Buderus Logamatic EMS RC35 Service Instructions


Add to my manuals
60 Pages

advertisement

Buderus Logamatic EMS RC35 Service Instructions | Manualzz
Installation and
service instructions
6 720 618 477-00.1RS
Room controller
For contractors
RC35 programming unit
Read carefully
before installation
and servicing.
6 720 642 298 (10/2009) GB
Logamatic EMS
Contents
Contents
Guide to instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1
Key to symbols and safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2
Product information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 EU Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Standard delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4 Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5 Validity of these instructions for function modules (accessories) . . . . . . . . . . . . . . . . . .
2.6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Choosing the right installation position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 Installation in reference room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.2 Installation on boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Types of installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Installation and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Attaching or removing the programming unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
10
10
11
11
12
13
4
Principles of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Overview of controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Introduction to the service menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Overview of the service menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
14
15
17
5
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 General commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Checklist: important parameters for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Quick commissioning (menu quick operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Detailed commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5 System handover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6 Shutting down/switching off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7 Operating information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
18
18
19
20
21
21
22
22
2
7
7
7
7
8
9
9
Logamatic EMS RC35 programming unit - Subject to technical modifications
Contents
6
System settings (Service menu – Settings) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Plant data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.1 Building type (adjusting the outside temperature) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.2 Minimum outside temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Boiler data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Heating circuit data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3.1 Assignment of programming unit/remote control unit in the software . . . . . . . . . . . . . .
6.3.2 Control mode (outside temp. contr./room influence) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3.3 Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3.4 Setback modes (night setback) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3.5 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 DHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 Solar data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6 RC35 calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7 Contact details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
23
24
25
26
27
31
31
32
33
34
36
39
40
41
7
Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1 Function test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Monitor value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3 Error message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4 Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.5 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
42
43
44
45
45
8
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
9
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
10 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
11 Service menu RC35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Logamatic EMS RC35 programming unit - Subject to technical modifications
3
Guide to instructions
Guide to instructions
These installation and service instructions contain all information on the function and settings of the
Logamatic RC35 programming unit.
Introduction to the service menu
Chapter 4.2 explains in detail the steps needed for programming all the settings in the service menu.
Operation is only briefly dealt with in the following sections.
Display texts
Words appearing on the display are shown in bold in flowing text.
Example: USER MENU
4
USER MENU
standard display
operation modes
switching programme
sum./win. threshold
Logamatic EMS RC35 programming unit - Subject to technical modifications
Key to symbols and safety instructions
1
1
Key to symbols and safety instructions
1.1 Key to symbols
Warning information
Warnings in this document are identified by a warning triangle and printed against a
grey background.
If there is a danger due to electricity, the exclamation mark in the warning triangle is
replaced by a lightning symbol.
Signal words at the start of a warning indicate the type and seriousness of the ensuing risk if
measures to prevent the risk are not taken.
• NOTE indicates that material losses may occur.
• CAUTION indicates that minor to medium injury may occur.
• WARNING indicates that severe injury may occur.
• DANGER indicates a risk to life.
Important information
Important information where there is no risk to people or property is indicated with the
adjacent symbol. It is bordered by horizontal lines above and below the text.
Additional symbols
Symbol
Explanation
B
Action step
Æ
Cross-reference to other parts of this document or to other documents
•
List/list entry
–
List/list entry (second level)
Tab. 1
Logamatic EMS RC35 programming unit - Subject to technical modifications
5
1
Key to symbols and safety instructions
1.2 Safety instructions
Installation and commissioning
B Observe these instructions to ensure correct operation.
B The appliance must only be installed and commissioned by an authorised installer.
Risk to life from electric shock
B The power supply must be connected by a qualified electrician.
B Observe the connection diagram.
B Before installation: isolate all poles of the power supply (230 V AC). Secure against unintentional
reconnection.
B Never install this appliance in wet rooms.
B Never connect this appliance to the 230 V mains.
Risk of damage due to operator error
Operator errors can lead to injuries and/or material losses.
B Ensure that children never operate this appliance unsupervised or play with it.
B Ensure that only individuals who can operate this appliance correctly have access to it.
Warning: frost
The heating system can freeze up in cold weather if it is not in operation.
B Leave the heating system permanently switched on.
B Enable frost protection.
B In case of faults: immediately remedy the fault.
6
Logamatic EMS RC35 programming unit - Subject to technical modifications
Product information
2
2
Product information
2.1 Correct use
The RC35 programming unit must only be used to operate and control Buderus heating systems.
B Always use this appliance correctly and in conjunction with the specified control systems.
B Observe all regulations and standards applicable to the installation and operation of the system
in your country!
The boiler must be equipped with EMS (energy management system) or UBA1.x (universal burner
controller).
Never operate the programming unit with the control units of the Logamatic 2000/4000 series.
We recommend always operating the heating system with the programming unit (only emergency
operation possible without programming unit).
If using remote control units RC2x produced before or in 2005, only two remote control units can
be connected. In case of related questions, please contact your local Buderus sales office.
These instructions describe all possible functions of the RC35 programming unit. Some of these
functions may not be available, depending on which boiler (combustion controller) is used. You will
find information on this in the relevant chapter.
For information regarding the combustion controller, see menu DIAGNOSIS\VERSIONS
(Æ page 45).
2.2 EU Declaration of Conformity
The design and operation of this product conform to the European Directives and the supplementary
national requirements. Its conformity is demonstrated by the CE designation. You can call up the
Declaration of Conformity for this product on the internet at www.buderus.de/konfo or request it
from your local Buderus sales office.
2.3 Standard delivery
•
•
•
•
RC35 programming unit
Operating instructions
Installation and service instructions
Wall mounting base, mounting materials
Logamatic EMS RC35 programming unit - Subject to technical modifications
7
2
Product information
2.4 Specification
Unit
V
W
W
mm
g
°C
°C
%
Power supply via BUS system
Power consumption
Power consumption with backlighting
Dimensions (width/height/depth)
Weight
Operating temperature
Storage temperature
Relative humidity
CE designation
Tab. 2
RC35
16 V DC
0.3
0.6
150/90/32
233
0 to +50
0 to +70
0 to 90
Specification - RC35 programming unit
Temperature sensor characteristics
When measuring temperature sensors, observe the following requirements:
• Isolate the system before measuring.
• Measure the resistance at the cable ends.
• The resistances represent mean values and are subject to tolerances.
Flow temperature sensor
Outside temperature sensor
°C
kΩ
– 20
96.358
– 15
72.510
– 10
55.054
–5
42.162
0
32.556
5
25.339
10
19.872
15
15.699
20
12.488
25
10.001
30
8.060
Tab. 3
8
DHW temperature sensor
°C
kΩ
10
19.872
16
15.699
20
12.488
25
10.001
30
8.060
35
6.535
40
5.331
45
4.372
50
3.606
55
2.989
°C
60
65
70
75
80
85
90
95
100
kΩ
2.490
2.084
1.753
1.481
1.256
1.070
0.915
0.786
0.677
Resistances of the temperature sensors, for EMS only
Logamatic EMS RC35 programming unit - Subject to technical modifications
Product information
2
2.5 Validity of these instructions for function modules (accessories)
These instructions also apply to the programming unit when used in conjunction with the MM10
mixer module and the WM10 low loss header module.
Additional setting options may be found in some menus, if your heating system is equipped with
alternative function modules (e.g. solar module SM10). These setting options are explained in a
separate manual.
2.6 Accessories
For detailed information regarding suitable accessories, see the catalogue.
• Mixer module MM101) for control of a 3-way valve. A description of the MM10 is included in the
RC35 instructions.
• Low loss header module WM101) for operating a low loss header
• Solar module and additional EMS modules (e.g. connection module ASM10)1)
• Remote control1) (e.g. RC2x, RC20/RF) respectively for controlling one heating circuit
• Outside temperature sensor, external room temperature sensor
1) The use of modules is not possible for boilers with UBA1.x or DBA.
Logamatic EMS RC35 programming unit - Subject to technical modifications
9
3
3
Installation
Installation
3.1 Choosing the right installation position
3.1.1 Installation in reference room
If the system is room-temperature controlled, the following requirements must be observed:
• Installation position on an internal wall (Æ Fig. 1)
• Maintain the specified distance from the door (to avoid draughts).
• Allow clearance below the programming unit (Æ Fig. 1, shaded area) (to ensure correct
temperature measurement).
• The reference room (= installation room) must be as representative as possible of the entire
home. External heat sources in the reference room (e.g. sunlight or other heat sources such as
an open fire) affect the control functions. This means it may be too cold in rooms without external
heat sources.
• Always open the thermostatic radiator valves fully in the reference room to prevent the two
temperature controllers influencing each other.
If there is no suitable reference room, we recommend setting the system to weathercompensated control instead (this requires an outside temperature sensor).
Alternatively, you could install an external room temperature sensor in the room with the
greatest heating requirements (e.g. living room).
6 720 618 477-01.1RS
Fig. 1
10
Minimum clearances for installation in a reference room
Logamatic EMS RC35 programming unit - Subject to technical modifications
Installation
3
3.1.2 Installation on boiler
Installation directly on the boiler is possible where the boiler is equipped with the Energy
Management System (EMS).
The outside temperature sensor for weather-compensated control is not delivered as standard, but
can be ordered as an accessory.
3.2 Types of installation
The programming unit can be installed in three different ways:
• As only programming unit in the system (factory setting): the programming unit is installed in the
living space (reference room) or on the boiler.
Example: detached house with one heating circuit.
• As the only programming unit in a heating system with two or more heating circuits1) (Æ Fig. 2
[1]).
Examples: underfloor heating on one floor, radiators on the others; or a main flat together with a
separate granny flat or doctor's surgery.
• In conjunction with a remote control (e.g. RC2x, RC20/RF, Fig. 2, [2]). In this case there are
always two separate heating circuits. Remote control units cannot be used for boilers with
UBA1.x.
Examples: underfloor heating on one floor, radiators on the others; or a main flat together with a
separate granny flat or doctor's surgery.
1
2
HC1
HC1
HC2
HC2
6 720 641 642-01.1RS
Fig. 2
1
2
Options for a heating system with two heating circuits
Both heating circuits are controlled by one programming unit.
Each heating circuit has its own programming unit / remote control unit.
1) Not possible with boilers with UBA1.x and DBA.
Logamatic EMS RC35 programming unit - Subject to technical modifications
11
3
Installation
3.3 Installation and connections
Only use the wall mounting base with screw terminals.
B Replace wall mounting bases without screw terminals that may already be installed.
The wall mounting base can be attached directly to the wall or on a flush box.
When mounting on a flush box, note the following:
B Draught from within the flush box must not be able to falsify the capture of the room temperature
by the programming unit.
If required, stuff the flush box with insulation material.
B Use horizontal or vertical fixing holes [4].
B Fit the wall mounting base (Æ Fig. 3, left).
B Connect the two-core BUS cable from the Energy Management System (EMS) at terminals “RC”
[5].
– Cable type: 2 x 0.75 mm2 (0.5 – 1.5 mm2), max. length 100 m
– Polarity is irrelevant for the two wires.
B Do not lay the cables parallel to power cables.
1
3
2
5
4
6
4
1
3
2
6 720 618 477-03.1RS
Fig. 3
1
2
3
4
5
6
12
Mounting the wall mounting base (left) and connecting the wires (right)
Hole drilled in the wall
Screws (included with the unit) for surface-mounting on the wall
Vertical mounting holes for mounting on a flush box
Horizontal mounting holes for mounting on a flush box
“RC” terminals for EMS (boiler)
“EXT” terminals for external room temperature sensor or for jumper
Logamatic EMS RC35 programming unit - Subject to technical modifications
Installation
3
B A jumper is required at terminals “EXT” [6] (delivered condition) if the RC35 programming unit is
operated without an external room temperature sensor.
B If the RC35 programming unit operates together with an external room temperature sensor, remove
the factory-fitted jumper at “EXT” and connect the external room temperature sensor in its place.
3.4 Attaching or removing the programming unit
Attaching the programming unit
1. Hook the programming unit at the top into the mounting plate in the direction of the arrow.
2. Push the programming unit at the bottom in the direction of the arrow against the mounting plate
until it clicks into place.
1.
2.
6 720 618 477-04.1RS
Fig. 4
Attaching the programming unit
Removing the programming unit
1. Press the button underneath the mounting plate in the direction of the arrow.
2. At the same time pull the programming unit forwards.
3. Remove the programming unit by lifting upward.
3.
2.
1.
Fig. 5
6 720 618 477-10.1RS
Removing the programming unit
Logamatic EMS RC35 programming unit - Subject to technical modifications
13
4
4
Principles of operation
Principles of operation
4.1 Overview of controls
Key to diagram:
1
2
Flap; pull the recessed grip on the left to
3
4
open
2
Display
3
Rotary selector for changing values and
temperatures or for navigating through
the menus
1
4
Buttons for basic functions:
When the LED lights up,
“AUT” (automatic)
•
“Daytime operation” (manual)
•
5
6 720 618 477-08.1RS
the switching program is active (automatic changeover between day and
night room temperatures).
the heating system operates at the set day room temperature. DHW
heating is enabled (factory setting).
“Nighttime operation” (manual)
•
the heating system operates at the set nighttime room temperature.
Frost protection is active. DHW heating is off (factory setting).
“DHW”
•
the DHW temperature has fallen below its set value. Pushing this key
means DHW will be heated up again (the LED flashes during heat-up).
5
Buttons for additional functions:
Function:
“Menu/OK”
Open the user menu and confirm the selection.
“Time”
Set the time.
“Date”
Set the date.
“Temperature”
Set the room temperature.
“Info”
Open the Info menu (to view values).
“Back”
Go back one step or one menu item.
When rotary selector is turned at the same time: change setting.
In Automatic mode, an additional LED lights up with the “AUT” LED to indicate which operating status is currently active (“day
mode” or “night mode”). Exception: in the case of boilers with UBA1.x, only the “AUT” LED lights up. The “DHW” LED can
also be switched off. On boilers with UBA1.x the “DHW” LED does not illuminate.
14
Logamatic EMS RC35 programming unit - Subject to technical modifications
Principles of operation
4
4.2 Introduction to the service menu
You can use the SERVICE MENU to set the parameters for the system. It also contains functions
for diagnosis, maintenance purposes, and carrying out a reset. The procedure for operation is
always the same:
1.
2.
3.
4.
5.
Open the flap (by pulling the recessed grip on the left).
Press
+
+
at the same time to open the SERVICE MENU.
Turn rotary selector
to change the selection.
Press
to make your selection.
To change the value, hold down
(the value starts flashing) and turn rotary selector
same time. Release
.
The modified value is saved.
6. Press
to go back one step.
Press
several times or close the flap to show the standard display again.
at the
Example: Setting the building type (adjusted time)
Operation
1.
Open the flap (by pulling the recessed grip on the left).
2.
Press
+
+
simultaneously,
to open the SERVICE MENU.
Result
Fr
outside temp.
h
1
SERVICE MENU
Bquick operation
settings
diagnosis
servicing
3.
Turn rotary selector
anti-clockwise, until settings is
selected.
Press
to confirm the selection.
SERVICE MENU
quick operation
Bsettings
diagnosis
servicing
Tab. 4
How to use the service menu (example)
Logamatic EMS RC35 programming unit - Subject to technical modifications
15
4
Principles of operation
Operation
4.
5.
Result
The SERVICE\SETTINGS menu opens.
Turn rotary selector
anti-clockwise until boiler data is
selected.
Press
to select boiler data.
Menu SETTINGS\BOILER opens.
SERVICE\SETTINGS
Bplant data
boiler data
domestic hot water
heating circuit 1
SETTINGS\BOILER
What type of building
do you have?
medium
6.
To change the value, hold down
(the value starts flashing) and turn rotary selector
same time.
at the
SETTINGS\BOILER
What type of building
do you have?
medium
7.
Release
.
The value stops flashing. The modified value is saved.
SETTINGS\BOILER
What type of building
do you have?
light
8.
If you have carried out this example as practice only, make
sure that the original setting is retained.
To do so, repeat steps 6 and 7 if necessary.
SETTINGS\BOILER
What type of building
do you have?
medium
9.
Press
to go back one step.
-orTo finish entering the settings: press
shut the flap.
several times or
The standard display re-appears.
You can enter all settings in the SERVICE MENU using this procedure.
Tab. 4
16
How to use the service menu (example)
Logamatic EMS RC35 programming unit - Subject to technical modifications
Principles of operation
4
4.3 Overview of the service menu
The SERVICE MENU is divided into the following menus and submenus:
Menu
quick operation
settings
(all parameters)
diagnosis
servicing1)2)
Reset1)
Tab. 5
Submenu
Contents/function
The most important parameters from the
“settings” menu to configure the heating system
plant data1)
Parameters: language, number of heating
circuits, installed modules, building type,
minimum outside temperature
Parameters: pump run-on time and modulation
boiler data1)2)
1)
heating circuit data Parameters of the installed heating circuits
domestic hot water1) Parameters for domestic hot water
solar data2)
If solar is installed: see documentation for the
solar module
RC35 calibration
Parameters: calibration of the displayed room
temperature
contact data
Entering the heating contractor's name and
telephone number
Activating individual components for test
function test1)2)
purposes
monitor value
Viewing target values and actual values
Viewing error messages
error message1)
htg. charact. curve
Viewing the set heating curve in the form of a
graph
versions
Viewing software versions
service interval
Setting times for maintenance, by hours run or
by date
current messages
Viewing service messages
RESET servicing
Resetting service messages
factory setting
Resetting all parameters to their factory settings
error list
service message
operating hours
Page
20
23
26
27
36
39
40
41
42
43
44
45
45
46
46
46
47
47
47
47
Service menu navigator
1) Limited use depending on the boiler used.
2) May not be available or possible, depending on the boiler used.
Logamatic EMS RC35 programming unit - Subject to technical modifications
17
5
5
Commissioning
Commissioning
5.1 General commissioning
Operation
1.
Result
Switch on the heating system.
While setting up the connection between the RC35 and EMS
or UBA1.x, the display shows the message on the right.
RC35 version:
connect to:
connection setup ...
please wait
If the display shows a different message, look it up in
Chapter 10, page 48.
2.
Set the language:
Open flap. Hold down
rotary selector
.
and select the language with
Open cover in order
to set language with
OK key.
language set:
English
3.
Set the date and time:
SET DATE
Hold down
and set the flashing values with rotary
selector
. Release button.
set year
Hold down
and set the flashing values with rotary
selector
. Release button.
01.01.2000
In the event of a power failure, the date and time are retained
for up to 8 hours. All other settings are saved.
4.
Press
+
+
SERVICE MENU.
simultaneously, to open the
SERVICE MENU
Bquick operation
settings
diagnosis
servicing
Tab. 6
General commissioning
If necessary, you can change the contrast on the display:
B Hold down
and
and turn rotary selector
at the same time.
18
Logamatic EMS RC35 programming unit - Subject to technical modifications
Commissioning
5
5.2 Checklist: important parameters for commissioning
When commissioning the device, ensure the satisfaction of both parties, making sure that the
heating system meets the customer's needs and will not give cause for complaints. In our
experience, the following parameters are very important for the satisfaction of the system user:
B Find out the system owner's requirements and preferences regarding:
Setting options
Factory
setting
SERVICE
MENU\
settings\
The required type of reduction
(night setback)
Outdoor setback
mode;
reduced operation;
Room setback mode;
shut-down mode
Outdoor
setback
mode
heating circuit x,
page 28
The required control mode
outside temp. contr.,
room temp. controlled
outside
temp. contr.
heating circuit x,
page 31
The correct heating curve
By means of the
following parameters:
design temperature,
minimum outside
temperature, offset,
and set room
temperature
The correct building type
(adjusting the outside temp.)
light, medium, heavy
medium
plant data,
page 24
The switching frequency of the
DHW circulation pump1)
permanent operation,
1 x, 2 x, 3 x, 4 x, 5 x,
6 x per hour for
3 minutes at a time
2x
domestic hot
water, page 37
Priority DHW
yes, no
yes
heating circuit x,
page 29
Switching program
(times)
Standard program
(e.g. family), user
defined program
family
heating circuit x,
page 30
Tab. 7
heating circuit x,
page 28
Checklist: important parameters for commissioning
1) This function is not available for boilers with UBA1.x, DBA, UBA-H3 or for DHW heating according to the
instantaneous water heating principle.
Logamatic EMS RC35 programming unit - Subject to technical modifications
19
5
Commissioning
5.3 Quick commissioning (menu quick operation)
B Press
to open menu quick operation.
SERVICE MENU
Bquick operation
settings
diagnosis
servicing
SHORTCUT\
BASIC SETUP
HYDR. SEP.
Input
Menu item
range
Which language should English, ...
be used?
Have you installed a
yes, no
module for the
hydraulic separator?
Is a sensor for a low
loss header
connected?
SYSTEM
NO. OF MIXERS
Is heating circuit 1
installed (unmixed
heating circuit)?
How many mixed
heating circuits are
installed?
HEATING CIRCUIT Which operating unit is
1
assigned to heating
circuit 1?
(and other heating
circuits)
How should heating
circuit 1 be controlled?
Which heating system
does heating circuit 1
have?
Tab. 8
20
Factory
setting
Francais
no
no,
no
on the
boiler,
on the low
loss header
module
yes, no
yes
0 to 3
0
RC2x/
RC20/RF,
RC35,
none
outside
temp.
contr.,
room temp.
controlled
radiator,
convector,
floor
RC35
outside
temp.
contr.
radiator
Other information
In conjunction with
MCM10 this setting is
automatically set to “yes”;
the mask is hidden.1)2)
When a low loss header
is used, connect the
temperature sensor to the
low loss header module.3)
Set the address at the
rotary coding switch on
the mixer module (factory
setting HC2).1)
Assigning programming
units to heating circuits
(Æ page 31). General
heating circuit data
(Æ page 27).
Set up any other heating
circuits as per heating
circuit 1.
Heating curve
(Æ page 32)
Quick operation menu navigator
Logamatic EMS RC35 programming unit - Subject to technical modifications
Commissioning
SHORTCUT\
DHW
5
Menu item
Have you installed
domestic hot water?
What should be used
for domestic hot water
heating?
To which temperature
should your domestic
hot water be heated?
SOLAR MODULE
Tab. 8
Have you installed a
solar module?
Input
range
yes, no
Factory
setting
no
3-way
switching
valve
cylinder
primary
pump
30 °C to
80 °C
3-way
switching
valve
5)
60 °C
To be able to change the
DHW temperature, set
DHW on the boiler
programming unit to
“AUT” or enable DHW.
yes, no
no
1)
Other information
4)
Quick operation menu navigator
1) Not possible or available on boilers with UBA1.x or DBA.
2) Not possible on boilers with UBA4.
3) Only possible on boilers with UBA4.
4) Not possible or not available with boilers with DBA.
5) Not available with boilers with UBA1.x, DBA or UBA-H3.
Check whether further settings are required using the checklist on page 19.
5.4 Detailed commissioning
B Check whether the factory settings in menu SERVICE\SETTINGS suit your heating system.
B Note down modified settings if needed.
5.5 System handover
B Ensure that no temperature limits for central heating and DHW have been set at the boiler
programming unit, so DHW and flow temperature can be regulated via the RC35 programming
unit.
B Explain to the customer how the device works and how to operate it.
B Inform customer about the selected settings.
Logamatic EMS RC35 programming unit - Subject to technical modifications
21
5
Commissioning
We recommend you hand these installation and service instructions to the customer for
safekeeping near the heating system.
5.6 Shutting down/switching off
The RC35 programming unit is powered via the heating system and remains permanently ON.
The heating system is only switched off, for example, for maintenance work.
B To start up and shut down the heating system: set the ON/OFF switch on the boiler programming
unit to 1 (ON) or 0 (OFF).
After shutting down or in the event of a power failure, the date and time are retained for
up to 8 hours. All other settings are retained permanently.
5.7 Operating information
EMS BUS subscribers
In a BUS system, only one subscriber can carry out the calculations for a heating circuit.
Consequently, only one RC35 programming unit may be installed in each heating system. If
additional room controllers (e.g. RC2x) are required, these must be installed as remote control
units1) with a set heating circuit address (Æ page 27).
Disable this on boilers with integral weather-compensated control.
Thermostatic radiator valves in the reference room
Radiators in the reference room do not require thermostatic valves2) for room temperaturedependent control. Fully open any thermostatic radiator valves in the reference room.
Pump kick1)
In all operating modes, all the heating circuit pumps are switched on and then off again for
10 seconds every Wednesday at 12 noon to prevent pump damage. The mixers are then set to
“OPEN” for 10 seconds and then “CLOSED”. All pumps and mixers then return to their normal,
regulated operation.
1) This function is not available on boilers with UBA1.x or DBA.
2) Room where a RC35 or RC2x/RC20/RF is installed.
22
Logamatic EMS RC35 programming unit - Subject to technical modifications
System settings (Service menu – Settings)
6
6
System settings (Service menu – Settings)
B Press
+
+
simultaneously to open the SERVICE MENU.
B Turn rotary selector
anti-clockwise, until settings is selected.
B Press
to open menu SERVICE\SETTINGS.
SERVICE MENU
quick operation
Bsettings
diagnosis
servicing
Note that the menu items shown will vary depending on the heating system.
6.1 Plant data
B Press
to select plant data.
The menu SETTINGS\SYSTEM opens.
SERVICE\SETTINGS
Bplant data
boiler data
domestic hot water
heating circuit 1
Input
Menu item
range
Which language should be used? English, ...
Have you installed a module for
yes, no
the hydraulic separator?
Is a sensor for a low loss header
connected?
Is heating circuit 1 installed
(unmixed heating circuit)?
How many mixed heating circuits
are installed?
Have you installed a solar
module?
Tab. 9
Factory
setting
Francais
no
no,
no
at the
boiler,
at the low
loss header
module
yes, no
yes
Other information
In conjunction with MCM10, this
setting is automatically set to “yes”;
the mask is hidden.1)2)
When a low loss header is used,
connect the temperature sensor to
the low loss header module.3)
0 to 3
0
Set the address at the rotary coding
switch on the mixer module (factory
setting HC2).1)
yes, no
no
1)
Navigator for service menu SETTINGS\SYSTEM
Logamatic EMS RC35 programming unit - Subject to technical modifications
23
6
System settings (Service menu – Settings)
Input
Menu item
range
Should the outside temp. damping yes, no
be switched off?
What type of building do you
have?
What is the lowest expected
outside temp. in your region?
Tab. 9
Factory
setting
no
light,
medium
medium,
heavy
– 30 °C to – 10 °C
0 °C
Other information
When selecting “yes” the following
parameter building type will be
hidden.
Building type (heat storage
capacity), Æ Chapter 6.1.1,
page 24.
Æ Chapter 6.1.2, page 25
Navigator for service menu SETTINGS\SYSTEM
1) Not possible or available on boilers with UBA1.x or DBA.
2) Not possible on boilers with UBA4.
3) Only possible on boilers with UBA4.
6.1.1 Building type (adjusting the outside temperature)
A building's heat storage capacity and its characteristic resistance to heat transfer will delay the
effect of outside temperature fluctuations on the rooms inside. Consequently, it is not the current
outside temperature that is crucial but the so-called adjusted outside temperature.
Parameter building type enables the adjustment to be applied that takes account of the fluctuating
outside temperatures. This enables the control to be matched to the characteristics of the building.
The control unit calculates the time constant for adjusting the outside temperature, using the factor
given in Tab. 10 for the stated building type and an internal multiplier, the “runtime” (= 6 minutes).
The time constant is the product of: factor x runtime = adjustment time constant in hours.
Parameter:
building type
light
medium
heavy
Type of construction
E.g. prefabricated building, wood-frame construction
E.g. a building constructed of hollow breeze blocks (factory
setting)
E.g. brick house
Factor
10
30
50
Tab. 10 Calculating the adjustment time constant
24
Logamatic EMS RC35 programming unit - Subject to technical modifications
System settings (Service menu – Settings)
6
Example:
2
1
6 720 618 477-05.1RS
Fig. 6
1
2
This greatly simplified example shows how the adjusted outside temperature follows the
outside temperature, but does not reach its extreme values.
Current outside temperature
Adjusted outside temperature
With the factory settings, changes in the outside temperature affect the calculation of
weather-compensated control after no more than three hours (30 x 6 minutes =
180 minutes).
B To monitor the calculated, adjusted outside temperature and the currently captured
outside temperature: open the menu diagnosis\monitor valueboiler / burner.
6.1.2 Minimum outside temperature
The minimum outside temperature is the mean of all the coldest outside temperatures of recent
years, and helps to determine the heating curve. The value can be taken from the heat requirement
calculation which should be done for every building, or from the climatic zone chart for your region.
Logamatic EMS RC35 programming unit - Subject to technical modifications
25
6
System settings (Service menu – Settings)
6.2 Boiler data
B Turn rotary selector
anti-clockwise until boiler data is selected.
B Press
to select boiler data.
The menu SETTINGS\BOILER is opened.
SERVICE\SETTINGS
plant data
Bboiler data
domestic hot water
heating circuit 1
Factory
Menu item
Input range setting
Boiler pump after-run time deactivated, 5 min
after burner stops?
1 to 60 min,
24 h
Set the pump logic
0 to 65 °C 47 °C
temperature:
Other information
Setting only possible with boilers with
internal pump.1)
Setting only possible in conjunction
with BRM10.
Tab. 11 Navigator for service menu SETTINGS\BOILER
1) Not possible or not available with boilers with UBA1.x.
26
Logamatic EMS RC35 programming unit - Subject to technical modifications
System settings (Service menu – Settings)
6
6.3 Heating circuit data
This chapter explains the settings for all heating circuits using heating circuit 1 as an example.
B Turn rotary selector
anti-clockwise until heating circuit 1 is selected.
B Press
to select heating circuit 1.
SERVICE\SETTINGS
The menu SETTINGS\HTG. CIRC. 1 is opened.
plant data
boiler data
domestic hot water
Bheating circuit 1
Menu item
Should heating circuit 1
be activated?
Which operating unit is
assigned to heating
circuit 1?
How should heating
circuit 1 be controlled?
Which heating system
does heating circuit 1
have?
Input range
yes, no
RC2x/RC20/RF,
RC35, none
Factory
setting
yes
Other information
RC35
See page 31.
For UBA1.x, RC2x is not available.
outside temp.
contr.,
room temp.
controlled
outside
temp.
contr.
radiator,
convector,
floor
radiator
If “none” is selected, then the type of
control is changed over to “outside
temp. contr.” and is then hidden.
“room temp. controlled” can only be
set if RC2x or RC35 have been
assigned.
When selecting “room temp. controlled” room flow will be used.
In case of HC1 setting “floor” only if
this concerns an oil/gas condensing
boiler. Additional heating circuits can
then be installed.
Use a safety thermostat with
underfloor heating systems.
Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1
Logamatic EMS RC35 programming unit - Subject to technical modifications
27
6
System settings (Service menu – Settings)
Menu item
Heating curve
std. tmp. ( – 10 °C)
Input range
30 °C to 90 °C
Factory
setting
Other information
75 °C
(radiator,
convector)
45 °C
(floor)
radiator,
convector:
75 °C
The value in brackets is the setting
for the minimum outside temperature
(Æ page 27). Adjustment only if the
control type is set to “outside temp.
contr.” ( Æ page 32).
max flow temp.
radiator,
Adjustment only if the control type is
convector:
set to “outside temp. contr.”
30 °C to 90 °C1)
( Æ page 32).
Enter the maximum
Adjustment
only if the control type is
floor:
floor: 50 °C
flow temperature:
set
to
“room
temp. contr.”
30 °C to 60 °C
( Æ page 32).
min flow temp.
5 °C to 70 °C
5 °C
Adjustment only if the control type is
set to “outside temp. contr.”
( Æ page 32).
Enter the minimum flow
Adjustment only if the control type is
temperature:
set to “room temp. contr.”
( Æ page 32).
rm. tmp. offset
– 5.0 K to +5.0 K 0.0 K
Offset of heating curve.
Enter the maximum room
influence:
0 K to 10 K
3K
Which type of reduction
should be implemented?
Outdoor setback Outdoor
mode,
setback
reduced operation, mode
Room setback
mode (only if
RC35 or RC2x has
been assigned to
the heating circuit),
shut-down mode
Adjustment only if the control type is
set to “outside temp. contr.”
( Æ page 32).
Adjustment only if the control type is
set to “outside temp. contr.”
( Æ page 31)
Night setback (Æ page 33)
Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1
28
Logamatic EMS RC35 programming unit - Subject to technical modifications
System settings (Service menu – Settings)
Menu item
What outside temp.
should be used for
reduced operation?
Frost protection
What temp. should be
used to trigger frost
protection?
Which frost protection
temp. should be used?
At what outside temp.
should reduction be
interrupted?
Should domestic hot
water priority be
activated?
Mixer2)
Is a mixer installed?
What running time
does the mixer have?
What increase should
be used for the boiler?
Screed drying2)
Should a drying cycle
be carried out?
Every how many days
should the flow temp.
be raised?
By how many Kelvin
should the flow temp.
be raised each time?
Input range
– 20 °C to
+10 °C
6
Factory
setting
5 °C
Other information
Temperature threshold for outdoor
setback mode (Æ page 33).
Adjustment only if the setback mode
is set to “Outdoor setback mode”.
outside temp.,
room temperature,
no frost protection
– 20 °C to
+10 °C
OFF,
– 30 °C to
+10 °C
yes, no
outside
temp.
yes, no
yes
Can only be set for heating circuit 2
onwards.2)
10 sec. to
600 sec.
0 K to 20 K
120 sec.
2)
5K
2)
yes, no
no
Adjustment only if floor has been
selected. DHW heating is not
enabled while screed is drying.2)
every day, every
2nd day to
every 5th day
0 K to 40 K
every day
2)
5K
2)
5 °C
OFF
Room temperature adjustment only if
RC2x or RC35 have been assigned
to the heating circuit (Æ page 34).
Refers to outside temperature
(Æ page 34).
Setback in accordance with
EN 12831 standard (Æ page 34).
no
Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1
Logamatic EMS RC35 programming unit - Subject to technical modifications
29
6
System settings (Service menu – Settings)
Menu item
What is the desired
maximum flow
temperature?
For how many days
should maximum flow
temp. be maintained?
Every how many days
should the flow temp.
be reduced?
Input range
25 °C to 60 °C
Factory
setting
45 °C
0 days to 20 days 4 days
direct normal
Every day
operat., every day,
every 2nd day to
every 5th day
By how many K should 0 K to 20 K
5K
the flow temp. be
reduced each time?
Do you wish to change
yes, no
no
the switching
programme?
Should the switching
yes, no
no
programme be optimised?
What reduction mode
should be used for
holiday?
What outside temp.
should be used?
Outdoor setback Outdoor
mode,
setback
reduced operation, mode
Room setback
mode, shut-down
mode
– 20 °C to
+10 °C
5 °C
Other information
2)
2)
2)
Adjustment only if, for flow
temperature reduction,“direct normal
operat.” has not been selected.4)
When selecting “yes” the system
jumps to the heating circuit
switching program.
Start and stop times are
automatically adjusted according to
the outside temperature, room
temperature and building type (heat
storage capacity).
See page 33.
Adjustment “Room setback mode”
only if a remote control (e.g. RC2x)
has been allocated to the heating
circuit.
If “reduced operation” has been
selected, the standard night temperature will be applied.
Temperature threshold for outdoor
setback mode (Æ page 33).
Adjustment only if setback mode for
holiday was set to “Outdoor setback
mode.”
Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1
1) The setting range can be limited, subject to boiler.
2) Not possible or available on boilers with UBA1.x or DBA.
30
Logamatic EMS RC35 programming unit - Subject to technical modifications
System settings (Service menu – Settings)
6
6.3.1 Assignment of programming unit/remote control unit in the software
This function is not available with boilers with UBA1.x and DBA.
Example: heating system with heating circuit 1 and heating circuit 2 (Æ page 11)
Setting: Which operating unit is
Alternative assigned to the heating circuit?
A
HC 1 = RC35, HC 2 = RC35
(Æ Fig. 2, [1], page 11)
B
HC 1 = none, HC 2 = RC35
(Æ Fig. 2, [1], page 11)
C
HC 1 = RC2x, HC 2 = RC35
(Æ Fig. 2, [2], page 11)
Effect
Same room temperatures for HC 1 and
HC 2
Room temperatures for HC 1 and HC 2
can be set separately
Room temperatures for HC 1 and HC 2
separately adjustable;
adjust the room temperature for HC 1 at
the RC2x
Tab. 13 Settings for room temperature depending on programming unit
6.3.2 Control mode (outside temp. contr./room influence)
The temperature of the heating water in the boiler is defined by the heating curve in the Logamatic
control unit. You can select whether this heating curve will be influenced solely by the outside
temperature, or by a mixture of outside temperature and room temperature.
• outside temp. contr.: If this setting is entered, the boiler temperature calculated in the control
unit will be regulated by variation in the adjusted outside temperature in combination with
selected settings for set room temperature, offset, design temperature and minimum outside
temperature. This temperature is then delivered to the radiators or underfloor heating system by
means of permanent operation of the heating circuit pump.
The only circumstances in which this setting can result in the heating circuit pump being
switched off are summer mode, night setback (subject to the selected setback mode) or DHW
mode (only with DHW priority).
• outside temp. contr. with room temperature hook-up (factory setting): this form of control
functions like a pure weather-compensated control with the difference that parameter maximum
room influence enables the determination whether and to what extent the room temperature
can influence the heating curve.
The programming unit/remote control must be installed in a reference room to ensure that a
representative room temperature is captured.
The higher the parameter is set, the higher the proportion of the room temperature effect on the
heating curve (factory setting 0 Kelvin). This applies when the room temperature exceeds or falls
below the set room temperature. If the maximum room influence parameter is set to 0, the
heating characteristics will be controlled solely by outside temperature.
Logamatic EMS RC35 programming unit - Subject to technical modifications
31
6
System settings (Service menu – Settings)
6.3.3 Heating curve
Parameters: design temperature, maximum and minimum flow temperature and room temperature
offset (parallel offset)
The heating curve is the basis for economical and comfortable operation of the heating system with
weather-compensated control. To calculate this curve, the Logamatic control system requires you
to enter a number of parameters for the heating system, from which it automatically calculates the
optimum heating curve by means of a mathematical formula, taking the adjusted outside temperature
and room control temperature into account.
The room control temperature is an internal operand which is a combination of the required room
temperature (set room temperature) and room influence.
This can be used by the user to influence the heating curve directly by varying the set room
temperature.
The heating curve (Æ Fig. 7, page 33) is generally determined by its base and end points. The base
point is located at 20 °C flow temperature at a room temperature of 20 °C with an adjusted outside
temperature of 20 °C. The end point of the heating curve must be set in accordance with the design
temperature of the heating system.
The two parameters minimum outside temperature (the lowest outside temperature to be
expected in a region, page 25) and std. temp. (the flow temperature that should be reached at
minimum outside temperature) are crucial for the heating curve (level/slope) (Æ Fig. 7, left).
The X-axis of the heating curve graph refers to the range from +20 °C to – 20 °C.
For parameter std. temp. the minimum outside temperature set under system data is
shown by a circle. However, if a minimum outside temperature below – 20 °C is
entered, then the depiction is no longer accurate (the circle then lies away from the
heating curve).
The minimum flow temperature parameter can be used to define a minimum set value (Æ Fig. 7,
[4], page 33). The burner starts again if the set value is no longer achieved.
The heating curve is offset in parallel either up or down by adjusting parameter rm. tmp. offset and/
or the set room temperature (Æ Fig. 7, right, page 33). Setting the offset may be advisable should
the room temperature measured by a thermometer deviate from the selected set value.
32
Logamatic EMS RC35 programming unit - Subject to technical modifications
System settings (Service menu – Settings)
1
6
5
2
4
3
TA
TA
6
T minA
7
T minA
6 720 618 477-06.1RS
Fig. 7
Setting the heating curve. Left: setting the gradient by means of design temperature and
minimum outside temperature. Right: parallel offset possible by means of offset or set
room temperature.
TminA Minimum outside temperature
TA
Design temperature (flow temperature that should be achieved at min. outside temperature)
1
Setting: design temperature 75 °C, minimum outside temperature – 10 °C (standard curve)
2
Setting: design temperature 75 °C, minimum outside temperature – 20 °C
3
Setting: design temperature 50 °C, minimum outside temperature – 10 °C
4
Setting: minimum flow temperature 35 °C
5
Setting: design temperature 75 °C, minimum outside temperature – 10 °C (standard curve)
6
Parallel offset of standard curve by changing the offset +3 or by increasing the set room temperature
7
Parallel offset of the standard curve by changing the offset – 3 or by reducing the set room temperature
6.3.4 Setback modes (night setback)
There are a number of different setback modes available, which allow night setback to be adjusted
to suit the differing needs of the user:
• reduced operation: the rooms are maintained at a reasonable temperature at night by constant
heating operation (pump runs constantly). A set room temperature for nighttime can be set. It is
at least 1 K lower than the set day temperature. The heating curve is calculated in accordance
with these details.
We recommend these settings for an underfloor heating system.
• shut-down mode: boiler and heating circuit pump are off, frost protection is active. The pump
only starts in frost protection mode.
This setting is not recommended if there is a risk that the building would cool down too severely.
Logamatic EMS RC35 programming unit - Subject to technical modifications
33
6
System settings (Service menu – Settings)
• Room setback mode: The heating system operates as if in setback mode (as described under
“reduced operation”), if the room temperature falls below the selected night temperature (set
value). Boiler and heating circuit pump stop (as described under setback mode “shut-down
mode”) if the room temperature exceeds the set night temperature by more than 1 K.
This setback mode is only possible if a programming unit/remote control is installed in a
representative room (reference room) or if the room temperature is captured by an external room
temperature sensor.
• Outdoor setback mode: The heating system operates as in reduced heating mode (as
described under setback mode “reduced operation”) if the adjusted outside temperature does
not reach the value of an adjustable outside temperature threshold. The heating system remains
off above this threshold (as described under setback mode “shut-down mode”). This setback
mode is suitable for heating circuits which do not have their own programming unit / remote
control unit. The operating mode protects the rooms from cooling down too much once a certain
outside temperature is reached.
6.3.5 Frost protection
The frost protection function offers the following options:
• no frost protection (frost protection is switched off).
• outside temp. (outside temperature sensor required) The heating circuit pump starts
automatically if the outside temperature falls below the adjustable frost protection temperature
threshold.
• room temperature (room temperature sensor of the RC35 or RC2x) The heating circuit pump
starts automatically if the room temperature falls below the permanently set value of 5 °C. The
heating circuit pump stops automatically if the room temperature rises above 7 °C.
CAUTION: System damage due to frost!
The settings no frost protection and room temperature provide either no frost
protection or inadequate frost protection. When these settings are selected, the display
shows a message indicating the risk of freezing.
B For reliable frost protection, use the outside temp. setting.
The setting room temperature offers no absolute frost protection, as lines routed
through external walls may freeze up, for example, although the temperature in the
reference room may be significantly above 5 °C.
At what outside temp. should reduction be interrupted?
EN 12831 requires that, for the maintenance of a level of comfortable heat, heating areas and heat
sources be designed to deliver a specific output if the heating system cools down to a specific value
through night setback.
34
Logamatic EMS RC35 programming unit - Subject to technical modifications
System settings (Service menu – Settings)
6
In parameter At what outside temp. should reduction be interrupted?, you can set an outside
temperature threshold (relative to the adjusted outside temperature, Æ page 24).
1
2
5°C
TV
TV
Fig. 8 shows how the frost protection function works, with and without this parameter activated.
Settings selected: frost protection by outside temp.; frost protection temp. 5 °C.
TA
1
2
5°C
TA
3
-15°C
6 720 618 477-07.1RS
Fig. 8
TA
TV
1
2
3
Effects of the parameter “At what outside temp. should reduction be interrupted?”.
Left: parameter set “OFF” (factory setting). Right: parameter set to – 15 °C.
Outside temperature
Flow temperature
Standby
Reduced mode (at set nighttime room temperature)
Heating mode (at set daytime room temperature)
The heating system changes from reduced mode to standard heating mode [3] if the outside
temperature falls below – 15 °C. This allows smaller heating surfaces to be utilised.
Logamatic EMS RC35 programming unit - Subject to technical modifications
35
6
System settings (Service menu – Settings)
6.4 DHW
WARNING: Risk of scalding at the hot water draw-off points.
There is a risk of scalding at the hot water draw-off points if DHW temperatures can be
set above 60 °C and during thermal disinfection.
B Advise customers that they should only draw off mixed water.
B Turn rotary selector
anti-clockwise until DHW is selected.
B Press
to select domestic hot water.
Menu SETTINGS\DHW opens.
Menu item
Input range
Have you installed domestic yes, no
hot water?
Limiting value for maximum
60 °C to 80 °C
dom. hot water temp. setting:
Factory
setting
no
60 °C
To which temperature should 30 °C to 80 °C
your domestic hot water be
heated?
60 °C
What should be used for
3-way switching
domestic hot water heating? valve, cylinder
primary pump
Do you wish to change the
yes, no
dom. hot water switching
programme?
3-way
switching
valve
no
SERVICE\SETTINGS
plant data
boiler data
Bdomestic hot water
heating circuit 1
Other information
DHW cannot be uninstalled in
the case of boilers with DBA.
Subject to the boiler in use, a
the maximum possible set
DHW temperature is limited to
60 °C.
If the limit has been set to
> 60 °C, this higher value can
also be selected in the “USER
MENU”.
1)
When selecting “yes” the
system jumps to the DHW
switching program.
Tab. 14 Navigator for service menu SETTINGS\DHW
36
Logamatic EMS RC35 programming unit - Subject to technical modifications
System settings (Service menu – Settings)
Menu item
DHW circulation2)3)
Is a circulation pump
installed?
How frequently should
the circul. pump be
switched on per hour?
6
Input range
Factory
setting
yes, no
no
once for 3 minutes, Twice for
twice for 3 minutes, 3 minutes
3 times for 3 minutes,
4 times for 3 minutes,
5 times for 3 minutes,
6 times for 3 minutes,
permanent operation
switch on circ. pump
Do you wish to change
the circulation switching
programme?
Other information
yes, no
Thermal disinfection2)
Should a thermal
yes, no
disinfection be carried
out?
What temperature should 60 °C to 80 °C4)
be used for thermal
disinfection?
On which day should the Monday, Tuesday,
thermal disinfection be
Wednesday,
performed?
Thursday, Friday,
Saturday, Sunday,
daily
At what time of day
0:00h to 23:00h
should the th. disinfection
be performed?
no
Graphical display of number of
times the pump is switched on
per hour.
When selecting “yes” the
system jumps to the DHW
circulation switching program.
no
70 °C
At temperatures above 60 °C
there is a risk of scalding at the
draw-off points during and after
thermal disinfection!
Tuesday
1:00h
Times entered must be whole
hours only (no minutes).
Tab. 14 Navigator for service menu SETTINGS\DHW
Logamatic EMS RC35 programming unit - Subject to technical modifications
37
6
System settings (Service menu – Settings)
Menu item
Input range
Should the LED of the single yes, no
charge key be activated?
Start delay for preheated
DHW (e.g. solar):
OFF,
1 sec. to 50 sec.
Factory
setting
yes
OFF
Other information
The heating once only function
is retained, but is no longer
indicated by the LED.5)
This function depends on the
boiler used.
Tab. 14 Navigator for service menu SETTINGS\DHW
1) Not possible or available on boilers with UBA1.x, UBA-H3 or DBA.
2) Not possible or available on boilers with UBA1.x or DBA.
3) On boilers with UBA-H3 subject to the availability of the PZ output (e.g. with module LM10).
4) Subject to the boiler in use, the temperature is permanently fixed an cannot be modified.
5) Not possible or available on boilers with UBA1.x.
38
Logamatic EMS RC35 programming unit - Subject to technical modifications
System settings (Service menu – Settings)
6
6.5 Solar data
B Turn rotary selector
anti-clockwise, until solar data1) is selected.
B Press
to select solar data.
Menu SETTINGS\SOLAR opens.
Menu item
What is the max. stor.
cylinder temp. of the solar
system?
What temp. must the
storage cylinder not fall
below?
What is the minimum pump
rating?
SERVICE\SETTINGS
boiler data
domestic hot water
heating circuit 1
Bsolar data
Other
information
Input range
30 °C to 90 °C
Factory setting
60 °C
30 °C to 54 °C, OFF
OFF
1)
20 % to 100 %
100 %
1)
1)
Tab. 15 Navigator for service menu\Settings\Solar data
1) Not possible or not available with boilers with UBA1.x or DBA.
For explanations of the settings, see the documentation for the solar module.
Logamatic EMS RC35 programming unit - Subject to technical modifications
39
6
System settings (Service menu – Settings)
6.6 RC35 calibration
B Turn rotary selector
anti-clockwise, until RC35 calibration is selected.
B Press
to select RC35 calibration.
SERVICE\SETTINGS
Menu SETTINGS\CALIB. RC35 opens.
domestic hot water
heating circuit 1
solar data
BRC35 calibration
Menu item
RC35 calibration
Input range
– 5.0 K to +5.0 K
Factory setting
0.0 K
Other
information
Tab. 16 Navigator for service menu SETTINGS\CALIB. RC35
Calibrating the displayed room temperature (calibration)
If there is a separate thermometer near the programming unit, it may show a different room
temperature to that shown on the programming unit. You can use this function to adjust (“calibrate”)
the programming unit to match the thermometer.
Before calibrating the room temperature, consider the following:
• Is the thermometer more accurate than the programming unit?
• Is the thermometer located close to programming unit so that they are both subject to the same
heat influences (e.g. sunlight, fireplace)?
A thermometer may indicate temperature fluctuations more slowly or rapidly than the
programming unit.
B Therefore, never calibrate the programming unit during phases when your heating
system is cooling down or heating up.
Example: if the thermometer is showing a temperature 0.5 °C higher than the programming unit,
enter +0.5 K as the calibration value.
40
Logamatic EMS RC35 programming unit - Subject to technical modifications
System settings (Service menu – Settings)
6
6.7 Contact details
Contact details are automatically displayed to the end user if a fault develops.
B Turn rotary selector
anti-clockwise, until contact data is selected.
B Press
to select contact data.
Menu SETTING\CONTACT opens.
Menu item
Name and tel. No. of
supplier:
Input range
___________
SERVICE\SETTINGS
heating circuit 1
solar data
RC35 calibration
Bcontact data
Other information
___________
Tab. 17 Navigator for service menu SETTING\CONTACT
Entering company name and telephone number
Two rows are available, each with 21 characters (capital letters, numbers and some other symbols).
The current cursor position will flash (marked by “_”).
1. Hold down
and turn rotary selector
at the same time to select another character.
Release
.
The modified character is saved.
2. Turn rotary selector
anti-clockwise or clockwise to move the cursor.
3. Enter a space to delete a character.
4. Press
to save your entries and leave the menu.
Logamatic EMS RC35 programming unit - Subject to technical modifications
41
7
7
Diagnosis
Diagnosis
The diagnosis service menu contains a number of tools for diagnosis:
•
•
•
•
•
function test1)2)
monitor value
error message3)
htg. charact. curve
versions
B Press
+
+
simultaneously to open the SERVICE MENU.
B Turn rotary selector
anti-clockwise until diagnosis is selected.
B Press
to open the SERVICE\DIAGNOSIS menu.
SERVICE MENU
quick operation
settings
Bdiagnosis
servicing
Note that the menu items shown will vary depending on the heating system.
7.1 Function test
You can use this menu to activate separate EMS components individually in order to test their
functions1), 2). The available functions and the possible settings vary depending on the system
installed.
B Hold down
and simultaneously turn the rotary selector to change
the setting:
e.g. BURNER OFF to BURNER ON.
The change takes effect when you release
.
B Turn rotary selector
(function test).
to change between different displays
FCT. TEST\BOILER
valve 1 cl. 2 cl.
ignition
OFF
flame
OFF
flame current 0.0μA
BBURNER
ON
FCT. TEST\BOILER
act. boil. tmp. 60°C
air temperature 32°C
flue gas temp.
78°C
flame
OFF
BBURNER
OFF
1) This function has a limited application on boilers with UBA-H3.
2) Not possible or not available with boilers with UBA1.x or DBA.
3) Boilers with DBA, UBA1.x or UBA-H3: restricted functionality only.
42
Logamatic EMS RC35 programming unit - Subject to technical modifications
Diagnosis
7
Observe the information which appears on the display when you switch to menus or
enter settings. Press any key or turn the rotary selector to confirm the information.
No settings will be allowed that might result in damage to the components. This is why
some settings may not be accepted.
7.2 Monitor value
You can use the monitor value menu to view the set and actual values for the heating system. The
set value will be displayed first and then the actual value. The values displayed for monitoring
purposes vary depending on the system installed.
If the values to be displayed do not all fit on the screen, they are displayed as a list. The
list can be moved up or down by turning rotary selector.
DIAGNOSIS\MONITOR VALUE
boiler/burner
MCM10/cascade
boiler1)
Pump module
hydraulic separator2)
domestic hot water
heating circuit 1
solar2)
module UM102)
wireless transm.2)
bus users2)
Other information
Only in conjunction with MCM10 (instead of “boiler/burner”)
Only in conjunction with MCM10 (instead of “boiler/burner”)
Values are displayed for additional heating circuits, if these
are installed.
For solid fuel boilers; EV2 = external interlock (input)
FB = strength of the wireless signal
Tab. 18 Navigator for service menu DIAGNOSIS\MON. VALUE
1) Depending on the boiler used, the monitor values are displayed in individual masks. Call up the monitor
values for the next boiler by turning the rotary selector. Symbol present = the corresponding function is
active. Explanation of symbols Æ Tab. 19, page 44.
2) Not possible or available on boilers with UBA1.x or DBA.
Logamatic EMS RC35 programming unit - Subject to technical modifications
43
7
Diagnosis
Burner operational
Heating demand
DHW demand
Flue gas test active
Service required / fault has occurred
Tab. 19 Explanation of the symbols for footnote 1), page 43
7.3 Error message
You can use the error message menu to view the most recent faults in the fault memory, in order
to investigate a fault, for example.
Faults are categorised as follows:
• current errors are all unresolved faults currently present in the system. These can be one of the
following types: locking, blocking or plant error.
• locking fault1): Manually reset the heating system after the fault has been removed. For this,
press RESET on the boiler.
• blocking fault1): With blocking faults, the heating system continues to operate automatically,
as soon as the fault has been removed.
• plant errors relating to the heating system are logged in the RC35. Exceptions are boiler or
burner faults that are either “locking” or “blocking” faults. The heating system keeps operating as
much as possible during the fault; a reset is not required.
For a list of the locking and blocking faults, which vary depending on the boiler, see the
installation and maintenance instructions for the boiler.
B Turn rotary selector
to show the next message.
1) Not possible on boilers with UBA1.x, DBA or UBA-H3
44
Logamatic EMS RC35 programming unit - Subject to technical modifications
Diagnosis
7
7.4 Heating curve
With the htg. charact. curve you can graphically display the heating curves of individual heating
circuits.
B If the system comprises several heating circuits:
Turn rotary selector
to display the heating curve of the next
heating circuit.
DIAG.\CHAR. CURVE HC2
90
21
targ. flow tmp.
57°C
7.5 Versions
You can use the INFO\VERSIONS menu to view the software versions for heating system
components.
B If the information cannot be shown in one display:
Turn rotary selector
to scroll to the next display.
Logamatic EMS RC35 programming unit - Subject to technical modifications
INFO\VERSIONS
RC35
UBA1.5
1.02
1.21
45
8
8
Service
Service
With the servicing menu (not possible on boilers with UBA1.x and DBA) you can set a service
interval as well as view and reset current service messages.
The interval can expire after a certain number of hours run or when a specific date is reached1). The
RC35 programming unit will then show a service message so that the customer can notify you to
arrange an appointment.
Service messages are indicated by an Hxx code, e.g. H07.
SERVICE MENU\
SERVICE
service interval
Menu item
How should
servicing
messages be
triggered?
For “by date”:
Annual servicing,
starting on:
current messages
RESET servicing
Input
range
No
messages,
by date, by
operation
hours
01.01.2000
For “by operation 1.000 h to
hours”: Boiler
6.000 h
operation hours
until next servicing
message
Message/code
Do you wish to
no, yes
reset the servicing
messages?
Factory
setting
No
messages
Other information
When selecting “date” or
“operating hours” the
system changes
automatically to the
corresponding setting.
01.01.2000 To set the date:
hold down
and turn
rotary selector at the
same time.
1.000 h
Number of hours of
operation with burner
switched on.
no
To view further
messages: turn rotary
selector.
When selecting “yes” all
service messages are
reset.
Observe the information
on the display.
Tab. 20 Navigator for SERVICE MENU\SERVICE
1) Depending on the boiler used, additional service intervals may be able to be set at the boiler
programming unit.
46
Logamatic EMS RC35 programming unit - Subject to technical modifications
Reset
9
9
Reset
The RESET menu allows you to reset
•
•
•
•
all parameters to their factory setting1),
the fault list1),
the service message2) and
the hours run2).
Following a reset to factory settings, you may need to adjust the parameters in
accordance with the actual system configuration.
B Turn rotary selector
to select a menu, e.g. error list.
B Press
to change to the display, e.g. Do you wish to reset the error list?
B Press
and turn rotary selector
to set the display to yes.
The reset is implemented after you release the button.
An appropriate message is shown during the reset; this will close automatically.
B Once reset is complete: confirm the new message by pressing any key.
1) On boilers with UBA1.x, DBA or UBA-H3 only all RC35 parameters are reset, but not the combustion
controller parameters.
2) This function is not available with boilers with UBA1.x or DBA.
Logamatic EMS RC35 programming unit - Subject to technical modifications
47
10
Troubleshooting
10 Troubleshooting
This fault table lists possible system faults, i.e. faults in EMS components. The heating system keeps
operating as long as possible in the event of a system fault; in other words, heating can continue.
Only use original Buderus spare parts. Losses caused by the use of parts not supplied
by Buderus are excluded from the Buderus warranty.
The fault displays are subject to the specific type of boiler used.
Abbreviations used:
SC = Fault code; x = heating circuit with number x, e.g. A23 for heating circuit 3
FC
= Fault code
HCx = Heating circuit with the number x
Events
SC FC display
A01 800 Outside
sensor is
defect.
Effect on control
Possible cause
Remedy
characteristics
The minimum outside Temperature sensor is B Check sensor
temperature is applied. incorrectly connected
connection and
or fitted.
sensor lead.
Breakage or short cir- B Check sensor
mounting.
cuit in the sensor lead.
B Compare resistance
Temperature sensor is
values with the
faulty.
sensor curve.
A01 808 DHW sensor DHW heating has
Temperature sensor is B Check sensor
1 is defect.
stopped.
incorrectly connected
connection and
or fitted.
sensor lead.
A01 809 DHW sensor
B
Check sensor
2 is defect.
Breakage or short cirmounting.
cuit in the sensor lead.
B Compare resistance
Temperature sensor is
values with the
faulty.
sensor curve.
Tab. 21 Fault table
48
Logamatic EMS RC35 programming unit - Subject to technical modifications
Troubleshooting
Events
SC FC display
A01 810 DHW stays
cold.
10
Effect on control
characteristics
The system
continuously tries to
heat the DHW cylinder
to the set DHW
temperature.
Possible cause
Remedy
Constant drawing or B Stop any leaks.
system leak.
Temperature sensor is B Check sensor
incorrectly connected
connection and
or fitted.
sensor lead.
Priority DHW is
Breakage or short cir- B Check sensor
mounting.
switched off once the cuit in the sensor lead.
error message has
B Compare resistance
Temperature sensor
been displayed.
values with the
faulty.
sensor curve.
Cylinder primary pump B Check that the
incorrectly connected
cylinder primary
or faulty.
pump is working,
e.g. by carrying out
a function test.
Thermal disinfection
Too much water
B Select thermal
A01 811 Thermal
disinfection at a
disinfection has been interrupted. drawn during thermal
disinfection.
time when no
was
unsuccessful.
additional heat
Boiler output is too
demand is made.
low for heat to be
used simultaneously
for other purposes
(e.g. second heating
circuit).
Temperature sensor is B Check sensor
incorrectly connected
connection and
or fitted.
sensor lead.
B
Check sensor
Breakage or short cirmounting.
cuit in the sensor lead.
B Compare resistance
Temperature sensor is
values with the
faulty.
sensor curve.
Cylinder primary pump B Check that the
faulty.
cylinder primary
pump is working,
e.g. by carrying out
a function test.
Tab. 21 Fault table
Logamatic EMS RC35 programming unit - Subject to technical modifications
49
10
Troubleshooting
Events
SC FC display
A01 815 Low loss
header
sensor
faulty.
A01
A01
A02
A11
A11
A11
Effect on control
characteristics
This may result in the
following heating
circuits receiving
insufficient heat.
Possible cause
Remedy
Temperature sensor is B Check sensor
incorrectly connected
connection and
or fitted.
sensor lead.
Breakage or short cir- B Check sensor
mounting.
cuit in the sensor lead.
B Compare resistance
Temperature sensor is
values with the
faulty.
sensor curve.
816 No communi- The boiler no longer
EMS BUS system is B Reset by switching
cation with
receives heat demand overloaded.
the heating system
UBA/MC10, signals; the heating
ON and OFF.
UBA3/MC10, DBA,
DBA, UBA-H3 system may no longer UBA-H3 or MCM10 is B If necessary inform
or MCM10.
generate heat.
faulty.
your local service
centre.
828 Water
Digital water pressure B Replace the water
pressure
sensor is faulty.
pressure sensor.
sensor is
defect.
816 No commu- BC10 settings are no Contact problem on
B Check BC10
nication with longer adopted by
BC10 or BC10 is
connection.
BC10.
RCxx devices.
faulty.
B Replace BC10 if
required.
801 internal error Heating system is in
Internal runtime error B Replace RC35.
emergency mode.
in RC35.
802 Time is not Restricted functionality Time details are
B Enter the current
yet set.
for:
time.
missing, e.g. due to
lengthy power failure.
• All switching
programs
• Error messages
803 Date is not
Restricted functionality Date details are
B Enter the current
yet set.
for:
missing, e.g. due to
date.
lengthy power failure.
• All switching
programs
• Holiday function
• Error messages
Tab. 21 Fault table
50
Logamatic EMS RC35 programming unit - Subject to technical modifications
Troubleshooting
10
Events
Effect on control
SC FC display
characteristics
A11 804 internal error Heating system is in
emergency mode.
A11 806 Room
Since the actual room
temperature temperature is
sensor is
missing, the following
defect.
cannot function:
• Room influence (for
weathercompensated
control)
• Switching point
optimisation
In the case of room
temperaturedependent control, the
system is regulated to
max. temperature for
HCx.
A11 816 No commu- RC20/RF unable to
nication with transmit data to RC35.
RC35.
Room temperature
control therefore not
possible for HC.
Possible cause
Remedy
Internal runtime error B Replace RC35.
in RC35.
Faulty integral
B Replace the remote
temperature sensor on
control unit.
the heating circuit's
programming unit /
remote control unit.
RC20/RF has
incorrect address.
B Check the address
(parameter P1) in
RC20/RF.
B Check connection
to RC35.
RC35 not present or
not connected
correctly.
A12 815 Low loss
This may result in the Temperature sensor is B Check sensor
header
following heating
incorrectly connected
connection and
sensor
circuits receiving
or fitted.
sensor lead.
faulty.
insufficient heat.
B
Check sensor
Breakage or short cirmounting.
cuit in the sensor lead.
B Compare resistance
Temperature sensor
values with the
faulty.
sensor curve.
A12 816 No commu- Heating circuit pump WM10 or BUS
B Check connections
nication with for heating circuit 1 is incorrectly connected
on WM10 and BUS
separator
permanently activated. or faulty.
cable.
module.
B Replace WM10.
RC35 does not
recognise WM10.
Tab. 21 Fault table
Logamatic EMS RC35 programming unit - Subject to technical modifications
51
10
Troubleshooting
Events
SC FC display
A18 825 Two master
operating
units in
system.
Effect on control
characteristics
RC35 and RC2x
regulate both heating
circuits and DHW.
Subject to the
selected heating
programs and the
required room
temperature, the
heating system may no
longer function
correctly.
DHW heating is malfunctioning.
A2x 806 Room
Since the actual room
temperature temperature is
for HCx is
missing, the following
defect.
cannot function:
• Room influence (for
weathercompensated
control)
• Switching point
optimisation
Possible cause
RC2x and RC35 are
both logged on as
master.
Remedy
B Change parameter
P1 in RC2x or
remove RC35 from
the EMS BUS.
Faulty integral
B Replace the remote
temperature sensor on
control unit.
the heating circuit's
programming unit /
remote control unit.
In the case of room
temperaturedependent control, the
system is regulated to
max. temperature for
HCx.
A2x 816 No commu- Since the actual room RC2x incorrectly
B Check address in
nication with temperature is
RC2x.
addressed, wired or
operating
missing, the following faulty.
B Check function and
unit HCx.
cannot function:
connection of the
Heating circuit has not
remote control unit.
been registered on the
• Room influence
B
Replace the remote
RFM20.
• Switching point
control unit.
optimisation
Tab. 21 Fault table
52
Logamatic EMS RC35 programming unit - Subject to technical modifications
Troubleshooting
Events
SC FC display
A2x 829 RC20/RF as
remote
control.
A2x 830 Low battery
for wireless
oper. unit
HCx.
A2x 839 No wireless
comm. with
oper. unit
HCx.
Wireless
malfunction.
10
Effect on control
characteristics
RC20/RF unable to
transmit data to RC35.
Room temperature
control therefore not
possible for this HC.
Possible cause
Remedy
RC20/RF address
B Set the operating
incorrectly allocated in
unit parameter in
RC35 or not installed
RC35 to RC20/RF.
in RC35.
B Check the
assignment of the
RC20/RF.
No effect if the battery Battery in RC20/RF
B Replace batteries.
is replaced in time.
for HCx is low.
Since the actual room RC20/RF is outside
temperature is
the range of reception.
missing, the following
cannot function:
Heating system has
been switched off.
• Room influence
When RFM20 was
• Switching point
replaced, the RC20/
optimisation
RF was not registered
The RFM20 operates on the new RFM20.
with the last values set
on the remote control
unit.
A2x 842 Frost
Since the actual room No programming unit /
prot.selected temperature is
remote control unit
but no
missing, the following assigned, although
rem.contr.
cannot function:
frost protection is
HCx.
set to room
• Room influence
temperature.
• Switching point
optimisation
No programming unit /
A2x 843 Room
EMS operates with the remote control unit
control
selected but last values set on the assigned, although
remote control unit.
no
room temp.
rem.contr.
controlled is set.
HCx.
B Bring the RC20/RF
within the range of
reception.
B Switch on the
heating system.
B Register the RC20/
RF (see
documentation for
RC20/RF).
B Check the
operating unit
parameter.
B Possibly change
over frost
protection to
outside temp.
B Check the
operating unit
parameter.
B Possibly change
over to outside
temp. contr.
Tab. 21 Fault table
Logamatic EMS RC35 programming unit - Subject to technical modifications
53
10
Troubleshooting
Events
SC FC display
A3x 807 HCx flow
sensor is
defect.
Effect on control
characteristics
The heating circuit
pump continues to be
controlled with
reference to the
default value.
Possible cause
Remedy
Temperature sensor is B Check sensor
incorrectly connected
connection and
or fitted.
sensor lead.
Breakage or short cir- B Check sensor
mounting.
cuit in the sensor lead.
B Compare resistance
The actuator is
Temperature sensor is
values with the
switched to zero volt
faulty.
sensor curve.
and remains in the last
active state (manually
adjustable).
A3x 816 No commu- Heating circuit x
Heating circuit
B Check rotary coding
nication with cannot be operated
addresses on MM10
switch on MM10.
HCx mixer
correctly.
and RC35 do not
module.
match.
MM10 and actuator
MM10 or BUS cable B Check connections
(mixer) are running
incorrectly connected
on MM10 and BUS
independently in
or faulty.
cable.
emergency mode.
B Replace MM10.
Heating circuit pump RC35 does not
recognise
MM10.
is being continuously
actuated.
Hxx
Service
message, no
plant error.
Monitor data in RC35
is invalid.
The heating system
Example: service
keeps operating as far interval has expired.
as possible.
Maintenance is
required, see boiler
documentation.
Tab. 21 Fault table
System faults do not need resetting. Contact your local service engineer or your
Buderus sales office if you cannot remedy the system fault yourself.
Other faults are described in the documents relating to the individual boiler.
54
Logamatic EMS RC35 programming unit - Subject to technical modifications
Logamatic EMS RC35 programming unit - Subject to technical modifications
Push & turn to set parameter.
room
quick operation
settings
diagnosis
servicing
RESET
SERVICE MENU
room
SERVICE\SETTINGS
factory setting
error list
service message
operating hours
SERVICE MENU\RESET
service interval
current messages
RESET
SERVICE MENU\SERVICE
function test
monitor value
error message
htg. charact. curve
versions
SERVICE\DIAGNOSIS
plant data
boiler data
heating circuit 1
heating circuit 2 etc.
domestic hot water
solar data
RC35 calibration
contact data
ON
OPEN
OFF
ON
date
no / yes
Do you wish to reset
all parameters to
the factory settings?
SERVICE MENU\RESET
How should servicing
messages be
triggered?
Hours run
SERVICE MENU\SERVICE
fuel valve
ignition
flame
flame current
BURNER
FCT. TEST\BOILER
e.g.
Heating circuit enabled,
remote control, type of control,
heating system, night setback,
holiday setback, interrupt
setback, htg. charact. curve,
htg. charact. curv
SETTINGS\HTG. CIRC. 2
yes / no
Which language should
be used?
English
SHORTCUT\HYDR. SEP.
Have you installed a
module for the
hydraulic separator?
SHORTCUT\BASIC SETUP
RC35 Service menu
flame current
boil.tmp.
boiler pump
outside temp.
damp.out.tmp.
MON. VALUE\BOILER
e.g.
std. tmp. (-10)
Max. flow
min flow temp.
rm. tmp. offset
SETTINGS\HTG. CIRC. 2
heating circuit 1,
no. mixers, remote control
units, DHW, charge pump,
solar
SHORTCUT
6 720 618 477-09.1TL
from: 09.10.06
durat.:
Outside sensor is defect.
A01
ERROR\PLANT
e.g.
SETTING\CONTACT
Name and tel. No. of
supplier:
Service menu RC35
11
11 Service menu RC35
55
Index
Index
A
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Actual values, viewing . . . . . . . . . . . . . . . . . . 43
Adjusting the outside temperature . . . . . . . . 24
B
Boiler data, Service menu – settings . . . . . . 26
Building type. . . . . . . . . . . . . . . . . . . . . . . . . . 24
C
Calibration, room temperature display . . . . . 40
Checklist, parameters for
commissioning . . . . . . . . . . . . . . . . . . . . . . . . 19
Combustion controller . . . . . . . . . . . . . . . . 7, 47
Commissioning. . . . . . . . . . . . . . . . . . . . . . . . 18
Commissioning, quick . . . . . . . . . . . . . . . . . . 20
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Contact details, entering . . . . . . . . . . . . . . . . 41
Control mode . . . . . . . . . . . . . . . . . . . . . . . . . 31
Controls, overview of . . . . . . . . . . . . . . . . . . . 14
Correct use. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Curve, Service menu – diagnosis. . . . . . . . . 45
D
Design temperature
(standard temperature) . . . . . . . . . . . . . . . . .
DHW
- Service menu – settings. . . . . . . . . . . . . .
- set value. . . . . . . . . . . . . . . . . . . . . . . . . . .
- temperature limit . . . . . . . . . . . . . . . . . . . .
DHW circulation. . . . . . . . . . . . . . . . . . . . . . .
DHW priority. . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnosis, Service menu . . . . . . . . . . . . . . . .
Disinfection, thermal . . . . . . . . . . . . . . . . . . .
Display contrast . . . . . . . . . . . . . . . . . . . . . . .
32
36
36
36
36
27
42
36
18
E
EMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 22
EMS BUS subscribers . . . . . . . . . . . . . . . . . 22
56
F
Faults, Service menu diagnosis . . . . . . . . . . 44
Flow temperature. . . . . . . . . . . . . . . . . . . . . . 32
Frost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Frost protection . . . . . . . . . . . . . . . . . . . . . . . 34
Function test, Service menu – diagnosis. . . 42
H
Heat storage capacity . . . . . . . . . . . . . . . . . .
Heating circuit
- installing. . . . . . . . . . . . . . . . . . . . . . . . . . .
- more than one heating circuit . . . . . . . . .
- Service menu – settings . . . . . . . . . . . . .
Heating curve
- instructions for setting . . . . . . . . . . . . . . .
- viewing. . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
23
11
27
32
45
I
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
L
Language, setting . . . . . . . . . . . . . . . . . . . . . 23
Low loss header module WM10 . . . . . . . . . . 9
Low loss header, installing . . . . . . . . . . . . . . 23
M
Minimum clearances . . . . . . . . . . . . . . . . . . . 10
Minimum outside temperature . . . . . . . . . . . 25
Mixer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Mixer module MM10 . . . . . . . . . . . . . . . . . . . . 9
Modulation, boiler pump . . . . . . . . . . . . . . . . 26
Monitor value, Service menu – diagnosis . . 43
N
Night setback . . . . . . . . . . . . . . . . . . . . . . . . . 33
O
Outdoor setback mode . . . . . . . . . . . . . . . . . 33
Outside temperature control . . . . . . . . . . . . 31
Outside temperature, adjusted. . . . . . . . . . . 24
Logamatic EMS RC35 programming unit - Subject to technical modifications
Index
P
Plant data, Service menu – Settings . . . . . . . 23
Power failure . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Programming unit
- assignment in software . . . . . . . . . . . . . . . 31
- attaching or removing . . . . . . . . . . . . . . . . 13
- for heating circuit . . . . . . . . . . . . . . . . . . . . 27
- only programming unit in the system . . . . 11
Pump kick . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Pump logic temperature . . . . . . . . . . . . . . . . . 26
Pump run-on time . . . . . . . . . . . . . . . . . . . . . . 26
Q
Quick operation, Service menu . . . . . . . . . . . 20
R
Reduced operation . . . . . . . . . . . . . . . . . . . . . 33
Reference room. . . . . . . . . . . . . . . . . . . . . . . . 10
Remote control unit. . . . . . . . . . . . . . . . . . . . . 11
Reset, Service menu. . . . . . . . . . . . . . . . . . . . 47
Room influence . . . . . . . . . . . . . . . . . . . . . . . . 31
Room setback mode. . . . . . . . . . . . . . . . . . . . 33
Room temperature offset . . . . . . . . . . . . . . . . 32
Solar module, installing . . . . . . . . . . . . . . . . . 23
Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Standard delivery . . . . . . . . . . . . . . . . . . . . . . . 7
Switching off . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Switching program, optimising . . . . . . . . . . . 27
System handover . . . . . . . . . . . . . . . . . . . . . . 21
T
Temperature sensor . . . . . . . . . . . . . . . . . . . . . 8
Testing components. . . . . . . . . . . . . . . . . . . . 42
Thermal disinfection . . . . . . . . . . . . . . . . . . . . 36
Thermostatic valves in reference room . . . . . 22
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 48
V
Versions, Service menu – diagnosis. . . . . . . 45
Versions, viewing . . . . . . . . . . . . . . . . . . . . . . 45
W
Weather-compensated control . . . . . . . . . . . 31
S
Safety instructions . . . . . . . . . . . . . . . . . . . . . . 6
Screed, drying . . . . . . . . . . . . . . . . . . . . . . . . . 27
Sensor characteristics . . . . . . . . . . . . . . . . . . . 8
Service interval, setting. . . . . . . . . . . . . . . . . . 46
Service menu, introduction. . . . . . . . . . . . . . . 15
Service menu, overview of the menus. . . . . . 17
Service messages, viewing/resetting . . . . . . 46
Service, Service menu . . . . . . . . . . . . . . . . . . 46
Set values, viewing . . . . . . . . . . . . . . . . . . . . . 43
Setback mode (night setback). . . . . . . . . . . . 33
Setback, interrupting (frost protection) . . . . . 34
Showing the fault memory . . . . . . . . . . . . . . . 44
Shutdown operation . . . . . . . . . . . . . . . . . . . . 33
Shutting down . . . . . . . . . . . . . . . . . . . . . . . . . 22
Single charge LED, switching off . . . . . . . . . 36
Solar data, Service menu – settings . . . . . . . 39
Logamatic EMS RC35 programming unit - Subject to technical modifications
57
Notes
58
Logamatic EMS RC35 programming unit - Subject to technical modifications
Notes
Logamatic EMS RC35 programming unit - Subject to technical modifications
59
Buderus
Cotswold Way, Warndon, Worcester WR4 9SW
Customer service: 0844 892 3004
Technical support: 0844 892 4224
Fax: 01905 753130
www.buderus-commercial.co.uk
In the UK and IE, Buderus is a brand name of
Bosch Thermotechnology Ltd.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Large, backlit display for easy viewing.
  • Intuitive menu-driven interface for simple operation.
  • Built-in temperature sensor for accurate temperature control.
  • Multiple programming options for maximum flexibility.
  • Energy-saving features to help reduce heating and cooling costs.
  • Compatible with a wide range of heating and cooling systems.

Related manuals

Frequently Answers and Questions

What can I do with the Buderus Logamatic EMS RC35?
The Buderus Logamatic EMS RC35 can be used to control a wide range of heating and cooling systems, including boilers, heat pumps, and air conditioners.
Is the Buderus Logamatic EMS RC35 easy to install?
Yes, the Buderus Logamatic EMS RC35 is easy to install. It comes with clear instructions and all the necessary mounting hardware.
What are the benefits of using the Buderus Logamatic EMS RC35?
The Buderus Logamatic EMS RC35 offers a number of benefits, including increased comfort, energy savings, and peace of mind.
Is the Buderus Logamatic EMS RC35 compatible with my heating and cooling system?
The Buderus Logamatic EMS RC35 is compatible with a wide range of heating and cooling systems. Please consult your local HVAC contractor for more information.

advertisement