Classic Heat Pumps
Vertical Packaged Heat Pumps
Single stage cooling models AVPA24-30-36-42-48-60 and
HVPA24-30-36-42-49-60 and
2-stage cooling models HVPSA36-42-49-60
General Description
The Marvair® Classic wall mounted heat pumps are the ideal HVAC system
for a wide variety of applications. The exterior mounting means that no
valuable interior space is required. The Classic heat pumps are packaged
units – the refrigerant piping and internal wiring are factory assembled
and thoroughly tested. All components are readily accessible for easy
service and maintenance. The energy efficient operation keeps operating
costs to a minimum and makes the Marvair heat pumps ideal problem
solvers for a wide variety of applications, including offices, classrooms and
telecommunication shelters.
Three Series to meet any Budget or Efficiency Requirement - Three
series of Classic heat pumps are available. The Classic HVPA models are
our most efficient models and feature EERs (Energy Efficiency Ratio) of up
to 11.50. No wall mount heat pump is more efficient. The HVPSA models
feature a 2-stage compressor that matches the cooling capacity to the
heat load. Our AVPA models have EERs of up to 9.75. The AVPA & HVPA
(single stage compressor units) are built in nominal cooling capacities of
2, 2½, 3, 3½, 4 and 5 tons. The HVPSA (2-stage compressor) units are
available in nominal cooling capacities of 3, 3½, 4 and 5 tons.
Outside Air for Ventilation or Free Cooling - A full range of accessories and options allows the Classic
heat pumps to be optimized for each application. For classrooms, a complete range of ventilation
options are available to meet the fresh air requirements of the ASHRAE 62 standard, “Ventilation
for Acceptable Indoor Air Quality”, including the exclusive Marvair GreenWheel® Energy Recovery
Ventilator. Where cooling is required during cool or cold weather, e.g., telecommunications shelters, a
factory installed economizer should be used. To insure proper operation and optimum performance, all
outside air ventilation packages are non-removable, factory installed and factory calibrated.
2-Stage Compressor -The HVPSA models feature a two stage compressor with a first stage capacity
of 65% of the total capacity. The two stage compressor offers better comfort by maintaining more
precise temperature and relative humidity levels with improved overall energy efficiency. During mild
days, the first stage can satisfy the load, minimizing temperature fluctuations providing steady, even
comfort. With Integrated Part Load Performance Values (IPLV) of up to 15.0, the Classic heat pump
with the two stage, high efficiency compressor can provide significant energy savings compared to
older, less efficient systems. The cooling mode has two stage operation; heating is single stage.
Quiet in the Classroom - In addition to high efficiency, the HVPA and HVPSA models minimize sound
levels in the classroom. A high efficiency axial fan moves air silently through the outdoor
coils. A low vibration, scroll compressor insures quiet operation as well as energy efficiency.
The indoor air mover utilizes a revolutionary electronically commutated motor (ECM). This
motor consumes a minimum of power with whisper quiet operation. The ECM automatically
adjusts its speed to maintain the proper air flow at various external static pressures.
Safety Listed and Energy Certified - All Classic heat pumps are built to UL standard 995, 2nd
edition and CAN/CSA C22, No. 236-5, 2nd edition. For energy efficiency and performance, the units
are tested and rated in accordance to the ANSI/AHRI (Air-Conditioning Heating and Refrigeration
Institute) Standard 390 (Single Package Vertical Units). All units meet or exceed the efficiency
requirements of ANSI/ASHRAE/IESNA 90.1.2007. The Classic heat pumps are commercial units and
are not intended for use in residential applications.
Dehumidification - The introduction of outside air can cause humidity levels to rise to unacceptable
levels. To reduce humidity, the Classic heat pumps can be ordered with a Hot Gas Reheat (HGR) coil.
The HGR coil allows the heat pump to dehumidify without adversely lowering the temperature in the
classroom and uses less energy than electric reheat. When used in conjunction with the GreenWheel®
ERV, humidity levels can be controlled at a minimum of expense. See page 4 for a detailed description
of the operation of the Hot Gas Reheat Coil.
Classic AVPA, HVPA & HVPSA PDS 8/2012 rev.3
Classic™ Heat Pump Features
High Efficiency
• Scroll compressors are standard
on all units.
• Lanced fins and rifled tubing
on the indoor & outdoor coils
maximize heat transfer.
• Electronically commutated indoor
blower motor on the HVPA &
HVPSA models and two speed
indoor blower motor on the AVPA
models.
Engineered Reliability
• PC board simplifies wiring,
consolidates several of the
electrical functions in one device.
• High refrigerant pressure switch
with lockout relay protects the
compressor in the event of
insufficient condenser air flow.
• Loss of charge pressure switch
with lockout relay protects the
compressor in the event of a
loss of refrigerant or inadequate
evaporator air flow.
• Time delay for short cycle protection.
• Copper tube, aluminum fin
evaporator and condenser coils.
• Corrosion resistant Dacromet®
external fasteners.
Ease of Installation
• LED’s on the control board
indicate operational status and
fault conditions.
• Refrigerant access valves are
standard
• All major components are readily
accessible
• Front control panel allows easy
access and complies with NEC
clearance codes on side by side
units.
• Major components accessible
from either side.
• Sloped top with flashing
eliminates need of rain hood.
• Built-in mounting flanges
facilitate installation and
minimize chance of water leaks.
• Factory installed disconnect on all
units, including 460v. models.
• Outside air hood included with
each unit.
Rugged Construction
• Baked on beige finish over
galvaneel steel on exterior sheet
metal.
Ease of Service
Outside Air for Ventilation
ASHRAE standard 62 requires 30 cfm of outside air per occupant of a classroom. To meet this requirement, Marvair
offers five ventilation packages for every budget and requirement.
•
•
•
•
•
•
GreenWheel® total Energy Recovery Ventilator that can recover both sensible and latent heat with efficiencies up to 65%. Ventilation Configuration “H”.
Manual, two position damper (open and closed) capable of 0 to 450 cfm of outside air; includes pressure relief. A 24-volt actuated motor controls the damper from an external input such as a time clock, CO2 sensor, energy management system or a manual switch. Ventilation Configuration “B”.
Manual damper capable of 0 to 450 cfm of outside air (not to exceed 40% of rated air flow), field adjustable, includes pressure relief. Ventilation Configuration “Z”.
Manual damper capable of 0 to 450 cfm of outside air (not to exceed 40% of rated air flow), field adjustable, no pressure relief. Ventilation Configuration “Y”.
Manual damper capable of up to 15% of rated airflow of outside air; field adjustable, no pressure relief. Ventilation Configuration “N”.
GreenCube total Energy Recovery Ventilator that can recover both sensible and latent heat. Includes two ventilation motors- one for intake air and a second for the exhaust air and two controllers to allow independent control of each motor. Ventilation Configuraton “Q”.
Outside Air Ventilation Schedule
Ventilation
Package
Designator*
Description
Outside Air Capability
Pressure
Relief
H
GreenWheel® ERV. Includes a ventilation intake air blower, a ventilation 0-450 CFM
intake air filter, a ventilation exhaust blower and a single fan speed
controller for both motors. Optional second fan speed controller for the
exhaust air. This second controller allows independent control of the
exhaust air motor and positive pressurization of the classroom.
Yes
B
Motorized, two position damper (open and closed) includes pressure
Up to 450 cfm, but not to
relief. A 24-volt actuated motor controls the damper from an external exceed 40% of the rated air
input such as a time clock, CO2 sensor, energy management system or flow of the heat pump.
a manual switch.
Yes
Z
Y
N
C
Q
Manual damper, field adjustable
Up to 450 cfm, but not to
exceed 40% of the rated air
flow of the heat pump.
Yes
Manual damper, field adjustable
Up to 450 cfm, but not to
exceed 40% of the rated air
flow of the heat pump.
No
Manual, fixed position damper
0-15% of rated air flow
No
Economizer
100% of rated air flow of
outside air
Yes
GreenCube ERV
0-300 cfm of outside air
Yes
*See Model Identification Chart.
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
2
Classic Heat Pump Ventilation Option
GreenWheel® ERV exhaust air motor controller – Allows independent control of the exhaust and intake blowers.
When used, the standard speed controller operates the intake blower and the optional second controller, the exhaust
blower. Individual blower control allows positive pressurization of the classroom. Field or factory installed.
The Unique Marvair® GreenWheel® Energy Recovery Ventilator
The Marvair® GreenWheel® ERV is a total energy (both sensible and latent) wheel that reduces both construction and
operating cost while ventilating the classroom to ASHRAE 62-1999 requirements. The use of the GreenWheel ERV
reduces the energy load of the outside air. Exhausting stale, inside air keeps indoor pollutants and harmful gases to
a minimum. The Marvair GreenWheel ERV has been tested and certified according to ARI Standard 1060.
How It Works - During the summer, cool dry air from the classroom is exhausted through the GreenWheel ERV to
the outside. As the air passes through the rotating wheel, the desiccant becomes cooler and drier. Simultaneously,
hot humid air is being pulled across the rotating wheel. The cool, dry desiccant absorbs moisture and heat from the
incoming air. The cooler, drier air is mixed with the return air from the classroom and distributed throughout the
room.
In the winter, warm moist air is exhausted through the GreenWheel ERV to the outside. As the air passes through
the rotating wheel, the desiccant becomes warmer and absorbs moisture. Simultaneously, cold dry air is being pulled
across the rotating wheel. The cold, dry air absorbs heat and moisture from the desiccant. The warmed air is mixed
with the return air from the classroom and distributed throughout the room.
Quality Components - The GreenWheel ERV Ventilation package consists of the GreenWheel cassette, an incoming
air blower, an exhaust air blower, an air filter for the incoming air and one fan speed controller that controls the
speed of both blower motors simultaneously. As an option, a second fan speed controller can be factory installed for
independent control of the exhaust air motor and positive pressurization of the classroom. Also, an optional filter on
the exhaust air is available on selected models. Please consult your Marvair representative for details. The two blowers
simultaneously pull fresh air from outside and exhaust air from the classroom through the rotating wheel. The air
streams are separated by an insulated partition so that the incoming fresh air is not mixed with the exhaust air. Two
variable speed blowers ensure that up to 450 CFM of outside air can be brought into the room and the indoor air is
properly exhausted. Variable speed blowers permit that the desired quantity of outside air is delivered into the room.
Optional independent exhaust air blower control allows positive pressurization of the classroom, i.e., more outside air
can be introduced through the GreenWheel ERV than is exhausted.
WINTER OPERATION
OUTSIDE 17°F DB/15°F WB
INSIDE 70°F DB/58°F WB
AIRFLOW: 450 SCFM
SUMMER OPERATION
OUTSIDE 95°F DB/75°F WB
INSIDE 80°F DB/67°F WB
AIRFLOW: 450 SCFM
GreenWheel® ERV
GreenWheel® ERV
86°F DB
71°F WB
48°F DB
43°F WB
95°F DB Fresh Air In
75°F WB
Inside
Outside
Inside
80°F DB
67°F WB
89°F DB
72°F WB
17°F DB
Fresh Air In
15°F WB
Outside
70°F DB
58°F WB
Classroom Air Out
39°F DB
37°F WB
Classroom Air Out
GreenWheel Performance
GreenWheel® ERV Performance
95° DB/73° WB Outside
80° DB/67° WB Inside
Energy Conserved, BTUH
Sensible Latent
Total
2,900
1,100
4,000
3,100
1,200
4,300
3,700
1,400
5,100
4,200
1,500
5,700
4,500
1,600
6,100
95° DB/80° WB Outside
80° DB/67° WB Inside
Energy Conserved, BTUH
Sensible Latent
Total
2,900
6,400
9,300
3,100
6,900
10,000
3,700
8,100
11,800
4,200
9,100
13,300
4,500
9,700
14,200
90° DB/74° WB Outside
75° DB/64° WB Inside
Energy Conserved, BTUH
Sensible Latent
Total
2800
3600
6400
3000
3800
6800
3600
4500
8100
4100
4900
9000
4300
5200
9500
80° DB/70° WB Outside
75° DB/64° WB Inside
Energy Conserved, BTUH
Sensible Latent
Total
900
2800
2700
1000
3000
4000
1200
3500
4700
1400
3800
5200
1400
4000
5400
60° DB/54° WB Outside
70° DB/58° WB Inside
Energy Conserved, BTUH
Sensible Latent
Total
1900
200
2100
2000
200
2200
2400
200
2600
2700
300
3000
2900
300
3200
40° DB/36° WB Outside
70° DB/58° WB Inside
Energy Conserved, BTUH
Sensible
Latent
Total
225
5600
3300
8900
250
6000
3600
9600
325
7200
4200
11400
400
8100
4600
12700
450
8600
4800
13400
*SCFM = Standard Cubic Feet per Minute
20° DB/18° WB Outside
70° DB/58° WB Inside
Energy Conserved, BTUH
Sensible
Latent
Total
9300
4900
14200
10000
5300
15300
12000
6200
18200
13500
6800
20300
14400
7100
21500
0° DB/7° WB Outside
70° DB/58° WB Inside
Energy Conserved, BTUH
Sensible
Latent
Total
13000
5700
18700
14000
6100
14100
16700
7100
23800
18900
7900
26800
20100
8200
28300
SCFM* of Outside Air
225
250
325
400
450
SCFM* of Outside Air
225
250
325
400
450
SCFM* of Outside Air
For performance of the GreenWheel ERV at conditions other than those shown, please contact your Marvair® representative or the factory. A
return filter grille is required on all HVPA24 heat pumps with the GreenWheel ERV ventilation option.
3
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Economizer
The economizer reduces the cost of air conditioning by using outside air when acceptable to cool the room. The
factory installed Marvair® economizer has integral pressure relief. On a signal from a thermostat that cooling is
required, either mechanical cooling with the compressor or free cooling with the economizer is provided. The Marvair
economizer is capable of bringing in outside air equal to 100% of the rated cooling capacity of the unit and has built
in pressure relief.
An internal enthalpy controller determines whether the outside air is sufficiently cool and dry to be used with cooling.
If suitable, the compressor is locked out and the economizer damper opens to bring in outside air. The temperature at
which the economizer opens is adjustable from approximately 55°F (13°C) to 73°F (23°C) at 50% RH. If the outside
air becomes too hot or humid, the economizer damper closes completely or to a minimum position and mechanical
cooling is activated. When used with minimum position potentiometer (optional), the Marvair® economizer can meet
requirements of ASHRAE Std. 62.
GreenCube™ ERV Ventilation Configuration “Q”
The Marvair GreenCube ERV is an enthalpy plate heat exchanger that transfers both sensible and latent energies
between outgoing and incoming air streams in a cross flow arrangement. Except for two air movers, it has no moving
parts. It can introduce up to a maximum of 300 cfm of outside air into the classroom. Two MERV 6 type filters are
used on both sides of the enthalpy core. The fresh air and exhaust motors have independent speed controllers to
permit each of the motors to be regulated independently.
The media is impregnated with a RC134 polymeric desiccant that exchanges water by direct vapor transfer using
molecular transport without the need of condensation. The GreenCube ERV will operate at temperatures as low as
10°F with no defrost mechanism. In addition, the desiccant is a bactericide.
The GreenCube ERV is only available on HVPSA units (2-stage compressor). All HVPSA units with the GreenCube
ERV, including the HVPSA36 and HVPSA42, are in the HVPSA49/60 cabinet (see page 27).
Hot Gas Reheat Operation
Marvair® heat pumps equipped with Hot Gas Reheat (HGR) allow the indoor humidity of the controlled environment
to be maintained at or below a certain humidity set point. These units do not have the ability to add humidity to the
classroom. Dehumidification is achieved by operating mechanical cooling in conjunction with a hot gas reheat coil.
Operation - If the humidity rises above the set point on the humidity controller and the temperature in the classroom
is satisfied, both mechanical cooling and the HGR coil operate to temper the air and lower the humidity. If the
temperature in the classroom rises above (or falls below) the set point of the thermostat and the unit is operating in
the dehumidification mode, the call for cooling (or heating) will override the call for dehumidification and the coil is
disengaged until the thermostat is satisfied. This assures the environment temperature is maintained as first priority
and humidity control is second.
Heat Pump PC Board
Each Classic heat pump has a PC board that controls the operation of the indoor blower, the compressor and the
reversing valve while providing high refrigerant pressure and loss of refrigerant protection with an integral defrost
function. In addition, the board has user selectable pins and potentiometers for multi-function control.
High & loss of refrigerant protection – If either of these fault conditions occur twice within an one hour, the control
board will enter into and indicate the lockout mode. In the lockout mode, the compressor will not operate, the alarm
output is energized and the red LED will blink to indicate which fault has occurred. The user can select either Normally
Open or Normally Closed contacts.
Compressor anti-short cycle protection – An integral three minute delay prevents compressor from destructive
short cycling.
Loss of Refrigerant By-pass Timer – To prevent nuisance fault alarms, the board ignores a loss of charge fault for
three minutes on start-up of the compressor.
Defrost Control – The defrost cycle removes ice build-up on the outdoor coil during the heating cycle. If the defrost
sensor senses a coil temperature of 32°F while in the heat mode, a 30, 60 or 90 minute (user selectable) delay period
will begin. After the delay period if the sensor is still calling for a defrost cycle, the outdoor fan will be stopped and
the reversing valve energized. The defrost cycle will stop if the defrost sensor registers a temperature of 50°F or after
10 minutes.
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
4
By moving a pin on the board, the user can have electric heat operating during the defrost cycle or not operate.
S-Circuit – The user can move a pin on the board to control whether the electric heat will operate simultaneously
with the compressor.
Indoor Blower Speed Control – a speed control potentiometer mounted on the board allows the user to vary the
blower speed on the AVPA heat pumps from 40% to 100% of rated air flow. (Not applicable to the HVPA and HVPSA
units with the electronically commutated indoor blower motor).
Ventilation Damper Relay – The board has a dedicated relay to control a two position – Open & Closed - motorized
fresh air damper (Ventilation Configuration “B”).
Protection of the Refrigerant Components
High Refrigerant Pressure Switch – The high pressure switch is located on the liquid line. It is electrically connected
to the PC board and will turn the compressor off if the pressure rises above the set point twice within one hour. This
protects the compressor if airflow is significantly reduced or lost through the coil performing the condenser function.
Loss of Charge Switch – The loss of charge switch is located on the liquid line. It is electrically connected to the PC
board and will turn the compressor off if the pressure drops above the set point twice within one hour. This protects
the compressor if airflow is significantly reduced or lost through the coil performing the evaporator function or there
is a loss of refrigerant.
Classic Heat Pump Options
Marvair® options can be used to provide optimum performance over a full range of operating conditions.
Adjustable Outdoor Thermostat – Will not allow electric resistance heat to be energized unless the outdoor
temperature is below the desired set point. Field or factory installed. Available on all Classic™ units.
Energy Management System (EMS) Relay Kit -Relay to control the unit. Available in 24, 120 or 240 VAC. Field
or factory installed.
Electric Reheat – Control provides simultaneous operation of compressor when in cooling mode and the electric
elements to provide dehumidification without over cooling the room. The electric element (kW) must be properly sized
for each model for proper operation. Factory installed. Available on all Classic™ units. Consult factory for details.
Phase Monitor - Monitors 3Ø power supply and will turn the air conditioner off if power supply is not phased properly.
Not required on 1Ø units.
Compressor sound jackets - Reduces sound of compressor
Special Application Packages and Coil Coatings
Coastal Environmental Package - Recommended for units to be installed near an ocean or on seacoast. Includes
corrosion resistant fasteners, sealed or partially sealed condenser fan motor, protective coating applied to all exposed
internal copper and metal in the condenser section and a protective coating on the condenser coil. See Coastal
Environmental Technical Bulletin for more details.
Protective Coil Coatings - Either the condenser or evaporator coil can be coated, However, coating of the evaporator
coil is not common. For harsh conditions, e.g., power plants, paper mills or sites were the unit will be exposed to salt
water; the coil should be coated. Note: Cooling capacity may be reduced by up to 5% on units with coated coils.
5
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Classic Heat Pump Model Identification
••• S A
•
Nominal Cooling
24 = 23,500
30 = 30,000
36 = 36,000
42 = 40,000
48/49 = 50,000
60 = 59,000
HP •
Power Supply
A = 208/230V,
1ø, 60Hz
C = 208/230V,
3ø, 60Hz
D = 460V,
3ø, 60Hz
System Type
Heat Pump
AVP = Air Source Vertical Package
HVP = High Efficiency Air Source Package
•
Ventilation Configuration
N =0-15% fresh air with manual
damper, no pressure relief.
Series
BTUH
BTUH
BTUH
BTUH
BTUH
BTUH
R410A
Refrigerant
2 Stage
Cooling
• ••
Y =0 to 450 cfm of outside air, field
adjustable, manual damper, no
pressure relief.
•
•••
Cabinet
100 = 200 = 300 = 400 = Color
Beige
Gray
Brown
White
Z =0 to 450 cfm of outside air, field
adjustable, manual damper,
includes pressure relief.
Electric Heat
00 = No Heat
040 = 4 kW
050 = 5 kW
060 = 6 kw
090 = 9 kW
100 = 10 kW
120 = 12 kW
150 = 15 kW
B =Motorized two position damper
(open & closed) capable of 0 to
450 cfm of outside air, includes
pressure relief.
C =Economizer; capable of 100%
of rated cooling capacity using
outside air.
Special Option Code
R =Electric Reheat
U = Scroll
Compressor
G =HGR (Hot Gas
Reheat
H =GreenWheel® energy recovery ventilator
Q =GreenCube energy recovery
ventilator
Accessories
Thermostats for Single Stage Heat Pumps (no electric heat)
Digital, non-programmable thermostat. 1 stage heat, 1 stage cool. Fan switch: Auto & On. Manual changeover system
switch: Cool-Off-Heat. Low temperature protection. °F or °C selectable. Thirty minute power loss memory retention.
Marvair P/N 50121.
Digital, seven day programmable thermostat. 1 stage heat, 1 stage cool. Fan switch: Auto & On. Auto-changeover.
Keypad lockout. Non-volatile program memory. Title 24 compliant. Marvair P/N 50123.
Digital, non-programmable thermostat. One stage cool/One stage heat. Manual or auto changeover. Fan mode:
Auto or On. Permanent retention of settings upon power loss. Field adjustable temperature calibration. Max heat and
minimum cool set points. Adjustable temperature differential. Remote sensor capable. Keypad lock out. Status LED.
°F or °C selectable. Marvair P/N 50186
Thermostats for Heat Pumps with Two Stage Heat
Digital, 7 day, 5-2 and 5-1-1 day programmable thermostat. Two stage heat/Two stage cool. Manual or auto
changeover. Fan: Auto & On. Permanent retention of setting on power loss. Field adjustable temperature calibration.
Adjustable max. setpoint for heating and min. adjustable setpoints for cooling.
Adjustable temperature differential. Keypad lockout. Status LED. °F or °C
selectable. Title 24 compliant. Marvair P/N 50107.
Digital, 7 day, 2 occupied & 2 unoccupied periods for each day of the week
programmable thermostat. Three stage heat/Three stage cool. Manual or
auto changeover. Fan: Auto & On. Ten year retention of programming
settings and 48 hour clock and day settings on power loss. Adjustable max.
setpoint for heating and min. adjustable setpoints for cooling. Adjustable
temperature differential. Keypad lockout. Status LED. °F or °C selectable.
Optional remote sensors for outdoor air, supply air and humidity. Title 24
compliant. Marvair P/N 50248.
Digital, non-programmable thermostat. Two stage heat/Two stage cool.
Manual or auto changeover. Fan: Auto & On. Permanent retention of setting
on power loss. Field adjustable temperature calibration. Adjustable max. setpoint for
heating and min. adjustable setpoints for cooling. Adjustable temperature differential. Keypad lockout. Status LED. °F
or °C selectable. Marvair P/N 50252.
MAR7000 Thermostat/Controller. The MAR7000 thermostat/controller is a stand alone, self-programming HVAC
controller designed to optimize performance of Marvair’s heat pumps and air conditioners. It can function as an
independent controller or used in conjunction with a BACnet network.
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
6
With built-in temperature and humidity sensors, motion sensing and an optional CO2 detection sensor, the
MAR7000 can control:
• Single or 2-stage air conditioners or heat pumps with supplemental hot water or electric heat,
• Hot gas dehumidification operation,
• An economizer cycle, and
• Marvair’s various ventilation options including the Marvair GreenWheel® Energy Recovery Ventilator.
The intelligent occupancy anticipation feature of the MAR7000 automatically programs occupied and unoccupied
settings for temperature, humidity, and ventilation requirements. The ventilation control can be based on
occupancy, demand, time, or a combination of these features. When vacant, the thermostat automatically reduces
the run time of the unit and adjusts ventilation to save energy. The intelligent occupancy feature can be turned off,
and the MAR7000 can be connected to a BACnet control system for remote control and operation of Marvair heat
pumps or air conditioners. The MAR7000 thermostat includes a precise, real time clock with capacitor back up to
maintain the program and set points for extended power outages.
Features include:
• User-friendly English-language menus (no obscure numeric codes) on a 64 x128 pixel, dot-matrix LCD display
with 5 buttons for data selection and entry,
• Built-in, factory-tested libraries of configurable application control sequences,
• Schedules that can easily be set uniquely by weekdays (Mon.–Fri.), weekend (Sat.–Sun.), entire week (Mon.–
Sun.), individual days, and/or holidays,
• Six On/Off and independent heating and cooling set point periods are available per day, and
•Three levels of password-protected access (user/operator/administrator) prevent disruption of operation and configuration
Thermostat guards
Clear thermostat guard with keylock & clear plastic cover & base. For use with 50121, 50123, 50186, 50107 and 50252
thermostats. Marvair P/N 50092.
Clear thermostat guard with keylock & clear plastic cover & base. For use with 50248 thermostat. Marvair P/N50119.
Humidity controller
Digital humidity controller. To be used with units with Hot Gas or electric reheat. Programmable dehumidistat, ventilation
control. Permanent memory retention of set points. Humidity sensor can be field calibrated. High & low dehumidification
set points. Outdoor temperature and humidity sensor included. ºF or ºC selectable. Marvair P/N 50254.
Grilles
Description
Size
Marvair P/N
For the AVPA24
Double deflection, aluminum supply grille
20” x 8“ (509mm x 203mm)
80674
Aluminum return grille
20” x 12” (509mm x 305mm)
80677
Return filter grille
20” x 12” (509mm x 305mm)
80671
For the AVPA30/36 & HVPA24*
Double deflection, aluminum supply grille
28” x 8“ (711mm x 203mm)
80675
Aluminum return grille
28” x 14” (711mm x 356mm)
80678
Return filter grille*
28” x 14” (711mm x 356mm
80672
*A return air filter grille is required on all AVPA24/30/36 & HVPA24 when GreenWheel® ERV is used.
For the AVPA42, 48, 60, & 72; HVPA30, 36, 42, 49 & 60 and HVPSA 36, 42, 49 & 60
Double deflection, aluminum supply grille
30” x 10“ (762mm x 254mm)
80676
Aluminum return grille
30” x 16” (762mm x 406mm)
80679
Return filter grille
30” x 16” (762mm x 406mm)
80673
Note: Return filter grilles should be used when the 2” (51mm) filter in the Classic unit is not accessible from the exterior of
the building. Filter used in the return filter grille is a 1” (25mm) thick filter. The return filter grille is not recommended for use
with the Classic II heat pumps with economizers.
7
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Certified Efficiency and Capacity Ratings at ANSI/ARI Standard 390 AVPA Heat Pumps
AVPA24
Model Number
AVPA30
AVPA36
AVPA42
AVPA48
AVPA60
HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD
Cooling BTUH1
24,000
29,000
35,000
42,000
46,000
54,000
9.30
9.40
9.30
9.20
9.50
9.00
High Temperature Heating
24,000
30,000
35,000
34,000
42,000
53,000
High Temperature COP4
3.00
3.00
3.00
3.00
3.00
3.00
Rated Air Flow (CFM5)
820
1,000
1,200
1,350
1,600
1,600
EER2
3
Cooling is rated at 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C DB/19.5°C WB) return air.
EER = Energy Efficiency Ratio
3
High Temperature Heating & COP are rated at 47°F DB/43°WB (8.3°C DB/6.1°C WB) outdoor and 70°F (21.1°C) return air.
4
COP = Coefficient of Performance
5
CFM = Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude. Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460
volts for “D” models. Operation of units at a different voltage from that of the rating point will affect performance and air flow.
1
2
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air DB AVPA Heat Pumps
Model Number
Total Capacity
Sensible Heat Ratio
Sensible Capacity
Rated Air Flow (CFM1)
AVPA24
AVPA30
AVPA36
AVPA42
AVPA48
AVPA60
HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD
24,000
29,000
35,000
42,000
46,000
0.78
0.74
0.70
0.70
0.72
54,000
0.67
18,770
21,385
24,560
29,545
33,060
36,260
820
1,000
1,200
1,350
1,600
1,600
CFM=Cubic Feet per Minute
Sensible Heat Ratios based upon ANSI/AHRI std. 390 outdoor conditions of 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C DB/19.5°C WB)
return air.
1
Cooling Performance (BTUH) at Various Outdoor Temperatures AVPA Heat Pumps
Model Number
Outdoor Temperature
75ºF/24ºC
80ºF/26.5ºC
85ºF/29ºC
90ºF/32ºC
95ºF/35ºC
AVPA24HP
27,840
26,880
25,920
24,960
24,000
100ºF/38ºC 105ºF/40.5ºC 110ºF/43.3ºC 115ºF/46ºC
23,040
22,080
21,120
20,640
AVPA30HP
33,640
32,480
31,320
30,160
29,000
27,840
26,680
25,520
24,940
AVPA36HP
40,600
39,200
37,800
36,400
35,000
33,600
32,200
30,800
30,100
AVPA42HP
48,720
47,040
45,360
43,680
42,000
40,320
38,640
36,960
36,120
AVPA48HP
53,360
51,520
49,680
47,840
46,000
44,160
42,320
40,480
39,560
AVPA60HP
62,640
60,480
58,320
56,160
54,000
51,840
49,680
47,520
46,440
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67°F WB (26.5°C DB/19.5°C WB). Return air at rated air flow.
Heating Performance (BTUH) at Various Outdoor Temperatures AVPA Heat Pumps
Outdoor Temperature
Model Number
10ºF
/-12.2ºC
17ºF /
-8.3ºC
20ºF /
-6.7ºC
30ºF /
-1.1ºC
40ºF /
4.4ºC
47ºF /
8.3ºC
50ºF /
10ºC
60ºF /
15.6ºC
70ºF /
21.1ºC
AVPA24HP
11,560
13,600
14,640
18,280
21,400
24,000
24,720
25,800
27,000
AVPA30HP
15,130
17,800
19,020
23,290
26,950
30,000
30,900
32,250
33,750
AVPA36HP
15,810
18,600
20,240
25,980
30,900
35,000
36,050
37,625
39,375
AVPA42HP
18,700
22,000
23,200
27,400
31,000
34,000
35,020
36,550
38,250
AVPA48HP
20,400
24,000
25,800
32,100
37,500
42,000
43,260
45,150
47,250
AVPA60HP
28,050
33,000
35,000
42,000
48,000
53,000
54,590
56,975
59,625
Based upon ANSI/AHRI std. 390 return air conditions of 70°F DB (21.1°C DB). Return air at rated air flow.
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
8
Air Flow (Cubic Feet per Minute)
External Static Pressure (WET COIL)
Model Number
0.10
0.20
0.25
0.30
670
0.40
AVPA24
860
810
740
AVPA30
1100
1000
960
920
810
AVPA36
1310
1220
1185
1150
1060
0.50
AVPA42
1650
1585
1520
1450
AVPA48
1900
1830
1760
1700
1620
AVPA60
1900
1830
1760
1700
1620
1360
Air flow ratings of 208-230v. Units are at 230v. Air flow ratings of 480 v. units are at 460 volts. Operation of units at a different
voltage from the rating point will affect air flow.
Electrical Characteristics Compressor, Fan, Ventilation & Blower Motors AVPA Heat Pumps
OTHER
MOTORS
COMPRESSOR
Model
Number
VOLTS-HZ-PH
OUTDOOR
FAN MOTOR
RLA1
LRA2
VOLTS-HZ-PH
RPM3 FLA4
INDOOR
BLOWER MOTOR
HP5
RPM3 FLA4
HP5
VENTILATION
GREENWHEEL® ERV
AMPS
OAM
6
EXM7
WD8
AVPA24HPA
208/230-60-1
12.8
64.0
208/230-60-1
1075
1.5
1/5
1075
1.5
1/5
1.0
1.0
0.2
AVPA30HPA
208/230-60-1
14.1
77.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
1.0
1.0
0.2
AVPA36HPA
208/230-60-1
17.9
112.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
1.0
1.0
0.2
AVPA42HPA
208/230-60-1
19.8
109.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
1.0
1.0
0.2
AVPA48HPA
208/230-60-1
21.8
117.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
1.0
1.0
0.2
AVPA60HPA
208/230-60-1
26.2
134.0
208/230-60-1
825
2.8
1/3
1075
5.2
3/4
1.0
1.0
0.2
AVPA24HPC
208/230-60-3
8.3
61.0
208/230-60-1
1075
1.5
1/5
1075
1.5
1/5
1.0
1.0
0.2
AVPA30HPC
208/230-60-3
9.0
71.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
1.0
1.0
0.2
AVPA36HPC
208/230-60-3
13.2
88.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
1.0
1.0
0.2
AVPA42HPC
208/230-60-3
13.6
83.1
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
1.0
1.0
0.2
AVPA48HPC
208/230-60-3
13.7
83.1
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
1.0
1.0
0.2
AVPA60HPC
208/230-60-3
15.6
111.0
208/230-60-1
825
2.8
1/3
1075
5.2
3/4
1.0
1.0
0.2
AVPA24HPD
460-60-3
5.1
28.0
208/230-60-1
1075
1.5
1/5
1075
1.5
1/5
1.0
1.0
0.2
AVPA30HPD
460-60-3
5.6
38.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
1.0
1.0
0.2
AVPA36HPD
460-60-3
6.0
44.0
208/230-60-1
1075
1.8
1/4
1075
2.5
1/4
1.0
1.0
0.2
AVPA42HPD
460-60-3
6.1
41.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
1.0
1.0
0.2
AVPA48HPD
460-60-3
6.2
41.0
208/230-60-1
825
2.8
1/3
1075
3.1
1/2
1.0
1.0
0.2
AVPA60HPD
460-60-3
7.7
52.0
208/230-60-1
825
2.8
1/3
1075
5.2
3/4
1.0
1.0
0.2
RLA = Rated Load Amps
2
HP = Horsepower
6
1
5
LRA = Locked Rotor Amps
3
RPM = Revolutions per Minute
4
OAM = Outside Air Mover
7
FLA = Full Load Amps
EXM = Exhaust Air Mover
8
WD = Wheel Drive Motor
The 460 volt units have a step down transformer for the 230 volt motors.
9
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) AVPA Heat Pumps with Ventilation Configurations:
Manual Damper, up to 15% outside air (“N”)
Manual Damper, up to 450 cfm of outside air (“Y”)
Manual Damper, up to 450 cfm of outside air with pressure relief (“Z”)
Motorized 2-Position Damper, up to 450 cfm of outside air w/Pressure Relief (“B”)
Economizer, Outside air with Pressure Relief (“C”)
ELECTRIC HEAT
BASIC
MODEL
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
150 = 15 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
VOLTS-HZ-PH
1
MCA
MFS
1
MCA
39.9
2
MFS
1
MCA
40
2
MFS
1
MCA
2
MFS
1
MCA
MFS
2
2
MCA
1
MFS
2
1
MCA
MFS
2
1
MCA
MFS
MCA1
MFS2
2
AVPA24HPA 208/230-1-60
19.0
30
45.0
50
50.3
60
60.6
70
71.1
80
AVPA30HPA 208/230-1-60
21.9
35
47.9
50
53.2
60
63.5
70
74.0
80
84.4
90
100.0
100
AVPA36HPA 208/230-1-60
26.7
40
52.7
60
58.0
60
68.3
70
78.8
80
89.2
90
104.8
110
AVPA42HPA 208/230-1-60
30.7
50
56.7
60
82.8
90
93.2
100
108.8
110
AVPA48HPA 208/230-1-60
33.2
50
59.2
60
85.3
90
95.7
100
111.3
120
AVPA60HPA 208/230-1-60
40.8
60
66.8
70
92.9
100
103.3
110
118.9
120
AVPA24HPC 208/230-3-60
13.4
20
31.4
35
40.5
45
AVPA30HPC 208/230-3-60
15.6
20
33.6
35
42.7
45
51.7
60
60.7
70
AVPA36HPC 208/230-3-60
20.8
30
38.8
40
47.9
50
56.9
60
65.9
70
AVPA42HPC 208/230-3-60
22.9
35
40.9
45
50.0
50
59.0
60
68.0
70
AVPA48HPC 208/230-3-60
23.0
35
41.0
45
50.1
60
59.1
60
68.1
70
AVPA60HPC 208/230-3-60
27.5
40
45.5
50
54.6
60
63.6
70
72.6
80
AVPA24HPD
460-3-60
7.9
15
16.9
20
21.4
25
25.9
30
30.4
35
AVPA30HPD
460-3-60
9.2
15
18.2
20
22.7
25
27.2
30
31.7
35
AVPA36HPD
460-3-60
9.7
15
18.7
20
23.2
25
27.7
30
32.2
35
AVPA42HPD
460-3-60
10.6
15
19.6
20
24.1
25
28.6
30
33.1
35
AVPA48HPD
460-3-60
10.7
15
19.7
20
24.2
25
28.7
30
33.2
35
13.6
20
22.6
25
27.1
30
31.6
35
36.1
40
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline
for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
AVPA60HPD
460-3-60
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) AVPA Heat Pumps with the “S” Circuit and Ventilation Configuration:
Manual Damper, up to 15% outside air (“N”)
Manual Damper, up to 450 cfm of outside air (“Y”)
Manual Damper, up to 450 cfm of outside air with pressure relief (“Z”)
Motorized 2-Position Damper, up to 450 cfm of outside air w/Pressure Relief (“B”)
Economizer, Outside air with Pressure Relief (“C”)
ELECTRIC HEAT
BASIC
MODEL
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
VOLTS-HZ-PH
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
AVPA24HPA 208/230-1-60
19.0
30
20.3
30
27.5
30
32.8
AVPA30HPA 208/230-1-60
21.9
35
28.5
35
AVPA36HPA 208/230-1-60
26.7
40
28.5
40
AVPA42HPA 208/230-1-60
30.7
50
30.7
AVPA48HPA 208/230-1-60
33.2
50
AVPA60HPA 208/230-1-60
40.8
60
AVPA24HPC 208/230-3-60
13.4
20
19.5
20
28.6
AVPA30HPC 208/230-3-60
15.6
20
20.5
25
AVPA36HPC 208/230-3-60
20.8
30
20.8
AVPA42HPC 208/230-3-60
22.9
35
AVPA48HPC 208/230-3-60
23.0
AVPA60HPC 208/230-3-60
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
35
53.6
60
33.8
35
54.6
33.8
35
54.6
50
33.2
40.8
150 = 15 kw
SPPE3
MCA1
MFS2
MCA1
MFS2
60
65.0
70
80.6
90
60
65.0
70
80.6
90
55.2
60
65.6
70
81.2
90
50
55.2
60
65.6
70
81.2
90
60
57.3
60
67.7
70
83.3
90
30
37.6
40
46.6
50
29.6
30
38.6
40
47.6
50
30
29.6
30
38.6
40
47.6
50
22.9
35
30.2
35
39.2
40
48.2
50
35
23.0
35
30.2
35
39.2
40
48.2
50
27.5
40
27.5
40
32.3
40
41.3
45
50.3
60
AVPA24HPD
460-3-60
7.9
15
9.8
15
14.3
15
18.8
20
23.3
25
AVPA30HPD
460-3-60
9.2
15
10.3
15
14.8
15
19.3
20
23.8
25
AVPA36HPD
460-3-60
9.7
15
10.3
15
14.8
15
19.3
20
23.8
25
AVPA42HPD
460-3-60
10.6
15
10.6
15
15.1
20
19.6
20
24.1
25
AVPA48HPD
460-3-60
10.7
15
10.7
15
15.1
20
19.6
20
24.1
25
13.6
20
13.6
20
16.1
20
20.6
25
25.1
30
“S” Circuit - Compressor and electric heat can NOT operate simultaneously.
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline
for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
AVPA60HPD
460-3-60
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
10
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) AVPA Heat Pumps Ratings and GreenWheel® Energy Recovery Ventilator Ventilation Configuration (“H”)
ELECTRIC HEAT
BASIC
MODEL
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
150 = 15 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
VOLTS-HZ-PH
1
MCA
MFS
1
MCA
42.1
2
MFS
1
MCA
45
2
MFS
1
MCA
2
MFS
1
MCA
MFS
2
2
MCA
1
MFS
2
1
MCA
MFS
2
MCA
1
MFS
MCA1
MFS2
2
AVPA24HPA 208/230-1-60
21.2
30
47.2
50
52.5
60
62.8
70
73.3
80
AVPA30HPA 208/230-1-60
24.1
35
49.1
50
55.4
60
65.7
70
76.2
80
86.6
90
102.2
110
AVPA36HPA 208/230-1-60
28.9
45
54.9
60
60.2
70
70.5
80
81.0
90
91.4
100
107.0
110
AVPA42HPA 208/230-1-60
32.9
50
58.9
60
85.0
90
95.4
100
111.0
120
AVPA48HPA 208/230-1-60
35.4
50
61.4
70
87.5
90
97.9
100
113.5
120
AVPA60HPA 208/230-1-60
43.0
60
69.0
70
95.1
100
105.5
110
121.1
130
AVPA24HPC 208/230-3-60
15.6
20
33.6
35
42.7
45
AVPA30HPC 208/230-3-60
17.8
25
35.8
35
44.9
45
53.9
60
62.9
70
AVPA36HPC 208/230-3-60
23.0
35
41.0
45
50.1
60
59.1
60
68.1
70
AVPA42HPC 208/230-3-60
25.1
35
43.1
45
52.2
60
61.2
70
70.2
80
AVPA48HPC 208/230-3-60
25.2
35
43.2
45
52.3
60
61.3
70
70.3
80
AVPA60HPC 208/230-3-60
29.7
45
47.7
50
56.8
60
65.8
70
74.8
80
AVPA24HPD
460-3-60
9.0
15
18.0
20
22.5
25
27.0
30
31.5
35
AVPA30HPD
460-3-60
10.3
15
19.3
20
23.8
25
28.3
30
32.8
35
AVPA36HPD
460-3-60
10.8
15
19.8
20
24.3
25
28.8
30
33.3
35
AVPA42HPD
460-3-60
11.7
15
20.7
20
25.2
30
29.7
30
34.2
35
AVPA48HPD
460-3-60
11.8
15
20.8
20
25.3
30
29.8
30
34.3
35
14.7
20
23.7
25
28.2
30
32.7
35
37.2
40
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline
for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
AVPA60HPD
460-3-60
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) AVPA Heat Pumps with the “S” Circuit and
GreenWheel® Energy Recovery Ventilator Ventilation Configuration (“H”)
ELECTRIC HEAT
BASIC
MODEL
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
VOLTS-HZ-PH
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
AVPA24HPA 208/230-1-60
21.2
30
22.5
30
29.7
30
35.0
AVPA30HPA 208/230-1-60
24.1
35
30.7
35
AVPA36HPA 208/230-1-60
28.9
45
30.7
45
AVPA42HPA 208/230-1-60
32.9
50
32.9
AVPA48HPA 208/230-1-60
35.4
50
AVPA60HPA 208/230-1-60
43.0
60
AVPA24HPC 208/230-3-60
15.6
20
21.7
25
30.8
AVPA30HPC 208/230-3-60
17.8
25
22.7
25
AVPA36HPC 208/230-3-60
23.0
35
23.0
AVPA42HPC 208/230-3-60
25.1
35
AVPA48HPC 208/230-3-60
25.2
AVPA60HPC 208/230-3-60
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
35
55.8
60
36.0
40
56.8
36.0
45
56.8
50
35.4
43.0
150 = 15 kw
SPPE3
MCA1
MFS2
MCA1
MFS2
60
67.2
70
80.6
90
60
67.2
70
80.6
90
57.4
60
67.8
70
81.2
90
50
57.4
60
67.8
70
81.2
90
60
59.5
60
69.9
70
83.3
90
35
39.8
40
46.6
50
31.8
35
40.8
45
47.6
50
30
31.8
35
40.8
45
47.6
50
25.1
35
32.4
35
41.4
45
48.2
50
35
25.2
35
32.4
35
41.4
45
48.2
50
29.7
45
29.7
45
34.5
45
43.5
45
50.3
60
AVPA24HPD
460-3-60
9.0
15
10.9
15
15.4
20
19.9
20
24.4
25
AVPA30HPD
460-3-60
10.3
15
11.4
15
15.9
20
20.4
25
24.9
25
AVPA36HPD
460-3-60
10.8
15
11.4
15
15.9
20
20.4
25
24.9
25
AVPA42HPD
460-3-60
11.7
15
11.7
15
16.2
20
20.7
25
25.2
30
AVPA48HPD
460-3-60
11.8
15
11.8
15
16.2
20
20.7
25
25.2
30
14.7
20
14.7
20
17.2
20
21.7
25
26.2
30
“S” Circuit - Compressor and electric heat can NOT operate simultaneously.
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline
for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
AVPA60HPD
460-3-60
11
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Unit Load Amps (Heating) AVPA Heat Pumps with Ventilation Configurations:
Manual Damper, up to 15% outside air (“N”)
Manual Damper, up to 450 cfm of outside air (“Y”)
Manual Damper, up to 450 cfm of outside air with pressure relief (“Z”)
Motorized 2-Position Damper, up to 450 cfm of outside air w/Pressure Relief (“B”)
Economizer, Outside air with Pressure Relief (“C”)
MODEL
NUMBER
VOLTAGE
CURRENT (AMPS)
PHASE
HERTZ
HP1
IBM2
TOTAL MAXIMUM HEATING AMPS
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS
(1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON AN
ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
AVPA24HPA
208-230/1/60
15.8
1.5
16.7
20.8
25.0
33.3
41.7
32.5
36.6
40.8
49.1
57.5
AVPA30HPA
208-230/1/60
18.4
2.5
16.7
20.8
25.0
33.3
41.7
50.0
62.5
35.1
39.2
43.4
51.7
60.1
68.4
80.9
AVPA36HPA
208-230/1/60
22.2
2.5
16.7
20.8
25.0
33.3
41.7
50.0
62.5
38.9
43.0
47.2
55.5
63.9
72.2
84.7
AVPA42HPA
208-230/1/60
25.7
3.1
20.8
41.7
50.0
62.5
46.5
67.4
75.7
88.2
AVPA48HPA
208-230/1/60
27.7
3.1
20.8
41.7
50.0
62.5
48.5
69.4
77.7
90.2
AVPA60HPA
208-230/1/60
34.2
5.2
20.8
41.7
50.0
62.5
55.0
75.9
84.2
96.7
AVPA24HPC
208-230/3/60
11.2
1.5
14.4
21.7
28.9
36.1
25.6
32.9
40.1
47.3
AVPA30HPC
208-230/3/60
13.3
2.5
14.4
21.7
28.9
36.1
27.7
35.0
42.2
49.4
AVPA36HPC
208-230/3/60
17.5
2.5
14.4
21.7
28.9
36.1
31.9
39.2
46.4
53.6
AVPA42HPC
208-230/3/60
19.5
3.1
14.4
21.7
28.9
36.1
33.9
41.2
48.4
55.6
AVPA48HPC
208-230/3/60
19.6
3.1
14.4
21.7
28.9
36.1
34.0
41.3
48.5
55.7
AVPA60HPC
208-230/3/60
23.6
5.2
14.4
21.7
28.9
36.1
38.0
45.3
52.5
59.7
AVPA24HPD
460/3/60
6.6
0.8
7.2
10.8
14.4
18.0
13.8
17.4
21.0
24.6
AVPA30HPD
460/3/60
7.8
1.3
7.2
10.8
14.4
18.0
15.0
18.6
22.2
25.8
AVPA36HPD
460/3/60
8.2
1.3
7.2
10.8
14.4
18.0
15.4
19.0
22.6
26.2
AVPA42HPD
460/3/60
9.1
1.6
7.2
10.8
14.4
18.0
16.3
19.9
23.5
27.1
AVPA48HPD
460/3/60
9.2
1.6
7.2
10.8
14.4
18.0
16.4
20.0
23.6
27.2
AVPA60HPD
460/3/60
11.7
2.6
7.2
10.8
14.4
18.0
18.9
22.5
26.1
29.7
2
HP = Heat Pump Unit Amps (includes Indoor Motor amps)
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the 208-230v. (HPA & HPC) models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the HPD models.
Total heating amps for single phase units with two circuits (#1 and #2) includes both circuits. Total heating and cooling amps includes all motors. Three phase models contain single phase motor loads.
Values shown are maximum phase loads. Loads are not equally balanced on each phase.
1
Unit Load Amps (Heating) AVPA Heat Pumps with GreenWheel® Energy Recovery Ventilator Ventilation Configuration (“H”)
MODEL
NUMBER
VOLTAGE
PHASE
HERTZ
CURRENT (AMPS)
HP1
IBM2
H3
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS
(1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
TOTAL MAXIMUM HEATING AMPS
INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON AN
ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
AVPA24HPA 208-230/1/60
18.0
1.5
2.2
16.7
20.8
25.0
33.3
41.7
18.2
38.8
43.0
51.3
59.7
AVPA30HPA 208-230/1/60
20.6
2.5
2.2
16.7
20.8
25.0
33.3
41.7
50.0
62.5
19.2
41.4
45.6
53.9
62.3
70.6
83.1
AVPA36HPA 208-230/1/60
24.4
2.5
2.2
16.7
20.8
25.0
33.3
41.7
50.0
62.5
19.2
45.2
49.4
57.7
66.1
74.4
86.9
AVPA42HPA 208-230/1/60
27.9
3.1
2.2
20.8
41.7
50.0
62.5
48.7
69.6
77.9
90.4
AVPA48HPA 208-230/1/60
29.9
3.1
2.2
20.8
41.7
50.0
62.5
50.7
71.6
79.9
92.4
20.8
41.7
57.2
78.1
86.4
98.9
AVPA60HPA 208-230/1/60
36.4
5.2
2.2
50.0
62.5
AVPA24HPC 208-230/3/60
13.4
1.5
2.2
14.4
21.7
28.9
36.1
27.8
35.1
42.3
49.5
AVPA30HPC 208-230/3/60
15.5
2.5
2.2
14.4
21.7
28.9
36.1
29.9
37.2
44.4
51.6
AVPA36HPC 208-230/3/60
19.7
2.5
2.2
14.4
21.7
28.9
36.1
34.1
41.4
48.6
55.8
AVPA42HPC 208-230/3/60
21.7
3.1
2.2
14.4
21.7
28.9
36.1
36.1
43.4
50.6
57.8
AVPA48HPC 208-230/3/60
21.8
3.1
2.2
14.4
21.7
28.9
36.1
36.2
43.5
50.7
57.9
AVPA60HPC 208-230/3/60
25.8
5.2
2.2
14.4
21.7
28.9
36.1
40.2
47.5
54.7
61.9
AVPA24HPD
460/3/60
7.7
0.8
1.1
7.2
10.8
14.4
18.0
14.9
18.5
22.1
25.7
AVPA30HPD
460/3/60
8.9
1.3
1.1
7.2
10.8
14.4
18.0
16.1
19.7
23.3
26.9
AVPA36HPD
460/3/60
9.3
1.3
1.1
7.2
10.8
14.4
18.0
16.5
20.1
23.7
27.3
AVPA42HPD
460/3/60
10.2
1.6
1.1
7.2
10.8
14.4
18.0
17.4
21.0
24.6
28.2
AVPA48HPD
460/3/60
10.3
1.6
1.1
7.2
10.8
14.4
18.0
17.5
21.1
24.7
28.3
2
3
HP = Heat Pump Unit Amps (includes Indoor Motor amps)
IBM = Indoor Blower Motor
H = GreenWheel ERV
Heating kW is rated at 240 volts on the 208-230v. (HPA & HPC) models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the HPD models.
Total heating amps for single phase units with two circuits (#1 and #2) includes both circuits. Total heating and cooling amps includes all motors. Three phase models contain single phase motor
loads. Values shown are maximum phase loads. Loads are not equally balanced on each phase.
1
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
12
Certified Efficiency and Capacity Ratings at ANSI/ARI Standard 390 for HVPA Heat Pumps with Single Stage Compressor
HVPA24HP1
Model Number
HVPA30
HVPA36
HVPA42HP1
HVPA49
HVPA60
HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD
Cooling BTUH1
23,600
28,000
34,600
40,500
47,000
56,500
EER2
11.00
11.50
11.00
10.50
11.50
10.50
High Temperature Heating
23,000
26,000
33,000
39,000
42,000
51,000
High Temperature COP3,4
3.25
3.00
3.25
3.25
3.25
3.00
Rated Air Flow (CFM5)
800
1,000
1,200
1,300
1,750
1,750
3
Cooling is rated at 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C DB/19.5°C WB) return air.
EER = Energy Efficiency Ratio
3
High Temperature Heating & COP is rated at 47°F DB/43°WB (8.3°C DB/6.1°C WB) outdoor and 70°F (21.1°C) return air.
4
COP = Coefficient of Performance
5
CFM = Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude. Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460
volts for “D” models.
Operation of units at a different voltage from that of the rating point will affect performance and air flow.
1
2
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air DB HVPA Heat Pumps with Single Stage Compressor
Model Number
Total Capacity
Sensible Heat Ratio
Sensible Capacity
Rated Air Flow (CFM1)
HVPA24HP1
HVPA30
HVPA36
HVPA42HP1
HVPA49
HVPA60
HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD HPA HPC HPD
23,600
28,000
34,600
40,500
47,000
0.74
0.73
0.74
0.70
0.75
56,500
0.71
17,435
20,460
25,490
28,415
35,200
40,295
800
1,000
1,200
1,300
1,750
1,750
CFM = Cubic Feet per Minute
1
Sensible Heat Ratios based upon ANSI/AHRI std. 390 outdoor conditions of 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C
DB/19.5°C WB) return air.
Cooling Performance (BTUH) at Various Outdoor Temperatures HVPA Heat Pumps with Single Stage Compressor
Model Number
Outdoor Temperature
75ºF/24ºC
80ºF/26.5ºC
85ºF/29ºC
90ºF/32ºC
95ºF/35ºC
HVPA24HP1
27,375
26,430
25,490
24,545
23,600
100ºF/38ºC 105ºF/40.5ºC 110ºF/43.3ºC 115ºF/46ºC
22,655
21,710
20,770
20,295
HVPA30HP
32,480
31,360
30,240
29,120
28,000
26,880
25,760
24,640
24,080
HVPA36HP
40,135
38,750
37,370
35,985
34,600
33,215
31,830
30,450
29,755
HVPA42HP1
46,980
45,360
43,740
42,120
40,500
38,880
37,260
35,640
34,830
HVPA49HP
54,520
52,640
50,760
48,880
47,000
45,120
43,240
41,360
40,420
HVPA60HP
65,540
63,280
61,020
58,760
56,500
54,240
51,980
49,720
48,590
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67°F WB (26.5°C DB/19.5°C WB). Return air at rated air flow.
Heating Performance (BTUH) at Various Outdoor Temperatures HVPA Heat Pumps with Single Stage Compressor
Model Number
Outdoor Temperature
10ºF /
-12.2ºC
17ºF /
-8.3ºC
20ºF /
-6.7ºC
30ºF /
-1.1ºC
40ºF /
4.4ºC
47ºF /
8.3ºC
50ºF /
10ºC
60ºF /
15.6ºC
70ºF /
21.1ºC
HVPA24HP1
9,775
11,500
12,650
16,675
20,125
23,000
23,690
24,725
25,875
HVPA30HP
12,410
14,600
15,740
19,730
23,150
26,000
26,780
27,950
29,250
HVPA36HP
14,110
16,600
18,240
23,980
28,900
33,000
33,990
35,475
37,125
HVPA42HP1
16,150
19,000
21,000
28,000
34,000
39,000
40,170
41,925
43,875
HVPA49HP
20,060
23,600
25,440
31,880
37,400
42,000
43,260
45,150
47,250
HVPA60HP
23,800
28,000
30,300
38,350
45,250
51,000
52,530
54,825
57,375
Based upon ANSI/AHRI std. 390 return air conditions of 70°F DB (21.1°C DB). Return air at rated air flow.
13
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Electrical Characteristics Compressor, Fan, Ventilation & Blower Motors HVPA Heat Pumps with Single Stage Compressor
OTHER
MOTORS
COMPRESSOR
Model
Number
VOLTS-HZ-PH
RLA1
INDOOR
BLOWER MOTOR
(ECM)
OUTDOOR
FAN MOTOR
LRA2
VOLTS-HZ-PH
RPM3 FLA4
HP5
RPM3 FLA4
VENTILATION
GREENWHEEL® ERV
AMPS
HP5
OAM6
EXM7
WD8
HVPA24HPA
208/230-60-1
12.8
64.0
208/230-60-1
825
1.8
1/4
1500
2.8
1/3
1.0
1.0
0.2
HVPA30HPA
208/230-60-1
12.8
77.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPA36HPA
208/230-60-1
16.6
112.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPA42HPA
208/230-60-1
19.8
109.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPA48HPA
208/230-60-1
21.8
117.0
208/230-60-1
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
HVPA60HPA
208/230-60-1
26.2
134.0
208/230-60-1
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
HVPA24HPC
208/230-60-3
7.7
61.0
208/230-60-1
825
1.8
1/4
1500
2.8
1/3
1.0
1.0
0.2
HVPA30HPC
208/230-60-3
8.3
71.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPA36HPC
208/230-60-3
10.4
88.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPA42HPC
208/230-60-3
13.6
83.1
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPA48HPC
208/230-60-3
13.7
83.1
208/230-60-1
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
HVPA60HPC
208/230-60-3
15.6
111.0
208/230-60-1
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
HVPA24HPD
460-60-3
4.0
28.0
208/230-60-1
825
1.8
1/4
1500
2.8
1/3
1.0
1.0
0.2
HVPA30HPD
460-60-3
5.1
38.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPA36HPD
460-60-3
5.8
44.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPA42HPD
460-60-3
6.1
41.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPA48HPD
460-60-3
6.2
41.0
208/230-60-1
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
HVPA60HPD
460-60-3
7.7
52.0
208/230-60-1
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
2
3
RLA = Rated Load Amps
LRA = Locked Rotor Amps
RPM = Revolutions per Minute
5
6
7
HP = Horsepower
OAM = Outside Air Mover
EXM = Exhaust Air Mover
The 460 volt units have a step down transformer for the 230 volt motors.
FLA = Full Load Amps
8
WD = Wheel Drive Motor
1
4
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) HVPA Heat Pumps w/Single Stage Compressor & Ventilation Configuration:
Manual Damper, up to 15% outside air (“N”)
Manual Damper, up to 450 cfm of outside air (“Y”)
Manual Damper, up to 450 cfm of outside air with pressure relief (“Z”)
Motorized, 2-Position Damper, up to 450 CFM of Outside Air w/Pressure Relief (“B”)
Economizer, Outside Air (“C”)
ELECTRIC HEAT
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
150 = 15 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
BASIC
MODEL
VOLTS-HZ-PH
1
MCA
HVPA24HPA
208/230-1-60
HVPA30HPA
208/230-1-60
HVPA36HPA
MFS
1
MFS
1
MCA
MCA
MCA1
MFS2
20.6
30
41.5
21.6
30
46.6
50
47.6
50
208/230-1-60
26.4
40
52.4
60
90
99.7
100
90
104.5
HVPA42HPA
208/230-1-60
30.4
50
56.4
110
92.9
100
108.5
HVPA48HPA
208/230-1-60
34.4
50
110
90
96.9
100
112.5
HVPA60HPA
208/230-1-60
39.9
60
120
100
102.4
110
118.0
HVPA24HPC
208/230-3-60
14.2
20
32.2
35
41.3
45
120
HVPA30HPC
208/230-3-60
16.0
20
34.0
35
43.1
HVPA36HPC
208/230-3-60
18.6
25
36.6
40
45.7
45
52.1
60
61.1
70
50
54.7
60
63.7
HVPA42HPC
208/230-3-60
22.6
35
40.6
45
70
49.7
50
58.7
60
67.7
HVPA48HPC
208/230-3-60
24.2
35
42.2
70
45
51.3
60
60.3
70
69.3
HVPA60HPC
208/230-3-60
26.6
40
70
44.6
45
53.7
60
62.7
70
71.7
HVPA24HPD
460-3-60
7.3
80
15
16.3
20
20.8
25
25.3
30
29.8
HVPA30HPD
460-3-60
30
9.2
15
18.2
20
22.7
25
27.2
30
31.7
HVPA36HPD
35
460-3-60
10.1
15
19.1
20
23.6
25
28.1
30
32.6
35
HVPA42HPD
460-3-60
10.4
15
19.4
20
23.9
25
28.4
30
32.9
35
HVPA48HPD
460-3-60
11.3
15
20.3
25
24.8
25
29.3
30
33.8
35
2
MFS
1
MCA
45
2
1
1
MCA
MFS
MCA
MFS
70
72.7
80
70
73.7
70
78.5
80
84.1
80
88.9
60
82.5
90
60.4
70
86.5
65.9
70
92.0
2
MFS
1
MCA
MFS
51.9
60
62.2
52.9
60
63.2
57.7
60
68.0
2
2
MCA
1
MFS
2
2
2
13.2
20
22.2
25
26.7
30
31.2
35
35.7
40
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline
for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
HVPA60HPD
460-3-60
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
14
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) HVPA Heat Pumps with Single Stage Compressor and “S” Circuit and
Ventilation Configurations:
Manual Damper, up to 15% outside air (“N”)
Manual Damper, up to 450 cfm of outside air (“Y”)
Manual Damper, up to 450 cfm of outside air with pressure relief (“Z”)
Motorized, 2-Position Damper, up to 450 CFM of Outside Air w/Pressure Relief (“B”)
Economizer, Outside Air (“C”)
ELECTRIC HEAT
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
150 = 15 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
BASIC
MODEL
VOLTS-HZ-PH
1
MCA
HVPA24HPA
208/230-1-60
HVPA30HPA
208/230-1-60
HVPA36HPA
MFS
1
MFS
1
1
MCA
MCA
MFS
MCA
MFS
MCA1
MFS2
20.6
30
23.7
21.6
30
28.8
30
34.1
28.8
30
34.1
208/230-1-60
26.4
40
28.8
40
34.1
60
65.3
70
80.9
90
60
65.3
70
80.9
HVPA42HPA
208/230-1-60
30.4
50
30.4
90
54.9
60
65.3
70
80.9
HVPA48HPA
208/230-1-60
34.4
50
90
50
56.4
60
66.8
70
82.4
HVPA60HPA
208/230-1-60
39.9
60
90
60
56.4
60
66.8
70
82.4
HVPA24HPC
208/230-3-60
14.2
20
20.8
25
29.9
90
30
38.9
40
47.9
HVPA30HPC
208/230-3-60
16.0
20
20.8
25
50
29.9
30
38.9
40
47.9
HVPA36HPC
208/230-3-60
18.6
25
20.8
50
25
29.9
30
38.9
40
47.9
HVPA42HPC
208/230-3-60
22.6
35
50
20.8
35
29.9
35
38.9
40
47.9
HVPA48HPC
208/230-3-60
24.2
50
35
24.2
35
31.4
35
40.4
45
49.4
HVPA60HPC
208/230-3-60
50
26.6
40
26.6
40
31.4
40
40.4
45
49.4
HVPA24HPD
50
460-3-60
7.3
15
10.4
15
14.9
15
19.4
20
23.9
25
HVPA30HPD
460-3-60
9.2
15
10.4
15
14.9
15
19.4
20
23.9
25
HVPA36HPD
460-3-60
10.1
15
10.4
15
14.9
15
19.4
20
23.9
25
HVPA42HPD
460-3-60
10.4
15
10.4
15
14.9
15
19.4
20
23.9
25
HVPA48HPD
460-3-60
11.3
15
11.3
15
15.7
20
20.2
25
24.7
25
2
MFS
1
MCA
30
2
1
MCA
MFS
35
54.9
60
35
54.9
40
54.9
50
34.4
39.9
2
2
MCA
1
MFS
2
MCA
1
MFS
2
2
2
13.2
20
13.2
20
15.7
20
20.2
25
24.7
25
S-Circuit - Compressor and electric heat do NOT operate simultaneously.
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline
for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
HVPA60HPD
460-3-60
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) HVPA Heat Pumps with Single Stage Compressor and GreenWheel® ERV Ventilation Configuration (“H”)
ELECTRIC HEAT
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
BASIC
MODEL
VOLTS-HZ-PH
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
HVPA24HPA
208/230-1-60
22.8
35
43.7
45
48.8
50
54.1
60
64.4
HVPA30HPA
208/230-1-60
23.8
35
49.8
50
55.1
60
HVPA36HPA
208/230-1-60
28.6
40
54.6
60
59.9
60
HVPA42HPA
208/230-1-60
32.6
50
58.6
HVPA48HPA
208/230-1-60
36.6
50
HVPA60HPA
208/230-1-60
42.1
60
HVPA24HPC
208/230-3-60
16.4
20
34.4
35
43.5
45
HVPA30HPC
208/230-3-60
18.2
25
36.2
40
45.3
HVPA36HPC
208/230-3-60
20.8
25
38.8
40
47.9
HVPA42HPC
208/230-3-60
24.8
35
42.8
45
HVPA48HPC
208/230-3-60
26.4
35
44.4
HVPA60HPC
208/230-3-60
28.8
40
HVPA24HPD
460-3-60
8.4
HVPA30HPD
460-3-60
HVPA36HPD
MCA1
MFS2
MCA1
MFS2
70
74.9
80
65.1
70
75.9
80
70.2
80
80.7
90
60
84.7
62.6
70
68.1
70
MCA1
150 = 15 kw
SPPE3
MFS2
MCA1
MFS2
86.3
90
101.9
110
91.1
100
106.7
110
90
95.1
100
110.7
120
88.7
90
99.1
100
114.7
120
94.2
100
104.6
110
120.2
130
50
54.3
60
63.3
70
50
56.9
60
65.9
70
51.9
60
60.9
70
69.9
70
45
53.5
60
62.5
70
71.5
80
46.8
50
55.9
60
64.9
70
73.9
80
15
17.4
20
21.9
25
26.4
30
30.9
35
10.3
15
19.3
20
23.8
25
28.3
30
32.8
35
460-3-60
11.2
15
20.2
25
24.7
25
29.2
30
33.7
35
HVPA42HPD
460-3-60
11.5
15
20.5
25
25.0
25
29.5
30
34.0
35
HVPA48HPD
460-3-60
12.4
15
21.4
25
25.9
30
30.4
35
34.9
35
14.3
20
23.3
25
27.8
30
32.3
35
36.8
40
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline
for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
HVPA60HPD
460-3-60
15
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) HVPA Heat Pumps w/Single Stage Compressor & “S” Circuit & GreenWheel® ERV Ventilation Configuration (“H”)
ELECTRIC HEAT
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
150 = 15 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
BASIC
MODEL
VOLTS-HZ-PH
1
MCA
HVPA24HPA
208/230-1-60
HVPA30HPA
208/230-1-60
HVPA36HPA
MFS
1
MFS
1
1
MCA
MCA
MFS
MCA
MFS
MCA1
MFS2
22.8
35
25.9
23.8
35
31.0
35
36.3
31.0
35
36.3
208/230-1-60
28.6
40
31.0
45
36.3
60
67.5
70
83.1
90
60
67.5
70
83.1
HVPA42HPA
208/230-1-60
32.6
50
32.6
90
57.1
60
67.5
70
83.1
HVPA48HPA
208/230-1-60
36.6
50
90
50
58.6
60
69.0
70
84.6
HVPA60HPA
208/230-1-60
42.1
60
90
60
58.6
60
69.0
70
84.6
HVPA24HPC
208/230-3-60
16.4
20
23.0
25
32.1
90
35
41.1
45
50.1
HVPA30HPC
208/230-3-60
18.2
25
23.0
25
60
32.1
35
41.1
45
50.1
HVPA36HPC
208/230-3-60
20.8
25
23.0
60
30
32.1
35
41.1
45
50.1
HVPA42HPC
208/230-3-60
24.8
35
60
24.8
35
32.1
35
41.1
45
50.1
HVPA48HPC
208/230-3-60
26.4
60
35
26.4
35
33.6
35
42.6
45
51.6
HVPA60HPC
208/230-3-60
60
28.8
40
28.8
40
33.6
40
42.6
45
51.6
HVPA24HPD
60
460-3-60
8.4
15
11.5
15
16.0
20
20.5
25
25.0
25
HVPA30HPD
460-3-60
10.3
15
11.5
15
16.0
20
20.5
25
25.0
25
HVPA36HPD
460-3-60
11.2
15
11.5
15
16.0
20
20.5
25
25.0
25
HVPA42HPD
460-3-60
11.5
15
11.5
15
16.0
20
20.5
25
25.0
25
HVPA48HPD
460-3-60
12.4
15
12.4
15
16.8
20
21.3
25
25.8
30
2
MFS
1
MCA
30
2
1
MCA
MFS
40
57.1
60
40
57.1
45
57.1
50
36.6
42.1
2
2
MCA
1
MFS
2
MCA
1
MFS
2
2
2
14.3
20
14.3
20
16.8
20
21.3
25
25.8
30
S-Circuit - Compressor and electric heat do NOT operate simultaneously.
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline
for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
HVPA60HPD
460-3-60
Unit Load Amps (Heating) HVPA Heat Pumps w/Single Stage Compressor & Ventilation Configuration:
Manual Damper, up to 15% outside air (“N”)
Manual Damper, up to 450 cfm of outside air (“Y”)
Manual Damper, up to 450 cfm of outside air with pressure relief (“Z”)
Motorized 2-Position Damper, up to 450 cfm of outside air w/Pressure Relief (“B”)
Economizer, Outside Air (“C”)
MODEL
NUMBER
VOLTAGE
PHASE
HERTZ
CURRENT (AMPS)
HP1
IBM2
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS
(1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
TOTAL MAXIMUM HEATING AMPS
INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON AN
ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
HVPA24HPA
208-230/1/60
17.4
2.8
16.7
20.8
25.0
33.3
41.7
34.1
38.2
42.4
50.7
59.1
HVPA30HPA
208-230/1/60
18.4
2.8
16.7
20.8
25.0
33.3
41.7
50.0
62.5
35.1
39.2
43.4
51.7
60.1
68.4
80.9
HVPA36HPA
208-230/1/60
22.2
2.8
16.7
20.8
25.0
33.3
41.7
50.0
62.5
38.9
43.0
47.2
55.5
63.9
72.2
84.7
HVPA42HPA
208-230/1/60
25.4
2.8
20.8
41.7
50.0
62.5
46.2
67.1
75.4
87.9
HVPA48HPA
208-230/1/60
28.9
4.3
20.8
41.7
50.0
62.5
49.7
70.6
78.9
91.4
HVPA60HPA
208-230/1/60
33.3
4.3
20.8
41.7
50.0
62.5
54.1
75.0
83.3
95.8
HVPA24HPC
208-230/3/60
12.3
2.8
14.4
21.7
28.9
36.1
26.7
34.0
41.2
48.4
HVPA30HPC
208-230/3/60
13.9
2.8
14.4
21.7
28.9
36.1
28.3
35.6
42.8
50.0
HVPA36HPC
208-230/3/60
17.5
2.8
14.4
21.7
28.9
36.1
31.9
39.2
46.4
53.6
HVPA42HPC
208-230/3/60
19.2
2.8
14.4
21.7
28.9
36.1
33.6
40.9
48.1
55.3
HVPA48HPC
208-230/3/60
20.8
4.3
14.4
21.7
28.9
36.1
35.2
42.5
49.7
56.9
HVPA60HPC
208-230/3/60
22.7
4.3
14.4
21.7
28.9
36.1
37.1
44.4
51.6
58.8
HVPA24HPD
460/3/60
6.3
1.4
7.2
10.8
14.4
18.0
13.5
17.1
20.7
24.3
HVPA30HPD
460/3/60
7.9
1.4
7.2
10.8
14.4
18.0
15.1
18.7
22.3
25.9
HVPA36HPD
460/3/60
8.6
1.4
7.2
10.8
14.4
18.0
15.8
19.4
23.0
26.6
HVPA42HPD
460/3/60
8.9
1.4
7.2
10.8
14.4
18.0
16.1
19.7
23.3
26.9
HVPA48HPD
460/3/60
9.8
2.2
7.2
10.8
14.4
18.0
17.0
20.6
24.2
27.8
HVPA60HPD
460/3/60
11.3
2.2
7.2
10.8
14.4
18.0
18.5
22.1
25.7
29.3
2
HP = Heat Pump Unit Amps (includes Indoor Motor amps)
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the 208-230v. (HPA & HPC) models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the HPD models.
Total heating amps for single phase units with two circuits (#1 and #2) includes both circuits. Total heating and cooling amps includes all motors. Three phase models contain single phase motor loads.
Values shown are maximum phase loads. Loads are not equally balanced on each phase.
1
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
16
Unit Load Amps (Heating) HVPA Heat Pumps with Single Stage Compressor and GreenWheel® ERV Ventilation Configuration (“H”)
MODEL
VOLTAGE
PHASE
CURRENT (AMPS)
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS
(1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
TOTAL MAXIMUM HEATING AMPS
INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON AN
ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
HP1
IBM2
H3
HVPA24HPA 208-230/1/60
19.6
2.8
2.2
16.7
20.8
25.0
33.3
41.7
19.5
40.4
44.6
52.9
61.3
HVPA30HPA 208-230/1/60
20.6
2.8
2.2
16.7
20.8
25.0
33.3
41.7
50.0
62.5
19.5
41.4
45.6
53.9
62.3
70.6
83.1
HVPA36HPA 208-230/1/60
24.4
2.8
2.2
16.7
20.8
25.0
33.3
41.7
50.0
62.5
19.5
45.2
49.4
57.7
66.1
74.4
86.9
HVPA42HPA 208-230/1/60
27.6
2.8
2.2
20.8
41.7
50.0
62.5
48.4
69.3
77.6
90.1
HVPA48HPA 208-230/1/60
31.1
4.3
2.2
20.8
41.7
50.0
62.5
51.9
72.8
81.1
93.6
HVPA60HPA 208-230/1/60
35.5
4.3
2.2
20.8
41.7
50.0
62.5
56.3
77.2
85.5
98.0
HVPA24HPC 208-230/3/60
14.5
2.8
2.2
14.4
21.7
28.9
36.1
28.9
36.2
43.4
50.6
HVPA30HPC 208-230/3/60
16.1
2.8
2.2
14.4
21.7
28.9
36.1
30.5
37.8
45.0
52.2
HVPA36HPC 208-230/3/60
19.7
2.8
2.2
14.4
21.7
28.9
36.1
34.1
41.4
48.6
55.8
HVPA42HPC 208-230/3/60
21.4
2.8
2.2
14.4
21.7
28.9
36.1
35.8
43.1
50.3
57.5
HVPA48HPC 208-230/3/60
23.0
4.3
2.2
14.4
21.7
28.9
36.1
37.4
44.7
51.9
59.1
HVPA60HPC 208-230/3/60
24.9
4.3
2.2
14.4
21.7
28.9
36.1
39.3
46.6
53.8
61.0
HVPA24HPD
460/3/60
7.4
1.4
1.1
7.2
10.8
14.4
18.0
14.6
18.2
21.8
25.4
HVPA30HPD
460/3/60
9.0
1.4
1.1
7.2
10.8
14.4
18.0
16.2
19.8
23.4
27.0
HVPA36HPD
460/3/60
9.7
1.4
1.1
7.2
10.8
14.4
18.0
16.9
20.5
24.1
27.7
HVPA42HPD
460/3/60
10.0
1.4
1.1
7.2
10.8
14.4
18.0
17.2
20.8
24.4
28.0
HVPA48HPD
460/3/60
10.9
2.2
1.1
7.2
10.8
14.4
18.0
18.1
21.7
25.3
28.9
HVPA60HPD
460/3/60
12.4
2.2
1.1
7.2
10.8
14.4
18.0
19.6
23.2
NUMBER
HERTZ
04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
26.8 30.4
2
3
HP = Heat Pump Unit Amps (includes Indoor Motor amps)
IBM = Indoor Blower Motor
H = GreenWheel ERV
Heating kW is rated at 240 volts on the 208-230v. (HPA & HPC) models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the HPD models.
Total heating amps for single phase units with two circuits (#1 and #2) includes both circuits. Total heating and cooling amps includes all motors. Three phase models contain single phase motor
loads. Values shown are maximum phase loads. Loads are not equally balanced on each phase.
1
17
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Certified Efficiency and Capacity Ratings at ANSI/ARI Standard 390 for HVPSA Heat Pumps with 2-Stage Compressor
HVPSA36HP1
Model Number
HPA
Cooling BTUH1 - 2nd Stage
EER2 - 2nd Stage
HPC
HVPSA42HP1
HPD
HPA
HPC
HPD
HVPSA49HP1
HPA
HPC
HPD
HVPSA60
HPA
HPC HPD
35,000
39,000
47,000
57,000
10.00
10.20
11.00
10.90
Integrated Part Load Value
14.00
13.60
15.0
14.80
High Temperature Heating4
31,400
37,600
39,000
50,500
3
High Temperature COP5
3.20
3.15
3.00
3.00
Rated Air Flow (CFM6)
1,200
1,300
1,750
1,750
Cooling is rated at 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C DB/19.5°C WB) return air.
EER = Energy Efficiency Ratio
3
Integrated Part Load Value is an integrated efficiency measure from 1st and 2nd stage capacity modulation.
4
High Temperature Heating & COP is rated at 47°F DB/43°WB (8.3°C DB/6.1°C WB) outdoor and 70°F (21.1°C) return air.
5
COP = Coefficient of Performance
6
CFM = Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude. Ratings are at 230 volts for 208/230 volt units (“A” & “C”
models) and 460 volts for “D” models.
Operation of units at a different voltage from that of the rating point will affect performance and air flow.
1
2
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air DB HVPSA Heat Pumps - Stage 2
HVPSA36HP1
Model Number
HPA
Total Capacity
HPC
HVPSA42HP1
HPD
HPA
35,000
Sensible Heat Ratio
HPC
HPD
HVPSA49HP1
HPA
39,000
HPC
HPD
HVPSA60
HPA
47,000
HPC
HPD
57,000
0.72
0.70
0.74
0.71
Sensible Capacity
25,485
27,460
34,710
40,605
Rated Air Flow (CFM)
1,200
1,300
1,750
1,750
CFM=Cubic Feet per Minute
Sensible Heat Ratios based upon ANSI/AHRI std. 390 outdoor conditions of 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C
DB/19.5°C WB) return air.
1
Cooling Performance (BTUH) at Various Oudoor Temperatures HVPSA Heat Pumps - Stage 2
Outdoor Temperature
Model
Number
75ºF/24ºC
HVPSA36HP1
40,600
39,200
37,800
36,400
35,000
33,600
32,200
30,800
30,100
HVPSA42HP1
45,240
43,680
42,120
40,560
39,000
37,440
35,880
34,320
33,540
HVPSA49HP1
54,520
52,640
50,760
48,880
47,000
45,120
43,240
41,360
40,420
HVPSA60HP
66,120
63,840
61,560
59,280
57,000
54,720
52,440
50,160
49,020
80ºF/26.5ºC 85ºF/29ºC
90ºF/32ºC
95ºF/35ºC 100ºF/38ºC 105ºF/40.5ºC 110ºF/43.3ºC 115ºF/46ºC
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67°F WB (26.5°C DB/19.5°C WB). Return air at rated air flow.
Heating Performance (BTUH) at Various Oudoor Temperatures HVPSA Heat Pumps with 2-Stage Compressor
Outdoor Temperature
Model
Number
10ºF/-12.2ºC 17ºF/-8.3ºC 20ºF/-6.7ºC 30ºF/-1.1ºC 40ºF/4.4ºC 47ºF/8.3ºC
50ºF/10ºC
60ºF/15.6ºC 70ºF/21.1ºC
HVPSA36HP1
14,620
17,200
18,620
23,590
27,850
31,400
32,342
33,755
35,325
HVPSA42HP1
17,680
20,800
22,420
28,090
32,950
37,000
38,110
39,775
41,625
HVPSA49HP1
18,700
22,000
23,700
29,650
34,750
39,000
40,170
41,925
43,875
HVPSA60HP
25,500
30,000
32,050
39,225
45,375
50,500
52,015
54,288
56,813
Based upon ANSI/AHRI std. 390 return air conditions of 70°F DB (21.1°C DB). Return air at rated air flow.
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
18
Electrical Characteristics - HVPSA Heat Pumps - 2-Stage Compressor
Manual Damper, up to 15% outside air (“N”)
Manual Damper, up to 450 cfm of outside air (“Y”)
Manual Damper, up to 450 cfm of outside air with pressure relief (“Z”)
Motorized 2-Position Damper, up to 450 cfm of outside air w/Pressure Relief (“B”)
Economizer, Outside air with Pressure Relief (“C”)
GreenWheel® Energy Recovery Ventilator (“H”)
Compressor, Fan, Ventilation & Blower Motors Model
Number
OTHER
MOTORS
COMPRESSOR
INDOOR
BLOWER MOTOR
(ECM)
OUTDOOR
FAN MOTOR
VOLTS-HZ-PH
RLA1
LRA2
VOLTS-HZ-PH
RPM3 FLA4
HP5
RPM3 FLA4
HVPSA24HPA
208/230-60-1
11.6
58.3
208/230-60-1
825
1.8
1/4
1500
2.8
HVPSA30HPA
208/230-60-1
13.1
73.0
208/230-60-1
825
2.8
1/3
1500
HVPSA36HP1A
208/230-60-1
15.2
83.0
208/230-60-1
825
2.8
1/3
HVPSA42HP1A
208/230-60-1
17.9
96.0
208/230-60-1
825
2.8
HVPSA49HP1A
208/230-60-1
21.1
104.0
208/230-60-1
825
HVPSA60HPA
208/230-60-1
27.1
152.9
208/230-60-1
HVPSA24HPC
208/230-60-3
6.5
55.4
HVPSA30HPC
208/230-60-3
8.6
HVPSA36HP1C
208/230-60-3
HVPSA42HP1C
HP5
VENTILATION
GREENWHEEL® ERV
AMPS
OAM6
EXM7
WD8
1/3
1.0
1.0
0.2
2.8
1/2
1.0
1.0
0.2
1500
2.8
1/2
1.0
1.0
0.2
1/3
1500
2.8
1/2
1.0
1.0
0.2
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
208/230-60-1
825
1.8
1/4
1500
2.8
1/3
1.0
1.0
0.2
58.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
11.6
73.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
208/230-60-3
14.1
88.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPSA49HP1C
208/230-60-3
14.0
83.1
208/230-60-1
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
HVPSA60HPC
208/230-60-3
16.5
110.0
208/230-60-1
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
HVPSA24HPD
460-60-3
3.5
28.0
208/230-60-1
825
1.8
1/4
1500
2.8
1/3
1.0
1.0
0.2
HVPSA30HPD
460-60-3
4.3
28.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPSA36HP1D
460-60-3
5.7
38.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPSA42HP1D
460-60-3
6.2
44.0
208/230-60-1
825
2.8
1/3
1500
2.8
1/2
1.0
1.0
0.2
HVPSA49HP1D
460-60-3
6.4
41.0
208/230-60-1
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
HVPSA60HPD
460-60-3
7.2
52.0
208/230-60-1
825
2.8
1/2
1500
4.3
3/4
1.0
1.0
0.2
2
RLA = Rated Load Amps
LRA = Locked Rotor Amps
5
6
HP = Horsepower
OAM = Outside Air Mover
The 460 volt units have a step down transformer for the 230 volt motors.
1
RPM = Revolutions per Minute
7
EXM = Exhaust Air Mover
3
FLA = Full Load Amps
8
WD = Wheel Drive Motor
4
Electrical Characteristics - HVPSA Heat Pumps - 2-Stage Compressor
GreenCube Energy Recovery Ventilator (“Q”)
Compressor, Fan, Ventilation & Blower MotorsModel
Number
OTHER
MOTORS
COMPRESSOR
INDOOR
BLOWER MOTOR
(ECM)
OUTDOOR
FAN MOTOR
VOLTS-HZ-PH
RLA1
LRA2
VOLTS-HZ-PH
RPM3
FLA4
HP5
RPM3
FLA4
HP5
HVPSA36HP1A
208/230-60-1
15.2
83.0
208/230-60-1
825
2.0
1/4
1500
2.8
HVPSA42HP1A
208/230-60-1
17.9
96.0
208/230-60-1
825
2.0
1/4
1500
HVPSA49HP1A
208/230-60-1
21.1
104.0
208/230-60-1
825
2.9
1/2
HVPSA60HPA
208/230-60-1
27.1
152.9
208/230-60-1
825
2.9
HVPSA36HP1C
208/230-60-3
11.6
73.0
208/230-60-1
825
HVPSA42HP1C
208/230-60-3
14.1
88.0
208/230-60-1
HVPSA49HP1C
208/230-60-3
14.0
83.1
HVPSA60HPC
208/230-60-3
16.5
HVPSA36HP1D
460-60-3
HVPSA42HP1D
GREENCUBE
ERV
AMPS
OAM6
EXM7
1/2
0.7
0.4
2.8
1/2
0.7
0.4
1500
4.3
3/4
0.7
0.4
1/2
1500
4.3
3/4
0.7
0.4
2.0
1/4
1500
2.8
1/2
0.7
0.4
825
2.0
1/4
1500
2.8
1/2
0.7
0.4
208/230-60-1
825
2.9
1/2
1500
4.3
3/4
0.7
0.4
110.0
208/230-60-1
825
2.9
1/2
1500
4.3
3/4
0.7
0.4
5.7
38.0
208/230-60-1
825
2.0
1/4
1500
2.8
1/2
0.7
0.4
460-60-3
6.2
44.0
208/230-60-1
825
2.0
1/4
1500
2.8
1/2
0.7
0.4
HVPSA49HP1D
460-60-3
6.4
41.0
208/230-60-1
825
2.9
1/2
1500
4.3
3/4
0.7
0.4
HVPSA60HPD
460-60-3
7.2
52.0
208/230-60-1
825
2.9
1/2
1500
4.3
3/4
0.7
0.4
2
3
RLA = Rated Load Amps
LRA = Locked Rotor Amps
RPM = Revolutions per Minute
5
6
7
HP = Horsepower
OAM = Outside Air Mover
EXM = Exhaust Air Mover
The 460 volt units have a step down transformer for the 230 volt motors.
1
VENTILATION
19
FLA = Full Load Amps
4
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) HVPSA Heat Pumps w/2-Stage Compressor and Ventilation Configurations:
Manual Damper, up to 15% outside air (“N”)
Manual Damper, up to 450 cfm of outside air (“Y”)
Manual Damper, up to 450 cfm of outside air with pressure relief (“Z”)
Motorized, 2-Position Damper, up to 450 CFM of Outside Air w/Pressure Relief (“B”)
Economizer, Outside Air (“C”)
ELECTRIC HEAT
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
BASIC MODEL
VOLTS-HZ-PH
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
HVPSA24HPA
208/230-1-60
19.1
30
40.0
40
45.1
50
50.4
60
60.7
HVPSA30HPA
208/230-1-60
22.0
35
48.0
50
53.3
60
63.6
HVPSA36HP1A 208/230-1-60
24.6
35
50.6
60
55.9
60
66.2
HVPSA42HP1A 208/230-1-60
28.0
45
54.0
HVPSA49HP1A 208/230-1-60
33.5
50
HVPSA60HPA
208/230-1-60
41.0
60
HVPSA24HPC
208/230-3-60
12.7
15
30.7
35
40.0
40
HVPSA30HPC
MCA1
MFS2
MCA1
MFS2
70
71.2
80
70
74.1
70
76.7
60
59.5
67.0
150 = 15 kw
SPPE3
MCA1
MFS2
MCA1
MFS2
80
84.5
90
100.1
110
80
87.1
90
102.7
110
80.1
90
90.5
100
106.1
110
60
85.6
90
96.0
100
111.6
120
70
93.1
100
103.5
110
119.1
120
208/230-3-60
16.4
20
34.4
35
43.7
45
52.5
60
61.5
70
HVPSA36HP1C 208/230-3-60
20.1
30
38.1
40
47.4
50
56.2
60
65.2
70
HVPSA42HP1C 208/230-3-60
23.2
35
41.2
45
50.5
60
59.3
60
68.3
70
HVPSA49HP1C 208/230-3-60
24.6
35
42.6
45
51.9
60
60.7
70
69.7
70
HVPSA60HPC
208/230-3-60
27.7
40
45.7
50
55.0
60
63.8
70
72.8
80
HVPSA24HPD
460-3-60
6.7
15
15.7
20
20.2
25
24.7
25
28.9
30
HVPSA30HPD
460-3-60
8.2
15
17.2
20
21.7
25
26.2
30
30.7
35
HVPSA36HP1D
460-3-60
9.9
15
18.9
20
23.4
25
27.9
30
32.4
35
HVPSA42HP1D
460-3-60
10.6
15
19.6
20
24.1
25
28.6
30
33.1
35
HVPSA49HP1D
460-3-60
11.6
15
20.6
25
25.1
30
29.6
30
34.1
35
12.6
15
21.6
25
26.1
30
30.6
35
35.1
40
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline
for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
HVPSA60HPD
460-3-60
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) HVPSA Heat Pumps with Two Stage Compressor and “S” Circuit and
Ventilation Configurations:
Manual Damper, up to 15% outside air (“N”)
Manual Damper, up to 450 cfm of outside air (“Y”)
Manual Damper, up to 450 cfm of outside air with pressure relief (“Z”)
Motorized, 2-Position Damper, up to 450 CFM of Outside Air w/Pressure Relief (“B”)
Economizer, Outside Air (“C”)
ELECTRIC HEAT
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
BASIC MODEL
VOLTS-HZ-PH
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
HVPSA24HPA
208/230-1-60
19.1
30
23.7
30
28.8
30
34.1
HVPSA30HPA
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
35
54.9
60
150 = 15 kw
SPPE3
MCA1
MFS2
MCA1
MFS2
208/230-1-60
22.0
35
28.8
35
34.1
35
54.9
60
65.3
70
80.9
90
HVPSA36HP1A 208/230-1-60
24.6
35
28.8
35
34.1
35
54.9
60
65.3
70
80.9
90
HVPSA42HP1A 208/230-1-60
28.0
45
28.8
45
54.9
60
65.3
70
80.9
90
HVPSA49HP1A 208/230-1-60
33.5
50
33.5
50
56.4
60
66.8
70
82.4
90
HVPSA60HPA
208/230-1-60
41.0
60
41.0
60
56.4
60
66.8
70
82.4
90
HVPSA24HPC
208/230-3-60
12.7
15
20.8
25
29.9
30
38.9
40
47.9
50
HVPSA30HPC
208/230-3-60
16.4
20
20.8
25
29.9
30
38.9
40
47.9
50
HVPSA36HP1C 208/230-3-60
20.1
30
20.8
30
29.9
30
38.9
40
47.9
50
HVPSA42HP1C 208/230-3-60
23.2
35
23.2
35
29.9
35
38.9
40
47.9
50
HVPSA49HP1C 208/230-3-60
24.6
35
24.6
35
31.4
35
40.4
45
49.4
50
HVPSA60HPC
208/230-3-60
27.7
40
27.7
40
31.4
40
40.4
45
49.4
50
HVPSA24HPD
460-3-60
6.7
15
10.4
15
14.9
15
19.4
20
23.9
25
HVPSA30HPD
460-3-60
8.2
15
10.4
15
14.9
15
19.4
20
23.9
25
HVPSA36HP1D
460-3-60
9.9
15
10.4
15
14.9
15
19.4
20
23.9
25
HVPSA42HP1D
460-3-60
10.6
15
10.6
15
14.9
15
19.4
20
23.9
25
HVPSA49HP1D
460-3-60
11.6
15
11.6
15
15.7
20
20.2
25
24.7
25
12.6
15
12.6
15
15.7
20
20.2
25
24.7
25
S-Circuit - Compressor and electric heat do NOT operate simultaneously.
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline for
estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
HVPSA60HPD
460-3-60
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
20
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) HVPSA Heat Pumps with 2-Stage Compressor and
GreenWheel® Energy Recovery Ventilator - Ventilation Configuration (“H”)
ELECTRIC HEAT
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
BASIC MODEL
VOLTS-HZ-PH
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
HVPSA24HPA
208/230-1-60
21.3
30
42.2
45
47.3
50
52.6
60
62.9
HVPSA30HPA
MCA1
MFS2
MCA1
MFS2
70
73.4
80
150 = 15 kw
SPPE3
MCA1
MFS2
MCA1
MFS2
208/230-1-60
24.2
35
50.2
60
55.5
60
65.8
70
76.3
80
86.7
90
102.3
110
HVPSA36HP1A 208/230-1-60
26.8
40
52.8
60
58.1
60
68.4
70
78.9
80
89.3
90
104.9
110
HVPSA42HP1A 208/230-1-60
30.2
45
56.2
60
82.3
90
92.7
100
108.3
120
HVPSA49HP1A 208/230-1-60
35.7
50
61.7
70
87.8
90
98.2
100
113.8
120
HVPSA60HPA
208/230-1-60
43.2
60
69.2
70
95.3
100
105.7
110
121.3
130
HVPSA24HPC
208/230-3-60
14.9
20
32.9
35
42.0
45
HVPSA30HPC
208/230-3-60
18.6
25
36.6
40
45.7
50
54.7
60
63.7
70
HVPSA36HP1C 208/230-3-60
22.3
30
40.3
45
49.4
50
58.4
60
67.4
70
HVPSA42HP1C 208/230-3-60
25.4
35
43.4
45
52.5
60
61.5
70
70.5
80
HVPSA49HP1C 208/230-3-60
26.8
40
44.8
45
53.9
60
62.9
70
71.9
80
HVPSA60HPC
208/230-3-60
29.9
45
47.9
50
57.0
60
66.0
70
75.0
80
HVPSA24HPD
460-3-60
7.8
15
16.8
20
21.3
25
25.8
30
30.3
35
HVPSA30HPD
460-3-60
9.3
15
18.3
20
22.8
25
27.3
30
31.8
35
HVPSA36HP1D
460-3-60
11.0
15
20.0
20
24.5
25
29.0
30
33.5
35
HVPSA42HP1D
460-3-60
11.7
15
20.7
25
25.2
30
29.7
30
34.2
35
HVPSA49HP1D
460-3-60
12.7
15
21.7
25
26.2
30
30.7
35
35.2
40
13.7
20
22.7
25
27.2
30
31.7
35
36.2
40
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline for
estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
HVPSA60HPD
460-3-60
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) HVPSA Heat Pumps with Two Stage Compressor and “S” Circuit
GreenWheel® Energy Recovery Ventilator - Ventilation Configuration (“H”)
ELECTRIC HEAT
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
BASIC MODEL
VOLTS-HZ-PH
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
HVPSA24HPA
208/230-1-60
21.3
30
25.9
30
31.0
35
36.3
HVPSA30HPA
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
40
57.1
60
150 = 15 kw
SPPE3
MCA1
MFS2
MCA1
MFS2
208/230-1-60
24.2
35
31.0
35
36.3
40
57.1
60
67.5
70
83.1
90
HVPSA36HP1A 208/230-1-60
26.8
40
31.0
40
36.3
40
57.1
60
67.5
70
83.1
90
HVPSA42HP1A 208/230-1-60
30.2
45
31.0
45
57.1
60
67.5
70
83.1
90
HVPSA49HP1A 208/230-1-60
35.7
50
35.7
50
58.6
60
69.0
70
84.6
90
HVPSA60HPA
208/230-1-60
43.2
60
43.2
60
58.6
60
69.0
70
84.6
90
HVPSA24HPC
208/230-3-60
14.9
20
23.0
25
32.1
35
41.1
45
50.1
60
HVPSA30HPC
208/230-3-60
18.6
25
23.0
25
32.1
35
41.1
45
50.1
60
HVPSA36HP1C 208/230-3-60
22.3
30
23.0
30
32.1
35
41.1
45
50.1
60
HVPSA42HP1C 208/230-3-60
25.4
35
25.4
35
32.1
35
41.1
45
50.1
60
HVPSA49HP1C 208/230-3-60
26.8
40
26.8
40
33.6
40
42.6
45
51.6
60
HVPSA60HPC
208/230-3-60
29.9
45
29.9
45
33.6
45
42.6
45
51.6
60
HVPSA24HPD
460-3-60
7.8
15
11.5
15
16.0
20
20.5
25
25.0
25
HVPSA30HPD
460-3-60
9.3
15
11.5
15
16.0
20
20.5
25
25.0
25
HVPSA36HP1D
460-3-60
11.0
15
11.5
15
16.0
20
20.5
25
25.0
25
HVPSA42HP1D
460-3-60
11.7
15
11.5
15
16.0
20
20.5
25
25.0
25
HVPSA49HP1D
460-3-60
12.7
15
12.7
15
16.8
20
21.3
25
25.8
30
13.7
20
13.7
20
16.8
20
21.3
25
25.8
30
S-Circuit - Compressor and electric heat do NOT operate simultaneously.
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline for
estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
HVPSA60HPD
460-3-60
21
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) HVPSA Heat Pump with 2- Stage Compressor & Ventilation Configuration:
Green Cube ERV - Ventilation Configuration (“Q”)
ELECTRIC HEAT
BASIC MODEL
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
VOLTS-HZ-PH
MCA1
MFS2
HVPSA36HP1A 208/230-1-60
24.9
HVPSA42HP1A 208/230-1-60
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
40
50.9
60
56.2
60
66.5
70
28.3
45
54.3
HVPSA49HP1A 208/230-1-60
34.7
50
HVPSA60HPA
208/230-1-60
42.2
60
HVPSA36HP1C 208/230-3-60
20.4
30
38.4
45
47.5
HVPSA42HP1C 208/230-3-60
23.5
35
41.5
45
HVPSA49HP1C 208/230-3-60
25.8
35
43.8
HVPSA60HPC
208/230-3-60
28.9
45
HVPSA36HP1D
460-3-60
10.1
HVPSA42HP1D
460-3-60
HVPSA49HP1D
460-3-60
MFS2
150 = 15 kw
SPPE3
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
77.0
80
87.4
90
103.0
110
60
80.4
90
90.8
100
106.4
110
60.7
70
86.8
90
97.2
100
112.8
120
68.2
70
94.3
100
104.7
110
120.3
130
50
56.5
60
65.5
70
50.6
60
59.6
60
68.6
70
45
52.9
60
61.9
70
70.9
80
46.9
50
56.0
60
65.0
70
74.0
80
15
19.1
20
23.6
25
28.1
30
32.6
35
10.7
15
19.7
20
24.2
30
28.7
30
33.2
35
12.2
15
21.2
25
25.7
30
30.2
35
34.7
35
13.2
20
22.2
25
26.7
30
31.2
35
35.7
40
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline for
estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
HVPSA60HPD
460-3-60
Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) HVPSA Heat Pumps with 2-Stage Compressor and “S” Circuit and
Ventilation Configurations:
Green Cube ERV - Ventilation Configuration (“Q”)
ELECTRIC HEAT
BASIC MODEL
000 = None
040 = 4 kw
050 = 5 kw
060 = 6 kw
080 = 8 kw
090 = 9 kw
100 = 10 kw
120 = 12 kw
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
SPPE3
VOLTS-HZ-PH
MCA1
MFS2
HVPSA36HP1A 208/230-1-60
24.9
HVPSA42HP1A 208/230-1-60
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
MCA1
40
29.9
40
35.2
40
28.3
45
29.9
HVPSA49HP1A 208/230-1-60
34.7
50
HVPSA60HPA
208/230-1-60
42.2
60
HVPSA36HP1C 208/230-3-60
20.4
30
21.9
30
31.0
HVPSA42HP1C 208/230-3-60
23.5
35
23.5
35
HVPSA49HP1C 208/230-3-60
25.8
35
25.8
HVPSA60HPC
208/230-3-60
28.9
45
HVPSA36HP1D
460-3-60
10.1
HVPSA42HP1D
460-3-60
HVPSA49HP1D
460-3-60
MFS2
150 = 15 kw
SPPE3
MCA1
MFS2
MCA1
MFS2
MCA1
MFS2
56.0
60
66.4
70
82.0
90
45
56.0
60
66.4
70
82.0
90
34.7
50
57.5
60
67.9
70
83.5
90
42.2
60
57.5
60
67.9
70
83.5
90
35
40.0
40
49.0
50
31.0
35
40.0
40
49.0
50
35
32.5
35
41.5
45
50.5
60
28.9
45
32.5
45
41.5
45
50.5
60
15
11.0
15
15.5
20
20.0
20
24.5
25
10.7
15
11.0
15
15.5
20
20.0
20
24.5
25
12.2
15
12.2
15
16.2
20
20.7
25
25.2
30
13.2
20
13.2
20
16.2
20
20.7
25
25.2
30
S-Circuit - Compressor and electric heat do NOT operate simultaneously.
1
2
3
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
MFS = Maximum Fuse or HACR Breaker Size
SPPE = Single Point Power Entry
MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline for
estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit.
HVPSA60HPD
460-3-60
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
22
Unit Load Amps (Heating) HVPSA Heat Pumps w/2-Stage Compressor & Ventilation Configuration:
Manual Damper, up to 15% outside air (“N”)
Manual Damper, up to 450 cfm of outside air (“Y”)
Manual Damper, up to 450 cfm of outside air with pressure relief (“Z”)
Motorized 2-Position Damper, up to 450 cfm of outside air w/Pressure Relief (“B”)
Economizer, Outside Air (“C”)
MODEL
NUMBER
VOLTAGE
PHASE
HERTZ
CURRENT (AMPS)
HP1
IBM2
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS
(1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
TOTAL MAXIMUM HEATING AMPS
INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON AN
ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
HVPSA24HPA
208-230/1/60
16.2
2.8
16.7
20.8
25.0
33.3
41.7
32.9
37.0
41.2
49.5
57.9
HVPSA30HPA
208-230/1/60
18.7
2.8
16.7
20.8
25.0
33.3
41.7
50.0
62.5
35.4
39.5
43.7
52.0
60.4
68.7
81.2
HVPSA36HP1A 208-230/1/60
20.8
2.8
16.7
20.8
25.0
33.3
41.7
50.0
62.5
37.5
41.6
45.8
54.1
62.5
70.8
83.3
HVPSA42HP1A 208-230/1/60
23.5
2.8
20.8
41.7
50.0
62.5
44.3
65.2
73.5
86.0
HVPSA49HP1A 208-230/1/60
28.2
4.3
20.8
41.7
50.0
62.5
49.0
69.9
78.2
90.7
HVPSA60HPA
208-230/1/60
34.2
4.3
20.8
41.7
50.0
62.5
55.0
75.9
84.2
96.7
HVPSA24HPC
208-230/3/60
11.1
2.8
14.4
21.7
28.9
36.1
25.5
32.8
40.0
47.2
HVPSA30HPC
208-230/3/60
14.2
2.8
14.4
21.7
28.9
36.1
28.6
35.9
43.1
50.3
HVPSA36HP1C 208-230/3/60
17.2
2.8
14.4
21.7
28.9
36.1
31.6
38.9
46.1
53.3
HVPSA42HP1C 208-230/3/60
19.7
2.8
14.4
21.7
28.9
36.1
34.1
41.4
48.6
55.8
HVPSA49HP1C 208-230/3/60
21.1
4.3
14.4
21.7
28.9
36.1
35.5
42.8
50.0
57.2
HVPSA60HPC
208-230/3/60
23.6
4.3
14.4
21.7
28.9
36.1
38.0
45.3
52.5
59.7
HVPSA24HPD
460/3/60
5.8
1.4
7.2
10.8
14.4
18.0
13.0
16.6
20.2
23.8
HVPSA30HPD
460/3/60
7.1
1.4
7.2
10.8
14.4
18.0
14.3
17.9
21.5
25.1
HVPSA36HP1D
460/3/60
8.5
1.4
7.2
10.8
14.4
18.0
15.7
19.3
22.9
26.5
HVPSA42HP1D
460/3/60
9.0
1.4
7.2
10.8
14.4
18.0
16.2
19.8
23.4
27.0
HVPSA49HP1D
460/3/60
10.0
2.2
7.2
10.8
14.4
18.0
17.2
20.8
24.4
28.0
HVPSA60HPD
460/3/60
10.8
2.2
7.2
10.8
14.4
18.0
18.0
21.6
25.2
28.8
2
HP = Heat Pump Unit Amps (includes Indoor Motor amps)
IBM = Indoor Blower Motor
Heating kW is rated at 240 volts on the 208-230v. (HPA & HPC) models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the HPD models.
Total heating amps for single phase units with two circuits (#1 and #2) includes both circuits. Total heating and cooling amps includes all motors. Three phase models contain single phase motor loads.
Values shown are maximum phase loads. Loads are not equally balanced on each phase.
1
Unit Load Amps (Heating) HVPSA Heat Pumps with 2-Stage Compressor and
GreenWheel® Energy Recovery Ventilator - Ventilation Configuration (“H”)
MODEL
NUMBER
VOLTAGE
PHASE
HERTZ
CURRENT (AMPS)
HP1
IBM2
H3
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS
(1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
TOTAL MAXIMUM HEATING AMPS
INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON AN
ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
HVPSA24HPA
208-230/1/60
18.4
2.8
2.2
16.7
20.8
25.0
33.3
41.7
19.5
39.2
43.4
51.7
60.1
HVPSA30HPA
208-230/1/60
20.9
2.8
2.2
16.7
20.8
25.0
33.3
41.7
50.0
62.5
19.5
41.7
45.9
54.2
62.6
70.9
83.4
HVPSA36HP1A 208-230/1/60
23.0
2.8
2.2
16.7
20.8
25.0
33.3
41.7
50.0
62.5
19.5
43.8
48.0
56.3
64.7
73.0
85.5
HVPSA42HP1A 208-230/1/60
25.7
2.8
2.2
20.8
41.7
50.0
62.5
46.5
67.4
75.7
88.2
HVPSA49HP1A 208-230/1/60
30.4
4.3
2.2
20.8
41.7
50.0
62.5
51.2
72.1
80.4
92.9
HVPSA60HPA
208-230/1/60
36.4
4.3
2.2
20.8
41.7
50.0
62.5
57.2
78.1
86.4
98.9
HVPSA24HPC
208-230/3/60
13.3
2.8
2.2
14.4
21.7
28.9
36.1
27.7
35.0
42.2
49.4
HVPSA30HPC
208-230/3/60
16.4
2.8
2.2
14.4
21.7
28.9
36.1
30.8
38.1
45.3
52.5
HVPSA36HP1C 208-230/3/60
19.4
2.8
2.2
14.4
21.7
28.9
36.1
33.8
41.1
48.3
55.5
HVPSA42HP1C 208-230/3/60
21.9
2.8
2.2
14.4
21.7
28.9
36.1
36.3
43.6
50.8
58.0
HVPSA49HP1C 208-230/3/60
23.3
4.3
2.2
14.4
21.7
28.9
36.1
37.7
45.0
52.2
59.4
HVPSA60HPC
208-230/3/60
25.8
4.3
2.2
14.4
21.7
28.9
36.1
40.2
47.5
54.7
61.9
HVPSA24HPD
460/3/60
6.9
1.4
1.1
7.2
10.8
14.4
18.0
14.1
17.7
21.3
24.9
HVPSA30HPD
460/3/60
8.2
1.4
1.1
7.2
10.8
14.4
18.0
15.4
19.0
22.6
26.2
HVPSA36HP1D
460/3/60
9.6
1.4
1.1
7.2
10.8
14.4
18.0
16.8
20.4
24.0
27.6
HVPSA42HP1D
460/3/60
10.1
1.4
1.1
7.2
10.8
14.4
18.0
17.3
20.9
24.5
28.1
HVPSA49HP1D
460/3/60
11.1
2.2
1.1
7.2
10.8
14.4
18.0
18.3
21.9
25.5
29.1
HVPSA60HPD
460/3/60
11.9
2.2
1.1
7.2
10.8
14.4
18.0
19.1
22.7
26.3
29.9
2
3
HP = Heat Pump Unit Amps (includes Indoor Motor amps)
IBM = Indoor Blower Motor
H = GreenWheel ERV
Heating kW is rated at 240 volts on the 208-230v. (HPA & HPC) models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the HPD models.
Total heating amps for single phase units with two circuits (#1 and #2) includes both circuits. Total heating and cooling amps includes all motors. Three phase models contain single phase motor loads.
Values shown are maximum phase loads. Loads are not equally balanced on each phase.
1
23
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Unit Load Amps (Heating) HVPSA Heat Pump with 2-stage Compressor and
GreenCube Energy Recovery Ventilator - Ventilation Configuration “Q”
MODEL
NUMBER
VOLTAGE
PHASE
HERTZ
CURRENT (AMPS)
HP1
IBM2
Q3
LOAD OF RESISTIVE HEATING - ELEMENTS ONLY (AMPS
(1) ALL HEATING ELEMENTS ARE ON A SEPARATE CIRCUIT
(2) SHADED VALUES (12 & 15 kW) UTILIZE TWO CIRCUITS
TOTAL MAXIMUM HEATING AMPS
INCLUDES AMPS FROM MOTOR(S) THAT ARE LOCATED ON AN
ELECTRICAL CIRCUIT THAT DOES NOT HAVE HEATERS
04 kW 05 kW 06 kW 08 kW 09 kW 10 kW 12 kW 15 kW 04 Kw 05 Kw 06 Kw 08 Kw 09 Kw 10 Kw 12 Kw 15 Kw
HVPSA36HP1A
208-230/1/60
21.1
2.8
1.1
41.7
50.0
62.5
62.8
71.1
83.6
HVPSA42HP1A
208-230/1/60
23.8
2.8
1.1
16.7
20.8
20.8
25.0
33.3
41.7
50.0
62.5
19.5
41.9
44.6
46.1
54.4
65.5
73.8
86.3
HVPSA49HP1A
208-230/1/60
29.4
4.3
1.1
20.8
41.7
50.0
62.5
50.2
71.1
79.4
91.9
HVPSA60HPA
208-230/1/60
35.4
4.3
1.1
20.8
41.7
50.0
62.5
56.2
77.1
85.4
97.9
HVPSA36HP1C
208-230/3/60
17.5
2.8
1.1
14.4
21.7
28.9
36.1
31.9
39.2
46.4
53.6
HVPSA42HP1C
208-230/3/60
20.0
2.8
1.1
14.4
21.7
28.9
36.1
34.4
41.7
48.9
56.1
HVPSA49HP1C
208-230/3/60
22.3
4.3
1.1
14.4
21.7
28.9
36.1
36.7
44.0
51.2
58.4
HVPSA60HPC
208-230/3/60
24.8
4.3
1.1
14.4
21.7
28.9
36.1
39.2
46.5
53.7
60.9
HVPSA36HP1D
460/3/60
8.7
1.4
0.6
7.2
10.8
14.4
18.0
15.9
19.5
23.1
26.7
HVPSA42HP1D
460/3/60
9.2
1.4
0.6
7.2
10.8
14.4
18.0
16.4
20.0
23.6
27.2
HVPSA49HP1D
460/3/60
10.6
2.2
0.6
7.2
10.8
14.4
18.0
17.8
21.4
25.0
28.6
HVPSA60HPD
460/3/60
11.4
2.2
0.6
7.2
10.8
14.4
18.0
18.6
22.2
25.8
29.4
1
2
3
HP = Heat Pump Unit Amps (includes Indoor Motor amps)
IBM = Indoor Blower Motor
Q = GreenCube ERV
Heating kW is rated at 240 volts on the 208-230v. (HPA & HPC) models. Derate heater output by 25% for operation at 208 volts. Heating kW is rated at 480 volts on the HPD models.
Total heating amps for single phase units with two circuits (#1 and #2) includes both circuits. Total heating and cooling amps includes all motors. Three phase models contain single phase motor loads.
Values shown are maximum phase loads. Loads are not equally balanced on each phase.
HVPA & HVPSA Air Flow (CFM) at Various Static Pressures
MODEL
0.10
0.20
0.25
0.30
0.40
0.50
24
800
770
725
680
600
500
30
1200
1100
1050
1000
900
800
36
1290
1170
1115
1060
1000
920
42
1500
1360
1295
1230
1160
1070
49
1900
1800
1700
1600
1500
1350
60
2200
2100
2000
1900
1800
1650
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
24
25
INCHES
25 x 16 x 1
AVPA24
RETURN AIR FILTER
635 x 406 x 25
MILLIMETERS
80135
PART NUMBER
1
FILTERS PER UNIT
286/130
Filter Size
275/125
WITH VENTILATION CONFIGURATION “C”, “B”, “Y”, & “Z”
LBS/KGS
WITH VENTILATION CONFIGURATION “N”
AVPA24
Shipping Weight (pounds/kilograms)
7
MERV RATING
Dimensional Data for AVPA24 (inches and mm)
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
26
RETURN AIR FILTER
AVPA30/36 & HVPA 24
30 x 16 x 1
INCHES
762 x 406 x 25
MILLIMETERS
80136
PART NUMBER
1
FILTERS PER UNIT
375/161
Filter Size
355/160
WITH VENTILATION CONFIGURATION “C”, “B”, “Y”, & “Z”
LBS/KGS
WITH VENTILATION CONFIGURATION “N”
AVPA30/36 & HVPA24
Shipping Weight (pounds/kilograms)
7
MERV RATING
Dimensional Data for AVPA30/36 and HVPA24
27
The GreenCube ERV is only available on HVPSA units
(2-stage compressor).
All HVPSA units with the GreenCube ERV, including the
HVPSA36 and HVPSA42 are in the HVPSA49/60 cabinet.
INCHES
36½ x 22 x 1
AVPA42/48/60,
HVPA30/36/42, &
HVPSA36/42
RETURN AIR FILTER
927 x 559 x 25
MILLIMETERS
80139
PART NUMBER
1
FILTERS PER UNIT
590/268
Filter Size
535/245
WITH VENTILATION CONFIGURATION “C”, “B”, “Y”, & “Z”
LBS/KGS
WITH VENTILATION CONFIGURATION “N”
AVPA42/48/60, HVPA30/36/42, & HVPSA36/42
Shipping Weight (pounds/kilograms)
7
MERV RATING
Dimensional Data for AVPA42/48/60, HVPA30/36/42 and
HVPSA36/42 (inches and mm)
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
28
NOTE: HEAT PUMPS WITH THE GREENCUBE® ERV
(Q VENTILATION CONFIGURATION) HAVE IDENTICAL
MOUNTINGS HOLES, THE SAME SUPPLY & RETURN AIR
OPENINGS AND THE SAME OVERALL DIMENSIONS. THE
CONTROL BOX ON UNITS WITH THE GREENCUBE ERV IS
ON THE RIGHT SIDE OF THE UNIT.
*Units with the GreenWheel ERV
RETURN AIR FILTER (OPT)**
INTAKE AIR FILTER**
EXHAUST AIR FILTER**
RETURN AIR FILTER (STD)**
RETURN AIR FILTER
INTAKE AIR FILTER*
HVPA49/60 & HVPSA49/60
Filter Size
406
406
248
248
x
x
x
x
635
635
222
222
x
x
x
x
25
51
19
19
457 x 610 x 25
356 x 356 x 25
MILLIMETERS
91968
92113
92113
92367
81199
80192
2
1
1
2
2
1
FILTERS PER UNIT
625/284
640/291
810/369
LBS/KGS
PART NUMBER
**Units with the GreenCube ERV
16 x 24 x 1
16 x 24 x 2
9¾ x 22¾ x ¾
9¾ x 22¾ x ¾
18 x 24 x1
14 x 14 x 1
INCHES
WITH VENTILATION CONFIGURATION “N”
WITH VENTILATION CONFIGURATION “C”, “B”, “Y”, & “Z”
WITH EITHER GREENWHEEL ERV OR GREENCUBE ERV
HVPA49/60 & HVPSA49/60
Shipping Weight (pounds/kilograms)
8
N/A
N/A
7
7
N/A
MERV RATING
Dimensional Data for HVPA49/60 and
HVPSA49/60 (inches and mm)
29
27½ x 13½ x 1
14 x 14 x 1
RETURN AIR FILTER*
INTAKE AIR FILTER
356 x 356 x 25
699 x 343 x 25
MILLIMETERS
80192
80769
PART NUMBER
1
1
FILTERS PER UNIT
375/161
LBS/KGS
*These units require a return filter grille. The filter shown is the filter in the return filter grille.
INCHES
AVPA24/30/36 &
HVPA24 with
GreeWheel ERV
Filter Size
With GreenWheel ERV
AVPA24/30/36 & HVPA24
Shipping Weight (pounds/kilograms)
N/A
7
MERV RATING
Dimensional Data for AVPA24/30/36 and HVPA24 with the
GreenWheel ERV (inches and mm)
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
30
36 x 22 x 1
14 x 14 x 1
RETURN AIR FILTER
INTAKE AIR FILTER*
*Units with the GreenWheel ERV
INCHES
AVPA42/48/60,
HVPA30/36/42, &
HVPSA36/42 with
GreenWheel ERV
Filter Size
With GreenWheel ERV
356 x 356 x 25
927 x 559 x 25
MILLIMETERS
80192
80139
PART NUMBER
AVPA42/48/60, HVPA30/36/42, & HVPSA36/42
1
1
FILTERS PER UNIT
590/268
LBS/KGS
Shipping Weight (pounds/kilograms)
N/A
7
MERV RATING
Dimensional Data for AVPA42/48/60, HVPA30/36/42,
& HVPSA36/42 with the GreenWheel ERV (inches and mm)
Notes
31
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
Notes
Please consult the Marvair® website at www.marvair.com for the latest product literature. Detailed dimensional data
is available upon request. A complete warranty statement can be found in each product’s Installation/Operation
Manual, on our website or by contacting Marvair at 229-273-3636. As part of the Marvair continuous improvement
program, specifications are subject to change without notice.
P.O. Box 400 • Cordele, GA 31010
156 Seedling Drive • Cordele, GA 31015
Ph: 229-273-3636 • Fax: 229-273-5154
Email: marvair@airxcel.com • Internet: www.marvair.com
Classic AVPA24-30-36-42-48-60, HVPA24-30-36-42-49-60 & HVPSA36-42-49-60 PDS 8/2012 rev.3
32
The Educated Air Conditioning Choice