Sierra Monitor Corporation 2050-10 Applicability & effectivity Instruction manual

Add to my manuals
14 Pages

advertisement

Sierra Monitor Corporation 2050-10 Applicability & effectivity Instruction manual | Manualzz

GAS MONITORS

MODELS 2050-00 & 2050-10

MODELS 2060-00 & 2060-10

GAS MONITORS

MODELS 2050-00 & 2050-10

MODELS 2060-00 & 2060-10

APPLICABILITY & EFFECTIVITY

This manual provides instructions for the following Sierra Monitor products:

Model

2050-00

2060-00

Description

Ammonia Gas Monitor

Halocarbon Gas Monitor

The instructions are effective for the above models as of January 1, 2004

Instruction Manual Part Number T10013

Rev. C

TABLE OF CONTENTS

SECTION

1.PRODUCT DESCRIPTION

1.1 Introduction

1.2 Application

1.3 Configuration

1.4 Temperature Range

1.5 Sensor

1.6 Remote Alarm

2. QUICK START

2.1 Overview

2.2 Wiring

3. OPERATION

3.1 Introduction

3.2 Alarms

3.3 Outputs

4. ALARM CALIBRATION

4.1 Factory Alarm Calibration

4.2 Frequency of Alarm Calibration Check

4.3 Alarm Calibration Check Process

4.4 Equipment Required

4.5 Alarm Calibration Procedure

5. SERVICE

5.1 Sensor Replacement

6. INSTALLATION

6.1 Gas Sensor Module Locations

6.2 Mounting

6.3 Wiring

6.4 Power Supply

6.5 Alarm Devices

7. ALARM CONFIGURATION

8. SPECIFICATIONS

9. ACCESSORIES AND REPLACEMENT PARTS

10. LIMITED WARRANTY

4

4

4

4

3

3

3

5

5

5

5

6

6

PAGE

2

2

2

1

1

1

1

10

11

11

11

7

8

8

8

8

8

8

Table of Contents

Instruction Manual

1.0 PRODUCT DESCRIPTION

1.1 Introduction

The Model 2050 Ammonia and Model 2060 Refrigerant/

Halocarbon Gas Monitors are continuous duty, low cost stationary monitors for detection of high levels (50-500

PPM) of ammonia and halocarbon ("freons") refrigerant gases. See the specifications page for a full list of available applicable halocarbons

Model

2050-00

2060-00

Gas

Ammonia

Halocarbons

T T L

X

X

Relay

Table 1.1 Gas Monitor Configurations

X

X

This manual provides instructions for both the 2050 and

2060 series Gas Monitors, including the relay versions.

1.2 Application

These monitors are primarily used in and around freezers, refrigerators, and compressor rooms to warn of leaks and dangerous levels of these gases.

1.3 Configuration factory setpoint for R12 is 500 ppm while the setpoint for R134 a is 50 ppm. See the specifications for more details.

The Model 2050 / 2060 is cross sensitive to other combustible gases. If combustible gasses in excess of 50 ppm are expected in the area please contact Sierra Monitor to determine amount of cross-sensitivity expected for the specific combustible gas. It is not recommended to use this unit in areas with combustible gases present.

An alarm is activated when the concentration of gas exceeds the user-adjustable level. An alarm condition activates the alarm light on the front of the monitor and generates an output signal. On Models 2050-00 and the

2060-00 the output signal a TTL (Transistor-Transistor-Logic signal) can activate a remote alarm through one of Sierra Monitor’s Alarm Panels. (The Model 2102

Dual Channel Alarm Panel can be connected up to 500 feet from the monitors. ) The models can be configured with a 0.5 amp, dry contact relay.

The monitors are housed in a polystyrene enclosure that is suitable for installation in freezer, refrigerator or other applications.

Test connections and adjustment controls are located on the outside of the enclosure and are easily used, even when the operator is wearing hand protection.

The Model 2050 Ammonia monitor has a factory alarm setpoint of

100 ppm NH

3

. This setpoint is user adjustible in the field over a range of 50 to 500 ppm NH

3

. The

Model 2050 calibration can be checked with Hydrogen gas.

The Model 2060 Halocarbon monitor can be calibrated with carbon monoxide and the factory setpoint varies for the specific type of halocarbon present. The

Page:

1

Figure 1.1 Outline View - 2050/2060 Series

2050/2060 Gas Monitors (5/04)

1.4 Temperature Range

The Model 2050 and 2060 have temperature compensated circuitry to provide stabilization in temperatures ranging from -4 o to 158 o F.

However, for optimum operation the unit should be calibrated at the normal temperature expected for the sensor location.

1.5 Semiconductor-Type Sensor

A solid-state semiconductor-type sensor and associated electronic circuitry ensure trouble-free, long-term operation. All the electronic circuitry needed to operate the monitor, except the DC input power, is contained in a compact unit. There are no pumps, filters, or chemical cells to replace or maintain. Except for periodic calibration to verify the alarm setting, no attention is required after installation. The user may adjust the alarm level by applying a different calibration gas concentration.

A sensor self-check feature will flash the alarms on and off alternatively should the sensor fail (open circuit).

The alarm flash includes LEDs, audible alarm, relay or alarm signal as applicable.

1.6. Remote Alarm Available

If a remote alarm is desired, Sierra Monitor’s Alarm Panels, the Model 2102 Dual Channel Alarm Panels can be connected up to 500 feet away from the monitors.

Instruction Manual

2050/2060 Gas Monitors (5/04)

Page:

2

Instruction Manual

2.0 QUICK START

2.1 Overview

The Gas Sensor Module has been supplied factory calibrated and ready for immediate installation and operation. An installer familiar with installation and operation of gas detection products can use this section to begin immediate use of the monitor.

2.2 Wiring

Each module requires four-conductor wiring (two wires for power and two wires for the signal).

2.2.1. Model 2050-2060 Series

The Model 2050-2060 series are designed to mount on any indoor vertical surface. Mount the monitor in the desired location.

The installation must meet any hazardous environmental codes for AC/DC electrical instrumentation.

2.2.2 Wiring Connection

Terminal positions on the electronics board are as follows:

Term inal Function

TB1-1 + VDC (9 – 24)

TB2-1

TB2-2

TB2-3

Relay NC (Norm ally C losed) or

O utput to M odel 2102 Safe

Relay Com m on

Relay NO (Norm ally O pen) or

O utput to M odel 2102 Alarm

Table 2.1

2.2.3 Start-up & Operation

To begin operation of the Gas Sensor Module provide 9 - 24 VDC from a regulated power supply such as one of the Sierra Monitor Alarm

Panels, 2102-XX. Each time the sensor module is powered up it will perform a warm-up for

2 - 60 minutes.

During warm-up the monitor will, first, cycle through safe/alarm/safe condition at one hertz.

This will be followed by a short period of continuous alarm before warm-up is completed.

2.2.4 Configuration

The default configuration for each module is to operate with a buzzer and a normally operating open (NOO) relay. The user can change this configuration using the jumpers provided. Refer to table 6.2.

Page: 3 2050/2060 Gas Monitors (5/04)

Instruction Manual

3.0 OPERATION

3.1 Introduction

Under normal conditions the gas sensor module does not require operator or technician intervention. The following are conditions under which the module requires attention:

- Routine periodic calibration

- Sensor replacement on a planned schedule

or when a sensor failure occurs.

- Periodic cleaning as necessary.

3.2 Alarms

Trouble Alarm

Interrupted contact closure and “red/green” visual indication (once the warm-up time is completed) after unit has been in operation, indicating either a failed sensor or calibration problems.

Buzzer

On/Off

Relay

Oscilating

Relay

Fail Safe

Oscilating

Three alarm conditions are possible. These can be detected visually at the optional Sierra Monitor controller and at the module.

3.3 Outputs

Warm-Up Alarm

Oscillating (On/Off) contact closure and “red/ green” visual indication when power is first connected to the module, followed by a continuous closure of approximately 2-60 minutes indicating warm-up.

Buzzer Relay Relay

Fail Safe

For the non-relay configurations a 5 volt DC TTL signal is provided to activate remote alarms such as the Sierra Monitor Alarm Panels. Relay configuration alarm conditions described above are transmitted to the annunciator as relay contact closures from the monitor.

The alarm outputs are non-latching closed contacts.

As soon as the gas concentration falls below the alarm set-point, the alarm will stop and the alarm output will cause the relay to de-energize and the contacts will open.

On/Off Oscilating Oscilating

During warm-up and failed sensor alarms the relays contact and the display LED's oscillate at approximately one hertz.

Gas Alarm

Sustained contact closure and solid red light

(once the warm-up time is completed) indicating the presence of gas at, or above, the pre-set alarm limit.

Table 2.1

Buzzer Relay

On Closed

Relay

Fail Safe

Open

Page: 4

Instruction Manual

4.0 ALARM CALIBRATION

4.1 Factory Alarm Calibration

The module has been factory calibrated to alarm as indicated in Table 4.1 and as marked on the calibration label shipped with the module.

Model Time Gas cc/min

2050-XX 100 sec. 100 ppm NH

3

50

2060-XX 60 sec. 500 ppm R11 50

500 ppm R12 50

50 ppm R22 50

100 ppm R113 50

70 ppm R123 50

50 ppm R134a 50

40 ppm R141b 50

40 ppm R142b 50

40 ppm R500 50

70 ppm R502 50

Table 4.1

of each gas sensor module be verified monthly during the first three months of operation and then quarterly. More frequent checks are necessary during periods of extreme humidity and temperature changes. The monitor should have operated continuously (uninterrupted) for at least 24 hours prior to calibration adjustment.

4.3 Alarm Calibration Check Process

The output signal of the gas sensor module is calibrated using a calibration gas mixture containing a known concentration of the gas of interest and a balance of air, or using a substitute gas. The concentration of the span gas must be equal to the alarm point desired.

The equivalent substitute gas is 80 ppm Hydrogen (H

(CO) for the Model 2060.

2 for the Model 2050 and 150 ppm Carbon Monoxide

Calibration requires application of the span gas to the sensor and adjustment of the sensitivity adjustment potentiometer.

)

4.2 Frequency of Alarm Calibration Check

The manufacturer recommends that the calibration

Warning: During calibration the alarm will turn on and remote alarms connected to the alarm relays will be activated. Disable the remote alarm if necessary.

Page: 5

Fig. 4-1 Location of Calibration Voltmeter Connections and Adjustments

2050/2060 Gas Monitors (5/04)

4.4 Equipment Required

The following tools and equipment will be required for calibration:

- Jewelers Screwdriver

- Calibration Gas

- Calibration gas delivery system

For accurate calibration use a gas mixture at the required concentration mixed in an air balance, rather than with an inert gas like nitrogen. This gas and the required delivery equipment such as the Model 1200-

26 Calibrator is available from Sierra Monitor Corporation.

4.5 Alarm Calibration Procedure

1.

The monitor should be in the safe condition prior to calibration (green LED “ON”).

Be sure that the area is non-hazardous before proceeding.

2.

With the monitor in operation, expose the sensor to a sample of calibration gas. Apply calibration gas directly to the sensor insuring that the delivery cup loosely covers the sensor. Use 80 PPM H

2

for the Model 2050 and 150 PPM CO for the Model

2060.

3.

The red LED on the face of the monitor should turn

"on". If the alarm occurs within 18-20 seconds and stops within one minute of the removal of the calibration gas, the monitor is in calibration and requires no further adjustment.

4.

If the monitor fails to alarm within 90 seconds of the application of the gas adjust the potentiometer counter clockwise until the alarm turns "on".

5.

If the monitor fails to stop alarming within one minute of the removal of the gas adjust the potentiometer clockwise until the alarm stops.

6.

After adjustment, repeat steps 4 and 5 to verify calibration.

7.

When the calibration is complete, reconnect any alarm equipment as necessary.

2050/2060 Gas Monitors (5/04)

Instruction Manual

Page: 6

Instruction Manual

5.0 SERVICE

5.1 Sensor Replacement

The gas sensor needs replacement when:

It is no longer possible to obtain correct calibration

The failed sensor alarm (oscillating red/green LED) is on

The sensor output signal is noisy, causing incorrect gas alarms.

To replace the sensor:

1.

Confirm that the system power has been removed.

2.

Remove the cover from the main enclosure.

3.

Unplug the sensor connector on the lower right hand corner of the electronics board.

4.

Unscrew the sensor assembly from the end of the enclosure.

5.

Reverse the preceding steps to install the new sensor assembly.

6.

Restore power and allow a minimum of 24 hours for stabilization before recalibration. The calibration should be re-verified after 6 days of continuous operation.

Page: 7

Figure 5-1 Model 2050/2060 Electronics Board Connections

2050/2060 Gas Monitors (5/04)

Instruction Manual

6.0 INSTALLATION

6.1 Gas Sensor Module Locations 6.4 Power Supply

The gas sensor module is a diffusion type sensor that should be located close to the anticipated source or destination of the gas hazard. For heavy gases such as H

2

S install the module within 24 inches of the ground. For lighter gases such as CO and combustible gases use a higher elevation.

The power supplied by the controlling device or an external power supply must meet the following specifications:

Voltage:9 - 24 VDC

Current: 250 mA

After optimum locations are determined based on the above recommendations, consideration should be given to placing the sensors in locations that are accessible for calibration service. Slight adjustments to the location of the sensor may have little impact on effectivity but major effect on accessibility.

6.5 Alarm Devices

The internal relay is rated at 0.5 Amp, normally open dry contact rated at 100 VDC/130 VAC.

6.2 Mounting

To mount the monitor, remove the four svrews in the cover plate and move the cover plate aside. Use screws through the monitoring holes visible in the four corners of the housing to mount the monitor to a wall.

- The installation must meed any hazardous environmental codes for AC/DC electrical instrumentation.

6.3 Wiring

Interconnect wiring from the controller to the module is by 4 conductor 22 AWG (or lower AWG) cable, conduit as necessary. Shielding is not required.

For installations where the distance from the controller to the sensor is greater than 500 feet, 18

AWG cable is recommended.

Terminal Function

TB1-1 + VDC (9 – 24)

TB2-1

TB2-2

TB2-3

Relay NC (Normally Closed) or

Output to Model 2102 Safe

Relay Common

Relay NO (Normally Open) or

Output to Model 2102 Alarm

Table 6.1

The terminal strip on the electronics board in the module. The wiring must be connected as indicated in Figure 6.1 depending upon the controller or relay configuration being used.

2050/2060 Gas Monitors (5/04)

Page:

8

Instruction Manual

Page: 9

Figure 6.1

Interconnect Wiring Table

2050/2060 Gas Monitors (5/04)

Instruction Manual

7.0 ALARM CONFIGURATION

Y es

M ode l 20X or 200X Configure d w ith Ala rm Re la y Output

B uz z er A c tive

Configura tion Jum pe rs

Relay Operation

Default

Ins tall Jum per

JP 6

No

Rem ove Jum per

JP 6

(B es t for 20X)

Norm ally

Not E nergiz ed

Default

Ins tall Jum per

JP 2 pins 1-2

Norm ally

E nergiz ed

Ins tall Jum per

JP 2 pins 2-3

P ower S upply

TB 1-1 TB 1-2

+ DCV

(9-24 V DC)

0 DC

Com m on

W iring Te rm ina tions

TB 2-1

NC

Output Term inals

TB 2-2

Com m on

TB 2-3

NO

M ode l 20X or 200X Configure d for Inte rfa ce to M ode l 2102 Ala rm P a ne l

Y es

Default

Ins tall Jum per

JP 6

B uz z er A c tive

No

Rem ove Jum per

JP 6

(B es t for 20X)

Configura tion Jum pe rs

Relay Operation

Norm ally Norm ally

E nergiz ed Not E nergiz ed

Default

N/A N/A

Interfac e S elec tion

M odel 2102

Ins tall Jum pers

JP 3 pins 1-2

JP 2 pins 1-2

P ower S upply

TB 1-1 TB 1-2

+ DCV

To M odel 2102

Term inal J5 -2 or J6-2

0 DC

To M odel 2102

Term inal J5 -3 or J6-3

W iring Te rm ina tions

Output Term inals

TB 2-3 TB 2-1

S afe

To M odel 2102

Term inal J5 -1 or J6-1

A larm

To M odel 2102

Term inal J5 -4 or

J6-4

Ta ble 6.2

Jum pe r Configura tion a nd W iring Te rm ina tions

TB 2-2

Not Us ed

No Power

Sensor Fail

Safe

Alarm

No Power

Sensor Fail

Safe

Alarm

Relay Operation

Normally Not Energized

TB2-1 NC TB2-2 Common TB2-3 NO

Open

Connected

Oscillating

Connected

Connected

Open

Open

Normally Energized - Fail Safe

TB2-1 NC TB2-2 Common TB2-3 NO

Connected Open

Open

Oscillating

Connected

Connected Open

Table 6.3

Relay Operating States

2050/2060 Gas Monitors (5/04)

Page: 10

Instruction Manual

8.0 SPECIFICATIONS

Indicators:

Sensor Type:

Green LED for Monitor “ON”/Safe

Red LED for Alarm

Solid-state metal oxide semiconductor

Alarm Setpoint::

2050 Series

2060 Series

100 ppm NH

3

R11

R12

500 ppm

500 ppm

R22 50 ppm

R113 100 ppm

R123 70 ppm

R134a 50 ppm

R141b 40 ppm

R142b 40 ppm

R500

R502

40 ppm

70 ppm

User adjustable with calibration over range of 50 to 500 ppm

9.0 ACCESSORIES AND REPLACEMENT PARTS

Calibration Gas:

2050 Series

2060 Series

80 ppm Hydrogen (H

2

)

150 ppm Carbon Monoxide (CO)

9 VDC, 250 mA Power:

Signal Output::

2050-00/2060-00

Response Time: Less than 90 seconds

Operating Temperature Range:

-4 o

to 158 o

F (-20 o

to 70 o

C)

Enclosure Material: Polystyrene

Size:

Nominal 5 volt DC, source 25 mA.

SAFE and ALARM Signals

0.5 AMP dry contact, 100 VDC, 130

VAC

Weight:

5.6 x 3.1 x 2.1 in.

(14.2 x 7.9 x 5.3 cm)

0.3 lb (0.15 Kg)

Alarm Panels

Model 2102-00 Alarm Panel - 2 channel

Model 2102-01 Alarm Panel - 2 channel with audible

Replacement parts

SPF22073 Sensor for 2050-XX

SPF22074 Sensor for 2060-XX

Calibration Accessories

1200-26 Gas Sensor Calibrator w/2 gas cylinders

(specify gas type/conc)

1290-10 Gas Cylinder - Carbon Monoxide 150 PPM

1290-11 Gas Cylinder - Hydrogen 80 PPM

10.0 LIMITED WARRANTY

SIERRA MONITOR CORPORATION warrants its products to be free from defects in workmanship or material under normal use and service for two year after date of shipment.

SMC will repair or replace without charge any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by SMC personnel.

In all cases SMC’s responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty.

All warranties hereunder are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without SMC approval or which have been subjected to accident, improper maintenance, installation or application, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables (ie. calibration gases, batteries), nor to any damage resulting from battery leakage.

Except for the express warranty stated above, SMC disclaims all warranties with regard to the products sold hereunder including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of SMC for damages including but not limited to consequential damages arising out of/or in connection with the use or performance of the product.