- Home
- Domestic appliances
- Large home appliances
- Water heaters & boilers
- York
- DGPH070ABTA
- Installation instructions
advertisement
MODELS:
SEALED COMBUSTION
DOWNFLOW GAS FURNACE
DGAA, DGAH, DGPA, AND DGPH
For Installation In:
1, Manufactured (Mobile) Homes
2.
RecreationaIVehicles & Park Models
3.
Modular Homes & Buildings
IMPORTANT - Only individuals having proven expedence with this type of equipment should attempt to perform set-up.
Proper furnace set-up and adjustment is the responsibility of the retailer/homeowner and is not covered under warranty.
FURNACE START-UP CHECK LIST
Has roof jack crown been correctly installed?
Has furnace gas valve and burner orifice been correctlycon-
vetted for Propane. gas where applicable?
Has furnace gas valve been de-rated for altitudes above 2000 feet where applicable?
Is gas line outlet pressure properly set for fuel type? (naturalgas is 3.5" W.C.; Propane is 10" W.C.)
Is cross-over duct installed per home builder and UPG installa- tion instructions?
Has furnace been operated through a complete heating cycle?
Has the pilot flame been adjusted properly? (DGPH and DGPA
Models)
035-16328-002 Rav. C (0902)
FURNACE SPECIFICATIONS
DGAA -- AUTOMATIC IGNITION -- WITH BUILT-IN COIL CABINET -- 4 TON - AIC READY
MODEL NO,
DGAA056BDTA
DGAA07OBDTA
DGAAO77BDTA
DGAAO9OBDTA
Factor'/Equipped for use with
NATURAL GAS
NATURAL GAS
NATURAL GAS
NATURAL GAS
Input/BTUH
56,000
70,000
77,000
90,000
OutputJBTUH
45,000
56,000
62,000
72,000
DGPA -- STANDING PILOT -- WITH BUILT-IN COIL CABINET -- 3 TON - AIC READY
DGPA056ABTA
DGPA070ABTA
DGPA077ABTA
DGPA090ABTA
NATURAL GAS
NATURAL GAS
NATURAL GAS
NATURAL GAS
56,000
70,000
77,000
90,000
45,000
56,000
62,000
72,000
DGPH -- STANDING PILOT -- WITH BUILT-IN COIL CABINET -- 3 TON - NO AIC CONTROLS
DGPHO56ABTA
DGPHO70ABTA
DGPH077ABTA
DGPH09OABTA
NATURALGAS
NATURALGAS
NATURALGAS
NATURALGAS
56,000
79,000
77,005
90,000
45,000
66,000
62,000
72,000
DGAH056BBSA
DGAHO77BBSA
DGAH -- AUTOMATIC IGNITION -- HEATING ONLY -- NO COIL CABINET
I NATURALGAS 45,006
NATURAL GAS 77,000 62,000
ELECTRICAL SPECIFICATIONS
Electdcal Power Supply
Breaker or Fuse
Thermostat Circuit
Nominal Anticipator Setting
Gas Valve Inlet
115 Volts - 60 Hz - 1 Phase
15 Arnp
24 Volt - 60 Hz - 40 VA
.50
1/2" NFPT
24-314"
19.1/2 °
24-314"
19-1/2"
76"
5g=1/2"
2
DGAH Series
FIGURE 1 : Furnace Dimensions
DGPH, DGPA & DGAA Series
Unitary Products Group
035-16328-002 Rev. C (0902)
GENERAL INFORMATION
NOTE: The words "Shall" or "Must" indicate a requirement which mance.
is essential to satisfactory and safe product perfor-
The words "Should" or "May" indicate a recommendation or advice which is not essential and not required but which may be useful or helpful.
IMPORTANT - These instructions are primarily intended to
assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes require licensed installation service personnel for this type of equipment. Read all instructions carefully before start- ing the installation.
I
I_WARNING
Improper installation may damage equipment,
can create a shook hazard, and will void the warran_
The furnace shall be installed so the electrical components are protected from water
The furnace is not to be used for temporary heat-
ing of buildings or structures under construction.
Do not test the fuel system at more than 14 inches water column after fumace has been connected to the fuel line. Such testing may void the warren_ Any test run above 14 inches water column may damage the furnace control valve which could cause an explosion, fire, or asphyxiation.
Recreational Vehicles in U.S.A.:
1.
Standard on Recreational Vehicles (NFPA 1192, formerly
NFPA 501C).
2.
National Electrical Code (NFPA 70).
Recreational Vehicles in Canada:
1, Unit installation shall comply with current CSA standard
CAN/CGA-Z240.4.2
- Installation Requirements for Propane Appliances and Equipment in Recreational Vehicles.
2.
Unit electrical widng and grounding shall comply with current CSA standard C22.2 No.148/CAN/CSA-Z240.6.2
- Electrical Requirements for recreational vehicles.
HIGH ALTITUDE INSTALLATION
For elevation above 2,000 feet, derate furnace input 4% for each 1,000 feet of elevation above sea level. Derating is accomplished by reducing the orifice size. See Derating
Chart for orifice size.
In Canada, for elevations from 2000 to 4500 feet derate by reducing gas manifold pressure to 3.0" W.C. for natural gas and 9.0" W.C. for LP gas.
INSTALLATION STANDARDS
CODECOMPLIANCE
The installer must comply with all local codes and regulations which govern the installation of this appliance. Local codes
and regulations shall take precedent over these regulations where applicable. In lieu of local codes, the appliance shall be installed in accordance with one or more of the following standards.
Manufactured homes in the U.S.A.:
1, Federal Manufactured Home Construction & Safety
Standard (HU.D. Title 24, Part 3280),
2.
National Fuel Gas Code (ANSI-Z223,1, NFPA-54).
3.
National Electrical Code (NFPA 70).
Manufactured homes in Canada:
1, Natural Gas and Propane Installation Code (CAN/CSA
B149,1).
2.
Canadian Electrical Code, Part 1 (CSA C22,1)
• Never attempt to alter or modify this furnace or any of its components.
• Never attempt to repair damaged or inoperable components. Such action could cause unsafe opera- tion, explosion, fire and/or asphyxiation.
• If a malfunction has occurred, or if you feel that the furnace is not operating as it should, contact a qualified service agency or gas utility for assistance.
MINIMUM FURNACE CLEARANCES
Access for servicing is an important factor in the location of any furnace. A minimum of 24 inches should be provided in front of the furnace for access to the heating elements and controls. This access may be provided by a closet door or by locating the furnace 24 inches from a facing wall or partition.
These furnaces are design certified for the following minimum clearances from combustible material in alcove or closet instanation
Table 1: MINIMUM CLEARANCES
BACK
SIDES
FRONT
TOP
ROOF JACK
DUCT
CLOSET
0"
0"
6"
2"
0"
0"
ALCOVE
0"
0"
24"
2"
0"
O"
Unitary Products Group 3
4
035-16328-002 C(0902)
RETURN AIR REQUIREMENTS
CLOSET INSTALLATIONS
Additional Requirements
Additional requirements for floor and ceiling return system for
closet installed sealed combustion heating appliance are given in the next paragraph.
Floor or Ceiling Return Air System
Listed in the next paragraph are the conditions to be met by
Manufactured Home Manufacturers to have U.L. acceptance
of in-floor or ceiling return air systems of closet installed direct vent forced air heating appliances for Manufactured
Homes to be sold in the United States.
1.
The return-air opening into the closet, regardless of location, is to be sized not less than specified on the appli-
ance's rating plate.
2.
If the return-air opening is located in the floor of the
closet (versus the vertical front or side wail), the opening is to be provided with means to prevent its inadvertent
closure by a fiat object placad over the opening.
3.
4.
5.
The cross-sectional area of the return duct system (when located in the floor or ceiling of the manufactured home) leading into the closet is to be not less than that of the opening specified on the appliance's rating plate.
The total free area of openings in the floor or ceiling reg-
isters serving the return-air duct system is to be not less than 150% of the size of the opening specified on the appliance's rating plate. At least one such register is to be located where likelihood of its being covered by carpeting, boxes, and other objects is minimized.
Materials located in the return duct system have a flame spread classification of 200 or less.
6.
7.
Non-combustiblepans having one-inch upturned flanges are located beneath openings in the floor return duct system.
Wiring materials located in the return duct system conform to Article 300-22 (B&C) of the National Electrical
Code (NFPA-70).
8.
Gas piping is not run in or through the return duct system.
9.
The negative pressure in the closet as determined by test with the air-circulating fan operating at high heating speed and the closet door closed is to be not more negative than minus 0.05-inch water column.
10.
For floor return systems, the manufactured home manufacturer or installer shall affix a prominent marking on or near the appliance where it is easily read when the ctoset door is open. The marking shall read:
_WARNING
HAZARD OF ASPHYXIATION, DO NOT COVER
OR RESTRICT FLOOR OPENING
AIR DISTRIBUTION SYSTEMS
For proper air distribution, the supply duct system shall be designed so that the static pressure does not exceed the listed static pressure rating on the furnace rating plate.
Three typicaldistdbution systems are illustrated in Figure 2.
Location, size and number of registers should be selected on the basis of best air distribution and floor plan of the home.
The Air Temperature Rise is to be adjusted to obtain a temperature dse within the range(s) specified on the furnace rating plate.
A
Single trunk duct _
E
B*
Dualtrunk duct with crossoverconnector
C
TransitionDuct withBranches
Transitionduct
Dualtrunk duct
Crossover
I
_r-.. 3
1. CrossoverDuct must becentered directlyunder furnace.
2. Use 12" DiameterRound or insulatedFlex-duct only.
3. TerminateFlex-duct(oppositefurnace) in the center of the trunk duct.
4. Flex_uct matedalmust be pulledtight-- No Loops or unnecessarydips-- Air Flow may be impeded.
FIGURE 2 : Air Distribution Systems
Unitary Products Group
Return Air Grille Part No.
7900-287P/A * White
250 SQ. IN
MINIMUM
FREE AREA B
Furnace to Closet Door Clearance --
5 Inches or more
The closet door MUST have a minimum o1250 Square Inches
of free area in the upper half of the door.
If opening for return air is located in the floor or sidewalls and
below the top of the furnace casing:
1. 6 inches minimum clearance must be provided on side where return is located, and
2. 6 inches minimum clearance must be maintained from the
Pont of furnace.
250 SQ. IN.
MINIMUM
FREE AREA 50 SQ LN
_ MINIMUM
FREE AREA
J_
DOOR i5_°_r _ac/_"t Return Air Closet Door Part No.
7900-7771/C * White
FIGURE 3 : Closet To Door Clearance - 6" or Greater
250 SQ, IN
MINIMUM t FREE AREA B
50 SQ IN.
MINIMUM
FREE AREA
250 SQ. IN
MINIMUM
FREE AREA
Furnace to Closet Door Clearance --
Greater than 1 Inch and Up to 5 Inches
1. The closet door MUST have a minimum of 250 Square Inches
of free area in the upper half of the door and a minimum of
50 Square Inches of free area in the lower area of the door.
The lower closet door grille may be omitted if an undercut of
2-1/2 inches is provided in the door.
2. A fully Iouvered closet door MUST have a minimum of 250
Square Inches of free area in the upper half of the door.
As an option to _e lower grill, an undercut of 2-1/2" will provide
50 Square Inches of free area.
FIGURE 4 : Furnace To Closet Door Clearance - 1" To 6"
_i_
MINIMUM
FREE AREA
Furnace to Closet Door Clearance --
Less than 1 Inch
The closet door MUST have three return air gdlles. The
total free area of the two upper grilles must be minimum of 250 Square Inches. The total free area of the lower gdlle MUST be a minimum of 50 Square Inches.
The grilles MUST BE ALIGNED directly opposite the return air grille of the furnace door.
50 SQ. IN.
FREE AREA
FIGURE 5 : Furnace To Closet Door Clearance - Less Than 1"
Unitary Products Group 5
6
ROOF JACK
AWARNING
Failure to follow aft venting instructions can result in fire, asphyxiation, or explosion.
[AkCAUTION
Only use the appropriate roof jack. See Figures 6
& 7 for correct application.
Do not exceed the maximum height as determined from Figures 6 & 7. Installer should allow an additional 1-1/2" travel before the flue pipe assembly is fully extended against the built-in stop.
This provides an additional safeguard against the flue assembly being pulled from the roof jack during transportation or other stress conditions.
EXISTING FURNACE REPLACEMENT
If this furnace replaces an existing furnace, do the following: f.
If a 2nd roof, roof cop or addition has been made to the existing roof of the home, remove the old roof jack completely! To avoid the possibility of an impropedy installed pipe or gaps in the old roof jack, INSTALL A NEW ROOF
JACK. Your ceiling and roof height will determine the correct roof jack to use. Refer to the vent selection table, of the furnace installation instructions.
2.
After unpacking the roof jack, check the rain caps. Insure they are not damaged, tilted or crooked. Do not twist, crush or sit on the roof cape during installation. Damaged roof cape will cause improper furnace operation. The furnace will not heat properly and could result in explosion.
3.
Before inserting the roof jack into the furnace top, inspect the furnace flue and combustion air opening for debris or insulation which might have fallen in during preinstallation steps. Do not proceed unless all debris has been cleaned out or removed.
4.
After installing roof jack on furnace top collar, check to make sure there is no gap in back or side between the pipe collar and the furnace casing top.
5.
6.
Use only the pipes provided with the roof jack assembly.
Do not add to or adapt other sheet metal pipes. Do not
cut, insert or add other pipes to this assembly.
In no case should there be a gap between sections of the flue pipe or the combustion air pipe. If necessary to prevent excessive air leakage, the installer should seal joints in the combustion air tube with aluminum type or other suitable sealant.
NEW HOME INSTALLATION
If this furnace is installedon a new home do the following:
1.
Inspect the furnace top collars for signs of insulation or ceiling debris which might have fallen in during cutting of the ceiling and roof holes. Remove all debris before continuing.
2.
After unpacking the roof jack, check the rain caps. Insure they are not damaged, tilted or crooked. Do not twist, crush or sit on the roof caps during installation. Damaged roof cops will cause improper furnace operation. The furnace will not heat properly and could result in explosion.
3.
Before inserting the vent pipe into the furnace top, inspect the furnace flue and combustion air opening for debris or insulationwhich have fallen in during pre-installation steps. Do not proceed unless all debris have been cleaned out or removed.
4.
After installing roof jack on furnace top collar, check to make sure there is no gap in back or side between the pipe collar end the furnace casing top. If necessary to prevent excessive air leakage, the installer should seal joints in the combustion air tube with aluminum type or other suitable sealant.
INSTALLATION IN SNOW REGIONS
When the combustion air pipe inlet is covered or blocked with
snow, the furnace will not operate properly due to the depleted combustion air supply.
Therefore, if the furnace will be located in regions where
snow accumulation on the roof exceeds 7" or in H. U.D. Snow
Load Zones, a roof jack extension (Part No. 7680B6541) is recommended.
LOCATING AND CUTTING ROOF JACK OPENING
To facilitate the proper installation of the roof jack, it is very important that the roof jack opening in the ceiling and roof be on the same vertical center line as the furnace flue collar. See
Figure 9.
Mark this location on ceiling and scribe a circle with a 5" radius (10" diameter) around this mark. Cut opening for roof jack through ceiling and roof. (If furnace was installed during construction, cover furnace and flue opening to prevent debris from entering flue when hole is cut for roof jack.)
INSTALLING ROOF JACK IN ROOF
(See Figure 6 & 7 for Dimensional requirements.)
Insert reef jack into opening in the roof.
The roof jack should be secured to the furnace before roof flange (flashing) is secured to the roof. This will insure a better alignment of the flue pipe and furnace flue collar. Caulk around and under roof flange to provide a water tight seal, before secoring roof jack flashing to roof.
Unitary Products Group
SWIVEL FLASHING
ADJUSTS FROM
0/12 TO 5/12 PITCH
4000-7101/C
4000-7121/C
4900-7141/C
4900-7151/C
4900-7171/C
SLANT
FLASHING
3/12 PITCH
4000-6101/A
4000-61211A
4000-6141/A
4000-6151/A
4009-6171/A
DGAH FURNACES
INSTALLATION DIMENSIONS
"A"
ADJUSTABLE HEIGHT
7O" _ 79"
75" _ 86"
83"to 104"
90"_ 116"
127" _ 15T'
2
The 4084-7141 s d mens onally the same as 4000-7141/C and is avallab e on y In Canada.
......
The 4084-7151 is dimensionally the same as 4000-7151/C and is available only in Canada.
DGPH, DGPA,& DGAAFURNACES
INSTALLATION DIMENSIONS
"B"
ADJUSTABLE HEIGHT
86" to 95"
91"to 102"
99"to 129"
106"to 132"
143" _ 173"
19 1/2"
FLUE
GASES
CAREFULLY
SEALANT
CAULK
SUPPLIED
ALL AROUND
By FURNACE
SWIVEL JOINT WITI-I
MANUFACTURER, 1_ f _ _ _ I _-
•
_
F_E S t t COMBUSTION 19 1/2
CAULK
,oF
/.
Not extend below the ceiling.
_ __ _
AND ROOF.
THIS IS THE INSTALLER S RESPONSIBILITY = L_ __ __
A
59-1/2"
, r
WARM AIR DUCT
-,iv
DGAH MODELS
.....
DUCT CONNECTOR
FIGURE 6 : Standard Roof Jack
FLOOR
B
76"
DGPH, DGPA,
DGAA, MODELS
/
DUCT CONNECTOR
_
1 F
WARM AIR DUCT
Unitary Products Group 7
8
I
SWIVEL FLASHING
ADJUSTS FROM
0/12 TO 5/12 PITCH
4000-8161/C
4000-8181/C
SLANT
FLASHING
3/12 PITCH
I 4000-9161/A
4000-9181/A
DGAH FURNACES
INSTALLATION DIMENSIONS
=A =
ADJUSTABLE HEIGHT
85" to 101"
99" to 129"
DGPH, DGPA, & DGAA FURNACES
INSTALLATION DIMENSIONS
"B"
ADJUSTABLE HEIGHT
101" to _17"
115" to 145"
CAULK
UNDER
FLASHING
ROOF
AND ROOE
IMPORTANT
A
59-1/2"
DGAH MODELS
WARM AIR DUCT DUCT CONNECTOR
FIGURE 7 : Roof Jack With Removable Crowns
FLOOR
DGPH, DGPA,
DGAA, MODELS
76 II
B
DUCT CONNECTOR
WARM AIR DUCT
Unitary Products Group
035-16328-002 Rev. C (0902)
DUCT CONNECTORS
I ..
=
, , T.
I
_
DUCT CONNECTOR DIMENSIONS
DUCT CONNECTOR
PART NUMBER
7990-6011
7990-6021
7990-6041
7990-6061
7990-6071
7990-6081
7990_I01
7990-6121 I
DUCT CONNECTOR
DEPTH
1"
2"
4-I/2"
6-1-2"
7-1/2"
8-1/2"
10-1/4"
12-!/4"
FIGURE 8 :
Duct Connector Dimensions
DUCT CONNECTOR DIMENSIONS
DUCT CONNECTOR
PART NUMBER
7990-6211
7990-6221
7990-6241
7990-6261
7990-6271
7990-6281
7990-6301
7990-6321
DUCT CONNECTOR
DEPTH
1"
2"
4-1/2"
6-1-2"
7-1/2"
8-1/2"
10-1/4"
I2-1/4"
REARWALL
OF ENCLOSURE i
CEILINGCUT-OUT
FLOORCUT-OUT
CONNECTOR
OPTIONAL GAS
L_
SUPPLY DUCT s
DUCTCONNECTOR
DEPTH
T
FLOOR
/
J
FLOOR
JOIST
ENTRANCE
-_
20_
OF FURNACE
_ FLOOR
FUTUREREFRIGERANT
LINE ENTRANCE
FIGURE 9 : Recommended Floor Cut-out
FIGURE 10 : Duct
Connector Depth
Unitary Products Group 9
_
LOCATOR BRACKET
NAI L_,AFLEATHEAD SC R EWS
FLOOR
NAILS, FLAT HEAD SCREWS
OR STAPLES
BEND TABS UNDER
OPENING TO
SECURE TO THE
SUPPLY DUCT
SUPPLY DUCT
SUPPLY DUCT
FIGURE tl : Duct Connector Screw Attachment
INSTALLATION OF SCREW A'B'ACHMENT DUCT
CONNECTOR
1,
2.
3.
4.
5.
Make floor cut out as shown in Figure 9.
Determine the depth of the floor cavity from the surface of the floor to the top of the supply air duct and select the
appropriate duct connector from the chart.
Place locating bracket (supplied with the duct connector) to the back edge of the floor opening. See Figure 11.
Apply a water based duct sealant to the 1/2" supply duct attachment flange of the duct connector.
Determine which of the four positions the duct connector best centers over the supply duct and insert it through the floor cutout.
6.
When propedy aligned with the supply duct, secure the duct connector to the floor with nails, flat head screws or staples.
7.
Use screws as required to secure the duct connector to the supply duct.
8.
Cut out the opening to the supply duct. If sealant was not used, the instaner should tape the mating flanges to provide s good air seal.
NOTE: Duct sealant and tape must be classified as meeting HUD Standard 3280.715, U.L. Standard 181A.
If tape is used to provide a better air seal, it should be a type
approved by the applicable national or local codes.
FIGURE t2 : Duct
Connector Tab Attachment
INSTALLATION OF TAB ATTACHMENT DUCT
CONNECTORS
1.
Make floor cut out as shown in Figure 9.
2.
Determine the depth of the floor cavity from the surface of the floor to the top of the supply air duct and select the appropriate duct connector from the chart.
3.
Place locating bracket (supplied with the duct connector) to the rear of the floor area for the furnace. See Figure
12.
4.
Determine which of the four positions the duct connector best centers over the supply duct and insert it through the floor cutout.
5.
Mark cut-out location on the supply duct and remove the duct connector.
6.
Cut out the opening to the supply duct.
7.
Bend tabs down through and back up under the supply duct.
8.
Secure the duct connector to the floor with nails, flat head screws or staples.
The duct connector is designed for use on ducts down to 12" in width. When using the connector on smaller width ducts, there will not be sufficientclearance to bend the tabs on two sides of the duct connector.
In such cases the tabs may be attached to the sides of the duct by using sheet metal screws or other suitable fasteners.
Holes for sheet metal screws are provided in three (3) tabs on
each side of the duct connector. If more than 3 tabs need to be used to provide a more secure and air tight connection, the remaining tabs can also be fastened to the duct with screws after drilling the required screw holes.
10 Unitary Products Group
035-16328-002 C(0902)
FURNACE SEATED
AGAINST THE
LOCATOR BRACKET \
SECUREFURNACE
TO FLOOR WITH
TWO NAILS OR
SCREWS.
FIGURE 13 : Installation of Furnace
INSTALLATION OF THE FURNACE
2.
3.
Remove the front panels and set the fumaca onto the duct connector. Slide it back until the rear of the unit engages the Iocator bracket.
Secure the front of the furnace with two screws at the mounting holes provided.
Secure the top of the furnace to a structural member using screw through the strap at the back of the furnace.
Strap may be moved to any of the holes located along the top back of the furnace. Installer may provide an equivalent method, such as screws through the casing side.
LA, CAUTION]
The inner flue pipe must be present.
It is mandatory that the combustion air pipe and
flue pipe assembly be fully engaged. The com- bustion air pipe MUST be securely fastened to the furnace with a sheet metal screw in the hole provided.
Use a 1/2" blunt or sharp end sheet metal screw to fasten roof jack combustionair pipe to furnace combustion air colla_ Screw hole is provided in
the pipe and collar Excessively long screws may extend to flue pipe and puncture it. Screws are not to exceed 1 1/2"in length.
NOTE: Combustion air tube and flue pipe are part of the
same assembly. Only the combustion air tube need be fas-
tened to the furnace.
2.
1.
Check to be certain that the flue pipe and combustion air tube are present.
Pull the telescoping flue tube and combustion air tube
assembly down from the roof jack. Slide the flue tube/
combustion air tube assembly down firmly over the fur-
nace flue outlet and combustion air cellar. Insure that the
back, side and front of combustion air tube collar is fully
engaged and is in contact with gasket, Fasten the com-
bustion air tube to the furnace combustion air collar
usinga 1/2 inchsheet metal screw. (Screw hole provided
in combustionair tube and fumaca combustionair collar.
See Figure 14.
COMBUSTION
SECURE STRAP
TO WALL_
It is mandatory that the combustion air and flue tube assembly
be fully engaged at back sides and front, and combustion air
tube securely fastened to the fumace with a sheet metal screw in the screw hole provided,
COMBUSTION
FRONT OF
FURNACE
FIGURE 14 : Connecting Roof JAck to Furnace
#8 OR #10 SCREW RECOMMENDED
Unitary Products Group 11
035-16328-092 Rev. C (0902)
CEILING RINGS
The coiling ring is to meet fire stop requirements. Accessory
Ceiling Ring (PIN 7660-2841) may be used, (See Figure 15) or the manufactured home manufacturer or the installer may use other approved methods to stop fire.
If required, three (3) sections of Accossory Ring may be used as shown in Figure 15 to provide closer clearance around roof jack,
FIGURE 15 : Ceiling Rings
ELECTRICAL
A
WIRING
IlIA CAUTIiQN
TO INSTALLER: Incoming power must be polarized. Observe color coding.
AWARNING!
B
SHOCK HAZARD - DISCONNECT ELECTRI-
CAL POWER SUPPLY TO THE UNIT BEFORE
SERVICING TO AVOID THE POSSIBILITY OF
SHOCK INJURY OR DAMAGE TO THE EQUIP-
MENT
CONNECT POWER SUPPLY WIRES
1.
Remove the field wiring cover.
2, Insert 115 volt wires through the large plastic bushing on the left side of the furnace (See Figure 16). If conduit is used it should be secured to the control box.
3.
Connect the "hot" wire to the BLACK pigtail lead, and the
"neutral" wire to the WHITE pigtail lead. Secure all connections with suitable wire nuts and wrap with electrical tape.
4.
Connect the "ground" wire to the grounding screw.
5.
Reinstall the control panel cover and secure mounting screw,
CONNECT THERMOSTAT WIRES
1.
Insert 24 volt wires through the small plastic bushing just above the control panel.
2.
Connect the thermostat wires to the furnace low voltage pigtails. See Figure17 (heating only) and Figure 18
(heating and cooling).
3.
Connect low-voltage circuit to the wall thermostat pigtails.
NOTE: Five-conductor thermostat cable is recommended for all installations to allow easy installation of an air conditioning system at a later time.
Eighteen gauge thermostat wire is highly recommended.
Smaller gauge thermostatwire may be used only if the guide-
line below is followed.
THERMOSTAT WIRE
LENGTH (FURNACE TO
THERMOSTAT)
0 - 45 feet
0 - 70 feet
THERMOSTAT
WlRE GAUGE
22
20
Do not use thermostat wire smaller than 22 gauge. If thermostat wire smaller than 18 gauge is used, pay particular attention that the connections between the different wire sizes are tight.
Operational problems may be caused by loose connections or by the use of thermostat wire that is too small to carry the required load. Any such problems are the responsibility of the installer.
A separate 115 _/A.C. supply circuit must be used for the furnaco. The circuit should be protected by a 15 amp fuse or circuit breaker.
THIS SCREW DOES
NOT NEED TO BE
REMOVED IN ORDER
TO REMOVE THE
FIELD WIRING COVER.
(JUST LOOSEN).
NOTE:
Cover should not be removed except when servicing the controls.
a
J
FIGURE 16 : Field Wiring
12 Unitary Products Group
WALL THERMOSTAT
Avoid locations where the thermostat could be subject to drafts from outside, or exposed to direct light from lamps, sun, fireplaces, etc., or affected by air from a duct register blowing directly on the thermostat.
The wall thermostat should be located 52 to 66 inches above the floor. The preferred location is on an inside wall situated in an area with good air circulation, and where the temperature will be reasonably representative of other living areas the thermostat is controlling.
NOTE: In order to provide proper ventilation control when using DGPH model furnaces with Coleman Blend
Air ventilation systems, it is required that a 4-wire wall thermostat and Blower Relay Kit 7900-7761 be installed,
FURNACE
CONTROL
BOX
FIGURE t7 : Wiring for Heat Only Thermostat
BLEND AIR
CONTROL BOX
;
E
FURNACE
CONTROL
BOX
WHITE
Q
WALL THERMOSTAT
FIGURE 18 : Wiring for Heat-Cool Thermostat
NOT FACTORYINSTALLED
Unitary Products Group 13
14
035-16328-002 Rev. C (0902)
WIRING DIAGRAMS
If"
MOTOR
B!OWER
LN
BLK
MANUAL RESET
LIMIT SWITCH
03
-c 4
05
06
07
4 8
02 °11
ORG ____ __Z
GND.
SCREW
24V SEC.
TRANSFORMER
120V PRI.
WHT
I INE ORG
FAN
SWITCH
(_
GRY
_c_ w
3 AMP FUSE
ORG o
AUTO
RESET
LIMIT
SWITCH
W R
WALL "lit
THERMOSTAT
E
NEU.
.,
.....
.
LI "
WHT
BLK
_.
TO EARTH GND.
Q
GND.
SCREW
SYSTEM
SWITCH
GAS
CONTROL
FIGURE 19 : Wiring Diagram for DGPH056, DGPH070, DGPH077
NOTE: in order to provide proper ventilation control when using DGPH model furnaces with Coleman Blend Air ventilation sys-
tems, it is required that a 4,-v,'irewall thermostat and Blower Relay Kit 7900-7761 be installed.
Unitary Products Group
035-16328-002 Rev. C (0902)
WHT
MANUAL RESET
LIMIT SWITCI o3
-o 4 o5 o6 o7
_8
ORG o2 1
TRANSFORMER
GND.
SCREW
LOAD
24V SEC.
120V PRI.
WHT
COMBUSTION
BLOWER
RELAY
FAN
SWITCH
BLU
BRN
WHT
[_ i
:{_]_
WHT
RED
3 AMP FUSE
AUTO RESET
LIMITSWITCH
ORG
I, W' i
NEU, WHT
_/
LI BLK iv.
TO EARTH GND.
@ GNO.
SCREW
BLK
SYSTEM
SWITCH o 1
PRESSURE
SWITCH _
_3
WALL qt
THERMOSTAT
GAS
CONTROL
FIGURE 20 : Wiring Diagram for DGPH090
NOTE: In order to provide proper ventilation control when using DGPH model furnaces with Coleman Blend Air ventilation sys-
tems, it is required that a 4-wire wall thermostat and Blower Relay Kit 7900-7761 be installed,
Unitary Products Group 15
16
035-16328-002 Rev. C (0902)
!
ORG ORG
I
BLOWER t
I BLEND-AIR
I CONTROL BOX
[ (IF EQUIPPED i
, , .
i
I
] i
{
K
4 s
BLK
6
MOTOR
7
MANUAL
RESET
LIMIT
SWITCH
9
WHT
I
:_g l
€ BLOWER
RELAY
GRY
ORG
I
TRANSFORMER
LOAD
..._ s°c%w
FAN
SWITCH
©
-
24V SEC.
>-
LINE
BRN
BLU i i i
, i
GRN
WHT
RED
3 AMP FUSE
[_]i BLK b
• r
1 AIC i CONDENSING
I UNIT
• J CONTACTORI
, L ......
J i' LUl
2°_w_ .,vAc
{_i NEU.
LI
WALL
"lit
THERMOSTAT i'_
_
_ WHT
!
BLK
TO EARTH GND.
Q
E
WHT
BLK
SYSTEM
SWITCH
Oo_3
AUTO
RESET
LIMIT
SWITCH
GAS
CONTROL
FIGURE 21 : Wiring Diagram for DGPA056, DGPA070, DGPA077
Unitary Products Group
035-16328-002 Rev. C (0902)
BLEND AIR
CONTROL BOX I
I
!
(IF EQUIPPED) I
RESET
LIMIT
SWITCH
BLOWER
MOTOR
ORG
2N
_5
)6
81
_2
'1
_,
/
GRY
A/C
BLOWER
RELAY
ORG
ORG
COMBUSTION
BLOWER
RELAY m
:).
EW
Z
_}_ i_
GRN
WriT
RED i_
W,
' I_ BLK
-J'
, F
-I AJC
I CONDENSING I l
I UNIT
CONTACTOR I
I
L .......
RED
3 AMP FUSE
NEU.
WHT
WA,,
THERMOSTAT
_,._
LI BLK
:J
"lit L
TO EARTH GND,
_
GND.
SCREW
FIGURE 22 : Wiring Diagram for DGPA090
FAN
SWITCH
WHT
/
IT
©
AUTO RESET
LIMIT SWITCH zl.oo m_
O _
BLK
PRESSURE _
SWITCH
SYSTEM
°°_ 3
SWI_
GAS
CONTROL
Unitary Products Group 17
18
UPPER
I LIMIT SWITCH
BLU
CRY
RED
ORG
WALL
THERMOSTAT
TO A]C
__,J
CONDENSING
UNIT (if equipped) ............
ERL_
BLOW
MOTOR
BLK
WHT
RED RED m O o o
BLK I
I I
I
I TO EARTH GROUND
NEUTRAL
115
VAC L1
WHT o
ca L o; WHT
GROUND
X o
BRN
BRN
BLK
BLK
WHT
WHT
7
TRANSFORMER
SYSTEM
SWITCH
VAC
BLK
Q
LIMIT
SWITCH
YEL i
©
COMBUSTION AIR
SWITCH
Or-o
O_w
;i3mc
5
Z i c---..--
I GAS
I VALVE
_----.--
HOT SURFACE
IGNITOR
INCOMING POWER MUST BE POLARIZED.
OBSERVE COLOR CODING.
FIGURE23 : Wiring Diagram for DGAA and DGAH Models
Unitary ProductsGroup
GAS PIPING
INSTALLATION AND CHECKING OF GAS LINE
Gas Supply piping must be sized in accordance with the recommendations contained in National Fuel Gas Code (ANSI-
Z223.1, NFPA-54) unless local codes or regulations state otherwise.
Matedals used and pipe sizing for U.S. manufactured homes must comply with requirements contained in Manufactured
Homes Al19.1, Recreational Vehicles Al19.2
and H.U.D.
Title 24, Section 3280.705 and any local or state codes.
NOTE: The gas line inlet on the gas valve is 1/2-14 N.ET
The gas line may be installed through the furnace floor or furnace side to the gas valve.
F& CAUTION
To install gas line and to connect it to the gas valve, care must be taken to hold gas valve firmly
to prevent misalignment of the bumer orifice, or to damage gas valve which could result in
improper heating, explosion, fire or asphyxiation.
DO NOT USE EXCESSIVE PIPE SEALANT ON
PIPE JOINTS. Pipe sealant, metal chips or other foreign material that could be deposited in the inlet of the gas valve, when gas pipe is installed or carried through the gas piping into the gas
valve inlet after installation, may cause the gas
valve to malfunction and could result in possible
improper heating, explosion, fire or asphyxiation.
Also, pipe sealant must be resistant to Propane gas.
Where regulations require, a main shut-off valve shaft be installed externally of furnace casing.
After piping has been installed, turn gas on and check aft connections with a leak detector or
soap solution.
Never use open flame to test for gas leaks as
fire or explosion could occur.
Do not test the fuel system at more than 14" HZC. after furnace has been connected to fuel line.
Such testing could void the warranty. Any test run
above 14" WC.
may damage furnace control valve which could cause an explosion, fire or asphyxiation.
I CAUTION!
If the gas input to the furnace is too great because of excessive gas pressure, wrong size orifice, high altitude, etc., the burnerflame will be
sooty and may produce carbon monoxide, which
could result in unsafe operation, explosion, and/
or fire or asphyxiation.
A dirt leg may be required by some local cedes to trap moisture and contaminations.
035-16328-002 Rev. C (0902)
For natural gas operation, the furnace is designed for 7" W.C.
inlet gas pressure. Pressure to main burner is then reduced to 3 1/2" W.C.
For Propane gas operation, the furnace is designed for 11"
W.C. inlet gas pressure. Pressure to main burner is then reduced to 10" W.C.
IMPORTANT - When converting gas valve from or to Pro- pane gas, it will be necessary to change main burner orifice to prevent an underfired or overfired condition. See label inside lower furnace door for complete instructions.
Pilot Adjustment
On models equipped with standing pilot ignition, the pilot should be adjusted so that the flame is approximately 1" in height (500 BTU / hr.). This will allow proper burner ignition without excessive fuel usage. The pilot adjustment screw is located on the top of the gas valve.
2,
3.
4.
5.
Observing Burner Operation
1,
Observe burner to make sure it ignites. Observe color of flame. On natural gas the flame will burn blue with appreciably yellow tips. On Propane gas a yellow flame may be expected. If flame is not the proper color call a qualified service technician for service.
Let furnace heat until blower cycles on.
Turn thermostat down.
Observe burner to make sure it shuts off.
Let the furnace cool and blower cycle off.
kWARNING]
Should overheating occur, or the gas supply fail
to shut off, shut off the manual gas valve to the furnace and allow bomer to run until furnace cools down and blower shuts off before shutting off the electdcal supply.
If any abnormalities are observed when checking for correct operation, such as burner failing to ignite or to turn off, sooty flame, etc., call your nearest authorized service technician as
shown in the Service Center List included in the home owner envelope with the furnace.
2.
If Furnace Fails to Operate Properly
1.
Check setting of thermostat - and position of HEAT/
COOL switch if air conditioning is installed. If a set-back type thermostat is employed be sure that the thermostat is in the correct operating mode.
3.
4.
5.
Check to see that electrical power is ON.
Check to see that the knob or switch on the gas control valve is in the full ON position.
Make sure filters are clean, return gdfies are not obstructed, and supply registers are open.
Be sure that furnace flue piping is open and unobstructed.
If the cause for the failure to operate is not obvious, do not
attempt to service the furnace yourself. Call a qualified ser- vice agency or your gas supplier.
Unitary Products Group 19
FINAL PROCEDURE
INSTALL FURNACE DOORS
Install the lower door first by sliding the bottom of the door down until the tabs on the casing base engage the slots in the bottom door end cap. Then push the top of the lower door in until the door clips snap into place. Install the upper door in a
similar manner, first engaging the slots in the top of the upper door on the tabs on the casing top. Then snap the bottom of the upper door into place against the casing.
FINISH AND TRIM
Alcove and Closet Installations may now be finished and trimmed as necessary.
/ AUTOMATIC
DAMPER
FURNACE AND AIR CONDITIONER
INSTALLATIONS
If an air conditioner is installed which does not use the blower for air distribution and operates completely independent of the furnace, the thermostat system must have an interlock to prevent the furnace and air conditioner from operating at the
same time. This interlock system usually contains a heat-cool switch which must be turned to either HEAT or COOL to acti- vate either heating or cooling operation, or a positive OFF switch on the cooling thermostat.
When used in connection with a cooling unit the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heat exchanger.
For installations with a parallel flow arrangement, the furnace must be equipped with a damper to prevent cold air from being discharged up around the heat exchanger.
Cold air causes condensation inside the exchanger and can cause it to rust out which can allow products of combustion to be circulated into the living area by the furnace blower resulting in possible asphyxiation.
An air flow activated automatic damper, PIN 7900-6771, is available from furnace manufacturer. See Figure 24.
NOTE: See label on coil panel for conversion and lighting instructions.
Obtain a temperature rise within the ranges specified on the name plate.
FURNACE
BASE
DUCT
CONNECTOR
NOTE: FOR BEST AIR DELIVERY INSTALL DAMPER
WITH BLADES PARALLEL TO SUPPLY DUCT.
FIGURE 24 : Anti-Backflow Damper
20 Unitary Products Group
HIGH ALTITUDE DERATION CHART
Elevation
Sea Level
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
Odfice
56,000--lnput
Drill
Dia.
Size
0.136
0.136
29
29
Pa_ #
9951-1361
9981--1361
0.128
0.128
0.128
0.128
0.129
0.120
0.120
0.116
30
30
30
30
31
31
31
32
9981--1281
9951--1281
9951-1281
9951-1281
9951--1291
9951-1201
9951_-1201
9951--1161
Odfce
Dia.
NATURAL GAS
70,000--Input
Dnll
Size
Pa_ #
Odfice
Dia
0.161
77,000--Input
Ddll
Size
Pa_ #
20 9951--1611 0,154
0.149
0,149
0,147
0,144
23
25
25
26
27
9951--1541
9951--1491
9951--1491
9951-1471
9951-1441
0.157
0.157
0.154
0.152
22
22
23
24
9951-1571
9951-1571
9951=1541
9951-1521
0.144
0.140
0.136
0.136
0.128
27
28
29
29
30
9951-1441
9951--1401
9951--1361
9951--1361
9951--1281
0.149
0.147
0.144
0.140
0.136
25
26
27
28
29
9951--1491
9951--1471
9951--1441
9951--1401
9951--1361
Odfice
Dia.
90,000--Input
Ddll
Size
Pa_ #
0.180
15 9951-1801
0.177
0.173
0.173
0.169
16
17
17
18
9951--1771
9951--1731
9951--1731
9951--1691
0.166
0.161
0.161
0.157
0.152
19
20
20
22
24
9981--1661
9951-1611
9951--1611
9951-1571
9951-1521
Elevation
Sea Level
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
Orifice
Dia.
56,000--Input
Ddll
Size
Pa_ #
0.082
0.081
0.078
0.078
0.078
0.076
0.076
0,073
0.073
0.070
48
46
47
47
47
48
48
49
49
50
9951--0821
9951--0811
9951--0781
9951--0781
9951--0781
9981--0761
9951--0761
9951--0731
9951--0731
9951--0731
Odfice
Dia.
0.093
0.093
0.089
0.089
0.089
0.086
0.086
0.082
0.081
0.078
42
42
43
43
43
44
44
45
46
47
Table shows 4% Input Reduction per 1,000 feet Elevation.
Reference Source: NFPA No. 54, ANSI Z 223.1, National
Fuel Gas Code.
PROPANE GAS
70,000--Input
Ddll
Size
Pad#
9951-0931
9951-0931
9951-0891
9951--0891
995%-0891
9951--0861
9951--0861
9951--0821
9951-0511
9951--0781
Orifice
Dia.
77,000--Input
Drill
Size
0.098
0.096
0.093
0.093
40
41
42
42
Pa_ #
9951_-0981
9981-0961
9951-0931
9951--0931
0.093
0089
0.089
0.086
8.086
0.082
42
43
43
44
44
48
9951--0931
9951--0891
9951--0891
9951--0861
9951--0881
9951-6821
Odfice
Dia.
90,000--Input
Ddll
Size
0.106
0.104
0.101
0.101
0.099
0.098
0.096
0.096
0.093
0.059
36
37
38
38
39
40
41
41
42
43
Pa_ #
9951-1061
9951--1041
9951--1011
9951-1011
9981--0991
9951--0981
9951-0961
9951-0961
9951--0931
9981-0891
For Canadian high altitude (2000 - 4500 feet), reduce gas manifold pressure to 3.0" W.C. for natural gas, 9,0"
W.C. for Propane gas.
Unitary Products Group 21
035-16328-002 C(0902)
REPAIR PARTS LIST
_ __'_
DGAA056BDTA
DGAA070BDTA
DGAA077BDTA
DGAA090BDTA
DGAH056BBSA
DGAH077BBSA
DGPA056ABTA
DGPA070ABTA
DGPA077ABTA
DGPA090ABTA
DGPH056ABTA
DGPH070ABTA
DGPH077ABTA
DGPH09OABTA i DGAA,DGAH
L DGP_ DGPH
®
[]
3--"
/
"4
DGAA, DGAH DGPA, DGPH
I
CONTROL BOX DETAIL
22 Unitary Products Group
DGAA
ITEM
2
4
14
15
16
17
18
6
7
8
9
10
29
21
23
26
27
28
29
30*
DESCRIPTION
Switch, Pressure
Tubing Silicone (2' Req'd)
Limit Switch, Manual(Upper)
Assembly, Booster (w/Motor)
Control Board, Integrated
Valve, Gas
Bracket, Valve
Thermostat (Heat/Cool)
Exchanger, Heat (w/Gaskets)
Sensor, Flame
Switch, System
Transformer (115-24V, 40 VA)
Switch, Limit
Burner Assembly, Auto Ignition
Includes items 10 & 15)
Ignitor, Hot Surface
Filter (2 Req'd) (16x20x1)
Panel, Door (Upper)
Panel, Door (Lower, Tall)
Motor (See note 2)
Assembly, Motor Mount (See Note 3)
Plug, Connector
Capacitor, Run (See Note 3)
Wheel, Blower
Relay, Fan
Relay, Booster
Switch, Fan
Thermocouple
Burner, Pilot
Tube, Pilot
Diagram, VVidng
DGAA056BDTA
024-27666-000
028-11957-000
025-35358-000
373-19801-820
031-01932-000
7990-328P
073-19801.664
373-19804-651
025-35354-000
7681-3301
2940A3541
025-35380-000
373-19801-403
1474-052P
1214-2511
373-19801-740
1468-220P
373-19606-190
025-21192-000
024-20063-000
1472-2761
.........
...........
........
...........
...........
.......
036-15289-001
DGAA070BDTA
1474-052P
1214-2511
DGAA077BDTA
024-27666-000
028-11957-000
026-35358-000
373-19801-820
024-27666-000
028-11957-000
025-35356-000
373-19801-820
031-01932-000
7990-328P
073-19801-064
031-01932-000
7990-328P
073-19801-064
Accessory (See Page 6)
373-19805-651
025-35354-000
373-19806-651
025-35354-000
7681-3301
2940A3541
625-35380-000
373-19801-403
7681-3301
2940A3541
025-35381-090
373-16801-403
Accessory (See Page 6)
373-19801-740
_468-220P
373-19806-100
025-21192-000
024-20063-006
1472-2761
035-15289-001
NOTE: *Not Shown
New replacement parts shown in bold face type at the first pdnting of parts list dated 9/02.
Ma_or components and suggested stocking items are shown with shaded ilem number
"<=Across from row indicates a change in that row.
--- Not applicable to specified model.
2. For Sedal Numbers lower then 001207164- Replacement DGAA motors also require Motor Mount
Assembly 373-19806-100 if replaced motor has integral, flex-arm motor mount.
3 DGAA wffh 5-Ton Blowers are provided as an accessory item and are nat standard equipment from the faatony. See Page 6
1474-052P
1214-2511
373-19801-740
1468-220P
373-19806-100
025-21192-000
024-20063-000
1472-2761
035-15289-601
DGAA09OBDTA
024-27666-000
028-11957-000
025-35358-009
373-19801-820
031-01932-000
7990-326P
073-19601-064
373-19806-650
025-35354-000
7681-3301
2946A3541
025-35381-000
373-19801-403
1474-052P
1214-2511
373-19801-740
1468-220P
373-19806-100
025-21192-000
024-20063-000
1472-2761
035-15289-001
Unitary Products Group 23
035-16328-002 Rev. C (0902)
DGAH
ITEM DESCRIPTION
2
Switch, Pressure
Tubing Silicone (2' Req'd)
Limit Switch,Manual (Upper)
4
6
7
8
Assembly, Booster (w/Motor)
Control Board, Integrated
Valve, Gas
Bracket, Valve
9
19
Thermostat (Heat/Cool)
Exchanger, Heat (w/Gasketa)
Sensor, Flame
_ Switch, System
Transformer (115-24V, 40 VA)
Switch, Limit
27
28
29
30*
14
15
16
17
18
Burner Assembly, Auto Ignition
Includes iternss 10 & 15)
Ignitor, Hot Surface
Filter (2 Req'd) (16x20×1)
Panel, Door (Upper)
29
21
Panel, Door (Lower, Short)
Motor (See Note 3)
Assembly, Motor Mount
Plug, Connector
Capacitor, Run
Wheel, Blower 23
Relay, Fan
25 ! Relay, Booster
Switch, Fan
Thermocouple
Burner, Pilot
Tube, Pilot
Diagram, Vvldng
DGAH056BBSA
024-27666-000
028-11957-000
025-35358-000
373-19801-820
DGAH077BBSA
024-27666-600
028-11957-000
025-35358-009
031-01932-006
7990-328P
073-19891-064
373-19601420
031-61932-069
7999-328P
073-19801-064
AP._essory (See Page 6)
373-19804-651 373-19806-651
625-35354-000
7661-3301
025-35354-000
2946A3541
7681-3391
2940A3541
025-35380-090
373-19891_-93
925-35381-900
373-19861-493
1474-952P
1214-2511
1474-052P
1214-2511
Accessory(See Page 6)
373-19801-790 373-19801-790
024-31948-009 924-31948-900
025-21192-000
1472-2761
035-15289-901
NOTE: *Not Shown
New replacement parts shown in bold face type at the first printing of parts list dated 9/02.
Major components and suggested stocking items are shown with shaded item number,
"<= Across from row indicates a change in that row
-- Not applicable to specified model.
025-21192-000
1472-2761
035-15269-901
3. DGAH with 5-Ton Blowers are provided as an accessory item and are not standard equipment from the factory. See page 6.
24 Unitary Products Group
035-16328-002 C(0902)
DGPA
6
7
8
9
10
ITEM
2
4
14
15
16
17
18
20
21
23
25
27
28
29
30*
DESCRIPTION
Switch, Pressure
Tubing Silicone (2' Req'd)
LimitSwitch,Manual(Upper)
Assembly, Booster (w/Motor)
Control Board, Integrated
Valve, Gas
Bracket, Valve
Thermostat (Heat/Cool)
Exchanger, Heat (w/Gaskets)
Sensor, Flame
Switch, System
Transformer (115-24V, 46 VA)
Switch, Limit
Standing Pilot, Burner Assembly
Includes items 10 & 15)
Ignitor, Hot Surface
Filter (2 Req'd) (16x20xl)
Panel, Door (Upper)
Panel, Door(Lower, Tall)
Motor (See Note 3)
Assembly, Motor Mount
Plug, Connector
Capacitor, Run
Wheel, Blower
Relay, Fan
Relay, Booster
Switch, Fan
Thermocouple
Burner, Pilot
Tube, Pilot
Diagram, tA_dng
DGPA086ABTA
.......
........
025-35358-000
........
..........
7956-336P
073-19801-064
373-19804-651
..........
7681-3301
2940A3541
025-35380-000
373-19801-401
........
1214-2511
373-19801-740
024-31948-000
..........
028-21192-000
.....
1472-2761
3110-3301
.......
7975-3281
7945-3481
9680-0141
029-22188-600
035-15287-001
DGPA070ABTA
025-35358-000
7956-336P
073-19601-064
373-19801-746
024-31948-000
DGPA077ABTA
025-35358_000
7956-336P
073-19801-064
Accessory (See Page 6)
373-19805-651 373-19806451
7681-3301
2940A3541
025-35380-069
373-19801-401
1214-2511
Accessory (See Page 6)
025-21192_000
1472-2761
3116-3301
7975-3281
7945-3481
9880-0141
029-22188-000
035-15287-001
NOTE: *Not Shown
New replacement pa_s shown in bold face type at the first pdnting of parts list dated 9/02
Major components and suggested stocking items are shown with shaded item numbe_
"<" Across from row indicates a change in that row.
-- Not applicable to specJfiedmodel.
3. DGPA with 4 or S-Ton Blowers are provided as an accessory item and are not standard equipment
from the factory See Page 6
7681-3301
2946A3541
025-35381-000
373-19801-401
1214-2511
373-19801-740
024-31948-000
028-21192-000
1472-2761
3119-3391
7975-3281
7945-3481
9880-0141
029-22168-006
035-15287-001
DGPA090ABTA
024-27666-000
028-11957-000
025-35358-000
373-19601-820
7956-336P
073-19801-064
373-19806-650
7681-3301
2940A3541
925-35381-000
373-19801*402
1214-2511
373-19801-740
024-31949-900
025-21192-000
024-20045-000
1472-2761
3110-3301
3110-3301
7975-3281
7945-3481
9880-0141
029-22188-960
035-15288-001
Unitary Products Group 25
035-16328-002 C(0902)
ITEM
2
Switch, Pressure
Tubing Silicone (2' Req'd}
LimitSwitch,Manual(Upper)
4
6
7
8
Assembly, Booster (w/Motor)
Control Board, Integrated
Valve, Gas
Bracket, Valve
Thermostat (Heat Only)
9 Exchanger, Heat (w/Gaskets)
10 !Sensor, Flame
Switch, System
14
15
16
17
18
20
21
23
25
26
27
28
29
30
DESCRIPTION
Transformer (115-24V, 40 VA)
Switch, Limit
Standing Pilot, Burner Assembly
Includes items 10 & 15)
Ignitor, Hot Surface
Filter (2 Req'd) (16x2Ox1)
Panel, Door (Upper)
Panel, Door (Lower, Tall)
Motor (See Note 3)
Assembly, Motor Mount
Plug, Connector
Capacitor, Run
Wheel, Blower
Relay, Fan
Relay, Booster
Switch, Fan
Thermocouple
Burner, Pilot
Tube, Pilot
Diagram, Wiring
DGPH
DGPH056ABTA DGPH070ABTA
025-35358-000
7956-336P
073-19801-064
373-19504451
7970-3331
2940A3541
025-35380-000
373-19801401
025-35358-000
DGPH077ABT/
025-35358-000
DGPH090ABTA
024-27666-000
028-11957-000
025-35358-000
373-19801-820
7956-336P
073-19801-064
7956-336P
073-19801-064
Accessory (See Page 6)
373-19805_651 373-19806451
---
7970-3331
2940A3541
025-35380-000
373-19801-401 n_
7970-3331
2940A3541
025-35381-000
373-19801401
7956-336P
073-19801-064
373-19806-650
7970-3331
2940A3541
025-35381-000
373-19801-402
1214-2511
373-19801-740
024-31948-000
025-21192-000
1472-2761
7975-3281
7945-3481
9880-0141
029-22188-000
035-15285-001
1214-2511 1214-2511
Accessory(See Page 6)
373-19801-740
024-31948-000
373-19801-740
024-31948-000
---
025-21192-000
__=
1472-2761
_.
025-21192-000
1472-2761
7975-3281
7945-3481
9880-0141
029*22185-000
035-15285-001
7975-3281
7945-3481
9880-0141
029-22188-000
035-15285-001
1214-2511
373-19801-740
024-31949-000
025-21192-000
024-20045-000
1472-2761
3110-3301
7975-3281
7945-3481
9880-0141
029-22188-900
035-15286-001
NOTE: *Not Shown
New replacement parts shown in bold face type at the first printing of parts list dated 9/02.
Major components and suggested stocking items are shown with shaded item numpen
"<= Across from row indimate$ a change in that row.
-- Not applicable to specified model.
3. DGPH with 4 or 5-Ton Blowers are provided as an accessory item and are not standard equipment from the factory. See page 6.
26 Unitary Products Group
035-16328-002 Rev. C (0902)
MODEL
NATURAL GAS
LP GAS
BURNER ORIFICE CHART (Normal Altitude Only 4)
056
9951-1361
9951-0821
070
9951-1541
9951-0931
NOTES
4, Contact Customer Service for installations at altitudes over 2000 feet above sea level.
=<=Across from row indicates a change in that row.
077
9951-1611
9951-0981
DESCRIPTION
Thermostat (Heat/Cool)
Thermostat (Heat Only)
Door Panel (Upper)
ACCESSORY PARTS LIST
DGAA
025-38251-000
......
373-19802-010
DGAH
026-38261-000
373-19802-010
4-Ton Blower Ass' Motor
7900-7741/A Run Capacitor (7.5 MFD)
Motor Mount
Blower Wheel
5-Ton BlowerAss' Motor
7900-7751 Run Capacitor (20 MFD)
Motor Mount
Blower Wheel
.....
--
.....
....
024-31975-000
024-20051-000
373-19802-930
1472-2761
--
024-31975-000
024-20051-000
373-19802-930
1472-2761
DGPA
025-38251-000
373-19802-010
1468-220
024-32020-000
373-19806-100
1472-2761
024-31975-000
024-20051-000
373-19802-930
1472-2761
090
9951-1801
9951-1061
DGPH
---
028-38252-000
373-19802-010
<
<
1468-220
024-32020-000
373-19806-100
1472-2781
024-31975-000
024-20051-000
373-19802-930
1472-2761
Unitary Products Group 27
NOTES
Subject to change without notice. Printed in U.S.A.
Copyright © by York Intemational Corp. 2002. All rights reserved.
Unitary
Products
Group
P.O.
Box
19014
035-16328-002 Rev. C (0902)
Supersedes: 0035-16328-002 Rev. B (1001)
Wichita
KS
67204-9014
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project