TAC MicroNet™ 100, 150, & 200 Series Controllers

• • TAC MicroNet™
100, 150, & 200 Series
Controllers
Designed for new or existing system installations, the MN 100, 150, and 200 controllers
provide control for:
• Unit Ventilators.
• Series Fan.
• Heat Pumps.
• Fan Coils.
• Packaged Rooftops.
• Field programmable using WorkPlace Tech
Tool.
• Uses LonMark HVAC profiles for interoperability.
• Capability to function in standalone mode or
as part of a LonWorks TP/FT-10 Free Topology communications network.
• Multiple controllers on a LonWorks FTT network creates a complex network of controllers for virtually any building control need.
• Proportional (P), Proportional Plus Integral
(PI), and Proportional Plus Integral and Derivative (PID) control for cooling and heating.
• The satellite profile allows the controller to
be used in a broad range of applications,
providing solutions for your building control
needs.
The TAC I/A Series MicroNet 100, 150, and 200 Controllers are interoperable controllers
designed in accordance with LonMark® guidelines. When programmed using WorkPlace
Tech Tool, or loaded with a pre-engineered application, these controllers provide control
for packaged rooftops, heat pumps, fan coils, unit ventilators, and similar applications.
Controllers feature Sensor Link (S-Link) support, LED indication, screw terminal blocks,
as well as DIN rail or panel mounting ability. These controllers can function in either
standalone mode or as part of a LonWorks® TP/FT-10 Free Topology communications
network.
The 100, 150, and 200 series controllers use the same physical packaging, but differ in
the onboard I/O points they provide.
The MN series controllers offer the advantages of standalone and networked control.
Using a TAC I/A Series MicroNet Sensor (MN-Sx series), the operator can monitor
controller performance and edit operational values. The WorkPlace Tech Tool software is
used to program the controllers.
Table-1 Model Chart.
Model
Description
1 Digital Input (DI)
TAC I/A Series
a
MNL-10Rxx MicroNet 100 Series
Controller
• Protective hinged covers provide access to
field wiring terminals.
2 Universal Inputs (UI)
4 Digital Outputs (DO)
3 Universal Inputs (UI)
TAC I/A Series
a
MNL-15Rxx MicroNet 150 Series
Controller
2 Digital Outputs (DO)
2 Analog Outputs (AO)
• Onboard LED indication without cover
removal.
• Plenum-rated enclosure allows direct mounting in plenum.
Inputs/Outputs
Profiles
Heat Pump
Fan Coil
Packaged Rooftop
Satellite
Heat Pump
Fan Coil
Packaged Rooftop
Satellite
2 Digital Inputs (DI)
TAC I/A Series
a
MNL-20Rxx MicroNet 200 Series
Controller
3 Universal Inputs (UI)
6 Digital Outputs (DO)
Heat Pump
Fan Coil
Packaged Rooftop
Satellite
2 Analog Outputs (AO)
a
xx denotes LONMARK profile and profile version /F=Fan Coil, H=Heat Pump, R=Rooftop,
S=Satellite). Satellite profile is based on Rooftop profile.
Software Capabilities
• Allows design of a complete custom application for each controller.
• Conforms to the LonMark guidelines.
• WorkPlace Tech Tool is capable of reconfiguring and editing application configuration data.
• HVAC interoperability achieved through use of
LonMark HVAC profiles.
• All controllers are field programmable, but
controllers with satellite profiles are especially suited for a broad range of applications,
providing solutions for your building control
needs.
Table-2 Inputs from MN-Sx TAC I/A Series MicroNet Sensor.
Inputs
Description
MN-Sx Sensor
Space Temperature
32 to 122 °F (0 to 50 °C)
MN-S1, MN-S1HT, MN-S2, MN-S2HT,
MN-S3, MN-S3HT, MN-S4, MN-S4HT,
MN-S4-FCS, MN-S4HT-FCS, MN-S5 and
MN-S5HT
Space Humidity
5 to 95% RH, Non-condensing
MN-S1HT, MN-S2HT, MN-S3HT,
MN-S4HT, MN-S4HT-FCS, and MN-S5HT
Adjustable Setpoint 40 to 95 °F (4 to 35°C)
MN-S3, MN-S3HT, MN-S4, MN-S4HT,
MN-S4-FCS, MN-S4HT-FCS, MN-S5, and
MN-S5HT
Override Pushbutton
For standalone occupancy control or remote status monitoring
of local status condition.
MN-S2, MN-S2HT, MN-S3, MN-S3HT,
MN-S4, MN-S4HT, MN-S5, and
MN-S5HT
Fan Operation and
Speed
Fan mode selection: On, Speed
(Low/Medium/High), or Auto.
MN-S4, MN-S4HT, MN-S4-FCS,
MN-S4HT-FCS, MN-S5, and MN-S5HT
System Mode
System mode selection: Heat,
Cool, Off, or Auto.
MN-S4, MN-S4HT, MN-S5, and
MN-S5HT
Emergency Heat
Emergency heat mode selection:
Enable or Disable
MN-S5 and MN-S5HT
Communications
LonWorks Networks
A LonWorks communications network uses an TP/FT-10 Free Topology configuration.
Controllers on a LonWorks network can communicate with each other in a peer-topeer fashion. A LonWorks network has a communications speed of 78k baud, using
unshielded, twisted-pair cabling, with connections that are not polarity sensitive.
S-Link
The Sensor Link (S-Link) communications wiring provides power and a communication interface for an MN-Sx TAC I/A Series MicroNet sensor. The various MN-Sx
sensors can provide room temperature, room humidity, setpoint adjustment, and occupancy override. This connection uses two-wire, unshielded cable and is not polarity
sensitive. Maximum wire length allowed between a controller and a TAC I/A Series
MicroNet Sensor is 200 ft (61 m).
2
SPECIFICATIONS
Dimensions
4-5/16 H x 4-3/8 W x 2 D in
(109 x 111 x 51 mm).
Ambient Limits
Universal Input
Operating Temperature
-40 to 140 °F (-40 to 60 °C).
Enclosure
Conforms to NEMA-1 requirements.
Shipping and Storage Temperature
-40 to 160 °F (-40 to 71 °C)
1K ohm Balco Input
-40 to 250 °F (-40 to 121°C) range.
TSMN-81011, TS-8000 Series or
equivalent.
Meets UL94-5V flammability for plenum application use.
Humidity
5 to 95% RH, non-condensing.
Conduit Knockouts
Wiring Terminals
Not applicable. Order optional MicroNet
Screw terminals. Each terminal accepts
Enclosure, MNA-FLO-1, if wiring to flexone AWG #16 to #24 (1.31 to 0.205
ible conduit is desired.
mm2 maximum) wire.
Power Supply Input
20.4 to 30 Vac, 50/60 Hz.
Maximum Power Consumption
15 VA @ 24 Vac, 50/60 Hz, excluding
relay output power.
Surge Immunity Compliance
IEEE C62.41 (IEEE-587, Category A &
B).
Agenc y Listings
FCC
Class B.
UL
UL-916 (File # E71385 Category PAZX).
UL Listed to Canadian Safety Standards
(CAN/CSA C22.2).
Digital Inputs
(MN 100 and MN 200 only) Dry Contact. Detection of closed switch requires
less than 300 ohm. Detection of open
switch requires more than 100K ohm.
Digital Outputs
Current Ratings
24 VA at 24 Vac, pilot duty.
1K ohm Platinum Input
-40 to 240 °F (-40 to 116 °C) range.
TSMN-58011, TS-5800 Series or
equivalent.
1k Resistance
0 to 1.5k ohms.
10K ohm Thermistor w/ 11K ohm Shunt
Resistor
-40 to 250 °F (-40 to 121 °C) range.
TSMN-57011-850, TS-5700-850 Series
or equivalent.
10k Resistance
0 to 10.5k ohms.
Voltage
0 to 5 Vdc.
Current
0 to 20 mA requires an external 250
ohm shunt resistor.
Digital Input
Dry Contact. Detection of closed switch
requires less than 300 ohms. Detection
of open switch requires more than 1.5K
ohms.
European Community – EMC Directive
89/336/EEC
EN61326
Analog Outputs
(MN 150 and MN 200 only).
Mounting
35 mm DIN rail or panel.
Current
0 to 20 mA. (Output load from 80 to
550 ohms).
3
PDA
TAC MicroNet Sensor
(MN-S5 Shown)
Desktop PC or
Notebook PC with
WorkPlace Tech
Tool Software 1
2
5
MNL-V3RVx
or MN 50
Controller
4
MN 100, MN 150, or
MN 200 Controller
SW
24H
SW 3
24H
2
24H
24H 1
SW
MNL-CIM
TAC MicroNet Controller
Interface Module
24G
GN
AO
D
S-L
Router 6
(if required)
DO1
24VAC
DO2
DO3
24VAC
DO4
934G
E9429
8.5VA + DO1-DO4 loads.
N2223
Temperature indicating and
Regulating Equipment
Power: 24VAC, 50/60Hz, Class 2,
CAUTION
Ambient Temp: -40°C to +60°C
UI: 5VDC Max, Class 2.
S-LK: 16VDC Max, Class 2.
DO1-DO4: 24VAC, 0.4A Max Total Load.
DO5: 250VAC, 3A Max, COS f = 0.4.
DO5
C5
RI SK OF ELECTRI CAL SHOCK OR FI RE. DO NOT
I NTERCONNECT SEPARATE CLASS 2 CI RCUI TS.
DI SCONNECT POWER BEFORE S ERVI CI NG.
This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
NTRETEN.
T E
device
must accept any interference received, including
and (2) This
device may DECONNECTER
not cause harmful interference,AVAN
interference that may cause undesired operation.
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
LONWORKS
Network
UNC Controller
I/A
T
MN
Se
X
M
I
rie
0
J1
s®
I/A Series
MNL-11RF2
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
SRVC
R
S
E
R
C
V
V
C
80
UI
K/C DI
OM
S-L
K
LO
N
LO
N
3
MNL-V1RVx or
MNL-V2RVx
Controller
MN 110 or MN 130
Controller
MN 800
Controller
4
TAC MicroNet Sensor
(MN-S3 Shown)
1 A PC can be connected to the LONWORKS TP/FT-10 Network, either directly or through the LONWORKS network jack of a
LONWORKS controller or MN-Sxxx Wall Sensor. The PC must have an Echelon® LonTalk® adapter card.
2 Programming any of the TAC I/A Series controllers, or the TAC I/A Series MN 800 controller, requires WorkPlace Tech Tool.
3 This controller is not suitable for exposed mounting on a wall or panel, or in any other easily accessible place due to the
possibility of personal contact with the high-voltage terminals. It must be mounted inside a suitable grounded metal enclosure.
4 MicroNet Sensors can be connected to any MN controller.
5 A PDA running the Pocket TAC I/A interface software may be used to communicate with TAC MicroNet I/A Series controllers.
6 When routers are used, WP Tech is able to communicate through them to any of the TAC I/A Series devices on the network.
TAC MicroNet Sensor MN 100, MN 150, or
MN 200 Controller
(MN-S5 Shown)
MN 800
Controller
MN 110 or MN 130
3 Controller
4
I/A
MN
rie
s®
934G
E9429
DO1
24VAC
DO2
DO3
24VAC
DO4
8.5VA + DO1-DO4 loads.
N2223
Temperature indicating and
Regulating Equipment
Power: 24VAC, 50/60Hz, Class 2,
CAUTION
Ambient Temp: -40°C to +60°C
UI: 5VDC Max, Class 2.
S-LK: 16VDC Max, Class 2.
DO1-DO4: 24VAC, 0.4A Max Total Load.
DO5: 250VAC, 3A Max, COS f = 0.4.
DO5
C5
RI SK OF ELECTRI CAL SHOCK OR FI RE. DO NOT
I NTERCONNECT SEPARATE CLASS 2 CI RCUI TS.
DI SCONNECT POWER BEFORE SE RVI CI NG.
This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
NTRETEN.
T E
device
must accept any interference received, including
and (2) This
device may DECONNECTER
not cause harmful interference,AVAN
interference that may cause undesired operation.
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
T
Desktop PC with TAC I/A Series
Enterprise Server
LONWORKS
Network
Se
80
0
X
M
I
J1
I/A Series
24G
D
S-L
UNC Controller
MNL-11RF2
CLO
SE
OP 24G
EN
SW 24G
24H
SW 3
24H
SW 2
24H
24H 1
GN
MNL-V1RVx or
MNL-V2RVx
Controller
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
SRVC
S
R
R
E
V
C
C
V
6 Router
(if required)
Ethernet
AO
CO
M
UI
K/C DI
OM
S-L
K
LO
N
LO
N
MNL-V3RVx
or MN 50
Controller
4
TAC MicroNet Sensor
(MN-S3 Shown)
Figure-1 TAC I/A Series MicroNet MN 100, 150, and 200 Series Controller Connectivity.
Copyright © 2006, TAC
All brand names, trademarks and registered trademarks are
the property of their respective owners. Information contained
within this document is subject to change without notice.
All rights reserved.
F-26291-6
TAC
1354 Clifford Avenue
PO Box 2940
Loves Park, IL 61132-2940
www.tac.com
Distributed, manufactured, and sold by TAC. I/A Series
trademarks are owned by Invensys Systems, Inc. and are used
on this product under master license from Invensys. Invensys
does not manufacture this product or provide any product
warranty or support. For service, support, and warranty information, contact TAC at 1-888-444-1311.