OC279---1.qxp
02.5.29 2:26 PM
Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
2002
No. OC279
TECHNICAL & SERVICE MANUAL
Series PMH Ceiling Cassettes R407C
Indoor unit
[Model names]
[Service Ref.]
PMH-P1BA2
PMH-P1.6BA2
PMH-P2BA2
PMH-P1BA
PMH-P1.6BA
PMH-P2BA
• This service manual
describes change points and
parts list.
Please refer to the OC238
REVISED EDITION-B as to
excluding this manual.
CONTENTS
1. TECHNICAL CHANGES ·····································3
2. SPECIFICATIONS ···············································4
3. WIRING DIAGRAM·················································7
4. PARTS LIST ························································8
INDOOR UNIT
CENTRALLY CONTROLLED
ON
1Hr.
OFF
CLOCK
CHECK
FILTER
CHECK MODE
TEST RUN
˚C
STAND BY
DEFROST
ERROR CODE
TEMP.
NOT AVAILABLE
FUNCTION
ON/OFF
REMOTE CONTROLLER
OC279---1.qxp
02.5.29 2:26 PM
Page 2
OC279---1.qxp
02.5.29 2:26 PM
1
Page 3
TECHNICAL CHANGES
● The width dimension of indoor unit on SPECIFICATIONS is wrong.
812(32) is the correct dimension.
W
mm(in.)
UNIT : 854(33-5/8) PANEL : 1000(39-3/8)
Dimensions
W
mm(in.)
UNIT : 812(32)
➔
Dimensions
PANEL : 1000(39-3/8)
● The compressor’s model name of outdoor unit for PUH-P2YGAA.UK on the SPECIFICATIONS page is wrong.
NE36YEJM is the correct model name
NE38YEJM
➔
PMH-P1BA1
➔
PMH-P1.6BA1 ➔
PMH-P2BA1
➔
NE36YEJM
PMH-P1BA2
PMH-P1.6BA2
PMH-P2BA2
● INDOOR CONTROLLER BOARD (I.B) has changed.
[T7W E13 310]
➔
[T7W E26 310]
● DRAIN PAN ASSY has changed.
➔
[R01 E10 529]
[R01 E04 529]
3
OC279---1.qxp
2
02.5.29 2:26 PM
Page 4
SPECIFICATIONS
Service Ref.
Item
Function
PMH-P1BA2
Cooling
10,700
3,150
1.15
Btu/h
W
kW
Capacity
Heating
11,600
3,400
1.06
REFRIGERANT PIPING
OUTDOOR UNIT
INDOOR UNIT
Total input
Service Ref.
PMH-P1BA2
Power supply(phase, cycle, voltage)
Single Phase, 50Hz, 220-230-240V
kW
0.04
Input
0.04
A
Running current
0.19
0.19
A
Starting current
0.21
0.21
External finish
Unit : Galvanized sheets with gray heat insulation, Grille munsell 0.98Y 8.99/0.63
Heat exchanger
Plate fin coil
Fan
Fan(drive) x No.
Lineflow fan (direct) x 1
kW
Fan motor output
0.028
Airflow(Lo - Mi2 - Mi1 - Hi) K/min(CFM)
6.3-6.8-7.6-8.4(222-240-268-297)
Pa(mmAq)
External static pressure
0(direct blow)
Operation control & Thermostat
Remote controller & built-in
dB
Noise level(Lo - Mi2 - Mi1 - Hi)
29-31-33-35
mm(in.)
Unit drain pipe I.D.
26(1)
mm(in.)
Dimensions
W
UNIT : 812(32)
PANEL : 1000(39-3/8)
mm(in.)
D
UNIT : 395(15-9/16) PANEL : 470(18-1/2)
mm(in.)
H
UNIT : 230(9-1/16) PANEL : 30(1-3/16)
kg(lbs)
Weight
UNIT : 14(31)
PANEL : 3.0(6.6)
Service Ref.
PUH-P1VGAA.UK
Power supply (phase, cycle, voltage)
Single Phase, 50Hz,
220-230-240V
A
Running current
4.92
4.52
A
Starting current
30
External finish
Munsell 5Y 7/1
Refrigerant control
Linear Expansion Valve
Compressor
Hermetic
Model
RE189VHSMT
kW
Motor output
0.85
Starter type
Line start
Protection devices
Inner thermostat, HP switch, Discharge thermo.
W
Crankcase heater
30
Heat exchanger
Plate fin coil
Fan
Fan(drive) x No.
Propeller (direct) x 1
kW
Fan motor output
0.070
K/min(CFM)
Airflow
45(1,590)
Defrost method
Reverse cycle
dB
Noise level
46
Cooling
dB
48
Heating
mm(in.)
Dimensions
900(35-7/16)
W
mm(in.)
330+20(13+3/4)
D
mm(in.)
650(25-5/8)
H
kg(lbs)
Weight
50(110)
Refrigerant
R407C
kg(lbs)
Charge
1.7(3.7)
L
Oil (Model)
0.57(Ester)MEL56
mm(in.)
Liquid
Pipe size O.D.
6.35(1/4)
mm(in.)
Gas
12.7(1/2)
Indoor side
Connection method
Flared
Outdoor side
Flared
Height difference
Between the indoor &
Max. 30m
Piping length
outdoor unit
Max. 30m
Notes1. Rating Conditions (ISO T1)
Cooling····Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F)
Heating····Indoor : D.B. 20˚C(68˚F)
Refrigerant piping length (one way) : 5m (16ft)
Outdoor
Outdoor
2. Guaranteed operating range
Cooling Upper limit
Lower limit
Upper limit
Heating
Lower limit
Indoor
D.B. 35˚C W.B. 22.5˚C
D.B. 19˚C W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C W.B. 18˚C
D.B. -11˚C W.B. -12˚C
4
: D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
: D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
3. Above data based on indicated voltage
Indoor Unit
Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz
OC279---1.qxp
02.5.29 2:26 PM
Page 5
Service Ref.
Item
Function
PMH-P1.6BA2
Cooling
15,000
4,400
1.65
Btu/h
W
kW
Capacity
Heating
17,100
5,000
1.70
REFRIGERANT PIPING
OUTDOOR UNIT
INDOOR UNIT
Total input
Service Ref.
PMH-P1.6BA2
Power supply(phase, cycle, voltage)
Single Phase, 50Hz, 220-230-240V
kW
0.06
Input
0.06
A
Running current
0.29
0.29
A
Starting current
0.32
0.32
External finish
Unit : Galvanized sheets with gray heat insulation, Grille munsell 0.98Y 8.99/0.63
Heat exchanger
Plate fin coil
Fan
Fan(drive) x No.
Lineflow fan (direct) x 1
kW
Fan motor output
0.028
Airflow(Lo - Mi2- Mi1 - Hi) K/min(CFM)
7.0-8.0-9.0-10.0(247-282-318-353)
Pa(mmAq)
External static pressure
0(direct blow)
Operation control & Thermostat
Remote controller & built-in
dB
Noise level(Lo - Mi2 - Mi1 - Hi)
34-36-38-40
mm(in.)
Unit drain pipe I.D.
26(1)
mm(in.)
Dimensions
W
UNIT : 812(32)
PANEL : 1000(39-3/8)
mm(in.)
D
UNIT : 395(15-9/16) PANEL : 470(18-1/2)
mm(in.)
H
UNIT : 230(9-1/16) PANEL : 30(1-3/16)
kg(lbs)
Weight
UNIT : 14(31)
PANEL : 3.0(6.6)
Service Ref.
PUH-P1.6VGAA.UK PUH-P1.6YGAA.UK PUH-P1.6VGAA.UK PUH-P1.6YGAA.UK
Single Phase, 50Hz, 3 phase, 50Hz, Single Phase, 50Hz, 3 phase, 50Hz,
Power supply (phase, cycle, voltage)
220-230-240V 380-400-415V(4wires) 220-230-240V 380-400-415V(4wires)
7.36
7.59
2.49
2.56
A
Running current
36
20
20
36
A
Starting current
External finish
Munsell 5Y 7/1
Refrigerant control
Linear Expansion Valve
Compressor
Hermetic
RE277VHSMT
RE277YFKM
RE277YFKM
RE277VHSMT
Model
kW
Motor output
1.3
Starter type
Line start
w1
w2
w2
w1
Protection devices
W
Crankcase heater
30
Heat exchanger
Plate fin coil
Fan
Fan(drive) x No.
Propeller (direct) x 1
kW
Fan motor output
0.070
K/min(CFM)
Airflow
45(1,590)
Defrost method
Reverse cycle
dB
Noise level
47
Cooling
dB
49
Heating
mm(in.)
Dimensions
900(35-7/16)
W
mm(in.)
330+20(13+3/4)
D
mm(in.)
650(25-5/8)
H
kg(lbs)
54(119)
Weight
R407C
Refrigerant
kg(lbs)
2.5(5.5)
Charge
L
0.57(Ester)MEL56
Oil (Model)
mm(in.)
9.52(3/8)
Liquid
Pipe size O.D.
mm(in.)
15.88(5/8)
Gas
Indoor side
Flared
Connection method
Outdoor side
Flared
Height difference
Max. 40m
Between the indoor &
Piping length
Max. 40m
outdoor unit
Notes1. Rating Conditions (ISO T1)
Cooling····Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F)
Heating····Indoor : D.B. 20˚C(68˚F)
Refrigerant piping length (one way) : 5m (16ft)
Outdoor
Outdoor
2. Guaranteed operating range
Cooling Upper limit
Lower limit
Upper limit
Heating
Lower limit
Indoor
D.B. 35˚C W.B. 22.5˚C
D.B. 19˚C W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C W.B. 18˚C
D.B. -11˚C W.B. -12˚C
w1: Inner thermostat, HP switch, Discharge thermo.
w2: Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
5
: D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
: D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
3. Above data based on indicated voltage
Indoor Unit
Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz
3 phase 415V 50Hz
OC279---1.qxp
02.5.29 2:26 PM
Page 6
Service Ref.
Item
Function
PMH-P2BA2
Cooling
18,400
5,400
2.35
Btu/h
W
kW
Capacity
Heating
21,450
6,250
2.42
REFRIGERANT PIPING
OUTDOOR UNIT
INDOOR UNIT
Total input
Service Ref.
PMH-P2BA2
Power supply(phase, cycle, voltage)
SinglePhase, 50Hz, 220-230-240V
kW
0.06
Input
0.06
A
Running current
0.29
0.29
A
Starting current
0.32
0.32
External finish
Unit : Galvanized sheets with gray heat insulation, Grille munsell 0.98Y 8.99/0.63
Heat exchanger
Plate fin coil
Fan
Fan(drive) x No.
Lineflow fan (direct) x 1
kW
Fan motor output
0.028
Airflow(Lo - Mi2 - Mi1 - Hi) K/min(CFM)
8.0-9.0-10.0-11.0(282-318-353-388)
Pa(mmAq)
External static pressure
0(direct blow)
Operation control & Thermostat
Remote controller & built-in
dB
Noise level(Lo - Mi2 - Mi1 - Hi)
36-38-40-42
mm(in.)
Unit drain pipe I.D.
26(1)
mm(in.)
Dimensions
W
UNIT : 812(32)
PANEL : 1000(39-3/8)
mm(in.)
D
UNIT : 395(15-9/16) PANEL : 470(18-1/2)
mm(in.)
H
UNIT : 230(9-1/16) PANEL : 30(1-3/16)
kg(lbs)
Weight
UNIT : 14(31)
PANEL : 3.0(6.6)
Service Ref.
PUH-P2VGAA.UK PUH-P2YGAA.UK PUH-P2VGAA.UK PUH-P2YGAA.UK
Single Phase, 50Hz, 3 phase, 50Hz, Single Phase, 50Hz, 3 phase, 50Hz,
Power supply (phase, cycle, voltage)
220-230-240V 380-400-415V(4wires) 220-230-240V 380-400-415V(4wires)
10.26
10.57
3.70
3.82
A
Running current
31
31
62
62
A
Starting current
External finish
Munsell 5Y 7/1
Refrigerant control
Linear Expansion Valve
Compressor
Hermetic
NE36YEJM
NE36YEJM
NE36VMJMT
NE36VMJMT
Model
kW
Motor output
1.6
Starter type
Line start
w2
w2
w1
w1
Protection devices
W
Crankcase heater
38
Heat exchanger
Plate fin coil
Fan
Fan(drive) x No.
Propeller (direct) x 1
kW
Fan motor output
0.070
K/min(CFM)
Airflow
55(1,940)
Defrost method
Reverse cycle
dB
Noise level
48
Cooling
dB
50
Heating
mm(in.)
Dimensions
900(35-7/16)
W
mm(in.)
330+20(13+3/4)
D
mm(in.)
855(33-5/8)
H
kg(lbs)
74(163)
Weight
R407C
Refrigerant
kg(lbs)
2.6(5.7)
Charge
L
1.2(Ester)MEL56
Oil (Model)
mm(in.)
9.52(3/8)
Liquid
Pipe size O.D.
mm(in.)
15.88(5/8)
Gas
Indoor side
Flared
Connection method
Outdoor side
Flared
Height difference
Max. 40m
Between the indoor &
Piping length
Max. 40m
outdoor unit
Notes1. Rating Conditions (ISO T1)
Cooling····Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F)
Heating····Indoor : D.B. 20˚C(68˚F)
Refrigerant piping length (one way) : 5m (16ft)
Outdoor
Outdoor
2. Guaranteed operating range
Cooling Upper limit
Lower limit
Upper limit
Heating
Lower limit
Indoor
D.B. 35˚C W.B. 22.5˚C
D.B. 19˚C W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C W.B. 18˚C
D.B. -11˚C W.B. -12˚C
w1: Inner thermostat, HP switch, Discharge thermo.
w2: Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
6
: D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
: D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
3. Above data based on indicated voltage
Indoor Unit
Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz
3 phase 415V 50Hz
OC279---1.qxp
02.5.29 2:26 PM
3
Page 7
WIRING DIAGRAM
PMH-P1BA2, PMH-P1.6BA2, PMH-P2BA2
[LEGEND]
DP
DS
MF
MV
TB4
TB5
TH1
TH2
TH5
NOTES:
1.Since the outdoor side electric wiring may change be sure to check
the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities, make
wiring matching terminal numbers (S1, S2, S3).
3.Symbols used in wiring diagram above are,
:Connector, :Terminal (block).
NAME
INDOOR CONTROLLER BOARD
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
FUSE (6.3A, 250V)
POWER SUPPLY (I.B)
POWER SUPPLY (R.B)
TRANSMISSION (INDOOR-OUTDOOR)
JUMPER WIRE (MODEL SELECTION)
JUMPER WIRE (CAPACITY CODE)
SWITCH (EMERGENCY OPERATION)
TRANSFORMER
RELAY (DRAIN PUMP)
VARISTOR
REMOTE CONTROLLER BOARD
CONNECTOR (PROGRAM TIMER)
TERMINAL BLOCK
(REMOTE CONTROLLER TRAMSMISSION LINE)
DRAIN-UP MACHINE
DRAIN SENSOR
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
Please set the voltage using the remote controller.
For the setting method, please refer to the indoor unit Installation Manual.
<w1>
Manufacture
MODELS
Service board
1 2 3 4 5
ON
OFF
SW1 PMH-P1/1.6/2BA2
J11 J12 J13 J14 J15
1 2 3 4
ON
OFF
PMH-P1BA2
J21 J22 J23 J24
1 2 3 4
ON
OFF
SW2 PMH-P1.6BA2
J21 J22 J23 J24
1 2 3 4
PMH-P2BA2
ON
OFF
J21 J22 J23 J24
OUTDOOR UNIT
S1
S2
S3
TERMINAL BLOCK
(REMOTE CONTROL TRANSMISSION LINE)
ROOM TEMPERATURE THERMISTOR
(0°C/15K", 25°C/5.4K" DETECT)
TB4
S1
S2
S3
PIPE TEMPERATURE THERMISTOR/LIQUID
(0°C/15K", 25°C/5.4K" DETECT)
<PUH-P1, 1.6, 2VGAA.UK>
POWER SUPPLY
~(1PHASE)
220 - 230 - 240V 50Hz
L
N
TB1
S1
S2
S3
<PUH-P1.6, 2YGAA.UK>
POWER SUPPLY
3N~(3PHASE 4WIRES)
380 - 400 - 415V 50Hz
L1
L2
L3
N
TB1
CONDENSER/EVAPORATOR TEMPERATURE
THERMISTOR (0°C/15K", 25°C/5.4K" DETECT)
R.B
TB5
MF
BLU
BLU
SYMBOL
I.B
CN2L
CN32
CN41
FUSE
LED1
LED2
LED3
SW1
SW2
SWE
T
X1
ZNR
R.B
CN2
TB6
5
I.B
2
1 TRANSMISSION WIRES DC12V
2 1
LED1
CN90
CN32
REMOTE
CONTROLLER
CN22
(BLU)
6 5 4 3 2 1
FAN
(WHT)
LED2
BRN
ORN
YLW
BLU
BLU
3
2
1
INTAKE
CN20
(RED)
2
1
LIQUID
CN21
(WHT)
2
1
PIPE
CN29
(BLK)
2
1
VANE
CN6V
(WHT)
6
5
4
3
2
1
5
3
1
POWER FUSE
CN03
(RED)
DP
D.SENSOR
CN31
(WHT)
ZNR
1
3
D.U.M
CNP
(YLW)
CN2
1 2
TB6
BLK
BLK
DS
BLK
BLK
TH1
BLK
BLK
TH2
BLK
BLK
TH5
BRN
RED
ORN
YLW
GRN
1
2
3 MV
4
5
T
X1
X1
LED3
CN41
CN2L
ON
SW1
J24
J23
J22
J21
J15
J14
J13
J12
J11
OFF
SWE
SW2
7
See fig : w1
OC279---1.qxp
4
02.5.29 2:26 PM
Page 8
PARTS LIST
PANEL PARTS
PMH-P1BA2
PMH-P1.6BA2
PMH-P2BA2
11
12
11
2
3
4
1
5
2
3
4
10
5
6
9
13
7
CENTRALLY CONTROLLED
ON
1Hr.
OFF
CLOCK
CHECK
FILTER
CHECK MODE
TEST RUN
˚C
STAND BY
DEFROST
ERROR CODE
TEMP.
NOT AVAILABLE
FUNCTION
ON/OFF
8
14
No.
Part No.
Part Name
Q'ty/set
Price
Wiring RecomRemarks
PMH-P1,1.6,2
Diagram mended
Specification
(Drawing No.) Symbol Q'ty
Unit Amount
BA2
1
T7W E11 003 AIR OUTLET GRILLE
1
2
R01 E00 055 LATCH
2
3
—
HANGER
2
4
R01 E00 099 PANEL HOOK
2
5
R01 E01 054 GRILLE CATCH
2
6
R01 E01 500 LL.FILTER
1
7
R01 E02 500 LL.FILTER
1
8
T7W E01 691 INTAKE GRILLE
1
9
R01 E00 054 GRILLE CATCH
2
10 R01 E00 648 RECEIVER COVER
1
11 R01 E00 044 MAGNET
2
12 R01 E00 096 SCREW CAP
1
13 T7W E06 713 REMOTE CONTROLLER
1
14 T7W A00 305 REMOTE CONTROLLER CABLE
1
8
(DT88D360H03)
OC279---1.qxp
02.5.29 2:26 PM
Page 9
FUNCTIONAL PARTS
PMH-P1BA2
PMH-P1.6BA2
PMH-P2BA2
24
23
1
SLEEVE
BEARING
2
22
3
21
4
20
19
16
5
15 VANE MOTOR
6
VANE
SLEEVE
17 18
14
7
/ EVAPORATOR
13 CONDENSER
TEMPERATURE THERMISTOR
8
12
PIPE TEMPERATURE
THERMISTOR / LIQUID
9
ROOM
TEMPERATURE
THERMISTOR
11
10
Part number that is circled is not shown in the figure.
No.
Part No.
1
2
3
4
5
6
7
—
—
R01 22A 102
R01 005 103
R01 E02 114
R01 E00 079
R01 E00 092
T7W E69 480
T7W E70 480
R01 E10 529
R01 E00 202
R01 E00 038
R01 E41 202
R01 E44 202
R01 E01 002
R01 E01 223
R01 E00 110
R01 31K 241
R01 E01 266
T7W E02 355
R01 E00 130
R01 E03 220
R01 E01 105
R01 E00 527
—
R01 E01 673
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Q'ty/set
Price
Wiring RecomRemarks
Diagram mended
Specification PMH-P·BA2 (Drawing
No.) Symbol Q'ty
Unit Amount
1 1.6 2
1 1 1 (DT00A478G78)
CABINET
1 1 1 (RG02L277H02)
COVER
1 1 1
BEARING MOUNT
1 1 1
SLEEVE BEARING
1 1 1
LINE FLOW FAN
1 1 1
STABILIZER ASSY
1 1 1
VANE SLEEVE
1
HEAT EXCHANGER
1 1
HEAT EXCHANGER
1 1 1
DRAIN PAN ASSY
TH1
1 1 1
ROOM TEMPERATURE THERMISTOR
1 1 1
GUIDE VANE
TH2
1 1 1
PIPE TEMPERATURE THERMISTOR / LIQUID
TH5
1
1
1
CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR
1 1 1
VANE
MV
1 1 1
VANE MOTOR
1 1 1
CASING ASSY
1 1 1
SENSOR HOLDER
DS
1 1 1
DRAIN SENSOR
DP
1
1
1
DRAIN PUMP
1 1 1
MOTOR SUPPORT
MF
1 1 1
FAN MOTOR
1 1 1
MOTOR MOUNT
1 1 1
DRAIN PIPE
1 1 1 (RG00L311G13)
CONTROL BOX COVER
1 1 1
SCREW ASSY
Part Name
9
OC279---1.qxp
02.5.29 2:26 PM
Page 10
ELECTRICAL PARTS
PMH-P1BA2
PMH-P1.6BA2
PMH-P2BA2
5
1
4
2
3
Q'ty/set
No.
Part No.
1
—
Part Name
CONTROL BOX
Price
Wiring RecomRemarks
Specification PMH-P1,1.6,2 (Drawing No.) Diagram mended
Unit Amount
Symbol Q'ty
BA2
(RG02B337G10)
1
2
T7W E13 716 TERMINAL BLOCK
3P (S1, S2, S3)
1
TB4
3
T7W 515 716 TERMINAL BLOCK
2P (1, 2)
1
TB5
4
T7W 520 239 FUSE
250V 6.3A
1
FUSE
5
T7W E26 310 INDOOR CONTROLLER BOARD
1
I.B
10
OC279---1.qxp
02.5.29 2:26 PM
Page 11
OC279---1.qxp
02.5.29 2:26 PM
Page 12
TM
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
cCopyright 2002 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in May 2002 No. OC279 247
Made in Japan
New publication, effective May 2002