INSTALLATION

MANUAL

SECURIT 800L+ CONTROL PANEL

With additional options

CONTENTS

Warnings

Standards

Warranty Statement

Product Description

Available Parts

Intended use

Specifications

Processor Version

Power Supply

Keypads

General

Factory Defaults

Installation

Mounting

Wiring

Battery

Detector Circuits

L+ as Latch Line

L+ as ID- (detector reset)

Sounders

Strobe

Keyswitch Connections

Aux DC power

PCB Layout

Mounting & wiring Keypads

Powering Up

Entering Engineering Mode

Programming

Chime

Sound options

Exit Time

Entry Time

Sounder Duration

Night & Hone Set Exit Time

Circuit Programming

Zone Selections

Extended Programming

Home Set Zone Selection

Engineer Access Code

Engineer Log Review

Engineer Test Options

Restoring Default Programming

Restoring Default Codes

Glossary Of Terms

Information Table

Sounder Wiring Chart

Fault Finding

Wiring Diagram

1

13

13

14

15

9

9

9

7

8

8

9/10

10

10

10

11

11

11/12

6

6

7

5

5

5

7

7

7

7

4

4

4

3

4

4

5

5

4

5

2

2

3

2

2

2

2

3

3

3

3

WARNINGS

Prolonged short circuit of any supply can cause damage to the unit. Take the necessary precautions in not allowing liquids to spill on or into the unit.

STANDARDS

This unit conforms to EMC directive 89/336/EEC & LVD 73/23/EEC. This unit has been tested and has proven to meet all current emission and immunity regulations as set out by the EU. This unit conforms to the requirements of BS4737 part 1 1986 which relates to security control equipment.

WARRANTY STATEMENT

This product is covered by the IntelliSense warranty in force as of the purchase date, a copy may be obtained from the address at the end of this document.

PRODUCT DESCRIPTION

The Securit 800L is an 8 zone programmable microprocessor control panel using state of the art technology and manufacturing techniques. The panel has many advanced features that can only be found in more expensive control panels. These features include two user codes, Chime, Fire, and Keypad PA. There are many options in the programming functions to allow the control panel to be versatile and user friendly. This panel is the ideal choice for residential or light commercial installations.

AVAILABLE PARTS

A selection of spares and extras are available. These are:-

Remote Keypad - giving full control over the control panel.

Spare PCB - for replacement in the event of failure.

These can be obtained from your original place of purchase.

INTENDED USE

This panel is designed to be used in residential and light commercial applications such as homes, small shops etc.

2

PROCESSOR

VERSION

POWER

SUPPLY

KEYPADS

GENERAL

FACTORY

DEFAULTS

SPECIFICATIONS

SPECIFICATION FOR SOFTWARE REVISION NUMBER V3.0

The software revision number is located on the top of the main processor

Power Supply

Mains Supply Voltage

PSU output voltage

Maximum output current

Aux. current

Battery Fuse

Panel Quiescent

Keypads

Supply Voltage

Quiescent Current

Active

Maximum number allowed

230 V AC Nominal

13.7 V Nominal

1 A (total)

500 mA Max.

1 A (20 mm)

40 mA

13.7 V

20 mA

45 mA

6

General

Normal operating temperature 0

°

C to 40

°

C

Humidity 10 to 90% R.H. non condensing

Dimensions

Control Panel Weight

Standby Battery

W 263 mm H 223 mm D 82 mm

2.7 kg Excluding Battery

7.0 Ah 12 V Rechargeable Lead Acid

Standby Time (load dependant) 24 hrs with 2.8 Ahr nom.

60 hrs with 7.0 Ahr nom.

Based on panel, Keypad, & 2 pir’s

40+20+25+25mA = 110mA Quiescent

Cable Runs

Zone/circuits

Sounder

100m max with 50mA load.

50m max with 7/0.2

100m max with 16/0.2 or 2 x 7/0.2

Factory Defaults

User/customer Code 1

User/customer Code 2

Engineer Code

Circuit 1

Circuit 2

Circuit 3

Circuit 4

Circuit 5

Circuit 6

Circuit 7

Circuit 8

Full Set Exit Time

Night set Exit Time

Entry time

Sounder Ring Time

Chimes

Programmable options

1234

Disabled (0000)

7890

Entry Circuit. (Fixed)

Alarm Circuit isolated in Night set.

Alarm Circuit.

Alarm Circuit.

Alarm Circuit.

Alarm Circuit.

Alarm Circuit.

P.A (Personal Attack)

30 Seconds

15 Seconds

30 Seconds

15 Minutes

Disabled

Non selected

3

INSTALLATION

Locate the control panel out of sight, such as in a hall, under stairs or in a cupboard where connection is easy and the detector zone and mains cables can be concealed. Avoid areas subject to high temperatures or humidity such as next to a boiler, airing cupboard or conservatory.

Mounting

1. Remove the lid screws and remove lid.

2. Remove the PCB or keypad packaging.

3. Place the panel in the selected position and mark the three fixing holes.

4. Mount the Panel securely using all three mounting hole positions.

5. Attach the tamper spring and mount the PCB onto the support pillars.

WIRING THE CONTROL PANEL

ELECTRICAL SAFETY NOTICE.

THIS PRODUCT MUST BE EARTHED

This Power Supply must be permanently connected to the mains supply in accordance with current IEE wiring regulation. A 3 amp fused spur, installed by a qualified electrician, is strongly recommended.

INSTALLATION

PROCEDURES

MOUNTING

PROCEDURE

MAINS POWER

WARNING

Any fault which could be mains related must be diagnosed and corrected by a qualified electrician to ensure continued safe operation.

CAUTION: Under certain circumstances the transformer metalwork can reach 70°C. this is normal and within prescribed limits.

Battery connection.

Maximum battery size 12V 7.0Ah

This panel requires a standby battery to be fitted to provide power in the event of mains failure. A valve regulated lead acid battery must be used.

Detector circuits

Connections are provided for up to eight detector circuits of which normally closed detection devices must be used. A common tamper loop is provided for all detection devices marked as 24 HR Tamper. One or more devices may be connected to each alarm circuit. These should be connected in a series configuration. These circuit connections are located to the bottom right of the PCB (see diagram B).

PIR Latch Line (L+)

In the event of two or more detectors (motion sensors or glassbreak detectors) being fitted to any single zone, latching detectors should be used. The 'L+' connection provides this function. It is low (0 V) when unset and high (12 V) when set. It should be connected to the appropriate

SET or LATCH terminal in your detector. See glossary for explanation.

4

BATTERY

SPECIFICATION

DETECTOR

CIRCUITS

LATCH LINE

DESCRIPTION

DETECTOR

RESET

SOUNDERS

EXTERNAL

DEVICES

AUXILIARY

POWER

Detector reset (L+ when programmed for ID)

Some detectors require the removal of power to reset (e.g. Viper Plus ® or

Smoke detectors). The L+ terminal can be programmed to be used as an 'ID' output using option 7-4. The L+ terminal should then be used as the negative supply for these devices. The positive supply should be taken from the AUX +.

Internal Sounders, Speakers, Strobe and Keyswitch Wiring.

DIAGRAM A

Keyswitch Connections

Open = ON

Closed = OFF

Z8 only

OFF

ON

A maximum of two 16 ohm speakers may be fitted in parallel.

External Sounder & Strobe.

Diagram A shows the connection for external sounder and strobe. Please note sounder trigger is applied negative. (Negative ring).

ST- Strobe switched negative trigger.

S Sounder switched negative trigger

+ Sounder hold off/strobe positive supply.

Sounder hold off supply & sounder tamper feed (negative)

-R Sounder tamper return. (negative)

AUX DC - Detector power.

The auxiliary power is provided from connections marked 'AUX'. This is to provide the 12 V supply for detectors e.g. movement or glassbreak detectors.

The auxiliary power output is rated at 500 mA max. (12 VDC nominal). See diagram B

PCB BOARD

LAYOUT

5

DIAGRAM B

MOUNTING A REMOTE KEYPAD MOUNTING

REMOTE

KEYPADS 1. Choose the keypad location and then mark the holes for mounting.

2. Make sure the cable is run through the backbox.

3. Screw the backbox in the selected position making sure it is not twisted.

WIRING A REMOTE KEYPAD

Use 6 core cable for connection of all remote keypads.

Connect the cable into the terminals shown below in diagram C making sure each wire goes to a like named terminal in the panel. C goes to C, D to

D, + to + and

- to -. Wire the tamper wires in series with your existing tamper loop.

WIRING

REMOTE

KEYPADS

Individual keypads do not need to be identified to the system. If more than one remote keypad is used it can be either wired back the control panel or daisy chained from another keypad. All connections are in parallel with the exception of the tamper circuit which MUST be wired in series. (see glossary of terms for series and parallel examples).

DIAGRAM C

KEYPAD

DIAGRAM

POWERING UP

INITIAL POWER UP The lid should remain off the main control panel so that engineer mode may be used. Alternatively, entering 7890 # can also be used to enter engineer mode. If the engineers code is entered and the panel is then left, it will set.

1. Switch the mains supply on, the internal sounder will start. This denotes a tamper alarm.

2. Enter 1 2 3 4 followed by the # (hash) key - this will silence the sounder and the TAMPER LED flashes. This has now acknowledged and cancelled the alarm, however because either the panel or keypad lid is removed your main tamper loop is open, this is normal.

3. Connect your battery and walk test the control panel. This will make sure all the zones are clear.

4. Power Down and complete the wiring of the control panel. NEVER wire the control panel live.

5. Power back up, cancel the alarm and enter engineering mode by entering 7, 8, 9, 0. The panel is now ready for programming.

6. If no programming is required close any lids that are open and press the

# key. This exits engineering mode. Now refer to the users manual for customer options.

INITIAL POWER

UP

NO

PROGRAMMING

NEEDED?

6

ENTER

ENGINEERING

MODE

EXIT

ENGINEERING

MODE

STAY IN

ENGINEERING

MODE

PROGRAMMING

To enter engineering mode, enter the engineering code and then press the #

(HASH) key. This forces the panel into engineering mode Note: If left unattended for approximately 60 seconds it will revert to day mode.

To exit engineering mode, confirm any options you have selected with the *

(STAR) key, then close ALL tamper circuits and wait for approximately 60 seconds after which the panel will automatically exit engineering mode or pressing the # (HASH) key will manually exit engineering.

If you need to stay in engineering for longer unattended periods, once in engineering mode open a tamper circuit. The easiest way to do this is to remove the lid of the panel or keypad.

PROGRAMMING

GENERAL

CHIME

SOUND

OPTIONS

TIMERS

EXIT TIME

ENTRY TIME

To exit all options press * to confirm the selection The accept tone will sound.

CHIME 2 1 (Range - any alarm zone)

Enter 2-1. Enter the keys corresponding to the zone(s) required to chime. On exit from engineer mode zones selected will be set to chime, the customer may disable chime only on zones programmed with this option (see user manual).

If no zones are selected the user will not be able to access their chime option and an error tone will be heard.

SOUND OPTIONS 2 2

Enter 1

Enter 2

Disable exit / entry sounds in part and home set

Disable accept / error sounds in part and home set

EXIT TIME 3 0 (Range 10-90 Seconds.)

Enter 3-0. A new time can be programmed by entering a key from the table.

Enter 1

Enter 2

Enter 3

Enter 4

Enter 5

Enter 6

ENTRY TIME

10 Seconds. Led 1 on.

15 Seconds. Led 2 on.

30 Seconds. Led 3 on. (Factory default)

45 Seconds. Led 4 on.

60 Seconds. Led 5 on.

90 Seconds. Led 6 on.

3-1 (Range 10-90 seconds)

Enter 3-1. A new time can be programmed by entering a key from the table.

Enter 1

Enter 2

Enter 3

Enter 4

Enter 5

Enter 6

10 Seconds. Led 1 on.

15 Seconds. Led 2 on.

30 Seconds. Led 3 on. (Factory default)

45 Seconds. Led 4 on.

60 Seconds. Led 5 on.

90 Seconds. Led 6 on.

7

SOUNDER DURATION (sounder ring time) 3-2 (Range 3-20 minutes)

Enter 3-2. A new time can be programmed by entering a key from the table.

Enter 1

Enter 2

Enter 3

Enter 4

Enter 5

Enter 6

3 minutes. Led 1 on.

4 minutes. Led 2 on.

5 minutes. Led 3 on.

10 minutes. Led 4 on.

15 minutes. Led 5 on. (Factory default)

20 minutes. Led 6 on.

SOUNDER

DURATION

NIGHT SET / HOME SET EXIT TIME 3-3 (Range 0-90 seconds)

Enter 3-3. A new time may be programmed by entering a key from the table.

Enter 0

Enter 1

Enter 2

Enter 3

Enter 4

Enter 5

Enter 6

0 Seconds. All LED's off ( Instant ).

10 Seconds. Led 1 on.

15 Seconds. Led 2 on. (Factory default)

30 Seconds. Led 3 on.

45 Seconds. Led 4 on.

60 Seconds. Led 5 on.

90 Seconds. Led 6 on.

NOTE: If extension speakers are fitted then the exit sounder volume for

Night or Home set can be altered by the control on the PCB marked

VOLUME

Option Option

Code Description

3-0

3-1

3-2

3-3

Exit Time (secs)

Entry Time (secs)

Sounder Duration (mins)

Results from choosing option no.

0 1

10

10

2

15

15

3

30

30

4

45

45

5

60

60

6

90

90

3 4 5 10 15 20

Night / Home Exit (secs) 0 10 15 30 45 60 90

Examples

Change the FULL set exit time to 60 seconds

ENTER THIS

Description

3-0

Choose full set

5 *

Select 60 seconds Confirm selection

Change the Sounder duration to 3 minutes

ENTER THIS

Description

3-2 1

Choose sounder Select 3 minutes

*

Confirm selection

Change the ENTRY time to 45 seconds

ENTER THIS

Description

3-1

Choose entry

4 *

Select 45 seconds Confirm selection

NIGHT / HOME

SET EXIT TIMER

SUMMARY

8

CIRCUIT

PROGRAMMING

CIRCUIT PROGRAMMING 4 (Range 2-7)

Circuits 2 - 7 can be reprogrammed to suit your requirements. Circuit 1 is fixed as a Final exit circuit. Circuit 8 has limited options.

ZONE

SELECTIONS

ENTER PROGRAM ZONE

4 - 2 2

4 - 3

4 - 4

4 - 5

3

4

5

ENTER PROGRAM ZONE

4 - 6

4 - 7

4 - 8

6

7

8

Select the circuit you wish to alter, it may then be programmed by entering one key from the following table.

N/S = Night Set

Option no.

Zones 2-7 Zone 8

1 Alarm Alarm

2

3

4

Alarm with walk through

Alarm & Isolate in Night Set

Alarm, Walk through & Isolate in N/S

Fire

PA

Keyswitch

5

6

Alarm, Walk through & N/S Entry

Fire

7 Entry Route

8 P.A

SEE GLOSSARY OF TERMS (p.11) FOR DESCRIPTIONS OF ZONE TYPES etc.

EXTENDED

PROGRAMMING

To program zone 3 as an “Entry Route” enter - 4 3 7 *

To program zone 8 as a “Keyswitch” enter - 4 8 4 *

Momentary keyswitch Turn and hold for 0.5 sec = FULL SET

Turn and hold for 2.3 sec = PART SET

EXTENDED PROGRAMMING OPTIONS 7 (Range 1-8)

HOME SET

ZONE

SELECTION

Enter 7 - 1 Disables sounder & strobe in night set.

Enter 7 - 2 Keypress tamper alarm (after 16 incorrect keypresses)

Enter 7 - 3 Full set door sense setting.

Enter 7 - 4 Convert L+ to ID- output.

Enter 7 - 5 Allow Manual Isolation of Zone 1 (Entry/Exit) In Night Set.

Enter 7 - 6 Remote Keypad PA Enable (Operated by * & # ).

Enter 7 - 7 L+ signals first to alarm.

Enter 7 - 8 Inhibit strobe in Night and Home Set and testing. (For speech dialler connection)

HOME SET ZONE SELECTION 8 (Range 1-8 N/A if Fire or PA)

The Home Set feature enables parts of the premises to be alarm protected while other parts are occupied. This is similar to Night Set except that an

Exit/Entry route is not required as part of the Setting or Unsetting procedure.

In programming mode press 8 to select Home Set zone selection mode, then by pressing the keys 1-8 on the keypad you will select which zones you want

ISOLATED during home set. As a key is pressed, its relevant LED on the display will toggle on or off. Any LED’s that are ON will be ISOLATED during home set and any that are off will remain ACTIVE.

9

ENGINEER ACCESS CODE 1-1

The engineer access code is programmed to 7890 by default. To change this code (while in engineering mode):

1. Enter 1-1. LEDs 1, 2, 3 and 4 will illuminate.

2. Enter the new 4 digit code. After each keypress one LED will go out.

The speaker will emit an accept tone if the new code is accepted.

If the speaker emits an error tone, then your new chosen code is invalid.

This could be due to a conflict with another code. At this time your old access code is still valid. Repeat the procedure using a different code.

ENGINEER EVENT LOG REVIEW 5 (Choices of set & unset)

The Panel stores the last set and unset states and the last alarm event. The log is arranged into SET and UNSET events. Log entries indicate the first and subsequent alarms and also isolated circuits. First to alarm is shown by the LED being ON continuously. Subsequent alarms are shown by the

LED(s) flashing and isolated circuits by the LED(s) pulsing slowly. The buzzer sounds whilst reviewing the SET logs and is silent while reviewing the UNSET logs.

To view the engineers log press the 5 key from the program mode. The log starts viewing DAY 1 SET. View the remaining logs by pressing the relevant key 2 for 2 nd

, 3 for 3 rd

and so on up to 9. Press the 0 key to get the last alarm condition.

The # key alternates between SET and UNSET logs and can be used at any time.

ENGINEER

ACCESS CODE

ENGINEER

LOG REVIEW

ENGINEER TEST OPTIONS 6 (Range 0-5)

To conduct testing activities first press the 6 key from within engineering mode and then one of the option below.

Enter 0

Enter 1

Enter 2

Enter 3

Enter 4

Enter 5

Internal buzzer ( entry exit sound etc. )

Internal Sounder ( Alarm sounds from speaker / keypad )

External Sounder

External Strobe

L+ Terminal( even if programmed as ID- )

FULL LOAD ( Everything enabled )

ENGINEER

TEST OPTIONS

10

FACTORY

DEFAULTS

FACTORY PROGRAMMING DEFAULTS 9 -9

Restoring programming Defaults.

RESTORE

DEFAULT

PROGRAMMING

Enter 9-9, The sounder will give a rapid pipping sound, wait for 5 seconds, an accept tone sounds, the factory programming defaults are restored. The user and engineer codes do not change.

Note: If any keys are pressed this procedure will be aborted.

RESTORE

DEFAULT

CODES

Restoring Code Defaults

1. Place the small link supplied with the spare fuses, on the memory link.

This is positioned above the volume control and is labelled “Memory

Default”.

2. Remove the mains and battery supply.

3. Wait a few seconds then re-connect the battery and then the mains

Refer to page 6 regarding initial power up. The speaker will emit the accept tone and the factory user code defaults will be restored.

4. Be sure to remove the link .

Locking the Engineer Code

Use this option with care. You can lock the engineer code to prevent unauthorised alteration. To enable the engineer code must end in 9. If the engineer code is lost, it will not be possible to enter engineer mode, the PCB will need to be replaced. This is considered to be a “Chargeable repair”.

GLOSSARY OF

TERMS

GLOSSARY OF TERMS

FULL SET

This is a setting method normally used when leaving the premises. Full system armed.

NIGHT SET

This is a setting method normally used when going to bed

HOME SET

This is a setting method normally used for high security protection whilst still inside the premises. For example an antiques cabinet etc.

ALARM

This is a zone that will trigger the panel when activated, providing the panel is set.

WALK THROUGH

This zone will be disabled during an entry period.

ISOLATE IN NIGHT SET

This simply means the zone will be disabled when the panel is NIGHT SET. For example downstairs

NIGHT SET ENTRY

When the panel is NIGHT SET the zone, when activated, will start the entry timer but if the panel is FULL SET then this zone will acts as an ALARM zone.

11

ENTRY CIRCUIT

This will start the entry timer when activated providing the panel is set.

FIRE (for use with smoke detectors etc.)

A zone that when activated emits an ascending sound from any internal speakers.

If the panel is set, external sirens and strobes will also sound but in an unset state the external sounders will pulse every two seconds.

TAMPER

This is a loop that should run through every device on your system. If broken, it triggers the internal speakers. If the panel is set, the external sounders and strobes will also trigger. The tamper LED is shown on the keypad as TPR.

CHIME

Chime is similar to a doorbell. This can be used to alert a user to a certain zone being triggered during the day.

DOOR SENSE SETTING

This allows you to have a variable FULL SET EXIT TIME. You can program the

EXIT time to maximum and when you full set the system, the exit time will drop to

8 seconds as soon as the EXIT door has closed thus avoiding the preset exit time.

KEYSWITCH

This allows the panel to be Full set, Part set, Unset and Reset via zone 8.

Note: To use the keyswitch for setting and unsetting, connect to zone 8 and program that zone to be KEYSWITCH. To set the panel, turn the key so that the contacts are open, hold in this position for about a second for full set or about 2 seconds for night set. To unset the panel, turn and hold for about ½ second. To reset open and close the keyswitch after an alarm condition.

THE ACCEPT TONE

This is heard when an action is accepted.

THE ERROR TONE

This is heard when an action is not accepted.

SERIES AND PARALLEL

GLOSSARY

OF TERMS

LATCHING DETECTORS

These detectors, when triggered during a set period, latch on to aid the process of alarm event origin checking. These detectors are only normally used if many detectors are to be used on a single zone but are to cover a large area of space.

12

THIS INFORMATION SHOULD BE KEPT EITHER INSIDE THE CONTROL PANEL OR

WITH THE INSTALLER. IT CAN BE USED TO REFER TO PROGRAMMING DETAILS

WHEN NEEDED.

ZONE

1

2

3

4

5

6

ZONE USE / LOCATION

7

8

TIMER

FULL

NIGHT

EXT

SOUNDER

TICK BOX

EXTENDED

OPTIONS

1

BATTERY VOLTAGE

AUX. VOLTAGE

INSTALLED BY

2 3 4 5

VALUE

6 7 8

RESISTANCE

SECONDS

SECONDS

MINUTES

CHECKED

V

V

CONTROL

PANEL

SONADE 2000

FLASHGUARD XL+

STARLIGHT 2000

AG 6 & AG 8

NOVA GUARD 2+T

SPIRIT AU1000

GENERAL

TERMINALS

ST-

SOUNDER CONNECTIONS

STROBE-

STROBE-

ST

ST-

STROBE-

STB-

STROBE

TRIG -

S-

B

SIREN-

-R

-SW

S-

TRG-

SIREN

TRIG -

+ -R

D

SUPPLY+

+H

A

SUPPLY-

-H

V+ V-

12V+

HOLD OFF +

SUPPLY+

12V-

HOLD OFF

-

SUPPLY-

T

TAMPER OUT

RTN

RET

R

RTN-

TAMPER

RETURN

NOTE: When installing a self-actuating sounder remove panel link between R- and -.

13

FAULT FINDING

A selection of common known problems and solutions are listed below.

Problem

Programmed 7-5 but zone

1 will not isolate in night set.

Cause

Have not MANUALLY isolated zone when setting panel.

Answer

When night setting enter code * 0 * 1.

Zone 1 is permanently lit

Tamper will not clear with lid on.

PA will not work on the keypad

Mains light not on.

Battery not taking over after mains fail

Remote keypad not responding

Memory default link is on.

Tamper loop open

Not holding * & # long enough or option not enabled

No mains

Battery fuse blown or battery not connected or flat battery.

Incorrect wiring

Remove link.

Check 24hr tamper, sounder tamper and all devices for an open tamper loop.

Be sure to HOLD * & # until the alarm activates. Enable option 7-2.

Check fuse & mains supply

Connect battery and check 1A battery fuse. Fit new battery.

Check wiring. C to C & D to D.

Zones failing to activate.

Zone activates during entry

Zone activates even in day mode

Incorrect wiring

Seeing an alarm zone on entry or deviating from entry route.

Programmed to PA or FIRE.

Make sure the devices are wired in series NOT parallel.

Make sure all zones on entry route are programmed with walkthrough.

Do not deviate.

Reprogram the zone to be an alarm zone or similar.

If you are still experiencing problems then contact our technical helpline with information at hand regarding your situation. If your problem stems from wiring, you may be required to write down wiring instructions so have a pen and paper at hand.

Question

General questions & Answers

Can two bell boxes be used on the system

Can a “sound bomb” be installed

How many PIR’s can be connected to a zone

Can the engineer set the panel without the need of a user code

What happens if the zone is still in fault when the bell cuts off

Will there be any further alarms

Answer

Yes, make sure tampers are in series and do not exceed the current limit

Yes, connect between AUX+ and S-. Be sure not to exceed maximum current rating.

While it is better practice to limit the number of detectors per zone, upto 10 may be fitted. Zone resistance should not exceed 50 ohms.

Yes, if the engineer code is entered the panel will start the set. The engineer code will also unset if the panel was set using the engineer code, it will not unset if a user set the panel.

The panel will re-arm. Any zone in fault will be temporally isolated and will re-arm when the fault clears.

Any further alarm activation’s will trigger the bells again for the selected time. If any zone activates three times in succession it will be isolated. Alarms can occur from other zones.

14

Wiring Diagram

Please Note:

IntelliSense are always endeavouring to improve quality and specification of all its products and may alter or amend this product and instructions without notice. All information is given in good faith but without warranty.

Certificate No CC106

IntelliSense UK

Unit 25 Walkers Road,

North Moons Moat Industrial Estate,

Redditch,

Worcestershire.

B98 9HE

Telephone:

Fax:

Technical Support

Email

Sales

Web

+44 (0) 1527 68111

+44 (0) 1527 68222

08457 660533 Local Rate, 9am – 5pm Weekdays (UK Only) [email protected]

[email protected]

www.getintellisense.co.uk

Printed & Manufactured in China by IntelliSense. Document No 5-051-613-00 Rev B

15