MGE Office Protection Systems
www.mgeops.com
EX RT
5/7/11 kVA
Introducing the EX RT. An all purpose high
performance on-line UPS for sensitive rack server
enclosures and harsh industrial environments.
High Reliability & Availability
◗ Internal static bypass
◗ I/O Box with Manual Bypass
Industrial Grade Performance
◗ Large input voltage range without
using battery power
◗ 40-70 Hz input frequency range
◗ Operating temperature: 0°C - 40°C
permanently, 0°C – 45°C for 8 Hours
◗ Stand alone solution with modular
design for industrial needs
Optimized Solution for
Infrastructure Network Integration
◗ Rack kit for an optimized mounting
with 3U height per module
◗ Brackets secure the UPS into the
rack enclosure
◗ 1 slot compatible with multiple MGE
communication card protocols
◗ Software application packages are
fully customized
The EX RT is a UPS designed for sensitive high density server environments
and harsh industrial applications. Specifically engineered to meet demanding
◗ Long backup time availabilities
◗ Input/Output box brackets secure
the I/O box during hot swapping
of power module
customer applications in IT systems, measuring instruments, PLC’s and industrial
PC markets, our UPS is fully compatible with genset redundancy requirements in
most instances. The manual bypass, hot swap I/O box and intuitive front panel
LCD control panel are just a few of the many differentiating features that make
the EX RT the ideal product for the 5 to 11 kVA power range.
E N E R G I Z E
Y O U R
E N T E R P R I S E
An Eaton Brand
The solution for high-density rack server enclosures and industrial environment
High-availability
◗ Hot swap battery and UPS modules prevent interruptions
◗ Internal and maintenance bypass are standard to achieve
the highest level of availability
◗ Large input voltage window without using battery power
◗ Automatic battery test and protection against deep discharges
Clear coat battery packaging with
thru-holes for diagnostics and testing
Hot-swappable I/O Box
Compatibility with any environment
Data room
Battery back-up
◗ Versatile rack or tower in 6U=power module + battery module
◗ Battery modules up to eight hours with the CLA*
charger module *CLA for external battery cabinet only
◗ Management through various protocols such as
HTTP/SNMP/XML/Telnet
◗ Integration with popular network management systems like HP
Openview, IBM Tivoli, CA Unicenter
◗ Integrated NEMA receptacles included with transformer configuration
◗ Optional rackmount PDU with NEMA or IEC sockets to facilitate
power distribution within the enclosure
Ergonomics
◗ Multilingual scrolling LCD front bezel control panel
◗ Simple setup on network or industrial mode permits system
shut down or service continuity in case of overload or short circuit
◗ Space saving battery connector cables and extra
long battery cables for separate battery racks
◗ Battery detection system automatically configures
battery modules and UPS
◗ UL 924 Emergency Lighting and Equipment (90 minute runtime)
battery cabinets available
High-end ergonomics
◗ Versatile 6U rack or tower design
◗ Multilingual LCD screen
◗ Two stands improve stability of the tower
◗ Event log for easy fault detection
◗ Up to five extra battery modules to extend
runtime up to two hours maximum
Industry and infrastructure
◗ Voltage free contacts are included for
remote status monitoring
◗ Battery integration system optimizes the footprint of extended
runtime solutions with automatic battery module detection
◗ Genset compatibility
◗ Integration with building management systems ( Jbus), six voltage
free contacts for remote status monitoring
◗ Temperature and humidity supervision with an environment
sensor triggers an orderly shutdown
Versatile form factor
Large choice of options to meet customer needs
◗ Universal 3U Transformer Module: System Earth Arrangement,
galvanic isolation for upstream and downstream UPS installation
EX RT with Battery Integration Kit
◗ Battery Integration System for optimized footprint: up to eight
modules stacked on a caster kit: one UPS module + six EXB battery
modules + one transformer module
◗ 3U CLA module for back up times up to eight hours
Load Protected
Battery Mode
Bypass Mode
User-friendly installation and operation
◗ Load metering in kW/kVA is permanently displayed on the LCD
◗ Operating mode, battery capacity in %, voltage measurement,
normal AC, bypass (separate AC) input/output, serial number
and power rating identification are available by scrolling up or down
◗ Event logs and fault diagnostics facilitate maintenance and repair
Fault Alarm
LCD 32 characters
Full customization through a configuration
panel in Personal Solution-Pac
◗ CLA, hot standby, ECO mode, frequency converter setup
◗ Low battery, battery test frequency, disable deep discharge protection
◗ AC bypass input tolerance settings for: frequency,
voltage- AC bypass transfer conditions
EX RT Back Panel (Transformer Module/Power Module/Battery Module)
Front Panel LCD Control Panel
LCD display, rotating (tower or rack format),
multilingual, backlit
EX RT Back Panel (Battery Module/Power Module)
3
4
6
5
8
7
9
1 L6-30R (Load 1)
2
1
2 Load 1 Breaker 30A
3 (4) 5-15/20R 120V (Load 2)
4 Load 2 Mini-Breaker 15A
5 L6-30R (Load 3)
6 Load 3 Breaker 30A
7 (4) 5-15/20R 120V (Load 4)
8 Load 4 Mini-Breaker 15A
9 Output Breaker
Easy integration in high-density enclosures.
Software unrivaled anywhere in the industry.
Power Management
MGE PowerServices™
Solution-Pac software suite on CD
Included for server protection and local or
remote UPS management
◗ Installation and Start-Up
Options
Network Management Card
◗ For Ethernet 10/100 network connection,
SNMP alerts and Web-based monitoring
◗ Extended Warranty Contracts
Environment Sensor for SNMP/Web card
◗ SNMP and Web monitoring of temperature +
humidity + status of 2 contacts
Management-Pac 2 software suite on CD
◗ NMS integration kit: HP OpenView,
IBM Tivoli Netview, CA Unicenter
Enterprise Power Management
◗ Device Monitoring/Management Application
Status information card
◗ Monitors for voltage free contacts and
remote power off function
◗ Start-Up Only
– Warranty + 1
– Warranty + 3
5 kVA/4 kW
EX RT Specifications
7 kVA/4.9 kW
11 kVA/8 kW
Performances
Technology
Online double conversion with PFC (Power Factor Correction) system
Nominal Input Voltage
120-280 V at <70% rated output
Input Voltage Range
156-280 V at 100 % rated output
Input Frequency Range
Output Voltage/Frequency
Overall Efficiency (Online Mode-ECO Mode)/
Harmonic Current Distortion
Crest Factor/Overload Capacity
40-70 Hz, frequency converter as a standard
200/208*/220/230/240/250 Volts; 120 V Output Voltage available with transformer; 50/60 Hz autoselect
90% - 97% /<5%
3:1 / 2 min if 102%<overload<110%, 1 min if 110%<overload<125%,
30 sec if 125%<overload<150%, 500msec. If overload >150%
weekly without load interruption(1)
45°C for 8 Hrs. 0°C to 40°C continuous
Battery Test
Operating Temperature
5 kVA/4 kW
7 kVA/4.9 kW
25/9
21/7
14/5
Standard Battery + 1 EXB
60/25
53/20
30/14
Standard Battery + 2 EXB
100/45
83/32
53/22
Standard Battery + 3 EXB
122/60
108/45
84/30
Standard Battery + 4 EXB
170/84
132/57
102/42
Standard Battery + 5 EXB
225/100
164/72
113/53
Back-up Times (in minutes at 50% /100% loads)
Standard Battery
11 kVA/8 kW
More back-up time available with CLA module, on request
Connection
Power Module Input/Output Terminal Block
Maximum Wire Size (Solid or Stranded Wire)
Step-Down Transformer
Output Configuration
Hardwired
10 mm / 6 AWG
Hardwired
Hardwired
10 mm / 6 AWG
13 mm / 4 AWG
120/208/240 VAC Output
Terminal Block, plus
(2) NEMA L6-30R (208V)
(8) NEMA 5-15/20R
Optional PDUs for additional NEMA or IEC receptacles
Communication
Port Type
6 voltage free dry contacts DB-9 rated at 2 A 48V DC, (1) RS 232, (1) RJ11 for RPO (Remote Power Off)
Slot
1 slot for MGE transverse communication card (HTTP, XML, Webcard, Jbus…)
Standards and Certification
Performance and Safety
EMC
Certification
Dimensions (H x W x D) in inches/Weight in pounds
Standard EX RT (Power Module + Battery Module) Form Factor (High Voltage)
IEC 62040-1/CEI 60950/UL 1778 and CSA 22.2 Standards
IEC 62040-2; EN 50091-2; FCC class A
UL/TÜV, GS mark, CB, C-Tick, CE
10.32 (6 U) X 17.49 X 26.25/192 for 5/7 kVA System, 211 for 11kVA System
Standard EX RT (Power Module + Battery Module + Transformer Module)
Form Factor (Low Voltage)
15.48 (9U) X 17.49 X 26.5/365 for 5/7 kVA Systems/384 for 11 kVA System
Power Module EX RT
5.16 (3 U) X 17.49 X 26.25/49.6 for 5/7kVA Unit, 60.6 for 11kVA Unit
Battery Module EXB RT
5.16 (3 U) X 17.49 X 25 / 142 for 5/7kVA Unit, 151 for 11kVA Unit
Charger Module EX RT CLA
Transformer Module EX RT
Part Number and Description
EX RT Standard Pack without Transformer (HV)
EX RT Standard Pack with Transformer (LV)
EX RT Power and Battery Modules
Power Module with rails
Battery Module with rails
EX RT Transformer
7 kVA Transformer with rails
11 kVA Transformer with rails
EX RT CLA Charger Module
CLA Charger with rails
Battery Integration Kit with Casters (max. 8 modules)
5.16 (3 U) X 17.49 X 23.75/25.40
5.16 (3 U) X 17.49 X 25/173
5 kVA/4 kW
7 kVA/4.9 kW
11 kVA/8 kW
86050
86201
86070
86203
86110
86205
86215
86207
86216
86207
86217
86209
–
–
86311
–
–
86211
86214
86214
86214
Stack kit with inter-module fastening, swivel wheels, brakes, leveling feet
86005
86005
86005
Installation Rack Kits for EX RT/EXB 5/7/11 kVA
Power Module Rail Kit
Battery Module, Transformer and CLA Charger Rail Kit
86001
86002
86001
86002
86001
86002
72-153653-01
–
Two year product warranty
–
Input Cord for 5 kVA System
8 foot cord with NEMA L6-30P
Warranty/Parts and Labor (US and Canada)
* : Default Voltage 1: Configurable 2: At Pn for 230 V input/output 3: Typical values after 3 discharge cycles, 3-5 years design life battery 4: More back-up time available with CLA module, on request
MGE Office Protection Systems
E N E R G I Z E
North & South America Headquarters
13 Whatney, Suite 101 • Irvine, CA 92618
tel (800) 279-7776 • fax (949) 268-2847
www.mgeops.com
EX RT
Revision 200
Effective: September 2007
Y O U R
E N T E R P R I S E