TECHNOLOGIES LTD
GDS 302
Single line sample unit
Specification Sheet ref C910
• Continuous monitoring
• Flammable, oxygen or toxic gases
• Easily installed and maintained
• 2 alarm levels
• Alarm relay outputs
• Delay to alarm options
• 4~20mA analogue output
• Compact size
• Comprehensive fault monitoring
• Line blockage monitoring
• Pump failure monitor
• Optional remote pumped sensor unit
Application
The GDS 302 system is designed to monitor gas levels in situations where the positioning of conventional gas sensors may not be practical. This may be due to equipment security, cable routing, access for detector head installation/maintenance, harsh environment or a cost effective means of monitoring designated hazardous areas, typically - tunnels, marine applications, underground/high level voids, process control, brewing, horticulture, livestock husbandry.
Operation
A gas sample is continuously extracted via a fixed sample line from the target area. The central unit provides gas level readouts with two alarm trip points, providing a range of signal outputs for annunciator or control functions.
Technical Data
Measurements
Power supply
Frequency
Consumption
Alarm Settings
Alarm delay
Outputs
•
Combustible Gas L.E.L %Vol, ppm
Toxic Gas - ppm, %Vol
Oxygen % Vol
•
230/115vAC or 24vDC ± 15%
The two voltages may be used simultaneously (standby batteries)
•
50/60Hz
•
10 watts
•
Digital setting (fully adjustable between zero and full scale)
•
T1 - 10 seconds, T2 - 30 seconds,
T1 + T2 - 10 minutes
•
Low alarm relay - S.P.C.O
•
High alarm relay - S.P.C.O
•
Fault alarm relay - S.P.C.O
•
Relays rated 5A/230vAC
ND or NE pre set normally de energised
•
Analogue 4-20mA/1-5v
•
24vDC - 100mA max
(Auxiliary equipment supply)
Indicators
Audible Alarm
Reset Switch
Test Switch
Inhibit
Protection
Environmental
Cable Entry
Sample Tube
Miscellaneous ref C910
•
Power - Green L.E.D.
•
Alarms - Low/High - Red L.E.D.
•
Fault - Amber L.E.D.
•
System test alarm L.E.D’s flashing
•
Low, High gas and Fault
Permanent mute option
•
Auto or Manual - pre set manual
•
Used to check alarm indicators, sounder and relay action
•
Isolation of alarm relays during service
•
IP65
•
Ambient temperature -5 to 45˚C
•
Storage temperature +10 to 60˚C
•
Humidity range 0 - 90 RH
•
Rear, side, top, bottom
•
6mm OD 4mm ID
•
Max. length 6m
•
Dimensions 240H 200W 60D
•
Weight 1.1kg
•
Cable entry - bottom, sides, rear
High
Low
Fault
Power
Reset
Test
GAS ALARM GDS-302
3 core cable - 1km
(24vDC Sig 4/2amA)
OUT
IN
Remote sensor unit
T1 –
T2 –
T1 & T2
LL –
O 2 –
RES –
TP1 –
Alarm delay - 10 secs
Alarm delay - 30 secs
Alarm delay - 10 minutes
Low/Low alarm
Oxygen sensor
Manual/Auto Reset
OV
TP2 +
TP3 –
TP4 +
TP5 –
]
] 4~20mA output
DPM span
TP6 and TP1 sensor supply mV=mA
0.5v=F.S.D
mV = mA
C915 ISO 9001
This document is not contractual and the equipment specification may be modified at any time without prior notice.
GDS Technologies Ltd
Fusion Point, Ash Lane
Garforth, Leeds LS25 2GA
Tel +44 (0)113 286 0166
Fax +44 (0)113 287 8178 [email protected]
www.gds-technologies.co.uk