advertisement
3216i, 32h8i, 3204i
User
Manual
3200i Range Process Indicators and Alarm Units
HA029006/5
Sept 2012
© 2012 Eurotherm Limited
All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior, written permission of Eurotherm Limited.
- - - - - - - - - - - - -
Eurotherm Limited pursues a policy of continuous development and product improvement. The specification in this document may therefore be changed without notice. The information in this document is given in good faith, but is intended for guidance only. Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.
3200i Series Indicators
3200i Series Process Indicators and Alarm Units
User Manual Part Number HA029006 Issue 5 Sept-12
Includes 3216i, 32h8i and 3204i Indicators.
Issue 5 of this manual applies to software version 1.03.
Contents
Contents
1.
Installation and Basic Operation ...................................................................................................5
1.1
Unpacking Your Indicator ............................................................................................................................. 5
1.2
Dimensions Front Views ............................................................................................................................... 5
1.3
Dimensions – Side and Top Views................................................................................................................ 5
1.4
Step 1: Installation ........................................................................................................................................ 6
1.4.1
Panel Mounting the Indicator ..................................................................................................................................................... 6
1.4.2
Panel Cut-out Sizes ....................................................................................................................................................................... 6
1.4.3
Recommended Minimum Spacing of Indicators. .................................................................................................................... 6
1.4.4
To Remove the Indicator from its Sleeve .................................................................................................................................. 6
1.5
Ordering Code ................................................................................................................................................ 7
2.
Step 2: Wiring................................................................................................................................. 8
2.1
Terminal Layout 32h8i Indicator ................................................................................................................... 8
2.2
Terminal Layout 3216i Indicator ................................................................................................................... 9
2.3
Terminal Layout 3204i Indicators.................................................................................................................. 9
2.4
Wire Sizes ...................................................................................................................................................... 10
2.5
Sensor Input (Measuring Input) ................................................................................................................... 10
2.6
Outputs - 1/8 and 1/4 DIN Indicators ......................................................................................................... 10
2.6.1
Output 1 & Output 4 (AA Relay) .............................................................................................................................................. 10
2.6.2
Output 3 Retransmission (Output 2 3216i) ............................................................................................................................ 10
2.6.3
Transmitter Supply ..................................................................................................................................................................... 10
2.6.4
Digital Inputs A and B................................................................................................................................................................ 11
2.6.5
Transducer Supply ..................................................................................................................................................................... 11
2.7
Indicator Power Supply ................................................................................................................................ 11
2.8
Example Wiring Diagram ............................................................................................................................. 11
2.9
Digital Communications (Optional) ............................................................................................................ 12
2.10
Additional Connections for 3216i .......................................................................................................... 12
2.10.1
Input/Output 1 & Output 2 ................................................................................................................................................. 12
3.
Safety and EMC Information ....................................................................................................... 13
3.1
Installation Safety Requirements ................................................................................................................. 13
4.
Switch On ....................................................................................................................................... 15
4.1
New Indicator ................................................................................................................................................ 15
4.1.1
To Re-Enter Quick Code Mode ............................................................................................................................................... 17
4.2
Pre-Configured Indicator or Subsequent Starts ........................................................................................ 17
4.3
Front panel layout ......................................................................................................................................... 17
4.3.1
Alarm Indication ......................................................................................................................................................................... 18
4.3.2
Out of Range Indication ............................................................................................................................................................ 18
4.3.3
Sensor Break Indication ............................................................................................................................................................ 18
4.4
Operator Parameters in Level 1 .................................................................................................................. 18
4.4.1
Tare Correction .......................................................................................................................................................................... 19
5.
Operator Level 2 ........................................................................................................................... 19
5.1
To Enter Level 2............................................................................................................................................. 19
5.1.1
To Return to Level 1 ................................................................................................................................................................... 19
5.2
Level 2 Parameters ....................................................................................................................................... 20
5.3
Strain Gauge Calibration .............................................................................................................................. 22
5.3.1
Load Cell Calibration ................................................................................................................................................................. 22
5.3.2
Comparison Calibration............................................................................................................................................................ 22
5.3.3
Shunt Calibration ....................................................................................................................................................................... 23
5.3.4
Manual Calibration .................................................................................................................................................................... 23
5.3.5
Automatic Calibration ............................................................................................................................................................... 23
5.3.6
Calibration Using a Digital Input ............................................................................................................................................. 23
5.4
Recipes ........................................................................................................................................................... 24
5.4.1
To Store Values in a Recipe ...................................................................................................................................................... 24
5.4.2
To Load a Recipe ....................................................................................................................................................................... 24
5.5
FM and Alarm Units ...................................................................................................................................... 24
Part No HA029006 Issue 5.0 Sept-12 CN28942 1
3200i Series Indicators
6.
Access to Further Parameters ..................................................................................................... 25
6.1
Level 3 ............................................................................................................................................................ 25
6.2
Configuration Level ...................................................................................................................................... 25
6.2.1
To Select Access Level 3 or Configuration Level ................................................................................................................... 26
6.3
Parameter lists ............................................................................................................................................... 27
6.3.1
To Choose Parameter List Headers ......................................................................................................................................... 27
6.3.2
To Locate a Parameter ............................................................................................................................................................... 27
6.3.3
How Parameters are Displayed ................................................................................................................................................ 27
6.3.4
To Change a Parameter Value .................................................................................................................................................. 27
6.3.5
To Return to the HOME Display ............................................................................................................................................... 27
6.3.6
Time Out ...................................................................................................................................................................................... 27
6.4
Navigation Diagram ..................................................................................................................................... 28
6.5
Access Parameters ........................................................................................................................................ 29
7.
Process Input ................................................................................................................................. 30
7.1
Process Input Parameters ............................................................................................................................ 30
7.1.1
Input Types and Ranges ............................................................................................................................................................ 31
7.1.2
Units .............................................................................................................................................................................................. 32
7.1.3
PV Offset....................................................................................................................................................................................... 33
7.1.4
PV Input Scaling .......................................................................................................................................................................... 33
8.
Input/Output Channels ................................................................................................................ 34
8.1
Output Channel 1 (OP-1) - 32h8i and 3204i Indicators ........................................................................... 34
8.2
Input/Output Channel 1 (I/O-1) - 3216i Indicator ..................................................................................... 35
8.3
Output Channel 2 (OP-2) - 3216i Indicator ............................................................................................... 36
8.3.1
Sense ............................................................................................................................................................................................ 37
8.3.2
Source ........................................................................................................................................................................................... 37
8.3.3
Power Fail ..................................................................................................................................................................................... 37
8.3.4
Example: To Configure OP-1 Relay to Operate on Alarms 1 and 2:- ................................................................................ 37
8.4
Output Channel 3 (OP-3) – 32h8i, 32h8i/SG and 3204i Indicators ....................................................... 38
8.4.1
Output Scaling ............................................................................................................................................................................ 38
8.5
AA Relay Channel (AA) (Output 4) .............................................................................................................. 39
9.
Digital Input .................................................................................................................................. 40
9.1
Digital Input Parameters .............................................................................................................................. 40
10.
Alarms ............................................................................................................................................ 41
10.1
Types of Alarm .......................................................................................................................................... 41
10.1.1
Alarm Relay Output ............................................................................................................................................................... 42
10.1.2
Alarm Indication .................................................................................................................................................................... 42
10.1.3
To Acknowledge An Alarm .................................................................................................................................................. 42
10.1.4
Pre-Alarms .............................................................................................................................................................................. 42
10.2
Behaviour of Alarms After a Power Cycle .............................................................................................. 43
10.2.1
Example 1 ............................................................................................................................................................................... 43
10.2.2
Example 2 ............................................................................................................................................................................... 43
10.2.3
Example 3 ............................................................................................................................................................................... 43
10.3
Alarm Parameters ..................................................................................................................................... 44
10.3.1
Example: To Configure Alarm 1......................................................................................................................................... 45
10.4
Diagnostic Alarms .................................................................................................................................... 46
11.
Recipe ............................................................................................................................................ 47
11.1
To Save Values in a Recipe ...................................................................................................................... 47
11.2
To Save Values in a Second Recipe ........................................................................................................ 47
11.3
To Select a Recipe to Run ........................................................................................................................ 48
12.
Digital Communications .............................................................................................................. 49
12.1
Digital Communications Wiring ............................................................................................................. 49
12.1.1
EIA 232 .................................................................................................................................................................................... 49
12.1.2
EIA 485 .................................................................................................................................................................................... 49
12.2
Digital Communications Parameters ..................................................................................................... 50
12.2.1
Broadcast Communications ................................................................................................................................................ 51
12.2.2
Broadcast Master Communications ................................................................................................................................... 51
12.2.3
Wiring Connections .............................................................................................................................................................. 51
12.3
Example: To Set Up Instrument Address ............................................................................................... 52
12.4
DATA ENCODING .................................................................................................................................... 52
12.5
Parameter Modbus Addresses................................................................................................................ 53
2 Part No HA029006 Issue 5.0 Sept-12
3200i Series Indicators
13.
Calibration ..................................................................................................................................... 57
13.1
To Check Input Calibration ...................................................................................................................... 57
13.1.1
Precautions ............................................................................................................................................................................ 57
13.1.2
To Check mV Input Calibration .......................................................................................................................................... 57
13.1.3
To Check Thermocouple Input Calibration ...................................................................................................................... 57
13.1.4
To Check RTD Input Calibration ........................................................................................................................................ 58
13.2
Offsets ........................................................................................................................................................ 58
13.2.1
Five Point Offset .................................................................................................................................................................... 58
13.3
Input Calibration ....................................................................................................................................... 59
13.3.1
To Calibrate mV Range ........................................................................................................................................................ 60
13.3.2
To Calibrate Thermocouple Ranges ................................................................................................................................. 60
13.3.3
To Calibrate RTD Ranges .................................................................................................................................................... 61
13.4
Output Calibration ................................................................................................................................... 62
13.4.1
To Calibrate mA Outputs .................................................................................................................................................... 62
13.4.2
To Return to Factory Calibration ........................................................................................................................................ 62
13.4.3
Transducer Calibration ........................................................................................................................................................ 62
13.5
Calibration Parameters ............................................................................................................................ 63
14.
Configuration Using iTools .......................................................................................................... 64
14.1
Loading an IDM ........................................................................................................................................ 64
14.2
Connecting a PC to the Indicator ............................................................................................................ 64
14.2.1
Using the H Communications Port..................................................................................................................................... 64
14.2.2
Configuration Clip ................................................................................................................................................................ 64
14.3
Starting iTools ........................................................................................................................................... 65
14.4
Configuring the Indicator Using the Wizard ......................................................................................... 66
14.4.1
To configure the Input ......................................................................................................................................................... 66
14.4.2
To Configure Alarms ............................................................................................................................................................ 67
14.4.3
To Configure Output 1 ........................................................................................................................................................ 67
14.4.4
To Customise Messages ...................................................................................................................................................... 68
14.4.5
To Promote Parameters ....................................................................................................................................................... 69
14.4.6
To Set Up Recipes ................................................................................................................................................................ 70
14.4.7
To Customise the Display .................................................................................................................................................... 71
14.4.8
Summary Tab ........................................................................................................................................................................ 71
14.5
Configuring the Indicator Using the Browser Views ............................................................................ 72
14.5.1
To configure the Input ......................................................................................................................................................... 72
14.5.2
To Configure Alarms ............................................................................................................................................................ 72
14.5.3
To Customise Messages ...................................................................................................................................................... 73
14.5.4
To Promote Parameters ....................................................................................................................................................... 74
14.6
To Load A Special Linearisation Table ................................................................................................... 75
14.7
To Set up Recipes ..................................................................................................................................... 76
14.7.1
Example:- Set Two Different Alarm Thresholds and Store in Recipes 1 and 2 .......................................................... 76
14.8
Summary .................................................................................................................................................... 77
14.9
Cloning ...................................................................................................................................................... 78
14.9.1
Save to File............................................................................................................................................................................. 78
14.9.2
To Clone a New Indicator .................................................................................................................................................... 78
15.
TECHNICAL SPECIFICATION ...................................................................................................... 79
16.
17.
Parameter Index ............................................................................................................................ 81
Index ............................................................................................................................................... 83
Part No HA029006 Issue 5.0 Sept-12 3
Issue Status of this Manual
Issue 2 applies to software version 1.03 and contains the following changes:-
Load cell and shunt calibration explained in more detail.
Separate ‘Set 2’ codes for 32h8i/3204i and 3216i for clarity
Add note on sensor break for transducers
Add note on FM and DIN3440 indicators.
Add calibration check in addition to re-calibration.
Add configuration by iTools Wizard
Add Pre-Alarm setpoint parameters
Issue 3 contains the following changes:
Section 8.3.4. change IO-1 to OP-1
Change power supply frequency specification from 50/60 Hz to 48 to 62 Hz
Section 12.5. add description of enumerations for parameter IM
Section 13.4.1. change the description in the example for Output Calibration.
Issue 4 contains the following changes:
Change power supply frequency specification from 50/60 Hz to 48 to 62 Hz
Section 1.5 and 5.5 change DIN3440 to EN14597 TW
Section 12.5 add description of enumerations for parameter IM
Add section 17 – Index
Issue 5 updates Technical Specification section 15.
3200i Series Indicators
4 Part No HA029006 Issue 5.0 Sept-12
3200i Series Indicators
1. Installation and Basic Operation
Thank you for choosing this 3200i series Process
Indicator.
These are available as:-
Model Size Inputs
DIN Pt100 RTD
V/mA/mV
DIN
32h8i/SG 1/8
DIN
Pt100 RTD
V/mA/mV
2 Digital
Strain gauge
Outputs
1 – Relay, Logic,
Analogue or dig in
2 – Relay, or
Analogue
4 Changeover relay
1 Changeover relay
3 Retransmission
4. Changeover relay and Transmitter PSU
As 32h8i
As 32h8i
DIN
Relay outputs can be configured for alarm and events and analogue retransmission of process variable. 2wire Modbus digital communications is available in all models.
The indicator may have been ordered to a hardware code only or pre-configured using an optional ‘Quick
Start’ code. The label fitted to the side of the sleeve shows the ordering code of the indicator. If the
Quick Code shows ***** the indicator will need to be configured when it is first switched on.
The User Guide supplied with the instrument describes installation and operation in Operator
Levels 1 and 2. This Engineering Handbook includes the User Guide but, in addition, explains operation in a deeper level of access (Level 3), and how to configure the instrument (Configuration Level).
1.1 Unpacking Your Indicator
The following items are included in the box:
• Indicator mounted in its sleeve
• Two panel retaining clips
• AN IP65 sealing gasket mounted on the sleeve
• Component packet containing a snubber for each relay output and a 2.49
Ω resistor for current inputs (see section 2)
• The Installation Guide Part Number HA029994
1.2 Dimensions Front Views
Models 32h8i
96mm (3.78in)
Latching ears
48mm
(1.89in)
Model 3204i
96mm (3.78in)
Model 3216i
48mm
(1.89in)
96mm
(3.78in)
Latching ears
1.3 Dimensions – Side and Top Views
Side View –1/16 DIN
2
48mm
(1.89in)
1
d = Fascia depth
1.25mm
(0.5in)
1
3 d
3
2
2
90mm (3.54in)
48mm
(1.89in)
Top View – 1/16 & 1/8 DIN
3 2
1
Latching ears
2
Panel retaining clip
3
IP65
Sealing
Gasket
1
96mm
(3.78in)
1
d 90mm (3.54in)
Side View –1/8 DIN & 1/4 DIN d
3
90mm (3.54in)
Part No HA029006 Issue 5.0 Sept-12 5
1.4 Step 1: Installation
This indicator is intended for permanent installation, for indoor use only, and enclosed in an electrical panel
Select a location which is subject to minimum vibrations, the ambient temperature is within 0 and
55 o
C (32 - 131 o
F) and humidity 5 to 95% RH non condensing.
The indicator can be mounted on a panel up to
15mm thick
To ensure IP65 and NEMA 4 front sealing against dust and water, mount on a non-textured surface.
Please read the safety information in section 3 before proceeding. The EMC Booklet part number
HA025464 gives further installation information.
1.4.1 Panel Mounting the Indicator
1. Prepare a cut-out in the mounting panel to the size shown. If a number of instruments are to be mounted in the same panel observe the minimum spacing shown.
2. Fit the IP65 sealing gasket behind the front bezel of the indicator
3. Insert the indicator through the cut-out
4. Spring the panel retaining clips into place.
Secure the indicator in position by holding it level and pushing both retaining clips forward.
5. Peel off the protective cover from the display
1.4.2 Panel Cut-out Sizes
Model
3216i
45 mm
- 0.0 + 0.6
1.77 inch
-0.00, +0.02
45 mm
- 0.0 + 0.6
1.77 inch
-0.00, +0.02
92 mm
- 0.0 + 0.8
3.62 inch
-0.00, +0.03
Model 32h8i
92 mm - 0.0 + 0.8
3.62 inch -0.00, +0.03
Model 3204i
3200iSeries Indicators
1.4.3 Recommended Minimum Spacing of
Indicators.
Applies to all Model sizes
10mm (0.4 inch)
38mm (1.5 inch)
(Not to scale)
1.4.4 To Remove the Indicator from its Sleeve
The indicator can be unplugged from its sleeve by easing the latching ears outwards and pulling it forward out of the sleeve. When plugging it back into its sleeve, ensure that the latching ears click back into place to maintain the IP65 sealing.
6 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
1.5 Ordering Code (Hardware)
1. Model No.
3216i 1/16 DIN size
1/8 DIN size Horizontal 32h8i
3204i 1/4 DIN size
2. Function
FM FM Alarm Unit
DN
SG
EN14597 TW alarm unit
Strain Gauge Input 32h8i only
3. Power Supply
VL 24Vac/dc
VH 100–230Vac
4. Outputs (OP1, OP2, OP3)
LRXX OP1 Logic, OP2 Relay
(3216i only)
RRXX OP1 Relay, OP2 Relay
(3216i only)
LDXX OP1 Logic, OP2 Analogue
(3216i only)
DRXX OP1 Analogue, OP2 Relay
(3216i only)
RXXX OP1 Relay
(32h8i & 3204i only)
RXDX OP1 Relay, OP3 Analogue
(32h8i & 3204i only)
5. AA Relay (OP4)
X Disabled
R Relay (Form C)
6. Options 3216i, 32h8i and 3204i
XXX
XXL
2XL
4XL
None
Digital input A
RS232 & Digital input A
RS485 & Digital input A
6. Options 32h8i/SG
XXX None
2XX RS232
4XX RS485
7. Fascia colour/type
G Green
S Silver
8/9 Product/Manual Language
ENG English
FRA French
GER German
ITA Italian
SPA Spanish
10. Input Adaptor
XX None
V1 0-10Vdc
A1 mA Burden Resistor
(2.49
Ω, 0.1%)
11. Warranty
Standard XXXXX
Extended WL005
12. Certificates
None XXXXX
CERT1
CERT2
13. Custom Label
XXXXX
Cert of conformity
5 Point Factory calibration
None
14. Special and Accessories
XXXXXX None
RES250
RES500
250 Ω for 0-5Vdc OP
500 Ω for 0-10Vdc OP
Example ordering code
32h8i - SG - VH - RXDX - R - 4XL - S - ENG - ENG - XX - XXXXX - XXXXX - XXXXX - XXXXX
This code describes a Silver fascia 1/8 DIN strain gauge indicator with two relays and one analogue output.
100-230Vac supply. EIA485 communications. English language product and manuals.
Part No HA029006 Issue 5.0 Sept-12 7
3200iSeries Indicators
2. Step 2: Wiring
Key to Symbols used in the wiring diagrams
Logic (SSR drive) output Relay output
Contact input mA analogue output
2.1 Terminal Layout 32h8i Indicator
!
Ensure that you have the correct supply for your indicator. Check order code of the indicator supplied
Low Voltage Supply
24Vac/dc
OR Line Supply
100 to 230Vac +15%
48 to 62 Hz
24 24
24V
Transmitter
Supply
OP3 DC
Retrans
V/mA
Dig in B
Output 1
(OP1)
Changeover
Relay
N L 3D 3C 3B 3A LC LB 2B 2A 1B 1A
Input Connections for
32h8i/SG Indicator - Strain gauge input
Note: Dig in A is not available with this indicator
Signal | Txdcr Supply
- +
Cal
1
Cal
2
Ext
-
Ext
+
- +
T/C
-
32h8i Indicator
V- V+ VI LA C CT HF HE HD AC AB AA
+
Pt100 Dig in A
B(-) A(+) COM
Digital Comms
AA Relay
(OP4) mV/
Volts mA
-
2.49
Ω
+
+
Sensor Input
- + - +
8 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
2.2 Terminal Layout 3216i Indicator
!
Ensure that you have the correct supply for your indicator. Check order code of the indicator supplied.
Input/Output 1
Output 2
+ +
- -
+
-
Line Supply
100 to 230Vac +15%
48 to 62 Hz
OR
Low Voltage Supply
24Vac/dc
1A
1B
2A
2B
L
N
24
24
Digital input A
CT AA
C AB
AA relay (OP4)
10V Potential divider module
Part No SUB21/IV10
LA AC
COM
A(+)
B(-)
HD
HE
HF
VI
V+
V-
Digital
Communications
EIA 232
EIA 485
+
+ +
2.49
Ω
+
10V Input
-
- - -
T/C PRT mA mV 0-10V
Sensor Input
100K Ω
806 Ω
2.3 Terminal Layout 3204i Indicators
!
Ensure that you have the correct supply for your indicator. Check order code of the indicator supplied
Output 1 (OP1)
Digital Input B
DC Retrans (OP3) mA only
24V Transmitter Supply
Line Supply
100 to 230Vac +15%
48 to 62 Hz
OR
Low Voltage Supply
24Vac/dc
1A
1B
2A
2B
LB
LC
3A
3B
3C
3D
L
N
24
24
+
-
+
24V
-
3204i Indicator
AA
AB
AC
HD
HE
HF
CT
C
LA
VI
V+
V-
+
-
T/C
AA Relay (OP4)
COM
A(+)
B(-)
Digital
Communications
EIA 232 or EIA 485
Digital input A
Pt100
+
2.49
Ω
- mA
- mV
Sensor Input
+
10V Potential divider module
Part No SUB21/IV10
+
100K Ω
806 Ω
Volts
-
10V Input
Part No HA029006 Issue 5.0 Sept-12 9
2.4 Wire Sizes
The screw terminals accept wire sizes from 0.5 to 1.5 mm (16 to 22AWG). Hinged covers prevent hands or metal making accidental contact with live wires. The rear terminal screws should be tightened to 0.4Nm
(3.5lb in).
2.5 Sensor Input (Measuring Input)
• Do not run input wires with power cables
• When shielded cable is used, it should be grounded at one point only
• Any external components (such as zener barriers) connected between sensor and input terminals may cause errors in measurement due to excessive and/or un-balanced line resistance, or leakage currents.
• Not isolated from the logic outputs & digital inputs
Thermocouple Input
V+
+
V-
-
Positive
Negative
• Use the correct compensating cable preferably shielded.
• It is not recommended to connect two or more instruments to one thermocouple
RTD Input
VI
V+
V-
PRT
PRT
Lead compensation
• The resistance of the three wires must be the same. The line resistance may cause errors if it exceeds 22 Ω.
Linear mA, or mV Inputs
+
V+
V-
-
2.49
Ω
Positive
Negative
• For a mA input connect the 2.49
Ω burden resistor supplied between the V+ and V- terminals as shown. For mV omit this resistor.
Linear Voltage Inputs
V+
V-
100K Ω
806 Ω
+
0-10V
Input
-
An external potential divider is required for
3216i and 3204i available as part no
SUB21/IV10.
Sensor break alarm does not operate if this adaptor is fitted.
3200iSeries Indicators
2.6 Outputs - 1/8 and 1/4 DIN Indicators
32h8i and 3204i indicators are supplied as standard with two changeover relay outputs as follows:-.
2.6.1 Output 1 & Output 4 (AA Relay)
Relay (Form C, changeover)
OP1
1A
1B
2A
OP4
AA
AB
AC
• Isolated output 300Vac CATII
• Contact rating:: 2A 264Vac resistive
• Output functions: Alarm/Event
* General Notes about Relays and Inductive Loads
High voltage transients may occur when switching inductive loads such as some contactors or solenoid valves. Through the internal contacts, these transients may introduce disturbances which could affect the performance of the instrument.
For this type of load it is recommended that a
‘snubber’ is connected across the normally open contact of the relay switching the load. The snubber recommended consists of a series connected resistor/capacitor (typically 15nF/100 Ω). A snubber will also prolong the life of the relay contacts.
A snubber should also be connected across the output terminal of a triac output to prevent false triggering under line transient conditions.
WARNING
When the relay contact is open, or it is connected to a high impedance load, it passes a current (typically
0.6mA at 110Vac and 1.2mA at 230Vac). You must ensure that this current will not hold on low power electrical loads. If the load is of this type the snubber should not be connected.
2.6.2 Output 3 Retransmission (Output 2 3216i)
OP3
• Isolated output 300Vac CATII
• Software configurable: 0-20mA or 4-
20mA plus 0-5V, 0-10V, 1-5V and 2-10V.
3A
3B
+
-
• Max load resistance: 500Ω
• Calibration accuracy: +(<0.25% of reading + <50 μA
• Output functions: PV retransmission.
• Output 2 (3216i) non-isolated
2.6.3 Transmitter Supply
A fixed 24Vdc supply is available to power an external transducer (not 3216i)
3C
3D
+
-
•
Isolated output 300Vac CATII
10 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
2.6.4 Digital Inputs A and B
Digital input A is not available in 32h8i/SG and optionally available on 3216i
Dig In A Dig In B
LA LB
C LC
• Not isolated from the sensor input
• Switching: 12Vdc at 40mA max
• Contact open > 500Ω. Contact closed < 200Ω
• Input functions: Please refer to the list in the quick codes.
2.6.5 Transducer Supply
In 32h8i/SG a 10Vdc supply is available as an excitation voltage for a bridge type transducer
Ext1
Ext2
+
-
• Minimum load resistance 300Ω
• Isolated output 300Vac CATII
2.7 Indicator Power Supply
1. Before connecting the indicator to the power line, make sure that the line voltage corresponds to the description on the identification label.
2. Use copper conductors only.
3. The power supply input is not fuse protected.
This should be provided externally.
4. For 24V the polarity is not important.
L
N
Line
Neutral
24
24
24V
24V
• High voltage supply: 100 to 230Vac, +15%,
48 to 62 Hz
• Low voltage supply:
24Vac, -15% +10%
24Vdc, -15% +20% +5% ripple voltage
• Recommended external fuse ratings are as follows:-
For 24 V ac/dc, fuse type: T rated 2A 250V
For 100 - 230Vac, fuse type: T rated
2A 250V.
2.8 Example Wiring Diagram
This shows 32h8i/SG connections for a strain gauge bridge.
N L
Fuse
N L 3D 3C 3B 3A LC LB 2B 2A 1B 1A
Internal
Signal
FET switch
- +
Cal
1
1
Cal
2
Ext
-
Txdcr
Supply
- +
Ext
+
HF HE HD AC AE AA
-
R
CAL
32h8i/SG Indicator
+
Strain
Gauge
Safety requirements for permanently connected equipment state:
• A switch or circuit breaker shall be included in the building installation
• It shall be in close proximity to the equipment and within easy reach of the operator
• It shall be marked as the disconnecting device for the equipment.
Note: a single switch or circuit breaker can drive more than one instrument.
Part No HA029006 Issue 5.0 Sept-12 11
2.9 Digital Communications (Optional)
Digital communications uses the Modbus protocol.
The interface may be ordered as EIA232 or EIA485
(2-wire).
• Isolated 300Vac CATII.
EIA 232 Connections
Com
Tx
Rx
Local Ground
Screen
HD Common
HE Rx A(+)
HF Tx B(-)
EIA 485 Connections
Rx Tx Com
Screen
* EIA232/ EIA485 2wire communications converter eg Type
KD485
220
Ω termination resistor on last instrument in the line
Tx Rx Com
*
RxB/ RxA/
TxB TxA Com
220
Ω termination resistor
Twisted pairs
Daisy Chain to further instruments
HD Common
HE Rx A(+)
HF Tx B(-)
3200iSeries Indicators
2.10 Additional Connections for 3216i
Connections for the 3216i indicator are similar to the
3216 indicator.
2.10.1 Input/Output 1 & Output 2
I/O1 may be configured as input or output.
Outputs can be logic (SSR drive), or relay, or mA dc.
Input is contact closure.
Relay Output (Form A, normally open)
OP1/2
1/2A
• Isolated output 300Vac CATII
• Contact rating: 2A 264Vac resistive
1/2B • Output functions: Alarm or event
Logic (SSR drive) Output
OP1
1A
1B
+
-
• Not isolated from the sensor input
• Output ON state: 12Vdc at 40mA max
• Output OFF state: <300mV, <100μA
• Output functions: Alarm or event
DC Output
OP1/2
1/2A
+
• Not isolated from the sensor input
• Software configurable: 0-20mA or 4-
20mA.
1/2B -
• Max load resistance: 500Ω
• Calibration accuracy: 1%, +100μA
• Output functions: Retransmission.
Logic Contact Closure Input (OP1 only)
OP1
1A
1B
• Not isolated from the sensor input
• Switching: 12Vdc at 40mA max
• Contact open > 500Ω. Contact closed < 150 Ω
• Input functions: Please refer to the list in the Quick Start codes.
12 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
3. Safety and EMC Information
This indicator is intended for industrial temperature and process applications when it will meet the requirements of the European Directives on Safety and EMC. Use in other applications, or failure to observe the installation instructions of this handbook may impair safety or EMC. The installer must ensure the safety and EMC of any particular installation.
Safety
This indicator complies with the European Low
Voltage Directive 2006/95/EC, by the application of the safety standard EN 61010.
Electromagnetic compatibility
This indicator conforms with the essential protection requirements of the EMC Directive 2004/108/EC by the application of a Technical Construction File. This instrument satisfies the general requirements of the industrial environment defined in EN 61326. For more information on product compliance refer to the
Technical Construction File.
GENERAL
The information contained in this manual is subject to change without notice. While every effort has been made to ensure the accuracy of the information, your supplier shall not be held liable for errors contained herein.
Unpacking and storage
The packaging should contain an instrument mounted in its sleeve, two mounting brackets for panel installation and an Installation & Operating guide. Certain ranges are supplied with an input adapter.
If on receipt, the packaging or the instrument is damaged, do not install the product but contact your supplier. If the instrument is to be stored before use, protect from humidity and dust in an ambient temperature range of -10
O
C to +70
O
C.
Service and repair
This indicator has no user serviceable parts. Contact your supplier for repair.
Caution: Charged capacitors
Before removing an instrument from its sleeve, disconnect the supply and wait at least two minutes to allow capacitors to discharge. It may be convenient to partially withdraw the instrument from the sleeve, then pause before completing the removal. In any case, avoid touching the exposed electronics of an instrument when withdrawing it from the sleeve.
Failure to observe these precautions may cause damage to components of the instrument or some discomfort to the user.
Electrostatic discharge precautions
When the indicator is removed from its sleeve, some of the exposed electronic components are vulnerable to damage by electrostatic discharge from someone handling the indicator. To avoid this, before handling the unplugged indicator discharge yourself to ground.
Cleaning
Do not use water or water based products to clean labels or they will become illegible. Isopropyl alcohol may be used to clean labels. A mild soap solution may be used to clean other exterior surfaces of the product.
3.1 Installation Safety Requirements
Safety Symbols
Various symbols may be used on the indicator. They have the following meaning:
!
Caution, (refer to accompanying documents)
Equipment protected throughout by DOUBLE
INSULATION
☺
Helpful hints
Personnel
Installation must only be carried out by suitably qualified personnel in accordance with the instructions in this handbook.
Enclosure of Live Parts
To prevent hands or metal tools touching parts that may be electrically live, the indicator must be enclosed in an enclosure.
Caution: Live sensors
The indicator is designed to operate if the temperature sensor is connected directly to an electrical heating element. However, you must ensure that service personnel do not touch connections to these inputs while they are live. With a live sensor, all cables, connectors and switches for connecting the sensor must be mains rated for use in
230Vac +15% CATII.
Wiring
It is important to connect the indicator in accordance with the wiring data given in this guide. Take particular care not to connect AC supplies to the low voltage sensor input or other low level inputs and outputs. Only use copper conductors for connections (except thermocouple inputs) and ensure that the wiring of installations comply with all local wiring regulations. For example in the UK use the latest version of the IEE wiring regulations,
(BS7671). In the USA use NEC Class 1 wiring methods.
Power Isolation
The installation must include a power isolating switch or circuit breaker. This device should be in close proximity to the indicator, within easy reach of the operator and marked as the disconnecting device for the instrument.
Overcurrent protection
The power supply to the system should be fused appropriately to protect the cabling to the units.
Part No HA029006 Issue 5.0 Sept-12 13
Voltage rating
The maximum continuous voltage applied between any of the following terminals must not exceed
230Vac:
• relay output to logic, dc or sensor connections;
• any connection to ground.
The indicator must not be wired to a three phase supply with an unearthed star connection. Under fault conditions such a supply could rise above
240Vac with respect to ground and the product would not be safe.
Conductive pollution
Electrically conductive pollution must be excluded from the cabinet in which the indicator is mounted.
For example, carbon dust is a form of electrically conductive pollution. To secure a suitable atmosphere in conditions of conductive pollution, fit an air filter to the air intake of the cabinet. Where condensation is likely, for example at low temperatures, include a thermostatically controlled heater in the cabinet.
This product has been designed to conform to
BSEN61010 installation category II, pollution degree 2.
These are defined as follows:-
Installation Category II (CAT II)
For equipment on nominal 230V supply, the maximum rated impulse voltage is 2500V.
Pollution Degree 2
Normally only non conductive pollution occurs.
Occasionally, however, a temporary conductivity caused by condensation shall be expected.
Grounding of the temperature sensor shield
In some installations it is common practice to replace the temperature sensor while the indicator is still powered up. Under these conditions, as additional protection against electric shock, we recommend that the shield of the temperature sensor is grounded. Do not rely on grounding through the framework of the machine.
Over-temperature protection
When designing any control system it is essential to consider what will happen if any part of the system should fail. In temperature control applications the primary danger is that the heating will remain constantly on. Apart from spoiling the product, this could damage any process machinery being controlled, or even cause a fire.
Reasons why the heating might remain constantly on include:
• the temperature sensor becoming detached from the process
• thermocouple wiring becoming short circuit;
• the controller failing with its heating output constantly on
• an external valve or contactor sticking in the heating condition
• the controller setpoint set too high.
Where damage or injury is possible, we recommend fitting a separate over-temperature protection unit,
3200iSeries Indicators with an independent temperature sensor, which will isolate the heating circuit.
This indicator can be used in addition to a controller as an over temperature device. It is recommended that the relay used to indicate the alarm condition should be set to high alarm configured with sensor break and inverse ‘ Inv’ operation so that it relaxes to the alarm condition when power is removed.
Installation requirements for EMC
To ensure compliance with the European EMC directive certain installation precautions are necessary as follows:
• For general guidance refer to Eurotherm
Controls EMC Installation Guide, HA025464.
• When using relay outputs it may be necessary to fit a filter suitable for suppressing the emissions.
The filter requirements will depend on the type of load.
• If the unit is used in table top equipment which is plugged into a standard power socket, then it is likely that compliance to the commercial and light industrial emissions standard is required. In this case to meet the conducted emissions requirement, a suitable mains filter should be installed.
Routing of wires
To minimise the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power cables. Where it is impractical to do this, use shielded cables with the shield grounded at both ends. In general keep cable lengths to a minimum.
14 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
4. Switch On
4.1 New Indicator
If the indicator is new and has not previously been configured, or following a ‘Cold Start’ (section 6.5), it will start up showing the ‘Quick Configuration’ codes.
This is a built in tool which enables you to configure the input type and range, the output functions and the display format.
!
Incorrect configuration can result in damage to the process and/or personal injury and must be carried out by a competent person authorised to do so. It is the responsibility of the person commissioning the instrument to ensure the configuration is correct
The quick code consists of two ‘SETS’ of five characters.
The upper section of the display shows the set selected, the lower section shows the five digits which make up the set.
Adjust these as follows:-.
1. Press any button .
The first character will change to a flashing ‘-‘.
SET 1
Input Type
Thermocouple
B Type B
Display units
Temperature
C
F o
C o
3 nn.nnn
(1)
K K 4 n.nnnn
P %
0 Pa
1 mPa
2 Kpa
Decimal point
32h8I only:
D L-m
E %RH
G %O2
RTD
P Pt100
Linear (all units)
M 0-80mV
2 0-20mA
3 Bar
5 PSI
6 Kg/cm
2
H %CO2
4 mBar J %CP
L V
M Amp
7 mmWG R mA
2. Press
V
or
W
to change the flashing character to the required code shown in the quick code tables –see next page. Note: An
x
indicates that the option is not fitted.
3. Press
to scroll to the next character.
☺
You cannot scroll to the next character until the current character is configured.
☺
To return to the first character press
6.
K C H C 0
PV Colour
(2)
32h8i only
G Green
R
C again, the display will show to press
Red
Colour change on Alarm.
Green to red
Set 1 is followed with R N G . H I
Then
R N G . L o
A
1
2
Set this for the maximum display range required
Set this for the minimum display range required
.
4. When all five characters have been configured the display will change to rng.hi followed by rng.lo which allows range high and low limits to be set.
5. The next press of
will select Set 2. Adjust each character as described for Set 1.
When the last character has been entered press
. Continue
if you wish to repeat the above quick codes or press
V
or
W
to if you are satisfied with the quick codes. The indicator will then automatically go to the operator level
Home display
First Alarm SP only
PV + Alarm SP
PV + Alarm SP
(Read only)
8 inWG T mV
4 4-20mA
Linear 32h8i
9 mmHG U Ohm
Set 2 follows these parameters
See next page
A Torr W ppm
0 0-10Vdc
1 1-5Vdc
B L-H Y RPM
(1) Up to 2 decimal places on 3216i and 3204i
Up to 4 decimal places on 32h8i
3 2-10Vdc
Z m-s
6 0-5Vdc (2) Colour change on top part of display only
Part No HA029006 Issue 5.0 Sept-12 15
R
N
SET 2 - 32h8i & 3204i
OP1
X Unconfigured
Relay or Logic Output
Alarm 1
Rate-of change - Rising
New alarm flag
With sensor Break
9 Rate-of change
With power Fail
C Rate-of change
With sensor
Break and power fail
G Rate-of change
SET 2 - 3216i
Relay or Logic Output
Alarm 1
N New alarm flag
With Sensor break
With power Fail
H 3 L W V
OP3
X Unconfigured
Analogue Output
PV Retransmission
1 4-20mA
2 0-20mA
3 0-5Vdc
4 1-5Vdc
32h8i
6 2-10Vdc h L g w x
IO1 and OP2
Analogue Output
PV Retransmission
1 4-20mA
2 0-20mA
X Unconfigured
Digital input I/O1 only
W Alarm acknowledge
K Keylock
U Remote up button
D Remote down button
V Recipe 2/1 select
OP4 (AA Relay)
X Unconfigured
Alarm 4
N
Rising
New alarm flag
With sensor Break
With power fail
With sensor
Break and power fail
OP4 (AA Relay)
X Unconfigured
Alarm 4
N New alarm flag
With sensor Break
With power fail
With Sensor break and power Fail M Peak Reset
Y Freeze PV
G Rate-of change
With sensor break and power fail
3200iSeries Indicators
Digital input A and B
X Unconfigured
(Dig in A not available on
32h8i/SG)
K Keylock
U
D
Remote up button
Remote down button
V
T
(1)
Z
(1)
Recipe 2/1 select
Automatic zero and span calibration –
32h8I/SG only
(1) linear ranges only on all indicators
Note:-
Alarm outputs are set to inverted when exiting from Quick Codes
Digital input A
X Unconfigured
K Keylock
U Remote up button
D Remote down button
V Recipe 2/1 select
Note:-
Alarm outputs are set to inverted when exiting from Quick Codes
16 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
4.1.1 To Re-Enter Quick Code Mode
If you need to re-enter the ‘Quick Configuration’ mode this can always be done as follows:-
1. Power down the indicator
2. Hold button down and power up the indicator again. Keep the button pressed until you are requested to enter a passcode.
3. Enter a passcode using the
V
or
W
buttons.
In a new indicator the passcode defaults to 4. If an incorrect passcode is entered you must repeat the whole procedure.
☺
Parameters may also be configured using a deeper level of access as described in subsequent chapters of this handbook. If this has been done and the Quick Code Mode is re-entered as described above, then the quick codes are shown with full stops
(e.g. G.S.2.G.A.) to indicate that the configuration has been changed.
4.2 Pre-Configured Indicator or
Subsequent Starts
A brief start up sequence consists of a self test in which all elements of the display are illuminated and the software version number is shown.
The indicator will briefly display the quick codes during start up and then proceed to Operator Level
1.
You will see the display shown below. It is called the
HOME display.
32h8i example
Process Value
Message Centre
Status Beacons
☺
If the Quick Codes do not appear during start up, this means that the indicator has been configured in a deeper level of access, as stated opposite. The quick codes may then not be valid and are therefore not shown.
4.3 Front panel layout
2
Operator Buttons
3
Message
Centre
1
Beacons:-
ALM Alarm active (Red)
OP1 Lit when output 1 is ON
OP2 This appears in 3216i only and is lit when output 2 is ON
OP3 Lit when output 3 is configured to retransmit the process value
OP4 Lit when output 4 (AA relay) is ON
2
Operator Buttons:-
From any display - press to return to the HOME display.
Press to select a new parameter. Hold down to continuously scroll through parameters.
W
Press to change or decrease a value.
V
Press to change or increase a value.
3
Message Centre
A scrolling message may appear in this section. For example, if a high alarm is configured to operate output 1, and a low alarm is configured to operate output 4, the scrolling messages ‘ALARM 1 HIGH’ and
‘ALARM 4 LOW’ are shown together with the beacons
‘ALM’, ‘OP1’ and ‘OP4’. ‘ALM’ flashes if the alarm has not been acknowledged.
If the input sensor is broken ‘ S.br’ appears in the top display and the scrolling message ‘INPUT SENSOR
BROKEN appears in the message centre.
Part No HA029006 Issue 5.0 Sept-12 17
4.3.1 Alarm Indication
Up to four alarms can be configured. If any alarm occurs, the red ALM beacon will flash. A scrolling text message will describe the source of the alarm, for example ALARM 1 H IGH . Any output attached to the alarm will operate.
Press alarm
and
(Ack) together to acknowledge the
If the alarm is still present the ALM beacon will light continuously.
By default alarms are configured as non-latching, deenergised in alarm. If you require latched alarms, please refer to the engineering handbook.
4.3.2 Out of Range Indication
If the input is too high HHHHH will be displayed
If the input is too low LLLLL will be displayed
4.3.3 Sensor Break Indication
An alarm condition ( S.br) is indicated if the sensor or the wiring between sensor and indicator becomes open circuit.
For a PRT input, sensor break is indicated if any one of the three wires is broken.
For mA input sensor break will not be detected due to the load resistor connected across the input terminals.
For Volts input sensor break may not be detected due to the potential divider network connected across the input terminals.
For a strain gauge transducer sensor break alarm will be indicated if either signal wires become open circuit or either of the supply wires becomes open circuit.
3200iSeries Indicators
4.4 Operator Parameters in Level 1
Operator level 1 is designed for day to day operation of the indicator and access to these parameters is not protected by a pass code.
Press
to step through the list of parameters.
The mnemonic of the parameter is shown in the lower display. After five seconds a scrolling text description of the parameter appears.
The value of the parameter is shown in the upper display. In level 1 the value is read only.
The parameters that appear depend upon the functions configured. They are:-
Parameter
Mnemonic
HIGH
LOW
TARE
A1 (----)
A2 (----)
A3 (----)
A4 (----)
Scrolling text and
Description
Availability
PEAK HIGH This is the highest reading that the indicator has recorded since switch on or since it was reset
PEAK LOW This is the lowest reading that the indicator has recorded since switch on or since it was reset
OFF No tare correction
TARE
FUNCTION
Linear inputs only
See also section
4.4.1.
On Select to automatically correct for tare weight
ALARM 1
SETPOINT
ALARM 2
SETPOINT faiL Displayed if the tare correction cannot be made
(----) shows the type of alarm configured. For example HI, LO, ROC.
This parameter sets the alarm thresholds.
ALARM 3
SETPOINT
ALARM 4
SETPOINT
18 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
4.4.1 Tare Correction
Tare correction is used, for example, when it is required to weigh the contents of a container but not the container itself.
The procedure is to place the empty container on the weigh bridge and ‘zero’ the indicator. Since it is likely that following containers will have different tare weights the tare function is available in operator level
1.
1. With the empty container placed on the weigh cell, press
until TARE is displayed.
2. Press
V or
W to select On
3. The weight of the container will automatically be taken form the total weight.
4.
FaiL will be displayed if the tare function fails, for example, if the weight is outside the high and low limits or a sensor break condition occurs. In this case correct the fault and repeat the procedure.
Alternatively, a digital input may have been set by selecting T in the quick codes (section 4.1) to provide this function via an external source such as a switch or pushbutton. In this case pressing the button will have the same effect as selecting ‘On’ in 2 above.
5. Operator Level 2
Level 2 provides access to additional parameters. It is protected by a security code.
5.1 To Enter Level 2
1. From any display press and hold
2. After a few seconds the display will show:-
.
3. Release .
(If no button is pressed for 45 seconds the display returns to the HOME display)
4. Press
V or
W to choose Lev 2 (Level 2)
5. After 2 seconds the
display will show:-
6. Press
V or
W
to enter the pass code. Default = ‘ 2’
7. If an incorrect code is entered the indicator reverts to Level 1.
5.1.1 To Return to Level 1
1. Press and hold
2. Press
W
to select
LEv 1
The indicator will return to the level 1 HOME display.
Note: A pass code is not required when going from a higher level to a lower level.
Part No HA029006 Issue 5.0 Sept-12 19
3200iSeries Indicators
5.2 Level 2 Parameters
As in Level 1, press
to step through the list of parameters.
The mnemonic of the parameter is shown in the message centre. After five seconds a scrolling text description of the parameter appears.
The value of the parameter is shown in the upper display. Press
V or
W to adjust this value.
If no key is pressed for 30 seconds the indicator returns to the HOME display.
Mnemonic
PRST
HIGH
LOW
TARE
SG.TYP
SHUNT
LO.CAL
HI.CAL
AUT,SG
A1 (----)
A2 (----)
A3 (----)
A4 (----)
ADDR
HOME
ID
REC.NO
STRAIN GAUGE CALIBRATION TYPE Select the calibration for the type of sensor in use.
SHUNT CALIBRATION To set the high calibration point for a bridge type strain gauge or pressure transducer.
STRAIN GAUGE LOW CAL 32h8i/SG only. See also section 5.3.
STRAIN GAUGE HIGH CAL 32h8i/SG only. See also
5.3.
STRAIN GAUGE AUTO CAL
32h8i/SG only. See also section 5.3.5.
ALARM 1 SETPOINT
ALARM 2 SETPOINT
ALARM 3 SETPOINT
ALARM 4 SETPOINT
ADDRESS Digital communications address for the instrument (if digital communications fitted)
HOME DISPLAY This configures the parameter which will be displayed in the HOME display in normal operation
CUSTOMER ID Customised instrument identification number
CURRENT RECIPE NUMBER The recipe currently in use.
See also section 5.4.
Backscroll is achieved when you are in this list by pressing
V while holding down
.
Scrolling Display and description
PEAK RESET Select On to reset the HIGH and LOW peak values. The display automatically returns to OFF
PEAK HIGH This is the highest reading that the indicator has recorded since switch on or since it was reset
PEAK LOW This is the lowest reading that the indicator has recorded since switch on or since it was reset
TARE FUNCTION
See also section 4.4.1.
To return to the HOME display at any time, press .
The following table shows a list of parameters available in Level 2.
Range
OFF
ON
Read only
Read only
OFF No tare correction
On Select to automatically correct for tare weight faiL Displayed if the tare correction cannot be made
SHnt Strain gauge bridge
ComP Comparison
CELL Load cell
OFF or 40.0 to 100.0%
No yes Perform automatic strain gauge calibration
(----) shows the type of alarm configured. For example HIGH, LOW,
1 to 254
PV Process variable aLm Alarm setpoint pv.aL
PV + Alarm SP p.a.ro
PV + Alarm SP read only
0 to 9999
STORE RECIPE TO SAVE
See also section 5.4. none No recipe
1 - 5 1 to 5 selected
FaiL Fail is shown if no recipe is saved none No recipe to store
1 - 5 1 to 5 done Recipe saved
20 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
Mnemonic Scrolling Display and description Range
UNITS DISPLAY UNITS The display units are shown in the top right hand corner of the display in normal operation. Units available are:-
O C O C none mpa mbar mmwg
No units displayed
Mpascals * milli Bar * mm water gauge * torr Torr * p.rh % Relative humidity *
P.CP ma ppm
SEC
PH mG
% carbon potential* milli amps *
Parts per million *
Seconds *
Ph * milli grams *
O F O F O k Kelvin
Perc kpa psi inwg
Percentage
Kpascals *
PSI * pa bar kgcm inches water gauge * mmhg
L-H Litres per hour * p.O 2 % O2 *
VoLt Volts * mV milli volts * rpm min
Revs per minute *
Minutes *
P.PH % Ph *
GrAm Grams *
Pascals *
Bar * kg/sq cm * mm mercury *
L-m Litres per minute * p.CO2 % CO2 *
Amp
Ohm m-s hrs mPH kG
Amps *
Ohms * milli seconds *
Hours *
Miles per hour *
Kilo grams *
* These units only appear in 32h8i indicators
☺
Press at any time to return immediately to the HOME screen at the top of the list.
☺
Hold
down to continuously scroll through the above list
Part No HA029006 Issue 5.0 Sept-12 21
5.3 Strain Gauge Calibration
The 32h8i/SG indicator is designed to operate with symmetrical bridge type strain gauges, nominally
350 Ω in each arm. It is generally necessary to calibrate the instrument to the transducer in use. This can be done in Operator Level 2 or 3 using any one of three methods. These are:-
CELL. Here a load cell is connected directly to the input terminals marked Signal + and – (section 5.3.1).
COMPARISON. The load cell is connected as above but the calibration is compared with a reference device or reference weight (section 5.3.2).
SHUNT. This is so called since it refers to switching a calibration resistor across one arm of a four wire measurement bridge in a strain gauge transducer
(section 5.3.3).
To configure the different modes:-
In Level 2, press
to scroll to SG.TYP and press
V or
W
to select CeLL, COmp or shnt
L
N
5.3.1 Load Cell Calibration
Connect a load cell as shown below:-
Fuse
N L 3D 3C 3B 3A LC LB 2B 2A 1B 1A
Load
Signal
- +
Cal
1
Cal
2
Txdcr
Supply
- +
Ext
-
Ext
+
HF HE HD AC AB AA
-
32h8i/SG Indicator
+
Output -
Sense -
Supply -
Output +
Supply +
Load cell
3200iSeries Indicators
If a 6-wire load cell is used the –ve Sense should be connected as shown above to the Cal 1 terminal. The
+ve sense wire is not connected.
If the load cell is 4-wire connect Cal 1 to the –ve supply, preferably at the load cell.
This wire compensates for voltage drop in the supply to the load cell due to lead resistance.
1. In Level 2, press
to scroll to LO.CAL.
2. Remove all weight from the load cell and press
V or
W
to select yes
3. The indicator will show busy as it calibrates the zero weight condition. pass or faiL will be indicated when the low point calibration is complete.
4. Now add a weight which represents the full scale span of the load cell
5. Repeat the above to calibrate the high point –
HI.CAL.
5.3.2 Comparison Calibration
Comparison calibration is most appropriate when calibrating the indicator against a second reference device.
The load cell is connected as shown in the previous example.
1. In Level 2, press
to scroll to LO.CAL and press
V or
W
to select yes
2. Press
to scroll to the next parameter - C.ADJ
(CALIBRATION ADJUST)
3. Press
V or
W
to set the low value calibration point as indicated by the reference device. As soon as the value is entered the indicator will show busy as it calibrates the minimum weight condition. pass or faiL will be indicated when the low point calibration is complete.
4. Repeat the above steps to calibrate the high point - HI.CAL
22 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
N
L
5.3.3 Shunt Calibration
A bridge type strain gauge is connected as shown.
Depending on the type of gauge, R
CAL
may be included internally or supplied as a separate item.
Strain
Gauge
Fuse
-
R
CAL
N L 3D 3C 3B 3A LC LB 2B 2A 1B 1A
Signal
- +
Internal
FET switch
Cal
1
Cal
2
Ex t
-
Txdcr
Supply
- +
Ext
+
HF HE HD AC AB AA
32h8i/SG Indicator
+
The high (span) and low (zero) adjustment of the transducer can be performed automatically or manually.
Manual allows the low point and high point to be calibrated individually.
Automatic performs both low and high point calibration by the selection of one parameter.
5.3.4 Manual Calibration
1. Remove all pressure from the transducer to establish a zero reference
2. In operator level 2, press
shown in the lower display.
until SHUNT is
3. Press
V or
W
to set the point at which the high calibration is to be done. This is typically
80% of the transducer span
4. Press
to scroll to LO.CAL and press
V or
W
to select yes
5. The indicator will show busy as it calibrates the minimum weight condition. pass or faiL will be indicated when the low point calibration is complete.
6. Press
to scroll to HI.CAL and repeat the above steps to calibrate 80% (as set in 3 above) of the transducer span
The high calibration value may be checked by shorting Cal 1 and Cal 2. For example a 0 – 3000psi probe will read 2400 when Cal 1 and Cal 2 are linked.
5.3.5 Automatic Calibration
1. Remove all pressure from the transducer to establish a zero reference
2. In operator level 2, press
shown in the lower display
until AUT.SG is
3. Press
V or
W
to select yes
The indicator will automatically perform the following sequence:- a. Disconnect the calibration resistor R
CAL b. Calculate the low point calibration value by continuously averaging two sets of 50 measurements of the input until stable readings are obtained.
Lo will be indicated during this process. c. Connect the calibration resistor by closing a contact between terminals VI and LA
Calculate the high point calibration value by continuously averaging two sets of 50 measurements of the input until stable readings are obtained. Hi will be indicated during this process.
5.3.6 Calibration Using a Digital Input
A digital input may have been set by selecting Z in the quick codes (section 4.1) to allow the transducer to be calibrated automatically via an external source such as a switch or pushbutton. In this case pressing the button will have the same effect as selecting yes in 3 above.
5.3.6.1 Fail
Fail will be displayed in any of the above calibration procedures if the calibration is not possible. For example, the input shows Sensor Break or is out of range or the transducer or load cell is not connected correctly. It is necessary to correct the fault and start the procedure again.
Part No HA029006 Issue 5.0 Sept-12 23
5.4 Recipes
It is possible to store operating values in up to five different recipes by taking a snapshot of the current settings and storing these in a recipe number.
Examples, of typical operating parameters may be alarm setpoint values. A particular recipe number may then be recalled for a particular process.
5.4.1 To Store Values in a Recipe
1. In the list of parameters, press
store
to select
2. Select a recipe number from 1 to 5 in which to store the current settings. The indicator will show done when the values are stored. All previous values which may have been stored in this recipe are overwritten.
5.4.2 To Load a Recipe
1. In the list of parameters, press
rec. no
to select
Select a recipe number from 1 to 5 in which the required settings have been stored. The values will automatically loaded from the recipe. If no values have been stored in that recipe, faiL will be indicated
3200iSeries Indicators
5.5 FM and Alarm Units
3200 indicators supplied to Function code FM are FM approved.
3200 indicators supplied to Function code DN are approved to EN14597.
The instrument label is marked accordingly.
In these instruments the alarm operating the AA relay output is set to inverted and latching. This function cannot be altered.
When the instrument is configured using the Quick
Start codes (section 4.1), Alarm 1 is used to operate both Outputs 1 and 4 (AA relay). The Quick Start configuration for the AA relay will enable and configure Alarm 4 but Alarm 4 will not be used to operate Output 4.
!
If Quick Start is used to configure Alarm 1 as a high alarm and Alarm 4 as a low alarm, then the resulting configuration will be that the high alarm 1 is used to drive both outputs 1 and 4. The low alarm 4 will not be connected to any output.
Further details on latching and blocking alarms can be found in section 10.1.
24 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
6. Access to Further Parameters
Parameters are available under different levels of security and are defined as Level 1 (Lev1), Level 2
(Lev2), Level 3 (Lev 3) and Configuration (C on f).
Level 1 has no passcode since it contains a minimal set of parameters generally sufficient to run the process on a daily basis. Level 2 allows access to parameters which may used in commissioning an indicator or settings between different products or batches. This has been described in the previous section.
Level 3 and Configuration level parameters are also available as follows:-
6.1 Level 3
Level 3 makes all operating parameters available and alterable (if not read only). It is typically used when commissioning an indicator
Examples are:-
Range limits, setting alarm levels, communications address.
6.2 Configuration Level
This level makes available all parameters including the operation parameters so that there is no need to switch between configuration and operation levels during commissioning. It is designed for those who may wish to change the fundamental characteristics of the instrument to match the process.
Examples are:-
Input (thermocouple type); Alarm type;
Communications type.
WARNING
Configuration level gives access to a wide range of parameters which match the indicator to the process. Incorrect configuration could result in damage to the process and/or personal injury. It is the responsibility of the person commissioning the process to ensure that the configuration is correct.
In configuration level the indicator is not providing alarm indication. Do not select configuration level on a live process.
Operating
Level
Level 1
Level 2
Level 3
Conf
Home
List
Full
Operator
Configuration Alarms
Yes
Yes
Yes
No
Part No HA029006 Issue 5.0 Sept-12 25
3200iSeries Indicators
6.2.1 To Select Access Level 3 or Configuration Level
Do This
1. From any display press and hold seconds
for more than 5
2. Press
V or
W to enter the passcode for Level 3
The Display You Should See Additional Notes
To Select Level 3
Lev 3 go to
3
0 code code
The display will pass from the current operating level, for example,
Lev 1 to Lev 3 as the button is held down.
(If no button is then pressed for about 50 seconds the display returns to the HOME display)
The default code is 3:
If an incorrect code is entered the display reverts to
‘g o t o ’.
If a correct code is entered the indicator is now in the level 3 will then revert to the HOME display
3. When the LEV3 GOTO view is shown, as in paragraph 1 above, press
‘
Conf’
V
to select
To Select Configuration level
Conf go to
0 code
Note:
V must be pressed quickly before the indicator requests the code for level 3
4. Press
V or
W to enter the passcode for Configuration level
4 code
Conf
The default code is 4:
If an incorrect code is entered the display reverts to
‘g o t o ’.
If a correct code is entered the indicator is now in
Configuration level will now show
Conf
5. Press and hold than 3 seconds
for more
6. Press
V
to select the required level eg LEV 1
To Return to a Lower Level
Conf go to
Lev1 go to
The choices are:
LEV 1 Level 1
LEV 2 Level 2
LEV 3 Level 3
ConF Configuration
It is not necessary to enter a code when going from a higher level to a lower level.
Alternatively, press and scroll to the A cce s list header, then press
to select the required level.
The display will then flash ‘
ConF’ for a few seconds and the indicator will then go through its start up sequence, starting in the level selected.
Do not power down while
Conf is flashing. If a power down does occur an error message will appear – see section 10.4 ‘Diagnostic Alarms’
☺
A special case exists if a security code has been configured as ‘0’ If this has been done it is not necessary to enter a code and the indicator will enter the chosen level immediately.
☺
When the indicator is in configuration level the
ACCESS list header can be selected from any view by holding down the seconds. Then press
button for more than 3
again to select ‘ACCES’
26 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
6.3 Parameter lists
Parameters are organised in lists. The top of the list shows the list header only. The name of the list header describes the generic function of the parameters within the list. For example, the list header ‘ALARM’ contains parameters which enable you to set up alarm conditions.
6.3.1 To Choose Parameter List Headers
Press . Each list header is selected in turn every time this key is pressed.
The name of the list header appears in the lower display, followed, after a few seconds, by a scrolling longer description of the name.
The following example shows how to select the first two list headers. (Views are shown for 32h8i indicator).
Scrolling parameter name
CONFIGURATION PROCESS
INPUT LIST
OUTPUT1 LIST
Keep pressing to select further list headers
The list is continuous
6.3.2 To Locate a Parameter
Choose the appropriate list, then press
. Each parameter in the list is selected in turn each time this button is pressed. The following example shows how to select the first two parameters in the ALARM List.
All parameters in all lists follow the same procedure.
(Views are shown for 32h8i indicator).
Alarm List Header
Parameter ‘Value’. In this case set to Full Scale High Alarm
Parameter mnemonic ‘a 1. ty p ’ followed by a scrolling message
‘a la rm 1 typ e ’
Parameter ‘Value’. In this case an
’numerical’ value, set to ‘112’
Parameter mnemonic ‘a 1. H I’ followed by a scrolling message
‘a la rm 1 se tp o in t’
Further parameters
☺
Press list header.
to jump back to the
6.3.3 How Parameters are Displayed
As shown above. whenever a parameter is selected it is displayed as a mnemonic, of four or five characters, for example ‘A1.TYP’.
After a few seconds this display is replaced by a scrolling banner which gives a more detailed description of the parameter. In this example ‘A1.TYP’
= ‘a la rm 1 type’. The scrolling banner is only shown once after the parameter is first accessed. (Views are shown for 32h8i indicator).
The name of the list header is also displayed in this way. a la rm 1 typ e ’
The upper part of the display shows the value of the parameter.
The lower part shows its mnemonic followed by the scrolling name of the parameter
6.3.4 To Change a Parameter Value
With the parameter selected, press
V
to increase the value, press
W
to decrease the value. If either key is held down the analogue value changes at an increasing rate.
The new value is entered after the key is released and is indicated by the display blinking. The exception to this is output ‘Power’ when in manual. In this case the value is entered continuously.
The upper display shows the parameter value the lower display shows the parameter name.
6.3.5 To Return to the HOME Display
Press +
.
On release of the keys the display returns to the
HOME list. The current operating level remains unchanged.
6.3.6 Time Out
A time out applies to the ‘Go To’ and ‘Control Mode’ parameters. If no key presses are detected within a period of 5 seconds the display will revert back to the
HOME list.
☺
Press and hold
to scroll parameters forward through the list. With
depressed, press scroll parameters backward.
V
to
Part No HA029006 Issue 5.0 Sept-12 27
3200iSeries Indicators
6.4 Navigation Diagram
The diagram below shows the all list headings available in configuration level for 32h8i indicator.
The parameters in a list are shown in tables in the following sections of this manual together with explanations of their meanings and possible use.
Press to continuously scroll around the list headers
Configuration level conf
Input list
INPUT
IN.TYP
UNITS
DEC.P
Output 1 list
Output 2/3 list
Output 4list Logic input list
OP-1 OP-2/3 AA LA / LB
1.ID
1.FUN
1.SRC
3.ID
3.FUN
3.RNG
4.TYP
4.FUN
4.SRC
L.TYP
L.D.IN
L.SENS
Alarm list
ALARM
A1.TYP
A1.--
A1.STS
Recipe list
RECIPE
REC.N
STORE
Section 11
Digital comms list
COMM
ID
ADDR
BAUD
Calibration list
CAL
PHASE
GO
SG.TYP
Access list
ACCES
GOTO
LEV2.P
LEV3.P
MV.HI
MV.LO
RNG.HI
RNG.L
PV.OF
FILT.T
FILT.D
CJC.TY
SB.TYP
1.SRCB
1.SRC
1.SRC
1.SENS
Section
8.1 or 8.2 for 3216i
3.LOW
3.HIGH
Section
8.3 and
8.4
4.SRCB
4.SRC
4.SRC
4.SENS
Section
8.5
Only
Logic input LB available in
32h8i/S
G
Section
9.1
A1.HY
A1.LAT
A1.BLK
A1.DL
A1.OF
The above are repeated for alarms
2 to 4
Section
10.3
PRTY
DELAY
RETRN
REG.A
Section
12.2
*
SHUNT
LO.CA
HI.CAL
AUT.S
* 32h8i/SG only
K.LOC
Section
13.5
CONF.
ID
HOME
COLO
COLD
PASS.C
MESG
Section
6.5
Press
to continuously scroll around parameters
SB.DIR
CJC.IN
PV.IN
MV.IN
P.RST
HIGH
LOW
TARE
Section
7.1.
☺
Lists may vary depending on the type of indicator and options configured. For example CJC.TYP and CJC.IN only appear if the Input Type is a thermocouple.
28 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
6.5 Access Parameters
The following table summarises the parameters available under the ACCESS list header
!
The Access List can be selected at any time when in configuration level by holding seconds, then press
V or W with still held down. key down for 3
ACCESS LIST
Name Scrolling
Display
G O T O GOTO
‘A C C S ’
Parameter Description Values Allowed
Allows you to change the access level of the indicator. Passwords prevent unauthorised change
Lev.1 Operator level 1
Lev.2 Operator level 2
Lev.3 Operator level 3
Conf Configuration level
Default Access
Level
Lev.1 Conf
PASSCODE
The Level 2 passcode 0-9999
0 = no passcode will be requested
The Level 3 passcode
PASSCODE
CONF.P CONFIG
PASSCODE
To set a Configuration level passcode
I D CUSTOMER ID To set the identification of the indicator
H O M E HOME
DISPLAY See
Note 1
DISPLAY
COLOUR
K . L O C K KEYBOARD
LOCK
ENABLE/
DISABLE
To configure the parameters to be displayed in the HOME display
To configure the colour of the top section of the display
To limit operation of the front panel buttons when in operator levels.
☺
If ALL has been selected, then to restore access to the keyboard, power up the indicator with the button held down and enter the configuration level passcode as described in section 4.1.1. This will take you to the Quick Code mode.
Press
to EX IT and select
YES.
The front panel buttons can then be operated as normal. pV Process Value – top display
Blank lower display aLm First configured alarm – top
Blank lower display pV.aL PV - top display
First configured alarm in lower section p.a.ro PV - top display
First configured alarm read only in lower section
Gr Green red Red g2R Green normal. Changes to red on alarm none Unlocked
ALL All buttons locked
Edit Edit keys locked
Use this parameter with care.
When set to yes the indicator will return to factory settings on the next power up
No Disable
YES Enable
P A S S . C FEATURE
PASSCODE
To enable chargeable options
2
3
4
Conf
Conf
Conf
Std Conf
Gr none Conf
Conf
Conf
Conf
MESSAGE using iTools configuration software.
This parameter calls up messages 1 to 15.
OFF The HOME display is configured according to the parameter HOME above
1 to Message 1
15
Message 15
Off Conf
The following sections in this handbook describe the parameters associated with each subject. The general format of these sections is a description of the subject, followed by the table of all parameters to be found in the list, followed by an example of how to configure or set up parameters.
Part No HA029006 Issue 5.0 Sept-12 29
3200iSeries Indicators
7. Process Input
Parameters in the input list configure the input to match your sensor. These parameters provide the following features:-
Input Type and linearisation
Display units and resolution
Input filter
Fault detection
User calibration
Over/Under range
Thermocouple (TC) and 3-wire resistance thermometer (RTD) temperature detectors
Linear input (-10 to +80mV) through external shunt or voltage divider, mA assumes a
2.49
Ω external shunt.
See the table in section 7.1.1. for the list of input types available
The change of display units and resolution will all the parameters related to the process variable
First order filter to provide damping of the input signal. This may be necessary to prevent the effects of excessive process noise on the PV input from causing poor control and indication. More typically used with linear process inputs.
Sensor break is indicated by an alarm message ‘Sbr’. For thermocouple it detects when the impedance is greater than pre-defined levels; for RTD when the resistance is less than 12 Ω.
Either by simple offset or by slope and gain. See section 13.2. for further details.
When the input signal exceeds the input span by more than 5% the PV will flash indicating under or over range. If the value is too high to fit the the number of characters on the display ‘HHHH’ or ‘LLLL’ will flash. The same indications apply when the display is not able to show the PV, for example, when the input is greater than
999.9
o
C with one decimal point.
7.1 Process Input Parameters
INPUT LIST
Name
IN.TYP
I N P U T
Scrolling
Display
INPUT TYPE
UNITS DISPLAY
UNITS
Parameter Description
Selects input linearisation and range
Display units shown on the instrument
Value
See section 7.1.1. for input types available none No units - only for custom linearisation
For a full list of units see section 7.1.2. nnnnn - No decimal point to n.nnnn - four decimal points
Default Access
Level o C
Conf
L3 R/O
L3
DEC.P DISPLAY
POINTS
Decimal point position nnnnn Conf
L3 R/O
80.00 Conf
HIGH
LOW
LIMIT
High limit for mV (mA) inputs (1)
(not 38h8i/SG)
Low limit for mV (mA) inputs
(1)
(not 38h8i/SG)
HIGH Range high limit for thermocouple RTD and mV inputs (1)
-10.00 to +80.00mV
-10.00 to +80.00mV
From the high limit of the selected input type to the ‘Low Range Limit’ parameter minus one display unit.
-10.00 Conf
Conf
L3 R/O
LIMIT
Range low limit for thermocouple RTD and mV inputs (1)
From the low limit of the selected input type to the ‘High Range Limit’ parameter minus one display unit.
Conf
L3 R/O
(1) See section 7.1.3 for an example of how to adjust the above four parameters.
PV.OFS PV OFFSET A simple offset applied to all input values.
See section 7.1.3.
Generally one decimal point more than PV
FILT.T FILTER TIME Input filter time constant
(first order digital filter)
OFF to 100.0 seconds 1.6
FILT.D DISPLAY
CJ.TYP
FILTER
CJC TYPE
Provides a filter for the displayed value
Configuration of the CJC type
(only shown for thermocouple inputs)
Off
No display filter
1
2
Zero the least significant digit
Zero the two least significant digits
Auto Automatic
0 o C Fixed at 0 o
C
50 o C Fixed at 50 o C
L3
L3
Off
L3
Auto Conf and if T/C
L3 R/O
SB.TYP SENSOR
BREAK TYPE
Defines the action which is applied to the output if the sensor breaks (open circuit) oFF No sensor break will be detected on on Open circuit sensor will be detected
Lat Latching
Conf
L3 R/O
30 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
SB.DIR SENSOR
BREAK
DIRECTION
CJC.IN CJC
TEMPERATURE
VALUE
MV.IN MILLIVOLT
INPUT VALUE
Current measured temperature
Millivolts measured at the rear PV Input terminals
P.RST
May be used, for example, in combination with retransmission of PV. The retransmitted value will either go to minimum or maximum output
Temperature measured at the rear terminal block.
Used in the CJC calculation
(only shown for thermocouple inputs)
HIGH
PEAK RESET Select ON to reset the HIGH and LOW peak values. The display automatically returns to OFF
PEAK HIGH This is the highest reading that the indicator has recorded since switch on or since it was reset
LOW PEAK LOW
TARE TARE
FUNCTION
This is the lowest reading that the indicator has recorded since switch on or since it was reset
To select Tare function up Up scale. Output goes to maximum
Dwn
Down scale. Output goes to minimum
Read only
Minimum display to maximum display range xx.xx mV - read only
OFF
On
Read only peak Values reset
Read only up Conf
Conf
L3 R/O and if T/C
Conf
L3 R/O
OFF L1
L1
L1
TA.OFS TARE OFFSET Allows an offset to be applied to TARE or to be reset to zero
7.1.1 Input Types and Ranges
OFF Off
ON Tare selected
FAIL Selection of the function failed
Instrument range. When TARE has been applied the Tare weight is shown here.
OFF L1
L3
Input Type
J.tc Thermocouple type J k.tc Thermocouple type K
L.tc Thermocouple type L r.tc Thermocouple type R
-210
-200
-200
-50
1200
1372
900
1700 o o o o
C -238 2192
C -238 2498
C -238 1652
C -58 3124 b.tc Thermocouple type B n.tc Thermocouple type N t.tc Thermocouple type T
S.tc Thermocouple type S
0
-200
-200
-50
1820
1300
400
1768 o o o o
C -32
C -58
3308
C -238 2372
C -238 752
3214 rtd Pt100 resistance thermometer mv mV or mA linear input
-200
-10.00
850
80.00 o
C -238 1562
VoLt Volts input -0.2 12.7
Cms Value received over digital communications (modbus address 203).
This value must be updated every 5 seconds or the indicator will show sensor break
S.gav Strain Gauge 32h8i only
Min
Range
Max
Range
Unit s
Min
Range
Max
Range
Unit s o
F o
F o
F o
F o
F o F o
F o
F o
F
Part No HA029006 Issue 5.0 Sept-12 31
3200iSeries Indicators p.rh
P.CP ma ppm
SEC
PH mG
7.1.2 Units
O C none mpa mbar mmwg o C O F
No units displayed Perc
Mpascals * milli Bar * mm water gauge * kpa psi inwg torr Torr * L-H
% Relative humidity
*
% carbon potential
* milli amps *
Parts per million *
Seconds *
Ph * milli grams * p.O 2
VoLt mV rpm min
P.PH
GrAm o F
Percentage
Kpascals *
PSI * inches water gauge *
Litres per hour *
O k pa bar kgcm mmhg
L-m
% O2 * p.CO2
Amp Volts * milli volts * Ohm
Revs per minute * m-s
Minutes *
% Ph *
Grams * hrs mPH kG
Kelvin
Pascals *
Bar * kg/sq cm * mm mercury *
Litres per minute *
* These units only appear in
32h8i indicators
% C/O2 *
Amps *
Ohms * milli seconds *
Hours *
Miles per hour *
Kilo grams *
32 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
7.1.3 PV Offset
All ranges of the indicator have been calibrated against traceable reference standards. This means that if the input type is changed it is not necessary to calibrate the indicator. There may be occasions, however, when you wish to apply an offset to the standard calibration to take account of known errors within the process, for example, a known sensor error or a known error due to the positioning of the sensor.
In these instances it is not advisable to change the reference (factory) calibration, but to apply a user defined offset.
PV Offset applies a single offset to the temperature or process value over the full display range of the indicator and can be adjusted in Level 3. It has the effect of moving the curve up a down about a central point as shown in the example below:-
Display
Reading
Fixed offset
(e.g. 2)
Factory calibration
Electrical Input
7.1.3.1 Example: To Apply an Offset:-
Connect the input of the indicator to the source device which you wish to calibrate to
Set the source to the desired calibration value
The indicator will display the current measurement of the value
If the display is correct, the indicator is correctly calibrated and no further action is necessary. If you wish to offset the reading:-
Display Do This
1. Select Level
3 or Conf as described in
Chapter 2. Then press to select ‘ INPUT’
Additional Notes
Scrolling display
‘p ro c e s s in p u t l is t’
2. Press
to scroll to ‘PV /O FS’
3. Press
V
or
W
to adjust the offset to the reading you require
2.0 pv.o fs
‘p v o f fs e t’
In this case an offset of 2.0 units is applied
It is also possible to apply a five point offset which adjusts both low and high points. This is done in Level
3 using the CAL List, and the procedure is described in the Calibration section 13.2.1.
7.1.4 PV Input Scaling
Input scaling applies to the linear mV and volts input ranges only. This is set by configuring the INPUT TYPE parameter to mV or VoLt, mV has an input range of –
10 to 80mV. Using an external burden resistor of
2.49
Ω, the indicator can be made to accept 4-20mA from a current source. Scaling of the input will match the displayed reading to the electrical input levels from the transducer. PV input scaling can only be adjusted in Configuration level and is not provided for direct thermocouple or RTD inputs.
The graph below shows an example of input scaling, where it is required to display 2.0 when the input is
4mV and 500.0 when the input is 20mV .
If the input exceeds +5% of the inp.Lo or inp.Hi settings, sensor break will be displayed.
Display
Reading
R N G . H I eg 500.0
For mA inputs
4-20mA = 9.96-49.8mV with 2.49
Ω load resistor
0-20mA = 0-49.8mV with
2.49
Ω load resistor mA input will detect sensor break if mA < 3mA
Use a current source to remove shunt resistor errors R n g . lo eg 2.0 in p . lo eg 4 mV in p . h i eg 20 mV
Electrical Input
7.1.4.1 Example: To Scale a Linear Input
Select Configuration level as described in Chapter 2.
Then:-
Do This Display Additional
Notes
1. Then press to select ‘ in p u t’ in p u t
‘p ro c e s s in p u t l is t’
2. Press
to scroll to ‘ in . ty p ’
V
3. Press or to ‘ mV or VoLt
W
4. Press
to scroll to ‘ in p . h i’
V
5. Press to ’
20.00
or
W
6. Press
to scroll to ‘ in p . lo ’
7. Press to ‘
4.00
V
or
W
8. Press
to scroll to ‘rn g . h i’
V
9. Press to ‘
500.0
or
W
10. Press
to scroll to ‘rn g . lo ’
11. Press to ‘ 2.0
V
or
W mv in . ty p
‘ in p u t ty p e ’
Scrolling display
‘ lin e a r in p u t h ig h ’
Scrolling display
‘ lin e a r in p u t lo w ’
500.0 rh g. h i
In operator level the indicator will read 500.0 for a mV input of 20.00
2.0 rh g. lo
In operator level the indicator will read 2.0 for a mV input of
4.00
Part No HA029006 Issue 5.0 Sept-12 33
3200iSeries Indicators
8. Input/Output Channels
Indicators may be ordered with relay, analogue or logic channels to provide different interfaces to plant devices.
The connections for these channels is made on terminals 1 to 3.
8.1 Output Channel 1 (OP-1) - 32h8i and 3204i Indicators
Output 1 is always a changeover relay in 32h8i and 3204i indicators and connected to terminals 1A, 1B and 2A. It is typically used to provide external indication of alarms. OP1 beacon is operated from this output.
Output 1 is configured using the parameters in the following table:-
OUTPUT LIST 1 ‘o p -1 ’
Name
1.I D
Scrolling Display
I/O 1 TYPE
Parameter
Description
Displays the type of output
1.FUNC I/O 1 FUNCTION The function may be turned off, otherwise set to d.out
1.SRC.A I/O 1 SOURCE A
1.SRC.B
1.SRC.C
1.SRC.D
I/O 1 SOURCE B
I/O 1 SOURCE C
I/O 1 SOURCE D
Selects the source of an event which will operate the output relay
The output status is the result of an OR of
Src A, Src B, Src C, and Src D
Up to four events can, therefore, operate the output
See section 8.3.2.
1.SENS I/O 1 SENSE To configure the sense of the output channel.
See also section 8.3.1
Value
ReLy Relay output none Disabled. If disabled no further parameters are shown d.out
Digital output none No event connected to the output
1.--Alarm 1 The --- indicates the
2.--Alarm 2 alarm type. If the
3.--Alarm 3 alarm is not
4.--Alarm4 configured
AL.(Alarm no) is shown
ALL.A
All alarms. Logical AND of alarms 1 to 4. nw.AL
Any new alarm
Pwr.f
Power fail. See also section
8.3.3.
O.rng
Output relay operates if the indicator input is over range sbr Sensor break alarm paL.1
Pre alarm 1 paL.2
Pre alarm 2 paL.3
Pre alarm 3 paL.4
Pre alarm 4 nor Normal
Inv Inverted
Default Access
Level
ReLy Read only
HEAt Conf none nor
Conf
Conf
34 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
8.2 Input/Output Channel 1 (I/O-1) - 3216i Indicator
In the case of the 3216i channel 1 can be configured as an input or an output. For 3216i the parameters are defined in the following table:-
INPUT/OUTPUT LIST 1 ‘IO -1 ’
Name
1.ID
Scrolling
Display
IO 1 TYPE
Parameter
Description
I/O channel 1 hardware type defined by the hardware fitted
1.FUNC IO 1 FUNCTION I/O channel 1 function.
1.SRC.B
SOURCE A
OUTPUT 1
SOURCE B
SOURCE C
SOURCE D
FUNCTION
1.SENS IO 1 SENSE
RANGE
LOW RANGE
These parameters only appear when the channel function is a
Digital output, i.e. 1.FUNC = d.out
These parameters have the same function as described above
See section 8.3.2. applicable to I/O 1 and only appears if the channel function is a Digital IP i.e. 1.FUNC = d.in
Only one function may be activated by a physical input
To configure the sense of the input or output channel.
See section 8.3.1
To configure 0-20mA or 4-20mA output
Only appears if the channel is DC output
To scale the DC output none No input or output fitted dC.OP
DC output (see note 1) reLy Relay output
L.IO Logic Input/Output none Disabled. If disabled no further parameters are shown d.out
Digital output. Shown if I/O 1
TYPE = reLy or L.IO d.in Digital input. Shown if I/O 1
TYPE =
L.IO
PV Process variable. Shown if I/O 1
TYPE = dc.OP none No event connected to the output
1.--Alarm 1 The --- indicates the
2.--Alarm 2 alarm type. If the
3.--Alarm 3 alarm is not
4.--Alarm4 configured
AL.(Alarm no) is shown
ALL.A
All alarms. Logical AND of alarms 1 to 4. nw.AL
Any new alarm
Sbr Sensor break alarm
Pwr.f
Power fail. See also section
8.3.3.
O.rng
Output operates if the indicator input is over range paL.1
Pre alarm 1 paL.2
Pre alarm 2 paL.3
Pre alarm 3 paL.4
Pre alarm 4 none Input not used
Ac.AL
Alarm acknowledge tare Tare (linear inputs only) aL.in
Alarm inhibit. See note 1 p.rst
Peak value reset free Freezes the current displayed value
Loc.b
Front keypad disable (keylock) rec Recipe select through IO1 digital input nor
Inv
Normal
Inverted
0.20 0-20mA output
4.20 4-20mA output
0 - 3000
Value Defaul t
As order ed
Access
Level
Read only none Conf none Conf
Ac.AL Conf nor Conf
L3
Conf
HIGH RANGE
Note 1:-
DC output calibration is described in section 13.4.
Part No HA029006 Issue 5.0 Sept-12 35
3200iSeries Indicators
8.3 Output Channel 2 (OP-2) - 3216i Indicator
Output 2 is only available in 3216i. It may be optionally ordered as a normally open relay or analogue output and is available on terminals 2A and 2B. If it is ordered as a relay it can be configured to operate on alarms (the same as
I/O1). If it is ordered as analogue it is configured to provide PV re-transmission.
OUTPUT LIST 2 ‘o p - 2 ’
Name
2.ID
Scrolling
Display
Parameter
Description
OUTPUT 2 TYPE Output channel 2 hardware type defined by the hardware fitted
Value Defaul t
As order ed
Access
Level
Read only
2.SRC.B
FUNCTION
SOURCE A
OUTPUT 2
SOURCE B
SOURCE C
SOURCE D
SENSE
RANGE
LOW RANGE
Output channel 2 function.
These parameters only appear when the channel function is a
Digital output, i.e. 2.FUNC = d.out
These parameters have the same function as described above
See section 8.3.2.
To configure the sense of the relay output.
See section 8.3.1.
To configure 0-20mA or 4-20mA output
Only appears if the channel is DC output
To scale the DC output none No input or output fitted dC.OP
DC output (see note 1) reLy Relay output none Disabled. If disabled no further parameters are shown d.out
Digital output. Shown if O/P 2
TYPE = reLy
PV Process variable. Shown if O/P
2 TYPE = dc.OP none No event connected to the output
1.---
Alarm 1 The --- indicates the
2.--Alarm 2 alarm type. If the
3.--Alarm 3 alarm is not
4.--Alarm4 configured
AL.(Alarm no) is shown
ALL.A
All alarms. Logical AND of alarms 1 to 4. nw.AL
Any new alarm
Sbr
Sensor break alarm
Pwr.f
Power fail. See also section
8.3.3.
O.rng
Output relay operates if the indicator input is over range paL.1
Pre alarm 1 paL.2
Pre alarm 2 paL.3
Pre alarm 3 paL.4
Pre alarm 4 nor Normal
Inv Inverted
0.20 0-20mA output
4.20 4-20mA output
0 - 3000 none Conf none Conf nor Conf
L3
Conf
HIGH RANGE
Note 1:-
DC output calibration is described in section 13.4.
36 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
8.3.1 Sense
For an alarm output set this parameter to ‘ Inv’ so that it de-energises to the alarm state.
If the module is an input (3216i channel 1 only),
‘normal’ means the function is activated when the input contact is closed, and ‘inverted’ means the function is activated when the input contact is open.
8.3.2 Source
The four parameters SOURCE A, SOURCE B, SOURCE
C, and SOURCE D appear when the output is configured as a digital output i.e. ‘-.FUNC’ = ‘ d.Out’ and provide the facility to connect up to four alarms to operate a single relay output. If any one of the events becomes true then the output relay will operate.
Each source
(SRC) may be chosen from:-
Alarm 1
Alarm 2
Alarm 3
Alarm 4
All alarms
Any new alarm
Power Fail
SRC.A
SRC.B
SRC.C
SRC.D
OR
8.3.3 Power Fail
Nor
SEnS
Inv
Output
An output, configured as a digital output, can be made to operate following a power fail. It can be acknowledged in the same manner as an alarm but no alarm message is given.
8.3.4 Example: To Configure OP-1 Relay to
Operate on Alarms 1 and 2:-
Do This Display Additional
Notes
1. From any display, press as many times as necessary to select
‘O p -1’
Scrolling display
‘o P -1 l is t’
2. Press
to scroll to ‘1. i d ’
3. Press
scroll to
‘1. F U N C ’
to
4. Press
V
or
W
to select
‘ d.out reLy
1. id d.out
1. fu n c
This is the identification of the hardware fitted and cannot be adjusted.
The output is configured as a digital output function.
Scrolling display
‘ i o 1 fu n c t i o n ’
5. Press
to scroll to ‘1. S R C . A ’
6. Press
V
or
W
to select the event which you want to operate the output
7. If a second event is required to operate the same output, press
to select ‘1. S R C . B ’
8. Press
V
or
W
to select the second event which you want to operate the output, eg
‘ AL.2’
9. Press
to scroll to ‘1. se n s’
10. Press
V
or
W
to select ‘ Inv’
The output will activate if either alarm 1 is triggered.
Note:-
1. indicates the alarm number,
Hi indicates the alarm type.
Scrolling display
‘o u t p u t 1 s o u rc e a ’
Scrolling display
‘o u t p u t 1 s o u rc e b ’
Note:- ‘
2’. indicates the alarm number,
AL is displayed if the alarm type is not configured.
Continue to select up to four events if required using
1.SR C . C and
1. S R C . D
‘Inverted’ means a relay output is energised for
0% PID demand
‘Normal’ means a relay output is energised for
100% PID demand
Scrolling display
‘ io 1 s e n s e ’
Part No HA029006 Issue 5.0 Sept-12 37
3200iSeries Indicators
8.4 Output Channel 3 (OP-3) – 32h8i, 32h8i/SG and 3204i Indicators
Output 3 is not available in 3216i. In 32h8i, 32h8i/SG and 3204i it is a 0-20mA dc output used for re-transmission of the PV and is available on terminals 3A and 3B. The way in which this output operates is determined by parameters in the OP- 3 List below:-
OUTPUT LIST 3 ‘op -3’
Name Scrolling
Display
Parameter Description Value
TYPE
Output channel 3 hardware type dC.Op
0-20mA output. See note 1
FUNCTION
Output channel 3 function none Disabled. If disabled no further parameters are shown pV Process variable re-transmission
The function may be turned off, otherwise set to
PV
RANGE transmission output range
0.10 0-10Vdc
0.5
Output
0-5Vdc
Output
2.10 2-10Vdc
Output
1.5 1-5Vdc
Output
0.20 2-20mA output
4.20 4-20mA output
OUTPUT 0- 99999 (9999 for 3204i)
LOW SCALE
Not available in 3204i
Default dC.Op
Access
Level
Read only
Conf
Conf
HIGH
SCALE
Note 1:-
DC output calibration is described in section 13.4.
8.4.1 Output Scaling
The output can be scaled so that the measuring device reads as required. For example, assume the following settings:-
Input mV
0 - 20
0 - 20
0 - 20
Display Reading
0 - 2000
0 - 2000
0 - 2000
0
0
0
3.LOW
2000
3000
1000
3.HIGH Output device reading mA
0 – 20
0 – 15
0 – 20 since the output saturates.
The device will also read
20mA for an input of
10mV and 10mA for an input of 5mV
Note: The above example is shown for output 3 which is only available in 32h8i, 32h8i/SG and 3204i indicators. For
3216i the outputs which can be configured as dc are 1 and 2.
38 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
8.5 AA Relay Channel (AA) (Output 4)
This is a changeover relay available in all indicators. Connections are made to terminals AA, AB, and AC. OP4 beacon is operated from the AA relay output channel. Output AA (4) has the same functionality as OP-1 – the parameters are repeated here for clarity.
OUTPUT AA LIST ‘a a ’
Name Scrolling
Display
FUNCTION
Parameter
Description
4 . T Y P E OUTPUT 4 TYPE Displays the type of output
The function may be turned off, otherwise set to d.out
4.SRC.B
SOURCE A
OUTPUT 4
SOURCE B
SOURCE C
SOURCE D
Selects the source of an event which will operate the output relay
The output status is the result of an OR of
Src A, Src B, Src C, and Src D
Up to four events can, therefore, operate the output
See section 8.3.2.
SENSE
To configure the sense of the output channel.
See also section 8.3.1
Value reLy Relay output none Disabled. If disabled no further parameters are shown d.out
Digital output none No event connected to the output
1.--Alarm 1 The --- indicates the
2.--Alarm 2 alarm type. If the
3.--Alarm 3 alarm is not
4.--Alarm4 configured
AL.(Alarm no) is shown
ALL.A
All alarms nw.AL
Any new alarm sbr
Sensor break alarm
Pwr.f
Power fail
See also section 8.3.3.
O.rng
Output relay operates if the indicator input is over range paL.1
Pre alarm 1 paL.2
Pre alarm 2 paL.3
Pre alarm 3 paL.4
Pre alarm 4 nor Normal
Inv Inverted
Defaul t
Access
Level reLy Read only
Conf none Conf nor Conf
Part No HA029006 Issue 5.0 Sept-12 39
3200iSeries Indicators
9. Digital Input
Availability 32h8i
Digital Input A
32h8i/SG 3204i 3216i
Always Never Always Optional
Digital Input B Always Always Always Never
9.1 Digital Input Parameters
The input is typically from a voltage free contact, which can be configured to operate a number of functions as determined by parameters in the LA and LB Lists:-
LOGIC INPUT LIST ‘ la ’ / ‘LB ’
Name Scrolling
Display
Parameter Description
TYPE
INPUT To configure the function
FUNCTION of the digital input
L.IP
Value
Logic input
Default Access
Level
As order code
Conf
Read only
Ac.AL
Conf
SENSE
INPUT To configure the polarity of the input channel none Input not used
Ac.AL
Alarm acknowledge gage Strain gauge (32h8i only) tare Tare (linear inputs only) aL.in
Alarm inhibit. See note 1 p.rst
Peak value reset free Freezes the current displayed value
Loc.b
Keylock rec Recipe select
UP Remote key ‘Up’ dwn Remote key ‘Down’ nor Normal
Inv Inverted nor Conf
Note1:-
This input may be used, for example, in part of an automated process where it is required to prevent alarms from being displayed during a particular part of the process. It should be used with care – blocking alarms or delayed alarms may be an alternative.
40 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
10. Alarms
Alarms are used to alert an operator when a pre-set level has been exceeded. They are indicated by a scrolling message on the display and the red ALM beacon. They may also switch an output – usually a relay (see section
8.3.2) to allow external devices to be operated when an alarm occurs.
10.1 Types of Alarm
Up to six different alarms are available:-
1. Alarm 1
2. Alarm 2
3. Alarm 3
4. Alarm 4
Configurable as any of:-
Rising Rate of Change r.roc - the alarm is triggered if the rate of increase in PV exceeds the set level
Falling Rate of Change F.roc. - the alarm is triggered if the rate of decrease in PV exceeds the set level
The alarm is triggered if the sensor is open circuit 5. Sensor
Fault Alarm
6. Power Fail An alarm is indicated after a power cycle. It is acknowledged and cancelled using ‘Ack’ buttons.
This may be useful to indicate that a power failure has occurred and the peak values will only apply since return of the power.
Hysteresis
Latching Alarm is used to hold the alarm condition once an alarm has been detected. It may be configured as:- none Non latching A non latching alarm will reset itself when the alarm condition is removed
Auto Automatic An auto latching alarm requires acknowledgement before it is reset. The acknowledgement can occur BEFORE the condition causing the alarm is removed.
Man Manual The alarm continues to be active until both the alarm condition is removed AND the alarm is acknowledged. The acknowledgement can only occur AFTER the condition causing the alarm is removed.
Evt Event ALM beacon does not light but an output associated with this parameter will activate. A scrolling message may be configured using iTools, as described in section 14.5.3. If a message has been configured it will scroll across the display while the event is true. An ‘Event’ is not acknowledged.
Blocking
Alarms
Rising rate of change
(units/minute) is the difference between the point at which the alarm switches ‘ON’ and the point at which it switches ‘OFF’. It is used to provide a definite indication of the alarm condition and to prevent alarm relay chatter.
The alarm may be masked during start up of a process. Blocking prevents the alarm from being activated until the process has first achieved a safe state. It is used to ignore start up conditions which are not representative of running conditions.
A blocking alarm is re-initiated after a setpoint change.
See section 10.1 for an explanation of the behaviour of blocking alarms under different conditions.
An alarm will be detected if the rate of
PV
Rate of change
> set rate
Hysteresis Positive rate of change in set in engineering units per minute change in a positive direction exceeds the
Rate of change
< set rate alarm threshold
Alarm ON Alarm OFF
Time
PV
Falling rate of change
(units/minute)
An alarm will be detected if the rate of change in a negative direction exceeds the alarm threshold
Rate of change
> set rate
Hysteresis
Rate of change
< set rate
Negative rate of change in set in engineering units per minute
Alarm ON Alarm OFF
Tim
Part No HA029006 Issue 5.0 Sept-12 41
10.1.1 Alarm Relay Output
Alarms can operate relay outputs 1, 2 or 4. Any individual alarm can operate an individual output or any combination of alarms, up to four, can operate an individual output. They are either supplied preconfigured in accordance with the ordering code or set up in the Quick Codes or in configuration level .
Section 8.3.2. describes how to configure the alarm outputs using the ‘SOURCE’ parameters.
10.1.2 Alarm Indication
•
ALM beacon flashing red = a new alarm
(unacknowledged)
•
This is accompanied by a scrolling alarm message. A typical default message will show the source of the alarm followed by the type of alarm. For example, ‘ALARM 1 HIGH’
•
Using Eurotherm iTools configuration package, it is also possible to download customised alarm messages. An example might be, ‘PROCESS
TOO HOT’.
•
If more than one alarm is present further messages are flashed in turn in the main display.
The alarm indication will continue while the alarm condition is present and is not acknowledged.
•
ALM beacon on continuously = alarm has been acknowledged.
10.1.3 To Acknowledge An Alarm
Press
and
W
‘Ack’ together.
The action, which now takes place, will depend on the type of latching, which has been configured
Non-Latched Alarms
Alarm condition present when the alarm is acknowledged.
•
ALM beacon on continuously.
•
The alarm message(s) will continue to scroll
This state will continue for as long as the alarm condition remains. When the alarm condition disappears all indication also disappears.
If a relay has been attached to the alarm output, it will de-energise when the alarm condition occurs and remain in this condition until acknowledged or the alarm is no longer present.
If the alarm condition disappears before it is acknowledged the alarm resets immediately.
Latched Alarms
See description in section 10.1.
3200iSeries Indicators
Power Fail Alarm
Alarm condition is indicated when the indicator is switched on.
It is reset using ‘Ack’ buttons
10.1.4 Pre-Alarms
A pre-alarm can be attached to High and Low alarms.
A pre alarm is activated when the PV exceeds a level set as an offset from the ALARM SETPOINT. In this way it always activates a set number of units before the ALARM SETPOINT is reached. It is used to activate a relay, see sections 8.3.2 and 10.1.1.
For example, assume a high alarm setpoint is 400 and the pre-alarm setpoint is 100 then the pre-alarm will activate when the PV = 300.
PV
HIGH ALARM SETPOINT 400 q
PRE ALARM OFFSET 100 r
Pre-Alarm output
Alarm output
For a low alarm set to the same values the pre-alarm will activate at 500.
PV q
PRE ALARM OFFSET 100 r
LOW ALARM SETPOINT
400
Pre-Alarm output
Alarm output
No message is indicated on the instrument display nor is the ALM beacon activated when a pre-alarm occurs.
However, a digital output (eg relay), attached to the alarm, is activated and the relevant OP beacon will illuminate.
42 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
10.2 Behaviour of Alarms After a Power
Cycle
The response of an alarm after a power cycle depends upon the latching type, whether it has been configured to be a blocking alarm, it's state and the acknowledge status of the alarm.
Alarm
ON
Alarm
OFF
Alarm
SP
PV
Power on
The response of active alarms after a power cycle is as follows:
For a non-latching alarm or an event alarm blocking will be re-instated, if configured. If blocking is not configured the active alarm will remain active. If the alarm condition has gone safe during the down time the alarm will return inactive.
For an auto-latching alarm blocking will be reinstated, if configured, only if the alarm had been acknowledged prior to the power cycle. If blocking is not configured or the alarm had not been acknowledged the active alarm will remain active. If the alarm condition has gone safe during the downtime the alarm will return inactive if it had been acknowledged prior to the power cycle else it will return safe but not acknowledged. If the alarm was safe but not acknowledged prior to the power cycle the alarm will return safe but not acknowledged.
For a manual-latching alarm blocking will not be reinstated and the active alarm will remain active. If the alarm condition has gone safe during the downtime the alarm will return safe but not acknowledged. If the alarm was safe but not acknowledged prior to the power cycle the alarm will return safe but not acknowledged.
The following examples show graphically the behaviour under different conditions:-
10.2.1 Example 1
Alarm configured as Absolute Low; Blocking: No
Latching
Powe r ff/
Powe r ff/
Alar m SP
Alarm
ON
Alarm
OFF
10.2.2 Example 2
Alarm configured as Absolute Low; Blocking: Manual
Latching
PV
Alarm
SP
Power on
Power off/on
Power off/on
Ack
PV
Alarm
ON
Alarm
OFF
Note: The alarm will only cancel when the alarm condition is no longer current AND then it is acknowledged
10.2.3 Example 3
Alarm configured as Absolute Low; Blocking: Auto
Latching
Power on
Power off/on
Power off/on
Ack
1
Ack 2 Ack
3
Ack 4
Ack 2 - alarm output remains in alarm condition but
ALM indication goes steady
Ack 3 - alarm output remains active until the condition causing the alarm disappears
Alarm
ON
Alarm
OFF
Ack 4 - alarm output remains active until acknowledged
Part No HA029006 Issue 5.0 Sept-12 43
3200iSeries Indicators
10.3 Alarm Parameters
Four alarms are available. Parameters do not appear if the Alarm Type = None. The following table shows the parameters to set up and configure alarms.
ALARM LIST
Name
‘ALARM ’
Scrolling Display Parameter Description Value Default Access
Level
As order code
Conf A1.TYP ALARM 1 TYPE Selects the type of alarm none Alarm not configured
Hi
Lo
Full Scale High
Full Scale Low r.roc
Rising rate of change
F.roc
Falling rate of change
A1.--- ALARM 1
SETPOINT
Alarm 1 threshold value.
The last three characters show the type of alarm configured from the above list
Indicates the status of the alarm
Instrument range
OUTPUT
OFF Alarm off
On Alarm on
0 to 9999
HYSTERESIS
See description at the beginning of this section
See description at the beginning of this section
A1.DLY
LATCHING TYPE
BLOCKING
DELAY TIME
See description at the beginning of this section
The alarm will not be indicated until the set time has elapsed
Auto Latching with automatic resetting
Man Latching with manual resetting
Evt Event (no alarm flashing beacon but messages can be displayed)
No No blocking yes Blocking
0:00 to 99:59 mm:ss
0:59 = 59 seconds
99:59 = 99 minutes 59 seconds
Instrument range A1.OFS ALARM
SETPOINT
OFFSET
OFFSET
Applies a fixed offset to a full scale high or full scale low alarm setpoint. This may be useful when used in conjunction with digital communications, where a variable value may be downloaded during different parts of a process.
Pre alarm setpoint set as a deviation from the ALARM
SETPOINT.
Only shown if the alarm is high or low.
See section 10.1.4.
Instrument range
The above parameters are repeated for Alarm 2, A2; Alarm 3, A3; Alarm 4, A4
0 code
No
0:00
0
0
L3
Read only
Conf
Conf
L3
L3
44 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
10.3.1 Example: To Configure Alarm 1
Enter configuration level as described. Then:-
Do This The Display You
Should See
1. Press as many times as necessary to select ‘ALARM ’
2. Press
to select ‘A1.TYP’
3. Press
V
or
W
to select the required alarm type
Hi a 1. typ
4. Press
to select ‘A1. - - - ‘
5. Press
V trip level
or
W
to set the alarm
215 a 1. h i
6. Press
to select ‘A1 STS’
Additional Notes
Alarm Type choices are:- none Alarm not configured
Hi Full Scale High
Lo Full Scale Low r.roc Rate of change rising
F.roc Rate of change falling
This is the alarm threshold setting for Alarm 1.
Characters (- - - ) shown after the alarm number indicate the type of alarm configured from the above list.
The alarm threshold is shown in the upper display.
In this example the high alarm will be detected when the measured value exceeds 215
This is a read only parameter which shows the status of the alarm output
7. Press
to select ‘A1 HYS’
8. Press
V hysteresis
or
W
to set the
In this example the alarm will cancel when the measured value decreases 2 units below the trip level (e.g. at 213 units in this example)
9. Press
to select ‘A1 LAT’
10. Press
V
or latching type
W
to select the
Latching Type choices are:- none No latching
Auto Automatic
Man Manual
Evt Event
See section 10.1 for an explanation of latching alarms
11. Press
to select ‘A1 BLK’
12. Press
V
or
W
to ‘
Yes’ or ‘No’
13. Repeat the above to configure alarms 2, 3 and 4 if required
14. Continue to press
to set up a delay before the alarm is indicated and to set a pre alarm level
Part No HA029006 Issue 5.0 Sept-12 45
3200iSeries Indicators
10.4 Diagnostic Alarms
Diagnostic alarms indicate a possible fault within the indicator or connected devices.
Display shows
E.Conf
E.CaL
E2.Er
EE.Er
E.Lin
What it means
A change made to a parameter takes a finite time to be entered. If the power to the indicator is turned off before the change has been entered then this alarm will occur.
Do not turn the power off to the indicator while
ConF is flashing
Calibration error
EEPROM error
Non-vol memory error
Invalid input type. This refers to custom linearisation which may not have been applied correctly or may have been corrupted.
What to do about it
Enter configuration mode then return to the required operating mode. It may be necessary to re-enter the parameter change since it will not have been entered in the previous configuration.
Re-instate Factory calibration
Return to factory for repair
Note the error and contact your supplier
Go to the INPUT list in configuration level and set a valid thermocouple or input type
46 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
11. Recipe
A recipe can take a snapshot of the current values and store these into a recipe number.
There are five recipes available, which can store a range of parameter values for different processes.
Each recipe can be given a name using iTools configuration software.
11.1 To Save Values in a Recipe
Do This
1. Press as many times as necessary to select ‘r e c i p ’
2. Press
to scroll to ‘S T O R E ’
V
or
W
3. Press to choose the recipe number to store eg
1
The Display You Should See
1 s to re done s to re
Additional Notes
Scrolling display R E C IP E L IS T
Scrolling display R E C I P E T O S A V E
The current parameter values are stored in Recipe 1
11.2 To Save Values in a Second Recipe
In this example the alarm 1 high setpoint will be changed and stored in recipe 2. All other values will remain the same as recipe 1:-
Do This
1. Press to scroll to ‘a la rm ’
The Display You Should See Scrolling display Additional Notes
Scrolling display a la rm lis t
Scrolling display a la rm 1 s e tp o in t
2. Press
to scroll to a 1. h i
3. Press
V
or value eg
22
W
to change the
4. Press to scroll to ‘ re c ip
5. Press to ‘s to re
6. Press
V
or
W
to
2 s to re
2 done s to re
Scrolling display R E C I P E L I S T
Scrolling display R E C IP E T O S A V E
Part No HA029006 Issue 5.0 Sept-12 47
3200iSeries Indicators
11.3 To Select a Recipe to Run
Do This
1. Press as many times as necessary to select ‘r e c i p ’
2. Press
to select ‘re c . n o ’
The Display You Should See
1
R e c . n o
Additional Notes
Scrolling display R E C IP E L IS T
Scrolling display C U R R E N T R E C IP E
N U M B E R
The values stored in Recipe 1 will now be loaded.
If a recipe number is chosen which has not been saved then
FAIL will be displayed
V
3. Press number
1
or
W
to choose recipe
48 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
12. Digital Communications
Digital Communications (or ‘comms’ for short) allows the indicator to communicate with a PC or a networked computer system.
This product conforms to MODBUS RTU ® protocol a full description of which can be found on www.modbus.org.
Two ports are available both using MODBUS RTU communication facilities:
1. a configuration port - intended to communicate with a system to download the instrument parameters and to perform manufacturing tests and calibration
2. an optional EIA232 or EIA 485 port on terminals
HD, HE and HF - intended for field communications using, for example, a PC running a SCADA package.
The two interfaces cannot operate at the same time.
For a full description of digital communications protocols (ModBus RTU) refer to the 2000 series
Communications Handbook, part number
HA026230, available on www.eurotherm.co.uk
.
Each parameter has its own unique ModBus address.
A list of these is given at the end of this section.
12.1 Digital Communications Wiring
12.1.1 EIA 232
To use EIA 232 the PC will be equipped with an EIA
232 port, usually referred to as COM 1.
To construct a cable for EIA 232 operation use a three core screened cable.
The terminals used for EIA 232 digital communications are listed in the table below. Some
PC's use a 25 way connector although the 9 way is more common.
Standard
Cable
Colour
PC socket pin no.
9 way 25 way
PC Function * Instrument
Terminal
Instrument
Function
White 2 3 Receive, Transmit,
TX
Receive,
RX
Red 5 7 Common HD Common
Link together
1
4
6
6
8
11
Rec'd line sig. detect Data terminal ready
Data set ready
Link together
7
8
4
5
Request to send
Clear to send
Screen 1 Ground
•
These are the functions normally assigned to socket pins. Please check your PC manual to confirm.
12.1.2 EIA 485
To use EIA 485, buffer the EIA 232 port of the PC with a suitable EIA 232/RS485 converter. The Eurotherm
Controls KD485 Communications Adapter unit is recommended for this purpose. The use of a EIA 485 board built into the computer is not recommended since this board may not be isolated, which may cause noise problems, and the RX terminals may not be biased correctly for this application.
To construct a cable for EIA 485 operation use a screened cable with one (EIA 485) twisted pair plus a separate core for common. Although common or screen connections are not necessary, their use will significantly improve noise immunity.
The terminals used for EIA 485 digital communications are listed in the table below.
Standard
Cable Colour
PC Function
*
RX+
Instrument
Terminal
Instrument
Function
Transmit, TX
(B+)
Receive, RX
TX+ (A+)
Screen Ground
•
These are the functions normally assigned to socket pins. Please check your PC manual to confirm .
See section 2.9 for wiring diagrams.
Part No HA029006 Issue 5.0 Sept-12 49
12.2 Digital Communications Parameters
The following table shows the parameters available.
DIGITAL COMMUNICATIONS LIST ‘comm s’
Name Scrolling
Display
PARAMETER
Parameter
Description communications broadcast parameter.
See section 12.2.2.
Value
I D MODULE
IDENTITY
Comms identity none No module fitted r232 EIA 232 Modbus interface r485 EIA 485 Modbus interface
1 to 254 A D D R ADDRESS Communications address of the instrument baud rate
1200 1200
2400 2400
4800 4800
9600 9600
P R T Y PARITY Communications parity
19.20
19,200 none No parity
Even Even parity
Odd Odd parity
Off No delay
TIME
DELAY To insert a delay between Rx and Tx to ensure that drivers have sufficient time to switch over.
On Fixed delay applied none None
PV Process Variable
0 to 9999
R E G . A D DESTINATION Parameter added in
ADDRESS the Slave address to which the master communications value will be written
See section 12.2.1.
3200iSeries Indicators
Default
As order code
Access
Level
Conf
L3 R/O
1
9600
L3
Conf
L3 R/O none Conf
L3 R/O
Conf
L3 R/O none
0
50 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
12.2.1 Broadcast Communications
Broadcast master communications, as a simple master, allows the 3200i indicator to send a single value to any number of slave instruments. Modbus broadcast using function code 6 (Write single value) must be used. This allows the 3200i to link with other products, without the need for a supervisory PC, to create a small system solution. The facility provides a simple and precise alternative to analogue retransmission.
The retransmitted parameter is Process Variable. The indicator will cease broadcast when it receives a valid request from a Modbus master - this allows iTools to be connected for commissioning purposes.
!
Warning
When using broadcast master communications, bear in mind that updated values are sent many times a second. Before using this facility, check that the instrument to which you wish to send values can accept continuous writes. Note that in common with many third party lower cost units, the Eurotherm
2200 series and the 3200 series prior to version
V1.10 do not accept continuous writes to the temperature setpoint. Damage to the internal nonvolatile memory could result from the use of this function. If in any doubt, contact the manufacturer of the device in question for advice.
When using the 3200 series controllers fitted with software version 1.10 and greater, use the Remote
Setpoint variable at Modbus address 26 if you need to write to a temperature setpoint. This has no write restrictions and may also have a local trim value applied. There is no restriction on writing to the 2400 or 3500 series.
12.2.2 Broadcast Master Communications
The 3200 broadcast master can be connected to up to
31 slaves if no segment repeaters are used. If repeaters are used to provide additional segments, 32 slaves are permitted in each new segment. The master is configured by setting the ‘RETRAN’ parameter to PV.
Once the function has been enabled, the instrument will send this value out over the communications link every control cycle (250ms).
Notes:-
1. The parameter being broadcast must be set to the same decimal point resolution in both master and slave instruments.
2. If iTools, or any other Modbus master, is connected to the port on which the broadcast master is enabled, then the broadcast is temporarily inhibited. It will restart approximately
30 seconds after iTools is removed. This is to allow reconfiguration of the instrument using iTools even when broadcast master communications is operating.
Slave 1 Slave 2
3200i
Master
Slave
31
12.2.3 Wiring Connections
The Digital Communications module for use as a master or slave uses terminals HD to HF.
EIA232 Connections
Rx connections in the master are wired to Tx connections of the slave
Tx connections in the master are wired to Rx connections of the slave
Rx A(+)
Rx A(+)
3200i
Master
EIA232 Tx B(-) Tx B(-)
Slave 1
EIA232
Com Com
EIA485 2-wire Connections
Connect A (+) in the master to A (+) of the slave
Connect B (-) in the master to B (-) of the slave
This is shown diagrammatically below
A (+)
A (+)
3200i
Master
EIA485 B (-) B (-)
Slave 1
EIA485
Com Com
Part No HA029006 Issue 5.0 Sept-12 51
12.3 Example: To Set Up Instrument
Address
This can be done in operator level 3:-
Do This Display View Additional Notes
Scrolling display
‘c om m s lis t’
1. Press as many times as necessary to select
‘COMMS LIST’
2. Press
to scroll to ‘ ID
Scrolling display
‘ id ’
3. Press
V
or
W
to select
EIA 232 or
EIA 485 comms
4. Press
to scroll to ‘ADDR ’
5. Press
V
or
W
to select the address for the particular indicator
Up to 254 can be chosen but note that no more than
33 instruments should be connected to a single EIA 485 link.
Scrolling display
‘a d d re s s ’
For further information see 2000 Series
Communications Handbook Part No. HA026230 which can be downloaded from www.eurotherm.co.uk
.
3200iSeries Indicators
12.4 DATA ENCODING
☺
Note that the Eurotherm iTools OPC server provides a straightforward means of accessing any variable in the 3200 indicator in the correct data format without the need to consider data representation. However, if you wish to write your own communications interface software, you will need to take the format used by the 3200 comms software into account.
Modbus data is normally encoded into a 16 bit signed integer representation.
Integer format data, including any value without a decimal point or represented by a textual value (for example ‘off’, or ‘on’), is sent as a simple integer value.
For floating point data, the value is represented as a
‘scaled integer’, in which the value is sent as an integer which gives the result of the value multiplied by 10 to the power of the decimal resolution for that value.
This is easiest to understand by reference to examples:
FP Value
FP Value Integer Representation
Integer Representation
9. 9
-1.0 10
123.5 1235
9.99 999
It may be necessary for the Modbus master to insert or remove a decimal point when using these values.
It is possible to read floating point data in a native 32 bit IEEE format. This is described in the Eurotherm
Series 2000 Communications Handbook (HA026230),
Chapter 7.
52 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
12.5 Parameter Modbus Addresses
Parameter
Mnemonic
Parameter Name
PV.IN PV (Temperature) Input Value (see also Modbus address 203 which allows writes over Modbus to this variable).
RNG.LO Input Range Low Limit
RNG.HI Input Range High Limit
Modbus
Address
(Decimal)
1
11
12
LOC.t
13
14
26
27 Local Trim – added to the remote setpoint to compensate for local temperature variations in a control zone.
47
66
67
68
69
StAt Instrument Status. This is a bitmap:
B0 – Alarm 1 Status
B1 – Alarm 2 Status
B2 – Alarm 3 Status
B3 – Alarm 4 Status
B5 – Sensor Break Status
B10 – PV Overrange (by > 5% of span)
B12 – New Alarm Status
In each case, a setting of 1 signifies
‘Active’, 0 signifies ‘Inactive’.
71
75
81
82
Di.IP
Home
-
Digital Inputs Status. This is a bitmap:
B0 – Logic input 1A
B1 – Logic input LA
B2 – Logic input LB
B7 – Power has failed since last alarm acknowledge
A value of 1 signifies the input is closed, otherwise it is zero. Values are undefined if options are not fitted or not configured as inputs.
87
101
Home Display.
0 – Standard PV display
4 – PV and Alarm 1 setpoint
6 – PV only
7 – PV and Alarm 1 setpoint read only
Instrument version number. Should be read as a hexadecimal number, for example a value of 0111 hex is instrument V1.11
106
107
108
- Instrument 122
126
127
ADDR Instrument Comms Address 131
141
146
199
0 – Operating mode - all algorithms and I/O are active
1 – Standby - control outputs are off
2 – Config Mode - all outputs are inactive
200
MV.IN
Green –
Red –
Green normal/Red on alarm –
Input value in millivolts 202
PV.CM Comms PV Value. This may be used to write to the Process
Variable (temperature) parameter over Modbus when a linearisation type of ‘Comms’ is selected, allowing the instrument to control to externally derived values.
If sensor break is turned on, it is necessary to write to this variable once every 5 seconds. Otherwise a sensor break alarm will be triggered as a failsafe. If this is not required, turn sensor break off.
203
204
215
223
Off –
On –
Fail -
SBR Sensor Break Status (0 = Off, 1 =
Active)
NEW.AL New Alarm Status (0 = Off, 1 =
Active)
Ac.All
A1.STS
A2.STS
A3.STS
A4.STS
258
260
261
Acknowledge all alarms (1 =
Acknowledge
274
Alarm 1 Status (0 = Off, 1 = Active) 294
Alarm 2 Status (0 = Off, 1 = Active)
Alarm 3 Status (0 = Off, 1 = Active) 296
Alarm 4 Status (0 = Off, 1 = Active)
295
297
298
REC.NO
Lev2.P
UNITS
Lev3.P
Recipe to Recall
Level 2 Code
Display Units
0 – Degrees C
1 – Degrees F
2 – Kelvin
3 – None
4 – Percent
Level 3 Code
299
300
301
313
314
515
516
Cold
517
518
519 If set to 1 instrument will reset to factory defaults on next reset or power cycle.
525
Part No HA029006 Issue 5.0 Sept-12 53
3200iSeries Indicators
0 – XXXX.
1 – XXX.X
2 – XX.XX
530
0 – Absolute Alarm Outputs Active
– others off
1 – All outputs inactive
A1.TYP
A2.TYP
A3.TYP
A4.TYP
A1.LAT
Alarm 1 Type
0 – Off
1 –Absolute High
2 – Absolute Low
3 – Deviation High
4 – Deviation Low
5 – Deviation Band
Alarm 2 Type
(as Alarm 1 Type)
Alarm 3 Type
(as Alarm 1 Type)
Alarm 4 Type
(as Alarm 1 Type)
Alarm 1 Latching Mode
0 – No latching
1 – Latch - Automatic Reset
2 – Latch – Manual Reset
A2.LAT
A3.LAT
Alarm 2 Latching Mode
(as Alarm 1 Latching Mode)
Alarm 3 Latching Mode
(as Alarm 1 Latching Mode)
A4.LAT Alarm 4 Latching Mode
(as Alarm 1 Latching Mode)
A1.BLK Alarm Blocking Mode Enable (0 =
OFF, 1 = BLOCK)
A2.BLK Alarm Blocking Mode Enable (0 =
OFF, 1 = BLOCK)
A3.BLK Alarm Blocking Mode Enable (0 =
OFF, 1 = BLOCK)
A4.BLK Alarm Blocking Mode Enable (0 =
OFF, 1 = BLOCK)
Di.OP Digital Outputs Status. This is a bitmap:
B0 – Output 1A
B1 – Output 2A
B2 – (not used)
B3 – Output 4/AA
It is possible to write to this status word to use the digital outputs in a telemetry output mode. Only outputs whose function is set to
‘none’ are affected, and the setting of any bits in the Digital Output
Status word will not affect outputs used for heat (for example) or other functions. Thus it is not necessary to mask in the settings of these bits when writing to this variable.
Alarm 1 delay
Alarm 2 delay
Alarm 3 delay
Alarm 4 delay
OFS.HI Adjust High Offset
533
541
542
543
544
537
538
539
536
540
545
546
547
551
552
553
554
555
556
557
558
559
560
OFS.LO Adjust Low Offset
PNT.HI Adjust High Point
PNT.LO Adjust Low Point
SB.TYP
SB.DIR
Sensor Break Type
0 – No Sensor Break
1 – Non-Latching Sensor Break
2 – Latching Sensor Break
Sensor break direction
Up –
Down –
Id Customer ID – May be set to any value between 0-9999 for identification of instruments in applications. Not used by the instrument itself.
P1.OFS Pre alarm offset 1
P2.OFS Pre alarm offset 2
P3.OFS Pre alarm offset 3
P4.OFS Pre alarm offset 4
561
562
563
578
579
629
640
641
642
643
P1.STS
P2.STS
Pre alarm 1 output status
Pre alarm 2 output status
644
645
P3.STS
HI.CAL
Pre alarm 3 output status
Strain gauge high cal
646
P4.STS Pre alarm 4 output status 647
PHASE
GO
Calibration Phase
0 – None
1 – 0 mv
2 – 50 mv
3 – 150 Ohm
4 – 400 Ohm
5 – CJC
6 – CT 0 mA
7 – CT 70 mA
8 – Factory Defaults
9 – Output 1 mA low cal
10 – Output 1 mA high cal
11 – Output 2 mA low cal
12 – Output 2 mA high cal
13 – Output 3 ma low cal
(3208/3204 only)
14 – Output 3 ma high cal
(3208/3204 only)
Calibration Start
0 – No
1 – Yes (start cal)
2 – Cal Busy
3 – Cal Pass
4 – Cal Fail
Note values 2-4 cannot be written but are status returns only
- Analogue Output Calibration
Value
SG.TYP Strain gauge cal type
Shunt
Comparison
Cell
769
775
780
768
781
LO.CAL Strain gauge low cal 782
783
784
No - 1
Yes - 2
785
54 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
IN.TYP
K.LOC
CJ.TYP
Allows instrument to be locked via a key/digital input
0 - unlocked,
1 – all keys locked
2 – Edit keys (raise and lower) disabled
3 – Mode key disabled
4 – Manual mode disabled
5 – Enter standby mode when
Mode combination pressed
6 – Timer keys disabled
Input Sensor Type
0 – J Type Thermocouple
1 – K Type Thermocouple
2 – L Type Thermocouple
3 – R Type Thermocouple
4 – B Type Thermocouple
5 – N Type Thermocouple
6 – T Type Thermocouple
7 – S Type Thermocouple
8 – RTD
9 – millivolt
10 – Comms Input (see Modbus address 203)
11 – Custom Input (Downloadable)
CJC Type
0 – Auto
1 – 0 Degrees C
2- 50 Degrees C
Linear Input High
Linear Input Low mV.HI mV.LO
L.D.IN
(LB)
L.SENS
(LB)
L.TYPE
L.D.IN
Logic Input A channel hardware type
0 – None
1 – Logic Inputs
Logic input A function
40 – None
41 – Acknowledge all alarms
42 – Select SP1/2
43 – Lock All Keys
44 – Timer Reset
45 – Timer Run
46 – Timer Run/Reset
47 – Timer Hold
48 – Auto/Manual Select
49 – Standby Select
L.SENS Configures the polarity of the logic input channel A (0 = Normal, 1 =
Inverted)
L.TYPE
(LB)
Logic Input B channel hardware type (3208/3204 only)
0 – None
1 – Logic Inputs
Logic input B function (3208/3204 only)
40 – None
41 – Acknowledge all alarms
42 – Select SP1/2
43 – Lock All Keys
44 – Timer Reset
45 – Timer Run
46 – Timer Run/Reset
47 – Timer Hold
48 – Auto/Manual Select
49 – Standby Select
Configures the polarity of the logic input channel B (0 = Normal, 1 =
Inverted) (3208/4 only)
1104
12290
12291
12306
12307
12352
12353
12361
12362
12363
12377
ID
BAUD
PRTY
DELAY
RETRN
Comms Module Type
0 – None
1 – RS485
2 – RS232
Baud Rate
0 – 9600
1 – 19200
2 – 4800
3 – 2400
4 – 1200
12544
Parity setting
0 – None
1 – Even
2 – Odd
RX/TX Delay – (0 = no delay, 1 = delay) Select if a delay is required between received and transmitted comms messages. Sometimes required when intelligent RS485 adaptors are used.
12550
Comms Retransmission Variable selection:
0 – Off
1 – Working Setpoint
2 – PV
3 – Output Power
4 – Error
12551
12548
12549
REG.AD Modbus register address to broadcast retransmission to. For example if you wish to retransmit the working setpoint from one
3200 to a group of slaves, and receive the master working setpoint into the slaves’ remote setpoint, set this variable to 26 (the address of the remote setpoint in the slave units).
Cal 3 offset
12552
12558
1.ID
1.D.IN
1.FUNC
1.RNG
Cal 4 offset
IO channel 1 hardware type
0 – None
1 – Relay
2 – Logic I/O
IO1 Digital input function
Logic input function
40 – None
41 – Acknowledge all alarms
42 – Select SP1/2
43 – Lock All Keys
I/O Channel Function
0 – None (or Telemetry Output)
1 – Digital Output
4 – Digital Input
10 – DC Output no function
14 – DC Output PV retransmission
IO Channel 1 DC Output Range
0 – 0-20mA
1 – 4-20mA
12559
12672
12673
12674
12675
1.SRC.A IO Channel 1 Source A
0 – None
1 – Alarm 1
2 – Alarm 2
3 – Alarm 3
4 – Alarm 4
5 – All Alarms (1-4)
6 – New Alarm
9 – Sensor Break Alarm
12676
12677
Part No HA029006 Issue 5.0 Sept-12 55
3200iSeries Indicators
2.ID
2.FUNC
2.RNG
1.SRC.B
1.SRC.C
IO Channel 1 Source B
As IO Channel 1 Source A
(Modbus address 12678)
IO Channel 1 Source C
As IO Channel 1 Source A
(Modbus address 12678)
1.SRC.D IO Channel 1 Source D
As IO Channel 1 Source A
(Modbus address 12678)
1.SENS Configures the polarity of the input or output channel (0 = Normal, 1 =
Inverted)
Output 2 Type
0 – None
1 – Relay
2 – Logic Output
Output 2 Channel function
0 – None (or Telemetry Output)
1 – Digital Output
10 – DC Output no function
14 – DC Output PV retransmission
IO Channel 2 DC Output Range
0 – 0-20mA
1 – 4-20mA
Output 2 low
12678 3.SENS Output 3 Polarity (0 = Normal, 1 =
Inverted)
Output 3 high
12810
12811
12736
12739
12740
12679
12680
12681
12682
12683
Output 3 telemetry 12812
4.TYPE
4.FUNC
Output AA Type
0 – None
1 – Relay
Output 4 Channel function
0 – None (or Telemetry Output)
1 – Digital Output
4.SRC.A
4.SRC.B
Output AA source A
As IO Channel 1 Source A
(Modbus address 12678)
Output AA source B
As IO Channel 1 Source A
(Modbus address 12678)
4.SRC.C
4.SRC.D
Output AA source C
As IO Channel 1 Source A
(Modbus address 12678)
Output AA source D
As IO Channel 1 Source A
(Modbus address 12678)
4.SENS Output AA sense (0 = Normal, 1 =
Inverted)
13056
13059
13062
13063
13064
13065
13066
15885
12741
2.SRC.A Output 2 source A
As IO Channel 1 Source A
(Modbus address 12678)
2.SRC.B Output 2 source B
As IO Channel 1 Source A
(Modbus address 12678)
2.SRC.C Output 2 source C
As IO Channel 1 Source A
(Modbus address 12678)
2.SRC.D Output 2 source D
As IO Channel 1 Source A
(Modbus address 12678)
12742
12743
12744
12745
12746 2.SENS Output 2 Polarity (0 = Normal, 1 =
Inverted)
Output 2 high 12747
12748
3.ID
3.FUNC
3.RNG
Output 3 Type
0 – None
1 – Relay
Output 3 Channel function
0 – None (or Telemetry Output)
1 – Digital Output
14 – DC Output PV retransmission
12800
12803
IO Channel 3 DC Output Range
0 – 0-20mA
1 – 4-20mA
Output 3 low
12804
12805
3.SRC.A
3.SRC.B
Output 3 source A
As IO Channel 1 Source A
(Modbus address 12678)
Output 3 source B
As IO Channel 1 Source A
(Modbus address 12678)
3.SRC.C Output 3 source C
As IO Channel 1 Source A
(Modbus address 12678)
3.SRC.D Output 3 source D
As IO Channel 1 Source A
(Modbus address 12678)
12806
12807
12808
12809
56 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
13. Calibration
All ranges are calibrated during manufacture to traceable standards for every input type. When changing ranges it is not necessary to calibrate the indicator. Furthermore, the use of a continuous automatic zero correction of the input ensures that the calibration of the instrument is optimised during normal operation.
To comply with statutory procedures such as the Heat
Treatment Specification AMS2750, the calibration of the instrument can be verified and re-calibrated if considered necessary in accordance with the instructions given in this chapter.
For example AMS2750 states:-
"Instructions for calibration and recalibration of ‘field test instrumentation’ and ‘control monitoring and recording instrumentation’ as defined by the NADCAP
Aerospace Material Specification for pyrometry
AMS2750D clause 3.2.5 (3.2.5.3 and sub clauses) including Instruction for the application and removal of offsets defined in clause 3.2.4”.
13.1 To Check Input Calibration
The PV Input may be configured as mV, mA, thermocouple or platinum resistance thermometer.
13.1.1 Precautions
Before checking or starting any calibration procedure the following precautions should be taken:-
1. When calibrating mV inputs make sure that the calibrating source output is set to less than 250mV before connecting it to the mV terminals. If accidentally a large potential is applied (even for less than 1 second), then at least one hour should elapse before commencing the calibration.
2. RTD and CJC calibration must not be carried out without prior mV calibration.
3. A pre-wired jig built using a spare instrument sleeve may help to speed up the calibration procedure especially if a number of instruments are to be calibrated.
4. Power should be turned on only after the instrument has been inserted in the sleeve of the pre-wired circuit. Power should also be turned off before removing the instrument from its sleeve.
5. Allow at least 10 minutes for the instrument to warm up after switch on.
13.1.2 To Check mV Input Calibration
The input may have been configured for a process input of mV, Volts or mA and scaled in Level 3 as described in section 7. The example described in section 7.1.4.1 assumes that the display is set up to read 2.0 for an input of 4.000mV and 500.0 for an input of 20.000mV.
To check this scaling, connect a milli-volt source, traceable to national standards, to terminals V+ and V- using copper cable as shown in the diagram below. mV
Source
Indicator VI
V+
V-
Copper cable
+
-
Ensure that no offsets (see sections 7.1.3 and 13.2) have been set in the indicator.
Set the mV source to 4.000mV. Check the display reads 2.0 +0.25% + 1LSD (least significant digit).
Set the mV source to 20.000mV. Check the display reads 500.0 +0.25% + 1LSD.
13.1.3 To Check Thermocouple Input Calibration
Connect a milli-volt source, traceable to national standards, to terminals V+ and V- as shown in the diagram below. The mV source must be capable of simulating the thermocouple cold junction temperature. It must be connected to the instrument using the correct type of thermocouple compensating cable for the thermocouple in use.
Indicator
VI
V+
V-
Thermocouple
Compensating cable
+
Thermocouple simulator set to
T/C type
-
Set the mV source to the same thermocouple type as that configured in the indicator.
Adjust the mV source to the minimum range. For a type J thermocouple, for example, the minimum range is -210
O
C. However, if it has been restricted using the Range Low parameter then set the mV source to this limit. Check that the reading on the display is within +0.25% of minimum range + 1LSD.
Adjust the mV source for to the maximum range. For a type J thermocouple, for example, the maximum range is 1200
O
C. However, if it has been restricted using the Range High parameter then set the mV source to this limit. Check that the reading on the display is within +0.25% of maximum range + 1LSD.
Intermediate points may be similarly checked if required.
Part No HA029006 Issue 5.0 Sept-12 57
13.1.4 To Check RTD Input Calibration
Connect a decade box with total resistance lower than
1K and resolution to two decimal places in place of the RTD as indicated on the connection diagram below before the instrument is powered up. If at any instant the instrument was powered up without this connection then at least 10 minutes must elapse from the time of restoring this connection before RTD calibration check can take place.
Indicator
VI
Matched impedance copper leads
Decade
Box
V+
V-
The RTD range of the instrument is -200 to 850
O
C. It is, however, unlikely that it will be necessary to check the instrument over this full range.
Set the resistance of the decade box to the minimum range. For example 0
O
C = 100.00
Ω. Check the calibration is within +0.25% of 0
O
+ 1LSD.
Set the resistance of the decade box to the maximum range. For example 200
O
C = 175.86
Ω. Check the calibration is within +0.25% of 200
O
+ 1LSD.
3200iSeries Indicators
13.2 Offsets
The process value can be offset to take into account known errors within the process. The offset can be applied to any Input Type (mV, V, mA, thermocouple or RTD).
A single offset can be applied - the procedure is carried out in the INPUT list and has been described in section 7.1.3.
It is also possible to adjust the low and high points as a five point offset. This can only be done in Level 3 in the ‘Cal ’ list and is described below.
13.2.1 Five Point Offset
A five point offset may be used to compensate for transducer or measurement non-linearities. The diagram shows an example of the type of discontinuity which might occur in a system.
Output
Hi
Cal Point 5
Cal Point 4
Cal Point 3
Output
Lo
Cal Point 1
Input Lo
Cal Point 2
Input Hi
In this case adjust each point in turn for the VALUE
WHICH THE INDICATOR SHOULD READ. For example if the value at point 1 should be 1.2345 then set Pnt.1 to this value. The following example shows how to do this.
Do This
1. Select Level 3 as described in Chapter 2.
Then press select ‘CAL’
to
Display View Notes
Scrolling message c a l i b r a t i o n l i s t
2. Press
to ‘u. ca l’
to scroll
3. Press to ‘ pnt.1’
V
or
W
Scrolling message u s e r c a l i b r a t i o n
To revert to the original values, select rSet
Note:- this is not an offset value
4. Press
to ‘C.Ad j’
to scroll
5. Press
V
or
W to the correct value
6. Repeat the above for points 1 to 5
In some cases it will not be necessary to adjust all 5 points. For example, a low and high adjustment may be all that is necessary as shown in the following diagrams.
58 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
Display
Reading
Display
Reading
High offset
(e.g. 6)
Low offset
(e.g. 1)
Factory calibration
Electrical
Input
Low offset
High offset
Factory calibration
Electrical
Input
In this case set Pnt.1 to the required low point value.
For the high point value you may select any point
Pnt.2 to Pnt.5. The instrument applies a straight line between the two points.
Note:-
The calibration points must be chosen consecutively – the five point calibration will not work if a higher point is inserted between other points.
13.3 Input Calibration
If the calibration is not within the specified accuracy follow the procedures in this section:-
In 3200 series instruments, inputs which can be calibrated are:-
• mV Input. This is a linear 80mV range calibrated at two fixed points. This should always be done before calibrating either thermocouple or resistance thermometer inputs. mA range calibration is included in the mV range.
• Thermocouple calibration involves calibrating the temperature offset of the CJC sensor only. Other aspects of thermocouple calibration are also included in mV calibration.
• Resistance Thermometer. This is also carried out at two fixed points - 150 Ω and 400Ω.
The precautions stated in section 13.1.1 should be observed.
Part No HA029006 Issue 5.0 Sept-12 59
13.3.1 To Calibrate mV Range
Calibration of the mV range is carried out using a 50 milli-volt source, connected as shown in the diagram below. mA calibration is included in this procedure.
Indicator VI
V+
Copper cable
+
50 mV
Source
V- -
For best results 0mV should be calibrated by disconnecting the copper wires from the mV source and short circuiting the input to the indicator
Select Conf Level as described in Chapter 2, s et the indicator input to mV range, then:-
Do This
1. From any display press as many times as necessary until the ‘CAL’ page header is displayed.
Display View Additional Notes
Scrolling display
‘ C A L IB R A T IO N
L IS T ’
2. Press
to select ‘P H A S E ’ none p h a s e
Scrolling display
‘ C A L IB R A T IO N p h a s e ’
3. Set mV source for 0mV
4. Press
V
or
W
to choose ‘
0’
5. Press select ‘G O ’
to
6. Press
V
or
W
to choose
‘
YES’
Scrolling display
‘ C A L IB R A T IO N s ta r t’
The indicator automatically calibrates to the injected input mV.
As it calibrates the display will show busy
then pass, assuming a successful calibration.
If it is not successful then ‘ FAIL ’ will be displayed. This may be due to incorrect input mV
7. Set mV source for 50mV
8. Press
to select ‘P H A S E ’
The indicator calibrates to the high point in the same way as the low point above
9. Press
V
or
W
to choose ‘
50’
10. Repeat 5 & 6 above
3200iSeries Indicators
13.3.2 To Calibrate Thermocouple Ranges
Thermocouples are calibrated, firstly, by following the previous procedure for the mV ranges, then calibrating the CJC.
This can be carried out using an external CJC reference source such as an ice bath or using a thermocouple mV source. Replace the copper cable shown in the diagram below with the appropriate compensating cable for the thermocouple in use.
VI
V+
Controller
Thermocouple
Compensating cable
Thermocouple simulator set to
T/C type and 0 o
C
+
V-
Set the mV source to internal compensation for the thermocouple in use and set the output for 0mV.
Then:-
Do This Display View Additional
Notes
1. From the mV calibration, press
V
or
W select ‘
CJC’
to
2. Press
select ‘GO ’
to
3. Press
V
or
W
to choose
‘
YES’
The indicator automatically calibrates to the CJC input at 0mV.
As it does this the display will show busy then pass , assuming a successful calibration.
If it is not successful then ‘ FAIL ’ will be displayed.
This may be due to an incorrect input mV
60 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
13.3.3 To Calibrate RTD Ranges
The two points at which the RTD range is calibrated are 150.00
Ω and 400.00Ω.
Before starting RTD calibration:
•
A decade box with total resistance lower than 1K must be connected in place of the RTD as indicated on the connection diagram below before the instrument is powered up. If at any instant the instrument was powered up without this connection then at least 10 minutes must elapse from the time of restoring this connection before RTD calibration can take place.
•
The instrument should be powered up for at least
10 minutes.
Before using or verifying RTD calibration:
•
The mV range must be calibrated first.
Controller
VI
V+
V-
Matched impedance copper leads
Decade Box
Do This
1. From any display press as many times as necessary until the ‘C A L ’ page header is displayed.
2. Press
‘P H A S E ’
to select
Display View Notes
Scrolling display
‘ C A L IB R A T
IO N L IS T ’
Scrolling display
‘ C A L IB R A T
IO N p h a s e ’
3. Set the decade box for 150.00
Ω
4. Press
V
or to choose ‘150 r’’
W
5. Press
‘GO ’
to select
V
6. Press or to choose ‘ YES’
W
Scrolling display
‘ C A L IB R A T
IO N s ta r t’
The indicator automatically calibrates to the injected
150.00
Ω input.
As it does this the display will show busy then pass , assuming a successful calibration.
If it is not successful then ‘ FAIL ’ will be displayed. This may be due to an incorrect input resistance
7. Set the decade box for 400.00
Ω
8. Press
V
or to choose ‘400 r’’
W
9. Repeat 5 and 6 above to calibrate the high point
The indicator will again automatically calibrates to the injected 400.00
Ω input.
If it is not successful then ‘ FAIL ’ will be displayed
Part No HA029006 Issue 5.0 Sept-12 61
13.4 Output Calibration
Output 3 (or outputs 1 or 2 in 3216i) may be configured to re-transmit the PV as an analogue, 0-
20mA, 4-20mA or 0-20V, 4-20V signal.
13.4.1 To Calibrate mA Outputs
Assume Output 3 (set to 0-20mA) is to be calibrated.
Connect an ammeter to terminals 3A/3B.
2.00
Digital ammeter
Controller
A +ve
B -ve
Errors in the reading on the ammeter can be calibrated out by selecting the appropriate calibration parameter. For example, if the ammeter reads an error at the zero end select the parameter 3.mA.L. The indicator then outputs 2.0mA. Then select ‘Value’ on the instrument display and adjust this until the error is corrected. Errors at the high end are corrected by the parameter 3.mA.H which outputs 18mA. This is illustrated by the procedure below
Select Configuration level. Then:-
Do This
1. From the ‘CAL’ list header press
to select ‘PHASE’
Display View Notes
3.ma.L phase
Scrolling message
‘calibrati on phase
V
2. Press or choose ‘
3.ma.L’
W
to
3. Press
‘v a lu e ’
to select
4. Press
V
or
W
to adjust this value so that it reads the same value as shown on the ammeter. For example if the meter reads
2.06 then set the controller reading for 206. The decimal point is not displayed on the controller so that 200 represents 2.00.
200 value
Scrolling message
‘ d c o u t p u t r e a d i n g
5. Press
‘PHASE’
to go back to
3.ma.H phase
Scrolling message
‘calibrati on phase
6. Press
V
or choose ‘ 3ma.H’
W
to
7. Press
‘v a lu e ’
to select
8. Press
V
or
W
to adjust this value so that it reads the same value as shown on the ammeter. The value represents 18.00mA
1800 value
Scrolling message
‘d c o u t p u t r e a d i n g
For voltage calibration repeat the above procedure using parameters
3.V.Lo and 3.V.Hi. The output calibration values are
1000 (1V) and 9000 (9V).
3200iSeries Indicators
13.4.2 To Return to Factory Calibration
Select Configuration level.
Then
Do This Display View Additional
Notes
1. From the ‘CAL’ list header press
‘PHASE’
to select
2. Press
V choose ‘ FAct’
or
W
to
3. Press
‘GO ’
to select
V
4. Press choose ‘ yes’
or
W
to
The indicator automatically returns to the factory values stored during manufacture
13.4.3 Transducer Calibration
Load cell, strain gauge or four wire bridge pressure transducers can be calibrated in configuration level as well as levels 2 and 3. The procedure is the same as described already in section 5.3.
62 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
13.5 Calibration Parameters
The following table lists the parameters available in the Calibration List.
CALIBRATION PARAMETER LIST
Name Scrolling
Display
U C A L USER
CALIBRATION
Parameter
Description
To calibrate the 5 point linerisation table.
Not 32h8i/SG
P H A S E CALIBRATION To calibrate low and
PHASE high offset
START
SG.TYP STRAIN
GAUGE
CALIBRATION
TYPE
SHUNT SHUNT
CALIBRATION calibration sequence
Selects the calibration for the sensor in use
‘cAL’
Value
IDLE
PnT.1
PnT.2
PnT.3
PnT.4
PnT.5 rset
Fact Return to factory settings
3.V.Hi High volts output from output 3
3.V.Lo Low volts output from output 3
3ma.H
3ma.L
High mA output from output 3
Low mA output from output 3 none
0
50
0V
10V
150r
400r
CJC
NO
Yes
Busy
Pass faiL
SHnt
Not selected
Select mV i/p low calibration point
Select mV i/p high calibration point
Select V i/p low calibration point
Select V i/p high calibration point
Select PRT i/p low cal point
Select PRT i/p high cal point
Select CJC calibration
Initial state
Start
Calibrating
Calibration successful
Calibration unsuccessful
4-wire bridge type pressure transducer
CELL
Comp
Load cell
Comparison
Off or 40.0 to 100.0
LO.CAL STRAIN
GAUGE LOW
CAL
H I . C A L STRAIN
GAUGE HIGH
CAL
AUT.SG STRAIN
GAUGE
AUTO CAL
To set the high calibration point for the pressure transducer in use
Calibrate the low point
Calibrate the high point
When selected this perform an automatic calibration to the strain gauge sensor.
See section 5.3.5.
NO
Yes
Busy
Pass faiL
NO
YES
Lo
Hi pass faiL
Initial state
Start
Calibrating
Calibration successful
Calibration unsuccessful
Initial state
Start auto calibration
These parameters automatically appear as the calibration takes place.
Default Access
Level
L3 only
Fact none
NO
CeLL
Off
NO
NO
Factory
Conf only
These parameters do not apply to
32h8i/SG
Conf
L2
These three parameters are only available in
32h8i/SG.
They are used to calibrate to the strain gauge sensor.
See section
5.3.
Part No HA029006 Issue 5.0 Sept-12 63
14. Configuration Using iTools
iTools is a configuration and monitoring package which will edit, store and ‘clone’ complete instrument configurations. iTools can be used to configure all the functions of the 3000 series indicators described in this manual.
It is also possible using iTools to configure additional functions such as customised messages and parameter promotion. These features are described in this chapter.
You may also wish to refer to the iTools Help Manual
Part No. HA028838 which can be downloaded from www.eurotherm.co.uk
. for further information on how to install, connect and generally operate iTools.
14.1 Loading an IDM
An IDM is a software file which defines the parameter addresses of a particular build of instrument. This is normally included with your iTools CD and iTools will then recognize the software version of your instrument. Alternatively, download the latest version of iTools. This may be found in www.eurotherm.co.uk.
If the build of your instrument is a non-standard, it may be necessary for you to download the IDM from the Eurotherm web site. The file will be of the format id32i_v107.exe, where id 32i is the instrument and V--
- is the software version number of the instrument.
To load the IDM
From windows START., select Programs → Eurotherm iTools → Advanced Tools → IDM Manager. Then
Install New IDM.
To register the new IDM
Copy the file to c:\Program
Files\Eurotherm\iTools\Devices.
3200iSeries Indicators
14.2 Connecting a PC to the Indicator
This may be done using digital communications port
H or by a configuration clip.
14.2.1 Using the H Communications Port
Connect the indicator to the EIA232 serial comms port of the PC shown in the diagram below.
Screen
EIA232
Connections
Com
Tx
Rx
HD Com
HE Rx
HF Tx
Local Ground
A cable is available from Eurotherm, part number
CABLE/9PINPC/NOPLUG/232/3.0m to connect an indicator to the EIA232 port of a PC. The white
(transparent) lead of this cable connects to terminal
HE and the black lead to terminal HF.
14.2.2 Configuration Clip
A Configuration Clip is available with iTools by quoting part number 3000CK in the iTools ordering code. The clip can be fitted into the side of a indicator as shown below.
The benefit of using this arrangement is that it is not necessary to power the indicator, since the clip provides the power to the internal memory of the indicator.
64 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
14.3 Starting iTools
Open iTools and, with the indicator connected, press on the iTools menu bar. iTools will search the communications ports and TCPIP connections for recognisable instruments. Indicators connected with the configuration clip (CPI), will be found at address 255 regardless of the address configured in the indicator.
When the instrument is detected a screen view similar to the one shown below will be displayed. The browser on the left shows the List Headers. To display parameters within a list double click the Header or select ‘Parameter
Explorer’. Click on a list header to display parameters associated with this list.
The instrument view may be turned on or off using the ‘View’ menu and selecting ‘Panel Views’.
The instrument may be configured using a Wizard or from the browser view. The following pages show a number of examples of how to configure various functions using either of these features.
It is assumed that the user is generally familiar with iTools and has a general understanding of Windows.
Part No HA029006 Issue 5.0 Sept-12 65
3200iSeries Indicators
14.4 Configuring the Indicator Using the Wizard
To open the Wizard press Next>> on the pop up or press from the iTools view .
The indicator will be set to configuration level. Since it will not operate the process in configuration level a warning message appears. When this is accepted the Wizard start up screen is shown:-
Select a tab to configure a function
14.4.1 To configure the Input
Select the ‘Input’ tab
To configure the input type, open the drop down box and select the input to match the sensor in use on your process. When the drop down box is opened the parameter
‘help’ description is also displayed.
This example configures the indicator for a type J thermocouple
Other functions may be configured using the appropriate tab.
A ‘help’ text is shown to the right of the wizard. This describes the feature which is selected.
A list of parameters which need to be configured follows this general description.
Click on the parameter for a description of its function.
66 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
14.4.2 To Configure Alarms
Up to four alarms are available in 3200 series indicators. Set the type of alarm, latching mode, blocking, threshold and hysteresis from drop down menus. Help text is shown together with a pictorial representation of the alarm operation.
14.4.3 To Configure Output 1
In 32h8i (shown in this example) the output is a changeover relay which can be configured to operate when up to four different alarms, selected from the drop down, occur. The example shows the relay configured to operate when any new alarm occurs.
Other features can be similarly configured by selecting the relevant tabs.
Part No HA029006 Issue 5.0 Sept-12 67
3200iSeries Indicators
14.4.4 To Customise Messages
The message which scrolls across the indicator display during normal operation may be customised.
Select the ‘Messages’ tab.
In this example the message ‘SHUT DOWN’ will be displayed if both Alarm 1 and Alarm 2 are active.
Indication Operation Action
Add a parameter
Click where the parameter is required
Select ‘Insert’
Choose the parameter from the pop up box eg
‘CAL.CalStart’
The parameter may be edited, removed or its position changed by selecting the relevant tab
Set the
Operator
From the ‘Operator:’ drop down box select ‘Mask’ – see Note 1.
Alternatively a message may be configured to appear if the enumeration of the parameter:-
= equals the ‘Value’
<> is greater or less than the ‘Value’
> is greater than the ‘Value’
< is less than the ‘Value’
Set the value
The bitmap list is given here and in the
Digital
Comms chapter
Set the priority
Enter the message
Download to the indicator
1. Click in the ‘Value’ box and press enter
2. From the pop up box either tick the bit field values or type in the decimal equivalent in
‘New Value’. In this example 3 (alarm 1 + alarm 2).
3. From the drop down select Low Medium or
High
4. In the message section enter SHUT DOWN
Instrument Status - Bitmap
B0 – Alarm 1 Status
B1 – Alarm 2 Status
B2 – Alarm 3 Status
B3 – Alarm 4 Status
B4 – Auto/Manual Status
B5 – Sensor Break Status
B6 – Loop Break Status
B7 – CT Low load current alarm status
B8 – CT High leakage current alarm status
B9 – Program End
B10 – PV Overrange (by > 5% of span)
B11 – CT Overcurrent alarm status
B12 – New Alarm Status
B13 – Timer/Ramp Running
B14 – Remote Fail, New Alarm
B15 – Autotune Status
In each case, a setting of 1 signifies ‘Active’, 0 signifies ‘Inactive’.
Device Flash Memory’ button
Note 1:- Mask allows any combination of parameters in the above bitmap field to activate the custom message.
The table below shows how this operates for the four alarm fields.
Value Bitmap
1
2
0001
0010
Parameter (Alarm) active
Alarm 1
Alarm 2
Value
5
6
Bitmap
0101
0110
Parameter (Alarm) active
Alarm 3 + Alarm 1
Alarm 2 + Alarm 3
Other parameters can be added by extending this table.
3 0011 Alarm 1 + Alarm 2 7 0111 Alarm 1 + Alarm 2 + Alarm
3
4 0100 Alarm 3 8 1000 Alarm 4
68 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
14.4.5 To Promote Parameters
The list of parameters which are available in operator levels 1 or 2 can be changed using the ‘Promote’ wizard. You can set the access to Read Only or Read/Write
Select ‘Promote’ tab.
Highlight a parameter.
Select the level of access you wish to be available to the available to the operator and whether it should be
Read/Write or Read only.
In the example below ‘Strain Gauge Low Cal’ will be available in Level 2 and will be read and Write access.
The list of parameters which can be made available in operator levels 1 or 2 can be changed using the ‘Insert’ tab.
Parameters may also be Edited, Removed or Moved up or down the list.
When inserting or editing a pop up box appears as shown.
Part No HA029006 Issue 5.0 Sept-12 69
3200iSeries Indicators
14.4.6 To Set Up Recipes
There are five recipes available, which can store a range of parameter values for different processes.
Select the ‘Recipe’ tab
14.4.6.1 Recipe Definition
Select ‘Recipe Definition’ tab to display the default parameters available to be stored in recipe. Double click on the parameter in the
‘Wired From’ column, a pop up allows you to delete or change to a different parameter.
14.4.6.2 Editing Recipe
Values
Select any one of the
Recipe01 to 05 tabs. It is necessary to set the values of all parameters. Start with the first followed by all other parameters.
To download the new values, press Next> or select any other tab. There is a delay whilst the recipe updates. To ensure the indicator accepts the new recipe values, select another recipe in the indicator itself, then go back to the recipe in which the changes were made.
14.4.6.3 Recipe Names
Names can be given to each of the five recipes by directly typing the name in the Value column. Each name is limited to a maximum of four characters – this being the limit of the characters which can be displayed on the front panel of the indicator. A character shown as ‘?’ signifies that it cannot be displayed on the indicator due to font limitations. To download a new recipe name press Next (or Back or select any other tab).
70 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
14.4.7 To Customise the Display
Press the ‘Display’ tab.
The operator display in this example will be green and display PV.
A customized static message, up to 9 characters long, may be displayed on the instrument when one particular event is true.
This message is taken from the message tab, see section 14.4.4, and in this example will show SHUT DOWN as a non scrolling message when alarm 1 occurs.
!
Erase
Instrument Memory must be used with care.
This setting is used to initialise instrument memory to default values. The memory will be cleared when the instrument is next reset or powered up. Following a clear, the instrument will start up in
QuickStart mode displaying XXXXX to indicate an unconfigured instrument. The cold start will not erase the calibration.
14.4.8 Summary Tab
The ‘Summary’ tab shows the terminal connections for the functions which have been configured together with a description of each function.
Press ‘Summary’ tab.
Part No HA029006 Issue 5.0 Sept-12 71
3200iSeries Indicators
14.5 Configuring the Indicator Using the Browser Views
Press (if necessary) to put the indicator into configuration level.
14.5.1 To configure the Input
Open the parameter list by double clicking INPUT in the browser or selecting ‘Parameter Explorer’.
Select input type from the drop down. Other parameters can also be set using the drop downs or by setting the analogue values.
Parameters shown in blue, in the iTools view, are not alterable.
14.5.2 To Configure Alarms
1. Select the list header from the browser – in this case ‘ALARM’ ‘1’
2. To configure ‘Alarm
Type’ open the drop down under the
‘Value’ column
4. Select the alarm type
– in this example HI.
(1) is the enumeration of the parameter.
5. Select and set all other parameters using the same procedure
72 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
14.5.3 To Customise Messages
In this example the alarm 1 message will read ‘TOO HOT’.
1. Press and select the ‘Message Table’ tag
2. Select Parameter ‘ALARM1 #1’
3. In the ‘Message Condition’ area change ‘Message’ to SHUT DOWN
4. Press ‘Update Device Flash Memory’ button
In the example shown below Alarm 2 message has also been configured to ‘TOO COLD’
Part No HA029006 Issue 5.0 Sept-12 73
14.5.4 To Promote Parameters
In this example the parameter ‘OP1.Sense’ is added to the to the Level 2 list.
1. Press and select the ‘Promote Parameters’ tab
2. Highlight the position where you want the new parameter to be placed
3. Press button and from the pop up window select the required parameter
4. In the Level box select Level 2 (or Level 1 + 2 if it is required to display this parameter in Level 1 as well)
5. In the Access box select ‘Read Only’ or ‘Read/Write’ as required
6. Press to remove a selected parameter
7. Press ‘Update Device Flash Memory’ button
3200iSeries Indicators
74 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
14.6 To Load A Special Linearisation Table
In addition to the built in standard linearisation tables, custom tables can be downloaded from files.
1. Press
2. Select the lineariastion table to be loaded from files with the extension .mtb. Linearisation files for different sensor types are supplied with iTools and may be found in Program Files ¤ Eurotherm ¤ iTools ¤
Linearisations ¤ Thermocouple etc.
3. In this example a Pt-PTRh(10%) thermocouple has been loaded into the indicator. The indicator will display the linearisation table downloaded:-
Part No HA029006 Issue 5.0 Sept-12 75
3200iSeries Indicators
14.7 To Set up Recipes
14.7.1 Example:- Set Two Different Alarm Thresholds and Store in Recipes 1 and 2
1. Set an alarm threshold e.g 300.
2. Select ‘RECIPE’ in the browser
3. In RecipeSave, select the recipe number e.g. 1
4. Set the alarm threshold to another value and save in Recipe 2
5. In RecipeNumber choose the recipe to run. Recipe 1 will now select the first alarm threshold and recipe 2 will select the second alarm threshold.
It may be more convenient to open more than one parameter list as shown in the above view. To do this, double click on each list header in turn. The lists can be arranged using Window in the main menu and choose Tile
Vertically, Tile Horizontally or Cascade.
76 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
14.8 Summary
Press to display the terminal connections for the functions which have been configured together with a summary of each function.
A summary of the features configured may be selected using the ‘Summary’ tab.
Part No HA029006 Issue 5.0 Sept-12 77
3200iSeries Indicators
14.9 Cloning
The cloning feature allows the configuration and parameter settings of one instrument to be copied into another.
Alternatively a configuration may be saved to file and this used to download to connected instruments. The feature allows new instruments to be rapidly set up using a known reference source or standard instrument. Every parameter and parameter value is downloaded to the new instrument which means that if the new instrument is used as a replacement it will contain exactly the same information as the original. Cloning is generally only possible if the following applies:
•
The target instrument has the same hardware configuration as the source instrument
•
The target instrument firmware (ie. Software built into the instrument) is the same as or a later version than that of the source instrument. The instrument firmware version is displayed on the instrument when power is applied.
•
Generally, cloning will copy all operational, engineering and configuration parameters that are writable. The communications address is not copied.
!
Every effort has been made to ensure that the information contained within the clone files is a replica of that configured in the instrument. It is the users responsibility to ensure that the information cloned from one instrument to another is correct for the process to be controlled, and that all parameters are correctly replicated into the target instrument.
Below is a brief description of how to use this feature. Further details are available in the iTools Handbook
14.9.1 Save to File
The configuration of the indictor made in the previous sections may be saved as a clone file. This file can then be used to download the configuration to further instruments.
From the File menu use ‘Save to File’ or use the ‘Save’ button on the Toolbar.
14.9.2 To Clone a New Indicator
Connect the new indictor to iTools and Scan to find this instrument as described at the beginning of this chapter.
From the File menu select ‘Load Values From File’ or select ‘Load’ from the toolbar. Choose the required file and follow the instruction. The new instrument will be configured to this file.
78 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
15. TECHNICAL SPECIFICATION
General
Temperature limits
Humidity limits
Panel sealing
Operation: 0 to 55°C (32 to 131°F),
Storage: -10 to 70°C (14 to 158°F)
Operation: RH: 5 to 90% noncondensing
Storage: RH: 5 to 90% non-condensing
IP 65, Nema 4X
Vibration 2g peak, 10 to 150Hz
Atmospheres
Electromagnetic compatibility
(EMC)
Electrical safety
Not suitable for use above 2000m or in explosive or corrosive atmospheres.
BS EN61326
BS EN61010 Installation cat. II; Pollution degree 2
Installation category II
The rated impulse voltage for equipment on nominal 230V supply is 2500V
Pollution degree 2 Normally only non conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation shall be expected.
Physical 3216i 3204i 32h8i
Panel mounting 1/16 DIN 1/4 DIN 1/8 DIN horizontal
Weight grams 250
Dimensions mm
48W x 48H x 90D
420
96W x 96H x
90D
350
96W x 48H x 90D
Panel cut-out dimensions mm
45W x 45H 92W x 92H
Operator interface
Type LCD TN with backlight
Main PV display 3216i 3204i
92W x 45H green green
32h8i
5 digits, green or red
Lower display
5 character starburst, green
5 character starburst, green
9 character starburst, green
Status beacon Units, outputs, alarms, active setpoint
Power requirements
3216i 100 to 240Vac, -15%, +10%
48 to 62Hz, max 6W
24Vac, -15%, +10%
24Vdc, -15%, +20%, +5% ripple voltage, max 6W
3204i, 32h8i 100 to 240Vac, -15%, +10%
48 to 62Hz, max 8W
24Vac, -15%, +10%
24Vdc, -15%, +20%, +5% ripple voltage, max 8W
Approvals
CE, cUL listed (file ES7766), Gost, FM,
EN14597TW approval number TW1222.
Transmitter PSU
Isolation 264Vac double insulated
Output Voltage 24Vdc, 20mA
Communications: serial communications option
Isolation
Transmission standard
Modbus RTU Master broadcast (1 parameter)
264Vac double insulated
EIA232 or EIA485 2-wire
Transmission standard
EIA232 or EIA485 2-wire
Process Variable Input
Calibration accuracy <+0.25% of reading +1LSD (1)
Sample rate
Isolation
9Hz (110mS)
264Vac double insulated from the PSU and communications
Resolution (μV) < 0.5μV with 1.6s filter (mV range)
< 0.25μV with 1.6s filter (Volts range)
Resolution (effective bits)
>17 bits
<0.1% of reading Linearisation accuracy
Drift with temperature
Common mode rejection
Series mode rejection
Input impedance
Cold junction compensation
External cold junction
Cold junction accuracy
Linear (process) input range
<50ppm (typical) <100ppm (worst case)
48 - 62 Hz, >-120db
48 - 62 Hz, >-93db
100M Ω (200KΩ on volts range C)
>30 to 1 rejection of ambient temperature
Reference of 0
O
C
<+1 o C at 25 o C ambient
Thermocouple
Types
RTD Type
-10 to 80mV, 0 to 10V with external potential divider module 100K
Ω/806Ω
(not 32h8i)
K, J, N, R, S, B, L, T, C, custom download (2)
3-wire, Pt100 DIN43760
Bulb current 0.2mA
Lead compensation No error for 22 ohms in all 3 leads
Input filter
Zero offset
Off to 100 seconds
User adjustable over the full display range
2-point gain & offset User calibration
Notes
(1) Calibration accuracy quoted over full ambient operating range and for all input linearisation types.
(2) Contact Eurotherm for details of availability of custom downloads for alternative sensors.
Part No HA029006 Issue 5.0 Sept-12 79
Strain gauge input (32h8i)
Input type:
Connection:
350 Ω Bridge
4 or 6 wire (6 uses internal shunt)
Calibration accuracy:
+0.1% of full scale
Sample time:
Isolation:
9hz (110ms)
264Vac double isolation from the PSU and communications
Sensitivity:
Input span:
Zero balance:
Functions
1.4 to 4mV/V
-27% to +127% of full scale (approx. –
10mV to +5mV):
+ 25% of full scale
Tare: + 25% of full scale
Resolution (mV): 0.3mV/V(typical) with 1.6s filter
14.3 bits Resolution
(effective bits):
Drift with temperature:
Common mode rejection:
<100ppm/°C of full scale
48-62Hz, >-120db
Series mode rejection:
Input filter:
AA relay
48-62Hz, >-60db
Off to 100s
Type
Rating
Form C changeover
Min: 100mA @ 12Vdc,
Max: 2A @ 264Vac resistive
Alarms or events
Digital input A/B
(B not in 3216i), A not on 32h8i with SG or SD)
Contact closure Open >600 Ω Closed <300Ω
Input current <13mA
Isolation
Functions
None from PV or system
264Vac double insulated from PSU and communications
Includes alarm acknowledge, keylock, alarm inhibit, freeze display, tare, auto zero, peak reset
Logic I/O module (3216i only)
Rating
Isolation
Functions
On/High 12Vdc at <44mA
Off/Low <300mV at 100 μA
None from PV or system
264Vac double insulated from PSU and communications
Alarms or events
Digital input
Contact closure Open >500 Ω Closed <150Ω
Isolation None from PV or system
264Vac double insulated from PSU and communications
Functions Includes alarm acknowledge, keylock, alarm inhibit, freeze display, tare, auto zero, peak reset
Relay output channels
Type 3216i Form A (normally open)
Rating
Functions
3204i
Min: 100mA @ 12Vdc, Max: 2A @
264Vac resistive
Alarms or events
3200iSeries Indicators
Analogue output
OP1, OP2 (3216i only)
Rating 0-20mA into <500 Ω
Accuracy + (<0.5% of reading + <100μA)
Resolution
Isolation
11.5 bits
None from PV or system.
264Vac double insulated from PSU and communications.
Functions Retransmission
OP 3 (not on 3216i)
Isolation: 264Vac double insulate
Functions:
Current Output
Retransmission
Rating:
Accuracy:
Resolution:
0-20mA into <500Ω
±(<0.25% of Reading + <50μA)
13.6 bits
Voltage Output (not on 3204i)
Rating:
Accuracy:
0-10V into >500Ω
±(<0.25% of Reading +<25mV)
Software features
Alarms
Number 4
Type
Latching
Absolute high and low, rate of change
(rising or falling)
Auto or manual latching, non-latching, event only
Output assignment
Number of characters
Up to four conditions can be assigned to one output
Custom messages
Number 15 scrolling text messages
127 characters per message max
Languages
Selection
English, German, French, Spanish, Italian
Active on any parameter status using conditional command
Recipes
Number
Selection
Scrolling text
5 with 19 parameters
HMI interface, communications or dig. IO
Transducer calibration
Calibration types
Shunt, load cell, comparison
Other features Auto-zero, tare
Other features
Display colour
(32h8i)
Upper display selectable green or red or change on alarm
Parameter help, custom messages
Display filter
Peak monitor
FM
Alarm 1 configuration:
Off to zero last 2 digits
Stores high and low values
Absolute hi or lo, de-energised in alarm
Latching output on Form C (AA) Relay
All alarms active on sensor break and power fail
Alarm setpoint: Adjustment protection via password
Configuration security
FM option prevents reconfiguration of alarm config
80 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
16. Parameter Index
This is a list of parameters in alpha/numeric order to help locate the section in which they are applicable.
Parameter Parameter Name Parameter list &
Section
INPUT
FUNCTION
I/O List 3216i section 8.2
1.FUNC I/O 1 FUNCTION
1.ID
1.RNG
I/O 1 TYPE
DC OUTPUT RANGE
Output 1 List section 8.1 and 8.2
Output 1 List section 8.1 and 8.2
I/O List 3216i section 8.2
1.SENS
1.SRC.A
1.SRC.B
1.SRC.C
1.SRC.D
I/O 1 SENSE
I/O 1 SOURCE A
I/O 1 SOURCE B
I/O 1 SOURCE C
I/O 1 SOURCE D
Output 1 List section 8.1 and 8.2
Output 1 List section 8.1 and 8.2
Output 1 List section 8.1 and 8.2
Output 1 List section 8.1 and 8.2
Output 1 List section 8.1 and 8.2
INPUT
FUNCTION
Output 2 List 3216i only section 8.3
2.FUNC I/O 2 FUNCTION
2.HIGH DC OUTPUT HIGH
RANGE
Output 2 List 3216i only section 8.3
Output 2 List 3216i only section 8.3
2.LOW
2.RNG
2.SENS
DC OUTPUT LOW
RANGE
DC OUTPUT RANGE
OUTPUT 2 SENSE
Output 2 List 3216i only section 8.3
Output 2 List 3216i only section 8.3
Output 2 List 3216i only section 8.3
2.SRC.A I/O 1 SOURCE A
2.SRC.B
2.SRC.C
2.SRC.D
3.FUNC
I/O 1 SOURCE B
I/O 1 SOURCE C
I/O 1 SOURCE D
FUNCTION
Output 2 List 3216i only section 8.3
Output 2 List 3216i only section 8.3
Output 2 List 3216i only section 8.3
Output 2 List 3216i only section 8.3
Output 3 List section 7.2.6
3.HIGH
3.ID
DC OUTPUT HIGH
SCALE
OUTPUT 3 TYPE
Output 3 List section 7.2.6
Output 3 List section 8.4
3.LOW
3.RNG
4.FUNC
DC OUTPUT LOW
SCALE
DC OUTPUT RANGE
I/O 1 FUNCTION
Output 3 List section 8.4
4.SENS
4.SRC.A
4.SRC.B
4.SRC.C
4.SRC.D
4.TYPE
I/O 1 SENSE
I/O 1 SOURCE A
I/O 1 SOURCE B
I/O 1 SOURCE C
I/O 1 SOURCE D
OUTPUT 4 TYPE
Output 3 List section 8.4
Output 4 List (AA Relay) section 8.5
Output 4 List (AA Relay) section 8.5
Output 4 List (AA Relay) section 8.5
Output 4 List (AA Relay) section 8.5
Output 4 List (AA Relay) section 8.5
Output 4 List (AA Relay) section 8.5
Output 4 List (AA Relay) section 8.5
Parameter
A1.---
A1.BLK
A1.DLY
A1.HYS
Parameter Name
ALARM 1 SETPOINT
Parameter list &
Section
Alarm List section 10.3 and
4.4
Alarm List section 10.3 ALARM 1 BLOCKING
DELAY TIME Alarm List section 10.3
ALARM 1 HYSTERESIS Alarm List section 10.3
A1.LAT ALARM 1 LATCHING
TYPE
Alarm List section 10.3
A1.OFS ALARM
OFFSET
Alarm List section 10.3
A1.STS ALARM 1 OUTPUT Alarm List section 10.3
A1.TYP ALARM 1 TYPE Alarm List section 10.3
ADDR ADDRESS
GAUGE
AUTO CAL
CJ.TYP
List section 12.2
Calibration List section 13.5
Communications
List section 12.2
CJC TYPE Input List section 7.1
CJC.IN CJC TEMPERATURE Input List section 7.1
Access List section 6.5
COLOR
CONF.P
ENABLE/ DISABLE
SET TOP DISPLAY
COLOUR
CONFIG PASSCODE
Access List section 6.5
Access List section 6.5
DEC.P
DELAY
DISPLAY POINTS
RX/TX DELAY TIME
E.CaL
E.Conf
E.Lin
E2.Er
EE.Er
FILT.D
FILT.T
GO
DISPLAY FILTER
FILTER TIME
CALIBRATION START
Input List section 7.1
Digital Communications
List section 12.2
Diagnostic Alarm List section 10.4
Diagnostic Alarm List section 10.4
Diagnostic Alarm List section 10.4
Diagnostic Alarm List section 10.4
Diagnostic Alarm List section 10.4
Input List section 7.1
Input List section 7.1
Calibration List section 13.5
GOTO GOTO
HI.CAL STRAIN
CAL
HIGH PEAK HIGH
Access List section 6.5
Calibration List section 13.5
Input List section 7.1 and
4.4
Access List section 6.5 HOME
ID
ID
IN.TYP
INP.HI
INP.LO
HOME DISPLAY See
Note 1
CUSTOMER ID
MODULE IDENTITY
INPUT TYPE
LINEAR INPUT HIGH
LINEAR INPUT LOW
Access List section 6.5
Digital Communications
List section 12.2
Input List section 7.1
Input List section 7.1
Input List section 7.1
K.LOCK KEYBOARD LOCK
INPUT
FUNCTION
L.SENS LOGIC INPUT SENSE
Access List section 6.5
Digital Input List section
9.1
Digital Input List section
Part No HA029006 Issue 5.0 Sept-12 81
Parameter Parameter Name
9.1
Parameter list &
Section
L.TYPE
LEV2.P
LEV3.P
LOGIC INPUT TYPE
LEVEL 2 PASSCODE
LEVEL 3 PASSCODE
Digital Input List section
9.1
Access List section 6.5
Access List section 6.5
LO.CAL STRAIN LOW
CAL
Calibration List section 13.5
LOW PEAK LOW Input List section 7.1 and
4.4
HOME
MESSAGE
Access List section 6.5
P1.OFS
P2.OFS
P3.OFS
P4.OFS
P1.STS
P2.STS
P3.STS
P4.STS
VALUE
PRE ALARM 1 OFFSET Alarm List section 10.3
PRE ALARM 2 OFFSET Alarm List section 10.3
PRE ALARM 3 OFFSET Alarm List section 10.3
PRE ALARM 4 OFFSET Alarm List section 10.3
Pre alarm 1 output status
Pre alarm 2 output status
Pre alarm 3 output status
Pre alarm 4 output status
PEAK RESET
FEATURE PASSCODE
Parameter Modbus address list section 12.5
Parameter Modbus address list section 12.5
Parameter Modbus address list section 12.5
Parameter Modbus address list section 12.5
Input List section 7.1
Access List section 6.5
P.RST
PASS.C
PHASE
PRTY PARITY
PV.IN
CALIBRATION PHASE Calibration List section 13.5
PV INPUT VALUE
Communications
List section 12.2
Input List section 7.1
PV.OFS PV OFFSET Input List section 7.1
REG.AD DESTINATION
ADDRESS
RETRN TRANSMITTED
PARAMETER
RNG.HI RANGE HIGH LIMIT
Digital Communications
List section 12.2
Digital Communications
List section 12.2
Input List section 7.1
RNG.LO RANGE LOW LIMIT Input List section 7.1
Input List section 7.1
SB.TYP
DIRECTION
SENSOR BREAK TYPE Input List section 7.1
GAUGE
CALIBRATION TYPE
Calibration List section 13.5
SHUNT SHUNT CALIBRATION Calibration List section 13.5
TA.OFS TARE OFFSET Input List section 7.1
TARE TARE FUNCTION
UCAL
UNITS
USER CALIBRATION
DISPLAY UNITS
Input List section 7.1 and
4.4
Calibration List section 13.5
Input List section 7.1
3200iSeries Indicators
82 Part No HA029006 Issue 5.0 Sept-12
3200iSeries Indicators
17. Index
Access Parameters ...................................................... 29
Acknowledge ..................................................... 42
ADDR ....................................................... 20, 50, 52
Address ............................................................... 52
Alarm .... 17, 18, 20, 24, 34, 35, 36, 39, 41, 72, 80
ALARM 1 BLOCKING ......................................... 44
ALARM 1 HYSTERESIS ....................................... 44
ALARM 1 LATCHING TYPE................................ 44
ALARM 1 OUTPUT ............................................. 44
ALARM 1 SETPOINT .......................................... 44
ALARM 1 TYPE.............................................. 44, 81
Alarm Relay ......................................................... 42
Automatic ...................................................... 23, 41
BAUD ................................................................... 50
Blocking Alarms ................................................. 41
Calibration ....................................... 22, 23, 33, 57
CALIBRATION ADJUST ..................................... 22
CJC TEMPERATURE ........................................... 31
CJC TYPE ............................................................ 30
COLD ............................................................. 29, 73
CONF.P ............................................................... 29
CONFIG PASSCODE ......................................... 29
Configuration ............................ 15, 25, 26, 29, 64
CT .................................................................. 54, 68
CUSTOMER ID .............................................. 20, 29
DC ..................................................... 12, 35, 36, 38
DC OUTPUT RANGE .............................. 35, 36, 38
DIGITAL INPUT FUNCTION .............................. 35
Dimensions .......................................................... 5
Display Mnemonic
1.D.IN .............................................................................. 35, 55
1.FUNC .............................................................. 34, 35, 37, 55
1.SENS ...................................................................... 34, 35, 56
1.SRC.A .............................................................. 34, 35, 37, 55
1.SRC.B .............................................................. 34, 35, 37, 56
1.SRC.C .............................................................. 34, 35, 37, 56
1.SRC.D .............................................................. 34, 35, 37, 56
2.FUNC ........................................................................... 36, 56
2.SENS ............................................................................ 36, 56
2.SRC.A ........................................................................... 36, 56
2.SRC.B ........................................................................... 36, 56
2.SRC.C ........................................................................... 36, 56
2.SRC.D ........................................................................... 36, 56
3.FUNC ........................................................................... 38, 56
3.SENS ................................................................................... 56
3.SRC.A .................................................................................. 56
3.SRC.B .................................................................................. 56
3.SRC.C .................................................................................. 56
3.SRC.D .................................................................................. 56
4.FUNC ........................................................................... 39, 56
4.SENS ............................................................................ 39, 56
4.SRC.A ........................................................................... 39, 56
4.SRC.B ........................................................................... 39, 56
4.SRC.C ........................................................................... 39, 56
4.SRC.D ........................................................................... 39, 56
4.TYPE ............................................................................. 39, 56
A1.---.......................................................................... 44, 45, 53
A1.BLK ............................................................................ 44, 54
A1.HYS ............................................................................ 44, 53
A1.LAT ............................................................................ 44, 54
A1.TYP ............................................................... 27, 44, 45, 54
Ac.AL ............................................................................... 35, 40
ADDR ................................................................. 20, 50, 52, 53
Auto .................................................................... 30, 41, 44, 55 b.tc .......................................................................................... 31
BAUD .............................................................................. 50, 55
C.ADJ ..................................................................................... 22
CAL .................................................................................. 20, 58
CJC ........................................................ 30, 31, 53, 55, 57, 60
Conf .................................................................... 25, 26, 29, 46
CT 54, 68 d.in .......................................................................................... 35
DEC.P .............................................................................. 30, 53
DELAY ....................................................................... 44, 50, 55
EVENT ....................................................................... 41, 44, 45
FILT.T ............................................................................... 30, 53
Heat ........................................................................................ 57
I/O-1 ....................................................................................... 35
IN.TYP ............................................................................. 30, 55
J.tc .......................................................................................... 31 k.tc .......................................................................................... 31
L.tc .......................................................................................... 31
LEV 1 ...................................................................................... 26
LEV 2 ...................................................................................... 26
LEV 3 ...................................................................................... 26
Loc.b ............................................................................... 35, 40 n.tc .......................................................................................... 31 none ................................................................................ 44, 50 nw.AL ................................................................. 34, 35, 36, 39
OFS.HI .................................................................................... 54
OFS.LO .................................................................................. 54
OP-2 ....................................................................................... 36
OP-3 ....................................................................................... 38
PNT.HI .................................................................................... 54
PNT.LO .................................................................................. 54
PRTY ................................................................................ 50, 55
PV.OFS ............................................................................ 30, 53 r.tc ........................................................................................... 31
REC.NO........................................................................... 20, 53
ReLy ........................................................................................ 34
RNG.HI ............................................................................ 30, 53
RNG.LO ........................................................................... 30, 53
S.tc .......................................................................................... 31
Sbr ............................................................................. 30, 35, 36
SP1 .......................................................................................... 55
STORE ....................................................................... 20, 47, 53 t.tc ........................................................................................... 31
TC 30
UNITS ........................................................................ 21, 30, 53
DISPLAY POINTS ................................................ 30
DISPLAY UNITS ............................................. 21, 30
Event ....................................................... 41, 44, 45
Fault detection .................................................... 30
FEATURE PASSCODE ........................................ 29
FILTER TIME ........................................................ 30
Part No HA029006 Issue 5.0 Sept-12 83
FUNCTION ................................ 20, 35, 36, 38, 39
GOTO ........................................................... 26, 29
Heat ...................................................................... 57
HOME .................................. 17, 19, 20, 21, 27, 29
HOME DISPLAY See Note 1 .............................. 29
Hysteresis ..................................................... 41, 53
I/O 1 FUNCTION ................................................ 34
I/O 1 SENSE ........................................................ 34
I/O 1 SOURCE A ................................................. 34
I/O 1 SOURCE B.................................................. 34
I/O 1 SOURCE C ................................................. 34
I/O 1 SOURCE D ................................................. 34
I/O 1 TYPE .................................................... 34, 35
ID ............................ 20, 29, 34, 35, 36, 38, 50, 52
Inductive Loads ................................................... 10
Input .... 10, 11, 12, 30, 33, 34, 35, 40, 57, 58, 59,
66, 72, 79
Input filter ............................................................ 30
Input Filter ........................................................... 79
Input Type
Type mV.......................................... 10, 21, 30, 31, 33, 57, 60
INPUT TYPE .................................................. 30, 33
Input Type and linearisation .............................. 30
Input/Output .......................................... 12, 34, 35
Installation ............................................... 6, 13, 14
Internet Site
UK 49, 52, 64
K.LOC ................................................................... 29
Latched Alarms ................................................... 42
Latching Alarm .................................................... 41
Lev.1 ..................................................................... 29
Lev.2 ..................................................................... 29
Lev.3 ..................................................................... 29
LEV2.P .................................................................. 29
LEV3.P .................................................................. 29
LEVEL 2 PASSCODE ........................................... 29
LEVEL 3 PASSCODE ........................................... 29
Linear ......................................... 10, 18, 30, 33, 79
LINEAR INPUT HIGH ........................................... 30
LINEAR INPUT LOW ........................................... 30
Logic ............................................ 8, 12, 35, 40, 80
LOGIC INPUT FUNCTION.................................. 40
LOGIC INPUT TYPE ............................................ 40
Manual ................................................... 23, 41, 45
3200iSeries Indicators
MILLIVOLT INPUT VALUE .................................. 31
Modbus ...................................... 12, 50, 51, 52, 53
MODULE IDENTITY ........................................... 50
Mounting .............................................................. 6
Non latching ....................................................... 41
OUTPUT 2 TYPE ................................................. 36
OUTPUT 3 TYPE ................................................. 38
OUTPUT HIGH ........................................ 35, 36, 38
Output Power ..................................................... 55
Over/Under range ............................................. 30
PID ....................................................................... 37
Power Supply ............................................... 11, 80
PV .......................................... 10, 30, 31, 33, 35, 41
PV INPUT VALUE ................................................ 31
PV OFFSET .......................................................... 30
Quick Start Code................................................... 7
RANGE HIGH LIMIT ........................................... 30
RANGE LOW LIMIT ............................................ 30
Recipe ........................... 20, 24, 35, 40, 47, 70, 76
Relay ......................... 8, 10, 12, 34, 35, 36, 37, 39
Reset .................................................................... 54
RTD ................................................... 10, 30, 58, 61
Run ................................................................ 48, 55
RX/TX DELAY TIME ............................................ 50
SENSE .............................................. 35, 36, 39, 40
SENSOR BREAK TYPE ....................................... 30
Sleeve ..................................................................... 6
Strain Gauge ................................................. 22, 79
Switch On........................................................... 15 terminals ................................................. 10, 49, 51
Tare……………………………..18, 19, 20, 31, 35
Thermocouple ..................... 10, 30, 31, 57, 59, 60
Type b – b.tc.......................................................................... 31
Type J – J.tc ........................................................................... 31
Type k – k.tc........................................................................... 31
Type L – L.tc........................................................................... 31
Type n – n.tc .......................................................................... 31
Type r – r.tc ............................................................................ 31
Type S – S.tc .......................................................................... 31
Type t – t.tc ............................................................................ 31
Timer ................................................................... 68
User calibration .................................................. 30
USER CALIBRATION .......................................... 63
Wiring ........................................... 8, 11, 13, 49, 51
84 Part No HA029006 Issue 5.0 Sept-12
Eurotherm: International sales and service
AUSTRALIA Melbourne
Invensys Process Systems
Australia Pty. Ltd.
T (+61 0) 8562 9800
F (+61 0) 8562 9801
AUSTRIA Vienna
Eurotherm GmbH
T (+43 1) 7987601
F (+43 1) 7987605
BELGIUM & LUXEMBOURG
Moha
Eurotherm S.A./N.V.
T (+32) 85 274080
F (+32) 85 274081
BRAZIL Campinas-SP
Eurotherm Ltda.
T (+5519) 3707 5333
F (+5519) 3707 5345
CHINA
Eurotherm China
T (+86 21) 61451188
F (+86 21) 61452602
Beijing Office
T (+86 10) 5909 5700
F (+86 10) 5909 5709/10
FRANCE Lyon
Eurotherm Automation SA
T (+33 478) 664500
F (+33 478) 352490
GERMANY Limburg
Invensys Systems GmbH
>EUROTHERM<
T (+49 6431) 2980
F (+49 6431) 298119
INDIA Mumbai
Invensys India Pvt. Ltd.
T (+91 22) 67579800
F (+91 22) 67579999
IRELAND Dublin
Eurotherm Ireland Limited
T (+353 1) 4691800
F (+353 1) 4691300
ITALY Como
Eurotherm S.r.l
T (+39 031) 975111
F (+39 031) 977512
KOREA Seoul
Invensys Operations Management
Korea
T (+82 2) 2090 0900
F (+82 2) 2090 0800
NETHERLANDS Alphen a/d Rijn
Eurotherm B.V.
T (+31 172) 411752
F (+31 172) 417260
POLAND Katowice
Invensys Eurotherm Sp z o.o.
T (+48 32) 7839500
F (+48 32) 7843608/7843609
Warsaw
Invensys Systems Sp z o.o.
T (+48 22) 8556010
F (+48 22) 8556011
SPAIN Madrid
Eurotherm España SA
T (+34 91) 6616001
F (+34 91) 6619093
SWEDEN Malmo
Eurotherm AB
T (+46 40) 384500
F (+46 40) 384545
SWITZERLAND Wollerau
Eurotherm Produkte (Schweiz) AG
T (+41 44) 7871040
F (+41 44) 7871044
UAE DUBAI
Invensys Middle East FZE
T (+971 4) 8074700
F (+971 4) 8074777
UNITED KINGDOM Worthing
Eurotherm Limited
T (+44 1903) 268500
F (+44 1903) 265982
U.S.A. Ashburn VA
Invensys Eurotherm
T (+1 703) 724 7300
F (+1 703) 724 7301
ED68
©Copyright Invensys Eurotherm Limited 2012
Invensys, Eurotherm, the Invensys Eurotherm logo, Chessell, EurothermSuite, Mini8, EPower, nanodac, Eycon, Eyris and Wonderware are trademarks of
Invensys plc, its subsidiaries and affiliates. All other brands may be trademarks of their respective owners.
All rights are strictly reserved. No part of this document may be reproduced, modified or transmitted in any form by any means, neither may it be stored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior written permission of Invensys Eurotherm Limited.
Invensys Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice. The information in this document is given in good faith, but is intended for guidance only. Invensys Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.
Represented by:
HA029006/5 (CN28942)
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 7 Installation and Basic Operation
- 7 Unpacking Your Indicator
- 7 Dimensions Front Views
- 7 Dimensions – Side and Top Views
- 8 Step 1: Installation
- 8 Panel Mounting the Indicator
- 8 Panel Cut-out Sizes
- 8 Recommended Minimum Spacing of Indicators
- 8 To Remove the Indicator from its Sleeve
- 9 Ordering Code
- 10 Step 2: Wiring
- 10 Terminal Layout 32h8i Indicator
- 11 Terminal Layout 3216i Indicator
- 11 Terminal Layout 3204i Indicators
- 12 Wire Sizes
- 12 Sensor Input (Measuring Input)
- 12 Outputs - 1/8 and 1/4 DIN Indicators
- 12 Output 1 & Output 4 (AA Relay)
- 12 Output 3 Retransmission (Output 2 3216i)
- 12 Transmitter Supply
- 13 Digital Inputs A and B
- 13 Transducer Supply
- 13 Indicator Power Supply
- 13 Example Wiring Diagram
- 14 Digital Communications (Optional)
- 14 Additional Connections for 3216i
- 14 Input/Output 1 & Output
- 15 Safety and EMC Information
- 15 Installation Safety Requirements
- 17 Switch On
- 17 New Indicator
- 19 To Re-Enter Quick Code Mode
- 19 Pre-Configured Indicator or Subsequent Starts
- 19 Front panel layout
- 20 Alarm Indication
- 20 Out of Range Indication
- 20 Sensor Break Indication
- 20 Operator Parameters in Level
- 21 Tare Correction
- 21 Operator Level
- 21 To Enter Level
- 21 To Return to Level
- 22 Level 2 Parameters
- 24 Strain Gauge Calibration
- 24 Load Cell Calibration
- 24 Comparison Calibration
- 25 Shunt Calibration
- 25 Manual Calibration
- 25 Automatic Calibration
- 25 Calibration Using a Digital Input
- 26 Recipes
- 26 To Store Values in a Recipe
- 26 To Load a Recipe
- 26 FM and Alarm Units
- 27 Access to Further Parameters
- 27 Level
- 27 Configuration Level
- 28 To Select Access Level 3 or Configuration Level
- 29 Parameter lists
- 29 To Choose Parameter List Headers
- 29 To Locate a Parameter
- 29 How Parameters are Displayed
- 29 To Change a Parameter Value
- 29 To Return to the HOME Display
- 29 Time Out
- 30 Navigation Diagram
- 31 Access Parameters
- 32 Process Input
- 32 Process Input Parameters
- 33 Input Types and Ranges
- 34 Units
- 35 PV Offset
- 35 PV Input Scaling
- 36 Input/Output Channels
- 36 Output Channel 1 (OP-1) - 32h8i and 3204i Indicators
- 37 Input/Output Channel 1 (I/O-1) - 3216i Indicator
- 38 Output Channel 2 (OP-2) - 3216i Indicator
- 39 Sense
- 39 Source
- 39 Power Fail
- 39 Example: To Configure OP-1 Relay to Operate on Alarms 1 and
- 40 Output Channel 3 (OP-3) – 32h8i, 32h8i/SG and 3204i Indicators
- 40 Output Scaling
- 41 AA Relay Channel (AA) (Output 4)
- 42 Digital Input
- 42 Digital Input Parameters
- 43 Alarms
- 43 Types of Alarm
- 44 Alarm Relay Output
- 44 Alarm Indication
- 44 To Acknowledge An Alarm
- 44 Pre-Alarms
- 45 Behaviour of Alarms After a Power Cycle
- 45 Example
- 46 Alarm Parameters
- 47 Example: To Configure Alarm
- 48 Diagnostic Alarms
- 49 Recipe
- 49 To Save Values in a Recipe
- 49 To Save Values in a Second Recipe
- 50 To Select a Recipe to Run
- 51 Digital Communications
- 51 Digital Communications Wiring
- 52 Digital Communications Parameters
- 53 Broadcast Communications
- 53 Broadcast Master Communications
- 53 Wiring Connections
- 54 Example: To Set Up Instrument Address
- 54 DATA ENCODING
- 55 Parameter Modbus Addresses