SIMATIC S5 135U, S5 155U/H

SIMATIC S5Ć135U, S5Ć155U/H
Central controllers/Expansion units
135U/155U central controller
The 135U/155U central conĆ
troller can be used optionally
for the construction of a
S5Ć135U, S5Ć155U or
S5Ć155H programmable conĆ
troller.
Application
Design
The 135U/155U central conĆ
troller comprises:
21 free slots
1 power supply chassis with
builtĆin fan
S5-135U, S5-155U
Depending on the extent of
the automation task, the cenĆ
tral controller can be
equipped with the following
CPUs:
CPU 948 (max. 4)
CPU 928B (max. 4)
CPU 928 (max. 4)
CPU 922 (max. 4)
Siemens ST 50 · 1998
All CPUs can also operate
jointly in multiprocessor
mode. When more than one of
these central modules is used
a 923A/923C coordinator is
required (see page 4/30).
S5-155H
One CPU 948R can be used
per central controller.
Two 135/155U central controlĆ
lers are required for a
S5Ć155H programmable conĆ
troller.
Power supply chassis
Redundant twoĆoutĆofĆthree
fan concept;
Should one fan cease operĆ
ating the speed of the other
fans is increased thus enabĆ
ling the programmable conĆ
troller to continue operation.
The defective fan can be reĆ
placed while the controller is
in operation
Redundant oneĆoutĆofĆtwo
battery concept;
In the case of a failure of the
main battery (Li battery) the
accu battery switches on
automatically for a period of
three weeks
Mains buffering to NAMUR:
20 ms
Enhanced electromagnetic
compatibility (EMC)
4/127
SIMATIC S5Ć135U, S5Ć155U/H
Central controllers/Expansion units
135U/155U central controller (continued)
Design
Possible configurations S5Ć135U/155U
Note the respective slot requirements of the modules!
Slot No.
3
11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163
923 A/C coordinator
CPU 922, CPU 928A, CPU 928B
CPU 948
IM 300Ć5, IM 301Ć5 interface modules2)
IM 300Ć3, IM 301Ć3, IM 304, IM 308, IM 308ĆB
interface modules
IM 308ĆC, IM 3071) interface modules
Digital input modules, digital output modules
Analog input modules, analog output modules
Intelligent I/O modules
For slot assignment, see Section 11
Communications processors3)
For slot assignment, see Section 11
Hardware interrupt processing
PG MUX function via 923C coordinator
Floating operation
1) Jumper selection on the IM 307 must be observed.
Interrupt transfer is only possible on slots 107 to 131.
2) In the case of 135U with Order No. 6ES5 135Ć3UA42 only slot 163.
3) Note the functions given in the lower half of the table.
Possible configurations of the S5Ć155H
Note the respective slot requirements of the modules!
Slot No.
3
11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163
CPU 946R4)
Communications processor6)
For slot assignment, see Section 11
Intelligent I/O modules
For slot assignment, see Section 11
IM 301Ć3, IM 304Ć3, IM 308Ć3, IM 308ĆB
interface modules
IM 300Ć5, IM 301Ć5 interface modules
IM 304 or IM 342R interface module for linking
the central controllers7)
Digital input modules5), digital output modules
Analog input modules, analog output modules
IM 308ĆC, IM 307
4)
5)
6)
7)
Occupied slots.
Redundant operation of digital input modules is not possible with an input voltage of 115/230 V AC.
The space requirements for the separate modules must be taken into account.
Subunit A with IM 324R, subunit B with IM 304.
4/128
Siemens ST 50 · 1998
SIMATIC S5Ć135U, S5Ć155U/H
Central controllers/Expansion units
135U/155U central controller (continued)
Principle of operation
Ordering data
135U/155U central controller
without CPU, without backup
battery, with power supply
230/120 V AC, 5 V/18 A,
15V/0.5 A, 24 V/1 A1)
230/120 V AC; 5 V/40 A,
15 V/2 A, 24 V/2.8 A
24 V DC; 5 V/18 A,
15 V/0.5 A, 24 V/1 A
24 V DC; 5 V/40 A,
15 V/2 A, 24 V/2.8 A1)
135U central controller
without CPU, without backup
battery
24 V DC; 5 V/10 A
Multiprocessor operation
When using several CPUs,
every single one processes
the tasks assigned to it indeĆ
pedently from the others. EvĆ
ery CPU features its own user
program memory, own time
and count cells and own bit
memories.
In a time sharing process the
coordinator assigns the acĆ
cess to the internal S5 bus
cyclically to the individual
CPUs. Thus, data collision on
the bus is prevented.
Additionally, the coordinator is
the intermediate memory for
the communication of the
CPUs with each other. Two alĆ
ternatives are available for
that:
The coupling bit memory exĆ
change for small amounts of
data suppored by the sysĆ
tem program of the CPUs
The multiprocessor commuĆ
nication for large amounts of
data
Order No.
Order No.
Backup battery (lithium battery)
6EW1 000-7AA
To be ordered as a separate item:
S5-135U/155U system manual
see page 4/155
Additional manuals
see page 4/155
6ES5 188-3UA22
Replaceable fan
6ES5 988-3NB41
6ES5 188-3UA32
Accessories, spare parts
see page 4/155
6ES5 188-3UA12
6ES5 188-3UA52
6ES5 135-3UA42
1) Also for S5Ć155H
Siemens ST 50 · 1998
4/129
SIMATIC S5Ć135U, S5Ć155U/H
Central controllers/Expansion units
155H central controller
The ZG155H central controller
is suitable for building a comĆ
plete S5-155H programmable
controller in a module subĆ
rack.
Application
Design
The central controller 155H is
a module subrack divided into
two halves. It has
10 slots (left half)
11 slots (right half)
Of these slots two each are
used for the power supply,
two for the CPU and one for
the IM 324R/IM 304.
Five (left half) or six (right
half) free slots are therefore
available.
The 155H is supplied with two
24V DC; 5V,14A power supĆ
plies and a fan subassembly.
One or two backup batteries
per power supply can also be
ordered to back up the CPU
(redundant backup).
Possible configurations of S5Ć155H
(redundant configuration)
Pay attention to the number of slots required!
Slot
3
11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163
Power supplies
CPU 948R/RL
Communications processor
Signal preprocessing modules
Interface modules IM 304, IM 324 R
Interface module IM 304
Interface module IM 308
Digital inputs/outputs
Analog inputs/outputs
Ordering data
Order No.
155H central controller
without CPU; without backup batĆ
tery, with two power supplies
24 V DC; 5 V/14 A
6ES5 188-3UH31
Backup battery
6ES7 971-0BA00
4/130
Order No.
To be ordered as a separate
item:
S5-155H manual
(with description of the 155H)
see Page 4/155
Other manuals
see Page 4/155
Accessories, parts
see Page 4/155
Siemens ST 50 · 1998
SIMATIC S5Ć135U, S5Ć155U/H
Central controllers/Expansion units
183U expansion unit
The 183U expansion unit is
designed for centralized and
distributed connection to cenĆ
tral controllers. It is also suitĆ
able for the centralized conĆ
nection to distributed
expansion units for S5Ć135U
and S5Ć155U.
Application
Design
The 183U expansion unit
comprises:
21 free slots
1 builtĆin power supply
chassis with fans
The 183U can be centrally
connected to the central
controller or to other expanĆ
sion units with the IM 312 inĆ
terface module. In addition
the 183U can be connected
distributed to central controlĆ
lers with the IM 310,
IM 314, IM 317 and IM 318 inĆ
terface modules.
A hardware interrupt is not
possible in the 183U expanĆ
sion unit. No battery backup
is provided for the RAM.
Possible configurations
Note the respective slot requirements of the modules!
Slot No.
3
11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163
IM 300 interface module
IM 310, IM 314, IM 317 or IM 318 interface modules
IM 312Ć3 interface module
Digital input modules, digital output modules
Analog input modules, analog output modules
Intelligent I/O modules
For slot assignment, see Section 11
313 monitoring module
Ordering data
183U expansion unit
with power supply
230/120 V AC; 5 V/18 A,
15 V/0.5 A, 24 V/1 A
24 V DC; 5 V/18 A, 15 V/0.5 A,
24 V/1 A
Siemens ST 50 · 1998
Order No.
Order No.
6ES5 183-3UA13
6ES5 183-3UA22
To be ordered as a separate item:
S5-135U/155U system manual
see page 4/155
Additional manuals
see page 4/155
Accessories, spare parts
see page 4/155
4/131
SIMATIC S5Ć135U, S5Ć155U/H
Central controllers/Expansion units
184U expansion unit
The 184U expansion unit is
designed for the centralized
connection to central controlĆ
lers and expansion units with
power supply chassis for
S5Ć135U and S5Ć155U.
Application
Design
The 184U expansion unit
comprises:
21 free slots
1 fan subassembly
The 184U can be centrally
connected to the central conĆ
troller or to other expansion
units by using the IM 312 inĆ
terface module.
A power supply chassis is not
required because the expanĆ
sion unit is supplied via the
connecting cable for the
IM 312Ć5 interface module.
A hardware interrupt is not
possible in the expansion
unit. Modules with RAM bakĆ
kup cannot be implemented
because there is no battery
backup for the supply volĆ
tage.
Possible configurations
Note the respective slot requirements of the modules!
Slot No.
3
11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163
IM 312Ć5 interface module
Digital input modules, digital output modules
Analog input modules, analog output modules
For slot assignment, see Section 11
Intelligent I/O modules
313 monitoring module
Ordering data
184U expansion unit
without power supply
With 230/120 V AC fan
With 24 V DC fan
4/132
Order No.
Order No.
6ES5 184-3UA11
6ES5 184-3UA21
To be ordered as a separate item:
S5-135U/155U system manual
see page 4/155
Additional manuals
see page 4/155
Accessories, spare parts
see page 4/155
Siemens ST 50 · 1998
SIMATIC S5Ć135U, S5Ć155U/H
Central controllers/Expansion units
EG 185U expansion unit
The EG 185U expansion unit
is suitable for the distributed
connection to central controlĆ
lers and other expansion units
S5Ć135U/155U. In addition,
the EG 185U makes switched
I/O design possible in the
case of the faultĆtolerant
S5Ć155H programmable conĆ
troller.
Application
Design
The EG 185U expansion unit
comprises:
21 free slots
1 builtĆin power supply
chassis with fans
The EG 185U can be conĆ
nected distributed to central
controllers or other expansion
units with the IM 314, IM 317
and IM 318 interface modĆ
ules.
All intelligent I/O modules (IP)
and communications procesĆ
sors (CP) can be connected
in the EG 185U.
Up to 8 communications proĆ
cessors can be programmed
via an interface if a 923C
coordinator is used.
A hardware interrupt is not
possible in the EG 185U exĆ
pansion unit. A backup batĆ
tery is provided for the RAM.
,
Possible configurations when connected
to S5Ć135U, S5Ć155U
Note the respective slot requirements of the modules!
Slot No.
3
11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163
923 C coordinator
IM 300Ć5 interface module
IM 314, IM 317 or IM 318 interface modules
IM 308ĆA interface module
Digital input modules, digital output modules
Analog input modules, analog output modules
Intelligent I/O modules
Communications processors
For slot assignment, see Section 11
Steckplatzbelegungen siehe Katalogteil ??
For slot assignment, see Section 11
IM 314R interface module (for the S5Ć155H)
313 monitoring module
Siemens ST 50 · 1998
4/133
SIMATIC S5Ć135U, S5Ć155U/H
Central controllers/Expansion units
185U expansion unit (continued)
Design (continued)
Possible configurations when connected
to S5Ć155H
Note the respective slot requirements of the modules!
Slot No.
3
11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163
IM 300Ć5C, IM 308 interface modules;
313 monitoring module
IM 314R interface module
Digital input modules, digital output modules
Analog input modules, analog output modules
Intelligent I/O modules
For slot assignment, see Section 11
Communications processors
For slot assignment, see Section 11
IM 308ĆC interface modules1)
1) Operation in EU only in combination with S5Ć155H
Ordering data
185U expansion unit
with power supply,
without backup battery
230/120V AC; 5V/18A,
15V/0.5A, 24V/1A
230/120V AC; 5V/40A, 15V/2A,
24V/2.8A
24V DC; 5V/18A, 15V/0.5A,
24V/1A
24V DC; 5V/40A, 15V/2A,
24V/2.8A
Backup battery (lithium battery)
4/134
Order No.
Order No.
6ES5 185-3UA13
To be ordered as a separate item:
S5-135U/155U system manual
see page 4/155
Additional manuals
see page 4/155
Accessories, spare parts
see page 4/155
6ES5 185-3UA33
6ES5 185-3UA23
6ES5 185-3UA43
6EW1 000-7AA
Siemens ST 50 · 1998
SIMATIC S5Ć135U, S5Ć155U/H
Central controllers/Expansion units
187U expansion unit
The 187U expansion unit is
designed for the centraĆlized
connection to central controlĆ
lers and expansion units with
power supply chassis for
S5Ć135U and S5Ć155U.
Application
Design
The 187U expansion unit
comprises:
11 free slots
A power supply chassis, fan
and wiring duct are not availĆ
able.
The 187U expansion unit can
be centrally connected to
central controllers or other exĆ
pansion units with the IM 312
interface module.
The power supply is delivered
by the connecting cable of the
IM 312Ć5 interface module.
A hardware alarm is not posĆ
sible in the 187U expansion
unit. No battery backup is
provided for the RAM.
Possible configurations
Note the respective slot requirements of the modules!
Slot No.
3
11 19
27 35
43 51 59 67 75 83
91 99 107 115 123 131 139 147 155 163
IM 312Ć5 interface module
Digital input modules, digital output modules
Analog input modules, analog output modules
313 monitoring module
Ordering data
Order No.
187U expansion unit
6ES5 187-5UA11
To be ordered as a separate item:
S5-135U/155U system manual
Siemens ST 50 · 1998
see page 4/155
Order No.
Additional manuals
see page 4/155
Accessories, spare parts
see page 4/155
4/135