)
43
1
2
3
4
5
6
7
8
9
75
1224
1180 <Suspension
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
The half bottom of FAN CASING
can be separated.
Electrical box
102
110
258
254
295
197
<Air intake>
70~90
13
2
15
650
280
16
288
120
165
90
Less than
210
38
130
300
5
Less than
Terminal block box
500
33
or more
PCA-RP71HA
2~3
06.5.15 0:52 PM
(Gap to ceiling)
OCS05A-2.qxp
Page 33
Unit : mm
Use the current nuts meeting the pipe size
of the outdoor unit.
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
The half bottom of FAN CASING
can be separated.
<Air intake>
1482
1520
outlet>
75
21
1 GAS SIDE
2 LIQUID SIDE
Available pipe size
<Suspension bolt pitch>
1370 <Air
1564
Suspension bolt
80
650
289
70
<Suspension bolt pitch>
320
495
[ 19.05
[ 15.88
[ 9.52
RP125
or more
85
140
2
4
Rear wall
298
176
105
Adjustable part
3
1
18
45
1520
Ceiling
246
6
440
(122)
7
440
or more
100
9
[2
22
0
[20
250
Less than
Allowing clearances
Terminal block box
8
: Factory flare nut attachment to the heat-exchanger
Filter element for the exchange
model:PAC-SG38KF-E (12pcs.)
360
handle
100
<Flexible hose(accessory)>
75
<Filter contour dimension>
Filter (4-pieces)
Inspection port
(pipe sensor)
75
1608
197
<liquid>
1
243
Electrical box
43
110
102
110
258
254
295
175
<Air outlet>
<Air intake>
70~90
13
120
90
<gas>
280
16
288
210
38
2
650
165
Refrigerant-pipe connection(gas pipe side/flared connection : 5/8F, 3/4F)
Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8F)
Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
Knock out hole for behind refrigerant-piping arrangement
Knock out hole for upper refrigerant-pipe arrangement
Knock out hole for wiring arrangement : 2- [ 27
Terminal block(indoor/outdoor connecting line)
Terminal block(remote controller)
Knock out hole (duct for fresh air intake) : 2- [ 200
Option parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pc.)
300
1
2
3
4
5
6
7
8
9
Less than
130
Terminal block box
15
Less than
130
90˚
5
500
34
or more
PCA-RP125HA
2~3
06.5.15 0:52 PM
(Gap to ceiling)
OCS05A-2.qxp
Page 34
Unit : mm
10
10
38
controller
Front side
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
235
70
600
71
250
270
180
130
Metal fixture
against overturning
530
520
260
240
370
340
125
132
15
111
Knock out hole
for branch duct
100
130 130
38
20
10
827
30
130
50
260
Knock out hole for
under-piping(120 70 oval)
Terminal block for
heater power supply 22
(Only PSH-P•GAH)
Terminal block for
indoor/outdoor
connection.
Knock out hole
for bottom fixing
95
50
Knock out hole for
wiring.[27
(Provided on both sides)
Front side
Rear side
A
105
Knock out hole
for under-piping
Drain pipe
Gas pipe [15.88(5/8F)
Liquid pipe [ 9.52(3/8F)
Knock out hole for piping and wiring
(140 80 oval)
47
95
Electrical parts box
277
461
20
20
160
218
VIEW "A"
100
240
115
40
1900
175
123
714
766
608
216
90
767
143
55
Rear side
110
35
590
40
186
66
100 or more
Front 1,000 or more
1. Service access allows for
insertion of screw driver.
2. Adjustable
100 or more
06.5.15 0:52 PM
480
INDOOR UNIT
PSA-RP71GA
1
2
300 or more
5 or more
OCS05A-2.qxp
Page 35
Unit : mm
controller
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
315
70
600
71
330
350
260
130
Metal fixture
against overturning
530
520
260
240
370
340
125
130 130
10
10
38
38
Front side
100
15
111
Knock out hole
for branch duct
130
50
260
20
132
40
1900
240
Knock out hole for
95
under-piping(120 70 oval)
Knock out hole for
wiring.[27 (Provided on both sides)
A
20
461
Front side
Rear side
105
[15.88(5/8F)
[19.05(3/4F)
Gas pipe
Drain pipe
[9.52(3/8F)
Liquid pipe
Knock out hole for piping and wiring
(140 80 oval)
47
95
[ 9.52
—
[ 19.05
[ 9.52
[ 15.88
[ 19.05
40
261
66
100 or more
Front 1,000 or more
1. Service access allows for
insertion of screw driver.
2. Adjustable
100 or more
RP100,125,140 P100,125,140
: Factry flare nut attachment to
the heat-exchanger
GAS SIDE
LIQUID SIDE
Available pipe size
Use the current nuts meeting the pipe size
of the outdoor unit.
Knock out hole
for under-piping
Electrical parts box
277
120
20
218
VIEW "A"
Knock out hole
for bottom fixing
Terminal block for
indoor/outdoor
connection.
Terminal block for
heater power supply
(Only PSH-P•GAH) 22
50
120
Rear side
115
10
827
30
255
123
714
766
608
216
140
767
201
77
110
36
590
06.5.15 0:52 PM
480
PSA-RP100GA
PSA-RP125GA
PSA-RP140GA
1
2
300 or more
5 or more
OCS05A-2.qxp
Page 36
Unit : mm
06.5.15 0:52 PM
Page 37
Unit : mm
OUTDOOR UNIT
PUHZ-RP35VHA2
PUHZ-RP50VHA2
400
[33 drain hole
347.5
365
300
Air intake
[33 drain hole
330
155
152
43.6
Air intake
45.4
40
18
23
32.5
4-10 o 21 oval hole
(M10 foundation bolt)
Service panel
Service panel
for charge plug
Air discharge
Handle for
moving
150
Connection for
gas pipe
90
10
155
300
43
35
600
Connection for
liquid pipe
183
69
287.5
Service port
Installation bolt pitch: 500
800
1. FOUNDATION BOLTS
2. PIPING-WIRING DIRECTION
Please secure the unit firmly Piping and wiring connection can
with 4 foundation (M10) bolts. be made from the rear direction only.
(Bolts, washer and nut must
be purchased locally.)
Free space around the outdoor unit
(basic example)
3. ATTACHING THE CONDUIT
100
mm
In order to attach the conduit, it is
necessary to fix the metal plate with
2 screws to the back panel. Procure
the metal plate and make screw holes
locally. It is recommended to use the
metal plate shown below. Align the
metal plate to the marks on the unit
and attach it.
<Foundation bolt height>
w1
re
r mo
mo
m
100
18 or below
100 mm or more as long as
no obstacle is placed on the
rear and light-and-left sides
of the unit.
Basically open
FOUNDATION
or m
ore
w1
w2
w The position and the size of
conduit hole depend on the
conduit to be used.
re
500
mm
o
or m
350
mm
40
20
or m
ore
2 sides should be open in
the right, left and rear side.
Minimum installation space for outdoor unit
80
w Conduit hole
60
OCS05A-2.qxp
w 1 In the place where short cycle tends to occur, cooling and heating
capacity and power consumption might get lowered 10%. Air outlet
guide (optional PAC-SG58SG) will help them improve.
w 2 If air discharges to the wall, the surface might get stained.
Holes for metal plate fixing screw
w The size of hole depends on the
screw to be used.
37
OCS05A-2.qxp
06.5.15 0:52 PM
Page 38
Unit : mm
Ov
Ov
er
10
mm
er
50
0m
m
F
R
E
E
Ov
er
10
Ov
er
mm
10
0m
m
PUHZ-RP60VHA2
PUHZ-RP71VHA2
38
mm
m
FREE
m
0m
Ov
er 1
10
Service space
Over
Front piping hole
(Knock-Out)
92
[92
Front trunking hole 40
(Knock-Out)
65
45
Power supply wiring hole
(2-[27Knock-Out)
19
92
75
Right piping hole
(Knock-Out)
55
[92
Air intake
Less than
500
40
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
65
92
[92
40
Handle for moving
Handle for moving
Rear piping hole
(Knock-Out)
Rear trunking hole
(Knock-Out)
Side Air Intake
Rear Air Intake
Piping and wiring connections
can be made from 4 directions:
FRONT,Right,Rear and Below.
4 PIPING-WIRING DIRECTIONS
Power supply wiring hole
(2-[27Knock-Out)
FOUNDATION
<Foundation bolt height>
45
Right trunking hole
(Knock-Out)
Power supply wiring hole
(2-[27Knock-Out)
500
Over
Handle for moving
Piping Knock-Out Hole Details
55
27
150
Dimensions of space needed
for service access are
shown in the below diagram.
1 • • • Refrigerant GAS pipe connction (FLARE)[15.88 (5/8F)
2 • • • Refrigerant LIQUID pipe connection (FLARE)[ 9.52 (3/8F)
w1 • • • Indication of STOP VALVE connection location.
m
0m
5
er 1
Ov
Example of Notes
er1
Ov
000
0m
er 1
Ov
63
73
30
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
23 27 92
Over
Over
3 FOUNDATION BOLTS
175
322
145
Air Discharge
Installation Feet
600
Rear Air Intake
66
175
2-U Shaped notched holes
(Foundation Bolt M10)
Handle for moving
30
220
145
145
Earth terminal
950
42
Side Air Intake
1350
2 SERVICE SPACE
Drain hole
(5-[33)
71
2
1
Handle for moving
Service panel
Terminal connection
Left • • • Power supply wiring
Right • • Indoor/Outdoor wiring
2-12o36 Oval holes
(Foundation Bolt M10)
71
635
371
417
1 FREE SPACE (Around the unit)
73 63
23
73 63
23
55
27
330
30
23
219
19
45
56
370
53
28
Front piping cover
RP·YHA2
RP·VHA2
A
930
1,076
Rear piping cover
Bottom piping hole
(Knock-Out)
w1 443
39
81
PUHZ-RP100VHA2
PUHZ-RP125VHA2
PUHZ-RP140VHA2
PUHZ-RP100YHA2
PUHZ-RP125YHA2
PUHZ-RP140YHA2
A
06.5.15 0:52 PM
w1 447
OCS05A-2.qxp
Page 39
Unit : mm
OCS05A-2.qxp
06.5.15 0:52 PM
Page 40
Unit : mm
WIRED REMOTE CONTROLLER
120
130
19
40
06.5.15 0:52 PM
Page 41
Unit : mm
WIRELESS REMOTE CONTROLLER
58
159.3
55
19
OCS05A-2.qxp
41
OCS05A-2.qxp
06.5.15 0:52 PM
Page 42
WIRING DIAGRAM
4
PLA-RP35AA
[LEGEND]
SYMBOL
P.B
I.B
FUSE
ZNR
BCR
CN2L
CN32
CN41
CN51
LED1
LED2
LED3
X1
X4
SW1
SW2
SWE
C
PLA-RP50AA
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE(T6.3AL250V)
VARISTOR
FAN CONTROL ELEMENT
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
POWER SUPPLY(I.B)
POWER SUPPLY(I.B)
TRANSMISSION(INDOOR-OUTDOOR)
RELAY(DRAIN PUMP)
RELAY(FAN MOTOR)
SWITCH(MODEL SELECTION) See table 1
SWITCH(CAPACITY CORD) See table 2
CONNECTOR(EMERGENCY OPERATION)
CAPACITOR(FAN MOTOR)
PLA-RP60AA
SYMBOL
MF
MV
H2
DP
DS
TB2
PLA-RP71AA
NAME
SYMBOL
FAN MOTOR
W.B
VANE MOTOR
RU
DEW PREVENTION HEATER
BZ
DRAIN-UP MACHINE
LED1
DRAIN SENSOR
LED2
TERMINAL BLOCK
SW1
(INDOOR UNIT POWER(OPTION))
SW2
TERMINAL BLOCK (INDOOR/
OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE
CONTROLLER TRANSMISSION LINE)
ROOM TEMP.THERMISTOR
(0˚C/15kΩ,25˚C/5.4kΩ DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0˚C/15kΩ,25˚C/5.4kΩ DETECT)
COND./EVA. TEMP. THERMISTOR
(0˚C/15kΩ,25˚C/5.4kΩ DETECT)
WIRED REMOTE CONTROLLER BOARD
TB4
TB5, TB6
TH1
TH2
TH5
R.B
NAME
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR)
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
GRILLE
MV MV MV MV
5
5
5
5
H2
5
MF
3
2
1
DC
13.1V
2
1
1 2 3 6 7 4 8 9 5 10
1 2 3
CNSK P.B
(RED)
CN2S
(WHT)
TB4
YLW S1
ORN S2
ORN
S3
BRN
TO OUTDOOR UNIT
5
1 2 3
DP
FAN 1 3 5
(WHT)
X4 X1
BRN
ORN
BLK
WHT
YLW
ORN
RED
WHT
D.U.M 1 3 D.HEATER 1 3
1 3
CNC(RED)
CNP
POWER
(BLU)
CNDK
(RED)
X4
1 3 VANE
CND POWER INDOOR/OUTDOOR CN6V
(ORN) CN2D COMMUNICATION (GRN)
(WHT)
CN3C
(BLU)
CN51 CN41 CN2L
1 3 POWER 1 2
FUSE
BCR
YLW
YLW
X1
ZNR
CN32
SWE SW2
SW1
ON
OFF
LED3 LED2
HEATER D.SENSOR
CN24
CN31
(YLW)
(WHT)
DS
Refer to tables 1
and 2.
BLU
BLU
1 2 3
LED1
INTAKE LIQUID PIPE REMOCON
CN20
CN21 CN29
CN22 WIRELESS
(RED) (WHT) (BLK)
(BLU) CN90
1 2 1 2 1 2
1 2 (WHT)
TH1
2
1
W.B
BZ
9
SW1
SW2
RU
R.B
1 2
TB6
TB2
RED
BLU
GRN/YLW
1 (Fig.1)
TH3
NOTES:
1.Symbols used in wiring diagram above are,
: Connector, : Terminal (block).
2.Indoor and outdoor connecting wires are made with polarities, make wiring
matching terminal numbers (S1,S2,S3).
3.Since the outdoor side electric wiring may change be sure to check the outdoor
unit electric wiring for servicing.
4.This dlagram shows the wiring of Indoor and Outdoor connecting wires
(specification of 230V), adopting superimposed system of power and signal.
I.B
1 3
1 ; When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig1.
2 ; For power supply system of this unit, refer to the caution label located near this diagram.
Table 1
Table 2
SW1
MODELS
Service board
PLA-RP. AA
LED1
TB5
TRANSMISSION WIRES
DC12V
TH2
LED2
CNB
1 2 3 4 5
ON
OFF
MODELS
SW2
Service board
PLA-RP35AA
PLA-RP50AA
PLA-RP60AA
PLA-RP71AA
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
ON
OFF
42
L
N
YLW TB4S1
ORN
S2
ORN
S3
BRN
YLW
ORN
I.B
YLW
YLW
RED
WHT
BLK
C
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR UNIT
Please set the voltage using the
remote controller.
For the setting method. please refer to
the indoor unit Installation Manual.
OCS05A-2.qxp
06.5.15 0:52 PM
Page 43
PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2
[LEGEND]
SYMBOL
P.B
FUSE
ZNR
IPM
I.B
CN2L
CN32
CN41
CN51
LED1
LED2
LED3
X1
SW1
SW2
SWE
MF
NAME
INDOOR POWER BOARD
FUSE(T5AL250V)
VARISTOR
POWER MODULE
INDOOR CONTROLLER BOARD
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
POWER SUPPLY(I.B)
POWER SUPPLY(I.B)
TRANSMISSION(INDOOR-OUTDOOR)
RELAY(DRAIN PUMP)
SWITCH(MODEL SELECTION)wSee table 1
SWITCH(CAPACITY CORD)wSee table 2
CONNECTOR(EMERGENCY OPERATION)
FAN MOTOR
SYMBOL
MV
H2
DP
DS
TB2
TB4
NAME
SYMBOL
VANE MOTOR
W.B
DEW PREVENTION HEATER
RU
DRAIN-UP MACHINE
BZ
DRAIN SENSOR
LED1
TERMINAL BLOCK (Indoor unit Power (option))
LED2
TERMINAL BLOCK
SW1
(INDOOR/OUTDOOR CONNECTING LINE)
SW2
TERMINAL BLOCK(REMOTE
CONTROLLER TRANSMISSION LINE)
REACTOR
ROOM TEMP.THERMISTOR
(0:/15k",25:/5.4k" DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0:/15k",25:/5.4k" DETECT)
COND./EVA. TEMP. THERMISTOR
(0:/15k",25:/5.4k" DETECT)
WIRED REMOTE CONTROLLER BOARD
TB5, TB6
DCL
TH1
TH2
TH5
R.B
NAME
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR)
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
5
MF
BLK
WHT
RED
3
2
1
5
3
1
IPM
CN2S
(WHT)
2
1
P.B
POSITION DETECTION
SENSOR INPUT
CN3
(WHT)
CN4
(WHT)
FUSE
TRANS
ZNR
RECTIFIER
3 FAN
2 CN2
1 (GRN)
CN01
(BLK)
5
3
1
CN03
(BLU)
DCL
YLW
TB4
YLW S1
ORN S2
ORN
S3
BRN
YLW
ORN
CN02
2 1 (GRN)
1 3 5
FAN 1 2 3
CN33
(GRN)
D.U.M 1 3
CNP
(BLU)
X1
D.HEATER 1 3
CNC
(RED)
X1
J42
J41
Refer to tables 1
and 2.
1 2 3
DS
PLA-RP100AA2
PLA-RP125AA2
LED1
SW1
SW2
1 2 3 4 5
1 2 3 4 5
ON
OFF
R.B
1 2
TB6
w1 (Fig.1)
CN01
(BLK)
Please set the voltage using the
remote controller.
For the setting method. please refer to
the indoor unit Installation Manual.
P.B
5
3
1
TB2
YLW
ORN
1 3
ON
OFF
43
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
Manufacture/Service
1 2 3 4 5
ON
OFF
RED
BLU
GRN/YLW
L
N
YLW TB4S1
ORN
S2
ORN
BRN
S3
I.B
PLA-RP140AA2
RU
TB5
w1 ; When work to supply power separately to indoor and outdoor unit was
applied, refer to Fig1.
w2 ; For power supply system of this unit, refer to the caution label located
near this diagram.
ON
OFF
LED2
CNB
: Connector, :
NOTES: 1.Symbols used in wiring diagram above are,
Terminal (block).
2.Indoor and outdoor connecting wires are made with polarities, make wiring
matching terminal numbers (S1,S2,S3).
3.Since the outdoor side electric wiring may change be sure to check the
outdoor unit electric wiring for servicing.
4.This dlagram shows the wiring of indoor and outdoor connecting wires.
(specification of 230V), adopting superimposed system of power and signal.
1 2 3 4 5
BZ
TRANSMISSION WIRES
DC12V
(Table 2) SW2 (CAPACITY CORD)
SW2
MODELS Manufacture/Service MODELS
H2
W.B
INTAKE LIQUID PIPE REMOCON
CN20
CN21 CN29 CN22 WIRELESS
(RED) (WHT) (BLK) (BLU) CN90
1 2 1 2 1 2 1 2 (WHT)
2
1
5
GRILLE
9
TH1
5
1 2 3 6 7 4 8 9 5 10
CN41 CN2L
wBe sure to turn off the source power
TH2
and then disconnect fan motor connector.
(Failure to do so will cause trouble in Fan motor) TH5
(Table 1) SW1 (MODEL SELECTION)
SW1
Manufacture/Service
5
5
CND INDOOR/OUTDOOR POWER CN6V
(ORN) COMMUNICATION CN2D (GRN)
CN3C (WHT)
5
(BLU)
CN32
BLU
BLU
SWE SW2
ON
OFF
5
1 2 VANE
1 3 POWER 1 3
CN51
LED3 LED2 LED1
SW1
Pair No. D.SENSOR
CN31
(WHT)
MV MV MV MV
BLK
WHT
BRN
ORN
ORN
YLW
YLW
YLW
I.B
GRILLE
YLW
YLW
PNK
WHT
BLK
DP
TO
OUTDOOR
UNIT
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR UNIT
OCS05A-2.qxp
06.5.15 0:52 PM
Page 44
PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA
PEAD-RP100EA2 PEAD-RP125EA PEAD-RP140EA
SYMBOL
I.B.
FUSE
ZNR
CN2L
CN24
CN32
CN41
CN51
CN90
LED1
LED2
LED3
SW1
NAME
SYMBOL
INDOOR CONTROLLER BOARD
SW2
FUSE(T6.3AL250V)
SWE
VARISTOR
X1
CONNECTOR(LOSSNAY)
X4
X5
CONNECTOR(HEATER)
CONNECTOR(REMOTE SWITCH)
X6
CONNECTOR(HA TERMINAL-A) P.B.
CONNECTOR(CENTRALLY CONTROL) DRAIN PUMP
CONNECTOR(WIRELESS)
DP
POWER SUPPLY(I.B.)
DS
POWER SUPPLY(REMOTE CONTROLLER) C
TRANSMISSION(INDOOR•OUTDOOR) MF
SWITCH(MODEL SELECTION)
NAME
SYMBOL
SWITCH(CAPACITY CORD)
TB4
SWITCH(EMERGENCY OPERATION)
RELAY(DRAIN PUMP)
TB5
RELAY(FAN MOTOR)
TH1
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
TH2
INDOOR POWER BOARD
(OPTIONAL PARTS)
TH5
DRAIN PUMP
DRAIN SENSOR
CAPACITOR(FAN MOTOR)
FAN MOTOR
NAME
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER)
INTAKE AIR TEMP. THERMISTOR
(0: /15t,25:/5.4t DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(0: /15t,25:/5.4t DETECT)
COND./EVA. TEMP. THERMISTOR
(0: /15t,25:/5.4t DETECT)
INSIDE SECTION OF CONTROL BOX
DS
TH1
TH2
TH5
1
B B
L L
U U
3
CN31
1 2
1 2
CN22
(BLU)
CN20
(RED)
I.B.
1 2
1 2 3
1 2 3 4 5 6 7 8 9
1 2 3 4
1 2
12 3 4 5
1 2 3
CN21 CN29
(WHT) (BLK)
CN31
(WHT)
CN90
(WHT)
CN41
(WHT)
CN24
(YLW)
CN51
(WHT)
CN32
(WHT)
1 2
1 2
SW1
CN2L
(RED)
SW2
SWE
ON
OFF
LED1
LED2
LED3
WHT
BLK
2
1
X1
(BLU)
CN3C
ZNR
W3B1
H L
T K
O3Y 1
R L
N W
W B
H L
T K
TO MA-REMOTE
CONTROLLER
DC8.7-13V
W
H
T
2
1
B
L
K
3
2 1
wA
X4
X1
FUSE
(ORN)
CND
O3B 1
R R
N N
TB5 BL
U B
2
L
1
U
X4 X5 X6
X5
CN2D
(WHT)
CN2S
(WHT)
(RED)
CNDK
P.B.
3
1
(BLU)
CNP
(WHT)
FAN
W P P B
H N N L
T K K K
<PEAD-RP35•50•60EA, 35EA2>
External static
pressure 30Pa
<PEAD-RP71•100•125•140EA, 100EA2>
External static pressure 70Pa
DP
<PEAD-RP35•50•60EA, 35EA2>
External static
pressure 70Pa
1
CNSK
(RED)
X6
7 5 3 1
Optional parts
1 2 3 4 5 6
Optional parts
1 2 3 4 5 6
(RED)
1 2 3 4 5 6
(RED)
(WHT)
TB4
S3
S2
S1
TO OUTDOOR UNIT
BRN
ORN
YLW
MF
C
MF
C
MODELS
SW1
SW2
Model selection Capacity cord
switch
switch
12345
ON
35EA(2)
OFF
12345
ON
50EA
OFF
12345
ON
60EA
OFF
12345
12345
ON
ON
71EA
OFF
OFF
12345
ON
100EA(2)
OFF
12345
ON
125EA
OFF
12345
ON
140EA
OFF
<PEAD-RP71•100•125•140EA, 100EA2>
External static
pressure 130Pa
<wA> (IN CASE OF CONNECT
THE REPLACEMENT WIRING)
L
N
1 2
1 2
TO CND
S1
S2
S3
1 2
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR
UNIT
TO CN3C
NOTE 1.SINCE THE OUTDOOR SIDE ELECTRIC WIRING MAY CHANGE BE SURE
TO CHECK THE OUTDOOR UNIT ELECTRIC WIRING FOR SERVICING.
2.INDOOR AND OUTDOOR CONNECTING WIRES ARE MADE WITH POLARITIES,
MAKE WIRING MATCHING TERMINAL NUMBERS(S1,S2,S3).
3.SYMBOLS USED IN WIRING DIAGRAM ABOVE ARE,
: CONNECTOR,
: TERMINAL.
4.THE WIRING BETWEEN MA-REMOTE CONTROLLER AND TB5 IS INCLUDED
IN THE PACKAGE.
44
OCS05A-2.qxp
06.5.15 0:52 PM
Page 45
PEAD-RP60GA
SYMBOL
I.B.
FUSE
ZNR
CN2L
CN24
CN32
CN41
CN51
CN90
LED1
LED2
LED3
PEAD-RP71GA
PEAD-RP100GA
NAME
NAME
SYMBOL
INDOOR CONTROLLER BOARD
SW1 SWITCH(MODEL SELECTION)
FUSE(T6.3AL250V)
SW2 SWITCH(CAPACITY CORD)
VARISTOR
SWE SWITCH(EMERGENCY OPERATION)
CONNECTOR(LOSSNAY)
X1 RELAY(DRAIN PUMP)
X4 RELAY(FAN MOTOR)
CONNECTOR(HEATER)
CONNECTOR(REMOTE SWITCH)
X5 RELAY(FAN MOTOR)
CONNECTOR(HA TERMINAL-A)
X6 RELAY(FAN MOTOR)
CONNECTOR(CENTRALLY CONTROL) P.B. INDOOR POWER BOARD
C
CAPACITOR(FAN MOTOR)
CONNECTOR(WIRELESS)
POWER SUPPLY(I.B.)
MF
FAN MOTOR
POWER SUPPLY(REMOTE CONTROLLER) TB4 TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TRANSMISSION(INDOOR•OUTDOOR)
NAME
SYMBOL
TERMINAL BLOCK(REMOTE CONTROLLER)
TB5
TH1
INTAKE AIR TEMP.THERMISTOR
(0: /15t,25:/5.4t DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(0: /15t,25:/5.4t DETECT)
TH5
COND./EVA. TEMP. THERMISTOR
(0: /15t,25:/5.4t DETECT)
INSIDE SECTION OF CONTROL BOX
TH1
TH2
TH5
1 2
1 2
1 2
1 2
CN22
(BLU)
CN20
(RED)
CN21
(WHT)
CN29
(BLK)
B B
L L
U U
I.B.
1 2 3
1 2 3 4 5 6 7 8 9
1 2 3 4
CN90
(WHT)
CN41
(WHT)
CN31
(WHT)
1 2
CN24
(YLW)
1 2 3 4 5
1 2 3
CN51
(WHT)
CN32
(WHT)
1 2
SW1
CN2L
(RED)
SW2
SWE
ON
LED1
LED2
LED3
OFF
X1
2
1
WHT
BLK
(BLU)
CN3C
O3B1
R R
N N
ZNR
TO MA-REMOTE
CONTROLLER
DC8.7-13V
(ORN)
CND
W3B1
H L
T K
O3Y1
R L
N W
W
H
T
wA
2
1
B
L
K
3
2 1
U B
L
U
2
1
X1
FUSE
W B
H L
T K
TB5 BL
X4 X5 X6
X5
CN2D
(WHT)
CN2S
(WHT)
(RED)
CNDK
3
1
(BLU)
CNP
X4
X6
7 5 3 1
B B O
L L R
U K G
CNSK
(RED)
1 2 3 4 5 6
1
TO OUTDOOR UNIT
(WHT)
MF
C
THE REPLACEMENT WIRING)
L
N
1 2
1 2
TO CND
S1
S2
S3
1 2
TO CN3C
POWER SUPPLY
~(1PHASE)
230V 50Hz
MODELS
SW1
SW2
Model selection Capacity cord
switch
switch
12345
ON
OFF
60GA
12345
12345
TO OUTDOOR
UNIT
230V
240V
BLU
5Pa
10Pa
20Pa
WHT
35Pa
50Pa
60Pa
RED
50Pa
70Pa
75Pa
(FACTORY SHIPMENT)
BRN
ORN
YLW
<wA> (IN CASE OF CONNECT
*External static pressure
CONNECTOR COLOR
220V
*
P.B.
TB4
S3
S2
S1
(WHT)
FAN
G Y Y B
R L L L
Y W W K
71GA
ON
OFF
ON
OFF
12345
ON
OFF
100GA
NOTE 1.SINCE THE OUTDOOR SIDE ELECTRIC WIRING MAY CHANGE BE SURE
TO CHECK THE OUTDOOR UNIT ELECTRIC WIRING FOR SERVICING.
2.INDOOR AND OUTDOOR CONNECTING WIRES ARE MADE WITH POLARITIES,
MAKE WIRING MATCHING TERMINAL NUMBERS(S1,S2,S3).
3.SYMBOLS USED IN WIRING DIAGRAM ABOVE ARE,
: CONNECTOR,
: TERMINAL.
4.THE WIRING BETWEEN MA-REMOTE CONTROLLER AND TB5 IS INCLUDED
IN THE PACKAGE.
45
06.5.15 0:52 PM
PKA-RP35GAL
Page 46
PKA-RP50GAL
P.B CNDK
(RED)
CN2S
(WHT)
1
2 DC13.1V
3
MF
w1 (Fig.1)
1
2
TB2
TB4
YLW
S1
S2
ORN
S3
ORN
BRN
1 2 3
BLK
WHT
POWER
POWER
1 2
1 3 VANE
CNDK 1 3 CND 1 3
CN6V
INDOOR/OUTDOOR (GRN)
(RED)
(ORN)
POWER
CN2D(WHT) COMMUNICATION
CN3C(BLU)
X4
BCR
ZNR
X4
CN41
CN2L
CN51
CN32
TO
OUTDOOR
UNIT
I.B
6
FUSE
FAN 1 3 5
(WHT)
YLW
ORN
I.B
RED
WHT
RED
WHT
BLK
C
RED
BLU
GRN/YLW
MV
POWER
SUPPLY
~(1PHASE)
230V 50Hz
L
N
YLW TB4S1
ORN
S2
ORN
S3
BRN
YLW
ORN
OCS05A-2.qxp
1 3
TO
OUTDOOR
UNIT
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
9
WIRELESS
CN90
(WHT)
LED3 LED2 LED1
SW2
SWE
ON
OFF
SW1
INTAKE
CN20
(RED)
LIQUID PIPE
CN21
CN29
(WHT) (BLK)
1 2
1 2
1 2
CNB
BZ
REMOCON
CN22
(BLU)
RU
RECEIVER LED1 LED2 SW2 SW1
1 2
W.B
Refer to tables 1
and 2 for service PCB.
R.B
2
1
TH2
TH1
TH5
TRANSMISSION WIRES DC12V
1
TB6
2
TB5
PKH-P35,50GALH models only
1 2
H1
YLW
YLW
I.B
HEATER
CN24
(YLW)
6
RED
88H
1
GRY
6
5 RED
SW1
Service board
1 2 3 4 5
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
SW1
SW2
SWE
X4
BCR
LED1
LED2
LED3
ON
OFF
FS1
FS2
26H
88H
RED
WHT
1
2
RED 5
TB2
L
3 RED
N
BLU
GRN/YLW
MODELS
PKA-RP35GAL
PKH-P35GALH
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
CONNECTOR <LOSSNAY>
CONNECTOR <REMOTE SWITCH>
CONNECTOR <HA TERMINAL-A>
CONNECTOR <CENTRALLY CONTROL>
SWITCH <MODEL SELECTION>wSee Table 1.
SWITCH <CAPACITY CODE>wSee Table 2.
SWITCH <EMERGENCY OPERATION>
RELAY <FAN MOTOR>
FAN CONTROL ELEMENT
POWER SUPPLY <I.B>
POWER SUPPLY <R.B>
TRANSMISSION <INDOOR-OUTDOOR>
Please set the voltage using the
remote controller.
For the setting method,please refer to
the indoor unit Installation Manual.
POWER SUPPLY
~(1PHASE)
230V 50Hz
SW2
Service board
MODELS
Service board
1 2 3 4 5
1 2 3 4 5
SYMBOL
C
MF
MV
TB2
TB4
TB5,TB6
TH1
TH2
TH5
ON
OFF
PKA-RP50GAL
PKH-P50GALH
NAME
CAPACITOR <FAN MOTOR>
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK (HEATER) wPKH-P.GALH
models only or option for PKA-RP.GAL models.
TERMINAL BLOCK <INDOOR/ OUTDOOR
CONNECTING LINE>
TERMINAL BLOCK <REMOTE CONTROLLER
TRANSMISSION LINE> <OPTION>
ROOM TEMP.THERMISTOR
<0:/ 15k", 25:/ 5.4k" DETECT>
PIPE TEMP.THERMISTOR/ LIQUID
<0:/ 15k", 25:/ 5.4k" DETECT>
COND./ EVA.TEMP.THERMISTOR
<0:/ 15k", 25:/ 5.4k" DETECT>
SYMBOL
W.B
RU
BZ
LED1
LED2
SW1
SW2
R.B
HEATER
FS1
FS2
H1
26H
88H
ON
OFF
NAME
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED <RUN INDICATOR>
LED <HOT ADJUST>
SWITCH (HEATING ON/ OFF>
SWITCH (COOLING ON/ OFF>
WIRED REMOTE CONTROLLER BOARD
THERMAL FUSE <104:10A>
THERMAL FUSE <84:10A>
HEATER
HEATER THERMAL SWITCH
HEATER CONTACTOR
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are,
: Connector,
: Terminal (block).
w1. When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig 1.
w2. For power supply system of this unit, refer to the caution label located near this diagram.
46
Page 47
PKA-RP60FAL
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
SW1
SW2
SWE
X4
BCR
LED1
LED2
LED3
PKA-RP71FAL
SYMBOL
C
MF
MV
TB2
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE(T6.3AL250V)
VARISTOR
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
SWITCH (MODEL SELECTION) wSee Table 1.
SWITCH (CAPACITY CODE) wSee Table 2.
SWITCH(EMERGENCY OPERATION)
RELAY(FAN MOTOR)
FAN CONTROL ELEMENT
POWER SUPPLY(I.B)
POWER SUPPLY(R.B)
TRANSMISSION(INDOOR-OUTDOOR)
NAME
CAPACITOR(FAN MOTOR)
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK (HEATER) wPKH-P.FALH
models only or option for PKA-RP.FAL models.
TERMINAL BLOCK(INDOOR/OUTDOOR
CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )(OPTION)
ROOM TEMP.THERMISTOR
(0;/15k', 25;/5.4k' DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0;/15k', 25;/5.4k' DETECT)
COND./EVA.TEMP.THERMISTOR
(0;/15k', 25;/5.4k' DETECT)
TB4
TB5
TH1
TH2
TH5
P.B CNDK
(RED)
1
2
TB4
YLW
S1
S2
ORN
S3
ORN
BRN
1 2 3
FAN 1 3 5
X4
BCR
POWER
POWER
1 2
1 3 VANE
CNDK 1 3 CND 1 3
CN6V
INDOOR/OUTDOOR (GRN)
(RED)
(ORN)
POWER
CN2D(WHT) COMMUNICATION
CN3C(BLU)
ZNR
X4
CN41
CN2L
CN51
CN32
NAME
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR )
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
WIREDREMOTE CONTROLLER BOARD(OPTION)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
HEATER
FS1,2 THERMAL FUSE(117; 10A:60,71FALH/
117; 16A:100FALH)
HEATER
H1
26H HEATER THERMAL SWITCH
88H HEATER CONTACTOR
w1 (Fig.1)
TB2
RED
BLU
GRN/YLW
TO
OUTDOOR
UNIT
I.B
6
FUSE
(WHT)
BLK
WHT
RED
WHT
RED
WHT
BLK
C
I.B
SYMBOL
W.B
RU
BZ
LED1
LED2
SW1
SW2
R.B
TB6
Please set the voltage
using the remote controller.
For the setting method,
please refer to the indoor
unit Installation Manual
CN2S
(WHT)
1
2 DC13.1V
3
MF
PKA-RP100FAL
1 3
MV
L
N
POWER
SUPPLY
(1PHASE)
230V 50Hz
YLW TB4S1
ORN
S2
ORN
S3
BRN
YLW
ORN
06.5.15 0:52 PM
YLW
ORN
OCS05A-2.qxp
TO
OUTDOOR
UNIT
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
9
WIRELESS
CN90
(WHT)
LED3 LED2 LED1
SWE
ON
OFF
SW2
SW1
INTAKE LIQUID PIPE
CN20 CN21
CN29
(RED) (WHT) (BLK)
1 2
1 2
1 2
CNB
BZ
REMOCON
CN22
(BLU)
RU
RECEIVER LED1 LED2 SW2 SW1
1 2
W.B
Refer to tables 1
and 2 for service PCB.
R.B
2
1
TH2
TH1
Table 1
SW1
Service board
1 2 3 4 5
ON
OFF
Service board
MODELS
1 2 3 4 5
PKA-RP60FAL
PKH-P60FALH
HEATER
PKA-RP71FAL
ON
OFF PKH-P71FALH
YLW
YLW
RED
1
1 2 3 4 5
MODELS
PKA-RP100FAL
ON
OFF PKH-P100FALH
Service board
1 2 3 4 5
ON
OFF
P100FALH models only
FS1
88H
SW2
Service board
MODELS
H1
CN24
1 2 (YLW)
6
1
TB6
2
TRANSMISSION WIRES DC12V
TB5
Table 2
PKH-P60
I.B
TH5
6
GRY
5 RED
FS2
26H
88H
RED
WHT
1
2
RED 5
TB2
L
3 RED
N
BLU
GRN/YLW
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are,
: Connector,
: Terminal (block).
w1. When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig 1.
w2. For power supply system of this unit, refer to the caution label located near this diagram.
47
POWER SUPPLY
(1PHASE)
230V 50Hz
OCS05A-2.qxp
06.5.15 0:52 PM
Page 48
PCA-RP50GA PCA-RP60GA
PCA-RP71GA
PCA-RP100GA PCA-RP125GA PCA-RP140GA
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
SWITCH (MODEL SELECTION) WSee Table 1.
SWITCH (CAPACITY CODE) WSee Table 2.
SWITCH(EMERGENCY OPERATION)
RELAY(DRAIN PUMP)
RELAY(FAN MOTOR)
FAN CONTROL ELEMENT
POWER SUPPLY(I.B)
POWER SUPPLY(R.B)
TRANSMISSION(INDOOR-OUTDOOR)
CAPACITOR(FAN MOTOR)
SYMBOL
MF
MV
DP
DS
TB2
TB4
TB5,TB6
TH1
TH2
TH5
R.B
P.B CNDK
(RED)
C
BRN
ORN
YLW
ORN
RED
WHT
RED
WHT
BLK
FUSE
D.U.M 1 3 POWER 1 3 POWER 1 3
1 2
1 3 VANE
CND
CNDK
CNP
6
INDOOR/OUTDOOR (CN6V)
POWER
(ORN)
(RED)
(BLU)
CN2D(WHT) COMMUNICATION GRN
CN3C(BLU)
X4
X1
CN41
CN2L WIRELESS
ZNR
CN90
CN51
CN32 (WHT)
X4
X1
LED3 LED2 LED1
D.SENSOR INTAKE LIQUID PIPE
CN31
CN20 CN21
CN29
(WHT)
(RED) (WHT) (BLK)
SW1
1 2
1 2
1 2
BLK
BLK
1 2 3
Refer to tables 1
and 2 for service PCB.
REMOCON
CN22
(BLU)
TB4
S1
S2
S3
MV
MV
9
100~140 TYPE
5
5
MV
CNB
Please set the voltage using the remote
controller.
For the setting method, please refer to
the indoor unit Installation Manual.
RU
RECEIVER LED1 LED2 SW2 SW1
W.B
2
1
TO OUTDOOR UNIT
50~71 TYPE
6
6
6
BZ
1 2
BLU
BLU
SW2
BLK
BLK
BCR
SWE
ON
OFF
YLW
ORN
ORN
BRN
DP
FAN 1 3 5
(WHT)
THERMAL FUSE(98;10A:50GAH/117;16A:100GAH
110;16A:60,71,125,140GAH)
HEATER
HEATER THERMAL SWITCH
HEATER CONTACTOR
1
2
(OPTION)
1 2 3
I.B
H1
26H
88H
NAME
WIRELESS REMOTE CONTROLLER BOARD(OPTION)
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR)
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
CN2S
(WHT)
1
2 DC13.1V
3
MF
SYMBOL
W.B
RU
BZ
LED1
LED2
SW1
SW2
HEATER
FS1,2
NAME
FAN MOTOR
VANE MOTOR
DRAIN-UP MACHINE (OPTION)
DRAIN SENSOR (OPTION)
TERMINAL BLOCK (HEATER) WPCH-P.GAH
models only or option for PCA RP.GA models.
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )
ROOM TEMP.THERMISTOR
(0;/15k', 25;/5.4k' DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0;/15k', 25;/5.4k' DETECT)
COND./EVA.TEMP.THERMISTOR
(0;/15k', 25;/5.4k' DETECT)
WIRED REMOTE CONTROLLER BOARD
BLK
WHT
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
SW1
SW2
SWE
X1
X4
BCR
LED1
LED2
LED3
C
TRANSMISSION WIRES DC12V
1 2
1 2
WWhen installing optional
TB5
drain-up machine disconnect
R.B
the CN31 jumper connector
1 2
and
replace
it
with
the
CN31
TB6
TH2
TH1
TH5
DRAIN SENSOR drain sensor (DS).
[Servicing]
(WHT) 1 2 3
When installing drain-up
Fasten terminal of the terminal board "TB4"equips lock system.
machine (Optional part).
To remove the fastened terminal, pull it while pressing the protruding
DS
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
H1
FS1
FS2
88H
RED
WHT
1
2
RED 5
W1 (Fig.1)
TB2
L
3 RED
N
BLU
POWER SUPPLY
~(1PHASE)
230V 50Hz
GRN/YLW
W1. When work to supply power separately to
Indoor and Outdoor unit was applied, refer to Fig 1.
W2. For power supply system of this unit,
refer to the caution label located near this diagram.
1 2
HEATER
CN24
(YLW)
I.B
YLW
YLW
I.B
RED
6
6
1 GRY
5 RED
88H
Table 2
SW2
Table 1
MODELS
PCA-RP.GA
PCH-P.GAH
SW1
Service board
1 2 3 4 5
ON
OFF
MODELS
Service board
PCA-RP50GA
PCH-P50GAH
1 2 3 4 5
PCA-RP60GA
PCH-P60GAH
1 2 3 4 5
PCA-RP71GA
PCH-P71GAH
1 2 3 4 5
MODELS
Service board
PCA-RP100GA
1 2 3 4 5
PCA-RP125GA
1 2 3 4 5
PCA-RP140GA
1 2 3 4 5
ON
OFF PCH-P100GAH
ON
OFF PCH-P125GAH
ON
OFF PCH-P140GAH
TB2
RED
BLU
GRN/YLW
ON
OFF
ON
OFF
26H
1 3
L
N
YLW TB4S1
ORN
S2
ORN
S3
BRN
YLW
ORN
PCH-P50~P140GAH
models only
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR UNIT
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
NOTES:
1. Since the outdoor side electric wiring may change be sure to
check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make
wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is
independent.
4. Symbols used in wiring diagram above are,
: Connector,
: Terminal (block).
ON
OFF
48
OCS05A-2.qxp
06.5.15 0:52 PM
PCA-RP71HA
Page 49
PCA-RP125HA
[ LEGEND ]
SYMBOL
P. B
I. B
FUSE
ZNR
CN2L
CN32
CN41
CN51
LED1
LED2
LED3
X1
X4
X5
X6
SW1
SW2
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROLL)
POWER SUPPLY (I. B)
POWER SUPPLY (R. B)
TRANSMISSION(INDOOR-OUTDOOR)
RELAY (DEW PREVENTION HEATER)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH (MODEL SELECTION) See Table 1.
SWITCH (CAPACITY CODE) See Table 2.
SYMBOL
MF1, MF2
C1, C2
H2
TB2
NAME
FAN MOTOR
CAPACITOR(FAN MOTOR)
DEW PREVENTION HEATER
TERMINAL BLOCK(INDOOR UNIT
POWER (OPTION))
TB4
TERMINAL BLOCK(INDOOR/OUTDOOR
TB5,TB6
CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
ROOM TEMP.THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
TH1
TH2
PIPE TEMP.THERMISTOR/LIQUID
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
TH5
COND./ EVA.TEMP.THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
R. B
WIRED REMOTE CONTROLLER BOARD
SWITCH (EMERGENCY OPERATION)
SWE
For PCA-RP125HA
1
1
I.B
FAN 1 3 5 7
(WHT)
DC13.1V
TB4
S1
S2
S3
YLW
ORN
ORN
BRN
FUSE
CN41
ZNR
LED3 LED2 LED1 INTAKE LIQUID
CN20
CN21
(RED) (WHT)
1 2
1 2
BLK
BLK
1 2
WHT
WHT
Refer to tables 1
and 2 for service PCB.
PIPE REMOCON
CN29
CN22
(BLK)
(BLU)
BLU
BLU
SW1
1 2
1 2
1 3
TH2
TH5
TH1
ON
OFF
YLW
ORN
ORN
CN2L
I.B
YLW
ORN
CN51 CN32
ON
OFF
Table 1
SW1
Service board
1 2 3 4 5
w1 (Fig.1)
D.HEATER 1 3 ROWER 1 3 ROWER 1 3
1 2
1 3
CNC
CNDK
CND
ROWER INDOOR/OUTDOOR
COMMUNICATION
(RED)
(RED)
(ORN)
CN2D(WHT) CN3C(BLU)
X6 X5 X4
SW2
TO
OUTDOOR
UNIT
RED
BLU
GRN/YLW
X6 X5 X4
SWE
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
1
2
BLK
WHT
H2
1
2
3
YLW
ORN
BRN
C2
GRY
CN2S
(WHT)
(RED)
YLW
YLW
ORN
C1
RED
P.B CNDK
RED
WHT
6 5 4 3 2 1
BLK
BLU
YLW
WHT
6 5 4 3 2 1
BLK
BLU
YLW
WHT
ORN
RED
BLK
BLU
YLW
WHT
MF2
ORN
RED
BLK
BLU
YLW
WHT
MF1
1 3
BRN
PCA-RP71HA
TB5
2
TRANSMISSION WIRES DC12V
1
SW2
MODELS
Service board
Service board
1 2 3 4 5
1 2 3 4 5
ON PCA-RP125HA
ON
OFF
OFF
NOTES:
1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1,S2,S3).
3.Symbols used in wiring diagram above are,
: Connector, : Terminal (block).
1 ; When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig1.
2 ; For power supply system of this unit, refer to the caution label located near this diagram.
49
POWER
SUPPLY
~(1PHASE)
230V 50Hz
TB4
S1
S2
S3
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
Table 2
MODELS
TB2
L
N
R.B
1
TB6
2
TO
OUTDOOR
UNIT
OCS05A-2.qxp
06.5.15 0:52 PM
PSA-RP71GA
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
LED1
LED2
LED3
Page 50
PSA-RP100GA
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
POWER SUPPLY (I.B)
POWER SUPPLY (R.B)
TRANSMISSION (INDOOR-OUTDOOR)
SYMBOL
I.B SW1
SW2
SWE
X2
X4
X5
X6
R.B
TB6
HEATER
FS1,2
H
26H
88H
PSA-RP125GA
NAME
SWITCH (MODEL SELECTION) See Table 1.
SWITCH (CAPACITY CODE) See Table 2.
SWITCH (EMERGENCY OPERATION)
RELAY (LOUVER)
RELAY (FAN MOTOR)
RELAY (FAN MOTOR)
RELAY (FAN MOTOR)
WIRED REMOTE CONTROLLER BOARD
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
THERMAL FUSE (110˚C16A)
HEATER
HEATER THERMAL SWITCH
HEATER CONTACTOR
PSA-RP140GA
SYMBOL
C
MF
ML
NAME
CAPACITOR (FAN MOTOR)
FAN MOTOR
LOUVER MOTOR
TB2
TERMINAL BLOCK (HEATER) PSH-P.GAH
models only or option for PSA-RP.GA models.
TB4
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TH1
ROOM TEMP.THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
TH2
PIPE TEMP.THERMISTOR/LIQUID
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
TH5
COND./EVA.TEMP.THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
INDOOR UNIT
TB4
YLW
S1
P.B
CNSK
(RED)
CN2S
(WHT)
2
1
ORN
S2
3
2
1
DC13.1V
S3
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
TO
OUTDOOR
UNIT
TB2
1 (Fig.1)
ORN
MF
RED
BLU
GRY/YLW
ML
C
2
1
2
1
2
1
X2
X6 X5 X4
LED3 LED2 LED1
SW2
SWE
ON
SW1
OFF
CN24
TH2
Refer to tables 1
and 2 for service PCB.
R.B
2
1
I.B
YLW
YLW
1
TB6
TH5
88H 6YLW
FS2
6
5
RED 26H
RED
FS1
RED
WHT
H
1
2
TB4
S1
S2
S3
I.B
POWER SUPPLY
~(1PHASE)
230V 50Hz
1 3
1 3
TO
OUTDOOR
UNIT
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
BLU
2
HEATER
CN24
(YLW)
RED
BLU
LIQUID WIRELESS
CN21
CN90
(WHT)
(WHT)
INTAKE
CN20 REMOCON 2
(RED)
CN22
(BLU) 1
PIPE
CN29
(BLK)
CN2L
CN41 CN32
1
TH1
PSH -P.GAH
models only
1 3
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
BRN
ORN
X6 X5 X4
CN51
ZNR
1 2
POWER
CN2D
(WHT)
YLW
ORN
X2
POWER 1 3
CND
(ORN)
L
N
BRN
ORN
POWER 1 3
CNDK
(RED)
BLK
WHT
RED
WHT
LOUVER 1 3
CNL
(YLW)
YLW
ORN
YLW
YLW
FAN 1 3 5 7
(WHT)
I.B
FUSE
BLK
BLU
YLW
WHT
RED
BLU
TRANSMISSION
WIRES DC12V
RED 5
88H
TB2
3 RED L
BLU N
GRN/YLW
POWER SUPPLY
~(1 PHASE)
230V 50Hz
Table 1
SW2
Service board
1
2 3 4 5
PSA-RP.GA
ON
PSH-P.GAH
OFF
MODELS
Table 2
SW2
Service board
1
2 3 4 5
PSA-RP71GA
ON
PSH-P71GAH
OFF
MODELS
PSA-RP100GA
PSH-P100GAH
1 2 3 4 5
PSA-RP125GA
PSH-P125GAH
1 2 3 4 5
PSA-RP140GA
PSH-P140GAH
1 2 3 4 5
1 ; When work to supply power separately to Indoor and Outdoor unit
was applied, refer to Fig1.
2 ; For power supply system of this unit, refer to the caution label
located near this diagram.
[NOTES]
1.Symbols used in wiring diagram above are,
: Connector, : Terminal (block).
2.Indoor and outdoor connecting wires are made with polarities, make wiring
matching terminal numbers (S1,S2,S3).
3.Since the outdoor side electric wiring may change be sure to check the outdoor
unit electric wiring for servicing.
4.This diagram shows the wiring of Indoor and Outdoor connecting wires
(specification of 230V), adopting superimposed system of power and signal.
ON
OFF
ON
OFF
ON
OFF
50
06.5.15 0:52 PM
Page 51
PUHZ-RP35VHA2
PUHZ-RP50VHA2
Symbols used in wiring diagram above are,
SYMBOL
TB1
MC
MF1
21S4
63H
SV
TH3, TH33
TH4
TH6
TH7
TH8
LEV(A),LEV(B)
ACL
P.B.
R/S
U/V/W
IPM
CB1~CB3
:Connector,
NAME
Terminal Block<Power Supply, Indoor/Outdoor>
Motor for Compressor
Fan Motors
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Solenoid Valve (Bypass Valve)
Thermistor<Outdoor Pipe>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Thermistor<Radiator Panel>
Electronic Expansion Valve
Reactor
Power Circuit Board
Connection Terminal<L/N-Phase>
Connection Terminal<U/V/W-Phase>
Inverter
Main Smoothing Capacitor
PUHZ-RP60VHA2
PUHZ-RP71VHA2
:Terminal(block)
SYMBOL
N.F.
LI/LO
NI/NO
E
52C
C.B.
SW1
SW4
SW5
SW6
SW7
SW8
SW9
SW10
LED1,LED2
F1~4
NAME
Noise Filter Circuit Board
Connection Terminal<L-Phase>
Connection Terminal<N-Phase>
Connection Terminal<Ground>
52C Relay
Controller Circuit Board
Switch<Forced Defrost, Defect History
Record Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch>
Switch<Model Select>
Switch<Function Setup>
Switch
Switch
Switch<Model Select>
Light Emitting Diodes
<Operation Inspection Indicators>
Fuse<T6.3AL250V>
SYMBOL
SWP
CN31
SS
CNM
CNMNT
NAME
Switch<Pump Down>
Connector<Emergency Operation>
Connector<Connection for Option>
Connector<A-Control Service Inspection Kit>
Connector
<Connected to Optional M-NET Adapter Board>
Connector
CNVMNT
<Connected to Optional M-NET Adapter Board>
Connector
CNDM
< Connected for Option (Contact Input)>
X51,X52,X55 Reray
TH7 TH6
12
TH33
(YLW)
1234
TH7/6
(RED)
TH3
TH4
LEV-A
LEV-B
SW11
SW1
LED2
SW7
3
CN52C
(RED)
12
A
CNS
(WHT) 3 2 1
12
34
F1
CNAC
(WHT)
F4
21S4
1 (GRN)
3
21S4
SV2
1 (BLU)
3
3
SS
1 (WHT)
SV
ACL
LO
NO
N.F.
S
W
CN3
(WHT)
CN2
(WHT)
CB2
CB3
3
1
CB1
CNAC2
(RED)
TH8
21
V
3
12
CN4
(WHT)
U
R
CN5
(RED)
1
I PM
21
PFC
52C
CN52C
(BLK)
7 6 54 3 2 1
RED
w2
U
BLK
WHT
P.B.
1 2
MC
W V
CNAC1
(WHT)
w1 MODEL SELECT
ON
OFF
1 2 3 4 5 6
50V
ON
OFF
60V
ON
OFF
ON
OFF
1 2 3 4 5 6
1 2
TB1
ON
OFF
1 2 3 4 5 6
71V
(RED)
CN5
1 2
ON
OFF
L
1 2
ON
OFF
1 2 3 4 5 6
N
S1 S2 S3
NO FUSE
BREAKER
1 2
POWER SUPPLY
~/N
230V 50Hz
w2 RP60/71V only
INDOOR
UNIT
M-NET ADAPTER
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
NAME
Terminal Block<M-net connection>
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting : 1st digit>
SYMBOL
SW12
LED1
LED2
LED3
LED4
LED5
NAME
Switch<Address setting : 2nd digit>
LED<Power Supply : DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission : Sending>
LED<Transmission : Recelving>
LED<Power Supply : DC12V>
51
NI
ON
OFF
SW10
E
35V
SW6
LI
MODEL
S
TB7
M-NET
X51
X52
F3
X55
F2
B
1 2
LED1
12
CN2M
(WHT)
wh 1
CN51
(WHT)
12345
CN4
(WHT)
21
CNDM
(WHT)
1
CN2
(WHT)
1234567
LED5
SW10
CN31
TRANS
CNDC
(PNK)
M-NET SUBSTRATE
SW9
SW6
SW5
SW1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CNM
(WHT)
LED4
123
63H
(YLW)
F5
SW4 SWP SW8
MF1
123456 123 12345
LEV-B
CNVMNT CNMNT
(RED)
(WHT)
(WHT)
SW12
LED3
w1
123456
LEV-A
(WHT)
12 12
TH3 TH4
(WHT) (WHT)
LED1
CNF1
(WHT)
LED2
4567
1
1
CND
(WHT)
TH33
C.B.
12345
CN5
(WHT)
When M-NET adaptor is connected
3
OCS05A-2.qxp
123
PUHZ-RP100VHA2
PUHZ-RP125VHA2
Symbols used in wiring diagram above are,
SYMBOL
TB1
MC
MF1,MF2
21S4
SV
63H
TH3
TH4
TH6
TH7
TH8
TH33
LEV-A,B
DCL
52C
RS
ACTM
CB
Page 52
:Connector,
NAME
Terminal Block<Power Supply, Indoor/Outdoor >
Motor for Compressor
Fan Motors
Solenoid Valve (Four-Way Valve)
Solenoid Valve (Bypass Valve)
High Pressure Switch
Thermistor<Outdoor Pipe>
Thermistor<Discharge>
Thermistor<Outdoor 2-Phase Pipe>
Thermistor<Outdoor>
Thermistor<Heat Sink>
Thermistor<Outdoor Pipe>
Electronic Expansion Valve
Reactor
52C Relay
Rush Current Protect Resistor
Active Filter Module
Main Smoothing Capacitor
PUHZ-RP140VHA2
:Terminal(block)
SYMBOL
P.B.
TABU/V/W
TABS/T
TABP1/P2/P
TABN1/N2/N
DS2,3
IPM
N.F.
LI/LO
NI/NO
EI
C.B.
F1~4
SW1
NAME
Power Circuit Board
Connection Terminal<U/V/W-Phase>
Connection Terminal<L/N-Phase>
Connection Terminal<DC Voltage>
Connection Terminal<DC Voltage>
Diode Bridge
Power Module
Noise Filter Circuit Board
Connection Lead<L-Phase>
Connection Lead<N-Phase>
Connection Terminal<Ground>
Controller Circuit Board
Fuse<T6.3AL250V>
Switch<Forced Defrost, Defect History Record
Reset, Refrigerant Address>
Switch<Test Operation>
Switch<Function Switch>
Switch<Model Select>
SW4
SW5
SW6
TH33 TH7 TH6 TH3 TH4
LEV-A
LEV-B
123456
123456
C.B.
SYMBOL
SW7
SW8
SW9
SW10
SWP
CN31
LED1,LED2
SS
CNM
CNMNT
CNVMNT
CNDM
NAME
Switch<Function Setup>
Switch
Switch
Switch<Model Select>
Switch<Pump Down>
Connector<Emergency Operation>
Light Emitting Diodes
<Operation Inspection Indicators>
Connector<Connection for Option>
Connector<A-Control Service Inspection Kit>
Connector<Connected to Optional M-NET Adapter Board>
Connector<Connected to Optional M-NET Adapter Board>
Connector< Connected for Option (Contact Input)>
When M-NET adaptor is connected
SW11
SW1
LED2
3
SW7
SW9
SW6
CN31
F1
F4
3
52C
21S4
1 (GRN) 3
1 (BLK) 3
21S4
CNDM
(WHT)
123
12345
TB7
A B S
M-NET
X51
CNAC
(WHT)
X52
F3
12
34
X53
F2
21
123
w1
CN51
(WHT)
CN4
(WHT)
X55
1
CN2
(WHT)
1234567
M-NET SUBSTRATE
LED1
CNM
(WHT)
LED4
12
CN2M
LED5 (WHT)
1 2 3 4 5 6 7 8 9 10 111213 14
TRANS
CNDC
(PNK)
CNS
(WHT) 3 2 1
LEV-B CNVMNT CNMNT
(RED) (WHT) (WHT)
SW10
63H
(YLW)
(WHT)
MF2
F5
LEV-A
(WHT)
TH3 TH4
(WHT) (WHT)
12345
SW12
LED3
w1
123
SW1
TH7/6
(RED)
12
SW4 SWP SW8 SW5
TH33
(YLW)
12
LED1
4 5 6 7 CNF2
MF1
1234
LED2
1
(WHT)
12
1
4 5 6 7 CNF1
3
1
CND
(WHT)
06.5.15 0:52 PM
12345
CN5
(WHT)
OCS05A-2.qxp
SV2
1 (BLU)
3
SS
1 (WHT)
SV
P.B.
~
+
~
N.F.
DS3
TABS
-
~
+
~
LO
NO
1 2
CN5
(RED)
NI
EI
-
DS2
TABP1
(WHT)
CNAC1
3 1
LI
RED
U
V
TABW
12
+
TABV
12
(RED)
CNAC2
3 1
TABN1
TABN2
BLK
12
TABP
CB
+
TABU
TABP2
CN3
(WHT)
CN5
(RED)
CN4
(WHT)
TABN
IPM
WHT
1234567
+
CN2
(WHT)
-
CNDC 1 3
(PNK)
123456
TH8
TABT
CNAF
(WHT)
W
MC
TB1 L
DCL
N
S1 S2 S3
L2
L1
RS
123456
+
P
-
N1
N2
I
ACTM
SW6
ON
100V OFF
NO FUSE
BREAKER
SW10
ON
OFF
1 2 3 4 5 6
INDOOR
UNIT
ON
125V OFF
1 2
ON
OFF
1 2 3 4 5 6
POWER SUPPLY
~/N
230V 50Hz
ON
140V OFF
NAME
Terminal Block<M-net connection>
Connector<Transmission>
Connector<Power Supply>
Connector<M-NET communication>
Switch<Status of communication>
Switch<Address setting : 1st digit>
Switch<Address setting : 2nd digit>
LED<Power Supply : DC5V>
LED<Connection to Outdoor Unit>
LED<Transmission : Sending>
LED<Transmission : Recelving>
LED<Power Supply : DC12V>
52
1 2
ON
OFF
1 2 3 4 5 6
M-NET ADAPTER
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
w1MODEL SELECT
MODEL
52C
1 2
OCS05A-2.qxp
06.5.15 0:52 PM
Page 53
PUHZ-RP100YHA2
SYMBOL
TB1
TB2
MC
MF1,MF2
21S4
SV
63H
TH3
TH4
TH6
TH7
TH33
LEV
ACL1~ACL4
CB1,CB2
CK
RS
P.B.
TB-U/V/W
TB-L1/L2/L3
TB-P2
TB-C1
TB-N1
CT1, CT2
PUHZ-RP125YHA2
NAME
Terminal Block(Power Supply )
Terminal Block(Indoor/Outdoor )
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
Solenoid Valve (Bypass Valve)
High Pressure Switch
Thermistor(Outdoor Pipe)
Thermistor(Discharge)
Thermistor(Outdoor 2-Phase Pipe)
Thermistor(Outdoor)
Thermistor(Outdoor Pipe)
Linear Expansion Valve
Reactor
Main Smoothing Capacitor
Capacitor
Rush Current Protect Resistor
Power Circuit Board
Connection Terminal(U/V/W-Phase)
Connection Terminal(L1/L2/L3-Power Supply)
Connection Terminal
Connection Terminal
Connection Terminal
Current Trans
SYMBOL
N.F.
LI1/LI2/LI3/NI
LO1/LO2/LO3/NO
GD1
CONV.B
L1-A1/IN
L1-A2/OU
L2-A2/OU
L3-A2/OU
N-IN
CK-OU
C.B.
F1,F2
F3,F4
SW1
SW4
SW5
SW6
SW7
SW8
SW9
SW10
SWP
PUHZ-RP140YHA2
NAME
Noise Filter Circuit Board
Connection Terminal(L1/L2/L3/N-Power Supply)
Connection Terminal(L1/L2/L3/N-Power Supply)
Connection Terminal(Ground)
Converter Circuit Board
Connection Terminal(L1-Power Supply)
Connection Terminal(L1-Power Supply)
Connection Terminal(L2-Power Supply)
Connection Terminal(L3-Power Supply)
Connection Terminal
Connection Terminal
Controller Circuit Board
FUSE(T6.3AL250V)
FUSE(T6.3AL250V)
Switch(Forced Defrost, Defect History Record
Reset, Refrigerant Adress)
Switch(Test Operation)
Switch(Function Switch)
Switch(Model Select)
Switch(Function Switch)
Switch(Function Switch)
Switch(Function Switch)
Switch(Model Select)
Switch(Pump Down)
SYMBOL
CN31
21S4
SV2
SS
LEV-A/LEV-B
63H
TH3
TH4
TH7/6
TH33
CNF1/CNF2
LED1/LED2
CNM
CNVMNT
CNMNT
CN3S
CNDM
CN51
NAME
Connector(Emergency Operation)
Connector(Four-Way Valve)
Connector(Bypass Valve)
Connector Connection for Option)
Connector(LEV)
Connector(High Pressure Switch)
Connector(Thermistor)
Connector(Thermistor)
Connector(Thermistor)
Connector(Thermistor)
Connector(Fan Motor Operation)
LED(Operatiion Inspection Indicators)
Connector(A-Control Service Inspection Kit)
Connector(Connect to Optional M-NET Adapter Board)
Connector(Connect to Optional M-NET Adapter Board)
Connector( Connection for Option)
Connector( Connection for Option)
Connector( Connection for Option)
M-NET ADAPTER
Terminal Block(M-NET connection )
Connector(Transmission)
Connector(Power Supply)
Connector(M-NET communication)
Switch(Status of communication)
Switch(Address setting: 1st digit)
Symbols used in wiring diagram above are,
SW12
LED1
LED2
LED3
LED4
LED5
: Connector,
Switch(Address setting. 2nd digit )
LED(Power Supply: DC5V)
LED(Connection to Outdoor Unit)
LED(Transmission: Sending)
LED(Transmission: Receiving)
LED(Power Supply: DC12V)
: Terminal(block)
63H
TH4
SV2
1 (BLU)
3
12345
CN5
(WHT)
SV
(w1 MODEL SELECT)
SW6
MODELS
P.B.
CT2
+
TB-W
BLK W
TB-V
WHT V
12
12
CN5 CN4
(RED) (WHT)
+
WHT
TB-L1
RED
140Y
ON
OFF
1 2 3 4 5 6
1 2
1 2 3 4 5 6
ON
OFF
1 2
TB-C1
TB-N1
CB1
CB2
CK
CNAC1 1
(WHT)
L1-A1
S3
N.F.
1 2
ON
OFF
123
CN7
(WHT)
TB-P2
S2
NO FUSE
BREAKER
1 2 3 4 5 6
L3-OU
BLK
TB-L2
ON
OFF
RS
TB2
S1
INDOOR
UNIT
-
TB-L3
125Y
CNCT 1 2
(RED)
3
SW10
ON
OFF
U
RED
TB-U
CT1
MC
ON
OFF
1
3 CNAC2
(RED)
L1-A2
1234567
CN2
(WHT)
100Y
CK-OU
123
CN7
(WHT)
CND
(WHT)
M-NET
L2-A2
21S4
3
TB7
A B S
SS
1 (WHT)
L1-OU
3
21S4
1 (GRN)
N-IN
BLK
F4
123
L2-OU
F1
CNS
(WHT) 3 2 1
w1
CONV.B.
L1-IN
F3
CNAC
(WHT)
12
34
X55
F2
SW12
LED3
LED4
LED1
CNDC
(PNK)
CN4
(WHT)
21
LED2
L3-A2
1
CN2
(WHT)
1234567
SW11
SW1
12
CN2M
LED5 (WHT)
CN31
X51
TRANS
SW9 SW7
w1
SW10
1 2 3 4 5 6 7 8 9 10 11121314
CNM
SW6
123456 123 12345
LEV-B CNVMNT CNMNT
(RED)
(WHT) (WHT)
3
F5
123456
LEV-A
(WHT)
SW1
4 5 6 7 CNF2
(WHT)
12 12
TH3 TH4
(WHT) (WHT)
LED1
1
1234
TH7/6
(RED)
M-NET ADAPTER (OPTION)
X52
MF2
12
TH33
(YLW)
LED2
4 5 6 7 CNF1 1 2 3
(WHT) CN3N
63H
(YLW)
3 1
1
MF1
LEV
LEV
C.B.
CN51 CNDM CN3S
(WHT) (WHT) (WHT)
12345 123 123
TH3
SW4 SWP SW8 SW5
TH33 TH7 TH6
BLU
TB7
CN5
CND
CN2M
SW1
SW11
ACL1
TB1
L1
RED
LI1
LO1
RED
L2
WHT
LI2
LO2
WHT
L3
BLK
LI3
LO3
BLK
NI
NO
ACL2
POWER SUPPLY
3N~
400V
50Hz
ACL3
N
BLU
GD1
GD2
53
CNDC 1
(PNK)
3
3
1 CNL
(BLU)
BLU
ACL4
OCS05A-2.qxp
5
06.5.15 0:52 PM
Page 54
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT
PLA-RP·AA(2)
PCA-RP·GA
PKA-RP·GAL
PKA-RP·FAL
PEAD-RP·EA(2) PEAD-RP·GA
PCA-RP·HA
PSA-RP·GA
Strainer(#50)
Heat exchanger
Refrigerant GAS pipe connection
(Flare)
Thermistor TH5
(Cond./Eva. temperature)
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant LIQUID pipe connection
(Flare)
Distributor
with strainer(#50)
Thermistor TH1
(Room temperature)
Thermistor TH2
Pipe temperature (Liquid)
Strainer(#50)
54
OCS05A-2.qxp
06.5.15 0:52 PM
Page 55
5-2. OUTDOOR UNIT
PUHZ-RP35VHA2
PUHZ-RP50VHA2
Heat exchanger
Stop valve
(with service port)
Refrigerant GAS pipe
connection(1/2F)
Thermistor TH6
(Outdoor 2-phase pipe)
Charge plug
Solenoid valve
(Four-way valve)
Thermistor TH7
(Outdoor)
Strainer
#50
Thermistor TH3
(Outdoor pipe)
Muffler
Distributor
High pressure
switch 63H
Thermistor TH4
(Discharge)
Strainer
#100
Thermistor TH33
(Outdoor pipe)
Muffler
Linear
expansion valve B
Compressor
Power
receiver
Linear expansion valve A
Stop valve
Refrigerant LIQUID pipe
connection(1/4F)
Strainer
#100
PUHZ-RP60VHA2
PUHZ-RP71VHA2
Heat exchanger
Ball valve
Refrigerant GAS pipe
connection(5/8F)
Strainer
#50
Thermistor TH7
(Outdoor)
Thermistor TH6
(Outdoor 2-phase pipe)
4-way valve
Oil separator
Bypass valve
Charge plug
(Low pressure)
Charge plug
(High pressure)
Capillary tube
O.D.4.0OI.D.2.4OL500
Capillary tube
O.D.2.5OI.D.0.6OL1000
Thermistor TH3
(Outdoor pipe)
Distributor
High pressure
switch 63H
Strainer
#100
Thermistor TH4
(Discharge)
Strainer
#100
Stop valve
(with service port)
Refrigerant LIQUID pipe
connection(3/8F)
Strainer
#100
Power
receiver
Linear
expansion
valve B
Thermistor TH33
(Outdoor pipe)
Muffler Compressor
Linear expansion valve A
Strainer
#100
Refrigerant flow in cooling
Refrigerant flow in heating
55
OCS05A-2.qxp
06.5.15 0:52 PM
Page 56
PUHZ-RP100VHA2
PUHZ-RP125VHA2
PUHZ-RP140VHA2
PUHZ-RP100YHA2
PUHZ-RP125YHA2
PUHZ-RP140YHA2
Heat exchanger
Refrigerant GAS pipe
connection(5/8F)
Ball valve Strainer
#50
Thermistor TH7
(Outdoor)
Thermistor TH6
(Outdoor 2-phase pipe)
Solenoid valve
(Four-way valve)
Charge plug
(High pressure)
Thermistor TH3
(Outdoor pipe)
Muffler
Charge plug
(Low pressure)
Distributor
High pressure
switch 63H
Strainer
#100
Thermistor TH4
(Discharge)
Strainer
#100
Thermistor TH33
(Outdoor pipe)
Linear
expansion valve B
Stop valve
(with service port)
Refrigerant LIQUID pipe
connection(3/8F)
Strainer
#100
Power
receiver
Strainer
#100
Compressor
Linear expansion valve A
Restrictor
valve
Strainer
#100
Strainer
#100
Replace filter
Solenoid valve
(Bypass valve)
Refrigerant flow in cooling
Refrigerant flow in heating
56
OCS05A-2.qxp
06.5.15 0:52 PM
6
Page 57
PERFORMANCE CURVES
FOR THE COMBINATION OF OUTDOOR UNIT PUHZ-RP•VHA2, PUHZ-RP100~140YHA2
Cooling capacity
1.4
Cooling capacity ratio
Indoor intake air wet-bulb temperature <W.B. :>
1.2
22
1.0
20
18
0.8
0.6
16
-5
0
5
10
15
20
25
30
35
40
46
Outdoor intake air dry-bulb temperature <D.B. :>
Cooling input
22 20
18
16
Cooling input ratio
1.2
1.0
0.8
0.6
Indoor intake air wet-bulb temperature <W.B. :>
0.4
-5
0
5
10
15
20
25
30
35
40
Outdoor intake air dry-bulb temperature <D.B. :>
Note : This diagrams show the case where the operation frequency of a compressor is fixed.
57
46
OCS05A-2.qxp
06.5.15 0:53 PM
Page 58
Heating capacity
Indoor intake air dry-bulb temperature <D.B. :>
Outdoor intake air wet-bulb temperature <W.B. :>
Heating input
Indoor intake air dry-bulb temperature <D.B. :>
Outdoor intake air wet-bulb temperature <W.B. :>
Note : This diagrams show the case where the operation frequency of a compressor is fixed.
58
OCS05A-2.qxp
06.5.15 0:53 PM
7
Page 59
CORRECTION FACTORS
PUHZ-RP·VHA2, PUHZ-RP100~140YHA2
Cooling capacity correction factors
Outdoor unit
Refrigerant piping length (one way)
30m
40m
50m
55m
5m
10m
20m
PUHZ-RP35VHA2
1.00
0.992
0.976
0.962
0.949
0.936
PUHZ-RP50VHA2
1.00
0.985
0.957
0.931
0.908
PUHZ-RP60VHA2
1.00
0.992
0.976
0.962
PUHZ-RP71VHA2
1.00
0.988
0.966
1.00
0.985
1.00
1.00
PUHZ-RP100VHA2
PUHZ-RP100YHA2
PUHZ-RP125VHA2
PUHZ-RP125YHA2
PUHZ-RP140VHA2
PUHZ-RP140YHA2
60m
70m
80m
0.930
—
—
—
0.886
0.876
—
—
—
0.949
0.936
0.930
—
—
—
0.946
0.929
0.913
0.905
—
—
—
0.957
0.931
0.908
0.886
0.876
0.865
0.846
0.829
0.981
0.946
0.914
0.885
0.858
0.845
0.834
0.812
0.792
0.976
0.931
0.893
0.858
0.827
0.813
0.800
0.775
0.753
60m
70m
80m
Heating capacity correction factors
5m
10m
20m
Refrigerant piping length (one way)
30m
40m
50m
55m
PUHZ-RP35VHA2
1.00
0.997
0.991
0.985
0.979
0.973
0.970
—
—
—
PUHZ-RP50VHA2
1.00
0.997
0.991
0.985
0.979
0.973
0.970
—
—
—
PUHZ-RP60VHA2
1.00
0.997
0.991
0.985
0.979
0.973
0.970
—
—
—
PUHZ-RP71VHA2
1.00
0.997
0.991
0.985
0.979
0.973
0.970
—
—
—
1.00
0.997
0.991
0.985
0.979
0.973
0.970
0.967
0.961
0.955
1.00
0.997
0.991
0.985
0.979
0.973
0.970
0.967
0.961
0.955
1.00
0.997
0.991
0.985
0.979
0.973
0.970
0.967
0.961
0.955
Outdoor unit
PUHZ-RP100VHA2
PUHZ-RP100YHA2
PUHZ-RP125VHA2
PUHZ-RP125YHA2
PUHZ-RP140VHA2
PUHZ-RP140YHA2
59
OCS05A-2.qxp
06.5.15 0:53 PM
8
Page 60
APPLICABLE EXTENSION PIPE FOR EACH MODEL
8-1. PIPE LENGTH
8-1-1. 1:1 SYSTEM
Pipe length
<Table 1> Maximum pipe length
Liquid
pipe
(mm)
Gas
pipe
(mm)
OD
Thickness
OD
Thickness
RP35•50
[6.35
t0.8
[9.52
[12.7
t0.8
t0.8
Standard size
30m w1
50m
[30m]
[30m]
10m
[10m]
RP60•71
[15.88
t1.0
w2
30m
[30m]
[12.7
t0.8
10m
[10m]
30m
[30m]
[9.52
t0.8
[15.88
t1.0
w2
30m
[20m]
Standard size
50m
[30m]
Standard size
50m w3
[30m]
30m
[20m]
RP100~140
[19.05
t1.0
[12.7
t0.8
[19.05
[15.88
t1.0
t1.0
<Marks in the table>
: It can be used.
: Cooling capacity is lowered.
: Additional refrigerant charge is required when
the pipe length exceeds 10m.
50m
[30m]
50m
[20m]
The maximum pipe length
Charge-less pipe length
50m
[30m]
30m
[20m]
50m
[20m]
w1. Maximum pipe length is RP50, it becomes 10m.
w2. Change the SW8-1 on the outdoor controller circuit board from OFF to ON.
w3. The maximum length is 75m in case of new pipes.
8-1-2. TWIN AND TRIPLE SYSTEM
(1) TWIN SYSTEM
(2) TRIPLE SYSTEM
<Table 2> Maximum pipe length
<Table 3> Maximum pipe length
RP71(RP35o2)
Main pipe
(mm)
[A]
Liquid pipe
Gas pipe
Liquid pipe
[6.35
Gas pipe
[12.7
[6.35
[12.7
Branch
pipe Liquid pipe [9.52
(mm) Gas pipe [15.88
[B, C]
Liquid pipe [12.7
Gas pipe
RP100(RP50o2)
[9.52
[9.52
[15.88
[15.88
Standard size Standard size
50m
50m w
[30m]
[30m]
50m
[30m]
[9.52
[19.05
[12.7
[19.05
50m
[30m]
50m
[20m]
50m
[30m]
50m
[20m]
50m
[30m]
RP125(RP60o2) • RP140(RP71o2)
[9.52
[15.88
Standard size
50m w
[30m]
[9.52
[19.05
[12.7
[19.05
50m
[30m]
50m
[20m]
RP140(RP50o3)
Main pipe
(mm)
[A]
ø9.52 ø9.52
ø15.88 ø19.05
Gas pipe
Liquid pipe ø6.35 Standard size
50m w 50m
Gas pipe ø12.7 [30m] [30m]
Liquid pipe
Branch
pipe Liquid pipe ø9.52
(mm) Gas pipe ø15.88
[B, C, D]
Liquid pipe ø12.7
50m
[30m]
50m
[20m]
50m
[20m]
Gas pipe ø19.05
[19.05
w The maximum length is 75m in case of new pipes.
w The maximum length is 75m in case of new pipes.
Indoor unit side
Indoor unit side
Indoor unit
Indoor unit
Indoor unit
Indoor unit
B
h
B
h
50m
[30m]
ø12.7
ø19.05
C
C
D
Indoor unit
Distribution pipe
Outdoor unit
H
H
Outdoor unit
Distribution pipe
Outdoor unit side
Outdoor unit side
A
A
<TRIPLE SYSTEM>
Total length A + B + C + D
RP140: 75 m
<TWIN SYSTEM>
Total length A + B + C
RP71
: 50 m
RP100-140: 75 m
60
OCS05A-3.qxp
06.5.15 0:54 PM
Page 61
8-2. ADJUSTING THE AMOUNT OF REFRIGERANT
• Check additional refrigerant charging amount referring to table 5.6 when liquid pipe is one size larger than standard diameter.
<Table 5> Required additional charge when the pipe size is larger than the standard diameter (1:1 SYSTEM)
Liquid pipe dia
Refrigerant amount to be added
35,50
[9.52
60 g per 1 m
60,71
[12.7
100 g per 1 m
100~140
[12.7
100 g per 1 m
<Table 6> Required additional charge when the pipe size is larger than the standard diameter (TWIN/TRIPLE SYSTEM)
Capacity
When the extension pipe length (main piping + branch piping) exceed 20 m
71~140
Additional refrigerant amount
W(g) = (100 o L1) + (60 o L2) + (30 o L3) - 2000
If the calculation produces a negative number ( W [ 0), additional charging is not necessary.
L1: [12.7 liquid pipe length (m)
L2: [9.52 liquid pipe length (m)
L3: [6.35 liquid pipe length (m)
<Table 7> Additional refrigerant charging amount for pipe of standard diameter
Type
Outdoor unit
1:1
PUHZ-RP35,50VHA2
system PUHZ-RP71VHA2
PUHZ-RP100~140
Type
Outdoor unit
Twin Triple PUHZ-RP71VHA2
system PUHZ-RP100~140
Permitted
pipe length
50m or less
Amount of unit
filling refrigerant (kg)
Additional refrigerant charging amount
for pipe length exceeding 30 m (kg)
31 — 40m 41 — 50m 51 — 60m 61 — 70m 71 — 75m
2.5kg
0.2kg
0.4kg
3.5kg
0.6kg
1.2kg
75m or less
5.0kg
0.6kg
1.2kg
Permitted
pipe length
Amount of unit
filling refrigerant (kg)
50m or less
3.5kg
0.6kg
1.2kg
75m or less
5.0kg
0.6kg
1.2kg
61
1.8kg
2.4kg
Additional refrigerant charging amount
for pipe length exceeding 30 m (kg)
—
31
40m 41 — 50m 51 — 60m 61 — 70m 71 — 75m
1.8kg
2.4kg
OCS05A-3.qxp
06.5.15 0:54 PM
Page 62
8-3. CAPACITY CORRECTION CURVES
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered comparing to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
[Sample calculation]
Indoor unit RP60 o 2 units (Twin system)
Outdoor unit RP125 o 1
■ Condition
Using existing pipes.
• Outdoor unit side
Liquid pipe [12.7 / Gas pipe [19.05
pipe length (A) 20m
• Indoor unit side
Liquid pipe [9.52 / Gas pipe [15.88
pipe length (B) 20m + (C) 15m
1) Farthest piping length
20m + 15m = 35m
Number of bends : 10
2) Corrected piping length 35m + 0.3 o 10 = 38m
3) Capacity correction
Outdoor unit side’s gas pipe [19.05
Standard [15.88 → 1 size up
Refer to 1Capacity curves <Standard size>
4) Capacity
Cooling capacity = Standard cooling capacity o 0.89
Heating capacity = Standard heating capacity o 0.98
1 Capacity curves for PUHZ-RP • HA2 model <Standard size>
Cooling
100
Heating
95
Heating RP35, 50, 60,
71, 100, 125 and 140
models
(Up to 55m for RP35,
50, 60, 71 models)
Capacity ratio [%]
Cooling RP35, 60 models
Cooling RP71 model
90
85
Cooling RP50, 100 models
80
Cooling RP125 model
75
Cooling RP140 model
Note: The permitted pipe length is up to 55m for RP35, 50, 60, 71 model.
The permitted pipe length is up to 80m for RP100 ~ 140 model.
70
5
10
15
20
25
30
35
40
45
50
55
Corrected pipe length [m]
62
60
65
70
75
80
OCS05A-3.qxp
06.5.15 0:54 PM
Page 63
2 Capacity curve for PUHZ-RP35, 50 models
<When gas pipe is one size smaller than standard size>
Cooling
100
Heating
Heating RP35, RP50 ([9.52)
Capacity ratio [%]
95
90
Cooling RP50
([9.52)
85
Cooling RP35 ([9.52)
80
5
10
15
20
25
30
35
Corrected pipe length [m]
3 Capacity curve for PUHZ-RP60, 71 models
<When gas pipe is one size smaller than standard size>
100
Heating RP60, RP71 ([12.7)
Capacity ratio [%]
95
90
85
80
Cooling RP60,RP71 ([12.7)
5
10
15
20
25
30
35
Corrected pipe length [m]
4 When gas pipe is one size larger than standard size for PUHZ-RP100, 125 and 140.
1 Capacity can be obtained by referring to capacity curves of standard size.
63
OCS05A-3.qxp
9
06.5.15 0:54 PM
Page 64
AIR FLOW DATA
9-1. OUTLET AIR SPEED AND COVERAGE RANGE
Air flow
Air speed
Coverage range
m3/min.
m/sec.
m
PLA-RP35AA
14
2.8
4.0
Air flow
Air speed
Coverage range
m3/min
m/sec
m
Air flow
Air speed
Coverage range
m3/min
Air flow m3/min
Air speed m/sec
Coverage range m (ft)
Air flow m3/min
Air speed m/sec
Coverage range m (ft)
Air flow
Air speed
Coverage range
m/sec
m
PLA-RP50AA
18
3.6
5.2
PLA-RP60AA
18
3.6
5.2
PLA-RP71AA
20
4.0
5.7
PLA-RP125AA2
30
6.6
8.9
PLA-RP140AA2
30
6.6
8.9
PCA-RP50GA PCA-RP60GA PCA-RP71GA PCA-RP100GA PCA-RP125GA PCA-RP140GA
34
34
18
13
25
18
4.4
4.4
3.8
3.7
4.1
3.8
15.2
15.2
10.4
8.8
12.6
10.4
PCA-RP71HA PCA-RP125HA
38
19
4.2
2.9
7.9
13.2
PKA-RP35GAL
PKA-RP50GAL
12
12
5.3
5.3
10(32.8)
10(32.8)
PKA-RP60FAL
PKA-RP71FAL
PKA-RP100FAL
20
20
28
4.9
4.9
5.4
12.4(40.7)
12.4(40.7)
15.3(50.2)
m3/min
m/sec
m
PLA-RP100AA2
28
4.9
7.4
PSA-RP71GA
18
2.6
8.3
PSA-RP100GA
31
4.5
14.3
PSA-RP125GA
33
4.8
15.2
PSA-RP140GA
35
4.9
16.1
The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally from
the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
64
OCS05A-3.qxp
06.5.15 0:54 PM
Page 65
9-2. PLA-RP·AA(2)
9-2-1. FRESH AIR INTAKE AMOUNT
65
OCS05A-3.qxp
06.5.15 0:54 PM
Page 66
66
OCS05A-3.qxp
06.5.15 0:54 PM
Page 67
9-2-2. BRANCH DUCT (Installation at site)
67
OCS05A-3.qxp
06.5.15 0:54 PM
Page 68
Branch duct air flow rate/static pressure characteristics
PLA-RP35AA
4-way air flow (horizontal vane) Rectangular duct
4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct
3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct
2-way air flow (horizontal vane) Round duct
68
OCS05A-3.qxp
06.5.15 0:54 PM
Page 69
PLA-RP50AA
PLA-RP60AA
4-way air flow (horizontal vane) Rectangular duct
4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct
3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct
2-way air flow (horizontal vane) Round duct
69
OCS05A-3.qxp
06.5.15 0:54 PM
Page 70
PLA-RP71AA
4-way air flow (horizontal vane) Round duct
Static pressure [Pa]
30
20
High
10
Low
0
1
2
3
4
5
6
Static pressure [Pa]
4-way air flow (horizontal vane) Rectangular duct
30
20
High
10
Low
0
1
2
3
Air flow rate [m3/min]
3-way air flow (horizontal vane) Rectangular duct
6
60
50
Static pressure [Pa]
Static pressure [Pa]
5
3-way air flow (horizontal vane) Round duct
60
40
High
30
20
Low
10
50
40
1
2
3
4
5
6
7
8
9
High
30
20
Low
10
0
0
1
2
3
4
Air flow rate [m /min]
2-way air flow (horizontal vane) Rectangular duct
5
6
7
2-way air flow (horizontal vane) Round duct
100
100
90
90
80
Static pressure [Pa]
80
70
60
High
50
40
Low
30
20
10
70
60
50
High
40
Low
30
20
10
0
1
2
3
4
5
6
7
8
9
10
8
Air flow rate [m3/min]
3
Static pressure [Pa]
4
Air flow rate [m3/min]
11
0
Air flow rate [m3/min]
1
2
3
4
5
6
Air flow rate [m3/min]
70
7
9
OCS05A-3.qxp
06.5.15 0:54 PM
Page 71
PLA-RP100AA2
4-way air flow (horizontal vane) Round duct
50
Static pressure [Pa]
Static pressure [Pa]
4-way air flow (horizontal vane) Rectangular duct
40
30
High
20
Low
10
0
1
2
3
4
5
6
7
8
9
50
40
30
High
20
Low
10
0
10
1
2
3
4
5
Air flow rate [m /min]
3
3-way air flow (horizontal vane) Rectangular duct
8
9
10
100
90
90
Static pressure [Pa]
Static pressure [Pa]
7
3-way air flow (horizontal vane) Round duct
100
80
70
60
High
50
40
30
Low
20
10
80
70
60
50
High
40
30
Low
20
10
0
1
2
3
4
5
6
7
8
9
10
11
12
13
0
14
1
Air flow rate [m3/min]
110
100
100
90
90
Static pressure
120
110
80
High
60
50
Low
40
30
50
4
5
6
7
8
9
10
11
12
13
14
15
7
8
9
10
11
12
13
14
High
40
Low
30
10
3
6
60
10
2
5
70
20
1
4
80
20
0
3
2-way air flow (horizontal vane) Round duct
120
70
2
Air flow rate [m3/min]
2-way air flow (horizontal vane) Rectangular duct
Static pressure [Pa]
6
Air flow rate [m3/min]
0
16
1
Air flow rate [m /min]
3
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Air flow rate [m3/min]
71
16
OCS05A-3.qxp
06.5.15 0:54 PM
Page 72
PLA-RP125AA2
PLA-RP140AA2
4-way air flow (horizontal vane) Round duct
50
50
40
30
High
20
Low
10
0
1
2
3
4
5
6
7
8
9
10
Static pressure [Pa]
Static pressure [Pa]
4-way air flow (horizontal vane) Rectangular duct
40
30
High
20
10
Low
0
1
2
3
4
5
100
100
90
90
80
70
60
High
40
Low
20
10
0
9
10
80
70
60
50
High
40
30
Low
20
10
1
2
3
4
5
6
7
8
9
10
11
12
13
0
14
1
2
3
4
5
6
Air flow rate [m /min]
3
2-way air flow (horizontal vane) Rectangular duct
120
110
110
100
100
90
80
70
High
50
40
Low
30
8
9
10
11
12
13
14
2-way air flow (horizontal vane) Round duct
120
60
7
Air flow rate [m3/min]
Static pressure[Pa]
Static pressure [Pa]
8
3-way air flow (horizontal vane) Round duct
Static pressure [Pa]
Static pressure [Pa]
3-way air flow (horizontal vane) Rectangular duct
30
7
Air flow rate [m /min]
Air flow rate [m /min]
50
6
3
3
20
10
90
80
70
60
50
High
40
Low
30
20
10
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
16
1
Air flow rate [m3/min]
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Air flow rate [m3/min]
72
16
OCS05A-3.qxp
06.5.15 0:54 PM
Page 73
9-2. PEAD-RP·EA, EA2, GA
9-2-1. FAN PERFORMANCE AND CORRECTED AIR FLOW
PEAD-RP35EA2 PEAD-RP50EA
Fan Performance <30Pa>
Corrected Air Flow
120
100
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
140
80
60
40
20
Cooling
1.0
0.9
0.8
8
6
8
10
10 12 14 16 18 20
Air Flow (CMM)
Fan Performance <70Pa>
160
12 14 16 18
Air flow (CMM)
20
22
12 14 16 18
Air flow (CMM)
20
22
Heating
1.3
140
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
1.1
Capacity
input
120
100
80
60
40
1.2
1.1
1.0
0.9
0.8
8
10
20
8
10 12 14 16 18 20 22
Air Flow (CMM)
Fan Performance <30Pa>
120
Correction factor
100
80
60
40
20
8
140
External static pressure (Pa)
(1Pa 0.1mmAq)
Corrected Air Flow
1.1
Capacity
input
Cooling
1.0
0.9
0.8
12 14 16 18 20 22
Air flow (CMM)
10 12 14 16 18 20 22 24
Air Flow (CMM)
24 26
Heating
Fan Performance <70Pa>
1.3
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
PEAD-RP60EA
120
100
80
60
40
1.2
1.1
1.0
0.9
0.8
12 14 16 18 20 22 24
Air flow (CMM)
20
10 12 14 16 18 20 22 24 26
Air Flow (CMM)
73
26
OCS05A-3.qxp
06.5.15 0:54 PM
Page 74
PEAD-RP71EA
Fan performance <70Pa>
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa = 0.1mmAq)
Recommended range
External static pressure (Pa)
(1Pa = 0.1mmAq)
200
180
160
140
Hi
Lo
120
100
80
60
40
20
180
160
140
120
Hi
Lo
100
80
60
40
20
12 16 20 24 28 32
12 16 20 24 28 32
A i r fl ow (C MM)
A i r fl o w (C M M )
Corrected Air Flow
Capacity
Input
Cooling
1.1
1.2
Correction factor
Correction factor
Heating
1.3
1.0
0.9
0.8
12
16
20
24
28
1.1
1.0
0.9
32
Air flow (CMM)
0.8
12
16
20
24
28
32
Air flow (CMM)
PEAD-RP100EA2 PEAD-RP125EA
Fan performance <70Pa>
Fan performance <130Pa>
Recommended range
220
External static pressure (Pa)
(1Pa = 0.1mmAq)
External static pressure (Pa)
(1Pa = 0.1mmAq)
Recommended range
200
180
160
140
120
100
Hi
80
60
Lo
40
20
220
200
180
160
140
120
100
32 34 36 38 40 42 44 46 48
60
40
32 34 36 38 40 42 44 46
A i r fl ow (C MM)
Heating
Corrected Air Flow
1.2
Correction factor
Capacity
Input
Cooling
Correction factor
1.1
1.0
0.9
34
36
Lo
20
A i r fl o w (C M M )
0.8
32
Hi
80
38
40
42
44
46
1.1
1.0
0.9
0.8
48
32
Air flow (CMM)
34
36
38
40
42
44
Air flow (CMM)
74
46
48
06.5.15 0:54 PM
Page 75
PEAD-RP140EA
Fan performance <70Pa>
Recommended range
External static pressure (Pa)
220
(1Pa = 0.1mmAq)
External static pressure (Pa)
Recommended range
200
180
160
140
120
100
80
60
40
Hi
Lo
200
(1Pa = 0.1mmAq)
Fan performance <130Pa>
180
160
140
120
100
80
Hi
60
Lo
40
20
20
36 38 40 42 44 46 48 50 52
36 38 40 42 44 46 48 50
A i r fl o w (C M M)
A i r fl ow (C MM )
Heating
Corrected Air Flow
Correction factor
1.1
1.0
0.9
0.8
36
1.2
Capacity
Input
Cooling
Correction factor
OCS05A-3.qxp
38
40
42
44
46
48
50
52
1.1
1.0
0.9
0.8
36
38
40
42
44
46
Air flow (CMM)
Air flow (CMM)
75
48
50
52
OCS05A-3.qxp
06.5.15 0:54 PM
Page 76
PEAD-RP60GA
PEAD-RP71GA
76
OCS05A-3.qxp
06.5.15 0:54 PM
Page 77
PEAD-RP100GA
77
OCS05A-3.qxp
10
06.5.15 0:54 PM
Page 78
NOISE CRITERION CURVES
NOTCH SPL(dB)
High
31
Medium1
29
Medium2
28
Low
27
PLA-RP35AA
LINE
PLA-RP50AA
PLA-RP60AA
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
250
500
1000
2000
4000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
8000
63
125
250
BAND CENTER FREQUENCIES, Hz
LINE
1000
2000
4000
NOTCH SPL(dB)
High
41
Medium1
39
Medium2
36
Low
33
PLA-RP100AA2
90
8000
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
125
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
63
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
500
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB)
High
34
Medium1
32
Medium2
30
Low
28
PLA-RP71AA
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
20
NOTCH SPL(dB)
High
33
Medium1
31
Medium2
29
Low
28
250
500
1000
2000
4000
8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
BAND CENTER FREQUENCIES, Hz
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
78
4000
8000
OCS05A-3.qxp
06.5.15 0:54 PM
Page 79
NOTCH SPL(dB)
45
High
43
Medium1
40
Medium2
37
Low
PLA-RP125AA2
LINE
PLA-RP140AA2
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NOTCH SPL(dB)
45
High
43
Medium1
40
Medium2
37
Low
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
63
125
250
BAND CENTER FREQUENCIES, Hz
500
1000
2000
BAND CENTER FREQUENCIES, Hz
UNIT
CEILING
1.5m
MICROPHONE
79
4000
8000
Page 80
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
PEAD-RP35EA2
PEAD-RP50EA
70
PEAD-RP35EA2
PEAD-RP50EA
(External static
pressure 30Pa)
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
06.5.15 0:54 PM
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
Approximate minimum
audible limit on
continuous noise
0
63
125
250
500
1000
2000
4000
70
High
Low
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
Approximate minimum
audible limit on
continuous noise
0
8000
63
(External static
pressure 30Pa)
High
Low
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
Approximate minimum
audible limit on
continuous noise
63
125
250
500
1000
2000
4000
250
500
PEAD-RP60EA
60
0
125
1000
2000
4000
8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
PEAD-RP60EA
70
(External static
pressure 70Pa)
60
OCTAVE BAND CENTER FREQUENCIES (Hz)
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCS05A-3.qxp
8000
70
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
Approximate minimum
audible limit on
continuous noise
0
63
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static
pressure 70Pa)
125
250
500
1000
2000
4000
OCTAVE BAND CENTER FREQUENCIES (Hz)
80
8000
OCS05A-3.qxp
06.5.15 0:55 PM
Page 81
81
OCS05A-3.qxp
06.5.15 0:55 PM
PKA-RP35GAL
PKA-RP50GAL
Page 82
NOTCH SPL(dB)
High
43
Medium1
41
38
Medium2
Low
36
LINE
PKA-RP60FAL
PKA-RP71FAL
90
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
70
10
63
125
250
500
1000
2000
4000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
20
NC-20
10
8000
63
125
250
500
PKA-RP100FAL
WALL
1m
MICROPHONE
2000
4000
8000
NOTCH SPL(dB)
High
46
Low
41
LINE
90
UNIT
1m
1000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 µbar)
LINE
90
80
20
NOTCH SPL(dB)
High
45
Low
39
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
82
4000
8000
06.5.15 0:55 PM
Page 83
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
PCA-RP50GA
NOTCH SPL(dB)
42
High
40
Medium1
38
Medium2
37
Low
PCA-RP60GA
PCA-RP71GA
LINE
90
90
80
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCS05A-3.qxp
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
NC-20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
250
500
1000
2000
4000
63
8000
125
PCA-RP100GA
NOTCH SPL(dB)
High
45
Medium1
43
Medium2
41
Low
40
80
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
500
1000
2000
2000
4000
8000
4000
NOTCH SPL(dB)
High
46
Medium1
45
Medium2
43
Low
41
LINE
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
250
1000
70
NC-20
10
125
500
PCA-RP125GA
LINE
90
63
250
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
NC-20
10
10
20
LINE
70
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NOTCH SPL(dB)
High
43
Medium1
41
Medium2
39
Low
37
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
8000
63
BAND CENTER FREQUENCIES, Hz
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
83
4000
8000
OCS05A-3.qxp
06.5.15 0:55 PM
PCA-RP140GA
Page 84
NOTCH SPL(dB)
High
48
Medium1
46
Medium2
44
Low
42
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
ceiling
1m
70
NC-70
1m
unit
about 1.4m
60
NC-60
MICROPHONE
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB)
High
38
Low
34
LINE
PCA-RP125HA
90
90
80
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
PCA-RP71HA
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
LINE
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NOTCH SPL(dB)
High
50
Low
44
NC-20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
10
63
125
250
500
1000
2000
4000
63
8000
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
84
4000
8000
06.5.15 0:55 PM
Page 85
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
PSA-RP71GA
NOTCH SPL(dB)
45
High
40
Low
PSA-RP100GA
LINE
90
90
80
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
HERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
LINE
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
HERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
63
BAND CENTER FREQUENCIES, Hz
PSA-RP125GA
NOTCH SPL(dB)
High
51
Low
46
LINE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
HERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
NOTCH SPL(dB)
High
49
Low
44
70
NC-20
10
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
OCS05A-3.qxp
4000
8000
BAND CENTER FREQUENCIES, Hz
85
4000
8000
OCS05A-3.qxp
06.5.15 0:55 PM
PSA-RP140GA
Page 86
NOTCH SPL(dB)
High
52
Low
47
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
HERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
MICROPHONE
1m
1m
unit
floor
86
OCS05A-3.qxp
06.5.15 0:55 PM
Page 87
MICROPHONE
1m
UNIT
1.5m
GROUND
PUHZ-RP35VHA2
PUHZ-RP50VHA2
MODE SPL(dB)
COOLING
44
HEATING
46
PUHZ-RP60VHA2
PUHZ-RP71VHA2
LINE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
BAND CENTER FREQUENCIES, Hz
PUHZ-RP100VHA2
PUHZ-RP100YHA2
MODE SPL(dB)
COOLING
49
HEATING
51
500
1000
2000
4000
8000
MODE SPL(dB)
COOLING
50
HEATING
52
LINE
90
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
250
PUHZ-RP125VHA2
PUHZ-RP140VHA2
PUHZ-RP125YHA2
PUHZ-RP140YHA2
LINE
80
10
125
NC-20
BAND CENTER FREQUENCIES, Hz
90
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
MODE SPL(dB)
COOLING
47
HEATING
48
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
BAND CENTER FREQUENCIES, Hz
87
8000
OCS05A-3.qxp
11
06.5.15 0:55 PM
Page 88
OPTIONAL PARTS
11-1. INDOOR UNIT
Part Name
Model Name
Remote sensor
Remote operation adapter
Multiple remote controller adapter
PAC-SE41TS-E
PAC-SF40RM-E
Remote on/off adapter
Power supply terminal kit
L/N/Earth
L/N
Multi-functional casement
High-efficiency filter element
(PAC-SG03TM-E is needed.)
Grille + Wireless remote controller
Grille + Wired remote controller
Space panel
Air outlet shutter plate
(20 set, 2pcs/set)
Wireless remote controller + Wireless Adapter
Drain lift up mechanism
High-efficiency filter
Duct flange for fresh air
Oil mist filter element (12pcs)
Decoration cover
(Front + Suspending bracket cover)
Wired remote controller
(with terminal bed)
Drain lift up mechanism
Motor
(for high external static pressure)
Drain lift up mechanism
Insulation kit
Applicable model
PAC-SA88HA-E (1pc.) All models
PAC-725AD (10pcs.)
PAC-SE55RA-E
PAC-SG96HR-E
All models
except PCA-RP·HA and
PEAD-RP·GA
PAC-SG97HR-E
PCA-RP·HA
PEAD-RP·GA
PAC-SG03TM-E
PAC-SG01KF
PLP-6AALM
PLP-6AAMD
PAC-SG04AS-E
PAC-SG06SP-E
PLA-RP·AA
PLA-RP·AA2
PAR-SL99B-E
PAC-SH20DM-E
PAC-SH21DM-E
PAC-SH22DM-E
PAC-SE80KF-E
PAC-SE81KF-E
PAC-SE82KF-E
PAC-SF28OF-E
PAC-SG38KF-E
PAC-SF81KC-E
PAC-SF82KC-E
PAR-21MAAT-E
PCA-RP·GA
PCA-RP50,60GA
PCA-RP71GA
PCA-RP100,125,140GA
PCA-RP50GA
PCA-RP60,71,100GA
PCA-RP125,140GA
PCA-RP·HA
PAC-SE90DM-E
PAC-SK003MT-F
PAC-KE03DM-F
PAC-SK010DK
88
PCA-RP71HA
PCA-RP125HA
PKA-RP·GAL
PKA-RP·FAL
PKA-RP·FAL
PEAD-RP125,140EA
PEAD-RP100EA2
PEAD-RP·EA,EA2
PEAD-RP·GA
OCS05A-3.qxp
06.5.15 0:55 PM
Page 89
11-2. OUTDOOR UNIT
Part Name
Model Name
Applicable model
M-NET adapter
PAC-SF80MA-E
All models
A-control service tool
PAC-SK52ST
Drain socket
PAC-SG61DS-E
PUHZ-RP35-140
Air outlet guide
PAC-SG58SG-E
PUHZ-RP35, 50
(RP100,125,140 needs two piece.)
PAC-SG59SG-E
PUHZ-RP60-140
Air protect guide
PAC-SG56AG-E
PUHZ-RP35, 50
PAC-SH63AG-E
PUHZ-RP60-140
PAC-SG63DP-E
PUHZ-RP35, 50
PAC-SG64DP-E
PUHZ-RP60-140
Drain pan
Filter dryer
( [6.35)
PAC-SG81DR-E
PUHZ-RP35, 50
Distribution pipe
( [9.52)
(Twin)
PAC-SG82DR-E
MSDD-50SR-E
PUHZ-RP60-140
PUHZ-RP100-140
(Triple)
MSDT-111R-E
PUHZ-RP140
Joint pipe
(Unit
Extension pipe)
( [6.35
[9.52)
PAC-SG72RJ-E
PUHZ-RP35, 50
( [9.52
[12.7)
PAC-SG73RJ-E
PUHZ-RP35, 50
PAC-SG75RJ-E
PUHZ-RP60-140
( [15.88
[19.05)
89
OCS05A-3.qxp
06.5.15 0:55 PM
Page 90
TM
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in May 2006 No.OCS05 REVISED EDITION-A PDF 8
Distributed in Feb. 2006 No.OCS05 PDF 8
Made in Japan.
New publication, effective May 2006.
Specifications subject to change without notice.