TP-8101, TP-8102, TP-8103,

TP-8124, TP-8125

Electronic, Proportional Controlling

Thermostats

General Instructions

TP-8101, TP-8102, TP-8103

These self-contained room temperature controllers conserve energy in heating and/or cooling applications requiring a single setpoint adjustment. See Table-1 for particular characteristics.

The heating and cooling equipment is precisely controlled from a single 1000 ohm Balco sensor operating through a single controller for heating and/or cooling. The controller provides a proportional output to control TAC System 8000 controlled devices for control of valves, dampers, electric heat, DX coils, etc.

TP-8124, TP-8125

These self-contained room controllers conserve energy in heating and/or cooling equipment in applications requiring heating and cooling setpoint adjustment.

See Table-1 for particular characteristics.

The heating and cooling equipment is precisely controlled from a single 1000 ohm Balco sensor operating through independent heating and cooling controllers. These controllers provide proportional outputs to control TAC

System 8000 controlled devices for control of valves, dampers, electric heat, DX coils, etc. The heating output

(OP1 to COM) can be programmed for direct-acting or reverse-acting operation. The cooling output (OP2 to COM) provides a direct-acting output only.

TP-8101,

TP-8102,

TP-8103

Single Setpoint

Adjustment

TP-8124

& TP-8125

Dual

Setpoint

Adjustment

90

80

70

60

50

Table-1

Part Number

TP-8101

TP-8101-116

TP-8102

TP-8103

TP-8124 Dual

Setpoints

TP-8125

Dual

Setpoints

Dial

Marking

°

°

°

°

°

F &

°

C

F &

F &

F &

F &

°

°

°

°

°

C

C

C

C

C

Control

Dial Range

Throttling

Range for 3

Vdc Output

Change

55-85

°

F

13-29

°

C

7-24 ° C

(45-75 ° F)

24-41

°

C

(75-105

°

F)

2, 3, 6 and

20

°

F Factory

Set 3

°

F By

Jumper/Pins

Heating

7-24

°

C

(45-75

°

F) cooling

21-38

°

C

(70-100

°

F)

Heating

7-24

°

C

(45-75 ° F)

Cooling

24-41 ° C

(75-105 ° F)

Heating and

Cooling

2-10

°

F

Independently

Adj.

Factory Set

3 ° F

Input

Voltage

20 Vdc

13 mA

20 Vdc

23 mA

Output

Voltage

2-15 Vdc or

15-2 Vdc

Control Action

Wiring

Connections

Number of

Controlled

Devices

Factory Set

Direct-acting

Jumper

Terminal 4 to 5

For

Reverse-acting

Jumper

Terminal 4 to 3

3 Color-coded

Pigtail Leads

Terminals for

Options See

Figure 2

6

TAC System

8000

Devices or 2

MP-5200

Series

Actuators

Heat 2-15 Vdc or

15-2 Vdc

Cool

2-15 Vdc

Heating Factory

Set

Reverse-acting

Jumper J7 to pin B for

Direct-acting

Cooling

Direct-acting only

Coded

Terminals see Figure 3

6

TAC System

8000

Devices or 2

MP-5200

Series

Actuators in both Heating and Cooling

Printed in U.S.A.

8-08

©

Copyright 2008 TAC All Rights Reserved.

F-18097-8

Features

1. TP-8124 meets ASHRAE 90-75 and DOE requirements.

TP-8125 meets DOD requirements.

2. Heating and cooling cannot operate simultaneously.

3. Heating/cooling deadband obtained by adjustable dual setpoints and throttling range.

4. Proportional outputs operate remote TAC System 8000 controlled devices such as valves, dampers, electric heat coils, etc.

5. Concealed adjustments eliminate occupant tampering.

INSTALLATION

Open the carton and visually inspect the device for part number and obvious defects before proceeding with the installation.

Mounting screws are provided.

Locate the controller where it will be exposed to unrestricted natural air circulation and to the average conditions of the controlled space. Do not locate it near sources of heat or cold

(such as lamps, motors, sunlight radiators and concealed pipes or ducts within the wall) which might affect the control point. Avoid locations where excessive vibration moisture.

Corrosive fumes or vapors are present, or where high radio frequency or electromagnetic generating devices are near.

Dimensions

111 mm (4-3/8") high x 77 mm (2-7/8") wide x 41 mm (1-5/8") deep.

Ambient Limits

Operation: 40 to 140

°

F (4.4 to 60

°

C). Storage: 40 to 160

°

F

(-40 to 71

°

C).

Figure-1

MODES OF OPERATION

1. Direct-acting control (DA): Increase in temperature at the sensor causes the controller output signal to increase.

2. Reverse-acting control (RA): Increase in temperature at the sensor causes the controller output signal to decrease.

THROTTLING RANGE

Throttling range (T.R.) is defined as the degrees (

°

F or

°

C) change at the temperature sensor in order to cause a 6 to 9

Vdc controller output signal change.

Figure-2 Terminal Nomenclature TP-8101, TP-8102, and

TP-8103.

Figure-3 Terminal Nomenclature TP-8124 and TP-8125.

WIRING

Make all electrical connections according to installation wiring diagrams. Comply with national and local electrical codes.

No. 18 multi-conductor thermostat cable may be used. Low voltage Class 2 wire is acceptable, but No. 18 or larger 600V wire should be used if splices are to be made in the same junction box with the voltage wiring.

The controller may be installed on either a 52 mm x 102 mm

(2" x 4") flush switch box or a surface switch box. To install, proceed as follows:

1. Wiring for the TP-8101, TP-8102 and TP-8103 is shown in

Figures 4 and 5. See Figures 6 and 7 for TP-8124 and

TP-8125 typical wiring.

2. “Pull” all wires required.

3. Connect all control wiring to the thermostat.

4. Remove the thermostat cover by loosening the screw at the bottom of the cover. Pull the cover out from the bottom and up to disengage it from the base.

5. Fasten the base to the box with the screws provided.

6. Replace the cover and tighten the cover screw.

2 ©

Copyright 2008 TAC All Rights Reserved.

F-18097-8

WIRING OF CONTROLLED DEVICES TO

CONTROLLER

Types of controlled devices and their power supplies:

1. Filtered and regulated power supplies: All TAC System

8000 controlled devices except MP-52XX and MP-54XX series actuators.

2. Filtered and unregulated power supplies: MP-54XX series actuators.

3. Unfiltered and unregulated power supplies: MP-52XX series actuators.

General rules for wiring controllers to controlled devices:

1. Never connect red lead (or +20 terminal) of any controlled device which has a regulated power supply to the red lead

(or +20 terminal) of any other controlled device.

2. Controlled devices with unfiltered and unregulated power supplies must be filtered. TAC System 8000 controllers will provide filtering for a maximum of two controlled devices by connecting the two red leads (+20 terminals) together at the controllers red lead (+20 terminal).

3. Controlled devices with filtered and unregulated supplies.

Up to six controlled devices with the red leads (+20 terminals) can be connected together. Number of units paralleled depends on the current (mA DC) requirements of the controller of adaptor.

Table-2 Devices and Their Internal Supplies.

Filtered & Regulated

CC-8101

Filtered &

Unregulated

MP-54XX

Actuators

Unfiltered &

Unregulated

MP-52XX

Actuators

CC-8102

CC-8103

CC-8118 Series

CC-8218 Series

CC-8111 Series

CP-8301 Series

CP-8161 Series

CP-8425 Series

CP-5501 Series

CP-8502 Series

Figure-4 TP-8101, TP-8102, and TP-8103 Typical Wiring without MP-52xx Actuators.

F-18097-8

©

Copyright 2008 TAC All Rights Reserved.

3

Figure-5 TP-8101, TP-8102, and TP-8103 Typical Wiring with MP-52xx Actuators.

4

Figure-6 TP-8124 and TP-8125 Typical Wiring with One or No Mp-52xx Actuators.

©

Copyright 2008 TAC All Rights Reserved.

F-18097-8

Figure-7 TP-8124 and TP-8125 Typical Wiring with Two MP-52xx Actuators.

ADJUSTMENTS

TP-8101, TP-8102, TP-8103

1. Turn the setpoint adjuster to the required temperature setting. Normally, no further adjustments are required.

2. Throttling range settings of 2, 3, 6 and 20

°

are available by placing the T. R. jumper on the proper selector pin.

See Figure 8. For other throttling ranges (1 through 60

°

) add a resistor to the auxiliary pins. Select the resistor from the chart below. Place the T. R. jumper on the auxiliary pin nearest the center of the controller.

TP-8124 and TP-8125

1. Remove the cover and turn the setpoint adjuster (SPA) to the required temperature for heating mode (typically 65

°

F).

Turn the setpoint adjuster (SPB) to the required temperature for the cooling mode (typically 78

°

F).

The cooling signal is direct-acting, and stages cooling or proportionally opens a normally closed chilled water valve with a temperature increase.

The heating signal is factory set for reverse-acting. With a temperature decrease, the signal stages electric heat or proportionally increases the electric heat output controlled by a TAC CP-8400 or CP-80000 Series SCR controller.

2. For applications that require a direct-acting signal in the heating mode, such as normally open heating valve, move jumper J7 to pin “B”.

Table-3 Throttling Range Resistor Values.

8.0

9.0

10.0

15.0

4.5

5.0

6.0

7.0

o

F T. R.

1

1.5

2.0

2.5

3.0

3.5

4.0

20.0

25.0

30.0

40.0

50.0

60.0

Auxiliary Resistor

4.3 Meg. ± 5%

3.0 Meg. ± 5%

2.2 Meg. ± 5%

1.8 Meg. ± 5%

1.5 Meg. ± 5%

1.2 Meg. ± 5%

1 Meg. ± 5%

975K, ± 1%

866K, ± 1%

732K, ± 1%

619K, ± 1%

549K, ± 1%

487K, ± 1%

432K, ± 1%

287K, ± 1%

215K, ± 1%

174K, ± 1%

143K, ± 1%

107K, ± 1%

84.5K, ± 1%

69.8K, ± 1%

TAC Part Number

E19-23-562

CYZR-481-860

CYZR-481-580

CYZR-481-680

CYZR-481-450

CYZR-481-610

CYZR-862-496

CYZR-862-477

CYZR-862-462

CYZR-862-445

CYZR-837-913

CYZR-837-130

E19-64-390

CYZR-837-890

F-18097-8

©

Copyright 2008 TAC All Rights Reserved.

5

6

3. The Temperature Deadband between heating and cooling is the difference in SPB and SPA settings. For example, the deadband is 13

°

F with SPA at 65

°

F and

SPB at 78

°

F.

4. The throttling ranges are factory set at 3

°

F for heating and cooling. These settings should not be changed for normal applications. Increase the throttling range only to achieve control stability (adjustable 2 to 10

°

F).

To adjust, turn the T. R. dial to position the required T. R. value closest to the thermostat cover.

5. Replace the cover.

Figure-8 TP-8101, TP-8102, and TP-8103.

Figure-9 TP-8124 or TP-8125.

SERVICE

TP-8101, TP-8102, TP-8103

Note: The TP-8101, TP-8102 and TP-8103 have been factory calibrated to produce a 7.5 Vdc output signal at the yellow and blue leads (TO+ and TS-) when the setpoint and the temperature at the sensing element agree.

1. Verify wiring per job wiring diagram.

2. Measure with a 20,000 ohm per Vdc VOM.

a. Power supply 20 Vdc Red (+) to blue (-) wires or test point pins TS- and TS+ (+ end of the 47

μ

ƒ

capacitor).

b. Output 2 to 15 Vdc: Yellow (+) to blue (-) wires or TO+ and TS- test pins. The voltage varies between 2-15 as the dial knob is rotated.

3. Consult EN 111 for additional service information.

4. Replace the controller if it is defective.

If calibration is necessary, proceed as follows:

1. Connect a 20,000 ohm per Vdc VOM between the yellow

(+) and blue (-) leads or TO+ and TS- pins on the thermostat.

2. With the thermostat cover on, insert a 5/64” Allen wrench through the hole on the right-hand side of the thermostat into the setpoint potentiometer shaft.

3. Measure the temperature at the thermostat.

4. Adjust the thermostat setpoint by rotating the Allen wrench until the setpoint dial reading equals the temperature measured in step 3 above.

5. Using the thumb of your left hand, hold the knob in place.

Avoid touching the lower left-hand corner of the thermostat where the sensor is located.

6. Rotate the Allen wrench until VOM reads 7.5 ± 3 Vdc.

7. The thermostat is calibrated.

TP-8124 and TP-8125

Note: The TP-8124 and TP-8125 have been factory calibrated to produce 6.0 Vdc output signals at OP1 and OP2 to COM terminals when the setpoints and the temperatures at the sensing element agree.

Test the power supply and output as follows:

1. Verify the wiring per the job wiring diagram.

2. Measure with a 20,000 ohm per Vdc VOM: a. Power supply 20 Vdc: ±20 (+) to COM (-).

b. Heating output: OP1 (+) to COM (-), Vdc varies between 2-15 as SPA is rotated.

c. Cooling output: OP2 (+) to COM (-). Vdc varies between 2-15 as SPB is rotated.

3. Replace the controller if it is defective.

If calibration is necessary, proceed as follows:

1. Remove the thermostat cover. Note room temperature.

©

Copyright 2008 TAC All Rights Reserved.

F-18097-8

2. If room temperature is 75

°

F or greater: a. Connect VOM internally to OP2 (+) and COM (-). See

Figure 10 for details.

b. Rotate SPB until VOM reads 6.0 ± 3 Vdc. SPB pointer must indicate the temperature measured. If not, hold

SPB shaft and rotate pointer (CCW) until it indicates the temperature measured.

SPB is calibrated.

c. Disconnect VOM lead from OP2 and reconnect to

OP1. Connect Jumper J7 to Pin A.

d. Connect 1 MEG ± 1% resistor (SYZE-13512 test kit) between AB1 and 6.2 connections.

e. Rotate SPA until VOM reads 6.0 ± Vdc. SPA should read temperature measured minus 10

°

F. If not, hold

SPA shaft and rotate pointer (CCW) until it indicates temperature measured minus 10

°

F.

SPA is calibrated.

3. If room temperature is 74

°

F or less: a. Connect VOM internally to OP1 (+) and COM (-). See

Figure11 for details.

b. Rotate SPA until VOM reads 6.0 ± 3 Vdc. SPA must indicate the temperature measured. If not, hold SPA shaft and rotate the pointer (CCW) until it indicates the measured temperature.

SPA is calibrated.

c. Disconnect VOM lead from OP1 and re-connect to

OP2. Connect Jumper J7 to Pin A.

d. Connect 1 MEG, ± 1% resistor (SYZE-13512 test kit) between AB2 and COM connections.

e. Rotate SPB until VOM reads 6.0 ± 3 Vdc. SPB should read the measured temperature plus 10

°

F. If not, hold

SPB shaft and rotate pointer (CCW) until it indicates the measured temperature plus 10

°

F.

SPB is calibrated.

Figure-10

F-18097-8

Figure-11 TP-8101, TP-8102., and TP-8103 Block Diagram.

©

Copyright 2008 TAC All Rights Reserved.

7

OPTIONS

TP-8101, TP-8102, TP-8103

Figure-12 TP-8124 and TP-8125 Block Diagram.

(TP-8124 and TP-8125 have no options.)

Remote Setpoint

Install the AT-8100 Series remote setpoint adjuster between terminals 1, 2 and 7. These are used for applications where the setpoint adjustment is mounted remote from the controller.

See Figure 15, 16, or 17.

Remove the dial rim from the setpoint knob using wire cutters.

Turn the dial to 70

°

F. The AT-11-404 blank cover is recommended to prevent dust infiltration.

Remote Sensing

Remove the internal 1000 ohm sensor and install the remote sensor (TS-8000 Series) between terminals 7 and 8. This is used for applications where the sensor is mounted remote from the controller. See Figure 14.

Summer-Winter Changeover

This is accomplished without remote setpoints or selective ratio discharge. The controller operates in either the DA or RA mode. See Figure 13.

Jumper 4 to 5 - DA (directing-acting): A temperature increase causes an output voltage increase.

Jumper 3 to 4 - RA (reverse-acting): A temperature increase causes an output voltage decrease.

Selective Ratio Discharge Control

Connect the ratio discharge sensor (Figure 20) to the room controller as shown in Figure 15, 16 or 17. This is used for room and discharge control applications.

Winter-Summer Operation

This is accomplished using selective ratio discharge and/or remote setpoints. For direct-acting see Figure 15. For reverse-acting, see Figure 16. For winter-summer switching, see Figure 17.

For panel mounting, see Figure 19.

8 ©

Copyright 2008 TAC All Rights Reserved.

F-18097-8

Figure-13 TP-8101, TP-8102, and TP-8103 with Single Pole Double Throw (SPDT) Winter-Summer Switching.

Figure-14 TP-8101, TP-8102, and TP-8103 with Remote Sensor.

F-18097-8

©

Copyright 2008 TAC All Rights Reserved.

9

Figure-15 TP-8101, TP-8102, and TP-8103 with Remote Setpoint and/or Selective Ratio Discharge Sensor.

Direct-Acting Output Only.

10

Figure-16 Tp-8101, TP-8102, and TP-8103 with Remote Setpoint and/or Selective Ratio Discharge Sensor

Reverse-Acting Output Only.

©

Copyright 2008 TAC All Rights Reserved F-18097-8

Figure-17 Tp-8101, TP-8102, and TP-8103 with Remote Setpoint and/or Selective Ratio Discharge Sensor with Double Pole

Double Throw (DPDT) Winter-Summer Switching.

F-18097-8

Figure-18 TP-8101, TP-8102, and TP-8103 with Night Depression and/or Morning Warm-Up.

©

Copyright 2008 TAC All Rights Reserved 11

Figure-19 TP-8101, TP-8102, and TP-8103 Mounted on AD-8951.

Figure-20 TS-8601 Ratio Discharge Sensor for use with TP-8101, TP-8102, and TP-8103.

MAINTENANCE

This is a quality product. Regular maintenance of the total system is recommended to assure optimum performance.

Copyright 2007, TAC

All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.

F-18097-8

TAC

1354 Clifford Avenue

P.O. Box 2940

Loves Park, IL 61132-2940 www.tac.com

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement