Siemens FIREFINDER-XLS Specifications

Add to my manuals
12 Pages

advertisement

Siemens FIREFINDER-XLS Specifications | Manualzz

s

Data Sheet 

Fire Safety & Security Products 

FireFinder

TM

XLS

Advanced Fire Alarm Control Panel

• point-capacity system

Windows ® laptop PC

ARCHITECT AND ENGINEER SPECIFICATIONS

Standard 2500 addressable,

Ability to network with other

FireFinder XLS systems

Powerful, easy-to-use programming capabilities

Fully field programmable, via

6" Backlit LCD display

User-friendly system interface

Touch screen for maintenance operations and function keys

Global annunciation and control capability

Multi-language display

Universal AC power input:

120VAC 240VAC @ 50 / 60Hz

12 amps of system power

(expandable to 48 amps)

Numerous Relays: Alarm, Trouble,

Programmable, etc.

SureWire TM addressable-loop technology

Polarity-insensitive detection circuits

(patented)

Useful diagnostic LEDs on all cards

Supports FirePrint TM application-specific detection

Intelligent / analog detection circuits:

Class A or Class B

Supports single-person test, “Walk Test”

Seismic certified

Modular assembly

Supervised remote printer

32-character custom messages

Thermal strip printer

Security-device monitoring

ƒ

( UL 1076 Listed)

Sprinkler Supervision

Degrade-mode operation

Coded outputs

NCCG Graphics support

UUKL Listed for smoke control

UL 864 9 th Edition Listed & ULC Listed;

FM, CSFM & NYMEA Approved

User help screens

Multiple command stations

Menu-driven operator commands

5000-event, history-logging capability with on-line and off-line reports

Multiple levels of password protection

Automatic environmental compensation for smoke detectors

Alarm verification

ƒ by device or zone

Pre-alarm operation

Logic-controlled output functions

Time-based-controlled output functions

Holiday schedule

City tie / leased line

200 notification-appliance-circuits

(NACs) capacity

Up to 3.0 amps (24VDC) per NAC

Built-in strobe synchronization protocol

Supports pre-action, deluge and agent releasing

Voice evacuation system (optional)

NEC 760 power-limited circuits

ƒ ( UL 864 Compliant)

Intelligent interface to building / process management systems

Operates as interactive peer with other

XLS or XLSV units in a XNET network

Distributed processing

Detector Sensitivity Readout / Printout

ƒ per NFPA 72

System Overview

FireFinder XLS is a microprocessor-based, advanced life-safety system that has a 6" display and large, lighted buttons; making it the most intuitive fire-alarm user interface in the industry. Through the use of the unique multiprocessor ‘Network’ design – along with the ability to utilize analog and conventional detection devices – FireFinder XLS exemplifies a flexible and highly configurable life-safety system.

Underwriter's Laboratories of Canada also lists the XLS for fire applications under ULC-S527. FireFinder XLS is Factory

Mutual Approved; as well as CSFM and NYMEA Approved for use in those specific locales. In addition to the standard fire applications, FireFinder XLS is UL Listed under the category UUKL for smoke control. FireFinder XLS can be used as a listed Fireman's Smoke Control Station in highrise office buildings, malls and other large structures.

FireFinder XLS is ideally suited for commercial, institutional and industrial fire detection and notification applications. XLS complies with the requirements of NFPA Standard 72, and is listed by

Underwriters Laboratories under their standard UL 864.

FireFinder XLS is UL Listed and FM Approved for

Sinorix

TM

clean-agent systems and pre-action or deluge sprinkler systems, which include foam or water applications. FireFinder XLS operates on the releasing requirements specified in NFPA 13 and 2001.

FireFinder

TM

XLS Overview

6300 s Industry, Inc.

Building Technologies Division

System Overview ─ (continued)

The FireFinder XLS system has been seismic qualified in accordance with:

ƒ

ƒ

ƒ

ƒ

ƒ

International Building Code, 2006 Edition

California Building Code, 2007 Edition

ASCE Standard 7, 2005 Edition

OSHPD CAN 2-1708A.5, Rev. 3

ICC-ES AC 156, Effective 1/1/2007

FireFinder XLS is also OSHPD preapproved under:

OSP-0057-10.

FireFinder XLS Components

The basic FireFinder XLS control unit consists of the following sub-assemblies: Person Machine Interface

(Model PM I ); Power Supply (Model PSC-12); Device Loop

Card (Model DLC); Zone Indicating Card (Model ZIC-4A);

Card cage (Model CC-5); I nner Door Blank Single Plate

(Model ID-SP); CAB-1, CAB-2 or CAB-3 enclosures.

Optional modules that can be installed with the XLS

System include: Card Cage (Model CC-2); Network

Interface Card (Model N I C-C); Zone Indicating Card 8 circuits (Models Z I C-8B / Z I C-2C); Control Relay Card

(Model CRC-6); Output Control Module (Model OCM-

16); Switch Control Module (Model SCM-8); LED

Control Module (Model LCM-8); Fan Control Module

(Model FCM-6); Supervised Input Module (Model S I M-16);

Power Supply Extender (Model PSX-12); Remote Network

Interface (Model RN I ); Remote Printer Module (Model

RPM); System Status Display (Model SSD); Multi-Point

Digital Alarm Communicator (Model MDACT); Two-

Module Remote Enclosure (Model REMBOX2); Four-

Module Remote Enclosure (Model REMBOX4).

The XLS panel is compatible with a full line of intelligent initiating devices, highlighted by the FirePrint applicationspecified detectors: Models HFP-11 and HFPT-11. XLS is also compatible with the NCC series of graphics command centers.

Model PM I contains the site-specific program configuration created in the Zeus system software-programming tool. The controller in Model PM I provides all system logic and supervision. Model PM I contains a large, 6" (1/4 VGA) monochrome LCD display, touch screen and LEDs for displaying system status. A sound is made when there is any unacknowledged event from Model PM I . The display is surrounded by keys that are used to control the displayed information and to navigate through these screens. Keys are also provided to obtain and enter "Help" into the menu features of Model PM I .

The FireFinder system is controlled and operated from

Model PM I . The intuitive person machine interface uses large, lighted buttons to prompt users as to the next correct system operation that is available (Acknowledge,

Silence, Unsilence, Audible or Reset).

DLC Device Loop Card

DLC Device Loop Card

The Device Loop Card (Model DLC) is the interface for connection with FireFinder XLS detectors and initiating devices ─ including manual stations, control and input devices. Model DLC plugs into one (1) slot of the CC-2 or CC-

5 card cage. Programming Model DLC is accomplished using the FireFinder XLS Zeus system softwareprogramming tool. Model DLC takes one (1) address on the network, and communicates with two (2) device circuits for a total of 252 detectors and devices. Model

DLC has 12 LEDs for diagnostic purposes, and provides ground-fault detection and zone-isolation circuitry.

PMI Person Machine Interface

PM

I

Person Machine Interface

The Person Machine I nterface (Model PM I ) is the core of the

FireFinder XLS system. Model PM I serves as both operator interface and central microprocessor for the

FireFinder XLS system. From Model PM I , the end user can acknowledge events, control the systemnotification appliance circuits and reset the system.

Detailed information about the nature and location of the events can also be displayed. s Industry, Inc.

Building Technologies Division

ZIC-4A Zone Indicating Card

Z

I

C-4A Zone Indicating Card

The Zone Indicating Card (Model ZIC-4A) provides four (4) fully supervised, programmable output circuits for use on the FireFinder XLS Fire Alarm Control Panel. Model

ZIC-4A supplies four (4) Class B (Style Y) or Class A (Style Z) type output circuits, power limited to 3.0 amps maximum per circuit.

FireFinder XLS Components

─ (cont.’d)

Each circuit can be independently programmed for use with listed audible or visual notification appliances, listed emergency audio speakers, municipal tie boxes, leased lines, or as releasing circuits. Model Z I C-4A plugs into one

(1) slot in the Model CC-5 or Model CC-2 card cage, and has on-board LEDs for system status and troubleshooting.

Indication of power, communication, internal operation, and ground-fault conditions are provided, as well as indication of circuit activation or Trouble conditions.

When Model N I C-C is used for XNET communications,

Model N I C-C provides communication between systems.

The maximum of XNET Model N I C-C cards on a single system (single node) is one (1), for a total of 64 XNET

Model N I C-C cards on a peer-to-peer networked system.

Model N I C-C has diagnostic LEDs that indicate: Card Fail,

CAN Fail, HNET Fail, XNET Fail, Ground Fault, Loop ‘A’ Fail and

Loop ‘B’ Fail. Model N I C-C Card also has LEDs to indicate

Power, Style and Active Networks.

ZIC-8B / ZIC-2C Zone Indicating Cards

Z

I

C-8B / Z

I

C-2C

The Zone I ndicating Card (Model ZIC-8B) provides eight (8) fully supervised, programmable output circuits for use on the FireFinder XLS fire-alarm control panel (FACP). Model

Z I C-8B supplies eight (8) Class B (Style Y) type output circuits, power limited to 2.0 amps maximum per circuit.

Each circuit can be independently programmed for use with listed audible or visual notification appliances, or listed emergency audio speakers. Model Z I C-8B plugs into one (1) slot in the Model CC-5 or Model CC-2 card cage, and has on-board LEDs for system status and troubleshooting.

Model Z I C-2C mounts directly on Model Z I C-8B, and allows each of the Model Z I C-8B output circuits to be used for two-channel voice applications. I ndication of power, communication, internal operation, and ground-fault conditions are provided, as well as indication of circuit activation or trouble conditions.

HL

I

M Line Isolator Module

HL

I

M Line

I solator Module

The loop-isolator module (Model HL I M) provides shortcircuit protection on FireFinder XLS intelligent device circuits (see: Model DLC). When Model HL I M detects a short circuit, Model HL I M is able to isolate the affected segment of the circuit – allowing the remaining devices to continue operation. Model HL I M is self-restoring – automatically reconnecting to circuit segment when the fault is removed. Model HL I M can be wired in either a

Style 4 or Style 6 configuration.

Model HL I M does not occupy a device address on the Model

DLC circuit, and does not require programming. Up to 15

Model HL I M modules may be installed on each Model DLC loop.

NIC-C Network Interface Card

N

I

C-C Network Interface Card

The Network I nterface Card (Model N I C-C) provides HNET or

XNET network communications between enclosures. I n addition to the HNET or XNET communication, Model N I C-C provides CAN network communication within an enclosure or external to the enclosure. HNET or XNET communication can be wired Style 4 or Style 7, but the CAN network can be wired Style 4 only.

When used for HNET communications, Model N I C-C provides communication between enclosures on a single system. s Industry, Inc.

Building Technologies Division

HCP Control Point Module

HCP Control Point Module

Model HCP provides an intelligent control point for the

FireFinder XLS Control Panel. Model HCP can be programmed as an independent, remotely located telephone zone, speaker zone or notification appliance circuit. Model HCP is designed to be used with the

Siemens – Fire Safety Notification-Appliance Circuits product line.

Model HCP communicates through the Model DLC analog loop, and can be wired either Class A (Style Z) or

Class B (Style Y). The 24 VDC power input comes from either the control panel or from any UL Listed powerlimited, auxiliary-power supply.

FireFinder XLS Components

─ (cont.’d)

CRC-6 Controllable Relay Card

CRC-6 Controllable Relay Card

The Controllable Relay Card (Model CRC-6) is used with the FireFinder XLS FACP. Model CRC-6 is designed to provide auxiliary control of building functions, such as: door-holder release, elevator capture, smoke control, lock release, etc. Model CRC-6 plugs into one (1) slot in the

Model CC-5 or Model CC-2 card cage. Model CRC-6 provides six (6), fully programmable relays. Each relay contains one (1) set of SPDT contacts rated at 4 Amps 30

VDC / 120VAC resistive and 3.5 amps 120VAC inductive (0.6

P.F.)

SIM-16 Supervised Input Module

S

I

M-16 Supervised Input Module

The Supervised input Module (Model S I M-16) is a remotely located, general-purpose input module. Model

S I M-16 provides 16 input circuits for remote system monitoring. Each input can be individually programmed as supervised (dry-contact only) or unsupervised (generalpurpose input.) Model S I M-16 has two (2) Form C relays.

The relays and inputs are programmed using the Zeus system software-programming tool.

CC-2 Card Cage-2 Slots CC-5 Card Cage-5 Slots

CC-5 / CC-2 Card Cages

The Models CC-5 / CC-2 card cages provide the physical mounting location and all wiring connection points for all fire-and-voice system options cards for the FireFinder XLS system. Model CC-5 has five (5) slots, while Model CC-2 has two (2) slots.

All cards plugged into the CC-5 / CC-2 card cage communicate with other FireFinder-XLS modules via a common data bus. Connectors are provided on the left and right side of the CC-5 to connect a 60-pin cable for communications with the FireFinder-XLS' operator interface, power supplies and amplifiers modules.

Field wiring to devices and circuits terminates on the

Models CC-5 / CC-2 card cages. All cards designed for use with the Models CC-5 / CC-2 route their field wiring terminations to the ‘top’ of the Model CC-5 / CC-2 card cages. These connections are all power limited. Internal wiring connections distribute 24VDC to cards or high-level audio signals (depending on application used) connect to the ‘bottom’ of the Model CC-5 / CC-2 card cages. These connections are all non-power limited.

All wiring connections to the Model CC-5 / CC-2 card cages are to removable terminal blocks. Terminal blocks are rated for use with wire sized 12AWG to 24AWG. Each connector is numbered to make wiring terminations to the correct position on the terminal block simple in order to reduce potential wiring errors.

CDC-4 Conventional Detector Card

CDC-4 Conventional Detector Card

The Conventional Detector Card (Model CDC-4) is used to monitor Siemens Fire Safety conventional detectors on the FireFinder XLS system. Model CDC-4 can be used in applications where conventional detectors are more suited than addressable detectors, such as hallways or large meeting rooms. Also, Model CDC-4 can be used to upgrade Siemens conventional fire-alarm panels to the FireFinder XLS system without requiring detector replacement. s Industry, Inc.

Building Technologies Division

SCM-8 Switch Control Module

SCM-8 Switch Control Module

The Switch Control Module (Model SCM-8) is a FireFinder

XLS-option module that provides manual control to the

Emergency Voice Evacuation System (EVAC) or manual fire-system control. Each Model SCM-8 module provides eight (8) momentary push-button switches and 16 light-emitting diodes (LEDs) to indicate their status.

Each switch is assigned two (2) LEDs, as well as a label to indicate the switch's programmed usage. The label slides behind a clear protective membrane. One of the

LEDs assigned to each switch is a dual-colored LED, which is used to indicate what type of signal is active.

FireFinder XLS Components

─ (cont.’d)

Each Model SCM-8 switch is fully programmable, and may be used to control speaker circuits and a wide range of general-system functions such as: All Call, All Evac,

Warden's Page, Speaker, etc. Any number of circuits may be grouped and controlled by a single switch. Switch usages and zone groupings are assigned using the Zeus system software-programming software. Model SCM-8 modules are mounted on a hinged panel, as a part of the

FireFinder XLS Command Console enclosure.

PSC-12 Power Supply Charger Module

The Power Supply Charger Module (Model PSC-12) is a high-current power supply that provides the FireFinder

XLS primary-regulated 24VDC power to operate. Model

PSC-12 is rated at 12Amps (Alarm) / 5Amps (Standby), and has a built-in battery charger, capable of charging up to 100

AH batteries. Model PSC-12 is an addressable-intelligent, microprocessor-controlled module that communicates its status to the system-operator interface (PMI). Model PMI is able to query the status of the power supply to obtain information regarding system-charging current, terminalloading information, ground-fault conditions and more.

LCM-8 LED Control Module

LCM-8 LED Control Module

The LED Control Module (Model LCM-8) is a FireFinder

XLS-option module that provides LED annunciation for

FireFinder XLS system activity. Each LCM-8 module contains eight (8) groups of two (2) LEDs – each of which can be assigned to desired outputs using the Zeus system software-programming tool.

Eight (8) LEDs are dual-color capable ( RED or GREEN /

flashing or steady). The remaining LEDs are AMBER

flashing or steady. A space is provided for labeling of LED functions. The label slides behind a clear, protective membrane. Model LCM-8 dimensions are identical to

Model SCM-8, and Model LCM-8 is mounted on the same hinged panel, as a part of the FireFinder XLS Command

Console enclosure.

FCM-6 Fan, Motor, Dampers

FCM-6 Fan, Motor, Dampers Control Module

The Fan, Motor, Dampers Control Module (Model FCM-6) is a

FireFinder XLS command-console option module that provides manual control of building HVAC system fans, motors, and dampers. Each Model FCM-6 module provides six (6) sets of three (3) push-button switches for manualsystem control. Each switch has three (3), associated

LEDs to indicate Fan / Damper / Motor status: OFF ( Red LED),

ON ( Green LED), TROUBLE ( Yellow LED).

PTB Power Termination Board

PTB Power Termination Board

Model PSC-12 comes packaged with a module called the

Power Termination Board (Model PTB). Model PTB is required for operation with Model PSC-12. Model PTB filters the power from the incoming AC mains, and distributes it to the Model PSC-12 power supply and the optional Model

PSX-12 power-supply extender.

Model PTB has an optional connector that can be used during system installation, commissioning and service to provide the technician with a place to plug in their laptop PC, if required. Model AC-ADPT is an optional accessory cable that allows connection on one side to Model PTB, via a keyed connector and on the other end directly into to the laptop's transformer.

Most laptop-computer external power transformers have removable AC power cords, which can be replaced by the optional Model AC-ADPT to temporarily provide an AC power source for laptop-PC usage during system installation, service and maintenance calls when needed.

PSX-12 Power Supply Extender

PSX-12 Power Supply Extender

The Power Supply Extender (Model PSX-12) is a high-current, auxiliary power supply that expands the main Model PSC-12 power supply and battery charger of the FireFinder XLS system with an additional 24VDC power. Model PSX-12 is rated at 12 Amps.

PSC-12 Power Supply Charger Module s Industry, Inc.

Building Technologies Division

FireFinder XLS Components

─ (cont.’d)

RNI Remote Network Interface

RN

I

Remote Network Interface

The Remote Network Interface (Model RNI) provides a connection point for use with equipment mounted in a remote-lobby enclosure on the FireFinder XLS FACP.

Model RNI is used to provide additional input, output and control features to the system remotely, via the main control panel. These additional features may include control switches and indicators: (Models SCM-8, LCM-8 and

FCM-6), remote-emergency paging microphones or telephones: (Models LVM, FMT), or controls used in graphic annunciators (Models SIM16, OCM-16) or systemstatus display with the ability to acknowledge alarms,

silence audibles and reset the system (Model SSD-C-

REM). Model RNI allows Model PMI to be mounted in the

Model REMBOX2 or Model REMBOX4 remote lobby enclosure.

RPM Remote Printer Module

RPM Remote Printer Module

The Remote Printer Module (Model RPM) provides a means of connecting the FireFinder XLS system to a printer, such as Model PAL-1, for creating a hard copy of system status and configuration reports. Simultaneously, Model

RPM provides an output port that can be configured to communicate with external systems.

Models SSD-C and SSD-C-INT have an integral keyswitch that enables these control buttons to operate.

Model SSD-C-REM is located within a locked cabinet.

Hence, no additional keyswitch is required for enabling the control buttons.

CAB1 Single Row Enclosure

CAB1 Single Row Enclosure

Model CAB 1, the smallest of the FireFinder XLS enclosures, can house a single Model CAB-MP cabinet mounting plate for mounting card cages, power supplies and bulk amplifiers. Model CAB1 also has four (4) mounting slots on the inner door for mounting Model PM I and Model I D-MP switch module brackets.

Model CAB1 comes complete with a black back box; black inner and outer doors; a single lock and key set on the outer door; a single, installed cabinet mounting plate (Model

CAB-MP), and a single, installed outer door lens plate

(Model OD-LP). A red version (Model CAB1R ) is also available – approximate size: 27" (68.6cm.) high, 26"

(66cm.) wide, and 8" (20.3cm.) deep.

System-Status Display

SSD-Series System-Status Display

The System Status Display (SSD-series model displays) is a remote LED / LCD display that shows the local status of a

FireFinder XLS system. An LED illuminates when Alarm,

Supervisory, Trouble, and Security events occur on the system. A (4) four-line liquid-crystal display (LCD) will give details of the event in alphanumeric form.

The display can be toggled to display additional events.

Optional remote system control capabilities are available.

Models SSD-C, SSD-C-INT, and Model SSD-C-REM have three

(3) additional control buttons to acknowledge events,

silence audible circuits, and reset the system. s Industry, Inc.

Building Technologies Division

MDACT - Multi-Point Digital Alarm

Communicator Transmitter

MDACT - Multi-Point Digital Alarm Communicator

Transmitter

The Multi-Point Digital Alarm Communicator Transmitter

(Model MDACT) is used in FireFinder XLS systems where point identification of Alarm, Supervisory, Security and

Trouble events is required at Central or Remote Receiving

Stations. An intelligent RS-485 communications protocol transmits all system information to Model MDACT.

The installer selects the specific event or groups of events that are set to transmit from Model MDACT over phone lines to listed receiving station equipment. In turn, Model MDACT can transmit point information, via the

Ademco Contact ID and the SIA protocol. A Mounting Plate

(Model MOM2-XMP), MOM-2 card cage, and an XMI

Interface Card are required for installation.

FireFinder XLS Components

─ (cont.’d)

TSP-40A Thermal Strip Printer

TSP-40A Thermal Strip Printer

The thermal strip printer (Model TSP-40A) is designed for use with the FireFinder XLS system. Model TSP-40A acts as an event-logging device, providing a permanent history report of all system activity. Model TSP-40A mounts in the FireFinder XLS Model CAB 1, Model CAB2 or Model CAB3 enclosure, and its printout is visible through a window in the locked-door enclosure. Printouts are automatically spooled onto a take-up reel for tidy, uniformed records storage.

CAB2 Two-Row Enclosure

CAB2 Two-Row Enclosure

The Two-Row Enclosure (Model CAB2) is the mid-sized

FireFinder XLS enclosure capable of housing up to two

(2) Model CAB-MP cabinet mounting plates. The inner door has two (2) rows of four (4) mounting slots. The outer door has space for mounting two (2) outer door plates (Models OD-LP, OD-BP or OD-GP). The outer door can be configured to open from either side. Model CAB2 consists of the Model CAB2-BB back box, the Model CAB2-

BD black inner and outer door package, and one (1) Model

OD-LP lens plate. The outer door has a single lock and key set installed. A red version (Model CAB2 R ) is also available.

Approximate size is 45” (114.3cm.) high, 26” (66cm.) wide, and 8” (20.3cm.) deep.

The outer door can be configured to open from either side. Model CAB3 consists of the Model CAB3-BB back box, the Model CAB3-BD black inner and outer door package, and one (1) Model OD-LP lens plate. The outer door has two (2) locks and key sets installed. A red version (Model

CAB3 R ) is also available. Approximate size is 63"

(160cm.) high, 26" (160cm.) wide, and 8" (20.3cm.) deep.

Enclosure Trim Kits

Trim kits are available for all system enclosures for semiflush mounting applications. Model CAB1-TK (for black enclosures) and the Model CAB1 R -TK (for red enclosures) fit inside the Models CAB1 and CAB1-R enclosures.

Similarly, Models CAB2-TK and CAB-2 R -TK fit inside the

Model CAB-2 enclosure, while Models CAB3-TK and CAB3 R -

TK fit the Model CAB-3 enclosure.

Remote Transponders

The FireFinder XLS system can use remote transponders for mounting additional modules such as amplifiers without requiring Model PMI or any control switches.

Special doors are available for systems using Model CAB-2 or Model CAB-3 remote transponders. These doors

(Models CAB2-XBD and CAB3-XBD) omit the unused inner door, and come complete with ventilation louvers built into the door.

Model CAB2-XBD fits into Model CAB2-BB, and Model

CAB3-XBD fits into Model CAB3-BB. Model CAB2-XBD and

CAB3-XBD are supplied in black. Red versions (Models

CAB2-X R D and CAB3-X R D) are also available. Complete box and door kits are available, Models CAB2-X and CAB3-X.

CAB-MP Cabinet Mounting Plate

CAB-MP Cabinet Mounting Plate

The Model CAB-MP cabinet mounting plate provides mounting for a single row of modules in a FireFinder XLS cabinet. Four (4) module spaces are available on Model

CAB-MP, which is used to mount the Model CC-5 card cage; the Model CC-2 card cage; the Model PSC-12 power supply; the Model PSX-12 power-supply extender, and the

Model ZAM-80 / 180-zone amplifiers.

CAB3 Three-Row Enclosure

CAB3 Three-Row Enclosure

Model CAB3, the single largest FireFinder XLS enclosure available, can house a maximum three (3)

Model CAB-MP cabinet mounting plates in the enclosure, and three (3) rows of inner-door mounting slots. s Industry, Inc.

Building Technologies Division

I

D-MP Inner Door Mounting Plate

FireFinder XLS Components

─ (cont.’d)

I

D-MP Inner Door Mounting Plate

The inner door mounting plate (Model I D-MP) is mounted on the inner door of any given model CAB enclosure. Model I D-MP plates are used to mount switch-control modules (Model SCM-8); LED control modules (Model LCM-8), or fan-control modules (Model

FCM-6).

Four (4) mounting plates are included in each Model I D-

MP. Each mounting plate has four (4) spaces for control modules, and can hold either four (4) Model SCM-8 modules (one [1] control module space for each module); four (4) LCM-8 (one [1]control module space for each module), or two (2) Model FCM-6 modules (two

[2] module spaces for each module).

Combinations are also allowed. Blank spaces in Model I D-

MP can be covered using the blank-control-module plate (Model BCM). Up to four (4) Model I D-MP modules can be mounted in a single row on the inner door.

OD-LP Outer Door Lens Plate

OD-LP Outer Door Lens Plate

The Outer Door Lens Plate (Model OD-LP) is a clear plastic lens plate mounted on the outer door of a system cabinet. It is used to allow operators to see the system interface and controls mounted on the inner door, but restricts access to unauthorized users. It covers an entire row on the outer door. A single lens plate is included with each OD-LP.

OD-BP Outer Door Blank Plate

OD-BP Outer Door Blank Plate

The Outer Door Blank Plate (Model OD-BP) is used to cover an entire row on the outer door of a system cabinet. It is used when there is no PMI or control modules mounted on the adjacent row of the inner door.

A single, blank plate is included in each Model OD-BP.

I

D-SP Inner Door Blank Single Plate

I

D-SP Inner Door, Blank Single Plate

The inner door, blank single plate (Model I D-SP) is used to cover any single-module blank spaces on the inner door not used to mount Model PMI or Model I D-MP. Up to four (4) Model I D-SP modules can be mounted in a single row on the inner door. Two (2) blank plates are included in each Model I D-SP.

I

D-FP Inner Door Full-Blank Plate

Model I D-FP is a blank plate that covers the full opening of the row on an inner door, and is used for applications requiring full, dead-front protection. A single, full blank plate is included in Model I D-FP.

BCM Blank Control Module Plate

BCM Blank Control-Module Plate

Model BCM plates can be mounted on a single I D-MP.

Four (4) blank module plates are included in each

Model BCM.

OD-GP Outer Door Grill Plate

OD-GP Outer Door Grill Plate

The Outer Door Grill Plate (Model OD-GP) also covers an entire row on the outer door of a system cabinet, but has four rows of ventilation louvers on it. The OD-GP is mounted in front of system bulk amplifiers, card amplifiers, or other modules that generate heat. Using the

OD-GP will permit airflow across these modules to aid in heat dissipation. A single grill plate is included with each OG-GP.

Remote System Enclosures

Models REMBOX2 and REMBOX4 are FireFinder XLS system enclosures that are used for remotely mounting inner-door modules like the Model PMI interface, switch modules, Model LVM live voice modules, and Model FMT firefighters master telephone modules. Models REMBOX2 and REMBOX4 are thinner than the regular CAB series of enclosures – just 5" (12.7cm.) deep overall, and are perfect for mounting in places where space is limited (e.g. – officecomplex lobbies or behind a receptionist's desk). s Industry, Inc.

Building Technologies Division

FireFinder XLS Components

─ (cont.’d)

No card cages, power supplies or bulk amplifiers can be mounted in a given REMBOX because of their smaller depth. However, Model PMI and modules (e.g. – the remote network interface module [Model RNI], the output control module [Model OCM-16], and the supervised input module [Model SIM-16]) can be mounted in a given REMBOX.

Due to the depth of the live voice module and the firefighters’ master telephone, no Model OCM-16 or Model

SIM-16 modules can be used simultaneously with Model

LVM or Model FMT. The REMBOX2 and the REMBOX4 are designed for flush mounting with no trim kit required.

Both enclosures also come with a clear lens plate on the cover.

A bracket known as Model REMBOX4-MP can be used to mount up to eight (8) output control modules (Model

OCM-16) or supervised input modules (SIM-16). The

REMBOX4-MP must be purchased separately.

Approximate size of the REMBOX4 is 24" (61cm.) wide,

18-1/2" (47cm.) high and 5" (12.7cm.) deep.

NRC Network Ring Card

NRC Network Ring Card

Model NRC (FM approval pending) provides XNET, peer-topeer communication between FireFinder XLS systems. One

(1) Model NRC is required for each XLS panel, in order to allow FireFinder XLS nodes to be wired in a Class A, Style 7 ring topology.

REMBOX2 Two Module Remote Enclosures

REMBOX2 Two Module Remote Enclosures

REMBOX2 has two (2) inner-door module spaces, and can hold a single Model PMI, up to two (2) switch module brackets and one (1) Model LVM. Combinations are also allowed.

REMBOX2 can also mount a single RNI remote network interface on a bracket included in the backbox. A bracket called the REMBOX2-MP can be used to mount up to four

OCM-16 output control modules or SIM-16 supervised input modules. Model REMBOX2-MP must be purchased separately. Approximate size of REMBOX2 is 14-1/2"

(36.8cm.) wide, 18-1/2" (47cm.) high and 5" (12.7cm.) deep.

NCC-G - Network Color Graphics

NCC-G - Network Color Graphics

Model NCC-G is a PC-based, color-graphics command center designed for use with the XNET network, and provides full control and annunciation for a XNET network for a maximum 63 XLS, MXL-IQ or MXL systems. The NCC-G is used to monitor and control alarms, troubles, security, supervisory and all system events from one of many XLS systems.

Model NCC-G maintains an extensive history log of all system events and has extensive report generation capabilities. User programmable function buttons allow site specific control functions. Multiple NCC-Gs may be connected to XNET network. Each NCC-G ordered separately.

REMBOX4 Four-Module Remote Enclosures

REMBOX4 Four-Module Remote Enclosures

Model REMBOX4 has space for mounting four (4) innerdoor modules. Any combination of Model PMI (twomodule spaces); switch module brackets; Model LVM, or Model FMT (one-module space each) can be used.

Unused module spaces can be covered with Model ID-SP blank plates. The REMBOX4 can also mount a single remote network interface (Model RNI) on a bracket included in the backbox. s Industry, Inc.

Building Technologies Division

MLC - MXL Line Card [for FireFinder XLS]

FireFinder XLS Components

─ (cont.’d)

MLC - MXL Line Card [for FireFinder XLS]

The MXL Line Card (Model MLC) is an optional card for the FireFinder XLS panel that supplies two (2) intelligent analog circuits, utilizing the Model ‘ I ‘ series;

Model ‘ ID ‘ series; Model ‘ IL ‘ series or Model ‘ FP ‘ seriestype intelligent devices. Model MLC occupies two (2) addresses on the HNET network, and devices connected to the Model MLC circuits are dynamically supervised by

FireFinder XLS through the use of a unique communications protocol.

XLS-MLE6-ADPT

XLS-MLE6/ R -ADPT − XLS MLE-6/ R Enclosure Adapter

Model XLS-MLE6-ADPT, which must be used in conjunction with Model CAB-MP, is an adapter that allows FireFinder XLS cards to be mounted in oldergeneration MXL Model MLE-6 large black enclosures.

Model XLS-MLE6 R -ADPT, which must be used in conjunction with Model CAB-MP, is an adapter that allows FireFinder XLS cards to be mounted in oldergeneration MXL MLE-6 R large red enclosures.

XLS-MSE2-ADPT

XLS-MSE2/ R -ADPT − XLS MSE-2/ R Enclosure Adapter

Model XLS-MSE2-ADPT, which must be used in conjunction with Model CAB-MP, is an adapter that allows FireFinder XLS cards to be mounted in oldergeneration MXL Model MSE-2 small black enclosures.

Model XLS-MSE2 R -ADPT, which must be used in conjunction with Model CAB-MP, is an adapter that allows FireFinder XLS cards to be mounted in oldergeneration MXL Model MSE-2 R small red enclosures.

XLS-MSE3-ADPT

XLS-MSE3/ R -ADPT − XLS MSE-3L/ R or MSE-3M/ R

Model XLS-MSE3-ADPT is an adapter that allows

FireFinder XLS cards to be mounted in oldergeneration MXL-IQ Model MSE-3L or Model MSE-3M black enclosure.

Model XLS-MSE3 R -ADPT is an adapter that allows

FireFinder XLS cards to be mounted in older- generation MXL-IQ Model MSE-3L R or Model MSE-3M R red enclosure.

XLS-MME3-ADPT

XLS-MME3/ R -ADPT − XLS MME-3/ R or MBR-2

Model XLS-MME3-ADPT, which must be used in conjunction with Model CAB-MP, is an adapter that allows FireFinder XLS cards to be mounted in older- generation MXL Model MME-3 or Model MBR-2 medium black enclosures.

Model XLS-MME3 R -ADPT, which must be used in conjunction with Model CAB-MP, is an adapter that allows FireFinder XLS cards to be mounted in oldergeneration MXL Model MME-3 R medium red enclosures.

XLS-RCC1-ADPT

XLS-RCC-1-ADPT − XLS RCC-1 Enclosure Adapter

Model XLS-RCC1-ADPT is an adapter that allows the

FireFinder XLS Model SSD/-C series remote annunciator to be mounted in older-generation Model RCC-1 surfacemount enclosure.

XLS-RCC13F-ADPT s Industry, Inc.

Building Technologies Division

FireFinder XLS Components

─ (cont.’d)

XLS-RCC13F/ R -ADPT − XLS RCC-1F/ R or RCC-3F/ R

Model XLS-RCC13F-ADPT is an adapter that allows the

FireFinder XLS Model SSD/-C series remote annunciator to be mounted in older-generation Model RCC-1F or Model

RCC-3F black, flush-mount enclosure.

Model XLS-RCC13F R -ADPT is an adapter that allows the

Model SSD/-C series to be mounted in older-generation

RCC-1F R and RCC-3F R , red flush-mount enclosure.

Details for Ordering

Model

Number

Part

Number

Description

── 599-050092 PMI and GPMI

AC-ADPT 500-633992

CAB-1

CAB-1R

[four (4) per package]

500-633007 Complete single-row cabinet, black

500-633728 Complete single-row cabinet, red

CAB1-TK 500-633013 Single-row trim-kit cabinet, black

CAB1 R -TK 500-633729 Single-row trim-kit cabinet, red

CAB2-BB 500-633009 (2) Two-row back box, black

CAB2R B

CAB2-BD

500-634941 (2) Two-row back box, red

500-633008 (2) Two-row inner & outer door set, black

CAB2R D

CAB2-TK

500-633755 (2) Two-row inner & outer door set, red

500-633014 (2) Two-row trim-kit cabinet, black

CAB2 R -TK 500-633753 (2) Two-row trim-kit cabinet, red

CAB2-XBD 599-633768 CAB2 transponder door

CAB2-X R D 500-633792 red

CAB3-BB

[mounts to CAB2R B]

500-633011 (3) Three-row back box, black

CAB3R B 500-634942 (3) Three-row back box, red

Details for Ordering ─ (continued)

Model

Number

Part

Number

Description

LCM-8 500-033100

[used for FireFinder XLS]

Mounting plate for Model MOM-2

MOM2-XMP 500-634822

[used for FireFinder XLS]

MXL module card cage

MOM-2 500-892766

NIC-C

[one (1) full slot]

500-033240 Network

NRC

OD-BP

OD-BPR

500-050337 Network ring card

500-633017 Outer door blank plate

500-634919 Outer door blank plate, red

OD-GPR

OD-GP

500-634920 Outer door grill plate, red

500-633018 Outer door grill plate

OD-LP 500-633016 Outer door lens plate

PAL-1 500-692407

PMI 500-033070 Person machine interface

PMI-INT 500-034160

Person machine interface

[with multi-lingual overlays]

PSC-12 500-033340

[12A @ 24VDC]

[12A @ 24VDC]

PTB 500-033390 Power termination board

(2) Two-module remote lobby enclosure, black

REMBOX2 R 500-650612 (2) Two-module remote lobby enclosure, red

REMBOX2-MP 500-634211

Mounting plate for Models

OCM-16 / SIM-16 in Model REMBOX2

REMBOX4 500-633914 (4) Four-module remote lobby enclosure, black

REMBOX4-MP 500-634212

Mounting plate for Models OCM-16 /

SIM-16 in Model REMBOX4

REMBOX4 R 500-650613 Four-module red

RNI

RPM

500-033420 Remote network interface module

500-033270 Remote printer module

SIM-16 500-034060 Supervised input module

CAB3R D

CAB3-TK

500-633757 (3) Three-row inner & outer door set, red

500-633015 (3) Three-row trim-kit cabinet, black

CAB3 R -TK 500-633754 (3) Three-row trim-kit cabinet, red

CAB3-XBD 599-633769 CAB3 transponder door

SSD-C 500-648733 System-status display with control

SSD-INT 500-034740 System-status display with multi-lingual overlays

SSD-C-INT 500-034750

SSD-C-REM 500-634773

System-status display with control and multilingual overlays

System-status display with control for remote lobby enclosure

CAB3-X R D 500-633793 red

CAB-MP

[mounts to CAB3R B]

500-633012 Back box module mounting plate

CAN Cable

3 ft. (91.4 cm.) Length required for:

CCL 599-634214

I nner Doors and from Row-to-Row on

CC-2

Model CAB-series Inner Doors

500-633440 Two (2) slot card cage

CC-5 500-633037 Five (5) slot card cage

CDC-4

CSB

500-034200 Conventional detector card

Controllable card

500-033130 CAN Sounder Board

FCM-6 500-033140

GPMI-UK 500-650066

Software-upgrade kit for PMI

{to allow global functionality}

HLIM

I D-FP 500-633029 (4) Four module inner-door blank plate

I

I

D-MP 500-633027

Inner-door enclosure mounting plate,

[four (4) per package] mounting plate,

[two (2) per package] s Industry, Inc.

Building Technologies Division

TSP-XB

TSP-XC

XLS-MLE6-ADPT

XLS-MLE6 R ADPT

XLS-MME3-ADPT

XLS-MME3 R -ADPT

XLS-MSE2-ADPT

XLS-MSE2 R -ADPT

500-849949 Brackets for thermal-strip printer

500-849950 Cables for thermal-strip printer

S54430-C9-A1 MLE-6 enclosure adapter for XLS, black

S54430-C9-A2 MLE-6 R enclosure adapter for XLS, red

S54430-C8-A1

MME-3 and MBR-2 enclosure adapters for

FireFinder XLS, black

S54430-C8-A2 MME-3 R enclosure adapter for XLS, red

S54430-C7-A1 MSE-2 enclosure adapter for XLS, black

S54430-C7-A2 MSE-2 R enclosure adapter for XLS, red

XLS-MSE3-ADPT

XLS-MSE3 R -ADPT

S54430-C14-A1

S54430-C14-A2

MXL-IQ MSE-3L and MSE-3M enclosure adapters for

XLS, black

MXLI Q MSE-3L R & MSE-3M R enclosure adapters for XLS, red

XLS-RCC1-ADPT S54430-Z14-A1 RCC-1enclosure adapter for XLS-SSD, black

XLS-RCC13F-ADPT S54430-Z13-A1 RCC-1F & RCC-3F enclosure adapters, black

XLS RCC13F R ADPT

ZIC-2C

ZIC-4A

ZIC-8B

S54430-Z13-A2 RCC-1F R & RCC-3F R enclosure adapters, red

500-648671 (2) Two-channel adapter card, (ZIC-8B)

500-033050 (4) Four-circuit zone indicating card

500-648670 (8) Eight-circuit zone indicating card

Note: Products are UL 864 9 th Edition Listed for indoor dry locations within a temperature range of 120+/-3°F

(49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative humidity of 93+/-2% at a temperature of 90+/-3°F (32+/-2°C).

Notice: This marketing data sheet is not intended to be used for system design or installation purposes.

For the most up-to-date information, refer to each product’s installation instructions.

s Industry, Inc.

Building Technologies Division

Fire Safety

8 Fernwood Road

Florham Park, NJ 07932

Tel: (973) 593-2600

FAX: (908) 547-6877

URL: www.SBT.Siemens.com/FIS

(SII‐FS)

Printed in U.S.A. 

 

Fire Safety

2 Kenview Boulevard

Brampton, Ontario

L6T 5E4 / Canada

Tel: (905) 799-9937

FAX: (905) 799-9858

October 2011

Supersedes sheet dated 8/11

(Rev. 7)