- Home
- Domestic appliances
- Large home appliances
- Water heaters & boilers
- WaterFurnace
- Premier2
- Installation manual
advertisement
Geothermal/Water Source Heat Pumps
• 3/4 thru 6 Ton
Installation Information
Water Piping Connections
Desuperheater Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
IM1555 11/06
PREMIER INSTALLATION MANUAL
Model Nomenclature
P 040 T L 3 2 0 C A D S S A
Family
P = Premier
Unit Capacity
MBTUH
Discharge Air Configuration
T = Top Discharge Vertical
E = End Discharge Horizontal
S = Side Discharge Horizontal
Return Air Configuration
L = Left
R= Right
Voltage
0 = 208-230/60/1 (Commercial)
1 = 208-230/60/1 (Residential)
2 = 265-277/60/1
3 = 208-230/60/3
4 = 460/60/3
Hot Water Option
0 = None
1 = Hot Water Generation
With Factory Installed Pump (Residential)
2 = Hot Water Generation
Without Pump (Commercial 022-066, 230 VAC only)
Note: * FX10 available only on units with PSC blowers without desuperheaters.
Vintage
A = All Others
B = P028(Single Phase),
P056(All Voltages)
Non-Standard Option Details
Non-Standard Options
S = Standard
4 = FX10*
5 = FX10 w/Open N2 Com. Card*
6 = FX10 w/LonWorks Com. Card*
7 = FX10 w/BacNet Com. Card*
Filter Options
D = 1" Pleated Disposable
Sound Kit
A = None
B = Blanket
Coax Options
C = Copper
N = Cupronickel
Blower Options
0 = PSC Blower
1 = ECM Blower
2 = Oversized ECM Blower Option
(040-046 Only)
2
Table of Contents
PREMIER INSTALLATION MANUAL
Closed Loop Ground Source Systems 8
Open Loop Ground Water Systems 9
Boiler/Cooling Tower Closed Loop Systems 10
System Cleaning & Flushing 11
Desuperheater Connection & Startup 12-13
15
Electronic Thermostat Installation 15
Standard Microprocessor Control Operation 30-31
Description of Unit Operation 36-37
Troubleshooting 38
3
PREMIER INSTALLATION MANUAL
General Installation Information
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch.
Electrical shock could cause personal injury.
Safety Considerations
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualifi ed service personnel should install, repair or service heating and air conditioning equipment.
Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing fi lters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fi re extinguisher available.
Moving and Storage
Move units in the normal “up” orientation as indicated by the arrows on each carton. Horizontal units may be moved and stored per the information on the carton. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked.
When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the cartons if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage. Units are to be stored in clean, dry location to prevent damage.
Unit Location
Locate the unit in an indoor area that allows for easy removal of the fi lter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide suffi cient room to make water, electrical and duct connection(s). If the unit is located in a confi ned space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be diffi cult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
Installing Vertical Units
Vertical units are available in left or right air return confi gurations. Vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the fl oor. It is not necessary to anchor the unit to the fl oor (see right). If access to the left side of the unit will be limited after installation, remove the two mounting screws on the left side of the control box before setting the unit (leave the two front mounting screws intact).
This will allow the control box to be removed with only the two front mounting screws for future service.
Figure 1: Vertical Unit Mounting
Vibration
Absorbing
Mesh or
Air
Pad
4
PREMIER INSTALLATION MANUAL
Installing Horizontal Units
Horizontal units are available with side or end discharge and may be fi eld converted from one to the other by replacing the discharge panel with a new panel which must be ordered separately. Horizontal units are normally suspended from a ceiling by four or six 3/8-inch diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit.
Lay out the threaded rods per the dimensions in Figure 3. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut. To allow fi lter access, one bracket on the fi lter side should be installed 180° from the position shown in the
Figure 2: Typical Horizontal Unit Installation fi gure below. The unit should be pitched approximately 1/4-inch towards the drain in both directions to facilitate the removal of condensate. Use only the bolts provided in the kit. The use of longer bolts could damage internal parts.
Some residential applications require the installation of hori-
Electric heat assembly
(optional)
Flexible Duct
Collar
Insulate supply plenum and use at least a 90° elbow to reduce noise
3/8”
Threaded rods (6)
To Line
Power
To Thermostat
P/T Plugs
Hose Kits zontal units on an attic fl oor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing mesh. The secondary drain pan prevents possible condensate overfl ow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the
Disconnects
Line Voltage
Hanging
Brackets
(included)
Ball V alves
Building Water
Loop
CAUTION: Do not use rods smaller than 3/8-inch diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling.
Figure 3: Hanger Location and Assembly
E
3/8”
Threaded Rod
(not supplied)
Vibration Isolator
W asher
A C
Compressor
Section
Air Handler
Section
B
D
P010-034, 4 hangers included
P040-066, 6 hangers included
Bolt and
Lockwasher
MODEL
P010, 013
P019
P022, 028, 034
P040, 046
P056
P066
A
24.8
24.8
24.8
27.8
27.8
27.8
Hex Nuts
(not supplied)
B
42.5
51.5
61.5
70.5
75.5
80.5
C
22.5
22.5
22.5
25.5
25.5
25.5
D
44.0
53.0
63.0
72.0
77.0
82.0
–
–
E
–
29.9
29.9
29.9
5
PREMIER INSTALLATION MANUAL
Duct System
An air outlet collar is provided on vertical top fl ow units and all horizontal units to facilitate a duct connection. A fl exible connector is recommended for discharge and return air duct connections on metal duct systems. Uninsulated duct should be insulated with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired if necessary.
The duct system should be sized to handle the design airfl ow quietly and effi ciently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fi berglass or constructed of ductboard for the fi rst 10 feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airfl ow is a problem, the blower speed can be changed (refer to pages 16-17).
CAUTION: Be sure to remove the shipping material from the blower discharge before connecting ductwork.
Water Piping
The proper water fl ow must be provided to each unit whenever the unit operates. To assure proper fl ow, use pressure/ temperature ports to determine the fl ow rate. These ports should be located adjacent to the supply and return water connections on the unit. The proper fl ow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.
All source water connections on residential units are swivel fi ttings that accept a 1-inch male pipe thread (MPT). The swivel connector has a rubber gasket seal similar to a rubber hose gasket, which when mated to the fl ush end of any 1-inch threaded pipe provides a leak-free seal without the need for thread sealing tape or compound. Check to ensure that the rubber seal is in the swivel connector prior to attempting any connection. The rubber seals are shipped attached to the waterline. To make the connection to a ground loop system, mate the brass connector (supplied in CK4L and CK3L connector kit) against the rubber gasket in the swivel connector and thread the female locking ring onto the pipe threads, while maintaining the brass connector in the desired direction. Tighten the connectors by hand, then gently snug the fi tting with pliers to provide a leak-proof joint. When connecting to an open loop (ground water) system, thread any 1-inch MPT fi tting (SCH80
PVC or copper) into the swivel connector and tighten in the same manner as noted above. The open and closed loop piping system should include pressure/temperature taps for serviceability.
All source water connections on commercial units are standard female pipe thread.
Never use fl exible hoses smaller than 1-inch inside diameter on the unit. Limit hose length to 10 feet per connection.
Check carefully for water leaks.
Freeze Protection
Set the freeze protection switch SW2-2 on the printed circuit board for applications using a closed loop antifreeze solution to “LOOP”. On applications using an open loop/groundwater system (or closed loop no antifreeze), set this dip switch to
“WELL”, the factory default setting. (Refer to the Dip Switch Field Selection table on page 20.)
6
PREMIER INSTALLATION MANUAL
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualifi ed service mechanic, as special solutions and pumping equipment are required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional fl ushing.
Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning.
Material pH
Scaling
Corrosion
Acidity/Alkalinity
Calcium and Magnesium Carbonate
Hydrogen Sulfide
Sulfates
Chlorine
Chlorides
Carbon Dioxide
Ammonia
Ammonia Chloride
Ammonia Nitrate
Ammonia Hydroxide
Ammonia Sulfate
Total Dissolved Solids (TDS)
Iron, Fe 2 + (Ferrous)
Bacterial Iron Potential
Copper
7- 9
(Total Hardness) less than 350 ppm
Less than .5 ppm
(rotten egg smell appears at 0.5 PPM)
Less than 125 ppm
Less than .5 ppm
Less than 20 ppm
Less than 50 ppm
Less than 2 ppm
Less than .5 ppm
Less than .5 ppm
Less than .5 ppm
Less than .5 ppm
Less than 1000 ppm
None
Iron Fouling
(Biological Growth)
Erosion
Iron Oxide
Suspended Solids
Threshold Velocity (Fresh Water)
Less than 1 ppm. Above this level deposition will occur.
Less than 10 ppm and filtered for max of 600 micron size
5-8 ft/sec
Note: Grains = PPM divided by 17 • mg/l is equivalent to PPM
90/10 Cupro-Nickel
5 - 9
(Total Hardness) less than 350 ppm
10 - 50 ppm
Less than 125 ppm
Less than .5 ppm
Less than125 ppm
10 - 50 ppm
Less than 2 ppm
Less than .5 ppm
Less than .5 ppm
Less than .5 ppm
Less than .5 ppm
1000-1500 ppm
None
Less than 1 ppm. Above this level deposition will occur.
Less than 10 ppm and filtered for max of 600 micron size
8-12 ft/sec
Condensate Drain
On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a
3/4-inch PVC female adapter and a fl exible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the fi eld-installed PVC condensate piping. On vertical units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary.
On horizontal units, a copper stub is provided for condensate drain piping connection. An external trap is required (see
Figures 4 and 5 below). If a vent is necessary, an open stand pipe may be applied to a tee in the fi eld-installed condensate piping.
Figure 4: Horizontal Drain Connection
Figure 5: Unit Pitch for Drain
Copper tube stub
Plastic Hose Clamps
(Included with unit)
Clear PVC hose
3/4" barb to glue adapter
Vent (if needed)
3/4" PVC
1/8" per foot
1.5"
1.5"
1/4'' Pitch
Drain
7
PREMIER INSTALLATION MANUAL
Closed Loop Ground Source Systems
Note: For closed loop systems with antifreeze protection, set SW2-2 to the “loop” position (see table on page 32).
Once piping is completed between the unit, fl ow center and the ground loop (see fi gure below), fi nal purging and charging of the loop is required. A fl ush cart (or a 1.5 HP pump minimum) is needed to achieve adequate fl ow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is normally adequate for good system operation. Loop static pressure will fl uctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fl uctuation is normal and should be considered when initially charging the system.
After pressurization, be sure to remove the plug in the end of the loop pump motor(s), if applicable, to allow trapped air to be discharged and to ensure that the motor housing has been fl ooded. Ensure that the loop fl ow center provides adequate fl ow through the unit by checking the pressure drop across the heat exchanger and comparing it to the unit capacity data in the specifi cation catalog. Usually 2.5 to 3 GPM of fl ow per ton of cooling capacity is recommended in earth loop applications. (See wiring diagram attached to the inside of the unit for pump wiring details.)
Figure 6: Closed Loop, Ground Source Application - Single unit with Flow Center
Unit Supply
Auxiliary Heat
Supply
GeoLink ®
Polyethylene w/
Armaflex ®
Insulation
TO
LOOP
Flexible Duct
Collar
Auxiliary
Heater
Knockout
Unit Power
Desuperheater
Connections
GeoLink
Flow
Center
®
Disconnects
(If Applicable)
Drain
External
Pump Power
Low
Voltage to
Thermostat
P/T Plugs
Vibration Absorbing Pad
Multiple Units on One Flow Center
When two units are connected to one loop pumping system, pump control is automatically achieved by connecting the SL terminals on connector P2 in both units with 2-wire thermostat wire. These terminals are polarity dependant. The loop pump(s) may be powered from either unit, whichever is more convenient. If either unit calls, the loop pump(s) will automatically start. The use of two units on one fl ow center is generally limited to a total of 20 GPM capacity.
GroundLoop Connector
Kits withArmaflex ®
(CK4S or CK4L)
Figure 7: Primary/Secondary Hook-up
Premier to Premier
Microprocessor Units
Premier Unit #1
Shut
Down
C C
SL1
In
SL1
Out
SL2
In
SL2
Out
With pump wired to Unit 1
With pump wired to
Unit 2
Premier to
Electromechanical Unit
Premier Unit #1
Shut
Down
C C
SL1
In
SL1
Out
SL2
In
SL2
Out
Shut
Down
C C
SL1
In
Premier Unit #2
SL1
Out
SL2
In
SL2
Out
C S
To Electromechanical Unit
8
PREMIER INSTALLATION MANUAL
Open Loop Ground Water Systems
Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Ensure proper water fl ow through the unit by checking pressure drop across the heat exchanger and comparing it to the fi gures in
Capacity Tables in the Specifi cation Catalog. Normally, about 2 GPM fl ow rate per ton of cooling capacity (1.5 GPM per ton minimum at 50°F) is needed in open loop systems.
Note: For open loop/ground water systems or systems that do not contain an antifreeze solution, set SW2-Switch #2 to the
“WELL” position.
Figure 8: Open System - Groundwater Application
Unit Supply
Aux. Heat Supply
Flexible
Duct Collar
Rubber Bladder
Expansion Tank
Auxiliary
Heater
Knockout
Desuperheater
Connections
Flow Control
Valve
(on outlet of
Solenoid Valve)
Solenoid
Valve
Water Out
Water In
Drain
Disconnects
(If Applicable)
Shut Off Valves
Shut Off Valves
(to isolate solenoid valve while acid flushing)
Compressor
Line Voltage
Low Voltage to Thermostat and Valve
P/T Plugs
Vibration
Absorbing Pad
Strainer
Boiler Drains
For HX Flushing
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local building codes (e.g. recharge well, storm sewer, drain fi eld, adjacent stream or pond, etc.). Most local codes forbid using the sanitary sewer for disposal. Consult your local building and zoning department to assure compliance in your area.
The water control solenoid is wired between the common pin
#2 connector P1 and pin #3 connector P3, and a jumper wire is connected between R and pin #1 connector P3 (refer to Figure
9). Notice that DIP switch 2-3, located on the PCB, must be switched to the “Comp” position so the valve will operate with the compressor.
Figure 9: Typical single-stage external 24V water solenoid valves (type PPV100 or BPV100) wiring
P1
C
R
2
1
Solenoid
Valve
ACC Com
1
ACC NC 2
ACC NO 3
Note: Switch SW2 - 3 to comp position.
9
PREMIER INSTALLATION MANUAL
Boiler/Cooling Tower Closed Loop Systems
Boiler/Cooling Tower
The water loop is usually maintained between 60°F and 90°F. Premier units allow 25°F to 110°F EWT for proper heating and cooling operation.
To reject excess heat from the water loop, the use of a closed circuit evaporative cooler or an open type cooling tower with a secondary heat exchanger between the tower and the water loop is recommended. If an open type cooling tower is used without a secondary heat, continuous chemical treatment and fi ltering of the water must be performed to ensure the water is free from damaging materials.
Water Piping Connections
Units should not be connected to the supply and return piping until the water system has been cleaned and fl ushed completely. Supply and return water connections are standard female pipe thread on commercial units (1-inch swivel on residential units). Never use fl exible hoses with an inside pipe diameter that is smaller than the water connections on the unit and limit the hose length to 10 feet or less per connection. High-pressure fl exible hoses provide sound attenuation for both normal unit operating noise and hydraulic pumping noise. Hard piping can also be brought directly to the unit although it is not recommended since no vibration or noise attenuation can be accomplished.
10
PREMIER INSTALLATION MANUAL
System Cleaning and Flushing
Prior to start up of any heat pump, the water circulating system must be cleaned and fl ushed of all dirt and debris. If the system is equipped with water shutoff valves, the supply and return runouts must be connected together at each unit location to prevent the introduction of dirt into the unit, (see Figure 10). The system should be fi lled at the water makeup connection with all air vents open. After fi lling, vents should be closed.
The contractor should start the main circulator with the pressure reducing valve makeup open. Vents should be checked in sequence to bleed off any trapped air and to verify circulation through all components of the system.
As water cirulates through the system, the contractor should check and repair any leaks found in the piping system.
Drain(s) at the lowest point(s) in the system should be opened for the initial fl ush and blowdown, making sure water fi ll valves are set at the same rate. Check the pressure gauge at the pump suction and manually adjust the makeup water valve to hold the same positive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if required, unil drain water is clean and clear.
The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to completely drain the system. Short circuited supply and return runouts should now be connected to the unit supply and return connections.
Refi ll the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specifi ed percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Environol™ brand antifreeze is recommended.
Once the system has been fi lled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog valves, strainers, fl ow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure. In boiler/tower applications, set the loop control panel set points to desired temperatures. Supply power to all motors and start the circulating pumps. After full fl ow has been established through all components including the heat rejector (regardless of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up and for air and water balancing.
Note: For closed loop systems with antifreeze protection, set SW2-2 to the “LOOP” position.
Figure 10: Flushing with Water Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Rubber Hose
Runouts initially connected together
Mains
11
PREMIER INSTALLATION MANUAL
Desuperheater Connections
Water Tank Preparation
Electric water heaters are recommended for use with the desuperheater in potable water systems. A tank with a 50-gallon minimum capacity should be installed. Multiple tanks may be piped in series to create larger buffer tanks.
Figure 11: Water Heater Connection Kit
Brass Nipple
Boiler Drain
Male Adapter
Brass Tee
Figure 12: Desuperheater Installation In Preheat Tank
Venting Waste Valve or Vent Coupling
3/4” x 3/4” x 1/2” tee Cold
Water In
Hot
Water Out
Figure 13: Typical Desuperheater Installation
Venting Waste Valve or Vent Coupling
3/4” x 3/4” x 1/2” tee Cold
Water In
Hot
Water Out
DHW
Water In
DHW
Water Out P/T Relief
Valve
In
P/T Relief
Valve
Drain Valve Drain Valve
DHW
Water In
Note: Desuperheater pump mounted externally with commercial units; internally in residential units.
DHW
Water Out
P/T Relief
Valve
In
Drain Valve
12
PREMIER INSTALLATION MANUAL
Initial Desuperheater Startup
Plumbing Installation
1.
Remove drain valve and fi tting from water heater.
6.
7.
8.
9.
2.
3.
4.
5.
10.
11.
Thread the 3/4-inch NPT x 3 1/2-inch brass nipple into the water heater drain port.
Attach the center port of the 3/4-inch FPT tee to the opposite end of the brass nipple.
Attach the 1/2-inch SWT x 3/4-inch NPT copper adapter to the side of the tee closest to the unit.
Install the drain valve on the tee opposite the adapter.
Run interconnecting tubing from the tee to DHW “WATER OUT” at the unit.
Cut the cold water “IN” line going to the water heater.
Insert the 3/4-inch x 3/4-inch x 1/2-inch reducing solder tee “IN” line with cold water line as shown.
Run interconnecting copper tubing between the unit DHW “WATER IN” and the tee (1/2-inch nominal) using (2) 1/2-inch sweat x 1-inch MPT adapters. The recommended maximum distance is 50 ft.
To prevent air entrapment in the system, install a vent coupling at the highest point of the interconnecting lines.
Insulate all exposed surfaces of both connection water lines with 3/8-inch wall closed cell insulation.
Note: All plumbing and piping connections must comply with local plumbing codes .
Desuperheater Startup
1. Close the drain valve to the water heater.
2. Open the cold water supply to the tank.
3. Open the hot water faucet in the house to bleed air from the system. Close when full.
4. Depress the handle on the pressure relief valve to bleed any remaining air from the tank then close.
5. If so equipped, unscrew the indicator plug on the motor end of the pump until all air is purged from the pump, then tighten the plug. Use vent couplings to bleed air from the lines.
6. Carefully inspect all plumbing for water leaks and correct as required.
7. Before restoring electrical supply to the water heater, adjust the temperature setting on the tank.
• On tanks with both upper and lower elements, the lower element should be turned down to the lowest setting, approximately 100°F. The upper element should be adjusted to 120°F to 130°F. Depending upon the specifi c needs of the customer, you may want to adjust the upper element differently.
• On tanks with a single element, lower the thermostat setting to 120°F.
8. After thermostat(s) is adjusted, replace the access cover and restore electrical supply to the water heater.
9. Make sure that any valves in the desuperheater water circulating circuit are open.
10. Turn on the Premier unit to fi rst stage heating.
11. The DHW pump should be running. Be sure the disable switch for the DHW pump (SW4) is ON. The DHW OFF
LED on the unit should not be illuminated.
12. The temperature difference between the water entering and leaving the desuperheater should be 5°F to 15°F. The
13. Allow the unit to heat water for 15 to 20 minutes to be sure operation is normal.
14. When the pump is fi rst started, open the inspection port (if equipped) until water dribbles out, then replace. Allow the pump to run for at least fi ve minutes to ensure that water has fi lled the circulator properly.
CAUTION: Never operate the DHW circulating pump while dry. If the unit is placed in operation before the desuperheater piping is connected, be sure that the pump switch is set to the OFF position.
Desuperheater Notes: When servicing a unit’s refrigeration circuit, it is always good practice to disable the desuperheater pump. This can be accomplished by using the DHW pump disable switch located on the front of the unit cabinet near the LED annunciator panel. The red DHW OFF LED will illuminate, indicating the DHW pump is disabled.
13
PREMIER INSTALLATION MANUAL
Electrical Connections
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Unit Power Connection
Connect the incoming line voltage wires to L1 and L2 or L1, L2, and L3 of the contactor as shown in Figures 14 and 15.
(For more information, refer to the Unit Electrical Data section in the Specifi cation Catalog SP1555.)
External Loop Pump Power Connection
If the unit is to be used with an external loop pump (FC1 or FC2 fl ow center), the pump(s) will be connected to the terminals on PB1 in the unit electrical box as shown in Figures 14 and 15. The pumps will automatically be cycled as required by the unit or by an SL signal from another Premier unit sharing the fl ow center.
Accessory Relay
A set of “dry” contacts has been provided to control accessory devices, such as 2-wire water solenoid valves on open loop installations, electronic air cleaners, humidifi ers, etc. This relay contact should be used only with 24 volt signals and not line voltage power. The relay has both normally open and normally closed contacts and can operate with either the fan or the compressor. Use DIP switch SW2-3 to cycle the relay with fan or compressor. The relay contacts are available on terminals #2 and #3 of P3. The default value of the switch is set to operate with fan. For use with electronic air fi lter.
208 Volt Operation
All Premier units are factory wired for 230 volt operation. There is a switch located on the control box which allows the installer to select 208 volt unit operation. Refer to Figures 14 and 15 below for switch location.
Figure 14: Line Voltage 208-230/60/1 Control Box
Compressor
Capacitor
Transformer
Compressor
Contactor
Ground
Lugs
208-230/60/1
Service with
Ground
L2
L1
Figure 15: Line Voltage 208-230/60/3 Control Box
Compressor
Contactor
208-230/60/3
Service with
Ground
Transformer
Ground
Lugs
L3
L2
L1
Voltage
Selection
Rocker Switch
PB1 PB1
Voltage
Selection
Rocker Switch
A
PS
C D A
PS
C D
Unit Control
Board
External Loop Pump(s)
208-230/60/1
1/2 HP Max
14
Unit Control
Board
External Loop Pump(s)
208-230/60/1
1/2 HPMax
PREMIER INSTALLATION MANUAL
Electronic Thermostat Installation
Position the thermostat subbase against the wall so that it is level and the thermostat wires protrude through the middle of the subbase. Mark the position of the subbase mounting holes and drill holes with a 3/16-inch bit. Install supplied anchors and secure base to the wall. Thermostat wire must be 8-conductor 18 AWG wire. Strip the wires back 1/4-inch (longer strip lengths may cause shorts) and insert the thermostat wires into the connector as shown. Tighten the screws to insure tight connections. The thermostat has the same type connectors, requiring the same wiring. See instructions enclosed in the thermostat for detailed installation and operation information.
Figure 16: Thermostat Wiring
R
C
Y1
Y2
W
O
G
L
24VAC (Hot)
24VAC (Common)
Compressor (1st Stage)
Compressor (2nd Stage)
Aux. Heat
Reversing Valve
Blower Relay
System Monitor
Figure 17: Logic Board Physical Layout
F1 F1
N.O.
CR1- DHW
Pump
N.O.
CR2- Loop
Pump
N.C.
N.O.
Com
CR3-
N.O.
CR4-
Com
P4
1 2 3
CC-GND
CC
CCLO
CCHI
Microprocessor
C
C
R
R
P1
1 2 3 4 5 6
Off
SW1
On
7
8
5
6
3
4
1
2
9
10
11
12
7 8
R C Y1 Y2 W O G L
Off
SW2
On
7
8
5
6
3
4
1
2
SW3
Off On
1
Shut
Down
P2
2 3 4 5 6 7
C C
SL1
IN
SL1
Out
SL2
IN
SL2
Out
3
4
1
2
5
8
1
2
3
4
5
6
7
P3
1 2 3
8
9
10
11
12
13
14
9
10
11
12
13
14
15
16
5
6
3
4
7
2
1
ACC
NO
ACC
NC
ACC
COM
P6
P5
Notes: DIP switch SW2-#8 is required to be in the “OFF” position for the control to recognize the 24VAC thermostat inputs.
The second stage compressor wire must be installed between the unit and the thermostat for proper control operation. SW3-
2 “OFF” to be used with zoned systems. SW3-2 “ON” to be used for unzoned systems. SW3-4 “OFF” is used with ECM and
17P501A01 Electric Heat board. SW3-4 “ON” is used with ECM2 and 17P514A01 Electric Heat board.
15
PREMIER INSTALLATION MANUAL
Wiring Schematics
P Series/E Series - Single Speed Wiring Schematic - 208-230/60/1, ECM Blower
97P618-19 10/13/05
Compressor
Note 11
S C
Optional Factory
Intstalled Internal Pump
208-230/60/1
Pump
Note 12
PTCR
Blu
Cap
Tan
Red
R
Blk
Black
Black
Current Switch
CS
Ext Pump
1/2 hp Total
208-230/60/1
Unit Power
208-230/60/1
L2
T2
CC
T1
L1
Pump Pump
2
PB1
2
1
1
G
NOTE 4
PS1
D
C
G
Blk/Wh
Gray/Wh
A
Blk Blk/Wh
Blu
Blu
NOTE 6
DHW
Pump
Pink
Yel
Gray
Or Brn
3A
FUSE
Blu
Fused L2 Fused L2
240V L2
240V L2
F1-10A 240V
240V L1
208V 240V
Transformer
Switch
NOTE 1
Red
208V
Blu
240V
NO NO NO NC NO NC
CR1 COM CR2 COM CR3 COM CR4 COM
Transformer
Yel
24V
Blk/Wh
CC
W
O
G
L1
Thermostat
R
C
Y1
Y2
Violet
Violet
NOTE 9
NOTE 2
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOTE 10
Optional
Electronic
Air-Filter
P2
Shut
Down
C
C
SL1 In
SL1 Out
Not
Used
6
7
4
5
NOTE 3
P3
Acc Com
Acc NC
Acc NO
1
2
3
P1
R
C
Y1
Y2
W
O
G
LO
CC
CC-GND
7
8
5
6
3
4
1
2
1 2 3
P4
Microprocessor
Logic Control
(DC Voltage)
ECM2
Air Flow
Settings
NOTE 7
SW1 On
7
8
5
6
9
3
4
1
2
10
11
12
SW2 On SW3
1
2
3
4
Test / Norm
Loop / Well
Fan / Comp
Dehum / Norm
5
6
No Htg3 / Htg3
Inputs / Norm
7 Outputs / Norm
8 24 VAC / TA32E12 (24 VDC)
On
1
2
3
4
5
2 Speed / 1 Speed
Zone (See Note 13)
No RPM / RPM
ECM, EH (See Note 8)
Must be ON
Main Logic PCB
R
4
5
14
13
7
8
P6
C
12
6
0
9
2
1
3
11
6
5
13
6
1
12
3
8
7
14
9
2
P5
11
4
10
Not Used
Not Used
Orange
Orange
Not Used
Not Used
Pink
Pink
Yellow
Yellow
Blue
Blue
Black
Black
LP
Not Used
Black
Violet
Yellow
Blue
Gray
Brown
Not Used
Not Used
Orange
Blue
Pink
White
Tan
Red
Not Used
T
T
CS
CO
RV
HWL
FP
HP
SW4
Y
R
R
G
R
R
R
R LED Normal Display Mode
Drain
Water Flow
High Press
Low Press
Air Flow
Status
DHW Limit
DHW off
Field Selection Dips - #1 On, #6 On, #7 On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure > 380 PSI Lockout **
Low Pressure < 15 PSI Lockout **
ECM2 RPM < 100 rpm Lockout
Microprocessor malfunction*
HWL thermistor > 130°F
DHW pump switch off
*Green LED not flashing
** E Series units High Pressure > 600 PSI, Low Pressure < 40 PSI
Current Fault Status
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure > 380 PSI
Low Pressure < 15 PSI
ECM2 RPM < 100 rpm
Not Used
HWL thermistor > 130°F
DHW pump switch off
Diagnostic Modes
Inputs
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
Outputs
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
Outputs2
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
16
PREMIER INSTALLATION MANUAL
Brn
Or
Grn
1 2 3 4 5 P11
ECM2
Fan Motor
3 15 16 10 8 P12
With optional ' EA' Series
Auxiliary ElectricHeat
Typical schematic shown
Brn
Or
Blu
Violet
Grn
1 2 3 4 5 P11
ECM2
Fan Motor
3 15 16 10 8 P12
Grn
P9
1
2
3
5
4
Auxiliary Electric Heat Power
208-230/60/1
L2 NOTE 5 L1
G L4 L2 L1 L3 G
F2
Brn
Or
Pink
Yel
Blk
Gray
PB2
Pink
Yel
Blk
Gray
ER1
2
1
4
3
P8
NO
Gray
ER2
NO
ER3
NO
Blk
Yel
2
3
1
P7
4
Gray
Blk
Yel
Pink
Pink
Yel
Blk
Gray
HE1
HE2
HE3
P2 1
ER4
NO
Pink
HE4
Gray
TS1
Blk
TS2
Yel
Pink
TS3
TS4
P10
1 2 3 4 5 6 EA Series PCB
17P514A01
P10
1
2
5
6
3
4
Black
Violet
Yellow
Blue
Gray
Orange
Blue
Pink
White
Tan
Red
L1
Legend
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Relay Contacts-
N.O., N.C.
Fuse
T
G
P
1 2 3
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
CS -
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
Current Switch
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
PSC Fan Speed Relay
PSC Fan Power Relay
Fuses
Freeze protection sensor
HE -
HP -
Heater element
High pressure switch
ER1 to ER4 Aux heat stage relays
LP -
PB1, PB2 -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
TS -
HWL -
Low pressure switch
Power blocks
Power strip
Reversing Valve coil
DIP package 12 position
DIP package 8 position
DIP package 5 position
Hot water pump enable switch
Thermal limit switch
Hot water limit sensor
Logic Board Physical Layout
CSA installed units only
Local codes may require a single source of power supply
Single Disconnect Power
208-230/60/1
Breaker box furnished by installer
L1 L2
F1 F1
N.O.
N.O.
N.C.
N.O.
N.O.
CR1- DHW
Pump
CC-GND
CC
CCLO
CCHI
P4
1 2 3
C
C
R
R
SW1
Off On
7
8
5
6
3
4
1
2
9
10
11
12
P1
1 2 3 4 5 6 7 8
R C Y1 Y2 W O G L
CR2- Loop
Pump
SW2
Off On
7
8
5
6
3
4
1
2
CR3-
Microprocessor
Com
SeriesLogic Board
SW3
Off On
3
4
1
2
5
1
Shut
Down
2 3
P2
C C
4
SL1
IN
5
SL1
Out
6
SL2
IN
7
SL2
Out
Com
CR4-
1
9
1
10
11
12
13
14
15
2
3
4
5
6
7
16
8
8
9
1
2
10
11
12
13
14
3
4
5
6
P3
2
7
ACC
NO
ACC
NC
3
ACC
COM
P6
P5
L1
Circuit Breakers
L2 L1 L2
Aux Elect Power
208-230/60/1
Unit Power
208-230/60/1
Notes:
1 - Place switch to 208V position to operate unit at 208V.
2 - Connection of remote unit that does not have a loop pump for slave operation
3 - 24V Accessory relay (see SW2 - 3 for description of operation)
4 - The blk/wh and gray/wh wires are removed when Aux Heat is installed
5 - Buss lugs L1 and L2 can be removed and dual power wire sets connected directly to box
box lugs L1, L2, and L3, L4.
6 - DHW pump only in models with hot water generation option.
7 - Air Flow Configuration Example: SW1 configured for dip 3 as low, dip 5 as medium, and dip 7 as high speed ECM2 fan.
8 - SW3 - 4 should be in the OFF position when using ECM motor and 17P501A01 electric heat board and should be ON when using ECM2 with 17P514A01 electric heat board.
9 - When using thermostat TA32E12, SW2 -8 should be in the ON position.
When using 24VAC thermostats, SW2-8 should be in the OFF position.
10- When optional electronic air-filter is installed, power for the electronic air-filter is provided by P2-2 and 24 VAC.
11- Optional pumping systems available on residential models only. Internal pump only available on P Series units.
12- Only on 024 and 035 E series models.
13- SW3-2 should be OFF to operate with zone control system and ON to operate with unzoned system.
17
PREMIER INSTALLATION MANUAL
Wiring Schematics
P Series - Single Speed Wiring Schematic - 208-230/60/1, PSC Blower
97P619-36 10/13/05
NOTE 10
Grn
P010-013
PSC
Fan Motor
Wh
Brn
Cap
Grn
P019-066
PSC
Fan Motor
Wh
Brn
Cap
Compressor
Cap
Blu
Tan
S
Red
R
C
Blk
Black
Black
Current Switch
CS
3 Air Flow Settings
3 Air Flow Settings
H M L
P13
Wh
Unit Power
208-230/60/1
L2
T2 T1
CC
L1
Ext Pump
1/2 hp Total
208-230/60/1
Pump Pump
G
H M L C
P13
Wh
Blk
2
PB1
2
1
1
Gray
Yel
Blk
Blk
G
Wh
Or Brn
NOTE 4
NOTE 6
DHW
Pump
Blk/Wh
Gray/Wh
PS1
D
C
A
Blk Blk/Wh
Pink
Blu
Blu
3A
FUSE
208V 240V
Transformer
Switch
NOTE 1
240V L2
240V L2
Fused L2 Fused L2
240V L1
Blu
F1-10A 240V
Red
208V
Blu
240V
NO NO NO NC NO NC
AR
B
Transformer
COM COM
CR1 CR2 CR3 COM CR4 COM
Black
R
Yel
24V
Blk/Wh
S
C
R
Blk
Red
Brown
CC
Violet
Thermostat
R
C
Y1
Y2
L
1
G
W
O
Violet
NOTE 8
NOTE 2
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOTE 9
Optional
Electronic
Air-Filter
P2
Shut
Down
C
C
SL1 In
SL1 Out
Not
Used
6
7
4
5
P1
R
C
Y1
Y2
W
O
G
LO
CC
CC-GND
5
6
7
8
3
4
1
2
NOTE 3
P3
Acc Com
Acc NC
Acc NO
1
2
3
1 2 3
P4
Microprocessor
Logic Control
(DC Voltage)
ECM2
Air Flow
Settings
NOTE 7
SW1 On
6
7
4
5
1
2
3
10
11
8
9
12
SW2 On
1
2
3
4
Test / Norm
Loop / Well
Fan / Comp
Dehum / Norm
5
6
No Htg3 / Htg3
Inputs / Norm
7 Outputs / Norm
8 24 VAC / TA32E12
SW3 On
1
2
3
4
5
2 Speed / 1 Speed
Zone (See Note 11)
No RPM / RPM
EH (See Note 7)
Must be ON
Main Logic PCB
9
2
P5
11
4
10
5
13
6
7
14
1
12
3
8
14
12
6
15
10
9
2
1
3
13
7
4
5
8
P6
C
11
16
Not Used
Not Used
Orange
Orange
Not Used
Not Used
Pink
Pink
Yellow
Yellow
Blue
Blue
Black
Black
Not Used
Not Used
Not Used
Orange
Blue
Pink
White
Tan
Red
Not Used
Black
Violet
Yellow
Blue
Gray
Brown
LP
T
T
CS
CO
RV
HWL
FP
HP
SW4
G
Y
R
R
R
R
R
R
LED Normal Display Mode
Drain
Water Flow
High Press
Low Press
Air Flow
Status
DHW Limit
DHW off
Field Selection Dips - #1 On, #6 On, #7 On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure > 380 PSI Lockout
Low Pressure < 15 PSI Lockout
ECM2 RPM < 100 rpm Lockout
Microprocessor malfunction*
HWL thermistor > 130°F
DHW pump switch off
*Green LED not flashing
Current Fault Status
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure > 380 PSI
Low Pressure < 15 PSI
ECM2 RPM < 100 rpm
Not Used
HWL thermistor > 130°F
DHW pump switch off
Diagnostic Modes
Inputs Outputs
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
Outputs2
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
18
PREMIER INSTALLATION MANUAL
With optional ' EA' Series
Auxiliary ElectricHeat
Typical schematic shown
Auxiliary Electric Heat Power
208-230/60/1
L2 NOTE 5 L1
G L4 L2 L1 L3 G
F2
Brn
Or
3
2
5
4
1
3
2
5
4
1
Blu
Violet
Pink
Yel
P2
Blk
Gray
1
PB2
Pink
Yel
Blk
Gray
ER1
4
3
2
1
P8
NO
ER2
Gray
NO
ER3
NO
Blk
Yel
2
3
1
P7
4
Gray
Blk
Yel
Pink
Pink
Yel
Blk
Gray
HE1
HE2
HE3
ER4
NO
Pink
HE4
Gray
TS1
Blk
TS2
Yel
Pink
TS3
TS4
P10
1 2 3 4 5 6
EA Series PCB
17P514A01
P12
3
15
16
10
8
P10
1
2
5
6
3
4
Orange
Blue
Pink
White
Tan
Red
L1
Legend
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Relay Contacts-
N.O., N.C.
Fuse
T
G
P
1 2 3
CS -
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
HE -
HP -
ER1 to ER4 -
Current Sensor
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
PSC Fan Speed Relay
PSC Fan Power Relay
Fuses
Freeze protection sensor
Heater element
High pressure switch
Aux heat stage relays
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
LP -
PB1, PB2 -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
TS -
HWL -
Low pressure switch
Power blocks
Power strip
Reversing Valve coil
DIP package 12 position
DIP package 8 position
DIP package 5 position
Hot water pump enable switch
Thermal limit switch
Hot water limit sensor
Logic Board Physical Layout
CSA installed units only
Local codes may require a single source of power supply
Single Disconnect Power
208-230/60/1
Breaker box furnished by installer
L1 L2
F1 F1
N.O.
N.O.
N.C.
N.O.
N.O.
CR1- DHW
Pump
CC-GND
CC
CCLO
CCHI
P4
1 2 3
C
C
R
R
SW1
Off On
7
8
5
6
3
4
1
2
9
10
11
12
P1
1 2 3 4 5 6 7 8
R C Y1 Y2 W O G L
CR2- Loop
Pump
CR3-
Logic Board
17P513A02
Com Com
Microprocessor
SW2
Off On
7
8
5
6
3
4
1
2
SW3
Off On
3
4
1
2
5
1
Shut
Down
2 3
P2
C C
4
SL1
IN
5
SL1
Out
6
SL2
IN
7
SL2
Out
CR4-
1
ACC
NO
9
10
11
12
13
14
15
2
3
4
5
6
7
16
8
8
9
1
2
10
11
12
13
14
3
4
5
6
2
P3
7
1
ACC
NC
3
ACC
COM
P6
P5
L1
Circuit Breakers
L2 L1 L2
Aux Elect Power
208-230/60/1
AT Unit Power
208-230/60/1
Notes:
1 - Place switch to 208V position to operate unit at 208V.
2 - Connection of remote unit that does not have a loop pump for slave operation.
3 - 24V Accessory relay (see SW2 - 3 for description of operation)
4 - The blk/wh and gray/wh wires are removed when Aux Heat is installed
5 - Buss lugs L1 and L2 can be removed and dual power wire sets connected directly to box lugs L1, L2, and L3, L4.
6 - DHW pump only in models with hot water generation option.
7 - SW3-4 should be in the ON position when using Premier 2 Electric Heat control 17P514A01, and it should be in the OFF position when using Premier Electric Heat control 17P501A01.
8 - When using thermostat TA32E12, SW2 -8 should be in the ON position. When using
24VAC thermostats, SW2-8 should be in the OFF position.
9 - When optional electronic air-filter is installed, power for the electronic air-filter is provided by
P2-2 and 24 VAC.
10- Unit may be wired with either example shown. Consult installation manual for blower speed wiring instructions.
11- SW3-2 should be OFF to operate with zone control system and ON to operate with unzoned system.
19
PREMIER INSTALLATION MANUAL
Wiring Schematics
P Series - Single Speed Wiring Schematic - 208-230/60/3, ECM Blower
97P618-20 10/13/05
Compressor
T3 T1
CS
Black
T2
Black
Red Blue
Current Switch
Blk
Ext Pump
1/2 hp Total
208-230/60/1
Pump Pump
G
2
PB1
2
1
1 G
Unit Power
208-230/60/3
L3
T3
L2
T2
CC
T1
L1
Blk/Wh
Gray/Wh
NOTE 4
C
A
PS1
D
Blk Blk/Wh
NO
Fused L2
NO
Yel Gray
Fused L2
NO NC NO NC
240V L2
F1-10A 240V
Or Brn
240V L1
208V 240V
Transformer
Switch
NOTE 1
Blu
240V
Red
208V
Transformer
24V
Yel Blk/Wh
NOTE 2
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOTE 8
Optional
Electronic
Air-Filter
CC
W
O
G
L1
Thermostat
R
C
Y1
Y2
Violet
Violet
NOTE 7
SW4
R
R
G
Y
R
R
R
R
P2
Shut
Down
C
C
SL1 In
SL1 Out
Not
Used
6
7
4
5
NOTE 3
P3
Acc Com
Acc NC
Acc NO
1
2
3
P1
R
C
Y1
Y2
W
O
G
LO
CC
CC-GND
1
2
3
4
7
8
5
6
CR1
COM
1 2 3
P4
CR2
COM
CR3 COM CR4 COM
Microprocessor
Logic Control
(DC Voltage)
ECM2
Air Flow
Settings
NOTE 5
SW1 On
6
7
4
5
8
9
1
2
3
10
11
12
SW2 On
1
2
3
4
Test / Norm
Loop / Well
Fan / Comp
Dehum / Norm
5
6
No Htg3 / Htg3
Inputs / Norm
7 Outputs / Norm
8 24 VAC / TA32E12
SW3 On
1
2
3
4
5
2 Speed / 1 Speed
Zone (See Note 9)
No RPM / RPM
ECM, EH (See Note 6)
Must be ON
Main Logic PCB
R
10
3
8
P5
11
4
9
2
13
6
7
14
1
12
5
15
10
9
2
1
3
14
12
6
7
4
5
8
P6
C
13
11
16
Not Used
Black
Violet
Yellow
Blue
Gray
Brown
Not Used
Not Used
Orange
Blue
Pink
White
Tan
Red
Not Used
Pink
Yellow
Yellow
Blue
Blue
Black
Black
Not Used
Not Used
Orange
Orange
Not Used
Not Used
Pink
LP
LED
Drain
Water Flow
High Press
Low Press
Air Flow
Status
DHW Limit
DHW off
Normal Display Mode
Field Selection Dips - #1 On, #6 On, #7 On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure > 380 PSI Lockout
Low Pressure < 15 PSI Lockout
ECM2 RPM < 100 rpm Lockout
Microprocessor malfunction*
HWL thermistor > 130°F
DHW pump switch off
*Green LED not flashing
Current Fault Status
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure > 380 PSI
Low Pressure < 15 PSI
ECM2 RPM < 100 rpm
Not Used
HWL thermistor > 130°F
DHW pump switch off
Diagnostic Modes
Inputs
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
Outputs
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
T
T
CS
Outputs2
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
CO
RV
HWL
FP
HP
20
PREMIER INSTALLATION MANUAL
Brn
Or
Grn
1 2 3 4 5 P11
ECM2
Fan Motor
NOTE 9
3 15 16 10 8 P12
P10
1
2
3
4
5
6
L1
Legend
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Relay Contacts-
N.O., N.C.
Fuse
P
T
G
CS -
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
HE -
HP -
ER1 to ER4 -
Current Switch
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
PSC Fan Speed Relay
PSC Fan Power Relay
Fuses
Freeze protection sensor
Heater element
High pressure switch
Aux heat stage relays
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
LP -
PB1, PB2 -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
TS -
HWL -
Low pressure switch
Power blocks
Power strip
Reversing Valve coil
DIP package 12 position
DIP package 8 position
DIP package 5 position
Hot water pump enable switch
Thermal limit switch
Hot water limit sensor
With optional ' EA' Series
Auxiliary ElectricHeat
Typical schematic shown
Brn
Or
Blu
Violet
Orange
Blue
Pink
White
Tan
Red
Black
Violet
Yellow
Blue
Gray
Grn
1 2 3 4 5 P11
ECM2
Fan Motor
NOTE 9
3 15 16 10 8 P12
Logic Board (Single-Speed Configuration) Physical Layout
Auxiliary Electric Heat Power
208-230/60/3
Grn
P9
1
2
3
5
4
Yel
Blk
P2
L1 L2 L3
F2
Brn
Or
PB2
Gray
1
G
Yel
Blk
Gray
2
1
4
3
P8
ER1
NO
ER2
Gray
NO Blk
ER3
Yel
NO
ER4
NO
2
3
4
1
P7
Gray
Blk
Yel
Yel
Blk
Gray
HE1
HE2
HE3
Gray
TS1
Blk
TS2
Yel
TS3
P10
1 2 3 4 5 6 EA Series PCB
17P514A01
P4
1 2 3
F1 F1
N.O.
N.O.
N.C.
N.O.
N.O.
Com Com
CR1- DHW
Pump
CC-GND
CC
CCLO
CCHI
CR2- Loop
Pump
C
C
R
R
SW1
Off On
7
8
6
5
3
4
1
2
9
10
11
12
P1
1 2 3 4 5 6 7 8
R C Y1 Y2 W O G L
SeriesLogic Board
17P513A02
Microprocessor
SW2
Off On
7
8
5
6
3
4
1
2
CR3-
SW3
Off On
3
4
1
2
5
1
Shut
Down
2 3
P2
C C
4
SL1
IN
5
SL1
Out
6
SL2
IN
7
SL2
Out
CR4-
1
ACC
NO
9
1
10
11
12
13
14
15
2
3
4
5
6
7
16
8
8
9
11
1
2
10
12
13
14
P3
2
5
6
7
3
4
ACC
NC
3
ACC
COM
P6
P5
Notes:
1 - Place switch to 208V position to operate unit at 208V.
2 - Connection of remote unit that does not have a loop pump for slave operation
3 - 24V Accessory relay (see SW2 - 3 for description of operation)
4 - The blk/wh and gray/wh wires are removed when Aux Heat is installed
(ECM2 only).
5 - Air Flow Configuration Example: SW1 configured for dip 3 as low, dip 5 as medium, and dip 7 as high speed ECM2 fan.
6 - SW3-4 should be in the OFF position when using ECM motor and 17P501A01 electric heat board and should be ON when using ECM2 with 17P514A01 electric heat board.
7 - When using thermostat TA32E12, SW2 -8 should be in the ON position.
When using 24VAC thermostats, SW2-8 should be in the OFF position.
8 - When optional electronic air-filter is installed, power for the electronic air-filter is provided by P2-2 and 24 VAC.
9 - SW3-2 should be OFF to operate with zone control system and ON to operate with un-zoned system.
21
PREMIER INSTALLATION MANUAL
Wiring Schematics
P Series - Single Speed Wiring Schematic - 208-230/60/3, PSC Blower
97P619-33 10/13/05
Compressor
PSC
Fan Motor
T3 T1
Brn
CS
Cap T2 Black
Grn
Wh
Black
Red Blue
Current Switch
Blk
3 Air Flow Settings
T3 T2 T1
H M L
P13
Unit Power
208-230/60/3
L3 L2
CC
L1
PS1 NOTE 4
Ext Pump
1/2 hp Total
208-230/60/1
Pump Pump
2
PB1
2
1
1
Black
White
G
Blk/Wh
Gray/Wh
D
C
Blk
Blk/Wh
G
A
208V 240V
Transformer
Switch
NOTE 1
Yel
Or Brn
Gray
Red
208V
Blu
240V
Fused L2
NO
Fused L2
NO NO NC NO
CR1
COM
CR2
COM
CR3 COM CR4 COM
NC
240V L2
F1-10A 240V
Black
240V L1
Transformer
24V
Yel Blk/Wh
NOTE 2
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOTE 8
Optional
Electronic
Air-Filter
CC
Thermostat
R
C
Y1
Y2
W
O
G
L1
Violet
Violet
NOTE 7 P2
Shut
Down
C
C
SL1 In
SL1 Out
Not
Used
6
7
4
5
NOTE 3
P3
Acc Com
Acc NC
Acc NO
1
2
3
P1
R
C
Y1
Y2
W
O
G
LO
CC
CC-GND
1
2
3
4
7
8
5
6
1 2 3
P4
SW4
R
R
G
Y
R
R
R
R
ECM2
Air Flow
Settings
NOTE 5
SW1 On
6
7
4
5
1
2
3
8
9
10
11
12
SW2 On
1
2
3
4
Test / Norm
Loop / Well
Fan / Comp
Dehum / Norm
5
6
No Htg3 / Htg3
Inputs / Norm
7 Outputs / Norm
8 24 VAC / TA32E12
SW3 On
1
2
3
4
5
2 Speed / 1 Speed
Zone (See Note 9)
No RPM / RPM
EH (See Note 6)
Must be ON
Main Logic PCB
LED Normal Display Mode
Drain
Water Flow
High Press
Field Selection Dips - #1 On, #6 On, #7 On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure > 380 PSI Lockout
Low Press
Air Flow
Low Pressure < 15 PSI Lockout
ECM2 RPM < 100 rpm Lockout
Status
DHW Limit
DHW off
*Green LED not flashing
Microprocessor malfunction*
HWL thermistor > 130°F
DHW pump switch off
Microprocessor
Logic Control
(DC Voltage)
Current Fault Status
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure > 380 PSI
Low Pressure < 15 PSI
ECM2 RPM < 100 rpm
Not Used
HWL thermistor > 130°F
DHW pump switch off
R
P5
11
4
9
2
10
3
8
13
6
7
1
12
5
14
15
10
9
2
1
3
14
12
6
7
4
5
8
P6
C
13
11
16
Diagnostic Modes
Inputs
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
Outputs
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
Pink
Yellow
Yellow
Blue
Blue
Black
Black
Not Used
Not Used
Orange
Orange
Not Used
Not Used
Pink
LP
Not Used
Black
Violet
Yellow
Blue
Gray
Brown
Not Used
Not Used
Orange
Blue
Pink
White
Tan
Red
Not Used
T
T
Outputs2
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
CS
CO
RV
HWL
FP
HP
22
PREMIER INSTALLATION MANUAL
Br n r
O
5
4
3
2
1
With optional ' EA' Series
Auxiliary ElectricHeat
Typical schematic shown
Brn
Or
Auxiliary Electric Heat Power
208-230/60/3
Grn
P9
1
2
3
5
4
Yel
Blk
P2
L1 L2
F2
L3
Brn
Or
PB2
Gray
1
G
Blk
Gray
2
1
4
3
P8
Yel
Blk
Gray
ER1
NO
ER2
Gray
NO
Blk
ER3
Yel
NO
2
3
4
1
P7
Gray
Blk
Yel
ER4
NO
HE1
HE2
HE3
Gray
TS1
Blk
TS2
Yel
TS3
P10
1 2 3 4 5 6 EA Series PCB
17P514A01
P12
3
15
16
10
8
P10
1
2
3
4
5
6
Orange
Blue
Pink
White
Tan
Red
Logic Board Physical Layout
L1
Legend
Factory Blower voltage wiring
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Relay Contacts-
N.O., N.C.
Fuse
P
T
G
CS -
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
HE -
HP -
ER1 to ER4 -
Current Switch
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
PSC Fan Speed Relay
PSC Fan Power Relay
Fuses
Freeze protection sensor
Heater element
High pressure switch
Aux heat stage relays
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
LP -
PB1, PB2 -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
TS -
HWL -
Low pressure switch
Power blocks
Power strip
Reversing Valve coil
DIP package 12 position
DIP package 8 position
DIP package 5 position
Hot water pump enable switch
Thermal limit switch
Hot water limit sensor P4
1 2 3
F1 F1
N.O.
N.O.
N.C.
N.O.
N.O.
CR1- DHW
Pump
CC-GND
CC
CCLO
CCHI
C
C
R
R
SW1
Off On
7
8
6
5
3
4
1
2
9
10
11
12
P1
1 2 3 4 5 6 7 8
R C Y1 Y2 W O G L
CR2- Loop
Pump
CR3-
SeriesLogic Board
17P513A02
Com Com
Microprocessor
SW2
Off On
7
8
5
6
3
4
1
2
SW3
Off On
3
4
1
2
5
1
Shut
Down
2 3
P2
C C
4
SL1
IN
5
SL1
Out
6
SL2
IN
7
SL2
Out
CR4-
1
ACC
NO
9
1
10
11
12
13
14
15
2
3
4
5
6
7
16
8
8
9
1
2
10
11
12
13
14
P3
2
3
4
5
6
7
ACC
NC
3
ACC
COM
P6
P5
Notes:
1 - Place switch to 208V position to operate unit at 208V.
2 - Connection of remote unit that does not have a loop pump for slave operation
3 - 24V Accessory relay (see SW2 - 3 for description of operation)
4 - The blk/wh and gray/wh wires are removed when Aux Heat is installed
(ECM2 only).
5 - Air Flow Configuration Example: SW1 configured for dip 3 as low, dip 5 as medium, and dip 7 as high speed ECM2 fan.
6 - SW3-4 should be in the ON position when using Electric Heat control
17P514A01, and it should be in the OFF position when using Electric
Heat control 17P501A01.
7 - When using thermostat TA32E12, SW2 -8 should be in the ON position.
When using 24VAC thermostats, SW2-8 should be in the OFF position.
8 - When optional electronic air-filter is installed, power for the electronic airfilter is provided by P2-2 and 24 VAC.
9 - SW3-2 should be OFF to operate with zone control system and ON to operate with un-zoned system.
23
PREMIER INSTALLATION MANUAL
Wiring Schematics
P Series - Single Speed Wiring Schematic - 265/60/1, ECM Blower
97P618-15 10/13/05
Compressor Current Switch
S C
Blu
CS
Black
R
Black Cap
Red
Tan
Blk
Notes:
1 - Connection of remote unit that does not have a loop pump for slave operation.
2 - 24V Accessory relay (see SW2 - 3 for description of operation)
3 - Air Flow Configuration Example: SW1 configured for dip 3 as low, dip 5 as medium, and dip 7 as high speed ECM2 fan.
4 - When using thermostat TA32E12, SW2 -8 should be in the ON position.
When using 24VAC thermostats, SW2-8 should be in the OFF position.
5 - When optional electronic air-filter is installed, power for the electronic air-filter is provided by P2-2 and 24 VAC.
6 - SW3-4 should be in the OFF position when using ECM motor and 17P501A01 electric heat board and should be ON when using ECM2 with 17P514A01 electric heat board.
7 - SW3-2 should be OFF to operate with zone control system and ON to operate with un-zoned system.
G
Unit Power
265/60/1
L2
T2 T1
CC
L1
Brn
Or
Grn
1 2 3 4 5 P11
240V L2
Fused L2 Fused L2
240V L2
F1-10A 240V
240V L1
Blk
Blu
265V
ECM2
Fan Motor
NO NO NO NC NO NC
CR1
COM
CR2
COM
CR3 COM CR4 COM
Transformer
Yel
24V
Blk/Wh
NOTE 1
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOTE 5
Optional
Electronic
Air-Filter
CC
Thermostat
R
C
Y1
Y2
W
O
G
L1
Violet
Violet
NOTE 4
SW4
Y
R
R
G
R
R
R
R
P2
Shut
Down
C
C
SL1 In
SL1 Out
Not
Used
6
7
4
5
NOTE 2
P3
Acc Com
Acc NC
Acc NO
1
2
3
P1
R
C
Y1
Y2
W
O
G
LO
CC
CC-GND
3
4
5
1
2
6
7
8
1 2 3
P4
Microprocessor
Logic Control
(DC Voltage)
ECM2
Air Flow
Settings
NOTE 3
SW1 On
7
8
5
6
3
4
1
2
9
10
11
12
SW2 On
1
2
3
4
Test / Norm
Loop / Well
Fan / Comp
Dehum / Norm
5
6
No Htg3 / Htg3
Inputs / Norm
7 Outputs / Norm
8 24 VAC / TA32E12
SW3
On
1
2
3
4
5
2 Speed / 1 Speed
Zone (See Note 7)
No RPM / RPM
ECM, EH (See Note 6)
Must be ON
Main Logic PCB
LED Normal Display Mode
Drain
Water Flow
High Press
Low Press
Air Flow
Status
Field Selection Dips - #1 On, #6 On, #7 On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure > 380 PSI Lockout
Low Pressure < 15 PSI Lockout
ECM2 RPM < 100 rpm Lockout
Microprocessor malfunction*
DHW Limit
DHW off
HWL thermistor > 130°F
DHW pump switch off
*Green LED not flashing
Current Fault Status
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure > 380 PSI
Low Pressure < 15 PSI
ECM2 RPM < 100 rpm
Not Used
HWL thermistor > 130°F
DHW pump switch off
R
10
9
2
1
3
12
6
15
7
4
5
14
8
13
P6
C
11
16
12
5
13
6
7
3
8
1
14
11
P5
4
9
2
10
Not Used
Black
Violet
Yellow
Blue
Gray
Brown
Not Used
Not Used
Orange
Blue
Pink
White
Tan
Red
Not Used
Not Used
Not Used
Orange
Orange
Not Used
Not Used
Pink
Pink
Yellow
Yellow
Blue
Blue
Black
Black
LP
Diagnostic Modes
Inputs
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
Outputs
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
T
T
3 15 16 10 8 P12
CS
Outputs2
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
CO
P10
1
2
5
6
3
4
RV
HWL
FP
HP
L1
Legend
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Relay Contacts-
N.O., N.C.
Fuse
CS -
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
HP -
LP -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
Current Switch
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
PSC Fan Speed Relay
PSC Fan Power Relay
Fuses
Freeze protection sensor
High pressure switch
Low pressure switch
Power strip
Reversing Valve coil
DIP package 12 position
DIP package 8 position
DIP package 5 position
Hot water pump enable switch
P
T
G
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
24
PREMIER INSTALLATION MANUAL
Wiring Schematics
P Series - Single Speed Wiring Schematic - 265/60/1, PSC Blower
97P619-21 10/13/05
Compressor Current Switch
NOTE 5
S C
Grn
P010-013
PSC
Fan Motor
Wh
Brn
Cap
3 Air Flow Settings
4 3 2 1 C
P13
4 Air Flow Settings
Grn
P019-034
PSC
Fan Motor
Wh
Brn
Cap
H M L
P13
Cap
Blu
Unit Power
265/60/1
Tan
L2
Red
R
T2 T1
CC
L1
Blk
Black
Black
CS
Notes:
1 - Connection of remote unit that does not have a loop pump for slave operation.
2 - 24V Accessory relay (see SW2 - 3 for description of operation)
3 - When using thermostat TA32E12, SW2 - 8 should be in the ON position.
When using 24VAC thermostats, SW2 - 8 should be in the OFF position.
4 - When optional electronic air-filter is installed, power for the electronic air-filter is provided by P2-2 and 24 VAC.
5 - Unit may be wired with either example shown. Consult installation manual for blower speed wiring instructions.
6 - SW3-4 should be in the OFF position when using the 17P501A01 electric heat board and should be ON when using the 17P514A01 electric heat board.
7 - SW3-2 should be OFF to operate with zone control system and ON to operate with un-zoned system.
Blk
Blk Wh
Wh G
Wh
Blk
RB
Blk
RB
Yellow
Black
Blk
Blu
265V
Fused L2 Fused L2
240V L2
240V L2
F1-10A 240V
240V L1
NO NO NO NC NO NC
NOTE 1
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOTE 4
Optional
Electronic
Air-Filter
CC
Thermostat
R
C
Y1
Y2
W
O
G
L1
Violet
Violet
NOTE 3
CR1
COM
P2
Shut
Down
C
C
SL1 In
SL1 Out
Not
Used
4
5
6
7
NOTE 2
P3
Acc Com
Acc NC
Acc NO
1
2
3
P1
R
C
Y1
Y2
W
O
G
LO
CC
CC-GND
6
7
4
5
8
1
2
3
1 2 3
P4
SW4
R
R
R
R
R
G
Y
R
CR2
COM
CR3 COM CR4 COM
Microprocessor
Logic Control
(DC Voltage)
ECM2
Air Flow
Settings
SW1 On
7
8
5
6
3
4
1
2
9
10
11
12
SW2 On
1
2
3
4
Test / Norm
Loop / Well
Fan / Comp
Dehum / Norm
5 No Htg3 / Htg3
6 Inputs / Norm
7 Outputs / Norm
8 24 VAC / TA32E12
SW3 On
1
4
5
2
3
2 Speed / 1 Speed
Zone (See Note 7)
No RPM / RPM
EH (See Note 6)
Must be ON
Main Logic PCB
LED Normal Display Mode
Drain
Water Flow
High Press
Low Press
Air Flow
Field Selection Dips - #1 On, #6 On, #7 On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure > 380 PSI Lockout
Low Pressure < 15 PSI Lockout
ECM2 RPM < 100 rpm Lockout
Status
DHW Limit
DHW off
Microprocessor malfunction*
HWL thermistor > 130°F
DHW pump switch off
*Green LED not flashing
Yellow
Current Fault Status
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure > 380 PSI
Low Pressure < 15 PSI
ECM2 RPM < 100 rpm
Not Used
HWL thermistor > 130°F
DHW pump switch off
Transformer
Yel
24V
Blk/Wh R
15
10
9
2
1
3
14
12
6
7
4
5
8
P6
C
13
11
16
12
5
13
3
8
1
6
7
14
9
2
10
P5
11
4
Not Used
Black
Violet
Yellow
Blue
Gray
Brown
Not Used
Not Used
Orange
Blue
Pink
White
Tan
Red
Not Used
Not Used
Not Used
Orange
Orange
Not Used
Not Used
Pink
Pink
Yellow
Yellow
Blue
Blue
Black
Black
LP
Diagnostic Modes
Inputs
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
Outputs
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
Outputs2
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
T
T
CS
CO
P12
3
15
16
10
8
P10
1
2
3
4
5
6
RV
HWL
FP
L1
Legend
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Relay Contacts-
N.O., N.C.
Fuse
HP -
LP -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
CS -
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
Current Switch
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
PSC Fan Speed Relay
PSC Fan Power Relay
Fuses
Freeze protection sensor
High pressure switch
Low pressure switch
Power strip
Reversing Valve coil
DIP package 12 position
DIP package 8 position
DIP package 5 position
Hot water pump enable switch
HP
P
T
G
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
25
PREMIER INSTALLATION MANUAL
Wiring Schematics
P Series - Single Speed Wiring Schematic - 460/60/3, ECM Blower
97P618-16 10/13/05
Notes:
Compressor
Current Switch
1 - 24V Accessory relay (see SW2 - 3 for description of operation)
T3 T1
2 - Air Flow Configuration Example: SW1 configured for dip 1 as low, dip 3 as medium, and dip 5 as high speed ECM2 fan.
3 - Connection of remote unit that does not have a loop pump for slave operation
T2
Black
CS
Unit Power
460/60/3
With Neutral
T3
Red
T2
Blue
Black
T1
Black
4 - When using thermostat TA32E12, SW2 -8 should be in the ON position.
When using 24VAC thermostats, SW2-8 should be in the OFF position.
5 - When optional electronic air-filter is installed, power for the electronic air-filter is provided by P2-2 and 24 VAC.
6 - 460 Volt units use a 265 volt, single phase ECM motor and require a dedicated neutral from the service panel.
G N L1 L2 L3 CC
7 - SW3-4 should be in the OFF position when using ECM motor and 17P501A01 electric heat board and should be ON when using ECM2 with 17P514A01 electric heat board.
L3 L2 L1
8- SW3-2 should be OFF to operate with zone control system and ON to operate with un-zoned system.
Note 6
Red
Brn
Violet
Or
White
CC Violet
Violet
Thermostat
R
C
Y1
Y2
W
O
G
L1
NOTE 4
NOTE 3
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOTE 5
Optional
Electronic
Air-Filter
P2
Shut
Down
C
C
SL1 In
SL1 Out
Not
Used
6
7
4
5
NOTE 1
P3
Acc Com
Acc NC
Acc NO
1
2
3
P1
R
C
Y1
Y2
W
O
G
LO
CC
CC-GND
3
4
5
1
2
6
7
8
NO
Fused L2
NO
Fused L2
NO NC NO
CR1
COM
CR2
COM
CR3 COM CR4 COM
NC
240V L2
F1-10A 240V
1 2 3
P4
SW4
Y
R
R
G
R
R
R
R
Microprocessor
Logic Control
(DC Voltage)
ECM2
Air Flow
Settings
NOTE 2
SW1 On
7
8
5
6
9
3
4
1
2
10
11
12
NOTE 3
SW2 On
1 Test / Norm
2
3
Loop / Well
Fan / Comp
4 Dehum / Norm
5 No Htg3 / Htg3
6 Inputs / Norm
7 Outputs / Norm
8 24 VAC / TA32E12
SW3 On
1
2
3
4
5
2 Speed / 1 Speed
Zone (See Note 8)
No RPM / RPM
ECM, EH (See Note 7)
Must be ON
Main Logic PCB
LED Normal Display Mode
Drain
Water Flow
High Press
Low Press
Field Selection Dips - #1 On, #6 On, #7 On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure > 380 PSI Lockout
Low Pressure < 15 PSI Lockout
Air Flow
Status
DHW Limit
DHW off
*Green LED not flashing
ECM2 RPM < 100 rpm Lockout
Microprocessor malfunction*
HWL thermistor > 130°F
DHW pump switch off
Current Fault Status
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure > 380 PSI
Low Pressure < 15 PSI
ECM2 RPM < 100 rpm
Not Used
HWL thermistor > 130°F
DHW pump switch off
Blk
Blu
460V
240V L1
Transformer
24V
Yel Blk/Wh
Grn
1 2 3 4 5 P11
ECM2
Fan Motor
3 15 16 10 8 P12
R
4
9
2
P5
11
10
13
6
7
14
1
12
3
8
5
2
1
3
10
9
12
6
15
7
4
5
14
8
13
P6
C
11
16
Not Used
Not Used
Orange
Orange
Not Used
Not Used
Diagnostic Modes
Inputs
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
Outputs
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
Not Used
Not Used
Orange
Blue
Pink
White
Tan
Red
Not Used
Black
Violet
Yellow
Blue
Gray
Brown
Not Used
Yellow
Yellow
Blue
Blue
Black
Black
LP
T
CO
P10
1
2
5
6
3
4
RV
L1
Legend
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Relay Contacts-
N.O., N.C.
Fuse
CS -
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
HP -
LP -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
Current Sensor
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
PSC Fan Speed Relay
PSC Fan Power Relay
Fuses
Freeze protection sensor
High pressure switch
Low pressure switch
Power strip
Reversing Valve coil
DIP package 12 position
DIP package 8 position
DIP package 5 position
Hot water pump enable switch
FP
CS
Outputs2
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
HP
P
T
G
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
26
PREMIER INSTALLATION MANUAL
NOTE 2
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOTE 5
Optional
Electronic
Air-Filter
CC Violet
Violet
Thermostat
R
C
Y1
Y2
W
O
G
L1
NOTE 3
Wiring Schematics
P Series - Single Speed Wiring Schematic - 460-575/60/3, PSC Blower
97P619-22 10/13/05
Current Switch
Green
PSC
Fan Motor
White
Brown
NOTE 4
Grn
PSC
Fan Motor
Brn
Wh
Cap
Refer to instructions below to change speeds.
- High - L1 to white side of capacitor, L2 to H on motor.
- Med - L1 to white side of capacitor, L2 to M on motor, orange wire to M1 on motor.
- Low - L1 to white side fo capacitor, L2 to L on motor,
Yellow wire to L1 on motor, Orange to M1 on motor.
Compressor
Red
T3
Blue
T2
T1
Black
Black
Black
CS
T3 T2 T1
3 Air flow
Settings
H M L Capacitor Unit Power
460/60/3
L3 L2
CC
L1
Ora Yel
Black
White
3 Air flow
Settings
H M L LI MI
MI LI
G
RB
Black
Blu
460V
Blk
Yellow
RB Black
1 2 3
P4
SW4
Y
R
R
G
R
R
R
R
NO
CR1
COM
P2
Shut
Down
C
C
SL1 In
SL1 Out
Not
Used
4
5
6
7
NOTE 1
P3
Acc Com
Acc NC
Acc NO
1
2
3
P1
R
C
Y1
Y2
W
O
G
LO
CC
CC-GND
7
8
5
6
3
4
1
2
Fused L2
NO
CR2
COM
Fused L2
NO
CR3 COM
NC NO
CR4 COM
Microprocessor
Logic Control
(DC Voltage)
NC
240V L2
F1-10A 240V
ECM2
Air Flow
Settings
SW1 On
6
7
4
5
1
2
3
10
11
8
9
12
SW2 On
1 Test / Norm
2
3
Loop / Well
Fan / Comp
4 Dehum / Norm
5
6
No Htg3 / Htg3
Inputs / Norm
7 Outputs / Norm
8 24 VAC / TA32E12
SW3 On
1
2
3
4
5
2 Speed / 1 Speed
Zone (See Note 6)
No RPM / RPM
EH (See Note 7)
Must be ON
Main Logic PCB
LED Normal Display Mode
Drain
Water Flow
High Press
Low Press
Air Flow
Status
Field Selection Dips - #1 On, #6 On, #7 On
Drain pan overflow Lockout
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure > 380 PSI Lockout
Low Pressure < 15 PSI Lockout
ECM2 RPM < 100 rpm Lockout
Microprocessor malfunction*
DHW Limit
DHW off
*Green LED not flashing
HWL thermistor > 130°F
DHW pump switch off
Yellow
Current Fault Status
#1 Off, #6 On, #7 On
Drain pan overflow
FP thermistor (loop<15°F, well<30°F)
High Pressure > 380 PSI
Low Pressure < 15 PSI
ECM2 RPM < 100 rpm
Not Used
HWL thermistor > 130°F
DHW pump switch off
12
5
13
3
8
1
6
7
14
9
2
10
P5
11
4
11
16
2
1
3
6
15
10
9
5
14
7
4
12
8
13
P6
C
240V L1
R
Yellow
Yellow
Blue
Blue
Black
Black
Not Used
Black
Violet
Yellow
Blue
Gray
Brown
Not Used
Not Used
Orange
Blue
Pink
White
Tan
Red
Not Used
Transformer
P10
1
2
3
4
5
6
16
10
8
P12
3
15
24V
Yel Blk/Wh
L1
Legend
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Relay Contacts-
N.O., N.C.
Fuse
CO
CS -
CC -
CO -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
HP -
LP -
PS -
RV -
SW1 -
SW2 -
SW3 -
SW4 -
Current Switch
Compressor Contactor
Condensate overflow sensor
DHW pump relay
Loop pump relay
PSC Fan Speed Relay
PSC Fan Power Relay
Fuses
Freeze protection sensor
High pressure switch
Low pressure switch
Power strip
Reversing Valve coil
DIP package 12 position
DIP package 8 position
DIP package 5 position
Hot water pump enable switch
Not Used
Not Used
Orange
Orange
Not Used
Not Used
LP
T
CS
RV
FP
P
T
G
Thermistor
Light emitting diode - Green
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
Switch -Hot Water On/Off
Polarized connector
Diagnostic Modes
Inputs
#6 Off, #7 On
Y1
Y2
O
G
W
SL1
Not Used
--
Outputs
#6 On, #7 Off
Compressor
Not Used
RV
FAN
DHW Pump
Loop Pump
Not Used
--
Outputs2
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi
Aux Heat #1
Aux Heat #2
AuxHeat #3
Aux Heat #4
--
HP
Notes:
1 - 24V Accessory relay (see SW2 - 3 for description of operation)
2 - Connection of remote unit that does not have a loop pump for slave operation.
3 - When using thermostat TA32E12, SW2 - 8 should be in the ON position. When using 24VAC thermostats, SW2 - 8 should be in the OFF position.
4 - Some fan motors may be terminated and wired with either example shown. Refer to instructions on motor to change speeds.
5 - When optional electronic air-filter is installed, power for the electronic air-filter is provided by
P2-2 and 24 VAC.
6 - SW3 - 2 should be OFF to operate with zone control system and ON to operate with un-zoned system.
7 - SW3-4 should be in the OFF position when using the 17P501A01 electric heat board and should be
ON when using the 17P514A01 electric heat board.
27
PREMIER INSTALLATION MANUAL
Fan Performance Data
ECM2 Motor
MODEL
P019
P022
P028
MAX
ESP
0.5
0.5
0.5
1
300
–
–
2
400
L
400
400
3
500
M
500
L
500
L
4
600
AIRFLOW DIP SWITCH SETTINGS
5
700
6
800
7
–
8
–
H
600
M
600
700
H
700
M
800
800
900
900
H
–
1000
9
–
–
1100
P034
P040
P046
P040 w/1hp*
P046 w/1hp*
P056
P066
0.5
0.5
0.5
0.75
0.75
0.75
0.75
–
650
650
800
L
800
750
750
10
–
–
–
11
–
–
–
12
–
–
–
–
750
–
850
L
850
600
950
700
L
M
800 900
M
1000
H
1100
H
1150
1050 1150 1250 1325 1375 1475
1225
–
1300
–
750
1000
M
1100
950
1300
H
1050 1150 1250 1325 1375 1475 1550 1600
L M H
1500 – – – – – – –
1000 1100 1300 1500 1600 1800
L M H
900 1000 1200
L
1400
M
1600 1700
–
1850
H
–
2000
–
2200
–
2300 2400
900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400
L M H
Notes: Factory settings are at recommended L-M-H DIP switch locations.
Factory L setting is minimum allowed for cooling.
M-H settings must be located within shaded CFM range.
CFM is controlled within 5% up to the maximum ESP.
Max ESP includes allowance for wet coil and standard fi lter.
* With optional 1 HP fan motor.
•
•
A 12-position DIP switch package on the control allows the airfl ow levels to be set for low, medium, and high speed when using the ECM2 blower motor. Only three of the DIP switches
• can be in the "on" position.
The fi rst "on" switch (the lowest position number) determines the low speed fan setting.
The second "on" switch determines the medium speed fan setting.
The third "on" switch determines the high speed fan setting.
The example to the right shows SW1 on the control board confi gured for the following P028 airfl ow settings.
Low Speed Fan: 500 CFM
Medium Speed Fan: 700 CFM
High Speed Fan: 900 CFM
Off
SW1
8
9
6
7
10
11
12
On
1
2
3
4
5
28
PREMIER INSTALLATION MANUAL
Fan Performance Data
PSC Motor
P028
P034
P040
P046
P056
L
H
M
L
H
M
L
H
M
L
H
M
L
H
M
MODEL
FAN
SPEED
MOTOR
HP
P010
H
MH
ML*
1/10
AIRFLOW (CFM) AT EXTERNAL STATIC PRESSURE (IN. WG)
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.60
0.70
0.80
0.90
1.00
450 440 420 410 380 360 340 330 310 300
410 400 380 370 350 330 310 300 280 270
–
–
–
–
–
–
–
–
–
–
P013
P019
P022
L
H
MH*
ML
L
H
M
L
H
M
1/10
1/6
1/5
370 360 340 330 310 290 280 270 250 240
310 300 280 270 250 240 230 220 210 200
450 440 420 410 390 370 350 340 320 310
400 390 380 370 350 340 320 310 290 280
370
330
790
1020
860
360
320
780
990
840
340
310
775
960
820
330
300
770
930
800
310
290
765
900
780
300
280
760
870
760
290
260
740
850
740
280
250
720
830
720
260
230
690
800
690
250
220
670
720 690 685 680 670 660 650 640 620 600
590 570 560 550 545 540 530 520 510 500
770
670
–
–
–
–
–
–
610
–
–
690
–
720 700 680 650 640 620 600 580 570 550 –
1120 1100 1070 1050 1040 1030 1020 1010 1000 980 830
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
1/3 1020 1000 980 960 920 880 860 840 820 790
1/2
1/2
1/2
860 850 840 830 810 800 780 760 740 710
1360 1340 1300 1270 1230 1200 1170 1150 1120 1090 990 870
1190 1170 1140 1120 1090 1060 1030 1010 970 930 – –
1010 990 970 950 940 920 900 880 860 840
– –
– –
1730 1700 1670 1650 1620 1580 1540 1490 1400 1290
–
–
1510 1500 1490 1480 1450 1430 1400 1380 1350 1320
1170 1160 1150 1140 1130 1120 1100 1080 1050 1030
– –
1710 1660 1630 1590 1560 1530 1490 1460 1410 1370
–
–
–
–
–
–
–
–
–
–
1870 1820 1780 1750 1720 1680 1630 1580 1450 1330 1190
–
1280 1250 1230 1220 1200 1180 1150 1120 1090 1050 –
– – – –
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
2180 2160 2130 2100 2070 2040 1990 1910 1810 1690
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
P066
L
H
M
L
3/4 2030 2010 1990 1970 1950 1930 1910 1880 1850 1830 1780 –
1790 1770 1760 1750 1730 1720 1700 1690 1670 1640 – –
1
–
–
–
–
–
–
– – – – 2540 2520 2490 2460 2430 2410 2320 2230 2130 1980 1820
2430 2390 2360 2340 2310 2290 2270 2250 2220 2190 2120 2050 – – –
2000 1980 1970 1950 1930 1920 1900 1860 1830 1780 – – – – –
Notes: Includes allowance for wet coil and clean factory installed fi lter.
A “ – “ in the table indicates operating range is not recommended.
Factory settings indicated in bold print.
* At 265V, the P010 is shipped on ML and the P013 on MH.
29
PREMIER INSTALLATION MANUAL
Standard Microprocessor Control Operation
The Premier control system is a microprocessor-based printed circuit board conveniently located in the unit control box for easy accessibility. The microprocessor provides control of the entire unit as well as outputs for status modes, faults, and diagnostics. Low voltage terminal strips provide all necessary terminals for fi eld connections. LEDs are located on the front of the unit for quick inspection without removing any access panels. The control offers optimal space conditioning. The board accepts traditional 24VAC thermostat inputs.
Startup
The unit will not operate until all the inputs and safety controls are checked for normal conditions. At fi rst power-up, a four-minute delay is employed before the compressor is energized.
Component Sequencing Delays
Components are sequenced and delayed for optimum space conditioning performance.
Accessory Relay
An accessory relay on the control board allows for fi eld connection of solenoid valves, electronic air cleaners, etc. The accessory relay has a normally open output and a normally closed output. The accessory relay is factory set to control the optional electronic air-cleaner.
Short Cycle Protection
The control employs a minimum “off” time of four minutes and a minimum “on” time of two minutes to provide for short cycle protection of the compressor.
Loop Pump SL Signals
A signal between multiple Premier control boards at the SL inputs and outputs (SL1-In and Out) will provide for remote control of the loop pump on any unit.
Condensate Overfl ow Protection
The Premier control board incorporates an impedance sensing liquid sensor at the top of the drain pan. Upon a continuous 30-second sensing of the condensate, compressor operation is suspended (see fault retry), the condensate overfl ow lockout LED begins fl ashing, and an output signal (LO) is made available for conneciton to a “fault” LED at the thermostat.
Shutdown Input
A simple grounded signal to the “shutdown” input on the control board puts the unit into shutdown mode. Compressor, hot water pump and fan operaiotn are suspended
Safety Controls
The Premier control receives separate signals for a high pressure switch for safety, a low pressure switch to prevent loss of charge damage, and a low suction temperature thermistor for freeze protection. Upon a continuous 30-second measurement of the fault (immediate for high pressure), compressor operation is suspended (see fault retry), the appropriate lockout
LED begins fl ashing, and an output signal (LO) is made available for connection to a “fault” LED at the thermostat.
Testing
The Premier control allows service personnel to shorten most timing delays for faster diagnostics (see fi eld selection DIP switch #1).
30
PREMIER INSTALLATION MANUAL
Standard Microprocessor Control Operation
Fault Retry
All faults (except for low RPM fault with the ECM2 fan motor) are retried twice before fi nally locking the unit out. The
“fault retry” feature is designed to prevent nuisance calls.
Diagnostics
The Premier control board allows all inputs and outputs to be displayed on the LEDs for fast and simple control board diagnosis (see fi eld selection DIP switches #6 and #7).
Resistance Heat Control
For units equipped with internal electric heaters, the electric heat control module contains the appropriate high-voltage control relays. Control signals energize the relays in the proper sequence, and the LED display board indicates which stages are energized.
Fan Speed Control
A DIP switch on the Premier control allows fi eld selection of low and medium fan speeds for cooling in the dehumidifi cation mode or medium and high fan speeds for cooling in the normal mode (ECM2 version only).
Hot Water High Limit
This mode occurs when the hot water thermistor temperature is at or above 130°F for 30 continuous seconds. The DHW limit status LED on the unit illuminates, and the hot water pump de-energizes. Hot water pump operations resume on the next compressor cycle or after 30 minutes of continuous compressor operation during the current thermostat demand cycle.
Hot Water Pump Switch
When the pump switch is engaged, hot water pump operation is disabled, and the pump status LED on the unit illuminates.
ECM2 Airfl ow Selection DIP Switches (SW1)
A 12-position DIP switch package on the Premier control allows the airfl ow levels to be set for low, medium and high speed when using the ECM2 blower motor (refer to the Blower table on page 28).
Only three of the DIP switches can be in the “on” position. The fi rst “on” switch (the lowest position number) determines the “low speed fan” setting. The second “on” switch determines the “medium speed fan” setting, and the third “on” switch determines the “high speed fan” setting.
31
PREMIER INSTALLATION MANUAL
DIP Switch Settings
Field Selection DIP Switches (SW2)
An eight-position DIP switch package on the control allows the fi eld selectable options shown in the table below.
FIELD SELECTION DIP SWITCHES (SW2)
DIP SWITCH
NUMBER
SW 2-
DESCRIPTION
1 Service Test Mode
Allows fi eld selection of “normal” or “test” operational modes. Test mode accelerates most timing functions 16 times to allow faster troubleshooting. Test mode also allows viewing the current status of the fault inputs on the LED display.
SW 2-
SW 2-
2 Freeze Protection Setting
Allows fi eld selection of freeze thermistor fault sensing temperatures for well water (30°F) or antifreeze-protected (15°F) earth loops.
3 Accessory Relay
Allows fi eld selection of the accessory relay to operate with the compressor or fan.
SW 2-
SW 2-
4 Fan Speed Control
Allows fi eld selection of reduced fan speed (85% of selected medium and high speed - ECM only) for cooling in the dehumidifi cation mode.
5 Auxiliary Off
Disables third-stage heating. Full emergency heat would still be available if needed.
SW 2-
SW 2-
SW 2-
Loop Water
Freeze Protection
15°F
Fan
OFF POSITION
Test Mode
Acc Relay Tracks
Dehumidifi cation
Fan Speeds
Disable Heating
Stage 3
6 Diagnostics-Inputs
Allows viewing the inputs from the thermostat to the control board such as Y1, Y2, O, G, W, and SL1-In on the LED display.
7 Diagnostics-Outputs
Allows viewing the outputs from the control board such as compressor, reversing valve, blower, hot water pump, and loop pump on the LED display
Diagnostic
Inputs/Output
Viewed at LEDs
Diagnostic
Outputs Viewed at LEDs
8 Thermostat Selection
Allows fi eld seleciton of the type of thermostat being connected to the Premier control. The DIP switch should be in the “off” position for 24VAC thermostats.
24 VAC
Thermostats
ON POSITION
Normal Timing
Operation
Well Water
Freeze Protection
30°F
Acc Relay Tracks
Compressor
Normal Fan
Speeds
Enable Heating
Stage 3
Normal Display
Viewd at LEDs
Normal Display
Viewed at LEDs
N/A
32
PREMIER INSTALLATION MANUAL
DIP Switch Settings
Factory Setup DIP Switches (SW3)
A fi ve-position DIP switch package on the control allows the fi eld selectable options shown in the table below.
FACTORY SETUP DIP SWITCHES (SW3)
DIP SWITCH
NUMBER
SW 3-
DESCRIPTION
1 Single-Speed
Confi gures the control for single-speed compressor operation and should always be left in the “ON” position.
SW 3-
SW 3-
OFF POSITION
Two-Speed Operation Single-Speed
Operation
2 Zoned/Finish on Second Stage
Confi gures control to operate with zoned or un-zoned systems
Zoned Systems
3 No RPM/RPM
Confi gures the control to monitor the RPM output of an
ECM/ECM2 blower motor. When using IntelliZone with a
PSC fan motor, the control should be confi gured for “NO
RPM” sensing.
PSC Fan/RPM
Monitoring
Disabled
ON POSITION
Un-Zoned Systems
ECM2 Fan/RPM
Monitoring
Enabled
SW 34 AT EH Board and ECM/Premier2 EH Board and ECM2
Confi gures the control to operate with electric heat control board (17P501A01) and ECM motor or with electric heat board (17P514A01) and ECM2
Electric Heat Control -
17P501A01
Electric Heat Control -
17P514A01
SW 35 Must be on Future Use Normal
33
PREMIER INSTALLATION MANUAL
FX10 Control Operation
(Optional Microprocessor)
•
•
•
•
•
•
•
•
FX10 Advanced Control
The Johnson Controls FX10 board is specifi cally designed for commercial heat pumps and provides control of the entire unit as well as input ports for Open N2, LonTalk,
BacNet communication protocols as well as an input port for a user interface. The user interface is an accessory item that can be used to aid in diagnostics and unit setup.
A 16-pin low voltage terminal board provides terminals for common fi eld connections. The FX10 Control provides:
Operational sequencing
High and low-pressure switch monitoring
General lockout
Freeze protection
Condensate overfl ow sensing
Lockout mode control
Emergency shutdown mode
Random start and short cycle protection
Main FX10 Board
(Shown with optional communication card)
User Interface
4 x 20 backlit LCD.
Short Cycle Protection
Allows a minimum compressor “off” time of four minutes and a minimum “on” time of two minutes.
•
•
•
Optional Plug-in Communication Modules -
(compatible with standard BAS protocols)
Open N2
LonTalk
BacNet
Random Start
A delay of 1 to 120 seconds is generated after each power-up to prevent simultaneous startup of all units within a building after the release from an unoccupied cycle or power loss.
Emergency Shutdown
A fi eld-applied dry contact can be used to place the control into emergency shutdown mode. During this mode, all outputs on the board are disabled.
Display
Requires DLI Card/Kit. Up to 2 displays, either 1 local and 1 remote, or 2 remote. (A 2-display confi guration requires identical displays.) Local display can be up to 3 meters from the controller, power supply, and data communication. Remote display can be up to 300 meters from the controller. Remote display must be independently powered with data communication done via 3 pole shielded cable.
Freeze Protection
Field selectable for 15° or 30°F (-9° or -1°C)
•
•
•
Installation Options
Stand-alone controlled by standard room thermostat
Stand-alone with a Zone Temperature Sensor (must have user interface to change set points beyond the allowed +/- 5°F)
Integrated into BAS by adding communication module
•
•
•
Inputs/Outputs
6 Analog Inputs
12 Digital Inputs
9 Digital Output Relays (or 7 relays & 2 triacs)
Control Timing & Fault Recognition Delays
Lead compressor “ON” delay 30 seconds
Lag compressor “ON” delay 60 seconds
(not applicable for single compressor models)
Minimum compressor “ON” time 2 minutes
(except for fault condition)
Short cycle delay
Random start delay
High pressure fault
Low pressure fault
4 minutes
0-120 seconds
<1 second
30 seconds
Freeze protection fault
Condensate overfl ow fault
Low pressure fault bypass
Freeze protection fault bypass
30 seconds
30 seconds
2 minutes
2 minutes
Accessory Outputs
Quantity 2. One cycled with fan, other with compressor.
Note: Refer to Submittal Data SD1981, Application Guide
AGFX10, or BACnet Protocol Implementation Conformance
Statement for more information.
34
PREMIER INSTALLATION MANUAL
Startup Procedures
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Before Powering Unit, Check The Following
:
High Voltage is correct and matches nameplate.
Fuses, breakers and wire size correct.
Low voltage wiring complete.
Piping completed and water system cleaned and fl ushed.
Air is purged from closed loop system.
Isolation valves are open, water control valves or loop pumps wired.
Condensate line open and correctly pitched.
Black/white and gray/white wires in unit control box have been removed if auxiliary heat has been installed in models
019-066.
Dip switches are set correctly.
DHW pump switch is “OFF” unless piping is completed and air has been purged.
Blower rotates freely – foam shipping support has been removed.
Blower speed correct (DIP switch setting ECM blowers only).
Air fi lter/cleaner is clean and in position.
Service/access panels are in place.
Return air temperature is between 50-80ºF heating and 60-95ºF cooling.
Air coil is clean.
Startup Steps
Note: Complete the Equipment Startup/Commissioning Check Sheet during this procedure. Refer to thermostat operating instructions and complete the startup procedure.
1. Initiate a control signal to energize the blower motor. Check blower operation. Desuperheater pump should be de-
energized.
2. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature.
3. First stage cooling will energize after a time delay.
4. Be sure that the compressor and water control valve or loop pump(s) are activated.
5. Verify that the water fl ow rate is correct by measuring the pressure drop through the heat exchanger using the P/T plugs and comparing to unit capacity data in specifi cation catalog.
6. Check the temperature of both the supply and discharge water. (Refer to the table on page 37.)
7. Check for an air temperature drop of 15°F to 20°F across the air coil, depending on the fan speed and entering water
temperature.
8. Decrease the cooling set point several degrees and verify high-speed blower operation.
9. Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop pumps
deactivate.
10. Initiate a control signal to place the unit in the heating mode. Heating setpoint must be set above room temperature.
11. First stage heating will energize after a time delay.
12. Check the temperature of both the supply and discharge water. (Refer to the table on page 37.)
13. Check for an air temperature rise of 20°F to 35°F across the air coil, depending on the fan speed and entering water
temperature.
15. If auxiliary electric heaters are installed, increase the heating setpoint until the electric heat banks are sequenced on when the thermostat is in the Emergency Heat mode. Check amperage of each element.
16. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pumps
deactivate.
17. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required.
18. Set system to desired normal operating mode and set temperature to maintain desired comfort level.
19. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
35
PREMIER INSTALLATION MANUAL
Description of Unit Operation
Note: Fan speed operation below applies only to units equiped with ECM blower motors.
Heating Operation
Heat, 1st Stage (Y1)
The fan motor is started on low speed immediately, the loop pump is energized 5 seconds after the “Y1” input is received, and the compressor is energized on low capacity 10 seconds after the “Y1” input. The fan is switched to medium speed 15 seconds after “Y1” input. The hot water pump is cycled 30 seconds after the “Y1” input.
Heat, 2nd Stage (Y1, Y2)
The hot water pump is de-energized, which directs all heat to satisfying the thermostat, and the fan changes to high speed 15 seconds after the “Y2”input.
Heat, 3rd Stage (Y1, Y2, W) additional stages of resistance heat engage sequentially every 5 minutes.
Emergency Heat
The fan is started on high speed, and the fi rst stage of resistance heat is energized 10 seconds after the “W” input.
Continuing demand will engage the additional stages of resistance heat sequentially every 2 minutes.
Cooling Operation
In all cooling operations, the reversing valve directly tracks the “O” input. Thus, anytime the “O” input is present, the reversing valve will be energized.
Cool, 1st Stage (Y1,O)
The fan motor is started on low speed immediately, the loop pump is energized 5 seconds after the “Y1” input is received, and the compressor is energized 10 seconds after the “Y1” input. In the ECM2 version, the fan is switched to medium speed 15 seconds after “Y1” input (remains in low speed if in dehumidifi cation mode). The hot water pump is cycled
30 seconds after the “Y1” input.
Cool, 2nd Stage (Y1, Y2, O)
The fan changes to high speed (85% of high speed if in dehumidifi cation mode) 15 seconds after the “Y2” input.
Fan (G only)
The fan starts on low speed. Regardless of fan input “G” from thermostat, the fan will remain on low speed for 30 seconds at the end of each heating, cooling or emergency heat cycle.
Lockout Conditions
During lockout mode, the appropriate unit and thermostat lockout LEDs will illuminate. The compressor, loop pump, hot water pump, and accessory outputs are de-energized. Unless the lockout is caused by an ECM2 low RPM fault, the fan will continue to run on low speed. If the thermostat calls for heating, emergency heat operation will occur.
Lockout modes of any kind can be reset at the thermostat after a 5-second waitinng perioud, which restores normal operation but keeeps the unit lockout LED illuminated. Interruption of power to the unit will reset a lockout without a waiting period and clear all lockout LEDs.
High Pressure
This lockout mode occurs when the normally closed safety switch is opened momentarily.
Low Pressure
This lockout mode occurs when the normally closed low pressure switch is opened for 30 continuous seconds.
Freeze Protection (Water Flow)
This lockout mode occurs when the freeze thermistor temperature is at or below the selected freeze protection point
(well 30°F or loop 15°F) for 30 continuous seconds.
Condensate Overfl ow
This lockout mode occurs when the condensate overfl ow level has been reached for 30 continuous seconds.
Fan RPM
When equipped with an ECM2 fan motor, the Premier control board monitors fan RPM to sense operation. This lockout mode occurs if the fan RPM falls below the low RPM limit (100 RPM) for 30 continuous seconds.
36
PREMIER INSTALLATION MANUAL
Operation Logic
OPERATION LOGIC
DATA
Compressor
ECM2 Normal
ECM2 Dehumidify
PSC
Rev Valve
Loop Pump
DHW Pump
Aux Heater
SL 1- Out
Emerg LED
T-Stat Signal
STG1
On
Med
Med
Low
Off
On
On
Off
On
On
Y1
HEATING
STG2
On
STG3
On
High
High
High
Off
On
Off
High
High
High
Off
On
Off
Off
On
Off
Y1, Y2
Staged
On
Off
Y1, Y2, W
EMERG
Off
High
High
High
Off
Off
Off
Staged
Off
On
W
COOLING
STG1
On
STG2
On
Med
Low
Low
On
On
On
High
Med
High
On
On
On
Off
On
Off
Y1, O
Off
On
Off
Y1, Y2, O
FAN ON SL1 - IN ON
–
Low
Low
–
–
–
–
–
–
Off
G
–
–
–
–
–
On
–
–
–
–
–
Typical Water and Air Temperature Changes
WATER
FLOW RATE
3 GPM/TON
1.5 GPM/TON
WATER TEMPERATURE CHANGE
RISE (CLG) DROP (HTG)
9-12
20-26
4-8
10-17
Water Pressure Drop
UNIT
P010
P013
P019
P022
P028
P034
P040
P046
P056
P066
GPM
4.0
5.5
7.0
5.0
7.0
9.0
3.0
4.0
5.0
3.0
4.5
6.0
5.0
8.0
11.0
6.0
9.0
12.0
1.5
2.0
2.5
1.5
2.5
3.5
8.0
11.0
14.0
10.0
13.0
16.0
30° EWT
1.2
2.1
3.2
2.4
3.9
6.2
1.2
2.1
3.5
1.5
3.2
6.0
1.7
3.5
6.2
2.2
4.5
7.2
2.1
3.4
5.2
2.0
4.6
8.1
2.6
4.8
7.5
3.7
6.1
9.3
AIR TEMPERATURE CHANGE
DROP (CLG) RISE (HTG)
15-20 20-35
50° EWT
1.2
2.0
3.1
2.2
3.7
5.9
1.2
2.0
3.3
1.4
3.1
5.8
1.6
3.3
5.9
2.1
4.3
6.8
2.0
3.2
4.9
1.9
4.4
7.7
2.5
4.6
7.2
3.5
5.8
8.9
PRESSURE DROP (PSI)
70° EWT
1.1
2.0
3.0
2.2
3.6
5.7
1.1
2.0
3.2
1.3
3.0
5.6
1.5
3.2
5.7
2.1
4.1
6.6
2.0
3.1
4.7
1.9
4.2
7.4
2.4
4.4
6.9
3.4
5.6
8.6
90° EWT
1.1
1.9
2.9
2.1
3.5
5.5
1.1
1.9
3.1
1.3
2.9
5.4
1.5
3.1
5.5
2.0
4.0
6.4
1.9
3.0
4.6
1.8
4.1
7.2
2.4
4.3
6.7
3.3
5.5
8.3
37
110° EWT
1.1
1.8
2.8
2.0
3.4
5.3
1.1
1.8
3.0
1.3
2.8
5.2
1.5
3.0
5.3
1.9
3.9
6.2
1.8
2.9
4.5
1.7
4.0
7.0
2.3
4.1
6.5
3.2
5.3
8.1
PREMIER INSTALLATION MANUAL
Troubleshooting
To check the unit control board for proper operation:
1.
Disconnect thermostat wires at the control board.
2.
Jumper the desired test input (Y1, Y2, W, O, or G) to the R terminal with the SW2-8 in the “OFF” position to simulate a thermostat signal.
3.
If control functions properly:
- Check for thermostat and fi eld control wiring (use the diagnostic inputs mode).
4. If control responds improperly:
- Ensure that component being controlled is functioning (Compressor, Blower, Reversing Valve, etc.)
- Ensure that wiring from control to the component is functioning (use the diagnostic outputs mode).
- If steps above check properly, replace unit control.
Note: Verify that air and water fl ow rates are at proper levels before servicing the refrigerant circuit.
LED Defi nition
LED
NORMAL DISPLAY
MODE
CURRENT FAULT
STATUS
Drain
Field Selection DIPs:
1-On, 6-On, 7-On
Drain Pan Overfl ow
Lockout
1-Off, 6-On, 7-On
Drain Pan Overfl ow
Water
Flow
High
Pressure
Low
Pressure
Airfl ow
Status
FP Thermistor
(Loop <15°F Well<30°F)
Lockout
High Pressure >380 PSI
Lockout
Low Pressure <15 PSI
Lockout
ECM2 RPM<100 RPM
Lockout
Microprocessor
Malfunction
FP Thermistor
(Loop<15°F, Well<30°F)
High Pressure >380 PSI
Low Pressure <15 PSI
ECM2 RPM <100 RPM
Not Used
DHW Limit HWL Thermistor >130°F HWL Thermistor >130°F
DHW Off DHW Pump Switch Off DHW Pump Switch Off
DIAGNOSTIC MODES
INPUTS OUTPUTS 1
1-N/A, 6-Off,
7-On
Y1
1-N/A, 6-On,
7-Off
Compressor
Y2
O
G
W
SL1
Not Used
–
Not Used
RV
Fan
DHW Pump
Loop Pump
Not Used
–
OUTPUTS 2
1-N/A, 6-Off,
7-Off
Blower Low
Blower Med
Blower High
Aux Heat #1
Aux Heat #2
Aux Heat #3
Aux Heat #4
–
Typical Superheat/Subcooling
ENTERING WATER
TEMPERATURE
30
50
70
90
HEATING COOLING
SUPERHEAT SUBCOOLING SUPERHEAT SUBCOOLING
9 - 14 5 - 9 25 - 35 15 - 25
10 - 14
12 - 16
N/A
5 - 9
5 - 8
N/A
10 - 18
9 - 14
8 - 13
15 - 25
13 - 18
13 - 18
Typical Suction & Discharge Pressures
ENTERING WATER
TEMPERATURE
HEATING
SUCTION DISCHARGE
30
50
70
90
35 - 45
55 - 65
70 - 90
90 - 110
170 - 200
185 - 220
200 - 240
220 - 260
COOLING
SUCTION DISCHARGE
62 - 77
70 - 83
73 - 86
75 - 88
95 - 125
125 - 165
170 - 210
220 - 260
38
PREMIER INSTALLATION MANUAL
Preventive Maintenance
Water Coil Maintenance
1.
Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to
2.
infi ltrate the water line. Lines should always be airtight.
Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure.
Note: On open loop systems, if the installation is in an area with a known high mineral content (125 PPM or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water fl owing through the unit the less chance for scaling.
Other Maintenance
Air Coil
To obtain maximum performance, the air coil should be cleaned before startup. A 10% solution of dishwasher detergent and water is recommended for both sides of coil; a thorough water rinse should follow.
CAUTION: Fin edges are sharp.
Fan Motors (ECM & PSC)
Blower Motors are equipped with sealed ball bearings and require no periodic oiling.
Desuperheater Coils
See Water Coil Maintenance section.
Filters
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating conditions and be replaced when necessary. Units should never be operated without a fi lter.
Condensate Drain
In areas where airborne bacteria produce a sludge in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty fi lters. Inspect twice a year to avoid the possibility of overfl ow.
Air Coil
The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken not to damage the aluminum fi ns while cleaning.
Replacement Procedures
Obtaining Parts
When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required.
In-warranty Material Return
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance.
39
Manufactured by WFI
9000 Conservation Way
Fort Wayne, IN 46809
WFI has a policy of continuous product research and development and reserves the right to change design and specifi cations without notice.
©2006 WFI.
Product:
Type:
Size:
Premier
Geothermal/Water Source Heat Pumps
3/4 thru 6 Tons
Document Type: Installation Manual
Part Number: IM1555
Release Date:
Supercedes:
11/06
IM1555 10/05
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project