注意事項 此安裝手冊只提供電氣規格、一般規格、安裝及配線等。 配線

 Communication
Message type
I/O polled, bit-strobe, change of state/cyclic
Baud rates
125 Kbps; 250 Kbps;
500 Kbps
Product code
64
Product type
12
Vendor ID
799 (Delta Electronics Inc.)
Baud rates (bps)
125K
250K
500K
Length (m)
500
250
100
LED Indicator & Troubleshooting
There are three LED indicators and one digit indicator on DVPDNET-SL. POWER LED displays if the
power of DVPDNET-SL is working normally; NS LED and MS LED display the communication connection
status of DVPDNET-SL; digit indicator displays the node addresses, error information and the error
messages from the slave.
Electrical Specification
NS
POWER LED
Network power input: 11 ~ 25V DC; Current: less than 50mA (25V DC)
LED Status
Environment
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Noise immunity
POWER
MS
Indication
Off
Power is abnormal.
Green light On
Power is normal.
How to correct
Make sure the scanner is powered.
--
LED Status
Environment
Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40 ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)
Vibration/shock
resistance
Standard: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 (TEST
Ea)
Certificates
Indication
1. Make sure the scanner is powered.
No power or duplicate ID check has
2. Make sure at least 1 node or more are communicating
not completed
in the network.
Off
Green light
flashing
No communication
Green light On
Normal operation
Red light flashing Error in communication
Installation
支持第二組伺服器 (Group 2 server) 從站和僅限第二組伺服器 (Group 2 only server) 從站。
支援 DeviceNet 主站模式和從站模式。
在 ElinkConfigurator 組態軟體中支援 EDS 檔配置。
支持網站建立各種 IO 連接:輪詢(Polled)、位選通(Bit-Strobe)、狀態改變(Change of State)、週期循環
(Cyclic)。
在預定義的主/從連接組中支援顯性連接(顯性報文)。
提供 380 位元組的空間作為 I/O 輸入資料區,同時也提供 380 位元組空間作為 I/O 輸出資料區。
-
-
產品外觀
2
模組名稱
擴充機介面
Refer to digit-indicator.
3
Power, MS, NS
1. Make sure all the devices have their unique address.
4
DIN
No correction is needed, or refer to digit-indicator.
1
--
2. Check the network for correcting media installation
Network error; cannot check
and baud rate.
duplicate ID; Bus-off (please refer to
digit-indicator)
3. Check if the node address of RTU-DNET is valid.
Red light On
Dimension
How to correct
產品簡介
功能特色
-
NS LED
繁體中文
此安裝手冊只提供電氣規格、一般規格、安裝及配線等。
配線時請務必關閉電源,請勿在上電時觸摸任何端子。
本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電
擊/衝擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開),防止非維
護人員操作或意外衝擊本體,造成危險及損壞。
DVPDNET
Module power voltage: All other power derived from PLC controller power
supply
DeviceNet
注意事項
5
6
4. Check if the network power is normal.
7
DVPDNET
MS LED
NS
4
5
6
3
7
2
8
0
5
LED Status
9
1
4
1
x10
Indication
3
7
8
2
0
x10
9
0
1
DR 1
DR 0
IN 1
IN 0
Off
No power
Green light
flashing
The master is not configured.
Green light On
Normal operation
Red light
flashing
Some slaves encounter
communication error.
Red light On
Internal fault in the scanner module Check if the configuration is valid. If the internal error still
(please refer to digit-indicator)
exists, replace the scanner with a new one.
LED Status
NS LED
MS LED
Off
Off
ENGLISH
2
Switch off the power when wiring. DO NOT tough any terminal when the power is switched on.
DVPDNET
DVPDNET-SL is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools are required for opening the enclosure) in case danger and damage on the
device may occur.
1
RUN
Off
Green
Duplicate ID check has not
completed.
Make sure at least 1 node or more are communicating in
the network and the baud rate is the same as the setting
in DVPDENT.
Red
Green
MAC ID detection failure or
Bus-off
Change the MAC ID setting and re-power DVPDNET.
Red
Red flashing
No 24V DC power from
DeviceNet network
Check if the network cable is correctly connected to
DVPDNET. Check the 24V DC network power.
Red
Red
Functions
PIN
Model name
2
Extension port
3
Power, MS, NS LED
4
DIN rail clip
Color
Content
1
V-
Black
0V DC
2
CAN_L
Blue
Signal-
3
Drain
-
Shield
4
CAN_H
White
Signal+
5
V+
Red
24V DC
5
4
3
2
1
MAC ID Setting
Switch setting
Content
4
5
6
2
Extension clip
1
3
2
0
DeviceNet connection port
6
9
9
1
Others
5
8
Function switch
0
Valid DeviceNet MAC ID setting
7
Address switch
8
Duplicate MAC ID check failure
Change the address and re-power DNET scanner.
F1
No scan list is active in the module
No slave device in the scan list. Configure the scanner
and download it to the scanner.
F2
Low voltage is detected
Check if the power of the scanner and PLC MPU is
normal.
F3
Entering Test Mode
Switch IN1 from ON to OFF and re-power the scanner.
電氣規格
DeviceNet
環境規格
Bus-off detected
Invalid DeviceNet MAC ID setting
2
條通訊線、2 條電源線、1 條遮蔽線
500V DC
輪詢,位元選通,狀態改變/循環 顯性
64
12
799 (Delta Electronics Inc.)
工作電源:由 PLC 主機提供電源
網路電源
電壓規格:11 ~ 25V DC;電流規格:小於 50mA (25V DC)
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
2. Check if the baud rate is correct.
3. Re-power the scanner.
I/O
125 Kbps; 250 Kbps; 500 Kbps
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
0ºC ~ 55ºC(溫度)
、50 ~ 95%(濕度)、污染等級 2
操作/儲存環境 操作:
儲存:-40ºC ~ 70ºC(溫度)、5 ~ 95%(濕度)
耐震動/衝擊
國際標準規範 IEC1131-2、IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 (TEST Ea)
標準
F5
No network power
Make sure the cable is correctly connected and check if
the network power is normal.
F6
Internal error; Flash or Ram check error
If the error still exists after re-power, replace the scanner
with a new one.
F7
Internal error; GPIO check error
If the error still exists after re-power, replace the scanner
with a new one.
F8
Error in factory manufacturing
If the error still exists after re-power, replace the scanner
with a new one.
F9
Internal error; EEPROM access failure
If the error still exists after re-power, replace the scanner
with a new one.
E0
Make sure that the device parameter in scan list matches
Device key parameter does not match scan list
the desired key parameter, including vendor ID, product
table.
code, device type and version.
E1
Data size returned does not match scan list.
Re-configure scan list using correct data size.
Salve device in scan list does not exist.
The desired slave device does not exist in the network.
Add device to the network.
安裝
外觀
DV PDNE T
MS
NS
4
5
6
7
8
2
Function Switch Setting
可插拔式連接 (5.08mm)
CAN
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
雜訊免疫力
1. Check if the network cable is normal.
F4
250K bps
ON
OFF
500K bps
IN0
ON
Retain the previous I/O data when the connection is off.
OFF
Clear the previous I/O data when the connection is off.
Interface
Removable connector (5.08mm)
Transmission
method
CAN
Transmission cable
2-wire twisted shielded cable with 2-wire bus power cable and drain
Electrical isolation
500V DC
E2
E3
Module fails to transmit a message
Make sure that the connection is valid and check if the
baud rate is correct.
E4
Error detected in sequence of fragmented I/O
messages from device.
Fragmented I/O data is invalid from slave device.
Retain I/O data setting
Reserved
E5
Slave device returns error response when the
Check if the salve is normal.
scanner attempts to communicate with it.
Cable Length and Baud Rates
E6
Data size returned is bigger than expected.
The maximum cable length in a segment depends on the transmission speed. DeviceNet communicates
at speeds from 125K bps to 500K bps over distances from 100 to 500 meters.
Check slave device configuration and scan list
configuration.
E7
Device is checking MAC ID.
No correction is needed, or check if the network
connection is normal.
IN1
1
x10
6
3
ON
5
2
OFF
4
1
DeviceNet Connection
1
125K bps
0
OFF
0
OFF
0
x10
9
Baud Rate
9
DR0
8
DR1
7
Specifications
9
連接器
通訊
訊息類型
串列傳輸速度
產品代碼
產品類型
廠商 ID
--
F0
9
0…63
4
7
8
Digit Indicator
6
接頭
傳輸方式
傳輸電纜
電氣絕緣
How to correct
Node address of scanner, normal operation
7
5
Signal
3
1
Indication
功能規格
DeviceNet
2
PIN Definition Of DevicetNet Connection Port
Product Profile
Unit: mm
Hardware error and no network Go to your manufacturer or distributor for
power
problem-solving.
Code
8
尺寸單位:mm
How to correct
Make sure the scanner is powered.
0 ~ 63
-
Indication
Digit Indicator LED
STOP
Supports Group 2 server device and Group 2 only server device.
Supports DeviceNet Master mode and Slave mode.
Supports EDS file configure in ElinkConfigurator software.
Supports network establishing all kinds of IO connections: polled, bit-strobe, change of state and
cyclic.
Supports explicit connection via Predefined Master/Slave Connection Set. (explicit message)
Offers 380 bytes for I/O input data and 380 bytes for I/O output data.
-Refer to digit-indicator and check the scanner setup.
DVP28SV
Introduction
-
Configure the scan list and re-download it to the scanner.
No power
Installing DVPDNET-SL With PLC MPU
Warning
This Instruction Sheet only provides descriptions for electrical specifications, general specifications,
installation and wiring.
Make sure the scanner is powered.
NS & MS LED
in millimeter and [inch]
How to correct
6
3
MS
指示燈
軌固定扣
訊息顯示器
擴充機固定扣
位址設定開關
功能設定開關
DeviceNet 連接器
DR 1
DR 0
IN 1
IN 0
尺寸單位:mm 和 [inch]
有效的 DeviceNet 通訊位址
F5
4
5
6
7
5
3
2
9
0
1
F9
125K bps
ON
250K bps
ON
OFF
IN0
ON
E2
500K bps
保持 I/O 數據設定
當網站斷線時,保持之前的 I/O 數據
當網站斷線時,清除之前的 I/O 數據
保留
OFF
E3
E4
E5
通訊電纜長度以及通訊速率
E6
最大通訊距離和通訊速率有關. 通訊速率為 125K 時,最大通訊距離為 500m;通訊速率為 500K 時,最大
E7
注意事項
通訊距離為 125m。詳細內容情參照下表。
通訊速率 (bps)
電纜長度 (m)
LED
125K
500
250K
250
燈指示說明及故障排除
500K
100
掃描模組有三個 LED 指示燈和一個數字顯示器。 POWER LED 用來顯示 DVPDNET-SL 的
工作電源是否正常;NS LED 與 MS LED 用來顯示 DVPDNET-SL 的通訊連接狀態;數位顯示器用來顯示
DVPDNET-SL 掃描模組的節點位址、錯誤資訊以及從站的錯誤訊息。
DVPDNET-SL
DVPDNET
POWER
MS
NS
POWER
LED
燈滅
綠燈亮
NS
燈狀態
燈顯示說明
顯示說明
工作電源不正常
工作電源正常
燈顯示說明
LED
燈狀態
顯示說明
無電源
沒有配置掃描模組
輸入/輸出資料正常
掃描列表中的從站工作不正常
紅燈亮
掃描模組內部錯誤
處理方法
檢查 DVPDNET-SL 電源並確認連接正常
配置掃描列表,配置完成後下載至掃描模組
無需處理
參考數位顯示器資訊,確認掃描列表內的從站資訊與實際連
接的從站一致
1.檢查配置是否正確
2.重新上電,如果錯誤依然存在,請退回工廠進行修復
尺寸单位:mm 和 [inch]
在 PLC 主机上安装 DVPDNET-SL 扫描模块
2
3
4
5
6
7
接头
传输方式
传输电缆
电气绝缘
DVP28SV
尺寸单位:mm
8
9
模块名称
扩充机接口
指示灯
导轨安装滑块
数码显示器
扩充机固定卡口
地址设定开关
功能设定开关
DeviceNet 连接器接口
Power, MS, NS
2
连接器的引脚定义
信号
1
V-
2
CAN_L
3
Drain
4
CAN_H
5
V+
地址开关设置
颜色
黑色
蓝色
F0
0V DC
5
4
3
2
1
Signal-
屏蔽线
-
白色
红色
Signal+
0 … 63
有效的 DeviceNet 通讯地址
无效的 DeviceNet 通讯地址
OFF
125K bps
OFF
ON
250K bps
可插拔式连接 (5.08mm)
ON
OFF
CAN
IN0
ON
IN1
500V DC
6
5
6
通讯速率
DR0
OFF
OFF
5
F6
F7
F8
F9
E0
DR1
条通讯线、2 条电源线、1 条屏蔽线
F3
F5
4
功能开关设置
F2
F4
4
F1
24V DC
说明
500K bps
保持 I/O 数据设定
当从站断线时,保持之前的 I/O 数据
当从站断线时,清除之前的 I/O 数据
保留
通讯电缆长度以及通讯速率
最大通讯距离和通讯速率有关. 通讯速率为 125K 时,最大通讯距离为 500m;通讯速率为 500K 时,最大
通讯距离为 125m。详细内容情参照下表。
MS
数码显示器显示说明
代码
0 ~ 63
说明
开关设置
其它
灯状态
显示说明
灯
灯灭 无电源
绿灯亮 重复地址检测未完成
红灯亮 绿灯亮 重复地址检测失败或者网
络总线中断 (BUS-OFF)
红灯亮 红灯闪烁 无网络电源
红灯亮 红灯亮 硬件错误
灯
灯灭
灯灭
1
引脚
灯和 MS 灯组合显示说明
LED
连接器
2
扫描模块内部错误
NS
DevicetNet
灯显示说明
红灯亮
NS
E1
E2
E3
E4
E5
E6
E7
处理方法
检查 DVPDNET-SL 工作电源是否正常
无需处理
处理方法
.检查 DVPDNET-SL 电源并确认连接正常
.确认网络上至少有一个节点可以正常通讯
无需处理或者参考数码显示器消除错误
无需处理
参考数码显示器代码消除错误
网络故障,节点地址重复、无网络 12.确认总线上所有的节点地址是唯一的
.检查网络安装是否正常
电源或者网络总线中断
3.检查 RTU-DNET 的节点地址是否为有效站号
(BUS-OFF)
4.检查网络电源是否正常
显示说明
无电源
没有配置扫描模块
输入/输出数据正常
扫描列表中的从站工作不正常
2
DVPDNET
显示说明
无电源或者重复地址检测未完成
没有与 DeviceNet 网络连接
在线并与 DeviceNet 网络连接正
常
通讯错误
LED 灯状态
灯灭
绿灯闪烁
绿灯亮
红灯闪烁
RUN
1
功能規格
0
x10
STOP
支持第二组服务器 (Group 2 server) 从站和仅限第二组服务器 (Group 2 only server) 从站。
支持 DeviceNet 主站模式和从站模式。
在 ElinkConfigurator 组态软件中支持 EDS 文件配置。
支持从站建立各种 I/O 连接:轮询(Polled)、位选通(Bit-Strobe)、状态改变(Change of State)、周期循环
(Cyclic)。
在预定义的主/从连接组中支持显性连接(显性报文)。
提供 380 字节的空间作为 I/O 输入数据区,同时也提供 380 字节空间作为 I/O 输出数据区。
DeviceNet
1
x10
6
DR 1
DR 0
IN 1
IN 0
產品簡介
产品外观
MS
6
8
處理方法
1.檢查 DVPDNET-SL 電源並確認連接正常
2.確認網路上至少有一個節點可以正常通訊
無需處理或者參考數位顯示器消除錯誤
無需處理
參考數位顯示器代碼消除錯誤
網路故障,節點位址重複、無網路 12.確認匯流排上所有的節點位址是唯一的
.檢查網路安裝是否正常
電源或者網路匯流排中斷
3.檢查 RTU-DNET 的節點位址是否為有效站號
(BUS-OFF)
4.檢查網路電源是否正常
LED 燈狀態
燈滅
綠燈閃爍
綠燈亮
紅燈閃爍
-
顯示說明
無電源或者重複地址檢測未完成
沒有與 DeviceNet 網路連接
線上並與 DeviceNet 網路連接正
常
通訊錯誤
燈顯示說明
-
5
7
MS
-
5
8
紅燈亮
處理方法
檢查 DVPDNET-SL 工作電源是否正常
無需處理
4
7
燈滅
綠燈閃爍
綠燈亮
紅燈閃爍
-
灯状态
灯灭
绿灯闪烁
绿灯亮
红灯闪烁
红灯亮
4
显示说明
工作电源不正常
工作电源正常
灯显示说明
NS
功能特色
-
灯状态
灯显示说明
LED
MS
此安装手册只提供电气规格、一般规格、安装及配线等。
配线时请务必关闭电源,请勿在上电时触摸任何端子。
本机为开放型 (OPEN TYPE) 机壳,因此使用者使用本机时,必须将之安装于具防尘、防潮及免于电
击/冲击意外之外壳配线箱内。另必须具备保护措施(如:特殊之工具或钥匙才可打开),防止非维
护人员操作或意外冲击本体,造成危险及损坏。
简体中文
燈指示說明及故障排除
DV PDNET
8
OFF
OFF
安裝
外型
7
OFF
E1
8
DR0
7
E0
通訊速率
DR1
IN1
F8
8
功能開關設置
F7
6
7
無效的 DeviceNet 通訊位址
F6
8
4
3
0 … 63
2
F4
說明
NS
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
0ºC ~ 55ºC(温度)
、50 ~ 95%(湿度)、污染等级 2
操作/储存环境 操作:
储存:-40ºC ~ 70ºC(温度)、5 ~ 95%(湿度)
耐震动/冲击
国际标准 IEC1131-2、IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 (TEST Ea)
认证
3
24V DC
開關設置
其他
F3
模拟 通讯
2
V+
位址開關設置
Signal+
杂讯免疫力
3
5
白色
紅色
F2
LED
灯灭
绿灯亮
电源线
数字
电源线: 数字
EFT (IEC 61131-2, IEC 61000-4-4):
: 2KV,
I/O: 1KV,
&
I/O: 1KV
Damped-Oscillatory Wave:
1KV,
I/O: 1KV
2
CAN_H
F1
100
NS
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
3
4
遮蔽線
-
3
Drain
5
4
3
2
1
Signal-
2
3
F0
0V DC
處理方法
無需處理
.確認掃描模組的節點位址是唯一的
2.將掃描模組重新上電
配置掃描列表,配置完成後下載至掃描模組
檢查掃描模組以及 PLC 主機的工作電源是否正常
將功能開關的 IN1 切換為 OFF 狀態,並對掃描模組重新上電
1.檢查網路電纜是否正常
2.確認網路上的節點設備串列傳輸速率設置一致
BUS-OFF
3.將掃描模組重新上電
1.檢查網路電纜是否正常
沒有檢測到網路電源
2.確認網路電源正常
內部錯誤,內部記憶體檢測出錯
將掃描模組重新上電,如果錯誤依然存在,退回工廠進行修復
內部錯誤,GPIO 檢測出錯
將掃描模組重新上電,如果錯誤依然存在,退回工廠進行修復
內部錯誤,工廠製造流程出錯
將掃描模組重新上電,如果錯誤依然存在,退回工廠進行修復
內部錯誤,配置資料記憶體訪問出錯
將掃描模組重新上電,如果錯誤依然存在,退回工廠進行修復
從站返回的識別參數與配置資料不一致 確認掃描列表裏配置的從站位址與網路上的從站位址一致,並
確認配置的從站與實際連接在網路上的從站是同一台設備
從站返回的 I/O 資料長度與掃描列表中配 重新配置從站的 I/O 資料長度,並下載至掃描模組,運行 PLC
置的不一致
主機
掃描列表中配置的從站不存在
檢查並確認掃描列表中配置的從站與網路連接正常
1.檢查掃描模組與網路連接是否正常
2.確認掃描模組串列傳輸速率與網路上其他節點的串列傳輸
掃描模組發送資料失敗
速率設置一致
從站傳送的 I/O 分段資料序列有錯誤
檢查從站是否工作正常
掃描模組于從站建立連接時,從站返回錯 檢查從站是否工作正常
誤資訊
從站返回的 I/O 資料長度超出掃描列表中 確認從站的 I/O 資料長度與掃描列表中配置的 I/O 資料長度一
配置的長度
致
掃描模組正在進行重複位址檢測
無需處理或者確認掃描模組與網路連接正常
1
500K
250
PO WER
MS
POWER
2
CAN_L
顯示說明
掃描模組的節點位址(正常工作時)
重複地址檢測失敗
掃描列表內沒有配置從站
工作電源電壓過低
掃描模組進入測試模式
250K
500
DVPDNET
1
V-
2
敘述
工作电源:由 PLC 主机提供电源
网络电源
电压规格:11 ~ 25V DC;电流规格:小于 50mA (25V DC)
环境规格
125K
扫描模块有三个 LED 指示灯和一个数字显示器。 POWER LED 用来显示 DVPDNET-SL 的
工作电源是否正常;NS LED 与 MS LED 用来显示 DVPDNET-SL 的通讯连接状态;数字显示器用来显示
DVPDNET-SL 扫描模块的节点地址、错误信息以及从站的错误讯息。
1
1
代碼
0 ~ 63
顏色
黑色
藍色
DVPDNET-SL
799 (Delta Electronics Inc.)
电气规格
DeviceNet
LED
0
信號
1
連接器的腳位定義
0
腳位
9
DevicetNet
數位顯示器顯示說明
2
64
12
0
RUN
STOP
125 Kbps; 250 Kbps; 500 Kbps
9
1
通讯速率 (bps)
电缆长度 (m)
轮询,位选通,状态改变/循环 显性
I/O
9
DVP28SV
通讯
讯息类型
传输速度
产品代码
产品类型
厂商 ID
1
DVPDNET
處理方法
檢查 DVPDNET-SL 電源是否正常
確認網路上至少有一個節點串列傳輸速率與掃描模組一致,
並且與掃描模組通訊正常
1.確認掃描模組的節點位址是唯一的
2.將掃描模組重新上電
1.檢查網路電纜連接是否正確
2.檢查網路電源是否正常
退回工廠進行修復
1
顯示說明
燈
燈滅 無電源
綠燈亮 重複地址檢測未完成
紅燈亮 綠燈亮 重複位址檢測失敗或者網
路匯流排中斷 (BUS-OFF)
紅燈亮 紅燈閃爍 無網路電源
紅燈亮 紅燈亮 硬體錯誤
MS
0
燈狀態
燈
燈滅
燈滅
0
燈和 MS 燈組合顯示說明
LED
NS
9
NS
2
9
在 PLC 主機上安裝 DVPDNET-SL 掃描模組
显示说明
扫描模块的节点地址(正常工作时)
重复地址检测失败
扫描列表内没有配置从站
工作电源电压过低
扫描模块进入测试模式
1
2
处理方法
检查 DVPDNET-SL 电源并确认连接正常
配置扫描列表,配置完成后下载至扫描模块
无需处理
参考数码显示器信息,确认扫描列表内的从站信息与实际连
接的从站一致
1.检查配置是否正确
2.重新上电,如果错误依然存在,请退回工厂进行修复
处理方法
检查 DVPDNET-SL 电源是否正常
确认网络上至少有一个节点波特率与扫描模块一致,并且与
扫描模块通讯正常
1.确认扫描模块的节点地址是唯一的
2.将扫描模块重新上电
1.检查网络电缆连接是否正确
2.检查网络电源是否正常
退回工厂进行修复
处理方法
无需处理
.确认扫描模块的节点地址是唯一的
2.将扫描模块重新上电
配置扫描列表,配置完成后下载至扫描模块
检查扫描模块以及 PLC 主机的工作电源是否正常
将功能开关的 IN1 切换为 OFF 状态,并对扫描模块重新上电
1.检查网络电缆是否正常
BUS-OFF
2.确认网络上的节点设备波特率设置一致
3.将扫描模块重新上电
1.检查网络电缆是否正常
没有检测到网络电源
2.确认网络电源正常
内部错误,内部存储器检测出错
将扫描模块重新上电,如果错误依然存在,退回工厂进行修复
内部错误,GPIO 检测出错
将扫描模块重新上电,如果错误依然存在,退回工厂进行修复
内部错误,工厂制造流程出错
将扫描模块重新上电,如果错误依然存在,退回工厂进行修复
内部错误,配置数据存储器访问出错
将扫描模块重新上电,如果错误依然存在,退回工厂进行修复
从站返回的识别参数与配置数据不一致 确认扫描列表里配置的从站地址与网络上的从站地址一致,并
确认配置的从站与实际连接在网络上的从站是同一台设备
从站返回的 I/O 数据长度与扫描列表中配 重新配置从站的 I/O 数据长度,并下载至扫描模块,运行 PLC
置的不一致
主机
扫描列表中配置的从站不存在
检查并确认扫描列表中配置的从站与网络连接正常
1.检查扫描模块与网络连接是否正常
扫描模块发送数据失败
2.确认扫描模块波特率与网络上其它节点的波特率设置一致
从站传送的 I/O 分段数据序列有错误
检查从站是否工作正常
扫描模块于从站建立连接时,从站返回错误 检查从站是否工作正常
信息
从站返回的 I/O 数据长度超出扫描列表中 确认从站的 I/O 数据长度与扫描列表中配置的 I/O 数据长度一致
配置的长度
扫描模块正在进行重复地址检测
无需处理或者确认扫描模块与网络连接正常
1