Mastervolt MASS 24/15-2 User's Manual


Add to my manuals
28 Pages

advertisement

Mastervolt MASS 24/15-2 User's Manual | Manualzz

USERS MANUAL / GEBRUIKERSHANDLEIDING / BETRIEBSANLEITUNG

MANUEL UTILISATEUR / MANUAL DE UTILIZACION / INSTRUZIONI PER L’USO

Mass Charger

MASS 24/15-2 MB; 24/25-2 MB; 24/25-2 DNV MB

FULL AUTOMATIC BATTERY CHARGER

MASTERVOLT

Snijdersbergweg 93,

1105 AN Amsterdam

The Netherlands

Tel.: +31-20-3422100

Fax.: +31-20-6971006 www.mastervolt.com

ENGLISH: PAGE 1

NEDERLANDS: PAGINA

DEUTSCH: SEITE

FRANÇAIS: PAGINA

113

ITALIANO: PÁGINA

Copyright © 2014 Mastervolt, v 1.2 March 2014

10000001887/01

TABLE OF CONTENTS

TABLE OF CONTENTS:

v 1.2 March 2014

1

 

GENERAL INFORMATION .............................................................................................................................................. 4

 

1.1

  Use of this manual .............................................................................................................................................. 4  

1.2

  Validity of this manual ........................................................................................................................................ 4  

1.3

  Use of pictograms .............................................................................................................................................. 4  

1.4

  Identification label ............................................................................................................................................... 4  

1.5

  Liability ............................................................................................................................................................... 4  

2

 

IMPORTANT SAFETY INSTRUCTIONS ......................................................................................................................... 5

 

2.1

  General .............................................................................................................................................................. 5  

2.2

  Explosive gases ................................................................................................................................................. 5  

2.3

  Warnings regarding the use of batteries ............................................................................................................. 6  

2.4

  Warning regarding life support applications........................................................................................................ 6  

2.5

  Guarantee specifications .................................................................................................................................... 6  

3

 

OPERATION .................................................................................................................................................................... 7

 

3.1

  Introduction ......................................................................................................................................................... 7  

3.1.1

  Switching on ...................................................................................................................................... 7  

3.1.2

  Switching off ...................................................................................................................................... 7  

3.2

  Theory of operation ............................................................................................................................................ 7  

3.3

  Front panel ......................................................................................................................................................... 7  

3.3.1

  Bulk (LED 1 illuminates) .................................................................................................................... 8  

3.3.2

  (LED 1 and 2 illuminate) .................................................................................................................... 8  

3.3.3

  Absorption (LED 1, 2 and 3 illuminate) .............................................................................................. 8  

3.3.4

  (LED 1 to 4 illuminate) ....................................................................................................................... 8  

3.3.5

  Float (LED 1 to 5 illuminate) .............................................................................................................. 8  

3.4

  Temperature compensated charging .................................................................................................................. 8  

3.5

  Compensation of the cable losses ...................................................................................................................... 8  

3.6

  alarm function ..................................................................................................................................................... 8  

3.7

  Charging a second battery ................................................................................................................................. 8  

3.8

  Equalize mode .................................................................................................................................................... 8  

4

 

INSTALLATION ............................................................................................................................................................... 9

 

4.1

  Installation environment ..................................................................................................................................... 9  

4.2

  Connections ....................................................................................................................................................... 9  

4.3

  Wiring ................................................................................................................................................................. 9  

4.3.1

  AC wiring ........................................................................................................................................... 9  

4.3.2

  AC safety grounding ........................................................................................................................ 10  

4.3.3

  DC wiring ......................................................................................................................................... 10  

4.4

  Battery capacity ................................................................................................................................................ 10  

4.5

  Battery isolator ................................................................................................................................................. 10  

4.6

  Connection of second battery (3A output) ..................................................................................................... 11  

4.7

  Temperature sensor ......................................................................................................................................... 11  

4.8

  Voltage sense ................................................................................................................................................... 11  

4.9

  Alarm function .................................................................................................................................................. 11  

4.9.1

  Standard alarm mode ...................................................................................................................... 11  

4.9.2

  DC alarm mode ............................................................................................................................... 11  

4.10

  DNV version ..................................................................................................................................................... 11  

4.11

  Connection of accessories ............................................................................................................................... 11  

4.12

  Overview connection compartment .................................................................................................................. 12  

4.13

  Things you need ............................................................................................................................................... 12  

4.14

  Connection ....................................................................................................................................................... 13  

4.15

  Installation step-by-step ................................................................................................................................... 14  

2

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV/ EN

TABLE OF CONTENTS

4.16

  Commissioning after installation ....................................................................................................................... 15  

4.16.1

  General ............................................................................................................................................ 15  

4.16.2

  MasterBus (optional) ....................................................................................................................... 15  

4.17

  Decommissioning ............................................................................................................................................. 15  

4.18

  Storage and transportation ............................................................................................................................... 15  

4.19

  Re-installation ................................................................................................................................................... 15  

5   DIP SWITCH SETTINGS ............................................................................................................................................... 16  

5.1

  DIP Switch operation ........................................................................................................................................ 16  

5.2

  DIP switch functions ......................................................................................................................................... 16  

5.2.1

  Force Float (DIP switch 1) ............................................................................................................... 16  

5.2.2

  Traction setting (DIP switch 2) ......................................................................................................... 16  

5.2.3

  Gel/AGM batteries (DIP switch 3) .................................................................................................... 16  

5.2.4

  Diode setting (DIP switch 4) ............................................................................................................ 16  

6

 

MASTERBUS ................................................................................................................................................................. 17

 

6.1

  What is MasterBus? ......................................................................................................................................... 17  

6.2

  How to set up a MasterBus network ................................................................................................................. 17  

7   MASTERBUS SETTINGS .............................................................................................................................................. 18  

7.1

  Device .............................................................................................................................................................. 18  

7.2

  Presets ............................................................................................................................................................. 18  

7.3

  General ............................................................................................................................................................ 18  

7.4

  Bulk .................................................................................................................................................................. 18  

7.5

  Absorption ........................................................................................................................................................ 18  

7.6

  Float ................................................................................................................................................................. 18  

7.7

  Alarm setpoints ................................................................................................................................................. 19  

7.8

  Traction settings ............................................................................................................................................... 19  

7.9

  Nicad settings ................................................................................................................................................... 19  

7.10

  MLi settings ...................................................................................................................................................... 19  

7.11

  Events .............................................................................................................................................................. 20  

7.11.1

  Mass Charger event source list (Mass Charger as event source) ................................................... 20  

7.11.2

  Mass Charger event target list (Mass Charger as event target) ...................................................... 20  

8   TROUBLE SHOOTING .................................................................................................................................................. 21  

8.1

  Fault finding table ............................................................................................................................................. 21  

9   TECHNICAL DATA ........................................................................................................................................................ 22  

9.1

  Specifications ................................................................................................................................................... 22  

9.2

  Dimensions ....................................................................................................................................................... 23  

9.3

  Characteristics (230 V AC) ............................................................................................................................... 24  

10   ORDERING INFORMATION .......................................................................................................................................... 26  

11

 

EC DECLARATION OF CONFORMITY ........................................................................................................................ 27

 

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

3

GENERAL INFORMATION

1.1 USE OF THIS MANUAL

Copyright © 2014 Mastervolt. All rights reserved.

Reproduction, transfer, distribution or storage of part or all of the contents in this document in any form without the prior written permission of Mastervolt is prohibited.

This manual contains important safety and operating instructions for the safe and effective operation, maintenance and possible correction of minor malfunctions of the Mass Charger.

It is therefore obligatory that every person who works on or with the Mass Charger is completely familiar with the contents of this manual, and that he/she carefully follows the instructions and important safety instructions contained herein.

1.2 VALIDITY OF THIS MANUAL

All of the specifications, provisions and instructions contained in this manual apply solely to standard versions of the Mass Charger delivered by Mastervolt.

This manual is valid for the following models:

Part no Model

40020156 Mass 24/15-2 230V/50-60Hz charger MB

40020256 Mass 24/25-2 230V/50-60Hz charger MB

40720266 Mass 24/25-2 230V/50-60Hz charger DNV

Enl.Cab. CSI MB

These models are further mentioned as “Mass Charger”

For other models see other manuals available on our website: www.mastervolt.com

1.3 USE OF PICTOGRAMS

Safety instructions and warnings are marked in this manual by the following pictograms:

WARNING

A WARNING refers to possible injury to the user or significant material damage to the Mass

Charger if the user does not (carefully) follow the procedures.

CAUTION!

Special data, restrictions and rules with regard to preventing damage.

A procedure, circumstance, etc which deserves extra attention.

1.4 IDENTIFICATION LABEL

IP 23

Type : ChargeMaster 24/80-3

Input : 120/230V AC 50/60 Hz 26A/13A

Design by

Mastervolt

Manufactured in China

Serial number

XD10A0005

Part number

Device version “A”

Figure 1: Identification label

The identification label is located at the right-hand side of the Mass Charger (see figure 1). Important technical information required for service, maintenance & secondary delivery of parts can be derived from the identification label.

CAUTION!

Never remove the identification label.

1.5 LIABILITY

Mastervolt can accept no liability for:

 consequential damage due to use of the Mass

Charger;

 possible errors in the manuals and their results.

4

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV/ EN

IMPORTANT SAFETY INSTRUCTIONS

2 IMPORTANT SAFETY INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS

WARNING

This chapter describes important safety and operating instructions for use of a Mass

Charger in residential, recreational vehicle (RV) and marine applications.

2.1 GENERAL

10 Short circuiting or reversing polarity will lead to serious damage to batteries, Mass Charger, wiring as well as accessories. Fuses can not prevent damage caused by reversed polarity and the warranty will be void.

11 In case of fire, you must use the fire extinguisher which is appropriate for electrical equipment.

12 If applied in a marine application in the United States, external connections to the Mass Charger shall comply with the United States Coast Guard Electrical

Regulations (33CFR183, Sub part I).

1 Before using the Mass Charger, read all instructions and cautionary markings on the Mass Charger, the batteries, and all appropriate sections of the manual.

2 To reduce the risk of electric shock – Do not expose

Mass Charger to rain, snow, spray, moisture, excessive pollution and condensing circumstances.

To reduce risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the Mass

Charger in a non-ventilated room, overheating may result.

3 Use of an attachment or spare part not recommended or sold by Mastervolt may result in a risk of fire, electric shock, or injury to persons.

4 The Mass Charger is designed to be permanently connected to an AC and DC electrical system.

Installation of, and work on the Mass Charger, may be carried out only by a qualified, authorised and trained technician or electrician, consistent with the locally applicable standards and regulations.

5 Make sure that all wiring is properly installed and in good electrical condition; and that wire size is large enough for AC ampere rating of the Mass Charger.

Check the wiring on a regular base, at least once a year. Do not use the Mass Charger when the wiring is undersized or damaged.

6 Do not operate the Mass Charger if it has received a sharp blow, been dropped, or otherwise damaged in any way; take it to a qualified serviceman.

7 Except for the connection compartment, see chapter

4, the Mass Charger may not be opened or disassembled. There are no serviceable parts inside the cabinet. Take it to a qualified, authorized and trained serviceman when service or repair is required.

Incorrect reassembly may result in a risk of electric shock or fire. Only qualified, electrician installers are authorized to open the connection compartment.

8 To reduce risk of electric shock, disconnect the Mass

Charger from both AC and DC electrical system before attempting any maintenance or cleaning.

Turning off controls will not reduce this risk.

9 The Mass Charger must be provided with an equipment-grounding conductor to the AC-input ground terminal. Grounding and all other wiring must comply with local codes and ordinances.

1 WARNING – RISK OF EXPLOSIVE GASES.

WORKING IN VICINITY OF A LEAD-ACID BATTERY

IS DANGEROUS. BATTERIES GENERATE

EXPLOSIVE GASES DURING NORMAL BATTERY

OPERATION. FOR THIS REASON, IT IS OF

UTMOST IMPORTANCE THAT EACH TIME

BEFORE USING THE MASS CHARGER, YOU READ

THIS MANUAL AND FOLLOW THE INSTRUCTIONS

EXACTLY.

2 To reduce risk of battery explosion, follow these instructions and those published by battery manufacturer and manufacturer of any equipment you intend to use in vicinity of the battery. Review cautionary marking on these products.

3 DANGER: To reduce the risk of explosion – Never use the Mass Charger in situations where there is danger of gas or dust explosion or an area in which ignition-protected equipment is required.

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

5

IMPORTANT SAFETY INSTRUCTIONS

2.3 WARNINGS REGARDING THE USE OF

BATTERIES

1 Someone should be within range of your voice or close enough to come to your aid when you work near a lead-acid battery.

2 Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or eyes.

3 Wear complete eye protection and clothing protection.

Avoid touching eyes while working near battery.

4 If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye, immediately flood eye with running cold water for at least 10 minutes and get medical attention immediately.

5 NEVER smoke or allow a spark or flame in vicinity of a battery or engine.

6 Do not short circuit batteries, as this may result in explosion and fire hazard! Be extra cautious to reduce risk of dropping a metal tool onto a battery. It might spark or short-circuit battery or other electrical part and may cause explosion.

7 Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a battery. A battery can produce a short-circuit current high enough to weld a ring or the like to metal, causing a severe burn.

8 Only use the Mass Charger for charging Lead-acid,

NiCad and Li-ion batteries and the supply of users attached to these batteries, in permanent systems. Do not use the Mass Charger for charging dry-cell batteries that are commonly used with home appliances. These batteries may burst and cause injury to persons and damage to property.

9 NEVER charge a frozen battery.

10 Excessive battery discharge and/or high charging voltages can cause serious damage to batteries. Do not exceed the recommended limits of discharge level of your batteries.

11 If it is necessary to remove a battery, always remove the grounded terminal from the battery first. Make sure all accessories are off, so as not to cause an arc.

12 Be sure that the area around the battery is well ventilated while the battery is being charged. Refer to the recommendations of the battery manufacturer.

13 Batteries are heavy! It may become a projectile if it is involved in an accident! Ensure adequate and secure mounting and always use suitable handling equipment for transportation.

2.4 WARNING REGARDING LIFE SUPPORT

APPLICATIONS

The Mass Charger is not sold for applications in any medical equipment intended for use as a component of any life support system unless a specific written agreement pertaining to such intended use is executed between the manufacturer and Mastervolt. Such agreement will require the equipment manufacturer either to contract additional reliability testing of the Mass Charger and/or to commit to undertake such testing as a part of the manufacturing process. In addition the manufacturer must agree to indemnify and not hold Mastervolt responsible for any claims arising from the use of the Mass Charger in the life support equipment.

2.5 GUARANTEE SPECIFICATIONS

Mastervolt guarantees that this unit has been built according to the legally applicable standards and specifications. Should work take place, which is not in accordance with the guidelines, instructions and specifications contained in this users manual, then damage may occur and/or the unit may not fulfil its specifications. All of these matters may mean that the guarantee becomes invalid.

The guarantee is limited to the costs of repair and/or replacement of the product. Costs for installation labor or shipping of the defective parts are not covered by this guarantee.

6

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV/ EN

OPERATION

3 OPERATION

3.1 INTRODUCTION

The MASS battery charger is a full-automatic high efficiency battery charger/rectifier, developed and produced by Mastervolt The MASS series features a family of advanced quality battery chargers. The Mass

Charger not only charges batteries rapidly and safely, it supplies the connected consumers at the same time. In addition, the Mass Charger is secured against short circuit, overload and high temperatures in an industrial environment.

3.1.1 Switching on

The battery charger will be switched on by the ON/OFF switch. One of the front LEDs will light up now and the charging starts immediately.

The battery charger will be switched off by the ON/OFF switch.

WARNING

Switching off the Mass Charger does not cut off the connection to the batteries or the ACsource. This means that voltages are still available inside the apparatus.

3.2 THEORY OF OPERATION

The battery charger is equipped with an intelligent 3-stage charge characteristic which takes care of an optimal charge of your batteries (see fig. 2). When switched on, the Mass Charger always starts at Bulk phase.

1 2 3 4 5

BULK ABSORPTION FLOAT

LEDs in charge stage, see fig. 5

30 100%

28

26

24

22

20 50% full charge voltage (V) charge current (A)

0% charge time

Fig. 2: Example: charge characteristic

To prevent your batteries from overcharging a new cycle only starts when the battery voltage has been under the level of 12.8/25.6 or 51.2V for longer than 30 seconds or after a hard reset by switching the on/off switch back and forward.

See figure 3. On the front of the Mass Charger LED 9 to

13 represent the charging current. The more LEDs are illuminated, the higher the charging current. LED 1-5 represent the charging state.

Fig 3: Front panel of the battery charger

Illuminating Meaning

LED’s

Normal operation, LED 6 illuminates green

1 Charger on, BULK stage

1+2+3

1+2+3+4

ABSORPTION, Uout = abs. (28.5V)

3 hrs after start max bulk timer, or I < return amps

1+2+3+4+5 FLOAT, 6 hrs after start max bulk timer, or I < return amps for 15 min or longer

Charge current 0-5% of full current 9

9+10

9+10+11

Charge current 5-25% of full current

Charge current 25-50% of full current

9+10+11+12 Charge current 50-75% of full current

9+10+11+12+13 Charge current 75-100% of full current

6 Green: normal operation, Red: fault condition, Off: standby or off

7

Fault condition, LED 6 illuminates red

6 red +1 Battery sense error

6 red +2

6 red +3

Green: MasterBus communication,

Off: no MasterBus communication

Charger temperature too high

Short circuit indication, charger will reduce the charge current to 25%

DC error, DC voltage too low or too high

Temperature sense error

6 red +4

6 red +5

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

7

OPERATION

3.3.1 Bulk (LED 1 illuminates)

The battery is empty when only the first LED Bulk/ON illuminates. In this stage the Mass Charger gives full current (see fig. 2 stage A) and the battery voltage will slowly increase.

3.3.2 (LED 1 and 2 illuminate)

After reaching the level of 27.6V (24V charger) the battery is charged for about 25% and the second LED will also illuminate. The Mass Charger still gives the maximum output current and the voltage will increase till the absorption voltage level (see fig. 2 stage A). The maximum time of stage A is 8 hours.

3.3.3 Absorption (LED 1, 2 and 3 illuminate)

The battery has been charged for 80% (fig. 2 stage B).

The Mass Charger limits the charge voltage to a safe level and the charge current will decrease slowly during charging.

3.3.4 (LED 1 to 4 illuminate)

The charge voltage is limited at the absorption level. As the battery is almost full, the charge current will further decrease.

3.3.5 Float (LED 1 to 5 illuminate)

When all LEDs are illuminated the battery is fully charged.

The float charge stage provides a lower output voltage, sufficient enough to maintain the batteries at 100% charge but low enough to prevent your batteries from unnecessary stress. In this stage the Mass Charger is able to supply full current to the connected users/loads.

The Mass Charger automatically resumes operation in Bulk stage after it was disconnected from an AC-source temporarily.

CHARGING

By installing the battery temperature sensor the charge voltages are automatically adapted for deviating temperatures. This can increase the battery’s life time substantially and save you a lot of money.

See figure 4. When the battery temperature is low, the charge voltage increases. On the other hand, when the battery temperature is high, the charge voltage is decreased. Over charge and gassing are prevented this way. This will extend the life of your batteries.

3.5 COMPENSATION OF THE CABLE LOSSES

The Mass Charger can compensate the voltage drop occurring over the DC cables. For this purpose the Mass

Charger is provided with terminals for sense wires. The sense wires are connected closest possible to the batteries in order to charge them with the right voltage.

When only the minus sense wire is connected only the losses of the minus DC cable will be compensated.

Connecting both cables produces the best result, all losses will be compensated until a maximum of 3V in total.

The battery charger is equipped with an integrated alarm function. External equipment can be controlled by the potential free contacts of this alarm. The maximum switch current of the relay is 1A. Exceeding the setpoints (refer to section 7.7) will activate the alarm.

3.7 CHARGING A SECOND BATTERY

Some installations have a main battery set and besides this a smaller (cranking) battery with the same voltage. It is possible to maintain this second battery with the 3A output of the battery charger.

An equalizing charge can be necessary after very deep discharges and/or inadequate charges. This has to be carried out according to the specifications of the battery manufacturer.

WARNING!

Equalization is ONLY applicable for wet type batteries and will damage gel/AGM/Spiral type batteries!

Incorrect use of the equalize mode may lead to hazardous situations. Do not smoke or use any naked flame or other sources of ignition due to risk of explosion. Always ventilate the battery room during equalizing to clear the air.

During equalizing the batteries are brought into the gas state and permitted load voltages may be exceeded. Refer to chapter 9 for characteristics. Therefore appropriate measures must be taken, e.g. disconnect all loads from the battery and ventilate the room. For these reasons the equalizing mode should only be used by trained technical engineers.

The equalizing mode can only be started when the Mass

Charger is in operation. To start the equalize mode, select

Equalize in the MasterBus device settings (section 7.2).

Battery temperature (°C)

Figure 4:

Temperature compensated charging

8

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / EN

4 INSTALLATION

During installation and commissioning of the Mass

Charger, the important safety instructions are applicable at all times. See chapter 2 of this manual.

Please check the contents of the box before you start with the installation. The contents of the box need to be:

 The Mass battery charger;

 Battery temperature sensor (incl. 6 mtr cable);

 A MasterBus terminating device;

 This user’s manual;

If one of these items is missing, please contact your supplier.

Choosing a location to install:

 Install the Mass charger in a well-ventilated room protected against rain, snow, spray, vapour, bilge, moisture and dust.

 Ambient temperature: 0 ... 60°C / 32°F … 140°F;

(power derating above 40°C / 104 °F to decrease the internal heat sink temperature).

 Humidity: 0-95% non condensing.

 Never use the Mass charger at a location where there is danger of gas or dust explosions

 Mount the Mass Charger in such a way that obstruction of the airflow through the ventilation openings is prevented. No objects must be located within a distance of 10 cm / 4 inch around the Mass

Charger.

 Mount the Mass Charger vertically, with the connecting cables downwards.

 Do not install the Mass Charger in the same compartment as the batteries. Do not mount the Mass

Charger straight above the batteries because of possible corrosive sulphur fumes.

4.2 CONNECTIONS

Before making the connection between the battery charger and the system be sure that the AC and DC system are switched off. Remove the fuses in order to protect yourself against unexpected start up.

INSTALLATION

4.3 WIRING

CAUTION!

The wire and fuse sizes stated in this manual are given as example only. Prescribed wire and fuse sizes may be different due to local applicable regulations and standards.

4.3.1

AC wiring

Check if the voltage of your mains source or generator corresponds with the AC input voltage of the battery charger as mentioned on the type number plate, see section 1.4.

Strip the cable according to fig. 5. It is important that the green/ yellow earth wire is ± 1 cm (0.4 inch) longer than the other wires. By accidentally pulling at the cable, the earth wire stays connected to the Mass Charger longer which offers additional safety. Connect the green/yellow wire to PE, brown to L1 and the blue wire to the N terminal. brown minimal green/yellow blue

Fig5

Don’t use a cross section that is smaller than indicated.

See table below to select the appropriate cross section for the AC wiring (up to 6m / 20ft length):

AC Current

3-4 Amp

Minimum cross section:

0.5 mm² AWG 19

4-6 Amp 0.75 mm² AWG 18

Connection of AC-wiring and recommended wire colours:

Wire color

Brown or black

Meaning

Phase

Must be connected to:

L1

Green/Yellow Earth PE / GND

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

9

INSTALLATION

4.3.2 AC safety grounding

WARNING!

The ground wire offers protection only if the cabinet of the Mass Charger is connected to the safety ground. Connect the ground terminal (PE

/ GND) to the hull or the chassis.

CAUTION!

For safe installation it is necessary to insert a

Residual Current Device (earth leakage switch) in the AC input circuit of the Mass Charger.

Keep the cable connection between charger and batteries shortest possible. If available, use coloured battery cables.

If this is not possible, mark the plus and the minus cables with coloured insulating tape, e.g. red for plus and blue/black for minus. Use the following diameters:

Model Mass Charger

Mass 24/15-2 MB

L <3 m

6 mm²

Length 3-6 m

10 mm²

Mass 24/25-2 MB

Mass 24/25-2 DNV MB

10 mm²

10 mm²

16 mm²

16 mm²

Connection of main batteries

1 Pull the cables through the cable glands of the Mass

Charger.

2 Crimp on the ring M6 terminals to the cable.

3 Connect the cables to the terminals of the Mass

Charger. Pay attention to the polarity, positive on positive / negative on negative.

4 Integrate a suitable fuse (charger fuse) in the positive cable. When using a DC distribution with fuses, no additional fuse is necessary.

5 Cut the cables at length and crimp on the ring terminals. Connect the cable to the DC distribution or batteries.

CAUTION

Reversing the positive and negative battery poles will severely damage the Mass Charger.

Too thin cables and/or loose connections can cause dangerous overheating of the cables and/or terminals.

Lay the positive and negative cables next to each other to limit the electro magnetic field around the cables. The negative cable should be connected directly to the negative post of the battery bank or the ground side of a current shunt. Do not use the hull or chassis frame as the negative conductor.

Always follow the instructions published by battery manufacturer. The minimum required battery capacity for

Mastervolt gel batteries is as follows:

Model Mass Charger Minimum required

Mass 24/15-2 MB

Mass 24/25-2 MB

Mass 24/25-2 DNV MB battery capacity

50 Ah

60 Ah

60 Ah

If one or more batteries or battery sets must be charged at the same time via one output, a battery isolator should be used. It isolates the different battery sets from one another, in order to prevent one discharging the other. A consequence of the battery isolator is a voltage drop of 0.6

Volt. This voltage drop can be compensated in two ways:

1 By changing DIP-switch 4 to On (Diode enabled);

2 By using the voltage sense function (see section 4.8);

CAUTION

Never use both methods. Your batteries will be overcharged and severely damaged!

Mastervolt offers several Battery Isolators, refer to www.mastervolt.com.

For a proper installation, see also the connection diagram included with the battery isolator.

Steps:

1 Check if the Mass Charger, the main supply and the

DC distribution are switched off.

2 Check if the Dc fuses have been removed.

3 Connect the battery isolator(s) using cables with the same diameter as the battery cables.

4 Compensate the voltage drop over the battery isolator by changing the setting of dip switch 4 (see fig. 7).

5 Switch on the Mass Charger.

10

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / EN

4.6 CONNECTION OF SECOND BATTERY

(3A OUTPUT)

The battery chargers are standard equipped with a second charge output of 3A in order to give a small second battery set like a starter battery a maintenance charge. The maximum charge current of the second output is 3A, which comes from the main output.

 Use 2.5 to 4 mm 2

cable for connection.

 Connect the minus of the second battery to the minus of the main battery.

 Connect the plus of the second battery to the +3A terminal of the Mass Charger (see fig. 7 and 8).

 Integrate a 10A slow blow fuse in the plus cable.

The standard temperature sensor is provided with 6 m cable and a double-sided tape for easy installation.

Determine the warmest place on the battery set and make it clean and grease free. Remove the piece of paper from the tape and stick the sensor on the battery. Plug the modular cable into a terminal at the right of the Mass

Charger (see fig. 7). It is not necessary to shorten the cable. When you want to shorten it anyway please notice the polarity of the plug and use the old connector as an example.

To shorten the charge time substantially, the battery cable losses can be compensated by using the sense function.

Use 0,75 mm

2

, preferably red and black wire and secure these with fuses of 2A slow blow. Connect the wires with the two upper terminals of the green connector at the right side of the cabinet (see fig. 7). Pay good attention to the polarity of the wires, red on +S and black on -S. Now connect the other side of the wires: black on the minus of the battery and red on the battery side of the Mass

Charger fuse.

4.9 ALARM FUNCTION

The battery charger is equipped with a potential free contacts alarm relay, see figure 7. The alarm function has two modes: standard (factory setting) and DC alarm mode

(continuous mode).

INSTALLATION

4.9.1 Standard alarm mode

In this mode the relay responds to all fault conditions that the Mass Charger can detect such as: no AC input voltage, too low DC voltage, voltage sense failure, temperature sense failure.

4.9.2 DC alarm mode

To enable this mode a DIP switch setting needs to be changed (switch 1 and 2 at ON). The alarm now works as a DC alarm and responds to the battery voltage only.

Note: In the DC alarm mode the electronics stay active permanently and drain a very small current of ± 25mA, also when the Mass Charger is switched off.

The Mass Charger 24/25-2 DNV is equipped with a larger connection compartment that offers more room for the cabling. Refer to section 9.2 Dimensions for more information on the larger DNV housing.

4.11 CONNECTION OF ACCESSORIES

The battery charger is equipped with several terminals for accessories. Cable to connect the accessories is not delivered as a standard. Accessories can be plugged in at all times. The standard remote panel must be connected with an appropriate communication cable.

Figure 6: Standard remote panel C3-RS, art. no 70403040

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

11

INSTALLATION

4.12 OVERVIEW CONNECTION COMPARTMENT

Figure 7 shows the Mass Charger connections.

2 AC cable gland

3 Screw terminal AC input (N,L)

4 MasterBus cable gland

5 Cable glands DC (+,-)

6 Output extra battery (max 3A)

7 Main positive output

8 Temperature sensor port

9 2 MasterBus ports

11 DIP switch module

12 Voltage sense/ potential free alarm contact

Figure 7: Overview connections Mass Charger

4.13 THINGS YOU NEED

Make sure you have all the parts you need to install the Mass Charger:

Product

Mass Charger (included)

Battery temperature sensor with cable and plug (included).

DC-cable to connect the positive DC connection (+) of the Mass Charger to the positive pole of the DCdistribution; for specifications see section 4.3.3.

Quantity

1

1

1

DC-cable to connect the negative DC connection (–) of the Mass Charger to the negative pole of the DCdistribution; for specifications see section 4.3.3.

DC-fuse holder with a DC-fuse, to be integrated in the positive DC-cable.

1

Screws / bolts (Ø 6mm) (with plugs) to mount the cabinet to a surface. Use mounting materials which are suitable to carry the weight of the Mass Charger

AC cable* to connect the AC input to an external power source (e.g. a shore connection or a generator set);

1

4

Batteries. See section 4.4 for recommended capacity

Appropriate and reliable cable terminals, cable lugs, battery terminals and cord end terminals

1

X

X

* Double insulated three wire cable with wire colours according to the locally applicable regulations. The applicable length and wire diameter depend on the electrical installation (see section 4.3.1).

We recommend as a minimum tool kit:

 Socket wrench 13mm to fix the DC-input (battery) cables

 Flat blade screw driver 1.0 x 4.0 mm to fix the screw terminals

 Tools to fix the screws / bolts (Ø 6mm) with plugs to mount the cabinets to a surface

 Philips screw driver to open the connection area of the Mass Charger

 2 mm flat blade screw driver for the sense terminal (figure 7 point 12).

12

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / EN

4.14 CONNECTION

WARNING

Let installation work be done by a licensed electrician. Before beginning with the connection of the wiring, make the AC distribution as well as the DC distribution voltage free.

CAUTION!

Short circuiting or reversing polarity may lead to serious damage to the batteries, the Mass

Charger, the cabling and/or the terminal connections. Fuses between the batteries and the Mass Charger can not prevent damage caused by reversed polarity. The damage as a result of reverse polarity is detectable by the service department and is not covered by the warranty.

This schematic is to illustrate the general placement of the

Mass Charger in a circuit. It is not meant to provide detailed wiring instructions for any particular electrical installation.

INSTALLATION

CAUTION!

Too-thin cables and/or loose connections can cause dangerous overheating of the cables and/or terminals. Therefore tighten all connections well, in order to limit transition resistance as far as possible. Use cables of the correct size.

NOTE:

If the battery temperature remains within 15-

25°C, connection of the battery temperature sensor is optional.

NOTE:

The Mass Charger is feasible for the connection of MasterBus and RS 232 compatible remote control panels.

AC voltage (V)

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

Figure 8: Installation drawing of the Mass Charger

13

INSTALLATION

4.15 INSTALLATION STEP-BY-STEP

1

Mark the position of the mounting spots using the drilling dimensions.

2

Place the four screws first and hang the Mass Charger over them. Then fix the Mass to the wall by securing the screws.

3

Open the connection compartment by loosening the two screws.

7

Attach the battery temperature sensor to the casing of the main battery bank .

Plug the temperature sensor cable into the

“temp.sensor” jack.

4

Feed the AC wiring through cable gland and connect the wiring to the screw terminals.

Tighten the cable gland firmly.

5

Connect the DC-cabling of the house bank, positive to +, negative to –.

+ -

6

Connect second battery bank:

Connect the DC-wiring of the second battery bank (max. 3A).

This bank has a common negative with the main battery.

7

Option: Connect the Mass Charger to the

MasterBus network.

8

The factory setting of the Mass Charger is optimal for most installations. Sometimes however, it is desirable to change these settings. See ch. 5 DIP switch adjustment and chapter 7 for MasterBus settings.

9

Check all wiring; see also figure 8 for wiring details. If everything is all right, close the connection compartment by fixing the two screws.

14

10

Continue with section 4.16 for commissioning of the Mass Charger.

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / EN

INSTALLATION

When your Mass Charger is not new, you have to take into account that former users may have changed the settings. Reset the Mass Charger to factory settings when there is any doubt (see section 7.1).

4.16.1 General

The factory settings of the Mass Charger are optimal for most installations. With some applications however, it is desirable to change these settings. Therefore several adjustments can be made. See chapters 5 and 7.

NOTE:

The DIP-switches must be adjusted prior to commissioning; all other settings can only be made after commissioning.

CAUTION!

Check the polarity of all wiring before commissioning: positive connected to positive

(red cables), negative connected to negative

(black cables).

If all wiring is OK, place the DC-fuse(s) of the DCdistribution to connect the batteries to the Mass Charger.

WARNING

When placing this fuse, a spark can occur, caused by the capacitors used in the Mass

Charger. This is particularly dangerous in places with insufficient ventilation, due to the gassing of the batteries an explosion can occur.

Avoid having flammable materials close by.

Now the Mass Charger is ready for operation. After switching on the AC power supply the Mass Charger will initiate the charging process.

During first commissioning the Mass Charger will be recognized by the MasterBus network automatically. The remote control panel of the MasterBus network will indicate that a new device was found.

Some settings can only be changed via the MasterBus interface. See chapter 7 for an overview of all available

MasterBus settings. Refer to the user’s manual of the remote control panel to change these settings.

4.17 DECOMMISSIONING

If it is necessary to put the Mass Charger out of operation, follow the instructions in order of succession as described below:

1 Switch OFF the Mass Charger (see section 3.1.2).

2 Remove the DC-fuse(s) of the DC-distribution and/or disconnect the batteries.

3 Remove the AC-fuse(s) of the AC-input and/or disconnect the AC-mains.

4 Open the connection compartment of the Mass

Charger.

5 Check with a suitable voltage meter whether the inputs and the outputs of the Mass Charger are voltage free.

6 Disconnect all the wiring.

Now the Mass Charger can be demounted in a safe way.

4.18 STORAGE AND TRANSPORTATION

When not installed, store the Mass Charger in the original packing, in a dry and dust free environment.

Always use the original packing for transportation. Contact your local Mastervolt Service Centre for further details if you want to return the apparatus for repair.

4.19 RE-INSTALLATION

To reinstall the Mass Charger, follow the instructions as described in this chapter (chapter 4).

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

15

DIP SWITCH SETTINGS

5 DIP SWITCH SETTINGS

The Mass Charger settings can be adjusted in two ways:

 By means of DIP-switches;

 Via the MasterBus network (by means of a remote control panel or an interface connected to a PC with

MasterAdjust software); see chapter 7.

Once a DIP switch has been set to On,

MasterBus settings are disabled.

CAUTION!

Invalid settings of the Mass Charger can cause serious damage to your batteries and/or the connected load! Adjustments of settings may be undertaken by authorised personnel only!

5.1 DIP SWITCH OPERATION

The Mass Charger has four DIP switches, see figure 9.

These switches are operated by flipping the levers to the other position, using a small screw driver.

5.2 DIP SWITCH FUNCTIONS

See the table below for the functional overview of the four

DIP switches

5.2.1 Force Float (DIP switch 1)

For special applications a fixed charge voltage can be required. The battery charger allows you to change the three stage charge program to a single stage program by activating the function "Force Float", switching DIP switch

1 to "ON".

The charge voltage will be fixed at 26.5V (24V charger)

4 3 2 1 DIP switches/ Settings

0 0 0 0 Standard

1 0 0 0 Diode

0 1 0 0 Gel/AGM

1 1 0 0 Diode Gel/AGM

0 0 1 0 Traction

1 0 1 0 Traction Diode

0 1 1 0 ContMon Traction

1 1 1 0 ContMon Traction

0 0 0 1 ForceFloat

1 0 0 1 ForceFloat Diode

0 1 0 1 ForceFloat Gel/AGM

1 1 0 1 ForceFloat Diode

0 0 1 1 ContMon

1 0 1 1 ContMon Diode

0 1 1 1 ContMon Gel

1 1 1 1 ContMon +

Figure 9: DIP-switches

5.2.2 Traction setting (DIP switch 2)

Setting for traction charging: +0.7 V during bulk and +0.4 V in absorption for 24 V batteries.

5.2.3 Gel/AGM batteries (DIP switch 3)

Some gel/AGM batteries need a higher float voltage for optimal charge. Changing the float voltage can by done by setting DIP switch 3 to "ON". The float voltage will increase to 27.6V (24V charger).

5.2.4 Diode setting (DIP switch 4)

Setting for +0.6 V voltage compensation in case a battery isolator is used.

1 = ON; 0 = OFF

ContMon: Continuous monitor mode. MasterBus,

RS232 and DC-alarm stay functioning at

Diode: mains failure. Remote stays functioning if it has its own power source.

Diode compensation on (+0.6V)

Traction float @ 24V charger).

Traction charging (+0.7V during bulk and

+0.4V in absorption @ 24V charger).

Force float: One step charge program with fixed float voltage.

16

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / EN

6 MASTERBUS

6.1 WHAT IS MASTERBUS?

All devices that are suitable for MasterBus are marked by the MasterBus symbol.

MasterBus is a fully decentralized data network for communication between the different Mastervolt system devices. It is CAN-bus based which has proven itself as a reliable bus-system in automotive applications. MasterBus is used as power management system for all connected devices, such as the inverter, battery charger, generator and many more. This enables communication between the connected devices, for instance to start the generator when the batteries are low.

MasterBus reduces complexity of electrical systems by using UTP patch cables. All system components are simply chained together. Therefore each device is equipped with two MasterBus data ports. As only a few

MasterBus cables are needed, installation and material costs are reduced importantly. New devices can be added to the existing network easily. Consequently the

MasterBus network is highly flexible for extended system configuration. Mastervolt also offers several interfaces like the Modbus and NMEA interface, making even non-

MasterBus devices suitable to operate in the MasterBus network.

For central monitoring and control of the connected devices Mastervolt offers four different panels, from the small Mastervision compatible 120 x 65mm LCD screen up to the full colour MasterView System panel. All monitoring panels can be used for monitoring, control and configuration of all connected MasterBus equipment.

CAUTION: Never connect a non-MasterBus device to the MasterBus network directly! This will void warranty of all MasterBus devices connected.

6.2 HOW TO SET UP A MASTERBUS

NETWORK

Every MasterBus device is equipped with two data ports.

When two or more devices are connected via these ports, a local data network called the MasterBus is formed.

Keep the following rules in mind:

Place a terminating device on both network ends.

OK

Do not make ring networks.

OK

Do not make T-connections in the network.

MASTERBUS

Connections between the devices are made by standard straight UTP patch cables.

At least one device in the network must be MasterBus powering (see specifications). As all powering devices are galvanic isolated, multiple powering devices are allowed.

OK

Terminating device

Terminating device

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

17

MASTERBUS SETTINGS

Below parameters can be changed via the MasterBus network by means of a remote control panel or by means of an interface connected to a PC with MasterAdjust software. See applicable user’s manuals for details.

Value

7.1 DEVICE

Meaning Factory setting Adjustable range

Language

Name

Language that is displayed on a monitoring device connected to the MasterBus.

Name for the Mass Charger.

Battery name

Factory settings

7.2 PRESETS

Name for the main battery bank.

Option to reset the Mass Charger to default settings.

English

CHG Mass+type*

Mass Charger

House Bank

Not reset

EN, NL, DE, FR, ES,

IT

0-12 characters

-

0-16 characters

Not reset, reset

Diode compensate Option for charger diode +0.6 V voltage compensation. If it is enabled, the compensation value is adjustable.

Forced float Option for Forced Float or constant voltage charging. If it is enabled, Forced Float voltage is adjustable.

Disabled Disabled,

Enabled: 0-2.50 V

Continuous mode Option to keep MasterBus powered by the battery when the Mass Charger is disabled.

Gel / AGM

Traction

NiCad

Li-ion

Equalize

Gel/ AGM settings option. It includes fully adjustable Bulk, Absorption and Float settings.

Traction settings option. See section 7.8. Disabled Disabled, Enabled

NiCad settings option See section 7.9. Disabled Disabled,

Li-ion settings option. See section 7.10. Disabled Disabled, Enabled

Option to enable Equalizing. Shows only when no other battery type has been selected.

Warning: Equalize is suitable for wet batteries only! Do not use Equalize for other battery types!

7.3 GENERAL

Max. current Maximum charge current, adjustable model dependent.

Temp. compensate Charge voltage compensation for temperature

(V/°C).

7.4 BULK

Bulk voltage

Max. bulk time

Min bulk time

Start bulk time

Bulk ret. volt.

Bulk ret. time

Bulk voltage

Maximum bulk timer

Minimum bulk timer

Voltage at which to start the bulk timer.

Return to Bulk voltage

Adjustable Return to Bulk time after the Return to

Bulk voltage has been reached.

7.5 ABSORPTION

Abs. voltage

Max absorption

Min absorp. time

Return amps

7.6 FLOAT

Float voltage

Equalize voltage

Equalize time

Absorption voltage

Maximum absorption timer

Minimum absorption timer

Return to Bulk current (in A)

Float voltage

Equalize voltage

Equalize time

Model dependent

-0.060 V/°C

28.50 V

360 min

2 min

27.60 V

25.60 V

30 sec

28.50 V

360 min

15 min

6.0 %*I max

26.50 V

31.00 V

360 min

0-100% * Imax

-1.000 .. 1.000 V/°C

16.00-32.00 V

0-600 min

0-600 min

16.00-32.00 V

16.00-32.00 V

0-255 sec

16.00-32.00 V

0-600 min

0-180 min

0-25% * I max

16.00-32.00 V

16.00-32.00 V

0-600 min

18

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / EN

Value

DC Alrm high on

DC Alrm high off

DC Alrm low on

DC Alrm low off

DC Alrm delay

Meaning

Alarm DC High on

Alarm DC High off

Alarm DC low on

Alarm DC low off

Alarm delay time

Bulk voltage

Max bulk time

Min bulk time

Start bulk time

Bulk ret. volt.

Bulk return time

Abs. voltage

Max absorp. time

Min absorp. time

Return amps

Float voltage

Bulk voltage

Maximum bulk time

Minimum bulk time

Start bulk time

Bulk return voltage

Bulk return time

Absorption voltage

Maximum absorption time

Minimum absorption time

Return to Bulk current (in A)

Traction float voltage

Bulk voltage

Max bulk time

Min bulk time

Start bulk time

Bulk ret. volt.

Bulk return time

Abs. voltage

Max absorp. time

Min absorp. time

Return amps

Float

Bulk voltage

Maximum bulk time

Minimum bulk time

Start bulk time

Bulk return voltage

Bulk return time

Absorption voltage

Maximum absorption time

Minimum absorption time

Return to Bulk current (in A)

NiCad float voltage

Bulk voltage

Max bulk time

Min bulk time

Start bulk time

Bulk ret. volt.

Bulk return time

Abs. voltage

Max absorp. time

Bulk voltage

Maximum bulk time

Minimum bulk time

Start bulk time

Bulk return voltage

Bulk return time

Absorption voltage

Maximum absorption time

Min absorp. time

Return amps

Minimum absorption time

Return to Bulk current (in A)

Forced Float

* Depending on model

LI-ion forced float voltage

Factory setting

32.00 V

31.00V

20.00V

22.00V

30 sec

29.20V

360 min

2 min

27.60 V

25.60 V

30 sec

28.90 V

480 min

15 min

6.0 %*I max

26.50 V

29.00 V

480 min

2 min

26.50 V

27.00 V

30 sec

31.00 V

240 min

240 min

6.0 %*I max

29.00 V

29.20 V

480 min

2 min

26.50 V

26.30 V

240 sec

29.20 V

240 min

15 min

6.0 %*I max

26.50 V

Adjustable range

16.00-32.00 V

16.00-32.00 V

16.00-32.00 V

16.00-32.00 V

0-255 sec

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

(read only)

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

19

MASTERBUS SETTINGS

7.11 EVENTS

Event x source

Event x target

See section 7.11.1 and 7.11.2

Select a connected MasterBus device that should take action due to a Mass Charger event.

Action to be taken by the target device. Event x command

Event x data Data is linked to the command. See also figure 10.

Event x+1 The next event appears after enabling Event x.

Disabled

Select…

Select…

Off

Disabled

Selectable targets are system dependent.

See command list in selected device manual

Off, On, Copy, Copy

Invert, Toggle.

See Event x.

Figure 10 shows the meaning of the event data.

Input (pulses)

The input is represented by an on/off switch.

Output (data)

On changes the status to On at the first signal.

Off changes the status to Off at the first signal.

Copy lets the status follow the input.

Copy Invert lets the status follow the opposite of the input

Copy is used for dimming too by holding the pulse switch pressed for a longer time.

Toggle changes the status at the first signal and back at the second signal. It is used in combination with a pulse switch.

Figure 10: Event data

7.11.1 Mass Charger event source list (Mass Charger as event source)

Charging Mass Charger state is On

Bulk

Absorption

Float

Failure

CSI

Equalize

TC Error

Fan

LED Bulk

LED 20-40

LED Abs

LED 60-80

LED Float

LED Failure

Charge stage is Bulk

Charge stage is Absorption

Charge stage is Float

Charger failure MasterBus alarm

Charger Status Interface MasterBus alarm to generate an audible alarm at charger failure

Mass Charger is in Equalize mode

Battery temperature sensor error

MasterBus signal for an external fan to start (at 50% load / 50°C)

LED Bulk illuminates

LED 2 illuminates (see figure 3)

LED Abs illuminates

LED 4 illuminates (see figure 3)

LED Float illuminates

LED Failure illuminates

7.11.2 Mass Charger event target list (Mass Charger as event target)

Mpc reduce Command to reduce AC current at a 5%/sec rate

Mpc off

Bulk

Absorption

Float

On/ Standby

Command to reduce AC current fast

Command to start the Bulk stage of charge

Command to start the Absorption stage of charge

Command to start the Float stage of charge

Command to switch on the Mass Charger

20

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / EN

TROUBLE SHOOTING

In case of a failure, the Mass Charger display shows an error code to help you find its source. See section 3.3 for error codes. If you cannot solve a problem with the aid of the fault finding table, contact your local Mastervolt

8.1 FAULT FINDING TABLE

Malfunction

No output voltage and/or current

Output voltage too low, charger supplies maximum current

Possible cause

No AC-input.

AC-input voltage too low (< 180VAC).

AC input frequency out of range.

Load that is connected to the batteries is larger than charger can supply.

Batteries not 100% charged.

Service Centre. See www.mastervolt.com. Make sure you have the article and serial number present if you have to contact your local Mastervolt Service Center to solve a problem (See section 1.4)

What to do

Check AC wiring, check remote control panel.

Check input voltage, check generator.

Check input voltage, check generator.

Reduce load taken from the batteries.

Charge current too low Batteries almost fully charged.

High ambient temperature.

Measure battery voltage. After some time this will be higher.

Nothing, this is normal when the battery is almost fully charged.

Nothing; if ambient temperature is more than 40°C the charge current is automatically reduced.

Check AC-input voltage.

Batteries not fully charged

Batteries are discharged too fast

Batteries are too warm, gassing

Low AC input voltage. At lower AC-input voltages the charge current is reduced.

See figure 12.

Charge current too low.

Current to load is too high.

Charge time too short.

Battery temperature too low.

Defective or old battery.

Battery capacity reduced due to wastage or sulphation, stagnation.

Defective battery (short circuit in cell).

Battery temperature too high.

Charge voltage too high.

See “Charge current too low”.

Reduce load taken from the batteries.

Use a battery charger with higher capacity.

Use the battery temperature sensor.

Check battery and replace if necessary.

Charge and recharge a few times, this might help.

Check battery and replace if necessary.

Check battery and replace if necessary.

Use the battery temperature sensor.

Check settings (see chapter 7).

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

21

TECHNICAL DATA

9.1 SPECIFICATIONS

Model Mass 24/15-2 MB Mass 24/25-2 MB Mass 24/25-2 DNV MB

INPUT

Mains voltage

Frequency

Inrush current

Input current

230V, -10% + 15%

50/60 Hz ± 5 Hz

230V, -10% + 15%

50/60 Hz ± 5 Hz

230V, -10% + 15%

50/60 Hz ± 5 Hz

None, the battery charger is equipped with a soft start in accordance with IEC 1003-3

2.5 A 3.6 A 3.6 A

Power factor (Cos phi)

Maximum efficiency

Input power

1

89%

550W

1

89%

800W

1

89%

800W

OUTPUT

Nominal voltage 24V DC

Max charge current (I max

)*

Outputs

15 A

1x15 A and 1x3 A

Charge characteristic*

Battery types*:

Default charge voltages at 25°C three-step, fully automatic

24V DC

25 A

1 x 25 A and 1x3 A three-step, fully automatic

24V DC

25 A

1 x 25 A and 1x3 A three-step, fully automatic

Flooded lead acid, gel/AGM lead acid, NiCd, Mastervolt MLi (see chapter 7 for settings) float 26.5V 26.5V 26.5V

Voltage ripple max. 100mV RMS with resistive load @ full power

3.75 A 6.25 A 6.25 A Short circuit current (1/4 of

I max

)

Cable size (within 3 mtrs)

Charger fuse (external)

ENVIRONMENTAL

6.0 mm2

20A

10 mm2

32A

10 mm2

32A

Ambient temperature

Cooling

Humidity

MASTERBUS

20 to 40°C @ 100% output power, derated with 2,5% / °C above 40°C

Forced air, by means of a ventilator with variable speed

Maximum 95%RV, non condensing

MasterBus menu languages

Dimensions (hxwxd) mm

English, Dutch, German, French, Spanish, Italian

See figure 11

Weight

* Adjustable, see chapter 5.

3.3 kg

Specifications are subject to change without prior notice.

See figure 11

3.3 kg

See figure 11

3.3 kg

22

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / EN

9.2 DIMENSIONS

TECHNICAL DATA

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

Figure 11:

Dimensions of C1 enclosure in mm [inch]

DNV version lengths are underlined

23

TECHNICAL DATA

9.3 CHARACTERISTICS (230 V AC)

Charge current vs input voltage

Figure 12: Charge current versus input voltage

288

Figure 13: Charge characteristic of the three-step Plus charging method (at 25°C / 77°F) For a 24V charger, multiply the voltages by two.

24

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / EN

Float voltage + 2.25V

= 15.50VDC

FLOAT

Float voltage

= 13.25VDC

EQUALIZE

10% of Imax

= voltage

= current

Max equalize time = 6hr

Start equalize cycle by jumper change (disabled when Gel)

Figure 14: Charge characteristic of the equalize charge cycle (at 25°C / 77°F)

TECHNICAL DATA

FLOAT

Figure 15: Temperature compensation characteristic (charge voltage versus temperature)

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

25

ORDERING INFORMATION

10 ORDERING INFORMATION

Part number

77040000

77040100

77040300

77040600

77041000

77041500

77042500

77050100

6502001030

6502100100

6502100150

Description

MasterBus terminating device

MasterBus connection cable (UTP patch cable), 1,0m / 3.3ft

MasterBus connection cable, 3.0m / 10ft

MasterBus connection cable, 6.0m / 20ft

MasterBus connection cable, 10m / 33ft

MasterBus connection cable, 15m / 49ft

MasterBus connection cable, 25m / 82ft

100m / 330ft MasterBus cable

Modular communication cable, cross wired, 6 pole, 6 meter / 19 ft

Modular communication cable, cross wired, 6 pole, 10 meter / 33 ft

Modular communication cable, cross wired, 6 pole, 15 meter / 49 ft

77050000

77030100

77010305

77010400

77020100

77020200

6384002000

6384003200

6381001000

701

6387000600

Set to assemble MasterBus cables. Delivery: 100m / 330ft cable, 50 pcs. modular jacks and crimping tool

MasterBus USB interface, interface between your PC and the MasterBus

MasterView Easy MkII, Touch screen to control and monitor all MasterBus products

MasterView System, Full-colour touch screen to control and monitor all MasterBus products

MasterShunt 500, DC-distribution module for exact readout of battery voltage, charge / discharge current, and state of charge a MasterView monitoring panel. continuous rating: 250A, peak current: 500A

DC Distribution 500, DC connection device with integrated fuses.

Industrial DC fuse 20A DIN 00

Industrial DC fuse 32A DIN 00

Fuse base DIN 00 (max. 160A)

Battery switch 275A

Double pole automatic circuit breaker DPN 6A-B, 1P+N

6387001000

6387001600

6385401610

41500500*

Double pole automatic circuit breaker DPN 10A-B, 1P+N

Double pole automatic circuit breaker DPN 16A-B, 1P+N

Double pole automatic circuit breaker and earth leakage switch DPN VIGI 16A / B / 16mA, 1P + N

Battery temperature sensor, incl. 6 meter / 19 ft cable

* standard included with the delivery of the Mass Charger

Mastervolt can offer a wide range of products for your electrical installation, including an extended program of components for your MasterBus network, AGM, gel and Li-ion batteries, shore power connections, DC distribution kits and many more.

See our website www.mastervolt.com for an extensive overview of all our products.

26

March 2014 / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / EN

EC DECLARATION OF CONFORMITY

11 EC DECLARATION OF CONFORMITY

We,

Manufacturer Mastervolt

1105 AN Amsterdam

The Netherlands

Declare under our sole responsibility that

Product:

Model:

Mass battery charger

Mass 24/15-2 MB (230 V)

Mass 24/25-2 MB (230 V)

Mass 24/25-2 CSI, DNV certified MB (230 V)

Is in conformity with the provisions of the following EC directives:

2006/95/EC (Safety directive); the following harmonized standards have been applied:

 EN 60950-1:2001+ A11:2004 Safety of Information technology equipment

 EN 60335-2-29: 2004 Safety of household and similar electrical appliances

2004/108/EC (EMC directive); the following harmonized standards have been applied:

 EN 61000-6-3: 2007 Emission for residential, commercial and light-industrial environments

 EN 61000-6-2: 2007

 EN 55022: 2006, Class B

Immunity for industrial environments

Information technology equipment - Radio disturbance characteristics

 IEC 61000-3-3

 IEC 61000-4-11

Voltage dip & flicker

Voltage dip & flicker measurement techniques

 IEC 6100-4-4

 IEC 6100-4-5

 IEC 6100-4-3

 IEC 6100-4-6

 IEC 6100-3-2

Burst and surge

Burst & surge measurement techniques

EMC test and measurement techniques

Conducted disturbance immunity

Limits for harmonic current emissions ≤16 A per phase

2011/65/EU (RoHS directive): all serial numbers with device version “N” or higher (refer to section 1.4)

Amsterdam, 18 March 2014

H.A. Poppelier

Product Manager marine & mobile

EN / Mass Charger 24/15-2; 24/25-2; 24/25-2 DNV / March 2014

27

Snijdersbergweg 93, 1105 AN Amsterdam, The Netherlands

Tel : + 31-20-3422100

Fax : + 31-20-6971006

Email : [email protected]

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement

Table of contents