AWH-1808ER/front 6/13/98 11:00 AM Page 1
ROOM AIR CONDITIONER
AWH-1808ER
SERVICE Manual
AIR CONDITIONER CONTENTS
1. Precautions
2. Product Specifications
3. Installation and Operating
Instructions
4. Disassembly and Reassembly
5. Troubleshooting
6. Exploded Views and Parts List
7. Block Diagram
8. PCB Diagram
9. Wiring Diagram
10. Schematic Diagrams
AWH-1808ER/front 6/13/98 11:00 AM Page 2
ELECTRONICS
©
Samsung Electronics Co., Ltd. NOV. 1997.
Printed in Korea.
Code No. DB81-10131A
AWH-1808ER-1 6/13/98 10:12 AM Page 1
1. Precautions
1. Warning: Prior to repair, disconnect the power cord from the circuit breaker.
2. Use proper parts: Use only exact replacement parts. (Also, we recommend replacing parts rather than repairing them.)
3. Use the proper tools: Use the proper tools and test equipment, and know how to use equipment may cause problems laterintermittent contact, for example.
4. Power Cord: Prior to repair, check the power cord and replace it if necessary.
5. Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in malfunction or fire.
6. After completing repairs and reassembly, check the insulation resistance, Procedure:
Prior to applying power, measure the resistance between the power cord and the ground terminal. The resistance must be greater than 30 megohms.
7. Make sure that the grounds are adequate.
8. Make sure that the installation conditions are satisfactory. Relocate the unit if necessary.
9. Keep children away from the unit while it is being repaired.
10. Be sure to clean the unit and its surrounding area.
Fig. 1-1 Avoid Dangerous Contact
Fig. 1-2 No Tapping and No Extension Cords
Fig. 1-3 No Kids Nearby!
Samsung Electronics
Fig. 1-4 Clean the Unit
1-1
AWH-1808ER-1 6/13/98 10:12 AM Page 3
2. Product Specifications
2-1 Table
Item
Type
Dimensions:
(Width X Height X Depth)
Packing Size
(Width X Height X Depth)
Voltage:
Phase
Frequency
Operating Current
Power Consumption
Refrigerant Type
Refrigerant Charge
Cooling Capacity
EER
Net Weight
Condenser
Condenser Fan
Evaporator
Evaporator Fan
Fan Motor
Compressor(Rotary)
Overload Protect
Compressor Capacitor
Fan Motor Capacitor
Fan Speed Control
Thermo Control
OFF Timer
Unit of Measure
mm mm
BTU/h
BTU/h.W
kg
Row
Type
Row
Type
Volt
-
Hz
A
W
FREON g
W
Model
-
µF/ VAC
µF/ VAC
-
hr
AWH-1808ER(Cooling/Heating)
Window
660 X 420 X 695
737 X 476 X 794
220 - 240
Single
50
9.0 / 7.7
2,050 / 1,730
R-22
860
17,000 / 16,500
8.3 / 9.5
59
2 X 16
Propeller Fan
3 X 14
Blower
IC-13435SWJ5A
48B180JV1E7
MRA12016-12007
40 / 450
(DUAL)
6 / 450
Fan speed switch (High & Low)
Thermistor
24
Remarks
Samsung Electronics 2-1
AWH-1808ER-1 6/13/98 10:12 AM Page 4
2-2 Dimensions
2-2-1 Main Unit
Unit : mm
Front view
660
Side view
2-2-2 Remote Control
Fan speed adjustment buttons
Temperature adjustment buttons
ON/OFF Buttons
Timer setting buttons
Mode selection buttons
(COOL, HEAT, FAN)
Air flow swing button
2-2 Samsung Electronics
AWH-1808ER-1 6/13/98 10:12 AM Page 5
3. Installation and Operating Instructions
3-1 Installation
* When selecting the area for installing the unit, be sure to obtain approval of the customer.
1. Make sure that you install the unit in an area that provides good ventilation.
The air conditioner must not be blocked by any obstacle affecting the air flow near the air inlet and air outlet.
2. Make sure that you install the unit in an area which can endure the weight and vibration of the unit.
6. Make sure that you install the unit in an area which provides easy drainage for condensed water.
7. Make sure that you install the unit in an area not exposed to rain or direct sunlight.
(Install a separate sunblind if exposed to direct sunlight.)
3. Make sure that you install the unit away from heat or vapor.
8. Do not install the unit in an area subjected to noise or vibration amplification which may affect your neighbor.
(Fix the unit firmly if mounted in a high place.)
4. Make sure that you install the unit in an area where the cooled air can be evenly spread in a room.
5. Make sure that you install the unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances.
(obtain a clearance of at least one meter)
Caution:
Do not use the air conditioner in such areas as a greasy area(including machine oil), saline area(sea side), or sulphuric area(hot spring). When using the air conditioner in these areas, special maintenance is required. Contact your local dealer or our service center for advice.
Samsung Electronics 3-1
AWH-1808ER-1 6/13/98 10:12 AM Page 6
3-2 Function Description
Remote control sensor
Air swing button
Deice indicator
Operating mode indicators
(HEAT, FAN, COOL)
Mode selection button
ON/OFF button
Power indicator
3-2-1 Cooling operation mode
The compressor is turned on and off according to the ambient temperature and set temperature.
1. Compressor on and off control
• Compressor on and off control according to the ambient temperature.
*
*
The compressor is turned off when "ambient temperature = set temperature -1˚C"
The compressor is turned on when "ambient temperature = set temperature +1˚C"
2. Default value after power reset ➔ set temperature = 24˚C
FAN SPEED = HIGH
3. Set temperature indicating (setting) range : 1˚C interval from 18˚C to 30˚C.
3-2-2 Heating operation mode
The compressor is turned on and off according to the ambient temperature and set temperature.
1. Compressor on and off control.
• Compressor on and off control according to the ambient temperature.
* The compressor is turned off when "ambient temperature = set temperature +1˚C"
* The compressor is turned on when "ambient temperature = set temperature -1˚C"
2. Default value after power reset ➔ set temperature = 24˚C
FAN SPEED = HIGH
3. Set temperature indicating (setting) range : 1˚C interval from 16˚C to 30˚C.
3-2-3 Fan operation mode
1. If "Fan operation mode" signal is received from remocon or panel.
➔ the compressor is immediately turned off and only fan motor is operated at set blowing speed.
➔ it changes such as "HIGH ➔ LOW ➔ HIGH"( if Fan speed is selected).
2. The initial FAN speed is set to "HIGH".
3. The set temperature can not be indicated and set.
Temperature/Timer settings
Temperature indicator
Timer indicator
Temperature adjusment button
Timer setting button
Fan speed indicators
Fan speed adjust button
3-2 Samsung Electronics
AWH-1808ER-1 6/13/98 10:12 AM Page 7
3-2-4 LED lamp and LED display indication in case of error detection
ERROR OPERADTION
ROOM THERMISTOR
(OPEN OR SHORT)
INDOOR PIPE THERMISTOR
(OPEN OR SHORT)
OUTDOOR PIPE THERMISTOR
(OPEN OR SHORT)
Lamp
COOL
LED LAMP DISPLAY
HEAT blinking at every second (on for 0.5s and off for 0.5s)
LED lamp off
FAN
7-SEG
LED DISPLAY
E1 displayed
E5 displayed
E6 displayed
1. Set operation in case of error occurrence.
• Malfunction of each temperature sensor (open, short)
- Error mode display, warning sound.
- The operation status is off.
2. The "outdoor pipe thermistor" error mode carry out checking only during heating operation and do nor carry out checking during and "FAN" operation.
Samsung Electronics 3-3
AWH-1808ER-1 6/13/98 10:12 AM Page 8
3-2-5 Panel key operation
Key name
Key discription
ON/OFF
Mode
Fan speed
Temp.
Air swing
Timer
Key operational function
Operation start and stop
* First ON = operation start, second ON = operation stop
* Continuous operation is not available.
Operation mode change (in case of model option heat pump)
* at every ON
- Selected as "COOL –> HEAT –> FAN". (Default=COOL)
* If operation is OFF, it is considered as an invalid key.
* Continuous operation is not available.
Indoor fan speed setting.
* At every ON -> selected as "HIGH -> LOW -> HIGH".
* If operation is OFF, it is considered as an invalid key.
* Continuous operation is not available.
Currently displayed set temperature circulation (in case of option -> ˚C)
* At every pressing, the set temperature is changed by 1˚C (cooling operation)
(24˚C -> 25˚C -> 26˚C -> 27˚C ---> 30˚C -> 18˚C -> 19˚C -> 20˚C ---> 24˚C).
* At every pressing, the set temperature is changed by 1˚C (heating operation)
(24˚C -> 25˚C -> 26˚C -> 27˚C ---> 30˚C -> 16˚C -> 17˚C -> 18˚C ---> 24˚C).
* Single and continuous operation is available.
* In case of the set temperature of 30˚C, when the "increase" key is pressed by remocon, temperature does not increase any more and waring, sound is generated.(cooling, heating operation) --> The panel key is circulated continuously.
* If operation is OFF, it is considered as an invalid key.
* In case of fan speed operation, it is considered as an invalid key.
Currently displayed set temperature circulation (in case of option --> ˚F)
* At every pressing, the set temperature is changed by 1˚F (cooling operation)
(75˚F -> 76˚F -> 77˚F ---> 86˚F -> 64˚F -> 65˚F -> 66˚F -> 67˚F ---> 75˚F).
* At every pressing, the set temperature is changed by 1˚F (heating operation)
(75˚F -> 76˚F -> 77˚F ---> 86˚F -> 61˚F -> 62˚F -> 63˚F -> 64˚F---> 75˚F).
* Single and continuous operation is available.
* In case of the set temperature of 86˚F, when the "increase" key is pressed by remocon, temperature does not increase any more and warning, sound is generated.(cooling, heating operation) --> The panel key is circulated continuously.
* If operation is OFF or fan speed, it is considered as an invalid key.
Left and right swing motor operation and stop.
* Once ON = Left and right swing motor operation, Another ON = Left and right swing motor stop.
* In case of cool blowing inhibition, it is considered as an invalid key.
(only in fan motor OFF range)
* In case of defrosting operation, it is considered as an invalid key.
(only in fan motor OFF range)
* Continuous operation is not available.
* In case of operation stop, when the fan motor is turned off it is considered as an invalid key.
* In case of deicing operation, the left and right swing motor does not operate.
(it operates when the fan motor is being operated)
Time increase by the convenient reserve (OFF TIMER) time control key.
* At every pressing the time is increased by 1 hour.
(- - > 01 -> 02 -> 03 -> 04 -> 05 - - - > 18 -> 19 -> 20 -> 21 -> 24 -> - - )
* "- - " means that the convenient reserve time is not set yet.
(convenient reserve cancelled)
* Single and continuous operation is available.
* If operation is OFF, it is considered as an invalid key.
3-4
Key Type
TACT
TACT
TACT
TACT
TACT
Samsung Electronics
AWH-1808ER-1 6/13/98 10:12 AM Page 9
3-2-6 LED lamp operation specifications
LAMP name
ON
COOL
DEICE
(1)
HEAT
FAN
HIGH
LOW
˚C
HR
(2)
Operations specifications
Operation ON condition : ON
Operation OFF condition : OFF
Blinking just after resetting : Automatic stop after turning on for 0.5 s and off for 0.5s for 3 minutes(if the operation/stop key is not pressed for 3 minutes).
The mode is set to " COOL " –> ON
Others –> OFF
The mode is set to "HEAT" -> ON
Others –> OFF
The mode is set to " FAN " –> ON
Others –> OFF
The fan speed is set to " HIGH " –> ON
Others –> OFF
The fan speed is set to " LOW " –> ON
Others –> OFF
The set temperature is displayed or set -> ON
Others –> OFF
During setting of the convenient reserve (OFF TIMER) time -> blinking
After setting of the convenient reserve (OFF TIMER) time -> ON
Others –> OFF
Till the "deicing" operation is completed during heating opertion -> ON
Others –> OFF
In case of (set) temperature display
-> NO. (1) 7 seg. LED display indicates temperature of the tens digit (˚C, ˚F)
-> NO. (2) 7 seg. LED display indicates temperature of the units digit (˚C, ˚F)
In case of time (OFF TIMER) display
-> NO. (1) 7 seg. LED display indicates time of the tens digit
-> NO. (2) 7 seg. LED display indicates time of the units digit
Samsung Electronics 3-5
AWH-1808ER-1 6/13/98 10:12 AM Page 10
Temperature
[˚C]
64
63
62
61
60
70
69
68
67
66
65
53
52
51
50
59
58
57
56
55
54
46
45
44
43
49
48
47
42
41
40
35
34
33
32
39
38
37
36
31
30
3-2-7 Resistor and voltage values table of room thermistor, indoor thermistor and outdoor thermistor for each temperature
THERMISTOR
[Kohm]
1.670
1.729
1.791
1.855
1.922
1.992
2.065
2.141
2.220
2.303
2.390
2.480
2.574
2.672
2.775
2.882
2.994
3.111
3.234
3.362
3.496
3.635
3.780
3.932
4.091
4.257
4.432
4.614
4.806
5.007
5.217
5.438
5.669
5.912
6.167
6.435
6.716
7.012
7.322
7.649
7.993
Voltage
[DC V]
0.715
0.737
0.759
0.782
0.806
0.830
0.855
0.881
0.908
0.936
0.964
0.993
1.023
1.054
1.086
1.118
1.152
1.186
1.221
1.258
1.295
1.333
1.371
1.411
1.451
1.493
1.535
1.578
1.623
1.668
1.741
1.761
1.809
1.857
1.907
1.957
2.008
2.060
2.113
2.167
2.221
-1
-2
-3
-4
-5
-6
-7
-8
-9
-10
5
4
3
2
1
0
9
8
7
6
16
15
14
13
19
18
17
12
11
10
Temperature
[˚C]
23
22
21
20
29
28
27
26
25
24
3.904
3.949
3.992
4.035
4.076
4.116
4.155
4.193
4.230
4.266
3.401
3.455
3.509
3.561
3.613
3.664
3.714
3.763
3.812
3.859
2.840
2.897
2.954
3.011
3.068
3.124
3.180
3.237
3.292
3.347
Voltage
[DC V]
2.275
2.331
2.387
2.443
2.500
2.556
2.612
2.669
2.726
2.782
35.66
37.59
39.64
41.82
44.14
46.60
49.22
52.01
54.98
58.14
21.28
22.38
23.54
24.76
26.06
27.44
28.90
30.45
32.10
33.85
13.15
13.78
14.44
15.14
15.88
16.66
17.48
18.36
19.28
20.25
THERMISTOR
[Kohm]
8.354
8.734
9.135
9.556
10.00
10.46
10.94
11.45
11.99
12.55
3-6 Samsung Electronics
AWH-1808ER-1 6/13/98 10:12 AM Page 11
3-2-8 About the safety devices
1. High temperature release : If temperature of the indoor pipe thermistor increases over the specified value during heating operation, following operation is carried out for safety of the equipment.
A condition : temperature of indoor pipe thermistor is below 47˚C
B condition : temperature of indoor pipe thermistor is between 58˚C and 63˚C
C condition : temperature of indoor pipe thermistor is over 63˚C
1) High temperature release operation OFF condition = A condition
-> compressor ON (only in THERMO ON condition)
-> fan motor speed = set fan speed and cool blowing inhibiting operation
2) High temperature release operation ON condition = B condition
-> compressor ON
-> fan motor speed = HIGH operation if it was LOW
= HIGH operation if it was HIGH
3) High temperature release operation ON condition = C condition
-> fan motor speed = set fan speed
-> compressor OFF
2. Low temperature release : If temperature of the indoor pipe thermistor decreases below the specified value during cooling operation, following operation is carried out for safety of the equipment.
A condition : temperature of indoor pipe thermistor is below -1˚C for more than 6 minutes
B condition : temperature of indoor pipe thermistor is over 5˚C
1) Low temperature release ON condition = A condition
-> compressor OFF
-> fan motor "set fan speed"
2) Low temperature release OFF condition = B condition
-> The compressor is turned on if ON condition is satisfied after comparing the ambient temperature with the set temperature
-> fan motor "set fan speed"
[Detailed description]
1) If temperature of indoor pipe thermistor is below -1˚C for more than 6 minutes, the fan motor continues to operate at the set fan speed and the compressor is turned off(Low temperature release operation)
2) If temperature of the indoor pipe thermistor increases over +5˚C during low temperature release operation, normal operation is recovered
: compressor ON, fan mtor set fan speed -> Low temperature release operation OFF
3) If temperature of indoor pipe thermistor increases over 0˚C during counting 6 minutes below -1˚C, the counter is reset.
Samsung Electronics 3-7
AWH-1808ER-1 6/13/98 10:12 AM Page 12
3. Deicing operation : If temperature of the outdoor pipe thermistor decreases below the specified value during heating operation, following operation is carried out for safety of the equipment.
OUTDOOR PIPE
Thermistor temperature (A-Condition)
12[˚C]
100min below
-4[˚C]
100min
COUNT
ON
100min
COUNT
OFF
100min
COUNT
ON
100min
OUTDOOR PIPE
Thermistor temperature (B-Condition)
12[˚C]
30min below
-6[˚C]
ON
5min
OFF
30min
COUNT
ON
30min
COUNT
OFF
30min
COUNT
ON
30min
OUTDOOR PIPE
Thermistor temperature (C-Condition)
12[˚C]
10min below
-8[˚C]
ON
5min
OFF
10min
COUNT
ON
10min
COUNT
OFF
10min
COUNT
ON
10min
ON
5min
OFF
3-8 Samsung Electronics
AWH-1808ER-1 6/13/98 10:12 AM Page 13
CYCLE
COMPRESSOR
1) Deicing detecting condition
• If one of A, B and C conditions is satisfied, deicing operation is carried out.(AUBUC)
• If counting time is overlapped due to detection reference temperature change during counting of the deicing condition, deicing operation starts when the counting time is finished first.
• The maximum counting time is 100 minutes.
- During deicing operation, the left and right swing motor is turned off and stops at the position before swing.
- If operation is turned off during deicing operation, it is finished and the compressor is turned off.
-> Deice lamp ON, fan motor OFF.
2) Display indication.
• The deice lamp is turned on additionally during deicing cycle.
• Only the deice lamp is turned off when deicing is finished.
3) In case of turning off during deicing operation.
• The compressor is turned off after finishing the deicing operation.
• The deice lamp is turned on during deicing cycle and is turned off when deicing is finished.
4) In case of changing mode to cooling operation during deicing operation.
• Cooling operation is carried out after carrying out deicing operation.
• After the compressor is turned off and 3 minutes is passed, it is restarted.
5) Load operation during deicing operation.
DEICE LED ON DEICE LED OFF
DEICE TIME
ON
1min
OFF
FAN
MOTOR
1sec
OFF
COOL BLOWING INHIBITION
THERMO ON
2sec
ON
SET FAN SPEED
AND COOL
BLOWING
INHIBITION
4-WAY
VALVE
ON OFF
55sec
Samsung Electronics 3-9
AWH-1808ER-1 6/13/98 10:12 AM Page 14
4. Cool blowing inhibiting control : In order to inhibit cool blowing during heating operation, the fan motor is operated when temperature of the indoor pipe thermistor is above the specified value.
• The fan motor speed is controlled according to the temperature of condition of the indoor pipe thermistor.
< Compressor OFF -> Compressor ON >
Indoor pipe thermistor
32˚C
30˚C
FAN MOTOR
CONTROL
SET FAN SPEED
LOW FAN
OFF
< Compressor ON -> Compressor OFF >
Indoor pipe thermistor
32˚C
31˚C
30˚C
LOW FAN
OFF
30sec
1) When the indoor pipe thermistor temperature is increasing indoor pipe thermistor temperature = below 32˚C --> fan motor OFF indoor pipe thermistor temperature = over 32˚C --> fan motor speed "set blower speed"
2) When the indoor pipe thermistor temperature is decreasing indoor pipe thermistor temperature = over 30˚C --> fan motor speed "set blower speed" indoor pipe thermistor temperature = below 30˚C --> fan motor speed "Low"
3) But if the compressor is operating, the fan motor is not turned off but is operated weakly even if the indoor pipe thermistor temperature decreases.
3-10 Samsung Electronics
AWH-1808ER-1 6/13/98 10:12 AM Page 15
< Compressor ON -> Compressor OFF > indoor pipe thermistor temperature = below 30˚C --> fan motor speed "Low" indoor pipe thermistor temperature = over 30˚C --> fan motor OFF
30s is passed after compressor is turned off --> fan motor OFF
3-2-9 Compressor delayed operation and 4-way valve delayed operation :
The compressor is turned on after 3 minutes from power resetting or compressor turning off during cooling or heating operation.
1) The compressor can be turned on after "3 minutes delay" from power resetting or compressor turning off.
2) The 4 way valve is turned off/on after "2 minutes and 55 seconds delay" in the on/off condition.
(during heating operation)
3) The operation is stopped after "2 minutes and 55 seconds delay" in the off condition when the 4 way valve is turned on.
Samsung Electronics 3-11
AWH-1808ER-1 6/13/98 10:12 AM Page 17
4. Disassembly and Reassembly
4-1 Compressor Replacement Flow Chart
Locate cause of defect
Release refrigerant
Disconnect electrical wiring from compressor
Cut refrigerant lines from compressor
Plug disconnected lines
Replace compressor
Y
Inspect electrical wiring for defects, and terminals for correct and secure connections
Solder discharge line Solder suction line
Problem?
N
Use nitrogen gas
Corrective action
Samsung Electronics
Y
Add oil as necessary
Check refrigerant oil level
Low oil level?
N
Perform soldering function
Fill system with nitrogen gas
Check for leakage
Leakage?
Y
N
Release nitrogen gas?
Evacuate system
Recharge system
Recharge system
4-1
AWH-1808ER-1 6/13/98 10:12 AM Page 18
4-2 Checking the oil
Fill the transparent container with 10cc of oil, and then conduct the test.
4-2-1 Oil quality
Refrigerant Cycle
Normal
Over-heated
Compressor damage
Color
Light Yellow
Brown
Dark brown
Oil Condition
Odor
No Odor
-
Pungent oil
4-2-2 Replacing and refilling the refrigerant oil
1. Replacing the compressor - Do not fill the system with oil as the compressor is already charged.
2. Replacing the condenser - Refill 50cc.
3. Replacing the evaporator - Refill 50cc.
4. Replacing the refrigerant - Refill 30cc.
5. The high pressure side is filled up with oil after the vacuum is completed.
6. When the refrigerant leaks, it is generally not necessary to refill the oil if the leakage is not severe.
Remarks
Return with the system
Oil Change
Oil Change
4-2 Samsung Electronics
AWH-1808ER-2 6/13/98 1:15 PM Page 1
4-3 Disassembly and Reassembly Procedure
Stop operating the air conditioner, and pull out the power cord before repair.
No.
①
Part name
Ass'y Grill
Procedures
1. Hold the lower part of the grill with two hands while pressing down on both sides of the lower part of the cabinet, pull it forward by about 30˚, and then lift it up for removal.
Remarks
➁
Ass'y Cabinet 1. Remove the screws on both sides of the cabinet to disconnect the cabinet and frame.
2. Pull the handle on the front side of the bottom, and remove the unit from the cabinet.
➂
Ass'y Control 1. Remove four machine screws, and earth wire screw.
2. Remove three lead wire assemblies and the deice sensor from the condenser, and remove two screw on the partition cover.
3. Take out the control box forward.
Samsung Electronics 4-3
AWH-1808ER-2 6/13/98 10:27 AM Page 2
Disassembly and Reassembly
No.
➃
Part name
Plate-Cover
Procedures
1. Remove 11 screws on the plate cover.
Remarks
➄
Ass'y-Evaporator 1. Remove two screws on the left side of the evaporator.
➅
Plate-Evap Casing 1. Lift up the evaporator, and remove the tray drain.
2. Remove two screws on the bottom side, and two screws on the left side of the plate evap casing.
4-4 Samsung Electronics
AWH-1808ER-2 6/13/98 10:27 AM Page 3
No.
➆
Part name
Blower
Procedures
1. Loosen the hexagon nut, and remove the blower.
Disassembly and Reassembly
Remarks
⑧
Propeller Fan 1. Loosen the hexagon nut, and remove the propeller fan.
⑨
Motor Supporte
& Motor
1. Remove four hexagon nuts on the base pan.
2. Move the motor-assembly toward the condenser, and lift up the motor-assembly from the frame.
3. Remove the clips on both sides carefully using the (-) driver.
Samsung Electronics 4-5
AWH-1808ER-2 6/13/98 10:27 AM Page 5
5. Troubleshooting
Check the basic checkpoints first to determine whether it is machine trouble or a problem in the operation method. When it is not related to the basic checkpoints, perform checking in accor dance with the procedures of troubleshooting by symptom.
5-1 Basic Checkpoints for Troubleshooting
1) Is the voltage of the power source appropriate ?
(1)It should be within the range of AC 198V ~ 264V.
(2)The air conditioner may not operate properly when the voltage is out of this range.
2) Is the connection with the fan motor, compressor wire, and starting condenser appropriately made ?
3) The symptoms listed in the table below are not indicative of machine trouble.
Symptom
No operation
Air flows, but no cooling no Heating
The remocon does not operate
No temperature setting
Cause and check
• Check whether there is power failure or the power plug is pulled out.
• Check whether the unit is stopped as a result of completion of the sleep time.
• Pull out the power plug for ten seconds, and then insert it again.
• Check whether the Air filter is clogged with dust or is dirty.
• Check whether the desired temperature is too high. Set the desired temperature to a lower level than the current temperature.(Cooling)
• Check whether it is in "FAN" mode.
• Check whether the desired temperature is too low. Set the desired temperature to a higher level than the current temperature.(Heating)
• Check whether the unit is deicing.
• Check whether battery is completely depleted.
• Check whether the battery is properly inserted.
• Check whether the receiving window of the remocon for the assembly panel PCB is blinded.
• Check whether the remocon is affected by jamming due to a neon sign.
• Check whether the unit is in "FAN" mode.
(In "FAN" mode, only the current temperature is displayed, and the desired temperature is not set.)
The "ON" lamp blinks continuously
• Press the ON/OFF button again.
• Pull out the power plug, and then insert it again.
•
Checking and Display of Fault Area
ERROR OPERATION
COOL
LED LAMP
HEAT
ROOM THERMISTOR
(OPEN OR SHORT)
INDOOR PIPE THERMISTOR
(OPEN OR SHORT)
OUTDOOR PIPE THERMISTOR
(OPEN OR SHORT)
*
Lamp --- blinking at every second (on for 0.5s and off for 0.5s)
--- LED Lamp off
FAN
7-SEG
LED DISPLAY
E1 displayed
E5 displayed
E6 displayed
Samsung Electronics 5-1
AWH-1808ER-2 6/13/98 10:27 AM Page 6
5-2 Troubleshooting by Symptom
5-2-1 No power
1) Check points
(1) Is the voltage of the power source normal ? (AC 198V ~ AC 264V)
(2) Is the electric wire in good contact ?(CN 71, RY 71)
(3) Is the output voltage of the IC01(KA 7812) normal ?(DC 11.5V ~ DC 12.5V)
(4) Is the output voltage of the IC02(KA 7805) normal ?(DC 4.5V ~ DC 5.5V)
Turn off the power, and then turn it on again five seconds later.
Y
Does the "ON" LED lamp of the assembly panel PCB blink for three minutes, and then go off?
N
Check whether the "ON" LED lamp is on, and the operation starts when pressing the ON/OFF button of the remocon.
N
Is the F701(3.15A) fuse blown?
N
Is the primary voltage of the trans normal?
(AC 198V ~ AC 264V)
Y
Is the secondary voltage of the trans normal?
(AC 13V ~ AC 17V)
Y
Is the rectifying diode(D101~D106) normal?
Y
Is the voltage of DC 17V ~ DC 23V applied at both ends of the C102 electrolytic condenser?
Is the voltage of DC 12V applied at both ends of the C104 electrolytic condenser?
Is the voltage of DC 5V applied at both ends of the C105 electrolytic condenser?
Y
Are the IC01(KA7812) and IC02(KA7805) normal?
Y
Replace the assembly main PCB.
Y
Y
N
N
N
N
N
Normal operation.
Normal operation.
Replace the fuse.
Check the power cord and electric wire.
Check and replace the trans.
• Check the D101 ~ D106 for cold soldering.
• Replace the diode
• Check both ends of the C102 for short and cold soldering.
• Check the +12V for a short.
• Check the +5V for a short.
• Check and replace the C102, C104, and C105.
• Check the IC01, and IC02 for cold soldering and a short.
• Replace the IC01, and IC02.
5-2 Samsung Electronics
AWH-1808ER-2 6/13/98 10:27 AM Page 7
5-2-2 When the assembly panel PCB is not operated
1) Check points
(1) Is the voltage of the power source normal ?(AC 198V ~ AC 264V)
(2) Is the electric wire in good contact ?(CN71, RY71)
(3) Is the connection of the assembly main PCB, and assembly panel PCB in good contact?
(CN91, CN92)
(4) Is the voltage of +12V normal ?(CN91 and CN 92 No 15 pin and No 18 pin : +12V±0.5V)
(5) Is the TACT switch of the Ass'y panel PCB pressed above 2 ea?
Turn off the power, and then turn it on again five seconds later.
Check the micom
(IC04) for a short, and replace it.
Check the micom
(IC04) for a short, and replace it.
Check the IC01 for a short, and replace it.
Check the IC02 for a short, and replace it.
When the LED lamp is not operated.
Y
N
N
Is the voltage of the micom
(IC04) No.36~39 port a square wave?
Y
Is the voltage of the micom
(IC04) No.56,58~63 port a square wave?
Y
N
Is the voltage of the
IC01 No. 13~16 a square wave?
Y
N
Is the voltage of the
IC02 No. 10~16 a square value?
Y
Replace the assembly panel PCB
When the TACT switch is not operated.
Y
Is the voltage of the micom (IC04) No.36~41port a square wave?
Y
Is the voltage of the micom(IC04) No.44port a square wave?
Y
Does the switching diode(D901~D906) operate normally?
Y
Replace the assembly panel PCB.
N Check the micom
(IC04) for a short, and replace it.
N
N
Check the micom
(IC04) for a short, and replace it.
Replace the faulty switching diode.
(D901~D906)
Samsung Electronics 5-3
AWH-1808ER-2 6/13/98 10:27 AM Page 8
5-2-3 When the remocon is not operated
1) Check points
(1) Is the voltage of the power source normal ? (AC 198 ~ AC 264V)
(2) Is the electric wire in good contact ? (CN71, RY71)
(3) Is the assembly main PCB in good contact with the assembly panel PCB?(CN91, CN92)
(4) Is the voltage of +12V and +5V of the assembly panel PCB normal?
(CN91 No 15 pin and No 18 pin : +12V, No 15 pin and No 17 pin : +5V)
Turn off the power, and then turn it on again five seconds later.
Does the "ON" LED lamp of the assembly panel PCB blink for three minutes, and then go off?
Y
Check whether the "ON" LED lamp is on and th peration starts when pressing the on/off button of the remocon.
N
Is the battery voltage of the remocon above
DC 2.5V?
Y
Does the X-TAL(CSB455EB) oscillate normally?
Y
Is the collector voltage of the remocon Q1, Q2(C2412) a square wave?
Y
Is the receiving output of the assembly panel PCB a square wave?(CN93 No.15(-), No.16(out))
Y
Is the input voltage of the micom(IC04) No. 26 pin of the assembly main PCB a aquare wave?
Y
Replace the assembly main PCB.
Y
Y
N
N
N
N
N
Go to the clause "No power".
The remocon is normally operated.
Replace the battery.
• Check the X-TAL for cold soldering and a short.
• Replace relevant components.
• Check the micom(IC1) Q1, and Q2 for cold soldering and a short.
• Replace relevant components.
• Check the RM41(recieving module) for cold soldering and a short.
• Replace relevant components.
• Check the R401 and C401 components.
• Check the micom(IC04).
5-4 Samsung Electronics
AWH-1808ER-2 6/13/98 10:27 AM Page 9
5-2-4 Wen the compressor is not operated
1) Check points
(1) Is the voltage of the power source normal ? (AC 198V ~ AC 264V)
(2) Is the desired temperature lower than the indoor temperature in the cool mode?
(Compressor stopped)
(3) Is the desired temperature higher than the indoor temperature in the HEAT mode?
(Compressor stopped)
(4) Is the starting condenser in good contact?
(5) Is the electric wire in good contact ? (CN71, RY71)
(6) Is the output voltage of the IC01(KA7812) and IC02(KA7805) normal ?
Turn off the power, and then turn it on again five seconds later.
Does the "ON" LED lamp of the assembly panel PCB blink for three minutes, and then go off?
Y
Check whether the "ON" LED lamp is on and the operation starts when pressing the on/off button of the remocon or assembly panel PCB?
Y
Check whether the compressor is activated in three minutes after turning on the power with the "COOL" or
"HEAT" LED lamp being switched on when selecting the cool mode of the remocon or assembly panel PCB.
N
Is the IC07 output normal?
When the compressor is ON, IC07 No. 14 pin –> Low.
Y
Does the relay(RY74) operate normally?
When the compressor is ON, the RY71 should operat.
Y
Is the compressor normal?
Y
Replace the compressor.
N
N
Y
N
N
N
Go to the clause "No power".
• Go to the clause "when he remocon does not operate".
• Go to the clause "when he assembly panel PCB does not operate".
Normal operation.
• Check the IC07 for short and cold soldering.
• Replace the IC07.
• Check the relay coil resistance.
(resistance : About 150
Ω
±20
Ω
)
• Replace the relay.
• Check the operation of the O.L.P, and replace it if necessary.
• Check the compressor resistance.(0
Ω
: short,
∞Ω
: open)
Samsung Electronics 5-5
AWH-1808ER-2 6/13/98 10:27 AM Page 10
5-2-5 Wen the air swing motor is not operated
1) Check points
(1) Is the voltage of the power source normal ?(AC198V ~ AC264V)
(2) Is the electric wire in good contact ?(CN71, RY71)
(3) Is the swing motor conector in good contact?(CN71)
(4) Is the terminal connected to the swing motor in good contact?
(5) Is the output voltage of the IC01(KA7812) and IC02(KA7805) normal?
Turn off the power, and then turn it on again five seconds later.
Does the "ON" LED lamp of the assembly panel PCB blink for three minutes, and then go off?
Y
Does the air-swing motor operate when pressing the air-swing button of the remote control or assembly panel PCB?
N
Is the IC07 output normal?
When the air-swing motor is on, IC07 No.
10 pin ➝ Low
Y
Does the relay(RY 75) operate normally?
When the air-swing motor is operated, the
RY74 should be operated.
Y
Is the air-swing motor normal?
Y
Replace the air-swing motor.
N
Y
N
N
N
Go to the clause "No power".
Normal operation.
• Check the IC07 for a short and cold soldering.
• Replace the IC07.
• Check the relay coil resistance.
(Normal: About 400
Ω
)
• Replace the relay.
• Check the air-swing motor resistance.
(0
Ω
: short,
∞Ω
: open)
5-6 Samsung Electronics
AWH-1808ER-2 6/13/98 10:27 AM Page 11
5-2-6 When the fan motor does not operate
1) Check points
(1) Is the voltage of the power source normal ?(AC198V ~ AC264V)
(2) Is the electric wire in good contact ?(CN71, RY71)
(3) Is the starting condenser in good contact?
(4) Is the fan motor connector in good contact?(CN73)
(5) Is the output voltage of the IC01(KA7812) and IC02(KA7805) normal ?
Turn off the power, and then turn it on again five seconds later.
Does the "ON" LED lamp of the assembly panel PCB blink for three minutes, and then go off?
Y
Check whether the "ON" LED lamp is on and the operation starts when pressing the on/off button of the remocon or assembly panel PCB.
Y
Does the LED lamp of the assembly panel PCB turn to High, and Low when setting the remocon or assembly panel PCB TACT switch (fan speed) to High, and LOW?
Y
Is the IC07 output normal?
When the fan motor is High, IC07 No. 13 pin –> LOW.
When the fan motor is Low, IC07 No. 12 pin –> LOW.
Y
Does the relay(RY 72, 73) operate normally?
When the fan motor is High, RY72 should operate.
When the fan motor is Low, RY73 should operate.
Y
Is the fan motor normal?
Y
Replace the fan motor.
N
N
N
N
N
N
Go to the clause "No power".
• Go to the clause of "when the remocon does not operated".
• Go to the clause "when the assembly panel PCB is not operated".
• Go to the clause "when the remocon does not operated".
• Go to the clause "when the assembly panel PCB is not operated".
• Check the IC07 for a short and cold soldering.
• Replace the IC07.
• Check the relay coil resistance.
(Normal: About 400
Ω
)
• Replace the relay.
• Check the fan motor resistance.
(0
Ω
: short,
∞Ω
: open)
Samsung Electronics 5-7
AWH-1808ER-2 6/13/98 10:27 AM Page 12
5-2-7 Wen the 4-way valve is not operated
1) Check points
(1) Is the voltage of the power source normal ?(AC198V ~ AC264V)
(2) Is the electric wire in good contact ?(CN72)
(3) Is the 4-way valve conector in good contact?(CN72)
(4) Is the output voltage of the IC01(KA7812) and IC02(KA7805) normal?
(5) Is the unit heating cycle?
Turn off the power, and then turn it on again five seconds later.
Does the "ON" LED lamp of the assembly panel PCB blink for three minutes, and then go off?
Y
Does the 4-way valve operate when pressing the HEAT button of the remote control or assembly panel PCB?
N
Is the IC077 output normal?
When the air-swing motor is on, IC07 No.
11 pin ➝ Low
Y
Does the relay(RY 74) operate normally?
When the air-swing motor is operated, the
RY74 should be operated.
Y
Is the 4-way valve coil normal?
Y
Replace the 4-way valve coil.
N
Y
N
N
N
Go to the clause "No power".
• Normal operation
(Operating the "Heat", relay about 3 minutes until the "4-way valve" operates.)
• Check the IC07 for a short and cold soldering.
• Replace the IC07.
• Check the relay coil resistance.
(Normal: About 400
Ω
)
• Replace the relay.
• Check the fan motor resistance.
(0
Ω
: short,
∞Ω
: open)
5-8 Samsung Electronics
AWH-1808ER-2 6/13/98 10:27 AM Page 14
6. Exploded View and Parts List
6-1 Main unit
6-1
14
7
1
4
13
12
34
5
32
31
6
15
10
9
2
3
16
2
3
4
8
6
5
1
14
13
11
33
10
11
9
8
27 28
29
24
25
26
30
19
20
19
18
17
21
22
23
Samsung Electronics
AWH-1808ER-2 6/13/98 10:27 AM Page 15
■ Part List
DB75-10022A
DB90-20167A
DB61-30452C
DB65-10089A
DB31-10117C
DB70-10603A
DB67-50028A
DB96-30263A
DB95-10263B
DB60-30028A
DB73-10004A
DB63-10165B
DB60-30018A
DB47-20001P
DB63-10355A
DB96-10564A
DB96-10557A
DB32-10045A
DB27-10030A
Code No.
DB92-10290B
DB63-30129A
DB63-40013A
DB96-40166A
DB73-20096A
DB62-31613A
DB71-50025A
DB70-10604A
DB94-30080A
DB61-10146A
DB70-10602A
DB72-10147A
DB70-10605A
DB90-10548B
DB61-40125A
31
32
33
34
26
27
28
29
30
21
22
23
24
25
16
17
18
19
20
11
12
13
14
15
8
9
6
7
10
No.
3
4
1
2
5
ABS
ASS'Y
SGCC-M
SK5-CSP
220~240V/50Hz
SGCC-M(Z22)
ABS+G/F
ASS'Y
48B180JV1E7
M8, ZPC
EPDM
NORYL, BLK
M5, SM20C
MRA12016-12007
CR
ASS’Y
ASS’Y
ASS’Y
ASS’Y
Specification
HIPS
ABS
FO-PS
ASS'Y
NBR
OD12.7
DAWH-3NB
SGCC-M(Z22)
ABS+G/F
FO-PS
SGCC-M(Z22)
FO-PU
SGCC-M(Z22)
ASS'Y
PP
Description
FRONT GRILLE
GUARD-AIR FILTER
TRAY-DRAIN
EVAPORATOR
RUBBER-COVER PIPE
4-WAY V/V(ASS’Y)
WIRE-HOLDER
PLATE-EVAP CASING
BLOWER-ASS'Y
CASE-EVAP
PLATE-PARTITION
SEAL-COVER
PLATE-COVER
CABINET
HOLDER-THERMISTER
DAMPER LEVER
PLATE-BOTTOM
SUPPORTER
CLIP-MOTOR
MOTOR-FAN
PLATE-COND CASING
FAN-PROPELLER
CONDENSER
ASS'Y-COMP
NUT-WASHER
GROMMET-ISOLATOR
COVER-TERMINAL
NUT-FLANGE
OLP
CAP-DRAIN
ASS’Y CAPI TUBE
ASS’Y DISTRIBUTOR
THEMISTOR COND
ASS’Y SOLENOID COIL
1
1
1
1
1
1
3
1
1
1
1
1
1
3
1
2
1
1
1
1
1
1
1
1
1
1
1
2
1
Q'TY
AWH-1808ER
1
1
1
1
1
Remarks
Samsung Electronics 6-2
AWH-1808ER-2 6/13/98 10:27 AM Page 16
6-2 Ass’y Control
10
9
14
13
11
2
3
4
8
6
5
1
6-3 Samsung Electronics
AWH-1808ER-3 6/13/98 10:29 AM Page 1
■ Part List
8
9
6
7
10
11
12
13
14
No.
3
4
1
2
5
Code No.
DB61-60091A
DB66-30142A
DB60-50010B
DB66-70022A
DB95-20065F
2501-001059
DB66-30143A
DB93-10464A
DB93-10465A
DB39-20358A
DB39-10084A
DB32-10005C
DB64-70074A
DB64-40163A
Description
FRAME-BLADE
BLADE-V
WASHER-STOP
ARM-BLADE
SWING-MOTOR
C-OIL
BLADE-H
ASS'Y MAIN PCB
ASS'Y PANEL PCB
C/W DISPLAY
POWER CORD
THERMISTOR
PANEL-CONTROL
INLAY-CONTROL
Specification
PS
PP
SUS-304
ABS
M2LJ49ZU32
6/40µF X
450VAC
PP
AWH-1808ER
AWH-1808ER
AWH-1808ER
AP3, 15A/250V
10KD SAH-151CH
PS
PC
Q'TY
AWH-1808ER
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
Samsung Electronics 6-4
AWH-1808ER-3 6/13/98 10:29 AM Page 2
6-3 ASS’Y REMOCON(DB93-30046E)
■ Part List
3
4
1
2
5
6
No.
Code No.
DB93-30026E
DB61-10022A
DB61-10011A
DB73-20013A
DB93-10462A
DB64-40008B
DB63-10081A
Description
ASS’Y REMOCON
CASE REMOCON(UPP)
CASE REMOCON(LOW)
RUBBER(BT)
ASS’Y REMOCON PCB
WINDOW REMOCON
COVER BATTERY
Specification
AHR-100
ABS
ABS
NBR
AWH-1808ER
PC T1.5
ABS, T2.0
Q'TY
AWH-1808ER
1
1
1
1
1
1
1
Remarks
6-5 Samsung Electronics
AWH-1808ER-3 6/13/98 10:29 AM Page 4
7. Block Diagram
7-1 Refrigerating Cycle Block Diagram
T1
Capillay tube
Check V/V
Heat exchanger
(Evaporator)
Heat exchanger
(Condenser)
T2
7-2 Basic Structure
7-2-1 Micom Control Diagram
MICOM
Indoor Temperature Sensor outdoor Temperature Sensor
Room Temperature Sensor
Deice Temperature Option
Deice Time Option
Receiving Unit of Remocon
A/D converter
Remocon Single Receiving
Remote Cotrol
FAN SPEED(HIGH,LOW)
TEMP. SETTING(▼▲)
TIMER SETTING(▼▲)
COOL
HEAT
FAN
ON/OFF
AIR SWING
• Air swing motor control
• Compressor control
• 4-way valve control
• Buzzer control
• Temperature control
Reset Circuit
Oscillation Circuit
7-1
Compressor
4-way valve
Cooling
Heating
LED CONTROL
• Mode(COOL, HEAT, FAN)
• ON
• Fan speed (Low, HiGH)
• Temperature Display
• Deice
• Temp
• HR
Compressor
Fan motor
4-way valve
Air swing motor
Power circuit (DC 5V)
Power circuit (DC 12V)
Down Trans (AC13V ~ AC17V)
Power input (AC198V ~ AC264V)
Samsung Electronics
AWH-1808ER-3 6/13/98 10:29 AM Page 5
MODEL OPTION
TEMPERATURE OPTION
GND
RS-232C
RS-232C
GND
GND
GND
BUZZER
GND
ROOM THERMISTOR
INDOOR PIPE THERMISTOR
OUTDOOR PIPE THERMISTOR
GND
GND
GND
DEICE TEMPERATURE OPTION
DEICE TIME OPTION
VCC
VCC
GND
GND
GND
GND
GND
REMOTE CONTROL SINGLE INPUT
RESET IC OUTPUT
GND
GND
10MHz RESONATOR
10MHz RESONATOR
GND
7-2-2 Micom Pin Assignment
( MB89635)
19 AVcc
20 AVr
21 AVss
22 P74
23 P73/INT3
24 P72/INT2
25 P71/INT1
26 P70/INT0
27 RST
28 MOD0
29 MOD1
30 X0
31 X1
32 Vss
1 P31
2 P30
3 P43
4 P42/UI2
5 P41/UO2
6 P40
7 P53
8 P52
9 P51/BZ
10 P50
11 P60/AN0
12 P61/AN1
13 P62/AN2
14 P63/AN3
15 P64/AN4
16 P65/AN5
17 P66/AN6
18 P67/AN7
P12 46
P13 45
P14 44
P15 43
P16 42
P17 41
P20 40
P21 39
P22 38
P23 37
P24 36
P25 35
P26 34
P27 33
P01 55
P02 54
P03 53
P04 52
P05 51
P06 50
P07 49
P10 48
P11 47
Vcc 64
P32 63
P33 62
P34 61
P35 60
P36 59
P37 58
Vss 57
P00 56
<MODEL OPTION>
P31(#1) OPTION
HIGH COOLING
NOTE
COOLING ONLY
LOW HEAT PUMP AWH-1808E(HEAT PUMP)
<DEICE TIME OPTION>
AN6(#7)
GND ~1V 2V~ 3V~ 4V~
0.9V
~1.9V
2.9V
3.9V
4.9V
standard standard
+1min standard
+2min standard
+3min standard
+4min
Samsung Electronics
VCC
GND
GND
GND
GND
GND
COMPRESSOR
HIGH(FAN MOTOR)
LOW(FAN MOTOR)
4-WAY
SWING MOTOR
GND
TEST(Time shortened)
Key Control
GND
GND
NC(OUTPUT PORT)
LED DISPLAY CONTROL
<TEMPERATURE DISPLAY OPTION>
P30(#2) OPTION
HIGH
LOW
°
C
°
F
NOTE
TEMP DISPLAY UNIT
TEMP DISPLAY UNIT
<DEICE TEMPERATURE OPTION>
GND ~1V 2V~ 3V~ 4V~
0.9V
~1.9V
2.9V
3.9V
4.9V
AN7(#18) standard
-2 ° C standard
-1 ° C standard standard
+1 ° C standard
+2 ° C
7-2
AWH-1808ER-3 6/13/98 10:29 AM Page 6
8. PCB Diagram
8-1 Main PCB ( ASS'Y CODE NO : DB93-10464A )
8-1 Samsung Electronics
AWH-1808ER-3 6/13/98 10:29 AM Page 7
■ Part List
2202-000121
DE47-40024A
DE47-30019A
2001-000065
DE27-20017A
3501-000399
2802-000103
2001-000290
DB09-10150A
DB47-90081A
DE13-20009A
DE30-20016A
1405-000147
3711-002662
3711-000940
3711-003783
3711-003405
3711-000203
3711-003407
DE39-60001A
DE41-10411A
DE26-20114A
DE60-60012A
2001-000241
Code No.
DB93-10464A
DE32-10037A
0402-000559
DE13-20008A
DE13-20016A
DE60-10100A
DE62-30039A
2001-000429
2001-000218
2001-000003
2001-001172
2202-000780
2401-000710
2401-000180
2401-001397
Description
ASSY MAIN PCB
FUSE
DIODE RECT
IC VOLT REGU
IC VOLT REGU
SCREW TAPPING
HEAT SINK
R-CARBON
R-METAL FILM
R-CARBON
R-CARBON
C-CERAMIC
C-AL
C-AL
C-AL
C-CERAMIC
FUSE HOLDER
SPARK KILLER
R-CARBON
IC-DRIVE
RELAY
CERAMIC RESONATOR
R-CARBON
IC-MCU
RELAY POWER
IC
BUZZER
VARISTOR
CONNECTOR HEADER
CONNECTOR WAFER
CONNECTOR WAFER
CONNECTOR WAFER
CONNECTOR WAFER
CONNECTOR WAFER
WIRE-SO, COPPER
PCB MAIN
TRANS L.V
PIN EYELET
R-CARBON
31
32
33
34
35
26
27
28
29
30
36
37
38
39
21
22
23
24
25
16
17
18
19
20
11
12
13
14
15
8
9
6
7
10
No.
3
4
1
2
5
Specification
AWH-1808ER
FST 250V 3.15A
D4G 400V
KA7812 TO-220AB
KA7805 TO-220AB
M3*6 FEFZY
AL H25
RD 1/8 TP 102-J
RD 1/8 TP 103-F
RD 1/8 TP 331-J
RD 1/2T 621-J
100nF/50V
2200uF/25V
1000uF/35V
470uF/25V
101K 0A/50V
FH-51H 7.5A
ESQ1201
RD 1/4 TP 103-J
KID 65003AP
JQ1A-12V
10Mhz
RD 1/8 TP 103-J
MB89635
JM1aN DC12V
KA7533 DIP
CBE 2220BA STICK
14D-471K
JSW250-02 WHT
SMW250-04 WHT
53134-1810 WHT
YW396-03AV BLK
YW396-03AV WHT
YW396-03AV RED
PI 0.6 SN 52MM
AWH-1808ER
230V 17V
OD 2.5 L 3.0
RD1/8TP152-J
Q'TY
6
1
1
1
1
F701
D101~D106
IC01
IC02
Remarks
1
3
1
1
3
R201
R401, R402, R403
R404~406
7
1
4
1
1
1
1
1
1
1
1
1
1
9
1
R602
C101, C103, C201,C401~403, C501, C502, C901
C104
C102
C105
C404
F701
SK71
R501
IC07
RY72~RY75
X501
R601, 407~410, 412, 301
IC04
RY71
1
1
1
1
1
1
1
1
1
7
1
1
5
1
IC03
BZ61
VA71
CN41
CN42
CN92
CN72
CN71
CN73
J1-J5, SW01, OP01
PCB
TN71
TN71
R411
Samsung Electronics 8-2
AWH-1808ER-3 6/13/98 10:29 AM Page 8
8-2 Display PCB (ASS'Y CODE NO : DB93-10465A)
■ Part List
No.
12
13
14
15
8
9
10
11
16
17
18
6
7
4
5
1
2
3
Description
ASS’Y PANEL PCB
LED LAMP
LED LAMP
MODULE REMOCON
CONNECTOR WAFER
LED DISPLAY
IC-SOURCE DRIVE
WIRE-SO, COPPER
SW TACT V
PCB PANEL
DIODE SWITCHING
R-CARBON
R-CARBON
LED-DISPLAY
IC-DRIVE
C-AL
C-CERAMIC
R-CARBON
Code No.
DB93-10465A
DB07-10021A
DB07-10019A
DB32-50023A
3711-003782
DB61-90080A
1003-000217
DE39-60001A
3404-000280
DE41-10412A
0401-000005
2001-000776
2001-000065
DE07-20028A
DE13-20017A
2401-001212
2201-000796
2001-000036
Specification Q'TY
AWH-1808ER
LTL-4233(GRN)
LTL-4213(RED)
TSOP 1238TBI
53156-1810WHT
ABS
UDN2981A
PI 06 SN 52MM
KPT-1115A
AWH-1808ER
1N4148
RD 1/2 TP 471
RD 1/4 TP 103-J
SSD-A3202GMT-S GR 1
KID65003AP 1
7
1
1
6
1
6
4.7uF 50V
1nF/50V
RD 1/4 TP 331-J
1
1
1
1
1
1
1
1
7
2
Remarks
LE03,LE05~LE10
LE02,LE04
RM41
CN91
LE01
IC02
C401
C402
R401
IC01
J1~J11, OP01
SW91~SW96
PCB
D901~D906
R902~R908
R402
8-3 Samsung Electronics
AWH-1808ER-3 6/13/98 10:29 AM Page 9
8-3 ASS’Y PCB-REMOCON (ASS’Y CODE NO : DB93-10462A)
■ Part List
No.
Description
4,5
6
7,8
9
1
2
3
PCB REMOCON
IC-MCU
RESONATOR
IR LED
C-ELEC
TR CHIP
R-CHIP
10
11
R-CHIP
R-CHIP
12,13 C-CERAMIC CHIP
14 BATTERY S/P-PLUS
15 BATTERY S/P-MINUS
(BOTTOM)
Code No.
DB09-10127A
(TOP)
Specification
KS51810-19
CSB 455EBL
SI5312-H
50V 4.7uF
2SC2412
RMC 1/10 1.0-J
RMC 1/10 560K-J
RMC 1/10 330-J
CL21 C101J BNCS
SWPB
SWPB
Q'TY
2
1
2
1
1
1
1
2
1
1
1
1
PCB
IC1
X1
LED1, LED2
C3
Q1,Q2
R1
-
R3
R4
C1, C2
+
Remarks
Samsung Electronics 8-4
AWH-1808ER-3 6/13/98 10:29 AM Page 10
9. Wiring Diagram
9-1 AWH-1808ER
9-1
AWH-1808ER : 6/40µF X 450VAC
AWH-1808ER-4 6/13/98 10:48 AM Page 1
10. Schematic Diagrams
10-1 Indoor Unit
Samsung Electronics 10-1
AWH-1808ER-3 6/13/98 10:30 AM Page 11
10-2 Remote Control
10-2 Samsung Electronics