AT30 Series (3-Phase)
Microprocessor Controlled SCR Battery Charger
The world's premium microprocessor
controlled digital SCR battery charger
The AT30 is the world's easiest operation float battery charger. It has over 20 years of
proven reliability and has become the industry's "gold standard " for all stationary
battery charging applications. We are so confident in our product that
we've backed the AT30 with our unrivaled
5 Year Standard Warranty.
CSA C22.2 · NRTL/C · UL 1012/UL 1564 compliant
Seismic qualified
ABS · CE certification available upon request
N56 W16665 Ridgewood Dr. Menomonee Falls, WI 53051 USA
Call: 1-800-554-2243 or email: stationary@sbsbattery.com
www.sbsbattery.com
What is the AT30?
Combining the performance and accuracy of a microprocessor with the reliability of SCR power conversion
technology makes the AT30 Series the standard in stationary battery chargers. AT30s are easy to install, operate
and maintain. The AT30 is packed with the most standard features and best warranty in the industry.
What are the most common applications for the AT30?
Utility & Communications
Power Generation
Substations
Microwave Relay Sites
Switchgear
Manufacturing
Emergency DC Power
DC Operated Breakers
Alarm Systems
Commercial
Alarm Systems
Uninterrupted Power Systems
DC Control Systems
Transportation
Signal Systems
Switchgear
Alarm Systems
PAGE 2
SPECIFICATIONS &
STANDARD FEATURES
SPECIFICATIONS
AC Input
Safety and Acceptance
• Voltage:
208 Vac 60Hz
240 Vac 60Hz
480 Vac 60Hz
550-600 Vac 60Hz
220 Vac 50/60Hz
380 Vac 50/60Hz
416 Vac 50/60Hz
• Input Voltage Tolerance:
+10%, -12%
• Input Frequency Tolerance:
±5%
• Efficiency:
85-90% typical for 130Vdc at 50-100% load
• Meets NEMA PE 5-1997 specification
• NEMA-1/IP20 type standard enclosure
DC Output
• Voltage Ratings:
12, 24, 48, or 130Vdc nominal
• Current Ratings (Adc):
25, 30, 40, 50, 75, 100,125, 150, 200,
250, 300, 400, 500, 600, 800, 1000
• Continuous Rating:
110% rated current at maximum equalize
voltage at 50ºC
• Current Limit Adjustment Range:
50% to 110% rated output
• Voltage Regulation:
±0.25% for line, load and temp. variations
*Regulation at max. equalize voltages may not meet ±0.25%
• Electrical Noise:
32dBrnc
• Ripple:
12/24/48Vdc
∙ Unfiltered on battery 1% Vrms
∙ Filtered on battery 30mVrms
∙ Filtered off battery 1% Vrms
∙ Battery Eliminator 30mVrms
130Vdc
∙ Unfiltered on battery 2% Vrms
∙ Filtered on battery 100mVrms
∙ Filtered off battery 2% Vrms
∙ Battery Eliminator 100mVrms
• Surge Withstand Capability:
Meets IEEE-472, ANSI C37.90a
• Third party agency approvals:
• CSA C22.2 compliant (up to and including 400A)
- NRTL/C · UL 1012/UL 1564 compliant
• Seismic qualified (5018/5030 cabinet styles only)
• ABS or CE certification available upon request.
• Made in the United States of America
Environmental
• Operating Ambient Temperature 0°F to 122°F (-18°C to 50°C) w/o derating
• Operating Altitude 10,000 feet (3,000 meters) above sea level w/o derating
• Relative Humidity 0% to 95% (without condensation)
• Audible Noise Less than 65 dBA at any point 5ft (1.5m) from any
vertical surface of enclosure
STANDARD FEATURES
• 5 Year Product Warranty
• Universal main control board
operates in any AT Series charger
• Alarm assembly with local LEDs
and summary relay contact for AC
Failure, DC Failure, High Vdc, Low
Vdc, Positive(+) and Negative(-)
ground fault
• High DC voltage shutdown
• Forced load share during
parallel operation
• Float/equalize selector switch
with indicating lights
• Manual equalize timer (0-255 hr.)
with indicating lights
• AC line failure automatic
equalize timer (0-255 hr.) with
indicating light
• AC On indicating light
• 1% Digital LED meter for
Vdc, Adc, timer hours and
alarm settings
• 6 pulse rectification
PAGE 3
• AC input and DC output
circuit breakers
• Membrane front panel
• Front panel controls can be
disabled for security
• A redundant analog circuit for
LVDC alarm, independent
of the microprocessor
• Redundant control loops for
higher reliability
• Local or remote voltage sense
with redundancy to protect
against remote sense failure
• Self-diagnostics
• Input & output MOV surge suppressors
• Reverse polarity protection via free
wheeling diodes
• CU-AL I/O compression lugs
• Switchboard wire, UL VW-1
• Enclosure pre-treated using a
5-stage iron phosphate process
with baked epoxy powder coating
in ANSI 61 gray
• NEMA 1 cabinet
Specifications subject to change.
CUSTOMIZE YOUR AT30
OPTIONS THAT LET YOU DESIGN YOUR CHARGER EXACTLY HOW YOU NEED IT!
SUMMARY OF OPTIONS
• DC output filtering: per
NEMA PE5 1996, standard
and battery eliminator
• Medium & High AIC Breakers
• AC Input/DC output fuses
• Auxiliary alarm relay board
• Copper ground bus
• AC lightning arrestor
• Fungus proofing (tropicalization)
• Static proofing
• Forced load share cable
• Communications kit: DNP3
Level 2 or MODBUS protocols
• Ethernet interface for comm. kit
• Battery temp. compensation
• NEMA 4 /12 type enclosure w/fan
• NEMA Type 2 Drip Shield
• Barrier type alarm terminal block
• End of discharge alarm
• Battery discharge alarm
• Zero-center ground
detection meter
• Analog AC voltmeter
• Analog AC ammeter
• Cabinet heater assembly
• CE marking upon request
• ABS certification upon request
• Fan control contactor
• Custom drawing package
w/ optional CAD and PDF files
ORDERING
Filtering
STANDARD
Output filtering is essential whenever there is need for low ac ripple
and low noise on the dc bus for critical loads. The standard dc
output filtering limits ripple to no more than 30mV RMS on 12, 24
& 48Vdc units, and 100mV RMS on 130Vdc units, measured at the
battery terminals. This feature meets the specifications of NEMA
standard PE5-1996, and is recommended for all long-life stationary
battery installations.
FACTORY
INSTALLATION
YES
Factory Installation use
Specification Table
on page 11
ORDERING
BATTERY ELIMINATOR
An additional "battery eliminator" feature is also available, meeting
the specifications of NEMA standard PE5-1996 with no battery
connected, measured at the dc output terminals. This feature is
recommended for sites where the battery may occasionally be
disconnected from the dc bus for maintenance. Additional filtering
is essential to limit ac ripple and noise for critical dc loads.
AVAILABLE FOR
FIELD INSTALLATION
YES
Contact factory with serial
number of original unit and type
of filtering upgrade.
ORDERING
Medium & High AIC Breaker
This feature provides thermal-magnetic circuit breakers with higher
Ampere Interrupting Capacity ratings than the standard. See the
tables on Page 11 for medium and high AIC breaker ratings.
FACTORY
INSTALLATION
YES
AVAILABLE FOR
FIELD INSTALLATION
NO
YES
Factory Installation use
Specification Table
on page 11
Contact factory with serial
number of original unit and type
of breaker upgrade for proper field
kit parts.
ORDERING
AC Input and/or DC Output Fuses
Default protection devices for the AT30 are molded case circuit
breakers. Fuses may also be ordered to augment them, wired in
series with the breakers. Three (3) ac input fuses provide 200 kAIC
protection. Two (2) dc output fuses provide 20 kAIC protection.
Fuses may also be ordered in conjunction with standard breakers
as a cost-saver. If an AT30 is ordered without breakers, fuses must
be ordered.
PAGE 4
FACTORY
INSTALLATION
YES
AVAILABLE FOR
FIELD INSTALLATION
YES
Factory Installation use
Specification Table
on page 11
Contact factory with serial
number of original unit and type
of fuses (ac and/or dc) for proper
field kit parts.
CUSTOMIZE YOUR AT30
OPTIONS THAT LET YOU DESIGN YOUR CHARGER EXACTLY HOW YOU NEED IT!
ORDERING
Auxiliary Alarm Relay Board
The AT30 features several industry-standard alarms, with individual
LED indicators on the front instrument panel, and are accessible to
the user via one (1) Summary Alarm contact on the Main Control
PC Board. This feature provides a separate user-accessed pc board,
featuring discreet two (2) form-C relay contacts for all six (6) alarms.
FACTORY
INSTALLATION
YES
AVAILABLE FOR
FIELD INSTALLATION
YES
Factory Installation use
Specification Table
on page 11
Field Installation use Part Number
Style 5018:
Style 5030:
Style 163:
Style 198:
EI0213-02
EI0213-03
EI0213-04
EI0213-05
ORDERING
Copper Ground Bus
This option provides a convenient means to tie the AT30 to the
site building ground. A copper ground bus bar is provided with
an extra CU-AL compression box lug.
FACTORY
INSTALLATION
YES
AVAILABLE FOR
FIELD INSTALLATION
YES
Factory Installation use
Specification Table
on page 11
Field Installation use Part Number
Style 5018: EI0195-02
Style 5030: EI0195-03
Style 163: EI0195-04
Style 198: EI0195-04
ORDERING
AC Lightning Arrestor
This options features an industrial-grade surge arrestor
in polycarbonate housing, rated for 20,000 Amperes. It is
recommended for installations with risk of frequent ac surges, such
as high elevations or severe weather.
FACTORY
INSTALLATION
YES
AVAILABLE FOR
FIELD INSTALLATION
YES
Factory Installation use
Specification Table
on page 11
Field Installation use Part Number
EJ1074-02
ORDERING
Fungus Proofing
FACTORY
INSTALLATION
This treatment is also referred to as "tropicalization". It coats
electrical components and internal wiring connections with a
fungus-resistant, non-conductive film (approx. 1 mil thickness).
User termination points are not coated, nor are relay contacts, and
any electrical connectors where the spray would interfere with
functionality. The application is fully cured at time of shipment.
YES
AVAILABLE FOR
FIELD INSTALLATION
NO
NO
Factory Installation use
Specification Tables on
pages 10 & 11
NOT AVAILABLE FOR
FIELD INSTALLATION
ORDERING
Static Proofing
Used in "arid" environments, this treatment coats electrical
components and connections with a static-resistant, nonconductive film (approx. 1 mil thickness). User termination points
are not coated, nor are relay contacts, and any electrical connectors
where the spray would interfere with functionality. The application
is fully cured at time of shipment.
FACTORY
INSTALLATION
YES
AVAILABLE FOR
FIELD INSTALLATION
NO
PAGE 5
Specify this
Factory
Installation
option
using the use
Specification Tables on
Specification
Tables
pages 10 &
11
on pages 10 & 11
NOT AVAILABLE FOR
FIELD INSTALLATION
Specifications subject to change.
CUSTOMIZE YOUR AT30
OPTIONS THAT LET YOU DESIGN YOUR CHARGER EXACTLY HOW YOU NEED IT!
ORDERING
Communications Kit
This option allows full remote monitoring of the AT30 and control
of the front panel features, using MODBUS or DNP3 Level 2
protocols. Standard serial (RS-232 & RS-485) connections are
provided for use with local SCADA systems.
Ethernet and Fiber Optics Modem interfaces are also available
options for use with the AT Communications Kit.
FACTORY
INSTALLATION
YES
AVAILABLE FOR
FIELD INSTALLATION
YES
Factory Installation use
Part Number when ordering
12Vdc: EJ5037-01
24Vdc: EJ5037-02
48Vdc: EJ5037-03
130Vdc: EJ5037-04
Field Installation use Part Number
12Vdc: EJ5037-11
24Vdc: EJ5037-12
48Vdc: EJ5037-13
130Vdc: EJ5037-14
ORDERING
Ethernet Gateway
FACTORY
Enable Serial Modbus/DNP3 devices to communicate with
an Ethernet host. Get 10BASE-T and 100BASE-T connectivity
over DNP/IP or Modbus TCP/IP with the combination of the
Communication Kit and Ethernet Gateway option.
INSTALLATION
YES
AVAILABLE FOR
Must be ordered with the Communications Kit option (above)!
FIELD INSTALLATION
YES
Factory and Field Installation use
Part Number when ordering
12Vdc Modbus: EJ5226-00
24Vdc Modbus: EJ5226-01
48Vdc Modbus: EJ5226-02
130Vdc Modbus: EJ5226-03
12Vdc DNP: EJ5226-10
24Vdc DNP: EJ5226-11
48Vdc DNP: EJ5226-12
130Vdc DNP: EJ5226-13
ORDERING
Temperature Compensation
Supplied in a kit, this option adjusts the AT30 dc output voltage
up or down, in response to battery temperature fluctuations.
Temperature is measured by an epoxy-enclosed thermistor. This
probe is mounted on or near the battery, and connected by a cable
to the Main Control PC Board. It is compatible with both leadacid and nickel-cadmium batteries, and recommended for VRLA
batteries. Cable lengths of 25, 50, 100, and 200 ft are available.
FACTORY
INSTALLATION
NO
AVAILABLE FOR
FIELD INSTALLATION
YES
CAN BE ORDERED WITH CHARGER
BUT MUST BE FIELD INSTALLED
Field Installation use Part Number
25ft: EJ5033-00
50ft: EJ5033-01
100ft: EJ5033-02
200ft: EJ5033-03
ORDERING
Barrier Type Alarm Terminal Blocks
This option features a separate molded phenolic terminal block,
wired directly to the Auxiliary Alarm Relay PC Board. It allows the
user to connect remote alarm wiring with ring or spade type lugs.
The #6-32 binder hear screw terminals are rated for 20A at 150 Vac/
Vdc, and accept wire sizes #16 to #14 AWG.
FACTORY
INSTALLATION
YES
Factory & Field Installation use
Part Number when ordering
AVAILABLE FOR
FIELD INSTALLATION
(1) FORM-C: EJ5130-01
(2) FORM-C: EJ5130-02
YES
ORDERING
Mechanical Lock For Front Door
The AT30 front panel controls can be disabled by setting a jumper
on the back of the Main Control PC board. For installations where
extra security is required, the front instrument panel, or door,
can be physically locked closed. This option provides a locking
provision on the enclosure, a padlock, and two (2) keys. A fully
installed door key lock is also available.
PAGE 6
FACTORY
INSTALLATION
YES
AVAILABLE FOR
FIELD INSTALLATION
Padlock - YES
Keylock - NO
Factory & Field Installation use
Part Number when ordering
Padlock Style 5018: EI0215-00
Padlock Style 5030: EI0215-01
Padlock Style 163: EI0215-02
Padlock Style 198: EI0215-03
Keylock Style 5018: EI0215-11
Keylock Style 5030: EI0215-12
Keylock Style 163: EI0215-13
Keylock Style 198: EI0215-14
Specifications subject to change.
CUSTOMIZE YOUR AT30
OPTIONS THAT LET YOU DESIGN YOUR CHARGER EXACTLY HOW YOU NEED IT!
ORDERING
Wall Mounting Brackets or Rack Mounting
AT30 Chargers in Style-5018 enclosures can be wall or rack
mounted. Wall-mounting brackets (EI5080-00) are shipped as a
field kit. Use of this option increases the vertical footprint of the
charger by 14”. Anchor bolts are not supplied.
The Style-5018 enclosure is also EIA 23” or 24” rack mountable.
Mounting brackets (EI0193-03) are factory installed. Relay rack
mounting hardware is not supplied.
FACTORY
INSTALLATION
Wall - No
Rack - Yes
AVAILABLE FOR
FIELD INSTALLATION
YES
Factory & Field Installation use
Part Number when ordering
WALL MOUNTING
Style-5018: EI5008-00
RACK MOUNTING
Style-5018 (23/24in): EI0193-03
ORDERING
NEMA Type 2 Drip Shield
Standard AT30 battery chargers are supplied in NEMA Type 1
vented enclosures. The optional drip shield prevents overhead
water and small falling particles from entering the top vented
panels, protecting internal equipment from damage. The
combined standard enclosure and drip shield meets the NEMA
Type 2 specification.
FACTORY
INSTALLATION
YES
Factory & Field Installation use
Part Number when ordering
AVAILABLE FOR
FIELD INSTALLATION
STYLE 5018: EI0191-02
STYLE 5030: EI0191-03
STYLE 163: EI0191-04
STYLE (23/34in):
198: EI0191-05
EI0193-03
Style-5018
YES
ORDERING
NEMA Type
4 or 12
Cabinet
2 Drip
Shield
With
this accessory,
a fully
assembled
standard
Standard
AT30 battery
chargers
are supplied
in AT30
NEMANEMA-1
Type 1
vented enclosure
installed
within
another
gasketed,overhead
sealed
enclosures.is The
optional
drip
shield prevents
cabinet.
The
combined
assemblyfrom
meets
the NEMA
Type
4 (Type 12
water and
small
falling particles
entering
the top
vented
optional)
enclosureinternal
specification.
120Vac
fan,
filters, and
panels, protecting
equipment
from
damage.
Theviewing
window
included.
combined
standard enclosure and drip shield meets the NEMA
Type 2 specification.
FACTORY
INSTALLATION
CONTACT SBS
YES
AVAILABLE FOR
FIELD INSTALLATION
YES
SUPPLEMENTAL PRODUCT
CONTACT SBS
ORDERING
Fan Control Contactor
Lead-acid batteries produce hydrogen gas. This small wallmounted external accessory provides a relay contactor to activate
a battery installation vent or exhaust fan. Available in 10A or 20A
models, the accessory is factory-set to provide relay closure when
the AT30 enters into Equalize mode.
FACTORY
INSTALLATION
CAN BE ORDERED WITH CHARGER
BUT MUST BE FIELD INSTALLED
NO
AVAILABLE FOR
FIELD INSTALLATION
YES
Field Installation use Part Number
10 Amp Rating: EJ5017-0#
20 Amp Rating: EJ5017-1#
Contact manufacturer for
specific part number
ORDERING
SUPPLEMENTAL PRODUCT
AT-DC Distribution Panel
This product augments AT30 with a customized dc distribution
panel for user-specified loads. The AT-DC is configurable to various
combinations of main and branch breakers. The AT-DC panel is
optimally supplied from the factory, mounted to the AT30 and prewired to the charger's dc output terminals. For further details, refer
to the AT-DC product literature (JF5032-00).
FACTORY
INSTALLATION
YES
EJ5110-##
AVAILABLE FOR
FIELD INSTALLATION
YES
PAGE 7
Factory & Field Installation use
Part Number when ordering
Refer to document (JF5032-00)
for model specific part number.
Specifications subject to change.
AT30 SERIES
SPECIFICATION CHART
DC Output
Rating
Volts
Float Adjust
11.0-14.5Vd
Equalize
Adjust
12Vdc
11.7-15.5Vdc
Float Adjust
22.0-29.5Vdc
Equalize
Adjust
24Vdc
23.4-31.0Vdc
Float Adjust
44.0-58.0Vdc
Equalize
Adjust
48Vdc
46.8-59.0Vdc
Float Adjust
110.0-141.0Vdc
Equalize
Adjust
117.0-143.0Vdc
130Vdc
AC Input Ampere Rating
Based on maximum rms value of the input
current delivered to the charger
under all operating conditions within
manufacturer’s specifications
Battery Charger AC Circuit
Breaker Ampere Rating
(standard AIC breakers)
Amps
208
220
240
480
600
208
220
240
480
600
50
75
100
125
150
200
250
300
50
75
100
125
150
200
250
300
400
500
600
800
1000
50
75
100
125
150
200
250
300
400
500
600
800
1000
25
30
40
50
75
100
125
150
200
250
300
400
500
600
800
1000
5
7
9
12
13
16
22
28
9
12
16
21
23
27
39
51
59
72
88
122
152
15
20
26
35
37
53
69
78
100
128
157
209
261
17
20
26
33
48
64
80
93
125
158
180
255
320
378
503
628
5
6
8
11
13
16
20
24
9
11
15
20
24
28
37
44
59
72
87
119
148
13
19
25
33
35
50
66
74
96
120
149
198
248
16
20
23
30
44
60
75
87
120
150
170
235
300
354
473
590
4
6
8
10
12
14
19
24
8
10
14
18
21
25
34
44
51
63
76
107
133
13
16
24
29
32
46
58
68
88
110
135
181
225
14
18
22
28
43
57
69
80
110
137
160
220
280
331
439
547
2
3
4
5
6
7
9
12
4
5
7
9
11
13
17
22
27
32
40
55
68
7
9
12
15
16
23
30
34
44
55
69
91
113
8
9
12
15
22
29
38
42
55
68
80
110
140
169
224
279
2
3
4
5
6
6
8
11
4
5
6
8
10
11
15
19
24
29
35
48
60
6
8
10
13
14
20
26
30
39
48
60
79
99
7
8
10
12
18
24
33
37
48
59
72
96
120
145
194
240
10
10
15
15
20
20
30
35
15
15
20
30
35
40
50
70
80
90
125
175
200
20
25
35
50
50
70
100
100
125
175
200
300
350
25
25
35
50
70
100
125
125
175
200
250
300
400
500
N/A
N/A
10
10
10
15
20
20
25
30
15
15
20
25
30
35
50
60
80
90
125
175
200
20
25
35
50
50
70
100
100
125
175
200
300
350
20
25
30
40
60
80
100
125
150
200
225
300
400
500
N/A
N/A
10
10
15
15
20
20
30
35
15
15
20
30
35
40
50
70
80
90
125
175
200
20
25
35
50
50
70
100
100
125
175
200
300
350
25
25
35
50
70
100
125
125
175
200
250
300
400
500
N/A
N/A
5
5
5
10
10
15
15
15
10
10
10
15
15
20
25
30
40
40
50
70
90
10
15
15
20
20
30
40
50
60
70
90
125
150
10
15
15
20
30
40
50
60
70
100
100
150
200
250
300
350
15
15
15
15
15
15
15
15
15
15
15
15
15
15
20
25
35
40
50
70
80
15
15
15
20
20
25
40
40
50
70
80
100
125
15
15
15
15
25
35
50
50
60
80
100
125
150
200
250
300
VAC
VAC
VAC
VAC
VAC
VAC
VAC
PAGE 8
VAC
VAC
DC
Circuit Cabinet
Breaker
Style
Rating
Approx.
Shipping
Weights
Watts (BTU/hr)
260 (118)
330 (150)
380 (173)
450 (205)
550 (250)
590 (268)
610 (277)
650 (295)
280 (127)
340 (154)
390 (177)
540 (245)
580 263)
610 (277)
650 (295)
690 (313)
1150 (522)
1300 (590)
1530 (694)
2020 (916)
2440 (1107)
310 (141}
390 (177)
500 (227)
550 (250)
600 (272)
660 (299)
720 (327)
760 (345)
1100 (499)
1350 (612)
1600 (726)
2020 (916)
2400 (1089)
370 (168)
380 (172)
390 (177)
400 (182)
490 (222)
650 (295)
740 (336)
750 (340)
820 (372)
1130 (513)
1330 (603)
1580 (717)
2150 (975)
2650 (1202)
3250 (1474)
4200 (1905)
229 (783)
340 (1160)
448 (1529)
560 (1911)
668 (2279)
890 (3039)
1113 (3799)
1327 (4531)
289 (987)
427 (1457)
560 (1911)
700 (2309)
833 (2843)
1101 (3759)
1376 (4699)
1652 (5638)
2202 (7518)
2730 (9319)
3275 (11183)
4367 (14910)
5459 (18638)
398 (1358)
584 (1994)
762 (2602)
953 (3253)
1131 (3860)
1491 (5091)
1864 (6363)
2237 (7636)
2949 (10068)
3686 (12585)
4424 (15102)
5898 (20137)
7373 (25171)
361 (1232)
416 (1421)
532 (1817)
647 (2208)
928 (3169)
1201 (4099)
1478 (5045)
1773 (6054)
2327 (7946)
2909 (9932)
3436 (11731)
4582 (15641)
5727 (16552)
6872 (23462)
9163 (31283)
11271 (38479)
lb.(kg)
Heat
Loss
VAC
80
100
150
175
200
250
350
400
80
100
150
175
200
250
350
400
600
700
800
1200
FUSE
80
100
150
175
200
250
350
400
600
700
800
1200
FUSE
40
50
60
80
100
150
175
200
250
350
400
600
700
800
1200
FUSE
5018
5018
5018
5030
5030
5030
5030
5030
5018
5018
5018
5030
5030
5030
5030
5030
163
163
163
198
198
5018
5018
5018
5030
5030
5030
5030
5030
163
163
198
198
198
5018
5018
5018
5018
5018
5030
5030
5030
5030
163
163
163
198
198
198
198
Specifications subject to change.
ZE
I
S
O
T
W
O
H
R
E
G
R
A
H
C
YOUR
(simplified
(
Ah x 1.R
t
formula)
)
Charger
+L = Continuous
Output Rating
AH=Ampere hours removed
R= Recharge factor (1 = Pb) or (3 = NiCd)
L= Additional standing load
t= Recharge time in hours
CABINET STYLES
& DIMENSIONS
For detailed CAD drawings of all
NEMA-1 type enclosures (and
optional NEMA-4 (12) type
enclosures), please contact SBS.
Cabinet Style 5018
30i
762 n
mm
54.25in
1378mm
27
71 .90i
0m n
m
Cabinet Style 5030
in
in
15 mm 9.14 m
1
m
38 1 86
4
Cabinet Style 163
Cabinet Style 198
PAGE 9
Specifications subject to change.
STANDARD
INTERNAL
LAYOUT BY
CABINET
STYLE
For detailed CAD
drawings of all NEMA-1
type enclosures (and
optional NEMA-4 (12)
type enclosures), please
contact SBS.
Rectifier Assembly
Rectifier Assembly
Microprocessor
Control Board
Microprocessor
Control Board
Filter Inductor
I/O Assembly
Filter Inductor
Input
Circuit Breaker
Output
Circuit Breaker
Input
Transformer
I/O Assembly
Output
Circuit Breaker
Input
Circuit Breaker
Input
Transformer
STYLE 5018 CABINET
STYLE 5030 CABINET
Rectifier Assembly
Microprocessor
Control Board
I/O Assembly
Input
Circuit Breaker
Output
Circuit Breaker
Input
Transformer
Filter Inductor
STYLE 163 CABINET
Microprocessor
Control Board
Rectifier Assembly
I/O Assembly
Input
Circuit Breaker
Input
Transformer
Output
Circuit Breaker
Filter Inductor
STYLE 198 CABINET
PAGE 10
Specifications subject to change.
AT30 - SPECIFICATION TABLE
A
SAMPLE
AT30
YOUR CODE
AT30
B
1
3
C
0
DESCRIPTION
A
B
C
Nominal DC
Output Voltage
Nominal DC
Output Current
D
DC Output
Filtering
E
AC Input
Voltage*
(3~)
0
CODE
AT30
012
024
048
130
025
030
040
050
075
100
125
150
200
250
300
400
500
600
800
1K0
U
F
E
208
240
480
550**
220
380
416
D
5
0
F
E
4
FEATURE
AT30 SERIES
12Vdc
24Vdc
48Vdc
130Vdc
25Adc
30Adc
40Adc
50Adc
75Adc
100Adc
125Adc
150Adc
200Adc
250Adc
300Adc
400Adc
500Adc
600Adc
800Adc
1000Adc
Unfiltered
Filtered
Eliminator
208V 60Hz
240V 60Hz
480V 60Hz
550V 60Hz
220V 50/60Hz
380V 50/60Hz
416V 50/60Hz
8
0
F
G
H
J
K
L
M
N
P
S
X
S
X
A
X
X
X
X
DESCRIPTION
F
AC Input
Circuit Breaker
Rating***
G
AC Input Fuses
H
DC Output
Circuit Breaker
Rating***
J
DC Output Fuses
K
Auxiliary Alarm
Relay Board
L
Copper
Ground Bus
M
AC Lightning
Arrestor
N
Fungus Proofing
P
Static Proofing
CODE
S
M
H
0
F
X
S
M
H
0
F
X
A
X
G
X
L
X
F
X
S
X
FEATURE
Standard AIC
Medium AIC
High AIC
No Breaker
Installed
Not Supplied
Standard AIC
Medium AIC
High AIC
No Breaker
Installed
Not Supplied
Installed
Not Supplied
Installed
Not Supplied
Installed
Not Supplied
Applied
Not Supplied
Applied
Not Supplied
* Contact factory for other AC input voltages not listed
** Applicable for 550 & 600Vac
*** If you do not order an AC input or DC output circuit
breaker, fuses will be provided.
Circuit Breaker AC & DC Ratings
STANDARD
Input: 5kAIC - 120/208/240/480Vac
14kAIC - 600Vac
Output: 5kAIC - 125Vdc
MEDIUM
HIGH
Input: 25kAIC - 120/208/240/480Vac
Input: 65kAIC - 120/208/240/480Vac
18kAIC - 600Vac
N/A - 600Vac
Output: 10kAIC - 250Vdc
Output: 20kAIC - 250Vdc
PAGE 11
Specifications subject to change.
OUR UNRIVALED
PRODUCT WARRANTY
Standard Warranty
(applies only to products delivered within the United States and Canada)
All charger products are warranted to be free from defects in material and workmanship
for a period of five (5) years from date of manufacture. During the term of the warranty
period: parts, assemblies, or components deemed to be defective will be repaired or
replaced at our option, free of charge. All costs related to removal, reinstallation and
transportation will be paid by the purchaser/customer and/or operator of the product.
Evaluation, repair and/or replacement of any defective part(s) are FOB manufacturer’s
factory.
This warranty does not cover products or parts that are damaged from improper use or
abuse, as determined by the manufacturer. Accessory items or additional items carry
only their respective manufacturer’s warranty. Consumable items (such as fuses and
electrolytic capacitors), which wear out under normal use are specifically not covered
by this standard warranty. Any consequential damage due to diagnosis or repair by any
party other than the manufacturer's authorized personnel is not covered
under this warranty.
NOTE: Requests for returns or claims must be submitted to our Factory Service Center
for Return Material Authorization (RMA) instructions and assignment. Returns that
do not follow this procedure will not be honored.
Extended warranty coverage available by request.
Other Products Available:
AT10 Microprocessor Battery Charger
AT Series Options & Accessories
AT Series Communications Module
AT-DC Series Distribution Panel
SCR/SCRF Series Utility Battery Charger
Mobile DC
Power System
Storage Battery Systems, LLC
800-554-2243
JF5006
JF5020
JF5014
JF5032
JF5010
Universal
Maintenance Charger
•
•
UMC Universal Maintenance Charger
Single Cell Charger
Mobile DC Power System
The EPIC Series Console
Best Battery Selector
AT10 Microprocessor
Battery Charger
JF5008
JF5007
JF5041
JF5043
JF5048
The EPIC
Series Console
N56 W16665 Ridgewood Drive • Menomonee Falls, WI 53051 USA
•
stationary@sbsbattery.com
www.sbsbattery.com
SBS reserves the right to change specifications and designs without notice.
Illustrations, data, dimensions and weights given in this brochure are for guidance only and cannot be held binding on the company.