Data Sheet Fire Safety & Security Products CerberusTM PRO Fire Safety System
The new dimension in fire protection
•
•
•
•
•
•
ARCHITECT AND ENGINEER SPECIFICATIONS
One (1) or (2) two-heightunit enclosures
•
•
•
•
Softkey buttons
Primary, regulated power
•
170-Watts is rated at 6.5 Amps
300-Watts is rated at 11.5 Amps
120VAC or 240VAC
50 / 60Hz @ 2.0A max.
Ability to network with other
Siemens Fire Safety systems
Built-in strobe synchronization protocol
Fully field programmable, via a
Windows®-laptop PC
Several relay commands: Alarm,
Trouble, Supervisory, etc.
Light-emitting diodes (LEDs) for:
Power, Alarm, Supervisory, Silenced,
Ground Fault, Trouble, and systemstatus LEDs
Alarm command has a larger, distinctive LED
LED-option provides LED annunciation of
system activity
Backlit, 2” ─x─ 4-3/4” liquid-crystal
display (LCD)
ƒ
ƒ
40-characters per row
Eight (8)-line display
Supervised remote printer, via
Remote Peripheral Module
RS─485 interface
End-user ‘Help’ screens
Four-way navigation menu with
extended-views capability
Multiple command stations
Menu-driven operator commands
5,000-event history-logging capability
with on-line and off-line reports
ƒ
Universal AC power input:
ƒ
•
•
•
•
Powerful, but user-friendly
system interface
ƒ
ƒ
•
•
•
•
Remote viewing for the 252point and 504-point systems
ƒ
ƒ
•
•
Standard 50-point, 252-point
and 504-point-capacity systems
•
•
Global annunciation and control capability
SureWireTM addressable-loop technology
ƒ
Polarity-insensitive (patented)
detection circuits
• Intelligent / analog detection circuits:
•
•
•
•
•
•
Class A or Class B
Supports FirePrintTM applicationspecific detection
Supports single-person, ‘Walk Test’
Sprinkler Supervision
Supports pre-action, deluge and
SinorixTM-agent releasing
Releasing-valve monitoring
Detector Sensitivity Readout / Printout
ƒ
per NFPA 72
Off-line reports can be viewed the
custom-configuration programming tool
•
•
Multiple levels of password protection
•
Alarm verification
Automatic environmental
compensation for smoke detectors
ƒ
by device or zone
•
•
•
•
•
•
•
•
Gas Alarm command for CO detection
•
NEC 760 power-limited circuits
Pre-alarm operation
Degrade-mode operation
Seismic certified
Logic-controlled output functions
Optional city-tie / leased-line module
Distributed processing
Optional notification-appliance-circuit
(NAC) expansion module
ƒ
ƒ
•
Up to 3.0 amps (24VDC) load per output
( UL 864-compliant)
UL 864 9th Edition Listed;
FM, CSFM and NYC Fire Dept. Pending
System Overview
The Cerberus PRO Fire Safety System ─ a new dimension
in fire protection from Siemens Industry − Fire Safety ─ is
a technologically advanced fire-and-life-safety system.
Each Cerberus PRO system provides easy operation via
its push-button soft keys; a backlit, 2” ─x─ 4-3/4” LCD
screen; as well as a (4) four-way navigation push
button ─ all located in the upper portion of each panel.
Through the use of its unique multiprocessor ‘Network’
design – along with its ability to utilize intelligent
detection devices – Cerberus PRO epitomizes a flexible
and highly configurable fire system. SureWireTM
addressable-loop technology is supported by Cerberus
PRO.
Cerberus PRO is ideally suited for small and mid-market
applications by providing 50, 252 and 504-point
addressable fire-alarm-control-panel (FACP) networking.
In conjunction with these new and improved FACPs is a
state-of-the-art line of intelligent detectors. For example,
the Multi-Criteria Fire / CO Detector [with ASAtechnologyTM]
is cutting-edge technology for specialized applications ─
such as carbon-monoxide detection ─ compared to
standardized detectors, while the Photoelectric Smoke
Detector uses microcontroller circuitry and surface-mount
technology for maximum reliability.
The Cerberus PRO Fire Safety System is UL 864 9th Edition
Listed.
Cerberus™ PRO Fire Safety System
s Industry, Inc.
Building Technologies Division
9800
Cerberus PRO Components
Standard Operating Units
50-point Cerberus PRO FACP
50-point Cerberus PRO FACP
Model FC901 is an addressable FACP that provides a costeffective solution for simple fire-alarm system applications.
Model FC901 contains one (1), built-in DACT and two (2)
NACs.
Small and compact in design, Model FC901 is ideal for
small fire-protection applications using less than 50
addressable devices:
ƒ
ƒ
ƒ
ƒ
ƒ
retail outlets / strip malls
doctor’s offices
dry cleaners
restaurants
banks, etc.
The dimensions of Model FC901 (connected to a oneheight-unit enclosure) are approximately as follows:
16.25” (H) [41.3 cm.] ─x─ 18” (W) [46 cm.] ─x─ 5”
(D) [41.3 cm.]
Operating Units with LEDS
Operating Interface Units
The Operating Interface Units (Models FCM2018-U3 and
FCM2019-U3) function as the operator interfaces and central
microprocessors for the Cerberus PRO FACPs (Models FC922
and FC924).
The Model FCM2018-U3 and Model FCM2019-U3 modules
provide multi-use capability for each end-user to efficiently
‘Acknowledge’ events; to quickly control the notificationappliance circuits (NACs) of the corresponding FACP, and to
permit a manual reset of the respective system. Detailed
information about the nature and location of the events can
also be displayed, via a 2”─x─ 4-3/4”, backlit LCD screen.
Models FCM2018-U3 and FCM2019-U3 contain the sitespecific program configuration created in the customconfiguration tool (Model FX901-U3). The controller in each
interface module provides all system logic and supervision.
The weight (without operating unit or batteries) is
approximately 9 Lbs [4082 g].
FCI2016-U1
(Periphery board for 252-point
Cerberus PRO Fire Safety system)
252 / 504-point Cerberus PRO Fire Safety system
252 / 504-point Cerberus PRO Fire Safety system
The Cerberus PRO Fire Safety Model FC922 (252-point)
and FC924 (504-point) addressable FACP is designed
to meet the fire-protection needs of mid-size
buildings.
This advanced panel offers features typically required
in mid-size buildings in a package that is easy to install
and competitively priced. Additionally, Models FC922
and FC924 are networkable, allowing the systems to
fulfill the growing fire-protection needs of the
building.
The following Cerberus PRO Fire Safety system
components are used in the 252-point / 504-point
FACP:
ƒ
ƒ
ƒ
ƒ
Operating units
Periphery boards
Power supplies
System enclosures
s Industry, Inc.
Building Technologies Division
FCI2017-U1
(Periphery board for 504-point
Cerberus PRO Fire Safety system)
Periphery Boards
The periphery boards (Models FCI2016-U1 and FCI2017U1) encompass the key components for operating the
Cerberus PRO panels (Models FC922 and FC924).
Each module operates and monitors input-device identity;
as well as controls the signaling-line circuits that
communicate with smoke detectors and other field
devices (i.e. ─ FDnet).
Each periphery board is equipped with two (2)
programmable ‘Class B’ (Style Y) or ‘one (1) Class A’ (Style
Z) NAC, providing 24VDC, nominal @ up to 3A per circuit
of audible / visual notification appliances.
The periphery boards mount directly on the enclosure
back boxes of the Model FC922 and Model FC922
Cerberus PRO panels. Models FCI2016-U1/ FCI2017-U1
provide two (2) parallel auxiliary powered, short-circuitprotected connections (regulated 24VDC, 1.5A max) that
supply power to external devices or modules. The system
periphery boards also include a Bell Follower terminal
connection.
Cerberus PRO Components ─ (continued)
Any of the accounts can send Alarm, Gas Alarm,
Supervisory, Trouble, Reset, or Trouble-restore data (or any
combination) as required. Each DACT can perform the
automatic 24-hour test required by NFPA, Chapter 4.
Fire Terminal Board
Fire Terminal Board (and equipment)
The Fire Terminal Unit and equipment connects to
FCNET network that can be configured for systemglobal view or specific-panel local view. This
configuration allows the operator for system control to
‘acknowledge’ events; control system NACs, and reset
the system.
The Fire Terminal Board and equipment allows for
connection to the Remote Peripheral Module (Model
FCA2018-U1) and / or the Remote Terminal Displays
(Models FT2014-U3 / R3; FT2015-U3 / R3).
A Cerberus PRO FACP can be controlled and operated
from the Fire Terminal Boards, which use large, lighted
buttons that prompt users to the next correct, available
system-operation event: Acknowledge, Silence,
Unsilence, Audible or Reset.)
The Fire Terminal Boards contain a large 6" display (1/4
VGA) monochrome LCD display, touch screen and LEDs
for displaying system status. An audible will sound
when there are unacknowledged events on the
system.
SAFEDLINK / FCnet Network Module
SAFEDLINK / FCnet Network Module
The SAFEDLINK network module (Model FN2001-A1) is
used to network up to 16 FACPs and the fire terminal
unit (Model FT2050), via the FCnet system bus. The
SAFEDLINK network module is plugged into the
Operating Unit (Models FCM2018-U3 or FCM2019-U3).
Model FN2001-A1 supports ‘peer-to-peer’ networking
between the following systems:
ƒ Model FC922
ƒ Model FC924
ƒ Model FT924
The Model FN2001-A1 connects to system-bus inputs and
outputs, and the module has ground-fault monitoring as
well as an integrated degrade-mode function.
Redundant networking is accomplished with one (1)
network module per panel [simple loop trouble]. There is
electrical isolation between the system bus and the FACP.
The Fire Terminal Boards contain the site-specific
program configuration which is created in the customconfiguration programming tool (Model FX901-U3).
170-Watt Power Supply
Digital Alarm
Communicator Transmitter
Digital Alarm Communicator Transmitter
The Digital Alarm Communicator Transmitter (DACT) is
used to provide communication between the Cerberus
PRO fire alarm control panels (Models FC922 and FC924)
and with either a central or remote monitoring station.
The Model FCA2015-U1 module mounts directly on the
back enclosure and connects to the periphery boards.
The DACT enables remote transmission of alarms and
events via a public telephone line.
Further, Model FCA2015-U1 supports two (2) lines and
four (4) accounts, and can transmit serial information
(including the address of the event) to the monitoring
station.
s Industry, Inc.
Building Technologies Division
300-Watt Power Supply
Power Supply Modules
The 170-Watt power supply (Model FP2011-U1) and 300Watt power supply (Model FP2012-U1) provide primary,
regulated (24VDC, nominal) power for normal operation
to Siemens ─ Fire Safety systems. Both power supplies
are filtered and regulated. Model FP2011-U1 is rated
24VDC, nominal, at 6.5 Amps, and Model FP2012-U1 is
rated 24VDC, nominal, at 11.5 Amps.
The 170-Watt power supply incorporates a 4.0A, nonresettable slow-blow fuse on the primary input, and
includes a built-in AC-line filter for surge and noise
suppression. Model FP2011-U1 mounts in a standard
Cerberus PRO-brand enclosure, and there are no
serviceable parts to be maintained.
Cerberus PRO Components ─ (continued)
The 300-Watt power supply incorporates two (2) 6.3A
replaceable, non-resettable slow-blow fuses on the
primary input and includes a built-in AC-line filter for
surge and noise suppression. Model FP2012-U1
mounts in a Cerberus PRO-brand enclosure, and there
are no serviceable parts to be maintained.
Model FP2011-U1 is used with Model PAD-4, as well as
with Models FC901, FC922 and FC924 FACPs. Model
FP2012-U1 operates with Model PAD-4, as well as with
Models FC922 and FC924 FACPs.
When installed on a Model FC922 or Model FC924
Cerberus PRO FACP, the releasing module contains an
integral manual-disconnect switch for releasing circuits.
This essential feature protects the releasing circuits from
accidental discharge during maintenance.
Activation can be accomplished via cross zoning of
automatic detectors or manual activation.
A pre-discharge countdown timer is available for display
at the operating units (Models FCM2018-U3 and
FCM2019-U3).
NAC Expansion Module
NAC Expansion Module
The NAC expansion module (Model FCI2011-U1) is an
optional module that is connected to the peripheral
boards (Models FCI2016-U1, FCI2017-U1), providing
additional NACs to 252-point and 504-point systems,
respectively.
One (1) ‘Class A’ or two (2) ‘Class B’ NACs are provided
with the following Cerberus PRO systems:
ƒ
ƒ
Model FC922
Model FC924
(252-point)
(504-point)
Each NAC is rated at 3 Amps. Each NAC expansion
module is monitored for open-line and short-circuit
conditions.
Releasing Module
Releasing Module
The Cerberus PRO Fire Safety System releasing module
(Model XCI2001-U1) is an optional module that is
connected to the peripheral boards (Models FCI2016U1, FCI2017-U1), providing additional NACs to 252point and 504-point systems, respectively.
Remote Peripheral Module
Remote Peripheral Module
(with RS─485 interface)
The Remote Peripheral Module (FCA2018-U1) provides a
means of connecting a Cerberus PRO Fire Safety system
to a parallel printer for creating a hard copy of systemstatus and configuration reports. This supervised,
intelligent module contains built-in transient protection
and plain-decimal addressing.
Model FCA2018-U1 is remotely connected to the Model
FCA2016-U1 RS─485 communication bus from any
Cerberus PRO Fire Safety system enclosure. Model
FCA2018-U1 uses ‘Class B’ (Style 4) or ‘Class A’ (Style 6)
wiring, and provides two (2) RS─232 (serial) ports and a
single parallel port that allow connection to the parallel
printer (Model PAL-1).
When Model PAL-1 is used with the remote peripheral
module, Model FCA2018-U1 supervises the printer for On
/ Off Line, Power On, Paper Out, Paper Jam, and wiringfault conditions, as required by UL for NFPA 72 proprietary
systems.
Event and report printing is generated at the operating
units (Models FCM2018-U3 and FCM2019-U3) on the
main Cerberus PRO system.
Model XCI2001-U1 supports activation of releasing
valves in pre-action / deluge systems (including doubleinterlock pre-action systems, or Sinorix engineered fire
suppression systems). Activation can be eventcontrolled or performed manually. Model XCI2001-U1
supports only ‘Class B’ releasing circuits.
Remote Display Terminal
(with [3] three control buttons)
s Industry, Inc.
Building Technologies Division
Cerberus PRO Components ─ (continued)
Remote Display Terminals (with RS─485 interface)
The Remote Display Terminals (Models FT2014-U3 /
R3and FT2015-U3 / R3) are LED / LCD units that show
the existing status of a Cerberus PRO FACP. A LED will
illuminate for any given Alarm, Supervisory and
Trouble Cerberus PRO-system event. A 2” ─x─ 4-3/4”
LCD screen will give details of the event in
alphanumeric form. The display screen can be scrolled
to reveal additional events. Optional remote-systemcontrol capabilities are also available.
When an event has been triggered to the FACP, the LCD
will show the following:
ƒ
ƒ
ƒ
ƒ
ƒ
Event type and zone
Time of the event
Custom message for that zone
Usage of the zone
’Unacknowledged’ or ‘Acknowledged’ event
The display has an event-initiated backlight feature
that also operates when any buttons are pressed.
The Model FT2014-series has a button used to silence
the local sounder. The Model FT2015-series has three
(3) control buttons for acknowledging events,
silencing audible circuits and resetting the system.
Additionally, there are three (3) user-programmable
buttons available. The Model FT2015-series has a key
switch that enables the control buttons to operate.
The remote display terminals are remotely connected
to the Cerberus PRO FACP, via the RS─485 interface.
The Model FC922 and FC924 Cerberus PRO panels
require the Model FCA2016-U1 RS─485 module to
provide communication to the remote display
terminals. Model FCA2016-U1 supports Style 4 or Style
6 wiring. Up to eight (8) modules can be supported on
a RS─485 bus.
Leased-Line / City-Tie Module
Leased-Line / City-Tie Module
The leased-line / city-tie module (Model FCI2020-U1) is
used as an optional module, providing a local-energy
output for municipal call-box connection. Model
FCI2020-U1 also gives a reverse-polarity output for
leased-line connection. Model FCI2020-U1 is installed
on the periphery board for Models FC922 and FC924
FACPs, respectively, but is installed on the back of the
main board of the Model FC901 FACP.
When used for connection to a municipal call box, the
city-tie function supports Alarm-event transmission.
When used for leased-line connection, the module
supports two (2) leased telephone lines for
transmitting Alarm, Trouble and Supervisory events.
s Industry, Inc.
Building Technologies Division
Single-Mode / Multi-Mode Fiber-Optic Module
Single-Mode / Multi-Mode Fiber-Optic Module
The single-mode (Model FN2006-U1) / multi-mode
(Model FN2007-U1) fiber-optic interface module can be
used to transmit RS─485 communication for the Cerberus
PRO Model FC922 and FC924 (FACP), as well as the
Model FT924 fire-alarm terminal.
The single-mode / multi-mode fiber-optic module
provides FCnet peer-to-peer network communication
between the Cerberus PRO 252-point and 504-point fire
systems.
Models FN2006-U1 / FN2007-U1 require 24 Volts DC
[nominal] power, and the Models FC922 or FC924 FACP
serve as the source for this power requirement. Models
FN2006-U1 / FN2007-U1 can also be powered from any
UL Listed, regulated 24VDC power supply, such as
Model PAD-4.
Models FN2006-U1 / FN2007-U1 can be mounted in a
Cerberus PRO one-height-unit or two-height unit
enclosure and can operate in a daisy-chain configuration.
The connection between single-mode fiber-optic modules
uses two (2), high-quality duplex 9/125 fiber-optic cables
and ST-style fiber connectors. The duplex fiber-optic cable
has two (2) cables in a single shield similar to an electrical
zip cord. Each segment of the fiber network can be up to
almost 10 miles.
For ‘Class B’ installations, each FACP or terminal at
either end of the daisy chain use one (1) duplex cable
for connection to the next networked panel or terminal.
FACPs or terminals within the daisy chain require two
(2) duplex cables: one (1) duplex cable for connection
to the previous FACP, and one (1) duplex cable for
connection to the next FACP.
For ‘Class A’ installations, each FACP or terminal requires
two (2) duplex cables: one (1) duplex cable for
connection to the previous FACP, and one (1) duplex
cable for connection to the next FACP.
Model FHB2001-U1
[for One-Height-Unit Enclosures]
Cerberus PRO Components ─ (continued)
One-Height-Unit Enclosure
For each Cerberus PRO panel, one (1) red or black back
box supports one (1) red or black outer door,
respectively. The inner door, which is available in
black, specifically stores the system operating units
(Models FCM2018-U3 and FCM2019-U3). The back
box supports the fire-terminal board (Model FTI2001U1), and optionally supports the DACT (Model
FCA2015-U1).
The one-height-unit enclosure is the smaller housing
for the Cerberus PRO Fire Safety System. The following
components comprise a complete one-height-unit
enclosure:
ƒ
ƒ
ƒ
ƒ
One (1) back box, (Model FHB2001-U1 / R1)
One (1) inner door, (Model FHD2004-U1)
One (1) outer door, (Model FHD2001-U3 / R3)
One (1) clear lens, (Model FHD2006-U1)
Approximate size: 15" (38.1 cm.) high;
20" (50.8 cm.) wide,
and 4.5" (11 cm.) deep.
Approximate size: 13.25" (33.7 cm.) high and 20" (50.8
cm.) wide.
Note: Model FHD2005-U1 is a solid blank plate used to provide
dead-front protection.
Outer-door clear windows
The window (Model FHD2006-U1) is a rugged Lexan®
lens, and is mounted to the opening of the outer door.
Approximate size: 10.25" (26.04 cm.) high and 17"
(43.2 cm.) wide.
Enclosure Trim Kits
Each size enclosure has a trim kit available in black and
red. The trim kit is used for flush mounting a Cerberus
PRO system enclosure. Model FHA2035-U1 / R1 is used
for the one-height-unit enclosure, and FHA2036-U1 / R1
is used for the two-height-unit enclosure.
DIN rail kit
The optional DIN Rail Kit (Model FHA2031-U1) mounts in
the back box of a one or two-height-unit enclosure, and
provides connection between internal-system wiring and
field wiring.
Battery bracket
An optional battery bracket (Model FHA2032-U1) can be
used to secure batteries up to 33AH. Model FHA2032-U1
is required to comply with seismic certification, pursuant
to ASC / SEI 7-05, Section 13.2.2.
Model FHB2002-U1
[for Two-Height-Unit Enclosures]
Two-Height-Unit Enclosure
The two-height-unit enclosure is the larger housing for
the Cerberus PRO Fire Safety System. The following
components comprise a complete two-height-unit
enclosure:
ƒ One (1) back box, (Model FHB2002-U1 / R1)
ƒ One (1) or two (2) inner doors,
(Models FHD2004-U1 or FHD2005-U1)
ƒ One (1) outer door,
(Model FHD2002-U3 / R3 or FHD2003-U3 / R2)
ƒ One (1) or two (2) clear windows, (Model FHD2006-U1)
Note: One (1) window is installed for Model FHD2002-U3 / R3
outer door, and two (2) windows are required for Model
FHD2003-U3 / R3.
Approximate size: 28.5" (72.4 cm.) high;
28" (71.2 cm.) wide,
and 6.0" (15.2 cm.) deep.
Inner doors
There are two (2) inner doors available for Cerberus
PRO system enclosures. Model FHD2004-U1 supports
one (1) operating unit {Model FCM2018-U3; with LED:
Model FCM2019-U3}, or one (1) to four (4) LED-option
modules (Model FCM2023-U3).
When less than four LED option modules are used, the
blank-option module (Model FCM2022-U3) covers
unused module spaces in the inner door.
s Industry, Inc.
Building Technologies Division
[LED option]
[Blank option]
LED-Option Module
Model FCM2023-U3 is a LED-option module that provides
LED annunciation of system activity.
The LED-option module contains 12 indicator zones, and
each zone contains one (1) red / green bi-color LED and
one (1) yellow LED.
Any event can be assigned to each LED, which may be
configured as a ‘static’ or ‘flashing’ indicator using the
Cerberus PRO Fire Safety system’s custom-programming
tool (Model FX901-U3). Normally the LED indicator is
used as a zone indicator.
The LED-option module is connected to the peripheral
data bus, and can be cascaded to up to a maximum of
four (4) LED modules. A space is provided for labeling of
LED functions. The label slides behind a clear, protective
membrane.
Cerberus PRO Components ─ (continued)
Blank Option Module
Model FCM2022-U3 is a Cerberus PRO Fire Safety blankoption module intended to cover any blank LED areas
where LED modules are not being occupied.
Model FCM2022-U3 and Model FCM2023-U3 are
mounted on the inner door of a Cerberus PRO Fire
Safety enclosure. Any combination of Models
FCM2022-U3 and FCM2023-U3 modules may be
mounted on the inner door. Up to four (4) total
modules can be supported.
Temperature and Humidity Range
Cerberus PRO products are UL 864 9th Edition
Listed for operation within the temperature range
of 32° to 120°F (0°C to 49°C), and a relative
humidity of 93+/-2% at a temperature of 90+/-3°F
(32+/-2°C).
Related Documentation
Model
Number
Data
Sheet
Number
Description
OH921
9600
HI921
9601
Multi-Criteria Fire Detector
Thermal (Heat) Detector
OP921
9602
Photoelectric Smoke Detector
OOHC941
9603
OOH941
9604
FDCIO422
9605
Multi-Criteria Fire / CO Detector
[with ASAtechnology™]
Multi-Criteria Fire Detector
[with ASAtechnology™]
4-Input / 4-Output Interface Module
s Industry, Inc.
Building Technologies Division
Details for Ordering
Model
Number
Part
Number
FCA2015-U1
FCA2016-U1
FCA2018-U1
FCM2018-U3
FCM2019-U3
FCI2016-U1
FCI2017-U1
FTI2001-A1
FHB2001-U1
FHB2001-R1
FHB2002-U1
FHB2002-R1
FHD2001-U3
FHD2001-R3
S54400-A63-A1
S54400-A39-A1
S54400-A65-A1
S54400-C40-A2
S54400-C41-A2
S54400-A55-A1
S54400-A56-A1
S54400-A58-A1
S54400-B47-A1
S54400-B47-A2
S54400-B48-A1
S54400-B48-A2
S54400-B45-A1
S54400-B40-A1
FHD2002-U3
S54400-B32-A1
FHD2002-R3
S54400-C53-A1
FHD2003-U3
S54400-C42-A1
FHD2003-R3
S54400-B46-A1
FHD2004-U1
FHD2005-U1
FHD2006-U1
FP2011-U1
FP2012-U1
FX901-U3
FN2001-A1
FCI2011-U1
FCI2020-U1
S54400-B52-A1
S54400-B53-A1
S54400-C46-A1
500-450222
S54400-Z60-A1
S54433-S105-A1
S54400-A60-A1
S54400-A54-A1
S54400-A57-A1
FH901-U3
S54433-B103-A3
FH901-R3
S54433-B103-A4
FCM901-U3 S54433-B101-A1
FT2014-U3
S54400-B80-A1
FT2014-R3
S54400-B73-A1
FT2015-U3
S54400-B88-A1
FT2015-R3
S54400-B16-A1
FCM2022-U3 S54400-C44-A2
FCM2023-U3 S54400-C45-A2
XCI2001-U1
S54400-A69-A1
Description
Digital dialer for Model FC901
RS─485 Interface
Remote Peripheral Module
Operating Interface Unit
Operating Interface Unit [with LED]
Periphery Board for Model FC922
Periphery Board for Model FC924
Fire Terminal Board
One-Height-Unit Back Box, black
One-Height-Unit Back Box, red
Two-Height-Unit Back Box, black
Two-Height-Unit Back Box, red
One-Height-Unit Outer Door, black
One-Height-Unit Outer Door, red
Two-Height-Unit Outer Door
[with one (1) window], black
Two-Height-Unit Outer Door
[with one (1) window], red
Two-Height-Unit Outer Door
[with two (2) windows], black
Two-Height-Unit Outer Door
[with two (2) windows], red
Inner door, black
Inner door, solid black
Clear-lens window
170-Watt Power Supply
300-Watt Power Supply
Cerberus PRO Configuration Tool
SafeDLINK Network Module
NAC Expansion Module
Leased-Line / City-Tie Module
System Enclosure, Black
{for 50-point system}
System Enclosure, Red
{for 50-point system}
50-point FACP main board
Remote Display Terminal, Black
Remote Display Terminal, Red
Remote Display Terminal, Black
Remote Display Terminal, Red
Blank-Option Module
LED-Option Module
Releasing Module
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.
s Industry, Inc.
Building Technologies Division
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (908) 547-6877
URL:
www.USA.Siemens.com/Cerberus-PRO
(SII‐FS)
Printed in U.S.A.
Fire Safety
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 / Canada
Tel: (905) 799-9937
FAX: (905) 799-9858
November 2011
New Issue