00_CV_3PN05140-1.fm Page 1 Friday, October 11, 2002 9:45 AM
OPERATION MANUAL
English
SPLIT SYSTEM
Air Conditioner
Deutsch
MODELS
(Ceiling suspension type)
FH(Y)35BJV1
FH(Y)45BJV1
FH(Y)60BJV1
FHY71BJV1
FHY100BJV1
FHY125BJV1
Français
FHYP35BV1
FHYP45BV1
FHYP60BV1
FHYP71BV1
FHYP100BV1
FHYP125BV1
FH35BZV1
FH45BZV1
FH60BZV1
FHQ35BUV1B
FHQ50BUV1B
FHQ60BUV1B
Español
Italiano
ÅëëçíéêÜ
Nederlands
Portugues
Russian
01_CV_3PN05140-1.fm Page 1 Wednesday, October 2, 2002 1:05 PM
5 12
4
2
1
3
7
hr
C
hr
6
8
NOT
AVAILABLE
TEST
9
11
10
13
L H
14
21
20
TEST
19
17
15
16
18
22
1
f
a
k
e
e
i
3
g
h
d
d
j
b
d
c
e
f
hr
C
k
2
[1]
4
H
01_CV_3PN05140-1.fm Page 2 Wednesday, October 2, 2002 1:05 PM
Thank you for purchasing this Daikin air conditioner. Carefully read this operation manual
before using the air conditioner. It will tell you
how to use the unit properly and help you if any
trouble occurs. After reading the manual, file it
away for future reference.
Óáò åõ÷áñéóôïýìå ðïõ áãïñÜóáôå ôç óõóêåõÞ
êëéìáôéóìïý. ÄéáâÜóôå ðñïóåêôéêÜ áõôÝò ôéò
ïäçãßåò ÷ñÞóçò ðñéí íá ÷ñçóéìïðïéÞóåôå ôç
óõóêåõÞ êëéìáôéóìïý.
Èá óáò ðïõí ðùò èá ÷ñçóéìïðïéÞóåôå óùóôÜ
ôç ìïíÜäá êáé èá óáò âïçèÞóïõí áí
åìöáíéóôïýí ðñïâëÞìáôá. Aöïý äéáâÜóåôå ôéò
ïäçãßåò, âÜëôå ôéò óôï áñ÷åßï óáò ãéá ìåëëïíôéêÞ
áíáöïñÜ.
Vielen Dank für den Kauf einer Klimaanlage von
Daikin. Bitte lesen Sie diese Bedienungsanleitung vor der Inbetriebnahme des Gerätes
gründlich durch. Hier wird erklärt, wie das Gerät
richtig eingesetzt wird und was bei Störungen zu
tun ist. In dieser Anleitung wird nur das Innenaggregat beschrieben. Verwenden Sie diese Anleitung zusammen mit der Bedienungsanleitung
des Außenaggregats. Nach dem Lesen der
Anleitung legen Sie diese griffbereit zum Nachschlagen auf.
Wij danken u voor de aankoop van deze Daikin
airconditioner. Lees deze bedrijfshandleiding
aandachtig door voordat u de airconditioner
gebruikt. Het omvat uitleg over het correcte
gebruik van de unit en biedt hulp in geval een
storing mocht optreden. Gebruik deze handleding voor verdere raadpleging.
Nous vous remercions pour votre acquisition de
ce climatiseur Daikin.
Lisez attentivement ce manuel avant d’utiliser le
climatiseur. Il vous expliquera comment vous
servir correctement de l’appareil et vous guidera
en cas de problème. Lorsque vous aurez lu le
manuel, rangez-le afin de pouvoir vous y référer
ultérieurement.
Obrigado pela sua compra deste aparelho de ar
condicionado Daikin.
Leia com atenção este manual de operação
antes de proceder à utilização do aparelho de ar
condicionado. Este indicar-lhe-á como deverá
utilizar a unidade correctamente e ajudá-lo-á no
caso de surgir qualquer problema. Depois de ler
o manual, guarde-o num local seguro a fim de o
poder consultar caso venha a ser preciso.
Le agradecemos la compra de este acondicionador de aire Daikin. Lea cuidadosamente el
manual de funcionamiento antes de utilizar el
acondicionador de aire. Dicho manual le indicará cómo utilizar adecuadamente la máquina y
le ayudará en caso de avería. Después de leer
el manual, consérvelo para consultas futuras.
Ñïàñèáî çà ïîêóïêó äàííîãî êîíäèöèîíåðà
ôèðìû Daikin. Äî íà÷àëà ðàáîòû ñ
êîíäèöèîíåðîì âíèìàòåëüíî èçó÷èòå
äàííîå ðóêîâîäñòâî ïî ýêñïëóàòàöèè. Â
íåì èçëàãàþòñÿ ïðàâèëà íàäëåæàùåãî
ïîëüçîâàíèÿ óñòðîéñòâîì è ïðèâîäÿòñÿ
ðåêîìåíäàöèè ïîëüçîâàòåëþ ïî ïîèñêó è
óñòðàíåíèþ íåèñïðàâíîñòåé. Ïîñëå
èçó÷åíèÿ ðóêîâîäñòâà ñîõðàíèòå åãî äëÿ
îáðàùåíèé â áóäóùåì.
La ringraziamo di aver acquistato questo condizionatore d’aria Daikin. Leggere attentamente
questo manuale prima di avviare il condizionatore. Ciò permetterà di usare correttamente
l’unità e di ottenere un aiuto in caso di anomalia
di funzionamento. Dopo aver letto il manuale,
conservarlo in un luogo accessibile per una
futura necessità.
02_EN_3PN05140-1.fm Page 1 Thursday, November 14, 2002 3:37 PM
CONTENTS
ILLUSTRATIONS................................................. [1]
1. WHAT TO DO BEFORE OPERATION .......... 1
2. SAFETY CONSIDERATIONS ....................... 2
3. OPERATION RANGE .................................... 3
4. INSTALLATION SITE .................................... 3
5. NAME AND FUNCTION OF EACH SWITCH
AND DISPLAY ON THE REMOTE
CONTROLLER .............................................. 4
6. OPERATION PROCEDURE.......................... 5
7. OPTIMUM OPERATION................................ 7
8. MAINTENANCE
(FOR SERVICE PERSONNEL) ..................... 8
9. NOT MALFUNCTION OF THE AIR
CONDITIONER.............................................. 9
10. TROUBLE SHOOTING................................ 11
1. WHAT TO DO BEFORE OPERATION
This operation manual is for the following systems
with standard control. Before initiating operation,
contact your Daikin dealer for the operation that corresponds to your system.
• Pair system or Simultaneous operation
system
Indoor unit
If your installation has a customized control system,
ask your Daikin dealer for the operation that corresponds to your system.
• Heat pump type
This system provides cooling, heating, automatic,
program dry, and fan operation modes.
• Cooling only type
This system provides cooling, program dry, and
fan operation modes.
PRECAUTIONS FOR GROUP CONTROL
SYSTEM OR TWO REMOTE CONTROLLER
CONTROL SYSTEM
This system provides two other control systems
beside individual control (one remote controller controls one indoor unit) system. Confirm the following if
your unit is of the following control system type.
• Group control system
One remote controller controls up to 16 indoor units.
All indoor units are equally set.
• Two remote controllers control system
Two remote controllers control one indoor unit (In case
of group control system, one group of indoor units)
The unit is individually operated.
NOTE
• Contact your Daikin dealer in case of changing
the combination or setting of group control and
two remote controllers control system.
Names and functions of parts
Outdoor unit
Refer to figure 2 on page [1]
Unit with
remote
controller
• Multi system
Indoor unit
Unit without remote
controller
(When used as
simultaneous
operation system)
Indoor unit
Outdoor unit
Unit with
remote
controller
Unit with
remote
controller
NOTE
• If the unit you purchased is controlled by a wireless remote controller, also refer to the wireless
remote controller’s operation manual.
1
a Indoor unit
Outdoor unit
• The external appearance of the outdoor unit
varies depending on its capacity class.
b
The outdoor unit shown in the figure is for
reference to indicate features.
Contact your Daikin Dealer and verify which
outdoor unit you have.
c Remote controller
d Inlet air
e Discharged air
f Air outlet
g Air flow flap (at air outlet)
h Refrigerant piping, connection electric wire
i Drain pipe
Suction grille
j
The built-in air filter removes dust and dirt.
Ground wire
k Wire to ground from the outdoor unit to prevent
electrical shocks.
English
02_EN_3PN05140-1.fm Page 2 Thursday, November 14, 2002 3:37 PM
2. SAFETY CONSIDERATIONS
We recommend that you read this instruction manual carefully before use to gain full advantage of the
function of the air conditioner, and to avoid malfunction due to erroneous handling.
This air conditioner comes under the term “appliances
not accessible to the general public.”
• The precautions described below are WARNING and CAUTION. These are very important
precautions concerning safety. Be sure to
observe all of them without fail.
WARNING .. These are the matters with possibilities leading to serious consequences such as death or serious
injury due to erroneous handling.
CAUTION ... These are the matters with possibilities leading to injury or material
damage due to erroneous handling including probabilities leading to serious consequences in
some cases.
• After reading, keep this manual at a place
where any user can read at any time. Furthermore, make certain that this operation manual
is handed to a new user when he takes over
the operation.
WARNING
Avoid exposure of your body directly to the
cold air for a long time, or avoid excessive
exposure of your body to the cold air.
Otherwise, your physical condition may be deteriorated and/or your health may be ruined.
When the air conditioner is in abnormal conditions (smell of something burning, etc),
unplug the power cord from the outlet, and
contact the dealer where you purchased the
air conditioner.
Continued operation under such circumstances
may result in a failure, electric shock, and fire.
Ask your dealer for installation of the air conditioner.
Incomplete installation performed by yourself
may result in a failure, a water leakage, electric
shock, and fire.
Ask your dealer for improvement, repair, and
maintenance.
Incomplete improvement, repair, and maintenance may result in a failure, a water leakage,
electric shock, and fire.
Do not insert your finger, a stick, etc., into the
air inlet, outlet, and fan blades.
A fan in high-speed running may result in injury.
For refrigerant leakage, consult your dealer.
When the air conditioner is to be installed in a
small room, it is necessary to take proper measures so that the amount of any leaked refrigerEnglish
ant does not exceed the limiting concentration
even when it leaks. If the refrigerant leaks
exceeding the level of limiting concentration, an
oxygen deficiency accident may happen.
For installation of separately sold component parts, ask a specialist.
Be sure to use the separately sold component
parts designated by our company.
Incomplete installation performed by yourself
may result in a failure, a water leakage, electric
shock, and fire.
Ask your dealer to move and reinstall the air
conditioner.
Incomplete installation may result in a failure, a
water leakage, electric shock, and fire.
The refrigerant in the air conditioner is safe and
normally does not leak. If the refrigerant leaks
inside the room, the contact with a fire of a burner,
a heater or a cooker may result in a harmful gas.
Do not use the air conditioner until when a service person confirms to finish repairing the portion where the refrigerant leaks.
CAUTION
Do not use the air conditioner for other purposes.
Do not use the air conditioner for a special application such as the storage of foods, animals and
plants, precision machines, and art objects as
otherwise the deterioration of quality may result.
Do not remove the air outlet of the outdoor unit.
The fan may get exposed and result in injury.
When the air conditioner is used in combination with burners or heaters, perform sufficient ventilation.
Insufficient ventilation may result in an oxygen
deficiency accident.
Check and make sure that foundation blocks
are not damaged after a long use.
If they are left in a damaged condition, the unit
may fall and result in injury.
Neither place a flammable spray bottle near
the air conditioner nor perform spraying.
Doing so may result in a fire.
To clean the air conditioner, stop operation,
and unplug the power cord from the outlet.
Otherwise, an electric shock and injury may result.
Do not operate the air conditioner with a wet hand.
An electric shock may result.
Do not use any fuse with improper capacity.
The use of a piece of wire and whatnot may
result in a failure and fire.
Do not place a burner or heater at a place
directly exposed to the wind from the air conditioner.
Incomplete combustion of the burner or heater
may result.
Do not allow a child to mount on the outdoor
unit or avoid placing any object on it.
Falling or tumbling may result in injury.
2
02_EN_3PN05140-1.fm Page 3 Thursday, November 14, 2002 3:37 PM
Do not expose animals and plants directly to
the wind from the air conditioner.
Adverse influence to animals and plants may
result.
Do not wash the air conditioner with water.
An electric shock may result.
Do not install the air conditioner at any place
where flammable gas may leak out.
If the gas leaks out and stays around the air conditioner, a fire may break out.
Be sure to install an earth leakage breaker.
Unless it is installed, an electric shock may
result.
Be sure the air conditioner is electrically
grounded.
Do not connect the grounding conductor to a gas
pipe, water pipe, lightning arrester, and the
grounding conductor for a telephone.
Imperfect grounding work may result in an electric shock.
Execute complete drain piping for perfect
drainage.
Incomplete piping may result in a water leakage.
HEATING
OUTDOOR UNIT
INDOOR
TEMPERATURE
RY35 · 45 · 60
DB
15 to 27
RY71 · 100 · 125
RYP71 · 100 · 125
RYEP71 · 100 · 125
DB
15 to 27
RZP71 · 100 · 125
DB
15 to 27
RXS35 · 50 · 60
DB
10 to 30
3MXS52
4MXS68 · 80
DB
10 to 30
OUTDOOR
TEMPERATURE
DB
WB
– 9 to 21
– 10 to 15.5
DB
– 9 to 21
WB
– 10 to 15.5
DB
WB
DB
WB
DB
WB
– 14 to 21
– 15 to 15.5
– 14 to 24
– 15 to 18
– 14 to 21
– 15 to 15.5
D B: Dry bulb temperature (°C)
WB: Wet bulb temperature (°C)
The setting temperature range of the remote controller is 16°C to 32°C.
3. OPERATION RANGE
If the temperature or the humidity is beyond the following conditions, safety devices may work and the
air conditioner may not operate, or sometimes,
water may drop from the indoor unit.
COOLING
INDOOR
OUTDOOR
OUTDOOR UNIT TEMPERA- HUMID- TEMPERATURE
TURE
ITY
DB 18 to 33
R35 · 45 · 60
DB – 15 to 46
WB 12 to 24
DB 18 to 33
RY35 · 45 · 60
DB – 5 to 46
WB 12 to 24
R71 · 100 · 125
DB 21 to 35
RP71 · 100 · 125
DB – 15 to 46
REP71 · 100 · 125 WB 14 to 25
RY71 · 100 · 125
DB 18 to 35
RYP71 · 100 · 125
80% or DB – 5 to 46
RYEP71 · 100 · 125 WB 12 to 25 below
DB 21 to 35
RZP71 · 100 · 125
DB – 5 to 50
WB 14 to 25
RS50 · 60
DB 21 to 32
RKS35 · 50 · 60
DB – 10 to 46
WB 14 to 23
RXS35 · 50 · 60
3MKS50
DB 21 to 32
4MKS58 · 75 · 90
DB – 10 to 46
3MXS52
WB 14 to 23
4MXS68 · 80
3
4. INSTALLATION SITE
Regarding places for installation
• Is the air conditioner installed at a well-ventilated place where there are no obstacles
around?
• Do not use the air conditioner in the following
places.
a.Filled with much mineral oil such as cutting oil
b.Where there is much salt such as a beach area
c.Where sulfured gas exists such as a hot-spring
resort
d.Where there are considerable voltage fluctuations such as a factory or plant
e.Vehicles and vessels
f .Where there is much spray of oil and vapor such
as a cookery, etc.
g.Where there are machines generating electromagnetic waves
h.Filled with acid and/or alkaline steam or vapor
• Is a snow protection measure taken?
For details, consult your dealer.
Regarding wiring
• All wiring must be performed by an authorized
electrician.
To do wiring, ask your dealer. Never do it by yourself.
• Make sure that a separate power supply circuit is provided for this air conditioner and
English
02_EN_3PN05140-1.fm Page 4 Thursday, November 14, 2002 3:37 PM
that all electrical work is carried out by qualified personnel according to local laws and
regulations.
5
DISPLAY “ ” “ ” “ ” “ ” “ ”
(OPERATION MODE)
This display shows the current OPERATION
MODE. For cooling only type, “ ” (Auto)
and “ ” (Heating) are not installed.
6
TEST” (INSPECTION/TEST
DISPLAY “
OPERATION)
When the INSPECTION/TEST OPERATION
BUTTON is pressed, the display shows the
system mode is in.
Pay attention to running noises, too
• Are the following places selected?
a.A place that can sufficiently withstand the
weight of the air conditioner with less running
noises and vibrations.
b.A place where the hot wind discharged from the
air outlet of the outdoor unit and the running
noises.
• Are you sure that there are no obstacles near
the air outlet of the outdoor unit?
Such obstacles may result in declined performance and increased running noises.
• If abnormal noises occur in use, stop the
operation of the air conditioner, and then consult your dealer or our service station.
5. NAME AND FUNCTION OF EACH
SWITCH AND DISPLAY ON THE
REMOTE CONTROLLER
Refer to figure 1 on page [1]
1
2
3
4
ON/OFF BUTTON
Press the button and the system will start.
Press the button again and the system will
stop.
OPERATION LAMP (RED)
The lamp lights up during operation.
DISPLAY “
” (UNDER CENTRALIZED CONTROL)
When this display shows, the system is
UNDER CENTRALIZED CONTROL.
DISPLAY “
” “ ”“
”“
”
(VENTILATION/AIR CLEANING)
This display shows that the total heat
exchange and the air cleaning unit are in
operation (These are optional accessories).
English
” (PROGRAMMED TIME)
hr
7
This display shows the PROGRAMMED TIME
of the system start or stop.
8
DISPLAY “
” (SET TEMPERATURE)
This display shows the set temperature.
9
DISPLAY “
” (FAN SPEED)
This display shows the set fan speed.
10
DISPLAY “ ” (AIR FLOW FLAP)
Refer to “AIR FLOW DIRECTION ADJUST”.
Regarding drainage of drain piping
• Is the drain piping executed to perform complete drainage?
If proper drainage is not carried out from the outdoor drain pipes during air-conditioning operation,
chances are that dust and dirt are clogged in the
pipe. This may result in a water leakage from the
indoor unit. Under such circumstances, stop the
operation of the air conditioner, and then consult
your dealer or our service station.
hr
DISPLAY “
C
DISPLAY “
” (TIME TO CLEAN AIR FIL11 TER)
Refer to “HOW TO CLEAN THE AIR FILTER”.
DISPLAY “
” (DEFROST)
Refer to “DEFROST OPERATION”.
NON-FUNCTIONING DISPLAY
If that particular function is not available,
pressing the button may display the words
“NOT AVAILABLE” for a few seconds.
13 When running multiple units simultaneously
The “NOT AVAILABLE” message will only be
appear if none of the indoor units is equipped
with the function. If even one unit is equipped
with the function, the display will not appear.
12
14
15
16
17
18
19
TIMER MODE START/STOP BUTTON
Refer to “PROGRAM TIMER OPERATION”.
TIMER ON/OFF BUTTON
Refer to “PROGRAM TIMER OPERATION”.
INSPECTION/TEST OPERATION BUTTON
This button is used only by qualified service
persons for maintenance purposes.
PROGRAMMING TIME BUTTON
Use this button for programming “START and/
or STOP” time.
TEMPERATURE SETTING BUTTON
Use this button for SETTING TEMPERATURE.
FILTER SIGN RESET BUTTON
Refer to “HOW TO CLEAN THE AIR FILTER”.
4
02_EN_3PN05140-1.fm Page 5 Thursday, November 14, 2002 3:37 PM
FAN SPEED CONTROL BUTTON
20 Press this button to select the fan speed,
HIGH or LOW, of your choice.
OPERATION MODE SELECTOR BUTTON
21 Press this button to select OPERATION
MODE.
AIR FLOW DIRECTION ADJUST BUTTON
22
Refer to “AIR FLOW DIRECTION ADJUST ”.
NOTE
• For the sake of explanation, all indications are
shown on the display in Figure 1 contrary to
actual running situations.
6. OPERATION PROCEDURE
Refer to figure 1 on page [1]
• Operating procedure varies with heat pump type
and cooling only type. Contact your Daikin dealer
to confirm your system type.
• To protect the unit, turn on the main power switch
6 hours before operation.
• If the main power supply is turned off during operation, operation will restart automatically after the
power turns back on again.
COOLING, HEATING, AUTOMATIC, FAN,
AND PROGRAM DRY OPERATION
Operate in the following order.
1
OPERATION MODE SELECTOR
Press OPERATION MODE SELECTOR button several times and select the OPERATION
MODE of your choice as follows.
COOLING OPERATION ......................... “
HEATING OPERATION .......................... “
AUTOMATIC OPERATION ..................... “
Refer to figure 3 on page [1]
• For cooling only type, “COOLING” , “FAN” and
“DRY” operation are able to select.
2
ON/OFF
Press ON/OFF BUTTON
OPERATION lamp lights up or goes off and the system starts or stops OPERATION.
[EXPLANATION OF HEATING OPERATION]
DEFROST OPERATION
• As the frost on the coil of an outdoor unit increase,
heating effect decreases and the system goes
into DEFROST OPERATION.
• The indoor unit fan stops and the remote controller display shows “
”.
• After 6 to 8 minutes (maximum 10 minutes) of
DEFROST OPERATION, the system returns to
HEATING OPERATION.
Regarding outside air temperature and heating capacity
• The heating capacity of the air conditioner
declines as the outside air temperature falls. In
such a case, use the air conditioner in combination with other heating systems.
• A warm air circulating system is employed, and
therefore it takes some time until the entire room
is warmed up after the start of operation.
• An indoor fan runs to discharge a gentle wind
automatically until the temperature inside the air
conditioner reaches a certain level. At this time,
the remote controller displays “
”. Leave it
as it stands and wait for a while.
• When the warm air stays under the ceiling and
your feet are cold, we recommend that you use a
circulator (a fan to circulate the air inside the
room). For details, consult your dealer.
”
”
”
• In this operation mode, COOL/HEAT
changeover is automatically conducted.
FAN OPERATION................................... “ ”
DRY OPERATION .................................. “ ”
• The function of this program is to decrease the
humidity in your room with the minimum temperature decrease.
• Micro computer automatically determines
TEMPERATURE and FAN SPEED.
• This system does not go into operation if the
room temperature is below 16°C.
5
English
02_EN_3PN05140-1.fm Page 6 Thursday, November 14, 2002 3:37 PM
ADJUSTMENT
For programming TEMPERATURE, FAN SPEED
and AIR FLOW DIRECTION, follow the procedure
shown below.
TEMPERATURE SETTING
Press the AIR FLOW DIRECTION ADJUST
button to select the air direction as following.
swing
Press TEMPERATURE SETTING button and
program the setting temperature.
Press AIR FLOW DIRECTION
ADJUST button to select the air
direction of your choice.
Each time this button is pressed, setting
temperature rises 1°C.
Each time this button is pressed, setting
temperature lowers 1°C.
• The setting is impossible for fan operation.
NOTE
• The setting temperature range of the remote controller is 16°C to 32°C.
FAN SPEED CONTROL
Press FAN SPEED CONTROL button.
High or Low fan speed can be selected.
The micro computer may sometimes control the fan
speed in order to protect the unit.
AIR FLOW DIRECTION ADJUST
• There are 2 ways of adjusting the air discharge
angle.
1. A. Up and down adjustment
2. B. Left and right direction
Fig. 1
A. Up and down
direction
The AIR FLOW FLAP display
swings as shown the left and
the air flow direction continuously varies. (Automatic swing
setting)
The AIR FLOW FLAP display
stops swinging and the air flow
direction is fixed (Fixed air flow
direction setting).
MOVEMENT OF THE AIR FLOW FLAP
For the following conditions, micro computer controls the air flow direction so it may be different from
the display.
Operation
mode
Cooling
Heating
• When room
temperature is
lower than the
set temperature
Operation
condition
• When room
temperature is
higher than the set
temperature
• At defrost operation
• When operating continuously at
downward air flow direction
Operation mode includes automatic operation.
B. LEFT AND RIGHT DIRECTION
• Adjusting air flow direction in the left and right
direction. (Refer to Fig. 1)
NOTE
• Only make adjustments after you have stopped
the air flow direction swing in a position where
adjustments are possible. Your hand may get
caught if you attempt to make adjustments while
the unit is swinging.
B. Left and right direction
A. UP AND DOWN DIRECTION
• The movable limit of the flap is changeable. Contact your Daikin dealer for details.
English
6
02_EN_3PN05140-1.fm Page 7 Thursday, November 14, 2002 3:37 PM
PROGRAM TIMER OPERATION
Operate in the following order.
• The timer is operated in the following two ways.
• Programming the stop time (
)
.... The system stops
operating after the set time has elapsed.
• Programming the start time (
)
.... The system starts
operating after the set time has elapsed.
• The timer can be programmed a maximum of 72
hours.
• The start and the stop time can be simultaneously
programmed.
1
TIMER MODE START/STOP
Press the TIMER MODE START/STOP button
several times and select the mode on the
display.
The display flashes.
For setting the timer stop .... “
For setting the timer start .... “
2
”
”
PROGRAMMING TIME
Press the PROGRAMMING TIME button and
set the time for stopping or starting the system.
When this button is pressed, the time
advances by 1 hour.
When this button is pressed, the time
goes backward by 1 hour.
3
TIMER ON/OFF
Press the TIMER ON/OFF BUTTON.
The timer setting procedure ends.
The display “
or
” changes from flashing light to a constant light.
• Press the TIMER ON/OFF BUTTON once again
to cancel programming. The display vanishes.
7. OPTIMUM OPERATION
Observe the following precautions to ensure the
system operates.
• Adjust the room temperature properly for a comfortable environment. Avoid excessive heating or
cooling.
• Prevent direct sunlight from entering a room during cooling operation by using curtains or blinds.
• Ventilate the room regularly.
Using the unit for long periods of time requires
attentive ventilation of the room.
• Do not place items that might be damaged by
water under the indoor unit.
Water may condensate and drip if the humidity
reaches 80% or if the drain exit gets clogged.
• Keep doors and windows closed. If the doors and
windows remain open, room air will flow out and
cause to decrease the effect of cooling and heating.
• Do not place other heaters directly below the
indoor unit.
They may deform due to the heat.
• Never place objects near the air inlet and the air
outlet of the unit. It may cause deterioration in the
effect or stop in the operation.
• Turn off the main power supply switch when it is
not used for long periods of time. When the main
power switch is turned on, some watts of electricity is being used even if the system is not operating. Turn off the main power supply switch for
saving energy. When reoperating, turn on the
main power supply switch 6hours before operation for smooth running (Refer to MAINTENANCE).
• When the display shows “
” (TIME TO CLEAN
AIR FILTER), ask a qualified service person to
clean the filters (Refer to MAINTENANCE).
Refer to figure 4 on page [1]
NOTE
• When setting the timer Off and On at the same
time, repeat the above procedure from 1 to 3
once again.
When the timer is programmed to stop the system
after 3 hours and start the system after 4 hours, the
system will stop after 3 hours and then 1 hour later
the system will start.
• After the timer is programmed, the display shows
the remaining time.
7
English
02_EN_3PN05140-1.fm Page 8 Thursday, November 14, 2002 3:37 PM
8. MAINTENANCE
(FOR SERVICE PERSONNEL)
ONLY A QUALIFIED SERVICE PERSON IS
ALLOWED TO PERFORM MAINTENANCE
IMPORTANT!
• BEFORE OBTAINING ACCESS TO TERMINAL
DEVICES, ALL POWER SUPPLY CIRCUITS
MUST BE INTERRUPTED
• To clean the air conditioner, be sure to stop operation, and turn the power switch off. Otherwise, an
electric shock and injury may result.
• Do not wash the air conditioner with water
Doing so may result in an electric shock.
• Be careful with a scaffold or staging
Caution must be exercised because of work at a
high place.
Fig. 2
knob
1. Open the suction grille.
Slide both knobs simultaneously as shown and
then pull them downward.
(Do the same procedure for closing.)
(Refer to Fig. 2)
2. Remove the air filters
Push the 2 tabs up, and slowly lower the grille.
(Refer to Fig. 3)
3. Clean the air filter.
Use vacuum cleaner A) or wash the air filter with
water B).
A)Using a vacuum cleaner
Remove water and dry in the shade.
tab
NOTE
• Do not wash the air conditioner with hot water of
more than 50°C, as doing so may result in discoloration and/or deformation.
• Do not expose it to fire, as doing so may result in
burning.
Fig. 4
clip
English
Clean the air filter when the display shows “
”
(TIME TO CLEAN AIR FILTER).
It will display that it will operate for a set amount of
time.
Increase the frequency of cleaning if the unit is
installed in a room where the air is extremely contaminated.
If the dirt becomes impossible to clean, change the
air filter (Air filter for exchange is optional).
B)Washing with water
When the air filter is very dirty, use soft brush
and neutral detergent.
Fig. 3
Fig. 5
HOW TO CLEAN THE AIR FILTER
4. Fix the air filter
Set the hatch of the air filter to the fook of the
suction grille, and fix the air filter.
(Refer to Fig. 5)
5. Close the suction grille.
Refer to item No. 1.
6. After turning on the power, press FILTER
SIGN RESET BUTTON.
The “TIME TO CLEAN AIR FILTER” display vanishes.
8
02_EN_3PN05140-1.fm Page 9 Thursday, November 14, 2002 3:37 PM
HOW TO CLEAN AIR OUTLET AND OUTSIDE
PANELS
• Clean with soft cloth.
• When it is difficult to remove stains, use water or
neutral detergent.
NOTE
• Do not use gasoline, benzene, thinner, polishing
powder, liquid insecticide. It may cause discoloring or warping.
• Do not let the indoor unit get wet. It may cause an
electric shock or a fire.
• Do not use water or air of 50°C or higher for cleaning air filters and outside panels.
HOW TO CLEAN THE SUCTION GRILLE
1. Open the suction grille.
Slide both knobs and then pull them downward.
(Do the same procedure for closing.)
2. Remove the air filter.
Refer to “HOW TO CLEAN THE AIR FILTER”.
(Refer to Fig. 3)
3. Remove the suction grille.
Open the suction grille and pull the clips on the
back of the suction grille forward.
(Refer to Fig. 4)
4. Clean the suction grille.
Wash with a soft bristle
brush and neutral detergent or water, and dry
throughly.
• When very grimy
Directly apply the type of detergent used for
cleaning ventilation fans or ovens, wait 10 minutes, and then rinse with water.
NOTE
• Do not wash the air conditioner with hot water of
more than 50°C, as doing so may result in discoloration and/or deformation.
5. Fix the air filter
Refer to “HOW TO CLEAN THE AIR FILTER ”.
6. Fix the suction grille.
Refer to item No. 3.
7. Close the suction grille.
Refer to item No. 1.
START UP AFTER A LONG STOP
Confirm the following
• Check that the air inlet and outlet are not blocked.
Remove any obstacle.
• Check if the earth is connected.
Might there be a broken wire somewhere?
Contact your dealer if there are any problems
Clean the air filter and outside panels
• After cleaning the air filter, make sure to attach it.
9
Turn on the main power supply switch
• The display on the remote controller will be shown
when the power is turned on.
• To protect the unit, turn on the main power switch
at least 6 hours before operation.
WHAT TO DO WHEN STOPPING THE SYSTEM FOR A LONG PERIOD
Turn on FAN OPERATION for a half day and dry
the unit.
• Refer to “6. OPERATION PROCEDURE”.
Cut off the power supply.
• When the main power switch is turned on, some
watts of electricity is being used even if the system is not operating.
Turn off the main power supply switch for saving
energy.
• The display on the remote controller will vanish
when the main power switch is turned off.
Clean the air filter and the exterior.
• Be sure to replace the air filter to its original place
after cleaning. Refer to “MAINTENANCE”.
9. NOT MALFUNCTION OF THE AIR
CONDITIONER
The following symptoms do not indicate air conditioner malfunction
I. THE SYSTEM DOES NOT OPERATE
• The system does not restart immediately after
the ON/OFF BUTTON is pressed.
If the OPERATION lamp lights, the system is in
normal condition.
It does not restart immediately because a safety
device operates to prevent overload of the system. After 3 minutes, the system will turn on again
automatically.
• The system does not restart immediately
when TEMPERATURE SETTING button is
returned to the former position after pushing
the button.
If the OPERATION lamp lights, the system is in
normal condition.
It does not restart immediately because a safety
device operates to prevent overload of the system. After 3 minutes, the system will turn on again
automatically.
English
02_EN_3PN05140-1.fm Page 10 Thursday, November 14, 2002 3:37 PM
• The system does not start when the display
shows “
” (UNDER CENTRALIZED
CONTROL) and it flashes for few seconds
after pressing an operation button.
This is because the system is under centralized control. Flashes on the display indicates that the system
cannot be controlled by the remote controller.
• The system does not start immediately after
the power supply is turned on.
Wait one minute until the micro computer is prepared for operation.
• The outdoor unit is stopped
This is because the room temperature has
reached the set temperature. The indoor unit
switches to fan operation.
II. WHEN “
” (UNDER CENTRALIZED CONTROL) IS DISPLAYED AND OPERATION IS DIFFERENT FROM THE REMOTE CONTROL DISPLAY.
This is because operating mode is controlled by a
micro computer, as shown below, depending on
the operating mode of the other connected indoor
units when using in a multi system.
• If the operating mode does not match that of the
other indoor units which are already running,
the indoor unit goes into standby mode (the fan
stops and the air flow flaps become horizontal).
The unit will go into the above mode if either cooling, dry, or fan operation mode are set together
with heating mode.
NOTE
• Normally, the operation mode in the room where
the unit is first run is given priority, but the following situations are exceptions, so please keep this
in mind.
a If the operation mode of the first room is FAN
Mode, then using Heating Mode in any room
after this will give priority to heating. In this situation, the air conditioner running in FAN Mode
will go on standby.
b With the Priority Room Setting active
Contact your Daikin dealer for the operation
that corresponds to your system.
• If the total capacity of all the indoor units running exceeds the limit, the indoor unit will go
into standby mode (fan and air flow direction
remain as set). (Only for cooling-only type.)
• If another indoor unit goes into heating mode
after cooling, the unit may go into dry mode
(fan operates whisper and the air flow flaps
become horizontal).
III.THE FAN SPEED IS DIFFERENT FROM THE
SETTING.
• Pressing the fan speed control button does
not change the fan speed.
English
When the room temperature reaches the set temperature in heating mode, the power supply from
the outdoor unit stops and the indoor unit goes
into whisper mode (in a multi system, the fan goes
back and forth between stop and whisper).
This is to prevent the cool air from being blown
directly onto anyone in the room.
IV.AIR BLOW DIRECTION IS NOT AS SPECIFIED.
• Actual air blow direction is not as shown on
the remote controller.
• Automatic swing setting does not work.
Refer to “AIR FLOW DIRECTION ADJUST”.
V. WHITE MIST COMES OUT OF A UNIT
• When humidity is high during cooling operation (In oily or dusty places)
If the inside of an indoor unit is extremely contaminated, the temperature distribution inside a room
becomes uneven. It is necessary to clean the
inside of the indoor unit. Ask your Daikin dealer for
details on cleaning the unit. This operation
requires a qualified service person.
• When the system is changed over to HEATING
OPERATION after DEFROST OPERATION.
Moisture generated by DEFROST becomes
steam and exists.
VI.NOISE OF AIR CONDITIONERS
• A ringing sound after the unit is started.
This sound is generated by the temperature
regulator working.
It will quiet down after about a minute.
• A continuous flow “Shuh” sound is heard
when the systems is in COOLING or DEFROST
OPERATION.
This is the sound of refrigerant gas flowing
through both indoor and outdoor units.
• A “Shuh” sound which is heard at the start or
immediately after the stop of operation or
which is heard at the start or immediately after
the stop of DEFROST OPERATION.
This is the noise of refrigerant caused by flow stop
and flow change.
• A continuous flow “Shah” sound is heard
when the system is in COOLING OPERATION
or at a stop.
The noise is heard when the drain pump is in operation.
• A “Pishi-pishi” squeaking sound is heard
when the system is in operation or after the
stop of operation.
Expansion and contraction of plastic parts caused
by temperature change makes this noise.
10
02_EN_3PN05140-1.fm Page 11 Thursday, November 14, 2002 3:37 PM
VII.DUST FROM THE UNITS
• Dust may blow out from the unit after starting
operation from long resting time.
Dust absorbed by the unit blows out.
II. If the system does not properly operate except
for the above mentioned case, and none of the
above mentioned malfunctions is evident,
investigate the system according to the following procedures.
VIII.THE UNITS GIVE OFF ODORS
The unit absorbs the smell of rooms, furniture,
cigarettes, etc., and then emits them.
1. If the system does not operate at all.
• Check if there is a power failure.
Wait until power is restored. If power failure
occurs during operation, the system automatically restarts immediately after the power supply recovers.
• Check if the fuse has blown or breaker has
worked.
Change the fuse or set the breaker.
IX.THE LIQUID CRYSTAL OF THE REMOTE CONTROLLER SHOW “
”
• It happens immediately after the main power
supply switch is turned on.
This shows that the remote controller is in normal
condition.
This continues temporary.
10. TROUBLE SHOOTING
I. If one of the following malfunctions occurs,
take the measures shown below and contact
your Daikin dealer.
The system must be repaired by a qualified service
person.
WARNING
When the air conditioner is in abnormal conditions (smell of something burning, etc),
unplug the power cord from the outlet, and
contact your dealer
Continued operation under such circumstances
may result in a failure, electric shock, and fire.
• If a safety device such as a fuse, a breaker, or an
earth leakage breaker frequently actuates, or ON/
OFF switch does not properly work.
Measure: Turn off the main power switch
• If water leaks from unit.
Measure: Stop the operation.
• If the display “
” (INSPECTION), “UNIT No.”,
and the OPERATION lamp flash and the “MALFUNCTION CODE” appears.
OPERATION lamp
UNIT No.
C
INSPECTION
display
L H
INDOOR UNIT
No. in which a
malfunction occurs
MALFUNCTION CODE
2. If the system stops operating after operating
the system.
• Check if the air inlet or outlet of outdoor or
indoor unit is blocked by obstacles.
Remove the obstacle and make it well-ventilated.
• Check if the air filter is clogged.
Ask a qualified service person to clean the air
filters (Refer to MAINTENANCE).
3. The system operates but it does not sufficiently cool or heat.
• If the air inlet or outlet of the indoor or the outdoor unit is blocked with obstacles.
Remove the obstacle and make it well-ventilated.
• If the air filter is clogged.
Ask a qualified service person to clean the air
filters (Refer to MAINTENANCE).
• If the set temperature is not proper (Refer to
ADJUSTMENT).
• If the FAN SPEED button is set to LOW
SPEED (Refer to ADJUSTMENT).
• If the air flow angle is not proper (Refer to AIR
FLOW DIRECTION ADJUST).
• If the doors or the windows are open.
Shut doors or windows to prevent wind from
coming in.
• If direct sunlight enters the room (when cooling).
Use curtains or blinds.
• When there are too many inhabitants in the
room (when cooling).
Cooling effect decreases if heat gain of the
room is too large.
• If the heat source of the room is excessive
(when cooling).
Cooling effect decreases if heat gain of the
room is too large.
Measure: Notify your Daikin dealer and inform
him/her of the display.
11
English
00_CV_3PN05140-1.fm Page 2 Friday, October 11, 2002 9:45 AM
3PN05140-1
EM02A059