SUBMITTAL DATA: PLA-A18BA4 & PUZ-A18NHA4
. . . . . . . . . . . . . . . . 18,000 BTU/H CEILING-CASSETTE HEAT-PUMP SYSTEM
Job Name: Location:
Purchaser: Engineer:
Submitted to:
Unit Designation:
Date:
For Reference Approval Construction
Schedule No.:
• Compact side-discharge outdoor unit
• Setback down to 50°F when used with MRCH1 Central Controller
• Quiet operation—indoor and outdoor units
• Built-in drain lift mechanism for condensate removal; lifts to 33-7/16"
• Wide air flow pattern for better air distribution
• Auto wave airflow in heating mode—unit independently cycles
through horizontal and vertical positions for more even heat distribution
• Independent vane adjustment
• Automatic fan speed control
• Limited warranty: five years on parts/defects, seven years on compressors
OPTIONAL ACCESSORIES
□ Multi-function Casement (PAC-SH53TM)
□ Air Outlet Shutter Plates (PAC-SH51SP)
□ High-efficiency (MERV 10) Filter (PAC-SH59KF)
Outdoor Unit
□ Drain Socket (PAC-SG61DS)
□ Three-pole Disconnect Switch (TAZ-MS303)
□ Wind Baffle (WB-PA1)
□ Air Outlet Guide (PAC-SG58SG)
□ Mounting Base (DSD-400N)
□ Wall-mounting Brackets (CWMB1)
Controller Options
□ Wireless Remote Controller Kit (MHK1) with Wall-mounted Central
Controller (MRCH1), Wireless Receiver (MIFH1), and cable*
□ Wall-mounted Central Controller (MRCH1)*
□ Wireless Receiver (MIFH1)*
□ Portable Central Controller (MCCH1; for use with Wireless Remote
Controller Kit MHK1)*
□ Outdoor Air Sensor (MOS1; for use with Central Controller (MRCH1),
Wireless Remote Controller Kit (MHK1) and Portable Central
Controller (MCCH1)*
*See Submittal for information on each option.
□ Wall-mounted Wired Remote Controller (PAR-21MAA)
□ M-NET Adapter (PAC-SF81MA)
□ CN51 Connector for Multiple Remote Controller Adapters/Duct Fan
Controller (PAC-725AD)
□ CN24 Relay Kit (CN24RELAY-KIT-CM)
□ CN32 Connector for Remote On/Off (PAC-715AD)
□ Remote Temperature Sensor (PAC-SE41TS)
□ Remote Operation Adapter - Display and On/Off (PAC-SF40RM)
□ Handheld Wireless Remote Controller (PAR-FL32MA; req. PAR-SA9FA)
□ Wireless Signal Receiver Module (PAR-SA9FA)
□ Lockdown Bracket for Handheld Controller (RCMKP1CB)
□ Control/Service Tool (PAC-SK52ST)
Rated Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18,000 Btu/h
Minimum Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8,000 Btu/h
SEER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14.2 Btu/h/W
EER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3 Btu/h/W
Total Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..1,940 W
Heating at 47°F*
Rated Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19,000 Btu/h
Minimum Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8,000 Btu/h
HSPF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9.8 Btu/h/W
COP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.93
Total Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..1,900 W
Rated Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13,000 Btu/h
Total Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..1,590 W
COP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.40
* Rating Conditions (Cooling)-Indoor: 80ºF (27ºC) DB/67ºF (19ºC) WB. Outdoor: 95ºF (35ºC) DB/ 75ºF (24ºC) WB.
(Heating at 47°F) - Indoor: 70ºF (21ºC) DB, 60ºF (16ºC) WB. Outdoor: 47ºF (8ºC) DB, 43ºF (6ºC) WB.
(Heating at 17ºF) - Indoor: 70ºF (21ºC) DB, 60ºF (16ºC) WB. Outdoor: 17ºF (-8.3ºC) DB, 15ºF (-9.4ºC) WB.
Power Supply . . . . . . . . . . . . . . . . . . . . 208 / 230V, 1-Phase, 60 Hz
Recommended Fuse/Breaker Size. . . . . . . . . . . . . . . . . . . . . . .15 A
Indoor - Outdoor S1-S2 . . . . . . . . . . . . . . . . . . . . . . AC 208 / 230V
Indoor - Outdoor S2-S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . .DC 24V
Indoor Unit: PLA-A18BA4
Outdoor Unit: PUZ-A18NHA4
OPERATING CONDITIONS
Indoor Intake Air Temp.
Outdoor Intake Air Temp.
115ºF (46ºC) DB
0ºF** (-18ºC) DB
Minimum 70ºF (21ºC) DB, 60ºF (16ºC) WB 12ºF (-11ºC) DB, 10ºF (-12ºC) WB temperature will be 23ºF (-5ºC) DB.
MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 A
Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.51 F.L.A.
Fan Motor Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 W
Airflow (Lo - M1 - M2 - Hi) . . . . . . . 420 - 490 - 570 - 640 Dry CFM
390 - 460 - 530 - 600 Wet CFM
Sound Level (Lo - M1 - M2 - Hi) . . . . . . . . . . 28 - 29 - 31 - 32 dB(A)
SHF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.81
Moisture Removal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.0 pt./h
D
H
DIMENSIONS
W
UNIT INCHES / MM
33-1/16 / 840
33-1/16 / 840
10-3/16 / 258
PANEL INCHES / MM
37-3/8 / 950
37-3/8 / 950
1-3/8 / 35
Weight (Unit/Grille) lbs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 / 13 kg . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 / 6
External Finish . . . . . . . . . . . . . . . . . . . . Munsell No. 6.4Y 8.9 / 0.4
Field Drainpipe Size O.D.. . . . . . . . . . . . . . . . . . . . . 1-1/4" / 32 mm
Compressor . . . . . . . . . . . . . . . . . . DC Inverter-driven Twin Rotary
MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .…13 A
MOCP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 A
Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.35 F.L.A.
Sound Pressure Level
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 dB(A)
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 dB(A)
D
H
DIMENSIONS
W
INCHES / MM
31-1/2 / 800
11-13/16 + 7/8 / 300 + 23
23-5/8 / 600
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91 lbs. / 41 kg
External Finish . . . . . . . . . . . . . . . . . . . . . .Munsell No. 3Y 7.8 / 1.1
Refrigerant Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R410A
Refrigerant Pipe Size O.D.
Gas Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1/2" / 12.7 mm
Liquid Side. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1/4" / 6.35 mm
Max. Refrigerant Pipe Length. . . . . . . . . . . . . . . . . . . . . 100' / 30 m
Max. Refrigerant Pipe Height Difference . . . . . . . . . . . . 100' / 30 m
Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flared
DIMENSIONS: PLA-A18BA4
25/32 to 1-25/32(20~45)
Ventilation air intake hole
Branch duct hole
Suspension bolt
M10 or 3/8
1
2
Suspension bolt lower edge
6-5/16
(160)
Ceiling hole
33-27/32 to 35-13/16(860~910)
31-7/8(810)
Suspension bolt pitch
25/32 to 1-25/32(20~45)
Detail connecting of branch duct (nominal 6" round or nominal 4 x 14" rectangular)
3-15/16
3-17/32 (90)
(100)
3-15/16
(100)
3-17/32
(90)
Cut out hole
For MA-Remote controller terminal block
Indoor unit/Outdoor unit connecting terminal block
For wiring replacement kit terminal block
-3/16 +1-3/8
7-3/8
(187.5)
(60)
2-3/8
33-1/16 (840)
(284)
11-3/16
(377)
14-27/32
6-5/16
(160)
Drainpipe connected to
1-1/4 in. O.D. PVC tube
Ceiling
Grille
+5 0
Branch duct hole
(
Connected the attached flexible pipe or socket.
)
Keep 25/64(10)to 19/32(15) between unit ceiling and ceiling slab.
(ø175)
ø6-7/8
Burring hole pitch
13-25/32
(350)
14ø1/8 (14-ø2.8)
Burring hole
ø5-29/32
Cut out hole
(ø150)
Detail drawing of ventilation air intake connection
Burring hole
3ø1/8(3-ø2.8)
120˚
Burring hole pitch
ø4-29/32(ø125)
120˚
Cut out hole
ø3-15/16(ø100)
*
*
Ceiling
23-1/2 (597)
Air intake hole
M
M
Drain lift mechanism clean hole and Drain emergency drainage hole
Auto vane
(Air outlet)
In case of standard grille In case of wireless remote controller
Emergency operation switch<Cooling>
Emergency operation switch<Heating>
Air intake grille
Receiver
DEFROST/STAND BY lamp
Operation lamp
Ceiling
M
Corner pocket
Grille
19-11/16
(500)
Air outlet hole
37-3/8
(950)
Indoor unit
M
3-17/64
(83)
Min.94-1/2(2400) from floor
Vane motor
1-27/64
(36)
Note1. Use 1-1/4 in. O.D. (32) PVC TUBE.
Drain lift mechanism is included.
2. Suspension bolt, use M10 or W3/8.
(Field supplied)
3. Electrical box may be removed for service purposes.
Make sure to slack the electrical wire little bit for control/power wires connection.
4. The height of the indoor unit is adjustable with the grille attached.
5. For the installation of the optional high efficiency filter, the optional multi-functional casement is required.
1) Add 5-5/16 (135mm) to the dimensions marked with an * in the figures
2) The optional high efficiency filter required optional multi-functional casement.
6. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation may occur.
7. As for necessary installation/service space, please refer to the bottom left figure.
Min.19-11/16(500)
Entire periphery
Floor
Models
PLA-A12BA4
PLA-A18BA4
1
Refrigerant pipe
···· ø6.35mm
Flared connection
····1/4
PLA-A24BA4
PLA-A30BA4
PLA-A36BA4
PLA-A42BA4
Refrigerant pipe
···· ø9.52mm
Flared connection
····3/8
2
Refrigerant pipe
···· ø12.7mm
Flared connection
····1/2
A B C D
9-1/2
(241)
10-3/16
(258)
3-5/32
(80)
2-29/32
(74)
Refrigerant pipe
···· ø15.88mm
Flared connection
····5/8 11-1/16
(281)
11-3/4
(298)
3-11/32
(85)
3-1/32
(77)
Handle
DIMENSIONS: PUZ-A18NHA4
400<15-25/32>
347.5<13-11/16>
Air intake
ø33<1-5/16> drain hole
Air intake
45.4<1-25/32>
4-oval hole
18<23/32>
Air discharge
40<1-9/16>
22<7/8>
2-ø22.2<7/8>
1/2 conduit hole
23<29/32>
FOUNDATION BOLTS
Please secure the unit firmly with 4 foundation M10<W3/8> bolts.
(Bolts, washers and nut must be purchased locally.)
<Foundation bolt height>
FOUNDATION
Service panel
Service panel for charge plug
Connection for liquid pipe
FLARE ø6.35<1/4>
150<5-29/32>
287.5<11-11/32>
Installation bolt pitch
500<19-11/16>
800<31-1/2>
Clearance space needed around the outdoor unit
Min.100mm<3-15/16> as long as no obstacle is placed on the rear and light-and-left sides of the unit
Service port
Connection for gas pipe
144<5-21/32>
FLARE ø12.7<1/2>
183<7-7/32>
69<2-23/32>
PIPING-WIRING DIRECTION
Piping and wiring connection can only be made from the back.
Min.100mm<3-15/16> Min.350mm<13-25/32>
*1
*2 *1
Min.500mm<19-11/16> Min.100mm<3-15/16>
2 sides should be open in the right, left and rear side.
Minimum installation space for outdoor unit
If the unit is installed in a place where short cycle can occur, cooling and heating capacity might be reduced by 10%. Using an air outlet guide (PAC-SG58SG-E) will help deflect exhaust air and improve performance.
C SD - PLA-A18BA4 - PUZ-A18NHA4 - 201011 © MITSUBISHI ELECTRIC / HVAC 2010
3400 Lawrenceville Suwanee Rd
Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
Toll Free: 800-433-4822 (#3) www.mehvac.com