Product data sheet
Characteristics
Complementary
Discrete output type
Contacts type and composition
Contacts material
Width pitch dimension
Voltage range
Connections - terminals
Tightening torque
Setting accuracy of time delay
Repeat accuracy
Voltage drift
Temperature drift
Minimum pulse duration
Reset time
Maximum switching voltage
Mechanical durability
[Ith] conventional free air thermal current
[Ie] rated operational current
Minimum switching capacity
Marking
Overvoltage category
[Ui] rated insulation voltage
Supply disconnection value
Operating position
Surge withstand
Power consumption in VA
Power consumption in W
Thu Nov 04 05:51:26 EDT 2010
RE8TA11BU industrial timing relay - 0.1..10 s - type A - 24 V
AC/DC, 110..240 V AC - 1 C/O
Main
Range of product
Commercial Reference
Product or component type
Component name
Time delay type
Time delay range
[Us] rated supply voltage
Sale per indivisible quantity
Zelio Time
RE8TA11BU
Optimum industrial timing relay
RE8
A
0.1...10 s
24 V AC/DC , 50/60 Hz
110...240 V AC , 50/60 Hz
1
Relay
1 C/O
Silver nickel contacts
22.5 mm
0.9...1.1 Us
Screw terminals 2 x 2.5 mm² , flexible cable without cable end
Screw terminals 2 x 1.5 mm² , flexible cable with cable end
0.6...1.1 N.m
+/- 20 % of full scale
< 1 %
< 2.5 %/V
< 0.2 %/°C
26 ms
50 ms
250 V
20000000 cycles
8 A
≤ 0.1 A at 250 V , DC-13 for 70 °C conforming to IEC 60947-5-1/1991
≤ 0.1 A at 250 V , DC-13 for 70 °C conforming to VDE 0660
≤ 0.2 A at 115 V , DC-13 for 70 °C conforming to IEC 60947-5-1/1991
≤ 0.2 A at 115 V , DC-13 for 70 °C conforming to VDE 0660
≤ 2 A at 24 V , DC-13 for 70 °C conforming to IEC 60947-5-1/1991
≤ 2 A at 24 V , DC-13 for 70 °C conforming to VDE 0660
≤ 3 A at 24 V , AC-15 for 70 °C conforming to IEC 60947-5-1/1991
≤ 3 A at 24 V , AC-15 for 70 °C conforming to VDE 0660
10 mA at 12 V
CE
III conforming to IEC 60664-1
250 V conforming to IEC
300 V conforming to CSA
> 0.1 Uc
Any position without derating factor
2 kV conforming to IEC 61000-4-5 level 3
0.7 VA at 24 V
1.8 VA at 110 V
8.5 VA at 240 V
0.5 W at 24 V
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Terminal description
Product weight
Environment
Immunity to microbreaks
Standards
Product certifications
Ambient air temperature for storage
Ambient air temperature for operation
Relative humidity
Vibration resistance
Shock resistance
IP degree of protection
Pollution degree
Dielectric test voltage
Non-dissipating shock wave
Resistance to electrostatic discharge
Resistance to electromagnetic fields
Resistance to fast transients
Disturbance radiated/conducted
RoHS EUR conformity date
RoHS EUR status
(15-16-18)OC_OFF
(A1-B1)CO
ALT
0.11 kg
3 ms
EN/IEC 61812-1
CSA
GL
UL
-40...85 °C
-20...60 °C
15...85 % 3K3 conforming to IEC 60721-3-3
0.35 mm 10...55 Hz conforming to IEC 60068-2-6
15 gn (duration = 11 ms conforming to IEC 60068-2-27
IP20 (terminals)
IP50 (casing)
3 conforming to IEC 60664-1
2.5 kV
4.8 kV
6 kV in contact conforming to IEC 61000-4-2 level 3
8 kV in air conforming to IEC 61000-4-2 level 3
10 V/m conforming to IEC 61000-4-3 level 3
2 kV conforming to IEC 61000-4-4 level 3
CISPR11 group 1- class A
CISPR22 - class A
0627
Compliant
2
Product data sheet
Technical Description
RE8TA11BU
Function A: Delay on Energisation
Description
The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Legend
Relay de-energised
Relay energised
Output open
Output closed
C Control contact
G Gate
R Relay or solid state output
R1/
R2
2 timed outputs
R2 inst.
The second output is instantaneous if the right position is selected
T Timing period
Ta Adjustable On-delay
Tr Adjustable Off-delay
U Supply
3
Product data sheet
Dimensions Drawings
Width 22.5 mm
Rail Mounting
RE8TA11BU
Screw Fixing
4
Product data sheet
Connections and Schema
RE8TA11BU
Internal Wiring Diagram
Recommended Application Wiring Diagram
5
Product data sheet
Performance Curves
RE8TA11BU
Performance Curves
A.C. Load Curve 1
Electrical durability of contacts on resistive loading millions of operating cycles
X Current broken in A
Y Millions of operating cycles
A.C. Load Curve 2
Reduction factor k for inductive loads (applies to values taken from durability curve 1).
X Power factor on breaking (cos ϕ)
Y Reduction factor k
Example: An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.1 A and cos ϕ = 0.3. For 0.1 A, curve 1 indicates a durability of approximately 1.5 million operating cycles. As the load is inductive, it is necessary to apply a reduction coefficient k to this number of cycles as indicated by curve 2. For cos ϕ = 0.3: k = 0.6 The electrical durability therefore becomes:1.5 10 6 operating cycles x 0.6 = 900 000 operating cycles.
D. C. Load Limit Curve
1
2
X Current in A
Y Voltage in V
3
L/R = 20 ms
L/R with load protection diode
Resistive load
6
advertisement