MAKING MODERN LIVING POSSIBLE
One Product – Numerous Applications
Electronic Controllers for Heating, Cooling,
Ventilation and Air Condition
Electronic Controllers from Danfoss:
Only a Few Products for an Endless Number
of Applications
The ECL Comfort and ECL Apex 10
product ranges consist of electronic
controllers for temperature control in
heating and domestic hot water (DHW)
systems. The controllers ensure a high
comfort level and optimum energy
utilization.
The components of ECL Comfort
The ECL Comfort range consists of ECL
Comfort 100, 200 and 300 – each in an
elegant and timeless design.
ECL Comfort 100 is the choice for
simple heating systems, for which the
installer or user prefers the traditional,
plain and analog operation.
ECL Comfort 200 appeals to users
who prefer a digital user interface
and the increased number of options
this provide. The series offers many
functional options and can be used
for commercial installations.
ECL Comfort 300 is the advanced
controller with a large number of
functions, such as: Two control circuits
+ thermostatic function, optimizer
function, 3 point control, LON
communication etc. The intelligent
card concept ensures optimum
user-friendliness of this advanced
controller.
2
The range also comprises an elegantly
designed remote control in two
versions, which is connected to the
controller via a two-wire cable.
ECL Comfort
– The future is in the Cards
The ECL Comfort range and its
advanced chip card not only meet
your present demands but also the
future requirements you might have
for heating control.
With ECL Comfort 300 new demands
are covered by new cards with new
settings. The few basic models and
the large variety of ECL Cards give you
a considerably better and quicker
overview of the unique application
opportunities offered by the ECL
Comfort range.
Some advantages of ECL Comfort:
Optimizer and boost function
Return temperature limitation
based on outdoor temperature
Frost protection
Heating cut–out function
Year clock and automatic changeover between summer and winter
time
Copy function to/from the
intelligent ECL Card
Anti-bacteria function (DHW circuit)
Communication via the
standardized LonTalk Protocol,
RS 232, and M-bus options
By means of the chosen card, it is easy
to set the controller and simple to
change the factory settings precisely
to the relevant type of system and
required settings.
The schedule in the ECL Comfort can
be programmed for each day in the
week. The building will be heated in
the comfort periods you request. This
is environmentally sound and saves
money.
3
Flexibility and Easy Operation
Auto tuning and motor protection
A precondition for a well functioning
heating system is that the correct
settings are made before it is put
to use. Adjustments are necessary
to preset the control parameters.
Presetting gives the following benefits:
A high degree of comfort
The introduction of automatic setting
of control parameters on the controller
itself, i.e. auto tuning and motor
protection, gives optimum control
of the DHW system. This ensures a
high degree of comfort, stable control
during idle operation and, subsequently,
longer motor life.
The setting of control parameters can
thus be reduced to one simple and
reliable procedure. Auto tuning is
especially necessary in DHW systems.
Improved protection against lime
deposits in DHW heat exchangers
All applications, updates and other
information are placed on the Danfoss
Heating Portal from where it can be
downloaded.
Remote service possibilities with
WebAccess
The WebAccess makes your ECL
Comfort 200 and 300 accessible via
Internet or modem.
Energy saving
Long operating life
Minimum service
You can define different levels of access
going from monitoring to wide control
of parameters in the ECL controller.
Some advantages of the
ECL Apex 10:
Temperature, pressure and
flow control
The WebAccess is used in a LON network – communicating with up to
4 ECL controllers. Other components
such as energy meters can also be
monitored via the WebAccess.
Data logging facilities
Alarm functions associated to
either system, application or
monitoring failures
ECL Apex 10 – configurable controller
The ECL Apex 10 is a dedicated district
heating controller preprogrammed
with all relevant control functions and
applications. The controller is applicable
in large substations and distributor
stations and can be connected as stand
alone or in network.
Easy and cost-effective
commissioning and service;
a variety of application templates
are ready for use
Back up/restore function for
similar applications
Different user levels for simple
controlling or programming
Auto Tuning
The result of
80
Auto Tuning with ECL Comfort
Tap Water (°C)
70
• Open for the tap water to get a constant
tapping load
60
50
• Activate Auto Tuning by pushing a button
40
30
Flow Rate (m3/h)
Tap
Water Temperature (°C)
As a consequence it can be used
in supervisory control and data
acquisition systems (SCADA).
The ECL Apex 10 can be extended
with a number of modules to fit
any heating application with up to
5 circuits within heating or DHW.
Sec. Flow (m3/h)
20
10
0
4 0.00
Time (min.)
5.00
10.00
15.00
20.00
25.00
30.00
• Wait 7-25 minutes to complete the tuning
5
Advanced Controlling in a Simple User Interface
ECL Comfort displays for
end users and installers
With ECL Comfort it is possible
to control all stages of the heat
consumption – right down to the
smallest detail – and at the same
time take external factors into
account such as the outdoor
Controller mode:
Shift button:
Circuit selector:
Used to switch between manual operation,
scheduled operation, constant comfort
temperature, constant setback temperature,
and stand-by mode.
Switches between the various settings you can
change: Temperature, changeover point etc.
Switches between the heating circuit and
DHW/heating circuit.
+/- buttons:
Arrow buttons:
End user displays
Installer displays
1
B
C
1
1035
3
0
Temperature control:
This display provides a quick overview of the outdoor and indoor
temperatures, the requested comfort
temperature, and the status mode of
the system.
Adjust different values and manual operation.
Move from line to line in the menus.
temperature, the insulation of the
heated area and the radiator capacity
of the building. It is an easy task to
operate ECL Comfort 200 and 300.
You only have to push a few buttons
to enter all the settings.
3
9
12
15
18
21
24
Normal display:
This display gives you a quick overview of the time, the outdoor and
indoor temperatures, the selected
comfort periods of the day, and the
status mode of the system.
2
3
ON
ON
3
6
9
12
15
C
ON
2
3
ON
ON
10
18
65
0
1
1
1035
19
6
ON
1
18
21
30
0
14
24
Time programming:
This display informs you about the
time interval of the comfort periods
if additional and personal comfort
periods have been entered to meet
the special demands you might have.
Control of system components:
Displays a status of the pumps,
motorized valves etc. in the heating
system as well as the current system
temperatures (flow and return
temperatures).
Control of system temperature:
Here the heat curve is set – the
relationship between required
flow temperature and outdoor
temperature.
Optimum start function:
The calculation of the optimum start
and stop times includes factors such
as insulation, radiators and system
capacity to ensure that the requested
temperature is reached at the
requested time.
Adjustment of control parameters
where each parameter has a short
description and the actual value is
shown. The primary values of the
heating circuit are shown in the top
of the window.
The primary parameters and sensor
values of the heating circuit.
Overview of all circuits;
heating and DHW.
ECL Apex 10 - Flexible user
interface and control functions
The controller and its service tool can
be operated by means of a PDA or a
PC and either on-site or remotely via
modem. The service tool offer four
different user levels: supervisor, service
user, daily user and default user.
Schedule (comfort/setback)
The required flow temperature is
typically based on the outdoor
temperature (weather compensation)
but can also be influenced by:
Return temperature, flow and
energy limitation
6
Optimized time control
Boost function
Maximum and minimum flow
temperature limitation
Anti-bacteria function
(DHW circuit)
7
Select Your ECL Comfort
Card
type
ECL Comfort
100B
100M
Type
of circuit
Boiler circuit
Heating circuit
Cooling
circuit
Hot water circuit
Others
–
–
P16
A
B
C
A
B
C
1
2
3
4
5
6
7
200
1
2
3
4
5
6
7
ECL Comfort
P17
P20
P30
Room panel
ECA 60/61/62/63
An ECA room or
remote panel for
installation in your
living room or your entrance hall makes
it possible to display and override your
ECL Comfort settings remotely.
Main features:
• Mode selection
(comfort temperature, reduced
temperature, automatic operation).
• Display of time, actual outdoor and
room temperature as well as the
lowest and highest outdoor
temperature since midnight.
• Setting of desired comfort and
reduced room temperature level
• Room temperature control via
built-in room sensor.
• Setting of periods - comfort
temperature or reduced temperature
depending on whether you are
present in the building or not.
C14
C25
C35
300
A
B
C
A
B
C
1
2
3
4
5
6
7
1
2
3
4
5
6
7
ECL Comfort
C37
*1
C47
*1
C55
*1
C60/C62
C66
*1
C67
(
C75
L05
301
A
B
C
1
2
3
4
5
6
7
*1
L66
*1
L76
*2
ECL Comfort
*1: Some systems need an optional relay module (ECA 80)
*2: Only together with 'ECL Comfort 301 with ECA 83'
Select Your ECL Apex 10
Controller and extension modules
Analog inputs (AI)
Accessories for the controller
series ECL Comfort
ECL Comfort 100
ECL Comfort 200
ECL Comfort
300/301
Type
ECA 60/62, Room panel
ECL Apex 10
ECA 61/63, Remote control
24 Va.c.
SIG
1
C37/C47 1), C55 2), C75 3)
ECA 84, M-Bus module
C37/C47/C66
ECA 86, I/O and alarm option
BUS
DO4
Alarm
C66
SIG
GND
SIG
GND
9
10
11
12
SIG
GND
13
14
+12V
+5V
SHLD
SHLD
15
16
17
18
AI 8
AI 9
AI 10
11
4
4
Low voltage
(max 80 V)
High voltage
(max 260 V)
Analog
outputs (AO)
0-10 V d.c.
Module with
switches
for override of
relay outputs
AI 11
SIG
GND
SIG
GND
SIG
GND
SIG
GND
+12V
+5V
SHLD
SHLD
19
20
21
22
23
24
25
26
27
28
29
30
A B
BUS
Service Tool
Service Pin
BUS Address
8
SIG
1
2
L
3
N
L
DI 1
4
5
N
L
DI 2
6
7
N
L
DI 3
1
8
SIG
N
DI 4
4
GND
AI 2
5
SIG
SIG
GND
8
9
10
11
12
13
GND
SIG
+12V
+5V
SHLD
SHLD
SIG
GND
6
7
GND
SIG
AI 3
GND
SIG
GND
AI 4
SIG
SIG
GND
16
17
GND
SIG
GND
14
15
GND
SIG
AI 1
AI 2
SIG
GND
18
19
GND
SIG
AI 3
+12V
+5V
SHLD
8
SHLD
20
21
22
23
24
GND
+12V
+5V
SHLD
SHLD
AI 4
Comm
1
ECA-XM 102B
7
No. 087B2621
8
Extension 8 DIH
1
1
2
2
3
3
4
4
5
5
6
6
7
7
No. 087B2750
8
Extension 8 AI / DO
8
Digital
Input
Relay
ECA-XM 205A
Override
8
8
X
8
SIG
1
L
DI 1
2
3
N
L
4
5
N
L
DI 2
DI 3
6
7
N
L
8
N
DI 4
1
SIG
2
3
GND
SIG
AI 1
4
GND
AI 2
5
SIG
7
SIG
Comm
1
1
1
2
2
2
3
4
4
5
6
5
ECA-XM 102B
7
No. 087B2621
8
Extension 8 DIH
6
7
8
Relay
SIG
GND
9
10
11
12
13
+12V
+5V
SHLD
SHLD
SIG
GND
SIG
GND
AI 4
Power
Comm
Digital
Input
SIG
8
GND
GND
6
GND
AI 3
Power
3
ECA-XM 205B
1) Control of a circulation pump and an alarm output signal
2) Control of a DHW pump or change-over valve
3) Control of two additional burner steps
4) Module to communicate the flow and energy parameter from a heat meter
5) Module to monitor temperatures and data points from the controller
3
SIG
Power
Comm
ECA-XM 102B
2
GND
AI 1
Power
6
ECA-XM 205A
Room panel, ECA 62
(as ECA 60 but with humidity sensor)
8
5
ECA-XM 204B
LON module – for network
connection
GND
7
4
BEA 0050, Auxiliary relay
Relay module – for extended
functionality
6
No. 087B2500
11 AI/ 8 DO
24 Va.c.
50/60 Hz 8 VA
MADE IN DENMARK
Servi
ce Pin
3
ECA 9010, Override module
Remote control, ECA 63
(as ECA 61 but with humidity sensor)
SIG
GND
5
ECL Apex 10
DO6
2
ECA 100, Analog time switch, week program
Remote control, ECA 61
SIG
DO5
ECA-XM 102A
5)
ECA-XM 204A
Room panel, ECA 60 with
built-in room temperature sensor
4
Service Tool
DO3
ECA-XM 101A
4)
ECA 87, RS232 remote control and data log
Analog clock for ECL Comfort
100B and 100M
GND
3
Triac
ON/OFF inputs (DI), opto
Extension modules
ECA 82, LON module
Connector set for panel mounting
SIG
2
Status
DO2
DO7
ECA 80, 2 x relay
Accessories
Socket for wall mounting
GND
Relay (SPDT)
Comm
DO1
ON/OFF outputs (DO)
For temperature, pressure,
flow and energy
transmitters, etc.
Power
DO8
8
All these product features are relevant
in order to obtain the best economically and individually adjusted heating
control.
*1
L32
A
B
C
1
2
3
4
5
6
7
)
• Setting of the service parameters:
heating cut out, minimum/
maximum room temperature
influence (only ECA 61/63).
• Setting of the time schedules for
the week program (only ECA 61/63).
• Humidity monitoring via built-in
humidity sensor (only ECA 62/63).
SIG
SIG
GND
16
17
GND
SIG
GND
14
15
GND
SIG
AI 1
AI 2
SIG
GND
18
19
GND
SIG
AI 3
+12V
+5V
SHLD
SHLD
20
21
22
23
24
GND
+12V
+5V
SHLD
SHLD
AI 4
8
8
8
8
7
3
3
4
5
6
ECA-XM 205A
7
No. 087B2750
8
Extension 8 AI / DO
Override
ECA-XM 210A*
X
2
2
The following extension module must be placed on the base part in the controller. There is only room for one module.
ECA-OB 003A
2
*) ECA-XM 210A is equipped with the M-Bus communication acc. to EN1434-3 and pulse input for frequencies up to 200 Hz.
Temperature sensors
Outdoor
Room
ECL Apex 10 in SCADA1) systems
ECL Apex 10 can communicate with
components and systems through
RS232 communication or modem
connection. The controller operates
with a standard interface supporting
an OPC data access server (OLE for
Process Control). The OPC is used to
move data from the ECL Apex 10 to
the SCADA system enabling network
monitoring.
Surface
Immersion
1) Supervisory Control And Data Acquisition.
RS232 module – for PC connection
9
Index for Cards and Applications
ECL Comfort
Card
Electronic temperature controller for weather compensated
flow temperature control of boiler systems.
11
100M
Electronic temperature controller for weather compensated flow
temperature control of directly or indirectly connected heating systems.
11
200
Electronic temperature controller, pre-programmed for a
variety of different applications. Each application has its own card
that describes the settings.
A
B
C
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
A
B
C
1
2
3
4
5
6
7
Page
100B
A
B
C
A
B
C
Application
ECL Comfort
100B
ECL Comfort
Weather compensated flow temperature
control of boiler systems.
System type
P16
12
P17
13
P20
14
P30
15
Boiler heated system
ECL Comfort
A
B
C
A
B
C
1
2
3
4
5
6
7
Electronic temperature controller programmed with ECL Cards for
large numbers of different systems.
300
1
2
3
4
5
6
7
ECL Comfort
A
B
C
A
B
C
1
2
3
4
5
6
7
1
2A
3B
4C
5
61
A
72
3 Comfort B
ECL
4
C
5
6
1
7
A
B
C
1
2
3
4
5
6
7
2
3
4
5
6
7
A
B
C
ECL Comfort
1
2
3
4
5
6
7
ECL Comfort
A
B
C
A
B
C
1
2
3
4
5
6
7
1
2
3
4
5
6
7
ECL Comfort
A
B
C
A
B
C
1
2
3
4
5
6
7
1
2
3
4
5
6
7
ECL Comfort
A
B
C
A
B
C
1
2
3
4
5
6
7
C14
16
C25
18
C35
19
C37
20
C47
22
C55
24
C60
25
C62
26
Weather compensated flow temperature control
C66
27
of directly or indirectly connected heating systems
C67
28
and boiler systems.
C75
30
System type 1:
System type 2:
Indirectly connected heating system
Boiler system with 4-way rotary valve
1
2
3
4
5
6
7
ECL Comfort Master / Slave Applications System type 1
31
ECL Comfort Master / Slave Applications System type 2
32
ECL Comfort
A
B
C
1
2
3
4
5
6
A
7
B
A
B
C
1
2
3
4
5
6
7
C
1
2
3
4
5
6
7
301
1
2
3
4
5
6
7
ECL Comfort
A
B
C
1
2
3
4
5
6
7
8
AI
SIG
1 GND
2 SIG
3 GND
4 SIG
5 GND
6 SIG
7 GND
8 SIG
9 GND
10 SIG
11 GND
12 SIG
13 GND
14 +12V
15 +5V
16 SHLD
17 SHLD
18
SIG
AI
9
19 GND
20 SIG
AI
10
21 GND
22 SIG
AI
11
23 GND
24 SIG
25 GND
26 +12V
27 +5V
SHLD
28
SHLD
29
30
ECL Comfort
24 Va.c.
A B
BUS
Service
Tool
Pin
Service ss
Addre
BUS
10
Electronic temperature controller programmed with ECL Cards for
large numbers of different systems.
L05
33
L10
36
L32
37
L66
38
L76
39
ECL Comfort
A
B
C
1
2
3
4
5
6
7
A
B
C
100M
ECL Comfort
ECL Apex 10
ECL code numbers
40
ECL Comfort Cards and Instructions
41
ECL Apex 10
42
ECL Apex 10 and ECA-XM modules
43
11
P16
ECL Comfort 200
Constant temperature control for DHW
circuits with flow system or storage tank
with built-in heating coil.
P17
ECL Comfort 200
Constant temperature control of DHW
circuits with storage charging system.
System type 1:
System type 2:
System type 1:
System type 2:
Constant temperature control of the DHW circuit
Constant temperature control of the DHW circuit
with storage tank with built-in heating coil
Constant temperature control of DHW circuit
with storage charging system
Constant temperature control of DHW circuit
with storage charging system
System type 3:
Constant temperature control of the DHW circuit
12
13
ECL Comfort 200
P20
P30
ECL Comfort 200
Weather compensated flow temperature
control of boiler systems.
Weather compensated flow temperature
control of heating systems with fixed
return temperature limitation.
System type 1:
System type 1:
System type 2:
Boiler heated system
Indirectly connected heating system
Directly connected heating system
System type 3:
System type 4:
Boiler system with 3-way valve
Boiler system with 4-way rotary valve
14
15
C14
ECL Comfort 300
Constant temperature control
(heating/cooling) of ventilation systems.
C14
ECL Comfort 300
Constant temperature control
(heating/cooling) of ventilation systems.
System type 1:
System type 2:
System type 5:
System type 6:
Unit heater system with constant room temperature control
Ventilation system with constant supply air control
Ventilation system with constant room temperature control
– heating and cooling
Ventilation system with constant room temperature control
– heating and heat recovery
System type 3:
System type 4:
System type 7:
System type 8:
Ventilation system with constant room temperature control
Ventilation system with constant room temperature
control and fresh air supply
Cooling system with constant cooling temperature
Cooling system with constant room temperature
16
17
C25
ECL Comfort 300
Weather compensated flow temperature
control of boiler heated systems and
constant temperature control of DHW
circuits.
C35
ECL Comfort 300
Weather compensated flow temperature
control of secondarily connected DHW
control of systems with fixed return
circuits with storage tank with built-in
temperature limitation. Constant temperature heating coil. Optional ON/OFF control
of the DHW circuit in connection with
primarily connected storage tank with
built-in heating coil.
System type 1:
System type 2:
System type 1:
System type 2:
Heating system with constant temperature
control of the DHW circuit
Heating system with constant temperature
control of the DHW circuit (DHW priority)
Indirectly connected heating system and secondarily
connected DHW storage tank with built-in heating coil
(DHW priority)
Indirectly connected heating system and secondarily
connected DHW storage tank with built-in heating coil
(optional DHW priority)
System type 3:
System type 3:
System type 4:
Weather compensated control of the heating system
Indirectly connected heating system and primarily
connected DHW storage tank with built-in heating coil
(optional DHW priority)
Directly connected heating system and DHW storage
tank with built-in heating coil (optional DHW priority)
18
19
C37
ECL Comfort 300
Weather compensated flow temperature
control of systems with sliding return
temperature limitation. Constant
temperature control of secondarily
connected DHW circuits with storage
charging system or storage tank with
built-in heating coil. Optional ON/OFF
control of the DHW circuit in connection
with primarily connected storage tank
with built-in heating coil.
C37
ECL Comfort 300
Weather compensated flow temperature
control of systems with sliding return
temperature limitation. Constant
temperature control of secondarily
connected DHW circuits with storage
charging system or storage tank with
built-in heating coil. Optional ON/OFF
control of the DHW circuit in connection
System type 1:
System type 2:
System type 5:
Indirectly connected system and secondarily connected
storage charging system (optional DHW priority)
Indirectly connected system and secondarily
connected storage charging system (DHW priority)
Indirectly connected system and primarily connected
storage tank with built-in heating coil (optional DHW priority)
with primarily connected storage tank
with built-in heating coil.
Please note: The following systems are only applicable
with the relay module ECA 80.
System type 3:
System type 4:
System type 6:
System type 7:
Indirectly connected system and secondarily connected
storage tank with built-in heating coil (optional DHW priority)
Indirectly connected system and secondarily connected
storage tank with built-in heating coil (DHW priority)
Indirectly connected system and secondarily connected
storage charging system (optional DHW priority)
Indirectly connected system and secondarily connected
storage charging system (DHW priority)
20
21
C47
ECL Comfort 300
Weather compensated flow temperature
control of systems with sliding return
temperature limitation. Constant
temperature control of DHW circuits
with storage charging system.
C47
ECL Comfort 300
Weather compensated flow temperature
control of systems with sliding return
temperature limitation. Constant
temperature control of DHW circuits
with storage charging system.
Please note: The following systems are
only applicable with the relay module
ECA 80.
System type 1:
System type 2:
System type 4:
System type 5:
Indirectly connected heating system with mixing loop
and secondarily connected storage tank with built-in
heating coil (optional DHW priority)
Indirectly connected heating system and primarily
connected storage charging system (optional DHW priority)
Indirectly connected heating system with mixing loop
and secondarily connected storage charging system (optional
DHW priority)
Indirectly connected heating system and secondarily
connected storage charging system with mixing circuit
(optional DHW priority)
System type 2a:
System type 3:
System type 6:
System type 6a:
Indirectly connected heating system and primarily
connected storage charging system (optional DHW priority)
Indirectly connected heating system and primarily
connected storage tank with built-in heating coil (optional
DHW priority)
Indirectly connected heating system and primarily connected
storage charging system with pre-controlled circuit (optional
DHW priority)
Indirectly connected heating system and primarily connected
storage charging system with pre-controlled circuit (optional
DHW priority)
22
23
C55
ECL Comfort 300
Boiler controller with constant
temperature control of DHW circuits
and weather compensated flow
temperature control of a mixed and an
unmixed heating circuit.
Please note: Relay module ECA 80 is a
necessary accessory!
C60
ECL Comfort 300
Weather compensated flow
temperature control with sliding
temperature limitation for two
independent heating circuits.
System type 1:
System type 2:
System type 1:
System type 2:
Weather compensated control of a mixed and an unmixed heating circuit and constant temperature control of the DHW circuit
Weather compensated control of a mixed and an unmixed heating circuit and constant temperature control of the DHW circuit
Two indirectly connected weather compensated
heating systems
Two directly connected weather compensated heating
systems
System type 3:
System type 3:
System type 4:
Weather compensated control of a mixed and an
unmixed heating circuit
Indirectly connected weather compensated heating
systems with mixing circuit
Weather compensated control of two mixed heating circuits
24
25
C62
ECL Comfort 300
Weather compensated flow temperature
control of heating systems with sliding
return temperature limitation for two
independent heating circuits.
C66
ECL Comfort 300
Weather compensated flow temperature
control of heating systems with sliding
return temperature limitation. Constant
temperature control of DHW circuits
with flow system or storage tank with
built-in heating coil.
System type 1:
System type 2:
System type 1:
System type 2:
Two indirectly connected weather compensated
heating systems
Two directly connected weather compensated
heating systems
Indirectly connected heating system and DHW circuit
Direcly connected heating system and DHW circuit
System type 3:
Indirectly connected weather compensated heating
system with additional mixing circuit
26
27
C67
ECL Comfort 300
Weather compensated flow temperature
control of heating systems with sliding
return temperature limitation for two
independent heating circuits. Constant
temperature control of the secondarily
connected DHW circuits with storage
tank with built-in heating coil. Optional
ON/OFF control of DHW circuits in
connection with primarily connected
storage tank with built-in heating coil.
Please note: Relay module ECA 80 is a
necessary accessory!
C67
ECL Comfort 300
Weather compensated flow temperature
control of heating systems with sliding
return temperature limitation for two
independent heating circuits. Constant
temperature control of the secondarily
connected DHW circuits with storage
tank with built-in heating coil. Optional
ON/OFF control of DHW circuits in
connection with primarily connected
storage tank with built-in heating coil.
System type 1:
System type 1a:
System type 4:
System type 4a:
Two indirectly connected heating systems and secondarily
connected storage tank with built-in heating coil (optional
DHW priority)
Two indirectly connected heating systems and secondarily
connected storage tank with built-in heating coil (DHW
priority)
Indirectly connected heating system with or without mixing
circuit and secondarily connected storage tank with built-in
heating coil (DHW priority)
Indirectly connected heating system with or without mixing
circuit and secondarily connected storage tank with built-in
heating coil (DHW priority)
System type 2:
System type 3:
System type 5:
System type 5a:
Two indirectly connected heating systems and primarily
connected storage tank with built-in heating coil (optional
DHW priority)
Indirectly connected heating system with or without mixing
circuit and primarily connected storage tank with built-in
heating coil (optional DHW priority)
Indirectly connected heating system with or without mixing
circuit and secondarily connected DHW storage charging
system (optional DHW priority)
Indirectly connected heating system with or without
mixing circuit and secondarily connected DHW storage
charging system (DHW priority)
28
29
C75
ECL Comfort 300
Multistage boiler controller with
constant temperature control of DHW
circuits and weather compensated flow
ECL Comfort Master / Slave Applications
control of a mixed and an unmixed
heating circuit. Please note: Relay
module ECA 80 is a necessary accessory!
System type 1:
System type 2a:
System type 1:
2-stage boiler control of a mixed and an unmixed heating
circuit and constant temperature control of the DHW circuit
3-stage boiler control of a mixed and an unmixed heating
circuit and constant temperature control of the DHW circuit
Example of connection of more (with address) ECL Comfort
controllers on the same BUS. The advantage is that only one
outdoor temperature sensor has to be connected to the
System type 2b:
System type 3:
3-stage boiler control of a mixed and an unmixed heating
circuit and constant temperature control of the DHW circuit
2-stage boilers with radiator circuit, mixing circuit
and DHW circuit
master. Via the BUS, the outdoor temperature signal,
time and date are sent to the slaves.
In the example above, the master can be ECL Comfort 200 with P30
application or ECL Comfort 300 with C35 / C37 / C47 / C60 / C62 /
C66 / C67. One slave is ECL Comfort 300 with C37, another slave is
ECL Comfort 100M.
30
31
ECL Comfort Master / Slave Applications
Weather compensated flow temperature
control for heat pump system (up to 2
stages), additional heating circuit and
System type 2:
Example of connection of more (with address) ECL Comfort
controllers on the same BUS. The advantage is that only
one outdoor temperature sensor has to be connected to the
master. Via the BUS, the outdoor temperature signal, time and
date are sent to the slaves. The slaves (with address) send the
desired flow temperature to the master. The master ensures
that the highest demand from the slaves is met.
L05
ECL Comfort 301
temperature control for DHW circuit.
Please note: Relay module ECA 80 is
a necessary accessory!
System type 1:
System type 2:
Weather compensated 1-stage heat pump with additional
electrical heat for heating and DHW circuits (DHW priority)
Weather compensated 2-stage heat pump for heating
and DHW circuits (DHW priority)
System type 3:
System type 4:
Weather compensated 1-stage heat pump with additional
electrical heat for heating
Weather compensated 2-stage heat pump for heating
In the example above, the master is ECL Comfort 300 with C47.
The slaves are ECL Comfort 300 with C62.
32
33
L05
ECL Comfort 301
Weather compensated flow temperature
control for heat pump system (up to 2
stages), additional heating circuit and
temperature control for DHW circuit.
ECL Comfort 301
Weather compensated flow temperature
control for heat pump system (up to 2
stages), additional heating circuit and
temperature control for DHW circuit.
System type 5:
System type 6:
System type 9:
Weather compensated 1-stage heat pump with additional
electrical heat for heating mixing circuit and DHW circuit
(DHW priority operation)
Weather compensated 1-stage heat pump with additional
electrical heat for heating mixing circuit and DHW circuit
(DHW priority or parallel operation)
Weather compensated 1-stage heat pump with additional
solar heating for heating mixing circuit and DHW circuit
(DHW priority or parallel operation)
System type 7:
System type 8:
Weather compensated 2-stage heat pump with additional
electrical heat for mixing circuit and DHW circuit (priority
operation)
Weather compensated 1-stage heat pump or boiler control for
heating mixing circuit
34
L05
The heat pump can optionally be operated with a solar system.
If a solar system is chosen, the ECA 86 module must be used
(instead of the ECA 80 module).
35
L10
ECL Comfort 301
Flow temperature control for keeping
areas snow and ice free.
L32
ECL Comfort 301
Weather compensated flow temperature
control in combined heating and
cooling systems, typically floor systems.
In addition, dew point and slab
temperatures are considered.
System type 1:
System type 2:
System type 1:
System type 2:
Flow temperature control based on two outdoor temperature
ranges
Flow temperature control based on two outdoor temperature
ranges and boiler return temperature protection
Weather compensated heating / cooling considering
dew point and slab temperature (typical system)
Weather compensated heating. Room and slab temperature
sensors can be connected (simple system)
System type 3:
System type 3:
System type 3:
Flow temperature control based on two outdoor temperature
ranges and slab temperature control
Flow temperature control based on two outdoor temperature
ranges and snow/ice detector*
Weather compensated heating and cooling operation
irrespective of dew point and slab temperature
(minimum system)
* Devireg™ 850, product from DEVI A/S
36
37
L66
ECL Comfort 301
Weather compensated flow temperature
control of heating systems with sliding
return temperature limitation and twin-
pump control. Constant temperature
control of DHW circuits with twinpump control.
Please note: Relay module ECA 80 is a
necessary accessory!
L76
ECL Comfort 301
Weather compensated flow temperature
control of two independent heating
systems with sliding return temperature
limitation. Constant temperature
control of DHW with flow switch
control.
System type 1:
System type 2:
System type 1:
System type 2:
Indirectly connected heating and DHW circuit
Directly connected heating circuit and
indirectly connected DHW circuit
Indirectly connected heating systems and DHW circuit with
flow switch control
Indirectly connected heating system and DHW circuit with
flow switch control
38
39
ECL Comfort
Code Numbers
ECL Comfort Cards and Instructions
Code Numbers
WebAccess accessories
1764
4692
4667
4686
4678
4668
4687
Czech
1762
Turkish
Russian
Hungarian
1765
Romanian
Slovenian
1754
Bulgarian
Estonian
1760
Croatian
Latvian
1761
Code
no.
087B-
ECL Comfort 100B (instructions only)
100B
1753
1750
1751
1752
ECL Comfort 100M (kit with ECL Card and instructions)
100M
1755
1756
1768
1758
1766
1767
1759
1763
ECL Comfort 200 (instructions only)
P16
4655
4663
4669
4693
4665
P17
4656
4664
4670
4679
4697
P20
4654
4660
4661
4662
P30
4650
4653
4657
4658
4677
4688
4675
4676
4651
4652
4674
4673
4671
4694
4843
4681
4666
4659
ECL Comfort 300 (kit with ECL card and instructions)
ECL Comfort accessories
ECA 60
ECA 61
ECA 62
ECA 63
ECA 80
ECA 82
ECA 84
ECA 86
ECA 87
Lithuanian
087B1188
087B1198
Dutch
WAH analog interface
WAS analog input, 4 channels
Swedish
087B1187
087B1194
087B1195
087B1196
087B1197
Spanish
WAH pulse interface
WAS digital input, 1 channel
WAS digital input, 2 channels
WAS digital input, 3 channels
WAS digital input, 4 channels
Analog
1757
Polish
Type
WebAccess
French
Code no.
087B1173
087B1189
087B1174
087B1179
WebAccess
German
Designation
WebAccess kit incl. 1 LON module and transformer
WebAccess kit with GSM modem incl. 1 LON module and transformer
LON extension module
WAS energy measuring module
Digital
087B1154
087B1149
087B1148
087B1145
English
Code no.
087B1100
087B1110
087B1120
087B1124
087B1130
087B1134
087B1131
087B1834
087B1835
087B1836
Finnish
ECL Comfort 100B/100M
ECL Comfort 200/300/301
ECL Comfort
ECL Comfort
Designation
Universal hardware - 230 V a.c.
Universal hardware - 230 V a.c.
Universal hardware - 230 V a.c.
Universal hardware - 24 V a.c.
Universal hardware - 230 V a.c.
Universal hardware - 24 V a.c.
Universal hardware - 230 V a.c. with 2 additional pulse connectors for heat meter
Universal hardware - 230 V a.c.
Universal hardware - 230 V a.c. with 2 additional pulse connectors for heat meter
Universal hardware - 230 V a.c. with 2 additional analog inputs and 2 analog
outputs
Socket for wall mounting
Socket for wall mounting
Connector set for panel mounting
Mounting kit for DIN rail
Danish
Type
ECL Comfort 100B
ECL Comfort 100M
ECL Comfort 200
ECL Comfort 200
ECL Comfort 300
ECL Comfort 300
ECL Comfort 300 with ECA 88
ECL Comfort 301
ECL Comfort 301 with ECA 88
ECL Comfort 301 with ECA 83
Language
ECL Comfort controllers and enclosures
Room panel with sensor
Remote control with 1 zone clock and sensor
Room panel with sensors (°C and % RH)
Remote control with sensors (°C and % RH)
Relay module - 2 x SPCO
LON communication module
M-Bus communication module
Temperature monitoring and alarm module
RS 232 remote control and data log
Modem cable (1.5 m) for ECA 87
PC cable (1.5 m) for ECA 87
087B1140
087B1141
087B1169
087B1143
087B1150
087B1152
087B1155
087B1158
087B1160
087B1171
087B1172
ECA 99
24 V transformer, Lübke (35 VA)
087B1156
ECA 100
Analog clock for ECL Comfort 100
087B1147
ECA 9010
Override module (for controller time programs)
087B3081
C14
4769
4824
4789
4836
C25
4782
4770
4771
4772
C35
4761
4774
C37
4762
4758
4775
C47
4823
4821
4818
4783
4807
4809
4756
4778
4810
C55
4828
4837
4860
4798
4830
4801
C62
4819
4760
4842
C66
4753
4757
4780
4754
4820
4817
4764
4825
4827
4776
4813
4750
C67
4840
4812
C60
C75
4848
4863
4833
4751
4831
4800
4752
4802
4846
4829
4847
4826
4779
4805
4851
4781
4806
4853
4755
4845
4795
4794
4803
4852
ECL Comfort 301 (kit with ECL card and instructions)
L05
L32
4870
4854
4877
4873
L66
L76
4871
4878
4879
Example: Code no. for a C47 card in German is 087B4818.
Data sheets are available on www.heating.danfoss.com under Documentation.
40
41
ECL Apex 10
ECL Apex 10 and ECA-XM Modules
Code Numbers
The ECL Apex 10 is a configurable
controller for temperature control in
district heating systems.
Example 1:
Example type 2:
Indirectly connected heating circuit with flow/energy limiting,
twin-pumps and makeup water
Indirectly connected heating and DHW circuit with filter guard
and twin-pumps
Type
ECL Apex 10
ECA-XM 101A
ECA-XM 102A
ECA-XM 102B
ECA-XM 204A
ECA-XM 204B
ECA-XM 205A
ECA-XM 205B
ECA-XM 210A
ECA-OB 003A
Designation
Main controller: 11 analog inputs, 4 digital outputs (relays) and 2x2 triac outputs
Extension module: 8 analog inputs
Extension module: 8 digital inputs for low voltage (galvanically separated)
Extension module: 8 digital inputs for high voltage (galvanically separated)
Extension module: 8 digital outputs (relays)
Extension module: 8 digital outputs (relays) with switches which allow each relay
to be controlled manually or automatically
Extension module: 8 analog inputs and 8 digital outputs (relays)
Extension module: 8 analog inputs and 8 digital outputs (relays) with switches
which allow each relay to be controlled manually or automatically
Extension module: M-Bus master (EN1434-3), 7 analog inputs, 2 digital inputs
for low voltage (for pulse input), 2 analog outputs (0 - 10 V) and 3 digital outputs
(relays)
Extension module: 2 analog outputs (0 - 10 V) with a resolution of 40 mV
Code no.
087B2500
087B2610
087B2620
087B2621
087B2740
087B2741
Designation
Service tool software for operation of the ECL Apex 10 controller (CD-ROM)
Cable between PC and ECL Apex 10 controller
Cable between PDA cable and ECL Apex 10 controller or
cable between null modem cable and ECL Apex 10 controller
24 V transformer, Lübke (35 VA)
Code no.
087B2510
080Z0262
080Z0261
087B2750
087B2751
087B2760
087B2530
ECL Apex 10 accessories
Type
ECA-ST 101A
ECA 99
087B1156
Temperature sensors for ECL Comfort and ECL Apex 10
Example 3:
Example 4:
Indirectly connected heating systems and DHW circuit with
flow registration
Indirectly connected heating circuit with flow/energy limiting,
twin-pumps and markup water and indirectly connected 2stage DHW circuit.
Pt 1000 (1000 Ω / 0 oC)
Type
ESMT
ESM-10
ESM-11
ESMB-12
ESMC
ESMU-100
ESMU-250
ESMU-100
ESMU-250
Designation
Outdoor temperature sensor
Room temperature sensor
Surface sensor
Universal sensor with 2.5 m cable
Surface sensor with 2 m cable
Immersion sensor, 100 mm, copper
Immersion sensor, 250 mm, copper
Immersion sensor, 100 mm, stainless steel
Immersion sensor, 250 mm, stainless steel
Code no.
084N1012
087B1164
087B1165
087B1184
087N0011
087B1180
087B1181
087B1182
087B1183
Designation
Immersion, stainless steel 100 mm, for ESMU-100, Cu (087B1180)
Immersion, stainless steel 250 mm, for ESMU-250, Cu (087B1181)
Immersion, stainless steel 100 mm, for ESMB-12 (087B1184)
Immersion, stainless steel 250 mm, for ESMB-12 (087B1184)
Code no.
087B1190
087B1191
087B1192
087B1193
Sensor pockets
Type
Pocket
Pocket
Pocket
Pocket
Data sheets are available on www.heating.danfoss.com under Documentation.
42
43
A Comprehensive Range of Electronic
Controllers and Motorized Control Valves
As a result of the strong commitment
of Danfoss to innovation and product
development, your demands will be
met in the best possible way.
These continuous development efforts
have formed the basis of our range of
electronic controllers and motorized
controls valves which performs perfectly
in combination or independently in an
application.
Danfoss A/S · DK-6430 Nordborg · Denmark · Tel.: +45 74 88 22 22 · Fax: +45 74 49 03 95
Homepage: www.heating.danfoss.com · E-mail: heating@danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.