advertisement
MODEL
MR-J2S-B GIJUTU SIRYOU
MODEL
CODE
1CW502
SH (NA) 030007-G (0711) MEE Printed in Japan
HEAD OFFICE : TOKYO BLDG MARUNOUCHI TOKYO 100-8310
This Instruction Manual uses recycled paper.
Specifications subject to change without notice.
General-Purpose AC Servo
J2-Super
Series
SSCNET Compatible
MODEL
MR-J2S- B
SERVO AMPLIFIER
INSTRUCTION MANUAL
G
Safety Instructions
(Always read these instructions before using the equipment.)
Do not attempt to install, operate, maintain or inspect the servo amplifier and servo motor until you have read through this Instruction Manual, Installation guide, Servo motor Instruction Manual and appended documents carefully and can use the equipment correctly. Do not use the servo amplifier and servo motor until you have a full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
WARNING
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight injury to personnel or may cause physical damage.
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols:
: Indicates what must not be done. For example, "No Fire" is indicated by
: Indicates what must be done. For example, grounding is indicated by .
.
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so on are classified into "POINT".
After reading this Instruction Manual, always keep it accessible to the operator.
A - 1
1. To prevent electric shock, note the following:
WARNING
Before wiring or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier, whether the charge lamp is off or not.
Connect the servo amplifier and servo motor to ground.
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, you may get an electric shock.
Operate the switches with dry hand to prevent an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, you may get an electric shock.
During power-on or operation, do not open the front cover of the servo amplifier. You may get an electric shock.
Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging area are exposed and you may get an electric shock.
Except for wiring or periodic inspection, do not remove the front cover even of the servo amplifier if the power is off. The servo amplifier is charged and you may get an electric shock.
2. To prevent fire, note the following:
CAUTION
Install the servo amplifier, servo motor and regenerative resistor on incombustible material. Installing them directly or close to combustibles will lead to a fire.
Always connect a magnetic contactor (MC) between the main circuit power supply and L
1
, L
2
, and L
3
of the servo amplifier, and configure the wiring to be able to shut down the power supply on the side of the servo amplifier’s power supply. If a magnetic contactor (MC) is not connected, continuous flow of a large current may cause a fire when the servo amplifier malfunctions.
When a regenerative resistor is used, use an alarm signal to switch main power off. Otherwise, a regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
3. To prevent injury, note the follow
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal. Otherwise, a burst, damage, etc. may occur.
Connect the terminals correctly to prevent a burst, damage, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.) with the servo amplifier heat sink, regenerative resistor, servo motor, etc. since they may be hot while power is on or for some time after power-off. Their temperatures may be high and you may get burnt or a parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
A - 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric shock, etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their weights.
Stacking in excess of the specified number of products is not allowed.
Do not carry the servo motor by the cables, shaft or encoder.
Do not hold the front cover to transport the servo amplifier. The servo amplifier may drop.
Install the servo amplifier in a load-bearing place in accordance with the Instruction Manual.
Do not climb or stand on servo equipment. Do not put heavy objects on equipment.
The servo amplifier and servo motor must be installed in the specified direction.
Leave specified clearances between the servo amplifier and control enclosure walls or other equipment.
Do not install or operate the servo amplifier and servo motor which has been damaged or has any parts missing.
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible matter from entering the servo amplifier and servo motor.
Do not drop or strike servo amplifier or servo motor. Isolate from all impact loads.
When you keep or use it, please fulfill the following environmental conditions.
Ambient
Ambient humidity
Ambience
Altitude
(Note)
Vibration
Environment temperature
Servo amplifier
Conditions
Servo motor
In [ ] 0 to 55 (non-freezing) operation [ ] 32 to 131 (non-freezing)
[ ] 20 to 65 (non-freezing)
In storage
In operation
In storage
[ ] 4 to 149 (non-freezing)
90%RH or less (non-condensing)
0 to 40 (non-freezing)
32 to 104 (non-freezing)
15 to 70 (non-freezing)
5 to 158 (non-freezing)
80%RH or less (non-condensing)
90%RH or less (non-condensing)
Indoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m (3280 ft) above sea level
[m/s 2 ] 5.9 or less
HC-KFS Series
HC-MFS Series
HC-UFS13 to 73
HC-SFS81
HC-SFS52 to 152
HC-SFS53 to 153
HC-RFS Series
HC-UFS 72 152
HC-SFS121 201
HC-SFS202 352
HC-SFS203 353
HC-UFS202 to 502
HC-SFS301
HC-SFS502 to 702
HA-LFS11K2 to 22K2
X Y : 49
X Y : 24.5
X : 24.5
Y : 49
X : 24.5
Y : 29.4
X : 11.7
Y : 29.4
[ft/s 2 ] 19.4 or less
HC-KFS Series
HC-MFS Series
HC-UFS 13 to 73
HC-SFS81
HC-SFS52 to 152
HC-SFS53 to 153
HC-RFS Series
HC-UFS 72 152
HC-SFS121 201
HC-SFS202 352
HC-SFS203 353
HC-UFS202 to 502
HC-SFS301
HC-SFS502 to 702
HA-LFS11K2 to 22K2
X Y : 161
X Y : 80
X : 80
Y : 161
X : 80
Y : 96
X : 38
Y : 96
Note. Except the servo motor with reduction gear.
A - 3
CAUTION
Securely attach the servo motor to the machine. If attach insecurely, the servo motor may come off during operation.
The servo motor with reduction gear must be installed in the specified direction to prevent oil leakage.
Take safety measures, e.g. provide covers, to prevent accidental access to the rotating parts of the servo motor during operation.
Never hit the servo motor or shaft, especially when coupling the servo motor to the machine. The encoder may become faulty.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break.
When the equipment has been stored for an extended period of time, consult Mitsubishi.
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may misoperate.
Do not install a power capacitor, surge absorber or radio noise filter (FR-BIF option) between the servo motor and servo amplifier.
Connect the output terminals (U, V, W) correctly. Otherwise, the servo motor will operate improperly.
Connect the servo motor power terminal (U, V, W) to the servo motor power input terminal (U, V, W) directly. Do not let a magnetic contactor, etc. intervene.
Servo amplifier
U
V
W
U
Servo motor
V
W
M
Servo amplifier
U
V
W
U
Servo motor
V
W
M
Do not connect AC power directly to the servo motor. Otherwise, a fault may occur.
The surge absorbing diode installed on the DC output signal relay of the servo amplifier must be wired in the specified direction. Otherwise, the forced stop (EM1) and other protective circuits may not operate.
Servo amplifier
COM
(24VDC)
Control output signal
RA
Servo amplifier
COM
(24VDC)
Control output signal
RA
When the cable is not tightened enough to the terminal block (connector), the cable or terminal block
(connector) may generate heat because of the poor contact. Be sure to tighten the cable with specified torque.
A - 4
(3) Test run adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to perform unexpected operation.
The parameter settings must not be changed excessively. Operation will be insatiable.
(4) Usage
CAUTION
Provide a forced stop circuit to ensure that operation can be stopped and power switched off immediately.
Any person who is involved in disassembly and repair should be fully competent to do the work.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off to prevent an accident. A sudden restart is made if an alarm is reset with the run signal on.
Do not modify the equipment.
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be caused by electronic equipment used near the servo amplifier.
Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break a servo amplifier.
Use the servo amplifier with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used for ordinary braking.
For such reasons as service life and mechanical structure (e.g. where a ball screw and the servo motor are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety, install a stopper on the machine side.
(5) Corrective actions
CAUTION
When it is assumed that a hazardous condition may take place at the occur due to a power failure or a product fault, use a servo motor with electromagnetic brake or an external brake mechanism for the purpose of prevention.
Configure the electromagnetic brake circuit so that it is activated not only by the interface unit signals but also by a forced stop (EM1).
Contacts must be open when servo-off, when an alarm occurrence and when an electromagnetic brake interlock (MBR).
Servo motor
RA EM1
Circuit must be opened during forced stop (EM1).
24VDC
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before restarting operation.
When power is restored after an instantaneous power failure, keep away from the machine because the machine may be restarted suddenly (design the machine so that it is secured against hazard if restarted).
A - 5
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the servo amplifier will deteriorate. To prevent a secondary accident due to a fault, it is recommended to replace the electrolytic capacitor every 10 years when used in general environment.
Please consult our sales representative.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn without covers and safety guards. When the equipment is operated, the covers and safety guards must be installed as specified. Operation must be performed in accordance with this Instruction Manual.
About processing of waste
When you discard servo amplifier, a battery (primary battery), and other option articles, please follow the law of each country (area).
FOR MAXIMUM SAFETY
These products have been manufactured as a general-purpose part for general industries, and have not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
Before using the products for special purposes such as nuclear power, electric power, aerospace, medicine, passenger movement vehicles or under water relays, contact Mitsubishi.
These products have been manufactured under strict quality control. However, when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If the total number of the following operations exceeds 100,000, the servo amplifier and/or converter unit may fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Write to the EEP-ROM due to device changes
Precautions for Choosing the Products
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused 0y faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.
A - 6
COMPLIANCE WITH EC DIRECTIVES
1. WHAT ARE EC DIRECTIVES?
The EC directives were issued to standardize the regulations of the EU countries and ensure smooth distribution of safety-guaranteed products. In the EU countries, the machinery directive (effective in
January, 1995), EMC directive (effective in January, 1996) and low voltage directive (effective in January,
1997) of the EC directives require that products to be sold should meet their fundamental safety requirements and carry the CE marks (CE marking). CE marking applies to machines and equipment into which servo amplifiers have been installed.
(1) EMC directive
The EMC directive applies not to the servo units alone but to servo-incorporated machines and equipment. This requires the EMC filters to be used with the servo-incorporated machines and equipment to comply with the EMC directive. For specific EMC directive conforming methods, refer to the EMC Installation Guidelines (IB(NA)67310).
(2) Low voltage directive
The low voltage directive applies also to servo units alone. Hence, they are designed to comply with the low voltage directive.
This servo is certified by TUV, third-party assessment organization, to comply with the low voltage directive.
(3) Machine directive
Not being machines, the servo amplifiers need not comply with this directive.
2. PRECAUTIONS FOR COMPLIANCE
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier :MR-J2S-10B to MR-J2S-22KB
MR-J2S-10B1 to MR-J2S-40B1
Servo motor :HC-KFS
HC-MFS
HC-SFS
HC-RFS
HC-UFS
HA-LFS
HC-LFS
(2) Configuration
Control box
(Note)
Reinforced insulating transformer
No-fuse breaker
NFB
Magnetic contactor
MC
Reinforced insulating type
24VDC power supply
Servo amplifier
Servo motor
M
Note. The insulating transformer is not required for the 11kW or more servo amplifier.
(3) Environment
Operate the servo amplifier at or above the contamination level 2 set forth in IEC60664-1. For this purpose, install the servo amplifier in a control box which is protected against water, oil, carbon, dust, dirt, etc. (IP54).
A - 7
(4) Power supply
(a) Operate the servo amplifier 7kW or less to meet the requirements of the overvoltage category II set forth in IEC60664-1. For this purpose, a reinforced insulating transformer conforming to the IEC or EN standard should be used in the power input section.
Since the 11kW or more servo amplifier can be used under the conditions of the overvoltage category III set forth in IEC60664-1, a reinforced insulating transformer is not required in the power input section.
(b) When supplying interface power from external, use a 24VDC power supply which has been insulation-reinforced in I/O.
(5) Grounding
(a) To prevent an electric shock, always connect the protective earth (PE) terminals (marked ) of the servo amplifier to the protective earth (PE) of the control box.
(b) Do not connect two ground cables to the same protective earth (PE) terminal ( ) Always connect the cables to the terminals one-to-one.
PE terminals PE terminals
(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE) terminals of the servo amplifier must be connected to the corresponding earth terminals.
(6) Wiring
(a) The cables to be connected to the terminal block of the servo amplifier must have crimping terminals provided with insulating tubes to prevent contact with adjacent terminals.
Crimping terminal
Insulating tube
Cable
(b) Use the servo motor side power connector which complies with the EN Standard. The EN Standard compliant power connector sets are available from us as options.
(7) Auxiliary equipment and options
(a) The no-fuse breaker and magnetic contactor used should be the EN or IEC standard-compliant products of the models described in section 12.2.2.
(b) The sizes of the cables described in section 12.2.1 meet the following requirements. To meet the other requirements, follow Table 5 and Appendix C in EN60204-1.
Ambient temperature: 40 (104) [ ( )]
Sheath: PVC (polyvinyl chloride)
Installed on wall surface or open table tray
(c) Use the EMC filter for noise reduction.
(8) Performing EMC tests
When EMC tests are run on a machine/device into which the servo amplifier has been installed, it must conform to the electromagnetic compatibility (immunity/emission) standards after it has satisfied the operating environment/electrical equipment specifications.
For the other EMC directive guidelines on the servo amplifier, refer to the EMC Installation
Guidelines(IB(NA)67310).
A - 8
CONFORMANCE WITH UL/C-UL STANDARD
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier :MR-J2S-10B to MR-J2S-22KB
MR-J2S-10B1 to MR-J2S-40B1
Servo motor :HC-KFS
HC-MFS
HC-SFS
HC-RFS
HC-UFS
HA-LFS
HC-LFS
(2) Installation
Install a cooling fan of 100CFM (2.8m
3 /min) air flow 4 in (10.16 cm) above the servo amplifier or provide cooling of at least equivalent capability.
(3) Short circuit rating
This servo amplifier conforms to the circuit whose peak current is limited to 5000A or less. Having been subjected to the short-circuit tests of the UL in the alternating-current circuit, the servo amplifier conforms to the above circuit.
(4) Capacitor discharge time
The capacitor discharge time is as listed below. To ensure safety, do not touch the charging section for
10 minutes after power-off.
Servo amplifier
MR-J2S-10B(1) 20B(1)
MR-J2S-40B(1) 60B
MR-J2S-70B to 350B
MR-J2S-500B 700B
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
Discharge time
[min]
3
5
1
2
4
6
8
(5) Options and auxiliary equipment
Use UL/C-UL standard-compliant products.
(6) Attachment of a servo motor
For the flange size of the machine side where the servo motor is installed, refer to “CONFORMANCE
WITH UL/C-UL STANDARD” in the Servo Motor Instruction Manual.
(7) About wiring protection
For installation in United States, branch circuit protection must be provided, in accordance with the
National Electrical Code and any applicable local codes.
For installation in Canada, branch circuit protection must be provided, in accordance with the Canada
Electrical Code and any applicable provincial codes.
A - 9
<<About the manuals>>
This Instruction Manual and the MELSERVO Servo Motor Instruction Manual are required if you use the General-Purpose AC servo MR-J2S-B for the first time. Always purchase them and use the MR-
J2S-B safely.
Also read the manual of the servo system controller.
Relevant manuals
Manual name
MELSERVO-J2-Super Series To Use the AC Servo Safely
(Packed with the servo amplifier)
MELSERVO Servo Motor Instruction Manual
EMC Installation Guidelines
Manual No.
IB(NA)0300010
SH(NA)3181
IB(NA)67310
A - 10
CONTENTS
1. FUNCTIONS AND CONFIGURATION 1- 1 to 1-22
1.1 Introduction.............................................................................................................................................. 1- 1
1.2 Function block diagram .......................................................................................................................... 1- 2
1.3 Servo amplifier standard specifications ................................................................................................ 1- 5
1.4 Function list ............................................................................................................................................. 1- 6
1.5 Model code definition .............................................................................................................................. 1- 7
1.6 Combination with servo motor............................................................................................................... 1- 8
1.7 Structure................................................................................................................................................... 1- 9
1.7.1 Parts identification ........................................................................................................................... 1- 9
1.7.2 Removal and reinstallation of the front cover .............................................................................. 1-14
1.8 Servo system with auxiliary equipment............................................................................................... 1-17
2. INSTALLATION 2- 1 to 2- 4
2.1 Environmental conditions....................................................................................................................... 2- 1
2.2 Installation direction and clearances .................................................................................................... 2- 2
2.3 Keep out foreign materials ..................................................................................................................... 2- 3
2.4 Cable stress .............................................................................................................................................. 2- 4
3. SIGNALS AND WIRING 3- 1 to 3-38
3.1 Connection example of control signal system....................................................................................... 3- 2
3.1.1 MR-J2S-700B or less ........................................................................................................................ 3- 2
3.1.2 MR-J2S-11KB or more ..................................................................................................................... 3- 4
3.2 I/O signals................................................................................................................................................. 3- 6
3.2.1 Connectors and signal arrangements............................................................................................. 3- 6
3.2.2 Signal explanations .......................................................................................................................... 3- 8
3.3 Alarm occurrence timing chart .............................................................................................................. 3- 9
3.4 Interfaces................................................................................................................................................. 3-10
3.4.1 Common line .................................................................................................................................... 3-10
3.4.2 Detailed description of the interfaces ............................................................................................ 3-11
3.5 Power line circuit.................................................................................................................................... 3-14
3.5.1 Connection example......................................................................................................................... 3-14
3.5.2 Terminals.......................................................................................................................................... 3-16
3.5.3 Power-on sequence........................................................................................................................... 3-17
3.6 Connection of servo amplifier and servo motor ................................................................................... 3-18
3.6.1 Connection instructions .................................................................................................................. 3-18
3.6.2 Connection diagram......................................................................................................................... 3-18
3.6.3 I/O terminals .................................................................................................................................... 3-20
3.7 Servo motor with electromagnetic brake ............................................................................................. 3-22
3.8 Grounding................................................................................................................................................ 3-26
3.9 Servo amplifier terminal block (TE2) wiring method ......................................................................... 3-27
3.9.1 For servo amplifier produced later than January, 2006.............................................................. 3-27
3.9.2 For servo amplifier produced earlier than December, 2005........................................................ 3-29
3.10 Instructions for the 3M connector....................................................................................................... 3-30
3.11 Control axis selection ........................................................................................................................... 3-31
1
3.12 Power line circuit of the MR-J2S-11KB to MR-J2S-22KB ............................................................... 3-32
3.12.1 Connection example ...................................................................................................................... 3-33
3.12.2 Servo amplifier terminals ............................................................................................................. 3-34
3.12.3 Servo motor terminals................................................................................................................... 3-35
4. OPERATION AND DISPLAY 4- 1 to 4- 8
4.1 When switching power on for the first time.......................................................................................... 4- 1
4.2 Start up..................................................................................................................................................... 4- 2
4.3 Servo amplifier display ........................................................................................................................... 4- 4
4.4 Test operation mode ................................................................................................................................ 4- 6
5. PARAMETERS 5- 1 to 5-20
5.1 Parameter write inhibit .......................................................................................................................... 5- 1
5.2 Lists........................................................................................................................................................... 5- 1
5.3 Analog monitor ....................................................................................................................................... 5-14
5.4 Replacement of MR-J2- B by MR-J2S- B....................................................................................... 5-17
5.4.1 Main modifications made to the parameters ................................................................................ 5-17
5.4.2 Explanation of the modified parameters....................................................................................... 5-18
6. GENERAL GAIN ADJUSTMENT 6- 1 to 6-12
6.1 Different adjustment methods ............................................................................................................... 6- 1
6.1.1 Adjustment on a single servo amplifier.......................................................................................... 6- 1
6.1.2 Adjustment using MR Configurator (servo configuration software) ........................................... 6- 3
6.2 Auto tuning .............................................................................................................................................. 6- 4
6.2.1 Auto tuning mode ............................................................................................................................. 6- 4
6.2.2 Auto tuning mode operation ............................................................................................................ 6- 5
6.2.3 Adjustment procedure by auto tuning............................................................................................ 6- 6
6.2.4 Response level setting in auto tuning mode................................................................................... 6- 7
6.3 Manual mode 1 (simple manual adjustment)....................................................................................... 6- 8
6.3.1 Operation of manual mode 1 ........................................................................................................... 6- 8
6.3.2 Adjustment by manual mode 1 ....................................................................................................... 6- 8
6.4 Interpolation mode ................................................................................................................................. 6-11
6.5 Differences in auto tuning between MELSERVO-J2 and MELSERVO-J2-Super .......................... 6-12
6.5.1 Response level setting ..................................................................................................................... 6-12
6.5.2 Auto tuning selection....................................................................................................................... 6-12
7. SPECIAL ADJUSTMENT FUNCTIONS 7- 1 to 7-10
7.1 Function block diagram .......................................................................................................................... 7- 1
7.2 Machine resonance suppression filter ................................................................................................... 7- 1
7.3 Adaptive vibration suppression control................................................................................................. 7- 3
7.4 Low-pass filter ......................................................................................................................................... 7- 4
7.5 Gain changing function........................................................................................................................... 7- 5
7.5.1 Applications....................................................................................................................................... 7- 5
7.5.2 Function block diagram.................................................................................................................... 7- 5
7.5.3 Parameters ........................................................................................................................................ 7- 6
7.5.4 Gain changing operation.................................................................................................................. 7- 8
2
8. INSPECTION 8- 1 to 8- 2
9. TROUBLESHOOTING 9- 1 to 9- 8
9.1 Alarms and warning list ......................................................................................................................... 9- 1
9.2 Remedies for alarms................................................................................................................................ 9- 2
9.3 Remedies for warnings............................................................................................................................ 9- 8
10. OUTLINE DIMENSION DRAWINGS 10- 1 to 10-10
10.1 Servo amplifiers................................................................................................................................... 10- 1
10.2 Connectors............................................................................................................................................ 10- 8
11. CHARACTERISTICS 11- 1 to 11- 8
11.1 Overload protection characteristics................................................................................................... 11- 1
11.2 Power supply equipment capacity and generated loss .................................................................... 11- 2
11.3 Dynamic brake characteristics........................................................................................................... 11- 5
11.3.1 Dynamic brake operation............................................................................................................. 11- 5
11.3.2 The dynamic brake at the load inertia moment ........................................................................ 11- 7
11.4 Encoder cable flexing life .................................................................................................................... 11- 7
11.5 Inrush currents at power-on of main circuit and control circuit .................................................... 11- 8
12. OPTIONS AND AUXILIARY EQUIPMENT 12- 1 to 12-64
12.1 Options.................................................................................................................................................. 12- 1
12.1.1 Regenerative options .................................................................................................................... 12- 1
12.1.2 FR-BU2 brake unit......................................................................................................................12-10
12.1.3 Power regeneration converter ....................................................................................................12-17
12.1.4 External dynamic brake..............................................................................................................12-20
12.1.5 Cables and connectors.................................................................................................................12-23
12.1.6 Maintenance junction card (MR-J2CN3TM) ............................................................................12-36
12.1.7 Battery (MR-BAT, A6BAT).........................................................................................................12-37
12.1.8 MR Configurator (servo configurations software)....................................................................12-37
12.1.9 Power regeneration common converter.....................................................................................12-39
12.1.10 Heat sink outside mounting attachment (MR-JACN)...........................................................12-43
12.2 Auxiliary equipment ..........................................................................................................................12-46
12.2.1 Recommended wires....................................................................................................................12-46
12.2.2 No-fuse breakers, fuses, magnetic contactors...........................................................................12-49
12.2.3 Power factor improving reactors ................................................................................................12-49
12.2.4 Power factor improving DC reactors..........................................................................................12-50
12.2.5 Relays............................................................................................................................................12-51
12.2.6 Surge absorbers ...........................................................................................................................12-51
12.2.7 Noise reduction techniques.........................................................................................................12-52
12.2.8 Leakage current breaker.............................................................................................................12-59
12.2.9 EMC filter.....................................................................................................................................12-61
13. ABSOLUTE POSITION DETECTION SYSTEM 13- 1 to 13- 4
13.1 Features................................................................................................................................................ 13- 1
3
13.2 Specifications ....................................................................................................................................... 13- 2
13.3 Battery installation procedure ........................................................................................................... 13- 3
13.4 Confirmation of absolute position detection data............................................................................. 13- 4
APPENDIX App- 2
App 1. Combination of servo amplifier and servo motor ...................................................................... App- 1
App 2. Change of connector sets to the RoHS compatible products .................................................... App- 2
4
Optional Servo Motor Instruction Manual CONTENTS
The rough table of contents of the optional MELSERVO Servo Motor Instruction Manual is introduced here for your reference. Note that the contents of the Servo Motor Instruction Manual are not included in the Servo Amplifier Instruction Manual.
1. INTRODUCTION
2. INSTALLATION
3. CONNECTORS USED FOR SERVO MOTOR WIRING
4. INSPECTION
5. SPECIFICATIONS
6. CHARACTERISTICS
7. OUTLINE DIMENSION DRAWINGS
8. CALCULATION METHODS FOR DESIGNING
5
MEMO
6
1. FUNCTIONS AND CONFIGURATION
1. FUNCTIONS AND CONFIGURATION
1.1 Introduction
The Mitsubishi MELSERVO-J2-Super series general-purpose AC servo is based on the MELSERVO-J2 series and has further higher performance and higher functions.
It is connected with a servo system controller or similar device via a serial bus (SSCNET) and the servo amplifier reads position data directly to perform operation.
Data from a command unit controls the speed and rotation direction of the servo motor and executes precision positioning.
A torque limit is imposed on the servo amplifier by the clamp circuit to protect the power transistor in the main circuit from overcurrent due to sudden acceleration/deceleration or overload. The torque limit value can be changed to any value with an external analog input or the parameter.
As this new series has the RS-232C serial communication function, a MR Configurator (servo configuration software)-installed personal computer or the like can be used to perform parameter setting, test operation, status display monitoring, gain adjustment, etc.
With real-time auto tuning, you can automatically adjust the servo gains according to the machine.
The MELSERVO-J2-Super series servo motor is equipped with an absolute position encoder which has the resolution of 131072 pulses/rev to ensure more accurate control as compared to the MELSERVO-J2 series. Simply adding a battery to the servo amplifier makes up an absolute position detection system.
This makes home position return unnecessary at power-on or alarm occurrence by setting a home position once.
1 - 1
1. FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
The function block diagram of this servo is shown below.
(1) MR-J2S-350B or less
Regenerative option
(Note 2)
Power supply
NFB MC
Servo amplifier
Diode stack Relay
L
1
L
L
2
3
P C
CHARGE lamp
Regenerative
TR
(Note 3) Cooling fan
D
(Note 1)
L
L
11
21
Control circuit power supply
Current detector
Dynamic brake
Base amplifier
Voltage detection
Overcurrent protection
Current detection
Position command input
Model position control
Model speed control
Virtual motor
Virtual encoder
Model position
Actual position control
Model speed
Actual speed control
Model torque
Current control
U
V
W
Servo motor
U
V
W
M
B1
B2
Electromagnetic brake
Encoder
CN1A
I/F Control
CN1B
Controller or
Servo amplifier
Servo amplifier or termination connector
RS-232C
CN3
D/A
MR-BAT
Optional battery
(for absolute position
detection system)
Analog monitor
(2 channels)
Personal computer
Note 1. The built-in regenerative resistor is not provided for the MR-J2S-10B (1).
2. For 1-phase 230V, connect the power supply to L
1
, L
2
and leave L
3
open.
L
3
is not provided for a 1-phase 100 to120V power supply. Refer to section 1.3 for the power supply specification.
3. Servo amplifiers MR-J2S-200B have a cooling fan.
1 - 2
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-500B, MR-J2S-700B
(Note)
Power supply
NFB MC
Servo amplifier
Diode stack Relay
L
1
L
2
L
3
CHARGE lamp
Regenerative option
P C N
Regenerative
TR
Cooling fan
L
11
L
21
Control circuit power supply
Current detector
Dynamic brake
Base amplifier
Voltage detection
Overcurrent
Protection
Current detection
Position command input
Model position control
Model speed control
Virtual motor
Virtual encoder
Model position
Actual position control
Model speed
Actual speed control
Model torque
Current control
U
V
W
Servo motor
U
V
W
M
B1
B2
Electromagnetic brake
Encoder
I/F Control
CN1A CN1B
Controller or
Servo amplifier
Servo amplifier or termination connector
RS-232C
CN3
D/A
MR-BAT
Optional battery
(for absolute position
detection system)
Analog monitor
(2 channels)
Personal computer
Note. Refer to section 1.3 for the power supply specification.
1 - 3
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-11KB or more
Regenerative option
(Note)
Power supply
NFB MC
Servo amplifier
L
2
L
3
L
1
Diode stack Thyristor
P1 P C
CHAR-
GE lamp
N
Regenrative
TR
L
L
11
21
Control circuit power supply
Cooling fan
Current detector
Base amplifier
Voltage detection
Overcurrent protection
Current detection
Position command input Model position control
Model speed control
Virtual motor
Virtual encoder
U
V
W
Servo motor
U
V
W
M
B1
B2
Electromagnetic brake
Encoder
Model position
Actual position control
Model speed
Actual speed control
Model torque
Current control
I/F Control
CN1A CN1B
Controller or
Servo amplifier
Servo amplifier or termination connector
Note. Refer to section 1.3 for the power supply specification.
RS-232C D/A
CN3 CN4
MR-BAT
Optional battery
(for absolute position
detection system)
Analog monitor
(2 channels)
Personal computer
1 - 4
1. FUNCTIONS AND CONFIGURATION
1.3 Servo amplifier standard specifications
Servo amplifier
MR-J2S10B 20B 40B 60B 70B 100B 200B 350B 500B 700B 11KB 15KB 22KB 10B1 20B1 40B1
Item
Voltage/frequency
Permissible voltage fluctuation
Ambient
Altitude
Vibration
Mass
3-phase 200 to 230VAC,
50/60Hz or 1-phase 230VAC,
50/60Hz
3-phase 200 to 230VAC:170 to 253VAC
1-phase 230VAC: 207 to
253VAC
3-phase 200 to 230VAC, 50/60Hz
3-phase 170 to 253VAC
1-phase 100 to
120VAC 50/60Hz
1-phase 85 to
127VAC
Permissible frequency fluctuation
Power supply capacity
Inrush current
90%RH or less (non-condensing)
Within 5%
Control system
Dynamic brake
Protective functions
Structure
Sine-wave PWM control, current control system
Built-in
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal relay), servo motor overheat protection, encoder fault protection, regenerative fault protection, undervoltage, instantaneous power failure protection, overspeed protection, excessive error protection
Self-cooled, open (IP00)
Force-cooling, open
(IP00)
External
Self-cooled, open(IP00)
Ambient temperature
In [ ] 0 to 55 (non-freezing) operation [ ] 32 to 131 (non-freezing)
[ ] 20 to 65 (non-freezing)
In storage
[ ] 4 to 149 (non-freezing)
Ambient humidity
In operation
In storage
Refer to section 11.2
Refer to section 11.5
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m (3280ft) above sea level
5.9 [m/s 2 ] or less
19.4 [ft/s 2 ] or less
[kg] 0.7
0.7
1.1
1.1
1.7
1.7
2.0
2.0
4.9
7.2
16 16 20 0.7
0.7
1.1
[lb] 1.5
1.5
2.4
2.4 3.75 3.75 4.4
4.4 10.8 15.9 35.3 35.3 44.1 1.5
1.5
2.4
1 - 5
1. FUNCTIONS AND CONFIGURATION
1.4 Function list
The following table lists the functions of this servo. For details of the functions, refer to the reference field.
Function
High-resolution encoder
Absolute position detection system
Adaptive vibration suppression control
Description Reference
High-resolution encoder of 131072 pulses/rev is used as a servo motor encoder.
Merely setting a home position once makes home position return unnecessary at every power-on.
Chapter 13
Servo amplifier detects mechanical resonance and sets filter characteristics automatically to suppress mechanical vibration.
Section 7.3
Low-pass filter
Machine analyzer function
Machine simulation
Gain search function
Suppresses high-frequency resonance which occurs as servo system response is increased.
Section 7.4
Analyzes the frequency characteristic of the mechanical system by simply connecting a MR Configurator (servo configuration software)-installed personal computer and servo amplifier.
Can simulate machine motions on a personal computer screen on the basis of the machine analyzer results. The MR Configurator (servo configuration software) is required.
Personal computer changes gains automatically and searches for overshootfree gains in a short time. The MR Configurator (servo configuration software) is required.
Slight vibration suppression control
Suppresses vibration of 1 pulse produced at a servo motor stop.
Parameter No.24
Auto tuning
Regenerative option
Brake unit
Return converter
Automatically adjusts the gain to optimum value if load applied to the servo motor shaft varies. Higher in performance than MELSERVO-J2 series servo amplifier.
Chapter 6
Used when the built-in regenerative resistor of the servo amplifier does not have sufficient regenerative capability for the regenerative power generated.
Section 12.1.1
Used when the regenerative option cannot provide enough regenerative power.
Can be used with the MR-J2S-500B to MR-J2S-22KB.
Used when the regenerative option cannot provide enough regenerative power.
Can be used with the MR-J2S-500B to MR-J2S-22KB.
Section 12.1.2
Section 12.1.3
Torque limit Servo motor torque can be limited to any value.
Parameters
No.10, 11
Forced stop signal automatic
ON
Forced stop (EM1) can be automatically switched on internally to invalidate it. Parameter No.23
Output signal (DO) forced output
Output signal can be forced on/off independently of the servo status.
Use this function for output signal wiring check, etc.
Section 4.4
(1) (e)
Test operation mode
Analog monitor output
JOG operation positioning operation motor-less operation DO forced output Section 4.4
Servo status is output in terms of voltage in real time.
Parameter No. 22
MR Configurator
(Servo configuration software)
Using a personal computer, parameter setting, test operation, status display, etc. can be performed.
Section 12.1.8
1 - 6
1. FUNCTIONS AND CONFIGURATION
1.5 Model code definition
(1) Rating plate
MITSUBISHI
MODEL
MR-J2S-60B
POWER :
INPUT :
OUTPUT :
600W
3.2A 3PH 1PH200-230V 50Hz
3PH 1PH200-230V 60Hz
5.5A 1PH 230V 50/60Hz
170V 0-360Hz 3.6A
SERIAL : A5
TC3 AAAAG52
PASSED
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
Model
Capacity
Applicable power supply
Rated output current
Serial number
(2) Model
MR–J2S–
Series
B MR–J2S–100B or less MR–J2S–200B 350B
With no regenerative resistor
Symbol Description
–PX
Indicates a servo amplifier of 11k to 22kW that does not use a regenerative resistor as standard accessory.
Power Supply
Symbol
None
Power supply
3-phase 200 to 230V
(Note 2) 1-phase 230V
(Note1)
1
1-phase 100V to 120V
Note 1. 1-phase 200V to 230V is supported
by 400W or less.
2. 1-phase 100V to 120V is supported
by 750W or less.
MR-J2S-500B
Rating plate
SSCNET compatible
10
20
40
60
70
100
200
Rated output
Symbol
Rated output [kW]
0.1
0.2
0.4
0.6
0.75
1
2
Symbol
350
500
700
11k
15k
22k
Rated output [kW]
3.5
5
7
11
15
22
Rating plate
MR-J2S-11KB 15KB
MR-J2S-700B
Rating plate
MR-J2S-22KB
Rating plate
Rating plate Rating plate
1 - 7
1. FUNCTIONS AND CONFIGURATION
1.6 Combination with servo motor
The following table lists combinations of servo amplifiers and servo motors. The same combinations apply to the models with electromagnetic brakes and the models with reduction gears.
Servo amplifier
MR-J2S-10B(1)
MR-J2S-20B(1)
MR-J2S-40B(1)
MR-J2S-60B
MR-J2S-70B
MR-J2S-100B
MR-J2S-200B
MR-J2S-350B
MR-J2S-500B
MR-J2S-700B
HC-KFS
053 13
23
43
(Note 1) 73
HC-MFS
053 13
23
43
73
Servo motors
HC-SFS
1000r/min 2000r/min 3000r/min
52 53
81 102 103
121 201 152 202 153 203
301 352 353
(Note 1)
502
(Note 1)
702
HC-RFS
HC-UFS
2000r/min 3000r/min
13
23
43
72
103 153 152
(Note 1) 203 (Note 1) 202
(Note 1)
353 503
(Note 1)
352 502
73
Servo amplifier
1000r/min
Servo motors
HA-LFS
1500r/min 2000r/min
(Note 1)
HC-LFS
MR-J2S-60B
MR-J2S-100B
MR-J2S-200B
MR-J2S-350B
52
102
152
202
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
(Note 2) 601 (Note 2)701M
(Note 1)
801 12K1
(Note 1) 15K1
(Note 1)
20K1 25K1
(Note 1)
11K1M
(Note 1)
15K1M
(Note 1)
22K1M
(Note 1)
502
(Note 1)
702
(Note 1)
11K2
(Note 1)
15K2
(Note 1)
22K2
302
Note 1. These servo motors may not be connected depending on the production time of the servo amplifier. Please refer to appendix.
2. Consult us since the servo amplifier to be used with any of these servo motors is optional.
1 - 8
1. FUNCTIONS AND CONFIGURATION
1.7 Structure
1.7.1 Parts identification
(1) MR-J2S-100B or less
5
6 7
8 9
A
B
D
01
EF
Name/Application Reference
Battery holder
Contains the battery for absolute position data backup.
Section 13.3
Battery connector (CON1)
Used to connect the battery for absolute position data backup.
Section 13.3
Display
The two-digit, seven-segment LED shows the servo status and alarm number.
Axis select switch (SW1)
Chapter 4
SW1
3
5
1
7 8 9
D
B
0
F
Used to set the axis number of the servo amplifier.
Section 3.11
Bus cable connector (CN1A)
Used to connect the servo system controller or preceding axis servo amplifier.
Bus cable connector (CN1B)
Used to connect the subsequent axis servo amplifier or termination connector (MR-A-TM).
Communication connector (CN3)
Used to connect a personal computer (RS-232C) or output analog monitor data.
Section 3.2
Section 3.2
Section 3.2
Section 12.1.5
Rating plate Section 1.5
Charge lamp
Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.2
Section 12.1.5
Main circuit terminal block (TE1)
Used to connect the input power supply and servo motor.
Control circuit terminal block (TE2)
Used to connect the control circuit power supply and regenerative option.
Section 3.5.2
Section 10.1
Section 3.5.2
Section 10.1
Section 12.1.1
Protective earth (PE) terminal ( )
Ground terminal.
Section 3.8
Section 10.1
1 - 9
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-200B MR-J2S-350B
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
5
6 7
8 9
A
B
D
01
EF
Name/Application Reference
Battery holder
Contains the battery for absolute position data backup.
Section 13.3
Battery connector (CON1)
Used to connect the battery for absolute position data backup.
Section 13.3
Display
The two-digit, seven-segment LED shows the servo status and alarm number.
Chapter 4
Axis select switch (SW1)
SW1
3
5
1
7 8 9
D
B
0
F
Used to set the axis number of the servo amplifier.
Section 3.11
Cooling fan
Fixed part
(4 places)
Bus cable connector (CN1A)
Used to connect the servo system controller or preceding axis servo amplifier.
Bus cable connector (CN1B)
Used to connect the subsequent axis servo amplifier or termination connector (MR-A-TM).
Communication connector (CN3)
Used to connect a personal computer (RS-232C) or output analog monitor data.
Section 3.2
Section 3.2
Section 3.2
Section 12.1.5
Rating plate Section 1.5
Charge lamp
Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.2
Section 12.1.5
Main circuit terminal block (TE1)
Used to connect the input power supply and servo motor.
Section 3.5.2
Section 10.1
Control circuit terminal block (TE2)
Used to connect the control circuit power supply and regenerative option.
Section 3.5.2
Section 10.1
Section 12.1.1
Protective earth (PE) terminal ( )
Ground terminal.
Section 3.8
Section 10.1
1 - 10
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-500B
5
6 7
8 9
A
B
D
01
EF
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
Name/Application
Battery connector (CON1)
Used to connect the battery for absolute position data backup.
Battery holder
Contains the battery for absolute position data backup.
Reference
Section 13.3
Section 13.3
Display
The two-digit, seven-segment LED shows the servo status and alarm number.
Chapter 4
Axis select switch (SW1)
SW1
3
5
1
7 8 9
D
B
0
F
Used to set the axis number of the servo amplifier.
Section 3.11
Fixed part
(4 places)
Cooling fan
Bus cable connector (CN1A)
Used to connect the servo system controller or preceding axis servo amplifier.
Section 3.2
Bus cable connector (CN1B)
Used to connect the subsequent axis servo amplifier or termination connector (MR-A-TM).
Communication connector (CN3)
Used to connect a personal computer (RS-232C) or output analog monitor data.
Section 3.2
Section 3.2
Section 12.1.5
Encoder connector (CN2)
Used to connect the servo motor encoder.
Charge lamp
Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Section 3.2
Section 12.1.5
Control circuit terminal block (TE2)
Used to connect the control circuit power supply.
Section 3.5.2
Section 10.1
Section 12.1.1
Main circuit terminal block (TE1)
Used to connect the input power supply, regenerative option and servo motor.
Section 3.5.2
Section 10.1
Rating plate
Protective earth (PE) terminal ( )
Ground terminal.
Section 1.5
Section 3.8
Section 10.1
1 - 11
1. FUNCTIONS AND CONFIGURATION
(4) MR-J2S-700B
5
6 7
8 9
A
B
D
01
EF
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
Name/Application
Battery connector (CON1)
Used to connect the battery for absolute position data backup.
Battery holder
Contains the battery for absolute position data backup.
Reference
Section 13.3
Section 13.3
Display
The two-digit, seven-segment LED shows the servo status and alarm number.
Chapter 4
Axis select switch (SW1)
SW1
3
5
1
7
8 9
D
B
0
F
Used to set the axis number of the servo amplifier.
Section 3.11
Cooling fan
Fixed part
(4 places)
Bus cable connector (CN1A)
Used to connect the servo system controller or preceding axis servo amplifier.
Section 3.2
Bus cable connector (CN1B)
Used to connect the subsequent axis servo amplifier or termination connector (MR-A-TM).
Communication connector (CN3)
Used to connect a personal computer (RS-232C) or output analog monitor data.
Section 3.2
Section 3.2
Section 12.1.5
Charge lamp
Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Control circuit terminal block (TE2)
Used to connect the control circuit power supply.
Section 3.5.2
Section 10.1
Section 12.1.1
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.2
Section 12.1.5
Rating plate Section 1.5
Main circuit terminal block (TE1)
Used to connect the input power supply, regenerative option and servo motor.
Section 3.5.2
Section 10.1
Protective earth (PE) terminal ( )
Ground terminal.
Section 3.8
Section 10.1
1 - 12
1. FUNCTIONS AND CONFIGURATION
(5) MR-J2S-11KB or more
Cooling fan
POINT
The servo amplifier is shown without the front cover. For removal of the front cover, refer to section 1.7.2.
Name/Application
Axis select switch (SW1)
SW1
D
E
F
0
B A 9
8
1
2
3
5
7 6
Used to set the axis number of the servo amplifier.
Reference
Section 3.11
Fixed part
(4 places)
Display
The two-digit, seven-segment LED shows the servo status and alarm number.
Chapter 4
Battery holder
Contains the battery for absolute position data backup.
Section 13.3
Battery connector (CON1)
Used to connect the battery for absolute position data backup.
Monitor output terminal (CN4)
Used to output monitor values on two channels in the
form of analog signals.
Communication connector (CN3)
Used to connect a personal computer (RS-232C) .
Section 13.3
Section 3.2
Section 12.1.5
Section 3.2
Section 12.1.5
Bus cable connector (CN1A)
Used to connect the servo system controller or preceding axis servo amplifier.
Bus cable connector (CN1B)
Used to connect the subsequent axis servo amplifier or termination connector (MR-A-TM).
Charge lamp
Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Section 3.2
Section 3.2
Control circuit terminal block (TE2)
Used to connect the control circuit power supply.
Encoder connector (CN2)
Used to connect the servo motor encoder.
I/O signal connector (CON2)
Used to connect digital I/O signals.
Rating plate
Section 3.5.2
Section 10.1
Section 12.1.1
Section 3.2
Section 12.1.5
Section 3.2
Section 12.1.5
Section 1.5
Main circuit terminal block (TE1)
Used to connect the input power supply, regenerative option and servo motor.
Section 3.5.2
Section 10.1
Protective earth (PE) terminal ( )
Ground terminal.
Section 3.8
Section 10.1
1 - 13
1. FUNCTIONS AND CONFIGURATION
1.7.2 Removal and reinstallation of the front cover
CAUTION
Before removing or installing the front cover, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
(1) For MR-J2S-350B or less
Removal of the front cover
1)
Reinstallation of the front cover
2)
Front cover hook
(2 places)
2)
Front cover
1) Hold down the removing knob.
2) Pull the front cover toward you.
1)
Front cover socket
(2 places)
1) Insert the front cover hooks into the front cover sockets of
the servo amplifier.
2) Press the front cover against the servo amplifier until the
removing knob clicks.
(2) For MR-J2S-500B
Removal of the front cover
1)
2)
Reinstallation of the front cover
Front cover hook
(2 places)
2)
1)
Front cover
1) Hold down the removing knob.
2) Pull the front cover toward you.
Front cover socket
(2 places)
1) Insert the front cover hooks into the front cover sockets of
the servo amplifier.
2) Press the front cover against the servo amplifier until the
removing knob clicks.
1 - 14
1. FUNCTIONS AND CONFIGURATION
(3) For MR-J2S-700B
Removal of the front cover Reinstallation of the front cover
Front cover hook
(2 places)
B)
2)
A)
1)
A)
1) Push the removing knob A) or B), and put you
finger into the front hole of the front cover.
2) Pull the front cover toward you.
(4) For MR-J2S-11KB or more
Removal of the front cover
2)
1)
Front cover socket
(2 places)
1) Insert the two front cover hooks at the bottom into the
sockets of the servo amplifier.
2) Press the front cover against the servo amplifier until the
removing knob clicks.
Mounting screws
(2 places)
Mounting screws (2 places)
1) Remove the front cover mounting screws (2 places)
and remove the front cover.
2) Remove the front cover mounting screws (2 places).
3) Remove the front cover by drawing it in the direction of arrow.
1 - 15
1. FUNCTIONS AND CONFIGURATION
Reinstallation of the front cover
Mounting screws
(2 places)
1) Insert the front cover in the direction of arrow.
2) Fix it with the mounting screws (2 places).
Mounting screws (2 places)
3) Fit the front cover and fix it with the mounting screws (2 places).
1 - 16
1. FUNCTIONS AND CONFIGURATION
1.8 Servo system with auxiliary equipment
WARNING
To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the servo amplifier to the protective earth (PE) of the control box.
(1) MR-J2S-100B or less
(a) For 3-phase 200V to 230V or 1-phase 230V
(Note 2)
Power supply
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
Reference
Section 12.2.2
Section 12.2.2
MR Configurator
(Servo configuration software)
Section 12.1.8
Options and auxiliary equipment Reference
Regenerative option
Cables
Section 12.1.1
Section 12.2.1
Power factor improving reactor Section 12.2.3
No-fuse breaker
(NFB) or fuse
Servo amplifier
Servo system controller or preceding axis servo amplifier
CN1B
To CN1A
Magnetic contactor
(MC) To CN1B
Subsequent axis servo amplifier
CN1A or
Termination connector
Power factor improving reactor
(FR-BAL)
CHARGE
To CN3
To CN2
L
1
L
2
L
3
U V W
Personal computer
MR Configurator
(Servo configuration software
MRZJW3-SETUP151E)
(Note 1)
Encoder cable
(Note 1)
Power supply lead
Control circuit terminal block
L
21
L
11
D
P
Regenerative option Servo motor
C
Note 1. The HC-SFS, HC-RFS series have cannon connectors.
2. A 1-phase 230V power supply may be used with the servo amplifier of MR-J2S-70B or less. For 1-phase 230V, connect the power supply to L
1
L
2
and leave L
3
open. Refer to section 1.3 for the power supply specification.
1 - 17
1. FUNCTIONS AND CONFIGURATION
(b) For 1-phase 100V to 120V
(Note 2)
Power supply
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Reference
Section 12.2.2
Section 12.2.2
Section 12.1.8
Options and auxiliary equipment Reference
Regenerative option
Cables
Section 12.1.1
Section 12.2.1
Power factor improving reactor Section 12.2.3
No-fuse breaker
(NFB) or fuse
Servo amplifier
Servo system controller or preceding axis servo amplifier
CN1B
To CN1A
Magnetic contactor
(MC)
To CN1B
Subsequent axis servo amplifier
CN1A or
Termination connector
To CN3
Power factor improving reactor
(FR-BAL)
To CN2
L
1
L
2
CHARGE
U V W
Personal computer
MR Configurator
(Servo configuration software
MRZJW3-SETUP151E)
(Note 1)
Encoder cable
(Note 1)
Power supply lead
Control circuit terminal block
L
21
L
11
D
Regenerative option
P
C
Note 1. The HC-SFS, HC-RFS series have cannon connectors.
2. Refer to section 1.3 for the power supply specification.
Servo motor
1 - 18
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-200B MR-J2S-350B
(Note)
Power supply
No-fuse breaker
(NFB) or fuse
Magnetic contactor
(MC)
Power factor improving reactor
(FA-BAL)
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Reference
Section 12.2.2
Section 12.2.2
Section 12.1.8
Options and auxiliary equipment Reference
Regenerative option
Cables
Section 12.1.1
Section 12.2.1
Power factor improving reactor Section 12.2.3
Servo amplifier
Servo system controller or
Preceding axis servo amplifier
CN1B
L
L
To CN2
11
21
To CN1A
To CN1B
To CN3
Subsequent axis servo amplifier
CN1A or
Termination connector
Personal computer
MR Configurator
(Servo configuration software
MRZJW3-
SETUP151E)
L
1
L
2
L
3
U V W P C
Regenerative option
Note. Refer to section 1.3 for the power supply specification.
1 - 19
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-500B
(Note 2)
Power supply
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Reference
Section 12.2.2
Section 12.2.2
Section 12.1.8
Options and auxiliary equipment Reference
Regenerative option
Cables
Section 12.1.1
Section 12.2.1
Power factor improving reactor Section 12.2.3
No-fuse breaker
(NFB) or fuse
Magnetic contactor
(MC)
Power factor improving reactor
(FA-BAL)
(Note 1) C P
Regenerative option
L
1
L
2
L
3
U
V
W
L
11
L
21
Servo amplifier
To CN1A
To CN1B
To CN3
To CN2
Servo system controller or
Preceding axis servo amplifier
CN1B
Subsequent axis servo amplifier
CN1A or
Termination connector
Personal computer
MR
Configurator
(Servo configuration software
MRZJW3-
SETUP151E)
Note 1. When using the regenerative option, remove the lead wires of the built-in regenerative resistor.
2. Refer to section 1.3 for the power supply specification.
1 - 20
1. FUNCTIONS AND CONFIGURATION
(4) MR-J2S-700B
(Note 2)
Power supply
No-fuse breaker
(NFB) or fuse
Magnetic contactor
(MC)
Power factor improving reactor
(FA-BAL)
L
3
L
2
L
1
L
21
L
11
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Reference
Section 12.2.2
Section 12.2.2
Section 12.1.8
Options and auxiliary equipment Reference
Regenerative option
Cables
Section 12.1.1
Section 12.2.1
Power factor improving reactor Section 12.2.3
Servo system controller or
Preceding axis servo amplifier
CN1B
Servo amplifier
To CN1A
To CN1B
To CN3
Subsequent axis servo amplifier
CN1A or
Termination connector
Personal computer
MR
Configurator
(Servo configuration software
MRZJW3-
SETUP151E)
To CN2
U
V
W
C P
(Note 1) Regenerative option
Note 1. When using the regenerative option, remove the lead wires of the built-in regenerative resistor.
2. Refer to section 1.3 for the power supply specification.
1 - 21
1. FUNCTIONS AND CONFIGURATION
(5) MR-J2S-11KB or more
(Note 3)
Power supply
No-fuse breaker(NFB) or fuse
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
Reference
Section 12.2.2
Section 12.2.2
MR Configurator
(Servo configuration software)
Section 12.1.8
Options and auxiliary equipment Reference
Regenerative option
Cables
Section 12.1.1
Section 12.2.1
Power factor improving reactor Section 12.2.3
Power factor improving DC reactor
Personal computer
Section 12.2.4
MR Configurator
(Servo configuration software
MRZJW3-SETUP151E)
Magnetic contactor
(MC)
(Note 2)
Power factor improving reactor
(FR-BAL)
L
21
L
11
L
3
L
2
L
1
To CN3
MITSUBISHI
Analog monitor
To CN4
To CN1A
To CN1B
Servo system controller or
Preceding axis servo amplifier
CN1B
Subsequent axis servo amplifier
CN1A or
Terminal connector
Forced stop etc.
To CON2
(Note 1) BW
BV
BU
U V W
C
To CN2
Regenerative option
P
(Note 2)
Power factor improving
DC reactor (FR-BEL)
Servo motor
HA-LFS series
Note 1. There is no BW when the HA-LFS 11K2 is used.
2. Use either the FR-BAL or FR-BEL power factor improving reactor.
3. Refer to section 1.3 for the power supply specification.
1 - 22
2. INSTALLATION
2. INSTALLATION
CAUTION
Stacking in excess of the limited number of products is not allowed.
Install the equipment on incombustible material. Installing them directly or close to combustibles will lead to a fire.
Install the equipment in a load-bearing place in accordance with this Instruction
Manual.
Do not get on or put heavy load on the equipment to prevent injury.
Use the equipment within the specified environmental condition range. (For the environmental conditions, refer to section 1.3.)
Provide an adequate protection to prevent screws, metallic detritus and other conductive matter or oil and other combustible matter from entering the servo amplifier.
Do not block the intake/exhaust ports of the servo amplifier. Otherwise, a fault may occur.
Do not subject the servo amplifier to drop impact or shock loads as they are precision equipment.
Do not install or operate a faulty servo amplifier.
When the product has been stored for an extended period of time, consult
Mitsubishi.
When treating the servo amplifier, be careful about the edged parts such as the corners of the servo amplifier.
2.1 Environmental conditions
Ambient
Environment temperature
In [ ] 0 to 55 (non-freezing) operation [ ] 32 to 131 (non-freezing)
In storage
[ ]
[ ]
20 to 65 (non-freezing)
4 to 149 (non-freezing)
Ambient humidity
Ambience
Altitude
Vibration
Conditions
In operation
In storage
90%RH or less (non-condensing)
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m (3280 ft) above sea level
[m/s
2
] 5.9 [m/s
2
] or less
[ft/s
2
] 19.4 [ft/s
2
] or less
2 - 1
2. INSTALLATION
2.2 Installation direction and clearances
CAUTION
The equipment must be installed in the specified direction. Otherwise, a fault may occur.
Leave specified clearances between the servo amplifier and control box inside walls or other equipment.
(1) Installation of one servo amplifier
Control box Control box
40mm
(1.6 in.) or more
Servo amplifier
10mm
(0.4 in.) or more
10mm
(0.4 in.) or more
Wiring clearance
70mm
(2.8 in.)
Top
Bottom
40mm
(1.6 in.) or more
2 - 2
2. INSTALLATION
(2) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the internal surface of the control box, and install a cooling fan to prevent the internal temperature of the control box from exceeding the environmental conditions.
Control box
100mm
(4.0 in.) or more
Servo amplifier
10mm
(0.4 in.) or more
30mm
(1.2 in.) or more
30mm
(1.2 in.) or more
40mm
(1.6 in.) or more
(3) Others
When using heat generating equipment such as the regenerative option, install them with full consideration of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
2.3 Keep out foreign materials
(1) When installing the unit in a control box, prevent drill chips and wire fragments from entering the servo amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control box or a cooling fan installed on the ceiling.
(3) When installing the control box in a place where there are much toxic gas, dirt and dust, conduct an air purge (force clean air into the control box from outside to make the internal pressure higher than the external pressure) to prevent such materials from entering the control box.
2 - 3
2. INSTALLATION
2.4 Cable stress
(1) The way of clamping the cable must be fully examined so that flexing stress and cable's own weight stress are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, brake) supplied with the servo motor, and flex the optional encoder cable or the power supply and brake wiring cables. Use the optional encoder cable within the flexing life range. Use the power supply and brake wiring cables within the flexing life of the cables.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner or stamped by workers or vehicles.
(4) For installation on a machine where the servo motor will move, the flexing radius should be made as large as possible. Refer to section 11.4 for the flexing life.
2 - 4
3. SIGNALS AND WIRING
3. SIGNALS AND WIRING
WARNING
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
Ground the servo amplifier and the servo motor securely.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, you may get an electric shock.
The cables should not be damaged, stressed excessively, loaded heavily, or pinched. Otherwise, you may get an electric shock.
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may misoperate, resulting in injury.
Connect cables to correct terminals to prevent a burst, fault, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay designed for control output should be fitted in the specified direction. Otherwise, the signal is not output due to a fault, disabling the forced stop(EM1) and other protective circuits.
Servo amplifier
COM
(24VDC)
Control output signal
RA
Servo amplifier
COM
(DC24V)
Control output signal
RA
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be given to electronic equipment used near the servo amplifier.
Do not install a power capacitor, surge suppressor or radio noise filter (FR-BIF option) with the power line of the servo motor.
When using the regenerative resistor, switch power off with the alarm signal.
Otherwise, a transistor fault or the like may overheat the regenerative resistor, causing a fire.
Do not modify the equipment.
During power-on, do not open or close the motor power line. Otherwise, a malfunction or faulty may occur.
POINT
CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to a failure. Connect them correctly.
3 - 1
3. SIGNALS AND WIRING
3.1 Connection example of control signal system
POINT
Refer to section 3.5 for the connection of the power supply system and to section 3.6 for connection with the servo motor.
3.1.1 MR-J2S-700B or less
(Note 9)
MR Configurator
(Servo configuration software)
Servo system controller
(Note 10, 14)
Bus cable (Option)
(Note 4)
Personal computer
15m(49.2ft) or less
Servo amplifier
CN3
(Note 5, 8)
(Note 5)
CN1A
CN3
13 MBR
5 COM
10 VDD
20 EM1
3 SG
6 LA
16 LAR
7 LB
17 LBR
8 LZ
18 LZR
4 MO1
1 LG
14 MO2
11 LG
Plate SD
10m(32.81ft) or less
RA1
(Note 2,6)
Magnetic brake interlock
When using the forced stop (EM1) or magnetic brake interlock (MBR), make sure to connect it.
(Note 3,4,7)
Forced stop
A
A
10k
10k
2m(6.56ft) or less
Encoder A-phase pulse
(differential line driver)
Encoder B-phase pulse
(differential line driver)
Encoder Z-phase pulse
(differential line driver)
Control common
Analog monitor output
Max. 1mA
Reading in both directions
(Note15)
Cable clamp
(Option)
(Note 5) SW1
CN1B
Setting: 0 (Note 1)
(Note 10, 14)
Bus cable
(Option)
MR-J2S-B
CN1A
(2 axis)
(Note 11)
SW1
CN1B
Setting: 1
MR-J2S-B
CN1A
(3 axis)
(Note 11)
SW1
CN1B
Setting: 2
(Note 13)
MR-A-TM
MR-J2S-B
CN1A
(n axis)
SW1
(Note 11)
CN1B
Setting: n 1
(Note 12) n 1 to 8
3 - 2
3. SIGNALS AND WIRING
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the servo amplifier to the protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output signals, disabling the forced stop (EM1) and other protective circuits.
3. If the controller does not have a forced stop function, always install a forced stop switch (Normally closed).
4. When a personal computer is connected for use of the test operation mode, always use the maintenance junction card (MR-
J2CN3TM) to enable the use of the forced stop (EM1). (Refer to section 12.1.6)
5. CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to a fault.
6. The sum of currents that flow in the external relays should be 80mA max.
7. When starting operation, always turn on the forced stop (EM1). (Normally closed contacts) By setting “0001” in parameter
No.23, the forced stop (EM1) can be made invalid.
8. When connecting the personal computer together with analog monitor outputs 1, 2, use the maintenance junction card (MR-
J2CN3TM). (Refer to section 12.1.3.)
9. Use MRZJW3-SETUP151E.
10. Use the bus cable at the overall distance of 30m(98.4ft) or less. In addition, to improve noise immunity, it is recommended to use a cable clamp and data line filters (three or four filters connected in series) near the connector outlet.
11. The wiring of the second and subsequent axes is omitted.
12. Up to eight axes (n 1 to 8) may be connected. The MR-J2S- B/MR-J2-03B5 servo amplifier may be connected on the same bus.
13. Always insert the termination connector (MR-A-TM) into CN1B of the servo amplifier located at the termination.
14. The bus cable used with the SSCNET depends on the preceding or subsequent controller or servo amplifier connected. Refer to the following table and choose the bus cable.
MR-J2S- B MR-J2-03B5
QD75M
Motion controller
Q172CPU(N)
Q173CPU(N)
A motion
MR-J2S- B MR-J2-03B5
Maintenance junction card
MR-J2HBUS M
Q172J2BCBL M(-B)
Q173J2B CBL M
MR-J2HBUS M-A
MR-J2HBUS M
15. When the A1SD75M (AD75M) is used as the controller, encoder pulses may not be output depending on the software version of the controller. For details, refer to the A1SD75M (AD75M) Manual.
3 - 3
3. SIGNALS AND WIRING
3.1.2 MR-J2S-11KB or more
(Note 7)
MR Configurator
(Servo configuration software)
Servo system controller
(Note 8, 12)
Bus cable (Option)
Cable clamp
(Option)
Personal computer
(Note 8, 12)
Bus cable
(Option)
15m(49.2ft) or less
Servo amplifier
(Note 4)
CN3
6
16
7
17
LA
LAR
LB
LBR
Encoder A-phase pulse
(differential line driver)
Encoder B-phase pulse
(differential line driver)
8 LZ
18 LZR
Encoder Z-phase pulse
(differential line driver)
1 LG
Plate SD
10m(32.81ft) or less
CN3
CON2
2 EM1
(Note 3, 6)
Forced stop
(Note 4)
CN1A
1
4
SG
DB
(Note 2, 5)
Dynamic brake
RA1 interlock
3 MBR RA2
Magnetic brake interlock
18 COM
15 VDD
CN4
1
2
4
MO1
MO2
LG
A
A
When using the forced stop (EM1), magnetic brake interlock (MBR) or dynamic brake interlock (DB), make sure to connect it.
2m(6.56ft) or less
10k
10k Analog monitor
Max. 1mA
Reading in both directions
(Note
13)
(Note 4)
SW1
CN1B
Setting : 0
(Note 1)
MR-J2S-B
CN1A (Note 9)
SW1
CN1B
Setting : 1
MR-J2S-B
CN1A (Note 9)
SW1
CN1B
Setting : 2
(Note 11)
MR-A-TM
MR-J2S-B
CN1A (Note 9)
SW1
CN1B
Setting: n-1
(Note 10) n= 1 to 8
3 - 4
3. SIGNALS AND WIRING
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the base unit to the protective earth
(PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the interface unit will be faulty and will not output signals, disabling the forced stop and other protective circuits.
3. If the controller does not have a forced stop (EM1) function, always install a forced stop switch (Normally closed).
4. CN1A, CN1B, and CN3 have the same shape. Wrong connection of the connectors will lead to a fault.
5. The sum of currents that flow in the external relays should be 80mA max.
6. When starting operation, always turn on the forced stop (EM1). (Normally closed contacts) By setting “0001” in DRU parameter
No.23 of the drive unit, the forced stop (EM1) can be made invalid.
7. Use MRZJW3-SETUP151E.
8. Use the bus cable at the overall distance of 30m(98.4ft) or less. In addition, to improve noise immunity, it is recommended to use a cable clamp and data line filters (three or four filters connected in series) near the connector outlet.
9. The wiring of the second and subsequent axes is omitted.
10. Up to eight axes (n 1 to 8) may be connected. The MR-J2S- B/MR-J2-03B5 servo amplifier may be connected on the same bus.
11. Always insert the termination connector (MR-A-TM) into CN1B of the interface unit located at the termination.
12. The bus cable used with the SSCNET depends on the preceding or subsequent controller or servo amplifier connected. Refer to the following table and choose the bus cable.
MR-J2S- B MR-J2-03B5
QD75M
Motion controller
Q172CPU(N)
Q173CPU(N)
A motion
MR-J2S- B MR-J2-03B5
Maintenance junction card
MR-J2HBUS M
Q172J2BCBL M(-B)
Q173J2B CBL M
MR-J2HBUS M-A
MR-J2HBUS M
13. When the A1SD75M (AD75M) is used as the controller, encoder pulses may not be output depending on the software version of the controller. For details, refer to the A1SD75M (AD75M) Manual.
3 - 5
3. SIGNALS AND WIRING
3.2 I/O signals
3.2.1 Connectors and signal arrangements
POINT
The pin configurations of the connectors are as viewed from the cable connector wiring section.
(1) MR-J2S-700B or less
CN1A
4
TD
6
2
RD
8
10
1
LG
12
RD*
3
5
LG
7
EMG
9
18
BT
20
14
TD*
16
11
LG
13
15
LG
17
EMG*
19
MITSUBISHI
MELSERVO-J2
CN1B
4
TD
6
2
RD
8
10
1
LG
3
5
LG
7
EMG
9
BT
12
RD*
11
LG
13
14
TD*
16
15
LG
17
18
EMG*
19
20
CN2
2
LG
4
1
LG
3
12
LG
14
11
LG
13
6
MD
8
10
5
7
MR
9
BAT
P5
15
16
MDR
18
17
MRR
19
20
P5
P5
The connector frames are
connected with the PE (earth)
terminal inside the servo amplifier.
CN3
2
RXD
4
MO1
6
LA
1
LG
3
SG
5
COM
11
12
LG
TXD
13
14
MO2
MBR
15
16
7
LAR
17
8
LB
18
LBR
LZ
9
LZR
19
10 20
VDD EM1
3 - 6
3. SIGNALS AND WIRING
(2) MR-J2S-11KB or more
CN1A
Same as the one of the
MR-J2S-700B or less.
CN1B
Same as the one of the
MR-J2S-700B or less.
CN2
2
LG
4
1
LG
3
12
LG
14
11
LG
13
6
MD
8
10
5 15
16
7
MR
MDR
18
9
P5
BAT
20
17
MRR
19
P5
P5
CHARGE
CN4
1
2
MO1
MO2
4 LG
CN3
6
LA
8
LZ
10
2
RXD
4
1
LG
3
12
TXD
14
11
LG
13
5
7
LB
9
15
16
LAR
18
17
LBR
LZR
19
20
MITSUBISHI
The connector frames are
connected with the PE (earth)
terminal inside the servo amplifier.
CON2
1
2
SG
EM1
4
3
MBR
DB
5
6
15
VDD
17
19
14
16
18
COM
7 20
8 21
9 22
10 23
11 24
12 25
13 26
3 - 7
3. SIGNALS AND WIRING
3.2.2 Signal explanations
For the I/O interfaces (symbols in I/O column in the table), refer to section 3.4.2.
(1) Connector applications
Connector
CN1A
CN1B
CN2
CN3
(Note)
(Note)
CN4
Name
Connector for bus cable from preceding axis.
Connector for bus cable to next axis
Encoder connector
Communication connector
(I/O signal connector)
Analog monitor output connector
CON2 IO signal connector
Note. These connectors are exclusive to the MR-J2S-11KB or more.
Function/Application
Used for connection with the controller or preceding-axis servo amplifier.
Used for connection with the next-axis servo amplifier or for connection of the termination connector.
Used for connection with the servo motor encoder.
Used for connection with the personal computer.
Serves as an I/O signal connector when the personal computer is not used.
Used to output analog monitor 1 (MO1) and analog monitor
2 (MO2).
Used to input a forced stop and output the dynamic brake interlock(DB), the electromagnetic brake interlock
(2) I/O signals
(a) Input signal
Signal
Forced stop
(b) Output signals
Electromagnetic brake interlock
Dynamic brake interlock
Signal
Encoder A-phase pulse
(Differential line driver)
Encoder B-phase pulse
(Differential line driver)
Encoder Z-phase pulse
(Differential line driver)
Analog monitor 1
Analog monitor 2
Symbol
MBR
DB
LA
LAR
LB
LBR
LZ
LZR
MO1
MO2
CN3
8
CN3
18
CN3
4
CN3
14
CN3
6
CN3
16
CN3
7
CN3
17
Connector Pin
No.
7kW or less
11kW or more
CN3
13
CON2
3
CON2
4
CN3
6
CN3
16
CN3
7
CN3
17
CN3
8
CN3
18
CN4
1
CN4
2
Function/Application
In the servo-off or alarm status, MBR turns off.
When using this signal, set 1 in the parameter No. 2.
When the dynamic brake is operated, DB turns off.
Outputs pulses per servo motor revolution set in parameter
No.38 in the differential line driver system. In CCW rotation of the servo motor, the encoder B-phase pulse lags the encoder A-phase pulse by a phase angle of /2.
The zero-phase signal of the encoder is output in the differential line driver system.
Used to output the data set in parameter No.22 to across
MO1-LG in terms of voltage. Resolution 10 bits
Used to output the data set in parameter No.22 to across
MO2-LG in terms of voltage. Resolution 10 bits
I/O Division
DO-1
DO-1
DO-2
DO-2
Analog output
Analog output
(c) Power supply
Symbol
EM1
Connector Pin
No.
7kW or less
11kW or more
CN3
20
CON2
2
Function/Application
Turn EM1 off (open EM1 common) to bring the motor to a forced stop state, in which the base circuit is shut off and the dynamic brake is operated.
Turn EM1 on (short EM1 common) in the forced stop state to reset that state.
I/O Division
DI-1
Internal power output for interface
Power input for digital interface
Common for digital interface
Shield
Signal
Control common
Symbol
VDD
COM
SG
LG
SD
Connector Pin
No.
7kW or less
11kW or more
Function/Application
CN3
10
CN3
5
CN3
3
CN3
1
11
CON2
15
CON2
18
CON2
1
CN4
4
Driver power output terminal for digital interface.
Used to output 24V 10% to across VDD-COM. Connect with COM.
Permissible current: 80mA
Driver power input terminal for digital interface.
Used to input 24VDC (200mA or more) for input interface.
Connect with VDD.
Common terminal to VDD and COM. Pins are connected internally.
Separated from LG.
Common terminal to MO1 and MO2.
Plate Plate Connect the external conductor of the shield cable.
3 - 8
3. SIGNALS AND WIRING
3.3 Alarm occurrence timing chart
CAUTION
When an alarm has occurred, remove its cause, make sure that the operation signal is not being input, ensure safety, and reset the alarm before restarting operation.
As soon as an alarm occurs, make the Servo off status and interrupt the main circuit power.
When an alarm occurs in the servo amplifier, the base circuit is shut off and the servo motor is coated to a stop. Switch off the main circuit power supply in the external sequence. To deactivate the alarm, power the control circuit off, then on or give the error reset or CPU reset command from the servo system controller. However, the alarm cannot be deactivated unless its cause is removed.
(Note)
Main circuit
Control circuit power ON
OFF
Base circuit
ON
OFF
Dynamic brake
Servo-on command
(from controller)
Valid
Invalid
ON
OFF
Brake operation
Power off
Brake operation
Power on
Alarm NO YES NO
1s
Reset command
(from controller)
ON
OFF
50ms or more
Alarm occurs. Remove cause of trouble.
Note. Switch off the main circuit power as soon as an alarm occurs.
YES
60ms or more
NO
(1) Overcurrent, overload 1 or overload 2
If operation is repeated by switching control circuit power off, then on to reset the overcurrent (32), overload 1 (50) or overload 2 (51) alarm after its occurrence, without removing its cause, the servo amplifier and servo motor may become faulty due to temperature rise. Securely remove the cause of the alarm and also allow about 30 minutes for cooling before resuming operation.
(2) Regenerative alarm
If operation is repeated by switching control circuit power off, then on to reset the regenerative (30) alarm after its occurrence, the external regenerative resistor will generate heat, resulting in an accident.
(3) Instantaneous power failure
Undervoltage (10) occurs when the input power is in either of the following statuses.
A power failure of the control circuit power supply continues for 60ms or longer and the control circuit is not completely off.
The bus voltage dropped to 200VDC or less for the MR-J2S B, or to 158VDC or less for the MR-J2S
B1.
3 - 9
3. SIGNALS AND WIRING
3.4 Interfaces
3.4.1 Common line
The following diagram shows the power supply and its common line.
To conform to the EMC directive, refer to the EMC Installation Guide lines (IB(NA)67310).
Servo amplifier
24VDC
VDD
COM MBR
RA
DI-1
EM1
SG
<Isolated>
Servo motor
M
LA .etc
LAR
.etc
LG
SD
MO1
MO2
LG
TXD
RXD
Differential line driver output
35mA max.
Analog monitor output
RS-232C
CN2
Servo motor encoder
MR
MRR
LG
SD
Ground
3 - 10
3. SIGNALS AND WIRING
3.4.2 Detailed description of the interfaces
This section gives the details of the I/O signal interfaces (refer to I/O Division in the table) indicated in section 3.2.2.
Refer to this section and connect the interfaces with the external equipment.
(1) Digital input interface DI-1
Give a signal with a relay or open collector transistor.
Servo amplifier
24VDC
VDD
R: Approx. 4.7
COM
For a transistor
Approx. 5mA
EM1
TR
V
CES
1.0V
I
CEO
100 A
Switch
SG
(2) Digital output interface DO-1
A lamp, relay or photocoupler can be driven. Provide a diode (D) for an inductive load, or an inrush current suppressing resistor (R) for a lamp load. (Permissible current: 40mA or less, inrush current:
100mA or less)
(a) Inductive load
Servo amplifier
24VDC
VDD
COM
Load
MBR
SG If the diode is not connected as shown, the servo amplifier will be damaged.
3 - 11
3. SIGNALS AND WIRING
(b) Lamp load
Servo amplifier
24VDC
VDD
COM
MBR
SG
R
(3) Encoder pulse output DO-2
(Differential line driver system)
1) Interface
Max. output current: 35mA
Servo amplifier
LA
(LB, LZ)
Am26LS32 or equivalent
150
Servo amplifier
LA
(LB, LZ)
LAR
(LBR, LZR)
LG
SD
LAR
(LBR, LZR)
SD
100
High-speed photocoupler
2) Pulse output
Servo motor CCW rotation
LA
LAR
LB
LBR
/2
LZ
LZR
T
400 s or more
Time cycle (T) is determined by the settings of parameter No.33 and 38.
3 - 12
3. SIGNALS AND WIRING
(4) Analog output
Output voltage : 10V
Max. output current :1mA
Resolution :10bit
Servo amplifier
MO1
(MO2)
LG
10k
Reading in one or both directions
1mA meter
A
SD
3 - 13
3. SIGNALS AND WIRING
3.5 Power line circuit
CAUTION
Always connect a magnetic contactor (MC) between the main circuit power supply and L
1 , L
2 , and L
3 of the servo amplifier, and configure the wiring to be able to shut down the power supply on the side of the servo amplifier’s power supply. If a magnetic contactor (MC) is not connected, continuous flow of a large current may cause a fire when the servo amplifier malfunctions.
Switch power off at detection of an alarm. Otherwise, a regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
POINT
For the power line circuit of the MR-J2S-11KB to MR-J2S-22KB, refer to section 3.12 where the power line circuit is shown together with the servo motor connection diagram.
3.5.1 Connection example
Wire the power supply/main circuit as shown below so that power is shut off and the servo-on command turned off as soon as an alarm occurs, a servo forced stop is made valid, or a controller forced stop is made valid. A no-fuse breaker (NFB) must be used with the input cables of the power supply.
(1) For 3-phase 200 to 230V power supply
(Note 2)
Alarm
RA1
Controller forced stop
RA2
Forced stop OFF
ON
MC
MC
SK
NFB MC
Power supply
3-phase
200 to 230V
(Note 1)
L
1
L
2
L
3
L
11
L
21
P
P
1
Servo amplifier
Forced stop
VDD
COM
EM1
SG
Note 1. Make sure to connect P
1
-P. (Factory-wired.) When using the power factor improving DC reactor, refer to section 12.2.4.
2. Configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
3 - 14
3. SIGNALS AND WIRING
(2) For 1-phase 100 to 120V or 1-phase 230V power supply
(Note 1)
Alarm
RA1
Controller forced stop
RA2
Forced stop OFF
ON
MC
NFB MC Power supply
1-phase
100 to 120V or
1-phase
230V
L
1
Servo amplifier
L
2
L
3
(Note 2)
L
11
L
21
MC
SK
Forced stop
VDD
COM
EM1
SG
Note 1. Configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
2. Not provided for 1-phase 100 to 120V.
3 - 15
3. SIGNALS AND WIRING
3.5.2 Terminals
The positions and signal arrangements of the terminal blocks change with the capacity of the servo amplifier. Refer to section 10.1.
Symbol
Connection Target
(Application)
Description
L
1
, L
2
, L
3
Main circuit power supply
Supply L
1
, L
2
and L
3
with the following power.
For 1-phase 230V, connect the power supply to L
1
/L
2
and leave L
3
open.
Power supply
Servo amplifier MR-J2S-10B to
70B
MR-J2S-100B to 22K
MR-J2S-10B1 to 40B1
3-phase 200 to 230VAC,
50/60Hz
1-phase 230VAC,
50/60Hz
1-phase 100 to 120VAC,
50/60Hz
L
1
L
L
2
1
L
2
L
3
L
1
L
2
U, V, W
L
11
P
1
, L
21
Servo motor output
Power factor improving DC reactor
Control circuit power supply
Connect to the servo motor power supply terminals (U, V, W). During power-on, do not open or close the motor power line. Otherwise, a malfunction or faulty may occur.
When not using the power factor improving DC reactor, connect P
1
and P.
(Factory-wired.)
When using the power factor improving DC reactor, disconnect the wiring across
P
1
-P and connect the power factor improving DC reactor across P
1
-P.
Refer to section 11.2.4.
Supply the following power to L
11
, L
21
.
Servo amplifier
Power supply
1-phase 200 to 230VAC,
50/60Hz
1-phase 100 to 120VAC,
50/60Hz
MR-J2S-10B to 700B
L
11
L
21
MR-J2S-10B1 to 40B1
L
11
L
21
P, C, D
N
Regenerative option
Return converter
Brake unit
Protective earth (PE)
1) MR-J2S-350B or less
When using servo amplifier built-in regenerative resistor, connect between P and D terminals. (Wired by default)
When using regenerative option, disconnect between P-D terminals and connect regenerative option to P terminal and C terminal.
2) MR-J2S-500B and 700B
MR-J2S-500B and 700B do not have D terminal.
When using servo amplifier built-in regenerative resistor, connect P terminal and C terminal. (Wired by default)
When using regenerative option, disconnect P terminal and C terminal and connect regenerative option to P terminal and C terminal.
Refer to section 12.1.1.
3) MR-J2S-11KB to 22KB
MR-J2S-11KB to 22KB do not have D terminal.
When not using the power supply return converter and the brake unit, make sure to connect the regenerative option to P terminal and C terminal.
Refer to section 12.1.1.
When using return converter/brake unit, connect to P terminal and N terminal.
Do not connect to servo amplifier MR-J2S-200B or less.
For details, refer to section 12.1.2 to 12.1.3.
Connect this terminal to the protective earth (PE) terminals of the servo motor and control box for grounding.
3 - 16
3. SIGNALS AND WIRING
3.5.3 Power-on sequence
(1) Power-on procedure
1) Always wire the power supply as shown in above section 3.5.1 using the magnetic contactor with the main circuit power supply (3-phase 200V: L 1 , L 2 , L 3 , 1-phase 230V: L 1 , L 2 , 1-phase: L 1 L 2 ).
Configure up an external sequence to switch off the magnetic contactor as soon as an alarm occurs.
2) Switch on the control circuit power supply L 11 , L 21 simultaneously with the main circuit power supply or before switching on the main circuit power supply. If the main circuit power supply is not on, the display shows the corresponding warning. However, by switching on the main circuit power supply, the warning disappears and the servo amplifier will operate properly.
3) The servo amplifier can accept the servo-on command within 3s the main circuit power supply is switched on. (Refer to paragraph (2) in this section.)
(2) Timing chart
SON accepted
(3s)
Main circuit
Control circuit
Base circuit
Servo-on command
(from controller) power
ON
OFF
ON
OFF
ON
OFF
60ms 10ms 60ms
(3) Forced stop
CAUTION
Install an forced stop circuit externally to ensure that operation can be stopped and power shut off immediately.
If the controller does not have a forced stop function, make up a circuit that switches off main circuit power as soon as EM1 is turned off at a forced stop. When EM1 is turned off, the dynamic brake is operated to stop the servo motor. At this time, the display shows the servo forced stop warning (E6).
During ordinary operation, do not use forced stop (EM1) to alternate stop and run. The service life of the servo amplifier may be shortened.
Servo amplifier
Forced stop
VDD
COM
EM1
SG
3 - 17
3. SIGNALS AND WIRING
3.6 Connection of servo amplifier and servo motor
3.6.1 Connection instructions
WARNING
Insulate the connections of the power supply terminals to prevent an electric shock.
CAUTION
Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier and servo motor. Otherwise, the servo motor will operate improperly.
Do not connect AC power supply directly to the servo motor. Otherwise, a fault may occur.
POINT
Do not apply the test lead bars or like of a tester directly to the pins of the connectors supplied with the servo motor. Doing so will deform the pins, causing poor contact.
The connection method differs according to the series and capacity of the servo motor and whether or not the servo motor has the electromagnetic brake. Perform wiring in accordance with this section.
(1) For grounding, connect the earth cable of the servo motor to the protective earth (PE) terminal ( ) of the servo amplifier and connect the ground cable of the servo amplifier to the earth via the protective earth of the control box. Do not connect them directly to the protective earth of the control panel.
Control box
Servo amplifier
Servo motor
PE terminal
(2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake.
Always use the power supply designed exclusively for the electromagnetic brake.
3.6.2 Connection diagram
CAUTION
During power-on, do not open or close the motor power line. Otherwise, a malfunction or faulty may occur.
POINT
For the connection diagram of the MR-J2S-11KB to MR-J2S-22KB, refer to section 3.12 where the connection diagram is shown together with the power line circuit.
The following table lists wiring methods according to the servo motor types. Use the connection diagram which conforms to the servo motor used. For cables required for wiring, refer to section 12.2.1. For encoder cable connection, refer to section 12.1.4. For the signal layouts of the connectors, refer to section
3.6.3.
For the servo motor connector, refer to chapter 3 of the Servo Motor Instruction Manual.
3 - 18
3. SIGNALS AND WIRING
Servo motor
HC-KFS053 (B) to 73 (B)
HC-MFS053 (B) to 73 (B)
HC-UFS13 (B) to 73 (B)
HC-SFS121 (B) to 301 (B)
HC-SFS202 (B) to 702 (B)
HC-SFS203 (B) 353 (B)
HC-UFS202 (B) to 502 (B)
HC-RFS353 (B) 503 (B)
HC-SFS81 (B)
HC-SFS52 (B) to 152 (B)
HC-SFS53 (B) to 153 (B)
HC-RFS103 (B) to 203 (B)
HC-UFS72 (B) 152 (B)
Connection diagram
Servo amplifier
U
V
W
U (Red)
V (White)
W (Black)
(Green)
Servo motor
Motor
(Note 1) 24VDC
B1
EM1
B2
To be shut off when servo-off or alarm occurrence
(Note 2)
Electromagnetic brake
CN2
Encoder cable
Encoder
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
Servo amplifier Servo motor
U
V
W
U
V
W
Motor
(Note 1) 24VDC
B1
B2
EM1
To be shut off when servo-off or alarm occurrence
(Note 2)
Electromagnetic brake
CN2
Servo amplifier
Encoder cable
Encoder
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
Servo motor
U
V
W
U
V
W
Motor
(Note 1)
24VDC
B1
B2
EM1
To be shut off when servo-off or alarm occurrence
(Note 2)
Electromagnetic brake
CN2
Encoder cable
Encoder
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
3 - 19
3. SIGNALS AND WIRING
3.6.3 I/O terminals
(1) HC-KFS HC-MFS HC-UFS3000r/min series a
Encoder cable 0.3m (0.98ft.)
With connector 1-172169-9
(Tyco Electronics)
Power supply connector
5557-04R-210
1 3
2 4
View b
Pin
3
4
1
2 b
Signal
U
V
W
(Earth)
Power supply lead
4-AWG19 0.3m (0.98ft.)
Power supply connector (Molex)
Without electromagnetic brake
5557-04R-210 (receptacle)
5556PBTL (Female terminal)
With electromagnetic brake
5557-06R-210 (receptacle)
5556PBTL (Female terminal)
Power supply connector
5557-06R-210
1 4
2 5
3 6
View b
Encoder connector signal arrangement
1
MR
4
MD
7
P5
2 3
MRR BAT
5
MDR
6
8 9
LG SHD
View a
5
6
3
4
Pin
1
2
Signal
U
V
W
(Earth)
(Note) B1
(Note) B2
Note. For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
3 - 20
3. SIGNALS AND WIRING
(2) HC-SFS HC-RFS HC-UFS2000 r/min series a
Encoder connector b
Brake connector c
Power supply connector
Servo motor
HC-SFS81(B)
HC-SFS52(B) to 152(B)
HC-SFS53(B) to 153(B)
HC-SFS121(B) to 301(B)
HC-SFS202(B) to 502 (B)
HC-SFS203(B) 353(B)
HC-UFS72(B) 152(B)
HC-UFS202(B) to 502(B)
Servo motor side connectors
For power supply For encoder
Electromagnetic brake connector
CE05-2A22-
23PD-B
CE05-2A24-
10PD-B
HC-SFS702(B)
HC-RFS103(B) to 203 (B)
CE05-2A32-
17PD-B
CE05-2A22-
23PD-B
HC-RFS353(B) 503(B)
CE05-2A24-
10PD-B
CE05-2A22-
23PD-B
CE05-2A24-
10PD-B
MS3102A20-
29P
The connector for power is shared.
MS3102A10SL-
4P
The connector for power is shared.
MS3102A10SL-
4P
Power supply connector signal arrangement
CE05-2A22-23PD-B CE05-2A24-10PD-B CE05-2A32-17PD-B
Key
F
G
H
E
D
View c
A
C
B
Pin
A
B
C
D
E
F
G
H
Signal
U
V
W
(Earth)
E
F
D
Key
G
View c
(Note) B1
(Note) B2
Note. For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
A
C
B
Encoder connector signal arrangement
MS3102A20-29P
Key
K
J
L
M
H
T
N
A
P
B
C
D
E
S
G
R
F
View a
Pin
A
B
C
D
E
G
H
J
Signal
MD
MDR
MR
MRR
BAT
LG
Pin
R
S
T
K
L
M
N
P
Signal
SD
LG
P5
Pin
A
B
C
D
E
F
G
Signal
U
V
W
(Earth)
(Note)
(Note)
B1
B2
D
C
Key
Note. For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
A
B
Pin
A
B
C
D
Signal
U
V
W
(Earth)
Electromagnetic brake connector signal arrangement
MS3102A10SL-4P
Key
A
View b
B
Pin
A
B
Signal
(Note) B1
(Note) B2
Note. For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
3 - 21
3. SIGNALS AND WIRING
3.7 Servo motor with electromagnetic brake
CAUTION
Configure the electromagnetic brake circuit so that it is activated not only by the interface unit signals but also by a forced stop (EM1).
Contacts must be open when servo-off, when an alarm occurrence and when an electromagnetic brake interlock (MBR).
Servo motor
RA EM1
Circuit must be opened during forced stop (EM1).
24VDC
Electromagnetic brake
The electromagnetic brake is provided for holding purpose and must not be used for ordinary braking.
Before performing the operation, be sure to confirm that the electromagnetic brake operates properly.
POINT
Refer to the Servo Motor Instruction Manual for specifications such as the power supply capacity and operation delay time of the electromagnetic brake.
Note the following when the servo motor equipped with electromagnetic brake is used.
1) Do not share the 24VDC interface power supply between the interface and electromagnetic brake. Always use the power supply designed exclusively for the electromagnetic brake.
2) The brake will operate when the power (24VDC) switches off.
3) Switch off the servo-on command after the servo motor has stopped.
(1) Connection diagram
Servo amplifier
VDD
COM
MBR RA
24VDC
RA
Forced stop
B1
Servo motor
B2
(2) Setting
In parameter No.21 (electromagnetic brake sequence output), set the time delay (Tb) from electromagnetic brake operation to base circuit shut-off at a servo off time as in the timing chart in (3) in this section.
3 - 22
3. SIGNALS AND WIRING
(3) Timing charts
(a) Servo-on command (from controller) ON/OFF
Tb [ms] after the servo-on is switched off, the servo lock is released and the servo motor coasts. If the electromagnetic brake is made valid in the servo lock status, the brake life may be shorter.
Therefore, when using the electromagnetic brake in a vertical lift application or the like, set delay time (Tb) to about the same as the electromagnetic brake operation delay time to prevent a drop.
Servo motor speed 0 r/min
(60ms)
Coasting
Tb
Base circuit
ON
OFF
Electromagnetic brake interlock
(MBR)
(Note 1) ON
OFF
Servo-on command
(from controller)
ON
OFF
Driving instruction
(from controller)
Electromagnetic brake
0 r/min
Release
Activate
(80ms)
(Note 3)
Electromagnetic brake operation delay time
Release delay time and external relay (Note 2)
Note 1. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
2. Electromagnetic brake is released after delaying for the release delay time of electromagnetic brake and operation time of external circuit relay. For the release delay time of electromagnetic brake, refer to the Servo Motor Instruction Manual.
3. After the electromagnetic brake is released, give the operation command from the controller.
(b) Forced stop command (from controller) or forced stop (EM1) ON/OFF
Servo motor speed
Forward rotation
0r/min
(10ms)
ON
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Electromagnetic brake release
(180ms)
Base circuit
OFF
(180ms)
Electromagnetic brake interlock (MBR)
(Note) ON
OFF
Forced stop command
(from controller) or
Forced stop (EM1)
Invalid (ON)
Valid (OFF)
Electromagnetic brake operation delay time
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 23
3. SIGNALS AND WIRING
(c) Alarm occurrence
Servo motor speed
Base circuit
Electromagnetic brake interlock (MBR)
Trouble (ALM)
Forward rotation
0r/min
(10ms)
ON
OFF
(Note) ON
OFF
No (ON)
Yes (OFF)
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Electromagnetic brake operation delay time
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
(d) Both main and control circuit power supplies off
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Servo motor speed
Forward rotation
0r/min
ON
Base circuit
OFF
Electromagnetic brake interlock (MBR)
(Note 2) ON
OFF
Trouble (ALM)
No (ON)
Yes (OFF)
Main circuit
Control circuit power
ON
OFF
(Note 1)
15 to 60ms
Electromagnetic brake operation delay time
(Note 2)
Note 1. Changes with the operating status.
2. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 24
3. SIGNALS AND WIRING
(e) Only main circuit power supply off (control circuit power supply remains on)
Servo motor speed
Forward rotation
0r/min
(Note 1)
15ms or more
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
ON
Base circuit
OFF
Electromagnetic brake interlock (MBR)
(Note 3) ON
OFF
Trouble (ALM)
No (ON)
Yes (OFF)
Electromagnetic brake operation delay time
(Note 2)
Main circuit power supply
ON
OFF
Note 1. Changes with the operating status.
2. When the main circuit power supply is off in a motor stop status, the main circuit off warning (E9) occurs and the trouble (ALM) does not turn off.
3. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 25
3. SIGNALS AND WIRING
3.8 Grounding
WARNING
Ground the servo amplifier and servo motor securely.
To prevent an electric shock, always connect the protective earth (PE) terminal
( ) of the servo amplifier with the protective earth (PE) of the control box.
The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on the wiring and ground cable routing, the servo amplifier may be affected by the switching noise (due to di/dt and dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always ground.
To conform to the EMC Directive, refer to the EMC Installation Guidelines (IB(NA)67310).
Control box
Servo motor
NFB
MC Servo amplifier
L
1
CN2
(Note 1)
Power supply
Encoder
L
2
L
3
L
11
L
21
U
V
W
U
V
W
M
CN1A
(Note 2)
Protective earth (PE)
Outer box
Ensure to connect it to PE terminal of the servo amplifier.
Do not connect it directly to the protective earth of the control panel.
Note 1. For 1-phase 230V, connect the power supply to L
1
L
2
and leave L
3
open.
There is no L
3
for 1-phase 100 to 120V power supply. Refer to section 1.3 for the power supply specification.
2. To reduce the influence of external noise, we recommend you to ground the bus cable near the controller using a cable clamping fixture or to connect three or four data line filters in series.
3 - 26
3. SIGNALS AND WIRING
3.9 Servo amplifier terminal block (TE2) wiring method
POINT
Refer to table 12.1 2) and (4) of section 12.2.1 for the wire sizes used for wiring.
3.9.1 For servo amplifier produced later than January, 2006
(1) Termination of the cables
(a) Solid wire
After the sheath has been stripped, the cable can be used as it is.
Sheath
Core
Approx. 10mm
(b) Twisted wire
1) When the cable is inserted directly
Use the cable after stripping the sheath and twisting the core. At this time, take care to avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder the core as it may cause a contact fault.
2) When the twisted wires are put together using a bar terminal
Use the bar terminal shown below.
Cable Size
[mm
2
] AWG
1.25/1.5
2/2.5
16
14
AI1.5-10BK
AI2.5-10BU
Bar Terminal Type
For 1 cable For 2 cables
AI-TWIN2 1.5-10BK
Crimping Tool Manufacturer
CRIMPFOX ZA 3 Phoenix Contact
Cut the cable running out of bar terminal to less than 0.5 mm
Less than 0.5mm
When using a bar terminal for 2 cables, insert the cables in the direction where the insulation sleeve does not interfere with next pole, and pressure then.
Pressure
Pressure
3 - 27
3. SIGNALS AND WIRING
(2) Connection
(a) When the cable is inserted directly
Insert the cable to the end pressing the button with a small flat-blade screwdriver or the like.
Button
Small flat blade screwdriver or the like
Twisted wire
When removing the short-circuit bar from across P-D, press the buttons of P and D alternately pulling the short-circuit bar. For the installation, insert the bar straight to the end.
(b) When the twisted wires are put together using a bar terminal
Insert a bar terminal with the odd-shaped side of the pressured terminal on the button side.
Bar terminal for one wire or solid wire
Bar terminal for two wires
When two cables are inserted into one opening, a bar terminal for 2 cables is required.
3 - 28
3. SIGNALS AND WIRING
3.9.2 For servo amplifier produced earlier than December, 2005
(1) Termination of the cables
Solid wire: After the sheath has been stripped, the cable can be used as it is.
Approx. 10mm
(0.39inch)
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder the core as it may cause a contact fault.
Alternatively, a bar terminal may be used to put the wires together.
Cable Size
[mm 2 ]
1.25/1.5
2/2.5
AWG
16 AI1.5-10BK
14 AI2.5-10BU
Bar Terminal Type
For 1 cable For 2 cables
AI-TWIN2 1.5-10BK
Crimping Tool Manufacturer
CRIMPFOX ZA 3 or
CRIMPFOX UD 6
Phoenix Contact
(2) Connection
Insert the core of the cable into the opening and tighten the screw with a flat-blade screwdriver so that the cable does not come off. (Tightening torque: 0.3 to 0.4N m(2.7 to 3.5 lb in)) Before inserting the cable into the opening, make sure that the screw of the terminal is fully loose.
When using a cable of 1.5mm
2 or less, two cables may be inserted into one opening.
Flat-blade screwdriver
Tip thickness 0.4 to 0.6mm
Overall width 2.5 to 3.5mm
To loosen.
To tighten.
Cable
Opening
Control circuit terminal block
Use of a flat-blade torque screwdriver is recommended to manage the screw tightening torque. The following table indicates the recommended products of the torque screwdriver for tightening torque management and the flat-blade bit for torque screwdriver. When managing torque with a Phillips bit, please consult us.
Product
Torque screwdriver
Bit for torque screwdriver
Model
N6L TDK
B-30, flat-blade, H3.5 X 73L
Manufacturer/Representative
Nakamura Seisakusho
Shiro Sangyo
3 - 29
3. SIGNALS AND WIRING
3.10 Instructions for the 3M connector
When fabricating an encoder cable or the like, securely connect the shielded external conductor of the cable to the ground plate as shown in this section and fix it to the connector shell.
External conductor Sheath
Strip the sheath.
Screw
Core
External conductor
Sheath
Pull back the external conductor to cover the sheath
Cable
Ground plate
Screw
3 - 30
3. SIGNALS AND WIRING
3.11 Control axis selection
POINT
The control axis number set to SW1 should be the same as the one set to the servo system controller.
Use the axis select switch (SW1) to set the control axis number for the servo. If the same numbers are set to different control axes in a single communication system, the system will not operate properly. The control axes may be set independently of the bus cable connection sequence.
Set the switch to "F" when executing the test operation mode using MR Configurator (servo configuration software).
Axis select switch (SW1)
3
5
6
7
8 9
A
B
D
2
1 0
F
E
9
A
B
7
8
5
6
E
F
C
D
No.
2
3
0
1
4
Description
Axis 1
Axis 2
Axis 3
Axis 4
Axis 5
Axis 6
Axis 7
Axis 8
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Test operation mode or when machine analyzer is used
(Refer to section 6.1.2)
3 - 31
3. SIGNALS AND WIRING
3.12 Power line circuit of the MR-J2S-11KB to MR-J2S-22KB
CAUTION
Always connect a magnetic contactor (MC) between the main circuit power supply and L1, L2, and L3 of the servo amplifier, and configure the wiring to be able to shut down the power supply on the side of the servo amplifier’s power supply. If a magnetic contactor (MC) is not connected, continuous flow of a large current may cause a fire when the servo amplifier malfunctions.
Switch power off at detection of an alarm. Otherwise, a regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
During power-on, do not open or close the motor power line. Otherwise, a malfunction or faulty may occur.
POINT
The power-on sequence is the same as in section 3.5.3.
3 - 32
3. SIGNALS AND WIRING
3.12.1 Connection example
Wire the power supply/main circuit as shown below so that power is shut off and the servo-on signal turned off as soon as an alarm occurs, a servo forced stop is made valid, a controller forced stop, or a servo motor thermal relay alarm is made valid. A no-fuse breaker (NFB) must be used with the input cables of the power supply.
Servo motor thermal relay
RA3
(Note 1)
Alarm
RA1
Controller forced stop
RA2
Forced stop OFF ON
MC
MC
SK
3-phase
200 to 230V
NFB
Forced stop
MC
(Note 4)
L
1
L
2
L
3
L
11
L
21
P
P
1
Servo amplifier (Note 2)
Dynamic break Servo motor
HA-LFS series
U
V
W
U
V
W
M
CN2
MR-JHSCBL M cable
Encoder
Cooling fan
BU
BV
BW (Note 3)
VDD
COM
EM1
SG
24VDC power supply
OHS1
RA3
OHS2 Servo motor thermal relay
Note 1. Configure up the power supply circuit which switches off the magnetic contactor after detection of alarm occurrence on the controller side.
2. When using the external dynamic break, refer to section 12.1.4.
3. Cooling fan power supply of the HA-LFS11K2 servo motor is 1-phase. Power supply specification of the cooling fan is different from that of the servo amplifier. Therefore, separate power supply is required.
4. Always connect P
1
and P. (Factory-wired.) When using the power factor improving DC reactor, refer to section 12.2.4.
3 - 33
3. SIGNALS AND WIRING
3.12.2 Servo amplifier terminals
The positions and signal arrangements of the terminal blocks change with the capacity of the servo amplifier. Refer to section 10.1.
Symbol
L
1
, L
2
, L
3
U, V, W
L
11
, L
21
P, C
N
Connection Target
(Application)
Description
Main circuit power supply Supply L
1
, L
2
and L
3
with three-phase 200 to 230VAC, 50/60Hz power.
Servo motor output Connect to the servo motor power supply terminals (U, V, W).
Control circuit power supply Supply L
11
and L
21
with single-phase 200 to 230VAC power.
Regenerative option
Return converter
Brake unit
The servo amplifier built-in regenerative resistor is not connected at the time of shipment.
When using the regenerative option, wire it across P-C.
Refer to section 12.1.1 for details.
When using the return converter or brake unit, connect it across P-N.
Refer to sections 12.1.2 and 12.1.3 for details.
P
1
, P
Protective earth (PE)
Connect this terminal to the protective earth (PE) terminals of the servo motor and control box for grounding.
Power factor improving DC reactors
P
1
-P are connected before shipment. When connecting a power factor improving
DC reactor, remove the short bar across P
1
-P. Refer to section 12.2.4 for details.
3 - 34
3. SIGNALS AND WIRING
3.12.3 Servo motor terminals
Terminal box Encoder connector
MS3102A20-29P
Terminal box inside (HA-LFS601 701M 11K2)
Thermal sensor terminal block
(OHS1 OHS2) M4
Encoder connector signal arrangement
MS3102A20-29P
Key
L
K
J
H
M
T
N
A
P
B
C
D
S R E
G
F
A
B
C
D
E
F
G
H
Pin Signal
MD
MDR
MR
MRR
BAT
LG
J
Pin Signal
N
P
K
L
M
R
S
T
SHD
LG
P5
Motor power supply terminal block
(U V W) M6 screw
Cooling fan terminal block
(BU BV) M4 screw
Earth terminal
M6 screw
Encoder connector
MS3102A20-29P
Terminal block signal arrangement
OHS1OHS2
U V W
BU BV
3 - 35
3. SIGNALS AND WIRING
Terminal box inside (HA-LFS801 12K1 11K1M 15K1M 15K2 22K2)
Cooling fan terminal block (BU BV BW)
M4 screw
Thermal sensor terminal block (OHS1 OHS2)
M4 screw
Motor power supply terminal block
(U V W) M8 screw
Earth terminal M6 screw
Encoder connector
MS3102A20-29
Terminal box inside (HA-LFS15K1 20K1 22K1M 25K1)
Encoder connector
MS3102A20-29P
Terminal block signal arrangement
BU BV BW OHS1OHS2
U V W
Motor power supply terminal block
(U V W) M8 screw
Earth terminal
M6 screw
Cooling fan terminal block
(BU BV BW) M4 screw
Earth terminal
M6 screw
Thermal sensor terminal block
(OHS1 OHS2) M4 screw
Terminal block signal arrangement
U V W
BU BV BW OHS1 OHS2
3 - 36
3. SIGNALS AND WIRING
Signal Name
Power supply
Cooling fan
Abbreviation Description
U V W Connect to the motor output terminals (U, V, W) of the servo amplifier.
Supply power which satisfies the following specifications.
(Note)
BU BV BW
11K2
Servo motor
HA-LFS601, 701M,
HA-LFS801 12K1,
11K1M, 15K1M,
15K2, 22K2
HA-LFS-15K1, 20K1,
22K1M
HA-LFS25K1
Voltage division
200V class
Voltage/frequency
1-phase 200 to 220VAC
50Hz
1-phase 200 to 230VAC
60Hz
3-phase 200 to 230VAC
50Hz/60Hz
Power consumption
[W]
42(50Hz)
54(60Hz)
62(50Hz)
76(60Hz)
Rated current
[A]
0.21(50Hz)
0.25(60Hz)
0.18(50Hz)
0.17(60Hz)
65(50Hz)
85(60Hz)
120(50Hz)
175(60Hz)
0.20(50Hz)
0.22(60Hz)
0.65(50Hz)
0.80(60Hz)
Motor thermal relay OHS1 OHS2 OHS1-OHS2 are opened when heat is generated to an abnormal temperature.
Earth terminal
For grounding, connect to the earth of the control box via the earth terminal of the servo amplifier.
Note. There is no BW when the HA-LFS11K2 is used.
3 - 37
3. SIGNALS AND WIRING
MEMO
3 - 38
4. OPERATION AND DISPLAY
4. OPERATION AND DISPLAY
4.1 When switching power on for the first time
Before starting operation, check the following.
(1) Wiring
(a) A correct power supply is connected to the power input terminals (L 1 , L 2 , L 3 , L 11 , L 21 ) of the servo amplifier.
(b) The servo motor power supply terminals (U, V, W) of the servo amplifier match in phase with the power input terminals (U, V, W) of the servo motor.
(c) The servo motor power supply terminals (U, V, W) of the servo amplifier are not shorted to the power input terminals (L 1 , L 2 , L 3 ) of the servo motor.
(d) The earth terminal of the servo motor is connected to the PE terminal of the servo amplifier.
(e) Note the following when using the regenerative option, brake unit or power regeneration converter.
1) For the MR-J2S-350B or less, the lead has been removed from across D-P of the control circuit terminal block, and twisted cables are used for its wiring.
2) For the MR-J2S-500B MR-J2S-700B, the lead has been removed from across P-C of the servo amplifier built-in regenerative resistor, and twisted cables are used for its wiring.
(f) 24VDC or higher voltages are not applied to the pins of connector CN3.
(g) SD and SG of connector CN3 are not shorted.
(h) The wiring cables are free from excessive force.
(i) CN1A should be connected with the bus cable connected to the servo system controller or preceding axis servo amplifier, and CN1B should connected with the bus cable connected to the subsequent axis servo amplifier or with the termination connector (MR-A-TM.)
(2) Axis number
The axis number setting of SW1 should be the same as that of the servo system controller. (Refer to section 3.11.)
(3) Parameters
On the servo system controller screen or using the MR Configurator (servo configuration software), make sure that correct values have been set in the parameters.
(4) Environment
Signal cables and power cables are not shorted by wire offcuts, metallic dust or the like.
(5) Machine
(a) The screws in the servo motor installation part and shaft-to-machine connection are tight.
(b) The servo motor and the machine connected with the servo motor can be operated.
4 - 1
4. OPERATION AND DISPLAY
4.2 Start up
WARNING
CAUTION
Do not operate the switches with wet hands. You may get an electric shock.
Do not operate the controller with the front cover removed. High-voltage terminals and charging area exposed and you may get an electric shock.
During power-on or operation, do not open the front cover. You may get an electric shock.
Before starting operation, check the parameters. Some machines may perform unexpected operation.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.) with the servo amplifier heat sink, regenerative resistor, servo motor, etc.since they may be hot while power is on or for some time after power-off. Their temperatures may be high and you may get burnt or a parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
Connect the servo motor with a machine after confirming that the servo motor operates properly alone.
(1) Power on
When the main and control circuit power supplies are switched on, "b1" (for the first axis) appears on the servo amplifier display.
In the absolute position detection system, first power-on results in the absolute position lost (25) alarm and the servo system cannot be switched on. This is not a failure and takes place due to the uncharged capacitor in the encoder.
The alarm can be deactivated by keeping power on for a few minutes in the alarm status and then switching power off once and on again.
Also in the absolute position detection system, if power is switched on at the servo motor speed of
500r/min or higher, position mismatch may occur due to external force or the like. Power must therefore be switched on when the servo motor is at a stop.
(2) Parameter setting
Set the parameters according to the structure and specifications of the machine. Refer to chapter 5 for the parameter definitions.
Parameter No.
Name
7
8
9
Rotation direction setting
Auto tuning
Servo response
Setting Description
0
Increase in positioning address rotates the motor in the CCW direction.
1 Used.
5 Slow response (initial value) is selected.
After setting the above parameters, switch power off once. Then switch power on again to make the set parameter values valid.
4 - 2
4. OPERATION AND DISPLAY
(3) Servo-on
Switch the servo-on in the following procedure.
1) Switch on main circuit/control circuit power supply.
2) The controller transmits the servo-on command.
When placed in the servo-on status, the servo amplifier is ready to operate and the servo motor is locked.
(4) Home position return
Always perform home position return before starting positioning operation.
(5) Stop
If any of the following situations occurs, the servo amplifier suspends the running of the servo motor and brings it to a stop.
When the servo motor is equipped with an electromagnetic brake, refer to section 3.7.
Servo system controller
Servo amplifier
Operation/command
Servo off command
Forced stop command
Alarm occurrence
Forced stop
(EM1) OFF
Stopping condition
The base circuit is shut off and the servo motor coasts.
The base circuit is shut off and the dynamic brake operates to bring the servo motor to stop. The controller forced stop warning
(E7) occurs.
The base circuit is shut off and the dynamic brake operates to bring the servo motor to stop.
The base circuit is shut off and the dynamic brake operates to bring the servo motor to stop. The servo forced stop warning
(E6) occurs.
4 - 3
4. OPERATION AND DISPLAY
4.3 Servo amplifier display
On the servo amplifier display (two-digit, seven-segment display), check the status of communication with the servo system controller at power-on, check the axis number, and diagnose a fault at occurrence of an alarm.
(1) Display sequence
Servo amplifier power ON
Waiting for servo system controller power to switch ON
Servo system controller power ON
Initial data communication with servo system controller
During forced stop and forced stop
(Note)
Ready ON
Ready OFF/servo OFF
When alarm occurs, alarm code appears.
(Note)
Servo ON
Ready ON/servo OFF or
Forced stop and forced stop reset
(Note) Ready ON/servo ON
Ordinary operation
Servo system controller power OFF
Servo system controller power ON
Note. The right-hand segments of b1, c1 and d1
indicate the axis number.
(Axis 1 in this example)
4 - 4
4. OPERATION AND DISPLAY
(2) Indication list
Indication Status Description
(Note 1)
(Note 1)
(Note 1)
(Note 2)
(Note 3)
AA
Ab
AC
Ad
AE b# d#
C#
**
88 b0.
Initializing
Initializing
Initializing
Initializing
Initialize completion
Ready OFF
Servo ON
Servo OFF
Alarm Warning
CPU error
Power to the servo system controller was switched off during power-on of the servo amplifier.
The servo amplifier was switched on when power to the servo system controller is off.
The axis No. set to the servo system controller does not match the axis No.
set with the axis setting switch (SW1) of the servo amplifier.
A servo amplifier fault occurred or an error took place in communication with the servo system controller. In this case, the indication changes.
"Ab" "AC" "Ad" "Ab"
The servo system controller is faulty.
Communication started between the servo system controller and servo amplifier.
The initial parameters from the servo system controller were received.
Initial data communication with the servo system controller was completed.
The ready off signal from the servo system controller was received.
The ready off signal from the servo system controller was received.
The ready off signal from the servo system controller was received.
The alarm No./warning No. that occurred is displayed. (Refer to section 9.1.)
Initial data communication with the servo system controller was completed.
JOG operation, positioning operation, programmed operation, DO forced output.
(Note 1) b#.
d#.
c#.
(Note 3)
Test operation mode
Motor-less operation
Note 1. # denotes any of numerals 0 to 8 and what it means is listed below.
#
4
5
6
2
3
0
1
7
8
Description
Set to the test operation mode.
First axis
Second axis
Third axis
Fourth axis
Fifth axis
Sixth axis
Seventh axis
Eighth axis
2. ** indicates the warning/alarm No.
3. Requires the MR Configurator (servo configuration software).
4 - 5
4. OPERATION AND DISPLAY
4.4 Test operation mode
CAUTION
The test operation mode is designed for servo operation confirmation and not for machine operation confirmation. Do not use this mode with the machine. Always use the servo motor alone.
If an operation fault occurred, use the forced stop (EM1) to make a stop.
By using a personal computer and the MR Configurator (servo configuration software MRZJW3-
SETUP121E), you can execute jog operation, positioning operation, motor-less operation and DO forced output without connecting the motion controller.
When executing the test operation at start up, confirm that the servo motor operates normally at the slowest speed.
(1) Test operation mode
(a) Jog operation
Jog operation can be performed without using the servo system controller. Use this operation with the forced stop reset. This operation may be used independently of whether the servo is on or off and whether the servo system controller is connected or not.
Exercise control on the jog operation screen of the MR Configurator (servo configuration software).
1) Operation pattern
Item
Speed [r/min]
Acceleration/deceleration time constant [ms]
Initial value
200
1000
Setting range
0 to max. speed
1 to 20000
2) Operation method
Operation
Forward rotation start
Reverse rotation start
Stop
Screen control
Click the "Forward" button.
Click the "Reverse" button.
Click the "Stop" button.
(b) Positioning operation
Positioning operation can be performed without using the servo system controller. Use this operation with the forced stop reset. This operation may be used independently of whether the servo is on or off and whether the servo system controller is connected or not.
Exercise control on the positioning operation screen of the MR Configurator (servo configuration software).
1) Operation pattern
Item
Travel [pulse]
Speed [r/min]
Acceleration/deceleration time constant [ms]
Initial value
100000
200
1000
Setting range
0 to 9999999
0 to max. speed
1 to 50000
2) Operation method
Operation
Forward rotation start
Reverse rotation start
Pause
Screen control
Click the "Forward" button.
Click the "Reverse" button.
Click the "Pause" button.
4 - 6
4. OPERATION AND DISPLAY
(c) Program operation
Positioning operation can be performed in two or more operation patterns combined, without using the servo system controller. Use this operation with the forced stop reset. This operation may be used independently of whether the servo is on or off and whether the servo system controller is connected or not.
Exercise control on the programmed operation screen of the MR Configurator (servo configuration software). For full information, refer to the MR Configurator (Servo Configuration Software)
Installation Guide.
Operation
Start
Stop
Screen Control
Click the "Start" button.
Click the "Reset" button.
(d) Motorless operation
POINT
Motor-less operation may be used with the MR Configurator (servo configuration software). Usually, however, use motor-less operation which is available by making the servo system controller parameter setting.
Without connecting the servo motor, output signals or status displays can be provided in response to the servo system controller commands as if the servo motor is actually running. This operation may be used to check the servo system controller sequence. Use this operation with the forced stop reset. Use this operation with the servo amplifier connected to the servo system controller.
Exercise control on the motor-less operation screen of the MR Configurator (servo configuration software).
1) Load conditions
Load torque
Load Item
Load inertia moment ratio
Condition
0
Same as servo motor inertia moment
2) Alarms
The following alarms and warning do not occur. However, the other alarms and warnings occur as when the servo motor is connected.
Encoder error 1 (16)
Encoder error 2 (20)
Absolute position erasure (25)
Battery cable breakage warning (92)
Battery warning (9F)
(e) Output signal (DO) forced output
Output signals can be switched on/off forcibly independently of the servo status. Use this function for output signal wiring check, etc.
Exercise control on the DO forced output screen of the MR Configurator (servo configuration software).
4 - 7
4. OPERATION AND DISPLAY
(2) Configuration
Configuration should be as in section 3.1. Always install a forced stop switch to enable a stop at occurrence of an alarm.
(3) Operation procedure
(a) Jog operation, positioning operation, program operation, DO forced output.
1) Switch power off.
2) Set SW1 to “F”.
When SW1 is set to the axis number and operation is performed by the servo system controller, the test operation mode screen is displayed on the personal computer, but no function is performed.
3) Switch servo amplifier power on.
When initialization is over, the display shows the following screen.
Decimal point flickers.
4) Perform operation with the personal computer.
(b) Motor-less operation
1) Switch off the servo amplifier.
2) Perform motor-less operation with the personal computer.
The display shows the following screen.
Decimal point flickers.
4 - 8
5. PARAMETERS
5. PARAMETERS
CAUTION
Never adjust or change the parameter values extremely as it will make operation instable.
POINT
When the servo amplifier is connected with the servo system controller, the parameters are set to the values of the servo system controller. Switching power off, then on makes the values set on the MR Configurator (servo configuration software) invalid and the servo system controller values valid.
In the manufacturer setting parameters, do not set any values other than the initial values.
Setting may not be made to some parameters and ranges depending on the model or version of the servo system controller. For details, refer to the servo system controller user's manual.
5.1 Parameter write inhibit
POINT
When setting the parameter values from the servo system controller, the parameter No. 40 setting need not be changed.
In this servo amplifier, the parameters are classified into the basic parameters (No. 1 to 11), adjustment parameters (No. 12 to 26) and expansion parameters (No. 27 to 40) according to their safety aspects and frequencies of use. The values of the basic parameters may be set/changed by the customer, but those of the adjustment and expansion parameters cannot. When in-depth adjustment such as gain adjustment is required, change the parameter No. 40 value to make all parameters accessible. Parameter No. 40 is made valid by switching power off, then on after setting its value.
The following table indicates the parameters which are enabled for reference and write by parameter No.
40 setting.
Setting Operation Operation from controller
Operation from MR Configurator
(servo configuration software)
0000(initial value)
000A
000C
000E
000F
100E
Reference
Write
Reference
Write
Reference
Write
Reference
Write
Reference
Write
Reference
Write
Parameter No. 1 to 75
Parameter No. 1 to 75
Parameter No. 1 to 75
Parameter No. 1 to 75
Parameter No. 1 to 75
Parameter No. 1 to 75
Parameter No. 1 to 11 40
Parameter No. 40
Parameter No. 1 to 40
Parameter No. 1 to 11 40
Parameter No. 1 to 40
Parameter No. 1 to 75
Parameter No. 1 to 40
Parameter No. 40
5.2 Lists
POINT
For any parameter whose symbol is preceded by*, set the parameter value and switch power off once, then switch it on again to make that parameter setting valid. The parameter is set when communication between the servo system controller and servo amplifier is established (b* is displayed). After that, power the servo amplifier off once and then on again.
5 - 1
5. PARAMETERS
(1) Item list
Classification
No. Symbol
5
6
3
4
1 *AMS Amplifier setting
2 *REG Regenerative resistor
For manufacturer setting by servo system controller
Automatically set from the servo system controller
7
8
9
10
11
12
13
14
15
16
17
*FBP
*POL Rotation direction selection
ATU
RSP
TLP
TLN
GD2
PG1
VG1
PG2
VG2
VIC
18 NCH Machine resonance suppression filter 1 (Notch filter)
19
20
21 MBR Electromagnetic brake sequence output
22 MOD Analog monitor output
23 *OP1 Optional function 1
24 *OP2 Optional function 2
25
26
27
28
29
30
31
FFC
INP
LPF
MO1
MO2
Feed forward gain
In-position range
Low-pass filter/adaptive vibration suppression control
For manufacturer setting
Analog monitor 1 offset
Analog monitor 2 offset
For manufacturer setting
ZSP Zero speed
ERZ
Feedback pulse number
Auto tuning
Servo response
Forward rotation torque limit (Note 2)
Reverse rotation torque limit (Note 2)
Ratio of load inertia to servo motor inertia (load inertia ratio)
Position control gain 1
Speed control gain 1
Position control gain 2
Speed control gain 2
Speed integral compensation
Error excessive alarm level
Name
32 OP5 Optional function 5
33 *OP6 Optional function 6
34
35
36
VPI
VDC
PI-PID control switch-over position droop
For manufacturer setting
Speed differential compensation
37 For manufacturer setting
38 *ENR Encoder pulses output
39 For manufacturer setting
40 *BLK Parameter write inhibit (Note 2)
(Note 1)
Initial
Value
0000
0000
0080
000
1
0
0
Unit
0001
7kW or less: 0005
11kW or more: 0002
300
300
7.0
7kW or less: 35
11kW or more: 19
7kW or less: 177
11kW or more: 96
7kW or less: 35
11kW or more: 19
7kW or less: 817
11kW or more:
455
7kW or less:48
11kW or more:91
0000
0
100
0
0001
0000
0000
0000
0
0
0
%
% times rad/s rad/s rad/s rad/s ms
% pulse ms mV mV
0001
50
80 r/min
(Note 3)
0.025rev
0000
0000
0
0
980 pulse
0010
4000 pulse/rev
0
0000
Customer setting
Note 1. Factory settings of the servo amplifier. Connecting it with the servo system controller and switching power on changes them to the settings of the servo system controller.
2. Setting and changing cannot be made from the peripheral software of the motion controller.
3. The setting unit of 0.025rev applies for the servo amplifier of software version B1 or later. For the amplifier of software version older than B1, the setting unit of 0.1rev is applied.
5 - 2
5. PARAMETERS
Classification
No. Symbol Name
45
46
47
41
42
43
44
For manufacturer setting
48
49 *CDP Gain changing selection
50
51
CDS
CDT
Gain changing condition
Gain changing time constant
52 GD2B Ratio of load inertia moment to servo motor inertia moment 2
53 PG2B Position control gain 2 changing ratio
54 VG2B Speed control gain 2 changing ratio
67
68
69
70
71
63
64
65
66
72
73
74
75
55 VICB Speed integral compensation changing ratio
56 For manufacturer setting
57
58
59
60 *OPC Optional function C
61
62
NH2 Machine resonance suppression filter 2
For manufacturer setting
Note. Depends on parameter No. 49 setting.
0
0
0
0
0
400
100
1
1
0
0
0
0
100
0000
0000
0000
0000
0000
0000
0000
0
0000
10
1
7.0
100
100
Initial
Value
500
0000
0111
20
50
0
0
Unit
(Note) ms time
%
%
%
Customer setting
5 - 3
5. PARAMETERS
(2) Details list
Classification
No.
Symbol Name and Function
1 *AMS Amplifier setting
Used to select the absolute position detection.
0 0 0
Initial
Value
0000
Absolute position detection selection
0: Invalid (Used in incremental system.)
1: Valid (Used in absolute position
detection system.)
2 *REG Regenerative resistor
Used to select the regenerative option used.
0 0
Regenerative selection option
00: Regenerative option is not used with 7kW or less servo amplifier (The built-in regenerative resistor is used. However, the MR-J2S-10B does not have a built-in regenerative resistor and therefore cannot use it.)
Supplied regenerative resistors or regenerative
option is used with 11k to 22kW amplifier
01: FR-RC, FR-BU2, FR-CV
05: MR-RB32
08: MR-RB30
09: MR-RB50 (Cooling fan is required)
0B: MR-RB31
0C: MR-RB51 (Cooling fan is required)
0E: When regenerative resistors or regenerative option supplied to 11k to 22kW are cooled by cooling fans to increase capability
10: MR-RB032
11: MR-RB12
The MR-RB65, 66 and 67 are regenerative options that have encased the GRZG400-2 ,
GRZG400-1 and GRZG400-0.8 , respectively.
When using any of these regenerative options, make the same parameter setting as when using the GRZG400-2 , GRZG400-1 or
GRZG400-0.8 (supplied regenerative resistors or regenerative option is used with 11k to 22kW servo amplifier).
Select the external dynamic brake.
0: Invalid
1: Valid
Select "1" when using the external dynamic brake with the MR-J2S-11KB to 22KB.
0000
POINT
Wrong setting may cause the regenerative option to burn.
If the regenerative option selected is not for use with the servo amplifier, parameter error (37) occurs.
3
4
5
For manufacturer setting by servo system controller
Automatically set from the servo system controller
0080
0000
1
5 - 4
Unit
Setting
Range
Refer to name and function column.
Refer to name and function column.
5. PARAMETERS
Classification
No. Symbol
6 *FBP
Name and Function
Feedback pulse number
Set the number of pulses per revolution in the controller side command unit. Information on the motor such as the feedback pulse value, present position, droop pulses and within-one-revolution position are derived from the values converted into the number of pulses set here.
Initial
Value
0
Setting Number of feedback pulses
0
1
6
16384
8192
32768
7 131072
255 Depending on the number of motor resolution pulses.
POINT
If the number of pulses set exceeds the actual motor resolution, the motor resolution is set automatically.
7 *POL Rotation direction selection
Used to select the rotation direction of the servo motor.
0: Forward rotation (CCW) with the increase of the positioning address.
1: Reverse rotation (CW) with the increase of the positioning address.
0
Unit
Setting
Range
Refer to name and function column.
Refer to name and function column.
CCW
8
CW
ATU Auto tuning
Used to select the gain adjustment mode of auto tuning.
0 0 0
Gain adjustment mode selection
(For details, refer to section 6.1.1.)
Set value
Gain adjustment mode
Description
0 Interpolation mode Fixes position control gain 1 (parameter
No. 13).
1
3
4
Auto tuning mode 1 Ordinary auto tuning.
Auto tuning mode 2 Fixes the load inertia moment ratio set in parameter No. 12.
Response level setting can be changed.
Manual mode1 Simple manual adjustment.
2 Manual mode 2 Manual adjustment of all gains.
0001 Refer to name and function column.
5 - 5
5. PARAMETERS
Classification
No. Symbol
9
Name and Function
RSP Servo response
Used to select the response of auto tuning.
10
11
12
13
Initial
Value
7kW or less
:0005
0 0 0
Response level selection
Set value
3
4
1
2
5
Response level
Low response
Machine resonance frequency guideline
15Hz
20Hz
25Hz
30Hz
35Hz
8
9
6
7
Middle
response
45Hz
55Hz
70Hz
85Hz
C
D
A
B
105Hz
130Hz
160Hz
200Hz
E
F
High response
240Hz
300Hz
If the machine hunts or generates large gear sound, decrease the set value.
To improve performance, e.g. shorten the settling time, increase the set value.
11kW or more
:0002
TLP Forward rotation torque limit
Assume that the rated torque is 100[%].
Used to limit the torque in the forward rotation driving mode and reverse rotation regenerative mode.
In other than the test operation mode on the MR Configurator (servo configuration software), the torque limit value on the servo system controller side is made valid.
TLN Reverse rotation torque limit
Assume that the rated torque is 100[%].
Used to limit the torque in the forward rotation driving mode and forward rotation regenerative mode.
In other than the test operation mode on the MR Configurator (servo configuration software), the torque limit value on the servo system controller side is made valid.
GD2 Ratio of load inertia to servo motor inertia (load inertia ratio)
Used to set the ratio of the load inertia (inertia moment) to the inertia moment of the servo motor shaft. When auto tuning mode 1 and interpolation mode is selected, the result of auto tuning is automatically used. (Refer to section 6.1.1)
PG1 Position control gain 1
Used to set the gain of position loop 1. Increase the gain to improve track ability performance in response to the position command.
When auto turning mode 1,2 is selected, the result of auto turning is automatically used.
300
300
7.0
7kW or less:35
11kW or more:19
Unit
%
% times rad/s
Setting
Range
Refer to name and function column.
0 to
500
0 to
500
0.0
to
300.0
4 to
2000
5 - 6
5. PARAMETERS
Classification
No. Symbol
14
15
16
17
Name and Function
VG1 Speed control gain 1
Normally this parameter setting need not be changed. Higher setting increases the response level but is liable to generate vibration and/or noise.
When auto tuning mode 1,2 and interpolation mode is selected, the result of auto tuning is automatically used.
PG2 Position control gain 2
Used to set the gain of the position loop.
Set this parameter to increase position response to load disturbance.
Higher setting increases the response level but is liable to generate vibration and/or noise.
When auto tuning mode 1 2, manual mode and interpolation mode is selected, the result of auto tuning is automatically used.
VG2 Speed control gain 2
Set this parameter when vibration occurs on machines of low rigidity or large backlash.
Higher setting increases the response level but is liable to generate vibration and/or noise.
When auto tuning mode 1 2 and interpolation mode is selected, the result of auto tuning is automatically used.
VIC Speed integral compensation
Used to set the constant of integral compensation.
When auto tuning mode 1 2 and interpolation mode is selected, the result of auto tuning is automatically used.
Initial
Value
7kW or less:177
11kW or more:96
7kW or less:35
11kW or more:19
7kW or less:817
11kW or more:455
7kW or less:48
11kW or more:91
0000 18 NCH Machine resonance suppression filter 1 (Notch filter)
Used to select the machine resonance suppression filter.
(Refer to section 7.2.)
0
Unit rad/s rad/s rad/s ms
Setting
Range
20 to
5000
1 to
1000
20 to
20000
1 to
1000
Refer to name and function column.
19
Notch frequency selection
Setting Frequency
00
01
Invalid
4500
02
03
04
05
2250
1500
1125
900
06
07
750
642.9
Setting
08
09
0A
0B
0C
0D
0E
0F
Frequency
562.5
500
450
409.1
375
346.2
321.4
300
Setting
10
11
12
13
14
15
16
17
Frequency
281.3
264.7
250
236.8
225
214.3
204.5
195.7
Setting
18
19
1A
1B
1C
1D
1E
1F
Frequency
187.5
180
173.1
166.7
160.1
155.2
150
145.2
Notch depth selection
Setting Depth
0
1
2
3
Deep to
Shallow
Gain
40dB
14dB
8dB
4dB
FFC Feed forward gain
Set the feed forward gain. When the setting is 100%, the droop pulses during operation at constant speed are nearly zero. However, sudden acceleration/deceleration will increase the overshoot. As a guideline, when the feed forward gain setting is 100%, set 1s or more as the acceleration/deceleration time constant up to the rated speed.
0 % 0 to
100
5 - 7
5. PARAMETERS
Classification
No. Symbol
20
Name and Function
INP In-position range
Used to set the droop pulse range in which the in-position (INP) will be output to the controller. Make setting in the feedback pulse unit
(parameter No. 6).
For example, when you want to set 10 m in the conditions that the ball screw is direct coupled, the lead is 10mm, and the feedback pulses are 8192 pulses/rev (parameter No. 6 : 1), set "8" as indicated by the following expression.
10 10
10 10
6
3
8192 8.192
8
21 MBR Electromagnetic brake sequence output
Used to set a time delay (Tb) from when the electromagnetic brake interlock signal (MBR) turns off until the base circuit is shut off.
22 MOD Analog monitor output
Used to select the signal provided to the analog monitor
(MO1) analog monitor (MO2).
(Refer to section 5.3.)
0 0
Initial
Value
100
0
0001
Unit pulse
Setting
Range
0 to
50000 ms 0 to
1000
Refer to name and function column.
9
A
7
8
B
4
5
6
Setting
2
3
0
1
Analog monitor1 (MO1) Analog monitor2 (MO2)
Servo motor speed ( 8V/max. speed)
Torque ( 8V/max. torque) (Note)
Servo motor speed ( 8V/max. speed)
Torque ( 8V/max. torque) (Note)
Current command ( 8V/max. current command)
Speed command ( 8/max. speed)
Droop pulses ( 10V/128 pulses)
Droop pulses ( 10V/2048 pulses)
Droop pulses ( 10V/8192 pulses)
Droop pulses ( 10V/32768 pulses)
Droop pulses ( 10V/131072 pulses)
Bus voltage ( 8V/400V)
Note. 8V is outputted at the maximum torque.
23 *OP1 Optional function 1
Used to make the servo forced stop function invalid.
0 0 0
Servo forced stop selection
0: Valid (Use the forced stop (EM1).)
1: Invalid (Do not use the forced stop (EM1).)
Automatically switched on internally
0000 Refer to name and function column.
5 - 8
5. PARAMETERS
Classification
No. Symbol Name and Function
24 *OP2 Optional function 2
Used to select slight vibration suppression control and motor-less operation
0 0
Slight vibration suppression control selection
Made valid when auto tuning selection is set to "0002" in parameter No.8.
Used to suppress vibration at a stop.
0: Invalid
1: Valid
Motor-less operation selection
0: Invalid
1: Makes motor-less operation valid.
When motor-less operation is made valid, signal output or
status display can be provided as if the servo motor is
running actually in response to the servo system controller
command, without the servo motor being connected.
Motor-less operation is performed as in the motor-less
operation using the MR Configurator (servo configuration
software). (Refer to (d), (1) of section 4.4.)
25 LPF Low-pass filter/adaptive vibration suppression control
Used to select the low-pass filter and adaptive vibration suppression control. (Refer to chapter 7.)
0
Initial
Value
0000
0000
26
Low-pass filter selection
0: Valid (Automatic adjustment)
1: Invalid
When you choose "valid", the filter of the handwidth represented by the following expression is set automatically.
For 1kW or less
VG2 setting 10
2 (1 GD2 setting 0.1)
[H z ]
For 2kW or more
VG2 setting 5
2 (1 GD2 setting 0.1)
[H z ]
Adaptive vibration suppression control selection
0: Invalid
1: Valid
Machine resonance frequency is always detected
and the filter is generated in response to resonance to
suppress machine vibration.
2: Held
The characteristics of the filter generated so far are
held, and detection of machine resonance is stopped.
Adaptive vibration suppression control sensitivity selection
Used to select the sensitivity of machine resonance detection.
0: Normal
1: Large sensitivity
For manufacturer setting
Do not change this value by any means.
0
Unit
Setting
Range
Refer to name and function column.
Refer to name and function column.
5 - 9
5. PARAMETERS
Classification
No. Symbol
27
Name and Function
MO1 Analog monitor 1 offset
Used to set the offset voltage of the analog monitor1 (MO1) output.
28 MO2 Analog monitor 2 offset
Used to set the offset voltage of the analog monitor2 (MO2) output.
29
30
For manufacturer setting
Do not change this value by any means.
ZSP Zero speed
Used to set the output range of the zero speed signal (ZSP).
Initial
Value
0
0
0001
Unit mV mV
50
31
32
ERZ Error excessive alarm level
Used to set the output range of the error excessive alarm.
Note: The setting unit of 0.025rev applies for the servo amplifier of software version B1 or later. For the amplifier of software version older than B1, the setting unit of 0.1rev is applied.
OP5 Optional function 5
Used to select PI-PID control switch-over.
0 0 0
PI-PID control switch over selection
0: PI control is always valid.
1: Droop-based switching is valid in position
control mode (refer to parameter No. 34).
2: PID control is always valid.
33 *OP6 Option function 6
Used to select the serial communication baud rate, serial communication response delay time setting and encoder pulse output setting.
0
Serial communication baud rate selection
0: 9600[bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
Serial communication response delay time
0: Invalid
1: Valid, replay sent in 800 s or more
Encoder pulse output setting selection
(refer to parameter No.38)
0: Pulse output designation
1: Division ratio setting
80
0000
0000 r/min
(Note)
0.025rev
0 to
10000
1 to
1000
Refer to name and function column.
Refer to name and function column.
Setting
Range
999 to
999
999 to
999
35
36
34 VPI PI-PID control switch-over position droop
Used to set the position droop value (number of pulses) at which PI control is switched over to PID control.
Set "0001" in parameter No. 32 to make this function valid.
For manufacturer setting
Do not change this value by any means.
VDC Speed differential compensation
Used to set the differential compensation.
37 For manufacturer setting
Do not change this value by any means.
5 - 10
0
0
980
0010 pulse 0 to
50000
0 to
1000
5. PARAMETERS
Classification
No. Symbol Name and Function
38 *ENR Encoder pulses output
Used to set the encoder pulses (A-phase, B-phase) output by the servo amplifier.
Set the value 4 times greater than the A-phase and B-phase pulses.
You can use parameter No. 33 to choose the pulse output setting or output division ratio setting.
The number of A-phase and B-phase pulses actually output is 1/4 times greater than the preset number of pulses.
The maximum output frequency is 1.3Mpps (after multiplication by
4). Use this parameter within this range.
For pulse output designation
Set "0 " (initial value) in parameter No. 33.
Set the number of pulses per servo motor revolution.
Pulse output set value [pulses/rev]
At the setting of 5600, for example, the actually output A-phase and B-phase pulses are as indicated below.
A-phase and B-phase pulses output
5600
4
1400[pulse]
39
40 *BLK
For output division ratio setting
Set "1 " in parameter No. 33.
The number of pulses per servo motor revolution is divided by the set value.
Pulse output
Resolution per servo motor revolution
Set value
[pulses/rev]
At the setting of 8, for example, the actually output A-phase and
B-phase pulses are as indicated below.
A-phase and B-phase pulses output
131072
8
1
4
4096[pulse]
For manufacturer setting
Do not change this value by any means.
Parameter write inhibit
Initial
Value
Unit
4000 pulse/rev
Setting
Range
1 to
65535
0
0000
Setting
0000
(initial value)
000A
Operation
Reference
Write
Operation from
Parameter No. 1 to 75 controller
Operation from
MR Configurator
(servo configuration)
Parameter No. 1 to 11 40
Parameter No. 40
Refer to name and function column.
000C
Reference
Write
Reference
Parameter No. 1 to 75
Parameter No. 1 to 75
Write
000E
000F
100E
Reference
Write
Reference
Write
Reference
Write
Parameter No. 1 to 75
Parameter No. 1 to 75
Parameter No. 1 to 75
Parameter No. 1 to 40
Parameter No. 1 to 11 40
Parameter No. 1 to 40
Parameter No. 1 to 75
Parameter No. 1 to 40
Parameter No. 40
5 - 11
5. PARAMETERS
Classification
No. Symbol Name and Function
44
45
46
41
42
43
For manufacturer setting
Do not change this value by any means.
47
48
49 *CDP Gain changing selection
Select the gain changing condition. (Refer to section 7.5)
0 0 0
Gain changing selection
Under any of the following conditions, the gains change on the basis of the parameter No. 52 to 55 settings.
0: Invalid
1: Control instructions from a controller.
2: Command frequency (Parameter No.50
setting)
3: Droop pulse value (Parameter No.50 setting)
4: Servo motor speed (Parameter No.50 setting)
Initial
Value
500
0000
0111
20
50
0
0
0
0000
50
51
CDS Gain changing condition
Used to set the value of gain changing condition (command frequency, droop pulses, servo motor speed) selected in parameter
No. 49. The set value unit changes with the changing condition item.
(Refer to section 7.5)
CDT Gain changing time constant
Used to set the time constant at which the gains will change in response to the conditions set in parameters No. PB26 and PB27.
(Refer to section 7.6.)
52 GD2B Ratio of load inertia moment to servo motor inertia moment 2
Used to set the ratio of load inertia moment to servo motor inertia moment when gain changing is valid.
53 PG2B Position control gain 2 changing ratio
Used to set the ratio of changing the position control gain 2 when gain changing is valid.
Made valid when auto tuning is invalid.
54 VG2B Speed control gain 2 changing ratio
Used to set the ratio of changing the speed control gain 2 when gain changing is valid.
Made valid when auto tuning is invalid.
55 VICB Speed integral compensation changing ratio
Used to set the ratio of changing the speed integral compensation when gain changing is valid. Made valid when auto tuning is invalid.
56
57
For manufacturer setting
Do not change this value by any means.
58
59
10
1
7.0
100
100
100
0000
0000
0000
0000
Unit kpps pulse r/min ms times
%
%
%
Setting
Range
Refer to
Name and function column.
0 to
9999
0 to
100
0 to
300.0
10 to
200
10 to
200
50 to
1000
5 - 12
5. PARAMETERS
Classification
No. Symbol Name and Function
60 *OPC Optional function C
Used to select the encoder pulse output direction.
0 0 0
Set value
0
Encoder pulse output phase changing
Changes the phases of A, B-phase encoder pulses output .
Servo motor rotation direction
CCW CW
A-phase
B-phase
A-phase
B-phase
1
A-phase
B-phase
A-phase
B-phase
Initial
Value
0000
61 NH2 Machine resonance suppression filter 2
Used to selection the machine resonance suppression filter 2. (Refer to section 7.2.)
0
0000
Notch frequency selection
Set "00" when you have set adaptive vibration suppression control to be "valid" or "held"
(parameter No. 25: 1 or 2 ).
Setting Frequency
04
05
06
07
00
01
02
03
Invalid
4500
2250
1500
1125
900
750
642.9
Setting
08
09
0A
0B
0C
0D
0E
0F
Frequency
562.5
500
450
409.1
375
346.2
321.4
300
Setting
10
11
12
13
14
15
16
17
Frequency
281.3
264.7
250
236.8
225
214.3
204.5
195.7
Setting Frequency
18
19
1A
1B
1C
1D
1E
1F
187.5
180
173.1
166.7
160.1
155.2
150
145.2
Notch depth selection
Setting
0
1
2
3
Depth
Deep to
Shallow
Gain
40dB
14dB
8dB
4dB
Unit
Setting
Range
Refer to
Name and function column.
Refer to
Name and function column.
5 - 13
5. PARAMETERS
Classification
No. Symbol
69
70
71
72
65
66
67
68
62
63
64
73
74
75
Name and Function
For manufacturer setting
Do not change this value by any means.
0
0
0
0
0
0
1
1
0
0
0
Initial
Value
0000
400
100
Unit
Setting
Range
5.3 Analog monitor
The servo status can be output to two channels in terms of voltage. The servo status can be monitored using an ammeter.
(1) Setting
Change the following digits of parameter No. 22.
Parameter No. 22
0 0
Analog monitor 2(MO2) output selection
(Signal output to across MO2-LG)
Analog monitor 1(MO1) output selection
(Signal output to across MO1-LG)
Parameters No. 27 and 28 can be used to set the offset voltages to the analog output voltages. The setting range is between 999 and 999mV.
Setting range [mV] Parameter No.
27
28
Description
Used to set the offset voltage for the analog monitor 1(MO) output.
Used to set the offset voltage for the analog monitor 2(MO2) output.
999 to 999
5 - 14
5. PARAMETERS
(2) Setting description
The servo amplifier is factory-set to output the servo motor speed to analog monitor (MO1) and the torque to analog monitor (MO2). The setting can be changed as listed below by changing the parameter No. 22 (Analog monitor output) value.
Refer to (3) in this section for the measurement point.
Setting Output item
0 Servo motor speed
Description
CCW direction
8[V]
Setting
6
Output item
Droop pulses
( 10V/128pulse)
Description
10[V]
CCW direction
Max. speed
0 Max. speed
128[pulse]
0
128[pulse]
1 Torque (Note)
8[V]
CW direction
8[V]
Driving in CCW direction
Max. torque
0 Max. torque
7 Droop pulses
( 10V/2048pulse)
CW direction
10[V]
10[V]
CCW direction
2048[pulse]
0 2048[pulse]
2 Servo motor speed
Driving in CW direction
8[V]
CW direction
8[V]
CCW direction
8 Droop pulses
( 10V/8192pulse)
CW direction
10[V]
10[V]
CCW direction
8192[pulse]
0 8192[pulse]
Max. speed 0 Max. speed
3 Torque (Note)
Driving in
CW direction
8[V]
Driving in
CCW direction
9 Droop pulses
( 10V/32768pulse)
CW direction
10[V]
10[V]
CCW direction
32768[pulse]
0 32768[pulse]
Max. torque 0 Max. torque
4 Current command
8[V]
Max. current
command
CCW direction
5 Speed command
0 Max. current
command
CW direction
8[V]
CCW direction
8[V]
Max. speed
0 Max. speed
A Droop pulses
( 10V/131072pulse)
CW direction
10[V]
10[V]
CCW direction
131072[pulse]
0
131072[pulse]
B Bus voltage
CW direction
10[V]
8[V]
0 400[V]
CW direction
Note. Outputs 8V at the maximum torque.
8[V]
5 - 15
5. PARAMETERS
(3) Analog monitor block diagram
5 - 16
5. PARAMETERS
5.4 Replacement of MR-J2- B by MR-J2S- B
When using the MR-J2S- B on the servo system controller peripheral software incompatible with the
MR-J2S- B, you cannot use some parameter functions. Read this section carefully and set appropriate values in the parameters.
5.4.1 Main modifications made to the parameters
The following table lists the parameters whose settings have been modified from the MR-J2- B or added to the MR-J2S- B. The peripheral software of the servo system controller may not be compatible with some parameters whose settings are different or have been added. For details, refer to the servo system controller manual.
Parameter
No.
Code Name Main modifications/additions
6
8
9
18
20
22
25
31
33
38
FBP
ATU
RSP
NCH Machine resonance suppression filter 1
(Notch filter)
INP In-position range
MOD
LPF
ERZ
OP6
ENR
Feedback pulse number
Auto tuning
Servo response level
Analog monitor output
Low-pass filter/adaptive vibration suppression control
Error excessive alarm level
Optional function 6
Encoder pulses output
The encoder resolution of the compatible motor changed to 131072 pulses/rev.
Gain adjustment modes were increased.
The response level setting range was increased to meet the enhanced response.
The machine resonance suppression filter (notch filter) setting range was increased.
The setting unit become the feedback pulse unit in parameter
No. 6.
The data that may be output by analog monitor was added.
The low-pass filter and adaptive vibration suppression control functions were newly added.
The setting unit was changed in response to the enhanced resolution
(131072 pulses/rev) of the encoder.
The communication baud rate with the personal computer was changed to max. 57600bps.
The encoder feedback pulses can be output from the servo amplifier.
These pulses can be set.
Note. As of November, 2003
(Note) Setting from peripheral software of conventional servo system controller
Setting cannot be made.
The resolution is 16384 pulses/rev.
Setting can be made but the added modes cannot be used.
Some response levels cannot be set.
Some filter frequencies cannot be set.
Setting can be made.
Setting can be made but the bus voltage cannot be set.
Setting can be made.
Setting can be made but the setting unit is [0.1 rev].
Setting cannot be made.
Setting cannot be made.
5 - 17
5. PARAMETERS
5.4.2 Explanation of the modified parameters
(1) Feedback pulse number (parameter No. 6)
This parameter was newly added to the MR-J2S- B. If the peripheral software of the servo system controller is not compatible with the MR-J2S- B, this parameter setting cannot be changed. When the servo motor used is the HC-KFS or HC-MFS, the feedback pulse number is 8192 pulses/rev, and when it is the HC-SFS, HC-RFS or HC-UFS, the feedback pulse number is 16384 pulses/rev.
(2) Auto tuning (parameter No. 8)
The set values of this parameter were newly added to the MR-J2S- B. If the peripheral software of the servo system controller is not compatible with the MR-J2S- B, the parameter settings are as indicated below. The auto tuning mode 2 and manual mode 1 cannot be used.
0 0 0
Gain adjustment mode selection
(For details, refer to section 6.1.1.)
Set value Gain adjustment mode
0 Interpolation mode
Description
Fixes position control gain 1
(parameter No. 13).
1
2
Auto tuning mode 1
Manual mode 2
Ordinary auto tuning.
Manual adjustment of all gains.
(3) Servo response level (parameter No. 9)
The set values of this parameter were newly added to the MR-J2S- B. In addition, the machine resonance frequency guidelines corresponding to the set values were changed. If the peripheral software of the servo system controller is not compatible with the MR-J2S- B, the parameter settings are as indicated below.
0 0 0
Auto tuning response level setting
Set value
7
8
5
6
3
4
1
2
B
C
9
A
Response level
Low response
Middle
response
High response
Machine resonance frequency guideline
15Hz
20Hz
25Hz
30Hz
35Hz
45Hz
55Hz
70Hz
85Hz
105Hz
130Hz
160Hz
5 - 18
5. PARAMETERS
(4) Machine resonance suppression filter 1 (parameter No. 18)
The settings of this parameter were changed for the MR-J2S- B. If the peripheral software of the servo system controller is not compatible with the MR-J2S- B, the parameter settings are as indicated below. The notch depth is 40dB.
0 0 0
4
5
2
3
6
7
0
1
Notch frequency selection
Set value Frequency
Invalid
4500
2250
1500
1125
900
750
642.9
Notch depth selection
Set value Depth
0 Deep
Gain
40dB
(5) In-position range (parameter No. 20)
The setting of this parameter was changed for the MR-J2S- B. The setting unit was changed from the conventional input pulse unit to the feedback pulse unit. For details, refer to section 5.2.
(6) Analog monitor output (parameter No. 22)
The setting of this parameter was changed for the MR-J2S- B. "Bus voltage" is a new choice, but you cannot select it if the peripheral software of the servo system controller is not compatible with the MR-
J2S- B.
Also, the droop pulse output is the encoder resolution unit of the actual motor. For details, refer to section 5.3.
(7) Low-pass filter/adaptive vibration suppression control (parameter No. 25)
This parameter was newly added to the MR-J2S- B. If the peripheral software of the servo system controller is not compatible with the MR-J2S- B, this parameter setting cannot be changed. Hence, the low-pass filter is "valid" and the adaptive vibration suppression control is "invalid". For details, refer to sections 7.3 and 7.4.
(8) Error excessive alarm level (parameter No. 31)
The setting of this parameter was changed for the MR-J2S- B. The setting unit was changed from conventional [k pulse] to [0.1rev]. If the peripheral software of the servo system controller is not compatible with the MR-J2S- B, the unit is set as [0.1rev] to the MR-J2S- B even when the onscreen setting unit is [k pulse]. For details, refer to section 5.2.
(9) Optional function 6 (parameter No. 33)
This parameter was newly added to the MR-J2S- B. If the peripheral software of the servo system controller is not compatible with the MR-J2S- B, this parameter setting cannot be changed. Hence, the serial communication baud rate is “9600 [bps]”, the serial communication response ready time is
“invalid”, and the encoder pulse output setting selection is "pulse output setting". For details, refer to section 5.2.
5 - 19
5. PARAMETERS
MEMO
5 - 20
6. GENERAL GAIN ADJUSTMENT
6. GENERAL GAIN ADJUSTMENT
6.1 Different adjustment methods
6.1.1 Adjustment on a single servo amplifier
The gain adjustment in this section can be made on a single servo amplifier. For gain adjustment, first execute auto tuning mode 1. If you are not satisfied with the results, execute auto tuning mode 2, manual mode 1 and manual mode 2 in this order.
(1) Gain adjustment mode explanation
Gain adjustment mode
Auto tuning mode 1
(initial value)
Auto tuning mode 2
Manual mode 1
Manual mode 2
Interpolation mode
Parameter No. 8 setting
0001
0003
0004
0002
0000
Estimation of load inertia moment ratio
Always estimated
Fixed to parameter No.
12 value
Automatically set parameters
GD2 (parameter No. 12)
PG1 (parameter No. 13)
VG1 (parameter No. 14)
PG2 (parameter No. 15)
VG2 (parameter No. 16)
VIC (parameter No. 17)
PG1 (parameter No. 13)
VG1 (parameter No. 14)
PG2 (parameter No. 15)
VG2 (parameter No. 16)
VIC (parameter No. 17)
VG1 (parameter No. 14)
PG2 (parameter No. 15)
Always estimated
Manually set parameters
RSP (parameter No. 9)
GD2 (parameter No. 12)
RSP (parameter No. 9)
GD2 (parameter No. 12)
PG2 (parameter No. 15)
VG2 (parameter No. 16)
VIC (parameter No. 17)
GD2 (parameter No. 12)
PG1 (parameter No. 13)
VG2 (parameter No. 16)
VIC (parameter No. 17)
GD2 (parameter No. 12)
PG1 (parameter No. 13)
VG1 (parameter No. 14)
PG2 (parameter No. 15)
VG2 (parameter No. 16)
VIC (parameter No. 17)
PG1 (parameter No. 13)
VG1 (parameter No. 14)
6 - 1
6. GENERAL GAIN ADJUSTMENT
(2) Adjustment sequence and mode usage
START
Yes
Interpolation
made for 2 or more axes?
No
Auto tuning mode 1
Operation
Yes
OK?
No
Auto tuning mode 2
Operation
Yes
OK?
No
Manual mode 1
Operation
Yes
OK?
No
Manual mode 2
END
No
Interpolation mode
Operation
OK?
Yes
Usage
Used when you want to match the position gain
(PG1) between 2 or more axes. Normally not used for other purposes.
Allows adjustment by merely changing the response level setting.
First use this mode to make adjustment.
Used when the conditions of auto tuning mode 1 are not met and the load inertia moment ratio could not be estimated properly, for example.
This mode permits adjustment easily with three gains if you were not satisfied with auto tuning results.
You can adjust all gains manually when you want to do fast settling or the like.
6 - 2
6. GENERAL GAIN ADJUSTMENT
6.1.2 Adjustment using MR Configurator (servo configuration software)
POINT
When using the machine analyzer, set the servo amplifier's axis number for
"F". (Refer to section 3.11.)
This section gives the functions and adjustment that may be performed by using the servo amplifier with the MR Configurator (servo configuration software) which operates on a personal computer.
Function
Machine analyzer
Gain search
Description
With the machine and servo motor coupled, the characteristic of the mechanical system can be measured by giving a random vibration command from the personal computer to the servo and measuring the machine response.
Adjustment
You can grasp the machine resonance frequency and determine the notch frequency of the machine resonance suppression filter.
You can automatically set the optimum gains in response to the machine characteristic. This simple adjustment is suitable for a machine which has large machine resonance and does not require much settling time.
You can automatically set gains which make positioning settling time shortest.
Machine simulation
Executing gain search under to-and-fro positioning command measures settling characteristic while simultaneously changing gains, and automatically searches for gains which make settling time shortest.
Response at positioning settling of a machine can be simulated from machine analyzer results on personal computer.
You can optimize gain adjustment and command pattern on personal computer.
6 - 3
6. GENERAL GAIN ADJUSTMENT
6.2 Auto tuning
6.2.1 Auto tuning mode
The servo amplifier has a real-time auto tuning function which estimates the machine characteristic (load inertia moment ratio) in real time and automatically sets the optimum gains according to that value. This function permits ease of gain adjustment of the servo amplifier.
(1) Auto tuning mode 1
The servo amplifier is factory-set to the auto tuning mode 1.
In this mode, the load inertia moment ratio of a machine is always estimated to set the optimum gains automatically.
The following parameters are automatically adjusted in the auto tuning mode 1.
Parameter No.
12
13
14
15
16
17
Abbreviation
GD2
PG1
VG1
PG2
VG2
VIC
Name
Ratio of load inertia moment to servo motor inertia moment
Position control gain 1
Speed control gain 1
Position control gain 2
Speed control gain 2
Speed integral compensation
POINT
The auto tuning mode 1 may not be performed properly if the following conditions are not satisfied.
Time to reach 2000r/min is the acceleration/deceleration time constant of 5s or less.
Speed is 150r/min or higher.
The ratio of load inertia moment to servo motor is not more than 100 times.
The acceleration/deceleration torque is 10% or more of the rated torque.
Under operating conditions which will impose sudden disturbance torque during acceleration/deceleration or on a machine which is extremely loose, auto tuning may not function properly, either. In such cases, use the auto tuning mode 2 or manual mode 1 2 to make gain adjustment.
(2) Auto tuning mode 2
Use the auto tuning mode 2 when proper gain adjustment cannot be made by auto tuning mode 1.
Since the load inertia moment ratio is not estimated in this mode, set the value of a correct load inertia moment ratio (parameter No. 12).
The following parameters are automatically adjusted in the auto tuning mode 2.
Parameter No.
13
14
15
16
17
Abbreviation
PG1
VG1
PG2
VG2
VIC
Position control gain 1
Speed control gain 1
Position control gain 2
Speed control gain 2
Speed integral compensation
Name
6 - 4
6. GENERAL GAIN ADJUSTMENT
6.2.2 Auto tuning mode operation
The block diagram of real-time auto tuning is shown below.
Command
Automatic setting
Servo motor
Load inertia moment
Encoder
Control gains
PG1,VG1
PG2,VG2,VIC
Current control
Current feedback
Gain table
Set 0 or 1 to turn on.
Real-time auto tuning section
Switch
Load inertia moment ratio estimation section
Position/speed feedback
Speed feedback
Parameter No.8
1
Parameter No.9
5
Auto tuning selection
Response level setting
Parameter No.12
Load inertia moment ratio estimation value
When a servo motor is accelerated/decelerated, the load inertia moment ratio estimation section always estimates the load inertia moment ratio from the current and speed of the servo motor. The results of estimation are written to parameter No. 12 (the ratio of load inertia moment to servo motor). These results can be confirmed on the status display screen of the MR Configurator (servo configuration software) section.
If the value of the load inertia moment ratio is already known or if estimation cannot be made properly, chose the "auto tuning mode 2" (parameter No. 8: 0003) to stop the estimation of the load inertia moment ratio (Switch in above diagram turned off), and set the load inertia moment ratio (parameter No. 12) manually.
From the preset load inertia moment ratio (parameter No. 12) value and response level (parameter No. 9), the optimum control gains are automatically set on the basis of the internal gain tale.
The auto tuning results are saved in the EEP-ROM of the servo amplifier every 6 minutes since power-on.
At power-on, auto tuning is performed with the value of each control gain saved in the EEP-ROM being used as an initial value.
POINT
If sudden disturbance torque is imposed during operation, the estimation of the inertia moment ratio may malfunction temporarily. In such a case, choose the "auto tuning mode 2" (parameter No. 8: 0003) and set the correct load inertia moment ratio in parameter No. 12.
When any of the auto tuning mode 1, auto tuning mode 2 and manual mode
1 settings is changed to the manual mode 2 setting, the current control gains and load inertia moment ratio estimation value are saved in the EEP-
ROM.
6 - 5
6. GENERAL GAIN ADJUSTMENT
6.2.3 Adjustment procedure by auto tuning
Since auto tuning is made valid before shipment from the factory, simply running the servo motor automatically sets the optimum gains that match the machine. Merely changing the response level setting value as required completes the adjustment. The adjustment procedure is as follows.
Auto tuning adjustment
Acceleration/deceleration repeated
Yes
Load inertia moment ratio estimation value stable?
No
Auto tuning conditions not satisfied.
(Estimation of load inertia moment ratio is difficult)
No
Yes
Choose the auto tuning mode 2
(parameter No. 8: 0003) and set the load inertia moment ratio
(parameter No. 12) manually.
Adjust response level setting so that desired response is achieved on vibration-free level.
Acceleration/deceleration repeated
Requested performance satisfied?
Yes
END
No
To manual mode
6 - 6
6. GENERAL GAIN ADJUSTMENT
6.2.4 Response level setting in auto tuning mode
Set the response (parameter No. 9) of the whole servo system. As the response level setting is increased, the track ability and settling time for a command decreases, but a too high response level will generate vibration. Hence, make setting until desired response is obtained within the vibration-free range.
If the response level setting cannot be increased up to the desired response because of machine resonance beyond 100Hz, adaptive vibration suppression control (parameter No. 25) or machine resonance suppression filter (parameter No. 18) may be used to suppress machine resonance. Suppressing machine resonance may allow the response level setting to increase. Refer to section 7.2, 7.3 for adaptive vibration suppression control and machine resonance suppression filter.
Parameter No. 9
5
Response level setting
Response level setting
D
E
F
A
B
C
7
8
5
6
9
1
2
3
4
Machine rigidity
Low
Middle
High
Machine characteristic
Machine resonance frequency guideline
Guideline of corresponding machine
15Hz
20Hz
25Hz
30Hz
Large conveyor
35Hz
45Hz
55Hz
70Hz
85Hz
Arm robot
General machine tool conveyor
105Hz
130Hz
160Hz
Precision working machine
Inserter
Mounter
Bonder 200Hz
240Hz
300Hz
6 - 7
6. GENERAL GAIN ADJUSTMENT
6.3 Manual mode 1 (simple manual adjustment)
If you are not satisfied with the adjustment of auto tuning, you can make simple manual adjustment with three parameters.
6.3.1 Operation of manual mode 1
In this mode, setting the three gains of position control gain 1 (PG1), speed control gain 2 (VG2) and speed integral compensation (VIC) automatically sets the other gains to the optimum values according to these gains.
GD2
User setting
PG1
VG2
VIC
Automatic setting
PG2
VG1
Therefore, you can adjust the model adaptive control system in the same image as the general PI control system (position gain, speed gain, speed integral time constant). Here, the position gain corresponds to
PG1, the speed gain to VG2 and the speed integral time constant to VIC. When making gain adjustment in this mode, set the load inertia moment ratio (parameter No. 12) correctly.
6.3.2 Adjustment by manual mode 1
POINT
If machine resonance occurs, adaptive vibration suppression control
(parameter No. 25) or machine resonance suppression filter (parameter No.
18) may be used to suppress machine resonance. (Refer to section 7.2, 7.3.)
(1) For speed control
(a) Parameters
The following parameters are used for gain adjustment.
Parameter No.
12
16
17
Abbreviation
GD2
VG2
VIC
Name
Ratio of load inertia moment to servo motor inertia moment
Speed control gain 2
Speed integral compensation
(b) Adjustment procedure
Step
1
2
3
4
5
Operation
Set an estimated value to the ratio of load inertia moment to servo motor inertia moment (parameter No. 12).
Increase the speed control gain 2 (parameter No. 16) within the vibration- and unusual noise-free range, and return slightly if vibration takes place.
Decrease the speed integral compensation (parameter No. 17) within the vibration-free range, and return slightly if vibration takes place.
If the gains cannot be increased due to mechanical system resonance or the like and the desired response cannot be achieved, response may be increased by suppressing resonance with adaptive vibration suppression control or machine resonance suppression filter and then executing steps 2 and 3.
While checking the settling characteristic and rotational status, fineadjust each gain.
Description
Increase the speed control gain.
Decrease the time constant of the speed integral compensation.
Suppression of machine resonance
Refer to section 7.2, 7.3.
Fine adjustment
6 - 8
6. GENERAL GAIN ADJUSTMENT
(c) Adjustment description
1) Speed control gain 2 (parameter No. 16)
This parameter determines the response level of the speed control loop. Increasing this value enhances response but a too high value will make the mechanical system liable to vibrate. The actual response frequency of the speed loop is as indicated in the following expression.
Speed loop response frequency(Hz)
Speed control gain setting
(1 ratio of load inertia moment to servo motor inertia moment) 2
2) Speed integral compensation (parameter No. 17)
To eliminate stationary deviation against a command, the speed control loop is under proportional integral control. For the speed integral compensation, set the time constant of this integral control. Increasing the setting lowers the response level. However, if the load inertia moment ratio is large or the mechanical system has any vibratory element, the mechanical system is liable to vibrate unless the setting is increased to some degree. The guideline is as indicated in the following expression.
Speed integral composition setting (ms)
2000 to 3000
Speed control gain 2 setting/ (1 ratio of load inertia moment to servo motor inertia moment.)
(2) For position control
(a) Parameters
The following parameters are used for gain adjustment.
Parameter No.
12
13
16
17
Abbreviation
GD2
PG1
VG2
VIC
Name
Ratio of load inertia moment to servo motor inertia moment
Position control gain 1
Speed control gain 2
Speed integral compensation
(b) Adjustment procedure
Step
1
2
3
4
5
6
7
Operation
Set an estimated value to the ratio of load inertia moment to servo motor inertia moment (parameter No. 12).
Set a slightly smaller value to the position control gain 1 (parameter
No. 13).
Increase the speed control gain 2 (parameter No. 16) within the vibration- and unusual noise-free range, and return slightly if vibration takes place.
Decrease the speed integral compensation (parameter No. 17) within the vibration-free range, and return slightly if vibration takes place.
Increase the position control gain 1 (parameter No. 13).
If the gains cannot be increased due to mechanical system resonance or the like and the desired response cannot be achieved, response may be increased by suppressing resonance with adaptive vibration suppression control or machine resonance suppression filter and then executing steps 3 to 5.
While checking the settling characteristic and rotational status, fineadjust each gain.
Description
Increase the speed control gain.
Decrease the time constant of the speed integral compensation.
Increase the position control gain.
Suppression of machine resonance
Refer to section 7.2 and 7.3.
Fine adjustment
6 - 9
6. GENERAL GAIN ADJUSTMENT
(c) Adjustment description
1) Position control gain 1 (parameter No. 13)
This parameter determines the response level of the position control loop. Increasing position control gain 1 improves track ability to a position command but a too high value will make overshooting liable to occur at the time of settling.
Position control gain 1 guideline
Speed control gain 2 setting
(1 ratio of load inertia moment to servo motor inertia moment)
(
1
to
1
5
)
2) Speed control gain 2 (parameter No. 16)
This parameter determines the response level of the speed control loop. Increasing this value enhances response but a too high value will make the mechanical system liable to vibrate. The actual response frequency of the speed loop is as indicated in the following expression.
Speed loop response frequency(Hz)
Speed control gain 2 setting
(1 ratio of load inertia moment to servo motor inertia moment) 22
3) Speed integral compensation (parameter No. 17)
To eliminate stationary deviation against a command, the speed control loop is under proportional integral control. For the speed integral compensation, set the time constant of this integral control. Increasing the setting lowers the response level. However, if the load inertia moment ratio is large or the mechanical system has any vibratory element, the mechanical system is liable to vibrate unless the setting is increased to some degree. The guideline is as indicated in the following expression.
Speed integral compensation setting(ms)
2000 to 3000
Speed control gain 2 setting/ (1 ratio of load inertia moment to servo motor inertia moment set value)
6 - 10
6. GENERAL GAIN ADJUSTMENT
6.4 Interpolation mode
The interpolation mode is used to match the position control gains of the axes when performing the interpolation operation of servo motors of two or more axes for an X-Y table or the like. In this mode, the position control gain 1 and speed control gain 1 which determine command track ability are set manually and the other gain adjusting parameters are set automatically.
(1) Parameter
(a) Automatically adjusted parameters
The following parameters are automatically adjusted by auto tuning.
Parameter No.
12
15
16
17
Abbreviation
GD2
PG2
VG2
VIC
Name
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
Speed control gain 2
Speed integral compensation
(b) Manually adjusted parameters
The following parameters are adjustable manually.
Parameter No.
13
14
Abbreviation
PG1
VG1
Position control gain 1
Speed control gain 1
Name
(2) Adjustment procedure
Step Operation
1
2
3
Choose the auto tuning mode 1 (parameter No. 8: 0001) and set the machine resonance frequency of the response level to 15Hz 1 (parameter No. 9: 0001).
During operation, increase the response level selection (parameter No. 9), and return the setting if vibration occurs.
Check the values of position control gain 1 (parameter No. 13) and speed control gain 1 (parameter No. 14).
4 Choose the interpolation mode (parameter No. 8: 0000).
5
6
7
Set the position control gain 1 of all the axes to be interpolated to the same value. At that time, adjust to the setting value of the axis, which has the smallest position control gain 1.
Using the speed control gain 1 value checked in step 3 as the guideline of the upper limit, look at the rotation status and set in speed control gain 1 the value three or more times greater than the position control gain 1 setting.
Looking at the interpolation characteristic and rotation status, fine-adjust the gains and response level setting.
Description
Select the auto tuning mode 1.
Adjustment in auto tuning mode
1.
Check the upper setting limits.
Select the interpolation mode.
Set position control gain 1.
Set speed control gain 1.
Fine adjustment.
(3) Adjustment description
(a) Position control gain 1 (parameter No.13)
This parameter determines the response level of the position control loop. Increasing PG1 improves track ability to a position command but a too high value will make overshooting liable to occur at the time of settling. The droop pulse value is determined by the following expression.
Droop pulse value (pulse)
Rotation speed (r/min)
60
131,072(pulse)
Position control gain set value
(b) Speed control gain 1 (parameter No. 14)
Set the response level of the speed loop of the model. Make setting using the following expression as a guideline.
Speed control gain 1 setting Position control gain 1 setting 3
6 - 11
6. GENERAL GAIN ADJUSTMENT
6.5 Differences in auto tuning between MELSERVO-J2 and MELSERVO-J2-Super
6.5.1 Response level setting
To meet higher response demands, the MELSERVO-J2-Super series has been changed in response level setting range from the MELSERVO-J2 series. The following table lists comparison of the response level setting.
Parameter No. 9
5
Response level setting
MELSERVO-J2 series
Response level setting Machine resonance frequency
1
2
3
4
5
20Hz
40Hz
60Hz
80Hz
100Hz
MELSERVO-J2-Super series
Response level setting Machine resonance frequency guideline
E
F
C
D
A
B
8
9
5
6
7
3
4
1
2
15Hz
20Hz
25Hz
30Hz
35Hz
45Hz
55Hz
70Hz
85Hz
105Hz
130Hz
160Hz
200Hz
240Hz
300Hz
Note that because of a slight difference in gain adjustment pattern, response may not be the same if the resonance frequency is set to the same value.
6.5.2 Auto tuning selection
The MELSERVO-J2-Super series has an addition of the load inertia moment ratio fixing mode. It also has the addition of the manual mode 1 which permits manual adjustment with three parameters.
Parameter No. 8
1
Gain adjustment mode selection
Gain adjustment mode
Interpolation mode
Auto tuning mode 1
Auto tuning
Auto tuning mode 2
Auto tuning invalid
Manual mode 1
Manual mode 2
Auto tuning selection
MELSERVO-J2 series MELSERVO-J2-Super series
0
1
0
1
2
3
4
2
Remarks
Position control gain 1 is fixed.
Ordinary auto tuning
Estimation of load inertia moment ratio stopped.
Response level setting valid.
Simple manual adjustment
Manual adjustment of all gains
6 - 12
7. SPECIAL ADJUSTMENT FUNCTIONS
7. SPECIAL ADJUSTMENT FUNCTIONS
POINT
The functions given in this chapter need not be used generally. Use them if you are not satisfied with the machine status after making adjustment in the methods in chapter 6.
If a mechanical system has a natural resonance point, increasing the servo system response level may cause the mechanical system to produce resonance (vibration or unusual noise) at that resonance frequency.
Using the machine resonance suppression filter and adaptive vibration suppression control functions can suppress the resonance of the mechanical system.
7.1 Function block diagram
Speed control
00
Parameter
No.18
0
Parameter
No.25
Machine resonance suppression filter 1 except
Adaptive vibration
suppression control 1
00 or 2
Low-pass filter
0
Parameter
No.25
Current command
Servo motor
1
Encoder
7.2 Machine resonance suppression filter
(1) Function
The machine resonance suppression filter is a filter function (notch filter) which decreases the gain of the specific frequency to suppress the resonance of the mechanical system. You can set the gain decreasing frequency (notch frequency) and gain decreasing depth.
Machine resonance point
Mechanical system response level
Frequency
Notch depth
Frequency
Notch frequency
POINT
The machine resonance suppression filter is a delay factor for the servo system. Hence, vibration may increase if you set a wrong resonance frequency or a too deep notch.
7 - 1
7. SPECIAL ADJUSTMENT FUNCTIONS
(2) Parameters
Set the notch frequency and notch depth of the machine resonance suppression filter 1 (parameter No.
18).
Parameter No. 18
Notch frequency selection
02
03
04
05
06
07
Setting Frequency
00
01
Invalid
4500
2250
1500
1125
900
750
642.9
0A
0B
0C
0D
0E
0F
Setting Frequency
08
09
562.5
500
450
409.1
375
346.2
321.4
300
Setting Frequency Setting Frequency
10
11
12
13
14
15
16
17
281.3
264.7
250
236.8
225
214.3
204.5
195.7
18
19
1A
1B
1C
1D
1E
1F
187.5
180
173.1
166.7
160.1
155.2
150
145.2
Notch depth selection
Setting Depth (Gain)
0
1
2
3
Deep ( 40dB)
( 14dB)
( 8dB)
Shallow ( 4dB)
POINT
If the frequency of machine resonance is unknown, decrease the notch frequency from higher to lower ones in order. The optimum notch frequency is set at the point where vibration is minimal.
A deeper notch has a higher effect on machine resonance suppression but increases a phase delay and may increase vibration.
The machine characteristic can be grasped beforehand by the machine analyzer on the MR Configurator (servo configuration software). This allows the required notch frequency and depth to be determined.
7 - 2
7. SPECIAL ADJUSTMENT FUNCTIONS
7.3 Adaptive vibration suppression control
(1) Function
Adaptive vibration suppression control is a function in which the servo amplifier detects machine resonance and sets the filter characteristics automatically to suppress mechanical system vibration.
Since the filter characteristics (frequency, depth) are set automatically, you need not be conscious of the resonance frequency of a mechanical system. Also, while adaptive vibration suppression control is valid, the servo amplifier always detects machine resonance, and if the resonance frequency changes, it changes the filter characteristics in response to that frequency.
Mechanical system response level
Machine resonance point
Frequency
Mechanical system response level
Machine resonance point
Frequency
Notch depth
Notch depth
Frequency Frequency
Notch frequency Notch frequency
When machine resonance is large and frequency is low When machine resonance is small and frequency is high
POINT
The machine resonance frequency which adaptive vibration suppression control can respond to is about 150 to 500Hz. Adaptive vibration suppression control has no effect on the resonance frequency outside this range. Use the machine resonance suppression filter for the machine resonance of such frequency.
Adaptive vibration suppression control may provide no effect on a mechanical system which has complex resonance characteristics or which has too large resonance.
Under operating conditions in which sudden disturbance torque is imposed during operation, the detection of the resonance frequency may malfunction temporarily, causing machine vibration. In such a case, set adaptive vibration suppression control to be "held" (parameter No. 25: 2 ) to fix the characteristics of the adaptive vibration suppression control filter.
7 - 3
7. SPECIAL ADJUSTMENT FUNCTIONS
(2) Parameters
The operation of adaptive vibration suppression control selection (parameter No. 25).
Parameter No. 25
Adaptive vibration suppression control selection
0: Invalid
1: Valid
Machine resonance frequency is always detected to generate the filter in response to resonance, suppressing machine vibration.
2: Held
Filter characteristics generated so far is held, and detection of machine resonance is stopped.
Adaptive vibration suppression control sensitivity selection
Set the sensitivity of detecting machine resonance.
0: Normal
1: Large sensitivity
POINT
Adaptive vibration suppression control is factory-set to be "invalid"
(parameter No. 25: 0000).
Selection the adaptive vibration suppression control sensitivity can change the sensitivity of detecting machine resonance. Selection of "large sensitivity" detects smaller machine resonance and generates a filter to suppress machine vibration. However, since a phase delay will also increase, the response of the servo system may not increase.
7.4 Low-pass filter
(1) Function
When a ball screw or the like is used, resonance of high frequency may occur as the response level of the servo system is increased. To prevent this, the low-pass filter is factory-set to be valid for a torque command. The filter frequency of this low-pass filter is automatically adjusted to the value in the following expression.
Filter frequency
(Hz) 2
Speed control gain 2 set value 10
(1 ratio of load inertia moment to servo motor inertia moment set value 0.1)
(2) Parameter
Set the operation of the low-pass filter (parameter No. 25).
Parameter No. 25
Low-pass filter selection
0: Valid (automatic adjustment) initial value
1: Invalid
POINT
In a mechanical system where rigidity is extremely high and resonance is difficult to occur, setting the low-pass filter to be "invalid" may increase the servo system response to shorten the settling time.
7 - 4
7. SPECIAL ADJUSTMENT FUNCTIONS
7.5 Gain changing function
This function can change the gains. You can change between gains during rotation and gains during stop or can use an external signal to change gains during operation.
7.5.1 Applications
This function is used when.
(1) You want to increase the gains during servo lock but decrease the gains to reduce noise during rotation.
(2) You want to increase the gains during settling to shorten the stop settling time.
(3) You want to change the gains using an external signal to ensure stability of the servo system since the load inertia moment ratio varies greatly during a stop (e.g. a large load is mounted on a carrier).
7.5.2 Function block diagram
The valid control gains PG2, VG2, VIC and GD2 of the actual loop are changed according to the conditions selected by gain changing selection CDP (parameter No. 49) and gain changing condition CDS (parameter
No. 50).
CDP
Parameter No.49
Control command of controller
Command pulse frequency
Droop pulses
Changing
Model speed
Comparator
CDS
Parameter No.50
GD2
Parameter No.12
GD2B
Parameter No.52
PG2
Parameter No.15
PG2 PG2B
100
VG2
Parameter No.16
VG2 VG2B
100
VIC
Parameter No.17
VIC VICB
100
7 - 5
Valid
GD2 value
Valid
PG2 value
Valid
VG2 value
Valid
VIC value
7. SPECIAL ADJUSTMENT FUNCTIONS
7.5.3 Parameters
When using the gain changing function, always set " 2 " in parameter No.8 (auto tuning) to choose the manual mode 2 of the gain adjustment modes. The gain changing function cannot be used in the auto tuning mode.
Parameter
No.
13
14
12
15
16
17
52
53
54
55
49
Abbrevi ation
Name
PG1 Position control gain 1
VG1 Speed control gain 1
GD2
Ratio of load inertia moment to servo motor inertia moment
PG2 Position control gain 2
VG2 Speed control gain 2
VIC Speed integral compensation
GD2B
PG2B
Ratio of load inertia moment to servo motor inertia moment 2
Position control gain 2 changing ratio
VG2B
VICB
Speed control gain 2 changing ratio
Speed integral compensation changing ratio
CDP Gain changing selection
50 CDS Gain changing condition
Unit rad/s rad/s
0.1
times rad/s rad/s ms
0.1
times
%
%
% kpps pulse r/min
Description
Position and speed gains of a model used to set the response level to a command. Always valid.
Control parameters before changing
Used to set the ratio of load inertia moment to servo motor inertia moment after changing.
Used to set the ratio (%) of the after-changing position control gain 2 to position control gain 2.
Used to set the ratio (%) of the after-changing speed control gain 2 to speed control gain 2.
Used to set the ratio (%) of the after-changing speed integral compensation to speed integral compensation.
Used to select the changing condition.
Used to set the changing condition values.
51 CDT Gain changing time constant ms
You can set the filter time constant for a gain change at changing.
7 - 6
7. SPECIAL ADJUSTMENT FUNCTIONS
(1) Parameters No. 12 to 17
These parameters are the same as in ordinary manual adjustment. Gain changing allows the values of ratio of load inertia moment to servo motor inertia moment, position control gain 2, speed control gain
2 and speed integral compensation to be changed.
(2) Ratio of load inertia moment to servo motor inertia moment 2 (parameter No. 52)
Set the ratio of load inertia moment to servo motor inertia moment after changing. If the load inertia moment ratio does not change, set it to the same value as ratio of load inertia moment to servo motor inertia moment (parameter No. 34).
(3) Position control gain 2 changing ratio (parameter No. 53), speed control gain 2 changing ratio (parameter
No. 54), speed integral compensation changing ratio (parameter No. 55)
Set the values of after-changing position control gain 2, speed control gain 2 and speed integral compensation in ratio (%). 100% setting means no gain change.
For example, at the setting of position control gain 2 100, speed control gain 2 2000, speed integral compensation 20 and position control gain 2 changing ratio 180%, speed control gain 2 changing ratio 150% and speed integral compensation changing ratio 80%, the after-changing values are as follows.
Position control gain 2 Position control gain 2 Position control gain 2 changing ratio /100 180rad/s
Speed control gain 2 Speed control gain 2 Speed control gain 2 changing ratio /100 3000rad/s
Speed integral compensation Speed integral compensation Speed integral compensation changing ratio /100 16ms
(4) Gain changing selection (parameter No. 49)
Used to set the gain changing condition. Choose the changing condition in the first digit. If setting "1" here, the gain changing can be switched with the control command of controller.
Parameter No. 49
Gain changing selection
Gains are changed in accordance with the settings of parameters No. 52 to 55 under any of the following conditions:
0: Invalid
1: Control command of controller
2: Command frequency is equal to higher than parameter No. 50 setting
3: Droop pulse value is equal to higher than parameter No. 50 setting
4: Servo motor speed is equal to higher than parameter No. 50 setting
(5) Gain changing condition (parameter No. 50)
When you selected "command frequency", "droop pulses" or "servo motor speed" in gain changing selection (parameter No.50), set the gain changing level.
The setting unit is as follows.
Gain changing condition
Command frequency
Droop pulses
Servo motor speed
Unit kpps pulse r/min
(6) Gain changing time constant (parameter No. 51)
You can set the primary delay filter to each gain at gain changing. This parameter is used to suppress shock given to the machine if the gain difference is large at gain changing, for example.
7 - 7
7. SPECIAL ADJUSTMENT FUNCTIONS
7.5.4 Gain changing operation
This operation will be described by way of setting examples.
(1) When you choose changing by external input
(a) Setting
Parameter No.
13
14
Abbreviation
PG1
VG1
12
15
16
17
52
53
54
55
GD2
PG2
VG2
VIC
GD2B
PG2B
VG2B
VICB
Name
Position control gain 1
Speed control gain 1
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
Speed control gain 2
Speed integral compensation
Ratio of load inertia moment to servo motor inertia moment 2
Position control gain 2 changing ratio
Speed control gain 2 changing ratio
Speed integral compensation changing ratio
49
51
CDP
CDT
Gain changing selection
Gain changing time constant
Setting
100
1000
4
120
3000
20
100
70
133
250
0001
Control command from controller
100
(b) Changing operation
Control command from controller
(CDP)
OFF
ON
After-changing gain
OFF
Unit rad/s rad/s
0.1 times rad/s rad/s ms
0.1 times
%
%
% ms
Change of each gain
Before-changing gain
CDT 100ms
Position control gain 1
Speed control gain 1
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
Speed control gain 2
Speed integral compensation
4.0
120
3000
20
100
1000
10.0
84
4000
50
4.0
120
3000
20
7 - 8
7. SPECIAL ADJUSTMENT FUNCTIONS
(2) When you choose changing by droop pulses
(a) Setting
Parameter No.
13
14
12
15
16
17
52
53
54
55
49
50
51
(b) Changing operation
Abbreviation
PG1
VG1
GD2
PG2
VG2
VIC
GD2B
PG2B
VG2B
VICB
CDP
CDS
CDT
Name
Position control gain 1
Speed control gain 1
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
Speed control gain 2
Speed integral compensation
Ratio of load inertia moment to servo motor inertia moment 2
Position control gain 2 changing ratio
Speed control gain 2 changing ratio
Speed integral compensation changing ratio
Gain changing selection
Gain changing condition
Gain changing time constant
Setting
100
1000
40
120
3000
20
100
70
133
250
0003
(Changed by droop pulses)
50
100
Unit rad/s rad/s
0.1 times rad/s rad/s ms
0.1 times
%
%
% pulse ms
Command pulse
Droop pulses
Droop pulses [pulses] 0
CDS
CDS
After-changing gain
Change of each gain
Before-changing gain
CDT 100ms
Position control gain 1
Speed control gain 1
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
Speed control gain 2
Speed integral compensation
4.0
120
3000
20
10.0
84
4000
50
100
1000
4.0
120
3000
20
10.0
84
4000
50
7 - 9
7. SPECIAL ADJUSTMENT FUNCTIONS
MEMO
7 - 10
8. INSPECTION
8. INSPECTION
WARNING
Before starting maintenance and/or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
Any person who is involved in inspection should be fully competent to do the work.
Otherwise, you may get an electric shock. For repair and parts replacement, contact your safes representative.
POINT
Do not test the servo amplifier with a megger (measure insulation resistance), or it may become faulty.
Do not disassemble and/or repair the equipment on customer side.
(1) Inspection
It is recommended to make the following checks periodically.
(a) Check for loose terminal block screws. Retighten any loose screws.
(b) Check the cables and the like for scratches and cracks. Perform periodic inspection according to operating conditions.
(2) Life
The following parts must be changed periodically as listed below. If any part is found faulty, it must be changed immediately even when it has not yet reached the end of its life, which depends on the operating method and environmental conditions. For parts replacement, please contact your sales representative.
Servo amplifier
Part name
Smoothing capacitor
Relay
Cooling fan
Absolute position battery
Life guideline
10 years
Number of power-on and number of forced stop times:100,000times.
10,000 to 30,000hours (2 to 3 years)
Refer to section 13.2
(a) Smoothing capacitor
Affected by ripple currents, etc. and deteriorates in characteristic. The life of the capacitor greatly depends on ambient temperature and operating conditions. The capacitor will reach the end of its life in 10 years of continuous operation in normal air-conditioned environment.
(b) Relays
Their contacts will wear due to switching currents and contact faults occur. Relays reach the end of their life when the cumulative number of power-on and forced stop times is 100,000, which depends on the power supply capacity.
(c) Servo amplifier cooling fan
The cooling fan bearings reach the end of their life in 10,000 to 30,000 hours. Normally, therefore, the cooling fan must be changed in a few years of continuous operation as a guideline.
It must also be changed if unusual noise or vibration is found during inspection.
8 - 1
8. INSPECTION
MEMO
8 - 2
9. TROUBLESHOOTING
9. TROUBLESHOOTING
9.1 Alarms and warning list
When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or warning has occurred, refer to section 9.2 or 9.3 and take the appropriate action.
After its cause has been removed, the alarm can be deactivated in any of the methods marked in the alarm deactivation column.
Alarm deactivation
Display Name Power
OFF ON
Error reset CPU reset
8E
88
92
96
9F
46
50
51
52
35
36
37
45
31
32
33
34
17
19
1A
20
24
25
30
10
12
13
15
16
E0
E1
E3
E4
E6
E7
E9
EE
Undervoltage
Memory error 1
Clock error
Memory error 2
Encoder error 1
Board error
Memory error 3
Motor combination error
Encoder error 2
Main circuit error
Absolute position erase
Regenerative error
Overspeed
Overcurrent
Overvoltage
CRC error
Command frequency error
Transfer error
Parameter error
Main circuit device overheat
Servo motor overheat
Overload 1
Overload 2
Error excessive
Serial communication error
Watchdog
Open battery cable warning
Home position setting warning
Battery warning
Excessive regenerative warning
Overload warning
Absolute position counter warning
Parameter warning
Servo forced stop warning
Controller forced stop warning
Main circuit off warning
SSCNET error warning
(Note 2)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
Removing the cause of occurrence
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1) deactivates the alarm automatically.
Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.
2. For confirming the connection to the servo system controller, the alarm may not be reset unless turning the power on twice or more times.
9 - 1
9. TROUBLESHOOTING
9.2 Remedies for alarms
CAUTION
When any alarm has occurred, eliminate its cause, ensure safety, then reset the alarm, and restart operation. Otherwise, injury may occur.
If an absolute position erase alarm (25) occurred, always make home position setting again. Otherwise, misoperation may occur.
As soon as an alarm occurs, mark Servo-off and power off the main circuit and control circuit.
POINT
When any of the following alarms has occurred, always remove its cause and allow about 30 minutes for cooling before resuming operation. If operation is resumed by switching control circuit power off, then on to reset the alarm, the servo amplifier and servo motor may become faulty. To protect the main circuit elements, any of these servo alarms cannot be deactivated from the servo system controller until the specified time elapses after its occurrence. Judging the load changing condition until the alarm occurs, the servo amplifier calculates this specified time automatically.
Regenerative error (30)
Overload 1 (50)
Overload 2 (51)
The alarm can be deactivated by switching power off, then on or by the error reset command CPU reset from the servo system controller. For details, refer to section 9.1.
When an alarm occurs, the dynamic brake is operated to stop the servo motor. At this time, the display indicates the alarm No.
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. The MR
Configurator (servo configuration software) may be used to refer to the cause.
Display
10
Name Definition
Undervoltage Power supply voltage dropped.
MR-J2S- B:
160VAC or less
MR-J2S- B1:
83VAC or less
Cause Action
1. Power supply voltage is low.
2. There was an instantaneous control circuit power failure of
60ms or longer.
3. Shortage of power supply capacity caused the power supply voltage to drop at start, etc.
4. Main voltage has dropped to the following voltage or less.
MR-J2S- B: 200VDC
MR-J2S- B1: 158VDC
5. Faulty parts in the servo amplifier
Check the power supply.
Change the servo amplifier.
Checking method
Alarm (10) occurs if power is switched on after CN1A, CN1B and CN3 connectors are disconnected.
12
13
Change the servo amplifier.
Memory error 1 RAM, memory fault
Clock error Printed board fault
Faulty parts in the servo amplifier
Checking method
Alarm (any of 12 and 13) occurs if power is switched on after disconnection of all cables but the control circuit power supply cables.
9 - 2
9. TROUBLESHOOTING
Display
15
16
17
19
Name Definition
Memory error 2 EEP-ROM fault
Cause
1. Faulty parts in the servo amplifier
Checking method
Alarm (15) occurs if power is switched on after disconnection of all cables but the control circuit power supply cables.
Action
Change the servo amplifier.
2. The number of write times to EEP-
ROM exceeded 100,000.
Encoder error 1 Communication error occurred
Board error
1. Encoder connector (CN2) disconnected.
between encoder 2. Encoder fault and servo amplifier. 3. Encoder cable faulty
(Wire breakage or shorted)
CPU/parts fault 1. Faulty parts in the servo amplifier
Checking method
Alarm (17) occurs if power is switched on after disconnection of all cable but the control circuit power supply cable.
Connect correctly.
Change the servo motor.
Repair or change the cable.
Change the servo amplifier.
The output terminals U, V, W of the servo amplifier and the input terminals U, V, W of the servo motor are
2. The wiring of U, V, W is disconnected or not connected.
not connected.
Memory error 3 ROM memory fault Faulty parts in the servo amplifier
Checking method
Alarm (19) occurs if power is switched on after disconnection of all cable but the control circuit power supply cable.
Correctly connect the output terminals U,
V, W of the servo amplifier and the input terminals U, V, W of the servo motor.
Change the servo amplifier.
1A Motor
20 combination error
Encoder error 2
24
25
Main circuit error
Absolute position erase
Wrong combination of servo amplifier and servo motor.
Communication
Wrong combination of servo amplifier and servo motor connected.
1. Encoder connector (CN2) error occurred between encoder disconnected.
2. Encoder fault and servo amplifier. 3. Encoder cable faulty
(Wire breakage or shorted)
Encoder detected acceleration error.
4. Excessive acceleration is occurred due to oscillation and others.
Ground fault occurred at the servo motor outputs
(U,V and W phases) of the servo amplifier.
1. Power input wires and servo motor output wires are in contact at main circuit terminal block (TE1).
2. Sheathes of servo motor power cables deteriorated, resulting in ground fault.
3. Main circuit of servo amplifier failed.
Checking method
Alarm (24) occurs if the servo is switched on after disconnecting the U, V, W power cables from the servo amplifier.
Use correct combination.
Connect correctly.
Change the servo motor.
Repair or change the cable.
1. Decrease the speed control gain 2.
2. Decrease the auto tuning response level.
Connect correctly.
Change the cable.
Change the servo amplifier.
Absolute position data in error
Power was switched on for the first time in the absolute position detection system.
1. Battery voltage low
2. Battery cable or battery is faulty.
3. Super capacitor of the absolute position encoder is not charged.
9 - 3
Change the battery.
Always make home position setting again.
After leaving the alarm occurring for a few minutes, switch power off, then on again.
Always make home position setting again.
9. TROUBLESHOOTING
Display
30
Name
Regenerative error
31
32
Overspeed
Overcurrent
Definition
Permissible regenerative power of the built-in regenerative resistor or regenerative option is exceeded.
Cause
1. Mismatch between used regenerative option and parameter No. 2 setting
2. Built-in regenerative resistor or regenerative option is not connected.
3. High-duty operation or continuous regenerative operation caused the permissible regenerative power of the regenerative option to be exceeded.
Checking method
Call the status display and check the regenerative load ratio.
Set correctly.
Connect correctly.
Action
1. Reduce the frequency of positioning.
2. Use the regenerative option of larger capacity.
3. Reduce the load.
Regenerative transistor fault
4. Power supply voltage is abnormal.
MR-J2S- B:260VAC or more
MR-J2S- B1:135VAC or more
5. Built-in regenerative resistor or regenerative option faulty.
6. Regenerative transistor faulty.
Checking method
1) The regenerative option has
overheated abnormally.
2) The alarm occurs even after
removal of the built-in
regenerative resistor or
regenerative option.
Review power supply
Change the servo amplifier or regenerative option.
Change the servo amplifier.
Speed has exceeded the instantaneous permissible speed.
1. Small acceleration/deceleration time constant caused overshoot to be large.
2. Servo system is instable to cause overshoot.
Increase acceleration/deceleration time constant.
1. Reset servo gain to proper value.
2. If servo gain cannot be set to proper value.
1) Reduce load inertia moment ratio; or
2) Reexamine acceleration/ deceleration time constant.
Change the servo motor.
Correct the wiring.
Current that flew is higher than the permissible current of the servo amplifier. (When the alarm (32) occurs, switch the power OFF and then ON to reset the alarm. Then, turn on the servo-on.
When the alarm (32) still occurs at the time, the transistor
(IPM IGBT) of the servo amplifier may be at fault. Do not switch the power
OFF/ON repeatedly; check the transistor according to the cause 2 checking method.)
Current higher than the permissible current flew in the regenerative transistor.
(MR-J2S-500B only)
3. Encoder faulty.
1. Short occurred in servo amplifier output phases U, V and W.
2. Transistor of the servo amplifier faulty.
Checking method
Alarm (32) occurs if power is switched on after U,V and W are disconnected.
3. Ground fault occurred in servo amplifier output phases U, V and
W.
4. External noise caused the overcurrent detection circuit to misoperate.
5. Improper wiring of the regenerative option.
Change the servo amplifier.
Correct the wiring.
Take noise suppression measures.
Wire the regenerative option correctly.
9 - 4
9. TROUBLESHOOTING
Display
33
34
35
36
37
45
Name
Overvoltage
CRC error
Definition
Converter bus voltage exceeded
400VDC.
Bus cable is faulty
Cause Action
1. Regenerative option is not used.
Use the regenerative option.
2. Though the regenerative option is used, the parameter No. 2 setting is " 00 (not used)".
Make correct setting.
3. Lead of built-in regenerative resistor or regenerative option is open or disconnected.
1. Change the lead.
2. Connect correctly.
4. Regenerative transistor faulty.
5. Wire breakage of built-in regenerative resistor or regenerative option
6. Capacity of built-in regenerative resistor or regenerative option is insufficient.
7. Power supply voltage high.
8. Ground fault occurred in servo amplifier output phases U, V and W.
Change the servo amplifier.
1. For wire breakage of built-in regenerative resistor, change the servo amplifier.
2. For wire breakage of regenerative option, change the regenerative option.
Add regenerative option or increase capacity.
Review the power supply.
Correct the wiring.
9. The jumper across BUE-SD of the
FR-BU2 brake unit is removed.
1. Bus cable disconnected.
2. Bus cable fault
Fit the jumper across BUE-SD.
Connect correctly.
Change the cable.
Command frequency error
Parameter error
Main circuit device overheat
Input frequency of command pulse is too high.
Transfer error Bus cable or printed board is faulty
3. Noise entere bus cable.
4. Termination connector disconnected.
5. The same No. exists in the servo amplifier side axis setting.
1. Command given is greater than the maximum speed of the servo motor.
2. Noise entered bus cable.
3. Servo system controller failure
1. Bus cable is disconnected.
2. Bus cable fault.
Take measures against noise.
Connect termination connector.
Set correctly.
Review operation program.
Take action against noise.
Change the servo system controller.
Connect the connector of the bus cable.
Change the cable.
3. Printed board is faulty.
4. Terimination connector disconnected
Change the servo amplifier.
Connect termination connector.
Parameter setting is wrong.
1. Servo amplifier fault caused the parameter setting to be rewritten.
2. There is a parameter whose value was set to outside the setting range by the controller.
Main circuit device overheat
Change the servo amplifier.
Change the parameter value to within the setting range.
3. The number of write times to EEP-
ROM exceeded 100,000 due to parameter write, etc.
1. Servo amplifier faulty.
Change the servo amplifier.
Change the servo amplifier.
The drive method is reviewed.
2. The power supply was turned on and off continuously by overloaded status.
3. Air cooling fan of servo amplifier stops.
1. Change the servo amplifier or cooling fan.
2. Reduce ambient temperature.
9 - 5
9. TROUBLESHOOTING
Display Name
46 Servo motor overheat
50
51
Overload 1
Overload 2
Definition
Servo motor temperature rise actuated the thermal sensor.
Load exceeded overload protection characteristic of servo amplifier.
Cause
1. Ambient temperature of servo motor is over 40 (104 ).
2. Servo motor is overloaded.
Action
Review environment so that ambient temperature is 0 to 40 (32 to 104 ).
1. Reduce load.
2. Review operation pattern.
3. Use servo motor that provides larger output.
Change the servo motor.
3. Thermal sensor in encoder is faulty.
1. Servo amplifier is used in excess of its continuous output current.
2. Servo system is instable and hunting.
3. Machine struck something.
1. Reduce load.
2. Review operation pattern.
3. Use servo motor that provides larger output.
1. Repeat acceleration/ deceleration to execute auto tuning.
2. Change the auto tuning response setting.
3. Set auto tuning to OFF and make gain adjustment manually.
1. Review operation pattern.
2. Install limit switches.
Connect correctly.
4. Wrong connection of servo motor.
Servo amplifier's output terminals
U, V, W do not match servo motor's input terminals U, V, W.
5. Encoder faulty.
Checking method
When the servo motor shaft is rotated with the servo off,the cumulative feedback pulses do not vary in proportion to the rotary angle of the shaft but the indication skips or returns midway.
Change the servo motor.
Machine collision or the like caused max.
For the time of the alarm occurrence, refer to the section
11.1.
1. Machine struck something.
2. Wrong connection of servo motor.
Servo amplifier's output terminals
U, V, W do not match servo motor's input terminals U, V, W.
3. Servo system is instable and hunting.
1. Review operation pattern.
2. Install limit switches.
Connect correctly.
1. Repeat acceleration/deceleration to execute auto tuning.
2. Change the auto tuning response setting.
3. Set auto tuning to OFF and make gain adjustment manually.
Change the servo motor.
4. Encoder faulty.
Checking method
When the servo motor shaft is rotated with the servo off,the cumulative feedback pulses do not vary in proportion to the rotary angle of the shaft but the indication skips or returns midway.
9 - 6
9. TROUBLESHOOTING
Display
52 (Note)
Name
Error excessive
8E Serial communication error
88 Watchdog
Definition
The deviation between the model position and the actual servo motor position exceeds the parameter No.31
setting value (initial value: 2 revolutions).
Cause
1. Acceleration/deceleration time constant is too small.
2. Torque limit value is too small.
3. Motor cannot be started due to torque shortage caused by power supply voltage drop.
4. Position control gain 1 (parameter
No.13) value is small.
5. Servo motor shaft was rotated by external force.
6. Machine struck something.
Action
Increase the acceleration/deceleration time constant.
Increase the torque limit value.
1. Review the power supply capacity.
2. Use servo motor which provides larger output.
Increase set value and adjust to ensure proper operation.
1. When torque is limited, increase the limit value.
2. Reduce load.
3. Use servo motor that provides larger output.
1. Review operation pattern.
2. Install limit switches.
Change the servo motor.
Connect correctly.
7. Encoder faulty
8. Wrong connection of servo motor.
Servo amplifier's output terminals
U, V, W do not match servo motor's input terminals U, V, W.
Serial communication error occurred between servo amplifier and communication device (e.g. personal computer).
1. Communication cable fault
(Open cable or short circuit)
2. Communication device (e.g.
personal computer) faulty
CPU, parts faulty Fault of parts in servo amplifier
Checking method
Alarm (88) occurs if power is switched on after disconnection of all cable but the control circuit power supply cable.
Repair or change the cable.
Change the communication device (e.g.
personal computer).
Change the servo amplifier.
Note. The error excessive detection for 2 revolutions is available only when the servo amplifier of software version B1 or later is used.
For the servo amplifier of software version older than B1, an error excessive alarm occurs when the deviation (deviation counter value) between the instructed position and the actual servo motor position exceeds the parameter No. 1 setting value (initial value: 8 revolutions).
9 - 7
9. TROUBLESHOOTING
9.3 Remedies for warnings
POINT
When any of the following alarms has occurred, do not resume operation by switching power of the servo amplifier OFF/ON repeatedly. The servo amplifier and servo motor may become faulty. If the power of the servo amplifier is switched OFF/ON during the alarms, allow more than 30 minutes for cooling before resuming operation.
Excessive regenerative warning (E0)
Overload warning 1 (E1)
If servo forced stop warning (E6), controller forced stop warning (E7) or SSCNET error warning (EE) occurs, the servo off status is established. If any other warning occurs, operation can be continued but an alarm may take place or proper operation may not be performed. Eliminate the cause of the warning according to this section. Use the MR Configurator (servo configuration software) to refer to the cause of warning.
Display
96
Name
92 Open battery cable warning
Home position setting warning
Definition
Absolute position detection system battery voltage is low.
Home position return could not be made in the precise position.
Cause
1. Battery cable is open.
2. Battery voltage supplied from the servo amplifier to the encoder fell to about
3.2V or less.
(Detected with the encoder)
1. Droop pulses remaining are greater than the in-position range setting.
2. Home position return was executed during operation command.
3. Creep speed high.
9F Battery warning Voltage of battery for absolute position detection system reduced.
E0 Excessive regenerative warning
There is a possibility that regenerative power may exceed permissible regenerative power of built-in regenerative resistor or regenerative option.
Battery voltage fell to 3.2V or less.
(Detected with the servo amplifier)
Regenerative power increased to 85% or more of permissible regenerative power of built-in regenerative resistor or regenerative option.
Checking method
Call the status display and check regenerative load ratio.
Action
Repair cable or changed.
Change the battery.
Remove the cause of droop pulse occurrence.
Reduce creep speed.
Change the battery.
1. Reduce frequency of positioning.
2. Change regenerative option for the one with larger capacity.
3. Reduce load.
E1 Overload warning
There is a possibility that overload alarm 1 or 2 may occur.
Load increased to 85% or more of overload alarm 1 or 2 occurrence level.
Refer to 50, 51.
Cause, checking method
Refer to 50, 51.
E3 Absolute position counter warning
Absolute position encoder pulses faulty.
1. Noise entered the encoder.
2. Encoder faulty.
E4
E6
E7
E9
EE
Parameter warning
Servo forced stop warning
Controller forced stop warning
Main circuit off warning
SSCNET error warning
Parameter outside setting range.
EM1 is off.
Servo-on command was issued with main circuit power off.
The servo system controller connected is not SSCNET-compatible.
Parameter value set from servo system controller is outside setting range
External forced stop was made valid.
(EM1 turned off.)
Forced stop signal was entered into the servo system controller.
Take noise suppression measures.
Change the servo motor.
Set it correctly.
Ensure safety and deactivate forced stop.
Ensure safety and deactivate forced stop.
Switch on main circuit power.
9 - 8
10. OUTLINE DIMENSION DRAWINGS
10. OUTLINE DIMENSION DRAWINGS
10.1 Servo amplifiers
(1) MR-J2S-10B to MR-J2S-60B
MR-J2S-10B1 to MR-J2S-40B1
70 (2.76)
6 ( 0.24) mounting hole B
A
MITSUBISHI
OPEN
C
N
1
A
E
N
C
C
N
2
L1 L2 L3
(Note)
C
N
3
U V W
C
N
1
B
6
(0.24)
PE terminal
135 (5.32)
Rating plate
TE1
[Unit: mm]
([Unit: in])
Terminal layout
(Terminal cover open)
MITSUBISHI
OPEN
C
N
2
E
N
C
C
N
1
A
C
N
3
C
N
1
B
TE2
4(0.16)
Servo amplifier
Variable dimensions
A B
Mass
[kg]([lb])
MR-J2S-10B(1)
MR-J2S-20B(1)
MR-J2S-40B(1)
MR-J2S-60B
50 (1.97)
70 (2.76)
6 (0.24)
22 (0.87)
0.7 (1.54)
1.1 (2.43)
Note. This data applies to the 3-phase 200 to 230V and 1-phase 230V power supply models.
Terminal signal layout
TE1
For 3-phase 200 to 230V and 1-phase 230V For 1-phase 100 to 120V
L
1
U
L
2
L
3
V W
L
1
U V
L
2
W
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
(28.676 [lb in])
TE2
Front
D C P L 21 L 11
PE terminals
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
10 - 1
10. OUTLINE DIMENSION DRAWINGS
(2) MR-J2S-70B MR-J2S-100B
6 ( 0.24) mounting hole
70(2.76)
22
(0.87)
MITSUBISHI
OPEN
C
N
1
A
E
N
C
C
N
2
L1 L2 L3
C
N
3
C
N
1
B
U V W
22
(0.87)
6(0.24)
42
(1.65)
PE terminal
6(0.24)
70(2.76) 190(7.48)
Rating plate
Servo amplifier
MR-J2S-70B
MR-J2S-100B
Mass
[kg]([lb])
1.7
(3.75)
Terminal signal layout
TE1
L
1
U
L
V
2
L
3
W
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
TE2
Front
D C P L
21
L
11
N
PE terminals
Mounting Screw
Screw Size:M5
Tightening torque:3.24[N m](28.676 [lb in])
6(0.24)
[Unit: mm]
([Unit: in])
Terminal layout
(Terminal cover open)
MITSUBISHI
OPEN
C
N
2
E
N
C
C
N
1
A
C
N
3
C
N
1
B
TE2 TE1
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
10 - 2
10. OUTLINE DIMENSION DRAWINGS
(3) MR-J2S-200B MR-J2S-350B
2- 6 ( 0.24) mounting hole
6
(0.24)
90(3.54)
78(3.07)
MITSUBISHI
70(2.76) 195(7.68)
[Unit: mm]
([Unit: in])
Terminal layout
MITSUBISHI
TE2
TE1
PE terminal
Cooling fan wind direction
Servo amplifier
MR-J2S-200B
MR-J2S-350B
Mass
[kg]([lb])
2.0
(4.41)
Terminal signal layout
TE1
L
1
L
2
L
3
U V W
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
TE2
L
11
L
21
D P C N
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
PE terminals
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
(28.676 [lb in])
10 - 3
10. OUTLINE DIMENSION DRAWINGS
(4) MR-J2S-500B
2- 6 ( 0.24) mounting hole
(0.24)
6
130(5.12)
118(4.65)
(0.24)
6
70
(2.76)
OPEN
MITSUBISHI
OPEN
C
N
1
A
C
N
2
C
N
1
B
C
N
3
[Unit: mm]
([Unit: in])
200(7.87)
(0.19) 5
TE1
Terminal layout
MITSUBISHI
OPEN
C
N
1
A
C
N
2
C
N
1
B
C
N
3
TE2
N.P. N.P.
6(0.24)
Cooling fan
Cooling fan wind direction
Cooling fan
Servo amplifier
MR-J2S-500B
Mass
[kg]([lb])
4.9(10.8)
TE1
L
1
C
P
L
2
L
3
V
W
N
U
Terminal signal layout
PE terminals
Terminal screw : M4
Tightening torque : 1.2 [N m](10.6[lb in])
Built-in regenerative resistor lead terminal fixing screw
Terminal screw : M4
Tightening torque : 1.2 [N m](10.6[lb in])
TE2
L
11
L
21
Terminal screw : M3.5
Tightening torque : 0.8 [N m](7[lb in])
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
(28.676 [lb in])
10 - 4
10. OUTLINE DIMENSION DRAWINGS
(5) MR-J2S-700B
2- 6( 0.24) mounting hole
(0.39)
10
180(7.09)
160(6.23) 10
(0.39)
70
(2.76)
MITSUBISHI
OPEN
C
N
1
A
C
2
C
N
3
C
N
1
B
OPEN
200(7.87)
138(5.43) 62
(2.44)
6(0.24)
[Unit: mm]
([Unit: in])
Terminal layout
MITSUBISHI
OPEN
C
N
1
A
C
2
C
N
1
B
C
N
3
TE2
TE1
Servo amplifier
MR-J2S-700B
6 (0.24)
Mass
[kg]([lb])
7.2(15.9)
Cooling fan Cooling fan wind direction
TE1
L
1
L
2
L
3
C P N U V
Terminal screw : M4
Tightening torque : 1.2 [N m](10[lb in])
W
TE2
L
11
L
21
Terminal screw : M3.5
Tightening torque : 0.8 [N m](7[lb in])
PE terminals
Built-in regenerative resistor lead terminal fixing screw
Terminal screw : M4
Tightening torque : 1.2 [N m](10[lb in])
Mounting Screw
Screw Size : M5
Tightening torque :
3.24[N m]
(28.676 [lb in]
10 - 5
10. OUTLINE DIMENSION DRAWINGS
(6) MR-J2S-11KB 15KB
2- 12( 0.47) mounting hole
(0.47)12
MITSUBISHI
CN4
Cooling fan
CN2
TE2
CHARGE
C
N
1
B
C
N
1
A
C
N
3
CON2
TE1
12(0.47)
236(9.29)
260(10.24) 12(0.47)
75
(2.95)
[Unit: mm]
([Unit: in])
Cooling fan wind direction
Servo amplifier
MR-J2S-11KB
MR-J2S-15KB
Mass
[kg]([lb])
15(33.1)
16(35.3)
TE1
Terminal signal layout
PE terminal
C N L
1
L
2
L
3
U V W P
1
Terminal screw : M6
Tightening torque : 3.0[N m] (26[lb in)]
P
TE2
Terminal screw : M6
Tightening torque : 6.0[N m] (52[lb in)]
Mounting Screw
Screw Size:M10
Tightening torque:
26.5[N m]
(234.545[lb in])
L
11
L
21
Terminal screw : M4
Tightening torque : 1.2[N m] (10.6[lb in])
10 - 6
10. OUTLINE DIMENSION DRAWINGS
(7) MR-J2S-22KB
2- 12( 0.47) mounting hole
(0.47)12
MITSUBISHI
Cooling fan
CN2 CHARGE
TE2
CN4
C
N
1
B
C
N
1
A
C
N
3
CON2
TE1
12(0.47)
326(12.84)
350(13.78) 12(0.47)
75
(2.95)
[Unit: mm]
([Unit: in])
Coolig fan wind direction
Servo amplifier
MR-J2S-22KB
Mass
[kg]([lb])
20(44.1)
Terminal signal layout
TE1
L
1
L
2
L
3
U V W P
1
Terminal screw : M8
Tightening torque : 6.0[N m] (52[lb in)]
P C N
TE2
L
11
L
21
Terminal screw : M4
Tightening torque : 1.2[N m] (10.6[lb in)]
PE terminal
Terminal screw : M8
Tightening torque : 6.0[N m] (52[lb in)]
Mounting Screw
Screw Size:M10
Tighting torque:
26.5[N m]
(234.545[lb in])
10 - 7
10. OUTLINE DIMENSION DRAWINGS
10.2 Connectors
(1) Servo amplifier side
<3M>
(a) Soldered type
Model
Connector : 10120-3000PE 10126-3000PE
Shell kit : 10320-52F0-008 10326-52F0-008
12.0(0.47)
[Unit: mm]
([Unit: in])
A 14.0
(0.55)
Logo, etc. are indicated here.
B 12.7
(0.50)
Connector
10120-3000PE
10126-3000PE
Shell kit
10320-52F0-008
10326-52F0-008
(b) Threaded type
Model
Connector : 10120-3000PE
Shell kit : 10320-52A0-008
Note. This is not available as option
and should be user-prepared.
A
Variable dimensions
B
22.0(0.87)
25.8(1.02)
33.3(1.31)
37.2(1.47)
12.0(0.47)
[Unit: mm]
([Unit: in])
22.0(0.87) 14.0
(0.55)
27.4
(1.08)
Logo, etc. are indicated here.
33.3
(1.31)
12.7
(0.50)
10 - 8
10. OUTLINE DIMENSION DRAWINGS
(c) Insulation displacement type
Model
Connector : 10120-6000EL
Shell kit : 10320-3210-000
6.7
( 0.26)
[Unit: mm]
([Unit: in])
2- 0.5
(0.02)
20.9(0.82) Logo, etc. are indicated here.
29.7
(1.17)
(2) Bus cable connector
(a) Honda Tsushin Industry PCR type
PCR-LS20LA1
13.0
(0.51)
HONDA
23.0(0.91)
14.2(0.56)
(0.04)1 12.2
(0.48)
1(0.04)
RS
A HOND
PCR-LS20LA1W
[Unit: mm]
([Unit: in])
10.4(0.41)
RS
27.4(1.08)
32.0(0.91)
27.4(1.08)
32.0(0.91) 1.9
(0.08)
1 12.2
(0.04) (0.48)
1
(0.04)
Number of Pins
20
Connector
PCR-S20FS (soldering type)
PCR-S20F (insulation displacement type)
(Note) Model
Case
PCR-LS20LA1
PCR-LS20LA1W
Note. PCR-S20F and PCR-LS20LA1W are not options and are to be supplied by the customer.
Crimping terminal
FHAT-002A
10 - 9
10. OUTLINE DIMENSION DRAWINGS
(b) Honda Tsushin Industry HDR type
Number of Pins
14
26
Connector
HDR-E14MG1
HDR-E26MG1
Model HDR
Connector case
HDR-E14LPA5
HDR-E26LPA5
Note. Not available from us and to be supplied by the customer.
(Note) Crimping terminal
Wire straightening tool : FHAT-0029
Insulation displacement tool : FHPT-0004C
Model Connector : HDR-E14MG1
Connector case : HDR-E14LPA5
Model Connector : HDR-E26MG1
Connector case : HDR-E26LPA5
[Unit: mm]
([Unit: in])
17 (0.67)
5.6 ( 0.22)
21.8 (0.86)
6 7 (0.24 0.28)
21 (0.83) 25.8 (1.02)
(3) Communication cable connector
<Japan Aviation Electronics Industry>
[Unit: mm]
([Unit: in])
B
A
Fitting fixing screwG F
E(max. diameter of cable used)
Type
DE-C1-J6-S6
C
D
A
1
34.5(1.36)
B
1
19(0.75)
C
0.25
24.99(0.98)
D
1
33(1.30)
E
6(0.24)
F
Reference
18(0.71)
G
#4-40
10 - 10
11. CHARACTERISTICS
11. CHARACTERISTICS
11.1 Overload protection characteristics
An electronic thermal relay is built in the servo amplifier to protect the servo motor and servo amplifier from overloads. Overload 1 alarm (50) occurs if overload operation performed is above the electronic thermal relay protection curve shown in any of Figs 11.1, Overload 2 alarm (51) occurs if the maximum current flew continuously for several seconds due to machine collision, etc. Use the equipment on the lefthand side area of the continuous or broken line in the graph.
In a machine like the one for vertical lift application where unbalanced torque will be produced, it is recommended to use the machine so that the unbalanced torque is 70% or less of the rated torque.
1000 1000
During rotation During rotation
100 100
During servo lock
10
During servo lock
10
1 1
0.1
0 50 100 150 200
(Note) Load ratio [%]
250 a. MR-J2S-10B to MR-J2S-100B
300
10000
0.1
0 50 100 150 200
(Note) Load ratio [%]
250 b. MR-J2S-200B to MR-J2S-350B
300
10000
1000
100
During servo lock
During rotation
1000
During rotation
100
10
During servo lock
10
1
0 50 100 150 200
(Note) Load ratio [%]
250 300
1
0 100 200
(Note) Load ratio [%] d. MR-J2S-11KB to MR-J2S-22KB
300 c. MR-J2S-500B MR-J2S-700B
Note. If operation that generates torque more than 100% of the rating is performed with an abnormally high frequency in a servo motor stop status (servo lock status) or in a 30r/min or less low-speed operation status, the servo amplifier may fail even when the electronic thermal relay protection is not activated.
Fig 11.1 Electronic thermal relay protection characteristics
11 - 1
11. CHARACTERISTICS
11.2 Power supply equipment capacity and generated loss
(1) Amount of heat generated by the servo amplifier
Table 11.1 indicates servo amplifiers' power supply capacities and losses generated under rated load.
For thermal design of an enclosure, use the values in Table 11.1 in consideration for the worst operating conditions. The actual amount of generated heat will be intermediate between values at rated torque and servo off according to the duty used during operation. When the servo motor is run at less than the maximum speed, the power supply capacity will be smaller than the value in the table, but the servo amplifier's generated heat will not change.
Table 11.1 Power supply capacity and generated heat per servo amplifier at rated output
Servo amplifier
MR-J2S-10B(1)
MR-J2S-20B(1)
MR-J2S-40B(1)
MR-J2S-60B
MR-J2S-70B
MR-J2S-100B
MR-J2S-200B
MR-J2S-350B
Servo motor
HC-KFS053 13
HC-MFS053 13
HC-UFS13
HC-KFS23
HC-MFS23
HC-UFS23
HC-KFS43
HC-MFS43
HC-UFS43
HC-SFS52
HC-SFS53
HC-LFS52
HC-KFS73
HC-MFS73
HC-UFS72 73
HC-SFS81
HC-SFS102 103
HC-LFS102
HC-SFS121
HC-SFS201
HC-SFS152 153
HC-SFS202 203
HC-RFS103
HC-RFS153
HC-UFS152
HC-LFS152
HC-SFS301
HC-SFS352 353
HC-RFS203
HC-UFS202
HC-LFS202
(Note 1)
Power supply capacity[kVA]
2.5
4.8
5.5
3.5
3.5
3.5
3.5
1.8
2.5
2.5
1.7
2.1
3.5
2.5
1.3
1.3
1.5
1.7
1.0
1.0
1.0
1.3
0.5
0.5
0.9
0.9
0.9
0.3
0.3
0.3
0.5
(Note 2)
Servo amplifier-generated heat[W]
At rated torque With servo off
90
120
130
90
90
90
90
50
90
90
50
90
90
90
50
50
50
50
40
40
40
50
25
25
35
35
35
25
25
25
25
20
20
20
20
20
20
20
15
20
20
15
20
20
20
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Area required for heat dissipation
[m 2 ]
1.8
2.7
2.7
1.8
1.8
1.8
1.8
1.0
1.8
1.8
1.0
1.8
1.8
1.8
1.0
1.0
1.0
1.0
0.8
0.8
0.8
1.0
0.5
0.5
0.7
0.7
0.7
0.5
0.5
0.5
0.5
[ft 2 ]
19.4
29.1
29.1
19.4
19.4
19.4
10.8
19.4
19.4
19.4
19.4
10.8
19.4
19.4
8.6
8.6
8.6
10.8
10.8
10.8
10.8
10.8
5.4
5.4
7.5
7.5
7.5
5.4
5.4
5.4
5.4
11 - 2
11. CHARACTERISTICS
Servo amplifier
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
Servo motor
HC-SFS502
HC-RFS353
HC-RFS503
HC-UFS352
HC-UFS502
HC-LFS302
HA-LFS502
HC-SFS702
HA-LFS702
HA-LFS11K2
HA-LFS801
HA-LFS12K1
HA-LFS11K1M
HA-LFS15K2
HA-LFS15K1
HA-LFS15K1M
HA-LFS22K2
HA-LFS20K1
HA-LFS25K1
HA-LFS22K1M
(Note 1)
Power supply capacity[kVA]
7.5
5.5
7.5
5.5
7.5
4.5
7.5
10.0
10.6
16.0
12.0
18.0
16.0
22.0
22.0
22.0
33.0
30.1
37.6
33.0
(Note 2)
Servo amplifier-generated heat[W]
At rated torque With servo off
195
135
195
300
300
530
195
195
195
120
390
580
530
640
640
640
850
775
970
850
25
25
25
25
25
45
25
25
25
25
45
45
45
45
45
45
55
55
55
55
Area required for heat dissipation
[m 2 ]
3.9
2.7
3.9
3.9
3.9
2.4
3.9
6.0
6.0
11
7.8
11.6
11.0
13
13
13
17
15.5
19.4
17.0
[ft 2 ]
42.0
29.1
83.9
124.8
118.4
139.0
139.0
139.0
183.0
166.8
42.0
42.0
42.0
25.8
42.0
64.6
64.6
118.4
208.8
193.0
Note 1. Note that the power supply capacity will vary according to the power supply impedance. This value assumes that the power factor improving reactor is not used.
2. Heat generated during regeneration is not included in the servo amplifier-generated heat. To calculate heat generated by the regenerative option, use Equation 12.1 refer to section 12.1.1.
11 - 3
11. CHARACTERISTICS
(2) Heat dissipation area for enclosed servo amplifier
The enclosed control box (hereafter called the control box) which will contain the servo amplifier should be designed to ensure that its temperature rise is within 10 at the ambient temperature of
40 . (With a 5 (41 ) safety margin, the system should operate within a maximum 55 (131 ) limit.) The necessary enclosure heat dissipation area can be calculated by Equation 11.1.
P
A K T............................................................................................................................................. (11.1) where, A : Heat dissipation area [m 2 ]
P : Loss generated in the control box [W]
T : Difference between internal and ambient temperatures [ ]
K : Heat dissipation coefficient [5 to 6]
When calculating the heat dissipation area with Equation 11.1, assume that P is the sum of all losses generated in the enclosure. Refer to Table 11.1 for heat generated by the servo amplifier. "A" indicates the effective area for heat dissipation, but if the enclosure is directly installed on an insulated wall, that extra amount must be added to the enclosure's surface area.
The required heat dissipation area will vary wit the conditions in the enclosure. If convection in the enclosure is poor and heat builds up, effective heat dissipation will not be possible. Therefore, arrangement of the equipment in the enclosure and the use of a cooling fan should be considered.
Table 11.1 lists the enclosure dissipation area for each servo amplifier when the servo amplifier is operated at the ambient temperature of 40 (104 ) under rated load.
(Outside)
(Inside)
Air flow
Fig. 11.2 Temperature distribution in enclosure
When air flows along the outer wall of the enclosure, effective heat exchange will be possible, because the temperature slope inside and outside the enclosure will be steeper.
11 - 4
11. CHARACTERISTICS
11.3 Dynamic brake characteristics
11.3.1 Dynamic brake operation
(1) Calculation of coasting distance
Fig. 11.3 shows the pattern in which the servo motor comes to a stop when the dynamic brake is operated. Use Equation 11.2 to calculate an approximate coasting distance to a stop. The dynamic brake time constant varies with the servo motor and machine operation speeds. (Refer to (2) in this section.)
Forced stop(EM1)
ON
OFF
Time constant
Machine speed
V
0 t e
Time
Fig. 11.3 Dynamic brake operation diagram
L max
V
0
60 t e 1
J
L
J
M
....................................................................................................................... (11.2)
L max
: Maximum coasting distance .................................................................................................[mm][in]
Vo : Machine rapid feed rate ........................................................................................ [mm/min][in/min]
J
M
J
L
: Servo motor inertial moment................................................................................. [kg cm
: Load inertia moment converted into equivalent value on servo motor shaft
2 ][oz in 2 ]
................................................................................................................................. [kg cm 2 ][oz in 2 ]
: Brake time constant ........................................................................................................................ [s] t e : Delay time of control section........................................................................................................... [s]
For 7kW or less servo, there is internal relay delay time of about 30ms. For 11k to 22kW servo, there is delay time of about 100ms caused by a delay of the external relay and a delay of the magnetic contactor built in the external dynamic brake.
(2) Dynamic brake time constant
The following shows necessary dynamic brake time constant for the equations (11.2).
16
14
12
10
8
6
053
73
23
4
2
43 13
0
0 500 1000 1500 2000 2500 3000
Speed[r/min]
20
18
16
14
12
10
8
6
4
2
0
0
23
73
053
43
13
500 1000 1500 2000 2500 3000
Speed [r/min]
HC-KFS series HC-MFS series
11 - 5
11. CHARACTERISTICS
120
100
80
40
35
30
25
20
15
10
5
0
0
121
201
301
50 500
Speed [r/min]
HC-SFS1000r/min series
81
1000
53
203
60
40 353
20
103
0
0 50 500 1000 1500
Speed [r/min]
153
2000 2500 3000
HC-SFS3000r/min series
20
15
10
5
0
0
40
35
30
25
100
90
80
70
60
50
40
30
20
10
0
0
72
152
352
502
202
500 1000 1500
Speed [r/min]
2000
HC-UFS 2000r/min series
15K2
22K2
11K2
500 1000 1500 2000
Speed [r/min]
HA-LFS series
11 - 6
20
15
10
5
0
0
45
40
35
30
25
352202
500
702
502
1000
Speed [r/min]
102
1500
52
152
2000
HC-SFS2000r/min series
18
16
14
12
10
8
6
4
2
0
0
103
153
503
353
203
500 1000 1500 2000 2500 3000
Speed [r/min]
HC-RFS series
70
73
60
50
40
30
20
13
23
43
10
0
0 50 500 10001500200025003000
Speed [r/min]
HC-UFS3000r/min series
20
15
10
5
0
0
40
35
30
25
302
500 1000 1500 2000
Speed [r/min]
HC-LFS series
11. CHARACTERISTICS
11.3.2 The dynamic brake at the load inertia moment
Use the dynamic brake under the load inertia moment ratio indicated in the following table. If the load inertia moment is higher than this value, the built-in dynamic brake may burn. If there is a possibility that the load inertia moment may exceed the value, contact Mitsubishi.
Servo amplifier
MR-J2S-10B to MR-J2S-200B
MR-J2S-10B1 to MR-J2S-40B1
MR-J2S-350B
MR-J2S-500B
MR-J2S-700B
(Note) MR-J2S-11KB to MR-J2S-22KB
Load inertia moment ratio [times]
Note. Assumes that the external dynamic brake is used.
30
16
15
(Note) 30
11.4 Encoder cable flexing life
The flexing life of the cables is shown below. This graph calculated values. Since they are not guaranteed values, provide a little allowance for these values.
1 10 8
5 10 7 a
1 10 7
5 10
1 10
5 10
6
6
5
1 10 5
5 10 4
1 10 4
5 10 3 b
1 10 3
4 7 10 20 40 70 100
Flexing radius [mm]
200 a : Long flexing-life encoder cable
MR-JCCBL M-H
MR-JHSCBL M-H
MR-ENCBL M-H b : Standard encoder cable
MR-JCCBL M-L
MR-JHSCBL M-L
11 - 7
11. CHARACTERISTICS
11.5 Inrush currents at power-on of main circuit and control circuit
The following table indicates the inrush currents (reference value) that will flow when the maximum permissible voltage (253VAC) is applied at the power supply capacity of 2500kVA and the wiring length of
10m.
Servo amplifier
MR-J2S-10B 20B
MR-J2S-40B 60B
MR-J2S-70B 100B
MR-J2S-200B 350B
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
MR-J2S-10B1 20B1
MR-J2S-40B1
Inrush Currents (A
0-p
)
Main circuit power supply (L
1
, L
2
, L
3
) Control circuit power supply (L
11
, L
21
)
30A (Attenuated to approx. 5A in 10ms)
30A (Attenuated to approx. 5A in 10ms)
54A (Attenuated to approx. 12A in 10ms)
70 to 100A
(Attenuated to approx. 0A in 0.5 to 1ms)
120A (Attenuated to approx. 12A in 20ms)
100 to 130A
(Attenuated to approx. 0A in 0.5 to 1ms)
44A (Attenuated to approx. 20A in 20ms)
88A (Attenuated to approx. 20A in 20ms)
30A
(Attenuated to approx. 0A in several ms)
235A (Attenuated to approx. 20A in 20ms)
59A (Attenuated to approx. 5A in 4ms)
72A (Attenuated to approx. 5A in 4ms)
100 to 130A
(Attenuated to approx. 0A in 0.5 to 1ms)
Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic contactors. (Refer to section 12.2.2.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be tripped by an inrush current.
11 - 8
12. OPTIONS AND AUXILIARY EQUIPMENT
12. OPTIONS AND AUXILIARY EQUIPMENT
WARNING
Before connecting any option or peripheral equipment, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
CAUTION
Use the specified auxiliary equipment and options. Unspecified ones may lead to a fault or fire.
12.1 Options
12.1.1 Regenerative options
CAUTION
The specified combinations of regenerative options and servo amplifiers may only be used. Otherwise, a fire may occur.
(1) Combination and regenerative power
The power values in the table are resistor-generated powers and not rated powers.
Servo amplifier Built-in regenerative resistor
MR-RB032
[40 ]
Regenerative power[W]
MR-RB12
[40 ]
MR-RB32
[40 ]
MR-RB30
[13 ]
MR-J2S-10B(1)
MR-J2S-20B(1)
MR-J2S-40B(1)
MR-J2S-60B
MR-J2S-70B
MR-J2S-100B
MR-J2S-200B
MR-J2S-350B
MR-J2S-500B
MR-J2S-700B
Note. Always install a cooling fan.
20
100
100
130
10
10
10
20
170
30
30
30
30
30
30
100
100
100
100
100
300
300
300
300
300
(Note)
MR-RB50
[13 ]
500
500
500
MR-RB31
[6.7 ]
300
(Note)
MR-RB51
[6.7 ]
500
Servo amplifier External regenerative resistor
(Accessory)
500 (800)
850 (1300)
850 (1300)
(Note) Regenerative power[W]
MR-RB65
[8 ]
500 (800)
MR-RB66
[5 ]
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
Note. Values in parentheses assume the installation of a cooling fan.
850 (1300)
MR-RB67
[4 ]
850 (1300)
12 - 1
12. OPTIONS AND AUXILIARY EQUIPMENT
(2) Selection of the regenerative option
(a) Simple selection method
In horizontal motion applications, select the regenerative option as described below.
When the servo motor is run without load in the regenerative mode from the running speed to a stop, the permissible duty is as indicated in section 5.1 of the separately available Servo Motor
Instruction Manual.
For the servo motor with a load, the permissible duty changes according to the inertia moment of the load and can be calculated by the following formula.
Permissible duty
Permissible duty for servo motor with no load (value indication section 5.1 in Servo Motor Instruction Manual)
(m l) ratedspeed running speed
2
[times/min] where m load inertia moment/servo motor inertia moment
From the permissible duty, find whether the regenerative option is required or not.
Permissible duty number of positioning times [times/min]
Select the regenerative option out of the combinations in (1) in this section.
(b) To make selection according to regenerative energy
Use the following method when regeneration occurs continuously in vertical motion applications or when it is desired to make an in-depth selection of the regenerative option.
a. Regenerative energy calculation
Use the following table to calculate the regenerative energy.
tf(1 cycle)
No
Up
M
Friction torque
T
F
( )
1)
T psa1 t1
(Driving)
2)
T psd1 t2
4)
Down
T psa2 t3
Time t4
T psd2
8)
5)
T
U
6)
3)
(Regenerative) 7)
( )
Formulas for calculating torque and energy in operation
Regenerative power
1) T
1
Torque applied to servo motor [N m]
(J
L
J
M
) No
9.55 10
4
1
T psa1
T U
T
F E 1
0.1047
2
Energy [J]
No T
1
T psa1
2)
3)
T
2
T
3
T
U
T
F
(J
L
J
M
) No
9.55 10
4
1
T psa1
T
U
T
F
E
2
E
3
0.1047 No T
2
0.1047
2
No T
3 t
1
T psd1
4), 8)
5)
T
4
T
5
T
U
(J
L
J
M
) No
9.55 10
4
1
T psa2
T
U
T
F
E
4
E 5
0 (No regeneration)
0.1047
2
No T
5 T psa2
6)
7)
T
6
T
7
T
U
T
F
(J L J M ) No
9.55 10
4
1
T psa2
T
U
T
F
E
6
E
7
0.1047 No T
6
0.1047
2
No T
7 t
3
T psd2
From the calculation results in 1) to 8), find the absolute value (Es) of the sum total of negative energies.
12 - 2
12. OPTIONS AND AUXILIARY EQUIPMENT b. Losses of servo motor and servo amplifier in regenerative mode
The following table lists the efficiencies and other data of the servo motor and servo amplifier in the regenerative mode.
Servo amplifier
MR-J2S-10B
MR-J2S-10B1
MR-J2S-20B
MR-J2S-20B1
MR-J2S-40B
MR-J2S-40A1
MR-J2S-60B
MR-J2S-70B
MR-J2S-100B
MR-J2S-200B
MR-J2S-350B
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
Inverse efficiency[%]
90
90
90
90
80
80
85
85
90
85
85
85
55
55
70
70
Capacitor charging[J]
70
120
170
250
18
18
40
40
45
11
12
11
9
4
9
4
Inverse efficiency ( ) :Efficiency including some efficiencies of the servo motor and servo amplifier when rated (regenerative) torque is generated at rated speed.
Since the efficiency varies with the speed and torque, allow for about 10%.
Capacitor charging (Ec) :Energy charged into the electrolytic capacitor in the servo amplifier.
Subtract the capacitor charging from the result of multiplying the sum total of regenerative energies by the inverse efficiency to calculate the energy consumed by the regenerative option.
ER [J] Es Ec
Calculate the power consumption of the regenerative option on the basis of single-cycle operation period tf
[s] to select the necessary regenerative option.
PR [W] ER/tf
(3) Parameter setting
Set parameter No.2 according to the option to be used.
The MR-RB65, 66 and 67 are regenerative options that have encased the GRZG400-2 , GRZG400-1 and GRZG400-0.8 , respectively. When using any of these regenerative options, make the same parameter setting as when using the GRZG400-2 , GRZG400-1 or GRZG400-0.8 (supplied regenerative resistors or regenerative option is used with 11kW or more servo amplifier).
Parameter No.2
0 0
Selection of regenerative
00: Regenerative option is not used with 7kW or less servo amplifier
(The built-in regenerative resistor is used. However, the MR-J2S-10B does not
have a built-in regenerative resistor and therefore cannot use it.)
Supplied regenerative resistors or regenerative option is used with 11k to 22kW
servo amplifier
01: FR-RC, FR-BU2, FR-CV
05: MR-RB32
08: MR-RB30
09: MR-RB50(Cooling fan is required)
0B: MR-RB31
0C: MR-RB51(Cooling fan is required)
0E: When regenerative resistors or regenerative option supplied to 11k to 22kW are
cooled by cooling fans to increase capability
10: MR-RB032
11: MR-RB12
12 - 3
12. OPTIONS AND AUXILIARY EQUIPMENT
(4) Connection of the regenerative option
POINT
When the MR-RB50 MR-RB51 is used, a cooling fan is required to cool it.
The cooling fan should be prepared by the customer.
The regenerative option will generate heat of about 100 . Fully examine heat dissipation, installation position, used cables, etc. before installing the option. For wiring, use flame-resistant cables and keep them clear of the regenerative option body. Always use twisted cables of max.
5m(16.4ft) length for connection with the servo amplifier.
(a) MR-J2S-350B or less
Always remove the wiring from across P-D and fit the regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is opened when the regenerative option overheats abnormally.
Servo amplifier
Always remove the lead from across P-D.
D
Regenerative option
P
P
C
C
G3
(Note 2)
G4
5m (16.4 ft) max.
Cooling fan(Note 1)
Note 1. When using the MR-RB50, forcibly cool it with a cooling fan (92 92, minimum air flow: 1.0m
3 ).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
For the MR-RB50 install the cooling fan as shown.
Top
Cooling fan Terminal block
[Unit : mm(in)]
Cooling fan installation screw hole dimensions
2-M3 screw hole
(for cooling fan installation)
Depth 10 or less
(Screw hole already machined)
Thermal relay
Bottom
82.5
(3.25)
40 (1.58)
Vertical installation
Horizontal installation Installation surface
12 - 4
12. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-J2S-500B MR-J2S-700B
Always remove the wiring (across P-C) of the servo amplifier built-in regenerative resistor and fit the regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is opened when the regenerative option overheats abnormally.
Always remove wiring (across P-C) of servo amplifier built-in regenerative resistor.
Servo amplifier
Regenerative option
P
P
C
C
G3
(Note 2)
G4
5m(16.4ft) or less
Cooling fan(Note 1)
Note 1. When using the MR-RB50 MR-RB51, forcibly cool it with a cooling fan (92 92, minimum air flow: 1.0m
3 ).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
When using the regenerative resistor option, remove the servo amplifier's built-in regenerative resistor terminals (across P-C), fit them back to back, and secure them to the frame with the accessory screw as shown below.
Mounting method
Accessory screw
For MR-J2S-500B For MR-J2S-700B
Accessory screw
12 - 5
Accessory screw
12. OPTIONS AND AUXILIARY EQUIPMENT
For the MR-RB50 MR-RB51 install the cooling fan as shown.
Top
Cooling fan Terminal block
[Unit : mm(in)]
Cooling fan installation screw hole dimensions
2-M3 screw hole
(for cooling fan installation)
Depth 10 or less
(Screw hole already machined)
Thermal relay
Bottom
82.5
(3.25)
40 (1.58)
Vertical installation
Horizontal installation Installation surface
(c) MR-J2S-11KB to MR-J2S-22KB (when using the supplied regenerative resistor)
When using the regenerative resistors supplied to the servo amplifier, the specified number of resistors (4 or 5 resistors) must be connected in series. If they are connected in parallel or in less than the specified number, the servo amplifier may become faulty and/or the regenerative resistors burn. Install the resistors at intervals of about 70mm. Cooling the resistors with two cooling fans
(92 92, minimum air flow : 1.0m
3 ) improves the regeneration capability. In this case, set "0E " in parameter No. 2.
5m or less
Do not remove the short bar.
Servo amplifier
P
1
P
C
(Note) Series connection
Cooling fan
Note. The number of resistors connected in series depends on the resistor type. Install a thermal sensor or like to configure a circuit that will shut off the main circuit power at abnormal overheat. The supplied regenerative resistor does not have a built-in thermal sensor. If the regenerative brake circuit fails, abnormal overheat of the resistor is expected to occur. On the customer side, please also install a thermal sensor for the resistor and provide a protective circuit that will shut off the main circuit power supply at abnormal overheat. The detection level of the thermal sensor changes depending on the resistor installation method. Please install the thermal sensor in the optimum position according to the customer's design standards, or use our regenerative option having built-in thermal sensor (MR-RB65, 66, 67).
Servo amplifier
Regenerative resistor
MR-J2S-11KB GRZG400-2
MR-J2S-15KB GRZG400-1
MR-J2S-22KB GRZG400-0.8
Regenerative power [W]
Normal Cooling
500
850
850
800
1300
1300
Resistance
[ ]
8
5
4
Number of resistors
4
5
5
12 - 6
12. OPTIONS AND AUXILIARY EQUIPMENT
(d) MR-J2S-11KB-PX to MR-J2S-22KB-PX (when using the regenerative option)
The MR-J2S-11KB-PX to MR-J2S-22KB-PX servo amplifiers are not supplied with regenerative resistors. When using any of these servo amplifiers, always use the MR-RB65, 66 or 67 regenerative option.
The MR-RB65, 66 and 67 are regenerative options that have encased the GRZG400-2
Ω
, GRZG400-
1
Ω
and GRZG400-0.8
Ω
, respectively. When using any of these regenerative options, make the same parameter setting as when using the GRZG400-2
Ω
, GRZG400-1
Ω
or GRZG400-0.8
Ω
(supplied regenerative resistors or regenerative option is used with 11kW or more servo amplifier).
Cooling the regenerative option with cooling fans improves regenerative capability.
The G3 and G4 terminals are for the thermal sensor. G3-G4 is opened when the regenerative option overheats abnormally.
Servo amplifier
Do not remove the short bar.
Regenerative option
P
1
P
C
(Note)
P
C
G3
G4
Configure up a circuit which shuts off main circuit power when thermal sensor operates.
Note. Specifications of contact across G3-G4
Maximum voltage :120V AC/DC
Maximum current :0.5A/4.8VDC
Maximum capacity : 2.4VA
Servo amplifier
MR-J2S-11KB-PX
MR-J2S-15KB-PX
MR-J2S-22KB-PX
Regenerative option model
MR-RB65
MR-RB66
MR-RB67
Resistance
[ ]
8
5
4
Regenerative power [W]
Without cooling fans
With cooling fans
500
850
850
800
1300
1300
When using cooling fans, install them using the mounting holes provided in the bottom of the regenerative option. In this case, set "0E " in parameter No. 2.
Top
MR-RB65 66 67
Bottom
TE1
2 cooling fans
(92 92, minimum air flow: 1.0m
3 )
Mounting screw
4-M3(0.118)
TE
G4 G3 C P
12 - 7
12. OPTIONS AND AUXILIARY EQUIPMENT
(5) Outline drawing
(a) MR-RB032 MR-RB12
LB
LA
6 (0.24) mounting hole
MR-RB
[Unit: mm (in)]
TE1
G3
G4
P
C
6 (0.24)
7 (0.28)
10
(0.39)
90 (3.54)
100 (3.94)
17
(0.67)
5 (0.20)
20
(0.79)
(b) MR-RB30 MR-RB31 MR-RB32
318 (12.5)
335 (13.2)
12 - 8
LC
LD
1.6 (0.06)
TE1
Terminal block
G3
G4
P
C
Terminal screw: M3
Tightening torque:
0.5 to 0.6 [N m](4 to 5 [lb in])
Mounting screw
Screw size: M5
Tightening torque:
3.24 [N m](28.676 [lb in])
Regenerative option
MR-RB032
MR-RB12
Variable dimensions Mass
LA LB LC LD [kg] [lb]
30
(1.18)
40
(1.58)
15
(0.59)
15
(0.59)
119
(4.69)
169
(6.65)
99
(3.9)
149
(5.87)
0.5 1.1
1.1 2.4
[Unit: mm (in)]
Terminal block
P
C
G3
G4
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [Ib in])
Mounting screw
Screw: M6
Tightening torque: 5.4 [N m] (47.79 [Ibi n])
Regenerative option
MR-RB30
MR-RB31
MR-RB32
Mass [kg] (Ib)
2.9 (6.4)
12. OPTIONS AND AUXILIARY EQUIPMENT
(c) MR-RB50 MR-RB51
49
(1.93)
82.5
(3.25)
Fan mounting screw
(2-M3 screw)
On opposite side
7 14 slot
Wind blows in the arrow direction
[Unit: mm (in)]
Terminal block
P
C
G3
G4
Terminal screw: M4
Tightening torque: 1.2 [N m]
(10.6 [Ib in])
Mounting screw
Screw: M6
Tightening torque: 5.4 [N m]
(47.79 [Ib in])
Regenerative option
MR-RB50
MR-RB51
Mass [kg] (Ib)
5.6 (12.3)
2.3
(0.09)
200 (7.87)
217 (8.54)
17
(0.67)
12
(0.47)
7 (0.28)
108 (4.25)
120 (4.72)
Approx.30 (1.18)
8 (0.32)
(d) MR-RB65 MR-RB66 MR-RB67
[Unit: mm (in)]
2- 10 ( 0.39) mounting hole
15 (0.59)
TE1
G4G3 CP
10 (0.39)
230 (9.06)
260 (10.2)
230 (9.06)
2.3 (0.09)
215 (8.47)
4-M3 screw
Cooling fan mounting
Terminal block
G4 G3 C P
Terminal screw: M5
Tightening torque: 2.0 [N m](17 [lb in])
Mounting screw
Screw size: M8
Tightening torque: 13.2 [N m](116.83 [lb in])
Regenerative option
MR-RB65
MR-RB66
MR-RB67
Mass
[kg]
10
11
11
(lb)
22.0
24.3
24.3
82.5 82.5
(3.25) (3.25)
(e) GRZG400-2 GRZG400-1 GRZG400-0.8 (standard accessories)
10 ( 5.5) (2.4) [Unit: mm (in)]
384
410
40
12 - 9
Mounting screw
Screw size: M8
Tightening torque: 13.2 [N m](116.83 [lb in])
12. OPTIONS AND AUXILIARY EQUIPMENT
12.1.2 FR-BU2 brake unit
POINT
The brake unit and resistor unit of other than 200V class are not applicable to the servo amplifier. Combination of different voltage class units and servo amplifier cannot be used.
Install a brake unit and a resistor unit on a flat surface vertically. When the unit is installed horizontally or diagonally, the heat dissipation effect diminishes.
Temperature of the resistor unit case rises to higher than 100 . Keep cables and flammable materials away from the case.
Ambient temperature condition of the brake unit is between 10 (14 ) and 50 (122 ). Note that the condition is different from the ambient temperature condition of the servo amplifier (between 0 (32 ) and
55 (131 )).
Configure the circuit to shut down the power-supply with the alarm output of the brake unit and resistor unit under abnormal condition.
Use the brake unit with a combination indicated in (1) of this section.
For executing a continuous regenerative operation, use FR-RC power regeneration converter or FR-CV power regeneration common converter.
Brake unit and regenerative options (Regenerative resistor) cannot be used simultaneously.
Connect the brake unit to the bus of the servo amplifier. As compared to the MR-RB regenerative option, the brake unit can return larger power. Use the brake unit when the regenerative option cannot provide sufficient regenerative capability.
When using the brake unit, set the parameter No.2 of the servo amplifier to " 01".
When using the brake unit, always refer to the FR-BU2-(H) Brake Unit Instruction Manual.
(1) Selection
Use a combination of servo amplifier, brake unit and resistor unit listed below.
Brake unit
FR-BU2-15K
Resistor unit
FR-BR-15K
Number of connected units
1
Permissible continuous power [kW]
0.99
Total resistance
[ ]
8
FR-BU2-30K
FR-BU2-55K
FR-BR-30K
FR-BR-55K
MT-BR5-55K
1
1
1
1.99
3.91
5.5
4
2
2
Applicable servo amplifier
MR-J2S-350B
MR-J2S-500B
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
MR-J2S-22KB
12 - 10
12. OPTIONS AND AUXILIARY EQUIPMENT
(2) Brake unit parameter setting
Normally, when using the FR-BU2, changing parameters is not necessary. Whether a parameter can be changed or not is listed below.
No.
Parameter
Name
0 Brake mode switchover
1 Monitor display data selection
2 Input terminal function selection 1
3 Input terminal function selection 2
77 Parameter write selection
78 Cumulative energization time carrying-over times
CLr Parameter clear
ECL Alarm history clear
C1 For manufacturer setting
Change possible/ impossible
Remarks
Impossible Do not change the parameter.
Possible Refer to the FR-BU2-(H) Brake Unit
Instruction Manual.
Impossible Do not change the parameter.
(3) Connection example
POINT
Connecting PR terminal of the brake unit to P terminal of the servo amplifier results in brake unit malfunction. Always connect the PR terminal of the brake unit to the PR terminal of the resistor unit.
(a) Combination with FR-BR resistor unit
(Note 7) Servo motor thermal relay
RA2
ALM
RA1
EM1
(Note 1)
Power supply
NFB MC
OFF
ON
MC
MC
SK
L
1
L
2
L
3
L
11
L
21
Servo amplifier
(Note 3)
P
1
P
D
P
(Note 9)
N
C
CN3
20
3
10
5
13
EM1
SG
VDD
COM
ALM
(Note 8)
(Note 2)
(Note 10)
P
PR
FR-BR
(Note 5)
TH1
TH2
FR-BU2
PR
P/
N/
(Note 4)
BUE
SD
MSG
SD
A
B
C
(Note 6)
12 - 11
12. OPTIONS AND AUXILIARY EQUIPMENT
Note 1. For power supply specifications, refer to section 1.3.
2. For the servo amplifier of 5k and 7kW, always disconnect the lead of built-in regenerative resistor, which is connected to the P and C terminals. For the servo amplifier of 11k to 22kW, do not connect a supplied regenerative resistor to the P and C terminals.
3. For the servo amplifier of 11k to 22kW, always connect P
1
and P (Factory-wired). When using the power factor improving DC reactor, refer to section 12.2.4.
4. Connect the P/ and N/ terminals of the brake unit to a correct destination. Wrong connection results in servo amplifier and brake unit malfunction.
5. Contact rating 1b contact, 110VAC_5A/220VAC_3A
Normal condition TH1-TH2 is conducting. Abnormal condition TH1-TH2 is not conducting.
6. Contact rating 230VAC_0.3A/30VDC_0.3A
Normal condition B-C is conducting/A-C is not conducting. Abnormal condition B-C is not conducting/A-C is conducting.
7. For the servo amplifier of 11kW or more, connect the thermal relay censor of the servo amplifier.
8. For the servo amplifier of 3.5kW, always disconnect the wiring between P and D terminals.
9. Do not connect more than one cable to each P and N terminals of the servo amplifier.
10. Make sure to connect BUE and SD (Factory-wired).
(b) Combination with MT-BR5 resistor unit
Servo motor thermal relay
RA2
ALM
RA1
EM1
OFF
ON
RA3
MC
MC
SK
(Note 1)
Power supply
NFB MC
L
1
L
2
L
3
L
11
L
21
Servo amplifier
CN3
20
3
10
5
13
EM1
SG
VDD
COM
ALM
C (Note 8)
P
1
P
(Note 2)
(Note 6)
N
(Note 7)
P
PR
MT-BR5
(Note 4)
TH1
TH2
FR-BU2
PR
P/
N/
(Note 3)
BUE
SD
MSG
SD
A
B
C
(Note 5)
SK
RA3
Note 1. For power supply specifications, refer to section 1.3.
2. Make sure to connect P
1
and P (Factory-wired). When using the power factor improving DC reactor, refer to section 12.2.4.
3. Connect the P/ and N/ terminals of the brake unit to a correct destination. Wrong connection results in servo amplifier and brake unit malfunction.
4. Contact rating 1a contact, 110VAC_5A/220VAC_3A
Normal condition TH1-TH2 is not conducting. Abnormal condition TH1-TH2 is conducting.
5. Contact rating 230VAC_0.3A/30VDC_0.3A
Normal condition B-C is conducting/A-C is not conducting. Abnormal condition B-C is not conducting/A-C is conducting.
6. Do not connect more than one cable to each P and N terminals of the servo amplifier.
7. Make sure to connect BUE and SD (Factory-wired).
8. For the servo amplifier of 22kW, do not connect a supplied regenerative resistor to the P and C terminals.
12 - 12
12. OPTIONS AND AUXILIARY EQUIPMENT
(c) Precautions for wiring
The cables between the servo amplifier and the brake unit, and between the resistor unit and the brake unit should be as short as possible. Always twist the cable longer than 5m (twist five times or more per one meter). Even when the cable is twisted, the cable should be less than 10m. Using cables longer than 5m without twisting or twisted cables longer than 10m, may result in the brake unit malfunction.
Servo amplifier Servo amplifier
Brake unit Resistor unit Brake unit Resistor unit
P
N
P
N
P
PR
P
PR
P
N
Twist P
N
P
PR
Twist P
PR
5m or less 5m or less 10m or less 10m or less
(d) Cables
For the brake unit, HIV cable (600V grade heat-resistant PVC insulated wire) is recommended.
a) Main circuit terminal
N/ P/ PR
Terminal block
Brake unit
FR-BU2-15K
FR-BU2-30K
FR-BU2-55K
Main circuit terminal screw size
M4
M5
M6
Crimping terminal
N/ , P/ ,
PR,
5.5-4
5.5-5
14-6
Tightening torque
[N m]
([lb in])
1.5 (13.3)
2.5 (22.1)
4.4 (38.9)
Cable size
N/ , P/ , PR,
HIV cables, etc. [mm 2 ]
3.5
5.5
14
AWG
12
10
6 b) Control circuit terminal
POINT
Undertightening can cause a cable disconnection or malfunction.
Overtightening can cause a short circuit or malfunction due to damage to the screw or the brake unit.
A B C
PC BUE SD
RES
Jumper
SD MSG MSG SD SD
Sheath
Core
6mm
Terminal block
Wire the stripped cable after twisting to prevent the cable from becoming loose. In addition, do not solder it.
Screw size: M3
Tightening torque: 0.5N m to 0.6N m
Cable size: 0.3mm
2
to 0.75 mm
2
Screw driver: Small flat-blade screwdriver
(Tip thickness: 0.4mm/Tip width 2.5mm)
12 - 13
12. OPTIONS AND AUXILIARY EQUIPMENT
(e) Crimping terminals for P and N terminals of servo amplifier
POINT
Always use recommended crimping terminals or equivalent since some crimping terminals cannot be installed depending on the size.
Servo amplifier
MR-J2S-350B
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
Brake unit
FR-BU2-15K
FR-BU2-15K
FR-BU2-30K
FR-BU2-30K
FR-BU2-30K
FR-BU2-55K
FR-BU2-30K
FR-BU2-55K
FR-BU2-55K
Number of connected units
1
1
1
1
1
1
1
1
1
Crimping terminal (Manufacturer)
FVD5.5-S4
(Japan Solderless Terminal)
FVD5.5-6(Japan Solderless Terminal)
FVD14-6(Japan Solderless Terminal)
FVD5.5-6(Japan Solderless Terminal)
FVD14-6(Japan Solderless Terminal)
FVD14-8(Japan Solderless Terminal)
Note. Symbols in the applicable tool field indicate the following applicable tools.
(Note)
Applicable tool b b a a a b
(4) Outline dimension drawings
(a) FR-BU2 brake unit
Symbol a b
Applicable tool
Body
Head
Dice
YNT-1210S
YF-1 E-4
YNE-38
DH-112 DH-122
Manufacturer
Japan Solderless
Terminal
[Unit: mm]
FR-BU2-15K
5 hole
(Screw size: M4)
6 56
68
5
6
Rating plate
18.5
52
132.5
62
4
12 - 14
12. OPTIONS AND AUXILIARY EQUIPMENT
FR-BU2-30K
2- 5 hole
(Screw size: M4)
6 96
108
FR-BU2-55K
2- 5 hole
(Screw size: M4)
5
6
Rating plate
18.5
52
129.5
59
5
6 158
170
5
6
Rating plate
18.5
52
142.5
72
5
12 - 15
12. OPTIONS AND AUXILIARY EQUIPMENT
(b) FR-BR resistor unit
2 C
[Unit: mm]
(Note)
Control circuit terminal
Main circuit terminal
(Note)
Approx. 35
C
W1 1
C
Approx. 35
For FR-BR-55K, a hanging bolt is placed on two locations (Indicated below).
Hanging bolt
204
W 5
(c) MT-BR5- (H) resistor unit
Note. Ventilation ports are provided on both sides and the top. The bottom is open.
Resistor unit
FR-BR-15K
FR-BR-30K
FR-BR-55K
W W1 H H1 H2 H3 D D1 C
170 100 450 410 20 432 220 3.2
6
340 270 600 560 20 582 220 4 10
480 410 700 620 40 670 450 3.2
12
Approximate mass
[kg] ([lb])
15 (33.1)
30 (66.1)
70 (154)
NP
Resistor unit
MT-BR5-55K
[Unit: mm]
Resistance value
2.0
Approximate mass
[kg] ([lb])
50 (110)
M6
M4
193
37 60
480
510
10 21
189
4 15 mounting hole 7.5
75 300
450
75
7.5
12 - 16
12. OPTIONS AND AUXILIARY EQUIPMENT
12.1.3 Power regeneration converter
When using the power regeneration converter, set " 01" in parameter No.2.
(1) Selection
The converters can continuously return 75% of the nominal regenerative power. They are applied to the servo amplifiers of the MR-J2S-500B to MR-J2S-22KB.
Power regeneration converter
FR-RC-15K
FR-RC-30K
FR-RC-55K
Nominal regenerative power
(kW)
Servo amplifier
15
30
55
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
500
300
200
100
50
30
20
0 50 75 100
Nominal regenerative power (%)
150
12 - 17
12. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection example
(Note 5)
Power supply
NFB
FR-RC
B C
RA2
Servo amplifier
L
11
L
21
(Note 3) Power factor improving reactor
MC FR-BAL
L
1
L
2
L
3
VDD
COM
EM1
SG
Ready
RDY
N/
SE
N
R/L
1
S/L
2
T/L
3
(Note 2)
C
P/
P P
1
(Note 4)
5m(16.4ft) or less
RDY output
A
B
C
B
C
Alarm output
EM1
RX
R
SX
S
(Note 1)
Phase detection terminals
TX
T
Power regeneration converter FR-RC
Operation ready
OFF
ON
MC MC
SK
Note 1. When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain removed, the
FR-RC will not operate.
2. When using servo amplifiers of 5kW and 7kW, always remove the lead of built-in regenerative resistor connected to P terminal and C terminal.
3. For the power factor improving reactor (FR-BAL) to be used, refer to POWER REGENERATION CONVERTER FR-RC
INSTRUCTION MANUAL (IB (NA) 67096). When using FR-BAL with the servo amplifier of 11 k to 22 kW, do not use with the power factor improving reactor (FR-BAL).
4. When using the servo amplifier of 11k to 22kW, make sure to connect P
1
and P. (Factory-wired.)
5. Refer to section 1.3 for the power supply specification.
12 - 18
12. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outside dimensions of the power regeneration converters
2- D hole
[Unit : mm(in)]
Mounting foot (removable)
Mounting foot movable
Rating plate
Front cover
Display panel window
Cooling fan
AA
A
D F
K
C
Heat generation area outside mounting dimension
Power regeneration converter
FR-RC-15K
FR-RC-30K
FR-RC-55K
A AA B BA C D E EE K F
270
(10.6)
340
(13.4)
480
(18.9)
200
(7.87)
270
(10.6)
410
(16.1)
450
(17.7)
600
(23.6)
700
(27.6)
432
(17.0)
582
(22.9)
670
(26.4)
195
(7.68)
195
(7.68)
250
(9.84)
10
(0.39)
10
(0.39)
12
(0.47)
10
(0.39)
10
(0.39)
15
(0.59)
8
(0.32)
8
(0.32)
15
(0.59)
3.2
(0.13)
3.2
(0.13)
3.2
(0.13)
87
(3.43)
90
(3.54)
135
(5.32)
Approx.
mass [kg(Ib)]
19
(41.9)
31
(68.3)
55
(121)
(4) Mounting hole machining dimensions
When the power regeneration converter is fitted to a totally enclosed type box, mount the heat generating area of the converter outside the box to provide heat generation measures. At this time, the mounting hole having the following dimensions is machined in the box.
(AA)
(Mounting hole)
(2- D hole)
Model
FR-RC-15K
FR-RC-30K
FR-RC-55K
A
260
(10.2)
330
(13.0)
470
(18.5)
B
412
(16.2)
562
(22.1)
642
(25.3)
D
10
(0.39)
10
(0.39)
12
(0.47)
[Unit : mm(in)]
AA
200
(7.87)
270
(10.6)
410
(16.1)
BA
432
(17.0)
582
(22.9)
670
(26.4) a
12 - 19
12. OPTIONS AND AUXILIARY EQUIPMENT
12.1.4 External dynamic brake
POINT
Configure up a sequence which switches off the contact of the brake unit after (or as soon as) it has turned off the servo on signal at a power failure or failure.
For the braking time taken when the dynamic brake is operated, refer to section 13.3.
The brake unit is rated for a short duration. Do not use it for high duty.
(1) Selection of dynamic brake
The dynamic brake is designed to bring the servo motor to a sudden stop when a power failure occurs or the protective circuit is activated, and is built in the 7kW or less servo amplifier. Since it is not built in the 11kW or more servo amplifier, purchase it separately if required. Set " 1 " in the parameter
No. 2.
Servo amplifier
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
Dynamic brake
DBU-11K
DBU-15K
DBU-22K
12 - 20
12. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection example
(Note 4)
Power supply
NFB
(Note 1) EM1
Operation-ready
ON
OFF
MC
MC
SK
MC
Servo amplifier
CON2
15 VDD
18
4
COM
DB
(Note 3)
L
1
L
2
L
3
L
11
L
21
P
P
1
U
V
W
CON2
2
1
Plate
EM1
SG
SD
RA1
EM1
(Note 2)
14 13 U V W
W
E
U
V
Servo motor
M
RA1 a b
Dynamic brake
Note 1. Configure up the circuit to switch power off in the external sequence at servo alarm occurrence.
2. Terminals 13, 14 are normally open contact outputs. If the dynamic brake is seized, terminals 13, 14 will open.
Therefore, configure up an external sequence to prevent servo-on.
3. When using the servo amplifier of 11k to 22kW, make sure to connect P
1
and P. (Factory-wired.) When using the power factor improving DC reactor, refer to section 12.2.4.
4. Refer to section 1.3 for the power supply specification.
Coasting
Servo motor rotation
Present
Alarm
Base
Absent
ON
OFF
RA1
ON
OFF
Dynamic brake
Invalid
Valid
Forced stop
(EM1)
Short
Open
Dynamic brake a. Timing chart at alarm occurrence
Coasting
Dynamic brake b. Timing chart at forced stop (EM1) validity
12 - 21
12. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outline dimension drawing
5
(0.2)
[Unit: mm]
([Unit: in])
D
(0.2)5
100(3.94)
C
D G
F
2.3(0.09)
Terminal block
E
(GND) a b 13 14
Screw : M3.5
Tightening torque: 0.8 [N m](7 [lb in])
Dynamic brake
DBU-11K
DBU-15K, 22K
U V W
Screw : M4
Tightening torque: 1.2 [N m](10.6 [lb in])
A
200
(7.87)
250
(9.84)
B
190
(7.48)
238
(9.37)
C
140
(5.51)
150
(5.91)
D
20
(0.79)
25
(0.98)
E
5
(0.2)
6
(0.24)
F
170
(6.69)
235
(9.25)
G
163.5
(6.44)
228
(8.98)
Mass
[kg]([Ib])
2 (4.41)
6 (13.23)
Connection wire [mm
2
]
5.5
5.5
12 - 22
12. OPTIONS AND AUXILIARY EQUIPMENT
12.1.5 Cables and connectors
(1) Cable make-up
The following cables are used for connection with the servo motor and other models.
The broken line areas in the diagram are not options.
Servo system controller Servo amplifier Servo amplifier
(Note 1)
Bus cable
CN1A CN1B
(Note 1)
Connector set
CN2 CN3
(Note 1)
Bus cable
(Note 1)
CN1A CN1B
13)
Termination connector
CN2 CN3
15)
Personal computer
14)
22)
(Note 2)
CON2 CN4
23) (Note 2)
3) 4) 5)
HA-LFS
To U, V, W
20) 21)
1) 2)
HC-KFS
HC-MFS
HC-UFS 3000r/min
7) 8)
16) 17) 18)
3) 4) 5)
19)
6)
HC-SFS
HC-RFS
HC-UFS 2000r/min
7) 8)
Note 1. The bus cable used with the SSCNET depends on the preceding or subsequent controller or servo amplifier connected.
Refer to the following table and choose the bus cable.
MR-J2-03B5
12) Connector set:MR-J2CN1 QD75M
Motion controller
Q172CPU(N)
Q173CPU(N)
A motion
MR-J2S- B
MR-J2-03B5
Maintenance junction card
MR-J2S- B
10) Bus cable :MR-J2HBUS M
24) Bus cable :Q172J2BCBL M(-B)
25) Bus cable :Q173J2B CBL M
9) Bus cable :MR-J2HBUS M-A
10) Bus cable :MR-J2HBUS M
11) Connector set:MR-J2CN1-A
12) Connector set:MR-J2CN1
2. The cable and connector are used for only servo amplifier of 11kW or more.
12 - 23
12. OPTIONS AND AUXILIARY EQUIPMENT
No.
Product Model
1) Standard encoder cable
MR-JCCBL M-L
Refer to (2) in this section.
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Description
Housing: 1-172161-9
Connector pin: 170359-1
(AMP or equivalent)
Cable clamp: MTI-0002
(Toa Electric Industry)
2) Long flexing life encoder cable
3) Standard encoder cable
MR-JCCBL M-H
Refer to (2) in this section.
MR-JHSCBL M-L
Refer to (2) in this section.
4) Long flexing life encoder cable
5) IP65-compliant encoder cable
MR-JHSCBL M-H
Refer to (2) in this section.
MR-ENCBL M-H
Refer to (2) in this section.
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Plug: D/MS3106B20-29S
Cable clamp: D/MS3057-12A
(DDK)
Plug: D/MS3106A20-29S (D190)
Cable clamp: CE3057-12A-3-D
Back shell: CE02-20BS-D
(DDK)
Application
Standard flexing life
IP20
6) Encoder connector set
MR-J2CNM Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Housing: 1-172161-9
Connector Pin: 170359-1
(AMP or equivalent)
Cable clamp: MTI-0002
(Toa Electric Industry)
Long flexing life
IP20
Standard flexing life
IP20
Long flexing life
Long flexing life
IP65
IP67
Not oilresistant.
IP20
7) Encoder connector set
MR-J2CNS Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Plug: D/MS3106B20-29S
Cable clamp: D/MS3057-12A
(DDK)
IP20
8) Encoder connector set
MR-ENCNS Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Plug: D/MS3106A20-29S (D190)
Cable clamp: CE3057-12A-3-D
Back shell: CE02-20BS-S-D
(DDK)
IP65
IP67
9) Bus cable MR-J2HBUS M-A
Refer to (4) in this section.
Connector: PCR-S20FS
Case: PCR-LS20LA1
(Honda Tsushin)
10) Bus cable MR-J2HBUS M
Refer to (4) in this section.
Connector: 10120-6000EL
Shell kit: 10320-3210-000
(3M or equivalent)
Connector: 10120-6000EL
Shell kit: 10320-3210-000
(3M or equivalent)
Connector: 10120-6000EL
Shell kit: 10320-3210-000
(3M or equivalent)
12 - 24
12. OPTIONS AND AUXILIARY EQUIPMENT
No.
Product
11) Connector set
Model
MR-J2CN1-A
Refer to (4) in this section
Connector: PCR-S20FS
Shell kit: PCR-LS20LA1
(Honda Tsushin)
Description
Connector: 10120-3000PL
Shell kit: 10320-52F0-008
(3M or equivalent)
Application
12) Control signal connector set
MR-J2CN1 Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
13) Termination connector
14) Maintenance junction card
15) Communication cable
MR-A-TM
MR-J2CN3TM Refer to section 12.1.6.
MR-CPCATCBL3M
Refer to (3) in this section.
Connector: 10120-6000EL
Shell kit: 10320-3210-000
(3M or equivalent)
16) Power supply connector set
17) Power supply connector set
18) Power supply connector set
19) Brake connector set
20) Power supply connector set
MR-PWCNS1
Refer to the Servo
Motor Instruction
Manual.
MR-PWCNS2
Refer to the Servo
Motor Instruction
Manual.
MR-PWCNS3
Refer to the Servo
Motor Instruction
Manual.
MR-BKCN
Refer to the Servo
Motor Instruction
Manual.
MR-PWCNK1
21) Power supply connector set
22) Connector Set
23) Monitor cable
MR-PWCNK2
MR-J2CMP2
MR-H3CBL1M
Qty: 2 each
Connector: DE-9SF-N
Case: DE-C1-J6-S6
(Japan Aviation Electronics)
For connection with PC-ATcompatible personal computer
Plug: CE05-6A22-23SD-D-BSS
Cable clamp:CE3057-12A-2-D
(DDK)
Plug: CE05-6A24-10S1D-D-BSS
Cable clamp: CE3057-16A-2-D
(DDK)
Plug: CE05-6A32-17SD-D-BSS
Cable clamp: CE3057-20A-1-D
(DDK)
Plug: D/MS3106A10SL-4S (D190) (DDK)
Cable connector: YS010-5-8 (Daiwa Dengyo)
EN
Standardcompliant
IP65 IP67
EN
Standardcompliant
IP65 IP67
IP20 Plug: 5559-04P-210
Terminal: 5558PBT3L (For AWG16)(6 pcs.)
(Molex)
Plug: 5559-06P-210
Terminal: 5558PBT3L (For AWG16)(8 pcs.)
(Molex)
Connector: 10126-3000PE
Shell kit: 10326-52F0-008
(3M or equivalent)
Servo amplifier side connector
(Tyco Electronics)
Housing: 171822-4
For motor with brake
IP20
12 - 25
12. OPTIONS AND AUXILIARY EQUIPMENT
No.
Product
24) Bus cable
25) Bus cable
Model
Q172J2BCBL M
(-B)
Refer to (4) in this section
Connector: HDR-E14MG1
Shell kit: HDR-E14LPA5
(Honda Tsushin)
Description
Connector: 10120-6000EL
Shell kit: 10320-3210-000
(3M or equivalent)
(Note)
Q173J2B CBL M
Refer to (4) in this section
Socket: HCN2-2.5S-2
Terminal: HCN2-2.5S-D-B
(Hirose Electric)
Note. When using the battery unit Q170BAT, use the
Q172J2BCBL M-B.
Connector: HDR-E26MG1
Shell kit: HDR-E26LPA5
(Honda Tsushin)
Connector: 10120-6000EL
Shell kit: 10320-3210-000
(3M or equivalent)
Application
12 - 26
12. OPTIONS AND AUXILIARY EQUIPMENT
(2) Encoder cable
CAUTION
If you have fabricated the encoder cable, connect it correctly.
Otherwise, misoperation or explosion may occur.
POINT
The encoder cable is not oil resistant.
Refer to section 11.4 for the flexing life of the encoder cable.
When the encoder cable is used, the sum of the resistance values of the cable used for P5 and the cable used for LG should be within 2.4 .
When soldering the wire to the connector pin, insulate and protect the connection portion using heat-shrinkable tubing.
Generally use the encoder cable available as our options. If the required length is not found in the options, fabricate the cable on the customer side.
(a) MR-JCCBL M-L MR-JCCBL M-H
These encoder cables are used with the HC-KFS HC-MFS HC-UFS3000r/min series servo motors.
1) Model explanation
Model: MR-JCCBL M-
Symbol
L
H
Specifications
Standard flexing life
Long flexing life
Symbol (Note) Cable length [m(ft)]
30
40
50
2
5
10
20
2 (6.56)
5 (16.4)
10 (32.8)
20 (65.6)
30 (98.4)
40 (131.2)
50 (164.0)
Note. MR-JCCBL M-H has no 40(131.2ft)
and 50m(164.0ft) sizes.
2) Connection diagram
The signal assignment of the encoder connector is as viewed from the pin side. For the pin assignment on the servo amplifier side, refer to section 3.2.1.
Servo amplifier
Encoder cable supplied to servo motor
Encoder connector
Encoder cable
(option or fabricated)
Servo motor
Encoder connector
1-172169-9 (Tyco Electronics)
CN2
50m(164.0ft) max.
30cm
(0.98ft)
Encoder
1 2 3
MR MRR BAT
4 5 6
MD MDR
7
P5
8 9
LG SHD
12 - 27
12. OPTIONS AND AUXILIARY EQUIPMENT
P5
LG
P5
LG
P5
LG
MR-JCCBL2M-L
MR-JCCBL5M-L
MR-JCCBL2M-H
MR-JCCBL5M-H
Drive unit side Encoder side
19
11
20
12
18
2
7
MR-JCCBL10M-L to
MR-JCCBL30M-L
Drive unit side
P5
LG
P5
LG
P5
LG
19
11
20
12
18
2
Encoder side
7
MR
MRR
7
17
MD 6
MDR 16
BAT
LG
9
1
8
1
2
4
5
3
MR
MRR
7
17
MD 6
MDR 16
BAT
LG
9
1
(Note) (Note)
SD Plate 9 SD Plate 9
Note. Always make connection for use in an absolute position detection system.
This wiring is not needed for use in an incremental system.
8
1
2
4
5
3
Drive unit side
P5
LG
P5
LG
P5
LG
19
11
20
12
18
2
MR-JCCBL10M-H to
MR-JCCBL50M-H
Encoder side
7
MR
MRR
MD
MDR 16
BAT
LG
SD
7
17
6
9
1
Plate
(Note)
8
1
2
4
5
3
9
When fabricating an encoder cable, use the recommended wires given in section 12.2.1 and the
MR-J2CNM connector set for encoder cable fabrication, and fabricate an encoder cable as shown in the following wiring diagram. Referring to this wiring diagram, you can fabricate an encoder cable of up to 50m(164.0ft) length including the length of the encoder cable supplied to the servo motor.
When the encoder cable is to be fabricated by the customer, the wiring of MD and MDR is not required.
Refer to chapter 3 of the servo motor instruction manual and choose the encode side connector according to the servo motor installation environment.
P5
LG
P5
LG
P5
LG
For use of AWG22
Drive unit side
(3M)
Encoder side
19
11
20
12
18
2
7
MR
MRR
7
17
8
1
2
BAT
LG
9
1
3
(Note)
SD Plate 9
Note. Always make connection for use in an absolute position detection system.
This wiring is not needed for use in an incremental system.
12 - 28
12. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-JHSCBL M-L MR-JHSCBL M-H MR-ENCBL M-H
These encoder cables are used with the HC-SFS HC-RFS HC-UFS2000r/min series servo motors.
1) Model explanation
Model: MR-JHSCBL M-
Symbol
L
H
Specifications
Standard flexing life
Long flexing life
Symbol (Note) Cable length [m(ft)]
30
40
50
2
5
10
20
2 (6.56)
5 (16.4)
10 (32.8)
20 (65.6)
30 (98.4)
40 (131.2)
50 (164.0)
Note. MR-JHSCBL M-L has no 40(131.2ft)
and 50m(164.0ft) sizes.
Model: MR-ENCBL M-H
Long flexing life
Symbol
30
40
50
2
5
10
20
Cable length [m(ft)]
2 (6.56)
5 (16.4)
10 (32.8)
20 (65.6)
30 (98.4)
40 (131.2)
50 (164.0)
2) Connection diagram
For the pin assignment on the servo amplifier side, refer to section 3.2.1.
Servo amplifier
Encoder cable
Encoder connector
Servo motor
(Optional or fabricated)
Encoder connector
CN2 Encoder
L
K
J
H
M
T
S
N
A B
P
G
R
C
D
E
F
50m(164.0ft) max.
Pin Signal
A MD
B MDR
C MR
D MRR
E
F BAT
G LG
H
J
N
P
R
S
T
Pin Signal
K
L
M
SHD
LG
P5
12 - 29
12. OPTIONS AND AUXILIARY EQUIPMENT
MR-JHSCBL2M-L
MR-JHSCBL5M-L
MR-JHSCBL2M-H
MR-JHSCBL10M-L to
MR-JHSCBL30M-L
MR-JHSCBL5M-H
MR-ENCBL2M-H
MR-ENCBL5M-H
Servo amplifier side Encoder side Servo amplifier side
MR-JHSCBL10M-H to
MR-JHSCBL50M-H
MR-ENCBL10M-H to
MR-ENCBL50M-H
Encoder side Servo amplifier side Encoder side
P5
LG
P5
LG
MR
MRR
P5
LG
BAT
LG
SD
17
18
2
9
1
19
11
20
12
7
S
R
C
D
(Note 1)
Plate N
(Note@2) Use of AWG24
(Less than 10m(32.8ft))
F
G
P5
LG
P5
LG
P5
LG
MR
MRR
BAT
LG
SD
19
11
20
12
18
2
7
17
9
1
S
R
C
D
F
G
(Note 1)
Plate N
Use of AWG22
(10m(32.8ft) to 50m(164.0ft))
P5
LG
P5
LG
P5
LG
MR
MRR
BAT
LG
SD
19
11
20
12
18
2
7
17
9
1
S
R
C
D
F
G
(Note 1)
Plate N
Use of AWG24
(10m(32.8ft) to 50m(164.0ft))
Note 1. This wiring is required for use in the absolute position detection system. This wiring is not needed for use in the incremental system.
2. AWG28 can be used for 5m(16.4ft) or less.
When fabricating an encoder cable, use the recommended wires given in section 12.2.1 and the
MR-J2CNS connector set for encoder cable fabrication, and fabricate an encoder cable in accordance with the optional encoder cable wiring diagram given in this section. You can fabricate an encoder cable of up to 50m(164.0ft) length.
Refer to chapter 3 of the servo motor instruction guide and choose the encode side connector according to the servo motor installation environment.
12 - 30
12. OPTIONS AND AUXILIARY EQUIPMENT
(3) Communication cable
POINT
This cable may not be used with some personal computers. After fully examining the signals of the RS-232C connector, refer to this section and fabricate the cable.
(a) Model definition
Model: MR-CPCATCBL3M
Cable length 3[m](10[ft])
(b) Connection diagram
MR-CPCATCBL3M
Personal computer side
TXD
RXD
GND
RTS
CTS
DSR
DTR
7
8
6
4
3
2
5
D-SUB9 pins
Servo amplifier side
Plate
2
1
12
11
FG
RXD
LG
TXD
LG
Half-pitch 20 pins
When fabricating the cable, refer to the connection diagram in this section.
The following must be observed in fabrication.
1) Always use a shielded, multi-core cable and connect the shield with FG securely.
2) The optional communication cable is 3m(10ft) long. When the cable is fabricated, its maximum length is 15m(49ft) in offices of good environment with minimal noise.
12 - 31
12. OPTIONS AND AUXILIARY EQUIPMENT
(4) Bus cable
CAUTION
When fabricating the bus cable, do not make incorrect connection. Doing so can cause misoperation or explosion.
When fabricating this cable, use the recommended cable given in section 12.2.1 and fabricate it in accordance with the connection diagram shown in this section. The overall distance of the bus cable on the same bus is 30m(98.4ft).
(a) MR-J2HBUS M-A
1) Model definition
Model: MR-J2HBUS M-A
Symbol
05
1
5
Cable length [m(ft)]
0.5 (1.64)
1 (3.28)
5 (16.4)
2) Connection diagram
MR-J2HBUS M-A
PCR-S20FS (Connector)
PCR-LS20LA1(Case)
10120-6000EL(Connector)
10320-3210-000(Shell kit)
LG
LG
RD
RD*
TD
TD*
LG
LG
EMG
EMG*
14
5
15
6
16
1
11
2
12
4
1
11
2
12
4
14
5
15
7
17
SD 20 Plate
12 - 32
12. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-J2HBUS M
1) Model definition
Model: MR-J2HBUS M
Symbol
05
1
5
Cable length [m(ft)]
0.5 (1.64)
1 (3.28)
5 (16.4)
2) Connection diagram
MR-J2HBUS M
10120-6000EL(Connector)
10320-3210-000(Shell kit)
10120-6000EL(Connector)
10320-3210-000(Shell kit)
LG
LG
RD
RD*
TD
TD*
LG
LG
EMG
EMG*
BAT
6
16
7
17
14
5
15
12
3
13
4
1
11
2
8
18
9
19
10
20
6
16
7
17
14
5
15
12
3
13
4
1
11
2
8
18
9
19
10
20
SD Plate Plate
12 - 33
12. OPTIONS AND AUXILIARY EQUIPMENT
(c) Q172J2BCBL M(-B)
When using the battery unit Q170BAT, use the Q172J2BCBL M-B. For the Q170BAT, refer to the Motion Controller Q Series User's Manual (IB(NA)0300021).
1) Model definition
Model: Q172J2BCBL M-
Symbol Connection of battery unit
No
-B
No
Yes
Symbol
05
1
5
Cable length [m(ft)]
0.5 (1.64)
1 (3.28)
5 (16.4)
2) Connection diagram
Q172J2BCBL M
HDR-E14MG1(Connector)
HDR-E14-LPA5(Connector case)
10120-6000EL(Connector)
10320-3210-000(Shell kit)
TD1
TD1*
LG
LG
RD
RD*
LG
BT
EMG
EMG*
SD
10
6
13
4
1
8
2
9
3
11
Shell
14
5
9
7
2
12
1
11
4
17
Plate
RD
RD*
LG
LG
TD
TD*
LG
BT
EMG
EMG*
SD
Q172J2BCBL M-B
HDR-E14MG1(Connector)
HDR-E14-LPA5(Connector case)
10120-6000EL(Connector)
10320-3210-000(Shell kit)
TD1
TD1*
LG
LG
RD
RD*
LG
BT
EMG
EMG*
SD
1
8
2
9
3
10
6
13
4
11
Shell
2
12
1
11
4
14
5
9
7
17
Plate
RD
RD*
LG
LG
TD
TD*
LG
BT
EMG
EMG*
SD
BAT
LG
1
2
HCN2-2.5S-2(Socket)
HNC2-2.5S-D-B(Terminal)
(d) Q173J2B CBL M
1) Model definition
Model: Q173J2B CBL M
Symbol
05
1
5
Symbol
No
2
3
4
Cable length [m(ft)]
0.5 (1.64)
1 (3.28)
5 (16.4)
SSCNET line number
SSCNET1 Line
SSCNET2 Line
SSCNET3 Line
SSCNET4 Line
12 - 34
12. OPTIONS AND AUXILIARY EQUIPMENT
2) Connection diagram
Q173J2B CBL M When =4
HDR-E26MG1(Connector)
HDR-E26-LPA5(Connector case)
TD1
TD1*
LG
LG
RD1
RD1*
LG
BT
EMG12
EMG12*
16
2
15
13
1
14
3
26
6
19
10120-6000EL(Connector)
10320-3210-000(Connector case)
SSCNET1 Line
2
12
1
11
4
14
5
9
7
17
Plate
RD
RD*
LG
LG
TD
TD*
LG
BT
EMG
EMG*
SD
= No
SSCNET2 Line
TD2
TD2*
RD2
RD2*
4
17
5
18
11
4
14
5
2
12
1
9
7
17
Plate
RD
RD*
LG
LG
TD
TD*
LG
BT
EMG
EMG*
SD
SSCNET3 Line
TD3
TD3*
LG
LG
RD3
RD3*
EMG34
EMG34*
22
8
21
7
20
9
12
25
11
4
14
5
2
12
1
9
7
17
Plate
RD
RD*
LG
LG
TD
TD*
LG
BT
EMG
EMG*
SD
SSCNET4 Line
TD4
TD4*
RD4
RD4*
SD
10
23
11
24
Shell
11
4
14
5
2
12
1
9
7
17
Plate
RD
RD*
LG
LG
TD
TD*
LG
BT
EMG
EMG*
SD
= 2
= 3
= 4
12 - 35
12. OPTIONS AND AUXILIARY EQUIPMENT
12.1.6 Maintenance junction card (MR-J2CN3TM)
POINT
The MR-J2S-11KB or more allows only the relaying of signals using
CN3A/CN3C. Since TE1 cannot be used, keep it open.
(1) Usage
The maintenance junction card (MR-J2CN3TM) is designed for use when a personal computer and analog monitor outputs are used at the same time.
Servo amplifier
Bus cable
MR-J2HBUS M
Maintenance junction card (MR-J2CN3TM) Communication cable
CN3B
CN3 CN3A
CN3C
A1 A2 A3 A4 B4 B3 B2 B1 B5 B6 A5 A6
VDD COM EM1 DI MBR EMGO SG PE LG LG MO1 MO2
Forced stop Analog monitor 2
RA1
Electromagnetic brake interlock Analog monitor 1
(2) Connection diagram
CN3A
13
14
15
16
9
10
11
12
17
18
19
20
5
6
7
8
3
4
1
2
Shell
CN3B
17
18
19
20
13
14
15
16
9
10
11
12
7
8
5
6
3
4
1
2
Shell
CN3C
B4
B3
B2
B1
A1
A2
A3
A4
B5
B6
A5
A6
TE1
LG
LG
MO1
MO2
VDD
COM
EM1
DI
MBR
EMGO
SG
PE
(3) Outline drawing
[Unit: mm]
([Unit: in])
CN3A CN3B CN3C
2- 5.3(0.21)(mounting hole)
A1
B1
TE1
88(3.47)
100(3.94)
12 - 36
A6
B6
3(0.12)
41.5(1.63)
Mass: 110g(0.24Ib)
12. OPTIONS AND AUXILIARY EQUIPMENT
12.1.7 Battery (MR-BAT, A6BAT)
POINT
The revision (Edition 44) of the Dangerous Goods Rule of the
International Air Transport Association (IATA) went into effect on
January 1, 2003 and was enforced immediately. In this rule, "provisions of the lithium and lithium ion batteries" were revised to tighten the restrictions on the air transportation of batteries. However, since this battery is non-dangerous goods (non-Class 9), air transportation of 24 or less batteries is outside the range of the restrictions. Air transportation of more than 24 batteries requires packing compliant with the Packing
Standard 903. When a self-certificate is necessary for battery safety tests, contact our branch or representative. For more information, consult our branch or representative. (As of November, 2007).
Use the battery to build an absolute position detection system.
12.1.8 MR Configurator (servo configurations software)
The MR Configurator (servo configuration software) uses the communication function of the servo amplifier to perform parameter setting changes, graph display, test operation, etc. on a personal computer.
(1) Specifications
Item
Communication signal Conforms to RS-232C.
Baud rate [bps]
Monitor
Alarm
Diagnostic
Parameters
Test operation
Advanced function
File operation
Others
Description
57600, 38400, 19200, 9600
Display, high speed monitor, trend graph
Minimum resolution changes with the processing speed of the personal computer.
Display, history, amplifier data
Digital I/O, no motor rotation, total power-on time, amplifier version info, motor information, tuning data, absolute encoder data, Axis name setting.
Parameter list, turning, change list, detailed information
Jog operation, positioning operation, motor-less operation, Do forced output, program operation.
Machine analyzer, gain search, machine simulation.
Data read, save, print
Automatic demo, help display
12 - 37
12. OPTIONS AND AUXILIARY EQUIPMENT
(2) System configuration
(a) Components
To use this software, the following components are required in addition to the servo amplifier and servo motor.
Model
(Note 2)
Personal computer
OS
Display
Keyboard
Mouse
Printer
Communication cable
(Note 1) Description
IBM PC-AT compatible where the English version of Windows ®
Windows NT ® Workstation 4.0, Windows ®
95, Windows
2000 Professional, Windows ®
® 98, Windows ® Me,
XP Professional and Windows
XP Home Edition operates
Processor: Pentium ® 133MHz or more (Windows
Windows
Pentium
Pentium
®
®
®
2000 Professional)
150MHz or more (Windows
300MHz or more (Windows
Memory:16MB or more (Windows ® 95)
®
®
®
95, Windows
Me)
® 98, Windows NT
XP Professional, Windows ®
® Workstation 4.0,
XP Home Edition)
24MB or more (Windows
32MB or more (Windows
®
®
98)
Me, Windows NT
Free hard disk space: 60MB or more
Serial port used
® Workstation 4.0, Windows
128MB or more (Windows ® XP Professional, Windows ®
® 2000 Professional)
XP Home Edition)
®
Windows ® 95, Windows ® 98, Windows ®
(English version)
Me, Windows NT ® Workstation 4.0, Windows ® 2000 Professional
One whose resolution is 800 600 or more and that can provide a high color (16 bit) display.
Connectable with the above personal computer.
Connectable with the above personal computer.
Connectable with the above personal computer. Note that a serial mouse is not used.
Connectable with the above personal computer.
MR-CPCATCBL3M
When this cannot be used, refer to section 12.1.5 (3) and fabricate.
Note 1. Windows and Windows NT are the registered trademarks of Microsoft Corporation in the United State and other countries.
Pentium is the registered trademarks of Intel Corporation.
2. On some personal computers, this software may not run properly.
(b) Configuration diagram
Servo amplifier
Personal computer
Communication cable
CN3 CN2 Servo motor
To RS-232C connector
12 - 38
12. OPTIONS AND AUXILIARY EQUIPMENT
12.1.9 Power regeneration common converter
POINT
For details of the power regeneration common converter FR-CV, refer to the FR-CV Installation Guide (IB(NA)0600075).
Do not supply power to the main circuit power supply terminals (L1, L2,
L3) of the servo amplifier. Doing so will fail the servo amplifier and FR-CV.
Connect the DC power supply between the FR-CV and servo amplifier with correct polarity. Connection with incorrect polarity will fail the FR-
CV and servo amplifier.
Two or more FR-CV's cannot be installed to improve regeneration capability. Two or more FR-CV's cannot be connected to the same DC power supply line.
When using the power regeneration common converter, set parameter No. 2 to " 01".
(1) Selection
The power regeneration common converter FR-CV can be used with 750W to 22kW servo amplifiers.
There are the following restrictions on use of the FR-CV.
(a) Up to six servo amplifiers can be connected to one FR-CV.
(b) FR-CV capacity [W] Total of rated capacities [W] of servo amplifiers connected to FR-CV 2
(c) The total of used servo motor rated currents should be equal to or less than the applicable current
[A] of the FR-CV.
(d) Among the servo amplifiers connected to the FR-CV, the servo amplifier of the maximum capacity should be equal to or less than the maximum connectable capacity [W].
The following table lists the restrictions.
Item
Maximum number of connected servo amplifiers
Total of connectable servo amplifier capacities [kW]
Total of connectable servo motor rated currents [A]
Maximum servo amplifier capacity [kW]
7.5K
3.75
33
3.5
11K
5.5
46
5
15K
7.5
61
7
FR-CV-
22K
6
11
90
11
30K
15
115
15
37K
18.5
145
15
55K
27.5
215
22
When using the FR-CV, always install the dedicated stand-alone reactor (FR-CVL).
Power regeneration common converter
FR-CV-7.5K(-AT)
FR-CV-11K(-AT)
FR-CV-15K(-AT)
FR-CV-22K(-AT)
FR-CV-30K(-AT)
FR-CV-37K
FR-CV-55K
Dedicated stand-alone reactor
FR-CVL-7.5K
FR-CVL-11K
FR-CVL-15K
FR-CVL-22K
FR-CVL-30K
FR-CVL-37K
FR-CVL-55K
12 - 39
12. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection diagram
(Note 8)
Power supply
NFB
MC
(Note 1)
RA1 RA2
FR-CVL
R/L
11
S/L
21
T/L
31
R2/L
12
S2/L
22
T2/L
32
RESET
(Note 1)
EM1 OFF ON
MC
MC
SK
FR-CV
R2/L
1
S2/L
2
P/L
T2/L
3
N/L
Servo amplifier
L
L
11
21
U
V
P
(Note 6)
W
N
CN2
Servo motor
U
V
W Thermal relay 0HS2
0HS1
(Note 2)
R/L
11
S/L
21
T/MC1
P24
SD
EM1
SG
COM
EM1
(Note 1)
RA1
(Note 5)
RES
RDYB
SD
RDYA
(Note 3)
RSO
(Note 4)
SE
A
RA1 (Note 1)
Servo system controller
B
C
24VDC power supply
RA2
Note 1. Configure a sequence that will shut off main circuit power at a forced stop or at FR-CV or servo amplifier alarm occurrence.
2. For the servo motor with thermal relay, configure a sequence that will shut off main circuit power when the thermal relay operates.
3. For the servo amplifier, configure a sequence that will switch the servo on after the FR-CV is ready.
4. For the FR-CV, the RSO signal turns off when it is put in a ready-to-operate status where the reset signal is input.
Configure a sequence that will make the servo inoperative when the RSO signal is on.
5. Configure a sequence that will make a stop with the forced stop input of the servo system controller if an alarm occurs in the FR-CV. When the servo system controller does not have a forced stop input, use the forced stop input of the servo amplifier to make a stop as shown in the diagram.
6. For 7kW or less servo amplifier, always remove the wiring (3.5kW or less: across P-D, 5k 7kW: across P-C) of built-in regenerative resistor.
7. When using the servo amplifier of 11k to 22kW, make sure to connect P
1
and P. (Factory-wired.)
8. Refer to section 1.3 for the power supply specification.
(3) Wires used for wiring
(a) Wire sizes
1) Across P-P, N-N
The following table indicates the connection wire sizes of the DC power supply (P, N terminals) between the FR-CV and servo amplifier. The used wires are based on the 600V vinyl wires.
Total of servo amplifier capacities [kW]
1 or less
2
5
7
11
15
22
Wires[mm 2 ]
2
3.5
5.5
8
14
22
50
12 - 40
12. OPTIONS AND AUXILIARY EQUIPMENT
2) Grounding
For grounding, use the wire of the size equal to or greater than that indicated in the following table, and make it as short as possible.
Power regeneration common converter
FR-CV-7.5K TO FR-CV-15K
FR-CV-22K • FR-CV-30K
FR-CV-37K • FR-CV-55K
Grounding wire size [mm 2 ]
14
22
38
(b) Example of selecting the wire sizes
When connecting multiple servo amplifiers, always use junction terminals for wiring the servo amplifier terminals P, N. Also, connect the servo amplifiers in the order of larger to smaller capacities.
FR-CV-55K
R2/L
1
P/L
S2/L
2
N/L
T2/L
3
R/L
11
S/L
21
T/MC1
50mm 2
Wire as short as possible.
22mm 2
Servo amplifier (15kW)
P
N
First unit:
50mm assuming that the total of servo amplifier
capacities is 27.5kW since 15kW + 7kW + 3.5kW
+ 2.0kW = 27.5kW.
22mm 2
8mm 2
Servo amplifier (7kW)
P
N
(Note)
Second unit:
22mm assuming that the total of servo amplifier
capacities is 15kW since 7kW + 3.5kW + 2.0kW =
12.5kW.
8mm 2
5.5mm
2
Servo amplifier (3.5kW)
P
N
(Note)
Third unit:
8mm assuming that the total of servo amplifier
capacities is 7kW since 3.5kW + 2.0kW = 5.5kW.
3.5mm
2
3.5mm
2
Servo amplifier (2kW)
P
N
(Note)
Fourth unit:
3.5mm assuming that the total of servo amplifier
capacities is 2kW since 2.0kW = 2.0kW.
Junction terminals
Overall wiring length 5m or less
Note. For 7kW or less servo amplifier, always remove the wiring (3.5kW or less: across P-D, 5k 7kW: across P-C) of built-in regenerative resistor.
(4) Other precautions
(a) Always use the FR-CVL as the power factor improving reactor. Do not use the FR-BAL or FR-BEL.
(b) The inputs/outputs (main circuits) of the FR-CV and servo amplifiers include high-frequency components and may provide electromagnetic wave interference to communication equipment
(such as AM radios) used near them. In this case, interference can be reduced by installing the radio noise filter (FR-BIF) or line noise filter (FR-BSF01, FR-BLF).
(c) The overall wiring length for connection of the DC power supply between the FR-CV and servo amplifiers should be 5m or less, and the wiring must be twisted.
12 - 41
12. OPTIONS AND AUXILIARY EQUIPMENT
(5) Specifications
Power regeneration common converter
FR-CV-
Item
Total of connectable servo amplifier capacities [kW]
Maximum servo amplifier capacity [kW]
Output
Power supply
Protective structure (JEM 1030), cooling system
Environment
Total of connectable servo motor rated currents [A]
Regenerative braking torque
Short-time rating
Continuous rating
Rated input AC voltage/frequency
Permissible AC voltage fluctuation
Permissible frequency fluctuation
Power supply capacity (Note 2) [kVA]
Ambient temperature
Ambient humidity
Ambience
Altitude, vibration
No-fuse breaker or leakage current breaker
7.5K
3.75
3.5
33
11K
5.5
5
46
15K
7.5
7
61
22K
11
11
90
100% torque
30K
15
15
115
37K
18.5
15
145
55K
27.5
22
215
Total capacity of applicable servo motors, 300% torque, 60s (Note 1)
17
Three-phase 200 to 220V 50Hz, 200 to 230V 60Hz
Three-phase 170 to 242V 50Hz, 170 to 253V 60Hz
20 28
5%
41 52
Open type (IP00), forced cooling
66 100
10 to 50 (14 to 122 )(non-freezing)
90%RH or less (non-condensing)
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt)
1000m or less above sea level, 5.9m/s 2 or less
30AF
30A
S-N20
50AF
50A
S-N35
100AF
75A
S-N50
100AF
100A
S-N65
225AF
125A
S-N95
225AF
125A
225AF
175A
S-N95 S-N125 Magnetic contactor
Note 1. This is the time when the protective function of the FR-CV is activated. The protective function of the servo amplifier is activated in the time indicated in section 11.1.
2. When connecting the capacity of connectable servo amplifier, specify the value of servo amplifier.
12 - 42
12. OPTIONS AND AUXILIARY EQUIPMENT
12.1.10 Heat sink outside mounting attachment (MR-JACN)
Use the heat sink outside mounting attachment to mount the heat generation area of the servo amplifier in the outside of the control box to dissipate servo amplifier-generated heat to the outside of the box and reduce the amount of heat generated in the box, thereby allowing a compact control box to be designed.
In the control box, machine a hole having the panel cut dimensions, fit the heat sink outside mounting attachment to the servo amplifier with the fitting screws (4 screws supplied), and install the servo amplifier to the control box.
The environment outside the control box when using the heat sink outside mounting attachment should be within the range of the servo amplifier operating environment conditions.
(1) Panel cut dimensions
D
4-M10 Screw
[Unit: mm(in)]
Changeable dimension
Model
MR-JACN15K
MR-JACN22K
A B C D
236
(9.291)
326
(12.835)
255
(10.039)
345
(13.583)
270
(10.63)
360
(14.173)
203
(7.992)
290
(11.417)
Servo amplifier
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
Punched hole
A
B
C
(2) How to assemble the attachment for a heat sink outside mounting attachment
Screw
(2 places)
Attachment
MR-JACN15K
Screw
(4 places)
Attachment
MR-JACN22K
12 - 43
12. OPTIONS AND AUXILIARY EQUIPMENT
(3) Fitting method
Attachment
Fit using the assembling screws.
Attachment
Servo amplifier
Servo amplifier
Punched hole
Control box a. Assembling the heat sink outside mounting attachment
(4) Outline dimension drawing
(a) MR-JACN15K (MR-J2S-11KB, MR-J2S-15KB) b. Installation to the control box
20 (0.787)
Panel
Servo amplifier
Attachment
Attachment
Servo amplifier
236 (9.291)
280 (11.024)
260 (10.236)
4- 12
Mounting hole
Panel
3.2 (0.126)
155 (6.102) 105
260
(4.134)
(10.236)
11.5
(0.453)
12 - 44
12. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-JACN22K (MR-J2S-22KB)
68(2.677)
Panel
Servo amplifier
326(12.835)
370(14.567)
350(13.78)
Attachment
Servo amplifier
Attachment
4- 12
Mounting hole
Panel
3.2(0.126)
155(6.102) 105 11.5
260
(4.134) (0.453)
(10.236)
12 - 45
12. OPTIONS AND AUXILIARY EQUIPMENT
12.2 Auxiliary equipment
Always use the devices indicated in this section or equivalent. To comply with the EN Standard or UL/C-
UL (CSA) Standard, use the products which conform to the corresponding standard.
12.2.1 Recommended wires
(1) Wires for power supply wiring
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
1) Main circuit power supply lead 3) Motor power supply lead
Servo amplifier Servo motor
Power supply
L
1
L
2
L
3
U
V
W
U
V
W Motor
4) Power regeneration
converter lead
2) Control power supply lead
L
11
L
21
5) Electromagnetic
brake lead
Power regeneration converter
Regenerative option
N
C
P
4) Regenerative option lead
Encoder cable
(refer to section 12.1.4)
Power supply
B1
B2
Electromagnetic brake
Encoder
Cooling fan
BU
BV
BW
Cooling fan lead
The following table lists wire sizes. The wires used assume that they are 600V vinyl wires and the wiring distance is 30m(98.4ft) max. If the wiring distance is over 30m(98.4ft), choose the wire size in consideration of voltage drop.
The alphabets (a, b, c) in the table correspond to the crimping terminals (Table 12.2) used to wire the servo amplifier. For connection with the terminal block TE2 of the MR-J2S-100B or less, refer to section 3.9.
The servo motor side connection method depends on the type and capacity of the servo motor. Refer to section 3.6.
To comply with the UL/C-UL (CSA) Standard, use UL-recognized copper wires rated at 60 (140 ) or more for wiring.
12 - 46
12. OPTIONS AND AUXILIARY EQUIPMENT
Table 12.1 Recommended wires
Servo amplifier
1) L
1
L
2
L
3
(Note 1) Wires [mm 2 ]
2) L
11
L
21
3) U V W P
1
P 4) P C N
MR-J2S-10B(1)
MR-J2S-20B(1)
MR-J2S-40B(1)
MR-J2S-60B
MR-J2S-70B
MR-J2S-100B
MR-J2S-200B
2 (AWG14) : a
1.25 (AWG16) : a
MR-J2S-350B
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
3.5 (AWG12) : b
5.5 (AWG10) : b
8 (AWG8) : c
14 (AWG6) :d
22 (AWG4) :e
50 (AWG1/0) :g
1.25
(AWG16)
2 (AWG14) : a
3.5 (AWG12) : b
(Note 2)
5.5 (AWG10) : b
5.5 (AWG10) : b
8 (AWG8) : c
22 (AWG4) :e
30 (AWG2) :f
60 (AWG2/0) :g
Note 1. For the crimping terminals and applicable tools, see the table 12.2.
2. 3.5mm
2 for use of the HC-RFS203 servo motor.
2 (AWG14) : a
3.5(AWG12): b
5.5(AWG10): b
5) B1 B2
1.25 (AWG16)
6) BU BV BW
2(AWG14)
Use wires 6) of the following sizes with the power regeneration converter (FR-RC).
Model
FR-RC-15K
FR-RC-30K
FR-RC-55K
Wires[mm 2 ]
14(AWG6)
14(AWG6)
22(AWG4)
Table 12.2 Recommended crimping terminals
Symbol a b
(Note 1 2) f c d e g
Servo amplifier side crimping terminals
Crimping terminal Applicable tool Manufacturer name
32959
FVD5.5-4
FVD8-5
FVD14-6
FVD22-6
38-S6
R38-6S
(Note 1) R60-8
47387
YNT-1210S
Body YF-1 E-4
Head YNE-38
Dice DH-111 DH-121
Body YF-1 E-4
Head YNE-38
Dice DH-112 DH-122
Body YF-1 E-4
Head YNE-38
Dice DH-113 DH-123
Body YPT-60-21
Dice TD-124 TD-112
Body YF-1 E-4
Head YET-60-1
Dice TD-124 TD-112
NOP60
NOM60
Body YDT-60-21
Dice TD-125 TD-113
Body YF-1 E-4
Head YET-60-1
Dice TD-125 TD-113
Tyco Electronics
Japan Solderless
Terminal
NICHIFU
Japan Solderless
Terminal
Note 1. Cover the crimped portion with an insulating tape.
2. Always use recommended crimping terminals or equivalent since some crimping terminals cannot be installed depending on the size.
12 - 47
12. OPTIONS AND AUXILIARY EQUIPMENT
(2) Wires for cables
When fabricating a cable, use the wire models given in the following table or equivalent.
Type Model
Length
[m(ft)]
Encoder cable
MR-JCCBL M-L
MR-JCCBL M-H
MR-JHSCBL M-L
MR-JHSCBL M-H
MR-ENCBL M-H
2 to 10
(6.56 to 32.8)
20 30
(65.6 98.4)
2 5
(6.56 16.4)
10 to 50
(32.8 to 164)
2 5
(6.56 16.4)
10 to 30
(32.8 to 98.4)
2 5
(6.56 16.4)
10 to 50
(32.8 to 164)
2 5
(6.56 16.4)
10 to 50
(32.8 to 164)
Communication cable
MR-CPCATCBL3M 3 (9.84)
Bus cable
MR-J2HBUS M
MR-J2HBUS M-A
Q172J2BCBL M(-B)
Q173J2B CBL M
0.5 to 5
(1.64 to 16.4)
Note 1. d is as shown below.
Table 12.3 Wires for option cables
Core size
[mm 2 ]
Number of Cores
Structure
[Wires/mm]
Characteristics of one core
Conductor resistance[ /mm]
Insulation coating
ODd[mm] (Note 1)
0.08
0.3
0.2
0.2
0.08
0.3
0.2
0.2
0.2
0.2
0.08
0.08
12
(6 pairs)
8
(4 pairs)
12
(6 pairs)
8
(4 pairs)
12
(6 pairs)
6
(3 pairs)
12
(6 pairs)
12
(6 pairs)
12
(6 pairs)
14
(7 pairs)
8
(4 pairs)
20
(10 pairs)
14
(7 pairs)
7/0.127
12/0.18
40/0.08
40/0.08
7/0.127
12/0.18
40/0.08
40/0.08
40/0.08
40/0.08
7/0.127
7/0.127
222
62
105
105
222
62
105
105
105
105
222
222
0.38
1.2
0.88
0.88
0.38
1.2
0.88
0.88
0.88
0.88
0.38
0.38
d
(Note 3)
Finishing
OD [mm]
5.6
8.2
7.2
8.0
4.7
8.2
6.5
7.2
6.5
7.2
4.6
6.1
5.5
Wire model
UL20276 AWG#28
6pair (BLACK)
UL20276 AWG#22
6pair (BLACK)
(Note 2)
A14B2343 6P
(Note 2)
A14B0238 7P
UL20276 AWG#28
4pair (BLACK)
UL20276 AWG#22
6pair (BLACK)
(Note 2)
A14B2339 4P
(Note 2)
A14B2343 6P
(Note 2)
A14B2339 4P
(Note 2)
A14B2343 6P
UL20276 AWG#28
3pair (BLACK)
UL20276 AWG#28
10pair (CREAM)
UL20276 AWG#28
7pair (CREAM)
Conductor Insulation sheath
2. Purchased from Toa Electric Industry
3. Standard OD. Max. OD is about 10% greater.
12 - 48
12. OPTIONS AND AUXILIARY EQUIPMENT
12.2.2 No-fuse breakers, fuses, magnetic contactors
Always use one no-fuse breaker and one magnetic contactor with one servo amplifier. When using a fuse instead of the no-fuse breaker, use the one having the specifications given in this section.
Servo amplifier No-fuse breaker
Fuse
Class Current [A] Voltage AC[V]
MR-J2S-10B(1)
MR-J2S-20B
30A frame 5A
30A frame 5A
K5
K5
MR-J2S-40B 20B1 30A frame 10A
MR-J2S-60B 40B1 30A frame 15A
MR-J2S-70B
MR-J2S-100B
30A frame 15A
30A frame 15A
MR-J2S-200B
MR-J2S-350B
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB
30A frame 20A
30A frame 30A
K5
K5
50A frame 50A K5
100A frame 75A K5
100A frame 100A K5
K5
K5
K5
K5
MR-J2S-15KB
MR-J2S-22KB
225A frame 125A K5
225A frame 175A K5
10
10
15
20
20
25
40
70
125
150
200
250
350
250
Magnetic contactor
S-N10
S-N18
S-N20
S-N35
S-N50
S-N65
S-N95
S-N25
12.2.3 Power factor improving reactors
The input power factor is improved to be about 90%. For use with a 1-phase power supply, it may be slightly lower than 90%.
[Unit : mm] Servo amplifier
NFB
MC
R
FR-BAL
X
MR-J2S- B
L
1
3-phase
200 to 230V
S Y
L 2
T Z
L 3
W D1
Installation screw
(Note)
1-phase
230V
NFB MC
R
FR-BAL
S
X
Y
Servo amplifier
MR-J2S- B
L
1
L
2
R X S Y T Z
T Z
C W1
1-phase
100 to 120V
NFB
MC
R
FR-BAL
S
X
Y
L
3
Servo amplifier
MR-J2S- B1
L
1
L
2
T Z
Note. For the 1-phase 230V power supply, Connect the power supply to L
1
, L
2
and leave L
3
open.
Servo amplifier Model
W W1
Dimensions [mm (in) ]
H D D1 C
MR-J2S-10B(1)/20B
MR-J2S-40B/20B1
FR-BAL-0.4K
135 (5.31) 120 (4.72) 115 (4.53) 59 (2.32) 45 0
-2.5
(1.77
0
-0.098
) 7.5 (0.29)
FR-BAL-0.75K 135 (5.31) 120 (4.72) 115 (4.53) 69 (2.72) 57 0
-2.5
(2.24
0
-0.098
) 7.5 (0.29)
MR-J2S-60B/70B/40B1 FR-BAL-1.5K
160 (6.30) 145 (5.71) 140 (5.51) 71 (2.79) 55 0
-2.5
(2.17
0
-0.098
) 7.5 (0.29)
MR-J2S-100B
MR-J2S-200B
FR-BAL-2.2K
160 (6.30) 145 (5.71) 140 (5.51) 91 (3.58) 75 0
-2.5
(2.95
0
-0.098
) 7.5 (0.29)
FR-BAL-3.7K
220 (8.66) 200 (7.87) 192 (7.56) 90 (3.54) 70 0
-2.5
(2.76
0
-0.098
) 10 (0.39)
MR-J2S-350B
MR-J2S-500B
FR-BAL-7.5K
220 (8.66) 200 (7.87) 194 (7.64) 120 (4.72) 100 0
-2.5
(3.94
0
-0.098
) 10 (0.39)
FR-BAL-11K 280 (11.02) 255 (10.04) 220 (8.66) 135 (5.31) 100 0
-2.5
(3.94
0
-0.098
) 12.5 (0.49)
MR-J2S-700B/11KB FR-BAL-15K 295 (11.61) 270 (10.62) 275 (10.83) 133 (5.24) 110 0
-2.5
(4.33
0
-0.098
) 12.5 (0.49)
MR-J2S-15KB FR-BAL-22K 290 (11.41) 240 (9.75) 301 (11.85) 199 (7.84) 170 5 (6.69 0.2) 25 (0.98)
MR-J2S-22KB FR-BAL-30K 290 (11.41) 240 (9.75) 301 (11.85) 219 (8.62) 190 5 (7.48 0.2) 25 (0.98)
Mounting screw size
Terminal screw size
M5
M5
M6
M6
M8
M4
M4
M4
M4
M8
M3.5
M3.5
M3.5
M3.5
M4
M5
M6
M6
M8
M8
Mass
[kg (lb)]
2.0 (4.4)
2.8 (6.17)
3.7 (8.16)
5.6 (12.35)
8.5 (18.74)
14.5 (32.0)
19 (41.9)
27 (59.5)
35 (77.16)
43 (94.79)
12 - 49
12. OPTIONS AND AUXILIARY EQUIPMENT
12.2.4 Power factor improving DC reactors
The input power factor is improved to be about 95%.
(Note 1) Terminal cover
Screw size G
Rating plate
E
A or less
2-F L
Notch
H
B or less
F
Mounting foot part
FR-BEL
5m or less
P
Servo amplifier
(Note2)
P
1
Note 1. Fit the supplied terminal cover after wiring.
2. When using the DC reactor, remove the short-circuit bar across P
1
-P.
Servo amplifier
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
Power factor improving DC reactors
A B C
Dimensions [mm (in) ]
D E F L G H
FR-BEL-15K 170(6.69) 93(3.66) 170(6.69)2.3(0.09)155(6.10) 6(0.24) 14(0.55) M8 56(2.21)
FR-BEL-22K 185(7.28)119(4.69)182(7.17)2.6(0.10)165(6.49) 7(0.28) 15(0.59) M8 70(2.77)
FR-BEL-30K 185(7.28)119(4.69)201(7.91)2.6(0.10)165(6.49) 7(0.28) 15(0.59) M8 70(2.77)
Terminal screw size
M5
M6
M6
Mass
[kg (lb)]
Used wire
[mm
2
]
3.8(8.38) 22(AWG4)
5.4(11.91) 30(AWG2)
6.7(14.77) 60(AWG1/0)
12 - 50
12. OPTIONS AND AUXILIARY EQUIPMENT
12.2.5 Relays
The following relays should be used with the interfaces.
Interface Selection example
Relay used for digital input signals (interface DI-1) To prevent defective contacts , use a relay for small signal
(twin contacts).
(Ex.) Omron : type G2A , MY
Relay used for digital output signals (interface DO-1) Small relay with 12VDC or 24VDC of 40mA or less
(Ex.) Omron : type MY
12.2.6 Surge absorbers
A surge absorber is required for the electromagnetic brake. Use the following surge absorber or equivalent.
Insulate the wiring as shown in the diagram.
Permissible circuit voltage
Maximum rating
Surge immunity
Energy immunity
AC[Vma] DC[V]
140 180
[A]
(Note)
500/time
[J]
5
Note. 1 time 8 20 s
Rated power
[W]
0.4
Maximum limit voltage
[A]
25
[V]
360
(Example) ERZV10D221 (Matsushita Electric Industry)
TNR-10V221K (Nippon Chemi-con)
Outline drawing [mm] ( [in] ) (ERZ-C10DK221)
13.5 (0.53) 4.7 1.0 (0.19 0.04)
Static capacity
(reference value)
[pF]
300
Varistor voltage rating (range) V1mA
[V]
220
(198 to 242)
0.8 (0.03)
Vinyl tube
Crimping terminal for M4 screw
12 - 51
12. OPTIONS AND AUXILIARY EQUIPMENT
12.2.7 Noise reduction techniques
Noises are classified into external noises which enter the servo amplifier to cause it to malfunction and those radiated by the servo amplifier to cause peripheral devices to malfunction. Since the servo amplifier is an electronic device which handles small signals, the following general noise reduction techniques are required.
Also, the servo amplifier can be a source of noise as its outputs are chopped by high carrier frequencies. If peripheral devices malfunction due to noises produced by the servo amplifier, noise suppression measures must be taken. The measures will vary slightly with the routes of noise transmission.
(1) Noise reduction techniques
(a) General reduction techniques
Avoid laying power lines (input and output cables) and signal cables side by side or do not bundle them together. Separate power lines from signal cables.
Use shielded, twisted pair cables for connection with the encoder and for control signal transmission, and connect the shield to the SD terminal.
Ground the servo amplifier, servo motor, etc. together at one point (refer to section 3.9).
(b) Reduction techniques for external noises that cause the servo amplifier to malfunction
If there are noise sources (such as a magnetic contactor, an electromagnetic brake, and many relays which make a large amount of noise) near the servo amplifier and the servo amplifier may malfunction, the following countermeasures are required.
Provide surge absorbers on the noise sources to suppress noises.
Attach data line filters to the signal cables.
Ground the shields of the encoder connecting cable and the control signal cables with cable clamp fittings.
Although a surge absorber is built into the servo amplifier, to protect the servo amplifier and other equipment against large exogenous noise and lightning surge, attaching a varistor to the power input section of the equipment is recommended.
12 - 52
12. OPTIONS AND AUXILIARY EQUIPMENT
(c) Techniques for noises radiated by the servo amplifier that cause peripheral devices to malfunction
Noises produced by the servo amplifier are classified into those radiated from the cables connected to the servo amplifier and its main circuits (input and output circuits), those induced electromagnetically or statically by the signal cables of the peripheral devices located near the main circuit cables, and those transmitted through the power supply cables.
Noises produced by servo amplifier
Noises transmitted in the air
Noise radiated directly from servo amplifier
Route 1)
Noise radiated from the power supply cable
Route 2)
Noise radiated from servo motor cable
Routes 4) and 5)
Route 3)
Magnetic induction noise
Static induction noise
Noises transmitted through electric channels
Route 6)
Noise transmitted through power supply cable
Noise sneaking from grounding cable due to leakage current
Route 7)
Route 8)
5)
Instrument
7)
Receiver
7) 7)
2)
3)
1)
Servo amplifier
4)
6)
2)
Sensor
power
supply
Sensor
8)
3)
Servo motor M
12 - 53
12. OPTIONS AND AUXILIARY EQUIPMENT
Noise transmission route
1) 2) 3)
4) 5) 6)
7)
8)
Suppression techniques
When measuring instruments, receivers, sensors, etc. which handle weak signals and may malfunction due to noise and/or their signal cables are contained in a control box together with the servo amplifier or run near the servo amplifier, such devices may malfunction due to noises transmitted through the air. The following techniques are required.
(1) Provide maximum clearance between easily affected devices and the servo amplifier.
(2) Provide maximum clearance between easily affected signal cables and the I/O cables of the servo amplifier.
(3) Avoid laying the power lines (I/O cables of the servo amplifier) and signal cables side by side or bundling them together.
(4) Insert a line noise filter to the I/O cables or a radio noise filter on the input line.
(5) Use shielded wires for signal and power cables or put cables in separate metal conduits.
When the power lines and the signal cables are laid side by side or bundled together, magnetic induction noise and static induction noise will be transmitted through the signal cables and malfunction may occur. The following techniques are required.
(1) Provide maximum clearance between easily affected devices and the servo amplifier.
(2) Provide maximum clearance between easily affected signal cables and the I/O cables of the servo amplifier.
(3) Avoid laying the power lines (I/O cables of the servo amplifier) and signal cables side by side or bundling them together.
(4) Use shielded wires for signal and power cables or put the cables in separate metal conduits.
When the power supply of peripheral devices is connected to the power supply of the servo amplifier system, noises produced by the servo amplifier may be transmitted back through the power supply cable and the devices may malfunction. The following techniques are required.
(1) Insert the radio noise filter (FR-BIF) on the power cables (input cables) of the servo amplifier.
(2) Insert the line noise filter (FR-BSF01 FR-BLF) on the power cables of the servo amplifier.
When the cables of peripheral devices are connected to the servo amplifier to make a closed loop circuit, leakage current may flow to malfunction the peripheral devices. If so, malfunction may be prevented by disconnecting the grounding cable of the peripheral device.
(2) Noise reduction products
(a) Data line filter
Noise can be prevented by installing a data line filter onto the encoder cable, etc.
For example, the ZCAT3035-1330 of TDK and the ESD-SR-25 of NEC Tokin are available as data line filters.
As a reference example, the impedance specifications of the ZCAT3035-1330 (TDK) are indicated below.
This impedances are reference values and not guaranteed values.
[Unit: mm]([Unit: in.])
Impedance[ ]
10 to 100MHz
80
100 to 500MHz
150
39 1(1.54 0.04)
34 1
(1.34 0.04)
Loop for fixing the cable band
TDK
Product name Lot number
Outline drawing (ZCAT3035-1330)
12 - 54
12. OPTIONS AND AUXILIARY EQUIPMENT
(b) Surge suppressor
The recommended surge suppressor for installation to an AC relay, AC valve, AC electromagnetic brake or the like near the servo amplifier is shown below. Use this product or equivalent.
MC
Relay
Surge suppressor
Surge suppressor
Rated voltage
AC[V]
200
C [ F] R [ ] Test voltage AC[V]
0.5
50
(1W)
Across
T-C 1000(1 to 5s)
Surge suppressor
This distance should be short
(within 20cm(0.79 in.)).
(Ex.) 972A.2003 50411
(Matsuo Electric Co.,Ltd. 200V rating)
Outline drawing [Unit: mm] ([Unit: in.])
Vinyl sheath
Blue vinyl cord Red vinyl cord
6(0.24)
18 1.5
(0.71 0.06)
10 3
(0.39
0.12)
10(0.39)or less 10(0.39)or less
200(7.87) or more
15 1(0.59 0.04)
48 1.5
(1.89 0.06)
200(7.87) or more
10 3
(0.39
0.15)
4(0.16)
31(1.22)
Note that a diode should be installed to a DC relay, DC valve or the like.
Maximum voltage: Not less than 4 times the drive voltage of the relay or the like
Maximum current: Not less than twice the drive current of the relay or the like
RA
Diode
(c) Cable clamp fitting (AERSBAN -SET)
Generally, the earth of the shielded cable may only be connected to the connector's SD terminal.
However, the effect can be increased by directly connecting the cable to an earth plate as shown below.
Install the earth plate near the servo amplifier for the encoder cable. Peel part of the cable sheath to expose the external conductor, and press that part against the earth plate with the cable clamp.
If the cable is thin, clamp several cables in a bunch.
The clamp comes as a set with the earth plate.
Strip the cable sheath of the clamped area.
Cable clamp
(A,B)
Cable
Earth plate cutter cable
12 - 55
External conductor
Clamp section diagram
12. OPTIONS AND AUXILIARY EQUIPMENT
Outline drawing
Earth plate
2- 5(0.20) hole installation hole
17.5(0.69)
[Unit: mm]
([Unit: in.])
Clamp section diagram
L or less 10(0.39)
0 0.
(Note)M4 screw
6
(0.24) 35(1.38)
22(0.87)
Note. Screw hole for grounding. Connect it to the earth plate of the control box.
Type
AERSBAN-DSET
AERSBAN-ESET
A
100
(3.94)
70
(2.76)
B
86
(3.39)
56
(2.20)
C
30
(1.18)
Accessory fittings clamp A: 2pcs.
clamp B: 1pc.
Clamp fitting
A
B
L
70
(2.76)
45
(1.77)
12 - 56
12. OPTIONS AND AUXILIARY EQUIPMENT
(d) Line noise filter (FR-BLF, FR-BSF01)
This filter is effective in suppressing noises radiated from the power supply side and output side of the servo amplifier and also in suppressing high-frequency leakage current (zero-phase current) especially within 0.5MHz to 5MHz band.
Connection diagram
Use the line noise filters for wires of the main power supply
(L
1
L
2
L
3
) and of the motor power supply (U V W). Pass each of the 3-phase wires through the line noise filter an equal number of times in the same direction. For the main power supply, the effect of the filter rises as the number of passes increases, but generally four passes would be appropriate. For the motor power supply, passes must be four times or less. Do not pass the grounding (earth) wire through the filter, or the effect of the filter will drop. Wind the wires by passing through the filter to satisfy the required number of passes as shown in
Example 1. If the wires are too thick to wind, use two or more filters to have the required number of passes as shown in
Example 2. Place the line noise filters as close to the servo amplifier as possible for their best performance.
Example 1
NFB MC
Servo amplifier
Power supply
L
1
L
2
Line noise filter
L
(Number of turns: 4)
3
Example 2
NFB MC
Servo amplifier
Power supply
L
1
L
2
Line noise filter
L
3
Two filters are used
(Total number of turns: 4)
Outline drawing [Unit: mm] ([Unit: in.])
FR-BSF01(for MR-J2S-200B or less)
Approx.110(4.33)
95 0.5(3.74 0.02) 2- 5(0.20)
Approx.65 (2.56)
33(1.30)
FR-BLF(MR-J2S-350B or more)
7(0.28)
130(5.12)
85(3.35)
160(6.30)
180(7.09)
(e) Radio noise filter (FR-BIF)...for the input side only
This filter is effective in suppressing noises radiated from the power supply side of the servo amplifier especially in 10MHz and lower radio frequency bands. The FR-BIF is designed for the input only.
Connection diagram
Make the connection cables as short as possible.
Grounding is always required.
When using the FR-BIF with a single-phase wire, always insulate the wires that are not used for wiring.
NFB MC Servo amplifier
Power supply
L
1
L
2
L
3
Outline drawing (Unit: mm) ([Unit: in.])
Leakage current: 4mA
Red White Blue Green
29 (1.14)
5 (0.20) hole
Radio noise filter FR-BIF
58 (2.28) 29 (1.14)
44 (1.73)
7 (0.28)
12 - 57
12. OPTIONS AND AUXILIARY EQUIPMENT
(f) Varistors for input power supply (Recommended)
Varistors are effective to prevent exogenous noise and lightning surge from entering the servo amplifier. When using a varistor, connect it between each phase of the input power supply of the equipment. For varistors, the TND20V-431K and TND20V-471K manufactured by Nippon Chemicon, are recommended. For detailed specification and usage of the varistors, refer to the manufacturer catalog.
Varistor
Maximum rating
Permissible circuit voltage
Surge current immunity
Energy immunity
AC[V rms
] DC[V]
TND20V-431K 275
TND20V-471K 300
350
385
8/20 s[A]
10000/1 time
7000/2 time
2ms[J]
195
215
Rated pulse power
[W]
1.0
Maximum limit voltage
[A] [V]
Static capacity
(reference value)
[pF]
100
710
775
1300
1200
Varistor voltage rating (range)
V1mA
[V]
430(387 to 473)
470(423 to 517)
D T Model
TND20V-431K
TND20V-471K
D
Max.
21.5
H
Max.
24.5
T
Max.
6.4
6.6
E
1.0
3.3
3.5
(Note)L min.
20
Note. For special purpose items for lead length (L), contact the manufacturer.
d
0.05
0.8
[Unit: mm]
W
1.0
10.0
W
d
E
12 - 58
12. OPTIONS AND AUXILIARY EQUIPMENT
12.2.8 Leakage current breaker
(1) Selection method
High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits.
Leakage currents containing harmonic contents are larger than those of the motor which is run with a commercial power supply.
Select a leakage current breaker according to the following formula, and ground the servo amplifier, servo motor, etc. securely.
Make the input and output cables as short as possible, and also make the grounding cable as long as possible (about 30cm (11.8 in)) to minimize leakage currents.
Rated sensitivity current 10 {Ig1 Ign Iga K (Ig2 Igm)} [mA] ..........(12.1)
Cable
NV
Noise filter
Ig1 Ign
Servo amplifier
Iga
Cable
Ig2
M
Igm
K: Constant considering the harmonic contents
Leakage current breaker
Type
Mitsubishi products
Models provided with harmonic and surge reduction techniques
General models
NV-SP
NV-SW
NV-CP
NV-CW
NV-HW
BV-C1
NFB
NV-L
K
1
3
Ig1: Leakage current on the electric channel from the leakage current breaker to the input terminals of the servo amplifier (Found from Fig. 12.1.)
Ig2: Leakage current on the electric channel from the output terminals of the servo amplifier to the servo motor (Found from Fig. 12.1.)
Ign: Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF)
Iga: Leakage current of the servo amplifier (Found from Table 12.5.)
Igm: Leakage current of the servo motor (Found from Table 12.4.)
120
100
80
60
40
[mA]
20
0
2 3.5
5.5
8 1422 38 80 150
30 60 100
Cable size[mm 2 ]
Fig. 12.1 Leakage current example
(Ig1, Ig2) for CV cable run
in metal conduit
Table 12.4 Servo motor's leakage current example (Igm)
Servo motor output [kW]
0.05 to 0.5
0.6 to 1.0
1.2 to 2.2
3 to 3.5
5
7
11
15
22
Leakage current [mA]
0.1
0.1
0.2
0.3
0.5
0.7
1.0
1.3
2.3
Table 12.5 Servo amplifier's leakage current example (Iga)
Servo amplifier capacity [kW]
Leakage current
[mA]
0.1 to 0.6
0.7 to 3.5
5 7
11 15
22
Servo amplifier
0.1
0.15
2
5.5
7
Table 12.6 Leakage circuit breaker selection example
Rated sensitivity current of leakage circuit breaker [mA]
MR-J2S-10B to MR-J2S-350B
MR-J2S-10B1 to MR-J2S-40B1
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB to MR-J2S-22KB
15
30
50
100
12 - 59
12. OPTIONS AND AUXILIARY EQUIPMENT
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions.
2mm 2 5m 2mm 2 5m
NV
Servo amplifier
MR-J2S-60B
M
Servo motor
HC-MFS73
Ig1 Iga Ig2 Igm
Use a leakage current breaker designed for suppressing harmonics/surges.
Find the terms of Equation (12.1) from the diagram.
Ig1 20
5
1000
0.1 [mA]
Ig2 20
5
1000
0.1 [mA]
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (12.1).
Ig 10 {0.1 0 0.1 1 (0.1 0.1)}
4 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity current (Ig) of 4[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-
SP/CP/SW/CW/HW series.
12 - 60
12. OPTIONS AND AUXILIARY EQUIPMENT
12.2.9 EMC filter
For compliance with the EMC directive of the EN standard, it is recommended to use the following filter.
Some EMC filters are large in leakage current.
(1) Combination with the servo amplifier
Servo amplifier
Model
Recommended filter
Leakage current [mA]
Mass
[kg]([Ib])
MR-J2S-10B to MR-J2S-100B
MR-J2S-10B1 to MR-J2S-40B1
MR-J2S-200B MR-J2S-350B
MR-J2S-500B
MR-J2S-700B
MR-J2S-11KB
MR-J2S-15KB
MR-J2S-22KB
(Note)
SF1252
SF1253
HF3040A-TM
(Note) HF3050A-TM
(Note) HF3060A-TMA
(Note) HF3080A-TMA
(Note) HF3100A-TMA
38
57
1.5
1.5
3.0
3.0
3.0
0.75(1.65)
1.37(3.02)
6.0(13.23)
6.7(14.77)
10.0(22.05)
13.0(28.66)
14.5(31.97)
Note. Soshin Electric. A surge protector is separately required to use any of these EMC filters. (Refer to the EMC Installation
Guidelines.)
(2) Connection example
(Note 1)
Power supply
NFB
EMC filter
(SF1252, SF1253)
LINE LOAD
L
1
L
1
L
2
L
3
L
L
2
3
(Note 2)
MC
Servo amplifier
L
1
L
2
(Note 1)
Power supply
L
3
L
11
L
21
NFB
EMC filter
(SOSHIN Electric Co., Ltd)
1
2
3
1
2
3
4
5
6
E
MC
Servo amplifier
L
1
L
2
L
3
L
11
L
21
Surge protector 1
(RAV-781BYZ-2)
(OKAYA Electric Industries
Co., Ltd.)
1 2 3
Surge protector 2
(RAV-781BXZ-4)
(OKAYA Electric Industries Co., Ltd.)
Note 1. For 1-phase 230V power supply, connect the power supply to L
1
, L
2
and leave L
3
open. There is no L
3
for 1-phase 100 to 120V power supply. Refer to section 1.3 for the power supply specification.
2. Connect when the power supply has earth.
12 - 61
12. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outline drawing
(a) EMC filter
SF1252
149.5(5.886)
L1
L2
L3
6.0(0.236)
LINE
(input side)
SF1253
209.5(8.248)
L1
L2
L3
[Unit: mm(in)]
6.0(0.236)
LINE
(input side)
L1'
L2'
L3'
LOAD
(output side)
8.5
(0.335)
42.0
(1.654)
16.0(0.63)
HF3040A-TM HF3050A-TM HF3060A-TMA
6-K
3-L 3-L
L1'
L2'
L3'
LOAD
(output side)
8.5
(0.335)
23.0(0.906)
49.0
(1.929)
M
C 1
B 2
A 5
C 1
H 2
J 2
Model
HF3040A-TM
HF3050A-TM
HF3060A-TMA
A
260
(10.24)
290
(11.42)
290
(11.42)
B
210
(8.27)
240
(9.45)
240
(9.45)
C
85
(8.35)
100
(3.94)
100
(3.94)
D
155
(6.10)
190
(7.48)
190
(7.48)
E
140
(5.51)
Dimensions [mm(in)]
F G
125
(4.92)
44
(1.73)
H
140
(5.51)
175
(6.89)
175
(6.89)
160
(6.29)
160
(6.29)
44
(1.73)
44
(1.73)
170
(6.69)
230
(9.06)
J
70
(2.76)
100
(3.94)
160
(6.29)
K
R3.25
(0.128), length
8 (0.32)
L
M5
M6
M6
M
M4
M4
M4
12 - 62
12. OPTIONS AND AUXILIARY EQUIPMENT
HF3080A-TMA HF3100A-TMA
8-K
3-L 3-L
M
C 1 C 1
B 2
A 5
C 1
H 2
J 2
Model
A B C
HF3080A-TMA
HF3100A-TMA
405
(15.95)
350
(13.78)
100
(3.94)
D
220
(8.66)
E
Dimensions [mm(in)]
F G
200
(7.87)
180
(7.09)
56
(2.21)
H
210
(8.27)
J
135
(5.32)
K
R4.25
(0.167), length
12(0.472)
L
M8
M
M6
12 - 63
12. OPTIONS AND AUXILIARY EQUIPMENT
(b) Surge protector
RAV-781BYZ-2
4.2 0.2
[Unit: mm]
1) 2)
Black Black
3)
Black
30 0
UL-1015AWG16
1 2 3
4.2 0.2
41 1.0
RAV-781BXZ-4
[Unit: mm]
1) 2) 3) 4)
1 2 3
41 1.0
30 0
UL-1015AWG16
12 - 64
13. ABSOLUTE POSITION DETECTION SYSTEM
13. ABSOLUTE POSITION DETECTION SYSTEM
CAUTION
If an absolute position erase alarm (25) or an absolute position counter warning
(E3) has occurred, always perform home position setting again. Not doing so can cause runaway.
13.1 Features
For normal operation, as shown below, the encoder consists of a detector designed to detect a position within one revolution and a cumulative revolution counter designed to detect the number of revolutions.
The absolute position detection system always detects the absolute position of the machine and keeps it battery-backed, independently of whether the servo system controller power is on or off.
Therefore, once home position return is made at the time of machine installation, home position return is not needed when power is switched on thereafter.
If a power failure or a fault occurs, restoration is easy.
Also, the absolute position data, which is battery-backed by the super capacitor in the encoder, can be retained within the specified period (cumulative revolution counter value retaining time) if the cable is unplugged or broken.
Servo system controller Servo amplifier
Position data
Current position
Home position data
LS0
CYC0
Battery MR-BAT
Servo motor
1 pulse/rev accumulative revolution counter
Super capacitor
Within one-revolution counter
Detecting the number of revolutions
Detecting the position within one revolution
High speed serial communication
13 - 1
13. ABSOLUTE POSITION DETECTION SYSTEM
13.2 Specifications
(1) Specification list
System
Battery
Item
Maximum revolution range
(Note 1) Maximum speed at power failure
(Note 2) Battery backup time
(Note 3) Data holding time during battery replacement
Battery storage period
500r/min
Description
Electronic battery backup system
1 piece of lithium battery ( primary battery, nominal 3.6V)
Type: MR-BAT or A6BAT
Home position 32767 rev.
Approx. 10,000 hours (battery life with power off)
2 hours at delivery, 1 hour in 5 years after delivery
5 years from date of manufacture
Note 1. Maximum speed available when the shaft is rotated by external force at the time of power failure or the like.
2. Time to hold data by a battery with power off. It is recommended to replace the battery in three years independently of whether power is kept on or off.
3. Period during which data can be held by the super capacitor in the encoder after power-off, with the battery voltage low or the battery removed, or during which data can be held with the encoder cable disconnected.
Battery replacement should be finished within this period.
(2) Configuration
Servo system controller Servo amplifier
CN1 CN2
CN5
Battery (MR-BAT)
Servo motor
(3) Parameter setting
Set "0001" in parameter No.1 to make the absolute position detection system valid.
Absolute position detection selection
0: Used in incremental system.
1: Used in absolute position
detection system.
13 - 2
13. ABSOLUTE POSITION DETECTION SYSTEM
13.3 Battery installation procedure
WARNING
Before installing a battery, turn off the main circuit power while keeping the control circuit power on. Wait for 15 minutes or more until the charge lamp turns off. Then, confirm that the voltage between P and N is safe with a voltage tester and others.
Otherwise, an electric shock may occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
POINT
The internal circuits of the servo amplifier may be damaged by static electricity. Always take the following precautions.
Ground human body and work bench.
Do not touch the conductive areas, such as connector pins and electrical parts, directly by hand.
1) Open the operation window. (When the model used is the MR-J2S-200B MR-J2S-350B, also remove the front cover.)
2) Install the battery in the battery holder.
3) Install the battery connector into CON1 until it clicks.
Battery connector
Operation window
Battery connector
CON1
CON1
Battery Battery holder
For MR-J2S-200B or less
Battery connector
CON1
Battery
Battery holder
For MR-J2S-200B MR-J2S-350B
CON1
Battery holder
Battery holder Battery
For MR-J2S-500B MR-J2S-700B
13 - 3
Battery connector
Battery
For MR-J2S-11KB or more
13. ABSOLUTE POSITION DETECTION SYSTEM
13.4 Confirmation of absolute position detection data
You can confirm the absolute position data with MR Configurator (servo configuration software).
Click "Diagnostics" and "Absolute Encoder Data" to open the absolute position data display screen.
(1) Clicking "Diagnostics" in the menu opens the sub-menu as shown below.
(2) By clicking "Absolute Encoder Data" in the sub-menu, the absolute encoder data display window appears.
(3) Click the "Close" button to close the absolute encoder data display window.
13 - 4
APPENDIX
App 1. Combination of servo amplifier and servo motor
The servo amplifier software versions compatible with the servo motors are indicated in the parentheses.
The servo amplifiers whose software versions are not indicated can be used regardless of the versions.
Servo motor
HC-KFS053
HC-KFS13
HC-KFS23
HC-KFS43
HC-KFS73
HC-MFS053
HC-MFS13
HC-MFS23
HC-MFS43
HC-MFS73
HC-SFS81
HC-SFS121
HC-SFS201
HC-SFS301
HC-SFS52
HC-SFS102
HC-SFS152
HC-SFS202
HC-SFS352
HC-SFS502
HC-SFS702
HC-SFS53
HC-SFS103
HC-SFS153
HC-SFS203
HC-SFS353
Servo amplifier
(Software version)
MR-J2S-10B
MR-J2S-10B1
MR-J2S-10B
MR-J2S-10B1
MR-J2S-20B
MR-J2S-20B1
MR-J2S-40B
MR-J2S-40B1
MR-J2S-70B (Version A3 or later)
MR-J2S-10B
MR-J2S-10B1
MR-J2S-10B
MR-J2S-10B1
MR-J2S-20B
MR-J2S-20B1
MR-J2S-40B
MR-J2S-40B1
MR-J2S-70B
MR-J2S-100B
MR-J2S-200B
MR-J2S-200B
MR-J2S-350B
MR-J2S-60B
MR-J2S-100B
MR-J2S-200B
MR-J2S-200B
MR-J2S-350B
MR-J2S-500B (Version B0 or later)
MR-J2S-700B (Version B0 or later)
MR-J2S-60B
MR-J2S-100B
MR-J2S-200B
MR-J2S-200B
MR-J2S-350B
Servo motor
HC-RFS103
HC-RFS153
HC-RFS203
HC-RFS353
HC-RFS503
HC-UFS72
HC-UFS152
HC-UFS202
HC-UFS352
HC-UFS502
HC-UFS13
Servo amplifier
(Software version)
MR-J2S-200B
MR-J2S-200B
MR-J2S-350B (Version B0 or later)
MR-J2S-500B (Version B0 or later)
MR-J2S-500B (Version B0 or later)
MR-J2S-70B
MR-J2S-200B
MR-J2S-350B (Version B0 or later)
MR-J2S-500B (Version B0 or later)
MR-J2S-500B (Version B0 or later)
MR-J2S-10B
MR-J2S-10B1
HC-UFS23
HC-UFS43
HC-UFS73
HC-LFS52
HC-LFS102
HC-LFS152
HC-LFS202
HC-LFS302
MR-J2S-20B
MR-J2S-20B1
MR-J2S-40B
MR-J2S-40B1
MR-J2S-70B
MR-J2S-60B (Version B3 or later)
MR-J2S-100B (Version B3 or later)
MR-J2S-200B (Version B3 or later)
MR-J2S-350B (Version B3 or later)
MR-J2S-500B (Version B3 or later)
HA-LFS801
HA-LFS12K1
HA-LFS15K1
HA-LFS20K1
HA-LFS25K1
MR-J2S-11KB (Version A3 or later)
MR-J2S-11KB (Version A3 or later)
MR-J2S-15KB (Version A3 or later)
MR-J2S-22KB (Version A3 or later)
MR-J2S-22KB (Version A3 or later)
HA-LFS11K1M MR-J2S-11KB (Version A4 or later)
HA-LFS15K1M MR-J2S-15KB (Version A3 or later)
HA-LFS502
HA-LFS702
MR-J2S-500B (Version B0 or later)
MR-J2S-700B (Version B0 or later)
HA-LFS11K2
HA-LFS15K2
HA-LFS22K2
MR-J2S-11KB (Version A3 or later)
MR-J2S-15KB (Version A3 or later)
MR-J2S-22KB (Version A3 or later)
App - 1
APPENDIX
App 2. Change of connector sets to the RoHS compatible products
Connector sets (options) in the following table are changed to the RoHS compatible products after
September, 2006 shipment.
Please accept that the current products might be mixed with RoHS compatible products based on availability.
Model
MR-J2CNM
MR-J2CN1
MR-J2CNS
MR-ENCBL M-H
MR-ENCNS
MR-PWCNS1
MR-PWCNS2
MR-PWCNS3
MR-BKCN
MR-J2CN1-A
Current Product
Amplifier connector (3M or equivalent)
10120-3000VE (connector)
Amplifier connector (3M or equivalent)
10120-3000VE (connector)
Encoder connector (DDK)
MS3057-12A (Cable clump)
MS3106B20-29S (Straight plug)
Amplifier connector (3M or equivalent)
10120-3000VE (connector)
MS3106A20-29S (D190) (Plug, DDK)
CE3057-12A-3 (D265) (Cable clump, DDK)
CE02-20BS-S (Back shell, DDK)
Power supply connector (DDK)
CE05-6A22-23SD-B-BSS (Connector and back shell)
CE3057-12A-2 (D265) (Cable clump)
Power supply connector (DDK)
CE05-6A24-24SD-B-BSS (Connector and back shell)
CE3057-16A-2 (D265) (Cable clump)
Power supply connector (DDK)
CE05-6A32-17SD-B-BSS (Connector and back shell)
CE3057-20A-1 (D265) (Cable clump)
Electromagnetic brake connector
MS3106A10SL-4S (D190) (Plug, DDK)
Controller connector (Honda Tsushin Industry)
PCR-S20FS (Connector)
Amplifier connector (3M or equivalent)
10120-3000VE (Connector)
Note. RoHS compatible 36210-0100FD may be packed with current connector sets.
RoHS Compatible Product
Amplifier connector (3M or equivalent)
10120-3000PE (connector)
Amplifier connector (3M or equivalent)
10120-3000PE (connector)
Encoder connector (DDK)
D/MS3057-12A (Cable clump)
D/MS3106B20-29S (Straight plug)
Amplifier connector (3M or equivalent)
10120-3000PE (connector)
D/MS3106A20-29S (D190) (Plug, DDK)
CE3057-12A-3-D (Cable clump, DDK)
CE02-20BS-S-D (Back shell, DDK)
Power supply connector (DDK)
CE05-6A22-23SD-D-BSS (Connector and back shell)
CE3057-12A-2-D (Cable clump)
Power supply connector (DDK)
CE05-6A24-10SD-B-BSS (Connector and back shell)
CE3057-16A-2-D (Cable clump)
Power supply connector (DDK)
CE05-6A32-17SD-D-BSS (Connector and back shell)
CE3057-20A-1-D (Cable clump)
Electromagnetic brake connector
D/MS3106A10SL-4S (D190) (Plug, DDK)
Controller connector (Honda Tsushin Industry)
PCR-S20FS (Connector)
Amplifier connector (3M or equivalent)
10120-3000PE (Connector)
App - 2
REVISIONS
*The manual number is given on the bottom left of the back cover.
Print Data *Manual Number Revision
Sep., 2000 SH(NA)030007-A First edition
Jan., 2001 SH(NA)030007-B Servo amplifier: Addition of MR-J2S-500B and MR-J2S-700B
Servo motor: Addition of HC-KFS73, HC-SFS502, HC-SFS702, HC-RFS353,
HC-RFS503, HC-UFS502 and HC-UFS352
Section 1.4: Addition of brake unit and regeneration converter
Section 1.7: Overall reexamination
Section 3.5.2: Addition of return converter and brake unit
Section 3.7: Reexamination of section 3.7 and later
Section 5.2 (2): Addition of regenerative brake option to parameter No. 2
Section 6.1.2: Addition of POINT
Changing of alarm 24 name
Section 9.2: Changes made to alarm 20 cause and action fields
Addition of alarm 33 causes 1, 2
Section 10.2 (2): Addition
Section 12.1.1 (3): Overall reexamination
Section 12.1.1 (4): Addition
Section 12.1.1 (5): Addition of MR-RB31 and MR-RB51 regenerative brake options
Section 12.1.2: Addition
Section 12.1.3: Addition
Section 12.1.4: Addition of power supply connector set
Section 12.2.1 (1): Changing of wiring diagram
Addition of brake unit and power regeneration converter wire size list
Section 12.2.8 (3): Addition of outline drawing
Oct., 2002 SH(NA)030007-C Servo amplifier: Addition of MR-J2S-11KB, MR-J2S-15KB and MR-J2S-22KB
Servo motor: Addition of HA-LFS and HC-LFS series
About processing of waste: Addition of about processing of waste
SAFETY INSTRUCTIONS: Addition of FOR MAXIMIM SAFETY
CONFORMANCE WITH UL/C-UL STANDARD:
Addition of MR-J2S-11KB to MR-J2S-22KB to(4) Capacitor discharge time
Addition of(6) Attachment of servo motor
Addition of(7) About wiring protection
Section 1.4: Modification made to the contents of the test operation mode
Section 1.7.1: Deletion of (6)
Section 3.1.1: Addition of MR-J2S-700B or less
Section 3.1.2: Addition of MR-J2S-11KB or less
Section 3.2.1 (2): Addition of MR-J2S-11KB or less
Section 3.2.2: Addition of 11kW and more to the connector pin No.
Section 3.2.2 (C): Addition of dynamic brake sequence
Section 3.3: Addition of Note
Section 3.4.2 (2), (3): Wiring reexamination
Section 3.5: Addition of POINT
Section 3.6.2: Addition of POINT
Section 3.6.3: Addition of Note
Section 3.9: Reexamination of contents
Section 3.12: Addition
Print Data *Manual Number Revision
Oct., 2002 SH(NA)030007-C Section 3.12.2: Addition of power factor improving DC reactor
Section 4.3 (2): Addition of initialization completion
Section 5.2 (2): Addition of external dynamic brake selection to parameter No. 2
Renaming of parameter Nos. 3 to 5
Reexamination of parameter No. 19 contents
Section 9.1: Addition of Note to alarm 30
Section 9.2: Addition of occurrence factor 4 to alarm 16
Changing of occurrence factor and checking method of alarm 50
Changing of occurrence factor and checking method of alarm 51
Section 10.1 (7), (8): Addition of MR-J2S-11KB, 15KB and 22KB
Section 10.2 (a): Addition of connectors and shell kits
Section 11.1 (4): Addition
Section 11.3: Reexamination of HC-KFS series dynamic brake time constants
Addition of HA-LFS series
Section 12.1.1 (3): Addition of sentences
Section 12.1.1 (4) (a): Reexamination of contents
Section 12.1.1 (4) (b): Reexamination of contents
Section 12.1.1 (4) (c): Addition of sentences
Section 12.1.1 (4) (d): Addition
Section 12.1.1 (5) (e): Addition
Section 12.1.2 (1), (3): Addition of FR-BU-55K brake unit
Section 12.1.2 (3) (a), (b): Addition of FR-BR-55K resistor unit
Section 12.1.3 (1), (3), (4): Addition of FR-RC-55K power regeneration converter
Section 12.1.4: Addition; reexamination of subsequent sections
Section 12.1.5: Addition of HA-LFS series wiring
Addition of connector sets and monitor cables
Section 12.1.6: Addition of POINT
Section 12.1.7 (1): Reexamination of contents
Section 12.1.7 (2) (a): Reexamination of contents
Section 12.2.1 (1): Addition of cooling fan wiring
Addition of FR-RC-30K and FR-RC-50K
Section 12.2.1 (2): Reexamination of optional cable table
Section 12.2.4: Addition of power factor improving DC reactor; reexamination of subsequent sections
Section 12.2.5: Changing of interface name into digital input signals
Section 12.2.8 (1): Reexamination of our leakage current breaker products
Section 12.2.9 (3): Addition of outline drawing
Section 13.3: Addition of MR-J2S-11KB and more
Section 13.4: Screen change
May., 2003 SH(NA)030007-D COMPLIANCE WITH EC DIRECTIVES 2 (6): Addition of (6)
CONFORMANCE WITH UL/C-UL STANDARD: Addition of (2) Air volume
(2.8m
3 /min)
Section 1.3: Inrush current addition
Section 3.1.1: Reexamination of table in Note
Section 3.1.2: Reexamination of table in Note
Section 3.6.3: Addition of power supply connector signal arrangement CE05-
2A32-17PD-B
Section 3.12.3: Change of terminal box inside of HA-LFS11K2
Section 5.2 (1): Reexamination of alarm 8 initial value
Section 5.2 (2): Addition of "Use of built-in regenerative brake resistor" to parameter No. 2
Section 5.2 (2): Reexamination of alarm 8 initial value
Print Data *Manual Number Revision
May., 2003 SH(NA)030007-D Section 9.1: Partial sentence change
Section 9.2: Partial POINT sentence reexamination
Section 9.2: Reexamination of alarm 12, 13 definitions
Reexamination of alarm 15 definition
Addition of alarm 37 occurrence factor and corrective action
Addition of During rotation: 2.5s or more to alarm 51
Section 10.2 (2) (a): Addition of model PCR
Section 11.3: Reexamination of explanation of te
Section 11.5: Addition of inrush currents at power-on of main circuit and control circuit
Section 12.1.2: Partial sentence addition
Section 12.1.3: Partial sentence addition
Section 12.1.3 (2): Addition of Note
Section 12.1.4 (2): Correction of connection example
Addition of Note
Section 12.1.5: Addition of bus cable connected to motion controller
Section 12.1.5 (4): Reexamination/addition of contents
Section 12.1.6: POINT sentence change
Section 12.2.1 (1): Correction of error in writing of recommended wire
MR-J2S-22KB wire size
Section 12.2.1 (2): Addition of bus cable Q172J2BCBL M/Q173J2B CBL M
Jan., 2004 SH(NA)030007-E Safety Instructions: Overall reexamination
Section 1.5 (2): Partial addition
Section 1.6: Table reexamination
Section 1.8 (3): Note addition
Section 1.8 (4): Note addition
Section 3.1.1: Note 15. reexamination
Section 3.1.2: Note 15. reexamination
Section 4.2: Partial reexamination/addition of CAUTION sentence
Section 5.2: Partial addition of POINT sentence
Section 5.2 (1): Addition of Note 3
Section 5.2 (2): Partial addition of parameter No. 2
Note addition of parameter No. 31
Section 5.4.2: (10) deletion
Section 9.2: Display 32 item addition, Partial reexamination/Note addition of display 52
Section 10.1: Overall reexamination
Section 11.2: Table change
Section 11.3: Partial text addition
Section 12.1.1 (3): Partial text deletion
Section 12.1.1 (4): Partial text change
Section 12.1.1 (5): Overall reexamination
Section 12.1.4 (2): Addition of Note 2
Section 12.1.7: POINT addition
Section 12.1.8 (1)(a): Partial table reexamination
Section 12.1.9 (2): Partial figure reexamination
Section 12.1.10: Addition
Section 12.2.9 (3): Partial reexamination
Appendix: Addition
WARNING of “To prevent electric shock”: Correction of “10 minutes” to “15 minutes”
Correction of axis switch model to “SW1”
Print Data *Manual Number Revision
Jan., 2006 SH(NA)030007-F Correction of “Thermal protector” to “Thermal sensor”
Safety Instructions: Addition of 4.(2) CAUTION sentence
Safety Instructions: Addition of 4.(4) CAUTION sentence
FOR MAXIMUM SAFETY: Sentence addition
EEP-ROM life: Sentence addition
Section 1.2 (1): Correction of error in writing
Section 1.2 (2): Correction of error in writing
Section 1.2 (3): Correction of error in writing
Section 1.5 (2): Reexamination of expression for Note of Power Supply
Section 1.7.1 (1): Reexamination of expression for Application of Encoder connector Correction of error in writing
Section 1.7.1 (2): Reexamination of expression for Application of Encoder connector Correction of error in writing
Section 1.7.1 (3): Reexamination of expression for Application of Encoder connector Correction of error in writing
Section 1.7.1 (4): Reexamination of expression for Application of Encoder connector Correction of error in writing
Section 1.7.1 (5): Reexamination of expression for Application of Encoder connector Correction of error in writing
Section 1.8 (1): Note 2. Sentence reexamination
Section 1.8 (1): Addition of “CN1B” for preceding axis servo amplifier
Section 1.8 (2): Addition of “CN1B” for preceding axis servo amplifier
Section 1.8 (3): Addition of “CN1B” for preceding axis servo amplifier
Section 1.8 (4): Addition of “CN1B” for preceding axis servo amplifier
Section 1.8 (5): Addition of “CN1B” for preceding axis servo amplifier
Chapter 2: Addition of CAUTION sentence
Section 3.1.1: Reexamination of connection example correction of error in writing
Section 3.1.2: Reexamination of connection example correction of error in writing
Section 3.2.2 (1): Correction of error in writing of CON2 Function description
Section 3.2.2 (2) (a): Correction of error in writing
Section 3.3 (3): Sentence reexamination
Section 3.4.2 (3) 2): Deletion of “OP”
Section 3.5.1 (1): Reexamination of connection example correction of error in writing/Note addition
Section 3.5.2: Addition of “Power factor improving DC reactor”
Main circuit power supply: Correction of error in writing of Servo amplifier model name
Reexamination of descriptions for Regenerative brake option,
Return converter and Brake unit
Section 3.7: Addition of CAUTION sentence
Section 3.7 (3) (d), (e): Reexamination of description
Correction of error in writing of Servo motor speed
Section 3.9: POINT addition
Section 3.9.1: Addition
Section 3.9.2: Addition
Section 3.12.3: Correction of Encoder connector position
Correction of error in writing of Terminal box inside
Section 4.4: Sentence addition
Section 5.2 (1), (2): Reexamination of English translation for parameter No.40
Print Data *Manual Number Revision
Jan., 2006 SH(NA)030007-F Section 5.2 (1), (2): Addition of parameter Nos. 49 to 55, 60, 61
Section 5.3: Sentence reexamination
Section 5.3 (2): Addition of Note for Torque
Section 7.5: Addition of “Gain changing function”
Section 9.1: Addition of Note 2
Section 9.2: Addition of CAUTION sentence
Reexamination of expression for 17 19
Addition of Cause 6 to Display 33
Section 9.3: POINT addition
Reexamination of description for Cause 2 of Display 92
Partial addition of sentence to Cause of Display 9F
Reexamination of description for Display E9
Section 11.1: Reexamination of Note sentence
Section 11.2: Note addition
Section 11.3: Reexamination of Dynamic brake time constant
Section 12.1.1 (2) (b): Partial reexamination of Table b. ”Losses of servo motor and servo amplifier in regenerative mode”
Section 12.1.1 (4): Partial reexamination of sentence
Section 12.1.1 (4) (c): Reexamination of Note sentence
Section 12.1.1 (5) (c): Change of outline drawings
Section 12.1.1 (5) (d): Change of outline drawings
Section 12.1.1 (5) (e): Change of outline drawings
Section 12.1.2 (2): Reexamination of connection example
Section 12.1.3 (2): Reexamination of connection example Note addition
Section 12.1.4 (2): Reexamination of connection example Note addition
Section 12.1.8 (2): Reexamination of descriptions
Section 12.1.9 (2): Addition of Note 6, 7
Section 12.1.9 (3) (b): Note addition
Section 12.1.10 (3): Partial change of error for Figure of “Fitting method”
Section 12.2.3: Partial change of outline drawing and wiring diagram
Section 12.2.7 (2) (d): Partial correction of outline dimension lines
Section 12.2.7 (2) (e): Partial change of connection diagram
Section 12.2.9 (3): Partial reexamination of outline drawing
Chapter 13: Addition of “absolute position counter warning (E3)” to CAUTION
Nov., 2007 SH(NA)030007-G Safety Instructions: 1 Change of sentence
2 Change of sentence
4-(2) Change of diagram
Addition of sentence
Section 1.2: Change of power supply notation
Partial change of diagram
Addition of Note
Section 1.7.2: Change of CAUTION sentence
Section 1.8: Change of power supply notation
Addition of Note
Chapter 2: Change and addition of CAUTION sentence
Chapter 3: Addition of WARNING sentence and phrase
Addition of CAUTION sentence
Section 3.4.2 (2) (a) (b): Partial change of diagram
Section 3.5: Addition of CAUTION sentence
Section 3.5.2: Addition of sentence
Section 3.6.2: Addition of CAUTION sentence
Section 3.7 (3) (a): Change of timing chart
Print Data *Manual Number Revision
Nov., 2007 SH(NA)030007-G Section 3.8: Change of power supply notation
Section 3.12: Addition and change of CAUTION sentence
Section 3.12.1: Addition of Note sentence
Section 5.1: Addition of item and change of parameter No. in table
Section 5.2 (1): Correction of error in writing of initial value for parameter
No.17
Correction of error in writing of name for parameter No.52
Correction of error in writing of name for parameter No.53
Correction of error in writing of name for parameter No.54
Correction of error in writing of name for parameter No.55
Section 5.2 (2): Correction of error in writing of name for parameter No.14
Correction of error in writing of name for parameter No.15
Correction of error in writing of name for parameter No.16
Correction of error in writing of initial value for parameter
No.18
Correction of error in writing of initial value for parameter
No.21
Addition and partial change of expansion parameter No.40
Correction of error in writing of name for parameter No.52
Section 6.4 (2): Change of operation explanation for step 5
Chapter 8: Change of WARNING sentence
Section 9.2: Addition of item for display 20
Correction of error in writing of name for display 30
Addition of sentence for display 32
Addition of Cause 9 to Display 33
Change of definition for Display 55
Section 10.1: Partial change and addition of phrase
Section 10.2: Change to RoHS compatible connectors
Section 11.3: Addition of title and partial change of sentence
Chapter 12: Change of WARNING sentence
Section 12.1.1 (2) (b): Partial change of energy formula
Section 12.1.1 (3): Partial change of notation
Section 12.1.1 (4): Change of cooling fan specification notation
Section 12.1.1 (5) (b): Change of outline drawing
Section 12.1.1 (5) (c): Change of outline drawing
Section 12.1.2: Significant change of contents
Section 12.1.4: Addition of POINT sentence
Change of power supply notation in diagram
Addition of Note
Section 12.1.5: Change to RoHS compatible connectors and cables
Section 12.1.8 (2) (a): Change of personal computer description
Section 12.1.9 (2): Change of power supply notation in diagram
Addition of Note
Section 12.2.1: Change of crimping terminal of “b” in table 12.2
Section 12.2.7 (2) (b): Addition of sentence for varistor recommendation
Section 12.2.7 (2) (d): Change of sentence in connection diagram
Partial change of outline drawing
Section 12.2.7 (2) (f): Addition of input power varistor (recommended)
Section 12.2.9 (2): Addition of diagram
Section 12.2.9 (3) (b): Addition of surge protector
Section 13.3: Change of WARNING sentence
App.2: Addition of List of RoHS Compatible Product
MODEL
MR-J2S-B GIJUTU SIRYOU
MODEL
CODE
1CW502
SH (NA) 030007-G (0711) MEE Printed in Japan
HEAD OFFICE : TOKYO BLDG MARUNOUCHI TOKYO 100-8310
This Instruction Manual uses recycled paper.
Specifications subject to change without notice.
General-Purpose AC Servo
J2-Super
Series
SSCNET Compatible
MODEL
MR-J2S- B
SERVO AMPLIFIER
INSTRUCTION MANUAL
G
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement