Evolve EVFE Troubleshooting guide

Add to my manuals
32 Pages

advertisement

Evolve EVFE Troubleshooting guide | Manualzz

Evolve Series

®

Water Filters

For Models:

• EVFE

• EVS

• EAG

• EACG

• EVBF

• EVBF-AN

TABLE OF CONTENTS

Preinstallation Instructions for Dealers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Bypass Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7

Programming Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9

Start-up Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Operating Displays and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-12

Replacement Mineral Instructions for Acid Neutralizing Air Filters . . . . . . . . . . 13

Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-18

Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-27

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-29

Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Quick Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-32

YOUR WATER TEST

Hardness _____________________ gpg

Iron __________________________ ppm pH ___________________________ number

*Nitrates ______________________ ppm

Manganese ___________________ ppm

Sulphur _______________________ yes/no

Total Dissolved Solids ___________

*Over 10 ppm may be harmful for human consumption.

Water conditioners do not remove nitrates or coliform bacteria, this requires specialized equipment.

Your Evolve Series water filters are precision built, high quality products. These units will deliver filtered water for many years to come, when installed and operated properly. Please study this manual carefully and understand the cautions and notes before installing. This manual should be kept for future reference. If you have any questions regarding your water conditioner, contact your local dealer or the manufacturer at the following:

1900 Prospect Court • Appleton, WI 54914

Phone: 920-739-9401 • Fax: 920-739-9406

PREINSTALLATION INSTRUCTIONS FOR DEALERS:

The manufacturer has preset the water treatment unit’s sequence of cycles and cycle times.

The dealer should read this page and guide the installer regarding day override, time of regeneration, service alarm and buzzer alarm settings before installation.

For the installer, the following must be used: see Operating Displays and Instructions for more details), Service Alarms (preset to “OFF”) and Buzzer Alarm

(preset to start at 6 a.m. and end at 10 p.m.)

• Read Normal Operating Displays

• Set Time of Day

• Read Power Loss & Error Display

For the homeowner, please read sections on Bypass Valve and Operating Displays and Maintenance.

During operation, the normal user display is time of day and gallons per minute.

Flow Rate, Vacation Mode, Capacity Remaining and Days to a Regeneration are optional displays but are not normally used. (Vacation Mode is used only when there will be no water usage for an extended period of time. If activated, once

50 gallons of water is used, the unit will automatically regenerate that night and resume normal operation.) Each of these can be viewed by pressing

NEXT

to scroll through them. When stepping through any programming, if no buttons are pressed within 5 minutes, the display returns to a normal user display. Any changes made prior to the 5 minute time out are incorporated. To quickly exit any Programming, Installer Settings, etc., press

SET CLOCK

. Any changes made prior to the exit are incorporated.

If desired, two regenerations within 24 hours are possible with a return to the preset program.

To do a double regeneration:

1. Press the

REGEN

button once. “REGEN TODAY” will flash on the display.

2. Press and hold the

REGEN

button for three seconds until a regeneration begins.

Once the valve has completed the immediate regeneration, the valve will regenerate one more time at the preset.

3

BYPASS VALVE:

The bypass valve is typically used to isolate the control valve from the plumbing system’s water pressure in order to perform control valve repairs or maintenance. The 1” full flow bypass valve incorporates four positions, including a diagnostic position that allows a service technician to have pressure to test a system while providing untreated bypass water to the building. Be sure to install bypass valve onto main control valve, before beginning plumbing. Or, make provisions in the plumbing system for a bypass. The bypass body and rotors are glass-filled Noryl ® and the nuts and caps are glass-filled polypropylene. All seals are self-lubricating

EPDM to help prevent valve seizing after long periods of non-use. Internal “O” Rings can easily be replaced if service is required.

The bypass consists of two interchangeable plug valves that are operated independently by red arrow shaped handles. The handles identify the direction of flow. The plug valves enable the bypass valve to operate in four positions.

1. NORMAL OPERATION POSITION: The inlet and outlet handles point in the direction of flow indicated by the engraved arrows on the control valve. Water flows through the control valve for normal operation of a water softener. During the regeneration cycle this position provides regeneration water to the unit, while also providing untreated water to the distribution system (Fig. 1).

2. BYPASS POSITION: The inlet and outlet handles point to the center of the bypass. The system is isolated from the water pressure in the plumbing system. Untreated water is supplied to the building (Fig. 2).

3. DIAGNOSTIC POSITION: The inlet handle points toward the control valve and the outlet handle points to the center of bypass valve. Untreated supply water is allowed to flow to the system and to the building, while not allowing water to exit from the system to the building (Fig. 3). This allows the service technician to draw brine and perform other tests without the test water going to the building.

NOTE: The system must be rinsed before returning the bypass valve to the normal position.

4. SHUT OFF POSITION: The inlet handle points to the center of the bypass valve and the outlet handle points away from the control valve. The water is shut off to the building. The water treatment system will depressurize upon opening a tap in the building. A negative pressure in the building combined with the softener being in regeneration could cause a siphoning of brine into the building. If water is available on the outlet side of the softener, it is an indication of water bypassing the system (Fig. 4) (i.e. a plumbing cross-connection somewhere in the building).

NORMAL

OPERATION

POSITION

BYPASS POSITION

DIAGNOSTIC

POSITION

SHUT OFF

POSITION

FIGURE 1 FIGURE 2 FIGURE 3 FIGURE 4

4

INSTALLATION:

GENERAL INSTALLATION & SERVICE WARNINGS

The control valve, fittings and/or bypass are designed to accommodate minor plumbing misalignments. There is a small amount of “give” to properly connect the piping, but the water softener is not designed to support the weight of the plumbing.

Do not use Vaseline, oils, other hydrocarbon lubricants or spray silicone anywhere. A silicone lubricant may be used on black

“O” Rings, but is not necessary. Avoid any type of lubricants, including silicone, on red or clear lip seals.

Do not use pipe dope or other sealants on threads. Teflon ® tape must be used on the threads of the 1” NPT inlet and outlet, the brine line connection at the control valve, and on the threads for the drain line connection. Teflon ® tape is not used on the nut connections or caps because “O” Ring seals are used. The nuts and caps are designed to be unscrewed or tightened by hand or with the special plastic Service Wrench, #CV3193-02. If necessary pliers can be used to unscrew the nut or cap. Do not use a pipe wrench to tighten nuts or caps. Do not place screwdriver in slots on caps and/or tap with a hammer.

SITE REQUIREMENTS

• water pressure – 25-100 psi

• water temperature – 33-100°F (0.5-37.7°C)

• electrical – 115/120V, 60Hz uninterrupted outlet

• current draw is 0.5 amperes

• the plug-in transformer is for dry locations only

• the tank should be on a firm level surface

WELL WATER INSTALLATION MUNICIPAL INSTALLATION

1. The distance between the drain and the water conditioner should be as short as possible.

2. Do not install any water conditioner with less than 10 feet of piping between its outlet and the inlet of a water heater.

CAUTION: To protect the unit in the event of a hot water heater backup, the manufacturer recommends the use of an expansion tank on the outlet side of the unit.

3. Do not locate unit where it or its connections (including the drain and overflow lines) will ever be subjected to room temperatures under 33°F.

4. Do not subject the tank to any vacuum, as this may cause an “implosion” and could result in leaking. If there is a possibility a vacuum could occur, please make provision for a vacuum breaker in the installation.

5. INLET/OUTLET PLUMBING: Be sure to install Bypass Valve onto main control valve before beginning plumbing.

Make provisions to bypass outside hydrant and cold hard water lines at this time. Install an inlet shutoff valve and plumb to the unit’s bypass valve inlet located at the right rear as you face the unit. There are a variety of installation fittings available. They are listed under Installation Fitting Assemblies, page 26-27. When assembling the installation fitting package (inlet and outlet), connect the fitting to the plumbing system first and then attach the nut, split ring and “O” Ring.

Heat from soldering or solvent cements may damage the nut, split ring or “O” Ring. Solder joints should be cool and solvent cements should be set before installing the nut, split ring and “O” Ring. Avoid getting solder flux, primer, and solvent cement on any part of the “O” Rings, split rings, bypass valve or control valve. If the building’s electrical system is grounded to the plumbing, install a copper grounding strap from the inlet to the outlet pipe. Plumbing must be done in accordance with all applicable local codes.

5

When installing an air regenerating filter the customer may experience, under certain conditions, small amounts of air (cloudy water) at the taps. This is normal. On rare occasions, this may result in “shots of air” at a particular fixture. By installing a loop or “U” on the outlet side of the unit, this will act as an air trap and improve this situation.

(Air charge models only)

Located inside the inlet is an internal check valve (see diagram at right).

This check valve holds the air in the system, preventing its escape from the tank. Plumbing codes may require the installation of a thermal expansion tank on the outlet side of the system to prevent a water heater backup condition.

(See Installation Diagrams on page 5.)

Provisions should be made to bypass outside hydrants that are not to have filtered water. It is also advisable to install hose bibs on the inlet and outside of the filter for future testing and service of the equipment. Where heavy sediment from the well is observed, it is advisable to install a cartridge or bag-style filter immediately upstream from the filter. A nominal micron rating of 50 to 100 is recommended. The purpose of this is to protect the control valve of any debris from the well.

If desired, a cartridge filter may be used after the system as a polishing filter.

6. INSTALLING GROUND: To maintain an electrical ground in metal plumbing of a home’s cold water piping (such as a copper plumbing system), install a ground clamp or jumper wiring. If replacing an existing filter, also replace the ground clamps/wire. If removing a filter, replace the piping with the same type of piping as the original to assure plumbing integrity and grounding.

7. DRAIN LINE: First, be sure that the drain can handle the backwash rate of the system. Solder joints near the valve must be done prior to connecting the drain line flow control fitting. Leave at least 6” between the drain line flow control fitting and solder joints. Failure to do this could cause interior damage to the flow control.

Backwash of an automatic filter can be directed into a septic tank in most cases, but because of the higher volume of water discharged, care should be taken. The backwash discharge can be directed to a subsurface drainage system or other safe location. Remember to follow all local codes.

When installing the drain line on any backwashing filter, especially Evolve filters that utilize air as the regenerant, hard piping such as PVC, Schedule 80 Plastic or copper is recommended. Remove the drain line nut (if included) and discard.

A 3/4” NPT connection on the elbow is provided. During backwash, high volumes of water (more than a softener) and air can be expelled. This release of air can cause a thrashing or movement of the drain line causing it to dislodge from the drain, resulting in water damage. In order to prevent this, it is recommended to use other means of securing the drain line

to the floor, wall or ceiling to avoid this thrashing of piping. Our patent pending Backwash Air cycle greatly reduces the chance of this occurring but should not be the only means of protection.

Where the drain line is elevated but empties into a drain below the level of the control valve, form a 7” loop at the discharge end of the line so that the bottom of the loop is level with the drain connection on the control valve. This will provide an adequate anti-siphon trap. Piping the drain line overhead <10 ft is normally not a problem. Be sure adequate pressure is available (40-60 psi is recommended). Where the drain empties into an overhead sewer line, a sink-type trap must be used. Run drain to its discharge point in accordance with plumbing codes. Pay special attention to codes for air gaps and anti-siphon devices.

CAUTION: Never insert a drain line into a drain, sewer line, or trap. Always allow an air gap between the drain line and the wastewater to prevent the possibility of sewage being back-siphoned into the conditioner.

TYPICAL DRAIN LINE INSTALLATIONS

6

8. CHECK VALVE: All air systems include an internal check valve and screen assembly as part of the air draw system (see diagram at

right). This check valve, screen, and elbow are exclusive to the air system and are not to be confused or interchanged with a brine elbow used on a softener. The gray color of the elbow indicates use with an air system vs. a black elbow which indicates use with a water softeners.

NOTE: Under certain conditions (finished basements, utility room, etc.)it may be advisable to disconnect the screen and run a 3 /

8

” line close to a drain, in case of check valve failure and water leakage.

Screen

Air fl ow

Air Check

Elbow

AIR DRAW

CHECK VALVE

ASSEMBLY

9. DISINFECTION OF SYSTEM: In situations where additional disinfection is needed, due to high levels of iron or sulfur bacteria, this may be accomplished with a small chlorine feeder (see diagram at right). It can be used in conjunction with air systems and is used to control bacterial growth within the filter vessel itself. It is not used to control bacteria downstream of the filter nor for disinfection of the water itself. Chlorine disinfection is not used with some medias such as Birm. Please consult distributor or factory for more details.

This tank operates much the same way a brine tank does with a water softener.

A small amount of water is added to the tank just prior to regeneration, which comes into contact with the chlorine pellets, dissolves them and is then drawn into the filter to disinfect the system periodically and then safely rinsed away. We recommend the use of pellets manufactured by Better Water Industries, available through the manufacturer or your local distributor.

To Dealer:

CAUTION: On certain Evolve air models, the Backwash Air cycle is not available when using the chlorine

CHLORINE FEEDER TANK

feeder tank. Drain line must be of rigid materials and affixed securely to floor, wall or ceiling. See Drain Line instructions.

This tank has many intended uses. If chlorine is being used, add only two or three pellets (two or three grams) of chlorine at a time. We recommend Better

Water Industries chlorine pellets. Do not overfill container. Use rubber gloves when handling pellets. Always read safety precautions of chemical container before adding to tank.

If chlorine is being used, never add or mix any chemical in chlorine tank other than chlorine. Always read safety precautions on container before adding any chemical to this tank. Only use in well ventilated area. Chlorine fumes can be corrosive and harmful. Inhalation of chlorine gas can be deadly. Use drip pan underneath tank in case of corrosion or leaking of tank. Always install an overflow line to the chlorine tank and run to an appropriate drain. Do not connect drain from filter to this tank. Drains should remain separate.

7

PROGRAMMING PROCEDURES:

1. Set time of day:

Time of day should only need to be set after extended power outages or when daylight saving time begins or ends. If an extended power outage occurs, the time of day will flash on and off indicating that the time should be reset.

STEP

SET CLOCK

.

Press

NEXT

to go to step 3.

STEP 3CURRENT TIME (MINUTES): Set the minutes using + or buttons. If it is desired to back up to the previous step press

REGEN

button once. Press

NEXT

to go to step 4.

STEP

NEXT

will exit

SET CLOCK

and return to the general operating display (page 9).

1 2 TIME

SET

HOUR

2:00

AM

3 TIME

SET

MINUTES

2:10

AM

4 CURRENT DAY

SET

MON

2. Programming:

NOTE: The manufacturer has preset the unit so that the gallons between regenerations will be automatically calculated after the hardness is entered.

STEP 1 – Press

NEXT

and + simultaneously for 3 seconds.

1

STEP 2HARDNESS: Will not show because the manufacturer programmed the system to regenerate every 1,000 gallons or every 3 days as the default.

NOTE: This display will show “–nA– (not available)” if “FILTER” is selected.

Press

NEXT

to go to step 3.

Press

REGEN

if you want to exit.

2

STEP 3DAYS BETWEEN REGENERATION (DAY OVERRIDE): The manufacturer has factory set 6 DAYS as the default. This is the maximum number of days between regenerations. If this is set to “OFF”, regeneration initiation is based solely on gallons used. If any number is set (allowable range from 1 to 28), a regeneration initiation will be called for on that day even if a sufficient number of gallons were not used to call for a regeneration.

Set Day Override using + or buttons (6 is recommended):

• set number of days between regeneration (1 to 28); or

3

WATER HARDNESS

SET

-nA-

GR

DAYS BETWEEN REGEN

SET

6

8

NOTE: This valve has the capability of regenerating up to six times in one day.

This can be observed by pressing the

CLOCK

and + buttons simultaneously, then using + or buttons to toggle the correct number of regenerations per day as desired (see example to right). Press

NEXT

to set the times per day or select

“OFF” to return to Days Between Regen. These settings are typically used in commercial settings.

Press

NEXT

to go to step 4. Press

REGEN

to return to the previous step.

STEP 4REGENERATION HOUR: The manufacturer has factory set 2:00 A.M. as the default. This is the hour of day for regeneration and can be reset by using

+ or buttons. “AM/PM” toggles after 12. The default time is 2:00 a.m.

(recommended for a normal household).

Press

NEXT

to go to step 5. Press

REGEN

to return to the previous step.

STEP 5 REGENERATION MINUTES: Set the minutes using + or buttons. Press

NEXT

to go to step 6. Press

REGEN

to return to previous step. To initiate an immediate manual regeneration, press and hold the

REGEN

button for three seconds. The system will begin to regenerate immediately. The control may be manually stepped through the regeneration cycles by pressing

REGEN

.

Press

NEXT

to go to step 6. Press

REGEN

to return to the previous step.

REGENS PER DAY

SET

4 PER

Example: Indicates unit set to regen 4 times in one day.

4 REGEN TIME HOUR

SET

2:00

AM

5 REGEN TIME MINUTES

SET

2:00

AM as the default. This feature is used to signal service into the future. This is typically set by the installing dealer to warn homeowner that service is required after a preset number of gallons have been consumed. If the feature is active, a specific gallon amount will appear.

Press

NEXT

three times to advance past this screen.

6 SERVICE ALARM

SET

OFF

GAL default. This feature is used to signal service into the future. This is typically set by the installing dealer to warn homeowner that service is required after a period of time has passed. If the feature is active, a specific number of days will appear.

Press

NEXT

three times to advance past this screen.

7 SERVICE ALARM

SET

OFF

YR

STEP 8 ALARM BUZZER: The manufacturer has factory set “ON” as the default. An alarm will sound (at the indicated time) after a regeneration, if there is no salt or if another error has occurred. Turn the alarm “OFF” or “ON” using the + or

buttons. Press

NEXT

.

NOTE: This feature allows you to program the time in which the alarm buzzer will sound, permitting the installer to pick a time when the owner will be home or awake to hear it.

Setting Alarm Buzzer Start Time: Press + or button to select the correct hour the buzzer is to start sounding. Be sure to also set AM or PM as necessary.

(Default is set to 6:00 a.m.) Press

NEXT

.

Setting Alarm Buzzer End Time: Press + or button to select the correct hour the buzzer is to stop sounding in the day. Be sure to also set

AM or PM as necessary. (Default is set to 10:00 p.m.) Press

NEXT

.

8 ALARM BUZZER START

SET

6:00

AM

ALARM BUZZER END

SET

10:00

PM

STEP 9 DISPLAY BACKLIGHT: The manufacturer has factory set “ON” as the default. Turn the light “OFF” or “ON” using the + or buttons. “OFF” will turn display backlight off after five minutes of keypad inactivity.

Press

NEXT

to exit installer programming.

9 LIGHT NORMALLY

SET

ON

9

START-UP INSTRUCTIONS:

FLUSHING OF SYSTEM:

To flush the system of any debris and air after installation is complete, please perform the following steps:

1. Rotate bypass handles to the bypass mode (see Fig. 2 of page 4).

2. Turn on inlet water and check for leaks in the newly installed plumbing.

3. Fully open a cold water faucet, preferable at a laundry sink or bathtub without an aerator.

4.

System regeneration sequence is in the following order. Some sequence differences may be noticed depending upon local conditions. (If it is desired to change this sequence, please refer to the Dealer Manual or contact the manufacturer.)

Sequencing for Various Filters:

Air Filters

1. Backwash Air

2. Backwash

3. Regenerant Draw Down (Air draw)

4. Return to service

Backwashing Filters

1. Backwash 4. Rinse

2. Rinse 5. Return to service

3. Backwash

Acid Neutralizers

1. Backwash 5. Filtering

2. Filtering 6. Rapid Rinse

3. Rapid Rinse 7. Return to service

4. Backwash

Inch Worm Feature: Evolve air units are programmed with the backwash air cycle feature (nicknamed “inch worm”). This unique feature allows for small movements or “inching” of the piston towards the backwash cycle. As the piston approaches this cycle, the backwash port opens slightly with each advancement, allowing air to escape to drain.

This cycle is ten very small mini steps of the piston which take place thirty seconds apart. Usually midway between the ten positions, the air begins to be released very slowly to the drain in normal operating conditions.

When first starting up an air sulfur or air iron, it is advised to step through these positions and go to the normal backwash cycle in order to fill the unit.

To advance in Backwash Air cycle:

1. Pushing the

NEXT

button will advance to each of the ten mini steps within the backwash air cycle. While there are usually eight steps to this cycle, the valve may make two or three movements for each step. Wait for these movements to complete before pressing

NEXT

again.

2. Pushing and holding the

REGEN

button for three seconds while in the Backwash Air cycle will skip the remaining mini steps and proceed to the next cycle of regeneration which is usually Backwash.

The system is now ready for filling with water and for testing.

1. Place the bypass valve into the bypass mode (Fig. 2 on page 4).

2. Press and hold the

REGEN

button until the motor starts. Release button. Put the valve into “BACKWASH” position. (Please

see note above.) Unplug the transformer so that the valve will not cycle to the next position. Open the inlet handle of the bypass valve very slightly allowing water to fill the tank slowly in order to expel air.

CAUTION: If water flows too rapidly, there will be a loss of media to the drain. Certain medias such as carbon, or other dry media, should not be backwashed immediately for extended periods of time. These medias need to “soak” in the water for a 24-hour period prior to full backwash conditions.

Media is dry and filling with water too quickly in backwash will result in media plugging the drain and valve assembly.

3. When the water is flowing steadily to the drain without the presence of air, slowly open the inlet valve. Restore power and momentarily press the

REGEN

button to advance the control to the “REGENERANT DRAW DOWN” position.

4. With the bypass still in the diagnostic mode (Fig. 3 on page 4), there should be a slow flow to the drain.

5. Press

REGEN

button in sequence until display returns to “TIME.” Place bypass valve in the normal operating mode

(Fig. 1 on page 4) by opening the outlet bypass handle.

6. Go to laundry tub or bathtub faucet, preferable a faucet without an aerator, and turn on cold water. Let the water run.

Note the color of water coming from faucet. If discolored, let water run until clear. If severely discolored, place unit into

“BACKWASH” position (step 2) and run water to the system’s drain until clear.

Note: At no time should there by large particles of media noticed at faucet or laundry tub. If this is seen, immediately shut off water and bypass system, as this could be an indication of a distributor failure. Contact manufacturer or distributor for assistance.

7. Place unit into regeneration again and allow to complete cycle. Upon completion, unit will be regenerated and will deliver treated water.

10

OPERATING DISPLAYS AND INSTRUCTIONS:

The air sulfur and air iron filter systems look and function much like any backwashing whole house filter; however, unlike these conventional filters, they use air as a regenerant. This atmospheric air (containing oxygen) helps convert iron or hydrogen sulfide into particles. These filters capture the particles of iron or hydrogen sulfide gas within the filter media. Your dealer has recommended the proper media depending on your local water conditions. In some cases where an acidic water condition (low pH) is present, the media may need to be periodically replenished if using this filter to raise the pH to an acceptable level. Consult dealer for this service. The system is prefactory set to regenerate every (3) three days at midnight. The frequency and start time of backwash/regeneration is adjustable to meet local operating conditions and contaminant levels. Total backwash and recharge time is normally one half hour.

1. GENERAL OPERATION: When the system is operating, one of five displays may be shown and will alternate with the installing dealer’s name and phone number for future service. Pressing

NEXT

will alternate between the displays. period of time

4. CAPACITY REMAINING which is the gallons that will be treated before the system signals a regeneration cycle the days override value only appear if set by dealer)

The user can scroll between the displays as desired.

1 TIME OF DAY

GPM

8 2:40

MON

PM

2 FLOW RATE

8.0

GPM

3 ON VACATION

NO

4 CAPACITY REMAINING

GPM

8 1600

GAL

5 DAYS TO A REGEN

GPM

8 3

6 PHONE NUMBER

DEALER NA

If the system has called for a regeneration that will occur at the preset time of regeneration, the words “REGEN

TODAY” will appear on the display.

If a water meter is installed, “GPM” flashes on the display when water is being treated, indicating gallons per minute going through the system.

2. VACATION MODE: This feature may be used to “shut down” the system while on vacation. The manufacturer has factory set “OFF” as the default. Turn feature “OFF” or “ON” using the + or buttons. When turned “ON”, the unit will not regenerate while there is no water usage. Once water usage is observed (minimum of 50 gallons), the unit will automatically regenerate that night and resume normal operation.

CAUTION: Depending on the severity of water conditions and the length of no water usage, it may not be recommended to use this feature. Please contact dealer or manufacturer for more information.

3. REGENERATION MODE: Typically a system is set to regenerate at a time of no water usage. If there is a demand for water when the system is regenerating, untreated water will be delivered. When the system begins to regenerate, the display will include information about the step of the regeneration process and the time remaining for that step to be completed. The system runs through the steps automatically and will reset itself to provide treated water when the regeneration has been completed.

REGENERATION MODE

BACKWASH

8:22

11

4. MANUAL REGENERATION: Sometimes there is a need to regenerate before the control valve calls for it. This may be needed if a period of heavy water use is anticipated.

press and release

REGEN

. The words “REGEN TODAY” will flash on the display to indicate that the system will regenerate at the next regeneration time (set in Programming, steps 4 and 5). If you pressed the

REGEN

button in error, pressing the button again will cancel the command.

REGEN button for three seconds. The system will begin to regenerate immediately.

This command cannot be cancelled.

Once a manual regeneration is initiated, the unit will enter the first regeneration cycle. Once the unit advances to its first position and subsequent positions thereafter (see Start Up Instructions for regeneration sequence), the water filter will deliver water, but it will be untreated.

5. POWER LOSS AND BATTERY REPLACEMENT: The transformer comes with a 15 foot power cord and is designed for use with the control valve; the transformer should only be used in a dry location.

In the event of a power outage, the control valve will remember all settings and time of day. If an extended power outage occurs, the control valve will keep time of day until the battery is depleted. When the battery becomes depleted, the only item that needs to be reset is the time of day and will be indicated by the time of day flashing or by a blank screen. All other settings are permanently stored in the nonvolatile memory.

If a power loss occurs and the time of day flashes or a blank screen occurs, this indicates that the battery is depleted. The time of day should be reset and the nonrechargeable battery should be replaced. The battery is a 3 Volt Lithium Coin Cell type 2032 and is readily available at most stores. To access battery location, remove front cover (see diagram on page 18 for battery location).

6. AUDIBLE ALARM: This control valve is equipped with an audible alarm and visual alarm. This alarm is set by the installing dealer and is used to warn of pending service, based on gallons or time.

To turn off alarm: If the audible alarm sounds, press any button on the face of the control valve to turn off and call the dealer for service.

To reset: Both the gallon alarm setting and time alarm setting are reset together by pushing and holding the + and – simultaneously for three seconds.

7. ERROR MESSAGE: If the word “ERROR” appears and flashes alternately with the dealer name and phone number, record the ERROR number and your contact servicing dealer promptly. This indicates that the control valve was not able to function properly.

MANUAL REGENERATION

REGEN TODAY and TIME OF DAY will flash alternately if a regeneration is expected tonight.

REGEN TODAY

GPM

8 2:40

MON

PM

BATTERY REPLACEMENT

ERROR

8. CHLORINE TANK AND MAINTENANCE: In severe cases where iron or sulfate bacteria conditions exist, the dealer may have installed a chlorine tank with your system (see diagram, page 7).

These bacteria are harmless to human health, however they can produce a slime and occasionally an odor that can be a nuisance. Filters equipped with a chlorine tank will periodically draw a chlorinated water solution into the filter tank killing these unwanted bacteria within the filter itself. The chlorine is rinsed from the system during the regeneration process. More specifically, a small amount of water will be added to the tank just prior to regeneration; this comes in contact with the chlorine pellets, dissolves them, and is drawn into the filter to disinfect the system periodically.

We recommend the use of pellets manufactured by Better Water Industries, available through your dealer. Periodically check storage tank and add two or three chlorine tablets (two or three grams) at a time.

CAUTION: This tank has many intended uses. If chlorine is being used, only add two or three pellets (two or three grams) of chlorine at a time. We recommend Better Water

Industries chlorine pellets. Do not overfill container. Use rubber gloves when handling pellets. Always read safety precautions of chemical container before adding to tank. Keep out of reach of children!

If chlorine is being used, never add or mix any chemical in chlorine tank other than chlorine. Only use in well ventilated area. Chlorine gas can be corrosive and harmful.

Inhalation of chlorine gas can be deadly. Use drip pan underneath tank in case of corrosion or leaking of tank.

12

REPLACEMENT MINERAL INSTRUCTIONS

FOR ACID NEUTRALIZERS:

The EACG Iron Filter/Acid Neutralizer will remove iron and also raise the pH of mildly acidic water. The EVAN

Upflow Acid Neutralizer will raise the pH of acidic water. The raising of pH utilizes a sacrificial mineral that will need replenishment every 6 to 12 months. Typically the media should not be below the halfway point in the tank. In order to check the mineral height and before adding mineral to the system, please follow these instructions.

1. Check the media height by shining a flashlight through the tank to see the height of the mineral. If the level is not seen, the top fill plug will have to be removed (if available) to measure the height. Proceed to step 2.

2. To remove top fill plug, turn off the source of the water and open a conditioned water tap to relieve the water pressure on the system. Place unit into the bypass mode. Unscrew the top fill plug.

CAUTION: Never unscrew top fill plug unless pressure is fully released from system.

Serious injury and/or flooding can occur.

3. Siphon out some water from the tank through the dome hole. This will allow room when adding the media.

4. Add the appropriate amount of calcite (replacement media) through the dome hole. If needed, siphon out more water as the media will displace the water inside the tank. Pay close attention to media level when filling. Do not

overfill. The additional media added should not be higher than two-thirds of the tank height when measuring from the bottom (see diagram). Once the right height has been achieved, replace top fill plug. Grease “O” ring if necessary using only silicone grease. Do not use petroleum based grease such as Vaseline. Tighten appropriately.

5. Leaving controller in the bypass position, turn on water source and refer to the start-up instructions of the controller and complete the procedure.

6. Once start up is complete, please check the top fill plug for any leaking.

13

TROUBLESHOOTING GUIDE:

PROBLEM CAUSE

A. No power at electric outlet

B. Control valve power adapter not plugged into outlet or power cord end not connected to PC board connection

CORRECTION

A. Repair outlet or use working outlet

B. Plug power adapter into outlet or connect power cord end to PC board connection

1. No display on

PC board

C. Improper power supply

D. Defective power adapter

E. Defective PC board

F. Dead battery

A. Power adapter plugged into electric outlet controlled by light switch

B. Tripped breaker switch and/or tripped GFI

C. Verify proper voltage is being delivered to

PC board

D. Replace power adapter

E. Replace PC board

F. Replace battery

A. Use uninterrupted outlet

2. PC board does not display correct time of day

C. Power outage

D. Defective PC board

A. Bypass valve in bypass position

3. Display does not indicate that water is flowing. Refer to user instructions for how the display indicates water is flowing.

B. Meter is not connected to meter connection on

PC board

C. Restricted/stalled meter turbine

D. Meter wire not installed securely into three pin connector

E. Defective meter

F. Defective PC board

4. Control valve regenerates at wrong time of day

5. Time of day flashes on and off

A. Power outage

B. Time of day not set correctly

C. Time of regeneration set incorrectly

D. Control valve set at “on 0” (immediate regeneration)

E. Control valve set at “NORMAL + on 0”

(delayed and/or immediate)

A. Power outage

B. Reset breaker switch and/or GFI switch

C. Reset time of day. If PC board has battery back up present the battery may be depleted.

See front cover and drive assembly drawing for instructions.

D. Replace PC board

A. Turn bypass handles to place bypass in service position

B. Connect meter to three pin connection labeled

METER on PC board

C. Remove meter and check for rotation or foreign material

D. Verify meter cable wires are installed securely into three pin connector labeled METER

E. Replace meter

F. Replace PC board

A. Reset time of day. If PC board has battery back up present the battery may be depleted.

See front cover and drive assembly drawing for instructions.

B. Reset to correct time of day

C. Reset regeneration time

D. Check programming setting and reset to

NORMAL (for a delayed regen time)

E. Check programming setting and reset to

NORMAL (for a delayed regen time)

A. Reset time of day. If PC board has battery back up present the battery may be depleted.

See front cover and drive assembly drawing for instructions.

6. Control valve does not regenerate automatically when the correct button(s)

A. Broken drive gear or drive cap assembly is depressed and held.

For timeclock valves the buttons are ▲ & .

For all other valves the button is REGEN.

B. Broken piston rod

C. Defective PC board

A. Replace drive gear or drive cap assembly

B. Replace piston rod

C. Defective PC board

14

PROBLEM CAUSE

A. Bypass valve in bypass position

7. Control valve does not regenerate automatically

B. Meter is not connected to meter connection on

PC board but does when the correct button(s) is depressed and held.

C. Restricted/stalled meter turbine

D. Incorrect programming For timeclock valves the buttons are ▲ & .

For all other valves the

E. Meter wire not installed securely into three pin connector button is REGEN.

F. Defective meter

G. Defective PC board

A. Bypass valve is open or faulty

B. Media is exhausted due to high water usage

C. Meter not registering

D. Water quality fluctuation

CORRECTION

A. Turn bypass handles to place bypass in service position

B. Connect meter to three pin connection labeled

METER on PC board

C. Remove meter and check for rotation or foreign material

D. Check for programming error

E. Verify meter cable wires are installed securely into three pin connector labeled METER

F. Replace meter

G. Replace PC board

A. Fully close bypass valve or replace

B. Check program settings or diagnostics for abnormal water usage

C. Remove meter and check for rotation or foreign material

D. Test water and adjust program values accordingly

8. Hard or untreated water is being delivered

E. No regenerant or low level of regenerant in regenerant tank

F. Control fails to draw in regenerant

E. Add proper regenerant to tank

G. Insufficient regenerant level in regenerant tank

H. Damaged seal/stack assembly

I. Control valve body type and piston type mix matched

J. Fouled media bed

A. Improper refill setting

9. Control valve uses too much regenerant

B. Improper program settings

A. Low water pressure

10. Residual regenerant being delivered to service

B. Incorrect injector size

C. Restricted drain line

11. Excessive water in regenerant tank

C. Control valve regenerates frequently

A. Improper program settings

B. Plugged injector

C. Drive cap assembly not tightened in properly

D. Damaged seal/stack assembly

E. Restricted or kinked drain line

F. Plugged backwash flow controller

G. Missing refill flow controller

F. Refer to Troubleshooting Guide number 12

G. Check refill setting in programming. Check refill flow control for restrictions or debris and clean or replace

H. Replace seal/stack assembly

I. Verify proper control valve body type and piston type match

J. Replace media bed

A. Check refill setting

B. Check program setting to make sure they are specific to the water quality and application needs

C. Check for leaking fixtures that may be exhausting capacity or system is undersized

A. Check incoming water pressure – water pressure must remain at minimum of 25 psi

B. Replace injector with correct size for the application

C. Check drain line for restrictions or debris and clean

A. Check refill setting

B. Remove injector and clean or replace

C. Retighten the drive cap assembly

D. Replace seal/stack

E. Check drain line for restrictions or debris and or unkink drain line

F. Remove backwash flow controller and clean or replace

G. Replace refill flow controller

15

TROUBLESHOOTING GUIDE cont’d:

PROBLEM

12. Control valve fails to draw in regenerant

13. Water running to drain

14. E1, Err – 1001,

Err – 101 =

Control unable to sense motor movement

CAUSE

A. Injector is plugged

B. Faulty regenerant piston

C. Regenerant line connection leak

D. Drain line restriction or debris cause excess back pressure

E. Drain line too long or too high

F. Low water pressure

CORRECTION

A. Remove injector and clean or replace

B. Replace regenerant piston

C. Inspect regenerant line for air leak

D. Inspect drain line and clean to correct restriction

E. Shorten length and or height

F. Check incoming water pressure – water pressure must remain at minimum of 25 psi

A. Power outage during regeneration

B. Damaged seal/stack assembly

C. Piston assembly failure

D. Drive cap assembly not tightened in properly

A. Upon power being restored control will finish the remaining regeneration time. Reset time of day. If PC board has battery back up present the battery may be depleted. See front cover and drive assembly drawing for instructions.

B. Replace seal/stack assembly

C. Replace piston assembly

D. Retighten the drive cap assembly

A. Motor not inserted fully to engage pinion, motor wires broken or disconnected

A. Disconnect power, make sure motor is fully engaged, check for broken wires, make sure two pin connector on motor is connected to the two pin connection on the PC board labeled

MOTOR. Press NEXT and REGEN buttons for

3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

B. PC board not properly snapped into drive bracket

B. Properly snap PC board into drive bracket and then Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

C. Missing reduction gears C. Replace missing gears

D. Board unable to read middle reduction gear

E. Defective Optical Encoder

D. Check foil on reduction gear; make sure no film is covering foil on reduction gear

E. Replace PC board

A. Foreign material is lodged in control valve

A. Open up control valve and pull out piston assembly and seal/stack assembly for inspection. Press NEXT and REGEN buttons for

3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

15. E2, Err – 1002, Err –

102 = Control valve motor ran too short and was unable to find the next cycle position and stalled

B. Mechanical binding

B. Check piston and seal/stack assembly, check reduction gears, check drive bracket and main drive gear interface. Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

C. Main drive gear too tight

C. Loosen main drive gear. Press NEXT and

REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

16

PROBLEM CAUSE CORRECTION

15. E2, Err – 1002, Err –

102 = Control valve motor ran too short and was unable to find the next cycle position and stalled

D. Improper voltage being delivered to PC board

E. Valve type is programmed incorrectly

D. Verify that proper voltage is being supplied.

Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for

5 seconds and then reconnect.

E. Verify valve body and program PC board to match

A. Motor failure during a regeneration

16. E3, Err – 1003, Err –

103 = Control valve motor ran too long and was unable to find the

B. Foreign matter built up on piston and stack assemblies creating friction and drag enough to time out motor next cycle position

A. Check motor connections then Press NEXT and

REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

B. Replace piston and stack assemblies. Press

NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

C. Drive bracket not snapped in properly and out enough that reduction gears and drive gear do not interface

C. Snap drive bracket in properly then Press

NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

17. E4, Err – 1004, Err –

104 = Control valve motor ran too long and timed out trying to reach home position

A. Drive bracket not snapped in properly and out enough that reduction gears and drive gear do not interface

18. Err -1006, Err – 106,

Err - 116 = MAV/

SEPS/ NHBP/ AUX

MAV valve motor ran too long and unable to find the proper park position

A. Control valve programmed for ALT A or B, nHbP, SEPS, or AUX MAV with out having a MAV or NHBP valve attached to operate that function

B. MAV/NHBP motor wire not connected to

PC board

Motorized Alternating

Valve = MAV

Separate Source = SEPS

No Hard Water Bypass

= NHBP

C. MAV/NHBP motor not fully engaged with reduction gears

Auxiliary MAV = AUX

MAV

D. Foreign matter built up on piston and stack assemblies creating friction and drag enough to time out motor

A. Snap drive bracket in properly then Press

NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

A. Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for

5 seconds and then reconnect. Then reprogram valve to proper setting

B. Connect MAV/NHBP motor to PC board two pin connection labeled DRIVE. Press NEXT and

REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

C. Properly insert motor into casing, do not force into casing Press NEXT and REGEN buttons for

3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

D. Replace piston and stack assemblies. Press

NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect.

17

TROUBLESHOOTING GUIDE cont’d:

PROBLEM CAUSE

19. Err – 1007, Err – 107,

Err - 117 = MAV/

SEPS/NHBP/AUX

MAV valve motor ran too short (stalled)

A. Foreign material is lodged in

MAV/NHBP valve while looking for proper park position

CORRECTION

A. Open up MAV/NHBP valve and check piston and seal/ stack assembly for foreign material.

Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for

5 seconds and then reconnect.

Motorized Alternating

Valve = MAV

Separate Source = SEPS

No Hard Water Bypass

= NHBP

B. Mechanical binding

B. Check piston and seal/stack assembly, check reduction gears, drive gear interface, and check

MAV/NHBP black drive pinion on motor for being jammed into motor body.

Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for

5 seconds and then reconnect.

Auxiliary MAV = AUX

MAV

20. Err – 109

21. Err – 201

22. Err – 204 = Leak detected

A. Invalid motor state detected

A. Invalid regeneration cycle step detected

A. Replace PC board

A. Replace PC board

A. Occurs when dP input is active for “ALARM” and the input is closed. The alarm buzzer will activate and the screen will display the error.

A. Check for low flow leak. Press NEXT and

REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC Board for 5 seconds and then reconnect to clear error.

23. Err – 402 = Power

Down Memory

24. Err – 403 = Program

Memory

A. Occurs when new software is flashed to a

PC board

25. Err – 404 =

Diagnostic Memory

A. Diagnostic memory failure during power down A. Replace PC board

A. Factory resets this error not seen in the field

A. Corrupt diagnostic display information is stored in the memory

A. Replace PC board

26. Err – 410 =

Configurator

Download

A. Occurs when downloading an invalid configuration file

A. Not seen in the field

18

1

REPLACEMENT PARTS:

1

2

3

4

5

6

7

Item No.

not shown

FRONT COVER AND DRIVE ASSEMBLY

Part No.

Description Qty.

CV3367-01-A Black cover

CV3367-01-WR-A Gray cover

CV3107-1

CV3106-1

Motor

Drive bracket & spring clip

CV3502WE Evolve PC board (used on chlorine generator models)

CV4022WU Evolve PC board (standard)

CV3110

CV3109

Drive gear, 12 x 36

Drive gear cover

CV3002CC

CV3526

Drive assembly, CC

Transformer, 110V-15V, DC (used on chlorine generator models) 1

-

CV3186 Transformer, 110V-12V, AC (standard)

CV3684-WR-GLD Optional weather cover

1

1

3

1

1

1

1

1

1

1

NOTE: Battery Location

4

5

6

7

2

3

19

REPLACEMENT PARTS:

1

13

14

5

4

7

3

8

10

2

Item No.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Part No.

PISTON ASSEMBLY

Description

CV3005

CV3430

CV3004

CV3135

CV3011

CV3011-01

CV3407

CV3174

CV3180

CV3105

1” spacer stack assembly

1.25” spacer stack assembly

Drive cap assembly

O-ring 228

1” piston assembly downflow

1” piston assembly upflow

1.25” piston assembly downflow

Regenerant piston

O-ring 337

O-ring 215

CV3358

CV3556

O-ring 219, 1.25” distributor

Screw, 1/4-20x1-1/2 18-8SS

CCI-00318337 Nut, 1/4-20 HEX 18-8SS

CV3016 QC2 clamp assembly (includes screw & nut)

CV3452

CV3015

CV3001-04

O-ring 230

WS1 QC2 tank adapter assembly (includes O-rings)

1” body assembly downflow

CV3001UP

CV3020

CV3368

1” body assembly upflow

1.25” body assembly downflow

Drive backplate

Qty.

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

20

12

11

6

7

NOTE: Not available on

1¼ " valve.

9

REPLACEMENT PARTS:

Item No.

6

7

8

9

10

1

2

3

4

5

BYPASS VALVE

Part No.

CV3151

CV3150

CV3105

CV3145

CV3146

CV3147

CV3148

CV3152

CV3155

CV3156

Description

Nut, 1” quick connect

Split ring

O-ring 215

Bypass rotor, 1”

Bypass cap

Bypass handle

Bypass rotor seal retainer

O-ring 135

O-ring 112

O-ring 214

Qty.

2

2

2

2

2

2

2

2

2

2

21

REPLACEMENT PARTS:

INJECTOR ASSEMBLIES

Item No.

Part No.

Description Qty.

1

2

3

4

5 not shown not shown

CV3176 Injector cap

CV3152 O-ring 135

CV3177-01 Injector screen

CV3010-1Z Injector assembly plug

CV3010-1A A injector assembly,

BLACK

CV3010-1B B injector assembly, BROWN

CV3010-1C C injector assembly, VIOLET

CV3010-1D D injector assembly,

RED

CV3010-1E E injector assembly,

WHITE

CV3010-1F F injector assembly,

BLUE

CV3010-1G G injector assembly, YELLOW

CV3010-1H H injector assembly, GREEN

CV3010-1I I injector assembly, ORANGE

CV3010-1J J injector assembly,

LIGHT BLUE

CV3010-1K K injector assembly,

LIGHT GREEN

CV3170

CV3171

O-ring 011, lower

O-ring 013, upper

1

1

1

1

1

*

*

* The injector plug and the injector each use one lower and one upper o-ring

1

CHECK VALVE ASSEMBLY

Item No.

1

Part No.

Description

CH4642-WR-A Air check valve assembly

Qty.

1

22

Item No.

4

3

2

6

5

1

BRINE ELBOW ASSEMBLY

Part No.

Description

CV3195-01 Refill port plug assembly

CH4615 Elbow locking clip

CS1197 Tube insert, 3/8”

CJCPG-6PBLK Nut, 3/8”

CH4613 Elbow cap, 3/8”

CV3163 O-ring 019

Qty.

1

1

1

1

1

1

REPLACEMENT PARTS:

Item No.

DRAIN LINE ASSEMBLY 3/4”

Part No.

Description Qty.

3

4

5

6

1

2

7

CH4615 Elbow locking clip

CPKP10TS8-BULK Optional insert, 5/8” tube

CV3192

CV3158-02

CV3163

CV3159-01

Optional nut, 3/4” drain elbow

Drain elbow, 3/4” NPT with O-ring

O-ring 019

DLFC retainer assembly

CV3162-007

CV3162-010

CV3162-013

CV3162-017

0.7 DLFC for 3/4” elbow

1.0 DLFC for 3/4” elbow

1.3 DLFC for 3/4” elbow

1.7 DLFC for 3/4” elbow

CV3162-022

CV3162-027

CV3162-032

CV3162-042

CV3162-053

CV3162-065

CV3162-075

CV3162-090

CV3162-100

2.2 DLFC for 3/4” elbow

2.7 DLFC for 3/4” elbow

3.2 DLFC for 3/4” elbow

4.2 DLFC for 3/4” elbow

5.3 DLFC for 3/4” elbow

6.5 DLFC for 3/4” elbow

7.5 DLFC for 3/4” elbow

9.0 DLFC for 3/4” elbow

10.0 DLFC for 3/4” elbow

1

8 CV3331 Drain elbow and retainer assembly

Items 2 and 3, nut and insert are only used with 1/2” I.D. by 5/8” O.D. polytubing. For other piping material, the

3/4” NPT is used.

1

1

1

1

1

1

3/4”

NPT

Proper DLFC orientation directs water flow towards the washer face with rounded edge and lettering. 

Water

Flow

23

REPLACEMENT PARTS:

Item No.

3

4

1

2

5

6

WATER METER & METER PLUG

Part No.

CV3151

CV3003

CV3118-01

CV3105

CV3003-01

CV3013

Description

Nut, 1” QC

Meter assembly, includes items 3 & 4

Turbine assembly

O-ring 215

Meter plug assembly

Optional mixing valve

Qty.

1

1

1

1

1

1

SERVICE WRENCH - CV3193-02

Although no tools are necessary to assemble or disassemble the valve, the Service Wrench,

(shown in various positions on the valve) is available to aid in assembly or disassembly.

24

REPLACEMENT PARTS:

Item No.

3

4

1

2

5

CHLORINE TANK ASSEMBLY

Part No.

Description

CH4600-50 474 safety float valve

CH4640-32 474 float assembly

CH4500-48 474 air check

CN1043 10” pad for feeder

CH7001 Grid for feeder

Qty.

1

1

1

1

1

1

2

3

4

5

25

INSTALLATION FITTING ASSEMBLIES:

Item

No.

1

2

3

4

1” PVC MALE NPT ELBOW

Part No.

Description

CV3007 1” PVC male NPT elbow assembly

CV3151 Nut, 1” quick connect

CV3150 Split ring

CV3105 O-ring 215

CV3149 Fitting

Qty.

2

2

2

2

2

3

4

1

2

Item

No.

3/4” & 1” PVC SOLVENT ELBOW

Part No.

Description Qty.

CV3007-01 3/4” & 1” PVC solvent elbow assembly 2

CV3151 Nut, 1” quick connect 2

CV3150 Split ring

CV3105 O-ring 215

CV3189 Fitting 2

2

2

3

4

1

2

Item

No.

1” BRASS SWEAT

Part No.

Description

CV3007-02 1” brass sweat assembly

CV3151 Nut, 1” quick connect

CV3150 Split ring

CV3105 O-ring 215

CV3188 Fitting

Qty.

2

2

2

2

2

3

4

1

2

Item

No.

3/4” BRASS SWEAT

Part No.

Description

CV3007-03 3/4” brass sweat assembly

CV3151 Nut, 1” quick connect

CV3150 Split ring

CV3105 O-ring 215

CV3188-01 Fitting

Qty.

2

2

2

2

2

3

4

1

2

Item

No.

1” PLASTIC MALE NPT

Part No.

Description

CV3007-04 1” plastic male NPT assembly

CV3151 Nut, 1” quick connect

CV3150 Split ring

CV3105 O-ring 215

CV3164 Fitting

Qty.

2

2

2

2

2

26

3

4

1

2

Item

No.

1-1/4” PLASTIC MALE

Part No.

Description

CV3007-05 1-1/4” plastic male assembly

CV3151 Nut, 1” quick connect

CV3150 Split ring

CV3105 O-ring 215

CV3317 Fitting

Qty.

2

2

2

2

2

1

2

3

4

Item

No.

1-1/4” & 1-1/2” BRASS SWEAT

Part No.

Description Qty.

CV3007-09 1-1/4 & 1-1/2” brass sweat assembly 2

CV3151 Nut, 1” quick connect 2

CV3150 Split ring

CV3105 O-ring 215

CV3375 Fitting

2

2

2

1

2

3

4

Item

No.

1-1/4” & 1-1/2” PVC SOLVENT

Part No.

Description Qty.

CV3007-07 1-1/4” & 1-1/2” PVC solvent assembly 2

CV3151 Nut, 1” quick connect 2

CV3150

CV3105

CV3352

Split ring

O-ring 215

Fitting

2

2

2

3

4

1

2

Item

No.

3/4” BRASS SHARK BITE

Part No.

Description

CV3007-12 3/4” brass Shark Bite assembly

CV3151 Nut, 1” quick connect

CV3150 Split ring

CV3105 O-ring 215

CV3628 Fitting

Qty.

2

2

2

2

2

3

4

1

2

Item

No.

1” BRASS SHARK BITE

Part No.

Description

CV3007-13 1” brass Shark Bite assembly

CV3151 Nut, 1” quick connect

CV3150

CV3105

CV3629

Split ring

O-ring 215

Fitting

Qty.

2

2

2

2

2

3

4

1

2

Item

No.

3/4” JOHN GUEST ELBOW

Part No.

Description

CV3007-15 3/4” John Guest elbow assembly

CV3151

CV3150

Nut, 1” quick connect

Split ring

CV3105

CV3790

O-ring 215

Fitting

Qty.

2

2

2

2

2

27

3

4

1

2

Item

No.

Part No.

1” JOHN GUEST

Description

CV3007-17 1” John Guest elbow assembly

CV3151

CV3150

Nut, 1” quick connect

Split ring

CV3105

CV4045

O-ring 215

Fitting

Qty.

2

2

2

2

2

SPECIFICATIONS:

SULFUR AND IRON AIR FILTERS

MODEL NUMBER EVS-1054 EVS-1248 EVS-1354 EVFE-1054 EVFE-1248 EVFE-1354

Mineral Type Catalytic Carbon Catalytic Carbon Catalytic Carbon Birm Birm Birm

Amount 1.0 1.5 2.0 1.0 1.5 2.0

Gravel Amount/Size (No. 1)

Gravel Amount/Size (No. 2)

14 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

14 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

(GPM) 5.0 6.0 7.0

1 Peak 18.0 19.0 19.0

2

(GPM) 5.3 9.0 10.0

Removal 1.0 1.0 1.0 5.0 5.0 5.0

3 Hydrogen 5.0 5.0 5.0 1.0 1.0 1.0

pH Range

Total Dimensions

Shipping Weight

Greater than 7.0

10”W x 62”H

Unit Filled 78 lb

Greater than 7.0

12”W x 56”H

Unit Filled 109 lb

Greater than 7.0

13”W x 62”H

Unit Filled 130 lb

Greater than 7.0

10”W x 52”H

Unit Filled 100 lb

Greater than 7.0

10”W x 62”H

Unit Filled 142 lb

Greater than 7.0

13”W x 62”H

Unit Filled 185 lb

NOTE: The EVS and EVFE are approved for use in the State of Wisconsin.

1 Not tested at peak fl ow rate. Water quality may vary.

2 Iron removal may vary for hydrogen sulfi de systems, depending on local conditions.

3 Hydrogen sulfi de removal may vary for iron systems, depending on local conditions.

AIR CAT FILTERS

MODEL NUMBER EAG-1054 EAG-1248 EAG-1354 EACG-1054AN EACG-1248AN EACG-1354AN

Mineral Type Greensand Plus Greensand Plus Greensand Plus Greensand Plus/Calcite Greensand Plus/Calcite Greensand Plus/Calcite

1 Amount 1.0 1.5 2.0 1.0 1.5 2.0

Gravel Amount/Size (No. 1)

Gravel Amount/Size (No. 2)

14 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

14 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

(Lbs) 13.0 19.0 22.0

2

(GPM) 3.0 3.0 5.0

Peak Flow (GPM) 6.0 8.0 10.0 6.0 8.0 10.0

3 Removal 4.0 4.0 4.0 4.0 4.0 4.0

4 Hydrogen 0.5 0.5 0.5 0.5 0.5 0.5

pH Range Greater than 7.0 Greater than 7.0 Greater than 7.0 Greater than 6.3 Greater than 6.3 Greater than 6.3

Total Dimensions

Shipping Weight

10”W x 62”H

Unit Filled 78 lb

12”W x 56”H

Unit Filled 109 lb

13”W x 62”H

Unit Filled 130 lb

10”W x 52”H

Unit Filled 100 lb

10”W x 62”H

Unit Filled 142 lb

13”W x 62”H

Unit Filled 185 lb

1 Amount of acid neutralizing media may vary depending on local conditions.

2 Not tested at peak fl ow rate. Water quality may vary.

3 Iron removal may vary, depending on local conditions.

4 Hydrogen sulfi de removal may vary, depending on local conditions.

CYCLE TIMES AND USAGE

Backwash Air

Regenerant Draw

MIN. GAL. MIN. GAL. MIN. GAL. MIN. GAL. MIN. GAL. MIN. GAL.

4 16 4 23 4 27 4 16 4 23 4 27

60 25 60 40 60 50 60 25 60 40 60 50

Height

Width

28

ACID NEUTRALIZERS

MODEL NUMBER EVBF-1044AN EVBF-1054AN EVBF-1354AN EVAN-1044 EVAN-1054 EVAN-1354

Mineral Type Calcite or Mix Calcite or Mix Calcite or Mix Calcite or Mix Calcite or Mix Calcite or Mix

Amount 1.0 1.5 2.5 1.0 1.5 2.5

Gravel Amount/Size (No. 1)

Gravel Amount/Size (No. 2)

14 lb 1/4 x 1/8

7 lb #20

14 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

14 lb 1/4 x 1/8

7 lb #20

14 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

Peak Flow (GPM)

(GPM) 5.0 5.0 6.0

11.0 11.0 16.0 8.0 9.0 12.0

(GPM) 5.0 5.0 7.0

Total Dimensions

Shipping Weight

10”W x 52”H

Unit Filled 118 lb

10”W x 62”H

Unit Filled 169 lb

13”W x 62”H

Unit Filled 255 lb

10”W x 50”H

Unit Filled 100 lb

10”W x 60”H

Unit Filled 151 lb

13”W x 60”H

Unit Filled 237 lb

BACKWASHING FILTERS

MODEL EVBF-1044 EVBF-1054 EVBF-1354 EVBF-1044 EVBF-1054 EVBF-1354

Amount 1.0 1.5 2.5 1.0 1.5 2.5

Gravel Amount/Size (No. 1)

Gravel Amount/Size (No. 2)

14 lb 1/4 x 1/8

7 lb #20

14 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

14 lb 1/4 x 1/8

7 lb #20

14 lb 1/4 x 1/8

7 lb #20

21 lb 1/4 x 1/8

7 lb #20

Peak Flow (GPM)

(GPM) 6.0 7.0 11.0

8.0 9.0 12.0 10.0 11.0 18.0

(GPM) 8.0 8.0 14.0

Total Dimensions

Shipping Weight

10”W x 52”H

Unit Filled 75 lb

10”W x 62”H

Unit Filled 90 lb

13”W x 62”H

Unit Filled 160 lb

10”W x 52”H

Unit Filled 85 lb

10”W x 62”H

Unit Filled 120 lb

13”W x 62”H

Unit Filled 190 lb

CYCLE TIMES AND USAGE

EVBF-1044 EVBF-1054 EVBF-1354 EVBF-1044 EVBF-1054 EVBF-1354

MIN. GAL. MIN. GAL. MIN. GAL. MIN. GAL. MIN. GAL. MIN. GAL.

26.5 26.5

26.5 5

Height Height

Height

Width

Acid Neutralizer

Width

Upflow Neutralizer

Width

Backwashing Filter

29

Evolve Series ® Water Conditioner Limited Warranty

Congratulations. You have purchased one of the fi nest water treatment systems available. In the unlikely event of a problem due to defects in material and workmanship, Water-Right ® proudly warrants our Evolve Series ® water conditioners to the original owner, at original installation location, when installed in accordance with Water-Right specifi cations from the date of original installation as follows:

For the LIFETIME of the original owner: Media tank, except for damages due to freezing, high pressure (120 PSI and above), extreme temperature

(100° F and above) or a vacuum on the system.

For a period of TEN YEARS:

For a period of FIVE YEARS:

For a period of ONE YEAR:

Brine tank.

Complete valve.

All other parts and components.

Any part found defective within the terms of this warranty will be repaired or replaced by the dealer at the manufacturer’s discretion. You pay only freight from our factory and local dealer charges. To obtain local warranty service, contact original dealer. If original dealer is unknown, contact Water-Right for authorized service dealer in your area. If no authorized dealer is located in your area, please ship defective part or component freight prepaid to:

1900 Prospect Ct.

Appleton, Wisconsin 54914

Water-Right, at its discretion, will repair or replace the part or component at its expense and return part freight collect.

The above provisions of the warranty are valid as long as the unit is connected in compliance with local plumbing codes and in an equivalent manner and condition of the original installation and is owned by the original owner.

This warranty does not cover expendable or misapplied medias, or damages due to accident, fi re, fl ood, freezing, or any other Act of God. Water-Right is not responsible for damages due to change in water conditions, misapplication, misuse, neglect, vacuum, oxidizing agents, alteration, or lack of maintenance. No responsibility is assumed for loss of use of the unit, inconvenience, loss or damage to real or personal property or any incidental or consequential damages. Furthermore, we assume no liability and extend no warranties, express or implied, for the use of this product with a non-potable water source. To the extent permitted by law, Water-Right disclaims all implied warranties, including without limitation warranties of merchantability and fi tness for particular purpose; to the extent required by law, any such implied warranties are limited in duration to the period specifi ed above for the specifi ed components.

Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specifi c legal rights, and you may also have other rights which vary from state to state.

30

QUICK REFERENCE GUIDE:

GENERAL OPERATION

When the system is operating, one of six displays will be shown:

1. time of day/gpm

2. flow rate

3. vacation mode

4. capacity remaining

5. days to a regen

6. dealer name and phone number

Pressing

NEXT

will toggle between the six choices.

TIME OF DAY

GPM

8 2:40

MON

PM

CAPACITY REMAINING

GPM

8 1600

GAL

FLOW RATE

8.0

GPM

ON VACATION

NO

DAYS TO A REGEN

GPM

8 3

PHONE NUMBER

DEALER NA

TO SET TIME OF DAY

In the event of a prolonged power outage, time of day flashes, indicating that this needs to be reset. All other information will be stored in memory no matter how long the power outage.

1. Accessed by pressing

SET CLOCK

2. Adjust hours with + and buttons, AM/PM toggles at 12

3. Press NEXT

4. Adjust minutes with + and buttons

5. Press

NEXT

6. Adjust current day with + and buttons

7. Press NEXT to complete and return to normal operation

MANUAL REGENERATION

NOTE: For softeners, if brine tank does not contain salt, fill with salt and wait at least two hours before regeneration.

If you need to initiate a manual regeneration, either immediately, or the same night at the preprogrammed time for regeneration (typically 2:00 AM), complete the following steps.

REGEN TODAY and TIME OF DAY will flash alternately if a regeneration is expected tonight.

REGEN TODAY

GPM

8 2:40

MON

PM

For Immediate Regeneration:

Press and hold REGEN until valve motor starts (typically 3 seconds).

For Regeneration the same night:

Press and release REGEN (notice that flashing “REGEN TODAY” appears).

ERROR

If the display toggles between “Error” and an error code (i.e. a number), call a service technician and report the error code.

BYPASS VALVE OPERATION

To shut off water to the system, position arrow handles as shown in the bypass operation diagram below. If your valve doesn’t look like the diagram below, contact your service technician for instructions on how to shut off water.

NORMAL OPERATION BYPASS OPERATION

TIME

SET

HOUR

2:00

AM

TIME

SET

MINUTES

CURRENT DAY

SET

MON

31

ADJUST HARDNESS, DAYS BETWEEN REGENERATION, TIME OF REGENERATION AND ALARM BUZZER

For initial set-up or to make adjustments, please complete the following steps.

1. Accessed by pressing

NEXT

and + button simultaneously

2. Adjust hardness using + and buttons

3. Press NEXT

4. Adjust days between regenerations using + and buttons

5. Press NEXT

6. Adjust time of regeneration hour with + and buttons,

AM/PM toggles at 12.

7. Press NEXT

8. Adjust time of regeneration minutes with + and buttons

9. Press NEXT

10. Turn service alarm time ON with + and buttons.

Default is OFF.

11. Press NEXT twice

12. Turn service alarm gallons ON with + and buttons.

Default is OFF.

13. Press NEXT twice

14. Turn alarm buzzer ON or OFF with + and buttons.

15. Press NEXT

16. Adjust alarm buzzer start time with + and buttons.

17. Press

NEXT

18. Adjust alarm buzzer end time with + and buttons.

19. Press

NEXT

20. Turn display backlight ON or OFF with + and buttons.

Default is ON.

21. Press

NEXT

to complete and return to normal operation.

WATER HARDNESS

SET

SET

20

GR

DAYS BETWEEN REGEN

SET

REGEN TIME HOUR

6

2:00

AM

REGEN TIME MINUTES

SET

2:00

AM

SERVICE ALARM GAL

SET

SET

SET

OFF

SERVICE ALARM TIME

OFF

ALARM BUZZER START

SET

6:00

AM

ALARM BUZZER END

8:00

PM

LIGHT NORMALLY

SET

ON

© 2014 Evolve Series All rights reserved.

LIT-EV FILT MAN ENVINK 9/14 1M

Manufactured exclusively for Evolve Series Dealers at:

1900 Prospect Court • Appleton, WI 54914

Phone: 920-739-9401 • Fax: 920-739-9406

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement