Bard W42A2-A00 The Wall Mount™ 3.5 Tons Electric Vertical Packaged Air Conditioner Installation instructions


Add to my manuals
26 Pages

advertisement

Bard W42A2-A00 The Wall Mount™ 3.5 Tons Electric Vertical Packaged Air Conditioner Installation instructions | Manualzz

INSTALLATION INSTRUCTIONS

WALL MOUNTED

PACKAGE AIR CONDITIONERS

MODELS

W17A2 W17L2

W18A2 W18L2

W24A2 W24L2

W30A2 W30L2

W36A2 W36L2

W42A2 W42L2

W48A2 W48L2

W60A2 W60L2

W70A2 W70L2

Bard Manufacturing Company, Inc.

Bryan, Ohio 43506

Since 1914...Moving ahead just as planned.

Manual : 2100-581C

Supersedes: 2100-581B

File: Volume III Tab 16

Date: 06-19-14

Manual 2100-581C

Page 1 of 26

Contents

Getting Other Information and Publications 3

Wall Mount General Information

Wall Mount Model Nomenclature .............................. 4

Shipping Damage ..................................................... 4

General ................................................................. 4

Duct Work ................................................................. 5

Filters ................................................................. 5

Fresh Air Intake ......................................................... 5

Condensate Drain .................................................... 5

Installation Instructions

Wall Mounting Information ........................................ 6

Mounting the Unit ...................................................... 6

Clearances Required ................................................ 6

Minimum Clearances ................................................ 6

Wiring – Main Power ............................................... 14

Wiring – Low Voltage Wiring ................................... 14

Start Up

General ............................................................... 15

Topping Off System Charge .................................... 15

Safety Practices ...................................................... 15

Important Installer Note ........................................... 16

High Pressure Switch .............................................. 16

Three Phase Scroll Compressor ............................. 16

Phase Monitor ......................................................... 16

Condenser Fan Operation ...................................... 16

Service Hints ........................................................... 16

Sequence of Operation ........................................... 17

Compressor Control Module ................................... 17

Adjustments ............................................................ 17

Pressure Service Ports ........................................... 17

Troubleshooting

Fan Blade Setting Dimensions ................................ 18

R-410A Refrigerant Charge .................................... 18

Removal of Fan Shroud .......................................... 18

Figures

Figure 1 Fresh Air Damper Assembly ..................... 5

Figure 2 Unit Dimensions ....................................... 7

Figure 3A Mounting Instructions ............................... 8

Figure 3B Mounting Instructions - W17 – 36 ................

9

Figure 3C Mounting Instructions - W42, 48, 60, 70 .... 10

Figure 4 Electric Heat Clearance ......................... 11

Figure 5 Wall Mounting Instructions ..................... 12

Figure 6 Wall Mounting Instructions ..................... 12

Figure 7 Common Wall Mounting Installations ..... 13

Figure 8 Fan Blade Setting ................................... 18

Tables

Table 1 Fan Blade Dimensions ........................... 18

Table 2 Cooling Pressure .................................... 19

Table 3 Electrical Specifications W**A ................ 20

Table 4 Electrical Specifications W**L ................ 21

Table 5 Recommended Airflow ........................... 22

Table 6 Indoor Blower Performance ................... 22

Table 7 Maximum ESP Electric Heat Only .......... 22

Table 8 Electric Heat ........................................... 23

Table 9A Optional Accessories — Right Hand ...... 24

Table 9B Optional Accessories — Left Hand ............25

Table 10 Vent & Control Options ........................... 26

Manual 2100-581C

Page 2 of 26

GETTING OTHER INFORMATION AND PUBLICATIONS

These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.

National Electrical Code ....................... ANSI/NFPA 70

FOR MORE INFORMATION, CONTACT

THESE PUBLISHERS:

ACCA Air Conditioning Contractors of America

1712 New Hampshire Ave. N.W.

Washington, DC 20009

Telephone: (202) 483-9370

Fax: (202) 234-4721

Standard for the Installation ............... ANSI/NFPA 90A of Air Conditioning and Ventilating Systems

Standard for Warm Air ....................... ANSI/NFPA 90B

Heating and Air Conditioning Systems

ANSI American National Standards Institute

11 West Street, 13th Floor

New York, NY 10036

Telephone: (212) 642-4900

Fax: (212) 302-1286

Load Calculation for ......................... ACCA Manual J

Residential Winter and Summer Air Conditioning

Duct Design for Residential ............... ACCA Manual D

Winter and Summer Air Conditioning and Equipment

Selection

ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.

1791 Tullie Circle, N.E.

Atlanta, GA 30329-2305

Telephone: (404) 636-8400

Fax: (404) 321-5478

NFPA National Fire Protection Association

Batterymarch Park

P.O. Box 9101

Quincy, MA 02269-9901

Telephone: (800) 344-3555

Fax: (617) 984-7057

Manual 2100-581C

Page 3 of 26

WALL MOUNT GENERAL INFORMATION

AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE

W 42 A 2 – A 10

MODEL NUMBER

CAPACITY

17 - 1½ Ton

18 - 1½ Ton

24 - 2 Ton

30 - 2½ Ton

36 - 3 Ton

42 - 3½ Ton

48 - 4 Ton

60 - 5 Ton

70 - 6 Ton

REVISIONS

VOLTS & PHASE

A - 230/208/60/1

B - 230/208/60/3

C - 460/60/3

A - Right Hand Air Conditioner

L - Left Hand Air Conditioner

KW

VENTILATION OPTIONS

X - Barometric Fresh Air Damper (Standard)

B - Blank-off Plate

M - Motorized Fresh Air Damper

V - Commercial Ventilator - Motorized with Exhaust

R - Energy Recovery Ventilator - Motorized with Exhaust

(See Spec. Sheet S3397)

S - Economizer - School Versions, Enthalpy

W - Economizer - Equipment Building, Enthalpy

T - Economizer - Equipment Building, DB Temp.

X X X X X A

CONTROL MODULES

(See Spec. Sheet S3397)

COLOR OPTIONS

X - Beige (Standard)

1 - White

4 - Buckeye Gray

5 - Desert Brown

6 - Dark Bronze

A - Aluminum

S - Stainless Steel

COIL OPTIONS

X - Standard

1 - Phenolic Coated Evaporator

2 - Phenolic Coated Condenser

3 - Phenolic Coated Evaporator

and Condenser

OUTLET OPTIONS

X - Front (Standard)

T - Top Outlet (W30A, W36A Only)

FILTER OPTIONS

X - One Inch Throwaway (Standard)

W - One Inch Washable

P - Two Inch Pleated

NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in building.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.

This appliance is not intended for use by persons

(including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

Children should be supervised to ensure that they do not play with the appliance.

The refrigerant system is completely assembled and charged. All internal wiring is complete.

The unit is designed for use with or without duct work.

Flanges are provided for attaching the supply and return ducts.

These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.

These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting

Procedure” and any tags and/or labels attached to the equipment.

While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.

Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA).

The air duct should be installed in accordance with the

Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating

Systems of Other Than Residence Type, NFPA No.

90A, and Residence Type Warm Air Heating and Air

Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.

Manual 2100-581C

Page 4 of 26

DUCT WORK

All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment.

Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.

Refer to Maximum ESP of operation Electric Heat Table 7.

Design the duct work according to methods given by the Air

Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.

Models W17 - W24 as approved for zero inch clearance to the supply duct. For model series W30, W36, W42, W48,

W60 and W70 a 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 4 for further details.

Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.

Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.

Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit

RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.

NOTE: If no return air duct is used, applicable installation codes may limit this cabinet to installation only in a single story structure.

FILTERS

A 1-inch throwaway filter is standard with each unit.

The filter slides into position making it easy to service.

This filter can be serviced from the outside by removing the filter access panel. A 1-inch washable filter and

2-inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2-inch filter by bending two (2) tabs down on each side of the filter support bracket.

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in the service door.

If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit.

The damper blade is locked in the closed position.

To allow the damper to operate, the maximum and minimum blade position stops must be installed. See

Figure 1.

All capacity, efficiency and cost of operation information is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency.

The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.

FIGURE 1

FRESH AIR DAMPER

Manual 2100-581C

Page 5 of 26

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3.

2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.

3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.

2. The unit itself is suitable for 0 inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material for model series

W30, W36, W42, W48, W60 and W70. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material. See

Figure 3 for details on opening sizes.

3. Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 3.

4. Mount bottom mounting bracket.

5. Hook top rain flashing, attached to front - right of supply flange for shipping, under back bend of top.

WARNING

Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death.

6. Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.

7. Secure rain flashing to wall and caulk across entire length of top. See Figure 3.

8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself

(depending upon wall construction). Be sure to observe required clearance if combustible wall.

9. On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.

Clearances Required for Service Access and Adequate Condenser Airflow

MODELS

LEFT

SIDE

RIGHT

SIDE

DISCHARGE

SIDE

W17A, W18A, W24A, W30A, W36A 15" 20" 10'

W17L, W18L, W24L, W30L, W36L

W42A, W48A, W60A, W70A

W42L, W48L, W60L, W70L

20"

20"

20"

15"

20"

20"

10'

10'

10'

NOTE: For side by side installation of two (2) W**A models there must be 20" between units. This can be reduced to 15" by using a

W**L model (left side compressor and controls) for the left unit and

WA (right side compressor and controls) for right unit.

See W**A Specification S3397 & W**L Specification S3400.

Minimum Clearances Required to

Combustible Materials

MODELS

W17A, L / W18A, L / W24A, L

SUPPLY AIR DUCT

FIRST THREE FEET CABINET

0" 0"

W30A, L / W36A, L

W42A, L / W48A, L

W60A, L / W70A, L

1/4"

1/4"

0"

0"

Manual 2100-581C

Page 6 of 26

FIGURE 2

Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)

DEPTH

(D)

HEIGHT

(H)

SUPPLY RETURN

A B C B E F G I J K L M N O P Q R S T

W17A, L

W18A, L

W24A, L

W30A, L

W36A, L

W42A, L

W48A, L

W60A, L

W70A, L

33.300

38.200

42.075

17.125

17.125

22.432

70.563

7.88 19.88 11.88 19.88 35.00 11.00 25.75 20.56 26.75 28.06 29.25 27.00 2.63 34.13 22.06 10.55 4.19

12.00

70.563

7.88 27.88 13.88 27.88 40.00 11.00 25.75 17.93 26.75 28.75 29.25 27.00 2.75 39.19 22.75 9.14

4.19

12.00

84.875

9.88 29.88 15.88 29.88 43.88 13.63 31.66 30.00 32.68 26.94 34.69 32.43 3.37 42.88 23.88 10.00 1.44

16.00

5.00

5.00

1.88

All dimensions are in inches. Dimensional drawings are not to scale.

W**A

RIGHT

UNIT

W

Built In

Rain Hood

4° Pitch

Heater

Access

Panel

C. Breaker/

Disconnect

Access Panel

(Lockable)

Hood for ERV and

ECONWMS models only

D

7.88

1

1.250

1

1.00

2.13

A

I

Side Wall

Mounting

Brackets

(Built In)

Shipping

Location

E

O

31.88

1

Supply Air Opening

B

.44

R

S

S

5.88

Filter Access Panel

Optional

C H Return Air Opening S

F

G

Ventilation Air

Condenser

Air Outlet flush vent door for

3"

Econ.

models

11"

Hood for models.

Low Voltage

High Voltage

Cond.

Air

Inlet

J

K

L

M

P

S

S

T

Drain N

Front View Side View Q Back View

MIS-2487 H j Optional top outlet (factory installed only) for W30A and W36A models only.

W**L

LEFT

UNIT

R

S

S

.44

E

O

Supply Air Opening

B

Mounting

(Built In)

2.13

A

Built In

4° Pitch

D

I

1.250

Heater

C. Breaker/

Disconnect

Access Panel

(Lockable)

Standard flush

Hood used on

ECONWMS only

W

Filter Access Panel 1 5.88

S

Return Air Opening

Optional

Entrances

C

3"

Ventilation Air F

S

H

S P

M

L K

J

Cond.

Air

Inlet

11"

Hood for

ECONWMT models.

Low Voltage

Condenser

Air Outlet

G

T

Drain Bottom

Installation

Back View

Q

N Side View Entrance Front View

MIS-3124 B

Manual 2100-581C

Page 7 of 26

Manual 2100-581C

Page 8 of 26

1 16

1 16

13 16

1 2

1 8

4" Ty

7 8

4" Ty

7 8

11 16

1 8

4" Ty

7 8

7 8

4" Ty

7 8

1 16

11 16

Manual 2100-581C

Page 9 of 26

Manual 2100-581C

Page 10 of 26

1 2

7 8

1 8

4" Ty

1 8

1 2

4" Ty

1 2

7 8

FIGURE 4

ELECTRIC HEAT CLEARANCE

W30A2, W30L2, W36A2, W36L2, W42A2, W42L2, W48A2, W48L2, W60A2, W60L2, W70A2, W70L2

NOTE 1: SIDE SECTION VIEW OF SUPPLY AIR

DUCT FOR WALL MOUNTED UNIT SHOWING 1/4

INCH CLEARANCE TO COMBUSTIBLE SURFACES.

WARNING

A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting.

It is important to insure that the 1/4 inch minimum spacing is maintained at all points.

Failure to do this could result in overheating the combustible material and may result in a fire causing damage, injury or death.

Manual 2100-581C

Page 11 of 26

FIGURE 5

WALL MOUNTING INSTRUCTIONS

SEE FIGURE 3 – MOUNTING INSTRUCTIONS

FACTORY SUPPLIED

RAIN FLASHING.

MOUNT ON UNIT

BEFORE INSTALLATION

WALL STRUCTURE

SUPPLY AIR

OPENING

SUPPLY AIR

DUCT

RETURN AIR

OPENING

RETURN AIR

OPENING

RETURN AIR

OPENING

WOOD OR STEEL SIDING

BOTTOM MOUNTING

INSTALLING UNIT.

SIDE VIEW MIS-548 A CONCRETE BLOCK WALL INSTALLATION

MIS-549 B

Manual 2100-581C

Page 12 of 26

WOOD FRAME WALL INSTALLATION

FIGURE 6

WALL MOUNTING INSTRUCTIONS

ATTACH TO TOP

PLATE OF WALL

SEE UNIT DIMENSIONS, FIGURE 2,

FOR ACTUAL DIMENSIONS.

E + 1.000

B

1.000

1.000" CLEARANCE

ALL AROUND DUCT

INTERIOR FINISHED WALL

OVER FRAME

1.000" CLEARANCE

ALL AROUND DUCT

SUPPLY DUCT

OPENING

A

I

RETURN DUCT

OPENING

C

EXTERIOR FINISH WALL

OVER FRAME

K

2 x 6

C L

FRAMING MATERIAL

2 x 4'S, 2 x 6'S &/OR

STRUCTURAL STEEL

ATTACH TO BOTTOM

PLATE OF WALL

THIS STRUCTURAL MEMBER

LOCATED TO MATCH STUD

SPACING FOR REST OF WALL.

A SECOND MEMBER MAY BE

REQUIRED FOR SOME WALLS.

FIGURE 7

COMMON WALL MOUNTING INSTALLATIONS

OUTSIDE

WALL

RAFTERS

FINISHED CEILING SURFACE

SUPPLY AIR DUCT

W/ GRILLE

RETURN AIR

OPENING W/ GRILLE

OUTSIDE

WALL

FREE AIR FLOW

NO DUCT

SUPPLY DUCT MAY BE LOCATED IN AN ATTIC

OR BELOW CEILING RAFTERS AS SHOWN

RAFTERS

SUPPLY AIR DUCT

FINISHED CEILING SURFACE

RETURN AIR

OPENING W/ GRILLE

DUCTED SUPPLY

RETURN AT UNIT

SUPPLY DUCT MAYBE LOCATED IN AN ATTIC

OR BELOW CEILING RAFTERS AS SHOWN

RAIN

FLASHING

RAFTERS

SUPPLY AIR DUCT

RAIN

FLASHING

OUTSIDE

WALL

FINISHED

CEILING SURFACE

WALL SLEEVE

RETURN AIR

SPACE

FALSE WALL

RETURN AIR GRILLE

OUTSIDE

WALL

FALSE WALL INSTALLATION

SUPPLY DUCT MAYBE LOCATED IN AN ATTIC

OR BELOW CEILING RAFTERS AS SHOWN

RAFTERS

SUPPLY AIR DUCT

LOWERED

CEILING SUPPLY AIR

GRILLE

FINISHED CEILING

SURFACE

CLOSET WALL

WALL

SLEEVE

RAISED FLOOR

RETURN AIR

RETURN AIR

GRILLE

CLOSET INSTALLATION

MIS-550 B

Manual 2100-581C

Page 13 of 26

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum

Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current.

Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper

Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay

Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door.

When shut, a padlock may be placed through the hole in the tab preventing entry.

See “Start Up” section for important information on three phase scroll compressor start ups.

See Tables 3 & 4 for Electrical Specifications.

WIRING – LOW VOLTAGE WIRING

All 230/208V, 1 phase and 3 phase equipment have dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and

208V taps are:

TAP RANGE

240

208

253 – 216

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

For wiring size and connections, refer to Wiring

Manual 2100-582.

Manual 2100-581C

Page 14 of 26

THESE UNITS REQUIRE R-410A

REFRIGERANT AND POLYOL

ESTER OIL.

GENERAL:

1. Use separate service equipment to avoid cross contamination of oil and refrigerants.

2. Use recovery equipment rated for R-410A

refrigerant.

3. Use manifold gauges rated for R-410A (800 psi/250 psi low).

4. R-410A is a binary blend of HFC-32 and HFC-125.

5. R-410A is nearly azeotropic - similar to R-22 and

R-12. Although nearly azeotropic, charge with liquid refrigerant.

6. R-410A operates at 40-70% higher pressure than

R-22, and systems designed for R-22 cannot withstand this higher pressure.

7. R-410A has an ozone depletion potential of zero, but must be reclaimed due to its global warming

potential.

8. R-410A compressors use polyolester oil.

9. Polyol Ester oil is hygroscopic; it will rapidly absorb moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used - even a deep vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug compressor immediately after removal. Purge with small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard

Manufacturing recommends reclaiming, evacuating

(see criteria above), and charging to the nameplate charge. If done correctly, topping off the system charge can be done without problems.

With R-410A, there are no significant changes in the refrigerant composition during multiple leaks and recharges. R-410A refrigerant is close to being an azeotropic blend (it behaves like a pure compound or single component refrigerant). The remaining refrigerant charge, in the system, may be used after leaks have occurred and then “top-off” the charge by utilizing the pressure charts on the inner control panel cover as a guideline.

START UP

REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to ensure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction.

WARNING

Failure to conform to these practices could lead to damage, injury or death.

SAFETY PRACTICES:

1. Never mix R-410A with other refrigerants.

2. Use gloves and safety glasses, Polyol Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin.

3. Never use air and R-410A to leak check; the mixture may become flammable.

4. Do not inhale R-410A – the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death can result from breathing this concentration.

5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if

exposed.

6. Use only cylinders rated DOT4BA/4BW 400.

7. Never fill cylinders over 80% of total capacity.

8. Store cylinders in a cool area, out of direct

sunlight.

9. Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge lines or cylinders. R-410A expands significantly at warmer temperatures. Once a cylinder or line is full of liquid, any further rise in temperature will cause it to burst.

Manual 2100-581C

Page 15 of 26

START UP (Continued)

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil with a dish washing detergent.

HIGH PRESSURE SWITCH

All W**A/W**L wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on again.

THREE PHASE SCROLL COMPRESSOR

START UP INFORMATION

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.

However, three phase compressors will rotate in either direction depending upon phasing of the power.

Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made.

Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized.

Reverse rotation also results in an elevated sound level over that with correct rotation, as well as substantially reduced current draw compared to tabulated values.

Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time, there will be no negative impact on the durability of the compressor.

However, reverse operation for over one hour may have a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse rotation for an extended period of time, the compressor’s internal protector will trip.

All three phase compressors are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same

Fusite terminal should maintain proper rotation direction.

The direction of rotation of the compressor may be changed by reversing any two line connections to the unit.

PHASE MONITOR

All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two

LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.

CONDENSER FAN OPERATION

NOTE: Certain models may be equipped with a low ambient control (LAC), and if so equipped, the condenser fan motor will have delayed start until system refrigerant operating pressure builds up. After starting, the fan motor may or may not cycle depending upon ambient conditions. This is normal operation.

Applies to W42, W48, W60 and W70 models only. The condenser fan motor on 230/208 volt, one and three phase, 60 HZ units is a two-speed motor that comes factory wired on high speed for peak performance. If ambient conditions permit, it can be reconnected to low speed (red wire) for lower sound level. See wiring diagram.

50 HZ models must have fan wired on low speed.

These models are factory wired on low speed.

SERVICE HINTS

1. Caution owner/operator to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces airflow through the system, which shortens equipment service life as well as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

Manual 2100-581C

Page 16 of 26

SEQUENCE OF OPERATION

COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. (See NOTE under Condenser Fan

Operation if equipped with Low Ambient Control.) The

G (indoor motor) circuit is automatically completed by the thermostat on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. On a call for heating, circuit

R-W1 make at the thermostat pulling in heat contactor for the strip heat and blower operation. On a call for second stage heat, R-W2 makes bringing on second heat contactor, if so equipped.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on all models covered by this manual. The compressor control module is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or anytime power is interrupted to the unit, the delay on make period begins, which will be 2 minutes plus 10% of the delay on break setting.

When the delay on make is complete and the high pressure switch and low pressure switch is closed, the compressor contactor is energized. Upon shutdown, the delay on break timer starts and prevents restart until the delay on break and delay on make periods have expired.

During routine operation of the unit with no power interruptions, the compressor will operate on demand with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle, the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout

Sequence

If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds, the unit will go into manual lockout condition and the alarm relay circuit will energize.

Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever the compressor is locked out due to

HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner unit model. The lockout features, both soft and manual, are a function of the

Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break

Timer

The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay on Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute (30 seconds) DOB = 123 second DOM

1.0 minute (60 seconds) DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM

3.0 minute (180 seconds) DOB = 138 second DOM

4.0 minute (240 seconds) DOB = 144 second DOM

5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

Typical Settings for Dual Unit Installation:

Unit 1: DOB set at 2 minutes, and DOM is 132 seconds

Unit 2: DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.

See Table 2.

Manual 2100-581C

Page 17 of 26

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

Shown in Figure 8 is the correct fan blade setting for proper air delivery across the outdoor coil. Refer to

Table 1 for unit specific dimension.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 8

FAN BLADE SETTING

AIRFLOW

MIS-1724

"A"

R-410A

REFRIGERANT CHARGE

This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.

The following pressure tables show nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.

REMOVAL OF FAN SHROUD

1. Disconnect all power to the unit.

2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.

3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws.

4. Unwire condenser fan motor.

5. Slide complete motor, fan blade, and shroud assembly out the left side of the unit.

6. Service motor/fan as needed.

7. Reverse steps to reinstall.

TABLE 1

FAN BLADE DIMENSION

Model

Dimension

A

W17A2 / W17L2

W18A2 / W18L2

W24A2 / W24L2

W30A2 / W30L2

W36A2 / W36L2

W42A2 / W42L2

W48A2 / W48L2

W60A2 / W60L2

W70A2 / W70L2

1.00"

1.25"

1.75"

Manual 2100-581C

Page 18 of 26

TABLE 2

COOLING PRESSURE TABLE

Air Temperature Entering Outdoor Coil °F

Model

Return Air Temp

(DB/WB)

Pressure 75 80

W17A/L

W18A/L

W24A/L

W30A/L

W36A/L

W42A/L

W48A/L

W60A/L

W70A/L

75/62

80/67

85/72

75/62

80/67

85/72

75/62

80/67

85/72

75/62

80/67

85/72

75/62

80/67

85/72

75/62

80/67

85/72

75/62

80/67

85/72

75/62

80/67

85/72

75/62

80/67

85/72

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low Side

High Side

Low side pressure ± 4 PSIG

High side pressure ± 10 PSIG

125

364

129

377

122

346

131

355

120

339

128

348

132

360

123

320

132

328

131

361

122

335

130

344

135

356

136

326

141

337

119

340

127

349

124

321

133

329

138

341

127

318

137

339

117

355

136

367

118

349

126

358

130

371

127

388

131

402

124

371

133

380

122

366

130

375

135

388

124

342

133

351

134

383

124

358

133

367

138

380

138

348

143

360

121

361

129

370

126

340

135

349

140

361

129

339

138

363

119

378

138

393

121

371

129

381

134

394

85

134

466

139

482

130

447

139

458

129

446

138

457

143

473

130

416

139

427

141

459

131

431

140

442

145

457

144

419

149

434

127

432

136

443

132

409

141

419

146

434

135

409

144

442

125

454

144

474

125

444

134

455

139

471

132

438

137

453

128

421

137

432

126

418

135

429

140

444

128

391

137

401

138

432

129

406

138

416

143

431

142

395

147

409

124

407

133

417

130

384

139

394

144

408

133

385

142

415

123

427

142

447

123

419

132

430

137

445

129

413

134

427

126

396

135

406

124

392

133

402

138

416

126

367

135

376

136

407

127

381

136

391

141

405

140

371

145

384

122

383

131

393

128

362

137

371

142

384

131

362

140

389

121

403

140

420

122

395

131

405

136

419

90 95 100 105 110 115 120

Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge weight.

NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check condenser fan wiring. See “Condenser Fan Operation”.

Manual 2100-581C

Page 19 of 26

136

494

141

511

131

473

140

485

130

473

139

485

144

502

132

443

141

454

143

487

133

456

142

468

147

484

146

445

151

461

129

459

138

471

133

434

142

445

147

461

137

434

146

470

127

482

145

502

127

470

136

482

141

499

138

523

143

541

133

499

142

512

132

501

141

514

146

532

134

469

143

481

145

518

135

483

144

495

149

512

148

471

153

487

131

488

140

500

135

461

144

473

149

490

138

459

148

498

129

510

147

530

129

497

138

510

143

528

140

553

145

572

135

526

144

539

134

529

143

543

148

562

136

496

145

509

147

550

137

509

146

522

151

540

150

498

155

515

133

518

142

531

137

490

146

503

151

521

140

486

150

527

131

539

149

558

131

525

140

538

145

557

142

585

147

605

137

553

146

567

135

558

144

572

149

592

137

526

147

539

149

584

137

536

147

550

152

569

153

526

158

544

135

550

144

564

138

521

148

534

153

553

143

513

152

558

133

570

151

587

132

553

141

567

146

587

144

618

149

640

138

580

148

595

136

586

145

601

150

622

139

554

149

568

151

619

139

565

149

579

154

599

155

555

160

574

137

583

146

598

140

553

150

567

155

587

145

541

154

588

135

603

153

616

134

583

143

598

148

619

TABLE 3

Electrical Specifications — W**A Series

MODEL

B06*

B09*

B15

W36A2-C00*, C0Z*

C06*

C09*

C15

W42A2-A00, A0Z

A05

A10

A15

A20

W42A2-B00, B0Z

B09

B15

B18

W42A2-C00, C0Z

C09

C15

W48A2-A00, A0Z

A05

A10

A15

A20

W48A2-B00, B0Z

B09

B15

B18

W48A2-C00, C0Z

C09

C15

W60A2-A00, A0Z

W17, 18A2-A00,A0Z

A05

A08

A10

W24A2-A00, A0Z

A04

A05

A08

A10

W24A2-B00, B0Z

B06

W24A2-C00, C0Z

C06

W30A2-A00*, A0Z*

A05*

A08

A10*

A15

W30A2-B00*, B0Z*

B06

B09*

B15

W30A2-C00*, C0Z*

C06

C09*

C15

W36A2-A00*, A0Z*

A05*

A08

A10*

A15

W36A2-B00*, B0Z*

A05

A10

A15

A20

W60A2-B00, B0Z

B09

B15

B18

W60A2-C00, C0Z

C09

C15

W70A2-A00, A0Z

A05

A10

A15

A20

W70A2-B00, B0Z

B09

B15

B18

W70A2-C00, C0Z

C09

C15

Rated

Volts &

Phase

230/208-1

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

No.

Field

Power

Circuits

1

1

1

1

1

1

1

1

1

1

1 or 2

1 or 2

1

1

1

1

1

1

1 or 2

1 or 2

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1 or 2

1

1

1

1

1

1

1 or 2

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1 or 2

1 or 2

1

1

1

1

1

1

1 or 2

1 or 2

1

2

1

1

1

1

1

1

2

1

1

Minimum

Circuit

Ampacity

13

17

26

42

27

33

51

60

39

58

84

110

12

17

26

39

24

33

51

60

32

58

84

110

12

16

26

32

24

33

51

11

47

58

84

23

17

26

29

32

33

51

11

12

58

84

18

24

11

24

32

47

56

15

22

9

21

25

30

46

16

30

46

56

56

59

85

111

15

18

27

56

42

60

86

112

28

35

53

N/A

38

38

53

N/A

19

19

27

Ground

Wire

12

12

10

10

10

10

10

10

10

10

8

6

14

12

10

10

10

10

10

10

10

10

8

6

14

12

10

10

10

10

10

14

10

10

8

10

12

10

10

10

10

10

14

14

10

8

12

10

14

10

10

10

10

12

10

14

10

10

10

10

12

10

10

10

10

10

8

6

12

12

10

10

10

10

10

N/A

10

10

8

6

10

10

10

N/A

10

10

10

Single Circuit j

Maximum

External

Fuse or

Ckt. Brkr.

20

20

30

60

40

40

60

60

50

60

90

125

15

20

30

50

35

35

60

60

50

60

90

125

15

20

30

50

30

35

60

15

50

60

90

30

20

30

35

35

35

60

15

15

60

90

20

25

15

35

35

50

60

20

25

15

30

30

30

50

20

30

50

60

60

60

90

125

20

20

30

60

60

60

90

125

40

40

60

N/A

60

60

60

N/A

30

30

35

Field

Power

Wire

Size

12

12

10

8

6

6

8

8

4

2

8

6

14

12

10

8

6

6

8

8

4

2

8

6

14

12

10

8

10

8

6

14

8

6

4

10

12

10

8

8

8

6

14

14

6

4

12

10

14

8

8

8

6

12

10

14

10

10

10

8

12

10

8

6

4

2

6

6

12

12

10

6

8

8

6

N/A

3

2

8

6

8

8

6

N/A

10

10

18

 Minimum

Circuit

Ampacity

Dual Circuit j Maximum

External Fuse or Ckt. Breaker

Field Power

Wire Size

Ground

Wire Size

Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B

58

58

58

58

58

58

60

60

35

59

59

38

26

26

26

52

26

52

26

52

28

26

52

28

60

60

60

60

60

60

60

60

40

60

60

60

30

30

30

60

30

60

30

60

30

30

60

30

6

6

6

6

6

6

6

6

8

6

6

8

10

10

10

6

10

6

10

6

10

10

6

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10 j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.

 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.

Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity

Adjustment Factors when more than three (3) current carrying conductors are in a raceway.

* Top outlet supply option is available only factory installed and only on the selected models.

IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National

Electrical Code and all local codes.

Manual 2100-581C

Page 20 of 26

TABLE 4

Electrical Specifications — W**L Series

MODEL

C15

W42L2-A00, A0Z

A05

A10

A15

W42L2-B00, B0Z

B09

B15

W42L2-C00, C0Z

C09

C15

W48L2-A00, A0Z

A05

A10

A15

W48L2-B00, B0Z

B09

B15

W48L2-C00, C0Z

C09

C15

W60L2-A00, A0Z

A05

A10

A15

W60L2-B00, B0Z

B09

B15

W60L2-C00, C0Z

C09

C15

W70L2-A0Z

A05

A10

A15

W70L2-B0Z

B09

B15

W70L2-C0Z

C09

C15

W17, 18L2-A00,A0Z

A05

A08

A10

W24L2-A00, A0Z

A05

A08

A10

W24L2-B00, B0Z

B06

W24L2-C00, C0Z

C06

W30L2-A00*, A0Z*

A05*

A08

A10*

A15

W30L2-B00*, B0Z*

B09*

B15

W30L2-C00*, C0Z*

C09*

C15

W36L2-A00*, A0Z*

A05*

A10*

A15

W36L2-B00*, B0Z*

B09*

B15

W36L2-C00*, C0Z*

C09*

Rated

Volts &

Phase

230/208-1

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

230/208-1

230/208-3

460-3

No.

Field

Power

Circuits

1 or 2

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1 or 2

1

1

1

1

1

1

1

1

1 or 2

1

1

1

1

1

1 or 2

1

1

1

1

1

1

1

1

1

1 or 2

1

1

1

1

1

1 or 2

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

Minimum

Circuit

Ampacity

15

18

27

56

86

28

35

53

26

42

42

60

33

51

13

17

38

53

19

19

27

56

59

85

38

39

58

84

27

12

17

26

39

84

24

33

51

26

32

32

58

33

51

11

16

32

58

84

23

11

17

26

29

84

18

33

51

24

32

47

58

15

22

9

11

21

30

46

56

16

30

46

56

Ground

Wire

12

12

10

10

8

10

10

10

10

10

10

10

10

10

12

12

10

10

10

10

10

10

10

8

10

10

10

8

10

14

12

10

10

8

10

10

10

10

10

10

10

10

10

14

12

10

10

8

10

14

12

10

10

8

12

10

10

10

10

10

10

12

10

14

14

10

10

10

10

12

10

10

10

Single Circuit j

Maximum

External

Fuse or

Ckt. Brkr.

20

20

30

60

90

40

40

60

30

60

60

60

40

60

20

20

60

60

30

30

35

60

60

90

60

50

60

90

40

15

20

30

50

90

35

35

60

30

50

50

60

35

60

15

20

35

60

90

30

15

20

30

35

90

20

35

60

35

35

50

60

20

25

15

15

30

30

50

60

20

30

50

60

Field

Power

Wire

Size

12

12

10

6

8

6

3

8

10

8

8

6

8

6

12

12

8

6

10

10

18

4

8

6

6

4

8

8

6

14

12

10

8

8

6

4

8

10

8

8

6

8

6

14

12

8

6

4

10

14

12

10

8

4

12

8

6

8

6

8

8

12

10

14

14

10

10

8

6

12

10

8

6

 Minimum

Circuit

Ampacity

Dual Circuit j Maximum

External Fuse or Ckt. Breaker

Field Power

Wire Size

Ground

Wire Size

Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B

58

58

58

58

60

59

26

26

26

26

26

26

60

60

60

60

60

60

30

30

30

30

30

30

6

6

6

6

6

6

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10 j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.

 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.

Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity

Adjustment Factors when more than three (3) current carrying conductors are in a raceway.

* Top outlet supply option is available only factory installed and only on the selected models.

IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National

Electrical Code and all local codes.

Manual 2100-581C

Page 21 of 26

TABLE 5

RECOMMENDED AIRFLOW

Model

W17A, W17L

W18A, W18L

W24A, W24L

W30A, W30L

W36A, W36L

W42A, W42L

W48A, W48L

W60A, W60L

W70A, W70L

Nominal

Rated

CFM *

600

550

800

1000

1100

1400

1550

1700

1700

Nominal

Rated

ESP *

.40

.45

.30

.30

.20

.45

.30

.40

.20

Recommended

Airflow Range

* Rated CFM and ESP on factory speed connection.

550 - 725

550 - 725

700 - 950

850 - 1300

930 - 1350

1600 - 1150

1750 - 1285

1950 - 1375

1950 - 1375

Factory Speed

Connection

Low

Low

Single

High

High

High

High

High

High

Speed

High

W17/18

Low

W24

Single High

TABLE 6

INDOOR BLOWER PERFORMANCE

W30

Low High

W36

Low High

W42/48

Low High

W60

Low High

W70

Low

ESP

(Inch

H20)

0.0

0.1

0.2

0.3

0.4

0.5

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

1045 1025 760 745 990 970 1370 1285 910 885 1415 1275 955 925 1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400

1010 970 730 715 945 925 1305 1225 885 860 1350 1215 945 915 1775 1725 1545 1500 2020 1960 1450 1405 1970 1770 1425 1340

940 905 700 685 890 870 1225 1135 850 815 1265 1125 925 900 1685 1640 1460 1415 1925 1865 1395 1355 1905 1700 1375 1295

860 830 670 655 820 800 1115 1020 790 755 1190 1060 875 850 1590 1550 1390 1345 1870 1815 1340 1300 1830 1645 1225 1150

780 750 610 595 735 720 1005 910 695 660 1085 975 780 755 1495 1460 1310 1270 1755 1705 1225 1185 1725 1550 1140 1070

665 640 485 455 605 590 865 775 590 560 970 865 640 615 1400 1365 1225 1185 1660 1610 1125 1085 1500 1350 1050 985

TABLE 7

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

Model

-B0Z

-B06

-B09

-B15

-B18

-C0Z

-C06

-C09

-C15

Outlet

Speed

-A0Z

-A04

-A05

-A08

-A10

-A15

-A20

W17A/L,

W18A/L,

W24A/L

FRONT

Single

.50

.50

.50

.50

.50

High

.50

.50

.50

.50

.40

.50

.50

.50

.45

FRONT

W30A/L, W36A/L

Low

.50

.50

.50

.45

.35

.50

.40

.50

.30

High

.50

.50

.50

.50

.45

TOP

Low

.50

.45

.35

.50

.40

W42A/L, W48A/L

High

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

FRONT

Low

.50

.50

.50

.50

.45

.50

.50

.50

.50

.50

.50

.50

.50

.45

.50

.50

.40

.35

.50

.45

.50

.40

.50

.50

.50

.50

Values shown are for units equipped with standard 1-inch throwaway filter or 1-inch washable filter.

Derate ESP by .15 for 2-inch pleated filters.

W60A/L, W70A/L

High

FRONT

Low

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.50

.40

.50

.50

.50

Manual 2100-581C

Page 22 of 26

Models

KW

4

5

6

8

9

10

12

15

18

20

Amps

240V-1

BTUH

16.7

13650

20.8

17065

33.3

41.6

27300

34130

62.5

83.2

51250

68260

Amps

208V-1

BTUH

14.4

10240

18.1

12800

TABLE 8

ELECTRIC HEAT

Amps

240V-3

BTUH

14.4

20500

28.8

20475

21.7

30600

36.2

25600

54.0

72.1

38400

51200

36.2

43.3

51200

61430

Amps

208V-3

BTUH

12.5

18.7

31.2

37.5

15360

23030

38400

46100

Amps

460V-3

BTUH

7.2

10.8

14.4

18.0

20500

30700

40950

51200

Manual 2100-581C

Page 23 of 26

TABLE 9A

OPTIONAL ACCESSORIES — RIGHT HAND

CIRCUIT BREAKER (WMCB) & PULL

Manual 2100-581A

Page 24 of 26

EHWA37-B15

EHWC03A-C06

EHWC03A-C09

EHWA03A-C12

EHWA03A-C15

EHWA05-A05

EHWA05-A10

EHWA05-A15

EHWA05-A20

EHWA05-B09

EHWA05-B15

EHW05A-B18

EHWA05-B18

EHWA05A-C09

EHWA02-A05 X

EHW02A-A08 X

EHWA02A-A10 X

EHWA24-A04

EHWA24-B06

EHWH24B-C06

EHWA03-A05

EHWA03-A08

EHWA03-A10

EHWA03-A15

EHWA03-B06

EHW36A-B06

EHWA03-B09

EHWA05A-C15

EHWA60-A05

EHW60A-B09

EHW70A-B09

EHW70A-B18

WMCB-01B

WMCB-02A

WMCB-02B

WMCB-03A

WMCB-04B

WMCB-05A

WMCB-05B

WMCB-06B

WMCB-08A

WMCB-09A

WMPD-01C

WMCB-08B

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

TABLE 9B

OPTIONAL ACCESSORIES — LEFT HAND

CIRCUIT BREAKER (WMCB) & PULL

EHWA02A-A05L

EHW02A-A08L

EHWA02-A10L

EHWA24-B06L

EHWA03-A05L

EHWA03-A08L

EHWA03-A10L

EHWA03-A15L

EHWA03-B09L

EHWA37-B15L

EHWC03-C09L

EHWA03-C15L

EHWA05-A05L

EHWA05-A10L

EHWA05-A15L

EHWA05-B09L

EHWA05-B15L

EHWA05A-C09L

EHWA05A-C15L

EHWA60-A05L

EHWA60-B09L

EHW70A-B09L

WMCB-01B

WMCB-02A

WMCB-02B

WMCB-03A

WMCB-04B

WMCB-05A

WMCB-05B

WMCB-06B

WMCB-08A

WMCB-09A

WMPD-01C

WMCB-09B

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X

X X

X

X X

X X X X

X

X

X

X

X

Manual 2100-581C

Page 25 of 26

TABLE 10

VENT & CONTROL OPTIONS

Part Number

CMC-14

CMC-15

CMC-23

CMC-24

CMC-28

BFAD-2

BOP-2

MFAD-2

CRV-2

ECONWMS-E2

ECONWMT-E2

ECONWMT-T2

ERVF-A2

ERVF-C2

BFAD-3

BOP-3

MFAD-3

CRVS-3

CRVP-3

ECONWMS-E3

ECONWMT-E3

ECONWMT-T3

ERVF-A3

ERVF-C3

BFAD-5

BOP-5

MFAD-5

CRVS-5

CRVP-5

ECONWMS-E5

ECONWMT-E5

ECONWMT-T5

ERVF-A5

ERVF-C5

Description

ODT

Start Kit (230V 1-Phase)

DDC

DDC

LAC

Barometric Fresh Air Damper - Standard

Blank Off Plate

Motorized Fresh Air Damper

Commercial Ventilator - Spring Return

Economizer - School Version, Enthalpy

Economizer - Bldg. Equipment, Enthalpy

Economizer - Bldg. Equipment, DB Temp.

Energy Recovery Ventilator - 230 Volt

Energy Recovery Ventilator - 460 Volt

Barometric Fresh Air Damper - Standard

Blank Off Plate

Motorized Fresh Air Damper

Commercial Ventilator - Spring Return

Commercial Ventilator - Power Return

Economizer - School Version, Enthalpy

Economizer - Bldg. Equipment, Enthalpy

Economizer - Bldg. Equipment, DB Temp.

Energy Recovery Ventilator - 230 Volt

Energy Recovery Ventilator - 460 Volt

Barometric Fresh Air Damper - Standard

Blank Off Plate

Motorized Fresh Air Damper

Commercial Ventilator - Spring Return

Commercial Ventilator - Power Return

Economizer - School Version, Enthalpy

Economizer - Bldg. Equipment, Enthalpy

Economizer - Bldg. Equipment, DB Temp.

Energy Recovery Ventilator - 230 Volt

Energy Recovery Ventilator - 460 Volt

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

Manual 2100-581C

Page 26 of 26

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement