Pulsar series
5/7/11 kVA
Eaton EX RT UPS
High reliability and availability
• Internal static bypass
• Input/output (I/O) box with manual bypass
Industrial grade performance
• Large input voltage range without using battery power
• 40–70 Hz input frequency range
•O
perating temperature: 0°–40°C permanently, 0°–45°C for
eight hours
• Standalone solution with modular design for industrial needs
Optimized solution for infrastructure network
integration
Versatile form factor
• Rack kit for an optimized mounting with 3U height per module
• Communications slot compatible with multiple communication
card protocols
• Software application packages are fully customized
• Long backup time availability—up to 8 hours and UL924
listed solutions
The Eaton® EX RT UPS is a UPS designed for sensitive highdensity server environments and harsh industrial applications.
Specifically engineered to meet demanding customer applications
in IT systems, measuring instruments, PLCs and industrial PC
markets, the EX RT is fully compatible with genset redundancy
requirements in most instances. The manual bypass, hot-swap
I/O box and intuitive LCD control panel are just a few of the many
differentiating features that make the EX RT the ideal product for
the 5–11 kVA power range.
Services
• Warranty: Two years, parts and labor (US and Canada)
•O
n-site services available for startup, preventive
maintenance and more
• Extended warranties available
The solution for high-density rack server enclosures
and industrial environments
High availability
• Hot-swap battery and UPS modules prevent interruptions
• Internal and maintenance bypass are standard to achieve the
highest level of availability
• Large input voltage window without using battery power
• Automatic battery test and protection against deep discharges
Clear coat battery packaging with
thru holes for diagnostic and testing
Hot-swappable I/O Box
Compatibility with any environment
Large choice of options to meet customer needs
Data room
•U
niversal 3U transformer module: system earth arrangement,
galvanic isolation for upstream and downstream UPS installation
•V
ersatile rack or tower in 6U, including the power and battery
modules
•M
anagement through various protocols such as HTTP/SNMP/
XML/Telnet
• Integration with popular network management systems like HP
Openview, IBM Tivoli, CA Unicenter
• Integrated NEMA receptacles included with transformer
configuration
• Optional rackmount PDU with NEMA or IEC sockets to facilitate
power distribution within the enclosure
Ergonomics
• Multilingual scrolling LCD front bezel control panel
•B
attery integration system for optimized footprint: up to eight
modules stacked on a caster kit—one UPS module, six EXB
battery modules and one transformer module
• 3U CLA module for backup times up to eight hours
User-friendly installation and operation
• Load metering in kW/kVA is permanently displayed on the LCD
•O
perating mode, battery capacity in percentage, voltage
measurement, normal AC, bypass (separate AC) input/output,
serial number and power rating identification are available by
scrolling up or down
• Event logs and fault diagnostics facilitate maintenance and repair
•S
imple setup on network or industrial mode permits system
shutdown or service continuity in case of overload or short circuit
• Event log for easy fault detection
Full customization through a configuration panel in Personal
Solution-Pac
Battery backup
•L
ow battery, battery test frequency, disable deep discharge
protection
• AC bypass input tolerance settings for: frequency, voltage-AC
bypass transfer condition
• Battery modules up to eight hours with the CLA* charger module
•S
pace saving battery connector cables and extra long battery
cables for separate battery racks
•B
attery detection system automatically configures battery
modules and UPS
•U
L 924 emergency lighting and equipment battery cabinets
available (90-minute runtime)
*CLA for external battery cabinet only
High-end ergonomics
• CLA, hot standby, ECO mode, frequency converter setup
EX RT with Battery Integration Kit
Load
Protected
Battery
Mode
Bypass
Mode
• Versatile 6U rack or tower design
• Multilingual LCD
• Two stands improve stability of the tower
•U
p to five extra battery modules to extend runtime up to two
hours
• Voltage-free contacts are included for remote status monitoring
Fault
Alarm
LCD 32
Characters
Industry and infrastructure
•B
attery integration system optimizes the footprint of extended
runtime solutions with automatic battery module detection
• Genset compatibility
• Integration with building management systems (Jbus), six
voltage-free contacts for remote status monitoring
•T
emperature and humidity supervision with an environment
sensor triggers an orderly shutdown
2
EATON CORPORATION
Eaton EX RT UPS
Front panel LCD control panel
LCD, rotating (tower/rack format),
multilingual, backlit
Communications software and connectivity
Eaton customer service and support
•P
ower management suite (included) comes with network-based
shutdown software (Windows, Linux, MacOS, VMware ESX,
Microsoft Hyper-V) and local or remote supervision up to five
nodes
•F
lex and PowerTrust on-site services from factory-trained
personnel for startup, preventive maintenance and more
•N
etwork Management Card (NMC) connects the UPS to an
Ethernet 10/100 network, raising SNMP or XML alarms and
supervising the UPS using a simple browser interface
•E
xtended warranty contracts available to provide up to five
years of warranty coverage
•U
PSgrade™ program for substitution of an old UPS (vendor
neutral), includes the EX RT 5 kVA model
•N
MC environment sensor monitors the temperature, humidity
and two relay contacts via SNMP or HTML
•E
nterprise Power Manager supervisor provides comprehensive
management of multiple UPSs and PDUs using a Windows PC
(vendor neutral)
•N
MS integration kits include HP OpenView, IBM Tivoli Netview,
CA Unicenter, etc.
•S
tatus information card monitors for voltage-free contacts and
Remote Power Off (RPO) function
Eaton NetWatch Client 5.0 has tested compatible
with Cisco Unified Communications Manager 4.3.
Go to www.eaton.com/PQ/cisco for disclaimer.
•N
etWatch 5.0 software automatically shuts down UPS-protected
devices, such as servers
EX RT Back Panel (Transformer Module/Power Module/Battery Module)
3
9
4
2
6
5
1
1. L6-30R (Load 1)
2. Load 1 breaker 30A
3. (4) 5-20R 120V (load 2)
4. Load 2 Mini-breaker 15A
5. L6-30R (Load 3)
6. Load 3 breaker 30A
7. (4) 5-20R 120V (load 4)
8. Load 4 Mini breaker 15A
9. Ouput breaker
8
7
EX RT Back Panel (Battery Module /Power Module)
1. Slot for communication cards
2. Output contracts communication port
3. Remote Emergency Power Off
communication port (REPO)
4. Connectors for automatic detection
of battery modules
5. RS232 communication port
6. Battery module connectors
to the UPS or the battery modules)
7. Manual bypass switch
8. Output terminal block
9. Normal AC source switch
10 Normal AC source terminal block
11 Bypass AC source terminal block
12 Battery circuit-breaker
EX RT BATTERY BACKUP TIMES (in minutes)*
Load
Internal
(VA/Watts) Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs +5 EBMs
EX RT 5000
500/400
170
358
540
740
892
1220
1000/800
91
170
260
355
505
540
1500/1200
49
110
170
240
290
355
2000/1600
33
84
120
170
235
260
2500/2000
25
60
100
122
170
225
3000/2400
21
46
75
110
135
170
3500/2800
16
39
64
95
119
140
4000/3200
13
31
57
84
105
120
4500/3600
11
27
52
68
92
110
5000/4000
9
25
45
60
84
100
EX RT 7000
700/490
121
266
447
578
756
889
1400/890
57
125
203
244
364
453
2100/1470
37
80
124
185
245
287
2800/1960
28
61
101
128
169
232
3500/2450
21
53
83
108
132
164
4200/2940
15
37
66
90
110
133
4900/3430
12
30
55
75
98
118
5600/3920
10
24
45
61
77
102
6300/4410
8
22
38
53
69
86
7000/4900
7
20
32
45
57
72
EX RT 11000
1100/800
90
191
293
392
525
637
2200/1600
40
93
143
199
261
312
3300/2400
25
61
96
135
172
201
4400/3200
18
43
71
99
120
142
5500/4000
14
30
53
84
102
113
6600/4800
11
24
44
60
86
102
7700/5600
9
20
34
51
67
87
8800/6400
7
17
27
43
56
68
9900/7200
6
15
24
35
48
60
11000/8000
5
14
22
30
42
53
* Backup times are approximate and may vary with equipment, configuration, battery age,
temperature, etc.
www.eaton.com/powerquality 1.800.356.5794
3
EX RT MODELS
Catalog
Number
Style
Number
Form
Factor
Rating
(VA/Watts)
Output
Voltage1
Input
Connection
Output
Receptacle
Dimensions
(H x W xD, inches)
Weight
(lb)
EXRTG5000-XL6UMS
86505
Rack/Tower
5000/4000
HV
Hardwired
Hardwired
10.32 (6U) x 17.49 x 26.25
192.0
EXRTG7000-XL6UMS
86507
Rack/Tower
7000/4900
HV
Hardwired
Hardwired
10.32 (6U) x 17.49 x 26.25
192.0
EXRTG11000-XL6UMS
86511
Rack/Tower
11000/8000
HV
Hardwired
Hardwired
10.32 (6U) x 17.49 x 26.25
211.0
EXRTL5000-XL9UMS
86506
Rack/Tower
5000/4000
LV
Hardwired
Hardwired + (2) NEMA
L6-30R + (8) NEMA 5-20R
15.48 (9U) x 17.49 x 26.25
365.0
EXRTL7000-XL9UMS
86508
Rack/Tower
7000/4900
LV
Hardwired
Hardwired + (2) NEMA
L6-30R + (8) NEMA 5-20R
15.48 (9U) x 17.49 x 26.25
365.0
EXRTL11000-XL9UMS
86512
Rack/Tower
11000/8000
LV
Hardwired
Hardwired + (2) NEMA
L6-30R + (8) NEMA 5-20R
15.48 (9U) x 17.49 x 26.25
384.0
1. HV = High-voltage (208, 240, etc.) and LV = Low-voltage (120V), also provides 208/240V
Technical specifications1
Topology
Online with automatic bypass
Standards and Certification
Performances
Performance and Safety
IEC 62040-1/CEI 60950/UL 1778 and CSA 22.2 Standards
Nominal Input Voltage
120–280V at <70% rated output
EMC
IEC 62040-2; EN 50091-2; FCC class A
Input Voltage Range
156–280V at 100% rated output
Warranty
Two years, parts and labor (US and Canada)
Input Frequency Range 40–70 Hz, frequency converter as a standard
Output Voltage/Frequency 200/2082/220/230/240/250V; 120V output voltage
available with transformer; 50/60 Hz autoselect
1. Due to continuing product improvement programs, specifications are subject to change without notice
2. Default voltage
3. Configurable to daily or monthly
Overall Efficiency (Online
Mode–ECO Mode)/Harmonic
Current Distortion
90–97%/<5%
Crest Factor/Overload Capacity 3:1 / 2 min if 102%<overload<110%, 1 min if
110%<overload<125%, 30 sec if 125%<over
load<150%, 500 msec if overload >150%
Battery Test Operating Temperature
EX RT INDIVIDUAL MODULES AND OPTIONS
Part Number and Description
5 kVA/4 kW
7 kVA/4.9 kW 11 kVA/8 kW
EX RT Power and Battery Modules
Power Module with rails
86056
86076
86116
Battery Module with rails
86079
86079
86119
Weekly without load interruption3
UL924 Battery Module
86218
86219
86220
45°C for 8 hr, 0°–40°C continuous
EX RT Transformer
86311
86311
Connection
7 kVA Transformer with rails
11 kVA Transformer with rails
EXRTL9140XFMR3U
Block Power Module
Input/Output Terminal Block
Maximum Wire Size (Solid or Stranded Wire)
Hardwired
5/7 kVA: 10 mm/6 AWG
11 kVA: 13 mm/4 AWG
EX RT CLA Charger Module
86004
86004
86004
Step-Down Transformer
120/208/240 Vac output
Battery Integration Kit with Casters
Output Configuration
Terminal block, plus (2) NEMA L6-30R (208V), (8)
NEMA 5-20R; optional PDUs for additional NEMA
or IEC receptacles
Stack kit with inter-module fastening, 86005
swivel wheels, brakes, leveling feet
86005
86005
CLA Charger with rails
Communication
Port Type
(6) voltage-free dry contacts DB-9 rated at 2A
48V DC, (1) RS 232, (1) RJ11 for RPO
(Remote Power Off)
Slot (1) slot for Mini-Slot communication card
[Network Management Card (SNMP/Web), NMC
ModBus/JBus, MC Contacts/Serial]
UNITED STATES
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
www.eaton.com/powerquality
Canada
Ontario: 416.798.0112
LATIN AMERICA
Argentina: 54.11.4124.4000
Brazil: 55.11.3616.8500
Caribbean: 1.949.452.9610
Mexico & Central America:
52.55.9000.5252
South Cone: 54.11.4343.6323
Europe/Middle East/Africa
Denmark: 45.3686.7910
Finland: 358.94.52.661
France: 33.1.6012.7400
Germany: 49.0.7841.604.0
Italy: 39.02.66.04.05.40
Norway: 47.23.03.65.50
Portugal: 55.11.3616.8500
Sweden: 46.8.598.940.00
United Kingdom: 44.1753.608.700
Asia Pacific
Australia/NZ: 61.2.9693.9366
China: 86.21.6361.5599
HK/Korea/Taiwan: 852.2745.6682
India: 91.11.4223.2300
Singapore/SEA: 65.6829.8888
Eaton, UPSgrade and Pulsar are trade
names, trademarks and/or service marks
of Eaton Corporation or its subsidiaries
and affiliates.
All other trademarks are the property
of their respective owners.
©2010 Eaton Corporation
All Rights Reserved
Printed in USA
EXRT01FXA
March 2010